Reliable SWC Bulletin
Text of the manual
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model SWC
Concealed Quick Response
Extended Coverage
Horizontal Sidewall Sprinkler
Bulletin 163 Rev. G
Bulletin 163 Rev. G
The Sidewall Concealer®
Coverage to 14 ft. x 26 ft.
(4.3m x 7.9m). 300 psi (20,7 bar) Rated.
Features:
1. Tamper resistant cover plate can prevent
the sprinkler from being used for unintended
purposes. No exposed thermal element.
2. 8.0 K Factor.
3. Sprinkler is approved for both
175 psi (12,0 bar) and
300 psi (20,7 bar) applications.
4.
Quick response, extended coverage performance.
5.
Push-on/thread-off, sturdy convenient cover plate.
6.
Factory assembled sprinkler and cup, shipped
complete with protective cap.
7.
Sprinkler assembly and cover plate separately
packaged.
8.
½” (13mm) adjustment .
9.
Utilizes the Model F1FR-300 QREC-9 Horizontal
Sidewall Sprinkler.
10. Cover plate available in standard white paint, special
bronze, black paint or flat white finishes.
Approval Organizations
1. Listed by Underwriters Laboratories Inc. and
UL certified for Canada (cULus).
2. NYC MEA 258-93-E
Patents: U.S. Patent No. 6,374,919
Product Description
The Reliable Model SWC Concealed Quick Response Extend-
ed Coverage Horizontal Sidewall Sprinkler is an attractive, con-
cealed sprinkler assembly that utilizes a push-on/thread-off cover
plate assembly. The assembly is shipped with a protective cap.
The Model CCP/HSW cover plate is attached to the skirt us-
ing 135°F (57°C) ordinary temperature classification solder. The
sprinkler and cup are easily installed into the sprinkler fitting using
the Model GFR1 Sprinkler Wrench.
When the ambient temperature rises, the solder holding the
cover plate melts, allowing the release of this part and thus expos-
ing the sprinkler inside to the rising ambient temperature.
The Model SWC utilizes a 3.0mm frangible glass bulb. This
quick response enables the sprinkler to apply water to a fire soon-
er than standard sprinklers of the same temperature rating.
This sprinkler can handle a maximum service pressure of 300
psi (20,7 bar).
Application and Installation
The Model SWC sprinkler is intended for installation in light haz-
ard occupancies in accordance with NFPA 13. This sprinkler is
especially well-suited for use in student dormitories, hotels, hospi-
tals and care facilities, and can be used where the pressure enter-
ing the sprinkler system is in excess of 175 psi (12 bar).
Model SWC Concealed Horizontal Sidewall sprinklers utilize
a Model F1FR-300 QREC-9 Horizontal Sidewall Sprinkler with a
threaded cup which is factory attached to the sprinkler. The as-
sembly is completed by the installation of the attractive, 135°F
(57°C) rated Model CCP/HSW push on / thread off cover plate
assembly.
Apply a Teflon* - based thread sealant to the sprinkler threads.
After a 25/8” (67mm) diameter hole is cut in the wall, the sprinkler
is easily installed with the Model GFR1 Wrench. When installing
the sprinkler, the protective cap is removed and the wrench is
positioned into the sprinkler/cup assembly until the two wrench
faces engage the wrenching flats on the sprinkler. The sprinkler
is then tightened into the pipe fitting. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should be
taken to prevent damage to the sprinkler. DO NOT WRENCH
ON ANY OTHER PART OF THE SPRINKLER. The cover plate
assembly is then pushed onto the cup. Cover plate assemblies
provide ½” (13mm) of cover adjustment. Final adjustment is
made by turning the cover plate clockwise until the skirt flange
makes full contact with the wall surface. Cover plate removal
requires turning in the counter clockwise direction.
Concealed cover plate/cup assemblies are listed only for use
with specific sprinklers. The use of any other concealed cover
plate/cup assembly with the Model F1FR-300 QREC-9 Horizon-
tal Sidewall Sprinkler or the use of the Model CCP/HSW con-
cealed cover plate assembly on any sprinkler with which it is
not specifically listed will void all guarantees, warranties, listings
and approvals.
