SLM50 suspended rising sections for the maintenance of electrical function

to DIN 4102 Part 12

© 2021 OBO Bettermann Holding GmbH & Co. KG

SLM50 suspended rising sections for the maintenance of electrical function Mounting instructions

3 | EN

SLM50 suspended vertical ladders with maintenance of electrical function Table of contents Table of contents 1 About these instructions 5 1.1 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Relevance of these instructions . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3 Types of warning information . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4 Basic standards and regulations . . . . . . . . . . . . . . . . . . . . . . . . 5 1.5 Applicable documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 Correct use 6 3 Safety 6 3.1 General safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.2 Personal protective equipment . . . . . . . . . . . . . . . . . . . . . . . . . 6 4 Necessary tools 7 5 System description 7 5.1 System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 5.1.1 Mounting variant 1: Direct mounting with head plate . . . . . . . . . . . . . . . . . . . 9 5.1.2 Mounting variant 2: Direct mounting with bracket . . . . . . . . . . . . . . . . . . . . . 9 5.1.3 Mounting variant 3: Mounting on transverse profile with head plate . . . . . . . . . . . . 9 5.1.4 Mounting variant 4: Mounting on lengthwise profile with head plate . . . . . . . . . . . 9 5.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 6 Mounting 10 6.1 Preparations for mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 6.2 Mounting vertical ladders up to a max. storey height of 3.5 m . . . . . . . . . 11 6.2.1 Mounting the ladder rails with head plates . . . . . . . . . . . . . . . . . . . . . . . 11 6.2.2 Mounting the ladder rails with a mounting bracket . . . . . . . . . . . . . . . . . . . 13 6.2.3 Mounting the ladder rails with transverse profiles . . . . . . . . . . . . . . . . . . . . 15 6.2.4 Mounting the ladder rails with lengthwise profiles . . . . . . . . . . . . . . . . . . . . 18 6.3 Mounting vertical ladders up to a max. storey height of 7.0 m . . . . . . . . .21 6.3.1 Mounting the ladder rails with head plates . . . . . . . . . . . . . . . . . . . . . . . 21 6.3.2 Mounting the ladder rails with transverse profiles . . . . . . . . . . . . . . . . . . . . 23 6.3.3 Mounting the ladder rails with lengthwise profiles . . . . . . . . . . . . . . . . . . . . 26 6.4 Mounting ladder rungs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 6.5 Mounting U support connectors . . . . . . . . . . . . . . . . . . . . . . . . .30 6.6 Fastening cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 6.7 Attaching the identification plate . . . . . . . . . . . . . . . . . . . . . . . .31 7 Additional required measures 32 7.1 Closing ceiling openings with insulation . . . . . . . . . . . . . . . . . . . .32 7.2 Mounting the strain relief . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 8 Retrofitting 34 9 Checking and maintaining the system 34 10 Dismantling the system 34 11 Disposing of the system 34 12 Technical data 35

5 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function About these instructions 1 About these instructions 1 1 Target group These instructions are intended for specialists and/or instructed technical personnel (e.g. engineers, architects, heads of construction, and mount- ing and installation engineers) who have had fire protection training and are charged with the planning or installation of suspended vertical lad- ders for the maintenance of electrical function. 1 2 Relevance of these instructions These instructions are based on the standards valid at the time of compil- ation (02/2021). Follow these instructions to ensure correct and safe use. Any images are intended merely as examples. Mounting results may look different. In these instructions, cables and lines are referred to simply as cables. Add the mounting instructions for construction acceptance after mount- ing to the construction file. 1 3 Types of warning information Type of risk! Shows a risky situation. If the safety instruction is not observed, then serious or fatal injuries may occur. Type of risk! Shows a risky situation. If the safety instruction is not observed, then medium or minor injuries may occur. Note! Indicates important information or assistance. 1 4 Basic standards and regulations – Standard support structure to DIN 4102 Part 12 1 5 Applicable documents – Surveyor's report no. GS 3.2/17-436-4-r1 (MFPA Leipzig) for standard support structure according to DIN 4102 Part 12 for cable routing on suspended rising sections – Surveyor's report no. GA-2020/044 (IBB) for standard support struc- ture according to DIN 4102 Part 12 for cable routing on suspended rising sections – General construction test certificates of the cable manufacturers Installation mechanical expertise WARNING CAUTION

6 | EN

OBO Bettermann Correct use 2 Correct use The rising section standard support structure, type SLM50C40F, is suit- able for suspended mounting under the ceiling and is used for vertical support and routing of cables for the maintenance of electrical function (E30–E90). The following mounting parameters must be maintained: – Suspension height max. 3.5 or 7 m – Width of the vertical cable ladder max. 600 mm – Cable load per vertical ladder max. 20 kg/m – Cable bundling, heavy current cables, max. quantity 3, max. diameter 25 mm – Cable bundling, installation cables, quantity not limited, total cable weight max. 3.0 kg/m 3 Safety 3 1 General safety information Observe the following general safety information: – All the appropriate regulations and technical regulations of other units, in particular those for electrical engineering, must be complied with. – Risk of cutting from plate edges. – The rising section should be included in the protection measures and/ or the equipotential bonding. – The inclusion in the equipotential bonding of the overall system must be performed by specialist personnel. 3 2 Personal protective equipment List of personal protective equipment to be used: Use hand protection Wear safety shoes Wear eye protection Wear head protection

7 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Necessary tools 4 Necessary tools List of required tools: – Angle grinder – Drill – Linear laser; spirit level – Wrench set – Ladder – Roller scaffolding or work platform 5 System description The SML50C40F.. vertical ladders, with a max. width of 600 mm, can be used as standard support structures in the mounting variants, according to the surveyors' reports, as suspended rising sections for the mainten- ance of electrical function (E30–E90). The suspended mounting of the vertical ladder can be performed regard- less of the structure or type and of the distance to the wall. For this, the vertical ladders are mounted flush to solid ceiling structures. Depending on the mounting version, the maximum storey height may not exceed 3.5 m or 7.0 m. Fig 1: Overview, mounting variants No Mounting variant Suitable for storey heights ≤ 3 5 m > 3 5 m – ≤ 7 0 m Direct ceiling mounting with head plates Direct ceiling mounting with mounting angles — Mounting in a direct run below the ceiling opening with transverse profiles Mounting in a direct run below the ceiling opening with lengthwise profiles Tab 1: Overview, mounting variants

8 | EN

OBO Bettermann System description 5 1 System overview Fig 2: 2 1 5 6 3 4 8 11 10 9 7 Overview of system components 1 SLM50 C... F vertical ladder 2 KUS 5 NOK head plate 3 GMS 3 VW 90 mounting bracket 4 KUS 5 head plate 5 US7 U support 6 M12 threaded rod 7 M12 anchor, fire protection-tested (e.g. bolt tie BZ12-15-35/110) 8 M12 truss-head bolt (with washer and nut) 9 M10 truss-head bolt (with washer and nut) 10 M12 hexagonal nut 11 M12 washer Note! The SML50 C... F vertical ladder 1 is required for all mounting variants and is 3 m long. The quantity of vertical ladders required per storey is dependent on the appropriate storey height. For storey heights > 3 m, 2 VUS 5 U support connectors are required for each additional vertical ladder.

9 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function System description 5 1 1 Mounting variant 1: Direct mounting with head plate No Designation Quantity/storey at ≤ 3 5 m > 3 5 m – ≤ 7 0 m 2 KUS 5 NOK head plate 4 4 9 M10 truss-head bolt 2 4 7 M12 anchor 4 4 Tab 2: System components, variant 1 5 1 2 Mounting variant 2: Direct mounting with bracket No Designation Quantity/storey at ≤ 3 5 m — 3 GMS 3 VW 90 mounting bracket 4 — 9 M10 truss-head bolt 2 — 7 M12 anchor 4 — Tab 3: System components, variant 2 5 1 3 Mounting variant 3: Mounting on transverse profile with head plate No Designation Quantity/storey at ≤ 3 5 m > 3 5 m – ≤ 7 0 m 2 KUS 5 NOK head plate 6 6 5 US7 U support 3 / 2* 3 / 2* 9 M10 truss-head bolt 2 4 7 M12 anchor 6 6 8 M12 truss-head bolt 4 4 6 M12 threaded rod 2 4 10 M12 hexagonal nut 8 16 11 M12 washer 6 12 Tab 4: System components, variant 3 5 1 4 Mounting variant 4: Mounting on lengthwise profile with head plate No Designation Quantity/storey at ≤ 3 5 m > 3 5 m – ≤ 7 0 m 2 KUS 5 NOK head plate — 6 4 Head plate KUS 5 6 — 5 US7 U support 6 / 4* 12 / 8* 9 M10 truss-head bolt 2 4 7 M12 anchor 12 24 8 M12 truss-head bolt 4 8 6 M12 threaded rod 2 4 10 M12 hexagonal nut 8 16 11 M12 washer 6 12 Tab 5: System components, variant 4 * If suspended vertical ladders are installed across multiple storeys, then fewer U supports are required for the installation from the 2nd storey.

10 | EN

OBO Bettermann Mounting 5 2 Accessories Designation Figure Function U support connector VUS 5 Connect 2 vertical ladders at a storey height > 3 m. Clamp clip 2056U M Cable fastening on the suspended vertical ladder. KS-E identification plate Identification of the cable system according to DIN 4102-12 Tab 6: Accessories 6 Mounting The SLM50 vertical ladder is supplied unmounted. With all mounting vari- ants, the ladder rails are first mounted to the ceiling fastening and then the ladder rungs for cable fastening inserted. Risk of injury! The size and weight of the components can cause injuries. Do not mount suspended vertical ladders on your own and use roller scaffolding or a raised platform or mounting lift. Wear personal protective equipment. 6 1 Preparations for mounting Before mounting, the ladder rails must be cut according to the storey height. Note! At a storey height of 3–6 m, 2 U support connectors are required. At a storey height of 6–7 m, 4 U support connectors are required. Along the length of the ladder rails, reckon with a gap of 13 mm per pair of connect- ors. Risk of cutting During cutting work, metal chips or sharp cut edges can cause injuries to eyes and hands! – Wear protective glasses and gloves. – Deburr cut edges. 1. Cut vertical ladders to the desired length, e.g. using an angle grinder. 2. Deburr cut edges. WARNING CAUTION

11 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 3 5 m 6 2 Mounting vertical ladders up to a max storey height of 3 5 m Function loss in the event of fire! At a storey height > 3.5 m, perfect functioning of the vertical ladder can- not be guaranteed in the event of fire. Only use mounting variants at a storey height of maximum 3.5 m. 6 2 1 Mounting the ladder rails with head plates Fig 3: a Drawing on the drill holes Note! Distance “a” is dependent on the width of the vertical ladder used. a = vertical ladder width – 50 mm. 1. Draw on two drill holes at spacing “a” behind the ceiling opening. Maintain the minimum edge spacing according to the approval of the anchor used. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 4: Mounting head plates 4. Mount head plates with the open sides facing each other, using one M12 anchor for the ceiling and one for the floor. WARNING

12 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 3 5 m Fig 5: Mounting ladder rails under the ceiling 5. Mount ladder rails under the ceiling with 1 M10 truss-head bolt each on the head plates. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! At a storey height > 3 m, additional ladder rails must be connected with the mounted ladder rails. See also “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 40 mm between the end of the ladder rail and the floor. Fig 6: min. 40 mm Moveable bearing on the floor WARNING

13 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 3 5 m 6 2 2 Mounting the ladder rails with a mounting bracket Fig 7: a Drawing on the drill holes Note! Distance “a” is dependent on the width of the vertical ladder used. a = vertical ladder width + 42 mm. 1. Draw on two drill holes at spacing “a” behind the ceiling opening. Maintain the minimum edge spacing according to the approval of the anchor used. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 8: Mounting installation profiles 4. Mount the installation profiles with 1 M12 anchor on the ceiling and floor. – Mount the installation profiles with the short side on the ceiling and floor. – Mount the installation profiles with the long side inward.

14 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 3 5 m Fig 9: Mounting ladder rails under the ceiling 5. Mount ladder rails under the ceiling with 1 M10 truss-head bolt each on the installation profiles. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! At a storey height > 3 m, additional ladder rails must be connected with the mounted ladder rails. See also “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 40 mm between the end of the ladder rail and the floor. Fig 10: min. 40 mm Moveable bearing on the floor WARNING

15 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 3 5 m 6 2 3 Mounting the ladder rails with transverse profiles 1. Draw the drill holes on next to the ceiling openings. Maintain the min- imum edge spacing according to the approval of the anchor used. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 11: max. 3,5 m Mounting transverse profiles 4. Mount the U supports in parallel to the vertical ladder, each with 2 M12 anchors. Fig 12: a Mount head plates under the ceiling. Note! The threaded rods must be mounted at a spacing of “a” to each other. a = vertical ladder width – 50 mm.

16 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 3 5 m 5. Run the first threaded rod through the lower U support and up to the ceiling opening and screw on the M12 nut and M12 washer. 6. Run the threaded rod through the lower side of the upper U support and screw tight from above using an M12 washer and M12 nut. 7. Lock from below with the previously screwed-on nut and washer. 8. Repeat steps 5–7 with the second threaded rod. 9. With the open sides facing each other, mount the head plates on the threaded rods, using 1 M12 washer and 2 M12 nuts. Fig 13: Mounting head plates on the floor Note! The head plates must be mounted vertically under the head plates under the ceiling. 10. With the open sides facing each other, mount the head plates on the floor, using 1 M12 truss-head bolt each on the U support. Fig 14: Mounting ladder rails under the ceiling

17 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 3 5 m 11. Mount ladder rails under the ceiling with 1 M10 truss-head bolt each on the head plates. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! At a storey height > 3 m, additional ladder rails must be mounted with the mounted ladder rails. See also “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 40 mm between the end of the ladder rail and the top side of the transverse profile. Fig 15: min. 40 mm Moveable bearing on the floor WARNING

18 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 3 5 m 6 2 4 Mounting the ladder rails with lengthwise profiles 1. Draw the drill holes on at spacing “a”, in front of and behind the ceiling openings. Maintain the minimum edge spacing according to the ap- proval of the anchor used. a = vertical ladder width – 50 mm. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 16: max. 3,5 m a Mounting lengthwise profiles 4. Mount the U supports at a 90° angle to the vertical ladder, each with 2 M12 anchors. Fig 17: Mounting head plates 5. Run the first threaded rod through the lower U support and up to the ceiling opening and screw on the M12 nut and M12 washer.

19 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 3 5 m 6. Run the threaded rod through the lower side of the upper U support and screw tight from above using an M12 washer and M12 nut. 7. Lock from below with the previously screwed-on nut and washer. 8. Repeat steps 5–7 with the second threaded rod. 9. With the open sides facing each other, mount the head plates on the threaded rods, using 1 M12 washer and 2 M12 nuts each. Fig 18: Mounting head plates on the floor Note! The head plates must be mounted vertically under the head plates under the ceiling. 10. With the open sides facing each other, mount the head plates on the floor, using 1 M12 truss-head bolt each on the U supports. Fig 19: Mounting ladder rails under the ceiling

20 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 3 5 m 11. Mount ladder rails under the ceiling with 1 M10 truss-head bolt each on the head plates. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! At a storey height > 3 m, additional ladder rails must be connected with the mounted ladder rails. See also “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 40 mm between the end of the ladder rail and the top side of the lengthwise profile. Fig 20: min. 40 mm Moveable bearing on the floor WARNING

21 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 7 0 m 6 3 Mounting vertical ladders up to a max storey height of 7 0 m Function loss in the event of fire! At a storey height > 7.0 m, perfect functioning of the vertical ladder can- not be guaranteed in the event of fire. Only use mounting variants at a storey height of maximum 7.0 m. Note! At a storey height > 3.5 m, after mounting of the vertical ladder, the ZSE90...LH strain relief must also be mounted. See also “7.2 Mounting the strain relief” on page 33. 6 3 1 Mounting the ladder rails with head plates Fig 21: a Drawing on the drill holes Note! Distance “a” is dependent on the width of the vertical ladder used. a = vertical ladder width – 50 mm. 1. Draw on two drill holes at spacing “a” behind the ceiling opening. Maintain the minimum edge spacing according to the approval of the anchor used. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 22: Mounting head plates 4. Mount head plates with the open sides facing each other, using 1 M12 anchor for the ceiling and 1 for the floor. WARNING

22 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 7 0 m Fig 23: Mounting ladder rails under the ceiling 5. Mount ladder rails under the ceiling with 2 M10 truss-head bolts each on the head plates. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! To connect additional ladder rails to the mounted ladder rails, see “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 70 mm between the end of the ladder rail and the floor. Fig 24: min. 70 mm Moveable bearing on the floor WARNING

23 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 7 0 m 6 3 2 Mounting the ladder rails with transverse profiles 1. Draw the drill holes on next to the ceiling openings. Maintain the min- imum edge spacing according to the approval of the anchor used. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 25: max. 7,0 m Mounting transverse profiles 4. Mount the U supports in parallel to the vertical ladder, each with 2 M12 anchors. Fig 26: x y y Mounting head plates Note! The threaded rods must be mounted at a spacing of y – x – y to each other. x = vertical ladder width – 150 mm; y = 100 mm.

