Saci MTA36 Operation & User’s Manual
Read Online
Read the Saci MTA36 Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
MTA36 User Manual
-1-
1. SAFETY PRECAUTIONS
The manufacturer is not responsible of the failure comply with the instructions in this
manual.
CAUTION:
Ensure that only qualified technicians work on the installation and maintenance.
Never work alone.
The electrical parameters supplied should be within the nominal range
Before any work with or on the equipment, isolate the voltage inputs and auxiliary
power supplies, cut the secondary of all CTs (current transformers), but never cut the
secondary of the PT. (Power Transformers)
Always use an appropriate voltage sensing device to ensure that everything is switched
off and that no voltage is present in any part of the equipment
Risk in the device
◆ The voltage of the auxiliary power supply is outside the nominal range
◆ The frequency of the power distribution system is outside the nominal range.
◆ The input polarity of the voltage or current is connected incorrectly.
◆ Remove or connect communication connections without switching off the device.
◆ Connect the cables to the terminal contrary to the instructions.
"Danger" is used to warn workers that a danger
exists; if the "Danger" is ignored, it will cause
severe personal injury, death, equipment
damage or property damage.
"Warning" is used to indicate that death or
serious personal injury may occur if proper
precautions are not taken.
MTA36 User Manual
-2-
2. ABOUT THIS MANUAL
This manual deals with the characteristics of the MTA36 measuring device in its
different versions and shows the necessary instructions for its correct installation and
start-up.
The differences between the versions are indicated by a letter and a number at the
end of the product description.
At the end of the manual you will find the ModBus register map necessary to
communicate with the equipment. However, this manual describes the configuration
and start-up of the equipment through the Saci software.
This software can be downloaded free from the Saci website (www.saci.es). To install
it, you only need to download and run the file. Once executed, follow the installation
instructions and you will have access to the application which you can communicate
with the equipment.
This manual assumes that user has knowledge about the network measurement
parameters and knows the measurement and power supply system’s where the
equipment will be installed.
If you have any questions about this user manual or the equipment, please contact
your local Saci distributor.
MTA36 User Manual
-3-
INDEX
1. SAFETY PRECAUTIONS ............................................................................................................... 1
2. ABOUT THIS MANUAL ............................................................................................................... 2
3. GENERAL DESCRIPTION ............................................................................................................. 5
3.1 Models ................................................................................................................................. 6
4. MEASUREMENT ......................................................................................................................... 6
4.1 Measure parameters through the user interface: .............................................................. 7
4.1.1 Network parameters .................................................................................................... 7
4.1.2 Energy ........................................................................................................................... 7
4.1.3 Harmonics .................................................................................................................... 8
4.1.4 Network quality ............................................................................................................ 9
4.1.5 Demand ........................................................................................................................ 9
4.1.6 Max/Min ..................................................................................................................... 10
4.1.7 Average values ........................................................................................................... 10
4.1.8 Freezing Data .............................................................................................................. 11
5. INSTALLATION ......................................................................................................................... 12
5.1 Dimensions ........................................................................................................................ 12
5.1.1 MTA36L ...................................................................................................................... 12
5.1.2 MTA36R ...................................................................................................................... 12
5.1.3 MTA36F ...................................................................................................................... 12
5.1.4 MTA36-IFLORA ........................................................................................................... 13
5.2 Assembly ........................................................................................................................... 13
5.2.1 Single-phase device assembly: ................................................................................... 13
5.2.2 Three phase device assembly: ................................................................................... 14
5.2.3 Communication module assembly: ............................................................................ 15
6. CONFIGURATION ..................................................................................................................... 17
1º Connect to the device. .................................................................................................... 17
2º Basic Configuration. ........................................................................................................ 17
3º Configuration of the tariffs. ............................................................................................ 19
MTA36 User Manual
-4-
4º LoRa configuration .......................................................................................................... 20
5. Module (only for MTA36-IFLORA) ................................................................................... 22
7. TECHNICAL SPECIFICATIONS ................................................................................................... 24
7.1 MTA36 Meters: ............................................................................................................. 24
7.2 MTA36-IFLORA: ............................................................................................................. 26
MTA36 User Manual
-5-
3. GENERAL DESCRIPTION
The MTA36 measuring transformer stands out because of its easy installation and the
high number of network parameters it can measure. These measurement power
meters are designed for the calculation and measurement of the electrical variables,
voltage, current, frequency, power, power factor, energy, harmonic components,
etc. of a power distribution network. It is available for both single-phase and three-
phase measurement.
Its revolutionary design brings together in the same device the instrument transformer
and the meter, which together with its communication options create a versatile and
easy-to-install device.
