RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNINGS:
• Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.
• To prevent wiring damage or abrasion, do not expose wiring to edges of sharp objects.
CAUTION:
• This fixture supports the following protocols – Triac and ELV at 120V ONLY. For 0-10V dimming, connect purple wire to the
V+ DIM lead and the grey wire to the V-DIM lead. This fixture is damp listed and suitable for indoor applications on walls.
Driver is 120V – 277V and 50Hz or 60 Hz.
HALV
Mounting the fixture on a standard 4 x 4 J-BOX.
This fixture is damp listed and suitable for indoor applications
on walls
1. Loosen the (4) driver/LED mounting phillips head screws and
separate the driver/LED assembly from the wall plate. No need
to remove the screws completely, use the keyhole. DO NOT
TOUCH THE LEDs. See Figure 1.
2. Set Driver/LED assembly aside.
3. Pull wires from j-box through the Wall Plate opening and
mount Wall Plate to junction box using screws provided with the
junction box. Making sure the ‘S’ hook notch is at the top.
4. Hang the Driver/LED Assembly on the ‘S’ hook as shown in
Figure 1a.
5. Make wiring connections. Push wire nuts through hole into
J box.
6. Replace Driver/LED Assembly making sure not to pinch any
wires.
7. Tighten Driver/LED mounting screws.
J-BOX WALL MOUNTING (standard models)
‘S’ Hook Notch
Wall Plate
Driver/LED
Assembly
DO NOT TOUCH LEDs
Driver/LED
Screw Keyhole
Wire Hole
Driver/LED mounting screws
‘S’ Hook
FIG.1
‘S’ Hook
‘S’ Hook
FIG.1a
HALV Indoor Architectural-Grade LED Wall Sconce
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
FIG.3
Wall box is installed before sheetrock.
1. Remove Driver/LED/Wall plate assembly by loosening
4 phillips head screws as shown in Figure 1. No need to
completely remove screws, keyhole slots provided. Retain
Hanger. Unplug connectors (if E2, E2/MVS, E2, E2/BL, or E2/LC)
and put Driver/LED/Wall plate aside.
2. Install Nailer Bars into wall box as shown in Figure 2.
3. Locate the wall box in the desired position between the studs
and affix using Nailer Bars.
4. Tighten 1 phillips head locating screw shown in Figure 2 to hold
wall box in position on the Nailer Bars.
5. Run wire to box.
Wall box is installed after sheetrock.
1. Remove Driver/LED/Wall plate assembly by loosening
4 phillips head screws as shown in Figure 1. No need to
completely remove screws, keyhole slots provided. Retain
Hanger. Unplug connectors (if E2, E2/MVS, E2, E2/BL, or LC/E2)
and put Driver/LED/Wall plate aside.
2. Discard Nailer Bars.
3. Move Stop Brackets from end to side and add Sheetrock
Clamps as shown in Figure 3 (on following page).
4. Using the template provided, cut opening in sheetrock. Leave
at least ¾” between box and stud.
5. Run wire to box.
6. Place Wall Box in opening and tighten 4 phillips head screws
to secure Wall Box.
FIG.1
` FIG.2
Hanger
Sheetrock Clamp
Stop Bracket
after relocation.
Move both
Stop Bracket screw
after relocation
Stop Bracket
before relocation
Stop Bracket screw
before relocation
Nailer Bar
Tighten to secure
in sheetrock
Hanger
Driver/LED/Wall
plate assembly
DO NOT TOUCH LEDs
Insert
screwdriver
though hole to
loosen screw
4 places
Hanger
Nailer bar
Stop Bracket
Discard for new
work install
Tighten this locating screw
to hold box in place
NEW CONSTRUCTION INSTALLATION
(models w/wall box)
REMODELER INSTALLATION
(models w/wall box)
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
INSTRUCTIONS
HALV Indoor Architectural-Grade LED Wall Sconce
CLEANING AND MAINTENANCE
TROUBLESHOOTING
1.
Use warm water, mild soap and a soft sponge or cloth. Any
acrylic cleaner may also be used. Do not use alcohol, glass
cleaners, acetone, lacquer thinner, solvents or abrasive
compounds. Do not use squeegees, scrapers or synthetic rags
that may scratch the panels.
a.
Lumicor® lenses – Novus® cleaner and polish is an
approved product for a clean shine that also protects from
static build up. See the “General Polishing & Basic Scratch
Repair” document at www.lumicor.com/ScratchRepair for
more information.
2. DO NOT OPEN THE FIXTURE TO CLEAN THE LEDs. DO NOT
TOUCH THE LEDs.
1. Check that the line voltage at the fixture is correct. Refer to
wiring directions.
2. Be sure the fixture is grounded properly.
1. Align Lens Frame over the Driver/LED assembly with the
phillips head mounting screw at the top. See Figure 5.
2. Inset the lens frame from the bottom with the bottom flush
against the wall. See Figure 5.
3. Tilt the top of the lens frame to the wall.
4. Make sure the frame is flush against the wall and tighten
mounting screw at the top using a 5/64” hex key.
LENS FRAME INSTALLATION
Driver / LED Assembly
DO NOT TOUCH LEDs
Mounting Screw
Lens Frame
FIG.5
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
1. Hang Driver/LED/Wall plate assembly on Hanger Bracket as
shown in Figure 4.
2. Make wire connections.
3. Remove Hanger Bracket and place in bottom of box for future
use.
4. Install Driver/LED/Wall plate and tighten 4 phillips head screws.
1. Hang Driver/LED/Wall plate assembly on Hanger as shown in
Figure 4 Energize fixture. Mate battery connection.
2. Mate connectors, except for battery connection. Make wiring
connections.
3. Energize fixture. Mate battery connection.
4. Remove Hanging Bracket and place in bottom of box for future
use.
5. Install Driver/LED/Wall plate and tighten 4 phillips head screws.
DRIVER/LED/WALL PLATE/ASSEMBLY
(with E2, E2/MVS, E2/BL, or LC/E2 Options)
DRIVER/LED/WALL PLATE/ASSEMBLY
(with LC option)
FIG.4
Hanger
HALV Indoor Architectural-Grade LED Wall Sconce
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts - 888 722-1000
e-mail
Answered promptly - [email protected]
Free Lighting Layouts
Answered online or by request
© 2019 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
DIMENSIONAL DRAWINGS
LENS FRAME ASSEMBLY (MODELS WITH BACK BOX)
LENS FRAME ASSEMBLY (STANDARD MODELS)
-
HALVLED-IN 0119
RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty.
19724 MICROWAVE SENSOR FOR D10
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: [email protected]
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
19724 is used with a120-277VAC dimmable driver and comes with a sensor antenna. Sensor is shipped with Factory Settings
outlined below under DIP Switch Settings. If settings other than factory pre-sets are desired, the consumer may change DIP
Switch Settings. For more detailed control of the sensor, the consumer can purchase MVSREM wireless commissioning tool
(remote) to re-program sensor settings.
SPECIFICATIONS
Sensor is not suitable for wet locations.
DIP Switch Settings
Switch positions referred to as R for right position and L for left position when
looking at sensor in orientation shown in Fig. 2, in which all switches are R.
See Fig. 1 and 2 for each setting’s corresponding switches. Setting options for
each category are noted in (parenthesis) below.
Factory Settings: designated in bold for each category
Detection Area:
Time Delay: how long lamp remains on at 100% after last
recognized motion
• 100% (RR)
• 75% (RL)
• 50% (LR)
• 10% (LL)
• 5s (RRR)
• 30s (RRL)
• 1min (RLR)
• 5min (RLL)
• 10min (LRR)
• 20min (LRL)
• 30min (LLL)
Fig. 2
Adjustable
Detection Area
Time Delay
Daylight
Sensor
Cut Off
Period
Dim Level
Sensor
Antenna
Interface
+
-
0-10V
L’ N N L
DIP Switches
Daylight Sensor:
Cut Off Period: how long reduced light output lasts after
time delay period before fixture switching off
Dim Level: light output level after time delay
• Disabled (RR)
• 5 fc (Daylight) (RL)
• 1 fc (Twilight) (LR)
• .2 fc (Darkness) (LL)
• 0s (RRR)
• 10s (RRL)
• 1min (RLR)
• 5min (RLL)
• 10min (LRR)
• 30min (LRL)
• 1hr (LLR)
• Always (LLL)
• 10% (RR)
• 20% (RL)
• 30% (LR)
• 50% (LL)
L R
DIP SWITCHES
Factory Settings shown below
L’ = driver
L = power source
Fig. 1
19724 Sensor
Antenna
19724 MICROWAVE SENSOR FOR D10
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: [email protected]
SENSOR COVERAGE DIAGRAM
Below diagrams represent best average coverage from lab testing. Actual
coverage may vary as metal on the fixtures can interfere with microwaves from
the sensor
Ceiling mounted detection pattern (m)
ceiling mounting height (m)
6
0
5
10%
30%
50%
75%
100%
OPERATION
Multi-level Dimming:
• 100% light
• Dimmed to: 10, 20, 30, 50*%
*50% not on remote
• Off
Cut Off Time Adjustment:
• Once room is vacated, light dims to selected % after
chosen hold time elapses
Daylight Sensing:
• Surrounding natural light keeps fixture light off until
room is occupied and natural light levels drop to
selected level
8 Hour* Manual Mode:
• Turn fixture off-on 3 times within 3 seconds
• Green LED on antenna will flash and fixture will flash 3
times if done correctly
• Fixture will remain 100% for 8 hours, then sensor will
come on automatically
• To cancel, turn the fixture off-on within 1 second
*Times out after one 8-hour cycle
Ambient Daylight Threshold*:
• Turn fixture off-on 2 times within 2 seconds
• Green LED on antenna will flash slowly for 5
seconds and fixture will blink twice if done correctly
