Lucent Technologies I Series Product Manual
Text of the manual
IR-30EC and IR-40EC
Series I Batteries
KS-23815
Product Manual
Select Code 157-622-020
Comcode 107078859
Issue 7
November 1998
© 1998 Lucent Technologies
Select Code 157-622-020
Comcode 107078859
Issue 7
November 1998
Lucent Technologies
IR-30EC and IR-40EC
Series I Batteries
Notice:
Every effort was made to ensure that the information in this
document was complete and accurate at the time of printing.
However, information is subject to change.
© 1998 Lucent Technologies
All Rights Reserved
Printed in U.S.A.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Table of Contents - 1
Table of Contents
1
Introduction
IR-30EC and IR-40EC Batteries
1 - 1
Customer Training
1 - 3
Customer Service
1 - 3
Technical Support
1 - 3
Product Repair and Return
1 - 3
Warranty Service
1 - 3
2
Product Description
Overview
2 - 1
Features
2 - 1
Specifications
2 - 2
3
Ordering Information
Batteries
3 - 1
4
Safety and Environmental
Safety Symbols
4 - 1
Safety Precautions
4 - 1
Poison
4 - 1
Electrical Hazard
4 - 3
Battery Gases
4 - 4
First Aid
4 - 6
Lifting Information
4 - 6
Transportation and Handling
4 - 6
Environmental
4 - 6
5
Battery Storage
State of New Battery
5 - 1
Storage Conditions
5 - 1
Storage Time
5 - 1
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
2 - Table of Contents
Issue 7 November 1998
6
Installation
Introduction
6 - 1
Installation Tools, Materials, and Test Equipment
6 - 1
Product Manual
6 - 1
Unpacking and Handling
6 - 2
Specific Unpacking Instructions
6 - 2
Battery String Location
6 - 4
Environmental Requirements
6 - 4
Mixing Batteries in a String
6 - 5
Mixing Parallel Strings of Batteries
6 - 5
Constant Current, Separate Chargers
6 - 5
Constant Voltage Chargers
6 - 5
Battery Installation
6 - 5
Initial Charging
6 - 6
Placing a Battery String Into Service
6 - 8
Installation Records
6 - 8
Voltage Measurements
6 - 8
7
Operation
Lead-acid Battery Gassing Rate
7 - 1
Service Life
7 - 2
Charging
7 - 3
Battery String Float Voltage
7 - 3
Charging Voltage Ripple
7 - 3
Battery and Ambient Temperatures
7 - 4
Capacity
7 - 5
Discharge Capacity Test
7 - 5
Recharge After Discharge
7 - 6
Boost Charge
7 - 7
8
Maintenance
Maintenance Schedule
8 - 1
Maintenance Routines
8 - 2
Individual Battery Voltages
8 - 2
Measuring Battery Temperatures
8 - 3
String Current Measurement
8 - 3
Inspection and Cleaning
8 - 3
Retorquing Inter-battery Connections
8 - 3
Flame Arrestor Vent Feature
8 - 3
Battery Replacement
8 - 4
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Table of Contents - 3
9
Discharge and Power Data
Discharge Capacity
9 - 1
Discharge Cycle Life
9 - 1
10
Installation and Maintenance Record
11
Material Safety Data Sheet
12
Product Warranty
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
List of Figures - 1
List of Figures
Figure 1-1: IR-30EC Battery
1 - 2
Figure 1-2: IR-40EC Battery
1 - 2
Figure 7-1: Temperature Versus Battery Capacity
(within 5%) for IR-30EC/40EC
7 - 5
Figure 9-1: Discharge Current (within 5%) vs.
Discharge Duration to 10.5V
(IR-30EC and IR-40EC)
9 - 2
Figure 9-2: Discharge Power (within 5%) vs.
Discharge Duration to 10.5V
(IR-30EC and IR-40EC)
9 - 3
Figure 9-3: Characteristic Discharge Curves
(within 5%) for IR-30EC
9 - 4
Figure 9-4: Constant Power Capacity for IR-30EC
9 - 4
Figure 9-5: Characteristic Discharge Curves
(within 5%) for IR-40EC
9 - 5
Figure 9-6: Constant Power Capacity for IR-40EC
9 - 5
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
List of Tables - 1
List of Tables
Table 2-A: IR-30EC and IR-40EC Battery Specifications 2 - 2
Table 3-A: IR-30EC and IR-40EC Batteries Ordering
Information
3 - 1
Table 3-B: Non-Standard Parts for IR-30EC and
IR-40EC Batteries
3 - 2
Table 6-A: Initial Charging
6 - 7
Table 8-A: Required Maintenance Routines
8 - 1
Table 9-A: Battery Discharge Amperes (within 5%)
for IR-30EC at 25°C (77°F)
9 - 6
Table 9-B: Battery Discharge Wattage (within 5%)
for IR-30EC at 25°C (77°F)
9 - 6
Table 9-C: Battery Discharge Amperes (within 5%)
for IR-40EC at 25°C (77°F)
9 - 7
Table 9-D: Battery Discharge Wattage (within 5%)
for IR-40EC at 25°C (77°F)
9 - 7
Table 12-A: New Battery Warranty Period and
Conditions
12 - 1
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Introduction 1 - 1
1
Introduction
IR-30EC and
IR-40EC
Batteries
This product manual (Select Code 157-622-020) provides
information on Lucent Technologies IR-30EC and IR-40EC
Series I batteries. The IR-30EC and IR-40EC batteries are
12-volt, stationary, valve-regulated, rechargeable, lead-acid
batteries, which are backed by Bell Laboratories, an
acknowledged leader in technology, research, and design of
power systems.
Lucent Technologies’ power products have proved their field
reliability by providing dependable standby reserve power for
the telecommunications industry for decades. All battery
components and manufacturing processes meet Lucent
Technologies’ strict specifications and quality standards.
Designed for applications where the loads are fairly small,
temperatures may vary, and long back-up time is desired,
IR-30EC and IR-40EC Series I batteries are an excellent choice
for subscriber loop, customer premises, and distributed power
cabinets.
Figures 1-1 and 1-2 illustrate the IR-30EC and IR-40EC Series I
batteries.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
1 - 2 Introduction
Issue 7 November 1998
Figure 1-1: IR-30EC Battery
Lucent
6.75 in.
(17.5 cm)
5.13 in.
(13.02 cm)
7.00 in.
(17.78 cm)
Figure 1-2: IR-40EC Battery
5.13 in.
(13.02 cm)
8.31 in.
(21.1 cm)
Lucent
7.00 in.
(17.78 cm)
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Introduction 1 - 3
Customer
Training
Lucent Technologies offers customer training on many Power
Systems products. For information call 1-972-284-2163. This
number is answered from 8:00 a.m. until 4:30 p.m., Central Time
Zone (Zone 6), Monday through Friday.
Customer
Service
For customers in the United States, Canada, Puerto Rico, and the
US Virgin Islands, call 1-800-THE-1PWR (1-800-843-1797).
Services provided through this contact include initiating the
spare parts procurement process for out of service emergencies,
ordering Lucent Technologies documents, and providing other
product and service information.
For other customers worldwide, call 001-972-840-0382. This
number is answered from 8:00 a.m. until 4:30 p.m., Central Time
Zone (Zone 6), Monday through Friday.
Technical
Support
Technical support for Lucent Technologies customers is
available around the world during the normal product warranty
period and also while specific contractual agreements extend
this service.
For customers in the United States, Canada, Puerto Rico, and the
US Virgin Islands, call 1-800-CAL-RTAC (1-800-225-7822) to
contact a product specialist to answer your technical questions
and assist in troubleshooting problems.
For other customers worldwide, contact your local field support
center or your sales representative to discuss your specific needs.
Product Repair
and Return
Repair and return service is provided for Lucent Technologies
customers around the world. For customers in the United States,
Canada, Puerto Rico, and the US Virgin Islands, call
1-800-255-1402 for information on returning of products for
repair.
For other customers worldwide, contact your sales
representative to discuss your particular circumstances.
Warranty
Service
For warranty service worldwide, contact your Warranty Service
Manager (WSM). The WSM serves specific customer-groups,
who have taken ownership of the product. For product
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
1 - 4 Introduction
Issue 7 November 1998
conformance issues prior to customer ownership, contact your
local customer service.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Product Description 2 - 1
2
Product Description
Overview
Lucent Technologies IR Series I batteries are configured in two
different ampere-hour capacities that are engineered to meet
specific and often unique application requirements: IR-30EC
and IR-40EC.
The valve-regulated design and construction of the IR-30EC and
IR-40EC batteries prevents electrolyte leakage and minimizes
water loss and maintenance throughout the design life. During
normal operation, oxygen is generated at the positive electrode
and hydrogen is generated at the negative electrode. In
conventional (flooded) lead-acid cells, these electrochemical
reactions result in water loss from the electrolyte. The
self-resealing pressure release safety valves in IR-30EC and
IR-40EC batteries are designed to aid in the electrochemical
recombination of nearly all the oxygen within the battery. In
addition, the safety valves prevent the build-up of excessive
internal pressure.
The IR-30EC and IR-40EC batteries comply with the
requirement for sealed battery/cell pressure release test of
UL1989, Standard for Standby Batteries.
Features
•
High energy density
•
Leak-resistant post seals
•
Flame arrestor
•
Flame-retardant 94-V0 polypropylene container and cover
•
Metal sleeve
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
2 - 2 Product Description
Issue 7 November 1998
Specifications
Table 2-A: IR-30EC and IR-40EC Battery Specifications
IR
Series I
Nominal
Voltage
Nominal
Ampere
Hours at
8-hour Rate
Charging
Method
Maximum
Dimensions
WxDxH
Weight
IR-30EC
12
25
Constant Voltage/
Constant Current
6.75 x 5.13 x 7.0 in.
17.2 x 13.0 x 17.8 cm
24 lbs.
10.9 kg
IR-40EC
12
34
Constant Voltage/
Constant Current
8.31 x 5.13 x 7.0 in.
21.1 x 13.0 x 17.8 cm
32 lbs.
14.5 kg
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Ordering Information 3 - 1
3
Ordering Information
Batteries
Table 3-A: IR-30EC and IR-40EC Batteries Ordering Information
Comcode
Model No.
Description
407928761
IR-30EC Battery
12V, 25Ah battery with standard 14 AWG lead
assembly terminating with 350537-6 AMP
contacts and a 1-480698-0 AMP
2-terminal plug
407976182*
IR-30EC Battery
equipped with
heavy-duty cable
12V, 25Ah battery equipped with 847307436
heavy-duty 10 AWG cable and 4-terminal plug
407928753
IR-40EC Battery
12V, 34Ah battery with standard 14 AWG lead
assembly terminating with 350537-6 AMP
contacts and a 1-480698-0 AMP 2-terminal plug
407976190*
IR-40EC Battery
equipped with
heavy-duty cable
12V, 34Ah battery equipped with 847307436
heavy-duty 10 AWG cable and 4-terminal plug
*Lucent Technologies IR-30EC and IR-40EC batteries are provided with a 14 AWG
lead assembly terminating with AMP #350537-6 contacts and an AMP #1-480698-0
plug as standard equipment. The standard lead assembly was designed to be
compatible with Lucent Technologies SLC 96 and SLC Series 5 applications where
reserve power of 5 hours or longer duration is required. The standard assembly may
not be suitable for applications where the battery load exceeds the 5-hour rate, and may
fail catastrophically at battery charge/discharge currents exceeding 18 amperes.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
3 - 2 Ordering Information
Issue 7 November 1998
Table 3-B: Non-Standard Parts for IR-30EC and IR-40EC Batteries
Comcode/
J-Code
Model No.
Description
846861664
Interbattery bus bar
Interbattery bus bar to connect IR-30EC and
IR-40EC batteries within a string
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Safety and Environmental 4 - 1
4
Safety and Environmental
Safety Symbols
Safety
Precautions
Read the following safety precautions carefully before
attempting to handle, unpack, and install the batteries. Fully
brief everyone with access to battery areas, or who are working
near or with batteries, on the hazards associated with lead-acid
batteries. Additional information can be found in the Material
Safety Data Sheet (MSDS) in Section 11 of this product manual.
Poison
HIGH VOLTAGE...
RISK OF SHOCK.
DO NOT TOUCH
UNINSULATED
TERMINALS OR
CONNECTORS.
SHIELD
EYES.
SHIELD
EYES.
EXPLOSIVE
GASES CAN CAUSE
BLINDNESS OR INJURY.
GASES
NO
SPARKS
FLAMES
SMOKING
SULFURIC
ACID
CAN CAUSE
BLINDNESS OR
SEVERE BURNS.
FLUSH EYES
IMMEDIATELY
WITH
WATER.
GET
MEDICAL
HELP FAST.
DANGER
POISON
CAUSES SEVERE BURNS
Valve-regulated batteries contain toxic materials (lead, lead
compounds, and sulfuric acid). Do not incinerate or
mutilate. Avoid contact with skin, eyes, or clothing.
Recycle batteries in approved reclamation centers
according to local, state, and federal regulations.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
4 - 2 Safety and Environmental
Issue 7 November 1998
All lead-acid batteries contain electrolyte (sulfuric acid and
water), a highly corrosive substance. Lucent Technologies
valve-regulated batteries are designed so that the electrolyte is
absorbed by the plates and separators. Electrolyte ordinarily
should not leak outside the battery container. However, it is
possible that certain types of physical damage and/or abusive
charging may force small quantities of electrolyte outside the
battery container.
Lucent Technologies valve-regulated batteries are safe;
however, accidents can occur.
•
When handling batteries or cells, wear protective equipment
(e.g., acid resistant rubber gloves, acid resistant rubber
aprons, and impact-resistant, splash-proof goggles or full
face mask).
•
Even when not handling batteries, wear splash-proof and
impact-resistant goggles while working around batteries or
on equipment containing batteries.
The MSDS in Section 11 contains information that everyone
needs to understand before having access to the batteries, such
as: health hazard summary, first aid procedures, fire and
explosion hazard data, reactivity data, special protection
information, environmental information (spill clean-up and
disposal), and special precautions.
The following items can be ordered from Lucent Technologies.
These items should be available to anyone working around
batteries. The local, state, or federal codes for certain
installations may require some of these items to be installed
and/or kept at the installation site.
•
Protective gear
•
Acid spill clean-up and management kits
•
Battery cleaning and maintenance kits
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Safety and Environmental 4 - 3
Electrical Hazard
Batteries differ from other sources of power in that they are
delivered to the points of installation as live units. A battery
gives no indication by its appearance of the potential energy
stored in it. Batteries have enormous short circuit capability that
can result in serious burns or create dangerous projectiles from
the object causing the short circuit.
•
Exercise extreme care to avoid any short circuits across the
battery terminals.
•
In a grounded battery system, use extreme care not to short
any metal objects from the ungrounded battery terminal to
ground (which can include the equipment metal chassis,
building structure, cable racks, etc.).
•
Even a single battery poses a potentially high energy hazard
if shorted. Shorting a battery may result in explosion of the
battery, injury to personnel, and damage to equipment. A
tool or other metal object causing the short may be thrown
or vaporized due to the energy produced by the battery or
system.
WARNING
ELECTRICAL HAZARD
In addition to proper job training and safety procedures, the
following are some basic precautions that should always be
followed when working with or around batteries (including
equipment connected to batteries):
•
Always use insulated tools.
•
Never place uninsulated metal objects on top of a
battery.
•
Remove all metal jewelry such as rings, watches,
bracelets, long necklaces, and any other metallic items.
•
Do not short circuit the battery.
•
Insure proper polarity when making connections.
•
Wear eye protection.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
4 - 4 Safety and Environmental
Issue 7 November 1998
A single battery is typically at low voltage; however, batteries
connected together in a system can pose a shock hazard in
addition to an energy hazard. When interconnection of the
batteries creates a hazardous voltage supply, post appropriate
warnings in the end systems or installations. All systems and/or
installations should consider the need for additional markings
based on the use of the battery, industry standards, and local,
state, and federal regulations.
Battery Gases
Valve-regulated batteries are designed to minimize the amount
of oxygen and hydrogen gas released from the battery under
normal conditions. However, abnormal conditions, such as high
temperature, abnormal charging, shorted cells, etc., can produce
greater amounts of gas. Even batteries under open circuit
conditions can produce gas. If not permitted to escape, this gas
can build up to explosive concentrations. Refer to Section 7,
Operation, for more information on gassing rates.
•
ALWAYS place batteries in a well-ventilated area.
•
NEVER place batteries in a sealed enclosure.
•
Make sure the area is properly ventilated before performing
any work.
•
Since gas generated by batteries is explosive, avoid creating
sparks (including those from static electricity), the use of an
open flame, or smoking near the batteries.
DANGER
RISK OF EXPLOSION
•
Battery gases can be highly explosive. NO sparks,
including sparks generated by electrostatic discharge
(ESD), or open flame are allowed near battery modules.
Do not smoke around batteries. Make sure the battery
area is properly ventilated before performing any work.
•
Do not place batteries in a sealed enclosure. Even
enclosures with ventilation need to be properly
evaluated to assure hydrogen will not accumulate to
explosive levels.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Safety and Environmental 4 - 5
•
Before performing any work operation, follow proper ESD
protection procedures to discharge the static electricity from
your body.
•
Never tamper with or block the vent caps of batteries.
Damaged or clogged vent caps may result in an explosion
due to excessive internal pressure. Such an explosion could
short circuit other battery modules, result in a fire, injure
personnel, or cause damage to equipment.
•
Never charge a battery that is visibly damaged or frozen
(typically at temperatures less than -40°C or -40°F).
•
Be alert to procedures that may create potential hazards,
such as creating sparks next to the batteries. Some
examples:
–
Avoid disconnecting the circuit at the battery terminals
while the battery is being discharged or charged.
–
Avoid making connections at the battery terminal with
the other end connected to a load or charging system
(unless the circuit has been verified to be open).
–
If there are no devices for opening the circuit before
disconnecting or connecting the battery, here are some
suggested procedures:
•
Make sure the free end of any wire connected to the
batteries is insulated until it is ready to be connected
to the load or charger or immediately after being
disconnected from the load or charger.
•
Connect to the battery terminals first before
connecting to the load or charging system.
•
Disconnect at the load or charger first before
disconnecting at the battery terminals.
Freshly charged batteries may produce explosive gas.
•
Avoid handling a freshly charged battery within 24 hours
after removing the charge. If it must be handled, use
extreme caution and avoid any sparks or touching the
battery in the area of the vents.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
4 - 6 Safety and Environmental
Issue 7 November 1998
To direct attention to the possible source of danger from battery
gases, post one or more warning signs, lettered in large
characters, in a conspicuous location near the batteries.
First Aid
Refer to the MSDS in Section 11 for first aid procedures.
Lifting
Information
Refer to “Unpacking and Handling” in the Installation section of
this product manual for specific handling instructions.
Transportation
and Handling
New batteries are shipped meeting United Nations standard,
DOT, IATA, IMDG, and other State and Government
regulations.
Old/used batteries should be considered as Hazardous Waste and
transported according to respective DOT, EPA, OSHA, and
other governing regulations or guidelines for Hazardous Waste.
Environmental
Do not discard batteries in trash cans.
Pb
Pb
Valve regulated batteries contain lead, lead compounds, and
sulfuric acid. Recycle batteries in approved reclamation
centers according to local, state, and federal regulations.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Battery Storage 5 - 1
5
Battery Storage
State of New
Battery
The IR-30EC and IR-40EC batteries are shipped in the charged
state. The open circuit voltage for a fully charged battery is
2.14-2.16V/cell.
Storage
Conditions
•
Store batteries in an upright position in a dry and cool
environment without exposure to direct sunlight.
•
Provide adequate ventilation during storage.
•
Do not stack pallets of batteries on top of each other during
storage.
Storage Time
Batteries may suffer irreversible capacity loss during long open
circuit stand. The maximum that a charged battery may remain
on open circuit is 6 months at 77°F. The open circuit time should
not exceed 3 months if the storage temperature exceeds 90°F.
The “charge by” date stamped on the shipping container is the
date the battery has been on open circuit for 6 months. If
batteries cannot be installed within this time period, follow the
procedures outlined in Table 6-A, “Initial Charging,” and record
the actions taken until normal installation can be initiated.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation 6 - 1
6
Installation
Introduction
This section describes the procedures for installing the IR-30EC
and IR-40EC batteries. Please review the safety precautions in
Section 4 before handling the batteries.
Installation
Tools,
Materials, and
Test Equipment
The following tools, materials, and test equipment are
recommended for installation, operation, maintenance, and
testing of the batteries:
•
Chemical and impact resistant safety goggles and safety
hard hat
•
Acid resistant gloves, rubber overshoes, and apron
•
Lime and/or soda (sodium bicarbonate or sal soda)
•
Class C fire extinguisher
•
Cleaning cloth
•
Insulated socket and a torque wrench capable of measuring
40 inch pounds
•
Insulated nut driver
•
Combination wrench set, screwdrivers
•
Sandpaper or abrasive cloth
•
Thermocouple-based or infrared-based temperature
measuring device
•
Digital multimeter (DMM) with an accuracy of 0.05 percent
on the dc scale
•
DC power source capable of supplying a minimum of 15V
per battery times the number of batteries in a string
Product Manual
One product manual is included with each pallet of batteries.
Order additional product manuals by calling Customer Service
at 1-800-THE-1PWR (1-800-843-1797). Specify Select Code
157-622-020.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
6 - 2 Installation
Issue 7 November 1998
Unpacking and
Handling
Use appropriate material handling equipment to ensure
personnel safety and equipment protection while installing the
batteries. Move crated batteries to a convenient predetermined
area where the appropriate unpacking and handling equipment
and tools are available.
Specific
Unpacking
Instructions
Inspect the battery visually for shipping damage before it is
completely unpacked. If it is determined that the battery should
be returned to the manufacturer, it will be easier to return at this
point than if the battery has been completely unpacked.
1. Examine the shipping container and record any signs of
external damage.
2. Search for any indications of acid spillage during
shipment. Record any indications of acid spillage on the
bill of lading before signing.
In case of acid spillage, refer to the Material Safety Data
Sheet in Section 11 for instructions regarding cleanup and
disposal. After unpacking, immediately check again for
electrolyte spills.
3. Check batteries for fractured jars and covers. Batteries
with fractured jars and covers are defective and must not
be used.
Note
Acid spillage is a valid criterion for rejection of product.
Warning
Wear an eye protection device and acid resistant rubber
gloves when cleaning up electrolyte spills. Wash hands
and face thoroughly after use.
Note
Fractured cases and covers are valid criteria for rejection
of product.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation 6 - 3
If a battery is found to be damaged when received, a claim
can be initiated for replacement. The battery must be
shipped back in its original carton.
4. Check the contents of the package against the packing list.
Report any missing parts immediately.
5. The packing list includes the order number. Record this
number on the “Installation and Maintenance Record.” The
order number for new batteries must be recorded on this
form for use in warranty validation.
6. While unpacking batteries for installation in the intended
site, mark each battery with a number using an
indelible-ink magic marker. Note its corresponding
number and serial number in the appropriate column under
“Voltage Measurements on Individual Batteries” on the
Installation and Maintenance Record (see Section 10).
7. Identify all batteries that will be used for monitoring
battery temperatures. Temperature measurements should
be made on one of the middle batteries of a string. If a
single shelf is provided for a string, monitor any one of the
middle batteries. If more than one shelf of batteries is
provided for a string, monitor the middle battery of each
shelf. If more than one stand is provided, monitor the
middle battery of each shelf on each stand. Decide on
which batteries will be used to represent battery
temperature and note their numbers in the “Battery
Number” column on the “Temperature Measurements on
Selected Batteries” portion of the Installation and
Maintenance Record. This will ensure that the same
batteries will be used for all future measurements.
8. This step is required only if inter-cell connectors are
being used in lieu of cable assemblies.
Battery module terminals are precoated with
NO-OX-ID A® at the time of manufacture. Ordinarily they
will not require cleaning and recoating. Clean the contact
surface areas of exposed copper post terminals with a dry
nonabrasive cloth and recoat only if they appear dirty.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
6 - 4 Installation
Issue 7 November 1998
9. If the case is dirty when removed from the shipping
container, clean the case with a cloth dampened with water
before installing it in the battery stand.
Battery String
Location
Environmental
Requirements
The operating environment must comply with the National
Electric Code Article 110, “Requirements for Electrical
Installations,” and Article 480-8, “Battery Locations,” and any
applicable state and local regulations.
The IR-30EC and IR-40EC Series I batteries, like all lead-acid
batteries, are affected by the ambient temperature. Maintain a
low ambient temperature and/or install a temperature
compensation device that adjusts rectifier float voltages in
response to high battery temperature.
Battery temperatures above 77°F (25°C) decrease battery life
while increasing battery capacity. For battery temperatures
lower than 77°F (25°C) the capacity will decrease, but battery
life will not be adversely affected. Battery temperatures within
the same string must be maintained uniformly.
When batteries are installed where they will be exposed to heat
radiation or direct sunlight, provide shields for the radiators or
blinds for the windows to maintain a low battery temperature. In
particular, the top row of a multi-tiered stand is apt to have a
higher environmental temperature than the bottom. Where
necessary, use fans or other means of ventilation to minimize the
Caution
Use only water to clean batteries.
Note
Lucent Technologies strongly recommends a temperature
compensation device in high-temperature environments.
Failure to use such a device may result in high battery
temperature that can cause premature battery failure and may
reduce or void the warranty.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation 6 - 5
temperature variation. See Section 8 for procedures to measure
battery temperature.
Mixing
Batteries in a
String
As batteries age, their characteristics change. As a general
practice it is not recommended to mix new batteries with older
batteries in a string. A weak battery in a string can cause the
entire string to fail prematurely.
Mixing Parallel
Strings of
Batteries
As a general practice, it is not recommended to mix strings of
VRLA batteries with different capacities. However, this may be
acceptable in some situations:
Constant Current,
Separate
Chargers
Some battery systems have a dedicated, constant current charger
per string.
Constant Voltage
Chargers
It is not recommended to mix “old” strings of batteries with
“new” strings of batteries.
Battery
Installation
The following precautions should be taken when installing the
IR-30EC and IR-40EC batteries:
•
IR-30EC and IR-40EC batteries should be installed in an
upright position as a precaution against electrolyte leakage.
Caution
Operating Lucent Technologies IR-30EC and IR-40EC
Series I batteries for any significant interval of time outside
recommended voltages and/or temperatures will cause
reduced performance and premature failure and may reduce or
void the warranty.
Note
To insure maximum battery performance, do not mix
Lucent Technologies IR-30EC and IR-40EC Series I
batteries with other types of batteries.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
6 - 6 Installation
Issue 7 November 1998
•
Do not install batteries so that the weight of the battery is
supported by the lead assembly.
Connect the batteries to the associated equipment by the lead
assembly that extends from the battery terminals to a connector
selected to mate with the associated equipment.
Initial Charging
To ensure full charge and adequate initial performance, store and
maintain batteries according to instructions in Section 5, Battery
Storage, and use the guidelines in this section to charge the
batteries at the time of installation.
The purpose of an initial charge is to compensate for self
discharge that occurred in the interval between manufacture and
installation. Under normal circumstances, the battery will regain
most of its capacity after several hours float charge; 90%
capacity should be obtained within 24 hours of float charge.
See Table 6-A for detailed initial charging instructions.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation 6 - 7
Table 6-A: Initial Charging
Battery Condition
Action
All batteries have similar date
codes and storage histories
and none are more than 6*
months old or they have been
maintained according to the
“Battery Storage” section of
this product manual.
Make voltage and polarity
checks and connect string(s)
to plant. Charge at the float
voltage of 13.5 ±0.06 volts
per battery.
The batteries have dissimilar
date codes (more than one
month apart) and they are
within the required recharge
period (charge-by date).
Using an external charger**,
charge the string at 13.98
±0.06 volts per 12V battery
for 24 hours. Continue the
charge for another 24 hours at
the plant float voltage: 13.5
±0.06 volts. Make voltage
and polarity checks and
connect the string(s) to the
plant.
The batteries are older than
6* months or have not been
maintained according to the
“Battery Storage” section of
this product manual.
Do not install. Replace
batteries.
*If the storage temperature exceeds 90°F (32°C), the open
circuit time should not exceed 3 months.
** The charger must have overcurrent protection in its
output, must be able to remain across the batteries in case of
an ac power failure, and should not have crowbar protection.
(Crowbar protection is an option used on some commercial
portable power supplies that clamps a short across the output
leads of the rectifier when the rectifier senses a higher
voltage at the load than it is generating. This feature should
not be used with batteries.)
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
6 - 8 Installation
Issue 7 November 1998
Placing a
Battery String
Into Service
Batteries should be in service within 48 hours of initial charge.
If a battery is left on open circuit for more than 48 hours after the
initial charge, treat it as if it had never received an initial charge.
Since battery performance is based on the output at the battery
terminals, the shortest electrical connection between the battery
system and the operating equipment results in maximum total
system performance.
When a cable different than the one provided with the battery is
used, cable size should be specified and installed that will
maintain appropriate voltage drop between the battery system
and the operating equipment. Excess voltage drop will reduce
the desired reserve time of the battery system.
When paralleling valve-regulated batteries, the capacity,
arrangement, and external circuit length should be identical for
each battery. Wide variations in the battery circuit resistance can
result in unbalanced charging (i.e., excess charging current in
some batteries and undercharging in others). As a result, cell
failures in one battery string and subsequent loss of performance
capabilities of that string will result in higher loads in the other
parallel string(s), which may exceed the ratings of the battery
connections. This can damage the battery and dramatically
shorten battery life.
Installation
Records
The “Installation and Maintenance Record” (see Section 10) is
required for warranty validation. The installer should use this
form to record the following measurements.
Voltage
Measurements
Before connecting parallel strings together or individual strings
to the plant bus, make three voltage measurements:
1. Make the first reading across the string to verify that the
batteries are connected properly and that the polarity is
correct. (The string voltage should equal at least 12.8 volts
times the number of batteries.)
2. Make the second measurement across the plant charge and
discharge battery buses. The voltage difference between
the string and plant should not exceed 0.05 volts unless the
plant is at 0 volts because the chargers are turned off. If a
larger differential exists, the string should be charged at the
plant voltage (or the plant voltage lowered) until the
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation 6 - 9
voltage differential is less than 0.05 volts. (This should
prevent arcing during the final connection.)
3. Make the final reading to record voltages of individual
batteries. (See “Individual Battery Voltages” in Section 8,
Maintenance, for measurement procedure.) Record these
in the Installation and Maintenance Record.
A DMM (digital multimeter) is suitable for battery voltage
readings. The accuracy of an equivalent meter should be 0.05
percent on the dc scale. The meter must be checked periodically
for accuracy and calibration.
After recording these initial measurements, the installer should
turn the Installation and Maintenance Record over to the
maintenance organization as part of their permanent records. See
Section 8, Maintenance, for maintenance routines and
measurements that must be recorded.
Caution
Exercise extreme caution when making voltage readings
to prevent accidental grounding or shorting of leads
during measuring operations. Connections at the meter
must be secure and free of any possibility of touching or
becoming grounded. Never remove connections at the
meter end without first disconnecting the test leads from
the battery. Remove test lead connections at the battery
immediately after each reading is taken. Review the safety
precautions in Section 4.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Operation 7 - 1
7
Operation
Lead-acid
Battery
Gassing Rate
This section provides general information and guidelines for
estimating the hydrogen gassing rates of lead-acid batteries on
charge. It is beyond the scope of this document to provide the
detailed methods or the engineering design required to maintain
safe levels of hydrogen in battery enclosures.
All lead-acid batteries generate hydrogen and oxygen gas at the
negative and positive plates, respectively. The generation of
these gases occurs during all conditions of use, including charge,
discharge, and while on open circuit during storage. The rate of
gas generation on discharge and open circuit is generally very
small but cannot be completely ignored. For this reason, never
place lead-acid batteries in an air-tight enclosure. Explosive
mixtures of hydrogen in air are present when the hydrogen
concentration exceeds four (4) percent by volume. The
concentration of oxygen does not significantly change the lower
explosive limit of hydrogen in air, and, therefore, only hydrogen
will be considered here.
If the concentration of hydrogen in air exceeds four (4) percent
by volume, there is a risk of explosion if the gas is ignited.
Therefore, to provide a margin of safety, lead-acid battery areas
must be ventilated to limit the accumulation of hydrogen gas
under all anticipated use conditions to a recommended
maximum of one (1) percent of the total free volume in the
enclosed battery area.
In flooded lead-acid batteries, gassing rates approach the
theoretical values calculated from the dissociation of water. In
valve-regulated, lead-acid batteries (VRLA) the recombination
of oxygen gas at the negative electrode results in reduced oxygen
and hydrogen evolution from the battery. Generally, VRLA
batteries evolve from less than 1% to 20% of the hydrogen
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
7 - 2 Operation
Issue 7 November 1998
produced by flooded lead-acid batteries under similar charging
currents, and are designed to achieve greater than 95%
recombination efficiency at normal float charge and
temperature. However, charging at voltages greater than the
nominal float voltage, charging at elevated temperatures,
shorted cell(s), and a number of other possible conditions may
result in significantly greater charging current and hydrogen
gassing. It is important to note that the hydrogen gassing rate at
0% recombination, the worst case condition, is the same for both
flooded and valve-regulated technologies at equivalent charging
currents and temperatures.
From electrochemical theory, if all the charging current is used
to generate gas, each cell will generate 0.016 cubic feet of
hydrogen per hour, per ampere of charging current at 77°F
(25°C) and one atmosphere pressure. For example, a 48V string
of lead-acid batteries requiring 1 ampere of float current at 77°F
can produce as much as 0.4 cubic feet of hydrogen per hour
(0.016ft3/hr x 1 ampere x 24 cells), or as little as 0.004 cubic feet
per hour at 99% recombination efficiency, a factor of 100
difference.
The quantity of fresh air required to maintain an explosion-safe
environment in the battery area (enclosure) will vary greatly
depending on many factors including, but not limited to, the age
and condition of the battery, the number of cells in the battery
area, the battery temperature, and the current flowing through
the batteries. Therefore, the design of a ventilation system for
batteries in a specific application requires careful consideration
of factors other than the gassing rate of new batteries in typical
operation. Typical gassing rates may be useful as a “best case”
condition, but cannot adequately address “worst case” or any
other operating condition that may occur during the service life
of the battery.
Service Life
Since battery temperature exceeding 77°F (25°C) will decrease
expected life by approximately 50% for each 18°F (10°C)
increase in average temperature, it is important to consider the
temperature of the battery environment when designing
equipment or determining battery life expectancy.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Operation 7 - 3
Charging
Lucent Technologies IR-30EC and IR-40EC batteries may be
charged either by constant potential or constant current chargers.
A potential of 13.38-13.62 ±0.06 volts per 12V battery is
recommended for constant voltage charging at 77°F (25°C).
When batteries are used in plants with a constant current charger,
such as Lucent Technologies 337A1, a constant current that
results in 13.38-14.4 volts per 12V battery 77°F (25°C) is
recommended for float-standby applications.
Battery String
Float Voltage
It is extremely important to maintain the battery at the proper
float voltage for constant voltage application. The recommended
float voltage per battery is 13.5 ±0.06 volts at a battery
temperature of 77°F (25°C).
To determine the battery string float voltage, use the following
equation:
Battery String Voltage = recommended float voltage per
battery x number of batteries
For example, a 4-battery string of IR-30EC or IR-40EC batteries
should be floated at:
Battery String Voltage = 13.5 volts x 4 batteries = 54.00
volts
Charging
Voltage Ripple
The amount of ac voltage ripple present on the charging voltage
for the battery can seriously affect battery performance.
Excessive ripple could result in sharply reduced battery life and
Caution
For constant voltage application, failure to reduce the float
voltages in systems without temperature compensation
may result in premature failure or thermal run-away.
Caution
Operating Lucent Technologies IR-30EC and IR-40EC
batteries for any significant interval of time outside
recommended temperatures will result in reduced
performance and premature failure and may void the
warranty.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
7 - 4 Operation
Issue 7 November 1998
increased gassing rates. Refer to “Lead-acid Battery Gassing
Rate.”
Both the amplitude and frequency of the ripple affect the degree
of battery degradation. As a guideline, the charging voltage
ripple for the IR-30EC and IR-40EC batteries should not exceed
60mV peak to peak per 12V battery or last longer in duration
than 8mSec.
Battery and
Ambient
Temperatures
Ambient temperature can affect the capacity and life of the
IR-30EC and IR-40EC batteries. The temperature that has the
most direct effect is the battery’s internal temperature. All
valve-regulated lead-acid batteries use oxygen recombination
technology, which generates more heat than conventional
flooded batteries. As a result, the battery temperature is often
higher than the ambient temperature.
