(Always read these precautions before using this equipment.)

Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product. In this manual, the safety precautions are ranked as "WARNING" and "CAUTION". Note that the caution level may lead to a serious accident according to the circumstances. Always follow the instructions of both levels because they are important to personal safety. Please save this manual to make it accessible when required and always forward it to the end user. [DESIGN PRECAUTIONS] WARNING ● Some failures of the GOT or cable may keep the outputs on or off. Some failures of a touch panel may cause malfunction of the input objects such as a touch switch. An external monitoring circuit should be provided to check for output signals which may lead to a serious accident. Not doing so can cause an accident due to false output or malfunction. ● Do not use the GOT as the warning device that may cause a serious accident. An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning. Not doing so can cause an accident due to false output or malfunction. ● When the GOT detects its backlight failure, the GOT disables the input operation on the touch switch(s). Thus, operators cannot operate the GOT with touches. The GOT backlight failure can be checked with a system signal of the GOT. ● Even when the display section has dimmed due to a failure of the liquid crystal section or the backlight on the GOT, the input operation of the touch switches may still be enabled. This may cause an incorrect operation of the touch switches. For example, if an operator assumes that the display section has dimmed because of the screen save function and touches the display section to cancel the screen save, a touch switch may be activated. WARNING Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury. CAUTION Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.

● The display section of the GOT is an analog-resistive type touch panel. Simultaneous pressing of two

or more areas on the display section may activate the switch between those areas. Do not press two or more areas simultaneously on the display section. Doing so may cause an accident due to incorrect output or malfunction. ● When programs or parameters of the controller (such as a PLC) that is monitored by the GOT are changed, be sure to shut off the power of the GOT promptly and power on the GOT again. Not doing so can cause an accident due to false output or malfunction. ● If a communication fault (including cable disconnection) occurs during monitoring on the GOT, communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative. A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur. Not doing so can cause an accident due to false output or malfunction. ● To maintain the security (confidentiality, integrity, and availability) of the GOT and the system against unauthorized access, DoS*1 attacks, computer viruses, and other cyberattacks from unreliable networks and devices via network, take appropriate measures such as firewalls, virtual private networks (VPNs), and antivirus solutions. Mitsubishi Electric shall have no responsibility or liability for any problems involving GOT trouble and system trouble by unauthorized access, DoS attacks, computer viruses, and other cyberattacks. *1 DoS: A denial-of-service (DoS) attack disrupts services by overloading systems or exploiting vulnerabilities, resulting in a denial-of-service (DoS) state. CAUTION ● Do not bundle the control and communication cables with main-circuit, power or other wiring. Run the above cables separately from such wiring and keep them a minimum of 100mm apart. Not doing so noise can cause a malfunction. ● Do not press the GOT display section with a pointed material as a pen or driver. Doing so can result in a damage or failure of the display section. ● When the GOT is connected to the Ethernet network, the available IP address is restricted according to the system configuration. When multiple GOTs are connected to the Ethernet network: Do not set the IP address (192.168.3.18) for the GOTs and the controllers in the network. When a single GOT is connected to the Ethernet network: Do not set the IP address (192.168.3.18) for the controllers except the GOT in the network. Doing so can cause the IP address duplication. The duplication can negatively affect the communication of the device with the IP address (192.168.3.18). The operation at the IP address duplication depends on the devices and the system. ● Turn on the controllers and the network devices to be ready for communication before they communicate with the GOT. Failure to do so can cause a communication error on the GOT. ● When the GOT is subject to shock or vibration, or some colors appear on the screen of the GOT, the screen of the GOT might flicker.

● Be sure to shut off all phases of the external power supply used by the system before mounting or

removing the GOT main unit to/from the panel. Not doing so can cause the unit to fail or malfunction. CAUTION ● Use the GOT in the environment that satisfies the general specifications described in this manual. Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration. ● When mounting the GOT to the control panel, tighten the mounting screws in the specified torque range (0.36N·m to 0.48N·m) with a Phillips-head screwdriver No.2. Undertightening can cause the GOT to drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the GOT. ● Remove the protective film of the GOT. When the user continues using the GOT with the protective film, the film may not be removed. ● Operate and store the GOT in environments without direct sunlight, high temperature, dust, humidity, and vibrations. ● Do not use the GOT in an environment with oil or chemicals. Doing so may cause failure or malfunction due to the oil or chemical entering into the GOT.

● Be sure to shut off all phases of the external power supply used by the system before wiring. Failure

to do so may result in an electric shock, product damage or malfunctions. CAUTION ● Please make sure to ground FG terminal of the GOT power supply section by applying 100Ω or less which is used exclusively for the GOT. Not doing so may cause an electric shock or malfunction. ● Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product. Not doing so can cause a fire or failure. ● Tighten the terminal screws of the GOT power supply section in the specified torque range (0.5N·m to 0.6N·m). Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT. ● Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction. ● Plug the communication cable into the GOT interface or the connector of the connected unit, and tighten the mounting screws and the terminal screws in the specified torque range. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.

[TEST OPERATION PRECAUTIONS]

[STARTUP/MAINTENANCE PRECAUTIONS] [STARTUP/MAINTENANCE PRECAUTIONS] WARNING ● Before performing the test operations of the user creation monitor screen (such as turning ON or OFF bit device, changing the word device current value, changing the settings or current values of the timer or counter, and changing the buffer memory current value), read through the manual carefully and make yourself familiar with the operation method. During test operation, never change the data of the devices which are used to perform significant operation for the system. False output or malfunction can cause an accident. WARNING ● When power is on, do not touch the terminals. Doing so can cause an electric shock or malfunction. ● Before starting cleaning or terminal screw retightening, always switch off the power externally in all phases. Not doing so can cause the unit to fail or malfunction. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit. CAUTION ● Do not disassemble or modify the unit. Doing so can cause a failure, malfunction, injury or fire. ● Do not touch the conductive and electronic parts of the unit directly. Doing so can cause a unit malfunction or failure. ● The cables connected to the unit must be run in ducts or clamped. Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault. ● When unplugging the cable connected to the unit, do not hold and pull from the cable portion. Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault. ● Do not drop the module or subject it to strong shock. A module damage may result. ● Before touching the unit, always touch grounded metals, etc. to discharge static electricity from human body, etc. Not doing so can cause the unit to fail or malfunction.

[TOUCH PANEL PRECAUTIONS]

[PRECAUTIONS WHEN THE DATA STORAGE IS IN USE] [PRECAUTIONS WHEN THE DATA STORAGE IS IN USE] [DISPOSAL PRECAUTIONS] CAUTION ● For the analog-resistive film type touch panels, normally the adjustment is not required. However, the difference between a touched position and the object position may occur as the period of use elapses. When any difference between a touched position and the object position occurs, execute the touch panel calibration. ● When any difference between a touched position and the object position occurs, other object may be activated. This may cause an unexpected operation due to incorrect output or malfunction. WARNING ● If the SD card mounted on drive A of the GOT is removed while the GOT is accessed, processing for the GOT might be interrupted about for 20 seconds. The GOT cannot be operated during this period. The functions that run in the background including a screen updating, alarm, logging, scripts, and others are also interrupted. Since this interruption makes an impact to the system operation, it might cause failure. After inhibiting access to the SD card on the GOT utility screen, check that the SD card access LED is off and remove the SD card. CAUTION ● If the data storage mounted on the GOT is removed while the GOT is accessed, the data storage and files are damaged. To remove the data storage from the GOT, check that the access to the data storage in SD card access LED, the system signal, and others is not performed. ● When removing the SD card from the GOT, make sure to support the SD card by hand as it may pop out. Failure to do so may cause the SD card to drop from the GOT, resulting in a failure or break. ● Before removing the USB device from the GOT, follow the procedure for removal on the utility screen of the GOT. After the successful completion dialog is displayed, remove the USB device by hand carefully. Failure to do so may cause the USB device to drop from the GOT, resulting in a failure or break. CAUTION ● When disposing of this product, treat it as industrial waste.

● Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be

exposed to the impact exceeding the impact resistance described in the general specifications of this manual, as they are precision devices. Failure to do so may cause the unit to fail. Check if the unit operates correctly after transportation. ● When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method). Additionally, disinfect and protect wood from insects before packing products.

SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 About Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Abbreviations and Generic Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 CHAPTER 1 OVERVIEW 19 1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Rough procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 CHAPTER 2 SYSTEM CONFIGURATION 23 2.1 Overall Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 2.2 Component List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Explanation of the GOT model name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 GOT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 Extension unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 CHAPTER 3 SPECIFICATIONS 27 3.1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 3.2 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 3.3 Power Supply Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 3.4 GOT Connector Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 RS-232 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 RS-422 interface and RS-422/485 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 CHAPTER 4 PART NAME 33 4.1 Front Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 4.2 Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 4.3 Bottom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 CHAPTER 5 EMC DIRECTIVE 39 5.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 Conforming standards in the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 5.2 EMC Directive Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 Installing the GOT on the control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Installing a noise filter (power supply line filter). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 System configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Connection of power cables and ground cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Fabricating a connection cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Grounding a cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46 CHAPTER 6 INSTALLATION 47 6.1 Control Panel Inside Dimensions for Mounting GOT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.2 Panel Cutting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 6.3 Mounting Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49

Control Panel Temperature and Mounting Angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

6.5 Installation Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 CHAPTER 7 WIRING 53 7.1 Power Supply Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Cable types and wire end processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Wiring example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 GOT's ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 The cause of malfunctions related wiring/Remedy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 7.2 Wiring Inside and Outside the Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Wiring inside . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Outside the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58 Attaching surge killers to control equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 CHAPTER 8 OPTION 61 8.1 SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Applicable SD card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Installation/removal procedure of SD card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 CHAPTER 9 UTILITY FUNCTION 63 9.1 Utility Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63 9.2 Utility Function List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 9.3 Utility Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66 Display operation of main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68 Utility basic configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 Basic operation of settings change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 CHAPTER 10 LANGUAGE SETTING (LANGUAGE) 73 10.1 Display language setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73 Display language setting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73 Language setting operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 CHAPTER 11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING) 75 11.1 Standard I/F Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Standard I/F functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Standard I/F display operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75 Display contents of standard I/F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76 Detail information setting operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79 Channel setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Driver setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 11.2 GOT IP Address Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Display operation of GOT IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 11.3 Ethernet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86 Setting function for Ethernet communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Display operation of Ethernet communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86 Display contents of Ethernet setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 11.4 Communication Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Communication monitor functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Communication monitor display operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Screen display content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 11.5 Ethernet Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93 11.6 Setting the Transparent Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 11.7 Keyword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96 Keyword functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96 Keyword display operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96 Regist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97 Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Clear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102 Protect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 CHAPTER 12 DISPLAY AND OPERATION SETTINGS (GOT SET UP) 105 12.1 Display Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Display setting functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Display operation of display setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106 Display setting operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 12.2 Operation Setting (Settings for Operation). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108 Operation setting functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108 Display operation of operation setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Setting operation of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Position correction of the touch panel (touch panel calibration setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Setting the utility call keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 12.3 Inherent Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Setting function for inherent information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Display operation of inherent information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Setting operation for inherent information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 12.4 GOT internal device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Setting the GOT internal device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 GOT internal device monitor display operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 GOT internal device monitor setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 12.5 VNC Server Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 VNC server function setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Display operation of the VNC server function setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 VNC server function setting operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 12.6 License Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 License management setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Display operation of the license management setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Setting operation of license management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121 12.7 IP Filter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122 IP filter setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Display operation of the IP filter setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Setting procedure for the IP filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 CHAPTER 13 SECURITY LEVEL AND OPERATOR SETTINGS (SECURITY SETTING) 129 13.1 Security Level Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129 13.2 Operator Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Operator information management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

Password change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141

Function setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 13.3 Login/Logout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 CHAPTER 14 CLOCK SETTINGS (TIME SETTING AND DISPLAY) 147 14.1 Time Setting and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147 Time setting and display functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 Clock synchronization method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148 Time setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Adjusting the clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151 Local time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155 CHAPTER 15 CONTROL OF VARIOUS DATA (DATA CONTROL) 159 15.1 Data Storage Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Data type and storage location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Checking version of basic system application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161 15.2 OS information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163 15.3 Resource Data Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 Alarm information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165 Recipe information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170 Logging information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .176 Image file management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 Operation log information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184 15.4 SD Card Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 Functions of SD card access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 Display operation of SD card access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .190 Operation of SD card access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 15.5 SD Card Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 15.6 Clear data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 Clear data functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .193 Clear data display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .193 Clear data operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 15.7 Data Copy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194 Display operation of data copy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194 Operation of data copy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195 15.8 BACKUP/RESTORE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 BACKUP/RESTORE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 System configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 Access range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202 Security and password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .205 Operation of backup/restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 Operation of backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212 Operation of restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214 Operation of keyword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216 15.9 Errors and Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217 CHAPTER 16 GOT SELF CHECK (DEBUG) 219 16.1 Device Monitor Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 System configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219

Devices that can be monitored . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .220 Display operation of device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221 Information displayed on the device monitor screen and key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .222 Basic operation of device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224 Device registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .225 Quick test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228 16.2 FX List Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232 Display operation of FX list editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234 Access range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .235 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .235 Display operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236 Operation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .238 Selection and operation of modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 Displaying sequence programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .241 Searching commands/devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .243 Writing commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .245 Changing operands, set values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .249 Deleting commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250 Sequence program all clear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251 PLC diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 Parameter setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .254 Keyword. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .256 List monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .258 Action for an incorrect key input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .259 Error messages and corrective actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260 16.3 FX3U-ENET-ADP Communication Setting Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .261 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 Display operation of FX3U-ENET-ADP communication setting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 Setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263 CHAPTER 17 MAINTENANCE 267 17.1 Touch Panel Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267 17.2 Touch Panel Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269 17.3 Clean. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271 CHAPTER 18 BootOS and System Application Installation Using Data Storage 273 18.1 Installing when starting the GOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .274 18.2 Installing using the data control function (Utility) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274 CHAPTER 19 INSTALLATION OF Boot OS AND BASIC SYSTEM APPLICATION 275 19.1 Boot OS and Basic System Application to be Installed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .275 19.2 Prior Preparations for Installing Boot OS and System Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .276 CHAPTER 20 ERROR MESSAGE LIST 277 CHAPTER 21 MAINTENANCE AND INSPECTION 279 21.1 Daily Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280 21.2 Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280

Cleaning Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .281

21.4 Backlight Shutoff Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282 Backlight shutoff detection and external alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282 CHAPTER 22 TROUBLESHOOTING 283 22.1 GOT Restoration Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 GOT status check sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284 GOT installation status check sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287 System configuration check sheet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293 CHAPTER 23 CONNECTION 295 CHAPTER 24 APPENDIX 297 24.1 External Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297 REVISIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .304 WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .305 TRADEMARKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .306

Thank you for choosing Mitsubishi Electric Graphic Operation Terminal (GOT).

Before using the product, read this manual carefully and make sure you understand the functions and performance of the GOT for correct use. About Manual The following manuals related to this product are available. Refer to each manual in accordance with the intended use. e-Manual e-Manual refers to the Mitsubishi Electric FA electronic book manuals that can be browsed using a dedicated tool. e-Manual has the following features: Required information can be cross-searched in multiple manuals. Other manuals can be accessed from the links in the manual. Hardware specifications of each part can be found from the product figures. Pages that users often browse can be bookmarked. Screen creation software manuals Connection manuals GOT SIMPLE series manuals Manual name Manual number (Model code) Format GT Works3 Installation Instructions - PDF GT Designer3 (GOT2000) Screen Design Manual SH-081220ENG (1D7ML9) PDF e-Manual GT Converter2 Version3 Operating Manual for GT Works3 SH-080862ENG (1D7MB2) PDF e-Manual Manual name Manual number (Model code) Format GOT2000 Series Connection Manual (Mitsubishi Product) For GT Works3 Version1 SH-081197ENG (1D7MJ8) PDF e-Manual GOT2000 Series Connection Manual (Non Mitsubishi Product 1) For GT Works3 Version1 SH-081198ENG PDF e-Manual GOT2000 Series Connection Manual (Non Mitsubishi Connecting Non-Mitsubishi products to the GOT Product 2) For GT Works3 Version1 SH-081199ENG PDF e-Manual GOT2000 Series Connection Manual (Microcomputer, MODBUS Products, Peripherals) For GT Works3 Version1 SH-081200ENG PDF e-Manual Manual name Manual number Format GOT SIMPLE Series User's Manual JY997D52901 PDF e-Manual

• Obtaining the specifications and operation methods of GT Designer3

• Setting available functions on GT Designer3 • Creating a screen displayed on the GOT • Obtaining useful functions to increase efficiency of drawing • Setting details for figures and objects • Setting functions for the data collection or trigger action • Setting functions to use peripheral devices • Simulating a created project on a personal computer GT Designer3 (GOT2000) Screen Design Manual Connecting a controller to the GOT • Obtaining information of Mitsubishi products applicable to the GOT • Connecting Mitsubishi products to the GOT • Connecting multiple controllers to one GOT (Multi-channel function) • Establishing communication between a personal computer and a controller via the GOT (FA transparent function) GOT2000 Series Connection Manual (Mitsubishi Product) For GT Works3 Version1 • Obtaining information of Non-Mitsubishi products applicable to the GOT • Connecting Non-Mitsubishi products to the GOT GOT2000 Series Connection Manual (Non Mitsubishi Product 1) For GT Works3 Version1 GOT2000 Series Connection Manual (Non Mitsubishi Connecting Non-Mitsubishi products to the GOT Product 2) For GT Works3 Version1 • Obtaining information of peripheral devices applicable to the GOT • Connecting peripheral devices including a bar code reader to the GOT GOT2000 Series Connection Manual (Microcomputer, MODBUS Products, Peripherals) For GT Works3 Version1 Transferring data to the GOT • Writing data to the GOT • Reading data from the GOT • Verifying an editing project to a GOT project GT Designer3 (GOT2000) Screen Design Manual Others • Obtaining specifications (including part names, external dimensions, and options) of each GOT • Installing the GOT GOT SIMPLE Series User's Manual • Operating the utility GOT SIMPLE Series User's Manual • Configuring the gateway function GT Designer3 (GOT2000) Screen Design Manual

Abbreviations and Generic Terms

GOT Communication interface Option Software ■Software related to GOT Abbreviations and generic terms Description GOT SIMPLE Series GS21 GS21-W-N GS2110-WTBD-N GS2107-WTBD-N GS21-W GS2110-WTBD GS2107-WTBD Abbreviations and generic terms Description Serial multi-drop connection unit GT01-RS4-M Abbreviations and generic terms Description SD card NZ1MEM-2GBSD, NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD, L1MEM-2GBSD, L1MEM- 4GBSD Abbreviations and generic terms Description GT Works3 SW1DNC-GTW3-J, SW1DND-GTW3-J, SW1DNC-GTW3-E, SW1DND-GTW3-E, SW1DND-GTW3-C GT Designer3 Version1 Screen drawing software GT Designer3 for GOT2000/GOT1000 series GT Designer3 Screen drawing software for GOT2000 series included in GT Works3 GT Designer3 (GOT2000) GT Designer3 (GOT1000) Screen drawing software for GOT1000 series included in GT Works3 GT Simulator3 Screen simulator GT Simulator3 for GOT2000/GOT1000/GOT900 series

Abbreviations and generic terms

Description GX Works3 SW□DND-GXW3-E (-EA) type programmable controller engineering software (□ indicates a version.) GX Works2 SW□DNC-GXW2-□ type programmable controller engineering software (□ indicates a version.) GX Simulator3 Simulation function of GX Works3 GX Simulator2 Simulation function of GX Works2 GX Simulator SW□D5C-LLT-E (-EV) type ladder logic test tool function software package (SW5D5C-LLT (-V) or later versions) (□ indicates a version.) GX Developer SW□D5C-GPPW-E (-EV)/SW□D5F-GPPW (-V) type software package (□ indicates a version.) GX LogViewer SW□DNN-VIEWER-E type software package (□ indicates a version.) PX Developer SW□D5C-FBDQ-E type FBD software package for process control (□ indicates a version.) MT Works2 Motion controller engineering environment MELSOFT MT Works2 (SW□DNDMTW2-E) (□ indicates a version.) MT Developer SW□RNC-GSV type integrated start-up support software for motion controller Q series (□ indicates a version.) CW Configurator C Controller module configuration and monitor tool (SW1DND-RCCPU-E) (□ indicates a version.) MR Configurator2 SW□DNC-MRC2-E type servo configuration software (□ indicates a version.) MR Configurator MRZJW□-SETUP type servo configuration software (□ indicates a version.) FR Configurator Inverter setup software (FR-SW□-SETUP-WE) (□ indicates a version.) NC Configurator2 CNC parameter setting support tool (FCSB1221) NC Configurator CNC parameter setting support tool FX Configurator-FP Parameter setting, monitoring, and testing software packages for FX3U-20SSC-H (SW□D5CFXSSCE) (□ indicates a version.) FX3U-ENET-L Configuration tool FX3U-ENET-L type Ethernet module setting software (SW1D5-FXENETL-E) RT ToolBox2 Robot program creation software (3D-11C-WINE) MX Component MX Component Version□ (SW□D5C-ACT-E, SW□D5C-ACT-EA) (□ indicates a version.) MX Sheet MX Sheet Version□ (SW□D5C-SHEET-E, SW□D5C-SHEET-EA) (□ indicates a version.) CPU Module Logging Configuration Tool CPU module logging configuration tool (SW1DNN-LLUTL-E) Abbreviations and generic terms Description SIEMENS Siemens AG PLC Programmable controller manufactured by each corporation

A GOT is installed on the panel surface of a control panel or operating panel and connects to the PLC within the control panel.

The GOT carries out switch operation, lamp display, data display, message display, etc. For the display screen, two kinds of screens are available: user screen and utility screen. ■User screen The user screen is a screen drawn by drawing software. The objects "Touch switch", "Lamp display", "Comment display", and "Numeric display" can be arbitrarily arranged on the display. Moreover, multiple screens created within drawing software can be individually selected or overlapped for the display. For details, refer to the following. GT Designer3 (GOT2000) Screen Design Manual ■Utility Screen The utility screen is a factory drawn horizontal screen that cannot be edited. The utility screen can be displayed on the GOT by installing the standard monitor OS from drawing software or an SD card to the GOT. Such as [Brightness] and [Time setting] can be set from the utility screen. For details, refer to the following. Page 63 UTILITY FUNCTION to Page 283 TROUBLESHOOTING PLC Connector for program GOT

Monitoring for turning on or off bit devices of a PLC, forcibly turning on or off the bit devices of a PLC, monitoring the word

device set value/current value and changing that numeric values are easily made. General-purpose properties of the display unit The display unit is used for engineers' stage replacement, setting change and troubleshooting or for operation guidance to an operator. • Monitor • Forcibly turning on or off • Set value change • Trouble check Improved monitoring performance and connectivity to FA devices • Multiple languages are displayed using the Unicode2.1-compatible fonts and beautiful characters are drawn using the TrueType, high quality fonts, and outline fonts *1 • Two types of display modes are available: 65536-color display and monochrome A fine and beautiful full-color display which shows even small characters clearly, is enabled in the 65536-color display by adopting the high intensity, wide viewing angle and high definition TFT color liquid crystal display. (Also compatible with digital screen displays with 65536 colors, BMP, etc.) High speed monitoring through high speed communication at maximum of 115.2kbps • High speed display and high speed touch switch response • The operation performance is improved by the analog touch panel. *1 Outline fonts are compatible only with GS21-W-N. More efficient GOT operations including screen design, startup, adjustment, management and maintenance works • The 9MB/15MB built-in flash memory is included as standard. *1 • SD card interface is included as standard. • RS-232 interface is included as standard. • RS-422 interface and RS-422/485 interface are included as standard. *2 • USB interface (device) is included as standard. • Ethernet interface is included as standard. • System font types are increased by the adoption of the font installation system. • Three types of alarms (user alarm, alarm history, and alarm popup display) are integrated, and realizing an efficient alarm notification. • "When, what, and how" the operation was performed can be checked with the GOT by using the operation log function (GS21-W-N only). *1 The memory capacity vary by model. *2 The available interfaces vary by model. Enhanced support of FA setup tools Connecting the GOT and the personal computer enables programming, rising, and adjustment of Mitsubishi Electric FA devices from the personal computer via the GOT.

The following shows the procedures before operating a GOT and the descriptions of each item.

Install GT Designer3 in a personal computer. GT Works3 Installation Instructions GS21 General Description Create project data. GT Designer3 (GOT2000) Screen Design Manual Wire for the GOT power supply and the controller. 7. WIRING GOT2000 Series Connection Manual for GT Works3 Version1 Wire for the controller power supply and I/O. Controller manuals Turn on the power of the GOT and controller. Install the OS to the GOT. GT Designer3 (GOT2000) Screen Design Manual Check that the OS is installed to the GOT. Download project data. GT Designer3 (GOT2000) Screen Design Manual Check that the monitoring is normal. Turn on the controller power and check that the GOT recognizes the controller.

2 SYSTEM CONFIGURATION

2.1 Overall Configuration 23 2 2 SYSTEM CONFIGURATION 2.1 Overall Configuration The overall configuration of GOT is as follows. For the connection methods applicable to GS series and cable, refer to the following. GOT2000 Series Connection Manual For GT Works3 Version1 *1 Only hard copy of the screen can be printed. 2.2 Component List Explanation of the GOT model name Bar code reader (Commercially available) Personal computer (Commercially available) Printer*1 (Commercially available) SD card GS21 series 0 7 - W Panel color 10: 10" wide screen 07: 7" wide screen Screen size W: 800×480 Resolution D: 24VDC Power type T: TFT color Display section B: Black T B D G S 2 1 - N N: Function extension version None: Standard Specially supported specification

2 SYSTEM CONFIGURATION

2.2 Component List GOT Extension unit Only available to GS21-W-N. Communication unit Software *1 The desired number of licenses (2 or more) can be purchased. For details, please contact your local sales office. *2 Volume license product and additional license product are also available. For more details, please refer to the MELSOFT iQ Works catalog (L(NA)08232ENG). *3 The product includes the following software. System Management Software [MELSOFT Navigator] Programmable Controller Engineering Software [MELSOFT GX Works3, GX Works2, GX Developer] Motion Controller Engineering Software [MELSOFT MT Works2] GOT Screen Design Software [MELSOFT GT Works3] Robot Engineering Software [MELSOFT RT ToolBox3 mini] Inverter Setup Software [MELSOFT FR Configurator2] Servo Setup Software [MELSOFT MR Configurator2] *4 This product does not include a DVD-ROM. The license certificate indicating the product ID number is issued only. *5 Each GOT requires one license. *6 Only available to GS21-W-N. Product name Model Specifications GOT GS2110-WTBD-N 10" [800 × 480 dots], TFT color liquid crystal, 65536 colors 24VDC, Memory capacity: 15MB, built-in Ethernet interface, built in RS-232 interface, built in RS-422/485 interface GS2107-WTBD-N 7" [800 × 480 dots], TFT color liquid crystal, 65536 colors 24VDC, Memory capacity: 15MB, built-in Ethernet interface, built in RS-232 interface, built in RS-422/485 interface GS2110-WTBD 10" [800 × 480 dots], TFT color liquid crystal, 65536 colors 24VDC, Memory capacity: 9MB, built-in Ethernet interface, built in RS-232 interface, built in RS-422 interface GS2107-WTBD 7" [800 × 480 dots], TFT color liquid crystal, 65536 colors 24VDC, Memory capacity: 9MB, built-in Ethernet interface, built in RS-232 interface, built in RS-422 interface Product name Model Specifications Serial multi-drop connection unit GT01-RS4-M For the GOT multi-drop connection Product name Model Description HMI/GOT Screen Design Software MELSOFT GT Works3 SW1DND-GTWK3-E English version Standard license product DVD-ROM SW1DND-GTWK3-EA Volume license product *1 SW1DND-GTWK3-EAZ Additional license product *1*4 SW1DND-GTWK3-C Simplified Chinese version Standard license product DVD-ROM FA Integrated Engineering Software MELSOFT iQ Works *2*3 SW2DND-IQWK-E English version Standard license product DVD-ROM VNC server function license *5*6 GT25-VNCSKEY-1 1 license GT25-VNCSKEY-5 5 licenses GT25-VNCSKEY-10 10 licenses GT25-VNCSKEY-20 20 licenses

2 SYSTEM CONFIGURATION

2.2 Component List 25 2 Option Connection cables for MITSUBISHI PLCs (Sold separately) Connection cables for SIEMENS PLCs (Sold separately) SD card (Sold separately) *1 Only available to GS21-W-N. Product name Model Cable length Description RS-422 conversion cable FA-CNV2402CBL 0.2 m For connecting the QCPU/L02SCPU(-P) and the RS-422 cable (GT01-C□R4- 25P, GT10-C□R4-25P, GT21-C□R4-25P5) For connecting the L6ADP-R2 and the RS-422 cable (GT01-C□R4-25P, GT10- C□R4-25P, GT21-C□R4-25P5) [MINI-DIN 6-pin ←→ D-sub 25-pin] FA-CNV2405CBL 0.5 m RS-422 Cable FXCPU direct connection cable, FX expansion board connection cable GT01-C10R4-8P 1m For connecting FXCPU (MINI DIN 8 pins connector) and GOT For connecting FXCPU expansion board (MINI DIN 8 pins connector) and GOT GT01-C30R4-8P 3m GT01-C100R4-8P 10m GT01-C200R4-8P 20m GT01-C300R4-8P 30m QnA/A/FXCPU direct connection cable, computer link connection cable GT01-C30R4-25P 3m QnA/A motion controller (A series) For connecting FXCPU (D-Sub 25 pins connector) and GOT For connecting FA-CNV CBL and GOT For connecting serial communication unit (AJ71QC24(N)-R4) and GOT GT01-C100R4-25P 10m GT01-C200R4-25P 20m GT01-C300R4-25P 30m Computer link connection cable GT09-C30R4-6C 3m For connecting computer link unit/serial communication unit and GOT GT09-C100R4-6C 10m GT09-C200R4-6C 20m GT09-C300R4-6C 30m RS-232 cable QCPU direct connection cable GT01-C30R2-6P 3m For connecting QCPU and GOT FX expansion board connection cable, FX special adaptor connection cable GT01-C30R2-9S 3m For connecting FXCPU expansion board (D-Sub 9 pins connector) and GOT For connecting FXCPU special adaptor (D-sub 9 pins connector) and GOT FX special adaptor connection GT01-C30R2-25P 3m For connecting FXCPU special adaptor (D-sub 25 pins connector) and GOT Computer link connection cable GT09-C30R2-9P 3m For connecting computer link unit/serial communication unit and GOT GT09-C30R2-25P 3m Product name Model Cable length Description RS-232 cable GT09-C30R20801-9S 3m For connecting SIEMENS HMI Adapter and GOT Product name Model Description SD card NZ1MEM-2GBSD *1 SD memory card 2GB NZ1MEM-4GBSD *1 SDHC memory card 4GB NZ1MEM-8GBSD *1 SDHC memory card 8GB NZ1MEM-16GBSD *1 SDHC memory card 16GB L1MEM-2GBSD SD memory card 2GB L1MEM-4GBSD SDHC memory card 4GB

2 SYSTEM CONFIGURATION

2.2 Component List PC connection cable (Sold separately) Bar code reader (Sold separately) *1 Some models with the operations checked by our company are usable. For the operation-checked models, contact your local distributor. Product name Model Cable length Description Project data transfer cable GT09-C30USB-5P 3m For connecting GOT (USB Mini-B) and personal computer (USB) Product name Model Description Bar code - Commercially-available bar code reader*1

3.1 General Specifications

27 3 3 SPECIFICATIONS 3.1 General Specifications *1 Includes the temperature inside the enclosure of the control panel on which the GOT is installed. *2 If the ambient temperature exceeds 40°C, the absolute humidity must not exceed 90% RH at 40°C. *3 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction. When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off. *4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the raged voltage of 300V is 2500V. *5 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used. In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation. Item Specifications Operating ambient temperature*1 0 to 50°C Storage ambient temperature -20 to 60°C Operating/Storage ambient humidity 10% RH to 90% RH, non-condensing*2 Vibration resistance Conforms to IEC 61131-2 Frequency Acceleration Half amplitude Sweep Count Under intermittent vibration 5 to 8.4Hz - 3.5mm 10times each in X, Y and Z directions 8.4 to 150Hz 9.8m/s2 - Under continuous vibration 5 to 8.4Hz - 1.75mm - 8.4 to 150Hz 4.9m/s2 - Shock resistance Conforms to IEC 61131-2 (147m/s2, 3 times each in the X, Y, and Z directions) Operating atmosphere No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (as well as at storage) Operating altitude*3 2000m (6562ft) max. Overvoltage category*4 II or less Pollution degree*5 2 or less Cooling method Self-cooling Grounding Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of 2 mm2 or more. If impossible, connect the ground cable to the control panel.

3.2 Performance Specifications

3.2 Performance Specifications The following shows the performance specifications. Item Specifications GS2110-WTBD-N GS2107-WTBD-N GS2110-WTBD GS2107-WTBD Display section*1*2 Type TFT color liquid crystal Screen size 10" 7" 10" 7" Resolution WVGA: 800 × 480 dots Display size W222(8.74) × H132.5(5.22) [mm] (inch) W154(6.06) × H85.9(3.38) [mm] (inch) W222(8.74) × H132.5(5.22) [mm] (inch) W154(6.06) × H85.9(3.38) [mm] (inch) Display character 16-dot standard font: 50 characters × 30 rows (two-byte characters) 12-dot standard font: 66 characters × 40 rows (two-byte characters) Display color 65536 colors Brightness 32-level adjustment Backlight*3 LED-type (no replacement required) Touch panel*4 Type Analog-resistive film type Key size Minimum 2 × 2 dots *7 (per key) Number of points touched simultaneously Simultaneous 2-point presses prohibited (Only one point can be touched.)*5 Life 1 million times (operating force 0.98N max.) Memory C drive Flash memory (Internal) (15MB), for storing project data, OS Flash memory (Internal) (9MB), for storing project data, OS Life (Number of write times) 100,000times Built-in interface RS-422/485 RS-422/485, 1ch Transmission speed: 115200/57600/38400/19200/9600/ 4800bps Connector shape: D-sub 9 pins (Female) Application: For communicating with controllers Terminating resistor: 330 Ω, 110 Ω, OPEN (Selectable by the terminating resistor setting switch.)*9 - RS-422 - RS-422, 1ch Transmission speed: 115200/57600/38400/19200/9600/ 4800bps Connector shape: D-sub 9 pins (Female) Application: For communicating with controllers Terminating resistor: 330Ω fixed RS-232 RS-232, 1ch Transmission speed: 115200/57600/38400/19200/9600/4800bps Connector shape: D-sub 9 pins (Male) Application: For communication with controllers and a bar code reader For PC connection (Project data read/write, FA transparent function) Ethernet Data Transfer method: 100BASE-TX, 10BASE-T, 1ch Connector shape: RJ-45 (modular jack) Application: For communication with controllers For PC connection (Project data read/write, FA transparent function) USB (Device) 1 channel (rear face) USB version: USB1.1 (Full-Speed 12 Mbps) Connector shape: Mini-B Application: For PC connection (Project data read/write, FA transparent function) SD card Conforms to the SD standard, 1ch Supported memory card: SDHC memory card, SD memory card Application: Project data read/write, logging data save Buzzer output Single tone (LONG/SHORT/OFF adjustable) Protective structure IP65F (only the front part of the panel)*6*8 External dimensions W272(10.71) × H214(8.43) × D56(2.21) [mm] (inch) W206(8.11) × H155(6.11) × D50(1.97) [mm] (inch) W272(10.71) × H214(8.43) × D56(2.21) [mm] (inch) W206(8.11) × H155(6.11) × D50(1.97) [mm] (inch) Panel cutting dimensions W258(10.16) × H200(7.88) [mm] (inch) W191(7.52) × H137(5.40) [mm] (inch) W258(10.16) × H200(7.88) [mm] (inch) W191(7.52) × H137(5.40) [mm] (inch) Weight (excluding a fitting) Approx. 1.3 (2.9) [kg] (lb) Approx. 0.9 (2.0) [kg] (lb) Approx. 1.3 (2.9) [kg] (lb) Approx. 0.9 (2.0) [kg] (lb)

3.2 Performance Specifications

29 3 *1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Flickers and partial discoloration may be generated on the liquid crystal display panel due to individual differences of panels. Please note that these phenomena appear due to its characteristic and are not caused by product defect. *2 Flickering may occur due to vibration, shock, or the display colors. *3 To prevent the display section from burning in and lengthen the backlight life, enable the screen save function and turn off the backlight. *4 When a stylus is used, the touch panel has a life of 100 thousand touches. The stylus must satisfy the following specifications. Material: Polyacetal resin Tip radius: 0.8mm or more *5 If you touch two points or more simultaneously on the touch panel, a touch switch near the touched points may operate unexpectedly. Do not press two or more areas simultaneously on the touch panel. *6 Note that this does not guarantee all users' operation environment. The GOT may not be used in an environment where the GOT is exposed to oil or chemicals for a long time, or where oil mist fills the air. *7 Minimum size of a key that can be arranged. To ensure safe use of the product, the following settings are recommended. Key size: 16 × 16 dots or larger Distance between keys: 16 dots or more *8 The suffix "F" of "IP65F" is a symbol that indicates protection rate against oil. It is described in the Appendix of Japanese Industrial Standard JIS C 0920. *9 For the GOT multi-drop connection, set the terminating resistor setting switch of the GOT according to the connection type. For details on the GOT multi-drop connection, refer to the following. GOT2000 Series Connection Manual (Mitsubishi Electric Products) For GT Works3 Version1 Compatible software package (Version of GT Designer3) Version 1.250L or later Version 1.105K or later Item Specifications GS2110-WTBD-N GS2107-WTBD-N GS2110-WTBD GS2107-WTBD

3.3 Power Supply Specifications

3.3 Power Supply Specifications Operation at momentary power failure The GOT continues to operate even upon 5ms or shorter instantaneous power failure. The GOT stops operating if there is extended power failure or voltage drop, while it automatically resumes operation as soon as the power is restored. Item Specifications GS2110-WTBD-N GS2107-WTBD-N GS2110-WTBD GS2107-WTBD Input power supply voltage 24VDC (+10% -15%), ripple voltage 200mV or less Power consumption 7.6W (317mA/24V) or less 6.5W (271mA/24V) or less 7.6W (317mA/24V) or less 6.5W (271mA/24V) or less Power consumption (At backlight off) 3.8W (158mA/24V) or less 3.8W (158mA/24V) or less 3.8W (158mA/24V) or less 3.8W (158mA/24V) or less Inrush current 17A or less (6ms, 25°C, at the maximum load) Permissible instantaneous power failure time Within 5ms Noise immunity Conforms to IEC61000-4-4, 2kV (power supply line) Dielectric withstand voltage 350VAC for 1 minute (across power supply terminals and earth) Insulation resistance 500VDC across power terminals and earth, 10 MΩ or more by an insulation resistance tester

3.4 GOT Connector Specifications

31 3 3.4 GOT Connector Specifications The following shows the specifications of connectors for the GOT. Refer to this section for creating a connection cable by the user. RS-232 interface The following shows the connector for the RS-232 interface of the GOT. For the connection cable connector of the GOT side, use a connector and a connector cover which can be connected to the GOT connector. Connector specifications Connector pin arrangement RS-422 interface and RS-422/485 interface The following shows the connector for the RS-422 interface and RS-422/485 interface of the GOT. For the connection cable connector of the GOT side, use a connector and a connector cover which can be connected to the GOT connector. Connector specifications Connector pin arrangement GOT Connector type Connector model Manufacturer GS series D-sub 9 pins (Male) Inch screw type 17LE-23090-27(D3CC) DDK Ltd. GOT Connector type Connector model Manufacturer GS series D-sub 9 pins (Female) M2.6 mm screw type 17LE-13090-27(D3AC) DDK Ltd. D-Sub 9pin male GOT main part connector see from the front 1 5 6 9 D-Sub 9pin female GOT main part connector see from the front 5 1 9 6

4 PART NAME

4.1 Front Panel 33 4 4 PART NAME 4.1 Front Panel No. Name Specifications (1) Display section Displays the utility screen and the user creation screen. (2) Touch panel For operating the touch switches in the utility screen and the user creation screen (1)(2)

4 PART NAME

4.2 Back Panel 4.2 Back Panel GS21-W-N • GS2110-WTBD-N • GS2107-WTBD-N For the names of parts, refer to the following. Page 36 Parts names of the back panel (8) (13) (11) (7) (5) (10) (9) (2) (1) (4) (12) (6) (8) (9) (10) (6) (2) (5) (1) (4) (12) (13) (11) (7)

4 PART NAME

4.2 Back Panel 35 4 GS21-W • GS2110-WTBD • GS2107-WTBD For the names of parts, refer to the following. Page 36 Parts names of the back panel (8) (11) (13) (5) (10) (9) (3) (1) (4) (12) (6) (8) (9) (10) (6) (3) (5) (1) (4) (12) (13) (11)

4 PART NAME

4.2 Back Panel Parts names of the back panel No. Name Specifications (1) RS-232 interface For communicating with controller (PLC, microcomputer board, RFID, etc) or personal computer (OS installation, project data download, FA transparent) (D-sub 9-pin male) (2) RS-422/485 interface For communicating with controller (PLC, microcomputer board, etc) (D-sub 9-pin female) (3) RS-422 interface For communicating with controller (PLC, microcomputer board, etc) (D-sub 9-pin female) (4) Ethernet interface For Ethernet communication with controller (PLC, microcomputer board, etc) (RJ-45 connector) (5) USB interface (Device) USB interface for data transfer and saving (6) Hole for preventing the USB cable from unplugging Hole for preventing the USB cable from unplugging with a banding band (7) Terminating resistor setting switch For switching the terminating resistor setting of the RS-422/485 communication port to 330 Ω, 110 Ω, or OPEN (8) Rating plate Model name, current consumption, production number, hardware version, and Boot OS version are described. (9) SD card interface Interface for mounting an SD card to the GOT (10) SD card access LED ON: SD card is accessed, OFF: SD card is not accessed (11) Vertical installation arrow mark For the vertical installation, install the GOT so that the arrow points upward. (12) Power terminal Power terminal and FG terminal (for power supply (24VDC) to GOT and grounding) (13) Ethernet communication status LED SD RD: Green light while data are being sent or received, 100M: Green light when the transmission speed is 100Mbps

4 PART NAME

4.3 Bottom 37 4 4.3 Bottom GS21-W-N • GS2110-WTBD-N • GS2107-WTBD-N For the names of parts, refer to the following. Page 37 Parts names of the bottom GS21-W • GS2110-WTBD • GS2107-WTBD For the names of parts, refer to the following. Page 37 Parts names of the bottom Parts names of the bottom No. Name Specifications (1) Hole for unit installation fittings Hole for the inserting installation fittings (accessory) during the GOT installation to the panel (4 holes at top and bottom) (1) (1) (1) (1)

5 EMC DIRECTIVE

5.1 Overview 39 5 5 EMC DIRECTIVE 5.1 Overview For the products sold in European countries, the conformance to the EMC Directive, which is one of the European Directives, has been a legal obligation since 1996. Manufacturers, who recognize that their products comply with the EMC Directive must declare that their products comply with the Directives and put a CE mark on the products. Sales representative in Europe The sales representative in Europe is as shown below. Company name: Mitsubishi Electric Europe BV Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany Conforming standards in the EMC Directive The GOT complies with the following standards in the EMC Directive. *1 The GOT is an open type device (designed to be integrated in equipment). Make sure to install the GOT on a control panel. This test item is conducted in the condition where the GOT is installed on a control panel and combined with the MITSUBISHI PLC. *2 QP: Quasi-peak value, Mean: Average value *3 This test item is conducted in the following conditions. · 30 MHz to 230 MHz QP: 40 dBμV/m (measured at 10 m) · 230MHz to 1000MHz QP: 47 dBμV/m (measured at 10 m) Applied standard Test standard Test details Standard value EN61131-2: 2007 CISPR16-2-3 Radiated noise*1 Test for measuring electromagnetic emissions from the product • 30 MHz to 230 MHz QP: 30 dBμV/m (measured at 30m)*2*3 • · 230MHz to 1000MHz QP: 37 dBμV/m (measured at 30m)*2*3 IEC61000-4-2 Electrostatic immunity*1 Immunity test in which static electricity is applied to the cabinet of the equipment • Contact discharge: ±4 kV • Aerial discharge: ±8kV IEC61000-4-3 Radiated electromagnetic field, amplitude modulation*1 Immunity test in which an electric field is applied to the product 80 MHz to 1000 MHz: 10 V/m 1.4GHz to 2GHz: 3V/m 2.0GHz to 2.7GHz: 1V/m (80% amplitude modulation at 1 kHz) IEC61000-4-4 Fast transient burst noise*1 Immunity test in which burst noise is applied to the power cables and the signal lines Power cable: 2 kV Digital I/O: 1 kV Analog I/O: 1 kV Signal cable: 1 kV IEC61000-4-5 Surge immunity*1 Immunity test in which lightening surge is applied to the product • DC power type Power cable (between cable and ground): ±0.5 kV Power cable (between cables): ±0.5 kV Data communication port: ±1kV IEC61000-4-6 Conducted RF immunity*1 Immunity test in which a noise inducted on the power cable and the signal lines is applied Power cable: 10V Data communication port: 10V IEC61000-4-8 Power supply frequency magnetic field immunity Test for checking normal operations under the circumstance exposed to the ferromagnetic field noise of the power supply frequency (50/60 Hz) 30 A/m

5 EMC DIRECTIVE

5.2 EMC Directive Requirements 5.2 EMC Directive Requirements The EMC Directive requires the following. • Strong electromagnetic waves are not emitted to the outside.: Emission (Electromagnetic interference) • The product is not affected by the electromagnetic waves from the outside.: Immunity (Electromagnetic sensitivity) To comply with the EMC Directive, this section explains the precautions for configuring equipment integrating the GOT. The data described herein are produced with our best, based on the regulation requirements and standards obtained by Mitsubishi. However, the data do not guarantee that the whole equipment produced according to the data comply with the above directive. The manufacturer of the equipment must determine the method to comply with the EMC Directive and conformance to the directive. Installing the GOT on the control panel The GOT is an open type device (designed to be integrated in equipment). Make sure to install the GOT in a control panel. This restriction ensures safety and also has a large effect of suppressing noise generated from the GOT by using the control panel. Control panel • The control panel must be conductive. • When fixing a top or bottom plate of the control panel with bolts, do not coat the plate and bolt surfaces so that they contact each other. Connect the door and the box using a thick grounding cable to ensure the low impedance under high frequency. • To ensure electric conductivity in the large area as much as possible between an inner plate and the control panel, do not coat the fixing bolt area of the inner plate and the control panel. • Ground the control panel using a thick grounding cable to ensure the low impedance under high frequency. • The diameter of cable holes on the control panel must be 10 cm or less. If the diameter of the hole is 10 cm or more, radio waves may leak. To reduce the chance of radio waves leaking out, ensure that the space between the control panel and its door is as small as possible. Pasting the following EMI gasket directly on the painted surface seals the space, reducing the leak of electric waves. Our test has been carried out on a panel having the damping characteristics of 37 dB max. and 30 dB mean (measured by 3m method with 30 to 300 MHz). Connection of power and ground cables Ground the GOT and connect power supply cables as shown below. ■Wiring the ground cable Provide a ground point near the GOT. Ground the frame ground terminal (FG terminal) of the GOT with the thickest and shortest cable as possible. ■Ground cable length The ground cable length must be 30 cm or shorter. The FG terminals pass the noise generated in the PLC system to the ground. Therefore, ensure an impedance as low as possible. Since the ground cables relieve the noise, the cables themselves carry a large noise. Thus, short wiring prevents the cable from acting as an antenna. (A long conductor is an antenna radiating noise more efficiently.) Manufacturer Series name Contact KITAGAWA INDUSTRIES CO., LTD. RFSG series (Recommended Product) +81-587-34-3651

5 EMC DIRECTIVE

5.2 EMC Directive Requirements 41 5 ■Treatment of the power cable and the ground cable Twist the ground cable led from the ground point with the power cable. Twisting with the ground cable relieves more noise from the power cable to the ground. When a noise filter is installed to the power cable, twisting the power cable and the ground cable may not be required. Installing a noise filter (power supply line filter) A noise filter is a part to effectively reduce conducted noise. Except some models, installation of a noise filter to the power supply lines is not necessary. However, installing the noise filter can reduce conducted noise. The noise filter is effective to reduce conducted noise in the band of 10 MHz or less. Use a noise filter equivalent to the following noise filters (double π-type filters). Precautions The following shows the precautions for installing a noise filter. ■Prohibition of bundling cables Do not bundle the input and output cables of the noise filter. Bundling the cables inducts the noise from the output-side cable into the input-side cable where noise has been eliminated by the noise filter. ■Grounding the noise filter Connect the ground terminal of the noise filter to the control panel with a short cable as much as possible (approximately 10 cm). Model Manufacturer Rated current Rated voltage FN343-3/05 SCHAFFNER 3A 250V FN660-6/06 SCHAFFNER 6A RSHN-2003 TDK 3A Input side (power supply side) Output side (device side) Filter Wire the input and output cables separately. Filter Input side (power supply side) Induction Output side (device side) Bundling the input and output cables inducts noise. Bundling

5 EMC DIRECTIVE

5.2 EMC Directive Requirements System configuration GOT Use the following GOTs having a CE mark on the rating plate. The following models are compliant with the EMC Directive at factory shipment. When any GOT other than the following does not comply with the EMC Directive. Connection type The following table lists the connection types compliant with the EMC Directive. ○: Compliant with EMC Directive, ×: Not compliant with EMC Directive *1 For the details of each connection type, refer to the following manual. GOT2000 Series Connection Manual (GT Works3 Version1) for the controller used *2 When connecting the GOT to other controllers such as a non-Mitsubishi PLC, fabricate connection cables and configure the system following the EMC Directive specifications. Page 44 Non-Mitsubishi PLC, inverter, and servo amplifier connections Connected devices When connecting the GOT to a non-Mitsubishi PLC, refer to the manual about the EMC Directive compliance of the connected device (such as a PLC and a microcomputer). Connection of power cables and ground cables Carry out wiring and connect the power and ground cables according to the following instruction. By the different wiring or connection method, the system may not comply with EMC Directive. Wiring method For connection of power cables and ground cables, refer to the following. Ground the frame ground terminal (FG terminal) of the GOT with the thickest and shortest cable as possible. Page 58 Wiring Inside and Outside the Panel Product name Model GS2110 GS2110-WTBD-N GS2110-WTBD GS2107 GS2107-WTBD-N GS2107-WTBD Connection type*1 GS21 Ethernet connection ○ Direct CPU connection ○ Computer link connection ○ Other connections (Connection with non-Mitsubishi PLC, inverter, servo amplifier) ○*2

5 EMC DIRECTIVE

5.2 EMC Directive Requirements 43 5 Fabricating a connection cable Fabricate the cables used for the GOT by the methods as shown in this section. The fabrication requires a ferrite core, cable clamp, and cable shielding materials. The following products have passed the Mitsubishi EMC Directive compliance test. • ZCAT3035-1330 ferrite core (TDK Corporation) • AD75CK-type cable clamp (Mitsubishi Electric Corporation) Ethernet connection ■Ethernet cable Strip off the sheath at both ends of the cable as shown in the figure below to expose braided shield for grounding. The braided shield sections are used for grounding with a cable clamp. Page 46 Grounding a cable • Connecting to the Ethernet interface of the GOT Direct CPU connection ■RS-232 cable and RS-422 cable Install a ferrite core to the cable in the positions as shown in the figure below. Personal computer side GOT side 230or less 40 40 400or less (9.06) (1.57) (1.57) (9.06) Unit: mm (inch) Ferrite core (ZCAT3035-1330) 120 or less (4.72) 120 or less (4.72) PLC side GOT s ide 230 or less 40 40 400 or less (9.06) (1.57) (1.57) (9.06) Unit: mm (inch) Ferrite core (ZCAT3035-1330) Finishing of wearing 120 or less (4.72) 120 or less (4.72)

5 EMC DIRECTIVE

5.2 EMC Directive Requirements Computer link connection ■RS-232 cable and RS-422 cable Strip off the sheath at both ends of the cable as shown in the figure below to expose braided shield sections for grounding. The braided shield sections are used for grounding with a cable clamp. Page 46 Grounding a cable Non-Mitsubishi PLC, inverter, and servo amplifier connections Create the cables (RS-232 cable, RS-422/485 cable) for connecting the GOT and a controller by yourself. For how to create a cable, refer to the following. GOT2000 Series Connection Manual For GT Works3 Version1 100 or less Ferrite core (ZCAT3035-1330) 100 or less (3.94) 230 or less 40 40 (9.06) (1.58) (1.58) 230 or less (9.06) (3.94) GOT side PLC CPU side Unit: mm (inch)

5 EMC DIRECTIVE

5.2 EMC Directive Requirements 45 5 Treatment of the RS-232 cable and RS-422/485 cable When the GOT is connected to a controller, configure the system according to the EMC Directive specifications for the controller. The following shows the recommended instructions to comply with the EMC Directive. However, the manufacturer of the equipment must determine the method to comply with the EMC Directive and conformance to the directive. • RS-422/485 cable When connecting each signal wire (except SG and FG wires), twist two signal wires as shown below. Connect two or more SG wires. • RS-232 cable Twist each signal wire (except SG and FG wires) with the SG wire. Install a ferrite core to the cable in the positions as shown in the figure below. Strip off the sheath at the both ends of the cable as shown in the figure below to expose braided shield for grounding. The braided shield sections are used for grounding with a cable clamp. SDA RDA RDB SDB RDA RDB SDA SDB RD RD SD SD DTR DTR DSR DSR SG SG 100 or less Ferrite core (ZCAT3035-1330) 100 or less (3.94) 230 or less 40 40 (9.06) (1.58) (1.58) 230 or less (9.06) (3.94) GOT side PLC CPU side Unit: mm (inch)

5 EMC DIRECTIVE

5.2 EMC Directive Requirements Grounding a cable Grounding method Ground the cable and ground cable to the control panel where the GOT and the PLC are installed. Ground the braided shield section of the cable to the control panel with the cable clamp (AD75CK). Precautions Do not arrange the cable clamp close to the other cables that are not clamped. The noise from the control panel may enter the cable clamp and adversely affect the GOT. Braided shield Cable clamps For the attachment details of cable clamps, refer to AD75CK-type Cable Clamping Instruction Manual .

6.1 Control Panel Inside Dimensions for Mounting GOT

47 6 6 INSTALLATION 6.1 Control Panel Inside Dimensions for Mounting GOT Mount the GOT onto the control panel while considering the following control panel inside dimensions. For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward. Applicable cable Some cables may need to be longer than the specified dimensions when connecting to the GOT. Therefore, consider the connector dimensions and bending radius of the cable as well for installation. MOUNTING PRECAUTIONS WARNING • Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT main unit to/from the controller. Not doing so can cause the unit to fail or malfunction. MOUNTING PRECAUTIONS CAUTION • • • • • Tighten the mounting screws within the specified torque range. Undertightening can cause the GOT to drop, short circuit or malfunction. In addition, undertightening can disable waterproof or oil proof effect. Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the GOT. In addition, the waterproof effect and oilproof effect may not be available due to the "distortion" of GOT or panel. Operate and store the GOT in environments without direct sunlight, dust, lamp black, conductive dust, corrosive gas, combustible gas, high temperature, condensation, wind, rain, vibrations and impacts. Electric shock, fire, malfunction, product damage or deterioration can be caused. Connect connection cables securely to the specified connectors while the power is turned OFF. Imperfect connection may cause malfunction or failure. Never drop cutting chips and electric wire chips into the ventilation window of the GOT when you drill screw holes or perform wiring. Otherwise, fire, failure or malfunction may be caused. Use the GOT in the environment that satisfies the general specifications described in this manual. Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration. Unit: mm(inch) 30(1.18)

6.2 Panel Cutting Dimensions

6.2 Panel Cutting Dimensions Cut holes in the following dimensions on the panel. Ensure 10mm of space in upper and lower parts of the panel for mounting fixtures. For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward. Unit: mm (inch) The C dimension shows the measurements for installing fittings on the control panel. Model A B C Panel thickness GS2110-WTBD-N GS2110-WTBD 258(10.16") (+2(0.08), 0(0)) 200(7.88") (+2(0.08), 0(0)) 10(0.39") or more 1.6(0.06") to 4(0.16") GS2107-WTBD-N GS2107-WTBD 191(7.52") (+2(0.08), 0(0)) 137(5.40") (+2(0.08), 0(0)) 10(0.39") or more 1.6(0.06") to 4(0.16") A C C B A C C B Horizontal Vertical

6.3 Mounting Position

49 6 6.3 Mounting Position When mounting the GOT, the following clearances must be maintained from other structures and devices. For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward. Horizontal installation Vertical installation Installation Environment A, D [mm] (inch) B [mm] (inch) C [mm] (inch) E [mm] (inch) In the presence of radiated-noise or heat- generating equipment nearby 50mm (1.97") or more Horizontal: 80mm (3.14") or more Vertical: 50mm (1.97") or more Horizontal: 50mm (3.14") or more Vertical: 80mm (3.14") or more 100mm (3.94") or more In the absence of radiated-noise or heat- generating equipment nearby 20mm (0.79") or more 20mm (0.79") or more 20mm (0.79") or more 20mm (0.79") or more C D E Panel thickness: 1.6 to 4mm (0.06" to 0.16") B A B A C D E Panel thickness: 1.6 to 4mm (0.06" to 0.16")

6.4 Control Panel Temperature and Mounting Angle

6.4 Control Panel Temperature and Mounting Angle When mounting the main unit to a control panel or similar fixture, set the GOT display section as shown below. Horizontal installation When the temperature inside the control panel is 40 to 50°C, the mounting angle should be in the range from 60 to 105 degrees. The GOT will have a longer lifetime if used within the mounting angles shown above. Ideally, the temperature inside the control panel should not exceed 0 to 40°C. Vertical installation When the temperature inside the control panel is 40 to 50°C, the mounting angle should be in the range from 60 to 105 degrees. The GOT will have a longer lifetime if used within the mounting angles shown above. Ideally, the temperature inside the control panel should not exceed 0 to 40°C. GOT back panel GOT display section Control panel, etc. 105° 60° GOT back panel GOT display section Control panel, etc. 105° 60°

6.5 Installation Procedure

51 6 6.5 Installation Procedure The GOT is designed to be embedded into a panel. Mount the GOT by following the procedure below. Refer to Page 48 Panel Cutting Dimensions for the panel cutting dimensions. In addition, the thickness of the installation panel face must be 1.6 to 4mm. Check that the packing is firmly attached with the GOT. If the packing is loose, attach the packing to the GOT securely. 1. Inserting into the panel face Insert the GOT from the front side of the panel. 2. Fixing the GOT Engage the hook of the mounting fixture (accessory) to the unit fixing hole of the GOT and fix them by tightening the mounting screws (accessory) in the torque range of 0.36 to 0.48N·m. 3. A protection film is attached on the display section of GOT prior to shipment. Remove the film when the installation is completed. Mounting hole Mounting fitting Mounting screw

6.5 Installation Procedure

Cautions on installation • Tightening the mounting screw Tighten the mounting screw within the specified torque. Under tightening can cause the GOT to drop. In addition, undertightening can disable waterproof or oil proof effect. Failure to do so may damage the unit, or distort the panel and make a surface waviness on the display area, leading to deterioration of the visibility or incorrect input from the touch panel. In addition, undertightening can disable waterproof or oil proof effect. Specified torque range: 0.36 to 0.48N·m • Installation panel surface Make sure that the panel surface is free from warpage, flaws and irregularities. Warpage, flaws and irregularities may disable the waterproof effect. Select proper panel thickness under consideration of the panel strength. (For example, the panel strength may be insufficient depending on the panel material and dimensions even if the panel thickness is acceptable. Insufficient panel strength may cause warpage depending on the installation positions of the GOT and other equipment.)

This chapter describes the wiring to the GOT power supply section.