• Surrounding fc will be measured and recorded for 1
second
• Green LED on antenna and fixture will light for 10 sec-
onds to indicate successful fc recording
• Most recent fc measurement overwrites any prior
*DIP settings (pg 1) and ambient lux overwrite eachother depending on latest action
Scene Mode:
• 100% detection range and 10% cut off dimming
Scene 1 (SC1): 1 min hold-time, 10 min cut off period,
.2 fc daylight sensor
Scene 2 (SC2): 5 min hold-time, 10 min cut off period,
.2 fc daylight sensor
Scene 3 (SC3): 10 min hold-time, 30 min cut off
period, 1 fc daylight sensor
Scene 4 (SC4): 10 min hold-time, always on bi-level
cut off period, 5 fc daylight sensor
SENSOR TECHNICAL DATA
Capacitance Load: 400W at 120V, 800W at 230V, 1000W at 277V
Operating Temperature: -20°C to +60°C (-4°F to +140°F)
Relay: Zero-cross relay
Maximum Mounting Height: 5m
Customizable Detection Area: 10, 50, 75 or 100%
Time Delay: 5s, 30s, 1min, 5min, 10min, 20min, 30min
Cut Off Period: 0s, 10s, 1min, 5min, 10min, 30min, 1hr, Bi-Level
Cut Off Dimming Level: 10, 20, 30, 50%
Cut Off Power: Less Than 1W
Daylight Threshold: About .2-5 fc or Disabled
Sensor Principle: High Frequency
Microwave Frequency: 5.8GHz +/- 75MHz
Microwave Power: <0.2mW
Detection Range Max: 16m across, 10m high
Detection Angle: About 30 to 150 degrees
9
0
4
10%
30%
50%
75%
100%
Wall mounted height (m)
Wall mounted detection pattern (m)
Fig. 3
Fig. 4
19724 MICROWAVE SENSOR FOR D10
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: [email protected]
TROUBLESHOOTING
If the sensor does not detect motion as expected:
• Check fixture mounting to compare fixture location and
sensor coverage with the coverage diagrams on pg 2
• Adjust fixture location as necessary
Fixture will not light/sensor does not detect motion:
• Make sure ON/OFF button was not selected as this
results in disabling the sensor
• Check all settings to be sure there is no conflicting
selection with the ambient light level
Fixture and sensor are too active:
• Check detection area setting and reduce coverage as
needed
• Increase time delay and/or adjust cut off period.
Basic Function Overview:
REMOTE CONTINUED
Detection Range Button Group: assigns detection range of
10, 50 or 100%; use coverage diagrams on pg 2 for guidance.
To limit area in which motion will set off sensor, use a smaller
percent. The sensor will not detect motion outside of 100%
and the fixture will not light.
Time Delay Button Group: assigns hold time of 30 seconds,
1 minute, 5 minutes, 10 minutes, or 30 minutes
Cut Off Button Group: assigns cut off period of 0 seconds,
10 seconds, 1 minute, 10 minutes, 30 minutes, or 1 hour. 0
seconds gives fixture on/off control rather than dimming.
+ ∞ keeps the light on always (if daylight sensor is disabled)
with Bi-Level dimming control.
Dim Level: assigns level of 10, 20, or 30% for dimmed light
output after time delay passes
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation operation or maintenance.
Easy Installation & Product Help
Tech Help Line
Call our experts 888 RAB-1000
©2016 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
rabweb.com
Visit our website for product info
email
Answered promptly [email protected]
19724 IN 0616
REMOTE
Sensor will beep one time
to indicate remote recieved
signal successfully
Remote settings will override
DIP Switch settings
ON/OFF: disables sensor;
light is permanently* on or off
*un-do permanent on/off by
selecting either Auto-Mode, RESET,
or any Scene mode button
Auto Mode: sensor activates
and all previously selected
settings remain programmed
RESET: overrides selected
settings; reverts to DIP
settings
Dim buttons: + dims up and
- dims down, adjusting lamp
brightness
Black Button: no function
Test 2s: automatic* test mode with 2 second time delay;
disables cut off period and daylight sensor
*un-do automatic test mode by selecting either RESET, any Scene mode
button, or hold time
Power 100% & Power 80%: adjusts power output; to save
energy select Power 80%. Must return to full output after initial
10,000 hours of LEDs by pressing Power 100%.
Group B:
Yellow Sun Button: Ambient Daylight Threshold;
records surrounding lux level and overwrites previously
recorded value
.2, 1 and 5 fc: sets daylight sensor at respective ambient light
values
Disable: disables daylight sensor; any motion
registered by sensor activates fixture light
SC1, SC2, SC3, SC4: assigns one of 4 pre-set scenes; see
“Operation” on pg 2 for scene descriptions
Fig. 5
100%
Reduced Level
Occupied
Time Delay
Cut Of
Group B
Fig. 6