Mitsubishi Electric GOT SIMPLE Series Operation & User’s Manual
Read Online
Read the Mitsubishi Electric GOT SIMPLE Series Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full
attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product.
In this manual, the safety precautions are ranked as "WARNING" and "CAUTION".
Note that the
caution level may lead to a serious accident according to the circumstances.
Always follow the instructions of both levels because they are important to personal safety.
Please save this manual to make it accessible when required and always forward it to the end user.
[DESIGN PRECAUTIONS]
WARNING
● Some failures of the GOT or cable may keep the outputs on or off. Some failures of a touch panel may
cause malfunction of the input objects such as a touch switch. An external monitoring circuit should be
provided to check for output signals which may lead to a serious accident. Not doing so can cause an
accident due to false output or malfunction.
● Do not use the GOT as the warning device that may cause a serious accident. An independent and
redundant hardware or mechanical interlock is required to configure the device that displays and
outputs serious warning. Not doing so can cause an accident due to false output or malfunction.
● When the GOT detects its backlight failure, the GOT disables the input operation on the touch
switch(s). Thus, operators cannot operate the GOT with touches. The GOT backlight failure can be
checked with a system signal of the GOT.
● Even when the display section has dimmed due to a failure of the liquid crystal section or the backlight
on the GOT, the input operation of the touch switches may still be enabled. This may cause an
incorrect operation of the touch switches. For example, if an operator assumes that the display
section has dimmed because of the screen save function and touches the display section to cancel
the screen save, a touch switch may be activated.
WARNING
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury or
physical damage.
● The display section of the GOT is an analog-resistive type touch panel. Simultaneous pressing of two
or more areas on the display section may activate the switch between those areas. Do not press two
or more areas simultaneously on the display section. Doing so may cause an accident due to incorrect
output or malfunction.
● When programs or parameters of the controller (such as a PLC) that is monitored by the GOT are
changed, be sure to shut off the power of the GOT promptly and power on the GOT again. Not doing
so can cause an accident due to false output or malfunction.
● If a communication fault (including cable disconnection) occurs during monitoring on the GOT,
communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative. A
system where the GOT is used should be configured to perform any significant operation to the
system by using the switches of a device other than the GOT on the assumption that a GOT
communication fault will occur. Not doing so can cause an accident due to false output or malfunction.
● To maintain the security (confidentiality, integrity, and availability) of the GOT and the system against
unauthorized access, DoS*1 attacks, computer viruses, and other cyberattacks from unreliable
networks and devices via network, take appropriate measures such as firewalls, virtual private
networks (VPNs), and antivirus solutions.
Mitsubishi Electric shall have no responsibility or liability for any problems involving GOT trouble and
system trouble by unauthorized access, DoS attacks, computer viruses, and other cyberattacks.
*1 DoS: A denial-of-service (DoS) attack disrupts services by overloading systems or exploiting
vulnerabilities, resulting in a denial-of-service (DoS) state.
CAUTION
● Do not bundle the control and communication cables with main-circuit, power or other wiring. Run the
above cables separately from such wiring and keep them a minimum of 100mm apart. Not doing so
noise can cause a malfunction.
● Do not press the GOT display section with a pointed material as a pen or driver. Doing so can result in
a damage or failure of the display section.
● When the GOT is connected to the Ethernet network, the available IP address is restricted according
to the system configuration.
When multiple GOTs are connected to the Ethernet network:
Do not set the IP address (192.168.3.18) for the GOTs and the controllers in the network.
When a single GOT is connected to the Ethernet network:
Do not set the IP address (192.168.3.18) for the controllers except the GOT in the network.
Doing so can cause the IP address duplication. The duplication can negatively affect the
communication of the device with the IP address (192.168.3.18). The operation at the IP address
duplication depends on the devices and the system.
● Turn on the controllers and the network devices to be ready for communication before they
communicate with the GOT. Failure to do so can cause a communication error on the GOT.
● When the GOT is subject to shock or vibration, or some colors appear on the screen of the GOT, the
screen of the GOT might flicker.
● Be sure to shut off all phases of the external power supply used by the system before mounting or
removing the GOT main unit to/from the panel. Not doing so can cause the unit to fail or malfunction.
CAUTION
● Use the GOT in the environment that satisfies the general specifications described in this manual. Not
doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
● When mounting the GOT to the control panel, tighten the mounting screws in the specified torque
range (0.36N·m to 0.48N·m) with a Phillips-head screwdriver No.2. Undertightening can cause the
GOT to drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction
due to the damage of the screws or the GOT.
● Remove the protective film of the GOT. When the user continues using the GOT with the protective
film, the film may not be removed.
● Operate and store the GOT in environments without direct sunlight, high temperature, dust, humidity,
and vibrations.
● Do not use the GOT in an environment with oil or chemicals. Doing so may cause failure or
malfunction due to the oil or chemical entering into the GOT.
● Be sure to shut off all phases of the external power supply used by the system before wiring. Failure
to do so may result in an electric shock, product damage or malfunctions.
CAUTION
● Please make sure to ground FG terminal of the GOT power supply section by applying 100Ω or less
which is used exclusively for the GOT. Not doing so may cause an electric shock or malfunction.
● Correctly wire the GOT power supply section after confirming the rated voltage and terminal
arrangement of the product. Not doing so can cause a fire or failure.
● Tighten the terminal screws of the GOT power supply section in the specified torque range (0.5N·m to
0.6N·m). Undertightening can cause a short circuit or malfunction. Overtightening can cause a short
circuit or malfunction due to the damage of the screws or the GOT.
● Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so
can cause a fire, failure or malfunction.
● Plug the communication cable into the GOT interface or the connector of the connected unit, and
tighten the mounting screws and the terminal screws in the specified torque range. Undertightening
can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to
the damage of the screws or unit.
[TEST OPERATION PRECAUTIONS]
[STARTUP/MAINTENANCE PRECAUTIONS]
[STARTUP/MAINTENANCE PRECAUTIONS]
WARNING
● Before performing the test operations of the user creation monitor screen (such as turning ON or OFF
bit device, changing the word device current value, changing the settings or current values of the
timer or counter, and changing the buffer memory current value), read through the manual carefully
and make yourself familiar with the operation method. During test operation, never change the data of
the devices which are used to perform significant operation for the system. False output or
malfunction can cause an accident.
WARNING
● When power is on, do not touch the terminals. Doing so can cause an electric shock or malfunction.
● Before starting cleaning or terminal screw retightening, always switch off the power externally in all
phases.
Not doing so can cause the unit to fail or malfunction.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
CAUTION
● Do not disassemble or modify the unit. Doing so can cause a failure, malfunction, injury or fire.
● Do not touch the conductive and electronic parts of the unit directly. Doing so can cause a unit
malfunction or failure.
● The cables connected to the unit must be run in ducts or clamped. Not doing so can cause the unit or
cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a
malfunction due to a cable connection fault.
● When unplugging the cable connected to the unit, do not hold and pull from the cable portion. Doing
so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection
fault.
● Do not drop the module or subject it to strong shock. A module damage may result.
● Before touching the unit, always touch grounded metals, etc. to discharge static electricity from
human body, etc. Not doing so can cause the unit to fail or malfunction.
[TOUCH PANEL PRECAUTIONS]
[PRECAUTIONS WHEN THE DATA STORAGE IS IN USE]
[PRECAUTIONS WHEN THE DATA STORAGE IS IN USE]
[DISPOSAL PRECAUTIONS]
CAUTION
● For the analog-resistive film type touch panels, normally the adjustment is not required.
However, the difference between a touched position and the object position may occur as the period
of use elapses. When any difference between a touched position and the object position occurs,
execute the touch panel calibration.
● When any difference between a touched position and the object position occurs, other object may be
activated. This may cause an unexpected operation due to incorrect output or malfunction.
WARNING
● If the SD card mounted on drive A of the GOT is removed while the GOT is accessed, processing for
the GOT might be interrupted about for 20 seconds. The GOT cannot be operated during this period.
The functions that run in the background including a screen updating, alarm, logging, scripts, and
others are also interrupted. Since this interruption makes an impact to the system operation, it might
cause failure. After inhibiting access to the SD card on the GOT utility screen, check that the SD card
access LED is off and remove the SD card.
CAUTION
● If the data storage mounted on the GOT is removed while the GOT is accessed, the data storage and
files are damaged. To remove the data storage from the GOT, check that the access to the data
storage in SD card access LED, the system signal, and others is not performed.
● When removing the SD card from the GOT, make sure to support the SD card by hand as it may pop
out. Failure to do so may cause the SD card to drop from the GOT, resulting in a failure or break.
● Before removing the USB device from the GOT, follow the procedure for removal on the utility screen
of the GOT. After the successful completion dialog is displayed, remove the USB device by hand
carefully. Failure to do so may cause the USB device to drop from the GOT, resulting in a failure or
break.
CAUTION
● When disposing of this product, treat it as industrial waste.
● Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be
exposed to the impact exceeding the impact resistance described in the general specifications of this
manual, as they are precision devices. Failure to do so may cause the unit to fail. Check if the unit
operates correctly after transportation.
● When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are
used for disinfecting and protecting wooden packaging from insects, they cause malfunction when
entering our products. Please take necessary precautions to ensure that remaining materials from
fumigant do not enter our products, or treat packaging with methods other than fumigation (heat
method). Additionally, disinfect and protect wood from insects before packing products.
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
About Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Abbreviations and Generic Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
CHAPTER 1 OVERVIEW
19
1.1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Rough procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CHAPTER 2 SYSTEM CONFIGURATION
23
2.1
Overall Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.2
Component List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Explanation of the GOT model name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
GOT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Extension unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
CHAPTER 3 SPECIFICATIONS
27
3.1
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.3
Power Supply Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.4
GOT Connector Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
RS-232 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
RS-422 interface and RS-422/485 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
CHAPTER 4 PART NAME
33
4.1
Front Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.2
Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.3
Bottom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
CHAPTER 5 EMC DIRECTIVE
39
5.1
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Conforming standards in the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2
EMC Directive Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Installing the GOT on the control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Installing a noise filter (power supply line filter). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
System configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Connection of power cables and ground cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Fabricating a connection cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Grounding a cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
CHAPTER 6 INSTALLATION
47
6.1
Control Panel Inside Dimensions for Mounting GOT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.2
Panel Cutting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
6.3
Mounting Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Temperature and Mounting Angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
6.5
Installation Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
CHAPTER 7 WIRING
53
7.1
Power Supply Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Cable types and wire end processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Wiring example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
GOT's ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
The cause of malfunctions related wiring/Remedy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
7.2
Wiring Inside and Outside the Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Wiring inside . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Outside the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Attaching surge killers to control equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
CHAPTER 8 OPTION
61
8.1
SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Applicable SD card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Installation/removal procedure of SD card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
CHAPTER 9 UTILITY FUNCTION
63
9.1
Utility Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
9.2
Utility Function List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
9.3
Utility Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
Display operation of main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Utility basic configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Basic operation of settings change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
CHAPTER 10 LANGUAGE SETTING (LANGUAGE)
73
10.1
Display language setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Display language setting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Language setting operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
CHAPTER 11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
75
11.1
Standard I/F Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Standard I/F functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Standard I/F display operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Display contents of standard I/F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Detail information setting operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Channel setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Driver setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11.2
GOT IP Address Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Display operation of GOT IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
11.3
Ethernet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Setting function for Ethernet communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Display operation of Ethernet communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Display contents of Ethernet setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
11.4
Communication Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Communication monitor functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Communication monitor display operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Screen display content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
11.5
Ethernet Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
11.6
Setting the Transparent Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
11.7
Keyword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Keyword functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Keyword display operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Regist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Clear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102
Protect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
CHAPTER 12 DISPLAY AND OPERATION SETTINGS (GOT SET UP)
105
12.1
Display Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Display setting functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Display operation of display setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
Display setting operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
12.2
Operation Setting (Settings for Operation). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Operation setting functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Display operation of operation setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Setting operation of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Position correction of the touch panel (touch panel calibration setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Setting the utility call keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
12.3
Inherent Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Setting function for inherent information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Display operation of inherent information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Setting operation for inherent information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
12.4
GOT internal device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Setting the GOT internal device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
GOT internal device monitor display operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
GOT internal device monitor setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
12.5
VNC Server Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
VNC server function setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Display operation of the VNC server function setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
VNC server function setting operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
12.6
License Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120
License management setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Display operation of the license management setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Setting operation of license management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
12.7
IP Filter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
IP filter setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Display operation of the IP filter setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Setting procedure for the IP filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
CHAPTER 13 SECURITY LEVEL AND OPERATOR SETTINGS (SECURITY SETTING)
129
13.1
Security Level Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
13.2
Operator Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Operator information management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Password change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
Function setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
13.3
Login/Logout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
CHAPTER 14 CLOCK SETTINGS (TIME SETTING AND DISPLAY)
147
14.1
Time Setting and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
Time setting and display functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Clock synchronization method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Time setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Adjusting the clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
Local time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
CHAPTER 15 CONTROL OF VARIOUS DATA (DATA CONTROL)
159
15.1
Data Storage Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Data type and storage location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Checking version of basic system application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161
15.2
OS information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
15.3
Resource Data Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Alarm information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165
Recipe information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170
Logging information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .176
Image file management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Operation log information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
15.4
SD Card Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Functions of SD card access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Display operation of SD card access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .190
Operation of SD card access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
15.5
SD Card Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
15.6
Clear data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Clear data functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .193
Clear data display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .193
Clear data operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
15.7
Data Copy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Display operation of data copy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Operation of data copy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195
15.8
BACKUP/RESTORE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
BACKUP/RESTORE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
System configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Access range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Security and password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .205
Operation of backup/restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Operation of backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Operation of restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
Operation of keyword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216
15.9
Errors and Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
CHAPTER 16 GOT SELF CHECK (DEBUG)
219
16.1
Device Monitor Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
System configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Devices that can be monitored . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .220
Display operation of device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Information displayed on the device monitor screen and key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .222
Basic operation of device monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
Device registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .225
Quick test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228
16.2
FX List Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232
Display operation of FX list editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Access range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .235
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .235
Display operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Operation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .238
Selection and operation of modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Displaying sequence programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .241
Searching commands/devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .243
Writing commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .245
Changing operands, set values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .249
Deleting commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250
Sequence program all clear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
PLC diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Parameter setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .254
Keyword. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .256
List monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .258
Action for an incorrect key input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .259
Error messages and corrective actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
16.3
FX3U-ENET-ADP Communication Setting Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .261
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Display operation of FX3U-ENET-ADP communication setting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
Setting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
CHAPTER 17 MAINTENANCE
267
17.1
Touch Panel Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
17.2
Touch Panel Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
17.3
Clean. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
CHAPTER 18 BootOS and System Application Installation Using Data Storage
273
18.1
Installing when starting the GOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .274
18.2
Installing using the data control function (Utility) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
CHAPTER 19 INSTALLATION OF Boot OS AND BASIC SYSTEM APPLICATION
275
19.1
Boot OS and Basic System Application to be Installed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .275
19.2
Prior Preparations for Installing Boot OS and System Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .276
CHAPTER 20 ERROR MESSAGE LIST
277
CHAPTER 21 MAINTENANCE AND INSPECTION
279
21.1
Daily Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
21.2
Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
Cleaning Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .281
21.4
Backlight Shutoff Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282
Backlight shutoff detection and external alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
CHAPTER 22 TROUBLESHOOTING
283
22.1
GOT Restoration Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
GOT status check sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
GOT installation status check sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
System configuration check sheet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
CHAPTER 23 CONNECTION
295
CHAPTER 24 APPENDIX
297
24.1
External Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
REVISIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .304
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .305
TRADEMARKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .306
Thank you for choosing Mitsubishi Electric Graphic Operation Terminal (GOT).
Before using the product, read this manual carefully and make sure you understand the functions and performance of the
GOT for correct use.
About Manual
The following manuals related to this product are available.
Refer to each manual in accordance with the intended use.
e-Manual
e-Manual refers to the Mitsubishi Electric FA electronic book manuals that can be browsed using a dedicated
tool.
e-Manual has the following features:
Required information can be cross-searched in multiple manuals.
Other manuals can be accessed from the links in the manual.
Hardware specifications of each part can be found from the product figures.
Pages that users often browse can be bookmarked.
Screen creation software manuals
Connection manuals
GOT SIMPLE series manuals
Manual name
Manual number
(Model code)
Format
GT Works3 Installation Instructions
-
PDF
GT Designer3 (GOT2000) Screen Design Manual
SH-081220ENG
(1D7ML9)
PDF
e-Manual
GT Converter2 Version3 Operating Manual for GT Works3
SH-080862ENG
(1D7MB2)
PDF
e-Manual
Manual name
Manual number
(Model code)
Format
GOT2000 Series Connection Manual (Mitsubishi Product) For GT Works3 Version1
SH-081197ENG
(1D7MJ8)
PDF
e-Manual
GOT2000 Series Connection Manual (Non Mitsubishi Product 1) For GT Works3 Version1
SH-081198ENG
PDF
e-Manual
GOT2000 Series Connection Manual (Non Mitsubishi Connecting Non-Mitsubishi products to the
GOT Product 2) For GT Works3 Version1
SH-081199ENG
PDF
e-Manual
GOT2000 Series Connection Manual (Microcomputer, MODBUS Products, Peripherals) For GT
Works3 Version1
SH-081200ENG
PDF
e-Manual
Manual name
Manual number
Format
GOT SIMPLE Series User's Manual
JY997D52901
PDF
e-Manual
• Obtaining the specifications and operation methods of GT Designer3
• Setting available functions on GT Designer3
• Creating a screen displayed on the GOT
• Obtaining useful functions to increase efficiency of drawing
• Setting details for figures and objects
• Setting functions for the data collection or trigger action
• Setting functions to use peripheral devices
• Simulating a created project on a personal computer
GT Designer3 (GOT2000) Screen Design Manual
Connecting a controller to the GOT
• Obtaining information of Mitsubishi products applicable to the GOT
• Connecting Mitsubishi products to the GOT
• Connecting multiple controllers to one GOT (Multi-channel function)
• Establishing communication between a personal computer and a controller via the GOT (FA transparent function)
GOT2000 Series Connection Manual (Mitsubishi Product) For GT Works3 Version1
• Obtaining information of Non-Mitsubishi products applicable to the GOT
• Connecting Non-Mitsubishi products to the GOT
GOT2000 Series Connection Manual (Non Mitsubishi Product 1) For GT Works3 Version1
GOT2000 Series Connection Manual (Non Mitsubishi Connecting Non-Mitsubishi products to the GOT Product 2) For GT
Works3 Version1
• Obtaining information of peripheral devices applicable to the GOT
• Connecting peripheral devices including a bar code reader to the GOT
GOT2000 Series Connection Manual (Microcomputer, MODBUS Products, Peripherals) For GT Works3 Version1
Transferring data to the GOT
• Writing data to the GOT
• Reading data from the GOT
• Verifying an editing project to a GOT project
GT Designer3 (GOT2000) Screen Design Manual
Others
• Obtaining specifications (including part names, external dimensions, and options) of each GOT
• Installing the GOT
GOT SIMPLE Series User's Manual
• Operating the utility
GOT SIMPLE Series User's Manual
• Configuring the gateway function
GT Designer3 (GOT2000) Screen Design Manual
Abbreviations and Generic Terms
GOT
Communication interface
Option
Software
■Software related to GOT
Abbreviations and generic terms
Description
GOT SIMPLE
Series
GS21
GS21-W-N
GS2110-WTBD-N
GS2107-WTBD-N
GS21-W
GS2110-WTBD
GS2107-WTBD
Abbreviations and generic terms
Description
Serial multi-drop connection unit
GT01-RS4-M
Abbreviations and generic terms
Description
SD card
NZ1MEM-2GBSD, NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD, L1MEM-2GBSD, L1MEM-
4GBSD
Abbreviations and generic terms
Description
GT Works3
SW1DNC-GTW3-J, SW1DND-GTW3-J, SW1DNC-GTW3-E, SW1DND-GTW3-E, SW1DND-GTW3-C
GT Designer3 Version1
Screen drawing software GT Designer3 for GOT2000/GOT1000 series
GT Designer3
Screen drawing software for GOT2000 series included in GT Works3
GT Designer3 (GOT2000)
GT Designer3 (GOT1000)
Screen drawing software for GOT1000 series included in GT Works3
GT Simulator3
Screen simulator GT Simulator3 for GOT2000/GOT1000/GOT900 series
Abbreviations and generic terms
Description
GX Works3
SW□DND-GXW3-E (-EA) type programmable controller engineering software
(□ indicates a version.)
GX Works2
SW□DNC-GXW2-□ type programmable controller engineering software
(□ indicates a version.)
GX Simulator3
Simulation function of GX Works3
GX Simulator2
Simulation function of GX Works2
GX Simulator
SW□D5C-LLT-E (-EV) type ladder logic test tool function software package
(SW5D5C-LLT (-V) or later versions)
(□ indicates a version.)
GX Developer
SW□D5C-GPPW-E (-EV)/SW□D5F-GPPW (-V) type software package
(□ indicates a version.)
GX LogViewer
SW□DNN-VIEWER-E type software package
(□ indicates a version.)
PX Developer
SW□D5C-FBDQ-E type FBD software package for process control
(□ indicates a version.)
MT Works2
Motion controller engineering environment MELSOFT MT Works2 (SW□DNDMTW2-E)
(□ indicates a version.)
MT Developer
SW□RNC-GSV type integrated start-up support software for motion controller Q series
(□ indicates a version.)
CW Configurator
C Controller module configuration and monitor tool (SW1DND-RCCPU-E)
(□ indicates a version.)
MR Configurator2
SW□DNC-MRC2-E type servo configuration software
(□ indicates a version.)
MR Configurator
MRZJW□-SETUP type servo configuration software
(□ indicates a version.)
FR Configurator
Inverter setup software (FR-SW□-SETUP-WE)
(□ indicates a version.)
NC Configurator2
CNC parameter setting support tool (FCSB1221)
NC Configurator
CNC parameter setting support tool
FX Configurator-FP
Parameter setting, monitoring, and testing software packages for FX3U-20SSC-H (SW□D5CFXSSCE)
(□ indicates a version.)
FX3U-ENET-L Configuration tool
FX3U-ENET-L type Ethernet module setting software (SW1D5-FXENETL-E)
RT ToolBox2
Robot program creation software (3D-11C-WINE)
MX Component
MX Component Version□ (SW□D5C-ACT-E, SW□D5C-ACT-EA)
(□ indicates a version.)
MX Sheet
MX Sheet Version□ (SW□D5C-SHEET-E, SW□D5C-SHEET-EA)
(□ indicates a version.)
CPU Module Logging Configuration Tool
CPU module logging configuration tool (SW1DNN-LLUTL-E)
Abbreviations and generic terms
Description
SIEMENS
Siemens AG
PLC
Programmable controller manufactured by each corporation
A GOT is installed on the panel surface of a control panel or operating panel and connects to the PLC within the control panel.
The GOT carries out switch operation, lamp display, data display, message display, etc.
For the display screen, two kinds of screens are available: user screen and utility screen.
■User screen
The user screen is a screen drawn by drawing software.
The objects "Touch switch", "Lamp display", "Comment display", and "Numeric display" can be arbitrarily arranged on the
display.
Moreover, multiple screens created within drawing software can be individually selected or overlapped for the display.
For details, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
■Utility Screen
The utility screen is a factory drawn horizontal screen that cannot be edited.
The utility screen can be displayed on the GOT by installing the standard monitor OS from drawing software or an SD card to
the GOT.
Such as [Brightness] and [Time setting] can be set from the utility screen.
For details, refer to the following.
Page 63 UTILITY FUNCTION to Page 283 TROUBLESHOOTING
PLC
Connector for
program
GOT
Monitoring for turning on or off bit devices of a PLC, forcibly turning on or off the bit devices of a PLC, monitoring the word
device set value/current value and changing that numeric values are easily made.
General-purpose properties of the display unit
The display unit is used for engineers' stage replacement, setting change and troubleshooting or for operation guidance to an
operator.
• Monitor
• Forcibly turning on or off
• Set value change
• Trouble check
Improved monitoring performance and connectivity to FA devices
• Multiple languages are displayed using the Unicode2.1-compatible fonts and beautiful characters are drawn using the
TrueType, high quality fonts, and outline fonts *1
• Two types of display modes are available: 65536-color display and monochrome
A fine and beautiful full-color display which shows even small characters clearly, is enabled in the 65536-color display by
adopting the high intensity, wide viewing angle and high definition TFT color liquid crystal display.
(Also compatible with digital screen displays with 65536 colors, BMP, etc.)
High speed monitoring through high speed communication at maximum of 115.2kbps
• High speed display and high speed touch switch response
• The operation performance is improved by the analog touch panel.
*1
Outline fonts are compatible only with GS21-W-N.
More efficient GOT operations including screen design, startup, adjustment,
management and maintenance works
• The 9MB/15MB built-in flash memory is included as standard. *1
• SD card interface is included as standard.
• RS-232 interface is included as standard.
• RS-422 interface and RS-422/485 interface are included as standard. *2
• USB interface (device) is included as standard.
• Ethernet interface is included as standard.
• System font types are increased by the adoption of the font installation system.
• Three types of alarms (user alarm, alarm history, and alarm popup display) are integrated, and realizing an efficient alarm
notification.
• "When, what, and how" the operation was performed can be checked with the GOT by using the operation log function
(GS21-W-N only).
*1
The memory capacity vary by model.
*2
The available interfaces vary by model.
Enhanced support of FA setup tools
Connecting the GOT and the personal computer enables programming, rising, and adjustment of Mitsubishi Electric FA
devices from the personal computer via the GOT.
The following shows the procedures before operating a GOT and the descriptions of each item.
Install GT Designer3 in a personal computer.
GT Works3 Installation Instructions
GS21 General Description
Create project data.
GT Designer3 (GOT2000) Screen Design Manual
Wire for the GOT power supply and the controller.
7. WIRING
GOT2000 Series Connection Manual for GT Works3 Version1
Wire for the controller power supply and I/O.
Controller manuals
Turn on the power of the GOT and controller.
Install the OS to the GOT.
GT Designer3 (GOT2000) Screen Design Manual
Check that the OS is installed to the GOT.
Download project data.
GT Designer3 (GOT2000) Screen Design Manual
Check that the monitoring is normal.
Turn on the controller power and check that the GOT
recognizes the controller.
2 SYSTEM CONFIGURATION
2.1 Overall Configuration
23
2
2
SYSTEM CONFIGURATION
2.1
Overall Configuration
The overall configuration of GOT is as follows.
For the connection methods applicable to GS series and cable, refer to the following.
GOT2000 Series Connection Manual For GT Works3 Version1
*1
Only hard copy of the screen can be printed.
2.2
Component List
Explanation of the GOT model name
Bar code reader
(Commercially available)
Personal computer
(Commercially available)
Printer*1
(Commercially available)
SD card
GS21 series
0 7
- W
Panel color
10: 10" wide screen
07: 7" wide screen
Screen size
W: 800×480
Resolution
D: 24VDC
Power type
T: TFT color
Display section
B: Black
T B D
G S 2 1
- N
N: Function extension version
None: Standard
Specially supported
specification
2 SYSTEM CONFIGURATION
2.2 Component List
GOT
Extension unit
Only available to GS21-W-N.
Communication unit
Software
*1
The desired number of licenses (2 or more) can be purchased. For details, please contact your local sales office.
*2
Volume license product and additional license product are also available. For more details, please refer to the MELSOFT iQ Works
catalog (L(NA)08232ENG).
*3
The product includes the following software.
System Management Software [MELSOFT Navigator]
Programmable Controller Engineering Software [MELSOFT GX Works3, GX Works2, GX Developer]
Motion Controller Engineering Software [MELSOFT MT Works2]
GOT Screen Design Software [MELSOFT GT Works3]
Robot Engineering Software [MELSOFT RT ToolBox3 mini]
Inverter Setup Software [MELSOFT FR Configurator2]
Servo Setup Software [MELSOFT MR Configurator2]
*4
This product does not include a DVD-ROM. The license certificate indicating the product ID number is issued only.
*5
Each GOT requires one license.
*6
Only available to GS21-W-N.
Product name
Model
Specifications
GOT
GS2110-WTBD-N
10" [800 × 480 dots], TFT color liquid crystal, 65536 colors
24VDC, Memory capacity: 15MB, built-in Ethernet interface, built in RS-232 interface, built in
RS-422/485 interface
GS2107-WTBD-N
7" [800 × 480 dots], TFT color liquid crystal, 65536 colors
24VDC, Memory capacity: 15MB, built-in Ethernet interface, built in RS-232 interface, built in
RS-422/485 interface
GS2110-WTBD
10" [800 × 480 dots], TFT color liquid crystal, 65536 colors
24VDC, Memory capacity: 9MB, built-in Ethernet interface, built in RS-232 interface, built in
RS-422 interface
GS2107-WTBD
7" [800 × 480 dots], TFT color liquid crystal, 65536 colors
24VDC, Memory capacity: 9MB, built-in Ethernet interface, built in RS-232 interface, built in
RS-422 interface
Product name
Model
Specifications
Serial multi-drop connection unit
GT01-RS4-M
For the GOT multi-drop connection
Product name
Model
Description
HMI/GOT Screen Design Software
MELSOFT GT Works3
SW1DND-GTWK3-E
English version
Standard license product
DVD-ROM
SW1DND-GTWK3-EA
Volume license product *1
SW1DND-GTWK3-EAZ
Additional license product *1*4
SW1DND-GTWK3-C
Simplified Chinese
version
Standard license product
DVD-ROM
FA Integrated Engineering Software
MELSOFT iQ Works *2*3
SW2DND-IQWK-E
English version
Standard license product
DVD-ROM
VNC server function license *5*6
GT25-VNCSKEY-1
1 license
GT25-VNCSKEY-5
5 licenses
GT25-VNCSKEY-10
10 licenses
GT25-VNCSKEY-20
20 licenses
2 SYSTEM CONFIGURATION
2.2 Component List
25
2
Option
Connection cables for MITSUBISHI PLCs (Sold separately)
Connection cables for SIEMENS PLCs (Sold separately)
SD card (Sold separately)
*1
Only available to GS21-W-N.
Product name
Model
Cable
length
Description
RS-422 conversion cable
FA-CNV2402CBL
0.2 m
For connecting the QCPU/L02SCPU(-P) and the RS-422 cable (GT01-C□R4-
25P, GT10-C□R4-25P, GT21-C□R4-25P5)
For connecting the L6ADP-R2 and the RS-422 cable (GT01-C□R4-25P, GT10-
C□R4-25P, GT21-C□R4-25P5)
[MINI-DIN 6-pin ←→ D-sub 25-pin]
FA-CNV2405CBL
0.5 m
RS-422
Cable
FXCPU direct connection
cable, FX expansion
board connection cable
GT01-C10R4-8P
1m
For connecting FXCPU (MINI DIN 8 pins connector) and GOT
For connecting FXCPU expansion board (MINI DIN 8 pins connector) and
GOT
GT01-C30R4-8P
3m
GT01-C100R4-8P
10m
GT01-C200R4-8P
20m
GT01-C300R4-8P
30m
QnA/A/FXCPU direct
connection cable,
computer link connection
cable
GT01-C30R4-25P
3m
QnA/A motion controller (A series)
For connecting FXCPU (D-Sub 25 pins connector) and GOT
For connecting FA-CNV
CBL and GOT
For connecting serial communication unit (AJ71QC24(N)-R4) and GOT
GT01-C100R4-25P
10m
GT01-C200R4-25P
20m
GT01-C300R4-25P
30m
Computer link connection
cable
GT09-C30R4-6C
3m
For connecting computer link unit/serial communication unit and GOT
GT09-C100R4-6C
10m
GT09-C200R4-6C
20m
GT09-C300R4-6C
30m
RS-232
cable
QCPU direct connection
cable
GT01-C30R2-6P
3m
For connecting QCPU and GOT
FX expansion board
connection cable, FX
special adaptor
connection cable
GT01-C30R2-9S
3m
For connecting FXCPU expansion board (D-Sub 9 pins connector) and GOT
For connecting FXCPU special adaptor (D-sub 9 pins connector) and GOT
FX special adaptor
connection
GT01-C30R2-25P
3m
For connecting FXCPU special adaptor (D-sub 25 pins connector) and GOT
Computer link connection
cable
GT09-C30R2-9P
3m
For connecting computer link unit/serial communication unit and GOT
GT09-C30R2-25P
3m
Product name
Model
Cable length
Description
RS-232 cable
GT09-C30R20801-9S
3m
For connecting SIEMENS HMI Adapter and GOT
Product name
Model
Description
SD card
NZ1MEM-2GBSD *1
SD memory card 2GB
NZ1MEM-4GBSD *1
SDHC memory card 4GB
NZ1MEM-8GBSD *1
SDHC memory card 8GB
NZ1MEM-16GBSD *1
SDHC memory card 16GB
L1MEM-2GBSD
SD memory card 2GB
L1MEM-4GBSD
SDHC memory card 4GB
2 SYSTEM CONFIGURATION
2.2 Component List
PC connection cable (Sold separately)
Bar code reader (Sold separately)
*1
Some models with the operations checked by our company are usable. For the operation-checked models, contact your local distributor.
Product name
Model
Cable length
Description
Project data transfer
cable
GT09-C30USB-5P
3m
For connecting GOT (USB Mini-B) and personal computer (USB)
Product name
Model
Description
Bar code
-
Commercially-available bar code reader*1
3.1 General Specifications
27
3
3
SPECIFICATIONS
3.1
General Specifications
*1
Includes the temperature inside the enclosure of the control panel on which the GOT is installed.
*2
If the ambient temperature exceeds 40°C, the absolute humidity must not exceed 90% RH at 40°C.
*3
Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this
instruction may cause a malfunction. When the air inside the control panel is purged by pressurization, the surface sheet may be lifted
by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.
*4
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for up to the raged voltage of 300V is 2500V.
*5
This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used. In pollution
degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Item
Specifications
Operating ambient temperature*1
0 to 50°C
Storage ambient temperature
-20 to 60°C
Operating/Storage ambient humidity
10% RH to 90% RH, non-condensing*2
Vibration resistance
Conforms to IEC
61131-2
Frequency
Acceleration
Half amplitude
Sweep Count
Under
intermittent
vibration
5 to 8.4Hz
-
3.5mm
10times each in
X, Y and Z
directions
8.4 to 150Hz
9.8m/s2
-
Under
continuous
vibration
5 to 8.4Hz
-
1.75mm
-
8.4 to 150Hz
4.9m/s2
-
Shock resistance
Conforms to IEC 61131-2 (147m/s2, 3 times each in the X, Y, and Z directions)
Operating atmosphere
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (as well as at storage)
Operating altitude*3
2000m (6562ft) max.
Overvoltage category*4
II or less
Pollution degree*5
2 or less
Cooling method
Self-cooling
Grounding
Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of 2
mm2 or more. If impossible, connect the ground cable to the control panel.
3.2 Performance Specifications
3.2
Performance Specifications
The following shows the performance specifications.
Item
Specifications
GS2110-WTBD-N
GS2107-WTBD-N
GS2110-WTBD
GS2107-WTBD
Display
section*1*2
Type
TFT color liquid crystal
Screen size
10"
7"
10"
7"
Resolution
WVGA: 800 × 480 dots
Display size
W222(8.74) × H132.5(5.22)
[mm] (inch)
W154(6.06) × H85.9(3.38)
[mm] (inch)
W222(8.74) × H132.5(5.22)
[mm] (inch)
W154(6.06) × H85.9(3.38)
[mm] (inch)
Display
character
16-dot standard font: 50 characters × 30 rows (two-byte characters)
12-dot standard font: 66 characters × 40 rows (two-byte characters)
Display color
65536 colors
Brightness
32-level adjustment
Backlight*3
LED-type (no replacement required)
Touch panel*4
Type
Analog-resistive film type
Key size
Minimum 2 × 2 dots *7 (per key)
Number of
points touched
simultaneously
Simultaneous 2-point presses prohibited (Only one point can be touched.)*5
Life
1 million times (operating force 0.98N max.)
Memory
C drive
Flash memory (Internal) (15MB), for storing project data,
OS
Flash memory (Internal) (9MB), for storing project data, OS
Life (Number of write times) 100,000times
Built-in
interface
RS-422/485
RS-422/485, 1ch
Transmission speed: 115200/57600/38400/19200/9600/
4800bps
Connector shape: D-sub 9 pins (Female)
Application: For communicating with controllers
Terminating resistor: 330 Ω, 110 Ω, OPEN (Selectable by
the terminating resistor setting switch.)*9
-
RS-422
-
RS-422, 1ch
Transmission speed: 115200/57600/38400/19200/9600/
4800bps
Connector shape: D-sub 9 pins (Female)
Application: For communicating with controllers
Terminating resistor: 330Ω fixed
RS-232
RS-232, 1ch
Transmission speed: 115200/57600/38400/19200/9600/4800bps
Connector shape: D-sub 9 pins (Male)
Application: For communication with controllers and a bar code reader
For PC connection (Project data read/write, FA transparent function)
Ethernet
Data Transfer method: 100BASE-TX, 10BASE-T, 1ch
Connector shape: RJ-45 (modular jack)
Application: For communication with controllers
For PC connection (Project data read/write, FA transparent function)
USB (Device)
1 channel (rear face)
USB version: USB1.1 (Full-Speed 12 Mbps)
Connector shape: Mini-B
Application: For PC connection (Project data read/write, FA transparent function)
SD card
Conforms to the SD standard, 1ch
Supported memory card: SDHC memory card, SD memory card
Application: Project data read/write, logging data save
Buzzer output
Single tone (LONG/SHORT/OFF adjustable)
Protective structure
IP65F (only the front part of the panel)*6*8
External dimensions
W272(10.71) × H214(8.43)
× D56(2.21) [mm] (inch)
W206(8.11) × H155(6.11) ×
D50(1.97) [mm] (inch)
W272(10.71) × H214(8.43)
× D56(2.21) [mm] (inch)
W206(8.11) × H155(6.11) ×
D50(1.97) [mm] (inch)
Panel cutting dimensions
W258(10.16) × H200(7.88)
[mm] (inch)
W191(7.52) × H137(5.40)
[mm] (inch)
W258(10.16) × H200(7.88)
[mm] (inch)
W191(7.52) × H137(5.40)
[mm] (inch)
Weight (excluding a fitting)
Approx. 1.3 (2.9) [kg] (lb)
Approx. 0.9 (2.0) [kg] (lb)
Approx. 1.3 (2.9) [kg] (lb)
Approx. 0.9 (2.0) [kg] (lb)
3.2 Performance Specifications
29
3
*1
Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is impossible to completely avoid this
symptom, as the liquid crystal display comprises of a great number of display elements. Flickers and partial discoloration may be
generated on the liquid crystal display panel due to individual differences of panels. Please note that these phenomena appear due to its
characteristic and are not caused by product defect.
*2
Flickering may occur due to vibration, shock, or the display colors.
*3
To prevent the display section from burning in and lengthen the backlight life, enable the screen save function and turn off the backlight.
*4
When a stylus is used, the touch panel has a life of 100 thousand touches.
The stylus must satisfy the following specifications.
Material: Polyacetal resin
Tip radius: 0.8mm or more
*5
If you touch two points or more simultaneously on the touch panel, a touch switch near the touched points may operate unexpectedly.
Do not press two or more areas simultaneously on the touch panel.
*6
Note that this does not guarantee all users' operation environment.
The GOT may not be used in an environment where the GOT is exposed to oil or chemicals for a long time, or where oil mist fills the air.
*7
Minimum size of a key that can be arranged.
To ensure safe use of the product, the following settings are recommended.
Key size: 16 × 16 dots or larger
Distance between keys: 16 dots or more
*8
The suffix "F" of "IP65F" is a symbol that indicates protection rate against oil. It is described in the Appendix of Japanese Industrial
Standard JIS C 0920.
*9
For the GOT multi-drop connection, set the terminating resistor setting switch of the GOT according to the connection type.
For details on the GOT multi-drop connection, refer to the following.
GOT2000 Series Connection Manual (Mitsubishi Electric Products) For GT Works3 Version1
Compatible software package
(Version of GT Designer3)
Version 1.250L or later
Version 1.105K or later
Item
Specifications
GS2110-WTBD-N
GS2107-WTBD-N
GS2110-WTBD
GS2107-WTBD
3.3 Power Supply Specifications
3.3
Power Supply Specifications
Operation at momentary power failure
The GOT continues to operate even upon 5ms or shorter instantaneous power failure.
The GOT stops operating if there is extended power failure or voltage drop, while it automatically resumes
operation as soon as the power is restored.
Item
Specifications
GS2110-WTBD-N
GS2107-WTBD-N
GS2110-WTBD
GS2107-WTBD
Input power supply voltage
24VDC (+10% -15%), ripple voltage 200mV or less
Power consumption
7.6W (317mA/24V) or less
6.5W (271mA/24V) or less
7.6W (317mA/24V) or less
6.5W (271mA/24V) or less
Power consumption (At
backlight off)
3.8W (158mA/24V) or less
3.8W (158mA/24V) or less
3.8W (158mA/24V) or less
3.8W (158mA/24V) or less
Inrush current
17A or less (6ms, 25°C, at the maximum load)
Permissible instantaneous
power failure time
Within 5ms
Noise immunity
Conforms to IEC61000-4-4, 2kV (power supply line)
Dielectric withstand voltage
350VAC for 1 minute (across power supply terminals and earth)
Insulation resistance
500VDC across power terminals and earth, 10 MΩ or more by an insulation resistance tester
3.4 GOT Connector Specifications
31
3
3.4
GOT Connector Specifications
The following shows the specifications of connectors for the GOT.
Refer to this section for creating a connection cable by the user.
RS-232 interface
The following shows the connector for the RS-232 interface of the GOT.
For the connection cable connector of the GOT side, use a connector and a connector cover which can be connected to the
GOT connector.
Connector specifications
Connector pin arrangement
RS-422 interface and RS-422/485 interface
The following shows the connector for the RS-422 interface and RS-422/485 interface of the GOT.
For the connection cable connector of the GOT side, use a connector and a connector cover which can be connected to the
GOT connector.
Connector specifications
Connector pin arrangement
GOT
Connector type
Connector model
Manufacturer
GS series
D-sub 9 pins (Male)
Inch screw type
17LE-23090-27(D3CC)
DDK Ltd.
GOT
Connector type
Connector model
Manufacturer
GS series
D-sub 9 pins (Female)
M2.6 mm screw type
17LE-13090-27(D3AC)
DDK Ltd.
D-Sub 9pin male
GOT main part connector
see from the front
1
5
6
9
D-Sub 9pin female
GOT main part connector
see from the front
5
1
9
6
4 PART NAME
4.1 Front Panel
33
4
4
PART NAME
4.1
Front Panel
No.
Name
Specifications
(1)
Display section
Displays the utility screen and the user creation screen.
(2)
Touch panel
For operating the touch switches in the utility screen and the user creation screen
(1)(2)
4 PART NAME
4.2 Back Panel
4.2
Back Panel
GS21-W-N
• GS2110-WTBD-N
• GS2107-WTBD-N
For the names of parts, refer to the following.
Page 36 Parts names of the back panel
(8) (13)
(11)
(7)
(5)
(10)
(9)
(2)
(1)
(4)
(12)
(6)
(8)
(9)
(10)
(6)
(2)
(5)
(1)
(4)
(12)
(13)
(11)
(7)
4 PART NAME
4.2 Back Panel
35
4
GS21-W
• GS2110-WTBD
• GS2107-WTBD
For the names of parts, refer to the following.
Page 36 Parts names of the back panel
(8)
(11)
(13)
(5)
(10)
(9)
(3)
(1)
(4)
(12)
(6)
(8)
(9)
(10)
(6)
(3)
(5)
(1)
(4)
(12)
(13)
(11)
4 PART NAME
4.2 Back Panel
Parts names of the back panel
No.
Name
Specifications
(1)
RS-232 interface
For communicating with controller (PLC, microcomputer board, RFID, etc) or personal
computer (OS installation, project data download, FA transparent) (D-sub 9-pin male)
(2)
RS-422/485 interface
For communicating with controller (PLC, microcomputer board, etc) (D-sub 9-pin female)
(3)
RS-422 interface
For communicating with controller (PLC, microcomputer board, etc) (D-sub 9-pin female)
(4)
Ethernet interface
For Ethernet communication with controller (PLC, microcomputer board, etc) (RJ-45
connector)
(5)
USB interface (Device)
USB interface for data transfer and saving
(6)
Hole for preventing the USB cable from unplugging
Hole for preventing the USB cable from unplugging with a banding band
(7)
Terminating resistor setting switch
For switching the terminating resistor setting of the RS-422/485 communication port to
330 Ω, 110 Ω, or OPEN
(8)
Rating plate
Model name, current consumption, production number, hardware version, and Boot OS
version are described.
(9)
SD card interface
Interface for mounting an SD card to the GOT
(10)
SD card access LED
ON: SD card is accessed, OFF: SD card is not accessed
(11)
Vertical installation arrow mark
For the vertical installation, install the GOT so that the arrow points upward.
(12)
Power terminal
Power terminal and FG terminal (for power supply (24VDC) to GOT and grounding)
(13)
Ethernet communication status LED
SD RD: Green light while data are being sent or received, 100M: Green light when the
transmission speed is 100Mbps
4 PART NAME
4.3 Bottom
37
4
4.3
Bottom
GS21-W-N
• GS2110-WTBD-N
• GS2107-WTBD-N
For the names of parts, refer to the following.
Page 37 Parts names of the bottom
GS21-W
• GS2110-WTBD
• GS2107-WTBD
For the names of parts, refer to the following.
Page 37 Parts names of the bottom
Parts names of the bottom
No.
Name
Specifications
(1)
Hole for unit installation fittings
Hole for the inserting installation fittings (accessory) during the GOT installation to the
panel (4 holes at top and bottom)
(1)
(1)
(1)
(1)
5 EMC DIRECTIVE
5.1 Overview
39
5
5
EMC DIRECTIVE
5.1
Overview
For the products sold in European countries, the conformance to the EMC Directive, which is one of the European Directives,
has been a legal obligation since 1996.
Manufacturers, who recognize that their products comply with the EMC Directive must declare that their products comply with
the Directives and put a CE mark on the products.
Sales representative in Europe
The sales representative in Europe is as shown below.
Company name: Mitsubishi Electric Europe BV
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
Conforming standards in the EMC Directive
The GOT complies with the following standards in the EMC Directive.
*1
The GOT is an open type device (designed to be integrated in equipment).
Make sure to install the GOT on a control panel.
This test item is conducted in the condition where the GOT is installed on a control panel and combined with the MITSUBISHI PLC.
*2
QP: Quasi-peak value, Mean: Average value
*3
This test item is conducted in the following conditions.
· 30 MHz to 230 MHz
QP: 40 dBμV/m (measured at 10 m)
· 230MHz to 1000MHz
QP: 47 dBμV/m (measured at 10 m)
Applied
standard
Test standard
Test details
Standard value
EN61131-2: 2007
CISPR16-2-3
Radiated noise*1
Test for measuring electromagnetic emissions
from the product
• 30 MHz to 230 MHz
QP: 30 dBμV/m (measured at 30m)*2*3
• · 230MHz to 1000MHz
QP: 37 dBμV/m (measured at 30m)*2*3
IEC61000-4-2
Electrostatic immunity*1
Immunity test in which static electricity is
applied to the cabinet of the equipment
• Contact discharge: ±4 kV
• Aerial discharge: ±8kV
IEC61000-4-3
Radiated electromagnetic field,
amplitude modulation*1
Immunity test in which an electric field is applied
to the product
80 MHz to 1000 MHz: 10 V/m
1.4GHz to 2GHz: 3V/m
2.0GHz to 2.7GHz: 1V/m
(80% amplitude modulation at 1 kHz)
IEC61000-4-4
Fast transient burst noise*1
Immunity test in which burst noise is applied to
the power cables and the signal lines
Power cable: 2 kV
Digital I/O: 1 kV
Analog I/O: 1 kV
Signal cable: 1 kV
IEC61000-4-5
Surge immunity*1
Immunity test in which lightening surge is
applied to the product
• DC power type
Power cable (between cable and ground): ±0.5 kV
Power cable (between cables): ±0.5 kV
Data communication port: ±1kV
IEC61000-4-6
Conducted RF immunity*1
Immunity test in which a noise inducted on the
power cable and the signal lines is applied
Power cable: 10V
Data communication port: 10V
IEC61000-4-8
Power supply frequency magnetic
field immunity
Test for checking normal operations under the
circumstance exposed to the ferromagnetic field
noise of the power supply frequency (50/60 Hz)
30 A/m
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
5.2
EMC Directive Requirements
The EMC Directive requires the following.
• Strong electromagnetic waves are not emitted to the outside.: Emission (Electromagnetic interference)
• The product is not affected by the electromagnetic waves from the outside.: Immunity (Electromagnetic sensitivity)
To comply with the EMC Directive, this section explains the precautions for configuring equipment integrating the GOT.
The data described herein are produced with our best, based on the regulation requirements and standards obtained by
Mitsubishi. However, the data do not guarantee that the whole equipment produced according to the data comply with the
above directive.
The manufacturer of the equipment must determine the method to comply with the EMC Directive and conformance to the
directive.
Installing the GOT on the control panel
The GOT is an open type device (designed to be integrated in equipment).
Make sure to install the GOT in a control panel.
This restriction ensures safety and also has a large effect of suppressing noise generated from the GOT by using the control
panel.
Control panel
• The control panel must be conductive.
• When fixing a top or bottom plate of the control panel with bolts, do not coat the plate and bolt surfaces so that they contact
each other. Connect the door and the box using a thick grounding cable to ensure the low impedance under high frequency.
• To ensure electric conductivity in the large area as much as possible between an inner plate and the control panel, do not
coat the fixing bolt area of the inner plate and the control panel.
• Ground the control panel using a thick grounding cable to ensure the low impedance under high frequency.
• The diameter of cable holes on the control panel must be 10 cm or less. If the diameter of the hole is 10 cm or more, radio
waves may leak. To reduce the chance of radio waves leaking out, ensure that the space between the control panel and its
door is as small as possible. Pasting the following EMI gasket directly on the painted surface seals the space, reducing the
leak of electric waves.
Our test has been carried out on a panel having the damping characteristics of 37 dB max. and 30 dB mean (measured by 3m
method with 30 to 300 MHz).
Connection of power and ground cables
Ground the GOT and connect power supply cables as shown below.
■Wiring the ground cable
Provide a ground point near the GOT.
Ground the frame ground terminal (FG terminal) of the GOT with the thickest and shortest cable as possible.
■Ground cable length
The ground cable length must be 30 cm or shorter.
The FG terminals pass the noise generated in the PLC system to the ground.
Therefore, ensure an impedance as low as possible.
Since the ground cables relieve the noise, the cables themselves carry a large noise.
Thus, short wiring prevents the cable from acting as an antenna.
(A long conductor is an antenna radiating noise more efficiently.)
Manufacturer
Series name
Contact
KITAGAWA INDUSTRIES CO., LTD.
RFSG series (Recommended Product)
+81-587-34-3651
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
41
5
■Treatment of the power cable and the ground cable
Twist the ground cable led from the ground point with the power cable.
Twisting with the ground cable relieves more noise from the power cable to the ground.
When a noise filter is installed to the power cable, twisting the power cable and the ground cable may not be required.
Installing a noise filter (power supply line filter)
A noise filter is a part to effectively reduce conducted noise.
Except some models, installation of a noise filter to the power supply lines is not necessary. However, installing the noise filter
can reduce conducted noise.
The noise filter is effective to reduce conducted noise in the band of 10 MHz or less.
Use a noise filter equivalent to the following noise filters (double π-type filters).
Precautions
The following shows the precautions for installing a noise filter.
■Prohibition of bundling cables
Do not bundle the input and output cables of the noise filter.
