Kubler PSU01 Operating Manual
Read Online
Read the Kubler PSU01 Operating Manual online using the built-in PDF viewer.
Text of the manual
PSU01 (Position Supervisor Unit inkl. Ants LES01)
Deutsch ist die Originalfassung
english
deutsch
R60953.0009 - Index 3
Operating Manual
PSU01 (Position Supervisor Unit incl. Ants LES01)
español
italiano
français
Instructions d'utilisation
PSU01 (Position Supervisor Unit avec Ants LES01)
Manuale d’istruzioni
PSU01 (Position Supervisor Unit incl. Ants LES01)
Instrucciones de utilización
PSU01 (Position Supervisor Unit incl. Ants LES01)
DE - Seite 2 (R60953.0009 3)
Herausgeber
Kübler Group, Fritz Kübler GmbH
Schubertstraße 47
78054 Villingen-Schwenningen
Germany
www.kuebler.com
Applikationssupport
Tel. +49 (0) 7720 3903-849
Fax +49 (0) 7720 21564
[email protected]
Dokumenten-Nr.
R60953.0009 - Index 3
Dokumenten-Name
Bedienungsanleitung
PSU01 (Position Supervisor Unit (PSU) inkl. Ants LES01)
Sprachversion
Deutsch (DE) - Deutsch ist die Originalversion
Ausgabedatum
01/2019 - Index 3
Copyright
©2019, Kübler Group, Fritz Kübler GmbH
Rechtliche Hinweise
Sämtliche Inhalte dieser Gerätebeschreibung unterliegen den Nutzungs- und Urheberrechten der
Kübler Gruppe, Fritz Kübler GmbH. Jegliche Vervielfältigung, Veränderung, Weiterverwendung und
Publikation in anderen elektronischen oder gedruckten Medien, sowie deren Veröffentlichung im Inter-
net, bedarf einer vorherigen schriftlichen Genehmigung durch die Fritz Kübler GmbH.
DE - Seite 3 (R60953.0009 3)
deutsch
Inhaltsverzeichnis
1.
Allgemeine Hinweise
5
1.1 Verwendete Abkürzungen
5
1.2 Verwendete Symbole / Warn- und Sicherheitshinweise
5
1.3 Zielgruppe
6
1.4 Sicherheitsrichtlinien
6
1.5 Montage- und Bedienpersonals
6
1.6 Gewährleistung und Haftung
6
1.7 Bestimmungsgemäße Verwendung
6
1.8 Transport & Lieferung
7
1.9 Lagerung
7
1.10 Mitgeltende Dokumente
7
2.
Produkteigenschaften
8
2.1 Funktion der PSU01
8
2.1.1 Endschalteremulation
9
2.1.2 Inspektionsendschalteremulation
9
2.1.3 Sicherheitsschaltung zur Türüberbrückung
9
2.1.4 Unintended Car Movement (UCM)
9
2.1.5 Verzögerungskontrollschalter
10
2.1.6 Übergeschwindigkeit Vorauslösung
10
2.1.7 Türzonenemulation
11
2.2 Besondere Merkmale
11
2.3 Lieferumfang PSU01
11
2.4 Beispiel eines Typenschilds
11
2.4.1 Auswerteeinheit / Position Supervisor Unit
11
2.4.2 Ants LES01
11
3.
Technische Beschreibung
12
3.1 Position Supervisor Unit (Auswerteeinheit)
12
3.2 Sicherheitskennwerte
13
3.3 Ants LES01 (Sensor)
13
4.
Mechanische Montage
14
4.1 Auswerteeinheit / Position Supervisor Unit
14
4.2 Ants LES01 (Sensor)
14
5.
Elektrische Installation
15
5.1 EMV Hinweise
15
5.2 Allgemeine Hinweise
15
5.2.1 Geltende Sicherheitsnormen
15
5.2.2 CE-Konformität
15
5.3 Elektrische Einbindung in die Aufzugsanlage
16
5.3.1 Anschlussübersicht PSU
17
5.3.2 Anschluss Ants LES01
18
5.4 Anschluss Sicherheitsrelais
18
5.4.1 Stecker X5: Sicherheitskreisausgang
18
5.4.2 Stecker X6: Türzonen-Relaisausgänge
19
5.4.3 Stecker X6: Relais Kontakt – Anschluss Türzonenanzeige
19
DE - Seite 4 (R60953.0009 3)
5.4.4 Stecker X7: Türüberbrückung
19
5.4.5 Stecker X8 (optional): Inspektion
19
6.
Inbetriebnahme nach EN81-20
20
6.1 Voraussetzungen
20
6.2 Übersicht zur Parametrisierung
21
6.3 Parametrisierung des Schutzraumes
22
6.4 Einlernen des oberen Endschalters bei verkürzten Schachtkopf
23
6.5 Parametrisierung der Verzögerungsendschalter
23
7.
Während des Betriebs
24
7.1 Normalbetrieb
24
7.1.1 Funktion der Türüberbrückung
24
7.1.1.1 Türüberbrückung für die Einfahrt zur vorzeitigen Türöffnung
24
7.1.1.2 Türüberbrückung für die Nachholung in einer Haltestelle
25
7.1.1.3 Türüberbrückung für den Schnellstart aus einer Haltestelle
25
7.1.2 Schutzmodus (Inspektion)
25
7.1.3 UCM Erkennung
26
7.1.4 Übergeschwindigkeit
27
7.1.5 Relaistest
27
7.2 Fehlermodus
27
7.3 LED Blinkmuster
28
7.4 Kommunikation
28
7.5 Störungen
28
7.6 Rücksetzen
29
7.6.1 Einen Fehler zurücksetzen
29
7.6.2 Alle Haltestellen rücksetzen
30
7.6.3 Auf Werkseinstellung zurücksetzen
30
8.
Prüfung der Funktionen
31
8.1 Endschalterfunktion
31
8.2 Inspektionsendschalterfunktion
31
8.3 Verzögerungsendschalterfunktion
31
8.4 UCM-Funktion
31
8.5 Türzonenemulation-Funktion
31
8.6 Übergeschwindigkeit (optional)
31
9.
Reparatur, Wartung und Entsorgung
32
9.1 Austausch von Komponenten
32
9.2 Wartung
32
9.3 Rückverfolgbarkeit
32
9.4 Entsorgung
32
9.5 Bestellbezeichnung und Ersatzteile
32
9.6 Service Adresse
33
DE - Seite 5 (R60953.0009 3)
deutsch
1. Allgemeine Hinweise
Bitte lesen Sie diese Bedienungsanleitung sorgfältig, bevor Sie mit der sicheren Auswerteeinheit arbei-
ten, sie montieren oder in Betrieb nehmen. Diese Bedienungsanleitung leitet das technische Perso-
nal des Maschinenherstellers bzw. Maschinenbetreibers zur sicheren Montage, Elektroinstallation,
Inbetriebnahme sowie zum Betrieb der sicheren Auswerteeinheit PSU an. Darüber hinaus sind für die
Planung und den Einsatz von Schutzeinrichtungen wie der sicheren Auswerteeinheit PSU technische
Fachkenntnisse notwendig, die nicht in diesem Dokument vermittelt werden.
Grundsätzlich sind die behördlichen und gesetzlichen Vorschriften beim Betrieb der sicheren Auswer-
teeinheit PSU einzuhalten.
1.1 Verwendete Abkürzungen
PSU01
Gesamtsystem Ants LES01 + Auswerteeinheit PSU
Ants LES01
Linear Encoder Safe, SIL3
PSU
Auswerteeinheit / Position Supervisor Unit, SIL3
UCM
Unintended Car Movement
1.2 Verwendete Symbole / Warn- und Sicherheitshinweise
Besonders wichtige Informationen in der Bedienungsanleitung sind wie folgt gekennzeichnet:
Dieses Symbol in Zusammenhang mit dem Signalwort „Gefahr“ bedeu-
tet eine unmittelbar drohende Gefahr für das Leben und die Gesun-
dheit von Personen.
Die Folgen bei Nichtbeachtung dieser Warnung sind Tod oder schwer-
ste Verletzungen.
Dieses Symbol in Zusammenhang mit dem Signalwort „Warnung“
bedeutet eine möglicherweise drohende Gefahr für das Leben und die
Gesundheit von Personen.
Die Folgen bei Nichtbeachtung dieser Warnung können Tod oder
schwerste Verletzungen sein.
Dieses Symbol in Zusammenhang mit dem Signalwort „Vorsicht“
bedeutet eine möglicherweise drohende Gefahr für das Leben und die
Gesundheit von Personen.
Die Folgen bei Nichtbeachtung dieser Warnung können leichte oder
geringfügige Verletzungen sein.
Tipps und Empfehlungen sowie Informationen für einen effizienten und
störungsfreien Betrieb.
DE - Seite 6 (R60953.0009 3)
1.3 Zielgruppe
Die PSU01 darf nur von befähigten Personen montiert, in Betrieb genommen, geprüft, gewartet und
verwendet werden. Befähigt ist, wer
• über eine geeignete technische Ausbildung verfügt und
• vom Maschinenbetreiber in der Bedienung unterwiesen wurde und
• den gültigen Sicherheitsrichtlinien unterwiesen wurde und
• Zugriff auf diese Bedienungsanleitung hat.
1.4 Sicherheitsrichtlinien
Bitte lesen Sie vor Inbetriebnahme des Gerätes die Bedienungsanleitung sorgfältig durch. Installa-
tionshinweise sind unbedingt zu beachten. Nehmen Sie das Gerät nur dann in Betrieb, wenn Sie die
Bedienungsanleitung gelesen und verstanden haben. Auswahl und Einbau der Geräte sowie ihre
steuerungstechnische Einbindung sind an eine qualifizierte Kenntnis der einschlägigen Gesetze und
normativen Anforderungen durch den Maschinenhersteller geknüpft.
Die Sicherheits- und Warnhinweise sind ein wichtiger Teil der Bedienungsanleitung und zwingend zu
beachen.
1.5 Montage- und Bedienpersonals
Der Betreiber ist dazu verpflichtet geeignete sicherheitsrelevante Maßnahmen zu ergreifen. Zur
Montage und Inbetriebnahme dürfen nur Personen eingesetzt werden die über die grundlegenden
Vorschriften der Unfallverhütung und Arbeitssicherheit Kenntnis und die Sicherheitshinweise in dieser
Anleitung gelesen und verstanden haben.
1.6 Gewährleistung und Haftung
Gewährleistungs- und Haftungsansprüche gehen verloren, wenn die PSU01 nicht bestimmungsgemäß
verwendet wird, etwaige Schäden auf Nichtbeachtung der Bedienungsanleitung zurückzuführen sind
oder das Montage- und Bedienpersonal nicht ordnungsgemäß ausgebildet bzw. geschult ist.
Bei Nichtbeachtung der Hinweise gehen alle Gewährleistungsansprüche und Garantien sowie auch
eventuelle Haftungsansprüche verloren. Es müssen alle für den Aufzug geltenden Vorschriften zur
Unfallverhütung beachtet werden. Um Schäden durch unsachgemäßen Umgang mit Spannungen und
Strömen zu verhindern, müssen alle einschlägigen und auch örtlichen Vorschriften beachtet werden,
insbesondere auch hinsichtlich Schutzmaßnahmen und richtiger Erdung.
1.7 Bestimmungsgemäße Verwendung
Die PSU01 wurde ausschließlich für den hier beschriebenen Verwendungszweck entwickelt:
DE - Seite 7 (R60953.0009 3)
deutsch
Die PSU01 dient zur sicheren Positionsauswertung zur Umsetzung der
Funktionen von Endschalter, Inspektionsendschalter, Verzögerungsen-
dschalter, Unintended Car Movement (UCM) sowie der sicheren Brü-
ckung des Sicherheitskreises bei vorzeitiger Türöffnung/Nachholung
von Aufzugsanlagen gemäß EN81-20. Sie bildet zusammen mit dem
Ants LES01 Sensor eine Systemeinheit.
Jede nicht ordnungsgemäße Verwendung kann gefährliche Situationen
hervorrufen.
Die Auswerteeinheit PSU darf nur in Verbindung mit dem Ants LES01
verwendet werden. Alle Angaben beider Bedienungsanleitungen
müssen strikt eingehalten werden. Die Bedienungsanleitung für den
Ants LES01 liegt diesem Produkt bei. Es wird hier explizit als integraler
Bestandteil darauf verwiesen.
Die Veränderung der Gesamtkonstruktion oder einzelner Bestandteile
für die Änderung des Einsatzbereiches bzw. der Verwendbarkeit der
PSU01 ist untersagt.
Für Schäden bei nicht ordnungsgemäßer Verwendung gehen alle
Ansprüche verloren und es haftet allein der Betreiber.
1.8 Transport & Lieferung
Untersuchen Sie die Lieferung sofort nach Erhalt auf etwaige Transportschäden. Teilen Sie diese so-
fort dem Transportunternehmen mit. Die Inbetriebnahme der Auswerteeinheit ist ggf. auszuschließen.
Wenn Sie die Auswerteeinheit nicht sofort einbauen, lagern sie das Gerät trocken und staubfrei, am
besten in der Transportverpackung, ein.
1.9 Lagerung
Das Gerät ist nach folgenden Bedingungen zu lagern:
• Trocken und staubfrei
• Mechanische Erschütterungen vermeiden
• Nicht im Freien aufbewahren
• Nicht die Temperatur- und Feuchtigkeitsgrenzen überschreiten (siehe technische Daten)
1.10 Mitgeltende Dokumente
Alle technischen Daten werden in den entsprechenden Datenblättern der PSU01 sowie des Ants
LES01 angegeben. Hierin finden Sie die mechanischen und elektrischen Kennwerte der PSU01.
Für die Inbetriebnahme des Ants LES01 ist die separate Bedienungsanleitung des Produktes
(R60200.0009) zu beachten.
Weiter gibt es eine Programmieranleitung, welche notwendig ist, um die PSU01 zu parametrisieren.
Diese ist im Regelfall nur für Steuerungshersteller von Interesse, um ihre Aufzugssteuerung entspre-
chend mit der PSU01 kompatibel zu machen. Diese Anleitung wird laufend aktuell gehalten und
steht auch auf unsere Homepage zum Download bereit. Die Parametrisierung kann auch mit jedem
CANopen Terminal hergestellt werden. Notwendige EDS Files liegen ebenfalls auf unserer Hompage
zum Download bereit.
DE - Seite 8 (R60953.0009 3)
2. Produkteigenschaften
Die Auwerteeinheit PSU ist eine sichere Positionsauswertung zur Umsetzung der Funktionen von
Endschaltern, Inspektionsendschaltern, Verzögerungsendschaltern, Unintended Car Movement (UCM)
sowie zur sicheren Brückung des Sicherheitskreises im Bereich der Türen bei vorzeitiger Türöffnung/
Nachholung von Aufzugsanlagen gemäß EN81-20.
Das Gesamtsystem PSU01 besteht aus zwei Geräten, dem Ants LES01 (Linear Encoder Safe) und
der hier beschriebenen Auswerteeinheit PSU (Position Supervisor Unit). Die PSU01 ist über einen
freien CAN-Bus mit einer externen kompatiblen Steuerung, einem CANopen Terminal oder einem
externen Programmiergerät verbunden, welches zum Parametrisieren der Sicherheitsfunktionen
dient. Die Parametrisierung ist nicht Bestandteil dieser Bedienungsanleitung. Diesbezüglich wird auf
das separate Programmierhandbuch verwiesen bzw. auf das jeweilige Handbuch der kompatiblen
Steuerung.
Die PSU01 empfängt von einem dieser Geräte über den freien CAN-Bus (Port X3) entsprechende
Parameter oder Reset-Kommandos und gibt an diese externen Geräte wie Aufzugssteuerungen
Informationen über Position, Zustand, etc. aus. Die reine Positionsausgabe wird auch optional über
SSI unterstützt.
Die Auswerteeinheit PSU und der Ants LES01 sind als Gesamtsystem zertifiziert und dürfen nur
zusammen betrieben werden. Werksseitig sind diese durch eine Set.ID gekennzeichnet. Ants LES01
liefert sicher die absoluten Positionen der Aufzugsanlage über einen zweiten privaten CAN-Bus und
übermittelt diese an die Auswerteeinheit PSU (Port X2). Ants LES01 ist zudem auch als eigenständi-
ges Produkt zertifiziert und verfügbar.
Der Ants LES01 als Bestandteil der PSU01 muss ordnungsgemäß
nach dessen Bedienungsanleitung in Betrieb genommen werden.
2.1 Funktion der PSU01
Die PSU01 erfüllt folgende Anforderungen an die moderne Aufzugsanlage:
• Endschalteremulation
• Inspektionsendschalteremulation bei verkürzten Schachtkopf/-grube
• Sicherheitsschaltung zur Überbrückung der Türkontakte
• Unintended Car Movement (UCM)
• Verzögerungsendschalteremulation
• Übergeschwindigkeit Vorauslösung
• Türzonenemulation zur Informationsweitergabe an eine optionale externe UCM-Einheit
Die Position Supervisor Unit erfüllt die Anforderungen der EN81 durch
• Das einmalige erlernen aller Haltestellen (wird bei der Inbetriebnahme durchgeführt)
• Sicherheitsrelais zum Öffnen des Sicherheitskreises
• Sicherheitsrelais zur Türüberbrückung
• Abfrage des Inspektionseingangs
DE - Seite 9 (R60953.0009 3)
deutsch
2.1.1 Endschalteremulation
Die Notendschalter werden gemäß EN81-20 Sicherheitsfunktion 5.12.2 simuliert. Neue Stationen
müssen zumindest 2 mm von den eingelernten Endschalterpositionen entfernt sein.
2.1.2 Inspektionsendschalteremulation
Die PSU01 ermöglicht die Überwachung des Schutzraums bei verkürztem Schachtkopf/-grube nach
EN81-21, 5.5.3.4 bzw. 5.7.3.4 (Inspektionsendschalter).
Diese Funktion wird durch einen zusätzlichen virtuellen Endschalter dargestellt, welcher fix im Abstand
von 1,2 m vom Endschalter positioniert ist. Es existiert je einer für verkürzte Puffer oben sowie für
verkürzte Puffer unten. Diese neuen Endschalter werden “Inspektionsendschalter” genannt.
Inspektionsendschalter sind in ihrer Position mit 1,2 m vom Endschal-
ter fixiert und können nicht verschoben werden.
Inspektionsendschalter sind optional und können bei der Erstkonfigura-
tion deaktiviert werden.
Bei aktivierten unterem Inspektionsendschalter kann es vorkommen,
dass die Kabine bei Betrieb vom Dach aus im Inspektionsendschalter-
bereich zum Stehen kommt, obwohl die unterste Haltestelle noch nicht
erreicht ist (1,2 m vom Endschalter).
2.1.3 Sicherheitsschaltung zur Türüberbrückung
Die PSU01 stellt eine Sicherheitsschaltung zur Überbrückung der Türkontakte nach EN81-20: 5.12.1.4
bereit.
PSU01 überbrückt auf Anforderung die Türkontakte einer bestimmten Haltestelle
• zur vorzeitigen Türöffnung
• zur Nachholung der Aufzugskabine sowie
• zum Schnellstart.
Eine externe Sicherheitsschaltung zur Brückung von Türen ist explizit
verboten.
2.1.4 Unintended Car Movement (UCM)
Die PSU01 stellt Schutz gegen unbeabsichtigte Bewegung des Fahrkorbs gemäß EN81-20 Si-
cherheitsfunktion 5.6.7. zur Verfügung. Hierbei wird als UCM-Zone die eingestellte Türzone (vgl. 2.1.2)
herangezogen. Dies bezieht sich lediglich auf die Länge der Zone, die UCM-Zonen sind immer aktiv
und könnten nicht selektiv geschalten werden.
Der Einsatz einer optionalen externen UCM-Einheit ist durch die Türzonenemulation (Port X6)
möglich.
DE - Seite 10 (R60953.0009 3)
Da die UCM-Erkennung in der PSU01 permanent aktiv ist, löst im
UCM-Fall auch die PSU01 aus und nicht nur die externe Einheit. Es
müssen entsprechend beide Geräte zurückgesetzt werden.
Die Ansteuerung für das Bremselement der Schutzeinrichtung ist
in der PSU01 vorhanden, wobei das Bremselement der Schutzein-
richtung selbst aber nicht Teil dieser Sicherheitsschaltung bzw. dieser
Beschreibung ist, sondern bauseits an der Aufzugsanlage vorhanden
sein muss. Die Entsprechenden Regelungen für dieses Element sind
einzuhalten.
Als Bremselemente der Schutzeinrichtung müssen Einrichtungen
verwendet werden, welche nach den Vorschriften der EN81-20, 5.6.7
geprüft worden sind und im Stande sind, den Aufzug innerhalb der
vorgeschriebenen Wegstrecke und Verzögerung zum Stillstand zu
bringen.
Eine Nachholung mit einer Geschwindigkeit von über 0,3 m/s erkennt
PSU01 immer als UCM Fall, unabhängig der UCM Zone.
2.1.5 Verzögerungskontrollschalter
Die PSU01 stellt die Funktion der Verzögerungskontrollschaltung bei verkürzten Puffern nach EN81-
20: 5.12.1.3 bereit.
Diese Funktion wird durch einen zusätzlichen geschwindigkeitsabhängigen virtuellen Endschalter dar-
gestellt, welcher (mittels CANopen) einmalig frei positionierbar ist. Diese neuen Endschalter werden
im Folgendem „Verzögerungsendschalter” genannt.
Es existiert je ein Verzögerungsendschalter für verkürzte Puffer oben sowie für verkürzte Puffer unten.
Die Auslösegeschwindigkeit ist mit 1 m/s festgelegt und kann nicht
geändert werden.
Die Position des Verzögerungsendschalters muss bei Bedarf verscho-
ben werden.
2.1.6
Übergeschwindigkeit Vorauslösung
PSU01 stellt die Funktion der Übergeschwindigkeit Vorauslösung (EN81-20: 5.6.2.2.1) bzw. Überge-
schwindigkeit Aufwärtsfahrt (EN81-20: 5.6.6) bereit und öffnet dann den Sicherheitskreis.
Diese Funktion ist nicht Bestandteil der SIL3-Zertifizierung und ersetzt
nicht die in der EN81 vorgeschriebenen Maßnahmen.
DE - Seite 11 (R60953.0009 3)
deutsch
2.1.7 Türzonenemulation
Die PSU01 stellt über zwei redundante Kanäle die Türzone bereit. Sie simuliert somit Türmagneten,
welche in der Montage entfallen können.
Standardmäßig werden alle Türzonen von der PSU01 simuliert sobald der Aufzug langsamer als
0,8 m/s fährt.
Die Türzone ist im Standard von der Schwelle ± 20 mm voreingestellt. Sie kann zwischen ± 5-200 mm
verändert werden. Genauere Informationen zu den Parametern entnehmen Sie bitte dem Program-
mierhandbuch.