The Warranty Period outlined in Section 12 is based on the
battery temperature, not the ambient temperature. Maintain a
low battery temperature by adjusting the ambient environment
temperature and/or air ventilation. Elevated battery temperatures
(greater than 25°C or 77°F) decrease battery life while
increasing battery capacity (see Section 6, “Environmental
Requirements”). Low temperatures do not affect battery life;
however, capacity decreases with decreasing temperatures.
Applications should allow for battery temperatures within the
same string to be at a uniform temperature.
Since hot air rises, the top row of a multi-tiered stand
configuration is likely to have higher temperatures than the
Caution
AC charging ripple greater in magnitude than 60mV peak
to peak per battery or longer in duration than 8mSec
should not be used without prior consent of Lucent
Technologies Power Systems; failure to comply can void
the warranty.
Caution
Operating Lucent Technologies IR-30EC and IR-40EC
batteries for any length of time outside the recommended
voltages and/or temperatures will cause reduced
performance and premature failure and reduce or void the
warranty.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Operation 7 - 5
bottom row. When necessary, use fans or other means of
ventilation to minimize temperature variations between modules
in the same string.
Capacity
The capacity of a battery is expressed as a percent of its rated
value. For example, if a battery is discharged at the 5-hour rate
and it lasts 5.25 hours before reaching 10.5 volts, it is said to
have 105% of its rated capacity.
Discharge
Capacity Test
This test is not required as a routine maintenance procedure.
However, a discharge test is the best way to determine if
sufficient reserve power is available.
The discharge capacity test should be run directly off float
charge without prior boost charge. Battery strings to be tested
should be on float for at least one month without a boost charge
or power failure exceeding 30 minutes.
Caution
Lucent Technologies strongly recommends a temperature
compensation device in high-temperature environments.
Failure to use such a device may result in high battery
temperature that can cause premature battery failure and
reduce or void the warranty.
Figure 7-1: Temperature Versus Battery Capacity (within 5%) for IR-30EC/40EC
Percent of
Available
Capacity
Battery Capacity vs. Temperature
110
100
90
80
70
60
50
Temperature (°F)
10
20
30
40
50
60
70
80
90
100
110
120
130
C Rate
8
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
7 - 6 Operation
Issue 7 November 1998
There are several different methods that can be used in testing
the capacity of the string. In general, the more definitive the test,
the longer and more difficult it is to perform. For example,
measuring individual battery voltages after 15 minutes on a plant
load discharge will highlight batteries with only 25% capacity.
However, it usually requires a 5-hour, off-line discharge test to
spot a 5% fading in capacity.
If it is determined that a discharge test should be part of the
maintenance program, try to carry out the test consistently from
site to site and interval to interval. In this way, comparisons and
trends can be easily noted. In selecting a test, the choices are as
follows:
•
single battery or string
•
partial or full discharge
•
constant or variable load
The easiest test to run is to shut off the ac power and let the plant
load discharge the batteries until 20% to 50% of the capacity has
been removed. The disadvantage of this type of test is that the
current may not be constant throughout the discharge, from
interval to interval, or from site to site. This disadvantage can be
overcome by adding an external load to the bus. This load can be
adjusted throughout the discharge to maintain a constant current.
In light of the above, a one-hour discharge similar to the plant
load of a single battery string off-line is the preferred routine
maintenance test. The one-hour discharge rate to 11.4 volts is a
reasonable value since it will leave approximately 60% reserve
at a lower rate. A single-string, off-line, five-hour rate to 10.5
volt discharge test should only be done on those rare occasions
where a very accurate appraisal of the capacity is required. It is
not suggested to be used on a routine basis.
To carry out a discharge test properly, measure and record the
time, current, battery voltages, and initial battery temperature.
The thermometer should be accurate to within 2°F (1°C) to
achieve reasonable accuracy. The current and the time should be
measured to an accuracy of 3% and the module voltage
measured to the nearest millivolt.
Recharge After
Discharge
Recharge at the normal float voltage of 13.5 volts per
cell/battery. The recharge should begin as soon as possible after
the discharge.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Operation 7 - 7
Boost Charge
Boost charging the IR-30EC and IR-40EC batteries is not
recommended without the concurrence of Lucent
Technologies. Call 1-800-225-7822 for technical assistance.
During a boost charge, water loss due to electrolysis is greatly
increased. In valve-regulated, lead-acid cells, frequent or
prolonged boost charges can result in premature failure caused
by cell dry-out. Boost charging at elevated battery temperatures
can be especially detrimental to the batteries.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Maintenance 8 - 1
8
Maintenance
Maintenance
Schedule
Proper maintenance ensures good performance, provides an
opportunity to view trends as they develop, and ensures that the
product remains under warranty coverage.
Table 8-A lists the required routines and intervals for
maintaining the IR-30EC and IR-40EC batteries. “Paragraph
Reference” refers to the procedures for performing the routines
that follow the table. (The procedures and intervals are the same
for all models of the IR-30EC and IR-40EC batteries.)
Table 8-A: Required Maintenance Routines
Routine
Action
Interval
Paragraph Reference
Individual Battery
Voltages
Measure/Record
Quarterly
“Individual Battery
Voltages”
Battery Temperature
Measure/Record
Quarterly
“Measuring Battery
Temperatures”
String Current
Measurement
Measure/Record
Quarterly
“String Current
Measurement”
Inter-module
Connections of Module
and Rack
Inspect
Quarterly
“Inspection and
Cleaning”
Clean
As needed
“Inspection and
Cleaning”
Retorque*
As needed
“Retorquing
Inter-battery
Connections”
*This procedure is required only if inter-cell connectors are being used in lieu
of cable assemblies.
Note: Failure to adhere to these maintenance schedules and to record results
will void the warranty.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
8 - 2 Maintenance
Issue 7 November 1998
Maintenance
Routines
When performing any maintenance activities, it is essential to
follow all safety procedures outlined in Section 4.
Section 10, Installation and Maintenance Record, contains a
form for recording the measurable parameters noted in Table
8-A. The maintenance person taking these measurements should
include the date on which measurements were taken as well as
their initials. This information will aid in establishing trends that
can be used to determine overall health of the batteries. The
completed forms will be used for any future warranty claims.
Individual Battery
Voltages
Using a calibrated digital voltmeter with at least two-digit
accuracy, measure the voltage across each battery terminal to
ensure they are floating properly. Record the data in the space
provided on the “Voltage Measurements on Individual
Batteries” portion of the Installation and Maintenance Record.
When making voltage measurements, please note the following:
•
Readings for each battery must be within ±0.18 volts of the
string average (the string average is calculated by dividing
the string voltage by the number of batteries in the string).
•
Any fully-charged battery that reads less than 13.0 volts on
float must be replaced.
Warning
An explosion could occur when sparks are created near
the battery string. Use insulated tools and discharge all
static electricity from your body before performing any
work.
Caution
Exercise extreme caution when making voltage readings
to prevent accidental grounding or shorting of leads
during measuring operations. Connections at the meter
must be secure and free of any possibility of touching or
becoming grounded. Never remove connections at the
meter end without first disconnecting the test leads from
the battery. Remove test lead connections at the battery
immediately after each reading is taken. Review the safety
precautions in Section 4.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Maintenance 8 - 3
•
Because float readings are affected by discharges and
recharges, these readings must be taken when the batteries
have been on continuous, uninterrupted float for at least one
month.
Measuring
Battery
Temperatures
Make temperature measurements using calibrated equipment,
such as an infrared-based or thermocouple-based measuring
device. Make all measurements on the negative terminal of the
selected batteries. If using a thermocouple device, place the
sensor on the negative terminal of the battery and wait a few
seconds for the meter to stabilize. Note the measured value in the
appropriate column on the “Temperature Measurement on
Selected Batteries” portion of the Installation and Maintenance
Record.