Bundling the cables inducts the noise from the output-side cable into the input-side cable where noise has been eliminated by
the noise filter.
■Grounding the noise filter
Connect the ground terminal of the noise filter to the control panel with a short cable as much as possible (approximately 10
cm).
Model
Manufacturer
Rated current
Rated voltage
FN343-3/05
SCHAFFNER
3A
250V
FN660-6/06
SCHAFFNER
6A
RSHN-2003
TDK
3A
Input side
(power supply side)
Output side
(device side)
Filter
Wire the input and output cables separately.
Filter
Input side
(power supply side)
Induction
Output side
(device side)
Bundling the input and output cables inducts noise.
Bundling
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
System configuration
GOT
Use the following GOTs having a CE mark on the rating plate.
The following models are compliant with the EMC Directive at factory shipment.
When any GOT other than the following does not comply with the EMC Directive.
Connection type
The following table lists the connection types compliant with the EMC Directive.
○: Compliant with EMC Directive, ×: Not compliant with EMC Directive
*1
For the details of each connection type, refer to the following manual.
GOT2000 Series Connection Manual (GT Works3 Version1) for the controller used
*2
When connecting the GOT to other controllers such as a non-Mitsubishi PLC, fabricate connection cables and configure the system
following the EMC Directive specifications.
Page 44 Non-Mitsubishi PLC, inverter, and servo amplifier connections
Connected devices
When connecting the GOT to a non-Mitsubishi PLC, refer to the manual about the EMC Directive compliance
of the connected device (such as a PLC and a microcomputer).
Connection of power cables and ground cables
Carry out wiring and connect the power and ground cables according to the following instruction.
By the different wiring or connection method, the system may not comply with EMC Directive.
Wiring method
For connection of power cables and ground cables, refer to the following.
Ground the frame ground terminal (FG terminal) of the GOT with the thickest and shortest cable as possible.
Page 58 Wiring Inside and Outside the Panel
Product name
Model
GS2110
GS2110-WTBD-N
GS2110-WTBD
GS2107
GS2107-WTBD-N
GS2107-WTBD
Connection type*1
GS21
Ethernet connection
○
Direct CPU connection
○
Computer link connection
○
Other connections
(Connection with non-Mitsubishi PLC, inverter, servo amplifier)
○*2
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
43
5
Fabricating a connection cable
Fabricate the cables used for the GOT by the methods as shown in this section.
The fabrication requires a ferrite core, cable clamp, and cable shielding materials.
The following products have passed the Mitsubishi EMC Directive compliance test.
• ZCAT3035-1330 ferrite core (TDK Corporation)
• AD75CK-type cable clamp (Mitsubishi Electric Corporation)
Ethernet connection
■Ethernet cable
Strip off the sheath at both ends of the cable as shown in the figure below to expose braided shield for grounding. The braided
shield sections are used for grounding with a cable clamp.
Page 46 Grounding a cable
• Connecting to the Ethernet interface of the GOT
Direct CPU connection
■RS-232 cable and RS-422 cable
Install a ferrite core to the cable in the positions as shown in the figure below.
Personal computer side
GOT side
230or less
40
40
400or less
(9.06)
(1.57)
(1.57)
(9.06)
Unit: mm (inch)
Ferrite core
(ZCAT3035-1330)
120
or less
(4.72)
120
or less
(4.72)
PLC side
GOT s ide
230 or less
40
40
400 or less
(9.06)
(1.57)
(1.57)
(9.06)
Unit: mm (inch)
Ferrite core
(ZCAT3035-1330)
Finishing of wearing
120 or less
(4.72)
120
or less
(4.72)
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
Computer link connection
■RS-232 cable and RS-422 cable
Strip off the sheath at both ends of the cable as shown in the figure below to expose braided shield sections for grounding.
The braided shield sections are used for grounding with a cable clamp.
Page 46 Grounding a cable
Non-Mitsubishi PLC, inverter, and servo amplifier connections
Create the cables (RS-232 cable, RS-422/485 cable) for connecting the GOT and a controller by yourself.
For how to create a cable, refer to the following.
GOT2000 Series Connection Manual For GT Works3 Version1
100 or less
Ferrite core
(ZCAT3035-1330)
100 or less
(3.94)
230 or less
40
40
(9.06)
(1.58)
(1.58)
230 or less
(9.06)
(3.94)
GOT side
PLC CPU side
Unit: mm (inch)
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
45
5
Treatment of the RS-232 cable and RS-422/485 cable
When the GOT is connected to a controller, configure the system according to the EMC Directive
specifications for the controller.
The following shows the recommended instructions to comply with the EMC Directive.
However, the manufacturer of the equipment must determine the method to comply with the EMC Directive
and conformance to the directive.
• RS-422/485 cable
When connecting each signal wire (except SG and FG wires), twist two signal wires as shown below.
Connect two or more SG wires.
• RS-232 cable
Twist each signal wire (except SG and FG wires) with the SG wire.
Install a ferrite core to the cable in the positions as shown in the figure below.
Strip off the sheath at the both ends of the cable as shown in the figure below to expose braided shield for
grounding. The braided shield sections are used for grounding with a cable clamp.
SDA
RDA
RDB
SDB
RDA
RDB
SDA
SDB
RD
RD
SD
SD
DTR
DTR
DSR
DSR
SG
SG
100 or less
Ferrite core
(ZCAT3035-1330)
100 or less
(3.94)
230 or less
40
40
(9.06)
(1.58)
(1.58)
230 or less
(9.06)
(3.94)
GOT side
PLC CPU side
Unit: mm (inch)
5 EMC DIRECTIVE
5.2 EMC Directive Requirements
Grounding a cable
Grounding method
Ground the cable and ground cable to the control panel where the GOT and the PLC are installed.
Ground the braided shield section of the cable to the control panel with the cable clamp (AD75CK).
Precautions
Do not arrange the cable clamp close to the other cables that are not clamped.
The noise from the control panel may enter the cable clamp and adversely affect the GOT.
Braided shield
Cable clamps
For the attachment details of
cable clamps, refer to
AD75CK-type Cable Clamping
Instruction Manual
.
6.1 Control Panel Inside Dimensions for Mounting GOT
47
6
6
INSTALLATION
6.1
Control Panel Inside Dimensions for Mounting
GOT
Mount the GOT onto the control panel while considering the following control panel inside dimensions.
For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward.
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to the GOT. Therefore,
consider the connector dimensions and bending radius of the cable as well for installation.
MOUNTING PRECAUTIONS
WARNING
• Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT
main unit to/from the controller.
Not doing so can cause the unit to fail or malfunction.
MOUNTING PRECAUTIONS
CAUTION
•
•
•
•
• Tighten the mounting screws within the specified torque range.
Undertightening can cause the GOT to drop, short circuit or malfunction. In addition, undertightening can disable
waterproof or oil proof effect.
Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the GOT. In addition,
the waterproof effect and oilproof effect may not be available due to the "distortion" of GOT or panel.
Operate and store the GOT in environments without direct sunlight, dust, lamp black, conductive dust, corrosive gas,
combustible gas, high temperature, condensation, wind, rain, vibrations and impacts.
Electric shock, fire, malfunction, product damage or deterioration can be caused.
Connect connection cables securely to the specified connectors while the power is turned OFF.
Imperfect connection may cause malfunction or failure.
Never drop cutting chips and electric wire chips into the ventilation window of the GOT when you drill screw holes or
perform wiring.
Otherwise, fire, failure or malfunction may be caused.
Use the GOT in the environment that satisfies the general specifications described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
Unit: mm(inch)
30(1.18)
6.2 Panel Cutting Dimensions
6.2
Panel Cutting Dimensions
Cut holes in the following dimensions on the panel.
Ensure 10mm of space in upper and lower parts of the panel for mounting fixtures.
For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward.
Unit: mm (inch)
The C dimension shows the measurements for installing fittings on the control panel.
Model
A
B
C
Panel thickness
GS2110-WTBD-N
GS2110-WTBD
258(10.16")
(+2(0.08), 0(0))
200(7.88")
(+2(0.08), 0(0))
10(0.39") or more
1.6(0.06") to 4(0.16")
GS2107-WTBD-N
GS2107-WTBD
191(7.52")
(+2(0.08), 0(0))
137(5.40")
(+2(0.08), 0(0))
10(0.39") or more
1.6(0.06") to 4(0.16")
A
C
C
B
A
C
C
B
Horizontal
Vertical
6.3 Mounting Position
49
6
6.3
Mounting Position
When mounting the GOT, the following clearances must be maintained from other structures and devices.
For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward.
Horizontal installation
Vertical installation
Installation Environment
A, D [mm] (inch)
B [mm] (inch)
C [mm] (inch)
E [mm] (inch)
In the presence of radiated-noise or heat-
generating equipment nearby
50mm (1.97") or more
Horizontal: 80mm (3.14")
or more
Vertical: 50mm (1.97") or
more
Horizontal: 50mm (3.14")
or more
Vertical: 80mm (3.14") or
more
100mm (3.94") or
more
In the absence of radiated-noise or heat-
generating equipment nearby
20mm (0.79") or more
20mm (0.79") or more
20mm (0.79") or more
20mm (0.79") or more
C
D
E
Panel thickness: 1.6 to 4mm
(0.06" to 0.16")
B
A
B
A
C
D
E
Panel thickness: 1.6 to 4mm
(0.06" to 0.16")
6.4 Control Panel Temperature and Mounting Angle
6.4
Control Panel Temperature and Mounting Angle
When mounting the main unit to a control panel or similar fixture, set the GOT display section as shown below.
Horizontal installation
When the temperature inside the control panel is 40 to 50°C, the mounting angle should be in the range from 60 to 105
degrees.
The GOT will have a longer lifetime if used within the mounting angles shown above.
Ideally, the temperature inside the control panel should not exceed 0 to 40°C.
Vertical installation
When the temperature inside the control panel is 40 to 50°C, the mounting angle should be in the range from 60 to 105
degrees.
The GOT will have a longer lifetime if used within the mounting angles shown above.
Ideally, the temperature inside the control panel should not exceed 0 to 40°C.
GOT
back panel
GOT
display
section
Control panel,
etc.
105°
60°
GOT
back panel
GOT
display
section
Control panel,
etc.
105°
60°
6.5 Installation Procedure
51
6
6.5
Installation Procedure
The GOT is designed to be embedded into a panel. Mount the GOT by following the procedure below.
Refer to Page 48 Panel Cutting Dimensions for the panel cutting dimensions.
In addition, the thickness of the installation panel face must be 1.6 to 4mm.
Check that the packing is firmly attached with the GOT.
If the packing is loose, attach the packing to the GOT securely.
1.
Inserting into the panel face
Insert the GOT from the front side of the panel.
2.
Fixing the GOT
Engage the hook of the mounting fixture (accessory) to the unit fixing hole of the
GOT and fix them by tightening the mounting screws (accessory) in the torque
range of 0.36 to 0.48N·m.
3.
A protection film is attached on the display section of GOT prior to shipment.
Remove the film when the installation is completed.
Mounting hole
Mounting
fitting
Mounting
screw
6.5 Installation Procedure
Cautions on installation
• Tightening the mounting screw
Tighten the mounting screw within the specified torque.
Under tightening can cause the GOT to drop. In addition, undertightening can disable waterproof or oil proof
effect.
Failure to do so may damage the unit, or distort the panel and make a surface waviness on the display area,
leading to deterioration of the visibility or incorrect input from the touch panel. In addition, undertightening can
disable waterproof or oil proof effect.
Specified torque range: 0.36 to 0.48N·m
• Installation panel surface
Make sure that the panel surface is free from warpage, flaws and irregularities. Warpage, flaws and
irregularities may disable the waterproof effect.
Select proper panel thickness under consideration of the panel strength.
(For example, the panel strength may be insufficient depending on the panel material and dimensions even if
the panel thickness is acceptable.
Insufficient panel strength may cause warpage depending on the installation positions of the GOT and other
equipment.)
This chapter describes the wiring to the GOT power supply section.
For the connection with a PLC, refer to the following.
GOT2000 Series Connection Manual For GT Works3 Version1
For the dimensional drawing of connection cables, refer to the following.
Page 297 External Dimensions
General preventive measures against noise
There are two kinds of noises: Radiated noise that is transmitted into the air and Conductive noise that is
directly transmitted along connected lines. Countermeasures must be taken considering both kinds of noises
and referring to the following 3 points.
• Protecting against noise
Keep signal lines away from noise sources such as a power cable or a high-power drive circuit.
Shield the signal lines.
• Reducing generated noise
Use a noise filter, etc. to reduce the level of the noise generated due to a source such as a high-power motor
drive circuit.
Attach surge killers to the terminals on the no fuse breakers (NFB), electromagnetic contactors, relays,
solenoid valves, and generators to suppress noise interference.
• Releasing noise to the ground
Make sure to connect the ground cable to the ground.
Use a short and thick cable to lower its ground resistance.
Ground the power system and the control system separately.
Be sure to shut off all phases of the external power supply used by the system before wiring.
Failure to do so may result in an electric shock, product damage or malfunctions.
Please make sure to ground FG terminal of the GOT power supply section by applying 100Ω or less which is used
exclusively for the GOT.
Not doing so may cause an electric shock or malfunction.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the
product.
Not doing so can cause a fire or failure.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT.
Not doing so can cause a fire, failure or malfunction.
Tighten the terminal screws of the GOT power supply section in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
WARNING
WIRING PRECAUTIONS
•
•
•
•
•
Plug the communication cable into the connector to be connected, and tighten the mounting screws and the terminal
screws in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
CAUTION
WIRING PRECAUTIONS
•
7.1 Power Supply Wiring
7.1
Power Supply Wiring
Connect the power supply to the power terminals on the back panel of the GOT.
Use a specified size power supply wire to prevent voltage drop, and tighten the terminal screws firmly to a specified torque.
Do not exceed the number of wires that are allowed to be connected.
Secure the wires to prevent stress from being directly applied to the terminal block or wire connections.
Cable types and wire end processing
Process the end of the electrical wire (solid or stranded), or attach a ferrules with plastic sleeve to the wire end.
Terminal screws should be tightened to between 0.3 to 0.5N·m. Terminal screws must be secured to prevent a loose
connection thus avoiding a malfunction.
When tightening terminal screws, do not exceed the specified torque. Failure to do so may cause equipment failures or
malfunctions.
Electrical wire size
Wire end processing
■Connecting the wire directly
Twist the end of the stranded wire. Make sure there are no wire whiskers.
Do not solder the wire end.
■Using a ferrules with plastic sleeve to connect the wire
A wire with a too thick of a wire sheath may not fit the insulation sleeve. Refer to the outline drawing for how to select the
proper size wire.
Electrical wire size
Solid wire
Stranded wire
Ferrules with plastic sleeve
0.5 to 2.5mm2
AWG20 to AWG14
0.5 to 2.5mm2
AWG20 to AWG14
0.5 to 2.5mm2
AWG20 to AWG14
Manufacturer
Model
Crimper type
Phoenix Contact Inc.
AI 0.75-8BU (0.5 to 0.75mm2)
CRIMPFOX UD6
AI 1.0-8RD (0.75 to 1.0mm2)
AI 1.5-8BK (1.0 to 1.5mm2)
AI 2.5-8BU (1.5 to 2.5mm2)
Approx. 6mm
8 to 12mm
14 to 18mm
2.8 to 4.2mm
Terminal
contact
section
Insulation sleeve
7.1 Power Supply Wiring
55
7
Tools
Use a small driver with a straight, untapered blade as shown below to tighten the power terminals.
Wiring example
Connect the power supply to the power terminals on the back panel of the GOT.
Tightening torque for the power terminals: 0.5 to 0.6N·m
GOT's ground
Grounding the GOT and other devices
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible. Provide class D (class 3) grounding. (Ground resistance must be 100Ω or
less.)
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
• Use the cable of 2mm2 or longer for grounding. Set the grounding point closer to the GOT to make the grounding cable
short as possible.
Manufacturer
Model
Phoenix Contact Inc.
SZS 0.6
3.5
0.6mm
3.5mm
Use a driver
with a flat end
Class D
grounding
DC24V +10%
- 15%
Other
device
GOT
Other
device
GOT
Other
device
GOT
(1) Independent ground
...... Best condition
(2) Shared grounding
...... Good condition
(3) Common grounding
...... Not allowed
Grounding
(100Ω or less)
Grounding
(100Ω or less)
7.1 Power Supply Wiring
The cause of malfunctions related wiring/Remedy
Grounding of the GOT may cause electric potential difference and noise interference, which may result in GOT malfunctions.
These problems may be resolved by taking the following measures.
Wiring path of the GOT's ground cable and power line
Bundling the GOT's ground cable and power line together can cause interference noise, which may result in malfunctions.
Keeping the GOT's ground cable and power line away from each other will help minimize noise interference.
Connecting the ground cable from the panel that houses control equipment to the
panel to which the GOT is grounded
When running a single ground cable from the panel that houses such piece of control equipment as a sequencer to the panel
to which the GOT is grounded, the ground cable may have to be directly connected to the terminal on the GOT.
If electric potential difference between the ground points created by it causes malfunctions, lowering the voltage as shown in
Remedy 1 below may solve the problem.
FG
Power supply
for power equipment
Power supply
for power equipment
Good: Wiring the ground cable away
from the power cable
FG
Bad: Bundling the ground cable and
the power cable
FG
Ground cable from
the panel that houses
control equipment
Connection cable
7.1 Power Supply Wiring
57
7
• Remedy 1 (Refer to the figures Remedy 1-1 and 1-2 below.)
If the electric potential difference between the ground cable and the panel that houses the GOT is creating problems, connect
the ground cable to the panel also. If the wiring method as shown in Remedy 1-1 is not feasible, follow Remedy 1-2.
If taking Remedy 1 worsens noise interference, taking Remedy 2 may alleviate it.
• Remedy 2 (Refer to the figures Remedy 2-1 and 2-2 below.)
Attach a ferrite core to the cable if noise from the GOT panel has adverse effects on the GOT when Remedy 1 is taken. Wind
the wire around the ferrite core several times (approx. 3times), if a ferrite core is used. If the wiring method as shown in
Remedy 2-1 is not feasible, follow Remedy 2-2.
FG
Ground cable from
the panel that houses
control equipment
Connection cable
Panel
grounding
Panel
grounding
Remedy1-1
Use the thickest
cable possible.
FG
Connection cable
Remedy1-2
Ground cable from
the panel that houses
control equipment
Use the thickest
cable possible.
Ground cable from
the panel that houses
control equipment
Connection cable
Remedy2-1
Use the thickest
cable possible.
Ground cable from
the panel that houses
control equipment
Use the thickest
cable possible.
FG
Connection cable
Remedy2-2
FG
Panel
grounding
Panel
grounding
Ferrite core
Ferrite core
7.2 Wiring Inside and Outside the Panel
7.2
Wiring Inside and Outside the Panel
Wiring inside
Run power lines, servo amplifier drive wires, and communication cables so that they do not cross each other.
Noise interference that is generated by cables that cross each other may cause malfunctions.
Surge suppressors are an effective way to filter out surge noise that is generated from no fuse breakers (NFB),
electromagnetic contactors (MC), relays (RA), solenoid valves, and induction motors.
Refer to the section to follow for surge killers.
Page 59 Attaching surge killers to control equipment
Outside the panel
To pull the power line and communication cable out of the panel, make two pullout holes away from each other and pull the
cables through.
Putting both cables through the same pullout hole will increase noise interference.
Keep the power line and communication cable inside the duct at least 100mm away from each other.
If that is not possible, the use of a metal separator inside the duct can reduce noise interference.
NFB
MC
PLC
MC
RA
RA
Terminal block
Crossing power lines and
communication cables
GOT connection cable
PLC I/O wire
Drive control wire
NFB
MC
PLC
MC
RA
RA
Terminal block
Uncrossed power lines and
communication cables
GOT connection cable
PLC I/O wire
Drive control wire
Power
cable
Power
cable
Power line
Connection
cable
Pullout hole
Pullout hole
Connection
cable
Power line
100mm or more
Separator
Signal line
Power line
Power line
Wiring duct
Signal line
7.2 Wiring Inside and Outside the Panel
59
7
Attaching surge killers to control equipment
If communication errors happen in synch with the on/off signals from certain control equipment (referred to as "load" hereafter)
such as no fuse breakers, electromagnetic contactors, relays, solenoid valves, and induction motors, surge noise interference
is suspected.
If this problem happens, keep the ground cable and communication cable away from the load.
If that is not possible, an installation of a surge killer will help reduce noise interference.
Place the surge killer as close to the load as possible.
Remedy for AC inductive load
Remedy for DC inductive load
Output
AC
C
R
L: Load
Keep the ground cable and
communication cable away
from each other.
Place the surge killer
near the load.
Output equipment
such as PLC output unit
Output
DC
D
L: Load
Keep the ground cable and
communication cable away
from each other.
Place the surge killer
near the load.
Output equipment
such as PLC output unit
8.1 SD Card
61
8
8
OPTION
8.1
SD Card
The SD card is used to transfer the OS or project data and to save the data of the alarm history function.
For details, refer to the following.
Page 159 CONTROL OF VARIOUS DATA (DATA CONTROL)
Applicable SD card
The following SD cards are applicable for GOT.
Installation/removal procedure of SD card
Install/remove the SD card when the power supply of the GOT is OFF or [Access inhibit] is set in the [SD card access] setting
of the GOT.
Installation
Model
Specifications
L1MEM-2GBSD
SD memory card 2GB
L1MEM-4GBSD
SDHC memory card 4GB
NZ1MEM-2GBSD
SDHC memory card 2GB
NZ1MEM-4GBSD
SDHC memory card 4GB
NZ1MEM-8GBSD
SDHC memory card 8GB
NZ1MEM-16GBSD
SDHC memory card 16GB
1.
Touch [Main Menu]
[Data]
[SD card access]
[Permissions] to set [Access inhibit].
Page 190 SD Card Access
Check that the SD card access LED turns off.
When the SD card access LED is off, the SD card can be
installed or removed even when the GOT is on.
2.
Insert a SD card into the SD card interface with its front
side (nameplate side) outside.
3.
Touch [SD card access]
[Access inhibit] to set
[Permissions]. Check that the SD card access LED
turns on.
SD card
surface
8.1 SD Card
Removal
Precautions when removing the SD card
• Do not pull out the SD card or power OFF the GOT while the SD card access LED is lit. To do so may cause
data corruption or malfunction.
• When removing the SD card from the GOT, make sure to support the SD card by hand as it may pop out.
Failure to do so may cause the SD card to drop from the GOT, resulting in a failure or break.
1.
Touch [Main Menu]
[Data]
[SD card access]
[Permissions] to set [Access inhibit].
Page 190 SD Card Access
Check that the SD card access LED turns off.
When the SD card access LED is off, the SD card can be
installed or removed even when the GOT is on.
2.
Push the SD card all the way inside and leave your
finger once, then remove the SD card.
9 UTILITY FUNCTION
9.1 Utility Execution
63
9
9
UTILITY FUNCTION
Utility is a function, which carries out connection of GOT and controller, screen display and operation method settings,
program/data control and self-check etc.
9.1
Utility Execution
For utility execution, utility has to be displayed by installing Boot OS and package data in the C drive (built in flash memory).
There are following two methods for installing Boot OS and package data.
Refer to the following for the installation which uses GT Designer3.
GT Designer3 (GOT2000) Screen Design Manual
For the installation methods of package data with an SD card, refer to the following.
Page 273 BootOS and System Application Installation Using Data Storage
Install directly
from GT Designer3
Via a USB interface or
Ethernet interface
GT Designer3
GT Designer3
Writing
package data
2) GT Designer3→SD card→GOT
GOT
GOT
Installing
package data
Installing Boot OS or Package data
When GOT is remote,
install using SD card
easily
Install SD
card to
the GOT
SD card
1) GT Designer3→GOT
9 UTILITY FUNCTION
9.2 Utility Function List
9.2
Utility Function List
The items in the following list can be set/operated on the utility screens.
Item
Functions overview
Reference
Language
Switching message languages
Page 73 LANGUAGE
SETTING (LANGUAGE)
Comm. Setting
Standard I/F
Assigning channel number and communication driver to communication
interface
Page 75 Standard I/F
Setting
GOT IP Address
Configuring GOT Ethernet setting
Page 84 GOT IP
Address Setting
Ethernet communication
Displaying the contents of Ethernet setting, changing the host
Page 86 Ethernet
Communication
Comm. Monitor
Checking the serial communication port communication
Page 90
Communication Monitor
Ethernet check
Checking the Ethernet communication port communication
Page 93 Ethernet
Check
Transparent mode
Setting the channel No. to be used for the communication for the FA
transparent function
Page 95 Setting the
Transparent Mode
Keyword
Setting or deleting sequence program protection key words and canceling
sequence program protection status for the FXCPU connection
Page 96 Keyword
GOT setup
Display
Setting the title display period
Page 105 Display
Settings
Setting the screen save time
Adjusting brightness
Operation
Setting the buzzer sound
Page 108 Operation
Setting (Settings for
Operation)
Setting the window move buzzer
Setting the key reaction speed
Touch panel calibration
Setting the utility call keys
Unique info
Setting the GOT ID No.
Page 115 Inherent
Information
GOT internal device monitor
Setting the Use/Disuse the GOT internal device monitor of GOT
diagnostics
Page 116 GOT internal
device monitor
VNC server function
VNC server function setting (GS21-W-N)
Page 118 VNC Server
Function
License management
Displaying the screen for registering and canceling a license (GS21-W-N)
Page 120 License
Management
IP filter setting
Setting the IP filter usage, filtering method, target IP address, and
exception IP address
Page 122 IP Filter
Setting
Security
Setting
Security level
Changing the security level
Page 129 Security
Level Authentication
Operator
Operator management
Page 131 Operator
Authentication
Password change
Function setting
Login/Logout
-
Page 145 Login/Logout
Time setting
Time setting
Page 147 Time Setting
and Display
9 UTILITY FUNCTION
9.2 Utility Function List
65
9
Data
OS information
OS information
Page 163 OS
information
Resource Data
Alarm info.
Converting alarm log files in G2A format → CSV/TXT format
Deleting or copying alarm log files
Page 165 Alarm
information
Recipe info.
Converting recipe files in G2P format → CSV/TXT format
Converting CSV/TXT format → Recipe files in G2P format
Deleting or copying recipe files
Page 170 Recipe
information
Logging info.
Deleting or copying logging files
Page 176 Logging
information
Image file
Deleting or copying hard copy files
Page 180 Image file
management
Operation log
information
Converting operation log files in G2O format → CSV/TXT format
Deleting or copying operation log files
Page 184 Operation
log information
SD card access
Setting the access permission of the SD card
Page 190 SD Card
Access
SD card format
Formatting the SD card
Page 191 SD Card
Format
Clear data
Clearing the project data and resource data on the GOT
Page 193 Clear data
Data copy
Transferring the project data or OS to the SD card
Page 194 Data Copy
Backup/restore
Setting the backup and restoration
Page 197 BACKUP/
RESTORE
Debug
Device monitor
Device monitor of PLC, test function, current value change of the buffer
memory and the buffer memory monitor of intelligent module
Page 219 Device
Monitor Function
FX list editor
Changing parameters and sequence program of FX PLC
Page 232 FX List
Editor
FX3U-ENET-ADP
Configuring the communication setting for FX3U-ENET-ADP stored in the
FXCPU
Page 261 FX3U-
ENET-ADP Communication
Setting Function
Maintenance
Touch panel calibration
Calibrating the touch panel reading error
Page 267 Touch Panel
Calibration
Touch panel check
Checking the touch panel operation
Page 269 Touch Panel
Check
Clean
Displaying the screen for cleaning the display
Page 271 Clean
Item
Functions overview
Reference
9 UTILITY FUNCTION
9.3 Utility Display
9.3
Utility Display
To display setting screens for each utility, the main menu has to be displayed first.
Main menu
The menu items that can be set at the GOT utility are displayed.
Touching a menu item in the main menu will display the setting screen or following selection screen for the item.
System message switch button
This button switches the language used for the utility.
When touching the [Language] button, the Select Language screen is displayed.
1.
Touch the language button of a desired language and touch the [OK] button to select the language.
2.
Touching the [ ] button switches the language on the utility to the selected one.
9 UTILITY FUNCTION
9.3 Utility Display
67
9
• When starting the GOT without selecting any language or the selected language and the installed fonts are
not matched
The following screen will be displayed.
Touching the button of a desired language restarts the GOT and the language is switched to the selected one.
• Selectable languages
The system message switch button is displayed only for the selectable languages.
The selectable languages differ depending on the fonts installed in the GOT.
For the relation between the selectable languages and the fonts, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
• System language switching using the device
The system language can be switched using the system language switching device set with GT Designer3.
For the setting method of the system language switching device, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
9 UTILITY FUNCTION
9.3 Utility Display
Display operation of main menu
The following four types of operation can display the main menu.
(Display the main menu after installing the standard monitor OS from GT Designer3 to the GOT built in flash memory.)
When project data is undownloaded
After the GOT is turned on, a dialog box for notifying of absence of project data is displayed. After the dialog box is displayed,
touch the [OK] button to display the main menu.
When touching utility call key
If you touch the utility call key while user-created screen is displayed, the main menu is displayed.
The utility call key is set in the position on the GOT screen upper left corner at factory shipment.
The utility function windows appear in the horizontal format, and this format cannot be changed.
The utility call key can be set by the GOT utility or GT Designer3.
For the setting method of the utility call key, refer to the following.
Page 113 Setting the utility call keys
GT Designer3 (GOT2000) Screen Design Manual
• Prohibited simultaneous 2-point presses
Do not touch 2 points or more on the GOT screen simultaneously. Touching 2 points or more simultaneously
may activate a part other than the touched point.
• Press time of the utility call key
When having set [Press time] of the utility call key setting screen to other than "0 (s)", keep pressing the touch
panel for the period set to [Press time] or more before leaving the finger from the touch panel.
For utility call key setting, refer to the following.
Page 113 Setting the utility call keys
• When the utility call key is not set
Even when the utility call key is not set (set to the zero point), you can display the main menu by performing
the following operation.
Pressing the special function switch set on the user-created screen
Turning on the power
supply of the GOT
Touch [OK] button
Horizontal format
Vertical format
9 UTILITY FUNCTION
9.3 Utility Display
69
9
When touching special function switch (utility)
If you touch the special function switch (utility) while user-created screen is displayed, the main menu is displayed.
The special function switch (utility) can be set as a touch switch that is displayed on a user-created screen by GT Designer3.
For the details of the special function switch, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
When limiting the display and operation of the utility
When limiting the display and operating users, set a password to the GOT using GT Designer3.
If a user tries to display the main menu of the utility, the password is displayed.
Refer to the following for the details related to the password setting.
GT Designer3 (GOT2000) Screen Design Manual
Special function switch
(Utility)
9 UTILITY FUNCTION
9.3 Utility Display
Utility basic configuration
The basic configuration of utility is as follows.
Title display
The screen title name is displayed in title display part.
Close/Return button
When a middle screen of the layers is displayed, if the [ ] (Close/return) button in the right corner of screen is touched, returns
to the previous screen.
If this button is touched when directly displayed from monitor screen, the screen is closed and returns to monitor screen.
Scroll button
For screens in which the content does not fit on one screen page, there is a right or down scroll button on the screen.
Scroll one line/column.
Scroll window.
Title display
Close/Return button
Display
Title display
Title display
9 UTILITY FUNCTION
9.3 Utility Display
71
9
Basic operation of settings change
Change of setting value
■Setting item, select button
Touch the select button to change the settings.
The setting methods differ depending on the setting items.
The following types of setting method are available.
Switching the setting value
The button repeats
every time it is pressed.
Enter the setting value with a keyboard.
Use these keys to enter numerical values. Touch the button to display a keyboard on the GOT screen.
For the keyboard operations, refer to the next page.
Move to another setting screen.
Touch the button to move to each setting screen.
For the setting method of each setting item, refer to the setting operation of each setting screen.
■[ ] (Close/Return) button
Reflect or cancel the changed settings.
[ ] (Close/Return) button
Touching this button closes the screen. Depending on the setting item, the GOT restarts.
Touch the [ ] button, and then the dialog box shown below is displayed.
(If no setting is changed, the dialog is not displayed.)
Operate following the message of the dialog box.
Description
Selection button
Description
Selection button
SHORT LONG OFF
9 UTILITY FUNCTION
9.3 Utility Display
Keyboard operations
1.
Touch the numerical value to be changed.
2.
The keyboard for entering numerical values and a cursor are displayed. The display position of the keyboard differs
depending on the position of the touched numerical value. (The keyboard is displayed at a position that does not disturb
users to input numerical values.)
3.
Input numerical value by the keyboard.
• [0] to [9] Key: Enter numerical values.
• [Enter] Key: Completes the numerical value input and closes the keyboard.
• [Cancel] Key: Cancels the numerical value input and closes the keyboard.
• [Del] Key: Deletes one character.
• [AC] Key: Deletes all characters.
• [*] key and the keys which are not mentioned do not function.
4.
Touching the [Enter] key completes the numerical value input and closes the keyboard.
Cursor
keyboard
10 LANGUAGE SETTING (LANGUAGE)
10.1 Display language setting
73
10
10 LANGUAGE SETTING (LANGUAGE)
10.1
Display language setting
Display language setting function
This function allows display language selection.
The items which can be set are shown below.
Language setting operation
Language
Switching the display language of the utility by devices
Any device can be used for switching the display language of the utility. For details, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
When using devices to switch the display language of the utility, it does not change even if the display
language is switched from the GOT utility screen.
Item
Description
Setting range
Language
Display language in which the utility functions and dialog windows are displayed can be selected or
confirmed in this menu
Japanese/English/Chinese
1.
Touch [Language] to bring up the set up screen.
2.
Select a display language by touching the corresponding button.
3.
After changing the setting, touch the [ ] button. The setting is saved
and the setting screen is closed.
Main Menu
Touch [Language]
Touch a language to be displayed.
Touch
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
75
11
11 COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
The following communication interfaces can be set.
11.1
Standard I/F Setting
Standard I/F functions
Standard I/F display operation
Item
Functions overview
Reference
Comm. Setting
Standard I/F
Assigning channel number and communication driver to communication
interface
Page 75 Standard I/F Setting
GOT IP Address
Configuring GOT Ethernet setting
Page 84 GOT IP Address
Setting
Ethernet communication
Displaying the contents of Ethernet setting, changing the host
Page 86 Ethernet
Communication
Comm. Monitor
Checking the serial communication port communication
Page 90 Communication
Monitor
Ethernet check
Checking the Ethernet communication port communication
Page 93 Ethernet Check
Transparent mode
Setting the channel No. to be used for the communication for the FA
transparent function
Page 95 Setting the
Transparent Mode
Keyword
Setting or deleting sequence program protection key words and canceling
sequence program protection status for the FXCPU connection
Page 96 Keyword
Function
Description
Channel no. display
Displays the channel number (CH No) that has been assigned by drawing
Communication driver display
Displays the communication driver that has been assigned by drawing software
Communication parameters display
Displays the communication parameters of the controllers that has been assigned by drawing software
Main Menu
Comm. Setting
Touch
[Comm. Setting].
Touch
[Standard I/F].
Standard I/F
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
Display contents of standard I/F
Described below are the display items on the standard I/F setting menu and their functions.
Display item
■Standard interface display BOX
The standard interface includes the following four types.
• Standard I/F-1(RS-422/485 or RS-422): For communication with a controller
• Standard I/F-2(RS232): For communication with PLC, PC (drawing software), modem, other equipment, bar code reader
and transparent
• Standard I/F-3(USB): For communication with PC (drawing software) and transparent
• Standard I/F-4(Ethermet): For communication with PC (drawing software) and other equipment
Available standard interfaces differ depending on the GOT model used.
○: Available, ×: Not available
• For GS2110-WTBD-N, GS2107-WTBD-N
GOT
Standard I/F-1
Standard I/F-2
Standard I/F-3
Standard I/F-4
RS-422/485
RS-422
RS-232
USB
Ethernet
GS2110-WTBD-N
GS2107-WTBD-N
○
×
○
○
○
GS2110-WTBD
GS2107-WTBD
×
○
○
○
○
Standard interface display BOX
Channel No.
specification
menu BOX
Driver display BOX
Drv button
Standard I/F-3(USB)
Standard I/F-1(RS-422/485)
Standard I/F-4(Ethernet)
Standard I/F-2(RS-232)
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
77
11
• For GS2110-WTBD, GS2107-WTBD
■Channel No. specification menu BOX
Set a channel number to be used by the standard interface.
Page 82 Channel setting operation
For the detail of the drivers which can be assigned to each channel, refer to the following.
Page 77 Driver display BOX
*1
"9" is automatically set to the standard I/F-3(USB).
■Driver display BOX
The driver display box displays the names of communication drivers assigned to channels or the communication drivers set in
the communication settings of drawing software.
For details of the communication drivers to be displayed, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
"Disuse" is displayed in the driver display box in the following cases:
• The communication driver is not installed.
Page 83 Driver setting operation
• "0" is set in the channel number specification menu box.
The channel number of the standard I/F-3(USB) is fixed to "9".
■[Drv] button
Displays the driver setting screen.
Select the driver to use on the driver setting screen.
Page 83 Driver setting operation
The [Drv] button is displayed in the following case.
• When a channel number other than channel 0 or 9 is set to the standard I/F-1, standard I/F-2, and standard I/F-4
0:
Set when the communication interface is not used.
1, 2:
Set when connecting to a controller.
8:
Set when connecting to a bar code reader or RFID.
9: *1
Set when connecting to a PC (drawing software).
*:
Set this channel when the gateway function (except when the connection with controllers is the Ethernet connection) or the Ethernet download function
is used.
Standard I/F-3(USB)
Standard I/F-1(RS-422)
Standard I/F-4(Ethernet)
Standard I/F-2(RS-232)
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
Precautions for communication between GOT and connected devices
• Installing [Communication driver] and downloading [Communication Settings]
To perform communication with the connected device, the following actions are necessary.
1) Installing communication drivers (Up to 2 drivers)
2) Assigning channel numbers and communication drivers to communication interfaces
3) Downloading contents (project data) assigned in step 2)
Perform 1), 2) and 3) with drawing software.
For details, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
• When the communication settings have not been downloaded
If the communication settings have not been downloaded with drawing software, set the communication
settings on the drawing software or in the GOT utility screen.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
79
11
Detail information setting operation
For Standard I/F-1(RS422) and Standard I/F-2(RS232)
1.
Touch each driver display box of the standard I/F-1 and standard I/F-
2.
2.
The screen jumps to the detailed information screen and the
communication parameter will appear.
3.
Touch the numerical values of baud rate to switch them repeatedly.
The numerical values are set using the ten-key depending on the setting.
"0" to "9":
Use these keys to enter numerical values. Enter "0" to disable the screen
saver function.
"ESC":
Closes the ten-key window without saving any value entered
"AC":
Deletes the entire string of numerical characters that are being entered
"DEL":
Deletes a digit from a string of numerical characters that are being
entered
"ENT":
Enters the value for the clock that has been entered and closes the ten-
key pad window
"+/-":
Switches between positive and negative values. (Only positive values are
valid for the clock setting.)
"." :
Invalid key (not used)
Touch [Driver display BOX].
Ex. 4800bps 9600bps 19200bps
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
Communication parameters
The types of items that are in the communication parameter setting menu depend on the type of
communication driver that is installed on the GOT in use.
Refer to the section below for the setting contents of various drivers.
GT Designer3 (GOT2000) Screen Design Manual
4.
Touch the [ ] button to display the window confirming whether to
save the settings.
5.
Touch the [YES] button to save the settings and restart. Touch the
[NO] button to discard the changes.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
81
11
For Standard I/F-4(Ethernet)
Communication parameter setting by drawing software
Set the communication parameter for each communication driver by selecting [Common]
[Controller
Setting].
GT Designer3 (GOT2000) Screen Design Manual
1.
Touch the driver display box of a communication parameter to be
set.
2.
The screen is switched to the communication detail setting. Set the
communication parameter on this screen.
GOT IP address setting
Page 84 GOT IP Address Setting
3.
When the [ ] button is touched, it returns to the previous screen.
4.
Touch the [ ] button to display the window confirming whether to
save the settings.
5.
Touch the [YES] button to save the settings and restart. Touch the
[NO] button to discard the changes.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
Channel setting operation
Channel number setting operation
1.
Touch the channel No. specification menu box to be set.
2.
When the channel setting window appears, select the channel
number.
3.
When the channel number is selected, the settings are fixed and the
window returns to the previous one. Therefore, touch the [ ] button.
4.
Touch the [ ] button to display the window confirming whether to
save the settings.
5.
Touch the [YES] button to save the settings and restart. Touch the
[NO] button to discard the changes.
Touch
Touch
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.1 Standard I/F Setting
83
11
Driver setting operation
Driver setting operation
1.
Touch [Drv] button to bring up the driver setting window.
2.
The available driver names are displayed on the driver setting
screen. Select the driver to use.
3.
When the channel number is selected, the settings are fixed and the
window returns to the previous one. Therefore, touch the [ ] button.
4.
Touch the [ ] button to display the window confirming whether to
save the settings.
5.
Touch the [YES] button to save the settings and restart. Touch the
[NO] button to discard the changes.
Touch [Drv]
Touch
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.2 GOT IP Address Setting
11.2
GOT IP Address Setting
This section describes the GOT Ethernet setting.
The GOT Ethernet setting can also be set with drawing software. For details, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
Standard
The table below shows the communication setting items and setting range.
*1
Set the value "0.0.0.0" when not using the subnet mask and default gateway.
Display operation of GOT IP address
Communication setting items
Setting range
Remark
IP Address
0.0.0.1 to 223.255.255.254
If a value outside the setting range is entered, the error message
"SET NUMBER IS INCORRECT." appears.
Subnet Mask*1
192.0.0.0 to 255.255.255.252
Default gateway*1
0.0.0.1 to 223.255.255.254
Per. S/W port No.
1024 to 5010, 5014 to 49152, 49171 to 65534
Set the port number for the GOT download.
Transparent port No.
1024 to 5010, 5014 to 49152, 49171 to 65534
Set the port number for the transparent of the GOT.
Main Menu
Comm. Setting
Touch
[Comm. Setting].
Touch
[GOT IP Address].
GOT IP Address
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.2 GOT IP Address Setting
85
11
Setting operation
1.
Touch the numerical part of the octet to be changed among the 1st to 4th
octets.
2.
When the ten-key pad appears, enter a numerical value in up to 3 digits,
and touch the
key. If a numerical value outside the setting range is
entered, the following error message appears. Enter a numerical value
again.
For the details of the setting range, refer to the following.
Page 261 Specifications
3.
If necessary, change the setting of [Per. S/W port No.] and [Transparent port
No.].
4.
After the setting change, touch the [×] key.
5.
When the screen shown on the left appears, touch the [YES] key.
Touch the numerical part
of the octet to be changed.
Touch
Touch[×]
Touch [YES]
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.3 Ethernet Communication
11.3
Ethernet Communication
Setting function for Ethernet communication
The contents of the Ethernet set in GT Designer3 can be checked.
The setting of the host station can be changed.
For the Ethernet setting, refer to the following.
GOT2000 Series Connection Manual for the controller used
Display operation of Ethernet communication
Channel Setting
Ethernet setting
Comm. Setting
Main menu
Touch [Comm. Setting].
Touch [Ethernet setting].
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.3 Ethernet Communication
87
11
Display contents of Ethernet setting
The following describes the setting items and the display contents of the Ethernet setting.
Channel select tab
Channels can be switched.
Switching to the channel which does not have the Ethernet setting is not available.
Ethernet setting items
The contents of the Ethernet setting configured in GT Designer3 are displayed.
Changing [Host], [Net No.], [Station No.] and [IP Address] are available.
Page 88 Change of host
Page 88 Change of Net No.
Page 89 Change of station No.
Page 89 Change of IP address
How to cancel the change of the setting in the [Ethernet setting] screen.
Cancel the settings changed in the [Ethernet setting] screen with the [Restore default settings] button.
The changed settings remain until they are canceled with the [Restore default settings] button.
The changed settings are not canceled even if writing the project data or system application to the GOT.
When the project data is written to the GOT without canceling the changed settings, those changed settings
are reflected to the Ethernet setting of the written project data.
(If the written project data does not have a channel with same Ethernet settings as that of the channel
changed in [Ethernet setting] screen, the changed settings are not reflected.)
Ethernet setting items
Channel select tab
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.3 Ethernet Communication
■Change of host
■Change of Net No.
1.
Touch the device to be set as the host.
2.
After the setting change, touch the [×] key. When the screen shown
on the left appears, touch the [YES] key.
1.
Touch the Net No. to be changed, and input the network No. to be
changed by the numeric keypad displayed.
2.
After the setting change, touch the [×] key. When the screen shown
on the left appears, touch the [YES] key.
Touch YES.
Touch YES.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.3 Ethernet Communication
89
11
■Change of station No.
■Change of IP address
1.
Touch the station No. to be changed, and input the station No. of the
destination Ethernet module to be changed by the numeric keypad
displayed.
2.
After the setting change, touch the [×] key. When the screen shown
on the left appears, touch the [YES] key.
1.
Touch the IP address to be changed, input the destination IP
address to be changed by the numeric keypad displayed.
2.
After the setting change, touch the [×] key. When the screen shown
on the left appears, touch the [YES] key.
Touch YES.
Touch YES.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.4 Communication Monitor
11.4
Communication Monitor
Communication monitor functions
Communication monitor display operation
Function
Description
Communication port-selection status display
Indicates the connection status of Standard I/F-1 and I/F-2.
Communication status display
Displays the communication status (SD: send, RD: receive)
Communication error status display
Displays an error message when a communication error occurs
Comm. Setting
Main Menu
Comm. Monitor
Touch
[Comm. Setting].
Touch
[Comm. Monitor].
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.4 Communication Monitor
91
11
Screen display content
Connection status of the communication ports
Indicates the connection status of Standard I/F-1 and I/F-2.
Listed in the table below are display items and the connection status (channel number).
Communication status
Displays the communication status of each communication port.
The SD and RD symbols appear in white on red (
,
) while data are being sent or received, and in black on gray
(
,
) at other times. They may appear lit depending on the communication status.
The SD and RD symbols on the screen indicate normal communication or cable disconnection.
Setting example
■[During normal communication (with connection to a device that supports the transparent
mode)]
■[When the connecting cable with the controller is disconnected]
Display item
Channel number
Remark
PLC
Ch1
"PLC" appears when connected to a controller (PLC or microcomputer)
Barcode
Ch8
"BCR" appears when connected to a bar code reader
TRANS.
Ch9
"TRANS." appears when the controller that is allocated to one of the communication ports supports the
transparent mode
"TRANS." automatically changes to "PC" when communicating with drawing software
Host(PC)
Ch9
"PC" appears when the controller that is allocated to one of the communication ports does not support the
transparent mode
Printer
ChA
Appears when connected to a printer.
Port
Channel number
Controller type
I/F-1
Ch1
MELSEC-FX
I/F-2
Ch8, Ch9
-
Connection status of
the communication ports
Communication error status
Communication status
The SD and RD symbols for I/F-1
Only the SD symbol next to I/F-1 blinks.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.4 Communication Monitor
Communication error status
Communication error status of each port is displayed on this screen.
The following table describes the communication status that each display item shows.
Display item
Status
Action
NO ERROR
No error
Communication is executed normally.
ERR Ovr.
Overrun error
The receive data is sent continuously with a short interval.
Let the baud rate (communication speed) be equivalent between the GOT and counterpart equipment.
ERR Frm.
Framing error
The communication frames of GOT and PLC are inconsistent.
Confirm the communication settings of GOT and PLC, such as data length, stop bit and baud rate.
ERR Prt.
Parity error
The parity check conditions of GOT and PLC are inconsistent.
Let the parity check condition (odd or even) of GOT and PLC be consistent.
ERR Text
Text error
The sum data is inconsistent. Or the contents of the receive data are not consistent with the send command from
the GOT.
Let the communication settings and contents of data be consistent between the GOT and counterpart equipment.
(If NAK is received while the GOT is connected to the microcomputer board, a text error occurs.)
TIME OUT
Communication timeout
Though receiving is started, receive data is not sent.
Check the wiring between the GOT and its communication target.
(When the GOT is connected to the microcomputer board, confirm the terminator, CR, wiring, etc.)
ERR Line
Control line error
The control line is not operating correctly.
Confirm the wiring of the control line.
ERR Cmd.
Command error
A command contained in the receive data is not consistent with the send command from the GOT.
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.5 Ethernet Check
93
11
11.5
Ethernet Check
Ethernet check function
The Ethernet status check function sends a ping to check the connection status of Ethernet.
Display operation of Ethernet check
Ethernet check
Main Menu
Debug
Touch
[Debug].
Touch
[Ethernet check].
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.5 Ethernet Check
Operation of Ethernet status check
1.
If the select button of [Destination IP] is touched, a keyboard is
displayed. Enter the IP address of the other terminal with the
keyboard.
2.
If the [Send ping] button is touched, a ping is sent to the IP
address entered in [Destination IP]. The timeout time is 5sec.
When the communication is completed
The [Response received.] dialog box is displayed.
When a communication error occurs
The [Timeout occurred.] dialog box is displayed.
Touch
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.6 Setting the Transparent Mode
95
11
11.6
Setting the Transparent Mode
Function of the transparent mode
When using the multi-channel function, the channel No. of a controller to which the FA transparent function is executed can be
set. For the multi-channel function and the FA transparent function, refer to the following.
GOT2000 Series Connection Manual (Mitsubishi Product) For GT Works3 Version1
Display operation the transparent mode setting
Operation the transparent mode
Function
Description
Setting range
ChNo.
The channel No. of a controller to which the FA transparent function is executed can be set.
1/2
(Default: 1)
1.
When the transparent ChNo. (numerical part) on the left is
touched, the screen for selecting a communication driver is
displayed. Select the channel to execute the FA transparent
function.
2.
If the [ ] button is touched, it returns to the GOT setup
screen.
Transparent mode
Main Menu
Comm. Setting
Touch
[Comm Setting]
Touch [Transparent mode]
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.7 Keyword
11.7
Keyword
Keyword functions
The operation related to a keyword of the FX series PLC can be performed.
Keyword display operation
Function
Description
Regist
Keyword is registered.
Delete
Registered keyword is deleted.
Clear
Keyword protection is cleared.
Protect
A keyword with cleared protection is reactivated for protection.
Main Menu
Comm. Setting
Channel Setting
Keyword
Touch
[Comm. Setting]
Touch
[Keyword]
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.7 Keyword
97
11
Regist
Keyword is registered.
1.
Touch "Regist" to display the selection screen for the registration.
For the FX series PLC, which is not compatible with Customer
Keyword, the keyword entry screen of [Step3] is displayed. Start
the operation from [Step3]. For the Customer Keyword
compatible models, refer to the manual of the PLC to be used.
2.
Select [Keyword] or [Keyword+Custom]. To register only
Keyword and 2nd keyword, touch [Keyword]. To register
Customer Keyword, touch [Keyword+Custom].
3.
Input a keyword. Touch the display part of the keyword to be
registered.
4.
The keyboard for entering a keyword is displayed. Character
types to be input can be changed by touching the [KEY] button.
Enter a keyword and touch the [ENT] key. For the keyword, 8
digits from 0 to 9 or A to F must be set.
5.
After completing the keyword entry, touch [Next]. When
[Keyword+Custom] is selected on the selection screen for the
registration, the Customer Keyword entry screen is displayed.
Enter it in the same way as for Keyword and 2nd keyword.
Touch
Touch
Touch
Touch
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
11.7 Keyword
6.
Set Registration condition. Touch Registration condition to
change the setting contents.
7.
After setting Registration condition, touch the [Execute] key. The
registration of the keyword is completed.
8.
The registration of the keyword is completed. Touch [OK].
Touch
All Protect Write Protect R/W Protect
Touch
Touch