24 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 7 0 m 5. Run the first threaded rod through the lower U support and up to the ceiling opening and screw on the M12 nut and M12 washer. 6. Run the threaded rod through the lower side of the upper U support and screw tight from above using an M12 washer and M12 nut. 7. Lock from below with the previously screwed-on nut and washer. 8. Repeat steps 5–7 with 3 further threaded rods. 9. With the open sides facing each other, mount the head plates on the threaded rods, using 1 M12 washer and 2 M12 nuts. Fig 27: Mounting head plates on the floor Note! The head plates must be mounted vertically under the head plates under the ceiling. 10. With the open sides facing each other, mount the head plates on the floor using 1 M12 truss-head bolt each on the U support. Fig 28: Mounting ladder rails under the ceiling

25 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 7 0 m 11. Mount the ladder rails under the ceiling with 2 M10 truss-head bolts each on the head plates. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! To connect additional ladder rails to the mounted ladder rails, see “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 70 mm between the end of the ladder rail and the top side of the trans- verse profile. Fig 29: min. 70 mm Moveable bearing on the floor WARNING

26 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 7 0 m 6 3 3 Mounting the ladder rails with lengthwise profiles 1. Draw the drill holes on at spacing y – x – y, in front of and behind the ceiling openings. x = vertical ladder width – 150 mm, y = 100 mm. 2. Using a linear laser, transfer the position of the drill holes to the floor. 3. Pre-drill the drill holes. Ø according to anchor type and approval. Fig 30: max. 7,0 m x y y Mounting lengthwise profiles 4. Mount the U support at a 90° angle to the vertical ladder, each with 2 M12 anchors. Fig 31: Mounting head plates 5. Run the first threaded rod through the lower U support and screw on the M12 nut and M12 washer. 6. Run the threaded rod through the lower side of the upper U support and screw tight from above using an M12 washer and M12 nut.

27 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting vertical ladders up to a max storey height of 7 0 m 7. Lock from below with the previously screwed-on nut and washer. 8. Repeat steps 5–7 with 3 further threaded rods. 9. With the opening facing inward, mount the head plates on the thread- ed rods, using 1 M12 washer and 2 M12 nuts each. Fig 32: Mounting head plates on the floor Note! The head plates must be mounted vertically under the head plates under the ceiling. 10. With the open sides facing each other, mount the head plates on the floor, using 1 M12 truss-head bolt each on the U supports. Fig 33: Mounting ladder rails under the ceiling 11. Mount ladder rails under the ceiling with 2 M10 truss-head bolts each on the head plates. – Mount the rails with the open sides facing each other. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders.

28 | EN

OBO Bettermann Mounting vertical ladders up to a max storey height of 7 0 m Note! To connect additional ladder rails to the mounted ladder rails, see “6.5 Mounting U support connectors” on page 30. Function loss through length expansion in the event of fire! If there is a fire, the material of the vertical ladders expands. Do not bolt the vertical ladder to the floor. Maintain a minimum distance of 70 mm between the end of the ladder rail and the top side of the lengthwise profile. Fig 34: min. 70 mm Moveable bearing on the floor WARNING

29 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Mounting ladder rungs 6 4 Mounting ladder rungs Fig 35: max. 300 Mounting ladder rungs 1. Insert the ladder rungs into the ladder rails at a distance of 300 mm from the interior. 2. Mount with 2 truss-head bolts each.

30 | EN

OBO Bettermann Mounting U support connectors 6 5 Mounting U support connectors The U support connector can connect two vertical ladder rails, in order to connect storey heights > 3.0 m. Fig 36: max. 300 mm Mounting U support connectors 1. Mount each of the U support connectors with 3 M10 truss-head bolts to the ladder rails already mounted under the ceiling. – Mount the connectors with the opening pointing inwards. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the connector. 2. Mount each additional ladder rail to the U support connectors with 3 truss-head bolts. – Mount the rails with the opening pointing inwards. – Place the bolts up to the limit in the slot, in order to prevent a verti- cal movement of the vertical ladders. Note! The maximum distance between the ladder rungs above and below the U support connector is 300 mm.

31 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Fastening cables 6 6 Fastening cables Function loss through excessive cable load! At an excessive cable load, the perfect functioning of the vertical ladder cannot be guaranteed in the event of fire. Observe the maximum cable load and specifications for the cable assignment. – Cable load per vertical ladder max. 20 kg/m – Cable bundling, heavy current cables, max. quantity 3, max. diameter 25 mm – Cable bundling, installation cables, quantity not limited, total cable weight max. 3.0 kg/m Fig 37: Fastening cables 1. Fasten cables to the ladder rungs with clamp clips, type 2056U M. 6 7 Attaching the identification plate The cable system must be given an identification plate, in accordance with DIN 4102 Part 12. 1. Clearly fill out the KS-E identification plate with a permanent marker. 2. Stick the KS-E identification plate to the ladder rail of the suspended vertical ladder. WARNING

32 | EN

OBO Bettermann Additional required measures 7 Additional required measures 7 1 Closing ceiling openings with insulation After mounting, the ceiling opening must be closed off with appropriate fire insulation. Note! For more information on mounting the fire insulation, see the mounting instructions of the appropriate insulation system. Fig 38: Fully mounted strain relief on suspended vertical ladder

33 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Additional required measures 7 2 Mounting the strain relief From storey heights of 3.5 m, the ZSE90... LH strain relief must be mounted as an effective support measure for suspended rising sections. Note! For more information on the mounting of the ZSE90...LH strain relief, see the ZSE90 mounting instructions. Fig 39: Fully mounted strain relief on suspended rising section

34 | EN

OBO Bettermann Retrofitting 8 Retrofitting Retrofitting of the suspended rising section is always possible at any time. During retrofitting, observe the following: – Do not exceed the maximum cable load of the vertical ladder, see also “6.6 Fastening cables” on page 31. – Observe the conditions for retrofitting the inserted insulation in the ceiling opening. – Observe the conditions for retrofitting any possibly mounted ZSE90 strain relief. 9 Checking and maintaining the system The suspended vertical ladder is maintenance-free. Carry out a visual inspection of the suspended vertical ladder as part of the inspection of the electrical systems. 10 Dismantling the system Dismantling of all the elements of the suspended rising section takes place in the reverse order to mounting. 11 Disposing of the system Comply with the local waste disposal regulations. – Product/system: As scrap metal – Packaging: As household waste Disposal after a fire Irritant effect! If there is a fire, burning cable insulation can create corrosive gases, which have an irritant and corrosive effect. When disposing of system components which have been subjected to a fire, wear breathing protection and protective clothing. If the system was subjected to fire damage, then the complete system must be removed and disposed of. We recommend obtaining the advice of the local fire damage restorer during disposal. CAUTION

35 | EN

SLM50 suspended vertical ladders for the maintenance of electrical function Technical data 12 Technical data Type Item no Designation Dimensions in mm (L x W) Vertical ladders SLM50C40F 20 FT 6010004 SLM 50 vertical ladder 3,000 x 200 SLM50C40F 30 FT 6010006 SLM 50 vertical ladder 3,000 x 300 SLM50C40F 40 FT 6010008 SLM 50 vertical ladder 3,000 x 400 SLM50C40F 50 FT 6010016 SLM 50 vertical ladder 3,000 x 500 SLM50C40F 60 FT 6010024 SLM 50 vertical ladder 3,000 x 600 Fastenings KUS 5 NOK 6348939 Head plate – KUS 5 FT 6348904 Head plate – GMS 3 VW 90 FT 1124661 Mounting bracket – US 7 40 FT 6340059 US 7 support – US 7 50 FT 6340075 US 7 support – US 7 60 FT 6340091 US 7 support – US 7 70 FT 6340113 US 7 support – US 7 80 FT 6340148 US 7 support – US 7 90 FT 6340164 US 7 support – US 7 100 FT 6340180 US 7 support – US 7 110 FT 6340199 US 7 support – US 7 120 FT 6340202 US 7 support – US 7 130 FT 6340210 US 7 support – US 7 140 FT 6340229 US 7 support – US 7 150 FT 6340237 US 7 support – VUS 5 FT 6018506 U support connector – FRS 10x25 F 8.8 6407560 Truss-head bolt – FRS 12x25 F 6406254 Truss-head bolt – TR M12 1M G 3141306 Threaded rod – HN M12 G 3400123 Hexagonal nut – WS M12 D24 G 3402096 Washer – Accessories KS-E EN 7205432 Identification plate – 2056U M 12 FT 1158007 Clamp clip – 2056U M 16 FT 1158015 Clamp clip – 2056U M 22 FT 1158023 Clamp clip – 2056U M 28 FT 1152031 Clamp clip – 2056U M 34 FT 1158058 Clamp clip – 2056U M 40 FT 1158066 Clamp clip – 2056U M 46 FT 1158074 Clamp clip – 2056U M 52 FT 1158082 Clamp clip – 2056U M 58 FT 1158090 Clamp clip – 2056U M 64 FT 1158104 Clamp clip – 2056U M 70 FT 1158112 Clamp clip – 2056U M 76 FT 1158120 Clamp clip – Tab 7: Technical data