Es sind maximal 200 Schwellen möglich. Schwellen müssen mindestens einen Abstand von 20 mm
zueinander haben. Überlappen sich benachbarte Türzonen, so werden diese verkürzt, sodass sich
zumindest ein zonenfreier Bereich von 10 mm ergibt bzw. werden diese zu einer gemeinsamen Zone
zusammengefasst.
Die redundanten Türzonen-Relais (Port X6) sind ausschließlich für eine
optionale externe UCM-Einheit ausgelegt und dürfen für keine andere
Sicherheitsfunktion des Aufzuges verwendet werden.
2.2 Besondere Merkmale
• Es sind keine mechanischen Endschalter mehr notwendig
• Es sind keine zusätzlichen Magnete zur vorzeitigen Türöffnung notwendig
• Einfacher Einbau durch Hutschienenmontage im Dachsteuer- oder Steuerkasten
2.3 Lieferumfang PSU01
• Auswerteeinheit / Position Supervisor Unit im Hutschienengehäuse.
• Ants LES01 (separate Bedienungsanleitung für Ants LES01 ist im Lieferumfang enthalten).
2.4 Beispiel eines Typenschilds
Auf der Auswerteeinheit ist ein Etikett angebracht. Es enthält folgende Informationen:
• Bestellbezeichnung
• SetID (Sensor + Auswerteeinheit)
• Typenbezeichnung / Seriennummer
• Zertifi katsnummer TÜV
• Spannungsversorgung
• CE-Kennzeichen
• Hinweis auf Bedienungsanleitung (Adresse)
2.4.1 Auswerteeinheit / Position Supervisor Unit
2
<
24 VDC PELV XXA
Fritz Kübler GmbH
Type: PSU01
SetID: 00070-11/2018 S-No: XX3333XX
8.PSU01.xxxx.xxxx
TÜV-A-AT-X-XX-XXXX-EUES
www.kuebler.com
0408
Schubertstraße 47
D-78054 Villingen-Schwenningen
2.4.2 Ants LES01
2
WH
BN
GN
YL
GND
+ 24
VDC
CAN
High
CAN
Low
Schubertstraße 47
D-78054 Villingen-Schwenningen
10-30 VDC
XXA ±10%
Fritz Kübler GmbH
Type: PSU01 (Ants LES01)
SetID: 00070-11/2018 S-No: XX1234XX
8.PSU01.xxxx.xxxx
TÜV-A-AT-X-XX-XXXX-XXXX
www.kuebler.com
0408
DE - Seite 12 (R60953.0009 3)
3. Technische Beschreibung
Im Folgenden werden technischen Daten zur PSU01 (Auswerteeinheit + Sensor) beschrieben.
3.1 Position Supervisor Unit (Auswerteeinheit)
Eigenschaft
Wert
Normbezüge
EN81-20, EN81-50, EN81-21
Gehäusematerial
Kunststoff
Gehäuseabmessung
70 mm (H) x 95 mm (L) x 30 mm (B)
Schnittstellen
2 x CAN (intern und öffentlich) , 1 x SSI (optional)
Protokoll
Intern: proprietär, öffentlich: CANopen, SSI: 2 x 25 Bit mit
PFB, Gray-Code, MSB-first
Anschlussart
picoMAX® eCOM 3.5, 7.5 (Anschluss und Kapitel 5)
Betriebsumgebungstemperatur
von -5°C bis +55°C
Lagertemperatur
von -10°C bis +70°C
Luftfeuchtigkeit
< 90% (nicht kondensierend)
Luftdruck
800 - 1013 hPa (bis 2000 m über NN)
Gebrauchsdauer
20 Jahre
Schutzart
IP00 (min. IP20 im Schaltschrank verbaut)
Versorgungsspannung
24 VDC Niederspannung PELV
Leistung
< 10 Watt
Maximale Distanz zum Sensor
100 m (interner CAN-Bus)
Abschaltzeit / Systemreaktionszeit
< 25 ms (inkl. Relais-Schaltzeit)
Maximale Anzahl der Stockwerke
200
Alle Leitungen und Hängekabel müssen gemäß EN81-20 5.10.6
doppelt isoliert oder mechanisch geschützt hergestellt werden. Auf
kurzschlussfreie Verlegung ist besonders zu achten.
DE - Seite 13 (R60953.0009 3)
deutsch
Die Anschlüsse der Auswerteeinheit haben folgende Eigenschaften:
Klemme
Funktionsbereich
Kabel
X1
Spannungsversorgung
24 VDC
0,75 mm2
X2
CAN1 - interner BUS zum
Sensor
Direkter Anschluss des Limes
Elevator Safe
Anschluss direkt ohne Verlänge-
rung oder 0,75 mm2 (max. 100 m)
über Hängekabel, TwistedPair mit
Schild
X3
CAN2 - CANopen
Direkter Anschluss Program-
miereinheit oder an kompatible
Steuerung. CAN-Bus konform.
Anschluss direkt oder 0,75 mm2
(max. 100 m) über Hängekabel,
TwistedPair mit Schild
X4
SSI (optional)
SSI konform
0,75 mm2 (max. 100 m) über Hän-
gekabel, TwistedPair mit Schild
X5
Sicherheitskreis Einbindung
48 ... 230 VAC max. 2 A,
24 VDC max. 1 A
0,75 mm2
X6
Türzonenemulation
24 VAC, 24 VDC, max. 10 mA
0,75 mm2
X7
Türüberbrückung
Auslösekreis
48 ... 230 VAC max. 2 A,
24 VDC max. 1 A
0,75 mm2
X8
Inspektion Abfrage
(optional)
48 ... 230 VAC, 24 VDC,
max. 2 A
0,75 mm2, maximal 170 m (bei
Überschreiten von 170 m ist
auf eine kapazitive Einkopplung
gesondert Bedacht zu nehmen
(siehe 5.2.2))
3.2 Sicherheitskennwerte
Sicherheitskennwerte
Normengrundlage
EN81-20, EN81-50, EN81-21, EN62061, EN61508-1-7,
EN60664-1, EN60950-1, EN61784-3
Klassifizierung
SIL3, kontinuierliche Anforderung
Systemstruktur
2-kanalig
PFHd-Wert
< 1 x 10-7
3.3 Ants LES01 (Sensor)
Technische Beschreibung siehe beigelegte Bedienungsanleitung R60200.0009.
DE - Seite 14 (R60953.0009 3)
4. Mechanische Montage
4.1 Auswerteeinheit / Position Supervisor Unit
Die Auswerteeinheit wird in einem Kunststoffgehäuse geliefert, welches zur Montage an der Hutschie-
ne geeignet ist. Die Auswerteeinheit muss nach EN81-20 in einem Schaltschrank (IP20) verbaut
werden.
Sie haben folgende Möglichkeiten die Auswerteeinheit zu montieren:
1. Montage der Auswerteeinheit am Kabinendach.
Der Sensor wird direkt an die Auswerteeinheit angeschlossen.
2. Montage der Auswerteeinheit im Steuerungskasten.
Der Sensor wird über das Hängekabel zur Auswerteeinheit geführt. Die maximale Länge der Bus-
Leitung von 100 m muss eingehalten werden.
In beiden Fällen wird eine Hutschiene vorausgesetzt. Die Auswerteeinheit PSU kann durch sein
Gehäuse einfach auf die Hutschiene aufgesetzt werden.
4.2 Ants LES01 (Sensor)
Details zur Montage von
• Band
• Montage-Kit
• Sensor
in der Applikation finden Sie in der Bedienungsanleitung R60200.0009 (ab Kapitel 3.2).
Die Sicherheits- und Warnhinweise müssen beachtet werden.
DE - Seite 15 (R60953.0009 3)
deutsch
5. Elektrische Installation
Bitte trennen Sie vor Stecken/Lösen der Signalleitung immer die Versorgungsspannung.
Zum Anschluss des Ants LES01 muss die entsprechende Bedienunganleitung beachtet werden. Alle
Leitungen und Hängekabel müssen gemäß EN81-20 5.10.6 doppelt isoliert oder mechanisch ge-
schützt hergestellt werden.
Das Bedien- bzw. Montagepersonal muss dafür sorgen, dass das
Gerät beim Einbau/Austausch nicht durch eine elektrostatische
Ladung/Entladung beschädigt wird. Ein direktes Berühren der Platine/
elektronische Bauteile sollte grundsätzlich verhindert werden, oder
geeignete Schutzmaßnahmen getroffen werden.
5.1 EMV Hinweise
• Verwenden Sie bei Busleitungen nur geschirmte und paarig verseilte Leitungen für die
Auswerteeinheit.
• Um Masseschleifen zu vermeiden, ist der Schirm nur an einem Punkt (PSU01 bereits durch PELV
geerdet) mit dem Potential (Schutzerde) verbunden.
• Achten Sie auf eine einwandfreie Befestigung der Leitungsschirme.
• Achten Sie bei der Verdrahtung Ihrer Anlage auf eine ordnungsgemäße Leitungsführung.
Trennen Sie die Verkabelung in Leitungsgruppen wie Motor-/Stromver-
sorgungsleitungen und Signal-/Daten-/Sicherheitskreisleitungen.
• Führen Sie Signal- und Datenleitungen möglichst eng an Masseflächen (Tragholmen,
Metallschienen, Schrankblechen) und nicht parallel zu Motor und Stromversorgungsleitung.
• Verbinden Sie alle Betriebsmittel impedanzarm mit dem Erdungs-/Schutzleitersystem.
5.2 Allgemeine Hinweise
5.2.1 Geltende Sicherheitsnormen
• Vor Inbetriebnahme sind alle benötigten Kabeladern laut Datenblatt anzuschließen!
Ants LES01 ist bereits Vorkonfektioniert und muss nur am Port X2 angesteckt werden. Isolieren
Sie alle nicht benötigten Enden der Ausgangssignale sauber, um Kurzschlüsse zu vermeiden.
• Die richtige Betriebsspannung und den maximal zulässigen Ausgangsstrom berücksichtigen
(siehe Datenblatt).
• Verwenden Sie eine Versorgungsspannungsquelle gemäß PELV.
5.2.2 CE-Konformität
Um CE-Konformität zu erreichen, ist eine EMV-gerechte Installation Voraussetzung:
• Als Steuerleitungen sind durchgehend geschirmte Kabel zu verwenden.
• Die Bus-Leitungen (Port X2, X3, X4) sind getrennt von Leitungen mit hohem Störpegel zu verlegen.
• Der Sicherheitskreis ist Normgerecht möglichst frei von kapazitiven Einkopplungen getrennt von
Leitungen mit hohem Störpegel zu verlegen.
DE - Seite 16 (R60953.0009 3)
• Sollten zu hohe kapazitive Einkoppelungen im Inspektionskreis vorhanden sein (siehe
Wartungsanweisung), so sind diese bauseitig durch Leistungswiderstände oder Kondensatoren
fachmännisch zu eliminieren.
• An der Spannungsversorgung der Elektronik (Auswerteeinheit PSU, Ants LES01, Steuerung) sollten
keine Verbraucher mit hohem Störpegel, wie z.B. Frequenzumrichter, Magnetventile, Schütze etc.
angeschlossen werden. Andernfalls ist für eine geeignete Spannungsfilterung zu sorgen.
5.3 Elektrische Einbindung in die Aufzugsanlage
Dieses Kapitel beschreibt die PSU01 im Gesamtsystem und erläutert die elektrische Einbindung in die
Aufzugsanlage.
Folgende Abbildung zeigt die richtige Einbindung der Auswerteeinheit PSU mit Ants LES01 in die
Aufzugsanlage.
Ansteuerung
Fahrschütze-/befehle
Fahrschütze
Schachttürkontakte
Kabinentürkontakt
AUFZUGSTEUERUNG
PELV
Versorgung
24VDC
Notstrom
12VDC
Sicherheitskreis
Rückleiter
Information
Türzone
(notstromgepuffert)
Türzonen-
überbrückung
Sicherheitskreis
Türzone
(redundant)
Türzone
Eingang Versorgung
Sicherheitskreis
Auswerteeinheit /
Position Supervisor Unit
Absolute Postition
Notendschalterbereich
CAN1
CAN2
SSI
Position/SSI (optional)
Positionswerte CAN-OPEN
Verriegelungskontakte
Ants LES01 (Sensor)
CE0408TÜV-A-AT XXX
Übersichtsschaltplan PSU01
Ants LES01 wird über ein CAN Interface mit der Auswerteeinheit /
Position Supervisor Unit von Kübler verbunden.
CE0408TÜV-A-AT XXX
1
GND
X1
2
24V
3
12V
24VDC
AC
AC
12VDC
22
ZONE2
X6
23
ZONE3
24
COM2/3
20
ZONE1
21
COM1
19
SC2
X5
18
SC1
28
X8
29
26
X7
27
4
24V
X2
5
GND
6
CAN1L
7
CAN1H
8
GND
9
24V
X3
10
CAN2L
11
CAN2H
12
GND
13
DATA1
X4
14
DATA2
15
CLK1
16
CLK2
17
GND
F2A
F2A
Inspektion
DE - Seite 17 (R60953.0009 3)
deutsch
5.3.1 Anschlussübersicht PSU
Die Auswerteeinheit PSU hat 8 Stecker, die nachfolgend übersichtlich und im Detail in den darauffol-
genden Kapiteln dargestellt werden.
Anschluss
Klemme
Nr.
Beschreibung
Versorgung
X1
1
2
3
GND
+24 VDC (Niederspannung nach PELV)
+12 VDC Batterieversorgung für Türzonenan-
zeige im Notbetrieb
CAN1 - intern
Ants LES01
X2
4
5
6
7
8
+24 VDC
GND
CAN1 LOW
CAN1 HIGH
GND
CAN2 - extern
CANopen
X3
9
10
11
12
+24 VDC
CAN2 LOW
CAN2 HIGH
GND
SSI Kommunikation
(optional)
X4
13
14
15
16
17
DATA1
DATA2
CLK1
CLK2
GND
Sicherheitskreis Ausgang
X5
18
19
SC1
SC2
DE - Seite 18 (R60953.0009 3)
Türzonenemulation
X6
20
21
22
23
24
ZONE1 (für Notstrombetieb)
COM1 (für Notstrombetieb)
ZONE2 Türzonenmagnet 1
ZONE3 Türzonenmagnet 2
COM2/3 gemeinsames Potential
Einbindung
Türüberbrückung
X7
26
27
Sicherheitskreiseingang
Sicherheitskreiseingang
Inspektion
X8
(optional)
28
29
Inspektionseingang 24VDC
Inspektionsausgang GND
5.3.2 Anschluss Ants LES01
Der Sensor hat 4 Ein-/Ausgänge, welche bereits bei der Fertigung richtig auf einen picoMAX® eCOM -
Stecker verdrahtet werden, für den direkten Einsatz an der Auswerteeinheit PSU.
Bei einem Anschluss über ein Hängekabel ist die Verdrahtung wie folgt durchzuführen:
Anschluss PSU01
Nr.
Beschreibung
Farbe des Drahtes vom Sensor
X2
4
+24 VDC
braun
5
GND
weiß
6
CAN1 LOW
gelb
7
CAN1 HIGH
grün
8
SLD
Schirm
Der maximale Abstand zur Auswerteeinheit darf 100 m nicht überschreiten. Diese 100 m sind als
Busleitung TwistedPair, geschirmt mit 0,5 mm2 auszuführen und können auch im Hängekabel mit-
geführt werden.
Im Allgemeinen ist bei der Installation von Bussen immer darauf zu achten, dass der Monteur nicht
elektrostatisch geladen ist um Beschädigungen am Gerät bei der Montage zu vermeiden.
5.4 Anschluss Sicherheitsrelais
Im Folgenden werden elektrische Maßnahmen zur Einbindung des Sicherheitskreise dargestellt.
5.4.1 Stecker X5: Sicherheitskreisausgang
Diese Klemmen 18 und 19 sind im Betrieb immer geschlossen und öffnet im Endschalter-, Verzöge-
rungsendschalter-, Inspektionsendschalterbereich, im Fehlermodus (Band oder PSU01 defekt) und im
UCM Fall.
Der Sicherheitskreis muss im AC Betrieb durch eine 2 A Sicherung
steuerungsseitig abzusichern. Im DC Betrieb durch eine 1 A Sicherung.
DE - Seite 19 (R60953.0009 3)
deutsch
5.4.2 Stecker X6: Türzonen-Relaisausgänge
Diese Klemmen 22, 23, 24 dienen als Eingänge für eine externe UCM Auswerteeinheit. Sie können
zur Auswertung der UCM Zone herangezogen werden, da sie wie klassische Magnetschalter zu sehen
sind und diese ersetzen.
Diese Kontakte sind redundant aber nicht selbstprüfend ausgelegt
und dürfen nur als Schachtinformation für eine Sicherheitsschal-
tung nach EN81-20 5.6.7 verwendet werden. Die entsprechende
Sicherheitsschaltung muss ein Fehlverhalten der Kontakte erkennen
können. Ein Redundanzverlust der Ausgangskontakte ist durch geei-
gnete Maßnahmen zu verhindern/erkennen.
Diese Klemmen 22 und 23 schließen mit dem gemeinsamen Potential auf Klemme 24, wenn sich die
Kabine in einer Türzone befindet.
5.4.3 Stecker X6: Relais Kontakt – Anschluss Türzonenanzeige
Die Notstromversorgung über eine 12 V Batterie ist optional und dient nur der Türzonenanzeige. Falls
die Spannung unter 20 V abfällt, geht die PSU01 in einen Fehlerzustand, öffnet alle Relais und es wird
nur noch noch die Türzone +/- 70 mm über die Klemmen 20 und 21 emuliert, um eine Notbefreiung zu
vereinfachen. Dieser Kontakt schließt wenn sich die Kabine in einer Türzone befindet.
5.4.4 Stecker X7: Türüberbrückung
Die Klemmen 26 und 27 dienen zur Überbrückung der Türkontakte und sind je nach Anforderung der
Steuerung geöffnet oder geschlossen.
Eine externe Sicherheitsschaltung zur Brückung von Türen ist explizit
verboten.
5.4.5 Stecker X8 (optional): Inspektion
Die Inspektion wird so verdrahtet, dass im Normalbetrieb 24 VDC am Inspektionseingang (Port X8)
liegen und im Inspektionsbetrieb diese 24 VDC abfallen. Somit erkennt die PSU01 ob sich der Aufzug
in Inspektion befindet oder nicht.
Um kapazitiven Einkoppelungen vorzubeugen müssen unbedingt die allgemeinen Richtlinien dieses
Kapitels sowie die Erfordernisse der Wartung (siehe weiter unten) berücksichtigt werden.
DE - Seite 20 (R60953.0009 3)
6. Inbetriebnahme nach EN81-20
Im Folgenden werden die Vorrausetzungen zur Inbetriebnahme der PSU01 für die Ausführung si-
cherheitsrelevanter Funktionen nach EN81/20 bzw. 50 beschrieben.
6.1 Voraussetzungen
Zur Erfüllung der Sicherheitsfunktionen muss die Auswerteeinheit PSU an das Positionssystem Ants
LES01 angeschlossen sein, welche den Anforderungen Nach EN81-20 entspricht.
Die Auswerteeinheit PSU darf nur in Verbindung mit dem sicheren
Positionslesesystem Ants LES01 verwendet werden.
Für weitere Fragen kontaktieren Sie bitte den Hersteller.
Vor Inbetriebnahme müssen die folgenden Maßnahmen durchgeführt worden sein.
Maßnahme
Beschreibung
Die Hardware ist spezifikationsgemäß
zu betreiben
Die Einsatzbedingungen werden in der Betriebsanleitung
festgehalten und sind jedenfalls einzuhalten.
Verbauen der Auswerteeinheit PSU
im geerdeten oder schutzisolierten
Gehäuses
Die Auswerteeinheit PSU muss im Schaltschrank oder
Dachsteuerkasten fest verbaut werden.
Korrekte Montage und Inbetriebnahme
des Ants LES01
Siehe dazu die Betriebsanleitung des Sensors,
R60200.0009
Richtige Einbindung der Türzonen
Die Einbindung der Türzonen muss wie in Kapitel 5.3
beschrieben eingebunden werden. Diese können zur
Erkennung der UCM Zone für die Einbindung einer
zusätzlichen externen UCM Auswerteinheit herangezogen
werden (siehe Punkt 2.1.7 Türzonenrelais).
Richtige Einbindung des
Sicherheitskreises
Der Sicherheitskreis muss an der Stelle der Endschalter
durch die Rückholung brückbar korrekt eingebunden
werden.
Im aktiven UCM Fall und im Inspektionsmodus im Bereich
der Inspektionsendschalter ist eine Rückholung der
Steuerung verboten.
Richtig Einbindung der
Türüberbrückung
Der Sicherheitskreis muss an der Stelle der Türkontakte
korrekt eingebunden werden (siehe 5.3).
Richtig eingebundenen Relais zur
Auslösung des UCM Aktivators
Die UCM Auslöseeinrichtung muss entsprechend den
Angaben des Aktuators korrekt eingebunden werden.
Erstmalige Wartung
Alle Schritte der wiederkehrenden Wartung müssen bei
Erstinbetriebnahme durchgeführt werden.
DE - Seite 21 (R60953.0009 3)
deutsch
6.2 Übersicht zur Parametrisierung
Nach dem Einbau muss die PSU01 erstmalig parametrisiert werden. Dies geschieht mit einem CANo-
penTerminal bzw. mit einer kompatiblen Steuerung.
Im Folgenden wird die Vorgehensweise vereinfacht skizziert.
Im Folgenden wird die Vorgehensweise vereinfacht skizziert.
DE - Seite 22 (R60953.0009 3)
Die folgende Tabelle zeigt die verschiedenen Zustände bezogen auf Sicherheitskreis und Si-
cherheitsschaltung zur Türüberbrückung.
Schritt
Beschreibung
Sicherheitskreis
Türüberbrückung
UCM
1
Erstinbetriebnahme
Offen
Nicht möglich
inaktiv
2
Endschalter oben anfahren
Offen
Nicht möglich
inaktiv
3
Endschalter unten anfahren
Offen
Nicht möglich
inaktiv
4
Verzögerungsendschalter
einstellen
Geschlossen
Nicht möglich
inaktiv
4
Jede Haltestelle einlernen
Geschlossen
Nicht möglich
inaktiv
5
Haltestellen bestätigen (durch
nochmaliges Anfahren der
Haltestellen)
Geschlossen
Nicht möglich
inaktiv
6
Normalbetrieb
Geschlossen
möglich
Aktiv
Sobald alle Haltestellen bestätigt wurden, geht die PSU01 in den Modus Normalbetrieb. Genauere In-
formationen zu den Parametern entnehmen Sie bitte dem Programmierhandbuch oder dem Handbuch
einer kompatiblen Steuerung bzw. der separat erhältlichen Programmiereinheit.
6.3 Parametrisierung des Schutzraumes
Im Auslieferzustand ist der Schutzraum (verkürzter Schachtkopf/-grube) immer aktiv. Das bedeutet,
dass Inspektionsendschalter zu Beginn beide (oben und unten) aktiviert (auch die Verkabelung gefor-
dert ist) sind.
Die Inspektionsendschalter können im Konfigurationsmodus selektiv ein-/ausgeschalten werden
(siehe Parametrisierhandbuch).
Im Folgenden werden die möglichen Optionen genauer beschrieben:
Option
Beschreibung
Schutzraum
Auf 0,6 m/s
begrenzt
Überbrückung in
Inspektion
0
Keine Inspektionsendschalter,
Inspektion nicht verkabelt
Kein
Nein
Möglich*
1
Inspektionsendschalter
oben und unten, Inspektion
verkabelt
Oben und unten
Ja
Nicht möglich
2
Inspektionsendschalter nur
oben, Inspektion verkabelt
Nur oben
Ja
Nicht möglich
3
Inspektionsendschalter nur
unten, Inspektion verkabelt
Nur unten
Ja
Nicht möglich
4
Keine Inspektionsendschalter,
Inspektion jedoch verkabelt
Kein
Ja
Nicht möglich
*Möglich, da PSU01 keine Informationen zum Inspektionsmodus erhält.
DE - Seite 23 (R60953.0009 3)
deutsch
Inspektionsendschalter sind in ihrer Position mit 1,2 m vom Endschal-
ter oben für den oberen Inspektionsendschalter und auch 1,2 m vom
Endschalter unten für den unteren Endschalter fixiert.
Die Positionen der Inspektionsendschalter können nicht verschoben
werden.
Sobald die Inspektion verkabelt ist, wird während der Inspektion die
Geschwindigkeit auf 0,6 m/s begrenzt. Sollte diese Geschwindigkeit
überschritten werden, so wird die Funktion “Übergeschwindigkeit”
ausgelöst und der Sicherheitskreis bis zum Stillstand des Aufzuges
geöffnet.
6.4 Einlernen des oberen Endschalters bei verkürzten Schachtkopf
Bei verkürzten Schachtköpfen, wo es nicht möglich ist, die obere Endschalterposition auf der Kabine
anzufahren, muss man folgendermaßen vorgehen:
Die Aufzugskabine wird exakt 1.500 mm unterhalb der gewünschten Endschalterposition positioniert.
Mit einem speziellen Befehl (siehe Parametrisierhandbuch) speichert die PSU01 die Position vorläufig
als Endschalter temporär. Befindet sich der Monteur z.B. auf Position 10.000 mm, so wird der obere
Endschalter auf 11.500 mm angenommen. Dieser ist noch nicht aktiv, der Zustand wechselt auch
nicht.
Kommt nun der Aufzug innerhalb von 15 Minuten auf dieser errechneten Position (oder oberhalb) zum
Stillstand, so wird diese errechnete Position (nicht die momentane) als oberer Endschalter akzeptiert
und das System wechselt automatisch in den nächsten Zustand (siehe Parametrisierhandbuch).
6.5 Parametrisierung der Verzögerungsendschalter
Zu Beginn sind beide Verzögerungsendschalter bis zum Erlernen der Endschalterpositionen inaktiv.
Sobald die Endschalter erlernt wurden sind die Verzögerungsendschal-
ter ident mit diesen, es wird jedoch eine Fahrt über 1 m/s (durch öffnen
des Sicherheitskreises) verhindert.
Dies solange bis die Verzögerungsendschalter explizit eingelernt
werden.
Für genauere Informationen zum Konfigurieren der Verzögerungsendschalter wird an das Parametri-
sierhandbuch verwiesen.
DE - Seite 24 (R60953.0009 3)
7. Während des Betriebs
Im folgendem Kapitel werden die verschiedenen Betriebsmodi beschrieben.
Die folgende Übersicht zeigt die Relaiszustände und den Sicherheitskreisstatus der jeweiligen
Betriebsmodi:
Betriebsmodus
Sicherheitskreis
Türüberbrückung
1
Einlernmodus (siehe Kapitel 4)
offen/geschlossen
offen
2
Normalbetrieb
- Türüberbrückung inaktiv
- Türüberbrückung aktiv
geschlossen
geschlossen
offen
geschlossen
3
Fehlermodus (Locked Mode)
offen
offen
7.1 Normalbetrieb
Im Normalbetrieb wertet die PSU01 die empfangenen Positionen aus und stellt alle Sicherheitsfunktio-
nen dar.
7.1.1 Funktion der Türüberbrückung
Die Türüberbrückung ist nur im Zustand “Normal Operation” aktiv (aktivierbar).
Die jeweilige Brückung wird nur unterhalb von 0,8 m/s und nur innerhalb der angeforderten Haltestelle
aktiv (0,3 m/s für Nachholung).
Sind Inspektionsendschalter aktiv bzw. ist zumindest die Inspektion
verkabelt und befindet sich der Aufzug in Inspektion, so wird eine
Brückung unterbunden.
Folgende Anwendungen können mit der Türüberbrückung der PSU01 realisiert werden, die abhängig
der gewünschten Türüberbrückungsanwendung von der Steuerung angefordert werden (siehe Para-
metrisierhandbuch).
7.1.1.1 Türüberbrückung für die Einfahrt zur vorzeitigen Türöffnung
Die Türüberbrückung für die Einfahrt zur vorzeitigen Türöffnung ist nur außerhalb der gewünschten
Haltestelle oder noch während der Einfahrt aktivierbar.
Im Stillstand in der entsprechenden Haltestelle hat sie keine Wirkung.
Die Steuerung muss die Brückung aktiv wieder ausschalten, wenn
diese nicht gebraucht wird. Verlässt der Aufzug aus einem vorigen
Stillstand mit gebrückten Türen die Türzone, so wird dies als UCM-Fall
erkannt.
DE - Seite 25 (R60953.0009 3)
deutsch
7.1.1.2 Türüberbrückung für die Nachholung in einer Haltestelle
Zur Nachholung der Aufzugskabine kann die Türüberbrückung nur innerhalb einer Zone unter 0,3 m/s
aktiviert werden. Dabei ist die Geschwindigkeit während der Nachholungsüberbrückung mit 0,3 m/s
kontrolliert. Eine Überschreitung erkennt die PSU01 als einen UCM-Fall.
Die Steuerung muss die Brückung aktiv wieder ausschalten, wenn
diese nicht gebraucht wird. Verlässt der Aufzug aus einem vorigen
Stillstand mit gebrückten Türen die Türzone, so wird dies als UCM-Fall
erkannt.
7.1.1.3 Türüberbrückung für den Schnellstart aus einer Haltestelle
Die Brückung für Schnellstart ist nur in einer Zone von ±2 cm um die Bündigposition der gewählten
Station aktivierbar/gültig. Sie deaktiviert sich beim Verlassen der Zone selbständig und muss nicht
unbedingt zurückgesetzt werden.
Die Steuerung hat Sorge zu tragen, dass der Sicherheitskreis der Türen vor dem Verlassen der redu-
zierten Zone geschlossen ist, sonst kommt es zum Stillstand (aufgrund des offenen Sicherheitskreises
der Türkontakte).
7.1.2 Schutzmodus (Inspektion)
Sind beide Inspektionsschalter deaktiviert, so wird das Eingangssignal
ignoriert. Eine Verdrahtung des Inspektions- /Schutzraums ist nicht
notwendig.
Ist Inspektion zumindest verkabelt, so wird die Türüberbrückung in der
Inspektion unterbunden, sowie die Geschwindigkeit in Inspektion mit
0,6 m/s beschränkt.
Die Steuerung muss auf geeignete Weise den Zustand der Inspektion-
sendschalter (gesetzt/oder nicht) darstellen.
Folgende Eigenschaften treffen zu, sobald ein Inspektionsendschalter gesetzt wurde.
Während der Inspektion wird die Geschwindigkeit auf 0,6 m/s begrenzt. Wird diese Geschwindigkeit
überschritten so löst die PSU01 die Funktion “Übergeschwindigkeit” aus. Dies führt zur Öffnung des
Sicherheitskreises bis zum Stillstand des Aufzuges.
Wenn der Aufzug in Inspektion ist und einen Inspektionsendschalter plus maximal 10 cm Hysterese
überfährt wird der Sicherheitskreis geöffnet und an die Steuerung gesendet (siehe Abbildung).
DE - Seite 26 (R60953.0009 3)
Es ist in der Verantwortung der Steuerung nur noch Fahrbefehle zuzulassen, welche aus dem
Inspektionsendschalter rausfahren. Ist eine derartige Fahrt von der Steuerung gewünscht, so sendet
sie der PSU01 den entsprechenden Befehl (siehe Parametrisierhandbuch). Der Sicherheitskreis wird
im Stillstand und bei Aufforderung durch die Steuerung wieder geschlossen, solange man sich in der
Hysteresezone befi ndet.
Durch ein “richtiges” Verlassen der Hysteresezone oder durch Abschalten der Inspektion, wird diese
Zone wieder aktiv.
Ein erneutes Reinfahren in diese Zone löst den gleichen Prozess erneut aus (s.o.).
Ein Überfahren der max. Hysteresezone des Inspektionsendschalters
(siehe Abbildung oben) führt immer zum Öffnen des Sicherheitskreises,
welcher auf Anforderung nicht mehr durch den PSU01 gebrückt wird.
Im Falle eines betätigten Inspektionsendschalters ist eine Rückholung
(Überbrückung) untersagt und schaltungstechnisch zu verhindern.
7.1.3 UCM Erkennung
Die UCM Überwachung der PSU01 wird scharf gestellt, sobald die Aufzugskabine in einer Türzone
hält. Unter folgenden Bedingungen wird PSU01 einen UCM Fall erkennen:
• die Geschwindigkeit in der Nachholung beträgt über 0,3 m/s
• der Aufzug verlässt die Türzone mit überbrückten Türen (z.B. durch einen Fehler der Steuerung
Ein erkannter UCM-Fall öffnet den Sicherheitskreis permanent. Voraus-
setzung dafür ist eine Bremseinrichtung nach EN81-20, 5.6.7 (Redun-
dant/Diagnose als Triebwerksbremse zertifi ziert).
Im Falle einer aktiven UCM-Sperre ist eine Rückholung durch die
Steuerung untersagt.
DE - Seite 27 (R60953.0009 3)
deutsch
Externe UCM-Einheiten können “parallel” angeschlossen werden. Die redundanten Türzonen-Relais
(Port X6) geben Türzoneninformationen laufend aus (vergleichbar mit festen Magnetschaltern), um die
Information an eine externe UCM Einheit zu liefern (Anlagen, die z.B. mit Einrückung arbeiten).
Achtung, da die UCM-Erkennung der PSU01 permanent aktiv ist, löst
im UCM-Fall auch die PSU01 aus und nicht nur die externe Einheit. Es
müssen entsprechend beide Geräte zurückgesetzt werden.
Die redundanten Türzonen-Relais (Port X6) sind ausschließlich für eine
optionale externe UCM-Einheit ausgelegt und dürfen für keine andere
Sicherheitsfunktion des Aufzuges verwendet werden.
7.1.4 Übergeschwindigkeit
PSU01 öffnet im Fall einer Übergeschwindigkeit den Sicherheitskreis und stellt somit eine Vo-
rauslösung zum Geschwindigkeitsbegrenzer bereit. Eine einstellbare Nenngeschwindigkeit verhindert
Fahrten über 115 % nach oben wie auch unten durch Öffnen des Sicherheitskreis.
Die Nenngeschwindigkeit des Aufzuges kann in mm/s festgelegt werden (siehe Parametri-
sierhandbuch).
Standardmäßig ist diese Geschwindigkeit auf 5 m/s gesetzt und somit wirkungslos.
Die Nenngeschwindigkeit kann im Stillstand laufend geändert werden.
Diese Funktion ist nicht Bestandteil der SIL3-Zertifizierung und ersetzt
nicht die in der EN81 vorgeschriebenen Maßnahmen.
7.1.5 Relaistest
Spätestens ein Mal pro Jahr wird ein Relaistest durchgeführt. Dieser startet im Stillstand und öffnet
alle Sicherheitsrelais. Eine angeschlossene kompatible Steuerung erfährt, dass PSU01 den Relaistest
gerade durchführt. Eine derartige Steuerung kann diesen Test durch einen Reset der PSU01 (siehe
Programmierhandbuch) zu einem selbst gewählten Zeitpunkt auslösen, solange dieser nicht länger als
ein Jahr ist. Nach jedem Selbsttest beginnt der Jahreszähler von neuem.
7.2 Fehlermodus
Im Fehlerfall geht die PSU01 in den Fehlermodus (PSU01 Lock) und es werden der Sicherheitskreis
sowie die Türzonen-Relais umgehend geöffnet. Das UCM-Relais öffnet etwas verzögert (Ausnahme
ein UCM-Fall tritt ein) um einen unnötigen Fang zu vermeiden. Die Reaktionszeit inkl. Öffnungszeit der
Relais kommt auf < 25 ms.
Abhängig von der Schwere des Fehlers geht die PSU01 sofort in den Lock Modus oder merkt sich
diesen Fehler. Die Fehler werden ausgegeben und können von einer kompatiblen Steuerung oder
über ein CANopen Terminal angezeigt werden.
DE - Seite 28 (R60953.0009 3)
Tritt ein PSU01-Lock auf, so muss von einem Monteur die Art des
Fehlers über ein CANopen Monitor oder eine kompatible Steuerung
ausgelesen werden und behoben werden. Dies kann ein UCM-Fall
sein aber auch ein kritischer Ausfall der Auswerteeinheit PSU (z.B.
Relais-Fehler) oder des Ants LES01 (Sensor Safe). Es liegt in der
Verantwortung des Monteurs eine gesperrte Anlage wieder sicher in
Betrieb zu nehmen.
Wie auf einen Fehler zu reagieren ist wird in Kapitel 7.3 - 7.6 beschrieben, wie ein Fehler zurückge-
setzt werden kann, wird in Kapitel 7.6 beschrieben. Auf jeden Fall ist auch die Fehlerbehandlung in der
Betriebsanleitung des Ants LES01 (Sensor Safe) zu berücksichtigen.
7.3 LED Blinkmuster
Die LEDs µP1 und µP2 blinken wie folgt:
Normalmodus
Blinken im Sekundentakt
Fehlermodus
Schnelles Blinken (5 x pro Sekunde)
7.4 Kommunikation
Die PSU01 übermittelt laufend Daten, im Fehlerfall vorrangig den Fehler. Die PSU01 macht gewisse
Systemparameter nach außen sichtbar. Sicherheitsrelevante Daten können nur gelesen werden. Ge-
nauere Informationen zu den Parametern entnehmen Sie bitte dem Programmierhandbuch.
7.5 Störungen
Bei Störungen gehen Sie bitte wie folgt vor:
1. Kontrollieren Sie auf richtige Montage des Ants LES01 (Sensor Safe).
2. Kontrollieren Sie auf richtige Montage der Position Supervisor Unit.
3. Kontrollieren Sie bitte auf korrekte Einbindung beider Systeme.
4. Kontrollieren Sie alle Anschlüsse auf ihre Richtigkeit.
Beziehen Sie auch alle Anweisungen der Ants LES01 Betriebsanleitung mit ein. Tritt ein PSU01-Lock
auf, so muss von einem Monteur der Fehlercode des Fehlers über ein CANopen Monitor (siehe Pro-
grammieranleitung) oder eine kompatible Steuerung ausgelesen werden und behoben werden. Eine
Übersicht möglicher Störungen zeigt folgende Tabelle:
Störung
Fehlercode
Maßnahme
Ants LES01 sendet keine
Position
2xx (entsprechen am
Sensor Fehler: 1-17)
Siehe Betriebsanleitung des
Ants LES01 (Sensor Safe)
Hardwarefehler
3, 11, 16, 17
Die PSU01 ist auszutauschen
Interner PSU01 Diagnose-
fehler
4-7, 11, 16, 18
Die PSU01 ist auszutauschen
Positionswert nicht plausibel
oder nicht innerhalb der Zeit
10, 12
Bus-Leitungen kontrollieren auf
mögliche Störungen testen.
DE - Seite 29 (R60953.0009 3)
deutsch
Spannungsabsenkung
13
Spannungsversorgung prüfen, Bela-
stung am Netzteil prüfen. Notstrom-
berieb (siehe oben) möglich.
Stromausfall
PSU01 startet mit Selbsttest neu
hoch. Keine Maßnahme notwendig.
UCM Modul geändert
14
PSU01 hat sich in den Auslieferzu-
stand zurück gesetzt. UCM-Option
gemäß Grundkonfiguration wieder
herstellen. PSU01 neu konfigu-
rieren. Die UCM-Option darf nicht
abgeändert werden.
Fehler in Sicherheitskrei-
seinbindung
15
Kontrolle, ob der Sicherheitskreis
richtig eingebunden wurde.
Ants LES01 im Lock
1
Normgerechte Wiederherstel-
lung der Aufzugsanlage und
anschließend Reset (siehe unten)
durchführen.
Keinen Sensor (Ants LES01)
gefunden
30
Verbindung zum Sensor Ants
LES01 prüfen.
Relaistest wird durchgeführt
101
Benachrichtigung
Ein (automatisches)
Zurücksetzen auf Werksein-
stellungen wird durchgeführt
102
Benachrichtigung
Keine Kommunikation mit
PSU01 möglich
Kann die PSU01 über CANopen
nicht erreicht werden, überprüfen
sie zuerst alle Netzwerkparameter
und Verkabelungen. Ist noch immer
keine Verbindung mehr möglich, ist
die PSU01 zu tauschen.
7.6 Rücksetzen
7.6.1 Einen Fehler zurücksetzen
Ein Fehler, welcher die PSU01 in den gesperrten Zustand (schnelles blinken beider Zustands LEDs)
gebracht hat, kann folgendermaßen zurückgesetzt werden:
1. Anlage befindet sich im Stillstand.
2. Knopf am PSU01 betätigen oder an der kompatiblen Steuerung einen Reset fordern.
3. Stromzufuhr der PSU01 innerhalb 15 Minuten unterbrechen.
4. Stromzufuhr wieder herstellen.
Die PSU01 führt daraufhin einen Selbsttest durch und geht wieder in den Normalmodus, sofern kein
Fehler erkannt wird.
DE - Seite 30 (R60953.0009 3)
Tritt ein PSU01-Lock auf, so muss von einem Monteur die Art des
Fehlers über ein CANopen Monitor (siehe Programmieranleitung)
oder eine kompatible Steuerung ausgelesen werden und behoben
werden. Dies kann ein UCM-Fall sein aber auch ein kritischer Ausfall
der Auswerteeinheit PSU (z.B. Relais-Fehler) oder des Ants LES01. Es
liegt in der Verantwortung des Monteurs eine gesperrte Anlage wieder
sicher in Betrieb zu nehmen.
Alle Bauteile müssen im einwandfreien Zustand arbeiten. Bitte ver-
gewissern Sie sich auch in der Beriebsanleitung des Ants LES01, wie
welche Fehler zu beheben bzw. zu behandeln sind.
Nach jedem Fehler, der den PSU01 in den Lock-Zustand bringt, ist auf
jeden Fall die komplette Länge des Aufzugschachtes im Normalbetrieb
fehlerfrei zu durchfahren, bevor der Aufzug wieder frei gegeben wer-
den kann. Treten wiederholt Fehler auf, so müssen Sie den Ursachen
nachgehen. Sind diese durch die oben beschriebenen erlaubten
Maßnahmen nicht behebbar, so ist der ganze PSU01 zu tauschen.
7.6.2 Alle Haltestellen rücksetzen
Es können alle Haltestellen gelöscht werden. Die Endschalterpositionen bleiben jedoch bestehen. Das
Zurücksetzten ist mit einer kompatiblen Steuerung, der externen Programmiereinheit oder mit einem
CANopen Terminal möglich. Zum Rücksetzen aller Haltestellen wird auf das Programmierhandbuch
verwiesen.
Nach Rücksetzen der Haltestellen ist die UCM Funktion erneut zu
prüfen (inkl. Bremsweg für Gesamtsystem).
7.6.3 Auf Werkseinstellung zurücksetzen
Das Gerät kann auf den Auslieferzustand zurückgesetzt werden. Alle bisher gespeicherten Parame-
ter wie Endschalterpositionen, Haltestellenpositionen, Türzonenlänge, etc. werden gelöscht. Die-
ses Zurücksetzten ist mit einer kompatiblen Steuerung, der externen Programmiereinheit oder mit
einem CANopen Terminal möglich. Zum Rücksetzen in den Auslieferzustand wird auf das Program-
mierhandbuch verwiesen.
Nach einem Zurücksetzen auf die Werkseinstellungen muss eine kom-
plette Abnahmeprüfung stattfinden.
DE - Seite 31 (R60953.0009 3)
deutsch
8. Prüfung der Funktionen
8.1 Endschalterfunktion
Zur Prüfung der Funktionstüchtigkeit der Endschalteremulation führen Sie bitte mit der angeschlosse-
nen Steuerung eine Endschalterfahrt durch. Bitte konsultieren Sie dazu die Bedienungsanleitung der
jeweiligen Steuerung und gehen gemäß den dort beschriebenen Vorgaben vor.
8.2 Inspektionsendschalterfunktion
Zur Prüfung der Funktionstüchtigkeit der Inspektionsendschalteremulation führen Sie bitte mit der
angeschlossenen Steuerung eine Inspektionsendschalterfahrt durch. Bitte konsultieren Sie dazu das
Betriebshandbuch der jeweiligen Steuerung und gehen gemäß den dort beschriebenen Vorgaben vor.
8.3 Verzögerungsendschalterfunktion
Zur Prüfung der Funktionstüchtigkeit der Verzögerungsendschalterfunktion führen Sie bitte mit der an-
geschlossenen Steuerung eine Verzögerungsendschalterfahrt durch. Bitte konsultieren Sie dazu das
Betriebshandbuch der jeweiligen Steuerung und gehen gemäß den dort beschriebenen Vorgaben vor.
8.4 UCM-Funktion
Zur Prüfung der UCM-Funktion führen Sie bitte mit der angeschlossenen Steuerung eine UCM Fahrt
durch. Dabei muss die Steuerung mit gebrückten Türen die Türzone verlassen. Bitte konsultieren
Sie dazu das Betriebshandbuch der jeweiligen Steuerung und gehen gemäß den dort beschriebenen
Vorgaben vor.
8.5 Türzonenemulation-Funktion
Beim Fahren mit einer Geschwindigkeit von unter 0,8 m/s muss überprüft werden ob die Türzonen
schalten.
Zur Prüfung der Funktionen von der Türzonenemulation für ein externes UCM Auswertegerät gehen
Sie bitte gemäß Vorgaben der Steuerung und des UCM Auswertegerätes vor. Bitte konsultieren Sie
dazu das Betriebshandbuch des jeweiligen Gerätes, welche diese Funktionen zur Verfügung stellt und
gehen gemäß den dort beschriebenen Vorgaben vor.
8.6 Übergeschwindigkeit (optional)
Zur Prüfung der Übergeschwindigkeit (sofern die Nominalgeschwindigkeit in der PSU01 eingestellt
wurde) führen Sie bitte mit der angeschlossenen Steuerung eine Übergeschwindigkeitsfahrt durch. Bit-
te konsultieren Sie dazu das Betriebshandbuch der jeweiligen Steuerung und gehen gemäß den dort
beschriebenen Vorgaben vor.
Sobald die Geschwindigkeit der Aufzugskabine +15 % der gespeicherten Normalgeschwindigkeit
überschreitet, öffnet die PSU01 den Sicherheitskreis und der Aufzug bleibt stehen.
DE - Seite 32 (R60953.0009 3)
9. Reparatur, Wartung und Entsorgung
Grundsätzlich erfordert Ants LES01 wenig Wartung. Bei einem defekten Bauteil, muss die komplette
PSU01 ersetzt werden.
Die PSU01 macht jährlich einen Relaistest und überprüft so die aufrechte Funktionalität der Si-
cherheitsrelais sowie anderer Bauteile. Dieser Relaistest kann auch von einer kompatiblen Steuerung
ausgelöst werden (siehe Programmierhandbuch).
9.1 Austausch von Komponenten
PSU01 kann nur als Gesamtsystem (Sensor und Auswerteeinheit) getauscht werden.
9.2 Wartung
Die Wartung hat zumindest einmal im Jahr statt zu finden. Hier muss folgendes überprüft werden:
1. PSU01 auf sichtbare Schäden untersuchen und von etwaigen Verunreinigungen befreien.
2. Die Funktionsprüfung gemäß 8. ist durchzuführen. Weiter ist zu Kontrollieren ob das Schalten der
Türzonen (Klemmen 22-24) noch immer in Übereinstimmung mit allen Haltestellen ist.
3. Sollte die PSU01 mit der Inspektion verkabelt sein muss folgendes im vollen Normalbetrieb der
Aufzugsanlage getestet werden. Im Falle einer negativen Prüfung muss man von einer kapaziti-
ven Einkoppelung im Inspektionskreis ausgehen. Diese ist bauseitig zu beheben. Sollte der Test
weiterhin negative ausfallen, so ist von einem defekten Bauteil der PSU01 auszugehen und diese
ist zu tauschen:
a. bei Inspektion ausgeschalten, muss die Kontrolllampe SK auf der Platine leuchten.
b. bei geöffneten Türen darf die Kontrollleuchte SK auf der Platine nicht leuchten.
4. Die Wirksamkeit der Funktion der Verzögerungsendschalter ist regelmäßig zu prüfen.
5. Hinweis zur Wartung des Ants LES01 (Sensor) entnehmen Sie der Bedienungsanleitung
R60200.0009.
9.3 Rückverfolgbarkeit
Es wird empfohlen die Rückverfolgbarkeit von Produkten mit Aufgaben der funktionalen Sicherheit-
stechnik sicherzustellen. Dies ist für eine schnelle Reaktion im Markt entscheidend.
9.4 Entsorgung
Die PSU01 ist so konstruiert, dass es die Umwelt so wenig wie möglich belastet. Es emittiert keine
Schadstoffe, enthält keine umweltschädlichen Substanzen und verbraucht im Betrieb nur sehr wenig
Energie. Unbrauchbare oder irreparable Geräte sowie Geräte welche ihren Produktlebenszyklus
überschritten haben sind entsprechend den jeweils gültigen Abfallbeseitigungsvorschriften für Elektro-
nikschrott zu entsorgen. Das Kunststoffgehäuse kann als Restmüll entsorgt werden.
9.5 Bestellbezeichnung und Ersatzteile
Alle Bestandteile können nur als Gesamtprodukt wiederbestellt werden. Ein Austausch von Kompo-
nenten ist nicht möglich. Hierfür kontaktieren Sie bitte die Kübler Gruppe, Fritz Kübler GmbH.
DE - Seite 33 (R60953.0009 3)
deutsch
9.6 Service Adresse
Kübler Gruppe
Fritz Kübler GmbH
Schubertstraße 47
78054 Villingen-Schwenningen
Deutschland
Tel. +49 7720 3903-849
www.kuebler.com
[email protected]
PSU01 (Position Supervisor Unit incl. Ants LES01)
R60953.0009 - Index 3
CANopen
®
LIFT
© CiA
EN - page 2 (R60953.0009 3)
Editor
Kübler Group, Fritz Kübler GmbH
Schubertstr. 47
78054 Villingen-Schwenningen
Germany
www.kuebler.com
Application support
Phone +49 (0) 7720 3903-952
Fax +49 (0) 7720 21564
[email protected]
Document no.
R60953.0009 - Index 3
Document name
Operating manual
PSU01 (Position Supervisor Unit (PSU) incl. Ants LES01)
Language version
English (EN) - German is the original version
Date of issue
01/2019 - Index 3
Copyright
©2019, Kübler Group, Fritz Kübler GmbH
Legal notice
All contents included in this manual are protected by the terms of use and copyrights of the Kübler
Group, Fritz Kübler GmbH. Any reproduction, modification, usage or publication in other electronic and
printed media as well as in the internet requires prior written authorization by Fritz Kuebler GmbH.
EN - page 3 (R60953.0009 3)
english
Table of contents
1.
General instructions
5
1.1 Abbreviations used
5
1.2 Symbols used / Warnings and safety information
5
1.3 Target group
6
1.4 Safety guidelines
6
1.5 Installation and operating personnel
6
1.6 Warranty and liability
6
1.7 Intended use
6
1.8 Transport & delivery
7
1.9 Storage
7
1.10 Other applicable documents
7
2.
Product characteristics
8
2.1 Function of the PSU01
8
2.1.1 Limit switch emulation
8
2.1.2 Inspection limit switch emulation
9
2.1.3 Safety circuit for door bypass
9
2.1.4 Unintended Car Movement (UCM)
9
2.1.5 Time-delayed control switch
10
2.1.6 Overspeed pre-tripping
10
2.1.7 Door zone emulation
10
2.2 Special features
11
2.3 Scope of delivery PSU01
11
2.4 Example of a type plate
11
2.4.1 Evaluation Unit / Position Supervior Unit
11
2.4.2 Ants LES01
11
3.
Technical description
12
3.1 Position Supervisor Unit (Evaluation Unit)
12
3.2 Safety characteristics
13
3.3 Ants LES01 (sensor)
13
4.
Mechanical installation
14
4.1 Evaluation Unit / Position Supervisor Unit
14
4.2 Ants LES01 (Sensor)
14
5.
Electrical installation
15
5.1 EMC notes
15
5.2 General instructions
15
5.2.1 Applicable safety standards
15
5.2.2 CE conformity
15
5.3 Electrical integration into the elevator system
16
5.3.1 Connection overview PSU
17
5.3.2 Connection of the Ants LES01
18
5.4 Safety relay connection
18
5.4.1 Plug X5: Safety circuit output
18
5.4.2 Plug X6: Door zone relay outputs
18
5.4.3 Plug X6: Relay contact – door zone display connection
19
EN - page 4 (R60953.0009 3)
5.4.4 Plug X7: Door bypass
19
5.4.5 Plug X8 (optional): Inspection
19
6.
Commissioning according to EN81-20
20
6.1 Requirement
20
6.2 Overview of the parameterization
21
6.3 Protected area parameterization
22
6.4 Teaching the top limit switch with reduced shaft head
23
6.5 Time-delayed limit switch parameterization
23
7.
During operation
24
7.1 Normal operation
24
7.1.1 Door bypass function
24
7.1.1.1 Door bypass for drive-in for early door opening
24
7.1.1.2 Door bypass for car level control at a stop
25
7.1.1.3 Door bypass for fast start from a stop
25
7.1.2 Protection mode (inspection)
25
7.1.3 UCM detection
26
7.1.4 Overspeed
27
7.1.5 Relay test
27
7.2 Error mode
27
7.3 LED flashing pattern
28
7.4 Communication
28
7.5 Failures
28
7.6 Resetting
29
7.6.1 Resetting an error
29
7.6.2 Resetting all stops
29
7.6.3 Resetting to factory setting
30
8.
Checking the functions
31
8.1 Limit switch function
31
8.2 Inspection limit switch function
31
8.3 Time-delayed limit switch function
31
8.4 UCM function
31
8.5 Door zone emulation function
31
8.6 Overspeed (optional)
31
9.
Repairs, maintenance and disposal
32
9.1 Replacing components
32
9.2 Maintenance
32
9.3 Traceability
32
9.4 Disposal
32
9.5 Order information and spare parts
32
9.6 Service addresse
33
EN - page 5 (R60953.0009 3)
english
1. General instructions
Please carefully read these operating instructions before you work with, mount or commission the safe
Evaluation Unit. These operating instructions instruct the technical personnel of the machine manufac-
turer or the machine operators with regard to the safe installation, electrical installation, commissioning
as well as the operation of the safe PSU Evaluation Unit. In addition, technical expertise that is not
imparted in this document is required for planning and using protection devices duch as the safe PSU
Evaluation Unit. As a rule, the official and legal regulations for operating the safe PSU Evaluation Unit
must be obeserved.
1.1 Abbreviations used
PSU01
Complete system Ants LES01 + Evaluation Unit PSU
Ants LES01
Linear Encoder Safe, SIL3
PSU
Evaluation Unit / Position Supervisor Unit, SIL3
UCM
Unintended Car Movement
1.2 Symbols used / Warnings and safety information
Particularly important information in the manual are identified as follows:
This symbol, together with the signal word “Danger”, indicates immedia-
tely imminent threat to life and health of persons.
The non-compliance with this warning will lead to death or severe
injuries.
This symbol, together with the signal word “Warning”, indicates a
potential danger to life and health of persons.
The non-compliance with this warning may lead to death or severe
injuries.
This symbol, together with the signal word “Caution”, indicates a poten-
tial danger to life and health of persons.
The non-compliance with this warning may lead to slight or minor
injuries.
Tips and recommendations as well as information for an efficient and
trouble-free operation.
EN - page 6 (R60953.0009 3)
1.3 Target group
The PSU01 may only be installed, commissioned, tested, maintained and used by qualified personnel.
Qualified personnel refers to someone
• who has a suitable technical training and
• has been instructed on how to operate the unit by the machine operator and
• has been instructed on the applicable safety guidelines and
• has access to these operating instructions.
1.4 Safety guidelines
Please read the operating instructions before commissioning the device. Installation notices must be
observed. Only commission the device if you have read and understood the operating instructions.
The selection of the devices and their integration into the control system require the qualified knowled-
ge of the relevant laws and normative requirements on part of the machine manufacturer.
The safety and warning instructions are an important part of the operating instructions and must be
followed.
1.5 Installation and operating personnel
The operator is obligated to take suitable safety-related measures. Only personnel who have knowled-
ge of the basic regulations for accident prevention and occupational safety and health and have
read and understood the safety information in these instructions may be deployed for installation and
commissioning.
1.6 Warranty and liability
The entitlement to warranty and liability is void if the Ants LES01 (Sensor Safe) is not used in the
intended manner, if any damage can be traced back to a failure to observe the operating instructions,
or if the installation and operating personnel are not properly qualified or trained.
Failure to observe these instructions voids all entitlement to warranty or guarantee as well as any
possible liability claims. All regulations concerning accident prevention which are applicable to the lift
must be observed. In order to prevent damage due to improper handling of electrical voltages and
currents, all relevant (including local) regulations must be observed, particularly in respect of protective
measures and proper earthing.
1.7 Intended use
The Position Supervisor Unit was developed exclusively for the intended use described here:
EN - page 7 (R60953.0009 3)
english
The PSU01 is used for the safe positioning evaluation for implementing
functions of limit switches, inspection limit switches, time-delayed limit
switches, unintended car movement (UCM) as well as for the safe
bypass of the safety circuit in case of premature door opening/relevel-
ling of elevator systems according to EN81-20. It forms a system unit
together with the Ants LES01 sensor.
Any unintended use can result in hazardous situations.
The PSU Evaluation Unit may only be used in conjunction with the Ants
LES01. All information provided in both operating instructions must be
strictly observed. The operating instructions for the Ants LES01 are
enclosed with this product. They are explicitly referred to here as an
integral part of the product.
1.8 Transport & delivery
Upon receiving the delivery, immediately check it for any transport damage. Immediately notify the
transport company of any damage. Damage may rule out the commissioning of the Position Super-
visor Unit. If you do not immediately install the Position Supervisor Unit, store the device at a dry
location free of dust - ideally in the transport packaging.
1.9 Storage
The device must be stored according to the following conditions:
• Dry and dust-free
• Avoid mechanical vibrations
• Do not store outdoors
• Do not exceed the temperature and humidity limits (see technical specifications)
1.10 Other applicable documents
All technical specifications are provided in the corresponding data sheets of the PSU01 as well as
of the Ants LES01. They contain the mechanical and electrical characteristic values of the Position
Supervisor Unit. The separate operating instruction (R60200.0009) of the product must be observed
for commissioning the Ants LES01.
In addition, there are programming instructions that are necessary to parameterise the PSU01. This is
generally only interesting for control manufacturers to ensure that their lift control system is compatible
with the PSU01.These instructions is continuously keep up to date and are also available for download
on our homepage. Each CANopen terminal can be used to parameterise the unit. The necessary EDS
files are always available for download on our homepage.
EN - page 8 (R60953.0009 3)
2. Product characteristics
The PSU Evaluation Unit is a safe position evaluation unit for implementing functions of limit switches,
inspection limit switches, time-delayed limit switches, Unintended Car Movement (UCM) as well as for
the safe bypass of the safety circuit in the area of the doors in case of premature door opening/relevel-
ling of elevator systems according to EN81-20.
The overall system PSU01 consists of two devices, the Ants LES01 (Linear Encoder Safe) and the
PSU Evaluation Unit (Position Supervisor Unit) described here. The PSU01 is connected via a free
CAN-bus to an external compatible control, a CANopen terminal or an external programming device,
which is used for parameterising the safety functions. The parametrisation procedure is not a part of
these operating instructions. In this respect, reference is made to the separate programming manual
or the respective manual of the compatible control.
The PSU01 receives corresponding parameters or reset commands from one of these devices via the
free CAN bus (Port X3) and outputs information about the position, state, etc. to these external devi-
ces as well as to elevator controls. The pure positioning output is also optionally supported via SSI.
The PSU Evaluation Unit and the Ants LES01 are certified as a complete system and may only be
operated together. They are factory-identified by a Set.ID. Ants LES01 safely provides the absolute
positions of the elevator plant via a second private CAN bus and forwards them to the PSU Evaluation
Unit (Port X2). Ants LES01 is moreover certified and available as a standalone product.
The Ants LES01 as part of the PSU01 must be correctly commissioned
according to its operating instructions.
2.1 Function of the PSU01
The PSU01 fulfils the following requirements for the state-of-the-art elevator system:
• Limit switch emulation
• Inspection limit switch emulation for reduced shaft head / shaft pit
• Safety circuit for bypassing the door contacts
• Unintended Car Movement (UCM)
• Time-delayed limit switch emulation
• Overspeed pre-tripping
• Door zone emulation for forwarding the information to an optional external UCM unit
The PSU01 fulfils the requirements according to EN81 by:
• The one-time teaching of all stops (performed during commissioning)
• Safety relays to open the safety circuit
• Safety relays for door bypass
• Inspection input query
2.1.1 Limit switch emulation
The emergency limit switches are simulated according to EN81-20 Safety function 5.12.2.
New stations must be at least 2 mm away from the taught limit switch positions.
EN - page 9 (R60953.0009 3)
english
2.1.2 Inspection limit switch emulation
The Position Supervisor Unit (PSU01) allows monitoring the protected area in case of reduced
shaft head / shaft pit according to EN81-21, 5.5.3.4 or 5.7.3.4 (inspection limit switch).
This function is represented by an additional virtual limit switch positioned at a fixed distance of 1.2 m
from the limit switch. One is present for shortened top buffers and one for shortened bottom buffers.
These new limit switches are called “inspection limit switches”.
The position of the inspection limit switches is fixed at 1.2 m from the
limit switch and cannot be moved.
The inspection limit switches are optional and can be disabled during
the first configuration.
When the lower inspection limit switch is enabled, it may happen that
the car, when operated by the installer standing on the car roof, stops
in the inspection limit switch area, even though the lowest stop has not
been reached (1.2 m from the limit switch).
2.1.3 Safety circuit for door bypass
The PSU01 provides a safety circuit for bypassing the door contacts according to EN81-20: 5.12.1.4.
The PSU01 bypasses, on request, the door contacts of a determined stop
• for early door opening
• for car level control and
• for a fast start.
An external safety circuit for bypassing doors is expressly forbidden.
2.1.4 Unintended Car Movement (UCM)
The PSU01 provides protection against the unintentional movement of the elevator car according
to EN81-20 safety function 5.6.7. The set door zone (see 2.1.2) is used as the UCM zone. This also
exclusively refers to the length of the zone. The UCM zones are always active and cannot be selecti-
vely switched.
The door zone emulation (Port X6) allows the use of an optional external UCM unit.
EN - page 10 (R60953.0009 3)
Since the UCM detection is permanently active in the PSU01, the
PSU01 also triggers in the case of an UCM event, and not only the
external unit. Accordingly, both devices must be reset.
The control for the brake element of the protection device is included
in the PSU01, but the brake element of the protection device itself is
not a part of his safety circuit or of this description.
It must be provided on site in the elevator plant. The regulations ap-
plicable to this element must be complied with.
The brake elements used for the protection device must be devices
tested in compliance with the provisions of EN81-20, 5.6.7 and which
are able to stop the elevator within the prescribed distance and delay.
A car level control at a speed exceeding 0.3 m/s is always detected by
the PSU01 as a UCM event, independently of the UCM zone.
2.1.5 Time-delayed control switch
The PSU01 provides the time delay control circuit function for shortened buffers according to EN81-
20: 5.12.1.3.
This function is represented by an additional speed-dependent virtual limit switch, which can be
positioned freely once (using CANopen). These new limit switches will be called „time-delayed limit
switches“ hereafter.
There is one time-delayed limit switch for shortened top buffers and one for shortened bottom buffers.
The tripping speed is set to 1 m/s and cannot be modified.
If necessary, the position of the time-delayed limit switch must be
shifted.
2.1.6 Overspeed pre-tripping
The PSU01 provides the overspeed pre-tripping function (EN81-20: 5.6.2.2.1) or upward travel over-
speed (EN81-20: 5.6.6) function and opens the safety circuit in case of such a event.
This function is not part of the SIL3 certification and does not replace
the measures prescribed in EN81.
2.1.7 Door zone emulation
The PSU01 provides the door zone via two redundant channels. It thus simulates door magnets, which
can be omitted at the assembly.
As standard, all door zones are simulated by the Evaluation Unit as soon as the elevator travels
slower than 0.8 m/s.
EN - page 11 (R60953.0009 3)
english
In the standard, the door zone is preset to ± 20 mm from the sill. It can be modifi ed between
± 5-200 mm. More detailed information on the parameters can be found in the programming
manual.
A maximum of 200 sills is possible. Sills must have a minimum distance of 20 mm from one another. If
neighboring door zones are overlapping, they will be shortened in order to have a zone-free area of at
least 10 mm, or they will be merged to a common zone.
The redundant door zone relays (port X6) are exclusively intended
for an optional external UCM unit and may not be used for any other
elevator safety function.
2.2 Special features
• Mechanical limit switches are no longer necessary
• No additional magnets are necessary for the premature door opening
• Easy installation through hat rail assembly in the roof control or control boxes
2.3 Scope of delivery PSU01
• Evaluation Unit / Position Supervisor Unit in top-hat rail housing.
• Ants LES01 (separate instruction manual for Ants LES01 is included in the scope of delivery).
2.4 Example of a type plate
A label is attached to the Position Supervisor Unit. It includes the following information:
• order code
• SetID (sensor + Evaluation Unit)
• type designation / serial number
• certifi cate number TÜV
• power supply
• CE mark
• reference to operating instructions (address)
2.4.1 Evaluation Unit / Position Supervior Unit
2
<
24 VDC PELV XXA
Fritz Kübler GmbH
Type: PSU01
SetID: 00070-11/2018 S-No: XX3333XX
8.PSU01.xxxx.xxxx
TÜV-A-AT-X-XX-XXXX-EUES
www.kuebler.com
0408
Schubertstraße 47
D-78054 Villingen-Schwenningen
2.4.2 Ants LES01
2
WH
BN
GN
YL
GND
+ 24
VDC
CAN
High
CAN
Low
Schubertstraße 47
D-78054 Villingen-Schwenningen
10-30 VDC
XXA ±10%
Fritz Kübler GmbH
Type: PSU01 (Ants LES01)
SetID: 00070-11/2018 S-No: XX1234XX
8.PSU01.xxxx.xxxx
TÜV-A-AT-X-XX-XXXX-XXXX
www.kuebler.com
0408
EN - page 12 (R60953.0009 3)
3. Technical description
The technical specifications for the PSU01 (Evaluation Unit + sensor) are described below.
3.1 Position Supervisor Unit (Evaluation Unit)
Feature
Value
Standard references
EN81-20, EN81-50, EN81-21
Housing material
Plastic
Housing dimensions
70 mm (H) x 95 mm (L) x 30 mm (W)
Interfaces
2 x CAN (internal and public) , 1 x SSI (optional)
Protocol
Internal: proprietary, public: CANopen, SSI: 2 x 25 bit with
PFB, grey code, MSB-first
Connection type
picoMAX® eCOM 3.5, 7.5 (connection and chapter 5)
Ambient operating temperature
From -5°C to +55°C
Storage temperature
From -10°C to +70°C
Humidity
< 90% (non-condensing)
Air pressure
800 - 1013 hPa (up to 2000 m over sea level)
Service life
20 years
Degree of protection
IP00 (min. IP20 when installed in the switching cabinet)
Supply voltage
24 VDC low-voltage PELV
Power
< 10 watts
Maximum distance to the encoder
100 m (internal CAN bus)
Deactivation time / system response
time
< 25 ms (incl. relay switching time)
Maximum number of floors
200
All lines and trailing cables must be manufactured with dual insulation
or mechanically protected according to EN81-20 5.10.6.
In particular, make sure that they are routed without any short circuits.
EN - page 13 (R60953.0009 3)
english
The connections of the Evaluation Unit has the following characteristics:
Terminal
Functional area
Cable
X1
Voltage supply
24 VDC
0.75 mm2
X2
CAN1 - interner BUS to the
encoder
Direct connection of the Ants
LES01 (Sensor Safe) encoder
Direction connection without
extension or 0.75 mm2 (max.
100 m) via trailing cables, twisted
pair with shield
X3
CAN2 - CAN OPEN
Direct connection of
programming unit or to
compatible control. Compliant
with CAN bus
Direct connection or 0.75 mm2
(max. 100 m) via trailing cables,
twisted pair with shield
X4
SSI (optional)
SSI compliant
0.75 mm2 (max. 100 m) via trailing
cables, twisted pair with shield
X5
Safety circuit integration
48 ... 230 VAC max. 2 A,
24 VDC max. 1 A
0.75 mm2
X6
Door zone emulation
24 VAC, 24 VDC, max. 10 mA
0.75 mm2
X7
Door bypass trip circuit
48 ... 230 VAC max. 2 A,
24 VDC max. 1 A
0.75 mm2
X8
Inspection query (optional)
48 ... 230 VAC, 24 VDC,
max. 2 A
0.75 mm2, maximum 170 m (if
170 m is exceeded, separate
capacitively coupled interference
must be considered (see 5.2.2))
3.2 Safety characteristics
Safety characteristics
Basic standards
EN81-20, EN81-50, EN81-21, EN62061, EN61508-1-7,
EN60664-1, EN60950-1, EN61784-3
Classification
SIL3, continuous mode
System structure
2 channels
PFHd value
< 1 x 10-7
3.3 Ants LES01 (sensor)
For technical description, see enclosed operating instructions R60200.0009.
EN - page 14 (R60953.0009 3)
4. Mechanical installation
4.1 Evaluation Unit / Position Supervisor Unit
The Evaluation Unit is supplied in a plastic housing, which is suitable for installation on a top-hat rail.
The Evaluation Unit must be installed in a switching cabinet (IP20) according to EN81-20.
The following options are available for mounting the Evaluation Unit:
1. Mount the Evaluation Unit on the cabin roof.
The sensor is connected directly to the Evaluation Unit.
2. Mount the Evaluation Unit in the control box.
The sensor is routed directly to the Evaluation Unit via the trailing cable. The maximum length of the
bus line of 100 m must be complied with.
In both cases, a top-hat rail is required. The PSU Evaluation Unit can be simply mounted on the top-
hat rail using its housing.
4.2 Ants LES01 (Sensor)
Details on mounting of
• tape
• mounting kit
• sensor
in the application you will find in the operating instruction R60200.0009 (from chapter 3.2).
The safety and warning instructions must be observed.
EN - page 15 (R60953.0009 3)
english
5. Electrical installation
Before unplugging/disconnecting the signal line, please always disconnect the voltage supply.
When connecting the Ants LES01, the corresponding operating instructions must be observed. All li-
nes and trailing cables must be manufactured with dual insulation or mechanically protected according
to EN81-20 5.10.6.
The operating personnel must ensure that the device is not damaged
by an electrostatic charge / discharge during installation / replacement.
A direct contact with the board / electronic components should be avoi-
ded or suitable protective measures should be taken.
5.1 EMC notes
• With bus lines, only use shielded and twisted pair lines for the Position Supervisor Unit.
• To prevent earth loops, the shield is only connected at one location (PSU01 is already earthed
through PELV) to the potential (protective earth).
• Make sure that the line shields are corrected fastened.
• Make sure that the lines are properly routed when wiring your system.
Disconnect the wiring in the ling groups, motor/power supply lines
and signal/data/safety circuit lines.
• Route the signal and data lines as close to the earth surfaces as possible (frame members, metallic
rails, cabinet covers) and not parallel to the motor and the power supply line.
• Connect all operating equipment ensuring low-impedance to the earth/protective conductor system.
5.2 General instructions
5.2.1 Applicable safety standards
• Prior to commissioning, all the necessary cable cores must be connected according to the data
sheet. The Ants LES01 is already pre-assembled and must only be plugged in at port X2. Pro-
perly insulate all unnecessary ends of the output signals to prevent short circuits.
• Take into consideration the correct operating voltage and the maximum permissible output current
(see data sheet).
• Use a supply voltage source according to PELV.
5.2.2 CE conformity
To achieve CE conformity, the installation must be carried out in an EMC-compliant manner:Use conti-
nuously shielded cables for control lines.
• Use continuously shielded cables for control lines.
• The bus lines (port X2, X3, X4) must be routed separately from lines with a high interference level.
• The safety circuit must be routed according to the standard as free as possible of capacitively
coupled interference, separately from lines with a high interference level.
EN - page 16 (R60953.0009 3)
• In case of excessive capacitively coupled interference in the inspection circuit (see maintenance
instructions), they must be correctly eliminated by the customer using power resistors or capacitors.
• No users with a high interference level, such as frequency converters, solenoid valves, contactors,
etc. should be connected to the voltage supply of the electronics (PSU Evaluation Unit, Ants LES01,
control). Otherwise, a suitable voltage filter must be provided.
5.3 Electrical integration into the elevator system
This chapter describes PSU01 in the overall system and explains the electrical integration into the lift
system.
The figure below displays the correct integration of the PSU Evaluation Unit with Ants LES01 in the
elevator system.
main contactor
activation
main contactors
landing door contacts
car door contact
LIFTCONTROL
PELV
supply
24VDC
emergency
power supply
12VDC
safety chain
ground
doorzone information
(battery-buffered)
doorzone
bridging
safety chain
doorzone
(redundant)
doorzone
supply input
safety chain
absolute position
emergency stop area
CAN1
CAN2
SSI
position/SSI (optional)
position-data CAN-OPEN
lock contacts
Ants LES01 (Sensor)
CE0408TÜV-A-AT XXX
Position Supervisor Unit
CE0408TÜV-A-AT XXX
1
GND
X1
2
24V
3
12V
24VDC
AC
AC
12VDC
22
ZONE2
X6
23
ZONE3
24
COM2/3
20
ZONE1
21
COM1
19
SC2
X5
18
SC1
28
X8
29
26
X7
27
4
24V
X2
5
GND
6
CAN1L
7
CAN1H
8
GND
9
24V
X3
10
CAN2L
11
CAN2H
12
GND
13
DATA1
X4
14
DATA2
15
CLK1
16
CLK2
17
GND
F2A
F2A
inspection
Wiring Diagram PSU01
Ants LES01 is connected to Kübler Position Supervisor Unit
via CAN interface.
EN - page 17 (R60953.0009 3)
english
5.3.1 Connection overview PSU
The PSU Evaluation Unit has 8 plugs that are clearly shown below and described in detail in the
following chapters.
Connection
Terminal
No.
Description
Supply
X1
1
2
3
GND
+24 VDC (low voltage according to PELV)
+12 VDC battery supply for the door zone
display during emergency operation
CAN1 - internal
Ants LES01
X2
4
5
6
7
8
+24 VDC
GND
CAN1 LOW
CAN1 HIGH
GND
CAN2 - external
CANopen
X3
9
10
11
12
+24 VDC
CAN2 LOW
CAN2 HIGH
GND
SSI communication
(optional)
X4
13
14
15
16
17
DATA1
DATA2
CLK1
CLK2
GND
Safety circuit output
X5
18
19
SC1
SC2
EN - page 18 (R60953.0009 3)
Door zone emulation
X6
20
21
22
23
24
ZONE1 (for emergency power supply)
COM1 (for emergency power supply)
ZONE2 door zone magnet 1
ZONE3 door zone magnet 2
COM2/3 shared potential
Door bypass integration
X7
26
27
Safety circuit input
Safety circuit input
Safety circuit query
X8
(optional)
28
29
Inspection input 24 VDC
INspection output GND
5.3.2 Connection of the Ants LES01
The sensor has 4 inputs/outputs, which are already correctly wired to a picoMAX® eCOM plug during
production, for direct use on the PSU Evaluation Unit.
When connecting via a trailing cable, the wiring must be performed as follows:
EVAL connection
No.
Description
Colour of the wire from the encoder
X2
4
+24 VDC
brown
5
GND
white
6
CAN1 LOW
yellow
7
CAN1 HIGH
green
8
SLD
shield
The maximum distance to the Evaluation Unit may not exceed 100 m. This 100 m must be carried out
as a twisted pair bus lines shielded with 0.5 mm2 and can also be routed in the trailing cable.
In general, when installing buses, the installation technician must always make sure that he is not
electrostatically charged to avoid damage to the device during installation.
5.4 Safety relay connection
Electrical measures for integrating the safety circuits are displayed below.
5.4.1 Plug X5: Safety circuit output
These terminals 18 and 19 are always closed during operation and open in the limit switch, time delay
limit switch, inspection limit switch areas, in error mode (tape or PSU01 faulty) and in case of an UCM.
In AC operation, the safety circuit must be protected with a 2 A fuse on
the control side. In DC operation, it must be protected with a 1 A fuse.
5.4.2 Plug X6: Door zone relay outputs
These terminals 22, 23, 24 are used as inputs for an external UCM Evaluation Unit. They can be used
for evaluating the UCM zone, as they are to be considered as classical magnetic switches, which they
replace.
EN - page 19 (R60953.0009 3)
english
These contacts have a redundant design, but do not perform any
auto-self test operations and may only be used as shaft information for
a safety circuit according to EN81-20 5.6.7. The corresponding safety
circuit must be able to detect a contact malfunction. Suitable measures
must be take to detect whether the output contacts loses its redundant
capabilities/prevent it altogether.
These terminals 22 and 23 close with the shared potential on terminal 24 of the cabin is located in a
door zone.
5.4.3 Plug X6: Relay contact – door zone display connection
The emergency power via a 12 V battery is optional and is only used for displaying the door zones.
If the voltage drops below 20 V, the PSU01 switches to a fault state, opens all relays and only the door
zone +/- 70 mm is emulated on terminals 20 and 21, to facilitate an emergency rescue.
This contact closes if the cabin is located in a door zone.
5.4.4 Plug X7: Door bypass
Terminals 26 and 27 are used to bypass the door contacts and are open or closed according to the
requests of the control.
An external safety circuit for bypassing doors is expressly forbidden.
5.4.5 Plug X8 (optional): Inspection
The inspection is to be wired so that, in normal operation, 24 VDC is applied at the inspection input
(port X8) and that this voltage drops in inspection mode. This allows the PSU01 to recognize whether
the elevator is in inspection mode or not.
In order to prevent capacitive couplings, the general guidelines of this chapter, as well as the mainte-
nance requirements (see below), must mandatorily be complied with.
EN - page 20 (R60953.0009 3)
6. Commissioning according to EN81-20
The requirements for commissioning the PSU01 for performing safety-relevant functions according to
EN81/20 or 50 are described below.
6.1 Requirement
To fulfil the safety functions, the PSU Evaluation Unit must be connected to the Ants LES01 position
system, which meets the requirements according to EN81-20.
The PSU Evaluation Unit may only be used in conjunction with the safe
position reading system Ants LES01.
If you have any further questions, please contact the manufacturer.
The following measures must be taken prior to commissioning.
Measure
Description
The hardware must be operated accor-
ding to specifications
The operating conditions are documented in the operating
instructions and must always be observed.
Installation of the PSU Evaluation
Unit in an earthed or double insulated
housing.
The PSU Evaluation Unit must be firmly mounted in the
cabinet or roof control box.
Correct installation and commissioning
of the Ants LES01
See the encoder operating instructions for this
(R60200.0009)
Correct integration of the door zones
The door zones must be integrated as described in chap-
ter 5.3. They can be used to detect the UCM zone for the
integration of an additional external UCM Evaluation Unit
(see point 2.1.7 Door zone relay).
Correct integration of the safety circuit
The safety circuit must be properly integrated at the
location of the limit switches and be bypassable by the
recovery operations.
Control recovery is forbidden in case of an active UCM
event and in inspection mode in the areas of the limit
switches.
Correctly integrated safety circuit
pickup
The safety circuit must be properly integrated at the loca-
tion of the door contacts (see 5.3).
Correctly integrated relay for tripping
the UCM actuator
The UCM trip unit must be correctly integrated according
to the actuator specifications.
Initial maintenance
All recurring maintenance steps must be performed during
the initial commissioning.
EN - page 21 (R60953.0009 3)
english
6.2 Overview of the parameterization
After installation, the PSU01 must be parameterised for the first time. This is performed with a
CANopen terminal or with a compatible control.
EN - page 22 (R60953.0009 3)
The following table shows the various states with respect to the safety circuit and to the door bypass
safety circuit.
Step
Description
Safety circuit
Door bypass
UCM
1
First commissioning
Open
Not possible
inactive
2
Touch top limit switch
Open
Not possible
inactive
3
Touch bottom limit switch
Open
Not possible
inactive
4
Set time-delayed limit switches
Closed
Not possible
inactive
4
Teach every stop
Closed
Not possible
inactive
5
Actuate stops (by moving
again to the stops)
Closed
Not possible
inactive
6
Normal operation
Closed
Possible
active
As soon as all stops have been actuated, the PSU01 switches to the normal operating mode. More
detailed information on the parameters can be found in the programming manual or in the manual of a
compatible control or of the separately available programming unit.
6.3 Protected area parameterization
As delivered, the protected area (reduced shaft head / shaft pit) is always active. This means that both
inspection limit switches (top and bottom) are initially enabled (also wiring is required).
The inspection limit switches can be enabled/disabled selectively in configuration mode (see parame-
terizing manual).
The possible options are described more in detail below:
Option
Description
Protected area
Limited to
0.6 m/s
Bypassing for
inspection
0
No inspection limit switches,
inspection not wired
None
No
Possible*
1
Inspection limit switches top
and bottom, inspection wired
Top and bottom
Yes
Not possible
2
Inspection limit switch only
top, inspection wired
Only top
Yes
Not possible
3
Inspection limit switch only
bottom, inspection wired
Only bottom
Yes
Not possible
4
No inspection limit switches,
but inspection wired
None
Yes
Not possible
*Possible, as PSU01 receives no information about the inspection mode.
EN - page 23 (R60953.0009 3)
english
The inspection limit switches are fixed at their position at a distance of
1.2 m from the top limit switch for the top inspection limit switch and
1.2 m from the bottom limit switch for the bottom inspection limit switch.
The positions of the inspection limit switches cannot be modified.
When the inspection is wired, the speed during inspection is limited to
0.6 l/s. If this speed is exceeded, the „overspeed“ function trips and the
safety circuit opens until the elevator has stopped.
6.4 Teaching the top limit switch with reduced shaft head
In the case of reduced shaft heads, where the top limit switch position cannot be reached on the car,
proceed as follows:
Position the elevator car exactly 1,500 mm underneath the required limit switch position. With a spe-
cial instruction (see parameterizing manual), the PSU01 saves the position temporarily as a tempo-
rary limit switch. E.g. if the installer is at position 10,000 mm, the top limit switch is assumed to be at
11,500 mm. It is not active yet, and the state does not change.
If the elevator stops within 15 minutes at (or above) this calculated position, this calculated position
(not the current position) is accepted as the top limit switch and the system switches automatically to
he next state (see parameterizing manual).
6.5 Time-delayed limit switch parameterization
At the beginning, both time-delayed limit switches are disabled until the teaching of the limit switch
positions.
As soon as the limit switches have been taught, the time-delayed limit
switches are identical with these, but a travel faster than 1 m/s is pre-
vented (by the opening of the safety circuit).
This state remains active until the time-delayed limit switches have
been explicitly taught in.
For detailed information on the configuration of the time-delayed limit switches, please refer to the
parameterizing manual.
EN - page 24 (R60953.0009 3)
7. During operation
The following chapter describes the different operating modes.
The following overview shows the relay states and the safety circuit status of the respective operating
modes:
Operating mode
Safety circuit
Door bypass
1
Teach-in mode (see chapter 4)
open/closed
open
2
Normal operation
- Door bypass inactive
- Door bypass active
closed
closed
open
closed
3
Error mode (locked mode)
open
open
7.1 Normal operation
In normal operation, the PSU01 evaluates the positions received and fulfills all safety functions.
7.1.1 Door bypass function
Door bypass is only active (activable) in the „Normal operation“ state.
The bypass will only become active for a speed lower than 0.8 m/s and only within the requested stop
(0.3 m/s for car level control).
If inspection limit switches are active, or if at least the inspection is
wired and the elevator is in inspection mode, bypass is inhibited.
The following applications are possible with the door bypass of the PSU01, which will be requested by
the control according to the required door bypass application (see parameterizing manual).
7.1.1.1 Door bypass for drive-in for early door opening
The door bypass for drive-in for early door opening can only be activated outside of the requested stop
or still during drive-in.
It has no effect during standstill at the corresponding stop.
The control must switch the active bypass off if it is not required. If,
after a previous standstill, the elevator leaves the door zone with
bypassed doors, this is detected as a UCM event.
EN - page 25 (R60953.0009 3)
english
7.1.1.2 Door bypass for car level control at a stop
The door bypass can only be activated within a zone at a speed lower than 0.3 m/s for elevator car
level control. The speed during car level control bypass is controlled at 0.3 m/s. Exceeding this speed
will be detected by the PSU01 as a UCM event.
The control must switch the active bypass off if it is not required. If,
after a previous standstill, the elevator leaves the door zone with
bypassed doors, this is detected as a UCM event.
7.1.1.3 Door bypass for fast start from a stop
Fast start bypass can only be activated/is only valid in a zone of ± 2 cm with respect to the flush
position of the selected station. It is de-activated automatically when leaving this zone and must not
necessarily be reset.
The control must make sure that the doors safety circuit is closed before leaving the reduced zone;
otherwise the elevator stops (because of the open door contacts safety circuit).
7.1.2 Protection mode (inspection)
If both inspection switches are disabled, the input signal is ignored.
Wiring the inspection / protection area is not necessary.
If the inspection is at least wired, the door bypass is inhibited during
inspection and the speed is limited to 0.6 m/s.
The control must represent suitably the state of the inspection limit
switches (actuated/or not).
The following features apply when an inspection limit switch is actuated.
Speed is limited to 0.6 m/s during inspection. If this speed is exceeded, the PSU01 triggers the „over-
speed“ function. This leads to the opening of the safety circuit until the standstill of the elevator.
If an elevator is in inspection mode and an inspection limit switch plus maximum 10 cm hysteresis is
overrun, the safety circuit opens and the info is sent to the control (see figure).
EN - page 26 (R60953.0009 3)
The control has then the responsibility to allow only travel instructions allowing to leave the inspection
limit switch. If such a travel is requested by the control, the PSU01 sends the corresponding instruction
(see parameterizing manual). The safety circuit closes again when the elevator stands still and upon
request by the control, as long as the elevator is in the hysteresis zone.
A „real“ leaving of the hysteresis zone or switching off the inspection mode re-activates this zone.
A repeated entering in this zone triggers the same process again (see above).
Overrunning the max. hysteresis zone of the inspection limit switch
(see figure above) always leads to the opening of the safety circuit,
which is no longer bypassed on request by the PSU01.
When an inspection limit switch is actuated, recovery (bypassing) is
forbidden and must be prevented by the circuitry.
7.1.3 UCM detection
The UCM detection of the PSU01 is enabled as soon as the elevator car stops in a door zone.
The PSU01 detects a UCM event in the following conditions:
• the car level control speed exceeds 0.3 m/s
• the elevator leaves the door zone with bypassed doors (e.g. due to a control fault)
A detected UCM event permanently opens the safety circuit. A braking
device compliant with EN81-20, 5.6.7 (redundant/diagnostic certified as
a drive brake) is a prerequisite for this.
If a UCM lock is active, recovery by the control is forbidden.
External UCM units can be connected in “parallel”. The redundant door zone relays (port X6) constan-
tly emit door zone information (comparable with fixed magnetic switches) to provide the information to
an external UCM unit (plants working e.g. by engaging).
Caution, since the UCM detection is permanently active in the PSU01,
in the case of an UCM event, the PSU01 will also trip, and not only the
external unit. Therefore both devices must be reset.
The redundant door zone relays (port X6) are exclusively intended
for an optional external UCM unit and may not be used for any other
elevator safety function.
EN - page 27 (R60953.0009 3)
english
7.1.4 Overspeed
In the case of overspeed, the PSU01 opens the safety circuit and therefore provides a pre-tripping with
respect to the speed limiter. An adjustable rated speed prevents travels exceeding 115 %, upwards as
well as downwards, by opening the safety circuit.
The rated speed of the elevator can be set in mm/s (see parameterizing manual).
As standard, this speed is set to 5 m/s and therefore ineffective.
The rated speed can be modified continuously during standstill.
This function is not part of the SIL3 certification and does not replace
the measures prescribed in EN81.
7.1.5 Relay test
A relay test is performed at least once a year. It starts during a standstill and opens all safety relays. A
connected compatible control receives the information that the PSU01 is currently performing the relay
test. Such control can trigger this test by resetting the PSU01 (see programming manual) at a moment
chosen by it, provided the interval between tests does not exceed one year. The twelve-month counter
starts over again after every self test.
7.2 Error mode
In case of an error, the PSU01 switches to the error mode (PSU01 lock), and the safety circuit and
door zone relays are immediately opened. The UCM relay opens with a slight delay (excepted in case
of an UCM event) to prevent an unnecessary catch. The reaction time, including the opening time of
the relays, is < 25 ms.
Depending on the severity of the error, the PSU01 switches immediately to lock mode or it memori-
zes this error. The errors are output and can be displayed by a compatible control or via a CANopen
terminal.
In the event of a PSU01 lock, an installer must read the error type on
a CANopen monitor or a compatible control and remedy it. This may
be an UCM event, but also a critical failure of the PSU Evaluation Unit
(e.g. relay failure) or of the Ants LES01 (Sensor Safe). It is the instal-
ler‘s responsibility to restart safely a locked plant.
The reaction to errors is described in chapter 7.3 - 7.6, resetting an error is described in chapter 7.6.
In any case, the error processing of the Ants LES01 (Sensor Safe) operating instructions is also to be
taken into consideration.
EN - page 28 (R60953.0009 3)
7.3 LED flashing pattern
The µP1 and µP2 LEDs flash as follows:
Normal mode
Flashing every second
Error mode
Quick flashing (5 times per second)
7.4 Communication
The PSU01 continuously transmits data, in the event of an error with priority to the error. The PSU01
allows visualizing certain system parameters. Safety-relevant data can only be read. More detailed
information on the parameters can be found in the programming manual.
7.5 Failures
In case of failures, proceed as follows:
1. Check the proper installation of the Ants LES01 (Sensor Safe).
2. Check the proper installation of the Position Supervisor Unit.
3. Check the proper integration of both systems.
4. Check the correctness of all connections.
Also take into consideration all instructions of the Ants LES01 operating instruction. In the event of
a PSU01 lock, an installer must read the error code on a CANopen monitor (see programing in-
structions) or a compatible control and remedy it. The following table shows an overview of possible
failures:
Failure
Error code
Measure
Ants LES01 sends no position
2xx (correspond to encoder
error: 1-17)
See Ants LES01 (Sensor Safe)
operating manual
Hardware error
3, 11, 16, 17
Replace the PSU01
Internal PSU01 diagnostic
error
4-7, 11, 16, 18
Replace the PSU01
Position value not plausible or
not within time
10, 12
Test bus lines for possible failures
Voltage drop
13
Check voltage supply, check power
supply unit load Emergency power
operation (see above) possible
Power failure
PSU01 restarts with a self test. No
measure required.
UCM module modified
14
PSU01 has reset to delivery
condition. Restore the UCM option
according to the basic configuration.
Reconfigure the PSU01. The UCM
option shall not be modified.
Error in the safety circuit
integration
15
Check whether the safety circuit has
been correctly integrated.
EN - page 29 (R60953.0009 3)
english
Ants LES01 in lock
1
Perform a standard-conforming
restoration of the elevator plant and
subsequently a reset (see below).
No sensor (Ants LES01)
found
30
Check the connection to the sensor
Ants LES01.
Relay test is being performed
101
Notification
An (automatic) reset to factory
settings is being performed
102
Notification
No communication possible
with PSU01
If the PSU01 cannot be reached via
CANopen, check first all network
parameters and wiring. If commu-
nication is still not possible, replace
the PSU01.
7.6 Resetting
7.6.1 Resetting an error
An error that switched the PSU01 to the locked state (fast flashing of both status LEDs) can be reset
as follows:
1. The plant is standing still.
2. Press the button at the PSU01 or request a reset at the compatible control.
3. Switch off the power supply of the PSU01 within 15 minutes.
4. Restore the power supply.
The PSU01 then performs a self test and switches back to normal mode, provided no error has been
detected.
In the event of a PSU01 lock, an installer must read the error type on a
CANopen monitor (see programming instructions) or a compatible con-
trol and remedy it. This may be an UCM event, but also a critical failure
of the PSU Evaluation Unit (e.g. relay failure) or of the Ants LES01. It is
the installer‘s responsibility to restart safely a locked plant.
All components must be in perfect operating condition. Please check
also in the Ants LES01 operating manual which and how errors are to
be remedied or processed.
If they cannot be remedied with the allowed measures described abo-
ve, the whole PSU01 must be replaced.
7.6.2 Resetting all stops
All stops can be erased. The limit switch positions remain unchanged. Resetting is possible using a
compatible control, the external programming unit or a CANopen terminal. To reset all stops, please
refer to the programming manual.
EN - page 30 (R60953.0009 3)
After the reset of the stops, the UCM function must be checked again
(incl. braking distance for overall system).
7.6.3 Resetting to factory setting
The device can be reset to the delivery condition. All parameters saved until now, such as the limit
switch positions, stop positions, door zone length, etc., are erased. Resetting is possible using a
compatible control, the external programming unit or a CANopen terminal. To reset to factory setting,
please refer to the programming manual.
A comprehensive acceptance test must be performed after resetting to
factory setting.
EN - page 31 (R60953.0009 3)
english
8. Checking the functions
8.1 Limit switch function
To check the functional ability of the limit switch emulation, carry out a limit switch travel with the con-
trol connected. To this purpose, consult the operating manual of the concerned control and proceed as
specified in the manual.
8.2 Inspection limit switch function
To check the functional ability of the inspection limit switch emulation, carry out an inspection limit
switch travel with the control connected. To this purpose, consult the operating manual of the concer-
ned control and proceed as specified in the manual.
8.3 Time-delayed limit switch function
To check the functional ability of the time-delayed limit switch function, carry out a time-delayed limit
switch travel with the control connected. To this purpose, consult the operating manual of the concer-
ned control and proceed as specified in the manual.
8.4 UCM function
To check the UCM function, carry out a UCM travel with the control connected. To this purpose, the
control must leave the door zone with the doors bypassed. To this purpose, consult the operating
manual of the concerned control and proceed as specified in the manual.
8.5 Door zone emulation function
While traveling at a speed slower than 0.8 m/s check whether the door zones switch.
To check the door zone emulation functions for an external UCM Evaluation Unit, proceed according
to the instructions of the control and of the UCM Evaluation Unit. To this purpose, consult the operating
manual of the concerned device that provides these functions and proceed as specified there.
8.6 Overspeed (optional)
To check the overspeed (provided the rated speed has been set in the PSU01), carry out an over-
speed travel with the control connected. To this purpose, consult the operating manual of the concer-
ned control and proceed as specified in the manual.
As soon as the speed of the elevator car exceeds the memorized normal speed by +15 %, PSU01
opens the safety circuit and the elevator stops.
EN - page 32 (R60953.0009 3)
9. Repairs, maintenance and disposal
The Ants LES01 basically require minimal maintenance. If a component is defective, the complete
PSU01 must be replaced.
The PSU01 performs an annual relay test and thus checks that the safety relay and other components
function correctly. This relay test can also be triggered by a compatible control (see programming
manual).
9.1 Replacing components
The PSU01 can also be replaced as an overall system (sensor and Evaluation Unit).
9.2 Maintenance
The maintenance must be performed at least once a year. The following must be checked:
1. Check the PSU01 for visible damage and remove any contamination.
2. Check the function according to 8. In addition, check whether the door zones still switch
(terminals 22-24) in compliance with all stops.
3. If the PSU01 must be wired wit the inspection, the following must be tested during normal elevator
plant operation. In case a check yields a negative result, it must be assumed there is capacitively
coupled interference in the inspection circuit. It must be eliminated by the customer. If the test still
yields a negative result, it must be assumed that there is a defective PSU01 component, which must
be replaced:
a. the SK indicator lamp on the board must light up in normal operation.
b. the SK indicator lamp on the board must be off in inspection mode.
4. The operating efficiency of the time-delayed limit switches must be checked.
5. For maintenance of the Ants LES01 (Sensor), refer to the operation manual (R60200.0009).
9.3 Traceability
We recommend ensuring the traceability of products that carry out functional safety system tasks. This
is critical for fast response times in the market.
9.4 Disposal
Position Supervisor Unit (PSU01) is designed to ensure that it has a minimal negative impact on
the environment. It does not emit any pollutants, does not contain any substances that are harmful
to the environment and only consumes very little energy during operation. Unusable or irreparable
devices as well as those which have reached the end of their product lifecycle must be disposed of in
accordance with the respective applicable waste disposal regulations for electrical waste. The plastic
housing can be disposed of as residual waste.
9.5 Order information and spare parts
All components can only be reordered as a complete product. Components cannot be replaced.
Please contact Kübler Group, Fritz Kübler GmbH for this.
EN - page 33 (R60953.0009 3)
english
9.6 Service addresse
Kübler Group
Fritz Kübler GmbH
Schubertstr. 47
78054 Villingen-Schwenningen
Germany
Phone +49 7720 3903-952
www.kuebler.com
[email protected]
R60953.0009 - Index 3
français
Instructions d'utilisation
PSU01 (Position Supervisor Unit avec Ants LES01)
CANopen
®
LIFT
© CiA
FR - page 2 (R60953.0009 3)
Editeur
Kübler Group, Fritz Kübler GmbH
Schubertstr. 47
78054 Villingen-Schwenningen
Allemagne
www.kuebler.com
Assistance applications
Téléphone +49 (0) 7720 3903-952
Télécopie +49 (0) 7720 21564
[email protected]
N° de document
R60953.0009 - Index 3
Nom du document
Instructions d'utilisation
PSU01 (Position Supervisor Unit (PSU) avec Ants LES01)
Langue
Français (FR) - La version originale est en langue allemande
Date d'édition
01/2019 - Index 3
Copyright
©2019, Kübler Group, Fritz Kübler GmbH
Mentions légales
L'ensemble du contenu de la présente notice est soumis aux droits d'utilisation et d'auteur du Groupe
Kübler, Fritz Kübler GmbH. Toute duplication, modification, utilisation ultérieure ou publication sur d'au-
tres média électroniques ou imprimés, ainsi que leur publication dans l'Internet, n'est permise qu'avec
l'autorisation écrite préalable de Fritz Kübler GmbH
FR - page 3 (R60953.0009 3)
français
Le sommaire
1.
Informations générales
5
1.1 Abréviations utilisées (FR)
5
1.2 Symboles / Avertissements et informations de sécurité utilisés (FR)
5
1.3 Groupe cible
6
1.4 Directives de sécurité
6
1.5 Personnel de montage et d'exploitation
6
1.6 Garantie et responsabilité
6
1.7 Utilisation conforme
6
1.8 Transport & livraison
7
1.9 Entreposage
7
1.10 Autres documents applicables
7
2.
Caractéristiques produit
8
2.1 Fonction de la PSU01
8
2.1.1 Emulation des fins de course
9
2.1.2 Emulation des fins de course d'inspection
9
2.1.3 Circuit de sécurité pour le contournement des portes
9
2.1.4 Mouvement incontrôlé de la cabine (UCM)
9
2.1.5 Commutateur de commande temporisé
10
2.1.6 Pré-déclenchement pour survitesse
10
2.1.7 Emulation de zone de porte
11
2.2 Caractéristiques spéciales
11
2.3 Etendue de la livraison de la PSU01
11
2.4 Exemple d'une plaquette signalétique
11
2.4.1 Unité d’exploitation / Position Supervisor Unit
11
2.4.2 Ants LES01
11
3.
Description technique
12
3.1 Unité de surveillance de position (unité d'évaluation)
12
3.2 Caractéristiques de sécurité
13
3.3 Ants LES01 (capteur)
13
4.
Installation mécanique
14
4.1 Unité d’exploitation / Position Supervisor Unit
14
4.2 Ants LES01 (capteur)
14
5.
Installation électrique
15
5.1 Remarques sur la CEM
15
5.2 Instructions générales
15
5.2.1 Normes de sécurité applicables
15
5.2.2 Conformité CE
16
5.3 Intégration électrique dans le système d'ascenseur
16
5.3.1 Présentation du raccordement de la PSU
17
5.3.2 Raccordement du Ants LES01
18
5.4 Raccordement du relais de sécurité
18
5.4.1 Connecteur X5 : Sortie du circuit de sécurité
18
5.4.2 Connecteur X6 : Sorties du relais de zone de porte
19
5.4.3 Connecteur X6 : Contact de relais – Raccordement affichage de zone de porte
19
FR - page 4 (R60953.0009 3)
5.4.4 Connecteur X7 : Contournement de porte
19
5.4.5 Connecteur X8 (option) : Inspection
19
6.
Mise en service selon EN81-20
20
6.1 Exigences
20
6.2 Présentation du paramétrage
21
6.3 Paramétrage de la zone protégée
22
6.4 Apprentissage du fin de course haut dans le cas d'une tête de cage raccourcie
23
6.5 Paramétrage des fins de course temporisés
23
7.
Pendant le fonctionnement
24
7.1 Fonctionnement normal.
24
7.1.1 Fonction de contournement de porte
24
7.1.1.1 Contournement de porte pour le "tir au but" pour l'ouverture de porte anticipée
24
7.1.1.2 Contournement de porte pour le nivellement de la cabine à un arrêt
25
7.1.1.3 Contournement de porte pour un départ rapide après un arrêt
25
7.1.2 Mode de protection (inspection)
25
7.1.3 Détection UCM
26
7.1.4 Survitesse
27
7.1.5 Test des relais
27
7.2 Mode d'erreur
27
7.3 Clignotement des LED
28
7.4 Communication
28
7.5 Défauts
28
7.6 Réinitialisation
29
7.6.1 Acquittement d'une erreur
29
7.6.2 Effacement de tous les points d'arrêt
30
7.6.3 Réinitialisation aux réglages d'usine
30
8.
Vérification des fonctions
31
8.1 Fonction de fin de course
31
8.2 Fonction de fin de course d'inspection
31
8.3 Fonction de fin de course temporisés
31
8.4 Fonction UCM
31
8.5 Fonction d'émulation de zone de porte
31
8.6 Survitesse (option)
31
9.
Réparation, maintenance et élimination
32
9.1 Remplacement de composants
32
9.2 Maintenance
32
9.3 Traçabilité
32
9.4 Elimination
32
9.5 Informations de commande et pièces de rechange
32
9.6 Adresse du service après-vente
33
FR - page 5 (R60953.0009 3)
français
1. Informations générales
Lisez attentivement ces instructions d’utilisation avant de travailler avec, de monter ou de mettre en
service l’unité d’exploitation sûre PSU. Ces instructions d’utilisation indiquent au personnel technique
du constructeur de la machine ou de l’exploitant de la machine les procédures sûres de montage, d’in-
stallation électrique et de mise en route, ainsi que l’utilisation de l’unité d’exploitation sûre PSU. Par
ailleurs, la planification et la mise en œuvre de dispositifs de protection comme l’unité d’exploitation
sûre PSU exigent des connaissances techniques qui ne sont pas communiquées par ce document.
Par principe, l’utilisation de l’unité d’exploitation sûre PSU nécessite le respect des exigences règle-
mentaires et légales.
1.1 Abréviations utilisées (FR)
PSU01
Système complet Ants LES01 + Unité d’exploitation PSU
Ants LES01
Linear Encoder Safe, SIL3
PSU
Unité d’exploitation / Position Supervisor Unit, SIL3
UCM
Unintended Car Movement
1.2 Symboles / Avertissements et informations de sécurité utilisés (FR)
Les informations particulièrement importantes de ce manuel sont identifiées comme suit :
Ce symbole, accompagné du mot « Danger », indique un risque
immédiat pour la vie et la santé des personnes.
Le non-respect de cet avertissement entraînera la mort ou des blessu-
res graves.
Ce symbole, accompagné du mot « Avertissement », indique un risque
potentiel pour la vie et la santé des personnes.
Le non-respect de cet avertissement peut entraîner la mort ou des
blessures graves.
Ce symbole, accompagné du mot « Attention », indique un risque
potentiel pour la vie et la santé des personnes.
Le non-respect de cet avertissement peut entraîner des blessures
légères ou mineures.
Conseils, recommandations et informations utiles pour un fonctionne-
ment efficace et sans problèmes.
FR - page 6 (R60953.0009 3)
1.3 Groupe cible
La PSU01 doit être installée, mise en service, testée, entretenue et utilisée uniquement par du person-
nel qualifié. Le terme personnel qualifié se réfère à des personnes
• qui ont une formation technique appropriée et
• qui ont été formées à l'utilisation de l'unité par l'exploitant et
• qui ont été informées des directives de sécurité en vigueur et
• qui ont accès à ces instructions d'utilisation.
1.4 Directives de sécurité
Lisez les instructions d'utilisation avant de mettre l'appareil en service. Conformez-vous aux instruc-
tions d'installation. Ne mettez l'appareil en service qu'après avoir lu et compris les instructions d'utili-
sation. La sélection des appareils et leur intégration dans le système de commande nécessitent une
connaissance qualifiée des lois et des exigences normatives applicables de la part du constructeur de
la machine.
Les consignes de sécurité et les avertissements constituent une partie importante des instructions
d'utilisation et doivent être respectés.
1.5 Personnel de montage et d'exploitation
L'exploitant est tenu de prendre des mesures de sécurité appropriées. Seul du personnel ayant la con-
naissance des règlementations de base de prévention des accidents et de la sécurité et de la santé au
travail et qui a lu et compris les informations de sécurité de ces instructions d'utilisation est autorisé à
réaliser l'installation et la mise en service.
1.6 Garantie et responsabilité
Le droit à la garantie et à la responsabilité est annulé si le Ants LES01 (Sensor Safe) n'est pas utilisé
de manière conforme à sa destination, si un dommage peut être attribué au non-respect des instruc-
tions d'utilisation, ou si le personnel d'installation ou d'exploitation n'est pas correctement qualifié ou
formé.
Le non-respect de ces instructions entraîne l'annulation de tout droit à la garantie et de tout éventuel
recours en responsabilité. Toutes les règlementations de prévention des accidents applicables aux
ascenseurs doivent être prises en compte. Afin d'éviter tout dommage dû à une manipulation inap-
propriée de tensions et de courants électriques, il faut se conformer à toutes les règlementations appli-
cables (également locales), notamment pour les mesures de protection et la mise à la terre correcte.
1.7 Utilisation conforme
L'unité de surveillance de position a été développée exclusivement pour l'utilisation conforme décrite
ici :
FR - page 7 (R60953.0009 3)
français
La PSU01 s’utilise pour l’évaluation sûre de la position, pour l’im-
plémentation de fonctions de fins de course, de fins de course
d’inspection, de fins de course temporisés, pour la surveillance des
mouvements incontrôlés de la cabine (UCM) et pour le contournement
sûr du circuit de sécurité pour l’ouverture de porte anticipée/le nivelle-
ment des systèmes d’ascenseur selon EN81-20. Elle forme une unité
de système conjointement avec le Ants LES01.
Toute utilisation non conforme peut entraîner des situations dangereu-
ses.
L’unité d’exploitation PSU ne peut s’utiliser qu’avec le Ants LES01.
Toutes les informations de ces instructions d’utilisation sont à respecter
strictement. Les instructions d’utilisation du Ants LES01 sont jointes
à ce produit. Il y est fait référence explicitement ici en tant que partie
intégrante du produit.
1.8 Transport & livraison
Vérifier immédiatement la présence de dommages dus au transport à la réception de la livraison.
Signaler immédiatement tout dommage au transporteur. Des dommages peuvent interdire la mise en
service de l'unité de surveillance de position. Si vous ne montez pas immédiatement l'unité de surveil-
lance de position, entreposer l'appareil en un endroit sec protégé de la poussière - idéalement dans
son emballage de transport.
1.9 Entreposage
L'appareil doit être entreposé dans les conditions suivantes :
• Au sec et protégé de la poussière
• Eviter les vibrations mécaniques
• Ne pas l'entreposer à l'air libre
• Ne pas dépasser les limites de température et d'humidité (voir les caractéristiques techniques)
1.10 Autres documents applicables
Toutes les spécifications techniques se trouvent sur les fiches techniques correspondantes de la
PSU01 et du Ants LES01. Elles indiquent les valeurs caractéristiques mécaniques et électriques
de l'unité de surveillance de position. Les instructions d'utilisation séparées (R60200.0009) du Ants
LES01 doivent être respectées pour sa mise en service.
Il existe également des instructions de programmation nécessaires pour le paramétrage de la PSU01.
Celle-ci n'est généralement destinée qu'aux fabricants des commandes pour leur permettre de rendre
que leur système de commande d'ascenseur compatible avec la PSU01. Elles sont remises à jour en
permanence et peuvent être téléchargées depuis notre site Internet. Le paramétrage peut s'effectuer
aussi à l'aide de n'importe quel terminal CANopen. Les fichiers EDS nécessaires peuvent également
être téléchargées depuis notre site Internet.
FR - page 8 (R60953.0009 3)
2. Caractéristiques produit
L’unité d’exploitation PSU est une unité sûre d’exploitation de la position pour l’implémentation de
fonctions de fins de course, de fins de course d’inspection, de fins de course temporisés, pour la
surveillance des mouvements incontrôlés de la cabine (UCM) et pour le contournement sûr du circuit
de sécurité dans la zone des portes pour l’ouverture de porte anticipée/le nivellement des système
d’ascenseur selon EN81-20.
Le système PSU01 complet se compose de deux appareils, le Ants LES01 (Linear Encoder Safe) et
l’unité d’exploitation PSU (Position Supervisor Unit) décrite ici. La PSU01 est reliée via un bus CAN
libre à une commande externe compatible, un terminal CANopen ou un appareil de programmation
externe, utilisé pour le paramétrage des fonctions de sécurité. La procédure de paramétrage ne fait
pas partie de ces instructions d’utilisation. A cet effet, se reporter au manuel de programmation séparé
ou au manuel de la commande compatible.
La PSU01 reçoit les paramètres correspondants ou les instructions de réinitialisation de l’un de ces
appareils via le bus CAN libre (port X3) et émet vers ces appareils externes comme les commandes
d’ascenseur des informations sur la position, l’état, etc. L’émission pure de la position est aussi sup-
portée en option via SSI.
L’unité d’exploitation PSU et le Ants LES01 sont certifiés comme un système complet et ne peuvent
fonctionner qu’ensemble. Ils sont identifiés d’usine par un Set.ID. Ants LES01 fournit en toute sécurité
les positions absolues de la cabine de l’ascenseur via un second bus CAN privé et les transmet à
l’unité d’exploitation PSU (port X2). Ants LES01 est en outre certifié et disponible comme produit
autonome.
Le Ants LES01, faisant partie de la PSU01, doit être mis en service
correctement conformément à ses instructions d'utilisation.
2.1 Fonction de la PSU01
La PSU01 répond aux exigences suivantes pour les systèmes d'ascenseur de dernière génération :
• Emulation des fins de course
• Emulation des fins de course d'inspection pour une tête/fosse de cage raccourcie
• Circuit de sécurité pour le contournement des contacts de porte
• Mouvement incontrôlé de la cabine (UCM)
• Emulation des fins de course temporisés
• Pré-déclenchement pour survitesse
• Emulation de la zone de porte pour transmission de l'information à une unité UCM externe en
option.
La PSU01 répond aux exigences de EN81 grâce à :
• L'apprentissage unique de tous les points d'arrêt (réalisé lors de la mise en service)
• Des relais de sécurité pour ouvrir le circuit de sécurité
• Des relais de sécurité pour le contournement des portes
• La lecture de l'entrée d'inspection
FR - page 9 (R60953.0009 3)
français
2.1.1 Emulation des fins de course
Les fins de course d'arrêt d'urgence sont simulés selon EN81-20 Fonction de sécurité 5.12.2.
Les nouvelles stations doivent être éloignées d'au moins 2 mm des positions des fins de course défi-
nies par apprentissage.
2.1.2 Emulation des fins de course d'inspection
L'unité de surveillance de position (PSU01) permet la surveillance de la zone protégée dans le cas
d'une tête/fosse de cage raccourcie selon EN81-21, 5.5.3.4 or 5.7.3.4 (fin de course d'inspection).
Cette fonction est représentée par un fin de course virtuel supplémentaire positionné à une distance
fixe de 1,2 m du fin de course. Un fin de course est prévu pour les amortisseurs hauts raccourcis et
un pour les amortisseurs bas raccourcis. Ces nouveaux fins de course sont appelés “fins de course
d'inspection”.
La position des fins de course d'inspection est fixée à 1,2 m des
fins de course et ne peut pas être déplacée.
Les fins de course d'inspection sont en option et peuvent être désac-
tivés lors de la première configuration.
Lorsque le fin de course d'inspection inférieur est activé, il est possible
que la cabine, lorsqu'elle est commandée par le monteur depuis le toit
de la cabine, s'arrêtedans la zone du fin de course d'inspection, bien
que l'arrêt le plus bas n'ait pas été atteint (1,2 m du fin de course).
2.1.3 Circuit de sécurité pour le contournement des portes
La PSU01 fournit un circuit de sécurité pour le contournement des contacts de porte selon
EN81-20 : 5.12.1.4.
La PSU01 contourne, sur demande, les contacts de porte d'un arrêt déterminé
• pour l'ouverture de porte anticipée
• pour le nivellement de la cabine et
• pour le départ rapide
Un circuit extérieur pour le contournement des portes est explicitement
interdit.
2.1.4 Mouvement incontrôlé de la cabine (UCM)
La PSU01 assure la protection contre les mouvements incontrôlés de la cabine selon EN81-20 Fon-
ction de sécurité 5.6.7. La zone de porte définie (voir 2.1.2) est utilisée comme zone UCM. Ceci ne
se rapporte qu'à la longueur de la zone. Les zones UCM sont toujours actives et ne peuvent pas être
commutées de manière sélective.
L'émulation de la zone de porte (port X6) permet l'utilisation d'une unité UCM externe en option.
FR - page 10 (R60953.0009 3)
Comme la détection UCM est active en permanence dans la PSU01,
celle-ci se déclenche également dans le cas d'un événement UCM, en
plus de l'unité externe. Il faut donc réinitialiser les deux appareils.
La commande de l'élément de freinage du dispositif de protection est
incluse dans la PSU01, mais l'élément de freinage du dispositif de
protection lui-même ne fait pas partie de ce circuit de sécurité ni de
cette description.Il doit être fourni et mis en place dans l'installation
d'ascenseur. Les règlementationsapplicables à cet élément doivent
être respectées.
Ce dispositif de protection doit faire appel à des éléments de freinage
testés conformément aux dispositions de EN81-20, 5.6.7, qui doivent
être en mesure d'immobiliser l'ascenseur dans la distance et le délai
prescrits.
Un nivellement de la cabine à une vitesse supérieure à 0,3 m/s est
toujours détecté par la PSU01 comme un événement UCM, indépen-
damment de la zone UCM.
2.1.5 Commutateur de commande temporisé
La PSU01 offre la fonction de circuit de commande temporisé pour amortisseurs raccourcis selon
EN81-20 : 5.12.1.3.
Cette fonction est représentée par un fin de course virtuel supplémentaire dépendant de la vitesse,
qui peut être positionné librement une fois (à l'aide de CANopen). Ces nouveaux fins de course sont
appelés "fins de course temporisés" dans la suite ce de manuel.
Un fin de course temporisé est prévu pour les amortisseurs hauts raccourcis et un pour les amortis-
seurs bas raccourcis.
La vitesse de déclenchement est fixée à 1 m/s et ne peut pas être
modifiée.
Si nécessaire, la position du fin de course temporisé doit
modifiée.
2.1.6 Pré-déclenchement pour survitesse
La PSU01 offre la fonction de pré-déclenchement pour survitesse (EN81-20: 5.6.2.2.1) ou la fonction
de survitesse en mouvement ascendant (EN81-20: 5.6.6) et ouvre le circuit de sécurité dans l'un de
ces cas.
Cette fonction ne fait pas partie de la certification SIL3 et ne remplace
pas les mesures prescrites par EN81.
FR - page 11 (R60953.0009 3)
français
2.1.7 Emulation de zone de porte
La PSU01 fournit l'émulation de zone de porte au moyen de deux canaux redondants. Elle simule
ainsi les aimants de porte, qui ne sont plus nécessaires lors du montage.
En standard, toutes les zones de porte sont simulées par l'unité d'évaluation dès que l'ascenseur se
déplace à une vitesse inférieure à 0,8 m/s.
En standard, la zone de porte est préréglée à ± 20 mm du palier. Elle peut être modifi ée dans la plage
de ± 5-200 mm. Des informations plus détaillées sur les paramètres peuvent être trouvées dans le
manuel de programmation.
Un maximum de 200 paliers est possible. Les paliers doivent être espacés d'au moins 20 mm. Si
des zones de porte voisines se chevauchent, elles seront raccourcies de sorte à avoir un espace sans
zone d'au moins 10 mm, ou elles seront fusionnées en une zone commune.
Les relais de zone de porte redondants (port X6) sont destinés exclu-
sivement à une unité UCM externe en option et ne peuvent pas être
utilisés pour une autre fonction de sécurité de l'ascenseur.
2.2 Caractéristiques spéciales
• Les fi ns de course mécaniques ne sont plus nécessaires
• il ne faut plus d'aimants supplémentaires pour l'ouverture de porte anticipée
• Installation aisée sur profi lé chapeau dans la commande sur le toit ou dans les boîtiers de commande.
2.3 Etendue de la livraison de la PSU01
• Unité d’exploitation / Position Supervisor Unit dans boîtier pour profi lé chapeau.
• Ants LES01 (y compris instructions d'utilisation séparées du LES01)
2.4 Exemple d'une plaquette signalétique
Une étiquette est fi xée sur l'unité de surveillance de position. Elle comporte les informations suivantes :
• référence de commande
• SetID (capteur + unité d'évaluation)
• désignation du type / numéro de série
• numéro du certifi cat TÜV
• alimentation électrique
• marque CE
• référence aux instructions d'utilisation (adresse)
2.4.1 Unité d’exploitation / Position Supervisor Unit
2
<
24 VDC PELV XXA
Fritz Kübler GmbH
Type: PSU01
SetID: 00070-11/2018 S-No: XX3333XX
8.PSU01.xxxx.xxxx
TÜV-A-AT-X-XX-XXXX-EUES
www.kuebler.com
0408
Schubertstraße 47
D-78054 Villingen-Schwenningen
2.4.2 Ants LES01
2
WH
BN
GN
YL
GND
+ 24
VDC
CAN
High
CAN
Low
Schubertstraße 47
D-78054 Villingen-Schwenningen
10-30 VDC
XXA ±10%
Fritz Kübler GmbH
Type: PSU01 (Ants LES01)
SetID: 00070-11/2018 S-No: XX1234XX
8.PSU01.xxxx.xxxx
TÜV-A-AT-X-XX-XXXX-XXXX
www.kuebler.com
0408
FR - page 12 (R60953.0009 3)
3. Description technique
Les caractéristiques techniques de la PSU01 (unité d'évaluation + capteur) sont décrites ci-dessous.
3.1 Unité de surveillance de position (unité d'évaluation)
Caractéristique
Valeur
Normes de référence
EN81-20, EN81-50, EN81-21
Matière du boîtier
Plastique
Dimensions du boîtier
70 mm (H) x 95 mm (L) x 30 mm (l)
Interfaces
2 x CAN (interne et public) , 1 x SSI (en option)
Protocole
Interne : propriétaire, public : CANopen, SSI : 2 x 25 bits
avec PFB, code grey, MSB en premier
Type de raccordement
picoMAX® eCOM 3.5, 7.5 (connexion et chapitre 5)
Température de fonctionnement
ambiante
De -5°C à +55°C
Température de stockage
De -10°C à +70°C
Humidité
< 90% (sans condensation)
Pression d'air
800 - 1013 hPa (jusqu'à 2000 m au-dessus du niveau de
la mer)
Vie utile
20 ans
Indice de protection
IP00 (min. IP20 si monté dans une armoire électrique)
Tension d’alimentation
24 VDC basse tension PELV
Puissance
< 10 watts
Distance maximale au codeur
100 m (bus CAN interne)
Temps de désactivation / temps de
réponse du système
< 25 ms (y compris temps de commutation du relais)
Nombre d'étages maximal
200
Toutes les lignes et câbles pendentifs doivent avoir une isolation
double ou être protégés mécaniquement selon EN81-20 5.10.6. Il faut
notamment veiller à ce qu'ils soient posés sans courts-circuits.
FR - page 13 (R60953.0009 3)
français
Caractéristiques des raccordements de l'unité d'évaluation :
Borne
Domaine fonctionnel
Câble
X1
Alimentation en tension
24 VDC
0,75 mm²
X2
CAN1 - BUS interne vers
le codeur
Raccordement direct du codeur
Ants LES01 (Sensor Safe)
Raccordement direct sans rallonge
ou 0,75 mm² (max. 100 m) par
câbles pendentifs, paire torsadée
avec blindage
X3
CAN2 - CAN OPEN
Raccordement direct de l'unité
de programmation ou de la
commande compatible. Confor-
me bus CAN.
Raccordement direct 0,75 mm²
(max.100 m) par câbles penden-
tifs, paire torsadée avec blindage
X4
SSI (option)
Conforme SSI
0,75 mm² (max.100 m) par câbles
pendentifs, paire torsadée avec
blindage
X5
Intégration du circuit de
sécurité
48 ... 230 VAC max. 2 A,
24 VDC max. 1 A
0,75 mm²
X6
Emulation de zone de porte
24 VAC, 24 VDC, max. 10 mA
0,75 mm²
X7
Circuit de déclenchement
contournement de porte
48 ... 230 VAC max. 2 A,
24 VDC max. 1 A
0,75 mm²
X8
Interrogation d’inspection
(option)
48 ... 230 VAC, 24 VDC,
max. 2 A
0.75 mm2, maximum 170 m (si
les 170 m sont dépassés, il faut
prendre en compte séparément le
couplage capacitif d'interférences
(voir 5.2.2))
3.2 Caractéristiques de sécurité
Caractéristiques de sécurité
Normes de base
EN81-20, EN81-50, EN81-21, EN62061, EN61508-1-7,
EN60664-1, EN60950-1, EN61784-3
Classification
SIL3, mode continu
Structure du système
2 canaux
Valeur PFHd
< 1 x 10-7
3.3 Ants LES01 (capteur)
Pour la description technique, voir les instructions d'utilisation R60200.0009 jointes.
FR - page 14 (R60953.0009 3)
4. Installation mécanique
4.1 Unité d’exploitation / Position Supervisor Unit
L’unité d’exploitation est fournie dans un boîtier plastique prévu pour un montage sur profilé chapeau.
L’unité d’exploitation doit être montée dans une armoire électrique (IP20) selon EN81-20.
Les options suivantes sont disponibles pour le montage de l’unité d’exploitation
1. Montage de l’unité d’exploitation sur le toit de la cabine.
Le capteur est relié directement à l’unité d’exploitation.
2. Montage de l’unité d’exploitation dans le coffret de commande.
Le capteur est relié à l’unité d’exploitation via le câble pendentif. La longueur maximale de la ligne
de bus de 100 m doit être respectée.
Dans les deux cas, il faut un profilé chapeau. L’unité d’exploitation PSU peut être simplement montée
sur le profilé chapeau par son boîtier.
4.2 Ants LES01 (capteur)
Des détails sur le montage
• de la bande
• du kit de montage
• du capteur
pour cette application sont donnés dans les instructions d'utilisation R60200.0009 (à partir du chapitre
3.2).
Les consignes de sécurité et les avertissements doivent être pris en compte.
FR - page 15 (R60953.0009 3)
français
5. Installation électrique
Avant de connecter/déconnecter la ligne de signal, toujours débrancher la tension d'alimentation.
Pour le raccordement du Ants LES01, respecter les instructions d'utilisation correspondantes. Toutes
les lignes et câbles pendentifs doivent avoir une isolation double ou être protégés mécaniquement
selon EN81-20 5.10.6.
Le personnel d'exploitation et de montage doit veiller à ce que l'appa-
reil ne soit pas endommagé par une charge / décharge électrostatique
lors de son montage / remplacement. Eviter tout contact direct avec le
circuit imprimé / les composants électroniques ou prendre les mesures
de protection appropriées.
5.1 Remarques sur la CEM
• Pour les lignes du bus, utiliser exclusivement des câbles blindés avec des paires torsadées pour
l'unité de surveillance de position.
• Pour éviter les boucles de terre, le blindage n'est relié qu'en un endroit (la PSU01 est déjà mise à la
terre par la PELV) au potentiel (terre de protection).
• Veiller à bien fixer les blindages des câbles.
• Veiller à un routage correct des câbles lors du câblage du système.
Débrancher le câblage par groupes de câbles comme les lignes
d'alimentation des moteurs/d'alimentation électrique et les lignes de
signal/données/circuit de sécurité.
• Faire passer les lignes de signal et de données le plus près possible de surfaces mises à la terre
(éléments du châssis, rails métalliques, parois des armoires) et ne pas les poser parallèles aux
câbles des moteurs et d'alimentation électrique.
• Raccorder tous les équipements avec une basse impédance au système de terre/de conducteur de
protection.
5.2 Instructions générales
5.2.1 Normes de sécurité applicables
• Avant la mise en service, tous les conducteurs nécessaires des câbles doivent être raccordés
conformément à la fiche technique. Le Ants LES01 est déjà préconfectionné, il suffit de le raccorder
au port X2. Isoler correctement toutes les extrémités des signaux de sortie inutilisés pour éviter les
courts-circuits.
• Prendre en compte la tension de fonctionnement correcte et le courant de sortie maximal
admissible (voir la fiche technique).
• Utiliser une source d'alimentation en tension conforme à PELV.
FR - page 16 (R60953.0009 3)
5.2.2 Conformité CE
Pour être conforme aux normes CE, l'installation doit être réalisée de manière conforme à la CEM.
• Utiliser pour les lignes de commande des câbles blindés sur toute leur longueur.
• Les lignes de bus (port X2, X3, X4) doivent être posées séparément des lignes présentant un
niveau d’interférences élevé.
• Le circuit de sécurité doit être installé conformément à la norme, aussi exempt que possible de tout
couplage capacitif d’interférences, séparé des lignes présentant un niveau d’interférences élevé.
• Si le circuit d’inspection présente trop d’interférences couplées capacitivement (voir les instructions
de maintenance), celles-ci doivent être éliminées de manière appropriée par le client au moyen de
résistances de puissance ou de condensateurs.
• Ne raccorder aucun consommateur présentant un niveau d’interférences élevé, comme des
variateurs de fréquence, des électrovannes, des contacteurs, etc.) à la tension d’alimentation de
l’électronique (unité d’exploitation PSU, Ants LES01, commande). Dans le cas contraire, fournir un
filtre de tension approprié.
5.3 Intégration électrique dans le système d'ascenseur
Ce chapitre décrit la PSU01 dans le système complet et explique son intégration électrique dans le
système d'ascenseur.
L’illustration ci-dessous montre l’intégration correcte de l’unité d’exploitation PSU, avec le Ants LES01,
dans le système d’ascenseur.
main contactor
activation
main contactors
landing door contacts
car door contact
LIFTCONTROL
PELV
supply
24VDC
emergency
power supply
12VDC
safety chain
ground
doorzone information
(battery-buffered)
doorzone
bridging
safety chain
doorzone
(redundant)
doorzone
supply input
safety chain
absolute position
emergency stop area
CAN1
CAN2
SSI
position/SSI (optional)
position-data CAN-OPEN
lock contacts
Ants LES01 (Sensor)
CE0408TÜV-A-AT XXX
Position Supervisor Unit
CE0408TÜV-A-AT XXX
1
GND
X1
2
24V
3
12V
24VDC
AC
AC
12VDC
22
ZONE2
X6
23
ZONE3
24
COM2/3
20
ZONE1
21
COM1
19
SC2
X5
18
SC1
28
X8
29
26
X7
27
4
24V
X2
5
GND
6
CAN1L
7
CAN1H
8
GND
9
24V
X3
10
CAN2L
11
CAN2H
12
GND
13
DATA1
X4
14
DATA2
15
CLK1
16
CLK2
17
GND
F2A
F2A
inspection
Wiring Diagram PSU01
Ants LES01 is connected to Kübler Position Supervisor Unit
via CAN interface.
FR - page 17 (R60953.0009 3)
français
5.3.1 Présentation du raccordement de la PSU
L’unité d’exploitation PSU est munie de 8 connecteurs présentés en détail dans les chapitres suivants.
Raccordement
Borne
N°
Description
Alimentation
X1
1
2
3
GND
+24 VDC (basse tension selon PELV)
+12 VDC alimentation par batterie pour l'affi-
chage des zones de porte en fonctionnement
de secours
CAN1 - interne
Ants LES01
X2
4
5
6
7
8
+24 VDC
GND
CAN1 LOW
CAN1 HIGH
GND
CAN2 - externe
CANopen
X3
9
10
11
12
+24 VDC
CAN2 LOW
CAN2 HIGH
GND
Communication SSI
(option)
X4
13
14
15
16
17
DATA1
DATA2
CLK1
CLK2
GND
Sortie du circuit de sécurité
X5
18
19
SC1
SC2
FR - page 18 (R60953.0009 3)
Emulation de zone de porte
X6
20
21
22
23
24
ZONE1 (pour alimentation de secours)
COM1 (pour alimentation de secours)
ZONE2 aimant de zone de porte 1
ZONE3 aimant de zone de porte 2
COM2/3 potentiel commun
Intégration contournement
de porte
X7
26
27
Entrée circuit de sécurité
Entrée circuit de sécurité
Inspection
X8
(option)
28
29
Entrée d'inspection 24 VDC
Sortie d'inspection GND
5.3.2 Raccordement du Ants LES01
Le capteur a 4 entrées/sorties déjà correctement reliées à un connecteur picoMAX® eCOM lors de la
fabrication, pour un raccordement direct à l’unité d’exploitation PSU.
Si le raccordement passe par un câble pendentif, le câblage doit être réalisé comme suit :
Raccordement
PSU01
N°
Description
Couleur du câble du codeur
X2
4
+24 VDC
brun
5
GND
blanc
6
CAN1 LOW
jaune
7
CAN1 HIGH
vert
8
SLD
blindage
La distance maximale à l'unité d'évaluation ne doit pas dépasser 100 m. Ces 100 m doivent être
réalisés avec un câble bus blindé à paires torsadées de 0,5 mm². Le passage par le câble pendentif
est possible.
En général, lors de l'installation d'un bus, le technicien doit toujours veiller à ne pas porter de charge
électrostatique pour éviter d'endommager l'appareil lors de son installation.
5.4 Raccordement du relais de sécurité
Les mesures électriques à prendre pour l'intégration des circuits de sécurité sont décrites ci-dessous.
5.4.1 Connecteur X5 : Sortie du circuit de sécurité
Ces bornes 18 et 19 sont toujours fermées en fonctionnement ; elles s'ouvrent dans les zones des fins
de course, des fins de course temporisés, des fins de course d'inspection, en mode d'erreur (bande ou
PSU01 défectueux) en en cas d'UCM.
En fonctionnement CA, le circuit de sécurité doit être protégé par un
fusible de 2A du côté de la commande. En fonctionnement CC, il doit
être protégé par un fusible de 1 A.
FR - page 19 (R60953.0009 3)
français
5.4.2 Connecteur X6 : Sorties du relais de zone de porte
Ces bornes 22, 23, 24 s'utilisent comme entrées pour une unité d'évaluation UCM externe. Elles
peuvent s'utiliser pour l'évaluation de la zone UCM, car elles peuvent être considérées comme des
commutateurs magnétiques classiques, qu'elles remplacent.
Ces contacts sont de conception redondante, mais sans auto-test, et
ne peuvent s'utiliser que comme information de cage pour un circuit de
sécurité selon EN81-20 5.6.7. Le circuit de sécurité correspondant doit
être en mesure de détecter un dysfonctionnement des contacts. Des
mesures appropriées doivent permettre de détecter/d'éviter la perte de
redondance des contacts de sortie.
Ces bornes 22 et 23 se ferment avec le potentiel commun de la borne 24 lorsque la cabine se trouve
dans une zone de porte.
5.4.3 Connecteur X6 : Contact de relais – Raccordement affichage de zone de porte
L'alimentation de secours par une batterie 12 V est en option et n'est utilisée que que pour l'affichage
des zones de porte. Si la tension chute au-dessous de 20 V, la PSU01 passe dans un état de défaut
et ouvre tous les relais ; uniquement la zone de porte +/- 70 mm est émulée sur les bornes 20 et 21
pour faciliter une libération des personnes.Ce contact se ferme lorsque la cabine se trouve dans une
zone de porte.
5.4.4 Connecteur X7 : Contournement de porte
Les bornes 26 et 27 sont utilisées pour contourner les contacts de porte et s'ouvrent ou se ferment en
fonction des requêtes de la commande.
Un circuit extérieur pour le contournement des portes est explicitement
interdit.
5.4.5 Connecteur X8 (option) : Inspection
L'inspection doit être câblée de sorte que, en fonctionnement normal, 24 VDC soient appliqués à l'en-
trée d'inspection (port X8) et que cette tension chute en mode d'inspection. Ceci permet à la PSU01
de détecter si l'ascenseur est en mode d'inspection ou non.
Afin d'éviter les couplages capacitifs, il convient de se conformer impérativement aux directives
générales de ce chapitre, ainsi qu'aux exigences de maintenance (voir ci-dessous).
FR - page 20 (R60953.0009 3)
6. Mise en service selon EN81-20
Les exigences pour la mise en service de la PSU01 pour la réalisation de fonctions importantes pour
la sécurité selon EN81/20 ou 50 sont décrites ci-dessous.
6.1 Exigences
Afin d’assurer les fonctions de sécurité, l’unité d’exploitation PSU doit être raccordée au système de
positionnement Ants LES01 conforme aux exigences de EN81-20.
L’unité d’exploitation PSU ne peut être utilisée qu’avec le système de
positionnement absolu sûr Ants LES01.
Pour toute autre question, merci de contacter la fabricant.
Les mesures suivantes doivent être prises avant la mise en service.
Mesure
Description
Le matériel doit être utilisé selon les
spécifications
Les conditions d'utilisation sont indiquées dans les in-
structions d'utilisation et doivent toujours être respectées.
Monter l’unité d’exploitation PSU dans
un coffret mis à la terre ou à double
isolation
L’unité d’exploitation PSU doit être montée de manière
fixe dans l’armoire électrique ou dans le boîtier de com-
mande situé sur le toit.
Montage et mise en service corrects
du Ants LES01
Voir les instructions d'utilisation du codeur à ce sujet
(R60200.0009)
Intégration correcte des zones de porte
Les zones de porte doivent être intégrées comme décrit
au chapitre 5.3. Elles peuvent être utilisées pour détecter
les zones UCM pour l'intégration d'une unité d'évaluation
UCM externe supplémentaire (voir par. 2.1.7 Relais de
zone de porte).
Intégration correcte du circuit de
sécurité
Le circuit de sécurité doit être intégré correctement à
l'emplacement des fins de course pour être contournable
par les opérations de rétablissement.
Le rétablissement de la commande est interdit si un
événement UCM est en cours et en mode d'inspection
dans la zone des fins de course d'inspection.
Intégration correcte du contournement
des portes
Le circuit de sécurité doit être intégré correctement
à l'emplacement des contacts de porte (voir 5.3).
Intégration correcte des relais pour le
déclenchement de l'actionneur UCM.
L'unité de déclenchement UCM doit être intégrée cor-
rectement conformément aux spécifications de l'action-
neur.
Maintenance initiale
Toutes les opérations de maintenance récurrentes doivent
être réalisées lors de la mise en service initiale.
FR - page 21 (R60953.0009 3)
français
6.2 Présentation du paramétrage
Après le montage, il faut réaliser le paramétrage initial de la PSU01. Cette opération s'effectue au
moyen d'un terminal CANopen ou d'une commande compatible.
FR - page 22 (R60953.0009 3)
Le tableau ci-dessous représente les différents états du circuit de sécurité et du circuit de sécurité
de contournement des portes.
Etape
Description
Circuit de
sécurité
Contournement
de porte
UCM
1
Première mise en service
Ouvert
Impossible
inactif
2
Actionnement du fin de course
haut
Ouvert
Impossible
inactif
3
Actionnement du fin de course
bas
Ouvert
Impossible
inactif
4
Réglage des fins de course
temporisés
Fermé
Impossible
inactif
4
Apprentissage de chaque
point d'arrêt
Fermé
Impossible
inactif
5
Actionner les points d'arrêt (en
retournant à chaque point)
Fermé
Impossible
inactif
6
Fonctionnement normal.
Fermé
Possible
actif
Dès que tous les points d'arrêt ont été actionnés, la PSU01 passe en mode de fonctionnement normal.
Vous trouverez davantage d'informations sur les paramètres dans le manuel de programmation ou
dans le manuel d'une commande compatible ou de l'unité de programmation disponible séparément.
6.3 Paramétrage de la zone protégée
La zone protégée (tête / fosse de cage raccourcie) est toujours active à la livraison. Ceci signifie que
les deux fins de course d'inspection (haut et bas) sont activés initialement (le câblage est également
nécessaire).
Les fins de course d'inspection peuvent être activés/désactivés de manière sélective en mode de
configuration (voir le manuel de paramétrage).
Les options possibles sont décrites plus en détail ci-dessous :
Option
Description
Zone protégée
Limité à
0,6 m/s
Contournement
pour l'inspection
0
Pas de fins de course
d'inspection, inspection pas
câblée
Aucune
Non
Possible*
1
Fins de course d'inspection
haut et bas, inspection câblée
Haut et bas
Oui
Impossible
2
Fins de course d'inspection
haut seulement, inspection
câblée
Haut seulement
Oui
Impossible
FR - page 23 (R60953.0009 3)
français
3
Fins de course d'inspection
bas seulement, inspection
câblée
Bas seulement
Oui
Impossible
4
Pas de fins de course d'in-
spection, mais inspection
câblée
Aucune
Oui
Impossible
*Possible, car la PSU01 ne reçoit aucune information sur le mode d'inspection.
Les fins de course d'inspection ont une position fixe à une distance de
1,2 m du fin de course haut pour le fin de course d'inspection haut et
de 1,2 m du fin de course bas pour le fin de course d'inspection bas.
Les positions des fins de course d'inspection ne peuvent pas être
modifiées.
Lorsque l'inspection est câblée, la vitesse pendant l'inspection est
limitée à 0,6 m/s. Si cette vitesse est dépassée, la fonction "survitesse"
se déclenche et le circuit de sécurité s'ouvre jusqu'à l'arrêt de l'ascen-
seur.
6.4 Apprentissage du fin de course haut dans le cas d'une tête de cage raccourcie
Dans le cas d'une tête de cage raccourcie, où la position du fin de course haut ne peut pas être attein-
te lorsque le technicien se trouve sur le toit de la cabine, procéder comme suit :
Positionner la cabine exactement à 1 500 mm au-dessous de la position du fin de course. Une instruc-
tion spéciale (voir le manuel de paramétrage) permet à la PSU01 de mémoriser temporairement cette
position comme un fin de course temporaire. P. ex. si le monteur se trouve à la position 10 000 mm,
le fin de course haut sera supposé se trouver à 11 500 mm. Il n'est pas actif pour l'instant, et l'état ne
change pas.
Si l'ascenseur s'arrête dans les 15 minutes à (ou au-dessus de) cette position calculée, cette posi-
tion calculée (et pas la position courante) est prise en compte comme fin de course supérieur et le
système passe automatiquement dans l'état suivant (voir le manuel de paramétrage).
6.5 Paramétrage des fins de course temporisés
Au début, les deux fins de course temporisés sont désactivés, jusqu'à l'apprentissage des positions
des fins de course.
Une fois que les fins de course ont été définis par apprentissage, les
fins de course temporisés sont identiques à ceux-ci, mais un dépla-
cement supérieur à 1 m/s est interdit (par l'ouverture du circuit de
sécurité).
Cet état reste actif jusqu'à ce que les fins de course temporisés aient
été explicitement définis par apprentissage.
Pour des informations plus détaillées sur la configuration des fins de course temporisés, voir le ma-
nuel de paramétrage.
FR - page 24 (R60953.0009 3)
7. Pendant le fonctionnement
Ce chapitre décrit les différents modes opératoires.
Le tableau ci-dessous montre les états des relais et du circuit de sécurité pour les différents modes
opératoires.
Mode opératoire
Circuit de sécurité
Contournement de
porte
1
Mode Apprentissage (voir chapitre
4)
ouvert/fermé
ouvert
2
Fonctionnement normal.
- Contournement des portes inactif
- Contournement des portes actif
fermé
fermé
ouvert
fermé
3
More Erreur (mode bloqué)
ouvert
ouvert
7.1 Fonctionnement normal.
En fonctionnement normal, la PSU01 évalue les positions reçues et réalise toutes les fonctions de
sécurité.
7.1.1 Fonction de contournement de porte
Le contournement de porte n'est actif (activable) que dans l'état "fonctionnement normal".
Le contournement ne s'active que pour une vitesse inférieure à 0,8 m/s et pour le point d'arrêt deman-
dé (0,3 m/s pour le nivellement).
Si des fins de course d'inspection sont actifs, ou si l'inspection est au
moins câblée et si l'ascenseur est en mode d'inspection, le contourne-
ment est inhibé.
Les applications suivantes sont possibles avec le contournement des portes de la PSU01, qui seront
demandées par la commande en fonction de l'application de contournement des portes souhaitée
(voir le manuel de paramétrage).
7.1.1.1 Contournement de porte pour le "tir au but" pour l'ouverture de porte anticipée
Le contournement de porte pour le "tir au but" pour l'ouverture de porte anticipée ne peut s'activer que
hors du point d'arrêt demandé ou encore pendant le "tir au but".
Il est sans effet pendant l'immobilisation au point d'arrêt correspondant.
FR - page 25 (R60953.0009 3)
français
La commande doit désactiver le contournement lorsqu'il n'est pas
nécessaire. Si, après une immobilisation, l'ascenseur quitte la zone
de porte avec le contournement des portes activé, ceci est détecté
comme un événement UCM.
7.1.1.2 Contournement de porte pour le nivellement de la cabine à un arrêt
Le contournement ne peut être activé que dans une zone à une vitesse inférieure à 0,3 m/s pour
le nivellement de la cabine. La vitesse lors du nivellement de la cabine est contrôlée à 0,3 m/s. Un
dépassement de cette vitesse est détecté par la PSU01 comme un événement UCM.
La commande doit désactiver le contournement lorsqu'il n'est pas
nécessaire. Si, après une immobilisation, l'ascenseur quitte la zone
de porte avec le contournement des portes activé, ceci est détecté
comme un événement UCM.
7.1.1.3 Contournement de porte pour un départ rapide après un arrêt
Le contournement pour le départ rapide ne peut être activé/n'est valide que dans une zone de ± 2
cm par rapport à la position de niveau à la station sélectionnée. Il se désactive automatiquement en
quittant la zone et ne nécessite pas impérativement de réinitialisation.
La commande doit veiller à ce que le circuit de sécurité des portes est fermé avant de quitter la zone
réduite ; dans le cas contraire, l'ascenseur s'immobilise (par le circuit de sécurité ouvert des contacts
de porte).
7.1.2 Mode de protection (inspection)
Si les deux fins de course d'inspection sont désactivés, le signal d'en-
trée est ignoré. Le câblage de la zone d'inspection / de protection n'est
pas nécessaire.
Si l'inspection est au moins câblée, le contournement de porte est
inhibé pendant l'inspection et la vitesse est limitée à 0,6 m/s.
La commande doit représenter de manière appropriée l'état des fins de
course d'inspection (actionnés ou non).
Les caractéristiques suivantes s'appliquent lorsqu'un fin de course d'inspection est actionné.
La vitesse est limitée à 0,6 m/s pendant l'inspection. Si cette vitesse est dépassée, la PSU01 déclen-
che la fonction "survitesse". Le circuit de sécurité s'ouvre alors jusqu'à l'immobilisation de l'ascenseur.
Si l'ascenseur est en mode d'inspection et si un fin de course d'inspection plus un maximum de 10 cm
pour l'hystérèse est dépassé, le circuit de sécurité s'ouvre et l'information est envoyée à la commande
(voir l'illustration)
FR - page 26 (R60953.0009 3)
La commande ne doit alors autoriser que les instructions de déplacement permettant de quitter le fin
de course d'inspection. Si la commande demande un tel déplacement, le PSU01 émet l'instruction
correspondante (voir le manuel de paramétrage). Le circuit de sécurité se referme lorsque l'ascenseur
est immobile et sur demande de la commande, tant qu'il se trouve dans la zone d'hystérèse.
Le "vrai" départ de la zone d'hystérèse ou la désactivation du mode d'inspection réactive cette zone.
Une nouvelle entrée dans cette zone redéclenche le même processus (voir ci-dessus).
Le dépassement de la zone d'hystérèse max. du fin de course d'in-
spection (voir l'illustration ci-dessus) entraîne toujours l'ouverture du
circuit de sécurité, qui n'est plus contourné sur demande par la PSU01.
Si un fin de course d'inspection est actionné, le rétablissement (con-
tournement) est interdit et doit être empêché par le câblage du circuit.
7.1.3 Détection UCM
La détection UCM de la PSU01 est activée dès que la cabine s'immobilise dans une zone de porte.
La PSU01 détecte un événement UCM dans les conditions suivantes :
• la vitesse de nivellement de la cabine dépasse 0,3 m/s
• l'ascenseur quitte la zone de porte avec les portes contournées (p. ex. du fait d'une défaillance de
la commande)
Un événement UCM détecté ouvre le circuit de sécurité de manière
permanente. Un dispositif de freinage conforme à EN81-20, 5.6.7
(redondant/diagnostic comme frein d'entraînement) est indispensable
pour cela.
Si un blocage UCM est actif, le rétablissement par la commande est
interdit.
Des unités UCM externes peuvent âtre connectées "en parallèle". Les relais de zone de porte redon-
dants (port X6) émettent en permanence des informations sur les zones de porte (de manière com-
FR - page 27 (R60953.0009 3)
français
parable à des commutateurs magnétiques fixes) pour fournir l'information à une unité UCM externe
(installations fonctionnant p. ex. par engagement).
Attention, la détection UCM de la PSU01 est active en permanence.
Dans le cas d'un événement UCM, la PSU01 se déclenchera égale-
ment, en plus de l'unité externe. Il faudra donc réinitialiser les deux
appareils.
Les relais de zone de porte redondants (port X6) sont destinés exclu-
sivement à une unité UCM externe en option et ne peuvent pas être
utilisés pour une autre fonction de sécurité de l'ascenseur.
7.1.4 Survitesse
En cas de survitesse, la PSU01 ouvre le circuit de sécurité, fournissant ainsi un pré-déclenchement
par rapport au limiteur de vitesse. Une vitesse nominale réglable empêche les déplacements à une
vitesse supérieure à 115 % en montée comme en descente en ouvrant le circuit de sécurité.
La vitesse nominale de l'ascenseur peut être réglée en mm/s (voir le manuel de paramétrage).
En standard, cette vitesse est réglée à 5 m/s et est donc sans effet.
La vitesse nominale peut être modifiée en continu lorsque l'ascenseur est immobile.
Cette fonction ne fait pas partie de la certification SIL3 et ne remplace
pas les mesures prescrites par EN81.
7.1.5 Test des relais
Un test des relais est réalisé au moins une fois par an. Il démarre lorsque l'ascenseur est immobile et
il ouvre tous les relais de sécurité. Une commande compatible raccordée reçoit l'information que la
PSU01 est en train d'effectuer le test des relais. Cette commande peut déclencher ce test en réini-
tialisant la PSU01 (voir le manuel de programmation) à un moment défini par elle, à la condition que
l'intervalle entre deux tests ne dépasse pas un an. Le compteur annuel recommence à zéro après
chaque auto-test.
7.2 Mode d'erreur
En cas d'erreur, la PSU01 passe en mode d'erreur (blocage PSU01) et le circuit de sécurité et les
relais de zone de porte s'ouvrent immédiatement. Le relais UCM s'ouvre avec un léger retard (sauf
dans le cas d'un événement UCM) pour éviter un déclenchement inutile du parachute. Le temps de
réaction, y compris le temps d'ouverture des relais, est < 25 ms.
Selon la gravité de l'erreur, la PSU01 passe immédiatement en mode bloqué, ou elle mémorise cette
erreur. Les erreurs sont émises et peuvent être affichées sur une commande compatible ou via un
terminal CANopen.
FR - page 28 (R60953.0009 3)
Dans le cas d’un blocage PSU01, un monteur doit lire le type d’erreur
sur un afficheur CANopen ou sur une commande compatible, et l’élimi-
ner. Il peut s’agir d’un événement UCM, mais aussi d’une défaillance
critique de l’unité d’exploitation PSU (p. ex. défaillance du relais) ou du
Ants LES01 (Sensor Safe). Il est de la responsabilité du monteur de
remettre en service une installation bloquée en toute sécurité.
La manière de réagir aux erreurs est décrite aux chapitres 7.3 - 7.6, l'acquittement d'une erreur est
décrite au chapitre 7.6. Il faut dans tous les cas prendre en compte également le traitement des er-
reurs des instructions d'utilisation du Ants LES01 (Sensor Safe).
7.3 Clignotement des LED
Les LED µP1 et µP2 clignotent comme suit :
Mode normal
Clignotement toutes les secondes
Mode d'erreur
Clignotement rapide (5 fois par seconde)
7.4 Communication
La PSU01 transmet continuellement des données, en cas d'erreur avec priorité à l'erreur. La PSU01
permet la visualisation de certains paramètres du système. Les données importantes pour la sécurité
sont en lecture seule. Des informations plus détaillées sur les paramètres peuvent être trouvées dans
le manuel de programmation.
7.5 Défauts
En cas de défauts, procéder comme suit:
1. Vérifier l'installation correcte du Ants LES01 (Sensor Safe).
2. Vérifier l'installation correcte de l'unité de surveillance de position.
3. Vérifier l'intégration correcte des deux systèmes.
4. S'assurer que tous les raccordements soient corrects.
Prendre également en compte toutes les instructions des instructions d'utilisation du Ants LES01.
Dans le cas d'un blocage PSU01, un monteur doit lire le code d'erreur sur un afficheur CANopen
(voir les instructions de programmation) ou sur une commande compatible, et l'éliminer. Le tableau
ci-dessous présente les défauts possibles:
Défaillance
Code d'erreur
Mesure
Ants LES01 n'envoie pas de
position
2xx (correspond à l'erreur
codeur : 1-17)
Voir les instructions d'utilisation
Ants LES01 (Sensor Safe)
Erreur matériel
3, 11, 16, 17
Remplacer la PSU01
Erreur de diagnostic interne
PSU01
4-7, 11, 16, 18
Remplacer la PSU01
Valeur de position non plausi-
ble ou non dans les délais
10, 12
Rechercher un possible défaut des
lignes du bus
FR - page 29 (R60953.0009 3)
français
Chute de tension
13
Vérifier l'alimentation en tension,
vérifier la charge sur le bloc d'ali-
mentation. Alimentation de secours
(voir ci-dessus) possible.
Panne de courant
La PSU01 redémarre avec un
auto-test. Aucune mesure n’est
nécessaire.
Module UCM modifié
14
La PSU01 s'est réinitialisée à son
état de livraison. Rétablir l'option
UCM selon la configuration de base.
Reconfigurer la PSU01. Il est inter-
dit de modifier l'option UCM.
Erreur dans l'intégration du
circuit de sécurité.
15
S'assurer que le circuit de sécurité a
été correctement intégré.
Ants LES01 bloqué
1
Remettre l'installation d'ascenseur
en état conformément aux normes,
puis effectuer une réinitialisation
(voir ci-dessous).
Aucun capteur (Ants LES01)
trouvé
30
Vérifier la liaison avec le capteur
Ants LES01.
Test des relais en cours
101
Notification
Exécution d'une réinitialisation
(automatique) aux réglages
d'usine
102
Notification
Aucune communication possi-
ble avec la PSU01
Si la PSU01 ne peut pas être at-
teinte via CANopen, vérifier d'abord
tous les paramètres réseau et le
câblage. Si la communication n'est
toujours pas possible, remplacer la
PSU01.
7.6 Réinitialisation
7.6.1 Acquittement d'une erreur
Une erreur qui a bloqué la PSU01 (clignotement rapide des deux LED d'état) peut s'acquitter comme
suit :
1. L'installation est à l'arrêt.
2. Presser le bouton sur la PSU01 ou demander un réinitialisation à la commande compatible.
3. Couper l'alimentation électrique de la PSU01 dans les 15 minutes.
4. Rétablir l'alimentation électrique.
La PSU01 réalise alors un auto-test et retourne dans le mode normal, à la condition qu'aucune erreur
n'ait été détectée.
FR - page 30 (R60953.0009 3)
Dans le cas d’un blocage PSU01, un monteur doit lire le type d’erreur
sur un afficheur CANopen (voir les instructions de programmation)
ou sur une commande compatible, et l’éliminer. Il peut s’agir d’un
événement UCM, mais aussi d’une défaillance critique de l’unité d’ex-
ploitation PSU (p. ex. défaillance du relais) ou du Ants LES01. Il est
de la responsabilité du monteur de remettre en service une installation
bloquée en toute sécurité.
Tous les composants doivent être en parfait état de fonctionnement.
Voir également dans les instructions d’utilisation du Ants LES01 com-
ment quelles erreurs doivent être éliminées ou traitées.
Si les mesures autorisées décrites ci-dessus ne permettent pas de les
éliminer, il faut remplacer la PSU01 en intégralité.
7.6.2 Effacement de tous les points d'arrêt
Il est possible d'effacer tous les points d'arrêts. Les positions des fins de course restent inchangées.
Cet effacement peut s'effectuer à l'aide d'une commande compatible, de l'unité de programmation
externe ou d'un terminal CANopen. Pour effacer tous les points d'arrêt, se reporter au manuel de
programmation.
Après l'effacement des points d'arrêt, il faut revérifier la fonction UCM
(y compris la distance de freinage pour le système complet).
7.6.3 Réinitialisation aux réglages d'usine
L'appareil peut être réinitialisé à son état à la livraison. Toue les paramètres mémorisés jusque-là
comme les positions des fins de course, les positions des points d'arrêt, la longueur de zone de porte,
etc., sont effacés. Cet effacement peut s'effectuer à l'aide d'une commande compatible, de l'unité de
programmation externe ou d'un terminal CANopen. Pour rétablir les réglages d'usine, se reporter au
manuel de programmation.
Un essai de réception complet doit être réalisé après la réinitialisation
aux réglages d'usine.
FR - page 31 (R60953.0009 3)
français
8. Vérification des fonctions
8.1 Fonction de fin de course
Pour vérifier la fonctionnalité de l'émulation des fins de course, effectuer une course de contrôle des
fins de course à l'aide de la commande connectée. Pour cela, se reporter au manuel d'utilisation de la
commande et procéder selon les indications du manuel.
8.2 Fonction de fin de course d'inspection
Pour vérifier la fonctionnalité de l'émulation des fins de course d'inspection, effectuer une course de
contrôle des fins de course d'inspection à l'aide de la commande connectée. Pour cela, se reporter au
manuel d'utilisation de la commande et procéder selon les indications du manuel.
8.3 Fonction de fin de course temporisés
Pour vérifier la fonctionnalité de l'émulation des fins de course temporisés, effectuer une course de
contrôle des fins de course temporisés à l'aide de la commande connectée. Pour cela, se reporter au
manuel d'utilisation de la commande et procéder selon les indications du manuel.
8.4 Fonction UCM
Pour vérifier la fonction UCM, effectuer une course de contrôle UCM à l'aide de la commande con-
nectée. Pour cela, la commande doit quitter la zone de porte avec les portes contournées. Pour cela,
se reporter au manuel d'utilisation de la commande et procéder selon les indications du manuel.
8.5 Fonction d'émulation de zone de porte
Vérifier si les zones de porte commutent lors d'un déplacement à une vitesse inférieure à 0,8 m/s.
Pour vérifier les fonctions d'émulation de zone de porte pour une unité d'évaluation UCM externe,
procéder selon les instructions de la commande et de l'unité d'évaluation UCM. Pour cela, se reporter
au manuel d'utilisation de l'appareil concerné fournissant ces fonctions et procéder selon les indica-
tions du manuel.
8.6 Survitesse (option)
Pour vérifier la survitesse (si la vitesse nominale a été réglée dans la PSU01), effectuer une course
en survitesse à l'aide de la commande connectée. Pour cela, se reporter au manuel d'utilisation de la
commande et procéder selon les indications du manuel.
Dès que la vitesse de la cabine dépasse la vitesse normale mémorisée de +15 %, la PSU01 ouvre le
circuit de sécurité et l'ascenseur s'immobilise.
FR - page 32 (R60953.0009 3)
9. Réparation, maintenance et élimination
Le Ants LES01 (Sensor Safe) exige en général une maintenance minimale. Si un composant est
défectueux, il faut remplacer la PSU01 en intégralité.
La PSU01 réalise un test de relais annuel, vérifiant ainsi le bon fonctionnement du relais de sécurité et
d'autres composants. Ce test de relais peut aussi être déclenché par une commande compatible (voir
le manuel de programmation).
9.1 Remplacement de composants
La PSU01 ne peut être remplacée qu'en entier (capteur et unité d'évaluation).
9.2 Maintenance
La maintenance doit être réalisée au moins une fois par an. Les point suivants sont à vérifier :
1. Rechercher les dommages visibles sur la PSU01 et la nettoyer.
2. Vérifier le fonctionnement comme décrit au chapitre 8. Vérifier également si les zones de porte
(commutent bien bornes 22-24) pour tous les points d'arrêt.
3. Si la PSU01 est câblée avec l’inspection, les points suivants doivent être contrôlés en
fonctionnement normal de l’installation d’ascenseur. Si un contrôle est négatif, il faut soupçonner un
couplage capacitif d’interférences. Celui-ci doit être éliminé par le client. Si le contrôle est toujours
négatif, il faut soupçonner une défaillance d’un composant de la PSU01, qui doit alors être rempla-
cée.
a. le voyant SK de la carte doit être allumé en fonctionnement normal.
a. le voyant SK de la carte doit être éteint en mode d'inspection.
4. La fonctionnalité des fins de course temporisés doit être contrôlée.
5. Pour la maintenance du Ants LES01 (capteur), se reporter aux instructions d'utilisation
(R60200.0009).
9.3 Traçabilité
Nous recommandons d'assurer la traçabilité des produits assurant des tâches de sécurité fonctionnel-
le. Ce point est déterminant pour une réaction rapide sur le marché.
9.4 Elimination
L'unité de surveillance de la position (PSU01) est conçue pour avoir un impact minimal sur l'environ-
nement. Elle n'émet pas de polluants, ne contient aucune substance nocive pour l'environnement et
son fonctionnement ne consomme que très peu d'énergie. Les appareils inutilisables ou irréparables,
ainsi que ceux ayant atteint la fin de leur durée de vie, doivent être éliminés conformément aux règle-
mentations nationales applicables concernant l'élimination des déchets électroniques. Le boîtier en
plastique peut être éliminé comme déchet résiduel.
9.5 Informations de commande et pièces de rechange
L'ensemble des éléments ne peut être commandé que sous la forme d'un produit complet. Les
composants ne peuvent pas être remplacés.
Contacter le Groupe Kübler, Fritz Kübler GmbH, à cet effet.