Lindab UltraLink FTCU Technical Information

Text of the manual

We reserve the right to make changes without prior notice

Introduction UltraLink® FTCU is a highly accurate flow controller, which measures the flow with an angled ultrasonic beam which can be calculated and compensated to a very high accuracy over the whole flow range. The method is very stable over time due to that it is not sensitive to dirt and the design minimizes the dust accumulation on the flow sensors. An increased focus on energy saving has led to ventilation systems requiring low min- imum flows. The low flows are a problem since they are very difficult to measure and it is makes it difficult to control the ventilation system. The new technology of UltraLink® makes it possible to measure lower air flows com- pared to today’s products while maintaining measurement accuracy. This offers great advantages for the user in terms of comfort and savings in energy consumption, which is of great interest. Content Introduction ....................................................................................................2 Overview ........................................................................................................3 Description .....................................................................................................3 Planning ..........................................................................................................4 Mounting ........................................................................................................6 Connections ...................................................................................................6 Power supply ..................................................................................................8 Display ............................................................................................................9 PIN-code ........................................................................................................9 Settings ........................................................................................................10 ID-numbers .................................................................................................. 14 Troubleshooting ........................................................................................... 14 Maintenance ................................................................................................. 14 Technical data .............................................................................................. 15 Airflows ......................................................................................................... 15 Appendix A – Modbus register .................................................................... 16

m³/h l/s m/s °C

% - Actual value m³/h l/s m/s Setpoint - - Lindab UltraLink Controller FTCU Airflow IP42 Patented Status m³/h l/s m/s °C Mode We reserve the right to make changes without prior notice Description Application The Controller is suitable for measuring and controlling air flow and measuring temperature. Communication is established with analog or digital signals using Modbus. Design The Controller consists of a sensor body attached to a damper body with Lindab Safe gaskets. You are not allowed to make any changes or adjustment to the motor or its end-stops! Two flow sensors are mounted on the sensor body and connected to a display unit. The display unit is mounted on top of a shelf on the damper body. The sensor and damper bodies can rotate relative to each other. This means that the sensors can be optimally positioned independently of the desired position of the display and damper body. Positioning the sensor body correctly after a disturbance is crucial for the measurement accuracy, see page 4 for directions on how to mount the Controller for optimal performance. For FTCU in dimensions 400 — 630, a flange holds the damper and sensor bodies together, the flange must be loosened by unscrewing a nut in order to rotate them. The nut of the flange on the FTCU dimension 400 is 10 mm and the nut on the FTCU dimension 500 — 630 is 13 mm. Note! The flow sensors are placed at a fixed distance to each other and they shall never be removed and not used as handles when turning the sensor body. Overview Display unit Status light CE-mark IP classification Air flow direction Mode button Display parameters Damper body Display unit Sensor body Flow sensor Air flow direction RTU TCP/IP Flange Dimension 100 - 315 Dimension 400 - 630 Bluetooth® logotype QR code

We reserve the right to make changes without prior notice

Planning The longer distance to disturbance, i.e. the longer straight duct before the Controller, the higher the measurement accuracy will be. However this is not the only factor which affects the accuracy of the measurement. The rotation of the sensor body and hence the positioning of the first flow sensor ( in the direction of the air flow) has an impact on the uncertainty of the measure- ment. It is not recommended to mount the Controller so that the first flow sensor (*) is placed on an outer radius of a fitting, see table below. For example: in the case of the bend in the table below, by rotating the sensor body to position the first sensor according to the first picture (with the first flow sensor on the inner radius of the bend), the Controller can be placed at the distance of two duct diameters from the disturbance to achieve 5 % uncertainty. Positioning the sensor body according to the second picture (with the first sensor on the outer radius of the bend), the Controller must be mounted five duct diameters from the disturbance to achieve the same level of uncertainty. Never use an UltraLink® on the outlet side of a duct fan. Place it on the inlet side or in worst case use a flow conditioner if it must be placed on the outlet side. Disturbance * Placement of first flow sensor Measurement uncertainty ± % or X l/s depending wich is the greatest of percentage or the absolute value for the specific product size, see table “Technical data” on page 15. a 2-4·Ød >4-5·Ød >5·Ød Bend a Ød * Inner radius 5 5 5 Bend a Ød * Outer radius (Not recommended) 20 10 5 Bend a Ød * a Ød * Side 10 5 5

We reserve the right to make changes without prior notice

Disturbance * Placement of first flow sensor Measurement uncertainty ± % or X l/s depending wich is the greatest of percentage or the absolute value for the specific product size, see table “Technical data” on page 15. a 2-4·Ød >4-5·Ød >5·Ød Reducer a Ød * Duct diameter decrease 5 5 5 Reducer a Ød * Duct diameter increase 10 5 5 T-piece a Ød * Inner radius 10 5 5 T-piece a Ød * Outer radius (Not recommended) 20 10 5 T-piece a Ød * Side 10 5 5 a Ød *

8 9 10 11 12

SCL SDA GND 3V3 14 15 16 13 We reserve the right to make changes without prior notice Mounting Mount the Controller into the air duct system according to the mounting instructions for Lindab Safe. Do not use the flow sensors as handles when you mount the Control- ler since this may cause damaged and changes in their positions might influence the measurement accuracy. Make sure the airflow arrow is pointing in the direction of the airflow. Position the damper body so that the display is visible from some direction. For future connections it is important that the screws on the lid of the display can be removed. Note the ID-number of the Controller. The ID can be found on the label of the box it was delivered in or on the label on the Controller itself and are the three last numbers of the serial no. Rotate the senor body to the correct position according to the chapter “Planning”, when it is positioned accurately it should be fixed with screws to the damper body in the same way as when you connect ducts and fittings. Controllers of sizes 400 — 630 has a flange which needs to be loosened by unscrewing a nut. This nut is 10 mm for dimension 400 Connections Connect the Controller to a remote terminal unit using RS485 or analog terminals. Connections are made in the terminal board which can be accessed when the lid of the display unit is removed. In the back of the lid there is a picture with a list of the terminals. 1. 24V, power supply (AC G, DC +) * 2. GND, power supply (AC G0, DC -) * 3. +B, connection for Modbus via RS485 4. -A, connection for Modbus via RS485 5. SH, shield 6. GND, ground (system neutral) 7. AO1, analog output 8. AO2, analog output 9. AIN, analog input 10. MO1, connection for motor 11. MO2, connection for motor 12. GND, ground (system neutral) 13. SCL, not used 14. SDA, not used 15. GND, ground (system neutral) 16. 3V3, not used (in case of biasing) *) When using AC terminal 1 (G) should have system potential and terminal 2 (G0) should be system neutral. Recommendations for wiring: Function Cable type 24 V Supply 2-wire, thickness depending on length and load, max. 1,5 mm² RS485 2-wire shielded twisted pair, min. 0,1 mm² (LIYCY cable) Supply the Controller with power from a transformer. and 13 mm for 500 — 630. By loosening the nut the sensor body can be turned into the desired position. Once this is achieved, the flange must be fastened by tightening the nut. To be able to connect cords to the terminal board the rubber cable grommet on the backside of the display unit must be punctured, preferably using an awl or something pointy to ensure tightness to the environment. When the cords have been connected they must be strain relieved. The cords can be attached to the shelf by using cable ties that are attached around cut outs in the shelf. The display unit and actuator is mounted to enable the Controller to be insulated up to 50 mm. You must under no circumstances make any holes or connect anything with screws to the sensor body since this will have an impact on measurement accuracy!

We reserve the right to make changes without prior notice

Digital connection Connect A on the RTU to -A on the display unit and B to +B. When connecting more than one Controller in series it is important to keep connecting -A to -A and +B to +B since crossing them will stop Modbus from working. The shield in the RS485 cable should be connected to ground at the transformer and then continuously connect to ”SH” on all the UltraL- inks that are powered from that transformer. If more than one transformer is used on the bus, the shield is broken at each transformer so ”SH” on every product only has connection to ground at the transformer from which its power is supplied. It is recommended to use RS485 cables with twisted pairs and shield, do not supply power in the same cable unless the cable is produced for that purpose. Analog connection When connecting the Controller using analog signals, it is important to connect the analog out signals on the Controller (AO1, AO2) to the analog in terminals on the RTU and the analog in signal (AIN) is connected to the analog out terminal on the RTU. Also make sure to connect the cables to the same analog ground. Bluetooth® connection If the product is equipped with Bluetooth (the Bluetooth logotype is printed on the display unit), wireless communication with the UltraLink can be established. Using a smartphone or tablet with the Lindab UltraLink App, nearby UltraLinks can be identified. It is then possible to connect to one unit and view information regarding that UltraLink, such as active measurements and settings. Mobile app The app “UltraLink” is available on both Android and iOS, it’s free to download from Google Play or App store. Like the PC configuration tool, all settings can be changed via the app. This means all settings can be individually chosen for the specific building, it is therefore necessary to protect the unit with the PIN code in the UltraLink menu. For a discription on how this is done, see page 9. Repeater If the bus is longer than 300 meters or if there are more than 30 devices, the system might need an RS485 repeater (FDS-R, see picture to the right) to be able to communicate in an efficient way. Biasing The master on the bus must have biasing on -A and +B. This is more or less standard on BMS-controllers, but if commu- nication should be established with a conventional computer using a RS485-USB converter, then it is important to make sure that the converter has a bias circuit. If communication fails and you are uncertain about existance of biasing, you can add biasing resistors in the screw terminal on one of the UltraLinks to see if this is the cause of the communication failure. Use 500 - 1000 Ω resistors and connect one resis- tor from -A to GND and one from +B to the 3V3 terminal. It is also recommendedto add a 120 Ω termination resistor between -A and +B on the last UltraLink on the bus to avoid signal reflections.

We reserve the right to make changes without prior notice

0,7 0,6 0,8 0,9 1 1,1 1,2 1,3 1,4 1,5 Wire cross section Area [ mm2 ] 0 0,1 0,2 0,3 0,4 0,5 0,20 0,15 0,10 0,05 0 Copper Resistance [ Ω/m ] Power supply Transformer sizing The needed size of 24 V AC transformer(s) can be defined by adding up the dimensioning power consumption [VA] of all the components. The transformer power must exceed this. Use only safety isolating transformers. Cal- culation of the current demand I: I = (P1+P2+…+Pn) / U [A] where: Pn is the dimensioned power consumption for each com- ponent [VA] U is the voltage (24) [V]. If the current demand I exceeds 6 A ( which corresponds to approximately 150 VA for a 24 V AC transformer ), it is necessary to use more transformers to prevent overheat- ing. Supply cable sizing The wire size of the supply cable can be determined by calculating the resistance per meter R. The calculation presupposes that a voltage drop of e.g. 2 V is accepted in the supply cable: R(per m) = Udrop / (I × L) [Ω/m] where: Udrop is the accepted voltage drop (2 V) in the cable [V] I is the current [A] L is the longest distance of supply cables from trans- former to a component [m] Power consumption The power consumption for dimensioning supply cables for an UltraLink® Controller is dependant on the size of the product. On page 15 in the table: “Technical data”, the power consumptions of different products are listed. It is not recommended to use a transformer with a higher capacity than 150 VA! Example: Udrop = 2 V, I = 4 A, L = 20 m R (per m) = 2V / (4A × 20 m) = 0,025 Ω/m In the diagram a Wire cross section Area of 0,7 mm² can be read. Wire cross section area as a function of resistance per m for copper wire

m³/h l/s m/s °C

% - Actual value m³/h l/s m/s Setpoint - - Lindab UltraLink Controller FTCU We reserve the right to make changes without prior notice Display The display can show useful information both with the diode flashing in green (status light) and with parameters in the LCD. If the product is equipped with Bluetooth, then the diode will also flash in blue every three seconds. If a device has been connected to the UltraLink via Blue- tooth, then the diode will flash in blue every other second. By short pressing the mode button you can change the displayed parameter. If the button is pressed for more than 5 seconds (long press) then the configuration menu will be visible. The arrow at the bottom of the display indicates the current parameter type and unit. For a detailed description on configurating the UltraLink using the mode button on the display, see page 13. Parameter structure The information menu is visible in the display as soon as the device is powered and by default the air flow in m³/h is shown. You can toggle between the different parameters in the menu by short pressing the Mode button. The arrows at the bottom of the menu indicates if the visible value is an actual reading or a set point and also what unit the current value has (if any). The following list of parameters are available; • Actual air flow (m³/h) • Actual air flow (l/s) • Actual air velocity (m/s) • Actual Temperature (°C) • Damper position (%, 100% = fully open) • Current set point (m³/h) • Current set point (l/s) • Current set point (m/s) • Controller’s ID number • Flow rate set point max *) • Flow rate set point min *) *) Only visible if analog control (register 4×071=1) and if the control variable is flow rate (4×070=2). If max and min values are the same the product is working as a constant flow regulator with set point according to that value. Status light The green status light indicates: Mode Function No light Controller is turned off Slow flashing light Motor is regulating Fast flashing light A problem has occurred, error code will be visible in display Constant light Controller is turned on and functioning as normal PIN code UltraLink with Bluetooth must be protected againt unauthorized access by PIN-code, which has to be stated before changes to the settings can be made. It is important to choose and change the code that the product is delivered with (1111), to ensure that no unauthorized changes are made. The Bluetooth radio can be disabled by setting register 4×007 to 0. The code can be changed in three ways: • using the configuration menu in the display, see page 13 for instructions. • connecting a PC via Modbus and using the “Configuration Tool” software. • connect a Bluetooth device and use the “UltraLink” application.

We reserve the right to make changes without prior notice

Settings All available settings are presented in the appendix. The settings can be changed via the RS485 bus and can be done from any device and configuration that can communicate using Modbus, but preferably the UltraLink® Configuration tool (See separate documentation). If the products is equipped with Bluetooth the settings can be changed with an app, which can downloaded from Google Play or App Store. Instructions for the most common settings are described below. For more register details see appendix. Digital communication settings Registers 4x001-4x009 are used to configure communication settings. When initializing contact for the first time the default settings will be active; Modbus id: Last three digits in the serial number (also visible in the display if the product has power) Baud rate: 19200 Parity: Odd Stop bits: 1 After updating any of the communication parameters the product needs to be power cycled for the changes to take effect. If communication fails with the default parameters selected in the UltraLink® configuration tool, then the communication settings on the Controller might have been changed previously. Verify the settings in the display (See page 9 for instruc- tions) Control settings The Controller can be read and controlled in several different ways. Primarily you need to set the following registers to determine what variable you will use to control the device and if the control signal comes analog or via bus; 1. Configure register 4×070 for what kind of set point you will control the device with (0 = no control, 1 = damper position, 2 = flow rate) 2. Configure register 4×071 for either bus or analog control of set points (0 = bus, 1 = analog) 3. During operation set points can be applied using registers 4x302 (damper position) and 4×314 (flow) depending on the setting from point 1 above. The set point for damper position has predefined limits 0–100%, where 0% means fully closed and 100% means fully open. The limits for flow has default values according to the table below but can be modified using registers 4×315 and 4×316. The default maximum values corresponds to the upper limit where accuracy is guaranteed. The value can be set higher, but this may cause worse accuracy of the readings. Default values for the relevant registers are according to the table below. (Default values for flow max corresponds to 15 m/s). Size Ø [mm] 4×314 Flow Set Point [l/s] 4×315 Flow Set Point Minimum [l/s] 4×316 Flow Set Point Maximum [l/s] 4×070 Damper Regulation Conf. 4×071 Damper Input Conf. 100 24 0 118 2 (Flow) 1 (Analog) 125 37 0 184 160 60 0 302 200 94 0 471 250 147 0 736 315 234 0 1169 400 377 0 1885 500 589 0 2945 630 935 0 4676 PLEASE LOOK IN THE APPENDED MODBUS REGISTER FOR INSTRUCTIONS ON HOW TO CHANGE REGISTER

We reserve the right to make changes without prior notice

VALUES. SOME VALUES HAS SCALE FACTORS AND SOME VALUES OCCUPY TWO REGISTERS! Analog in settings If using analog communication (4×071=1) you need to specify the operational voltage range and also corresponding max and min values; 1. Configure register 4×500 for analog in level configuration ( (0) 0-10V, (1) 10-0V, (2) 2-10V, (3) 10-2V) if you are using analog control of the set points. (If set points are controlled via bus this point can be ignored) 2. Configure registers 4×501–504 with relevant data for max and min levels for the voltage range selected in previous step. Register 4×501–502 are used if the device is controlled with angle (4×070=1) and registers 4×503–504 are used if the devi- ce is controlled using flow (4×070=2). If set points are controlled via bus this point can be ignored. Default values for the relevant registers are according to the table below. (Default values for flow max corresponds to 7 m/s). Size Ø [mm] 4x070 Damper Regulation Conf. 4x500 Analog In Level config 4x501 Angle Min [%] *) 4x502 Angle Max [%] *) 4x503 Flow Min [l/s] 4x504 Flow Max [l/s] 100 2 (Flow) 2 (2-10V) 0 100 0 55 125 0 100 0 86 160 0 100 0 141 200 0 100 0 220 250 0 100 0 344 315 0 100 0 546 400 0 100 0 880 500 0 100 0 1374 630 0 100 0 2182 *) 0% means fully closed damper position and 100% means fully open damper position. PLEASE LOOK IN THE APPENDED MODBUS REGISTER FOR INSTRUCTIONS ON HOW TO CHANGE REGISTER VALUES. SOME VALUES HAS SCALE FACTORS AND SOME VALUES OCCUPY TWO REGISTERS! Analog out settings Analog out is always active but you need to specify what kind of data you want to read on the two ports; 1. Configure registers 4×401 and 4×431 for the variables you want to read on the analog out terminals (0 = Flow, 1 = Tempe- rature, 2 = Damper position). 2. Configure registers 4×400 and 4×430 for analog out level configuration ( (0) 0-10V, (1) 10-0V, (2) 2-10V, (3) 10-2V) 3. Configure registers 4×401–409 and 4×431–439 with relevant data for max and min levels for the voltage range selected in step 2. You only need to configure the max and min values corresponding to the variable selected in step 1. Size Ø [mm] 4x400 Level Conf. 4x401 Unit Conf. 4x402 Temp Min [°C] 4x403 Temp Max [°C] 4x404 Flow Min [l/s] 4x406 Flow Max [l/s] 4x408 Angle Min [%] *) 4x409 Angle Max [%] *) 100 2 (2-10V) 0 (Flow) 0 50 0 55 0 100 125 0 50 0 86 0 100 160 0 50 0 141 0 100 200 0 50 0 220 0 100 250 0 50 0 344 0 100 315 0 50 0 546 0 100 400 0 50 0 880 0 100 500 0 50 0 1374 0 100 630 0 50 0 2182 0 100 *) 0% means fully closed damper position and 100% means fully open damper position.

We reserve the right to make changes without prior notice

Default values for the relevant registers related to “Analog Out 2” are according to the table below (Default values for flow max corresponds to 7 m/s). Size Ø [mm] 4x430 Level Config 4x431 Unit Conf. 4x432 Temp Min [°C] 4x433 Temp Max [°C] 4x434 Flow Min [l/s] 4x436 Flow Max [l/s] 4x438 Angle Min [%] *) 4x439 Angle Max [%] *) 100 2 (2-10V) 2 (Angle) 0 50 0 55 0 100 125 0 50 0 86 0 100 160 0 50 0 141 0 100 200 0 50 0 220 0 100 250 0 50 0 344 0 100 315 0 50 0 546 0 100 400 0 50 0 880 0 100 500 0 50 0 1374 0 100 630 0 50 0 2182 0 100 *) 0% means fully closed damper position and 100% means fully open damper position. PLEASE LOOK IN THE APPENDED MODBUS REGISTER FOR INSTRUCTIONS ON HOW TO CHANGE REGISTER VALUES. SOME VALUES HAS SCALE FACTORS AND SOME VALUES OCCUPY TWO REGISTERS! Settings for override The controller has two different override functions that can be initiated either over the bus or with analog input (only in case of input voltage range of 2-10 V or 10-2 V). If controlled via bus (register 4x071 = 0), then the damper can be forced (register 4x151) to fully open or fully closed position, or the flow rate setpoint can be set to minimum or maximum flow rate setpoint (according to registers 4x315 and 4x316, respectively). If the unit is controlled with analog input (4x071 = 1), then the damper can be forced to fully closed position (regardless the settings in register 4x501, which represents the mini- mum angle (fully closed) of the damper in normal mode). Override function by bus: 1. Normal mode, no override (register 4x151 = 0). 2. Go to maximum flow rate setpoint (register 4x151 = 1). 3. Go to minimum flow rate setpoint (register 4x151 = 2). 4. Go to fully open damper position (register 4x151 = 3). 5. Go to fully closed damper position (register 4x151 = 4). If an override is initiated, it can be restored either manually by setting register 4x151 to 0, or automatically after the prede- fined override timeout in register 4x150. Analog override function: In analog mode (4x071 = 1), the override function can only be called if input voltage range is set to 2-10 V or 10-2 V (4x500 = 2 or 3, respectively) and the controlled variable is flow rate (4x070 = 2). If these settings are active, the override function is set as follows: 1. Normal mode, no override (input voltage ≥ 2 V). 2. Go to fully closed damper position (if input voltage is lower than the value defined in register 4x511).

We reserve the right to make changes without prior notice

Configuration menu structure The configuration menu is activated by long pressing the button (5 sec). After long pressing the button a new menu will appear with three different options; • Con.Set (Connection settings) • AIn.Set (Analog In settings) • Cancel (Cancel and return to information menu) You can toggle between the three options by short pressing the button. Select the option you want and long press to proceed down in the menu structure. Under Con.Set (connection settings) you can find the following options (toggle with short press, select with long press); Menu tag Description Options Description • Pr. Protocol Pr.PAS Pr.Mod Pascal protocol Modbus • b. Baud rate b.9600 b.19200 b.38400 b.76800 Baud rate 9600 Baud rate 19200 Baud rate 38400 Baud rate 76800 • bit. Stop bits bit.1 bit.2 1 stop bits 2 stop bits • P. Parity P.odd P.even P.none Odd parity Even parity Parity none • Id. Modbus Id Id.x Modbus id (x = value) *) • PLA. PLA address for Pascal PLA.x PLA address (x = value) *) • ELA. ELA address for Pascal ELA.x ELA address (x = value) *) • Pi. Pin-code Pi.xxxx Default: xxxx = 1111 • Cnt. Control by bus Cnt.bus Cnt.AIn Control by bus Control by analog in • Store Store changes Strores changes on long press • Cancel Cancel Cancel and ignore changes on long press Under AIn.Set (analog in settings) you can find the following options (toggle with short press, select with long press). Menu tag Description Options Description • qH. Max flow (l/s) qH.x Maximum air flow (x = value) *) • qL. Min flow (l/s) qL.x Minimum air flow (x = value) *) • r. Voltage range r.0-10 r.10-0 r.2-10 r.10-2 Voltage range 0-10V Voltage range 10-0V Voltage range 2-10V Voltage range 10-2V • Store Store changes Stores changes on long press • Cancel Cancel Cancel and ignore changes on long press *) To change the value you need to long press until a blinking cursor appears under the first single number in the current value. After that you short press to toggle to the desired number, then you long press to move the blinking cursor to the next single number in the current value. Proceed until the new value has been set and long press to continue.

l/s m/s °C

% - Actual value m³/h l/s m/s Setpoint - - Controller FTCU Ø125 Serial no. 132600052 UltraLink Lindab® We reserve the right to make changes without prior notice ID-numbers The Controllers have from production been given an ID-number between 1 to 239. The given ID-number can be seen on the label on the outside of the box the Con- troller is delivered in, the ID-number is the same as the three last digits in the serial number. If two or more Modbus devices have the same ID-number it is necessary to apply changes so that each of them get an unique ID-number to allow communication. To change the Modbus ID register of an UltraLink® all other devices with the same ID must be disconnected. It is more efficient to change the ID in the display under “Con.Set” (See page 13 for more info). The register for Modbus ID is a holding register with address 4x001. Error code Problem Comment Err001 Motor not working correctly Check motor cables and connections Err002 Angle sensor not working correctly Try to recalibrate using UltraLink® Configuration tool Err003 Flow set point not reached Check if the AHU supplying enough air Err004 Problems with flow measurement Might be caused by: • something blocking the flow sensors • an electronic fault • the flow sensors are not connected properly into the display unit • the sensor body is flawed Err032 Factory data is corrupted Reset to factory defaults using UltraLink® configuration tool Maintenance Normally does not require any maintenance. The visible parts of the device can be wiped with a damp cloth. If communication fails, please verify the following before contacting support: • Check settings for Baud rate, parity and stop bit and make sure the master uses the same settings as the UltraLinks. • -A and +B are continuously connected between all the products without any mixups of -A and +B. Star connection is not allowed. • The cables for power supply are connected identical on all products and transformers connecting G to G (24V) and G0 to G0 (GND). • The shield is continuous along the bus and grounded only at the transformer and the last UltraLink on the bus. • There are not more than 30 devices on the bus. (Try a repeater if you have more than 30 devices.) • The total length of the bus is maximum 300 m. (Try with a repeater if you have more than 300 m bus cable.) • Try to establish communication with a PC using Control Center and a biased RS485-USB converter. Troubleshooting If a problem occurs the status light will start to flash and an error code will be displayed.

We reserve the right to make changes without prior notice

Technical data Power supply DC 24 (18—32) V AC 24 (24—28) V Cable Max outer diameter 7 mm Power consumption Dim. 100 - 315 2 W Dim. 400 - 630 3 W Power consumption For wiring, dim. 100 - 315 3 VA For wiring, dim. 400 - 630 5 VA IP class 42 Tightness class to the environment EN 12237 D Tightness class, past a closed damper EN 1751 4 Pressure class, closed damper Dim. 100 - 315 C (max 5000 Pa) Dim. 400 - 630 B (max 2500 Pa) Storage temperature range -30 to +50 °C Maximum ambient moisture 95 % RH Connection RS485 standard or analog Cable RS485 standard cable, 2-wire shielded twisted pair, min. 0,1 mm² (LIYCY cable) Protocol Modbus Output Flow Flow Velocity Temperature Damper position (0% fully closed, 100% fully open) m³/h l/s m/s °C % Velocity range For guaranteed measurement uncertainty 0,2 — 15,0 m/s Measurement uncertainty, flow (min. 5 diamters of straight duct before the UltraLink.) Depending on which is the greatest of the percentage or the absolute value for the specific product size. ±5 Dim. 100 = ±1,00 Dim. 125 = ±1,25 Dim. 160 = ±1,60 Dim. 200 = ±2,00 Dim. 250 = ±2,50 Dim. 315 = ±3,15 Dim. 400 = ±4,00 Dim. 500 = ±5,00 Dim. 630 = ±6,30 % or l/s l/s l/s l/s l/s l/s l/s l/s l/s Temperature range -10 to +50 °C Measurement uncertainty, temperature ±1 °C Screws on lid of display unit TX10 4 pcs Bluetooth signal Frequency 2402 — 2480 MHz Output power -40 to +9 dB Airflows Ø [mm] 0,2 m/s 7,0 m/s 15,0 m/s m³/h l/s m³/h l/s m³/h l/s 100 6 2 198 55 425 118 125 9 3 309 86 662 184 160 14 4 507 141 1087 302 200 23 6 792 220 1696 471 250 35 10 1237 344 2650 736 315 56 16 1964 546 4208 1169 400 90 25 3167 880 6786 1885 500 141 39 4948 1374 10603 2945 630 224 62 7855 2182 16833 4676

We reserve the right to make changes without prior notice

Appendix A – Modbus register Address : Modbus register address (3x indicates Input & 4x indicates Holding) UltraLink® : Type of UltraLink® where the register is available (Indicated by “x”) Name: Name of register Description: Short description of register. Data type: Data type for register (16bit contained in one register, 32bit and float in two consecutive registers) . Unit: Unit for register value (if any). Div: Scale factor for stored value (divide register value with “div” to get correct value). Default: Default setting. Min: Minimum value allowed for the register. Max: Maximum value allowed for the register. Access: RO for read only (Input registers) and RW for read and write (Holding registers). Address UltraLink® Name Description Data type Unit Div Default Min Max Access Controller Monitor INPUT REGISTERS 3x008 X X Product Nominal Size Nominal diameter of duct 16bit mm RO 3x013 X X Unit Status Current unit status: 0 = Normal mode; 1 = Locating flow; 2 = Override control; 3 = Error; 4 = Control loop regulating; 5 = Angle sensor calibrating 16bit RO Flow info 3x150 X X Velocity in m/s Velocity in m/s Float m/s RO 3x152 X X Air flow in m³/h Air flow in m³/h Float m³/h RO 3x154 X X Air flow in l/s Air flow in l/s Float l/s RO Temperature info 3x200 X X Current temperature in ºC Temperature in degree celcius. 16bit ºC 10 RO Damper info 3x251 X Damper open in % Damper actual position in percentage open. 16bit % 10 RO 3x252 X Damper motor action Damper motor action: 0 = Motor stopped. 1 = Motor opening damper 2 = Motor closing damper 16bit RO Alarms 3x400 X X Alarm Register 1 Alarms 1-32 - bitwise: 1 = Motor not working. 2 = Angle sensor not working correctly. 3 = Flow setpoint not reached. 4 = Flow measure problems. 5 = Damper is regulating. 6 = Not used. 7 - 31 = Reserved for future use. 32 = Factory data is corrupted. 32bit RO Other 3×500 X X Signal amplification Current signal amplification 16bit 0 3 20 RO

We reserve the right to make changes without prior notice

Address UltraLink® Name Description Data type Unit Div Default Min Max Access Controller Monitor HOLDING REGISTERS Communication settings 4x001 X X Communication id Modbus address 16bit 1 239 RW 4x002 X X RS485 Baud Rate Conf. Baudrate: 0 = 9600 1 = 19200 2 = 38400 3 = 76800 16bit 1 0 3 RW 4x003 X X RS485 Parity Conf. Parity: 0 = Odd; 1 = Even; 2 = None 16bit 0 0 2 RW 4x004 X X RS485 Stop Bit Conf. Number of stopbits: 1 or 2. 16bit 1 1 2 RW 4x005 X X RS485 Protocol Conf. Protocol: 0 = Modbus; 1 = Not used; 2 = Pascal; 16bit 0 0 2 RW 4×006 X X Bluetooth Password Password which must be provided to pair Bluetooth devices. This password can always be changed from wired connection. From wireless it can only be changed when connection is established using current password. 16bit 1111 0000 9999 RW 4×007 X X Bluetooth Enable Enable Bluetooth Communication 0 = Bluetooth turned off; 1 = Bluetooth turned on; 16bit 1 0 2 RW 4x008 X X PLA ID used for Pascal 16bit 1 239 RW 4x009 X X ELA ID used for Pascal 16bit 1 239 RW 4×010 X X Bluetooth TX Power Level Configure TX Power Level dBm. Accep- ted values: -40, -20, -16, -12, -8, -4, 0, 2, 3, 4, 5, 6, 7, 8, 9 16bit 0 -40 9 RW System configuration 4x070 X Damper Regulation Conf. Specifies how damper is regulated: 0 = Regulator turned off 1 = Regulate damper angle 2 = Regulate flow 16bit 2 0 2 RW 4x071 X Damper Input Conf. Specifies input to control damper: 0 = Modbus or Pascal 1 = Analog input 16bit 1 0 1 RW 4x082 X X Execute Factory Reset Factory reset of all parameters. Unit will restart 0 = Do nothing; 1 = Factory Reset 16bit 0 0 1 RW 4x083 X X Execute Reboot Reboot the unit 0 = Do nothing; 1 = Reboot the unit; 16bit 0 0 1 RW Override configuration 4x150 X Damper Override Timeout Time before returning to normal mode 16bit min 120 0 600 RW 4x151 X Damper Override Conf. 0 = Normal mode; 1 = Override control - Max open; 2 = Override control - Min open; 3 = Override control - 100% open; 4 = Override control - 100% closed 16bit 0 0 4 RW Damper 4x300 X Execute Angle Calibration 0 = Do nothing; 1 = Start recalibration of the angle sensor; 2 = Start recalibration when starting up; 16bit 0 0 2 RW 4x302 X Angle Set Point Angle setpoint used in normal mode. (Only relevant when 4x070 is set to 1 ) 16bit % 0 0 100 RW 4x314 X Flow Set Point Flow setpoint used in normal mode. (Only relevant when 4x070 is set to 2 ) 16bit l/s * 0 4700 RW * = the value depends on the dimension of the product.

We reserve the right to make changes without prior notice

* = the value depends on the dimension of the product. Address UltraLink® Name Description Data type Unit Div Default Min Max Access Controller Monitor 4x315 X Flow Set Point Minimum Flow setpoint min. 16bit l/s * 0 4700 RW 4x316 X Flow Set Point Maximum Flow setpoint max. 16bit l/s * 0 4700 RW Analog output 4x400 X X Analog Output 1 Level Conf. Analog output config: 0 = 0-10 V, 1 = 10-0 V, 2 = 2-10 V, 3 = 10-2 V. 16bit 2 0 3 RW 4x401 X X Analog Output 1 Unit Conf. Show: 0 = Flow; 1 = Temperature; 2 = Angle; 16bit 0 0 2 RW 4x402 X X Analog Output 1 Temp. Min. Min temperature shown = Min output voltage (Only relevant when 4x401 is set to 1 ) 16bit ºC 0 -40 50 RW 4x403 X X Analog Output 1 Temp. Max. Max temperature shown = Max output voltage (Only relevant when 4x401 is set to 1 ) 16bit ºC 50 -40 50 RW 4x404 X X Analog Output 1 Flow Min. Min flow shown = Min output voltage (Only relevant when 4x401 is set to 0 ) 16bit l/s 0 -4700 4700 RW 4x406 X X Analog Output 1 Flow Max. Max flow shown = Max output voltage (Only relevant when 4x401 is set to 0 ) 16bit l/s * -4700 4700 RW 4x408 X Analog Output 1 % Open Min. Min open % shown = Min output voltage (Only relevant when 4x401 is set to 2 ) 16bit % 10 0 0 1000 RW 4x409 X Analog Output 1 % Open Max. Max open % shown = Max output volta- ge (Only relevant when 4x401 is set to 2 ) 16bit % 10 1000 0 1000 RW 4x430 X X Analog Output 2 Level Conf. Analog output config: 0 = 0-10 V, 1 = 10-0 V, 2 = 2-10 V, 3 = 10-2 V. 16bit 2 0 3 RW 4x431 X X Analog Output 2 Unit Conf. Show: 0 = Flow 1 = Temperature 2 = Angle 16bit 2 0 2 RW 4x432 X X Analog Output 2 Temp. Min. Min temperature shown = Min output voltage (Only relevat when 4x431 is set to 1 ) 16bit ºC 0 -40 50 RW 4x433 X X Analog Output 2 Temp. Max. Max temperature shown = Max output voltage (Only relevant when 4x431 is set to 1 ) 16bit ºC 50 -40 50 RW 4x434 X X Analog Output 2 Flow Min. Min flow shown = Min output voltage (Only relevant when 4x431 is set to 0 ) 16bit l/s 0 -4700 4700 RW 4x436 X X Analog Output 2 Flow Max. Max flow shown = Max output voltage (Only relevant when 4x431 is set to 0 ) 16bit l/s * -4700 4700 RW 4x438 X Analog Output 2 % Open Min. Min open % shown = Min output voltage Only relevant when 4x431 is set to 2 ) 16bit % 10 0 0 1000 RW 4x439 X Analog Output 2 % Open Max. Max open % shown = Max output volta- ge (Only relevant when 4x431 is set to 2 ) 16bit % 10 1000 0 1000 RW

We reserve the right to make changes without prior notice

Address UltraLink® Name Description Data type Unit Div Default Min Max Access Controller Monitor Analog input (Settings below are only relevant when register 4x071 is set to 1) 4x500 X Analog In Level Conf. Analog input: 0 = 0-10 V, 1 = 10-0 V, 2 = 2-10 V, 3 = 10-2 V. 16bit 2 0 3 RW 4x501 X Analog In Angle Minimum Min angle = min voltage 16bit % 0 0 100 RW 4x502 X Analog In Angle Maximum Max = max voltage 16bit % 100 0 100 RW 4x503 X Analog In Flow Minimum Min flow = min voltage (Must be equal or higher than register 4x315) 16bit l/s 0 0 4700 RW 4x504 X Analog In Flow Maximum Max flow = max voltage (Must be equal or lower than register 4x316) 16bit l/s * 0 4700 RW 4x510 X Analog In Override Low Trigger Min. Lowest voltage level to activate 1st Override level (Only relevant when 4x500 is set to 2 or 3) 16bit V 10 0 0 20 RW 4x511 X Analog In Override Low Trigger Max. Highest voltage level to activate 1st Override level (Only relevant when 4x500 is set to 2 or 3) 16bit V 10 8 0 20 RW * = the value depends on the dimension of the product.

At Lindab, good thinking is a philosophy that gui-

des us in everything we do. We have made it our mission to create a healthy indoor climate – and to simplify the construction of sustainable buil- dings. We do that by designing innovative pro- ducts and solutions that are easy to use, as well as offering efficient availability and logistics. We are also working on ways to reduce our impact on our environment and climate. We do that by de- veloping methods to produce our solutions using a minimum of energy and natural resources, and by reducing negative effects on the environment. We use steel in our products. It’s one of few materi- als that can be recycled an infinite number of times without losing any of its properties. That means less carbon emissions in nature and less energy wasted. We simplify construction 2018-12-06