DEVICE
It consists of a main transformer on which communications are concentrated
and two auxiliary ones (in three-phase network's case) that communicate the
measurements to the main transformer.
Possibility of wireless communication through LoRa, making installation even
easier and saving costs.
LED indicators for connection and communication.
Insulation piercing installation system for the voltage.
Open transformers that allow the installation of the equipment without
opening the circuit.
USER'S INTERFACE
Real-time data on all network parameters.
Available in several languages.
Intuitive design.
COMMUNICATIONS
ModBus-RTU communication protocol.
Possibility of communication through RS-485 network (up to 9600 bps).
Possibility of wireless communication through LoRa (up to 9600 bps).
MEASUREMENTS
Measured in all 4 quadrants. Class 1.
Measurement of maximum and current demand.
Measurement up to the harmonic 31. Measurement of the harmonic distortion
of both voltage and current.
MTA36 User Manual
-6-
Measurement of network unbalance.
TARIFFS
Up to 4 fully configurable tariffs.
Consumption of the current month, the previous 12 months and total
consumption.
3.1 Models
Model
Description
MTA36L1
Single-phase power meter with LoRa communications
MTA36R1
Single-phase power meter with RS485 communications
MTA36L3
Three-phase power meter with LoRa communications
MTA36R3
Three-phase power meter with RS485 communications
MTA36F3
Auxiliary transformer
MTA36-IFLORA
RS-485/LoRa communication module
4. MEASUREMENT
Voltage
Current
Power
Power factor
Frequency
Demand
Energy
Total harmonic distortion
Imbalance
Contact point temperature
The following list shows the variables that can be measured including relative variables
calculated from the basic electrical parameters:
Measurement variable
Instant
Máx
Mín
Demand
Average
Sum
Units
V1 V2 V3
√
√
√
√
[V,kV]
V12 V23 V31
√
√
√
√
[V,kV]
I1 I2 I3
√
√
√
√
√
[A,kA]
F
√
√
√
√
[Hz]
P P1 P2 P3
√
√
√
√
√
[kW,MW,GW]
Q Q1 Q2 Q3
√
√
√
√
[kvar,Mvar,Gvar]
S S1 S2 S3
√
√
√
√
[kVA,MVA,GVA]
PF PF1 PF2 PF3
√
√
√
√
-
EP+ EP-
√
[kWh,MWh,
GWh]
MTA36 User Manual
-7-
4.1 Measure parameters through the user interface:
4.1.1 Network parameters
The device measures the voltage, current, frequency, power and power factor of each
phase and of the system.
4.1.2 Energy
The device supports excellent energy measurement functions such as the following:
Bi-directional energy measurement.
Four quadrants of reactive energy measurement
Metering of tariff energy (CDU)
All energy values are calculated on the basis of the secondary value; whose minimum
resolution is 1WH of 1varh. Whenever the device is connected, the primary energy
value increases or decreases at the rate of 1Wh(1varh). Users can reset the energy
data through the application according to specific needs.
EQ1 EQ2 EQ3 EQ4
√
[kvarh,MvarhGvarh
]
Energy storage
√
THDV1 THDV2 THDV3
√
[% ]
THDI1 THDI2 THDI3
√
[% ]
Harmonics RMS-U (1-31th)
√
[% ]
Harmonics RMS-I (1-31th)
√
[% ]
Unbalance-U
√
[% ]
Unbalance-I
√
[% ]
Puncture temperature
√
ºC
MTA36 User Manual
-8-
The device supports the tariff energy measurement of four time zones at most. There
are two fully configurable tariff days that can be set for all 12 months of the year.
4.1.3 Harmonics
The instrument supports network harmonics (2-31st) RMS value. It also measures
harmonic distortion and voltage and current unbalance.
MTA36 User Manual
-9-
4.1.4 Network quality
The device measures the phase angle of voltage and current. The phase angle of
voltage and current of each phase is shown. The phase angle of A phase voltage is
default set to 0°. The phase angle of other types of signals is shown in relation to the A
phase voltage (unit: °). It also measures the voltage deviation and frequency.
4.1.5 Demand
The instrument supports independent demand logging channels that can measure the
maximum demand value and the present value of both current and power. It is
possible to reset the maximum demand from the application.
MTA36 User Manual
-10-
4.1.6 Max/Min
When the measured value is the maximum or minimum value, in an instant, the
instrument will record this value in the non-volatile memory.
These maximum or minimum values include three-phase voltage, line voltage,
frequency, three-phase current, total and three-phase active power, total and three-
phase reactive power, total apparent power and the total power factor.