For the connection with a PLC, refer to the following. GOT2000 Series Connection Manual For GT Works3 Version1 For the dimensional drawing of connection cables, refer to the following. Page 297 External Dimensions General preventive measures against noise There are two kinds of noises: Radiated noise that is transmitted into the air and Conductive noise that is directly transmitted along connected lines. Countermeasures must be taken considering both kinds of noises and referring to the following 3 points. • Protecting against noise Keep signal lines away from noise sources such as a power cable or a high-power drive circuit. Shield the signal lines. • Reducing generated noise Use a noise filter, etc. to reduce the level of the noise generated due to a source such as a high-power motor drive circuit. Attach surge killers to the terminals on the no fuse breakers (NFB), electromagnetic contactors, relays, solenoid valves, and generators to suppress noise interference. • Releasing noise to the ground Make sure to connect the ground cable to the ground. Use a short and thick cable to lower its ground resistance. Ground the power system and the control system separately. Be sure to shut off all phases of the external power supply used by the system before wiring. Failure to do so may result in an electric shock, product damage or malfunctions. Please make sure to ground FG terminal of the GOT power supply section by applying 100Ω or less which is used exclusively for the GOT. Not doing so may cause an electric shock or malfunction. Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product. Not doing so can cause a fire or failure. Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction. Tighten the terminal screws of the GOT power supply section in the specified torque range. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT. WARNING WIRING PRECAUTIONS • • • • • Plug the communication cable into the connector to be connected, and tighten the mounting screws and the terminal screws in the specified torque range. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit. CAUTION WIRING PRECAUTIONS •

7.1 Power Supply Wiring

7.1 Power Supply Wiring Connect the power supply to the power terminals on the back panel of the GOT. Use a specified size power supply wire to prevent voltage drop, and tighten the terminal screws firmly to a specified torque. Do not exceed the number of wires that are allowed to be connected. Secure the wires to prevent stress from being directly applied to the terminal block or wire connections. Cable types and wire end processing Process the end of the electrical wire (solid or stranded), or attach a ferrules with plastic sleeve to the wire end. Terminal screws should be tightened to between 0.3 to 0.5N·m. Terminal screws must be secured to prevent a loose connection thus avoiding a malfunction. When tightening terminal screws, do not exceed the specified torque. Failure to do so may cause equipment failures or malfunctions. Electrical wire size Wire end processing ■Connecting the wire directly Twist the end of the stranded wire. Make sure there are no wire whiskers. Do not solder the wire end. ■Using a ferrules with plastic sleeve to connect the wire A wire with a too thick of a wire sheath may not fit the insulation sleeve. Refer to the outline drawing for how to select the proper size wire. Electrical wire size Solid wire Stranded wire Ferrules with plastic sleeve 0.5 to 2.5mm2 AWG20 to AWG14 0.5 to 2.5mm2 AWG20 to AWG14 0.5 to 2.5mm2 AWG20 to AWG14 Manufacturer Model Crimper type Phoenix Contact Inc. AI 0.75-8BU (0.5 to 0.75mm2) CRIMPFOX UD6 AI 1.0-8RD (0.75 to 1.0mm2) AI 1.5-8BK (1.0 to 1.5mm2) AI 2.5-8BU (1.5 to 2.5mm2) Approx. 6mm 8 to 12mm 14 to 18mm 2.8 to 4.2mm Terminal contact section Insulation sleeve

7.1 Power Supply Wiring

55 7 Tools Use a small driver with a straight, untapered blade as shown below to tighten the power terminals. Wiring example Connect the power supply to the power terminals on the back panel of the GOT. Tightening torque for the power terminals: 0.5 to 0.6N·m GOT's ground Grounding the GOT and other devices Make sure to carry out the followings for grounding. • Carry out the independent grounding if possible. Provide class D (class 3) grounding. (Ground resistance must be 100Ω or less.) • If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below. • Use the cable of 2mm2 or longer for grounding. Set the grounding point closer to the GOT to make the grounding cable short as possible. Manufacturer Model Phoenix Contact Inc. SZS 0.6 3.5 0.6mm 3.5mm Use a driver with a flat end Class D grounding DC24V +10% - 15% Other device GOT Other device GOT Other device GOT (1) Independent ground ...... Best condition (2) Shared grounding ...... Good condition (3) Common grounding ...... Not allowed Grounding (100Ω or less) Grounding (100Ω or less)

7.1 Power Supply Wiring

The cause of malfunctions related wiring/Remedy Grounding of the GOT may cause electric potential difference and noise interference, which may result in GOT malfunctions. These problems may be resolved by taking the following measures. Wiring path of the GOT's ground cable and power line Bundling the GOT's ground cable and power line together can cause interference noise, which may result in malfunctions. Keeping the GOT's ground cable and power line away from each other will help minimize noise interference. Connecting the ground cable from the panel that houses control equipment to the panel to which the GOT is grounded When running a single ground cable from the panel that houses such piece of control equipment as a sequencer to the panel to which the GOT is grounded, the ground cable may have to be directly connected to the terminal on the GOT. If electric potential difference between the ground points created by it causes malfunctions, lowering the voltage as shown in Remedy 1 below may solve the problem. FG Power supply for power equipment Power supply for power equipment Good: Wiring the ground cable away from the power cable FG Bad: Bundling the ground cable and the power cable FG Ground cable from the panel that houses control equipment Connection cable

7.1 Power Supply Wiring

57 7 • Remedy 1 (Refer to the figures Remedy 1-1 and 1-2 below.) If the electric potential difference between the ground cable and the panel that houses the GOT is creating problems, connect the ground cable to the panel also. If the wiring method as shown in Remedy 1-1 is not feasible, follow Remedy 1-2. If taking Remedy 1 worsens noise interference, taking Remedy 2 may alleviate it. • Remedy 2 (Refer to the figures Remedy 2-1 and 2-2 below.) Attach a ferrite core to the cable if noise from the GOT panel has adverse effects on the GOT when Remedy 1 is taken. Wind the wire around the ferrite core several times (approx. 3times), if a ferrite core is used. If the wiring method as shown in Remedy 2-1 is not feasible, follow Remedy 2-2. FG Ground cable from the panel that houses control equipment Connection cable Panel grounding Panel grounding Remedy1-1 Use the thickest cable possible. FG Connection cable Remedy1-2 Ground cable from the panel that houses control equipment Use the thickest cable possible. Ground cable from the panel that houses control equipment Connection cable Remedy2-1 Use the thickest cable possible. Ground cable from the panel that houses control equipment Use the thickest cable possible. FG Connection cable Remedy2-2 FG Panel grounding Panel grounding Ferrite core Ferrite core

7.2 Wiring Inside and Outside the Panel

7.2 Wiring Inside and Outside the Panel Wiring inside Run power lines, servo amplifier drive wires, and communication cables so that they do not cross each other. Noise interference that is generated by cables that cross each other may cause malfunctions. Surge suppressors are an effective way to filter out surge noise that is generated from no fuse breakers (NFB), electromagnetic contactors (MC), relays (RA), solenoid valves, and induction motors. Refer to the section to follow for surge killers. Page 59 Attaching surge killers to control equipment Outside the panel To pull the power line and communication cable out of the panel, make two pullout holes away from each other and pull the cables through. Putting both cables through the same pullout hole will increase noise interference. Keep the power line and communication cable inside the duct at least 100mm away from each other. If that is not possible, the use of a metal separator inside the duct can reduce noise interference. NFB MC PLC MC RA RA Terminal block Crossing power lines and communication cables GOT connection cable PLC I/O wire Drive control wire NFB MC PLC MC RA RA Terminal block Uncrossed power lines and communication cables GOT connection cable PLC I/O wire Drive control wire Power cable Power cable Power line Connection cable Pullout hole Pullout hole Connection cable Power line 100mm or more Separator Signal line Power line Power line Wiring duct Signal line

7.2 Wiring Inside and Outside the Panel

59 7 Attaching surge killers to control equipment If communication errors happen in synch with the on/off signals from certain control equipment (referred to as "load" hereafter) such as no fuse breakers, electromagnetic contactors, relays, solenoid valves, and induction motors, surge noise interference is suspected. If this problem happens, keep the ground cable and communication cable away from the load. If that is not possible, an installation of a surge killer will help reduce noise interference. Place the surge killer as close to the load as possible. Remedy for AC inductive load Remedy for DC inductive load Output AC C R L: Load Keep the ground cable and communication cable away from each other. Place the surge killer near the load. Output equipment such as PLC output unit Output DC D L: Load Keep the ground cable and communication cable away from each other. Place the surge killer near the load. Output equipment such as PLC output unit

8.1 SD Card

61 8 8 OPTION 8.1 SD Card The SD card is used to transfer the OS or project data and to save the data of the alarm history function. For details, refer to the following. Page 159 CONTROL OF VARIOUS DATA (DATA CONTROL) Applicable SD card The following SD cards are applicable for GOT. Installation/removal procedure of SD card Install/remove the SD card when the power supply of the GOT is OFF or [Access inhibit] is set in the [SD card access] setting of the GOT. Installation Model Specifications L1MEM-2GBSD SD memory card 2GB L1MEM-4GBSD SDHC memory card 4GB NZ1MEM-2GBSD SDHC memory card 2GB NZ1MEM-4GBSD SDHC memory card 4GB NZ1MEM-8GBSD SDHC memory card 8GB NZ1MEM-16GBSD SDHC memory card 16GB 1. Touch [Main Menu] [Data] [SD card access] [Permissions] to set [Access inhibit]. Page 190 SD Card Access Check that the SD card access LED turns off. When the SD card access LED is off, the SD card can be installed or removed even when the GOT is on. 2. Insert a SD card into the SD card interface with its front side (nameplate side) outside. 3. Touch [SD card access] [Access inhibit] to set [Permissions]. Check that the SD card access LED turns on. SD card surface

8.1 SD Card

Removal Precautions when removing the SD card • Do not pull out the SD card or power OFF the GOT while the SD card access LED is lit. To do so may cause data corruption or malfunction. • When removing the SD card from the GOT, make sure to support the SD card by hand as it may pop out. Failure to do so may cause the SD card to drop from the GOT, resulting in a failure or break. 1. Touch [Main Menu] [Data] [SD card access] [Permissions] to set [Access inhibit]. Page 190 SD Card Access Check that the SD card access LED turns off. When the SD card access LED is off, the SD card can be installed or removed even when the GOT is on. 2. Push the SD card all the way inside and leave your finger once, then remove the SD card.

9 UTILITY FUNCTION

9.1 Utility Execution 63 9 9 UTILITY FUNCTION Utility is a function, which carries out connection of GOT and controller, screen display and operation method settings, program/data control and self-check etc. 9.1 Utility Execution For utility execution, utility has to be displayed by installing Boot OS and package data in the C drive (built in flash memory). There are following two methods for installing Boot OS and package data. Refer to the following for the installation which uses GT Designer3. GT Designer3 (GOT2000) Screen Design Manual For the installation methods of package data with an SD card, refer to the following. Page 273 BootOS and System Application Installation Using Data Storage Install directly from GT Designer3 Via a USB interface or Ethernet interface GT Designer3 GT Designer3 Writing package data 2) GT Designer3→SD card→GOT GOT GOT Installing package data Installing Boot OS or Package data When GOT is remote, install using SD card easily Install SD card to the GOT SD card 1) GT Designer3→GOT

9 UTILITY FUNCTION

9.2 Utility Function List 9.2 Utility Function List The items in the following list can be set/operated on the utility screens. Item Functions overview Reference Language Switching message languages Page 73 LANGUAGE SETTING (LANGUAGE) Comm. Setting Standard I/F Assigning channel number and communication driver to communication interface Page 75 Standard I/F Setting GOT IP Address Configuring GOT Ethernet setting Page 84 GOT IP Address Setting Ethernet communication Displaying the contents of Ethernet setting, changing the host Page 86 Ethernet Communication Comm. Monitor Checking the serial communication port communication Page 90 Communication Monitor Ethernet check Checking the Ethernet communication port communication Page 93 Ethernet Check Transparent mode Setting the channel No. to be used for the communication for the FA transparent function Page 95 Setting the Transparent Mode Keyword Setting or deleting sequence program protection key words and canceling sequence program protection status for the FXCPU connection Page 96 Keyword GOT setup Display Setting the title display period Page 105 Display Settings Setting the screen save time Adjusting brightness Operation Setting the buzzer sound Page 108 Operation Setting (Settings for Operation) Setting the window move buzzer Setting the key reaction speed Touch panel calibration Setting the utility call keys Unique info Setting the GOT ID No. Page 115 Inherent Information GOT internal device monitor Setting the Use/Disuse the GOT internal device monitor of GOT diagnostics Page 116 GOT internal device monitor VNC server function VNC server function setting (GS21-W-N) Page 118 VNC Server Function License management Displaying the screen for registering and canceling a license (GS21-W-N) Page 120 License Management IP filter setting Setting the IP filter usage, filtering method, target IP address, and exception IP address Page 122 IP Filter Setting Security Setting Security level Changing the security level Page 129 Security Level Authentication Operator Operator management Page 131 Operator Authentication Password change Function setting Login/Logout - Page 145 Login/Logout Time setting Time setting Page 147 Time Setting and Display

9 UTILITY FUNCTION

9.2 Utility Function List 65 9 Data OS information OS information Page 163 OS information Resource Data Alarm info. Converting alarm log files in G2A format → CSV/TXT format Deleting or copying alarm log files Page 165 Alarm information Recipe info. Converting recipe files in G2P format → CSV/TXT format Converting CSV/TXT format → Recipe files in G2P format Deleting or copying recipe files Page 170 Recipe information Logging info. Deleting or copying logging files Page 176 Logging information Image file Deleting or copying hard copy files Page 180 Image file management Operation log information Converting operation log files in G2O format → CSV/TXT format Deleting or copying operation log files Page 184 Operation log information SD card access Setting the access permission of the SD card Page 190 SD Card Access SD card format Formatting the SD card Page 191 SD Card Format Clear data Clearing the project data and resource data on the GOT Page 193 Clear data Data copy Transferring the project data or OS to the SD card Page 194 Data Copy Backup/restore Setting the backup and restoration Page 197 BACKUP/ RESTORE Debug Device monitor Device monitor of PLC, test function, current value change of the buffer memory and the buffer memory monitor of intelligent module Page 219 Device Monitor Function FX list editor Changing parameters and sequence program of FX PLC Page 232 FX List Editor FX3U-ENET-ADP Configuring the communication setting for FX3U-ENET-ADP stored in the FXCPU Page 261 FX3U- ENET-ADP Communication Setting Function Maintenance Touch panel calibration Calibrating the touch panel reading error Page 267 Touch Panel Calibration Touch panel check Checking the touch panel operation Page 269 Touch Panel Check Clean Displaying the screen for cleaning the display Page 271 Clean Item Functions overview Reference

9 UTILITY FUNCTION

9.3 Utility Display 9.3 Utility Display To display setting screens for each utility, the main menu has to be displayed first. Main menu The menu items that can be set at the GOT utility are displayed. Touching a menu item in the main menu will display the setting screen or following selection screen for the item. System message switch button This button switches the language used for the utility. When touching the [Language] button, the Select Language screen is displayed. 1. Touch the language button of a desired language and touch the [OK] button to select the language. 2. Touching the [ ] button switches the language on the utility to the selected one.

