Redlion CUB4I Manual
Read Online
Read the Redlion CUB4I Manual online using the built-in PDF viewer.
Text of the manual
� LCD, POSITIVE REFLECTIVE OR NEGATIVE TRANSMISSIVE
WITH YELLOW/GREEN OR RED BACKLIGHTING
� FOUR SELECTABLE D.C. RANGES
0 to 199.9 mV, 1.999 V, 19.99 V, 199.9 V (CUB4V)
0 to 199.9 µA, 1.999 mA, 19.99 mA, 199.9 mA (CUB4I)
� 0.6 INCH (15.2 mm) HIGH LCD DIGITS
� BUILT-IN SCALING PROVIDED
� AUTO ZEROING CIRCUIT
� SELECTABLE DECIMAL POINTS
� WIRE CONNECTIONS MADE VIA SCREW CLAMP TYPE
TERMINALS
� FITS DIN STANDARD CUT-OUT 2.68" (68 mm) x 1.30" (33 mm)
� NEMA 4X/IP65 SEALED FRONT PANEL BEZEL
� 9 TO 28 VDC POWERED
DESCRIPTION
The CUB4 Volt and Current Meters are designed and manufactured using the
latest technology for a high quality, compact, affordable instrument for use in
industrial environments. Each unit has a 3½-digit LCD display with 0.6 inch
(15.2 mm) high digits and a DIP switch selectable decimal point. The displays
are available in positive image reflective (black digits, reflective background) or
negative image transmissive (illuminated digits, dark background) with red or
yellow/green backlighting.
The units are constructed of a lightweight, high impact plastic case with a
clear viewing window. The sealed front panel meets NEMA 4X/IP65
specifications for wash-down and/or dusty environments, when properly
installed. A CUB4V or CUB4I unit can be mounted in the same panel cutout as
the CUBVD and CUBID units.
The optional Micro Line/Sensor Power Supply (MLPS1000) is designed to
attach to the rear of an installed CUB4V or CUB4I to provide the necessary power
for the unit. The optional supply can be powered from a 85-250 VAC source.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. DISPLAY: 3½-digit (-1999 to 1999), 0.6" (15.2 mm) high digits. Minus (-)
sign is displayed when voltage or current is negative.
2. DECIMAL POINTS: DIP switch selectable decimal points allow the display
to be read in tenths, hundredths or thousandths.
3. POWER REQUIREMENTS:
Reflective Versions: 9 to 28 VDC at 4 mA max.
Backlight Versions: 9 to 28 VDC @ 35 mA typ., 50 mA max. Above 26
VDC, derate operating temperature to 50°C.
4. INPUT RANGES:
D.C. VOLTAGE
D.C. CURRENT
(DIP Switch Selectable)
(JMPR. Selectable)
±199.9 mVDC
±199.9 µADC
±1.999 VDC
±1.999 mADC
±19.99 VDC
±19.99 mADC
±199.9 VDC
±199.9 mADC
5. ACCURACY: (@ 23°C, less than 85% RH)
D.C. Voltage: ±(0.1% + 1 digit)
D.C. Current:
199.9 µA, 1.999 mA, 19.99 mA ranges: ±(0.1% + 1 digit)
199.9 mA range: ±(0.15% + 1 digit)
6. OVERRANGE RATINGS, PROTECTION & INDICATION:
9 to 28 VDC power circuit is not isolated from the signal circuit.
Max Input Voltage:
0 to 199.9 mVDC Range: 75 VDC
All other voltage Ranges: 300 VDC
Max Input Current:
199.9 µA through 19.99 mA: 10 times max. range current
199.9 mA: 1 amp
Overrange Indication: Overrange is indicated by a “1” displayed in the
most significant digit and the blanking of the three least significant digits.
7. READING RATE: 2.5 readings per second
8. RESPONSE TIME: 1.5 seconds to settle for a step change
9. NORMAL MODE REJECTION: 60 dB 50/60 Hz
MODEL CUB4I - MINIATURE D.C. CURRENT METER &
MODEL CUB4V - MINIATURE D.C. VOLTMETER
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip
installation is 2.15" (54.6) H x 3.00" (76.2) W.
UL Recognized Component,
File # E179259
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
Bulletin No. CUB4V/I-J
Drawing No. LP0256
Released 10/06
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
The unit should be installed in a location that does not
exceed the maximum operating temperature and provides
good air circulation. Placing the unit near devices that
generate excessive heat should be avoided. The bezel should
be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils,
etc.) to operate the keypad of the unit.
Installation
The CUB4 Volt and Current meters meet
NEMA 4X/IP65 requirements for indoor use, when properly
installed. The units are intended to be mounted into an enclosed panel. A
sponge rubber gasket, mounting clip, two screws, and nut fasteners are
provided to install and seal the unit in the panel cutout.
The following procedure assures proper installation:
1.Cut panel opening to specified dimensions. Remove burrs and clean panel
opening.
2. Carefully remove center section of the panel gasket and discard. Slide
gasket over rear of the unit to the back of the bezel.
3. Slide nut fastener into slot on mounting clip and then insert mounting screw
through nut on both sides of mounting clip. Tip of mounting screw should
NOT project through hole on clip.
4. Install CUB4 unit through panel cutout.
5. Slide mounting clip over rear of unit until clip is against back of panel. The
mounting clip and CUB4 housing have a latching feature to hold the unit in
place until tightened.
Note: Hold the CUB4 front bezel in place when sliding the mounting clip into
position.
6. Alternately tighten each mounting screw to ensure uniform gasket pressure.
Visually inspect the gasket for proper seal. The gasket should be
compressed approximately 75 to 80% of its original thickness.
(Recommended torque is 28 to 36 in-oz.)
7. If the gasket is not adequately compressed and the mounting screws cannot
be tightened any further, loosen mounting screws and insure that the clip is
latched as close as possible to the panel.
8. Repeat step #6 for tightening the mounting screws.
10. INPUT IMPEDANCE:
Voltmeter: 1 MΩ
Current Meter:
199.9 µA - 1 KΩ
1.999 mA - 100 Ω
19.99 mA - 10 Ω
199.9 mA - 1 Ω
11. CERTIFICATIONS AND COMPLIANCES:
SAFETY
ULRecognized Component, File # E179259, UL3101-1, CSAC22.2 No. 1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate # UL2356A-179259/USA,
CB Scheme Test Report # 98ME60090-000098
Issued by Underwriters Laboratories, Inc.
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m.
Process signal may deviate during EMI disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
I/O and power cables are routed in metal conduit connected to earth
ground.
2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms.
Process signal may deviate during EMI disturbance.
For operation without loss of performance:
Install power line filter RLC#LFIL0000 or equivalent at the unit.
Refer to the EMC Installation Guidelines section of this bulletin for
additional information.
12. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0° to 60°C (above 50°C, derate backlight
operating voltage to 26 VDC maximum).
Storage Temperature: -40° to 80°C
Operating and Storage Humidity: 85% max relative humidity (non-
condensing) from 0 to 60°C.
Vibration According to IEC 68-2-6: 5 to 500 Hz, in X, Y, Z direction for
1.5 hours, 5g’s.
Shock According to IEC 68-2-27: Operational 30 g, 11 msec in 3 directions.
Temperature Coefficient: 100 PPM/°C
Altitude: Up to 2000 meters.
13. CONSTRUCTION: High impact plastic case with clear viewing window.
(Panel gasket and mounting clip included.) This unit is rated for NEMA
4X/IP65 indoor use. Installation Category II, Pollution Degree 2
14. WEIGHT: 3.3 oz. (93.5 g)
Power mains class A
Enclosure class A
EN 55011
RF interference
Emissions to EN 50081-2
Level 4; 30 A/m
150 KHz - 80 MHz
EN 61000-4-8
Level 3; 10 V/rms 2
EN 61000-4-6
RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/O
EN 61000-4-4
Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m 1
EN 61000-4-3
Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contact
EN 61000-4-2
Electrostatic discharge
200 Hz, 50% duty cycle
900 MHz ± 5 MHz
Immunity to EN 50082-2
Level 3; 10 V/m
Simulation of cordless telephone ENV 50204
Power frequency magnetic fields
EMC Installation Guidelines
Although this unit is designed with a high degree of immunity to
ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of
electrical noise, source or coupling method into the unit may be different for
various installations. Cable length, routing and shield termination are very
important and can mean the difference between a successful or a troublesome
installation. Listed below are some EMC guidelines for successful installation
in an industrial environment.
1. The unit should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in
order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure.
The following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
WIRING CONNECTIONS
The electrical connections are made via screw-clamp terminals located on
the back of the unit. When wiring the unit, use the label to identify the wire
position with the proper function. All conductors should meet voltage and
current ratings for each terminal. Also cabling should conform to appropriate
standards of good installation, local codes and regulations. It is recommended
that power supplied to the unit be protected by a fuse or circuit breaker. Strip
the wire, leaving approximately ¼" bare wire exposed (stranded wires should
be tinned with solder). Insert the wire into the screw-clamp terminal and tighten
the screw until the wire is clamped tightly. Each terminal can accept up to two
#14 AWG wires.
DECIMAL POINT SELECTION
The CUB4 Volt and Current Meters can be set-up to read in 10ths, 100ths, or
1000ths. The decimal point position is DIP switch selectable for one of three
locations. If all the DIP switches are set to the “OFF” position, then NO
decimal point will appear in the display. The DIP switches are located at the rear
of the unit.
CUB4V SIGNAL INPUT
The voltage range is selected by setting one of the DIP switches S1 to S4
for the desired input voltage. The unit will indicate the direct readout for the
range selected.
Note: Only one Voltage Range switch (S1-S4) should be selected (ON).
The SCALE DIP switch (S5) and the Scaling Potentiometer are used
when it is necessary to scale the display to indicate other engineering units.
The Scale switch should be left in the “OFF” position when the application
requires direct voltage readout on the display.
The Calibration Potentiometer has been set at the factory and should not be
adjusted unless the unit is being re-calibrated with an accurate voltage source.
The power supply common and signal common are connected internally
at the same screw terminal marked COMM. The power supply common,
and the signal common must be at the same voltage potential. The voltmeter
cannot measure a voltage with a reference that is different than the power
supply common.
Caution: The Maximum Voltage for each switch position must not
be exceeded or the unit may be damaged (See Specifications).
Caution: 9 to 28 VDC power circuit is not isolated from the
signal circuit.
In many industrial applications, a voltmeter is required to display a reading
in terms of PSI, RPM, or some other unit of measure. The signal voltage being
measured is normally generated by a transducer which senses the variable and
delivers a linear output voltage. To provide the desired readout at the specified
voltage, the voltmeter must be scaled. The Scale switch, when in the “ON”
position, enables the Scale Potentiometer. The Scale Potentiometer is used with
a voltage range to provide a method of scaling the unit. The voltage DIP
switches are used to select one of the four coarse Division Factor ranges and the
Scale Potentiometer is a fine scale adjustment within the selected range. The
chart below shows the division factor range associated with each range
selection switch.
DIVISION FACTOR RANGE SELECTION CHART
S1: 0-199.9 mVDC (0.1 D.F. 1.2)
S2: 0-1.999 VDC (1.2 D.F. 10.5)
S3: 0-19.99 VDC (10.5 D.F. 100.5)
S4: 0-199.9 VDC (100.5 D.F. 1300)
Note: Enabling the Scale Potentiometer does NOT affect the calibration of
the unit.
To determine the proper voltage range for an application requiring scaling,
the “Division Factor” required to provide the proper display reading must first
be determined by using the following formula.
USING THE FORMULA:
D.F = VT x D.D.P.
D.R.
WHERE:
VT
=
Maximum Transducer Output
D.D.P.
=
Display Decimal Point
D.F.
=
Division Factor
D.R.
=
Desired Reading
D.D.P.
0.000
=
1
The DISPLAY DECIMAL POINT (D.D.P.)
00.00
=
10
is determined by the desired decimal
000.0
=
100
point placement in the readout.
0000
=
1000
After the Division Factor for the application has been calculated, the proper
voltage range switch that will provide for the Division Factor is set to the “ON”
position. Use the “Division Factor Range Selection Chart” to choose the proper
DIP switch setting.
Note: Only one voltage DIP switch should be turned on. Set the switch before
the voltage signal is applied.
EXAMPLE: A relative humidity transducer delivers a 7.0 VDC voltage at a
relative humidity of 75%.
D.F. = VT x D.D.P. = 7.0 x 1000 = 93.3
D.R. 75
This Division Factor is between 10.5 and 100.5, therefore DIP switch
position S3 is set to the “ON” position. The Scaling Potentiometer is then
adjusted for the desired readout at a known relative humidity.
CUB4I SIGNAL INPUT
The CUB4 Current Meter has four current ranges that are selected by
positioning the jumper in the proper location on the male header strip.
The SCALE DIP switch (S1) and the Scaling Potentiometer are used
when it is necessary to scale the display to indicate other engineering units.
The Scale switch should be left in the “OFF” position when the application
requires direct current readout on the display.
When the power supply is floating (unreferenced) to the desired
measurement points, the (-) signal input and the power supply common
should be connected. If the power supply is not floating (referenced), the
common mode voltage between the (-) signal input and power supply
common terminal must not be greater than 1.0 V peak. A common mode
voltage higher than 1.0 V peak will result in a measurement error.
The Calibration Potentiometer has been set at the factory and should not be
adjusted unless the unit is being re-calibrated with an accurate current source.
Caution: The Maximum Current for each jumper position must not
be exceeded or the unit may be damaged (See Specifications).
BLOCK DIAGRAM CUB4V
CURRENT METER SCALING
The CUB4 Current Meter display can be scaled to almost any lower
numerical value. Setting the Scale switch to the “ON” position enables the
Scale Potentiometer, which is used with the current range selection jumper to
scale the unit. The Scale potentiometer can be set to divide the normal current
reading by a division factor between 1 and 13.
EXAMPLE: The CUB4 Current Meter has been connected to measure a circuit
current to 120.0 mA maximum. However, in this application, the display is to
indicate percent of load current with 120.0 mA equivalent to 100.0 percent.
The scale potentiometer is adjusted to reduce the normal 120.0 mA signal input
display reading of 120.0 to indicate the desired reading of 100.0 on the display.
Scaling to obtain a numerical readout higher than the normal value of the
current can also be accomplished in most cases by selecting a lower current
range. However, the maximum current for the range must not be exceeded.
(See Specifications for maximum input currents.)
BLOCK DIAGRAM CUB4I
Indicating the Speed of a D.C. Motor
A foreman in a plant wants to get a more accurate indication of the speed
at which a variable speed DC motor drive is operating. The only indication
he has now is the position of a dial on the control panel.
The motor has a tachometer generator that will output a 10 VDC signal
when the motor is running at its maximum speed of 1800 RPM. The power
supply of the control has a 15 VDC output that can supply power to
the CUB4V.
Since this application requires a non-standard readout, it will be
necessary to scale the display. The Scale DIP switch is set to the “ON”
position to enable the Scale Potentiometer. The Division Factor is calculated
using the formula:
D.F.
=
(Maximum output) x D.D.P.
(Desired Display)
D.F.
=
10 x 1000
1800
D.F.
=
5.5
Since the division factor falls between 1.2 and 10.5, DIP switch position S2
is set to the “ON” position, according to the Division Factor Selection Chart.
To scale the CUB4 Voltmeter, the motor is run at full speed and a
calibrated photo tachometer is used to obtain the exact speed. The Scale
Potentiometer on the CUB4 Voltmeter is then adjusted until the display
reading agrees with the tachometer. Alternately, the output of a precision
voltage source set to +10 VDC can be connected to the signal input of the
unit and then adjust the scaling potentiometer for the desired reading.
ORDERING INFORMATION
TYPICAL VOLT & CURRENT MEASUREMENT APPLICATIONS
CURRENT METER APPLICATION
Analog Meter Replacement
A manufacturer wants to replace several 1 mA DC analog meter
movements with easy to read CUB4 Current Meters with backlighting. One
application involves measuring the flow rate of a liquid to indicate 0 to 250
gallons per minute.
Since 1 mA of current flow requires a display reading of 250, the CUB4
Current Meter will need to be scaled. The Scale DIP switch is set to the
“ON” position enabling the Scale Potentiometer. The proper current range
for the application is then selected. The Scale potentiometer will divide the
display reading by 1 to 13, for the particular current range selected. A
reading of 250 is 4 times less than the normal reading at 1 mA for the 0 to
1.999 mA range, therefore the jumper is installed in the 0-1.999 mA range
position. No decimal point is selected because the resolution is 1 gallon.
The CUB4 Current Meter can now be scaled. Apply 1 mA to the signal
input and adjust the scale potentiometer to the desired reading.
TROUBLESHOOTING
For further technical assistance, contact technical support at the appropriate
company numbers listed.
MODEL NO.
DESCRIPTION
PART NUMBERS
DC Voltmeter
CUB4V000
CUB4V
CUB4V010
CUB4V020
DC Current Meter
CUB4I000
CUB4I
CUB4I010
DC Current Meter W/Red Backlighting
CUB4I020
MLPS
Micro Line/Sensor Power Supply
MLPS1000
DC Voltmeter W/Red Backlighting
DC Voltmeter W/Yel-Grn Backlighting
DC Current Meter W/Yel-Grn Backlighting
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
Red Lion Controls
20 Willow Springs Circle
York PA 17402
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls AP
31, Kaki Bukit Road 3,
#06-04/05 TechLink
Singapore 417818
Tel +65 6744-6613
Fax +65 6743-3360
Red Lion Controls BV
Basicweg 11b
NL - 3821 BR Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793