It is possible to reset these values through the application.
4.1.7 Average values
The device records the average value of voltage, current, frequency, power and power
factor of each phase and of the system.
MTA36 User Manual
-11-
4.1.8 Freezing Data
The device is capable of recording the active power of each phase and total; and the
active energy imported from each phase and total each a certain time, which is
adjustable by the user through the configuration menu.
MTA36 User Manual
-12-
5. INSTALLATION
5.1 Dimensions
5.1.1 MTA36L
5.1.2 MTA36R
5.1.3 MTA36F
The length of the cable connecting the MTA36F with the communication cable is 1m.
∅ 36
92
64
6
18.5
71
20
92
64
6
18.5
71
13
∅ 36
∅ 36
90
64
6
18.5
71
MTA36 User Manual
-13-
5.1.4 MTA36-IFLORA
5.2 Assembly
5.2.1 Single-phase device assembly:
1
Connect the N line to the
Un wiring hole. Use the
insulated piercing
connector for that.
2
Open
the
puncture
transformer, and connect
the transformer to the
cable
and
close
the
transformer and tighten
screws.
Make
sure
that
the
current direction of the
cable is consistent with
the
arrow
on
the
transformer.
N
MTA36 User Manual
-14-
3
Tighten the puncture knob
until
the
red
power
indicator
on
the
transformer is lit.
5.2.2 Three phase device assembly:
1
Connect the N line to
the Un wiring hole of
the puncture
transformer, and
tighten the N line
wiring hole fastening
screws. Use the
insulated piercing
connector for that.
2
Open the puncture
transformer,
and
connect
the
MTA36L3 to the L2-
phase cable and close
the transformer and
tighten screws.
Make sure that the
current direction of
the
cable
is
consistent with the
arrow
on
the
transformer.
3
Connect
two
MTA36F3
transformer to the
L1-phase
and
L3-
phase
cables
respectively,
and
connect the lead wire
to the corresponding
wiring port of the
SDT13.
N
N
L2
N
L2
L1
L3
MTA36 User Manual
-15-
4
Tighten the puncture
knobs until the red
power indicator lights
on L2 transformer are
lit.
Note: In the field installation, it is recommended to use insulating gloves to operate to
prevent electric shock
If the cable diameter is small, the cable can be fixed with a tie.
5.2.3 Communication module assembly:
To ensure proper operation of the device, please avoid placing it near high-powered
electrical equipment or equipment that can produce strong EMF signals, as this
equipment may decrease the transmission power or transmit a poor quality signal.
35mm standard DIN-rail
N
L2
L1
L3
MTA36 User Manual
-17-
6. CONFIGURATION
Once the device is installed, the application is downloaded and the communication is
made, the device has to be configured according to its installation:
1º Connect to the device.
To communicate with the instrument through the ModBus protocol it is necessary that
the instrument has an identity (by default all the instruments have the identity 1)
When connected to the RS485 model, it can be connected via a COM port or via
TCP/IP. In this case you must enter the IP address and port.
Once connected, just press the close button and enter the configuration menu
2º Basic Configuration.
In the configuration menu we enter the basic configuration menu and introduce the
network parameters. Here we can change the identity of the equipment (max 247)*,
the freezing data refresh time and the voltage and current input value.
MTA36 User Manual
-18-
The equipment does not have RCT (Real Clock Time), but the time can be introduced.
By pressing the synchronize button, the device will take the date and time from the
computer to which it is connected (as it does not have RCT, the time can be delayed, it
is advisable to synchronize the device from time to time for its correct operation,
mainly in tariff mode).
For the demand side configuration, the energy demand is calculated using the
arithmetic integration of the power values over a period of time divided by the length
of the period. The result is equivalent to the energy accumulated during the period of
time divided by the length of the period.
The current demand is calculated using the arithmetic integration of the rms current
values over a period of time divided by the period length.
The duration of the intervals for calculating the demand is taken care of by the
equipment. Several methods can be implemented:
Fixed block interval (fix): the intervals are consecutive, the power meter calculates and
updates the demand at the end of each interval.
Note: 15min is only an example.
Sliding block interval (slip): the intervals are sliding. The equipment calculates and
updates the demand at the slip rate.
Note: 15min is only an example.
Relative time parameters are set as t (slip time, unit: minutes) and T (slip block
interval, unit: minute)
MTA36 User Manual
-19-
Fixed interval mode means that the average demand value in T minutes is calculated
for each T block, and then the value is recorded. A month's demand is automatically
recorded at a fixed time.
Sliding interval mode means that the average demand value of the last T minutes is
calculated, and then the value is recorded. The demand of a month is automatically
recorded at a fixed time.