9 UTILITY FUNCTION

9.3 Utility Display 67 9 • When starting the GOT without selecting any language or the selected language and the installed fonts are not matched The following screen will be displayed. Touching the button of a desired language restarts the GOT and the language is switched to the selected one. • Selectable languages The system message switch button is displayed only for the selectable languages. The selectable languages differ depending on the fonts installed in the GOT. For the relation between the selectable languages and the fonts, refer to the following. GT Designer3 (GOT2000) Screen Design Manual • System language switching using the device The system language can be switched using the system language switching device set with GT Designer3. For the setting method of the system language switching device, refer to the following. GT Designer3 (GOT2000) Screen Design Manual

9 UTILITY FUNCTION

9.3 Utility Display Display operation of main menu The following four types of operation can display the main menu. (Display the main menu after installing the standard monitor OS from GT Designer3 to the GOT built in flash memory.) When project data is undownloaded After the GOT is turned on, a dialog box for notifying of absence of project data is displayed. After the dialog box is displayed, touch the [OK] button to display the main menu. When touching utility call key If you touch the utility call key while user-created screen is displayed, the main menu is displayed. The utility call key is set in the position on the GOT screen upper left corner at factory shipment. The utility function windows appear in the horizontal format, and this format cannot be changed. The utility call key can be set by the GOT utility or GT Designer3. For the setting method of the utility call key, refer to the following. Page 113 Setting the utility call keys GT Designer3 (GOT2000) Screen Design Manual • Prohibited simultaneous 2-point presses Do not touch 2 points or more on the GOT screen simultaneously. Touching 2 points or more simultaneously may activate a part other than the touched point. • Press time of the utility call key When having set [Press time] of the utility call key setting screen to other than "0 (s)", keep pressing the touch panel for the period set to [Press time] or more before leaving the finger from the touch panel. For utility call key setting, refer to the following. Page 113 Setting the utility call keys • When the utility call key is not set Even when the utility call key is not set (set to the zero point), you can display the main menu by performing the following operation. Pressing the special function switch set on the user-created screen Turning on the power supply of the GOT Touch [OK] button Horizontal format Vertical format

9 UTILITY FUNCTION

9.3 Utility Display 69 9 When touching special function switch (utility) If you touch the special function switch (utility) while user-created screen is displayed, the main menu is displayed. The special function switch (utility) can be set as a touch switch that is displayed on a user-created screen by GT Designer3. For the details of the special function switch, refer to the following. GT Designer3 (GOT2000) Screen Design Manual When limiting the display and operation of the utility When limiting the display and operating users, set a password to the GOT using GT Designer3. If a user tries to display the main menu of the utility, the password is displayed. Refer to the following for the details related to the password setting. GT Designer3 (GOT2000) Screen Design Manual Special function switch (Utility)

9 UTILITY FUNCTION

9.3 Utility Display Utility basic configuration The basic configuration of utility is as follows. Title display The screen title name is displayed in title display part. Close/Return button When a middle screen of the layers is displayed, if the [ ] (Close/return) button in the right corner of screen is touched, returns to the previous screen. If this button is touched when directly displayed from monitor screen, the screen is closed and returns to monitor screen. Scroll button For screens in which the content does not fit on one screen page, there is a right or down scroll button on the screen. Scroll one line/column. Scroll window. Title display Close/Return button Display Title display Title display

9 UTILITY FUNCTION

9.3 Utility Display 71 9 Basic operation of settings change Change of setting value ■Setting item, select button Touch the select button to change the settings. The setting methods differ depending on the setting items. The following types of setting method are available. Switching the setting value The button repeats every time it is pressed. Enter the setting value with a keyboard. Use these keys to enter numerical values. Touch the button to display a keyboard on the GOT screen. For the keyboard operations, refer to the next page. Move to another setting screen. Touch the button to move to each setting screen. For the setting method of each setting item, refer to the setting operation of each setting screen. ■[ ] (Close/Return) button Reflect or cancel the changed settings. [ ] (Close/Return) button Touching this button closes the screen. Depending on the setting item, the GOT restarts. Touch the [ ] button, and then the dialog box shown below is displayed. (If no setting is changed, the dialog is not displayed.) Operate following the message of the dialog box. Description Selection button Description Selection button SHORT LONG OFF

9 UTILITY FUNCTION

9.3 Utility Display Keyboard operations 1. Touch the numerical value to be changed. 2. The keyboard for entering numerical values and a cursor are displayed. The display position of the keyboard differs depending on the position of the touched numerical value. (The keyboard is displayed at a position that does not disturb users to input numerical values.) 3. Input numerical value by the keyboard. • [0] to [9] Key: Enter numerical values. • [Enter] Key: Completes the numerical value input and closes the keyboard. • [Cancel] Key: Cancels the numerical value input and closes the keyboard. • [Del] Key: Deletes one character. • [AC] Key: Deletes all characters. • [*] key and the keys which are not mentioned do not function. 4. Touching the [Enter] key completes the numerical value input and closes the keyboard. Cursor keyboard

10 LANGUAGE SETTING (LANGUAGE)

10.1 Display language setting 73 10 10 LANGUAGE SETTING (LANGUAGE) 10.1 Display language setting Display language setting function This function allows display language selection. The items which can be set are shown below. Language setting operation Language Switching the display language of the utility by devices Any device can be used for switching the display language of the utility. For details, refer to the following. GT Designer3 (GOT2000) Screen Design Manual When using devices to switch the display language of the utility, it does not change even if the display language is switched from the GOT utility screen. Item Description Setting range Language Display language in which the utility functions and dialog windows are displayed can be selected or confirmed in this menu Japanese/English/Chinese 1. Touch [Language] to bring up the set up screen. 2. Select a display language by touching the corresponding button. 3. After changing the setting, touch the [ ] button. The setting is saved and the setting screen is closed. Main Menu Touch [Language] Touch a language to be displayed. Touch

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting 75 11 11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING) The following communication interfaces can be set. 11.1 Standard I/F Setting Standard I/F functions Standard I/F display operation Item Functions overview Reference Comm. Setting Standard I/F Assigning channel number and communication driver to communication interface Page 75 Standard I/F Setting GOT IP Address Configuring GOT Ethernet setting Page 84 GOT IP Address Setting Ethernet communication Displaying the contents of Ethernet setting, changing the host Page 86 Ethernet Communication Comm. Monitor Checking the serial communication port communication Page 90 Communication Monitor Ethernet check Checking the Ethernet communication port communication Page 93 Ethernet Check Transparent mode Setting the channel No. to be used for the communication for the FA transparent function Page 95 Setting the Transparent Mode Keyword Setting or deleting sequence program protection key words and canceling sequence program protection status for the FXCPU connection Page 96 Keyword Function Description Channel no. display Displays the channel number (CH No) that has been assigned by drawing Communication driver display Displays the communication driver that has been assigned by drawing software Communication parameters display Displays the communication parameters of the controllers that has been assigned by drawing software Main Menu Comm. Setting Touch [Comm. Setting]. Touch [Standard I/F]. Standard I/F

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting Display contents of standard I/F Described below are the display items on the standard I/F setting menu and their functions. Display item ■Standard interface display BOX The standard interface includes the following four types. • Standard I/F-1(RS-422/485 or RS-422): For communication with a controller • Standard I/F-2(RS232): For communication with PLC, PC (drawing software), modem, other equipment, bar code reader and transparent • Standard I/F-3(USB): For communication with PC (drawing software) and transparent • Standard I/F-4(Ethermet): For communication with PC (drawing software) and other equipment Available standard interfaces differ depending on the GOT model used. ○: Available, ×: Not available • For GS2110-WTBD-N, GS2107-WTBD-N GOT Standard I/F-1 Standard I/F-2 Standard I/F-3 Standard I/F-4 RS-422/485 RS-422 RS-232 USB Ethernet GS2110-WTBD-N GS2107-WTBD-N ○ × ○ ○ ○ GS2110-WTBD GS2107-WTBD × ○ ○ ○ ○ Standard interface display BOX Channel No. specification menu BOX Driver display BOX Drv button Standard I/F-3(USB) Standard I/F-1(RS-422/485) Standard I/F-4(Ethernet) Standard I/F-2(RS-232)

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting 77 11 • For GS2110-WTBD, GS2107-WTBD ■Channel No. specification menu BOX Set a channel number to be used by the standard interface. Page 82 Channel setting operation For the detail of the drivers which can be assigned to each channel, refer to the following. Page 77 Driver display BOX *1 "9" is automatically set to the standard I/F-3(USB). ■Driver display BOX The driver display box displays the names of communication drivers assigned to channels or the communication drivers set in the communication settings of drawing software. For details of the communication drivers to be displayed, refer to the following. GT Designer3 (GOT2000) Screen Design Manual "Disuse" is displayed in the driver display box in the following cases: • The communication driver is not installed. Page 83 Driver setting operation • "0" is set in the channel number specification menu box. The channel number of the standard I/F-3(USB) is fixed to "9". ■[Drv] button Displays the driver setting screen. Select the driver to use on the driver setting screen. Page 83 Driver setting operation The [Drv] button is displayed in the following case. • When a channel number other than channel 0 or 9 is set to the standard I/F-1, standard I/F-2, and standard I/F-4 0: Set when the communication interface is not used. 1, 2: Set when connecting to a controller. 8: Set when connecting to a bar code reader or RFID. 9: *1 Set when connecting to a PC (drawing software). *: Set this channel when the gateway function (except when the connection with controllers is the Ethernet connection) or the Ethernet download function is used. Standard I/F-3(USB) Standard I/F-1(RS-422) Standard I/F-4(Ethernet) Standard I/F-2(RS-232)

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting Precautions for communication between GOT and connected devices • Installing [Communication driver] and downloading [Communication Settings] To perform communication with the connected device, the following actions are necessary. 1) Installing communication drivers (Up to 2 drivers) 2) Assigning channel numbers and communication drivers to communication interfaces 3) Downloading contents (project data) assigned in step 2) Perform 1), 2) and 3) with drawing software. For details, refer to the following. GT Designer3 (GOT2000) Screen Design Manual • When the communication settings have not been downloaded If the communication settings have not been downloaded with drawing software, set the communication settings on the drawing software or in the GOT utility screen.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting 79 11 Detail information setting operation For Standard I/F-1(RS422) and Standard I/F-2(RS232) 1. Touch each driver display box of the standard I/F-1 and standard I/F- 2. 2. The screen jumps to the detailed information screen and the communication parameter will appear. 3. Touch the numerical values of baud rate to switch them repeatedly. The numerical values are set using the ten-key depending on the setting. "0" to "9": Use these keys to enter numerical values. Enter "0" to disable the screen saver function. "ESC": Closes the ten-key window without saving any value entered "AC": Deletes the entire string of numerical characters that are being entered "DEL": Deletes a digit from a string of numerical characters that are being entered "ENT": Enters the value for the clock that has been entered and closes the ten- key pad window "+/-": Switches between positive and negative values. (Only positive values are valid for the clock setting.) "." : Invalid key (not used) Touch [Driver display BOX]. Ex. 4800bps 9600bps 19200bps

