Lucent Technologies H569-445 Product Manual
Text of the manual
Secondary DC Power
Distribution Bay
H569-445
Product Manual
Select Code 157-005-104
Comcode 108405283
Issue 5
May 2000
© 2000 Lucent Technologies
Select Code 157-005-104
Comcode 108405283
Issue 5
May 2000
Lucent Technologies
Secondary DC Power Distribution Bay
H569-455
Notice:
The information, specifications, and procedures in this manual
are subject to change without notice. Lucent Technologies
assumes no responsibility for any errors that may appear in this
document.
© 2000 Lucent Technologies
All Rights Reserved
Printed in U.S.A.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Table of Contents - 1
Table of Contents
1
Introduction
Product Summary
1 - 1
Documentation
1 - 3
Customer Assistance Contacts
1 - 3
Customer Training
1 - 3
Customer Service
1 - 3
Technical Support
1 - 3
Product Repair and Return
1 - 4
Warranty Service
1 - 4
On-Line Power Systems Product Manuals
1 - 4
2
Product Description
Cabinet Arrangements
2 - 1
Features
2 - 2
Specifications
2 - 2
Cabinet Types and Features
2 - 3
Load Bus Arrangements
2 - 8
Discharge Return Bus Options
2 - 10
Lugs and Hardware
2 - 13
Breakers and Fuses
2 - 13
External Return Bus Bars
2 - 14
Digital Meters and Monitoring Shunts
2 - 15
G-70
2 - 15
G-71
2 - 16
ED83127-30 Fuse Panels
2 - 17
Groups 30A-30D
2 - 17
Groups 31A and 31B
2 - 19
Alarm Circuit Module (BEP1)
2 - 20
Detailed Circuit Description
2 - 23
Monitoring Multiple Alarm Modules for Negative Plants
2 - 25
Monitoring Multiple Alarm Modules for Positive Plants
2 - 27
Reference Data
2 - 28
3
Safety
Safety Statements
3 - 1
Warning Statements and Safety Symbols
3 - 3
Precautions
3 - 5
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - Table of Contents
Issue 5 May 2000
4
Product Warranty
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
List of Figures - 1
List of Figures
Figure 1-1: H569-445 Secondary DC Power
Distribution Bay
1 - 2
Figure 2-1: 2-1/2-Foot Extension Cabinet
2 - 4
Figure 2-2: 2-Foot or 4-1/2-Foot Extension Cabinet
2 - 5
Figure 2-3: Fuse Panel Position Numbering
2 - 6
Figure 2-4: Circuit Breaker Panel Position Numbering
2 - 7
Figure 2-5: Group 20 Load Connection Points
2 - 9
Figure 2-6: External Discharge Return Bus Options
on Cable Rack
2 - 11
Figure 2-7: Bus Bar Hole Pattern and Numbering
Schemes
2 - 12
Figure 2-8: G-70 Digital Meter
2 - 15
Figure 2-9: G-71 Digital Meter
2 - 16
Figure 2-10: H569-445 Group 30A-30D Fuse Panel
(One Shown; Two Are Provided Per Group)
2 - 18
Figure 2-11: H569-445 Groups 31A and 31B
Circuit Breaker Panel
2 - 19
Figure 2-12: A-CP/BEP1 Board Layout
2 - 21
Figure 2-13: A-CP/BEP1 Input/Output Connections
(Alarm Module With No Power Is in “Normal” State)
2 - 22
Figure 2-14: Frame Alarm
2 - 24
Figure 2-15: P102 Factory Alarm Wiring
2 - 25
Figure 2-16: P101 Frame Power Loss Alarm Wiring
2 - 26
Figure 2-17: Fuse or Circuit Breaker Alarm Wiring
for Positive Plant P101
2 - 27
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
List of Tables - 1
List of Tables
Table 2-A: Lugs and Hardware for Breakers and Fuses
2 - 13
Table 2-B: Lugs and Hardware for External Return Bus Bars
2 - 14
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Introduction 1 - 1
1
Introduction
Product
Summary
This product manual (Select Code 157-005-104) describes the
H569-445 Secondary DC Power Distribution Bay. This unit is also
known as a Battery Distribution Fuse Bay (BDFB) or a Battery
Distribution Circuit Breaker Bay (BDCCB). The H569-445 series bay
is shown in Figure 1-1. It serves as a secondary fuse or circuit breaker
distribution center for dc power delivered from a central office battery
plant to the using equipment. It provides space-efficient branch loading
for distributing +24, -48, or ±130 volt dc power, or combinations of
these voltages from different battery plants. (BDCBB versions of the
Distribution Bay do not offer the ±130 volt dc option.)
In many applications, telecommunication equipment requires power
redundancy from the battery plant. A BDFB or BDCBB provides this
redundancy through the use of multiple load buses. The H569-445 is a
cabinetized distribution system that supports these applications by
providing up to six distinct load buses for the 7-foot cabinet or up to
eight distinct load buses for the 9-foot cabinet.
Each load bus has a rated current carrying capacity of 600 amperes.
Each load bus may be configured to include one or multiple fuse or
circuit breaker panels. Each fuse panel provides 20 mounting positions
that may be equipped with either WP-92461 cartridge fuses that range
from 3 to 70 amperes and/or GMT fuse modules containing three fuses
ranging from 1/2 to 5 amperes. Fuse panels may also be equipped with
70-150 ampere TPL type fuse blocks. Each circuit breaker panel
provides 20 positions for circuit breakers ranging from 3 to 100
amperes.
Additional features include: digital meters; remote monitoring
capability for alarms; multiple cabinet heights, and optional 2-hole
ground bus arrangements mounted either in the cabinet or external to
the cabinet on a cable rack. These options and many more provide
greater flexibility for customers with different distribution
requirements.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
1 - 2 Introduction
Issue 5 May 2000
Figure 1-1: H569-445 Secondary DC Power
Distribution Bay
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Introduction 1 - 3
Documentation
This product manual (Select Code 157-005-104) is part of a set of
documentation developed to assist engineering and installation
personnel. Additional product information includes the following:
•
H569-445 Ordering and Installation Guide
•
T-83150-30 Wiring Drawing
•
SD-83150-01 Schematic Drawing
This documentation is provided with each H569-445 bay in
Documentation Service Kit, Comcode 848296505.
