Omron E5ZN Manual
Text of the manual
E5ZN (Orders for the E5ZN series will not be accepted after March 31, 2019.)
• The E5ZN is a Temperature Controller that features the ability to be built into equipment.
• The E5ZN is equipped with RS-485 communications, so process values can be monitored and parameters can be read or written from the host
system.
• The Terminal Unit can be separated from the Controller, so maintenance can be performed on the Controller without changing the wiring.
• If two or more Controllers are connected to the same host system, use an expansion Terminal Unit and close mounting to safe space and
reduce wiring.
Using Setting Switches
Controller
Front panel
Terminal Unit
Standard Model
Expansion Model
Baud Rate
Operation Indicators
Unit Number Switch
Set the baud rate of the Controller to match the baud rate of the host system.
• POWER
Lights when power is turned ON.
• ERROR
Lights when an input error (e.g., memory error or input error for any channel) occurs.
• SD/RD (Send Data/Receive Data)
Light during communications with the host.
• OUT1, OUT2 (Control Output 1, Control Output 2)
Light when the control output 1 or the control output 2 functions are ON.
• SUB1, SUB2 (Auxiliary Output 1, Auxiliary Output 2)
Light when the auxiliary output 1 or the auxiliary output 2 functions are ON.
Front Panel
Set the unit number to identify the Controller connected to the host system and to the Setting Display Unit
(E5ZN-SDL).
The unit number is hexadecimal.
Switch settings 0 to F correspond to unit numbers 00 to 15.
Set a different unit number for each E5ZN if more than one is connected using RS-485 communications.
Communications cannot be performed if the same unit number is used more than once on the same line.
Setting
0
00
1
01
Default setting
Default setting
2
02
3
03
4
04
5
05
6
06
7
07
8
08
9
09
A
10
B
11
C
12
D
13
E
14
F
15
Unit number
Setting
0
4800
1
9600
2
19200
3
38400
4
5
6
Do not set.
7
8
9
Baud rate (bps)
0
1
2
3
4
5
9
8
7
6
0
1
2
3
4
5
6
7
F
E
D
C
B
A
9
8
Note: All units are in millimeters unless otherwise indicated.
The following figure shows the Terminal Unit mounted.
Note: 1. Always use this Terminal Unit if individual Controllers are used.
2. Use this Terminal Unit from the second Controller on if two or more Controllers are mounted side by side.
Mounting Terminal Units Together
From 0 to 15 Expansion Terminal Units (E5ZN-SCT18S) can be
connected to a standard Terminal Unit (E5ZN-SCT24S). Terminal
Units can be mounted together by interlocking their side connectors.
Attach a connector cover to the Terminal Unit on the right end.
Terminal Unit
E5ZN-SCT24S (See note 1.)
Terminal Unit
E5ZN-SCT18S (See note 2.)
30
4.7
4.7
27
35
46
112
5.2
22.5
27
35
46
112
130
72.8
130
72.8
Side connectors
Connector cover
Mounting to the DIN Track
Mounting
Catch the hook located on the top of the Controller onto the DIN
Track and press the Controller until it locks into place.
Removing the Controller
Pull down on the hooks with a flat-blade screwdriver and lift up on the
Controller.
Mounting the End Plate
Always attach End Plates on both ends of the Controller.
Mounting Bracket
Mount the E5ZN on a DIN Track. Mount the DIN Track using screws
in at least three places in the control panel.
• DIN Track
PFP-50N (50 cm)
PFP-100N (100 cm)
Install the DIN Track vertically to the ground.
Mounting the Controller
Mounting Procedure
Firmly insert the Controller following the guides on the Controller and Terminal Unit.
Removing the Controller
(1) Lower the hooks.
(2) Catch the
upper
hook
onto the
DIN
Track.
(3) Press in
on the
Controller.
(4) Make sure the
Controller is
locked into place.
Flat-blade screwdriver
Mounting one Controller
Side-by-side Mounting
(1)
(2)
Vertical
Correct
Horizontal
Incorrect
Push in the Controller following the guides
until it clicks into place.
Pull out the Controller while pushing
the hook on the end of the Controller.
(1)
(2)
(1)
The sensor input type, alarm type, control cycle, and other initial hardware settings that were made using DIP switches on previous models are
now made using the setup display on the E5ZN-SDL. Change the setup display by pressing the LEVEL and MODE Keys. The amount of time the
keys are pressed determines what parameter is entered.
Interpreting Typical Examples
Typical Example 1
M
M
M
This symbol means that
there are further
parameters. Keep pressing
the MODE Key until the
system switches to the
intended parameter.
Changing Parameters
Changing Values
Set values in each
display can be
changed by pressing
the U and D Keys.
Input type:
0 K thermocouple −200 to 1300°C
Control method: ON/OFF control
Alarm type:
2 upper limit
Alarm value 1:
20°C (Set the deviation in
Set point:
100°C
E5ZN unit number: 3
Channel number:
1
Power ON
Start operation.
Set the channel number.
Set the unit number.
Set the control method.
Set the alarm type.
Set input specifications.
Set alarm values.
Power ON
Process value/
set point
Input type
For
ON/OFF
control
Alarm 1 type
For PID
control
Control stops.
Operation Level
Initial Setting Level
Press the Key for at least three seconds.
Set the unit number and channel by
pressing the UNIT and CH Keys.
Press the Key for at least one second.
M
Process
value/set point
To operate
Alarm value 1
To stop
Operation Level
M
Operation Level
Initial Setting Level
Operation Level
M
M
M
M
Select "Run"
using the
U and D Keys.
Press the U
and D Keys to
set the alarm
value to 20°C.
Press the U and
D Keys to set the
set point to 100°C.
Check the input
type.
Select ON/OFF
control by using
the U and D
Keys.
Check the alarm
type.
Setup Procedure
Typical Example 2
Input type:
4 T thermocouple −200 to 400°C
Control method: PID control
Calculate PID constants using AT (auto-tuning).
Alarm type:
2 upper limit
Alarm value 1:
30°C
Set point:
150°C
E5ZN unit number: 1
Channel number:
2
Check the alarm type.
Operation Level
Start operation
Set the channel number.
Set the unit number.
Set the control method.
Set the alarm type.
Set input specifications.
Power ON
Process
value/set point
Input type
For ON/OFF
control
Control period (OUT1)
(unit: seconds)
For PID
control
Control stops.
Operation Level
Initial Setting Level
Press the Key for at least 3 s.
Set the unit number using the UNIT Key.
AT ends and operation starts.
Initial Setting Level
Set the channel number using the CH Key.
Alarm 1 type
Press the . Key for at least one second.
Set to pid when PID control is used.
M
M
M
M
Power ON
Process value/
set point
To
operate
Alarm value 1
To stop
Operation level
M
M
M
PV/SP
After AT execution.
During AT execution.
SP will flash while AT
is being executed.
After AT execution.
During AT execution.
Press the Key (for less than 1 s).
To execute AT
Execute AT.
Adjustment Level
Press the Key for less than one second.
To stop AT
AT execution
Adjustment Level
(for PID control)
Use the U and
D Keys to set the
input type to 4.
Use the U and
D Keys to check
that the control is
PID.
Check the control
period.
Check the alarm
type.
Press the U and
D Keys to set the
set point to 150°C.
Press the U and
D Keys to set the
alarm value to
30°C.
Select "Run"
using the U and
D Keys.
Set to on to execute AT and
to off to stop AT.
Recommended settings: 20 s for a
relay output and 2 s for a voltage/
SSR output.
Setup Procedure
Using Copy Mode
This function can be used only when control is stopped. When copying settings, first finish making settings for the Temperature Controller in the
normal mode, then upload and download in Copy Mode.
Upload (Temperature Controller to
Setting Display Unit)
Step 1
Press the COPY Key for at least 1 s to enter Copy Mode.
Step 2
Use the UP and DOWN Keys to select up on Display No. 2. Press the
UNIT Key to select the unit number for the upload.
Any unit number from 0 to f or "-" (all units) can be selected.
Step 3
Press the LEVEL Key for at least 1 s to start the upload.
Note: 1. up will flash on Display No. 2 during the upload.
2. The mode will return automatically to the Operation Level
when the upload has been completed.
Download (Setting Display Unit to
Temperature Controller)
Step 1
Press the COPY Key for at least 1 s to enter the copy mode.
Step 2
Use the UP and DOWN Keys to select down.
The possible selections are up and down.
Step 3
Press the UNIT Key to select the unit number for which data has
been uploaded. Any unit number from 0 to f can be selected (for
each Unit). The unit number for any Controllers without uploaded
data, however, will not be displayed. Also, selection will not be
possible if the uploaded information in the display was uploaded from
all Controllers. The UNIT display will be "-".
Note: For example, to download setting data from unit number 1 to
unit number 2, change the unit number from 2 to 1, and change
the number of unit number 1 to another unit number or
disconnect the socket connected to unit number 1. Be sure that
there is only one Controller with the same unit number on the
network at any one time.
Step 4
Press the LEVEL Key for at least 1 s to start the download.
Note: 1. down will flash on Display No. 2 during the download.
2. The mode will return automatically to the Operation Level
when the download has been completed.
Supplementary Explanation
To download to all Temperature Controllers, use the same
configuration as when the data was uploaded. Downloading is not
possible in the following circumstances. If downloading is not
possible, down will flash and then the upload display will be shown.
• An E5ZN has been added or deleted since the upload.
• The same number of Controllers are connected as when the
upload was executed, but when the unit numbers are different.
• The resistance thermometer/thermocouple type configuration is
different.
Copying Parameters from an E5ZN
Master to Other E5ZNs
This section describes how to copy parameters from Unit 1, used as
the master, to Units 2 and 3, as shown in the following diagram.
Data uploaded to the E5ZN-SDL can be downloaded only to a
Controller whose unit number has been uploaded. Therefore, after
copying the Master parameters, change the unit number of the
Controller where the data is to be downloaded to the unit number
from which data was uploaded (i.e., the master's unit number), and
then download the parameter data.
Step 1
Select Copy Mode.
Press the COPY Key for at least 1 s to enter Copy Mode.
Step 2
Press the UNIT Key to select the unit number of the master. In this
example, the master is unit number 1, so select 1.
Step 3
Upload all the parameters from the Master.
In this example, all the parameters from unit number 1 will be
uploaded to the E5ZN-SDL. Press the LEVEL Key for at least one
second to start the upload. up will flash on the display during the
upload.
The mode will return automatically to Run Mode when the upload
has been completed.
copy
up
0
copy
down
0
23
0
0
E5ZN-SDL
System Configuration
Master
E5ZN 1
E5ZN 2
E5ZN 3
23
0
0
copy
up
1
copy
up
1
Change the unit number of the Controller to which the data is to be
downloaded to the unit number of the Controller from which the data
was uploaded. When uploading has been completed, turn OFF the
power and disconnect the uploaded Controller (unit number 1) from
the socket or change the unit number to avoid using the same unit
number twice during the download.
In this example, change the unit number of the master from 1 to 5,
and change the unit number of the Controller to which the data is to
be downloaded from number 2 to number 1. The system
configuration will change to the configuration shown in the following
diagram.
Step 5
Select Copy Mode.
Turn ON the power and press the COPY Key for at least 1 s to enter
the Copy Mode.
Step 6
Set the download mode and the copy destination.
Use the DOWN Key to select down on Display No. 2. Press the UNIT
Key to select unit number 1. (The lowest unit number that is being
uploaded will be displayed in the download unit number display. At
initialization, there is no upload data, so the unit number display is
blank.)
Step 7
Press the UNIT Key for at least 1 s to start the download.
down will flash on the display during the download.
The mode will return automatically to Run Mode when the download
has been completed.
Step 8
Copying to Other Controllers
Repeat steps 4 to 7 to continue copying the data.
The following example shows copying data to unit number 3.
Turn OFF the power and change unit number 1 back to unit number
2.
Change unit number 3, where the data is to be downloaded, to unit
number 1. The system configuration is shown in the following
diagram. Turn ON the power and follow steps 4 to 7 to copy data to
unit number 3.
Step 9
Changing back to the original unit number.
After copying has been completed, turn OFF the power and change
back to the original the unit numbers.
In this example, turn OFF the power and change unit number 5 to
unit number 1, and change unit number 1 to unit number 3.
23
0
0
Master
Copy
destination
E5ZN 5
E5ZN 1
E5ZN 3
copy
up
0
copy
down
1
copy
down
1
23
0
0
Master
Copy
source
Copy
destination
E5ZN 5
E5ZN 2
E5ZN 1
Operating Procedure Overview
Parameters are divided into groups called levels. Each of the items that is set in any of the levels is called a parameter.
The parameters on the E5ZN are divided into the following seven levels:
❍: Indicates items that can be set.
Note: To move to the Advanced Function Setting Level, set the Initial Setting/Communications Protection parameter in the Protect Level to 0.
Of these levels in normal mode, the Initial Setting Level, Communications Setting Level, and Advanced Function Setting Level can be used only
when operation is stopped. Operation stops when any of these four levels are selected.
It is possible to enter Copy Mode while control is being performed, but copy operations (e.g., upload and download) can be used only when control
has stopped.
Mode/Level
During
operation
Operation
stopped
Normal
mode
Protect Level
❍
---
Operation Level
❍
---
Adjustment Level
❍
---
Initial Setting Level
---
❍
Advanced Function Setting Level
---
❍
Communications Setting Level
---
❍
Copy mode
---
❍
Operation Level
Adjustment Level
Power ON
Initial Setting Level
Communications
Setting Level
Advanced Function Setting Level
Protect Level
Copy
Mode
Control stops.
Password input
set value "−169"
During operation
Operation stopped
and M
Keys 3 s min.
and M
Keys 1 s min.
Key less
than 1 s
Key
3 s min.
Normal Mode
COPY Key
less than
1 s
COPY Key
1 s min.
Key less
than 1 s
Key
1 s min.
Flashes for Key
1 s or longer.
Key
1 s min.
Description of Modes
Protect Level
• To enter the Protect Level, simultaneously press the
and M
Keys for at least 3 s in the Operation Level or Adjustment Level.
The Protect Level is for preventing unwanted or accidental
modification of parameters. Protected levels will not be displayed,
and so the parameters in that level cannot be modified.
Operation Level
• This level is displayed first when you turn ON the power to the
E5ZN. You can move to the Protect Level, Initial Setting Level, or
Adjustment Level from this level.
• During operation, the PV, SP, and MV can be monitored, and the
SP, alarm value, upper limit alarm and lower limit alarm can be
monitored and modified.
Adjustment Level
• To enter the Adjustment Level, press the
Key for less than 1 s.
• This level is for entering set values and offset values for control.
The level contains parameters for setting the auto-tuning,
communications writing ON/OFF, hysteresis, multi-SP, input
correction values, heater burnout alarm (HBA) settings, PID
constants, etc. You can move to the top parameter of the Initial
Setting Level and Operation Level from here.
Initial Setting Level
• To enter the Initial Setting Level, press the
Key for at least 3 s in
the Operation Level or Adjustment Level. The first display flashes
after 1 s. The Initial Setting Level is for specifying the input type,
selecting the control method, setting the control period, setting
direct/reverse operation, and selecting the alarm type. You can
move to the Advanced Function Setting Level or Communications
Setting Level from this level. To return to the Operation Level, press
the
Key for at least 1 s. To move to the Communications Setup
Level, press the
Key for less than 1 s.
(The display will be blank ("----") when you move from the Initial
Setting Level to the Operation Level.)
Advanced Function Setting Level
• To enter the Advanced Function Setting Level, you must enter 0 for
the Initial Setting/Communications Protection parameter in Protect
Level, and then enter the password (−169) in the Initial Setting
Level.
• You can move only to the Initial Setting Level from the Advanced
Function Setting Level.
• The Advanced Function Setting Level sets the MV limits, event
input assignments, standby sequences, alarm hysteresis, and other
parameters.
Communications Setting Level
• To enter the Communications Setting Level, press the
Key for
less than 1 s in the Initial Setting Level. When the communications
settings are to be used, set the communications conditions in this
level. Communications with a host device (e.g., computer) enables
SPs to be read and written, and MVs to be monitored.
Initial setting value
CH
CH
L Key 1 s min.
CH
L Key
L Key
A
P
A
A
A
A
A
A
A
A
A
A
A
Top of initial setting level
P
P
A
P
Top of advanced function setting level
CH
ch2:
ch1:
Advanced function
setting level
Move to
the
advanced
function
setting
level by
entering
the
password
"−169".
Multi-SP used
SP ramp set
value
Parameter
initialize
Number of
multi-SP
used
Event input
allocation
Standby sequence
reset
Alarm 1 open
in alarm
Alarm 1
hysteresis
Alarm 2 open
in alarm
Alarm 2
hysteresis
Alarm 3 open
in alarm
Alarm 3
hysteresis
HBA used
Heater Burnout Latch
Heater burnout
hysteresis
Operation after
power ON
OUT1 transfer
output upper limit
OUT1 transfer
output lower limit
Control output 2
allocation
Auxiliary output 1
allocation
Auxiliary output 2
allocation
Auxiliary output 3
allocation
Auxiliary output 4
allocation
OUT2 transfer
output upper limit
OUT2 transfer
output lower limit
SUB3 transfer
output upper limit
SUB3 transfer
output lower limit
SUB4 transfer
output upper limit
SUB4 transfer
output lower limit
Current output type
Input type
Scaling upper limit
Scaling lower limit
Decimal point
Temperature unit
PID control and
ON/OFF control
switching
Alarm 1 type
Alarm 2 type
Alarm 3 type
Control output 1
allocation
SP upper limit
SP lower limit
Control period
(heat)
Control period
(cool)
Direct/reverse
operation
in-h
100
01
in-h
100
01
in-h
100
0
alh1
0.2
C
1
0
alh2
0.2
C
1
0
hbu
on
u
0
hbl
off
u
0
mspu
off
u
0
eV-m
1
u
0
M
M
M
M
M
M
a1lt
off
1
0
a2lt
off
1
0
a3lt
off
1
0
inf
0.0
1
0
pVad
off
u
0
M
isdp
off
u
0
init
off
u
0
eV
none
u
0
rest
a
u
0
al1n
n-o
1
0
al2n
n-o
1
0
alfa
0.65
u
0
ol-h
105.0
1
0
ol-l
-
5.0
1
0
sero
off
u
0
hbh
0.1
1
0
M
ot-2
0
u
0
M
amoV
0
u
0
sedu
3
u
0
M
istp
0
u
0
cjc
on
u
0
sprt
0
1
0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
al3n
n-o
1
0
alh3
0.2
C
1
0
M
M
M
sub4
17
u
0
out2
5
u
0
M
sub1
2
u
0
M
sub2
7
u
0
M
sub3
12
u
0
M
tr1h
1300
u
0
M
cont
no
u
0
M
tr3h
1300
u
0
M
tr1l
-200
u
0
M
tr2h
1300
u
0
tr2l
-200
u
0
M
M
tr3l
-200
u
0
M
tr4h
1300
u
0
M
M
ot-1
0
u
0
tr4l
-200
u
0
in-l
0
1
0
dp
0
1
0
sl-h
1300
C
1
0
sl-l
- 200
C
1
0
cntl
onof
1
0
alt1
2
1
0
cp
2
1
0
alt2
2
1
0
in-t
0
u
0
in-h
100
1
0
d-u
c
u
0
alt3
2
1
0
c-cp
2
1
0
oreV
or-r
1
0
out1
0
u
0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
len
7
u
0
sbit
2
u
0
prty
eVen
u
0
sdwt
20
u
0
M
M
M
M
2
M
Additional PV display
The display below indicates that
there is setting data for ch1 or ch2.
CH
Press the Button to switch
between the screens for ch1 and ch2.
: This symbol indicates setting data that is displayed only for models with pulse output.
("Models with pulse output" is used here to indicate models with voltage output or transistor output.)
: This symbol indicates setting data that is displayed only for models with analog output.
Communications
setting level
L Key
1 s max.
Communica-
tions data
length
Communica-
tions stop bit
Communica-
tions parity
Communica-
tions
response wait
time
Voltage output type
Sensor error
indicator used
Move to advanced
function setting level
α
MV upper limit
MV lower limit
Input digital filter
Additional
temperature input
shift value display
Temperature
input shift type
Alarm 1 latch
Alarm 2 latch
Alarm 3 latch
Input error output
Cold junction
compensating
method
The setting data that can be set from the E5ZN-SDL Setting Display Unit is shown below.
Depending on the protection settings and other factors, some settings may not be displayed.
A password is required to move to the advanced function setting level.
L Key, 1 s min.
Adjustment level
Operation level
Protect level
Copy mode
COPY Key
1 s min.
L Key, 1 s min.
L and M
Keys 1 s min.
L and M
Keys 3 s min.
Top of operation level
P
P
P
Top of adjustment level
Returns
automatically or
when the COPY
Key is pressed
for 1 s max.
Run/stop
Alarm value 1
Upper-limit alarm
value 1
Lower-limit alarm
value 1
Alarm value 2
PV
PV/SP
Multi-SP
SP ramp monitor
Heater current
value monitor
Upper-limit alarm
value 2
Lower-limit alarm
value 2
Alarm value 3
MV monitor for
heating
MV monitor for
cooling
SP 0
SP 1
Temperature
input shift
Cancel AT execution.
Allow/prohibit
communications
writing
Heater current
value monitor
Heater burnout
detection
Upper-limit temperature
input shift value
Lower-limit temperature
input shift value
Proportional band
Integral time
Derivative time
M
wtpt
off
u
0
M
M
at
off
1
0
ct
0.0
1
0
hb
0.0
1
0
sp-0
0
C
1
0
sp-1
0
C
1
0
cmwt
on
u
0
oapt
0
u
0
icpt
0u
0
M
M
M
M
M
25
0
C
1
0
sp-m
0
C
1
0
ct
0.0
1
0
m-sp
0
1
0
r-s
stop
1
0
al-1
0
C
1
0
al1h
0
C
1
0
al1l
0
C
1
0
al-2
0
C
1
0
al2h
0
C
1
0
al2l
0
C
1
0
al-3
0
C
1
0
o
0.0
1
0
c-o
0.0
1
0
25
C
1
0
ins
0.0
C
1
0
insh
0.0
C
1
0
insl
0.0
C
1
0
p
8.0
C
1
0
i
233
1
0
d
40
1
0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
c-sc
1.00
1
0
c-db
0.0
C
1
0
of-r
50.0
1
0
hys
1.0
C
1
0
chys
1.0
C
1
0
M
M
M
M
M
Operation/
adjustment
protection
Initial setting/
communications
protection
Setting change
protection
During control
Control stopped
1 s min.
3 s min.
Cooling coefficient
Dead band
Manual reset value
Heating hysteresis
Cooling hysteresis
Set the input type corresponding to the sensor used. The E5ZN
supports two types of inputs: resistance thermometers and
thermocouples. The setting is different for each input type. Refer to
the following tables and set the correct value for the temperature
range and the sensor used. The same input type is used by channel
1 and channel 2.
Resistance Thermometer Input
Thermocouple Input
Note: The default settings are 0.
Output Assignments
• The following table shows the default functions assigned to each
output terminal.
Note 1. Only for models with analog output.
The functions can be changed as desired by setting output
assignments. Refer to the following table for functions that can be
allocated. Different outputs can be allocated to the same function.
Note 2. Assignment is not possible for SUB1 or SUB2.
• If Control Output (Cooling) is assigned to an output for channel 1,
heating/cooling control will be performed for channel 1. If Control
Output (Cooling) is assigned to an output for channel 2, heating/
cooling control will be performed for channel 2.
Input Type
Name
Set
Value
Input SP Range
Resistance
thermome-
ter
Pt100
0
−200 to 850
(°C)/
−300 to 1500 (°F)
1
−199.9 to 500.0 (°C)/ −199.9 to 900.0 (°F)
2
0.0 to 100.0 (°C)/
0.0 to 210.0 (°F)
JPt100
3
−199.9 to 500.0 (°C)/ −199.9 to 900.0 (°F)
4
0.0 to 100.0 (°C)/
0.0 to 210.0 (°F)
Input Type
Name
Set
Value
Input SP Range
Thermo-
couple
K
0
−200 to 1300 (°C)/
−300 to 2300 (°F)
1
−20.0 to 500.0 (°C)/
0.0 to 900.0 (°F)
J
2
−100 to 850
(°C)/
−100 to 1500 (°F)
3
−20.0 to 400.0 (°C)/
0.0 to 750.0 (°F)
T
4
−200 to 400
(°C)/
−300 to 700 (°F)
17
−199.9 to 400.0 (°C)/ −199.9 to 700.0 (°F)
E
5
0 to 600
(°C)/
0 to 1100 (°F)
L
6
−100 to 850
(°C)/
−100 to 1500 (°F)
U
7
−200 to 400
(°C)/
−300 to 700 (°F)
18
−199.9 to 400.0 (°C)/ −199.9 to 700.0 (°F)
N
8
−200 to1300 (°C)/
−300 to 2300 (°F)
R
9
0 to 1700 (°C)/
0 to 3000 (°F)
S
10
0 to 1700 (°C)/
0 to 3000 (°F)
B
11
100 to1800 (°C)/
300 to 3200 (°F)
ES1A
Infrared
Tempera-
ture
Sensor
K10 to 70°C
12
0 to 90
(°C)/
0 to 190 (°F)
K60 to 120°C
13
0 to 120
(°C)/
0 to 240 (°F)
K115 to 165°C
14
0 to 165
(°C)/
0 to 320 (°F)
K160 to 260°C
15
0 to 260
(°C)/
0 to 500 (°F)
Analog
input
0 to 50 mV
16
One of following ranges depending on the
scaling: −1999 to 9999, −199.9 to 999.9
Name
Terminal
number
Setting
OUT1 (control output 1)
7, 8
Channel 1 control output (heating)
OUT2 (control output 2)
1, 2
Channel 2 control output (heating)
SUB1 (auxiliary output 1) 13, 15
Channel 1 Alarm 1 and HB alarm OR
output
SUB2 (auxiliary output 2) 14, 15
Channel 2 Alarm 1 and HB alarm OR
output
SUB3 (auxiliary output 3) 16, 17
Channel 1 Transfer output: PV (See note
1.)
SUB4 (auxiliary output 4) 16, 18
Channel 2 Transfer output: PV (See note
1.)
Set value
Function
0
Channel 1 Control output (heating)
1
Channel 1 Control output (cooling)
2
Channel 1 Alarm 1 and HB alarm OR output
3
Channel 1 Alarm 2 output
4
Channel 1 Alarm 3 output
5
Channel 2 Control output (heating)
6
Channel 2 Control output (cooling)
7
Channel 2 Alarm 1 and HB alarm OR output
8
Channel 2 Alarm 2 output
9
Channel 2 Alarm 3 output
10
Channel 1 Transfer output: Present SP (See note 2.)
11
Channel 1 Transfer output: Ramp SP (See note 2.)
12
Channel 1 Transfer output: PV (See note 2.)
13
Channel 1 Transfer output: MV (heating) (See note 2.)
14
Channel 1 Transfer output: MV (cooling) (See note 2.)
15
Channel 2 Transfer output: Present SP (See note 2.)
16
Channel 2 Transfer output: Ramp SP (See note 2.)
17
Channel 2 Transfer output: PV (See note 2.)
18
Channel 2 Transfer output: MV (heating) (See note 2.)
19
Channel 2 Transfer output: MV (cooling) (See note 2.)
Allocating an Alarm 2 Output to the SUB2 Auxiliary Output 2
for Channel 1
Use host communications or the E5ZN-SDL Setting Display Unit to
set 3 as assignment for auxiliary output 2.
Alarms 1 and 2
Note: 1. With set values 1, 4 and 5, the upper and lower limit values
can be set independently for each alarm type and are
expressed as "L" and "H."
2. Set value: 1, Upper- and lower-limit alarm
3. Set value: 4, Upper- and lower-limit range
4. Set value: 5, Upper- and lower-limit with standby sequence
For upper- and lower-limit alarms in the above diagrams, the
alarm is always OFF in cases 1 and 2 if the hysteresis for
the upper and lower limits overlaps, and the alarm is always
OFF for case 3.
5. Set value: 5, Upper- and lower-limit with standby sequence
alarm.
Alarm is always OFF when the upper-limit and lower-limit
hysteresis overlaps.
6. Refer to Alarm Hysteresis for information on standby
sequences.
Alarm 3
Note: If the alarm type is set to value from 1 to 7, set the alarm value
as the deviation from the SP.
Use host communications or the E5ZN-SDL Setting Display Unit to
set the alarm type separately for each alarm for alarms 1 to 3. The
default settings are for an upper-limit alarm (set value: 2). Set the
alarms separately for each channel.
Set
value
Alarm type
Alarm output
When alarm value X is
positive
When alarm value X is
negative
0
No alarm
Output OFF
1
Upper and
lower limits
(See note 1.)
(See note 2.)
2
Upper limit
3
Lower limit
4
Upper and
lower limits of
range (See
note 1.)
(See note 3.)
5
Upper- and
lower-limit
alarm with
standby se-
quence (See
notes 1 and 6.) (See note 5.)
(See note 4.)
6
Upper-limit
alarm with
standby se-
quence (See
note 6.)
7
Lower-limit
alarm with
standby se-
quence
8
Absolute-val-
ue upper limit
9
Absolute-val-
ue lower limit
10
Absolute-val-
ue upper limit
with standby
sequence
(See note 6.)
11
Absolute-val-
ue lower limit
with standby
sequence
(See note 6.)
L
ON
OFF
H
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
L
ON
OFF
H
SP
L
ON
OFF
H
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
L
H SP
L
H
SP
L
H
SP
L
H
SP
SPLH
Case 1
Case 2
Case 3 (Always ON)
H < 0, L < 0
H < 0, L > 0
H < L
H > 0, L < 0
H > L
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L
L
H SP
L
H
SP
L
H SP
H L
SP
L
H
SP
Case 1
Case 2
Case 3 (Always ON)
H < 0, L < 0
H < 0, L > 0
H > 0, L < 0
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L
Set
value
Alarm type
Alarm output
When alarm value X is
positive
When alarm value X is
negative
0
No alarm
Output OFF
1
Upper and
lower limits
Always ON
2
Upper limit
3
Lower limit
4
Upper and
lower limits of
range
Always OFF
5
Upper- and
lower-limit
alarm with
standby se-
quence
Always OFF
6
Upper-limit
alarm with
standby se-
quence
7
Lower-limit
alarm with
standby se-
quence
8
Absolute-val-
ue upper limit
9
Absolute-val-
ue lower limit
10
Absolute-val-
ue upper limit
with standby
sequence
11
Absolute-val-
ue lower limit
with standby
sequence
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
X
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
If an error occurs, an error message will be displayed on the E5ZN-SDL Setting Display Unit.
Use the error message to check the type of error and correct the error accordingly.
PV display
Error
Meaning
Action
Operation
Input error
The input value has exceeded the control
range∗.
∗Control Range
Resistance thermometer or thermocouple
input:
SP lower limit −20°C to SP upper limit
20°C
(SP lower limit −40°F to SP upper limit
40°F)
ES1A input:
Same as input indication range
Analog input:
−5% to 105% of scaling range
Check the wiring of inputs for
mistakes in wiring, disconnections,
short-circuits, and the input type. If
no abnormality is found in the
wiring and input type, turn the
power OFF then back ON again. If
the display remains the same, the
E5ZN must be repaired. If the
display is restored, then electrical
noise may be affecting the control
system. Check for electrical noise.
After the error occurs, the
error is displayed, and control
outputs turn OFF.
Alarm outputs operate as if
the upper limit has been
exceeded.
This error message is
displayed when the PV or PV/
SP is displayed.
Display Range
Over
This message does not indicate an error. It is
displayed if the PV exceeds the display range
and the control range is larger than the
display range (−1999 (−199.9) to 9999
(999.9)).
• Less than -1999 (−199.9):
• More than 9999 (999.9):
---
Control continues and
operation is normal. This
message is displayed when
the PV or PV/SP is displayed.
Memory Error
There is an error in the internal memory
operation for the E5ZN-SDL Setting Display
Unit.
First, turn the power OFF then back
ON again. If the display remains the
same, the E5ZN must be replaced.
If the display is restored, then
electrical noise may be affecting
the control system. Check for
electrical noise.
Key operations are not
possible.
Current Value
Exceeded
This error is displayed when the heater
current value exceeds 55.0 A.
---
Control continues and
operation is normal. This
error message is displayed
when the heater current value
monitor is displayed.
Disabled Status This error is displayed when one of the
following errors has occurred in the
connection with the E5ZN.
• The connecting cable is disconnected.
• The power supply to the E5ZN-SDL has
been turned OFF while in Copy Mode.
• A memory error has occurred in the E5ZN.
The control output and alarm outputs will be
OFF for the E5ZN generating the error.
---
Controllers that do not show
this disabled status will
continue operation and will
operate normally. The
selected Controller and the
channel status will be
displayed.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.