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting Communication parameters The types of items that are in the communication parameter setting menu depend on the type of communication driver that is installed on the GOT in use. Refer to the section below for the setting contents of various drivers. GT Designer3 (GOT2000) Screen Design Manual 4. Touch the [ ] button to display the window confirming whether to save the settings. 5. Touch the [YES] button to save the settings and restart. Touch the [NO] button to discard the changes.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting 81 11 For Standard I/F-4(Ethernet) Communication parameter setting by drawing software Set the communication parameter for each communication driver by selecting [Common] [Controller Setting]. GT Designer3 (GOT2000) Screen Design Manual 1. Touch the driver display box of a communication parameter to be set. 2. The screen is switched to the communication detail setting. Set the communication parameter on this screen. GOT IP address setting Page 84 GOT IP Address Setting 3. When the [ ] button is touched, it returns to the previous screen. 4. Touch the [ ] button to display the window confirming whether to save the settings. 5. Touch the [YES] button to save the settings and restart. Touch the [NO] button to discard the changes.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting Channel setting operation Channel number setting operation 1. Touch the channel No. specification menu box to be set. 2. When the channel setting window appears, select the channel number. 3. When the channel number is selected, the settings are fixed and the window returns to the previous one. Therefore, touch the [ ] button. 4. Touch the [ ] button to display the window confirming whether to save the settings. 5. Touch the [YES] button to save the settings and restart. Touch the [NO] button to discard the changes. Touch Touch

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.1 Standard I/F Setting 83 11 Driver setting operation Driver setting operation 1. Touch [Drv] button to bring up the driver setting window. 2. The available driver names are displayed on the driver setting screen. Select the driver to use. 3. When the channel number is selected, the settings are fixed and the window returns to the previous one. Therefore, touch the [ ] button. 4. Touch the [ ] button to display the window confirming whether to save the settings. 5. Touch the [YES] button to save the settings and restart. Touch the [NO] button to discard the changes. Touch [Drv] Touch

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.2 GOT IP Address Setting 11.2 GOT IP Address Setting This section describes the GOT Ethernet setting. The GOT Ethernet setting can also be set with drawing software. For details, refer to the following. GT Designer3 (GOT2000) Screen Design Manual Standard The table below shows the communication setting items and setting range. *1 Set the value "0.0.0.0" when not using the subnet mask and default gateway. Display operation of GOT IP address Communication setting items Setting range Remark IP Address 0.0.0.1 to 223.255.255.254 If a value outside the setting range is entered, the error message "SET NUMBER IS INCORRECT." appears. Subnet Mask*1 192.0.0.0 to 255.255.255.252 Default gateway*1 0.0.0.1 to 223.255.255.254 Per. S/W port No. 1024 to 5010, 5014 to 49152, 49171 to 65534 Set the port number for the GOT download. Transparent port No. 1024 to 5010, 5014 to 49152, 49171 to 65534 Set the port number for the transparent of the GOT. Main Menu Comm. Setting Touch [Comm. Setting]. Touch [GOT IP Address]. GOT IP Address

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.2 GOT IP Address Setting 85 11 Setting operation 1. Touch the numerical part of the octet to be changed among the 1st to 4th octets. 2. When the ten-key pad appears, enter a numerical value in up to 3 digits, and touch the key. If a numerical value outside the setting range is entered, the following error message appears. Enter a numerical value again. For the details of the setting range, refer to the following. Page 261 Specifications 3. If necessary, change the setting of [Per. S/W port No.] and [Transparent port No.]. 4. After the setting change, touch the [×] key. 5. When the screen shown on the left appears, touch the [YES] key. Touch the numerical part of the octet to be changed. Touch Touch[×] Touch [YES]

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.3 Ethernet Communication 11.3 Ethernet Communication Setting function for Ethernet communication The contents of the Ethernet set in GT Designer3 can be checked. The setting of the host station can be changed. For the Ethernet setting, refer to the following. GOT2000 Series Connection Manual for the controller used Display operation of Ethernet communication Channel Setting Ethernet setting Comm. Setting Main menu Touch [Comm. Setting]. Touch [Ethernet setting].

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.3 Ethernet Communication 87 11 Display contents of Ethernet setting The following describes the setting items and the display contents of the Ethernet setting. Channel select tab Channels can be switched. Switching to the channel which does not have the Ethernet setting is not available. Ethernet setting items The contents of the Ethernet setting configured in GT Designer3 are displayed. Changing [Host], [Net No.], [Station No.] and [IP Address] are available. Page 88 Change of host Page 88 Change of Net No. Page 89 Change of station No. Page 89 Change of IP address How to cancel the change of the setting in the [Ethernet setting] screen. Cancel the settings changed in the [Ethernet setting] screen with the [Restore default settings] button. The changed settings remain until they are canceled with the [Restore default settings] button. The changed settings are not canceled even if writing the project data or system application to the GOT. When the project data is written to the GOT without canceling the changed settings, those changed settings are reflected to the Ethernet setting of the written project data. (If the written project data does not have a channel with same Ethernet settings as that of the channel changed in [Ethernet setting] screen, the changed settings are not reflected.) Ethernet setting items Channel select tab

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.3 Ethernet Communication ■Change of host ■Change of Net No. 1. Touch the device to be set as the host. 2. After the setting change, touch the [×] key. When the screen shown on the left appears, touch the [YES] key. 1. Touch the Net No. to be changed, and input the network No. to be changed by the numeric keypad displayed. 2. After the setting change, touch the [×] key. When the screen shown on the left appears, touch the [YES] key. Touch YES. Touch YES.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.3 Ethernet Communication 89 11 ■Change of station No. ■Change of IP address 1. Touch the station No. to be changed, and input the station No. of the destination Ethernet module to be changed by the numeric keypad displayed. 2. After the setting change, touch the [×] key. When the screen shown on the left appears, touch the [YES] key. 1. Touch the IP address to be changed, input the destination IP address to be changed by the numeric keypad displayed. 2. After the setting change, touch the [×] key. When the screen shown on the left appears, touch the [YES] key. Touch YES. Touch YES.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.4 Communication Monitor 11.4 Communication Monitor Communication monitor functions Communication monitor display operation Function Description Communication port-selection status display Indicates the connection status of Standard I/F-1 and I/F-2. Communication status display Displays the communication status (SD: send, RD: receive) Communication error status display Displays an error message when a communication error occurs Comm. Setting Main Menu Comm. Monitor Touch [Comm. Setting]. Touch [Comm. Monitor].

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.4 Communication Monitor 91 11 Screen display content Connection status of the communication ports Indicates the connection status of Standard I/F-1 and I/F-2. Listed in the table below are display items and the connection status (channel number). Communication status Displays the communication status of each communication port. The SD and RD symbols appear in white on red ( , ) while data are being sent or received, and in black on gray ( , ) at other times. They may appear lit depending on the communication status. The SD and RD symbols on the screen indicate normal communication or cable disconnection. Setting example ■[During normal communication (with connection to a device that supports the transparent mode)] ■[When the connecting cable with the controller is disconnected] Display item Channel number Remark PLC Ch1 "PLC" appears when connected to a controller (PLC or microcomputer) Barcode Ch8 "BCR" appears when connected to a bar code reader TRANS. Ch9 "TRANS." appears when the controller that is allocated to one of the communication ports supports the transparent mode "TRANS." automatically changes to "PC" when communicating with drawing software Host(PC) Ch9 "PC" appears when the controller that is allocated to one of the communication ports does not support the transparent mode Printer ChA Appears when connected to a printer. Port Channel number Controller type I/F-1 Ch1 MELSEC-FX I/F-2 Ch8, Ch9 - Connection status of the communication ports Communication error status Communication status The SD and RD symbols for I/F-1 Only the SD symbol next to I/F-1 blinks.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.4 Communication Monitor Communication error status Communication error status of each port is displayed on this screen. The following table describes the communication status that each display item shows. Display item Status Action NO ERROR No error Communication is executed normally. ERR Ovr. Overrun error The receive data is sent continuously with a short interval. Let the baud rate (communication speed) be equivalent between the GOT and counterpart equipment. ERR Frm. Framing error The communication frames of GOT and PLC are inconsistent. Confirm the communication settings of GOT and PLC, such as data length, stop bit and baud rate. ERR Prt. Parity error The parity check conditions of GOT and PLC are inconsistent. Let the parity check condition (odd or even) of GOT and PLC be consistent. ERR Text Text error The sum data is inconsistent. Or the contents of the receive data are not consistent with the send command from the GOT. Let the communication settings and contents of data be consistent between the GOT and counterpart equipment. (If NAK is received while the GOT is connected to the microcomputer board, a text error occurs.) TIME OUT Communication timeout Though receiving is started, receive data is not sent. Check the wiring between the GOT and its communication target. (When the GOT is connected to the microcomputer board, confirm the terminator, CR, wiring, etc.) ERR Line Control line error The control line is not operating correctly. Confirm the wiring of the control line. ERR Cmd. Command error A command contained in the receive data is not consistent with the send command from the GOT.

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.5 Ethernet Check 93 11 11.5 Ethernet Check Ethernet check function The Ethernet status check function sends a ping to check the connection status of Ethernet. Display operation of Ethernet check Ethernet check Main Menu Debug Touch [Debug]. Touch [Ethernet check].

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.5 Ethernet Check Operation of Ethernet status check 1. If the select button of [Destination IP] is touched, a keyboard is displayed. Enter the IP address of the other terminal with the keyboard. 2. If the [Send ping] button is touched, a ping is sent to the IP address entered in [Destination IP]. The timeout time is 5sec. When the communication is completed The [Response received.] dialog box is displayed. When a communication error occurs The [Timeout occurred.] dialog box is displayed. Touch

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.6 Setting the Transparent Mode 95 11 11.6 Setting the Transparent Mode Function of the transparent mode When using the multi-channel function, the channel No. of a controller to which the FA transparent function is executed can be set. For the multi-channel function and the FA transparent function, refer to the following. GOT2000 Series Connection Manual (Mitsubishi Product) For GT Works3 Version1 Display operation the transparent mode setting Operation the transparent mode Function Description Setting range ChNo. The channel No. of a controller to which the FA transparent function is executed can be set. 1/2 (Default: 1) 1. When the transparent ChNo. (numerical part) on the left is touched, the screen for selecting a communication driver is displayed. Select the channel to execute the FA transparent function. 2. If the [ ] button is touched, it returns to the GOT setup screen. Transparent mode Main Menu Comm. Setting Touch [Comm Setting] Touch [Transparent mode]

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.7 Keyword 11.7 Keyword Keyword functions The operation related to a keyword of the FX series PLC can be performed. Keyword display operation Function Description Regist Keyword is registered. Delete Registered keyword is deleted. Clear Keyword protection is cleared. Protect A keyword with cleared protection is reactivated for protection. Main Menu Comm. Setting Channel Setting Keyword Touch [Comm. Setting] Touch [Keyword]

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.7 Keyword 97 11 Regist Keyword is registered. 1. Touch "Regist" to display the selection screen for the registration. For the FX series PLC, which is not compatible with Customer Keyword, the keyword entry screen of [Step3] is displayed. Start the operation from [Step3]. For the Customer Keyword compatible models, refer to the manual of the PLC to be used. 2. Select [Keyword] or [Keyword+Custom]. To register only Keyword and 2nd keyword, touch [Keyword]. To register Customer Keyword, touch [Keyword+Custom]. 3. Input a keyword. Touch the display part of the keyword to be registered. 4. The keyboard for entering a keyword is displayed. Character types to be input can be changed by touching the [KEY] button. Enter a keyword and touch the [ENT] key. For the keyword, 8 digits from 0 to 9 or A to F must be set. 5. After completing the keyword entry, touch [Next]. When [Keyword+Custom] is selected on the selection screen for the registration, the Customer Keyword entry screen is displayed. Enter it in the same way as for Keyword and 2nd keyword. Touch Touch Touch Touch

11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)

11.7 Keyword 6. Set Registration condition. Touch Registration condition to change the setting contents. 7. After setting Registration condition, touch the [Execute] key. The registration of the keyword is completed. 8. The registration of the keyword is completed. Touch [OK]. Touch All Protect Write Protect R/W Protect Touch Touch