String Current
Measurement
Use a calibrated DMM and current probe placed around a string
cable to make individual battery string current measurements.
Note the measured value in the appropriate column in the “String
Float Current Measurements” portion of the Installation and
Maintenance Record.
Inspection and
Cleaning
A visual inspection of the battery plant should be done on a
quarterly basis. If necessary, the battery modules and racks can
be cleaned using a soft cloth dampened in water. The
inter-battery connections should be inspected for corrosion.
Report any sign of acid or corrosion to Lucent Technologies.
Retorquing
Inter-battery
Connections
This procedure is required only if inter-cell connectors are
being used in lieu of cable assemblies.
Ensure that all battery connections are tight. If required, retorque
these connections to 40 ±10 inch-pounds, using an insulated
5/16-inch socket and torque wrench.
Flame Arrestor
Vent Feature
The vent and flame arrestor are maintenance free and do not
require attention under normal circumstances. However, do
Caution
Over-tightening of the inter-module connectors could strip
the bolt and/or nut threads, resulting in loose connections.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
8 - 4 Maintenance
Issue 7 November 1998
NOT allow gas vents to become clogged or excessive internal
pressure may result.
Battery
Replacement
As batteries age, their characteristics change. As a general
practice it is not recommended to mix new batteries with older
batteries in a string. A weak battery in a string can cause the
entire string to fail prematurely.
Should it become necessary to replace one or more batteries in a
battery string, the replacement battery(ies) must be charged
according to Table 6-A. Do not exceed the time on charge.
Following the initial charge, keep the battery(ies) on continuous
float until the replacement can be made. The time between
discontinuing the float charge and the completion of
replacement should not exceed 24 hours.
Note
To insure maximum battery performance, do not mix
Lucent Technologies IR-30EC and IR-40EC Series I
batteries with other types of batteries.
Caution
Make sure the batteries are at equal float charge before
connecting them into a string.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Discharge and Power Data 9 - 1
9
Discharge and Power Data
Discharge
Capacity
The discharge capacity of Lucent Technologies IR-30EC and
IR-40EC batteries is directly related to temperature and
inversely related to the discharge rate. The maximum
recommended discharge rate is the 1-hour rate.
Discharge Cycle
Life
Discharge rate, recharge parameters, and depth of discharge all
contribute to discharge cycle life. The most important factor in
determining discharge cycle life for Lucent Technologies
IR-30EC and IR-40EC and most other lead-acid battery designs
is generally the depth of discharge (capacity removed/capacity
available). The more completely a battery is discharged, the
lower the number of cycles available prior to failure, which is
defined as 80% of rated capacity.
Lucent Technologies IR-30EC and IR-40EC battery
applications have been optimized to deliver high capacity per
unit volume in predominately float-standby applications where
deep, long duration discharges are relatively infrequent.
Therefore, the number of discharge cycles that may occur
throughout the battery's life is not considered to be a significant
factor in battery failure. It is not recommended for applications
that require deep and/or frequent cycling.
Caution
Discharge of batteries below 1.75V per cell may result in
recharge abnormalities and premature failure.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
9 - 2 Discharge and Power Data
Issue 7 November 1998
Figure 9-1: Discharge Current (within 5%) vs. Discharge Duration to 10.5V
(IR-30EC and IR-40EC)
100.0
10.0
1.0
0.1
Discharge
Current
(Amps)
0.1
1
10
100
Discharge Current vs. Discharge Duration
Discharge Duration (Hours)
IR30EC
IR40EC
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Discharge and Power Data 9 - 3
Figure 9-2: Discharge Power (within 5%) vs. Discharge Duration to 10.5V
(IR-30EC and IR-40EC)
10,000
1,000
100
10
Discharge
Power
(Watts)
0.01
0.1
1
10
Discharge Power vs. Discharge Duration
Discharge Duration (Hours)
IR30EC
IR40EC
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
9 - 4 Discharge and Power Data
Issue 7 November 1998
Figure 9-3: Characteristic Discharge Curves (within 5%) for IR-30EC
Volts
0.1
1
10
100
IR-30EC Characteristic Discharge Curves @ 77°F (25°C)
(Constant Current)
Discharge Duration (Hours)
13.5
13
12.5
12
11.5
11
10.5
7.7A
18.2A
2.8A
3.4A
5.1A
Figure 9-4: Constant Power Capacity for IR-30EC
Volts
0.1
1
10
100
Discharge Duration (Hours)
13.5
13
12.5
12
11.5
11
10.5
33.4W
40.7W
214.9W
60.8W
IR-30EC Characteristic Discharge Curves @ 77°F (25°C)
(Constant Power)
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Discharge and Power Data 9 - 5
Figure 9-5: Characteristic Discharge Curves (within 5%) for IR-40EC
Volts
0.1
1
10
100
IR-40EC Characteristic Discharge Curves @ 77°F (25°C)
(Constant Current)
Discharge Duration (Hours)
4.4A
6.6A
13.5
13
12.5
12
11.5
11
10.5
24.2A
10.1A
3.6A
Figure 9-6: Constant Power Capacity for IR-40EC
Volts
0.1
1
10
100
IR-40EC Characteristic Discharge Curves @ 77°F (25°C)
(Constant Power)
Discharge Duration (Hours)
80.1W
13.5
13
12.5
12
11.5
11
10.5
286.6W
121.7W
53.2W
43.6W
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
9 - 6 Discharge and Power Data
Issue 7 November 1998
Table 9-A: Battery Discharge Amperes (within 5%) for IR-30EC at 25°C (77°F)
Hours Reserve
End of Discharge Voltage per Battery
(Cut-off Voltage Per Cell)
10.5V
(1.75V)
10.8V
(1.80V)
11.0V
(1.84V)
11.3V
(1.88V)
11.4V
(1.90V)
1*
18.15
17.84
17.35
16.46
16.13
3
7.73
7.63
7.43
7.09
6.93
5
5.05
4.98
4.86
4.63
4.53
8
3.38
3.34
3.25
3.10
3.02
10
2.78
2.75
2.67
2.53
2.48
15
1.85
1.80
1.63
1.61
1.60
20
1.49
1.47
1.43
1.33
1.32
24
1.26
1.24
1.21
1.14
1.11
*See Note in Table 3-A.
Table 9-B: Battery Discharge Wattage (within 5%) for IR-30EC at 25°C (77°F)
Hours Reserve
End of Discharge Voltage per Battery
(Cut-off Voltage Per Cell)
10.5V
(1.75V)
10.8V
(1.80V)
11.0V
(1.84V)
11.3V
(1.88V)
11.4V
(1.90V)
1*
214.9
211.8
206.7
197.4
193.3
3
92.8
91.6
89.6
85.6
83.8
5
60.8
60.0
58.7
56.15
55.0
8
40.7
40.2
39.3
37.5
36.7
10
33.4
33.1
32.2
31.44
30.1
15
23.5
23.3
22.5
22.0
21.6
20
18.0
17.7
17.3
16.4
16.0
24
15.2
15.0
14.6
13.8
13.5
*See Note in Table 3-A.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Discharge and Power Data 9 - 7
Table 9-C: Battery Discharge Amperes (within 5%) for IR-40EC at 25°C (77°F)
Hours Reserve
End of Discharge Voltage per Battery
(Cut-off Voltage Per Cell)
10.5V
(1.75V)
10.8V
(1.80V)
11.0V
(1.84V)
11.3V
(1.88V)
11.4V
(1.90V)
1*
24.19
23.79
23.14
22.16
21.51
3
10.14
10.01
9.69
9.30
9.03
5
6.65
6.57
6.36
6.09
5.89
8
4.43
4.38
4.23
4.04
3.91
10
3.62
3.58
3.46
3.31
3.20
15
2.49
2.46
2.38
2.27
2.19
20
1.91
1.89
1.83
1.74
1.68
24
1.61
1.59
1.54
1.46
1.41
*See Note in Table 3-A.