Customer
Assistance
Contacts
Customer Training
Lucent Technologies offers customer training on many Power Systems
products. For information call 1-972-284-2163. This number is
answered from 8:00 a.m. until 4:30 p.m., Central Time Zone (Zone 6),
Monday through Friday.
Customer Service
For customers in the United States, Canada, Puerto Rico, and the US
Virgin Islands, call 1-800-THE-1PWR (1-800-843-1797). Services
provided through this contact include initiating the spare parts
procurement process for out of service emergencies, ordering Lucent
Technologies documents, and providing other product and service
information.
For other customers worldwide, call 001-972-840-0382. This number
is answered from 8:00 a.m. until 4:30 p.m., Central Time Zone (Zone
6), Monday through Friday.
Technical Support
Technical support for Lucent Technologies customers is available
around the world during the normal product warranty period and also
while specific contractual agreements extend this service.
For customers in the United States, Canada, Puerto Rico, and the US
Virgin Islands, call 1-800-CAL-RTAC (1-800-225-7822) to contact a
product specialist to answer your technical questions and assist in
troubleshooting problems.
For other customers worldwide, contact your local field support center
or your sales representative to discuss your specific needs.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
1 - 4 Introduction
Issue 5 May 2000
Customer Assistance Contacts, continued
Product Repair and
Return
Repair and return service is provided for Lucent Technologies
customers around the world.
For customers in the United States, Canada, Puerto Rico, and the US
Virgin Islands, call 1-800-255-1402 for information on returning of
products for repair.
For other customers worldwide, contact your sales representative to
discuss your particular circumstances.
Warranty Service
For domestic warranty service, contact your Warranty Service Manager
(WSM). For international warranty service, contact your sales
representative.
On-Line Power
Systems Product
Manuals
For Lucent Technologies users logging in from inside the corporate
firewall, the address of the “Power Systems On-Line Product Manuals”
page is http://www.cic.lucent.com/lineage.html.
For customers logging in from outside the firewall, the address is
http://www.lucent8.com/lineage.html. The annual subscription fee for
access to this site is $25. To obtain a password, follow the instructions
on-line or call 1-888-Lucent8 (1-888-582-3688). When prompted for
an order number, enter or say “167-790-010.”
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 1
2
Product Description
Cabinet
Arrangements
The Secondary DC Power Distribution Bay, Model H569-445, is
available in five cabinet arrangements. These include:
7-foot cabinet: 26 inches wide by 15 inches deep
7-foot cabinet with 2-foot extension cabinet
7-foot cabinet with 4-1/2-foot extension cabinet
9-foot cabinet: 26 inches wide by 18 inches deep
9-foot cabinet with 2-1/2-foot extension cabinet
The 7-foot cabinet has six fuse or circuit breaker panel positions and the
9-foot cabinet has eight fuse or circuit breaker panel positions. Alarms
include both remote signaling and visual indication of fuse or circuit
breaker failure and panel power loss.
The 7-foot cabinet may be configured with one to six separate load
buses. The 9-foot cabinet may be configured with one to eight separate
load buses.All input battery and battery return feeds are terminated at
the load connection point on the fuse or circuit breaker panel. Each load
connection point has a 800A monitoring shunt. A digital meter is also
provided with each bay.
Load leads from each fuse or circuit breaker are routed along cable
troughs on either side of the cabinet. Discharge return leads from the
load equipment can be handled in one of two ways. A discharge return
bus bar arrangement mounted either on the fuse or circuit breaker
panels in the cabinet or external to the cabinet on a cable rack. Both
configurations comply with Bellcore 2-Hole grounding requirements.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 2 Product Description
Issue 5 May 2000
Features
The following is a list of the many features provided with this product:
•
Distributes +24, -48, or ±130 volt dc power (±130 volt not offered
with BDCBB)
•
7-, 9-, or 11-1/2-foot cabinet arrangements
•
One to eight load buses
•
Digital meter
•
Cable entry from the top or bottom of cabinet
•
120 cartridge fuse or circuit breaker positions in 7-foot cabinet
•
160 cartridge fuse or circuit breaker positions in 9-foot cabinet
•
Accommodates fuse sizes 1/2 to 150 amperes or circuit breaker
sizes 3 to 100 amperes.
•
800-ampere monitoring shunts
•
Frame alarm indicator lamp
•
Panel fuse or circuit breaker alarm and power loss indicator lamps
•
Individual fuse or circuit breaker alarm indicator
•
Alarm circuit modules for remote monitoring
•
Optional internal or external ground bus arrangements
Specifications
Group 1 Cabinet: Six fuse or circuit breaker panel positions
Height
84 inches (2134mm)
Width
26 inches (660mm)
Depth
15 inches (381mm)
Weight
approx. 375 pounds (6 panels)
Group 2 Cabinet: Eight fuse or circuit breaker panel positions
Height
108 inches (2743mm)
Width
26 inches (660mm)
Depth
18 inches (457mm)
Weight
approx. 450 pounds (8 panels)
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 3
Cabinet Types
and Features
Two cabinet types and three cabinet extension options are available:
Group 1
7 ft Cabinet
Group 2
9 ft Cabinet
848258562
2-1/2 ft Extension Cabinet for 9 ft cabinet
848258588
4-1/2 ft Extension Cabinet for 7 ft Cabinet
848258570
2 ft extension cabinet for 7 ft cabinet
The Group 1 cabinet contains six fuse or circuit breaker panel positions
and the Group 2 cabinet has eight fuse or circuit breaker positions. Each
of these panel positions must be equipped with either a fuse panel, a
circuit breaker panel, or a Group 90 blank panel.
The 848258562 2-1/2-foot extension cabinet mounts on top of the
9-foot cabinet as shown in Figure 2-1. Constructed in the same manner
as the other cabinets, it offers a clean, aesthetically pleasing solution for
11-1/2-foot central office applications. Interconnection hardware and
interframe ground cabling and mounting hardware are furnished to
provide a continuous frame ground to the top of the cabinet.
The 848258588 4-1/2-foot extension cabinet for the Group 1 cabinet
offers another option for the 11-1/2-foot office environment. The
848258570 2-foot extension cabinet for the Group 1 cabinet to offers a
similar option for the 9-foot environment. The extensions, shown in
Figure 2-2, may be disassembled if future wire center modernization
requires a 7-foot office environment. Intercabinet ground cable and
mounting hardware is furnished to provide a continuous frame ground
to the top of the cabinet.
The frame ground connection is located on top of each cabinet.
Connection is made using a 1/4 inch double hole terminal lug on .625
inch centers. For ground wire connection greater than 2 gauge, order
Comcode 846337798 bus bar adapter to allow for 3/8 inch double hole
terminal lugs on 1.00 inch centers.
Cabinets may be configured for either top or bottom cable entry. For
either configuration, the dc cable designations may start with position
1 at the top left or bottom right. Figures 2-3 and 2-4 show the possible
configurations. When ordering fuse or circuit breaker panels for the
distribution bay it is important to remember the numbering schemes
associated with top and bottom feed applications. Refer to Figures 2-3
and 2-4 for fuse or circuit breaker panel position numbers for each
application. This information is necessary to communicate where fuse
or circuit breaker panels with different configurations should be located
on factory orders. Panel numbering is also stamped on the front of each
cabinet at the factory as an installation reference.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 4 Product Description
Issue 5 May 2000
Cabinet Types and Features, continued
Figure 2-1: 2-1/2-Foot Extension Cabinet
9' Cabinet
Frame
Mounting
Hardware
Ground Strap
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 5
Cabinet Types and Features, continued
Figure 2-2: 2-Foot or 4-1/2-Foot Extension Cabinet
7' Cabinet
7' Cabinet
Frame
Mounting
Hardware
Frame
Mounting
Hardware
Ground
Strap
Ground
Strap
Lucent
Lucent
2'
4-1/2'
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 6 Product Description
Issue 5 May 2000
Cabinet Types and Features, continued
Figure 2-3: Fuse Panel Position Numbering
Group 10A: Top Feed A
Group 10D: Bottom Feed B
or
Note: 7 foot cabinet shown.
Similar for 9 foot cabinet.
Panel Position 1
(fuse panel shown)
Panel Position 2
(fuse panel shown)
Panel Position 3
(fuse panel shown)
Panel Position 5
(blank panel shown)
Panel Position 4
(fuse panel shown)
Panel Position 6
(blank panel shown)
Populated with DC panels from
the top down. Cables are
routed out
of cabinet.
bottom
Populated with DC panels from
the top down. Cables are
routed out
top of cabinet.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 7
Cabinet Types and Features, continued
Figure 2-4: Circuit Breaker Panel Position Numbering
Group 10B: Top Feed B
Group 10C: Bottom Feed A
or
Note: 7 foot cabinet shown.
Similar for 9 foot cabinet.
Panel Position 6
(blank panel shown)
Panel Position 5
(blank panel shown)
Panel Position 4
(fuse panel shown)
Panel Position 2
(fuse panel shown)
Panel Position 3
(fuse panel shown)
Panel Position 1
(fuse panel shown)
Populated with DC panels from
the bottom up. Cables are
routed out
of cabinet.
bottom
Populated with DC panels from
the bottom up. Cables are
routed out
of cabinet.
top
Note
Equip fuse or circuit breaker panels starting at panel position 1
to eliminate possible cable congestion when installing
additional fuse or circuit breaker panels in the field.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 8 Product Description
Issue 5 May 2000
Load Bus
Arrangements
The bus bars used in the distribution bay are sized to provide a rated
current carrying capacity of 600 amperes. (A minimum of two 750
KCMIL feeder cables are required per shunt for currents larger than
500 amps per shunt.) A load bus is defined as one or more fuse or circuit
breaker panels protected by a single circuit breaker or fuse at the battery
plant. Cable from the battery plant is terminated at the load connection
mounted on the dc panel.Group 20 provides load connection points for
two load buses. Figure 2-5 shows this Group 20 load connection. As
Figure 2-5 shows, battery is bused across a load monitoring shunt to
each fuse/circuit breaker panel.
Note: Group 20 provides connection points for two side-by-side loads.
If fewer load buses are required, it is possible to connect fuse or circuit
breaker panel battery buses together using a Group 40 bus bar link. This
feature is shown on Figure 2-5. This may be desirable for two or four
load distribution bays where more than twenty fuse or circuit breaker
positions are required for a single load. Only fuse or circuit breaker
panels mounted above or below one another may be connected, i.e.,
panels mounted on the left side of the cabinet cannot be joined to panels
mounted on the right side of the cabinet. Remember that the 600
ampere capacity per load bus applies even if multiple fuse panels are
connected together.
Note: Group 40 provides two bus bar links, one for the left side and one
for the right side.
Note
All bus bars used in this product are copper with a solder plate
finish. Bus bars do not require buffing or the application of
NO-OX before connection to terminal lugs or other bus bars.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 9
Load Bus Arrangements, continued
Figure 2-5: Group 20 Load Connection Points
Group 20 Load Connection
Battery Input
Cable Connection
800A Shunts
Group 61 Bus Bar
(Group 61 provides 1 left side
and 1 right side bus bar.)
Group 40 Bus Bar Link
(Group 40 provides 1 left side
and 1 right side bus bar.)
Group 61A Panel Return Bus
(Group 61A provides 1 left side
and 1 right side bus bar.)
Panel Return Bus Link
(included with panel return bus.)
This illustration is an example of a
two-load cabinet equipped with six
panels and internal return connections.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 10 Product Description
Issue 5 May 2000
Discharge
Return Bus
Options
Two optional discharge return bus options are available for terminating
fuse or circuit breaker return leads: (1) Bus bar returns located in the
distribution bay (G-61 and G-61A) or (2) A return bus located outside
the distribution bay on a cable rack.
The first option involves a bus bar arrangement similar to the battery
bus connection scheme discussed in the previous section. Discharge
return cable from the battery plant is terminated at the top (or bottom)
of the cabinet adjacent to the battery input cabling on Group 61 bus
bars. Group 61 provides bus bars to connect the battery plant discharge
return cabling to Group 61A bus bars mounted on each fuse or circuit
breaker panel adjacent to the fuse blocks or circuit breakers. This option
is shown in Figure 2-5. Internal returns offer the advantage of paired
leads directly from the fuse or circuit breaker and eliminates the need
for identification tags on each return lead. The discharge return bus is
designed for terminating 1/4 inch double hole terminal lugs.