*RS485 version:
For the RS485 version, the MTA36R, the modbus identity is configured differently. A
table with the different identities according to the position of the tab at the top is
shown below:
TAB POSITION
MODBUS IDENTITY
0
User-defined
1
2
2
1
3
3
4
8
5
10
6
9
7
11
8
4
9
6
A
5
B
7
C
12
D
14
E
13
F
0
To change the identity of the 0 position it is necessary to write it from position F. To do
this:
1. The tab is positioned in position F.
2. Using the software, the device is connected with the identity 0.
3. Enter the Configuration->Basic configuration menu.
4. Enter the desired identity and press the save button.
5. In the software, the communication with the device is cut off.
6. The tab is changed to position 0.
7. Using the software you connect the device with the desired identity.
3º Configuration of the tariffs.
It is possible to configure two different tariff days with time intervals and up to 4
different tariffs.
It is also possible to configure which day of the tariff is each month.
MTA36 User Manual
-20-
4º LoRa configuration
*Only for devices with LoRa communication
The equipment has 16 different communication channels, each with different
frequencies. The European band is 868 MHz. The frequency, in MHz, of each of the
different channels is shown.
To configure a channel in the instrument you must place the tab at the top of the
device on the number of the channel you want to configure it on. You must take into
account that the number 0 corresponds to channel 1, the 1 to channel 2... and so on
until the F that corresponds to channel 16. The F channel is recommended not to be
MTA36 User Manual
-21-
used because it is a synchronization channel used to configure the devices. Its
frequency is always the same regardless of the band used
Below is a table with the parameters of the 16 channels according to their frequency
band:
868
Channel
Position
Frequency (MHz)
Spread spectrum
Band width (kHz)
Speed in open air (bps)
Sensitivity (dBm)
1
0
869.53
7
125
4800
-125
2
1
871.46
7
125
4800
-125
3
2
872.91
7
125
4800
-125
4
3
874.43
7
125
4800
-125
5
4
875.95
7
250
9600
-122
6
5
877.48
7
250
9600
-122
7
6
878.86
7
250
9600
-122
8
7
880.32
7
250
9600
-122
9
8
884.87
8
125
2400
-128
10
9
883.41
8
125
2400
-128
11
A
884.97
8
125
2400
-128
12
B
886.58
8
125
2400
-128
13
C
889.06
12
500
800
-130
14
D
891.39
12
500
800
-130
15
E
894.82
12
500
800
-130
16
F
866.50
7
125
4800
-125
468
Canal
Posición
Frecuencia (MHz)
Spread spectrum
Ancho de banda (kHz)
Velocidad en el aire
(bps)
Sensibilidad (dBm)
1
0
471.53
7
125
4800
-125
2
1
473.46
7
125
4800
-125
3
2
474.91
7
125
4800
-125
4
3
476.43
7
125
4800
-125
5
4
477.95
7
250
9600
-122
MTA36 User Manual
-22-
6
5
479.48
7
250
9600
-122
7
6
480.86
7
250
9600
-122
8
7
482.32
7
250
9600
-122
9
8
483.87
8
125
2400
-128
10
9
485.41
8
125
2400
-128
11
A
486.97
8
125
2400
-128
12
B
488.58
8
125
2400
-128
13
C
491.06
12
500
800
-130
14
D
493.39
12
500
800
-130
15
E
496.82
12
500
800
-130
16
F
866.50
7
125
4800
-125
915
Canal
Posición
Frecuencia (MHz)
Spread spectrum
Ancho de banda (kHz)
Velocidad en el aire
(bps)
Sensibilidad (dBm)
1
0
918.53
7
125
4800
-125
2
1
920.46
7
125
4800
-125
3
2
921.91
7
125
4800
-125
4
3
922.43
7
125
4800
-125
5
4
924.95
7
250
9600
-122
6
5
926.48
7
250
9600
-122
7
6
927.86
7
250
9600
-122
8
7
929.32
7
250
9600
-122
9
8
930.87
8
125
2400
-128
10
9
932.41
8
125
2400
-128
11
A
933.97
8
125
2400
-128
12
B
935.58
8
125
2400
-128
13
C
938.06
12
500
800
-130
14
D
940.39
12
500
800
-130
15
E
943.82
12
500
800
-130
16
F
866.50
7
125
4800
-125
5. Module (only for MTA36-IFLORA)
If the MTA36-IFLORA communication module is available, it can be configured through
this screen.
You can configure the communication channel, which must coincide with the one set
in the equipment. It is possible to enter the desired frequency from the manual mode.
You can also configure the transmission power (from 0 to 20 mW) and the timeout
when receiving and sending records (up to 65535 ms). For example, when the
MTA36 User Manual
-23-
transmission speed is 4800 bauds in the air, and you want to receive 20 registers, and
the sending and response time is 200 ms, it is recommended to set a timeout of 200
ms.
On the other hand, it is possible to configure the communication speed between the
module and the computer, choosing the speed; the mode is fixed (N-8-1).
There is a manual configuration mode where you can set the communication
frequency, in MHz, the bandwidth in kHz and the spread spectrum, which indicates the
number of bits used to encode a symbol. The higher the SS, the lower the transfer rate,
but the higher the immunity to interference
A table of the default channel settings is shown below:
Channel
Frequency (MHz)
Spread spectrum
Band width (kHz)
Speed in open air (bps)
Sensitivity (dBm)
1
869.53
7
125
4800
-125
2
871.46
7
125
4800
-125
3
872.91
7
125
4800
-125
4
874.43
7
125
4800
-125
5
875.95
7
250
9600
-122
6
877.48
7
250
9600
-122
7
878.86
7
250
9600
-122
8
880.32
7
250
9600
-122
9
884.87
8
125
2400
-128
10
883.41
8
125
2400
-128
11
884.97
8
125
2400
-128
12
886.58
8
125
2400
-128
13
889.06
12
500
800
-130
14
891.39
12
500
800
-130
15
894.82
12
500
800
-130
16
866.50
7
125
4800
-125
MTA36 User Manual
-24-
The default identity of the communication module is 0xFF. If this identity conflicts with
your installation, please contact us to configure the address according to your
preferences.
7. TECHNICAL SPECIFICATIONS
7.1 MTA36 Meters:
Precision
Voltage and current
0.5%
Energy and power factor
1%
Frequency
±0.01Hz
Active energy
IEC62053-22, class 1
Reactive energy
IEC62053-23, class 2
Puncture temperature
±2 ºC
Working environment conditions
Storage temperature
-25°C -- 70°C
Relative humidity
≤95%RH,non-condensing
Working altitude
≤2500m
Antifouling level
No corrosion gas
Protection grade
Panel IP54,case IP20
Insulation
Resistance of the signal, power and output terminal to
the shell is >100MΩ
Withstand voltage
Input and power supply≥2kV, input and output≥2kV
, power supply and output≥2kV
Cable section
Minimum: 16mm2
Maximum: 510mm2
Working power supply
Nominal range
AC/DC(80~270)V
Consumption
≤5VA
Withstand voltage
≥2kV
Voltage input
Range
3×230/400V
Resolution
0.1 V
Impedance
≥1.7 MΩ/phase
Consumption
≤0.1 VA /phase
Overload
Continuous:1.2Vn,Instantaneous:2Vn/10s
Frequency
45-65 Hz
MTA36 User Manual
-25-
Current input
Range
50(600)A
Resolution
1 mA
Impedance
≤20mΩ/phase
Consumption
≤0.2 VA /phase
Overload
Continuous:1.2In, Instantaneous:10In/5s
Communication interface
Physical interface
RS-485
LoRa
Baud rate
Up to 9600bps Up to 9600bps
Communication protocol
Modbus-RTU
Modbus-RTU
Insulation voltage
2000 VAC (1
min)
--
Communication rate
--
1 km indoor
10 km outdoor
Electromagnetic compatibility
Electrostatic discharge immunity
Level IEC 61000-4-2-III
Radiated susceptibility
Level IEC 61000-4-3-III
Electrical fast transient pulse immunity
Level IEC 61000-4-4-IV
Shock (surge) noise immunity
Level IEC 61000-4-5-IV
Conducted interference noise immunity
of
radio
frequency
field
induced
conduction
Level IEC 61000-4-6-III
Power
frequency
magnetic
field
immunity
Level IEC 61000-4-8-III
Voltage sag and short interruption
immunity
Level IEC 61000-4-11-III
MTA36 User Manual
-26-
7.2 MTA36-IFLORA:
Wireless
interface
T/R frequency
860MHz~900MHz,0.1MHz
Modulation
method
LORA
Transmitting power
+17.6dBm/100mW
Receiving sensitivity [email protected]
RS485
interface
Communication
method
Semi duplex
Baud rate
2400~19200bps, defaulted as
9600bps
Data format
n81
Power
supply
Voltage range
AC/DC 80~270V
Consumption
<2VA
Working environment
-25℃~70℃,≤93%RH
Storage environment
-40℃~85℃,≤93%RH
Communication rate
1 km indoor
10 km outdoor