Table 9-D: Battery Discharge Wattage (within 5%) for IR-40EC at 25°C (77°F)
Hours Reserve
End of Discharge Voltage per Battery
(Cut-off Voltage Per Cell)
10.5V
(1.75V)
10.8V
(1.80V)
11.0V
(1.84V)
11.3V
(1.88V)
11.4V
(1.90V)
1*
286.60
282.40
275.70
265.08
257.80
3
121.70
120.20
116.60
112.32
109.20
5
80.10
79.10
76.80
73.72
71.50
8
53.20
52.70
51.10
48.94
47.40
10
43.60
43.10
41.80
40.05
38.80
15
29.97
29.70
28.79
27.51
26.64
20
23.30
22.80
22.10
21.10
20.40
24
19.40
19.20
18.60
17.79
17.20
*See Note in Table 3-A.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation and Maintenance Record 10 - 1
10
Installation and Maintenance
Record
The form in this section should be reproduced and used as the
Installation and Maintenance Record for batteries.
The battery installer should follow the instructions in Section 6,
“Unpacking and Handling” and “Installation Records,” to begin
the recordkeeping. The installer should then turn these
records over to the Maintenance organization, who becomes
responsible for taking the measurements detailed in this
section and for maintaining the form. If a warranty claim is
made, the Maintenance organization will be required to show the
“Installation and Maintenance Record” to support the claim.
Refer to Section 8, Maintenance, for required actions and
measurements.
Note
Failure to adhere to the maintenance schedules and
routines described in the Maintenance section of this
product manual will void the product warranty and may
result in reduced performance of your batteries.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
10 - 2 Installation and Maintenance Record
Issue 7 November 1998
Company Name:
Installation and Maintenance Record (Page 1)
String Voltage:
Initials
Measurement
Date
Serial
Number
Order
Number
Battery
Number
Site Address:
Voltage across charge and discharge buses:
If the voltage difference between the string and the charge/discharge buses is less than 0.05V, the system is ready. Make individual battery voltage
measurements and record in the table below.
Voltage Measurements on Individual Batteries
Battery Type:
Voltage Difference:
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Installation and Maintenance Record 10 - 3
Company Name:
Initials
Initials
Test Date
Battery
Temperature
Test Start Time
Test End Time
Start Voltage
(Vdc)
End Voltage
(Vdc)
Test Current
(A)
Percent
Capacity
Measurement
Date
Measurement
Date
Battery
Number
Battery
Number
Site Address:
Temperature Measurements on Selected Batteries
String Float Current Measurements
Battery Capacity Measurements
Battery Type:
Installation and Maintenance Record (Page 2)
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
10 - 4 Installation and Maintenance Record
Issue 7 November 1998
Date
Comments
Installation and Maintenance Record (Page 3)
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Material Safety Data Sheet 11 - 1
11
Material Safety Data Sheet
This section contains the Material Safety Data Sheet for the
IR-30EC and IR-40EC batteries.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
11 - 2 Material Safety Data Sheet
Issue 7 November 1998
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Material Safety Data Sheet 11 - 3
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
11 - 4 Material Safety Data Sheet
Issue 7 November 1998
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Material Safety Data Sheet 11 - 5
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Product Warranty 12 - 1
12
Product Warranty
IR-30EC and IR-40EC Batteries Product Warranty:
A. Seller warrants to customer that:
1. As of the date title to product sold (Product) passes,
Seller will have the right to sell, transfer, and assign
such product, and the title conveyed by Seller shall be
good;
2. Upon shipment, Product will be free from defects in
material and workmanship, and will conform to Seller's
specification.
B. The Warranty periods and conditions applicable to new
products are listed in Table 12-A:
Table 12-A: New Battery Warranty Period and Conditions
Warranted Years
of Life
Annual Average
of Daily
Maximum Battery
Temperature
(see Note)
Full
Replacement
Pro-Rata
Replacement
5 years
77°F
(25°C)
2 years
3 years
3 years
90°F
(32°C)
1 year
2 years
1 year
110°F
(43°C)
6 months
6 months
Note: Operating the IR-30EC or IR-40EC battery for any length of time
above 77°F (25°C) will result in reduced performance and premature
failure. Operation or storage above 122°F (50°C) will void the product
warranty.
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
12 - 2 Product Warranty
Issue 7 November 1998
Temperature and maintenance records shall be maintained
by Customer in accordance with Seller's published
instructions in the Maintenance section of this manual.
Failure to do so may void the warranty.
• End of life is defined as 80% of rated capacity (see
Operation section for Discharge Capacity Test).
• Cycles and discharge depth shall not exceed:
–
60 cycles during Warranted years of life with an 80
percent discharge depth.
The Warranty Period commences on the date of shipment.
C. If, during the Warranty Period and under the Warranty
Conditions, a defect or nonconformity is identified in a
Product and Customer notifies Seller in writing of such
defect or nonconformity, and follows Seller's instructions
regarding return of defective or nonconforming Products,
Seller shall, at its option, either replace such Product
without charge or provide a credit as specified in the
pro-rata replacement section of this warranty.
If notification of defect is:
• Within the years of the full replacement portion of the
Warranty, Seller will replace the Product.
• Within the years of the pro-rata replacement portion of
the Warranty, Seller will, at its option, either replace the
Product or provide a credit based on the following
pro-rata formula: C = [(WR - ML)/WR] x PR
where:
C =
Credit
ML = Months of Life Obtained
PR = Current Replacement Billing Price
WR = Warranted Months of Life as
determined in paragraph “B”.
Credit will be applied to a replacement Lucent
Technologies product.
D. If Seller has elected to replace a defective Product, the cost
of removal and the reinstallation shall be borne by
Customer. Products returned for replacement will be
accepted by Seller only in accordance with its instructions
for such returns. The transportation expense and risk of
Lucent Technologies IR-30EC and IR-40EC Series I Batteries
Issue 7 November 1998
Product Warranty 12 - 3
loss associated with returning such Product to Seller shall
be borne by Customer. Seller shall bear the cost of
transportation and risk of loss of the replacing Product to
the destination originally designated by Customer at time
of purchase. When Seller has elected to replace Product or
give credit, Product shall remain the Customer's property
to be disposed of in accordance with Federal, State, and
local regulations for hazardous materials.
E. If Seller determines that a Product for which warranty
service is claimed is not defective or nonconforming,
Customer shall pay or reimburse Seller for all costs of
handling, inspecting, testing, disposal, and transportation,
and, if applicable, traveling and related expenses.
F. Seller makes no warranty with respect to defective
conditions or nonconformities resulting from actions of
anyone other than Seller or its subcontractor, caused by
any of the following: modifications, misuse, neglect,
accident, or abuse; improper wiring, repairing, alteration,
installation, storage, or maintenance; use in a manner not
in accordance with Seller's specifications, or operating
instructions, or failure of Customer to apply previously
applicable Seller modifications and corrections. In
addition, Seller makes no warranty with respect to
Products which have had their serial numbers or month
and year of manufacture removed or altered.
G. This warranty shall run only to Customer who is a direct
purchaser from the Seller.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND