Notifier NAM-232 Quick Start Manual
Text of the manual
DN-5331 • 08/19/04 — Page 1 of 2
GENERAL
The NAM-232 Network Adapter Module functions as an in-
terface between the AFP-200, AFP-300, and AFP-400 Fire
Alarm Control Panels and the NOTI•FIRE• NET™. The
control panels each consume a single-node address on the
network. The NAM-232 interfaces to the control panels
through the EIA-232 serial communications port.
NOTI•FIRE•NET™ is a series of systems that allow a group
of Fire Alarm Control Panels and other control equipment to
connect together to form a true peer-to-peer network. Equip-
ment that connects to NOTI•FIRE• NET™ and communi-
cates with other equipment using the network may be re-
ferred to as a network node. An NFS-3030/NFS-640 Fire
Alarm System with an NCM Network Control Module installed;
an NCA Network Control Annunciator with an NCM installed;
an AM2020/AFP1010 Fire Alarm System with a SIB-NET Se-
rial Interface Board installed; an NCS Network Control Sta-
tion; an INA Intelligent Network Annunciator; and an AFP-
200/300/400 with a NAM-232 may all be network nodes. The
network supports communications over a twisted-pair wire
or fiber-optic medium. A network combination of both wire
and fiber may exist in the same network.
NOTE: Refer to manual network configuration section for panel
compatibility.
NOTI•FIRE•NET™ is a trademark of NOTIFIER, 1994.
NETWORK FEATURES
AFP-200:
1. The network has the ability to send Acknowledge, Si-
lence, and Reset commands to the AFP-200.
2. Limited cooperative control-by-event (CCBE). Zones 1-
45 are network independent. Zones 46-89 are initialized
as one (1) “OR” equation.
3. The local node can send or receive network zone activa-
tions.
AFP-300/AFP-400:
1. Read/Alter Status; Group Enable/Disable; Individual Point
Enable/Disable.
2. The network has the ability to send Acknowledge, Si-
lence, and Reset commands to the AFP-300/AFP-400.
3. Cooperative control-by-event (CCBE). Zones 1-99 are
network independent.
4. The local node can send or receive network zone activa-
tions.
5. Remote ACS control via the INA EIA-485 port. Two (2)
annunciator addresses for a total of 128 annunciator
points per AFP-300/AFP-400 system.
FEATURES
NAM-232W: Network Adapter Module (Wire)
• Supports twisted-pair wire medium.
• Data is regenerated at each node.
• DIP switch selectable single-port or dual-port monitoring.
Network Adapter Module
Wire (NAM-232W)
S635
7165-0028:164
7165-0028:181
7170-0028:182
Section: Network Systems
• DIP switch selectable network drill option.
• Selectable Earth Fault detection per channel.
• Provides electrical isolation between nodes.
• Transmission rate of 312.5 Kbaud.
• Compatible with NOTI•FIRE•NET™ Release 2.5 (or
higher).
• Diagnostic LED indicators.
MEA
California
State Fire
Marshal
NAM-232
Network Adapter Module
August 18, 2004
DN-5331 • A0-250
5331wire.wmf
104-93-E Vol. VIII
(NAM-232W)
CS118
Made in the U.S.A.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
NOTIFIER® is a Honeywell company.
Page 2 of 2 — DN-5331 • 08/19/04
Network Adapter Module Fiber (NAM-232F)
LED INDICATORS
• RECON: This yellow LED should remain off at all
times when the network is operating properly. If it
illuminates periodically, check the network media and
thresholds using the MET-1 (Media Evaluation Tool).
• STATB: This yellow LED illuminates when the NAM-
232 is not receiving valid data from NOTI•FIRE•
NET™ on Port “B”.
• RCVDB: This green LED illuminates when the NAM-
232 is receiving data from the NOTI•FIRE•NET™ on
Channel “B” (wire or fiber connection).
• B HI (NAM-232W only): This green LED illuminates
to indicate the NAM-232W Channel “B” is set for
high threshold (N/A on NAM-232F).
• A HI (NAM-232W only): This green LED illuminates
to indicate the NAM-232W Channel “A” is set for
high threshold (N/A on NAM-232F).
• RCVDA: This green LED illuminates when the NAM-
232 is receiving data from the NOTI•FIRE•NET™ on
Channel “A” (wire or fiber connection).
• STATA: This yellow LED illuminates when the NAM-
232 is not receiving valid data from NOTI•FIRE•NET™
on Port “A”.
• PULSE: This green LED illuminates when the NAM-
232 is transmitting data to NOTI•FIRE•NET™.
• TROUBLE: This yellow LED indicates that the NAM-
232 is not functioning.
• TXD: This green LED indicates when the NAM-232
is transmitting data over the EIA-232 interface to the
AFP-200, AFP-300, AFP-400 FACP.
• RXD: This green LED indicates when the NAM-232
is receiving data over the EIA-232 interface from the
AFP-200, AFP-300, AFP-400 FACP.
NETWORK CONFIGURATION
EXAMPLE
• NFPA Style 4 & 7 network operation.
FEATURES, continued
NAM-232F: Network Adapter Module (Fiber)
• Supports fiber optic medium.
• Transmission rate of 312.5 Kbaud.
• DIP switch selectable single-port or dual-port monitoring.
• DIP switch selectable network drill option.
• Data is regenerated at each node.
• Data is immune to all environmental noise.
• Diagnostic LED indicators.
• Optical isolation prevents ground loops.
• High level of data security.
• NFPA Style 4 & 7 network operation.
MOUNTING
The NAM-232 normally mounts inside the back of the control
panel cabinet. The NAM-232 can also mount in the cabinet of
other nodes on the network, provided that the distance be-
tween the NAM-232 and its host node is not greater than 50
feet (15.24 m).
GENERAL NOTES:
1) AFP-200, AFP-300, and AFP-400 lose local CRT capability
when connected to the NAM-232.
2) AFP-200 system loses local printer and CRT capability when
connected to the NAM-232.
5331conf.wmf
5331fibr.wmf
*NOTE, NOTI•FIRE•NET™:
NOTI•FIRE•NET™ version 3.0 network will not support the
ONYX™ Series of products (NFS-640, NFS-3030, NCA, NCS-
W/F-ONYX, or NWS). NOTI•FIRE•NET™ version 4.0 network will
not support the INA, NFS-3030, or NWS. NOTI•FIRE•NET™ ver-
sion 5.0 network will not support the INA.
*NOTE, NAM-232 FIRMWARE UPGRADE:
The NAM-232 comes from the factory with firmware for a version
3.0 network. To upgrade the NAM-232 for a version 4.0 network,
order NROM-NAM4.0M. To upgrade the NAM-232 for a version
5.0 network, order NROM-NAM5.0M.