Note: Group 61 and 61A provide two bus bar links, one for the left side
and one for the right side.
The drawback to this cabling scheme is that you are limited to 600
amperes capacity due to the size of the bus bars. A second concern is
the potential cable congestion resulting from twice the number of leads
in the distribution bay. For these reasons, the internal discharge return
option is recommended only for applications with smaller ultimate
capacities. For most applications, the external return bus option is
recommended.
The external discharge return bus bar options are shown in Figures 2-6
and 2-7. The external bus is mounted on a standard 15 or 20 inch ladder
type cable rack. Options 848258679 and 848258687 are rated for 2400
amperes of current. Option 848258679 provides the first bus bar and the
cable rack mounting hardware. Option 848258687 provides a bus bar,
the connecting bus bar and insulating standoffs for stacking additional
tiers as required. The ED83019-50 G1 bus bar assembly has a 1200
ampere current rating.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 11
Discharge Return Bus Options, continued
Figure 2-6: External Discharge Return Bus Options
on Cable Rack
848258687
848258679
ED83019-50 Group 1
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 12 Product Description
Issue 5 May 2000
Discharge Return Bus Options, continued
Figure 2-7: Bus Bar Hole Pattern and Numbering
Schemes
Row A for 1st Level
Row D for 2nd Level
Row C for 1st Level
Row F for 2nd Level
15.62 REF
(for 15 Inch Cable Rack)
20.62 REF
(for 20 Inch Cable Rack)
Row "A"
Row "D"
Row "B"
Row "C"
Top View
848258679 and 848258687
Top View
ED83019-50 Group 1
804067320
Terminal Strip
(2 Places)
846957645 Bus Bar
Row B for 1st Level
Row E for 2nd Level
.221 Dia. on .62 Centers
(24 Places)
.437 Dia. on 1.00 Centers
(25 Places)
26.00
REF
6.00 REF
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 13
Lugs and Hardware
Breakers and Fuses
Table 2-A: Lugs and Hardware for Breakers and Fuses
Lug
Comcode
Type
Wire Gauge
Hardware
Std
Flex
406338152
Load
14-10
14-10
Provided
406144428
Return
Provided
405356189
Load
8
8
Provided
406021626
Return
Provided
405347436
Load
6
6
Provided
405347519
Return
Provided
405347543
Load
4
4
Provided
405347576
Return
Provided
405348186
Load
2
--
Provided
405348202
Return
Provided
405347659
Load
--
2
Provided
405347683
Return
Provided
406338707
Load
1/0
--
Provided
407817568
Return
Provided
406467187
Load
2/0
1/0
Provided
407817550
Return
Provided
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 14 Product Description
Issue 5 May 2000
Lugs and Hardware, continued
External Return
Bus Bars
Table 2-B: Lugs and Hardware for External Return Bus Bars
Lug
Comcode
Wire Gauge
Std
Flex
405356171
10-14
10-14
Rows B & E for
848258679 & 848258687
& Rows A & D for
ED83019-50 G1*
405348178
8
8
406338400
6
6
406332841
6
6
Rows A, C, D, & F for
848258679 & 848258687
& Rows B & C for
ED83019-50 G1*
405332940
4
4
406338665
2
--
405348228
1/0
--
405348236
2/0
1/0
406021725
--
2/0
405348251
4/0
--
405347923
--
4/0
405348277
350
--
Rows C & F for
848258679 & 848258687
& Row C for
ED83019-50 G1*
406021915
--
350
405348293
500
--
406434241
--
500
406335141
750
--
405434290
--
750
847073756
Hardware Kit Bolt Size (8-32, 10-32, 10-24)
847073731
Hardware Kit bolt Size (3/8-16) (Grade 2)
* Refer to Figure 2-7.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 15
Digital Meters
and Monitoring
Shunts
As discussed in the previous sections, there are six possible load buses
in the 7-foot distribution bay, three per side, and eight possible load
buses in the 9-foot distribution bay, four per side. Each load bus is
equipped with an 800 ampere shunt per Group 20. Group 20 provides
two shunts, one for the left dc panel and one for the right dc panel.
Shunts are provided to determine actual current use and the remaining
capacity of each load bus. They can either be monitored externally by
other office equipment or in the distribution bay with a digital meter.
Two digital meters are available for monitoring the shunt currents and
the panel voltages: G-70 and G-71.
G-70
The G-70 digital meter monitors only the 800-ampere shunts (see
Figure 2-8. It is available for 24-, 48-, and 130-volt systems. The shunts
are wired to the meter through a rotary switch, enabling the user to
select any of the possible load buses. The meter is powered from the
first equipped panel position.
Note: If the power is lost to the first equipped panel position, the meter
will lose power as well.
Figure 2-8: G-70 Digital Meter
Rotary Switch
Meter Display
Stamping Area for
Load Designations
CURRENT (AMPERES)
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 16 Product Description
Issue 5 May 2000
Digital Meters and Monitoring Shunts, continued
G-71
The G-71 digital meter monitors the 800-ampere shunts, as well as each
distribution panel voltage (see Figure 2-9). It is available only for the
48-volt system. The shunts are wired to the meter through a rotary
switch, enabling the user to select any of the possible load buses. the
meter is powered from the load panel selected with the rotary switch. A
toggle switch is used to select voltage or current.
Note: If the power is lost to the panel selected with the rotary switch,
the meter will lose power as well.
Figure 2-9: G-71 Digital Meter
Meter Display
Rotary Switch
Stamping Area for
Load Designations
Voltage / Current
Toggle Switch
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 17
ED83127-30
Fuse Panels
Groups 30A-30D
Each fuse panel is equipped with 20 single position fuse blocks for TPS
fuses. If alternate fuse blocks are desired, they can be ordered
separately and installed in the field. Spare fuse holders are supplied
with the fuse panels.
The Group 30A-30D fuse panels shown in Figure 2-10 provide two
fuse panels, each with 20 3-70 ampere cartridge type fuse holders,
comcode 406686980. These fuse blocks are UL recognized and provide
a more compact design than previous fuse holders. The fuse block was
developed by USD (Underwriters Switching Devices) to accommodate
the WP-92461 series of fuses. These fuses offer a big advantage over
other fuse types in that they are UL recognized to UL standard 198L
“DC Industrial Fuses” and have a 170 Vdc, 100,000 ampere interrupt
rating.
Note: Each of the fuse panel groups (30A-30D) provides two fuse
panels, one for the right side and one for the left side.
ED83127-30 G-B (field installed) provides one GMT fuse module
containing three fuse positions. Each fuse position may be equipped
with a GMT fuse ranging from 1/2 to 5 amperes. The GMT fuse module
offers the customer the option of using the distribution bay for small
miscellaneous loads in the office that might otherwise require a
separate fuse panel.
ED83127-30 G-D (field installed) provides one 70-150A TPL type fuse
block. These fuse blocks occupy two positions within the fuse panel.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 18 Product Description
Issue 5 May 2000
ED83127-30 Fuse Panels, continued
Figure 2-10: H569-445 Group 30A-30D Fuse Panel
(One Shown; Two Are Provided Per Group)
Front
Back
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 19
ED83127-30 Fuse Panels, continued
Groups 31A and
31B
Groups 31A and 31B each provide two circuit breaker panels, one for
the left side and one for the right side of the bay. See Figure 2-11 (one
shown; two provided per group). Each circuit breaker panel has 20
positions. The circuit breakers are sized from 3 to 100 amperes. They
are UL listed. The breakers are rated at 80Vdc with a 10,000 amp
interrupt capacity. The ±130V option is not offered for circuit breaker
panels.
Figure 2-11: H569-445 Groups 31A and 31B
Circuit Breaker Panel
Front
Back
Circuit Breaker
(shown for reference)
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 20 Product Description
Issue 5 May 2000
Alarm Circuit
Module (BEP1)
The alarm circuit module, apparatus code A-CP/BEP1, provides a
means for indicating a power loss and a fuse or circuit breaker alarm for
each fuse or circuit breaker panel. Indications of these alarms are by
means of an LED and by contact closures.
The BEP1 pack will accept nominal input voltages of 24 and 48 volts.
Operation in ±130 volt distribution bay frames (not an option for circuit
breaker distribution frames) is achieved by addition of a dropping
resistor mounted on the fuse panel to drop the nominal 130 volt level to
the nominal 48 volt level.
The BEP1 alarm module is provided with the fuse or circuit breaker
panels. These groups describe the nominal voltage at which the fuse
(24, 48, or 130 volts) or circuit breaker panel will operate (24 or 48
volts). Figure 2-12 shows the layout of the alarm circuit module and
Figure 2-13 shows the input (P102) and output (P101) connector pin
descriptions. The alarm module provides two Form C contacts for
power loss and three Form C contacts for fuse or circuit breaker failure.
The alarm output connector references of audible, visual and remote
given with each alarm module are arbitrary and are provided as a
suggested standard for remote monitoring equipment. However,
installation personnel may select any set of Form C contacts.
When power loss to a panel occurs, a closure exists between pins 1 and
2 and pins 3 and 4 on the output connector (P101), while an open
condition exists between pins 1 and 9 and pins 3 and 10.
When a fuse or circuit breaker operates on a panel, a closure exists
between pins 8 and 15, pins 11 and 12, and pins 13 and 14 of connector
P101, while an open condition exists between pins 7 and 8, pins 6 and
12, and pins 5 and 13.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 21
Alarm Circuit Module (BEP1), continued
Figure 2-12: A-CP/BEP1 Board Layout
CR101
CR102
P102
CR103
BEP1
SER
SS4
DS101
DS102
SERIAL NUMBER
R104
K101
R101
P101
K102
R103
U101
R102
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 22 Product Description
Issue 5 May 2000
Alarm Circuit Module (BEP1), continued
Figure 2-13: A-CP/BEP1 Input/Output Connections
(Alarm Module With No Power Is in “Normal” State)
K101-4
K101-6
K101-13
K101-11
K102-6
K102-5
K102-11
K102-13
K101-8
K101-9
K102-7
K102-3
K102-4
K102-8
K102-9
C1
NO1
C2
NO2
NC1
NC2
NC3
C3
NC1
NC2
NO2
C2
C1
NO1
NO3
Closed
Closed
Open
Open
Open
Open
Open
Closed
Closed
Closed
Power Loss (Aud)
Power Loss (Aud)
Power Loss (Vis / Remote)
Power Loss (Vis / Remote)
FAJ (Aud)
FAJ (Vis)
FAJ (Remote)
FAJ (Remote)
Power Loss (Aud)
Power Loss (Vis / Remote)
FAJ (Vis)
FAJ (Vis)
FAJ (Aud)
FAJ (Aud)
FAJ (Remote)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Fuse/Circuit Breaker
Alarm Signal Input
To Succeeding BEP1
Fuse/Circuit Breaker
Alarm Signal Output
PWR (48V / 130V / 140V)
FAJ (24V)
FAJ (48V / 130V / 140V)
From Preceeding BEP1
or Frame Fuse/Circuit
Breaker Alarm
PWR (24V)
From Preceeding BEP1
or to External RTN Bus
To Succeeding BEP1
(W-Y)
(W-S)
(W-BL)
(W-BL)
(BL)
(Y)
(Y)
(W-Y)
(W-S)
(BL)
(BR)
(BR)
Pins 3 and 10
provide ABS to
each circuit pack.
Alarm State
Pins 2 and 9
send ABS to
light Frame Alarm.
P102
P101
Panel Alarm Input Connector
Remote Alarm Output Connector
Power Loss Relay, Normal Operating Condition:
Fuse Alarm Relay, Normal Operating Condition:
Open condition exists between pins 1 & 2, and pins 3 & 4.
Closed condition exists between pins 1 & 9, and pins 3 & 10.
When power loss occurs, the above conditions are reversed.
Open condition exists between pins 13 & 14, 11 & 12, and pins 8 & 15.
Closed condition exists between pins 5 & 13, pins 6 & 12, and pins 7 & 8.
When fuse alarm occurs, the above conditions are reversed.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 23
Alarm Circuit Module (BEP1), continued
Detailed Circuit
Description
The BEP1 consists of two monitoring circuits, one for panel power loss
and the other for fuse failures. These circuits are described as follows.
Power Input: DC power (24, 48, or 130 Vdc through external resistor)
is provided to P102 pins 11 or 6. Nominal input voltage to bridge
CR101 is 24 Vdc. Bridge CR101 allows the BEP1 to operate from
either positive or negative voltages. Output voltage of nominal 22 Vdc
from CR101 is applied to relay K101 and LED DS101. Relay K101 is
held normally operated and DS101 (green) is illuminated. Fuse or
circuit breaker alarm power is provided through P102 pins 7 or 8.
Bridge CR102 allows operation from either voltage polarity. CR102
output of 22 Vdc nominal is applied to relay K102 and LED DS102
(red). Fuse or circuit breaker alarm power is normally present only
when a fuse or circuit breaker blows and thus K102 is normally released
and DS102 is extinguished. The return path for the power monitor and
fuse or circuit breaker alarm monitor is through P102-12 & 14.
Power Loss Alarm: Loss of bus voltage will cause relay K101 to
release and LED DS101 (green) to extinguish. Two Form C contacts on
K101 are available through P101 to monitor for power loss.
Fuse or Circuit Breaker Alarm: A cleared fuse or circuit breaker will
apply power through P102 to operate relay K102 and illuminate LED
DS102 (red). Three Form C contacts on K102 are provided through
P101 for external alarms.
Frame Alarm: In addition to the individual panel alarm indicators,
there is a frame alarm lamp at the top of the bay. This frame alarm lights
when power is lost to a fuse or circuit breaker panel or there is a fuse or
circuit breaker alarm. Power for lighting the frame lamp is brought
from the battery plant on an auxiliary battery supply (ABS) lead. Figure
2-14 shows the frame alarm and ABS termination points at the top of
the cabinet. When ABS is from a positive ground battery plant, it is
brought into the distribution bay on terminal E3. This signal is daisy
chained through all the circuit modules. A fuse or circuit breaker failure
or power loss on a circuit module sends the ABS signal back up to the
frame lamp socket. The ABS return lead back to the battery plant is also
connected to the frame alarm lamp via terminal E4 to complete the
circuit.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 24 Product Description
Issue 5 May 2000
Alarm Circuit Module (BEP1), continued
Detailed Circuit
Description,
continued
In some installations, the use of a ABS lead from the battery plant may
not be available or desirable. An alternative alarming method
substitutes power from a load bus for ABS. A 22-gauge wire may be
run from the battery bus of fuse or circuit breaker panel number 1 to
terminal E3. The return lead from the frame lamp via terminal 4 would
go to the discharge return bus located on the cable rack. The obvious
consequence of this option is if power is lost to fuse or circuit breaker
panel number 1, the frame alarm will not light.
Figure 2-14: Frame Alarm
Option "Y" ABS
(Negative Ground System)
Option "Y" ABS RTN
(Negative Ground System)
202A
Term
202A
Term
E4
E3
(W-Y)
22 Ga.
(W-S)
22 Ga.
Option "X" ABS RTN
(Positive Ground System)
Option "X" ABS
(Positive Ground System)
To
(24, 48, or 130V)
Battery Plant
From
(24, 48, or 130V)
Battery Plant
To
Alarm Signaling
Circuit Modules
From
Alarm Signaling
Circuit Modules
407226786 Lens Cover
406156729 Lamp Socket
407226836 Lamp (24V)*
or
407227172 Lamp (48V)*
(factory installed)
or
407227164 Lamp for (130V)*
Install lamp type appropriate for
battery voltage of ABS lead.
*
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 25
Alarm Circuit Module (BEP1), continued
Monitoring
Multiple Alarm
Modules for
Negative Plants
In most distribution bay applications, customers require remote
monitoring of a frame, fuse or circuit breaker alarm only and not
individual load buses. Therefore, fuse or circuit breaker alarms on
multiple packs may be connected so that the remote fuse or circuit
breaker alarm signal on one pack can be operated from the other packs.
This daisy chain is factory wired so that frame fuse or circuit breaker
alarm may be monitored from the position 1 alarm module. A fuse or
circuit breaker alarm on any pack will cause current flow through
opto-isolator U101 causing it to turn on and apply voltage to P102 pins
4 and 5. Pins 4 or 5 are alternately connected from pack to pack
providing a common fuse or circuit breaker alarm output signal. The
position 1 alarm module monitors the other packs by connecting its
P102 pin 1 fuse or circuit breaker alarm input to P102 pin 4 of the
position 2 alarm module. See Figure 2-15. Thus voltage from any pack
with an active fuse or circuit breaker alarm will cause K102 of the
position 1 pack to be operated via P102 pin 1, causing an alarm on its
P101 contacts. This feature is intended to provide a local visual
indication of a fuse or circuit breaker alarm (DS102 of the pack with the
alarm) and remote monitoring of the Form C contacts of a single alarm
module. All packs will alarm independently by simply disconnecting
pin 1.
Figure 2-15: P102 Factory Alarm Wiring
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
14
14
14
14
1
2
3
4
5
6
7
8
Monitored PWB
From Frame
Alarm LED
To Frame Alarm
Terminal E3
Refer to Figure
2-13 for specific
connector pin
details.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 26 Product Description
Issue 5 May 2000
Alarm Circuit Module (BEP1), continued
Monitoring
Multiple Alarm
Modules for
Negative Plants,
continued
Remote monitoring of power loss is furnished for individual fuse or
circuit breaker panels. However, power loss alarms will probably not be
remotely monitored in most applications because loss of power in a
distribution bay usually results in a number of other simultaneous
alarms from the battery plant and load equipment. If power loss alarm
for the entire cabinet is desired, the installer must connect the alarm
module output pins P101 - 1, 2, 3, 4, (close on alarm) or 1, 3, 9, 10 (open
on alarm) as shown in Figure 2-16. The connections can be made with
26-gauge solid wire soldered or wire-wrapped to the 405095043 output
connectors. These connectors are furnished with each alarm module.
Figure 2-16: P101 Frame Power Loss Alarm Wiring
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
1
2
3
4
5
6
7
8
Refer to Figure
2-13 for specific
connector pin
details.
Open on Alarm
Power Loss (Aud)
Close on Alarm
Power Loss (Aud)
Open on Alarm
Power Loss
(Vis/Remote)
Close on Alarm
Power Loss
(Vis/Remote)
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
1
2
3
4
5
6
7
8
Monitored PWB
Refer to Figure
2-13 for specific
connector pin
details.
Close on Alarm Wiring
Open on Alarm Wiring
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Description 2 - 27
Alarm Circuit Module (BEP1), continued
Monitoring
Multiple Alarm
Modules for
Positive Plants
Opto-isolator U101 is current-direction sensitive. Therefore, remote
monitoring of frame alarms for positive plants is wired differently than
for negative plants. For positive plants, fuse alarms on multiple packs
should be daisy-chained together via P101. This allows the remote fuse
or circuit breaker alarm signal on any pack to be monitored from the
position 1 alarm module. Three Form C contacts are provided. They
must be connected to alarm module output pins on connector P101 - 5,
6, 7, 8, 11, 12, 13, 14, and 15 (see Figure 2-17). The connections can be
made with 26-gauge solid wire and wire-tapped to the 405095043
output connector provided with each alarm module.
Figure 2-17: Fuse or Circuit Breaker Alarm Wiring
for Positive Plant P101
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
1
2
3
4
5
6
7
8
Monitored PWB
Refer to Figure
2-13 for specific
connector pin
details.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
2 - 28 Product Description
Issue 5 May 2000
Alarm Circuit Module (BEP1), continued
Reference Data
Input Voltage: 24V (21 to 30 Vdc), 48V (42 to 60 Vdc)
Current Drain: 12 milliamps normal operation, 22 milliamps with
fuse or circuit breaker alarm.
Functional Designations:
R101
Dropping resistor 48V to 24V, power monitor
R102
LED current limit resistor, power monitor
R103
Dropping Resistor 48V to 24V, fuse alarm
R104
LED current limit resistor, fuse alarm
U101
Opto-isolator, remote fuse alarm
K101
Relay, 24V, power monitor
K102
Relay, 24V, fuse alarm
CR101
Diode bridge, power monitor
CR102
Diode bridge, fuse alarm
CR103
Voltage blocking diode
DS101
Green power LED
DS102
Red fuse alarm LED
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Safety 3 - 1
3
Safety
Safety
Statements
Please read and follow all safety instructions and warnings before
installing, maintaining, or repairing the power system. Reference the
individual module product manuals for additional safety statements
specific to the modules.
•
The H569-445 Secondary DC Power Distribution Bay is
Underwriters Laboratories (UL) Listed per: Subject Letter 1801
(DC Power Distribution Centers for Telecommunications
Equipment) for use in the USA.
•
Install only in restricted access areas (dedicated equipment rooms,
equipment closets, or the like) in accordance with articles 110-16,
110-17, and 110-18 of the U.S. National Electrical Code (NEC),
ANSI/NFPA No. 70, and pursuant to applicable local codes.
•
This equipment is to be used in controlled environments (an area
where the humidity is maintained at levels that cannot cause
condensation on the equipment, the contaminating dust is
controlled, and the steady-state ambient temperature is within the
range specified).
•
This equipment has been evaluated for use in a continuous ambient
temperature of up to 113° Fahrenheit (45° Celsius).
•
This equipment must not be installed over combustible surfaces.
•
For installations in the U.S. and Canada, Listed/Certified
compression connectors are to be used to terminate Listed/
Certified field-wired conductors where required. For all
installations, the appropriate connector is to be applied only to the
correct size conductor as specified by the connector manufacturer
using only the connector manufacturer's recommended tooling or
tooling approved for that connector.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
3 - 2 Safety
Issue 5 May 2000
Safety Statements, continued
•
If the proper connector for the country of installation is not
provided, obtain appropriate connectors and follow manufacturer's
and all local requirements for proper connections. All national and
local rules and regulations are to be followed when making field
connections.
•
The field wiring connections have been evaluated for connection
of minimum 90°C conductors sized per the U.S. National
Electrical Code using 75°C ampacity tables.
•
Torque electrical connections to the values specified on labels or in
the product documentation.
•
Battery input cables must be dressed to avoid damage to the
insulation (caused by routing around sharp edges or routed in areas
where wires could get pinched) and undue stress on the
connectors.
•
The short circuit current capability of the battery input to the
distribution panel must not exceed 10,000 amperes.
•
Fuses/circuit breakers may not be provided with the equipment.
Refer to the product documentation for the proper hardware. Use
only the parts specified in the equipment documentation. Installing
fuses or circuit breakers not specified for use in this equipment
may result in injury to service personnel or equipment damage.
•
External loading must not exceed 80% of its fuse/circuit breaker
current rating.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Safety 3 - 3
Warning
Statements and
Safety Symbols
The symbols may sometimes be accompanied by some type of
statement; e.g., “Hazardous voltage/energy inside. Risk of injury. This
unit must be accessed only by qualified personnel.”
This symbol identifies the need to refer to
the equipment instructions for important
information.
These symbols (or equivalent) are used to
identify the presence of hazardous ac
mains voltage.
This symbol is used to identify the
presence of hazardous ac or dc voltages. It
may also be used to warn of hazardous
energy levels.
This symbol is used to identify the need
for safety glasses and may sometimes be
accompanied by some type of statement,
for example: “Fuses can cause arcing and
sparks. Risk of eye injury. Always wear
safety glasses.”
One of these two symbols (or equivalent)
may be used to identify the presence of
rectifier and battery voltages. The symbol
may sometimes be accompanied by some
type of statement, for example: “Battery
voltage present. Risk of injury due to high
current. Avoid contacting conductors with
uninsulated metal objects. Follow safety
precautions.”
Lucent Technologies Secondary DC Power Distribution Bay H569-445
3 - 4 Safety
Issue 5 May 2000
Warning Statements and Safety Symbols, continued
The symbols may sometimes be accompanied by some type of
statement; e.g., “Hazardous voltage/energy inside. Risk of injury. This
unit must be accessed only by qualified personnel.”
This symbol is used to identify the
presence of a hot surface. It may also be
accompanied by a statement explaining
the hazard. A symbol like this with a
lightning bolt through the hand also
means that the part is or could be at
hazardous voltage levels.
This symbol is used to identify the
presence of a hot surface. The marked
item should not be touched without taking
care.
This symbol is used to identify the
protective safety earth ground for the
equipment.
This symbol is used to identify other
bonding points within the equipment.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Safety 3 - 5
Precautions
When working on or using this type of equipment, the following
precautions should be noted:
•
This unit must be installed, serviced, and operated only by skilled
and qualified personnel who have the necessary knowledge and
practical experience with electrical equipment and who understand
the hazards that can arise when working on this type of equipment.
•
Hazardous energy and voltages are present in the unit and on the
interface cables that can shock or cause serious injury. Follow all
safety warnings and practices when servicing this equipment.
Exercise care when servicing this area.
•
Batteries may be connected in parallel with the output of the
rectifiers. Turning off the rectifiers will not necessarily remove
power from the bus. Make sure the battery power is also
disconnected and/or follow safety procedures while working on
any equipment that contains hazardous energy/voltage.
•
In addition to proper job training and safety procedures, the
following are some basic precautions that should always be used:
–
Use only properly insulated tools.
–
Remove all metallic objects (key chains, glasses, rings,
watches, or other jewelry).
–
Wear safety glasses. Fuses can produce sparks. High energy
levels on buses and distribution components can produce
severe arcing.
–
Test circuits before touching.
–
Lock out and tag circuit breakers/fuses when possible to
prevent accidental turn on.
–
Be aware of potential hazards before servicing equipment.
–
Identify exposed hazardous electrical potentials on connectors,
wiring, etc. (note the condition of these circuits, especially
wiring).
–
Use care when removing or replacing covers; avoid contacting
circuits.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Warranty 4 - 1
4
Product Warranty
A. Seller warrants to Customer only, that:
1. As of the date title to Products passes, Seller will have the
right to sell, transfer, and assign such Products and the title
conveyed by Seller shall be good;
2. Upon shipment, Seller’s Manufactured Products will be free
from defects in material and workmanship, and will conform
to Seller’s specifications or any other agreed-upon
specification referenced in the order for such Product;
3. With respect to Vendor items, Seller, to the extent permitted,
does hereby assign to Customer the warranties given to Seller
by its Vendor of such Vendor Items, such assignment to be
effective upon Customer’s acceptance of such Vendor Items.
With respect to Vendor items recommended by Seller in its
specifications for which the Vendor's warranty cannot be
assigned to Customer, or if assigned, less than Sixty (60) days
remain of the Vendor's warranty or warranty period when the
Vendor's items are shipped to Customer or when Seller
submits its notice of completion of installation if installed by
Seller, Seller warrants that such Vendor's items will be free
from defects in material and workmanship on the date of
shipment to Customer. In such an event, the applicable
Warranty Period will be sixty (60) days.
B. The Warranty Period listed below is applicable to Seller’s
Manufactured Products furnished pursuant to this Agreement,
unless otherwise stated:
Lucent Technologies Secondary DC Power Distribution Bay H569-445
4 - 2 Product Warranty
Issue 5 May 2000
C. If, under normal and proper use during the applicable Warranty
Period, a defect or nonconformity is identified in a Product and
Customer notifies Seller in writing of such defect or
nonconformity promptly after Customer discovers such defect or
nonconformity, and follows Seller's instructions regarding return
of defective or nonconforming Products, Seller shall, at its option
attempt first to repair or replace such Product without charge at its
facility or, if not feasible, provide a refund or credit based on the
original purchase price and installation charges if installed by
Seller. Where Seller has elected to repair a Seller’s Manufactured
Product (other than Cable and Wire Products) which has been
installed by Seller and Seller ascertains that the Product is not
readily returnable for repair, Seller will repair the Product at
Customer’s site.
With respect to Cable and Wire Products manufactured by Seller
which Seller elects to repair but which are not readily returnable
for repair, whether or not installed by Seller, Seller at its option,
may repair the cable and Wire Products at Customer’s site.
D. If Seller has elected to repair or replace a defective Product,
Customer shall have the option of removing and reinstalling or
having Seller remove and reinstall the defective or
nonconforming Product. The cost of the removal and the
reinstallation shall be borne by Customer. With respect to Cable
and Wire Products, Customer has the further responsibility, at its
expense, to make the Cable and Wire Products accessible for
repair or replacement and to restore the site. Products returned for
repair or replacement will be accepted by Seller only in
accordance with its instructions and procedures for such returns.
Warranty Period
Product Type
New Product
Repaired Product
or Part*
Central Office
Power
Equipment**
24 Months
6 Months
* The Warranty Period for a repaired Product or part thereof
is as listed or, in the case of Products under Warranty, is the
period listed or the unexpired term of the new Product
Warranty Period, whichever is longer.
** The Warranty Period for Products ordered for Use in
Systems or equipment Manufactured by and furnished by
Seller is that of the initial Systems or equipment.
Lucent Technologies Secondary DC Power Distribution Bay H569-445
Issue 5 May 2000
Product Warranty 4 - 3
The transportation expense associated with returning such
Product to Seller shall be borne by Customer. Seller shall pay the
cost of transportation of the repair or replacing Product to the
destination designated by Customer within the Territory.
E. The defective or nonconforming Products or parts which are
replaced shall become Seller's property.
F. If Seller determines that a Product for which warranty service is
claimed is not defective or nonconforming, Customer shall pay
Seller all costs of handling, inspecting, testing, and transportation
and, if applicable, traveling and related expenses.
G. Seller makes no warranty with respect to defective conditions or
nonconformities resulting from actions of anyone other than
Seller or its subcontractors, caused by any of the following:
modifications, misuse, neglect, accident, or abuse; improper
wiring, repairing, splicing, alteration, installation, storage, or
maintenance; use in a manner not in accordance with Seller’s or
Vendor’s specifications or operating instructions, or failure of
Customer to apply previously applicable Seller modifications and
corrections. In addition, Seller makes no warranty with respect to
Products which have had their serial numbers or month and year
of manufacture removed, altered, or with respect to expendable
items, including, without limitation, fuses, light bulbs, motor
brushes, and the like.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND ARE
IN LIEU OF ALL OTHER EXPRESS AND IMPLIED
WARRANTIES, INCLUDING BUT NOT LIMITED TO
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. CUSTOMER’S SOLE AND
EXCLUSIVE REMEDY SHALL BE SELLER’S OBLIGATION TO
REPAIR, REPLACE, CREDIT, OR REFUND AS SET FORTH
ABOVE IN THIS WARRANTY.
© 2000 Lucent Technologies
All Rights Reserved
Printed in U.S.A.