* DuPont Registered Trademark
Width x Length
Temperature
Rating
Defl ector to Ceiling
Dimension
gpm
L/min
psi
bar
ft. x ft.
m x m
Sprinkler
Cover
inches
mm
29
29
29
109.8
109.8
109.8
13.1
13.1
13.1
0,9
0,9
0,9
16 x 14
16 x 16
16 x 18
4.9 x 4.3
4.9 x 4.9
4.9 x 5.5
135°F (57°C)/ 155°F (68°C)
135°F (57°C)/ 155°F (68°C)
135°F (57°C)/ 155°F (68°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
4 - 12
4 - 12
4 - 12
102 - 305
102 - 305
102 - 305
37
37
140.1
140.1
21.4
21.4
1,5
1,5
16 x 20
16 x 22
4.9 x 6.0
4.9 x 6.7
135°F (57°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
4 - 12
4 - 12
102 - 305
102 - 305
39
46
33
147.6
174.1
124.9
23.8
33.1
17.0
1,6
2,25
1,2
14 x 26
14 x 26
18 x 18
4.3 x 7.9
4.3 x 7.9
5.5 x 5.5
135°F (57°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
4 - 6
6 - 12
4 - 12
102 - 153
153 - 305
102 - 305
40
46
33
151.4
174.1
124.9
25.0
33.1
17.0
1,7
2,25
1,2
18 x 22
14 x 26
18 x 18
5.5 x 6.7
4.3 x 7.9
5.5 x 5.5
155°F (68°C)
155°F (68°C)
155°F (68°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
4 - 12
6 - 12
4 - 12
102 - 305
153 - 305
102 -305
Minimum spacing between sprinklers - 8 feet (2.4m).
Approval Type
Quick Response Extended Coverage - Light Hazard
Model SWC Concealed Sprinklers should be inspected
quarterly and the sprinkler maintained in accordance with
NFPA 25. Do not clean sprinklers with soap and water, am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
cover plate assembly, which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in their original cartons and
packaging until used to minimize the potential for damage
to sprinklers that would cause improper operation or non-
operation.
Model SWC Concealed Quick Response
Extended Coverage Horizontal
Sidewall Sprinkler Specifi cation
Sprinklers shall be a [quick response – cULus Listed]
[quick response - New York City MEA Approved (258-93-E)]
extended coverage concealed horizontal sprinkler with EC-
9 deflector and adjustable cover plate for light hazard, inte-
rior, non-corrosive applications. Sprinklers to be of bronze
frame construction with brass cover plate and copper alloy
retainer flange assembly. Water seal assembly shall consist
of a Teflon* coated Belleville spring washer and machined
brass cup with 3 mm glass bulb containing no plastic parts.
Method of attaching the cover plate to the sprinkler cup shall
be a push-on and thread-off design allowing a ½” cover
plate adjustment. Sprinklers shall have a nominal K-factor
of 8.0 (115.3), and ¾” NPT thread. Sprinkler temperature
rating shall be 135°F (57°C) with a cover plate temperature
rating of 135°F (57°C). Sprinklers shall be capable of a max-
imum coverage area of 16 ft. x 22 ft. (4.9 m x 6.7 m), with
a minimum lateral spacing of 8 ft. (2.4 m). Rated working
pressure shall be 300 psi (20,7 bar). A plastic protective
cap shall be provided and factory installed inside the sprin-
kler cup to protect the sprinkler from damage, which could
occur during construction before the cover plate is installed.
Standard cover plate finish: [White] [Custom Color– specify].
Concealed horizontal sidewall sprinklers shall be Reliable
Model SWC, SIN R5962 (Bulletin 163).
UL Listing Category
Sprinklers, Automatic and Open
Quick Response Extended coverage Sprinklers
Ordering Information
Specify:
1. Model SWC Sidewall Concealer®
2. Cover Plate Finish.
Installation Wrench
Model GFR1 Sprinkler Wrench
Installation Aid
A protective plastic cap is included for use during instal-
lation.
Cover Plate Finishes(1)
Standard Finishes
White Paint
Special Application Finishes
Bronze
Black Paint
Flat White Paint
(1) Other colors and finishes are available. Consult factory for details.
Note: Paint or any other coatings applied over the factory
finish will void all approvals and warranties.
*DuPont Registered Trademark
Figure 1
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588
Sales Offices
(800) 848-6051
Sales Fax
(914) 829-2042
Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 10/13
P/N 9999970167
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection