SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
Issue
05
Date
2020-08-30
HUAWEI TECHNOLOGIES CO., LTD.
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website:
https://e.huawei.com
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
i
About This Document
Overview
This document describes the SUN2000-175KTL-H0, SUN2000-185KTL-INH0, and
SUN2000-185KTL-H1 (SUN2000 for short) in terms of their installation, electrical
connections, commissioning, maintenance, and troubleshooting. Before installing
and operating the inverter, ensure that you are familiar with the features,
functions, and safety precautions provided in this document.
Intended Audience
This document is intended for photovoltaic (PV) plant operating personnel and
qualified electricians.
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates a hazard with a high level of risk which,
if not avoided, will result in death or serious
injury.
Indicates a hazard with a medium level of risk
which, if not avoided, could result in death or
serious injury.
Indicates a hazard with a low level of risk which,
if not avoided, could result in minor or moderate
injury.
Indicates a potentially hazardous situation which,
if not avoided, could result in equipment damage,
data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to
personal injury.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
About This Document
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
ii
Supplements the important information in the
main text.
NOTE is used to address information not related
to personal injury, equipment damage, and
environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue
contains all updates made in previous issues.
Issue 05 (2020-08-30)
Updated 2.1 Product Overview.
Updated 4.3.1 Environment Requirements.
Updated 4.5 Installing the Inverter.
Updated 6.2 System Power-On.
Updated 7.1 Operations with the App.
Updated 8.3 Routine Maintenance.
Issue 04 (2020-03-03)
Updated 1 Safety Information.
Updated 2.3.1 Label Description.
Updated 5.8 Installing the Communications Cable.
Updated 7.1 Operations with the App.
Updated 10 Technical Data.
Added A Securing Y-Branch Connectors.
Added C Domain Name List of Management Systems.
Issue 03 (2019-09-10)
Updated 5.7 Installing the DC Input Power Cable.
Updated 8.5 Troubleshooting.
Added B String Access Detection.
Issue 02 (2019-06-05)
Updated 2.2 Appearance.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
About This Document
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
iii
Issue 01 (2019-05-15)
This issue is used for first office application (FOA).
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
About This Document
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
iv
About This Document................................................................................................................ ii
1 Safety Information.................................................................................................................. 1
1.1 General Safety.......................................................................................................................................................................... 1
1.2 Personnel Requirements....................................................................................................................................................... 2
1.3 Electrical Safety........................................................................................................................................................................3
1.4 Installation Environment Requirements.......................................................................................................................... 4
1.5 Mechanical Safety................................................................................................................................................................... 4
1.6 Commissioning......................................................................................................................................................................... 5
1.7 Maintenance and Replacement..........................................................................................................................................6
2 Overview....................................................................................................................................7
2.1 Product Overview.................................................................................................................................................................... 7
2.2 Appearance................................................................................................................................................................................9
2.3 Label Description.................................................................................................................................................................. 12
2.3.1 Label Description............................................................................................................................................................... 12
2.3.2 Product Nameplate...........................................................................................................................................................14
2.4 Working Principles................................................................................................................................................................ 14
2.4.1 Circuit Diagram.................................................................................................................................................................. 14
2.4.2 Working Modes.................................................................................................................................................................. 15
3 Solar Inverter Storage.......................................................................................................... 17
4 Installation..............................................................................................................................19
4.1 Checking Before Installation............................................................................................................................................. 19
4.2 Preparing Tools...................................................................................................................................................................... 20
4.3 Determining the Installation Position............................................................................................................................21
4.3.1 Environment Requirements............................................................................................................................................21
4.3.2 Space Requirements......................................................................................................................................................... 23
4.4 Installing the Mounting Bracket...................................................................................................................................... 25
4.4.1 Support-mounted Installation.......................................................................................................................................26
4.4.2 Wall-mounted Installation............................................................................................................................................. 27
4.5 Installing the Inverter.......................................................................................................................................................... 28
5 Electrical Connections.......................................................................................................... 31
5.1 Precautions..............................................................................................................................................................................31
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
Contents
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
v
5.2 Crimping an OT or DT Terminal...................................................................................................................................... 31
5.3 Opening the Maintenance Compartment Door.........................................................................................................34
5.4 (Optional) Replacing the Crimping Module................................................................................................................36
5.5 (Optional) Installing the Power Cable of the Tracking System............................................................................ 36
5.6 Connecting the AC Output Power Cable...................................................................................................................... 37
5.7 Installing the DC Input Power Cable..............................................................................................................................41
5.8 Installing the Communications Cable............................................................................................................................46
5.9 Closing the Maintenance Compartment Door........................................................................................................... 49
6 System Commissioning........................................................................................................ 51
6.1 Check Before Power-on ..................................................................................................................................................... 51
6.2 System Power-On................................................................................................................................................................. 51
7 Man-Machine Interactions..................................................................................................53
7.1 Operations with the App.................................................................................................................................................... 53
7.1.1 App Introduction................................................................................................................................................................53
7.1.2 Downloading and Installing the App..........................................................................................................................55
7.1.3 Logging In to the App......................................................................................................................................................55
7.1.4 Operations Related to the Advanced User............................................................................................................... 58
7.1.4.1 Setting Grid Parameters...............................................................................................................................................59
7.1.4.2 Setting Protection Parameters...................................................................................................................................59
7.1.4.3 Setting Feature Parameters........................................................................................................................................ 60
7.1.5 Operations Related to the Special User.....................................................................................................................64
7.1.5.1 Setting Grid Parameters...............................................................................................................................................64
7.1.5.2 Setting Protection Parameters...................................................................................................................................67
7.1.5.3 Setting Feature Parameters........................................................................................................................................ 68
7.1.5.4 Setting Power Adjustment Parameters...................................................................................................................72
7.2 Operations with a USB Flash Drive................................................................................................................................ 76
7.2.1 Exporting Configurations................................................................................................................................................ 76
7.2.2 Importing Configurations............................................................................................................................................... 78
7.2.3 Exporting Data................................................................................................................................................................... 79
7.2.4 Upgrading............................................................................................................................................................................ 80
8 Maintenance...........................................................................................................................82
8.1 System Power-Off.................................................................................................................................................................82
8.2 Power-Off for Troubleshooting........................................................................................................................................ 82
8.3 Routine Maintenance.......................................................................................................................................................... 84
8.4 Replacing a Fan..................................................................................................................................................................... 86
8.5 Troubleshooting.....................................................................................................................................................................89
9 Handling the Inverter...........................................................................................................98
9.1 Removing the SUN2000..................................................................................................................................................... 98
9.2 Packing the SUN2000..........................................................................................................................................................98
9.3 Disposing of the SUN2000................................................................................................................................................ 98
10 Technical Data..................................................................................................................... 99
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
Contents
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
vi
A Securing Y-Branch Connectors.........................................................................................103
B String Access Detection.....................................................................................................106
C Domain Name List of Management Systems...............................................................109
D Grid Code..............................................................................................................................110
E Acronyms and Abbreviations............................................................................................114
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
Contents
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
vii
1 Safety Information
1.1 General Safety
Statement
Before installing, operating, and maintaining the equipment, read this document
and observe all the safety instructions on the equipment and in this document.
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this
document do not cover all the safety instructions. They are only supplements to
the safety instructions. Huawei will not be liable for any consequence caused by
the violation of general safety requirements or design, production, and usage
safety standards.
Ensure that the equipment is used in environments that meet its design
specifications. Otherwise, the equipment may become faulty, and the resulting
equipment malfunction, component damage, personal injuries, or property
damage are not covered under the warranty.
Follow local laws and regulations when installing, operating, or maintaining the
equipment. The safety instructions in this document are only supplements to local
laws and regulations.
Huawei will not be liable for any consequences of the following circumstances:
●
Operation beyond the conditions specified in this document
●
Installation or use in environments which are not specified in relevant
international or national standards
●
Unauthorized modifications to the product or software code or removal of the
product
●
Failure to follow the operation instructions and safety precautions on the
product and in this document
●
Equipment damage due to force majeure, such as earthquakes, fire, and
storms
●
Damage caused during transportation by the customer
●
Storage conditions that do not meet the requirements specified in this
document
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
1 Safety Information
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
1
Do not work with power on during installation.
●
Do not install, use, or operate outdoor equipment and cables (including but
not limited to moving equipment, operating equipment and cables, inserting
connectors to or removing connectors from signal ports connected to outdoor
facilities, working at heights, and performing outdoor installation) in harsh
weather conditions such as lightning, rain, snow, and level 6 or stronger wind.
●
After installing the equipment, remove idle packing materials such as cartons,
foam, plastics, and cable ties from the equipment area.
●
In the case of a fire, immediately leave the building or the equipment area,
and turn on the fire alarm bell or make an emergency call. Do not enter the
building on fire in any case.
●
Do not scrawl, damage, or block any warning label on the equipment.
●
Tighten the screws using tools when installing the equipment.
●
Understand the components and functioning of a grid-tied PV power system
and relevant local standards.
●
Repaint any paint scratches caused during equipment transportation or
installation in a timely manner. Equipment with scratches cannot be exposed
to an outdoor environment for a long period of time.
●
Do not open the host panel of the equipment.
Personal Safety
●
If there is a probability of personal injury or equipment damage during
operations on the equipment, immediately stop the operations, report the
case to the supervisor, and take feasible protective measures.
●
Use tools correctly to avoid hurting people or damaging the equipment.
●
Do not touch the energized equipment, as the enclosure is hot.
1.2 Personnel Requirements
●
Personnel who plan to install or maintain Huawei equipment must receive
thorough training, understand all necessary safety precautions, and be able to
correctly perform all operations.
●
Only qualified professionals or trained personnel are allowed to install,
operate, and maintain the equipment.
●
Only qualified professionals are allowed to remove safety facilities and inspect
the equipment.
●
Personnel who will operate the equipment, including operators, trained
personnel, and professionals, should possess the local national required
qualifications in special operations such as high-voltage operations, working
at heights, and operations of special equipment.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
1 Safety Information
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
2
Only professionals or authorized personnel are allowed to replace the
equipment or components (including software).
NO TE
●
Professionals: personnel who are trained or experienced in equipment operations
and are clear of the sources and degree of various potential hazards in equipment
installation, operation, and maintenance
●
Trained personnel: personnel who are technically trained, have required experience,
are aware of possible hazards on themselves in certain operations, and are able to
take protective measures to minimize the hazards on themselves and other people
●
Operators: operation personnel who may come in contact with the equipment,
except trained personnel and professionals
1.3 Electrical Safety
Grounding
●
For the equipment that needs to be grounded, install the ground cable first
when installing the equipment and remove the ground cable last when
removing the equipment.
●
Do not damage the ground conductor.
●
Do not operate the equipment in the absence of a properly installed ground
conductor.
●
Ensure that the equipment is connected permanently to the protective
ground. Before operating the equipment, check its electrical connection to
ensure that it is securely grounded.
General Requirements
D ANGER
Before connecting cables, ensure that the equipment is intact. Otherwise, electric
shocks or fire may occur.
●
Ensure that all electrical connections comply with local electrical standards.
●
Obtain approval from the local electric utility company before using the
equipment in grid-tied mode.
●
Ensure that the cables you prepared meet local regulations.
●
Use dedicated insulated tools when performing high-voltage operations.
AC and DC Power
D ANGER
Do not connect or disconnect power cables with power on. Transient contact
between the core of the power cable and the conductor will generate electric arcs
or sparks, which may cause fire or personal injury.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
1 Safety Information
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
3
Before making electrical connections, switch off the disconnector on the
upstream device to cut off the power supply if people may contact energized
components.
●
Before connecting a power cable, check that the label on the power cable is
correct.
●
If the equipment has multiple inputs, disconnect all the inputs before
operating the equipment.
Cabling
●
When routing cables, ensure that a distance of at least 30 mm exists between
the cables and heat-generating components or areas. This prevents damage
to the insulation layer of the cables.
●
Bind cables of the same type together. When routing cables of different types,
ensure that they are at least 30 mm away from each other.
●
Ensure that the cables used in a grid-tied PV power system are properly
connected and insulated and meet specifications.
1.4 Installation Environment Requirements
●
Ensure that the equipment is installed in a well ventilated environment.
●
To prevent fire due to high temperature, ensure that the ventilation vents or
heat dissipation system are not blocked when the equipment is running.
●
Do not expose the equipment to flammable or explosive gas or smoke. Do
not perform any operation on the equipment in such environments.
1.5 Mechanical Safety
Using Ladders
●
Use wooden or fiberglass ladders when you need to perform live working at
heights.
●
When a step ladder is used, ensure that the pull ropes are secured and the
ladder is held firm.
●
Before using a ladder, check that it is intact and confirm its load bearing
capacity. Do not overload it.
●
Ensure that the wider end of the ladder is at the bottom, or protective
measures have been taken at the bottom to prevent the ladder from sliding.
●
Ensure that the ladder is securely positioned. The recommended angle for a
ladder against the floor is 75 degrees, as shown in the following figure. An
angle rule can be used to measure the angle.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
1 Safety Information
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
4
When climbing a ladder, take the following precautions to reduce risks and
ensure safety:
–
Keep your body steady.
–
Do not climb higher than the fourth rung of the ladder from the top.
–
Ensure that your body's center of gravity does not shift outside the legs
of the ladder.
Drilling Holes
When drilling holes into a wall or floor, observe the following safety precautions:
●
Wear goggles and protective gloves when drilling holes.
●
When drilling holes, protect the equipment from shavings. After drilling, clean
up any shavings that have accumulated inside or outside the equipment.
Moving Heavy Objects
●
Be cautious to avoid injury when moving heavy objects.
●
When moving the equipment by hand, wear protective gloves to prevent
injuries.
1.6 Commissioning
When the equipment is powered on for the first time, ensure that professional
personnel set parameters correctly. Incorrect settings may result in inconsistency
with local certification and affect the normal operation of the equipment.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
1 Safety Information
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
5
1.7 Maintenance and Replacement
D ANGER
High voltage generated by the equipment during operation may cause an electric
shock, which could result in death, serious injury, or serious property damage.
Prior to maintenance, power off the equipment and strictly comply with the safety
precautions in this document and relevant documents.
●
Maintain the equipment with sufficient knowledge of this document and
using proper tools and testing equipment.
●
Before maintaining the equipment, power it off and follow the instructions on
the delayed discharge label to ensure that the equipment is powered off.
●
Place temporary warning signs or erect fences to prevent unauthorized access
to the maintenance site.
●
If the equipment is faulty, contact your dealer.
●
The equipment can be powered on only after all faults are rectified. Failing to
do so may escalate faults or damage the equipment.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
1 Safety Information
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
6
2.1 Product Overview
Function
The SUN2000 inverter is a three-phase grid-tied PV string inverter that converts
the DC power generated by PV strings into AC power and feeds the power into the
power grid.
Model
This document involves the following product models:
●
SUN2000-175KTL-H0
●
SUN2000-185KTL-INH0
●
SUN2000-185KTL-H1
Figure 2-1 Model description (SUN2000-185KTL-INH0 is used as an example)
Table 2-1 Model description
Tag
Meaning
Value
1
Series
SUN2000: three-phase grid-tied PV
string inverter
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
7
● 175K: The rated output power is
175 kW.
● 185K: The maximum active
power is 185 kW.
3
Topology
TL: transformerless
4
Region
IN: India
5
Product code
H0/H1: product series with the
1500 V DC input voltage
NO TE
The SUN2000-175KTL-H0 is applicable only to the Chinese mainland. For other countries or
regions, Huawei does not provide quality assurance.
Network Application
The inverter applies to grid-tied PV systems for commercial rooftop PV plants and
large PV plants. Typically, a grid-tied PV system consists of the PV string, inverter,
AC power distribution unit, and step-up transformer.
Figure 2-2 Network application
(A) PV string
(B) Inverter
(C) AC distribution unit (ACDU)
(D) Step-up transformer
(E) Power grid
NO TE
The SUN2000 is powered by a dedicated power transformer instead of connecting to low
voltage overhead power lines.
Supported Power Grid
The inverter supports the IT power grid.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
8
Figure 2-3 Supported power grid
NO TE
The SUN2000 can also apply to the AC power system with the neutral point grounding of
the step-up transformer. The SUN2000 itself does not connect to any neutral wire.
Figure 2-4 AC power system with the neutral point grounding
2.2 Appearance
Dimensions
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
9
(1) PV connection
indicator
(2) Grid-tied indicator
(3) Communication
indicator
(4) Alarm/Maintenance
indicator
(5) Host panel
(6) Maintenance
compartment
Table 2-2 LED description
Display
Category
Indicator Status
Meaning
PV indication
LED1
LED4
-
Steady
green
-
At least one PV string is properly connected, and
the DC input voltage of the corresponding MPPT
circuit is at least 500 V.
Blinking
green at
long
intervals
-
The test on the cable connection of PV strings is
complete, cables are correctly connected, and the
buzzer does not buzz.
Blinking red
at long
intervals
-
The test on the cable connection of PV strings is in
progress and the buzzer does not buzz.
Steady red
-
The test on the cable connection of PV strings is
complete, cables are incorrectly connected, and the
buzzer buzzes.
Blinking
green at
short
intervals
Red
An environmental fault occurs at DC side.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
10
The inverter disconnects from all PV strings, or the
DC input voltage of all MPPT circuits is less than
500 V.
Grid-tied
indication
LED2
LED4
NA
Steady
green
-
The inverter is in grid-tied mode.
Blinking
green at
short
intervals
Red
An environmental fault occurs at AC side.
Off
-
The inverter is not in grid-tied mode.
Communicatio
ns indication
LED3
-
Blinking green at short
intervals
The inverter receives data over RS485 or MBUS
communication.
Off
The inverter has not received data over RS485 or
MBUS communication for 10 seconds.
Alarm/O&M
indication
LED4
-
Steady red
A major alarm is generated.
Blinking red at short
intervals
A minor alarm is generated.
Blinking red at long
intervals
A warning alarm is generated.
Steady green
Local maintenance succeeds.
Blinking green at long
intervals
In local maintenance or shuts down over a
command.
Blinking green at short
intervals
Local maintenance fails.
Off
No alarm is generated, and no local maintenance
operations are performed.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
11
Local maintenance refers to operations performed after a universal serial bus (USB)
flash drive, Bluetooth module, WLAN module, or USB data cable is inserted into the USB
port of the inverter. For example, local maintenance includes configuration import and
export using a USB flash drive, and connecting to the SUN2000 app over a Bluetooth
module, WLAN module, or USB data cable.
●
If the alarming and the local maintenance happen concurrently, the alarm/maintenance
indicator shows the local maintenance state first. After the USB flash drive, Bluetooth
module, WLAN module, or USB data cable is removed, the indicator shows the alarm
state.
Bottom View
(1) DC input terminals (controlled by
DC SWITCH 1)
(2) DC switch 1 (DC SWITCH 1)
(3) DC input terminals (controlled by
DC SWITCH 2)
(4) DC switch 2 (DC SWITCH 2)
(5) DC input terminals (controlled by
DC SWITCH 3)
(6) DC switch 3 (DC SWITCH 3)
(7) Ventilation valve
(8) USB port (USB)
(9) Communications port (COM)
(10) AC output cable port
(11) Power cable port for the tracking
system
2.3 Label Description
2.3.1 Label Description
Symbol
Name
Meaning
Running warning
Potential hazards exist after the
inverter is powered on. Take
protective measures when operating
the inverter.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
12
Do not touch a running inverter, as
the shell becomes hot during
operation.
Large current warning
Before powering on the inverter,
ensure that the inverter is grounded
because there is a large contact
current after the inverter is powered
on.
Delayed discharge
● High voltage exists after the
inverter is powered on. Only
qualified and trained electrical
technicians are allowed to
perform operations on the
inverter.
● Residual voltage exists after the
inverter is powered off. It takes
15 minutes for the inverter to
discharge to the safe voltage.
Refer to documentation
Reminds operators to refer to the
documents shipped with the inverter.
Grounding
Indicates the position for connecting
the protective earthing (PE) cable.
Operation warning
Do not remove the DC input
connector when the inverter is
running.
Fan operation warning
High voltage exists after the inverter
is powered on. Do not touch the
fans when the inverter is working.
Fan replacement warning
Before replacing a fan, disconnect its
power connectors.
Inverter ESN label
Indicates the inverter serial number.
Weight label
The inverter needs to be carried by
four persons or using a pallet truck.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
13
2.3.2 Product Nameplate
Figure 2-5 Nameplate (SUN2000-175KTL-H0 is used as an example)
(1) Trademark and product model
(2) Important technical specifications
(3) Compliance symbols
(4) Company name and country of manufacture
NO TE
The nameplate figure is for reference only.
2.4 Working Principles
2.4.1 Circuit Diagram
The inverter receives inputs from 18 PV strings. Then the inputs are grouped into
nine MPPT circuits inside the inverter to track the maximum power point of the PV
strings. The DC power is then converted into three-phase AC power through an
inverter circuit. Surge protection is supported on both the DC and AC sides.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
14
Figure 2-6 Inverter conceptual diagram
2.4.2 Working Modes
The SUN2000 can work in Standby, Operating, or Shutdown mode.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
15
Figure 2-7 Working modes
Table 2-3 Working mode description
Working
Mode
Description
Standby
The SUN2000 enters Standby mode when the external
environment does not meet the operating requirements. In
Standby mode:
● The SUN2000 continuously performs status check and enters
the Operating mode once the operating requirements are met.
● The SUN2000 enters Shutdown mode after detecting a
shutdown command or a fault after startup.
Operating
In Operating mode:
● The SUN2000 converts DC power from PV strings into AC power
and feeds the power to the power grid.
● The SUN2000 tracks the maximum power point to maximize
the PV string output.
● If the SUN2000 detects a fault or a shutdown command, it
enters the Shutdown mode.
● The SUN2000 enters Standby mode after detecting that the PV
string output power is not suitable for connecting to the power
grid for generating power.
Shutdown
● In Standby or Operating mode, the SUN2000 enters Shutdown
mode after detecting a fault or shutdown command.
● In Shutdown mode, the SUN2000 enters Standby mode after
detecting a startup command or that the fault is rectified.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
2 Overview
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
16
3 Solar Inverter Storage
The following requirements should be met if the solar inverter is not put into use
immediately:
●
Do not remove the packing materials, and check the packing materials
regularly (recommended: every three months). If any rodent bites are found,
replace the packing materials immediately. If the solar inverter is unpacked
but not put into use immediately, put it inside the original package with the
desiccant bag, and seal it using tape.
●
The ambient temperature and humidity should be suitable for the storage.
The air must not contain corrosive or flammable gases.
Figure 3-1 Storage temperature and humidity
●
The solar inverter should be stored in a clean and dry place and be protected
from dust and water vapor corrosion. The solar inverter must be protected
against rain and water.
●
Do not tilt the package or place it upside down.
●
To avoid personal injury or device damage, stack inverters with caution to
prevent them from falling over.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
3 Solar Inverter Storage
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
17
Figure 3-2 Maximum number of pile-up layers allowed
●
If the solar inverter has been stored for more than two years, it must be
checked and tested by professionals before being put into use.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
3 Solar Inverter Storage
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
18
4.1 Checking Before Installation
Outer Packing Materials
Before unpacking the inverter, check the outer packing materials for damage, such
as holes and cracks, and check the inverter model. If any damage is found or the
inverter model is not what you requested, do not unpack the package and contact
your supplier as soon as possible.
Figure 4-1 Position of the inverter model label
(1) Position of the model label
NO TE
You are advised to remove the packing materials within 24 hours before installing the
inverter.
Package Contents
After unpacking the inverter, check that the contents are intact and complete. If
any damage is found or any component is missing, contact your supplier.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
19
For details about the number of contents, see the Packing List in the packing case.
4.2 Preparing Tools
Type
Tool
Installation
tools
Hammer drill
Drill bit: Φ14 mm
and Φ16 mm
Socket wrench set
Torque wrench
Diagonal pliers
Wire stripper
Flat-head
screwdriver
Head: 0.6 mm x 3.5
mm
Rubber mallet
Utility knife
Cable cutter
Crimping tool
Model:
32.6020-22100-HZ;
manufacturer:
Staubli
Removal wrench
Model: 13001462;
manufacturer:
Staubli
Vacuum cleaner
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
20
≥ 1500 V DC
Marker
Measuring tape
Bubble or digital
level
Hydraulic pliers
Heat shrink tubing
Heat gun
Binding strap
Personal
protective
equipment
(PPE)
Safety gloves
Safety goggles
Anti-dust
respirator
Safety boots
4.3 Determining the Installation Position
4.3.1 Environment Requirements
Basic Requirements
●
Do not install the inverter in working or living areas.
●
If the device is installed in public places (such as parking lots, stations, and
factories) other than working and living areas, install a protective net outside
the device, set up a safety warning sign to isolate the device, and prevent
unauthorized personnel from approaching the inverter. This is to avoid
personal injury or property loss caused by accidental contact or other reasons
during device operation.
●
Do not install the inverter in areas with flammable materials.
●
Do not install the inverter in areas with explosive materials.
●
Do not install the inveter in areas with corrosive materials.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
21
Do not install the inverter where its enclosure and heat sinks are easily
accessible, because the voltage is high and these parts are hot during
operation.
●
Install the inverter in a well-ventilated environment for heat dissipation
●
If the inverter is installed in an airtight environment, a heat dissipation device
or ventilation device must be installed to ensure that the indoor ambient
temperature is not higher than the external ambient temperature during
operation.
●
You are advised to install the inverter in a sheltered place or install an awning
over it.
●
The inverter will be corroded in salt areas. Before installing the inverter
outdoors in salt areas, consult Huawei. A salt area refers to the region within
500 meters from the coast or prone to sea breeze. The regions prone to sea
breeze vary with weather conditions (such as typhoons and monsoons) or
terrains (such as dams and hills).
Figure 4-2 Installation environment
Mounting Structure Requirements
●
The mounting structure where the inverter is installed must be fire resistant.
●
Do not install the inverter on flammable building materials.
●
The inverter is heavy. Ensure that the installation surface is solid enough to
bear the weight load.
●
In residential areas, do not install the inverter on drywalls or walls made of
similar materials which have a weak sound insulation performance because
the noise generated by the inverter is noticeable.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
22
Figure 4-3 Mounting structure
4.3.2 Space Requirements
●
Reserve enough clearance around the inverter and select an appropriate
installation angle to ensure sufficient space for installation and heat
dissipation.
Figure 4-4 Installation space
NO TE
For ease of installing the inverter on the mounting bracket, connecting cables to the
bottom of the inverter, and maintaining the inverter in future, it is recommended that
the bottom clearance be between 600 mm and 730 mm. If you have any question
about the clearance, consult the local technical support engineers.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
23
Figure 4-5 Installation angle
●
When installing multiple inverters, install them in horizontal mode if sufficient
space is available and install them in triangle mode if no sufficient space is
available. Stacked installation is not recommended.
Figure 4-6 Horizontal installation mode (recommended)
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
24
Figure 4-7 Triangle installation mode (recommended)
Figure 4-8 Stacked installation mode (not recommended)
4.4 Installing the Mounting Bracket
Installation Precautions
Figure 4-9 shows the inverter mounting bracket dimensions.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
25
Figure 4-9 Mounting bracket dimensions
NO TE
The inverter mounting bracket has four groups of tapped holes, each group containing four
tapped holes. Mark any hole in each group based on site requirements and mark four holes
in total. The two round holes are recommended.
Before installing the mounting bracket, remove the security torx wrench from the
mounting bracket and set it aside.
Figure 4-10 Removing a security torx wrench
4.4.1 Support-mounted Installation
Support-mounted Installation
Step 1 Install the mounting bracket.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
26
Figure 4-11 Installing the mounting bracket
----End
4.4.2 Wall-mounted Installation
Wall-mounted Installation
Step 1 Install the mounting bracket.
WARNING
Avoid drilling holes in the water pipes and power cables buried in the wall.
NO TICE
● To prevent dust inhalation or contact with eyes, wear safety goggles and an
anti-dust respirator when drilling holes.
● Clean up any dust in and around the holes using a vacuum cleaner and
measure the distance between holes. If the holes are inaccurately positioned,
drill a new set of holes.
● Level the head of the expansion sleeve with the concrete wall after removing
the bolt, spring washer, and flat washer. Otherwise, the mounting bracket will
not be securely installed on the wall.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
27
Figure 4-12 Securing the mounting bracket
----End
4.5 Installing the Inverter
Preparing for the Installation
Before installing the inverter, take it out from the packing case and move it to the
installation position.
NO TE
Handles are packed in a fitting bag and are not delivered with the inverter.
Figure 4-13 Taking out and moving the inverter
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
28
● Move the inverter with the help of other three persons or using an appropriate
transportation tool.
● Do not place the inverter with its wiring terminals at the bottom contacting the
floor or any other objects because the terminals are not designed to bear the
weight of the inverter.
● When you need to temporally place the inverter on the ground, use foam,
paper, or other protection material to prevent damage to its cover.
● Do not lift or hoist the inverter using the bottom holes of the handles to
prevent the handles from cracking.
Figure 4-14 Lifting positions
Installing the Inverter
Step 1 Mount the inverter on the mounting bracket.
Step 2 Tighten the two screws at the bottom of the inverter.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
29
Figure 4-15 Installation
----End
Supplementary Notes
If the inverter is installed in a high position, you can hoist it.
Figure 4-16 Hoisting the inverter
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
4 Installation
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
30
5 Electrical Connections
5.1 Precautions
D ANGER
Before connecting cables, ensure that all DC switches on the inverter are OFF.
Otherwise, the high voltage of the inverter may result in electric shocks.
WARNING
● The device damage caused by incorrect cable connections is beyond the
warranty scope.
● Only qualified technicians can perform operations about electrical connection.
● Wear proper PPE at all time when connecting cables.
NO TE
The cable colors shown in the electrical connection diagrams provided in this chapter are
for reference only. Select cables in accordance with local cable specifications (green-and-
yellow cables are only used for protective earthing).
5.2 Crimping an OT or DT Terminal
Requirements for the OT or DT Terminal
●
If a copper cable is used, use copper wiring terminals.
●
If a copper-clad aluminum cable is used, use copper wiring terminals.
●
If an aluminum alloy cable is used, use copper-aluminum transition wiring
terminals, or aluminum wiring terminals along with copper-aluminum
transition spacers.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
31
● Do not connect aluminum wiring terminals to the AC terminal block. Otherwise
the electrochemical corrosion will occur and affect the reliability of cable
connections.
● Comply with the IEC61238-1 requirements when using copper-aluminum
transition wiring terminals, or aluminum wiring terminals along with copper-
aluminum transition spacers.
● If copper-aluminum transition spacers are used, pay attention to the front and
rear sides. Ensure that the aluminum sides of spacers are in contact with
aluminum wiring terminals, and copper sides of spacers are in contact with the
AC terminal block.
Figure 5-1 Requirements for the OT/DT terminal
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
32
Crimping an OT or DT Terminal
NO TICE
● Pay attention not to scratch the core wire when stripping a cable.
● The cavity formed after the conductor crimp strip of the OT or DT terminal is
crimped must wrap the core wires completely. The core wires must contact the
OT or DT terminal closely.
● Wrap the wire crimping area with a heat shrink tubing or PVC insulation tape.
The heat shrink tubing is used as an example.
● When using a heat gun, protect devices from being scorched.
Figure 5-2 Crimping an OT terminal
(1) Cable
(2) Core
(3) Heat shrink tubing
(4) OT terminal
(5) Hydraulic pliers
(6) Heat gun
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
33
Figure 5-3 Crimping a DT terminal
(1) Cable
(2) Core
(3) Heat shrink tubing
(4) DT terminal
(5) Hydraulic pliers
(6) Heat gun
5.3 Opening the Maintenance Compartment Door
Precautions
NO TICE
● Do not open the host panel cover of the inverter.
● Before opening the maintenance compartment door, ensure that no electrical
connections are made for the inverter on the AC or DC side.
● If you need to open the maintenance compartment door in rainy or snowy
days, take protective measures to prevent rain or snow entering the
maintenance compartment. If unavoidable, do not open the maintenance
compartment door.
● Do not leave unused screws in the maintenance compartment.
Procedure
Step 1 Partially loosen the two screws on the maintenance compartment door.
Step 2 Open the maintenance compartment door and install a support bar.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
34
Figure 5-4 Opening the maintenance compartment door
Step 3 Remove the accessories that are bound in the maintenance compartment for
future use.
NO TE
For some models, a three-hole rubber plug is bound in the maintenance compartment.
After removing the rubber plug, save it properly for future use
Figure 5-5 Removing the accessories from the maintenance compartment
(1) Crimping modules
----End
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
35
5.4 (Optional) Replacing the Crimping Module
Procedure
NO TE
If the AC output power cable has a single core, replace the crimping module.
Step 1 Replace the crimping module.
Figure 5-6 Replacing the crimping module
----End
5.5 (Optional) Installing the Power Cable of the
Tracking System
Precautions
NO TICE
● A switch-disconnector-fuse or fuse-switch-disconnector with a voltage of no
less than 800 V, current of 16 A, and protection type of gM needs to be
installed between the inverter and the tracker controller for protection.
● The cable between the wiring terminal on the power cable and the switch-
disconnector-fuse or fuse-switch-disconnector should be less than or equal to
2.5 m.
● Connect the power cable of the tracking system before the AC output power
cable. Otherwise, reworking will be caused.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
36
Recommended: dual-layer three-core outdoor copper cable with a conductor
cross-sectional area of 10 mm2
Procedure
Step 1 Connect the power cable of the tracking system to the terminal block.
Figure 5-7 Cable connection
----End
5.6 Connecting the AC Output Power Cable
Precautions
A three-phase AC switch should be installed on the AC side of the inverter. To
ensure that the inverter can safely disconnect itself from the power grid when an
exception occurs, select a proper overcurrent protection device in compliance with
local power distribution regulations.
WARNING
Do not connect loads between the inverter and the AC switch.
The inverter is integrated with a comprehensive residual current detection unit to
distinguish fault current from residual current. Upon detecting that the residual
current exceeds the threshold, the inverter immediately disconnects from the
power grid.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
37
Cable Connection Precautions
NO TICE
● The cable outer diameter can be measured using the ruler sticker in the
maintenance compartment.
● Ensure that the cable jacket is in the maintenance compartment.
● Ensure that the AC output power cable is secured. Failing to do so may cause
the solar inverter to malfunction or damage to its terminal block by issues such
as overheating.
●
The ground point on the enclosure is preferred to connect to the PE cable for
the inverter.
●
The PE point in the maintenance compartment is used for connecting to the
PE cable included in the multi-core AC power cable.
●
There are two ground points on the chassis shell and you only need either of
them.
●
It is recommended that the PE cable of the inverter be connected to a nearby
ground point. For a system with multiple inverters connected in parallel,
connect the ground points of all inverters to ensure equipotential connections
to ground cables.
Cable Specifications
●
If you connect a ground cable to the ground point on the chassis shell, you
are advised to use a three-core (L1, L2, and L3) outdoor cable or three single-
core outdoor cables.
●
If you connect a ground cable to the ground point in the maintenance
compartment, you are advised to use a four-core (L1, L2, L3, and PE) outdoor
cable.
●
You need to prepare the OT or DT terminal that matches the cable.
Table 5-1 AC power cable specifications
Cable Type
Conductor Cross-
Sectional Area
Cable Outer Diameter
Copper-core cable
50–240 mm2
● Multi-core cable: 24–
66 mm
● Single-core cable: 14–
32 mm
Copper-clad aluminum
cable and aluminum
alloy cable
● Multi-core cable: 70–
240 mm2
● Single-core cable: 70–
240 mm2
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
38
The cable diameter must comply with local cable standards. The factors that affect cable
selection include the rated current, cable type, routing mode, ambient temperature, and
maximum expected line loss.
Table 5-2 PE cable specifications
Conductor Cross-Sectional Area S of
the AC Power Cable (Unit: mm2)
Conductor Cross-Sectional Area SP of
the PE Cable (Unit: mm2)
S > 35
SP ≥ S/2
The specifications are valid only if the conductors of the PE cable and AC power
cable use the same material. If the materials are different, ensure that the
conductor cross-sectional area of the PE cable produces a conductance
equivalent to that of the cable specified in this table. The specifications of the
PE cable are subject to this table or calculated according to IEC 60364-5-54.
Connecting the PE Cable
Step 1 Secure the PE cable using the ground screw.
Figure 5-8 Cable connection
Step 2 (Optional) Apply silica gel or paint on the ground terminal to protect it against
corrosion.
----End
Connecting the AC Output Power Cable (Multi-core)
Step 1 Connect the AC cable to the terminal block.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
39
Sufficient slack should be provided in the PE cable to ensure that the last cable
bearing the force is the PE cable when the AC output power cable bears pulling
force due to force majeure.
Figure 5-9 Cable connection
----End
Connecting the AC Output Power Cable (Single-core)
Step 1 Connect the AC cable to the terminal block.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
40
Figure 5-10 Cable connection
----End
5.7 Installing the DC Input Power Cable
Precautions
D ANGER
● Before connecting the DC input power cable, ensure that the DC voltage is
within the safe range (lower than 60 V DC) and that the three DC switches on
the inverter are set to OFF. Failure to do so may result in electric shocks.
● When the inverter operates in grid-tied mode, do not perform maintenance or
operations on the DC circuit, such as connecting or disconnecting a PV string or
a PV module in the PV string. Failure to do so may cause electric shocks or
arcing, which may also cause fire.
WARNING
Ensure that the following conditions are met. Otherwise, the inverter may be
damaged, or even a fire could happen.
● The open-circuit voltage of each PV string must always be 1500 V DC or lower.
● The polarities of electric connections are correct on the DC input side. The
positive and negative terminals of a PV module connect to corresponding
positive and negative DC input terminals of the inverter.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
41
● Ensure that the PV module output is well insulated to ground.
● The PV strings connecting to the same MPPT circuit should contain the same
number of identical PV modules.
● The solar inverter does not support full parallel connection for PV strings (full
parallel connection: PV strings connect to one another in parallel outside the
solar inverter and then connect to the solar inverter separately).
● During the installation of PV strings and the inverter, the positive or negative
terminals of PV strings may be short-circuited to ground if the power cable is
not properly installed or routed. In this case, an AC or DC short circuit may
occur and damage the inverter. The caused device damage is not covered under
any warranty.
Terminal Description
The inverter provides 18 DC input terminals, which are controlled by its three DC
switches. DC SWITCH 1 controls DC input terminals 1–6, DC SWITCH 2 controls DC
input terminals 7–12, and DC SWITCH 3 controls DC input terminals 13–18.
Figure 5-11 DC terminals
Requirements for selecting DC input terminals:
1.
Evenly distribute the DC input power cables on the DC input terminals
controlled by the three DC switches.
2.
Maximize the number of connected MPPT circuits.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
42
Wiring Description of Y-branch Connectors
NO TICE
● Y-branch connectors can be purchased from Huawei or the manufacturers
based on the following recommended models: If the rated current of the fuse
of the Y-branch connector is 15 A, the recommended model is 904095944
(Luxshare) or A040959443039 (Comlink); if the rated current of the fuse of the
Y-branch connector is 20 A, the recommended model is 904095945 (Luxshare)
or A040959453039 (Comlink).
● Do not use Y-branch connectors that are not recommended.
● When connecting cables to recommended Y-branch connectors, ensure that the
connectors to be paired match each other and are from the same
manufacturer. Otherwise, the contact resistance of the connectors may exceed
the allowed value. In this case, the connectors may be heated and oxidized,
which may cause faults.
● When the Y-branch connector is used with the MC4 EVO2 contacts, you are
advised to use the 32.6020-22100-HZ (Staubli) crimping tool. You can also use
the PV-CZM-22100 (Staubli) crimping tool. When choosing PV-CZM-22100
(Staubli), do not use the locator. Otherwise, the metal contacts would be
damaged.
● Ensure that the locking nuts of all connectors are tightened.
● Do not bind more than three fuse enclosures together. Otherwise, the fuses and
their enclosures may be damaged due to overheating. It is recommended that a
clearance of 10 mm or more be reserved between fuse enclosures. You are
advised not to bind the fuse enclosures with other heat emitting conductors.
● Do not place the Y-branch connector harness on the ground. A safe distance
must be reserved between the Y-branch connector harness and the ground to
avoid impact caused by water on the ground to the harness.
● It is recommended that Y-branch connectors be connected from the PV string
side or connected to the solar inverter with a safe distance of at least 4 m and
bound to the PV support.
● The DC input terminals of the solar inverter are prone to damage under stress.
When Y-branch connectors are connected to the solar inverter, bind and secure
the connectors to prevent the DC input terminals from bearing stress. For
details, see A Securing Y-Branch Connectors.
Wiring rules:
1.
A maximum of one set of Y-branch connectors can be used for each MPPT.
2.
The PV+ on the inverter side must be connected to the PV+ on the PV string
side, and the PV– on the inverter side must be connected to the PV– on the
string side.
3.
Preferentially and evenly connect the Y-branch connectors to the MPPTs
controlled by DC SWITCH 2 or DC SWITCH 3.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
43
Number of Y-
branch
Connector
Sets
Recommended
MPPT to Be
Connected
Number of Y-
branch
Connector
Sets
Recommended
MPPT to Be
Connected
1
MPPT9
2
MPPT6 and MPPT9
3
MPPT6, MPPT7 and
MPPT9
4
MPPT4, MPPT6,
MPPT7, and MPPT9
5
MPPT4, MPPT6,
MPPT7, MPPT8,
and MPPT9
6
MPPT4, MPPT5,
MPPT6, MPPT7,
MPPT8, and MPPT9
7
MPPT3, MPPT4,
MPPT5, MPPT6,
MPPT7, MPPT8,
and MPPT9
8
MPPT1, MPPT3,
MPPT4, MPPT5,
MPPT6, MPPT7,
MPPT8, and MPPT9
9
MPPT1, MPPT2,
MPPT3, MPPT4,
MPPT5, MPPT6,
MPPT7, MPPT8,
and MPPT9
N/A
N/A
Figure 5-12 Connecting Y-branch connectors to the PV strings
(recommended)
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
44
Figure 5-13 Connecting Y-branch connectors to the solar inverter with a safe
distance (recommended)
Figure 5-14 Connecting Y-branch connectors to the solar inverter
Cable Specifications
Cable Type
Conductor Cross-
sectional Area (Unit:
mm2)
Cable Outer Diameter
(Unit: mm)
PV cable that meets the
1500 V standard
4–6
4.7–6.4
NO TICE
Cables with high rigidity, such as armored cables, are not recommended, because
poor contact may be caused by the bending of cables.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
45
Use the MC4 EVO2 PV connectors delivered with the inverter. If the PV connectors
are lost or damaged, purchase the connectors of the same model. The device
damage caused by incompatible PV connectors is beyond the warranty scope.
Step 1 Install the DC input power cable.
NO TICE
● The DC voltage measurement range of the multimeter must be at least 1500 V.
● If the voltage is a negative value, the DC input polarity is incorrect and needs
correction.
● If the voltage is greater than 1500 V, too many PV modules configured to the
same string. Remove some PV modules.
Figure 5-15 Cable connection
----End
5.8 Installing the Communications Cable
Precautions
When routing communications cables, separate communications cables from
power cables to prevent communication from being affected.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
46
Pin Definitions of Communications Ports
Figure 5-16 Communications ports
Port
Pin
Definition
Pin
Definition
Description
RS485-1
1
RS485A IN, RS485
differential signal+
2
RS485A OUT, RS485
differential signal+
Used for cascading
inverters or
connecting to
devices such as the
SmartLogger.
3
RS485B IN, RS485
differential signal–
4
RS485B OUT, RS485
differential signal–
PE
5
PE, shielding ground
6
PE, shielding ground
-
RS485-2
7
RS485A, RS485
differential signal+
8
RS485B, RS485
differential signal–
Used for connecting
to RS485 slave
devices.
Procedure
Step 1 Install the communications cable.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
47
Figure 5-17 Cable connection (4–8 mm four-hole rubber plug)
NO TICE
Block unused cable holes using plugs and tighten cable glands.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
48
Figure 5-18 Cable connection (4–8 mm two-hole rubber plug)
NO TICE
● If three communications cables are to be connected, use the three-hole rubber
plug that is bound in the maintenance compartment.
● Block unused cable holes using plugs and tighten cable glands.
----End
5.9 Closing the Maintenance Compartment Door
Procedure
Step 1 Adjust the support bar, close the maintenance compartment door and tighten the
two screws on the door.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
49
Figure 5-19 Closing the door
----End
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
5 Electrical Connections
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
50
6 System Commissioning
6.1 Check Before Power-on
1.
The inverter is installed correctly and securely.
2.
Check that the DC switches and downstream AC output switch are OFF.
3.
Check that all ground cables are connected securely and reliably.
4.
All AC output power cables are connected correctly and securely, without
open circuits or short circuits.
5.
All DC input power cables are connected correctly and securely, without open
circuits or short circuits.
6.
The communications cable is connected correctly and securely.
7.
Check that the maintenance compartment interior is clean and tidy, without
foreign matter.
8.
The maintenance compartment door is closed and the door screws are
tightened.
9.
Idle DC input terminals are sealed.
10. Idle USB ports are plugged with waterproof plugs.
6.2 System Power-On
Precautions
NO TICE
● Before turning on the AC switch between the inverter and the power grid,
check that the AC voltage is within the specified range using a multimeter.
● If the solar inverter has not been running for more than half a year after being
mounted, it must be checked and tested by professionals before being put into
operation.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
6 System Commissioning
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
51
Step 1 Turn on the AC switch between the inverter and the grid.
NO TICE
If you perform Step 2 before Step 1, the inverter reports a fault about abnormal
shutdown. The inverter can start normally after the fault is automatically cleared.
Step 2 Turn the DC switches at the bottom of the inverter to ON.
----End
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
6 System Commissioning
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
52
7 Man-Machine Interactions
7.1 Operations with the App
7.1.1 App Introduction
Functions
●
The FusionSolar app is recommended when the SUN2000 is connected to the
FusionSolar hosting cloud. The SUN2000 app is recommended when the
SUN2000 is connected to other management systems.
●
The SUN2000 or FusionSolar app (app for short) is a mobile phone app that
communicates with the SUN2000 over a WLAN/Bluetooth module or a USB
data cable to allow for querying alarms, setting parameters, and performing
routine maintenance as an easy-to-use maintenance platform.
Connection Mode
After the DC or AC side of the SUN2000 is powered on, you can connect the app
to it through a WLAN module, a Bluetooth module or a USB data cable.
NO TICE
● Over a WLAN module: The USB-Adapter2000-C WLAN module is supported.
● Over a Bluetooth module: The USB-Adapter2000-B Bluetooth module is
supported.
● Over a USB data cable: The USB 2.0 port is supported. Use the USB data cable
delivered with the mobile phone.
● Mobile phone operating system: Android 4.0 or later.
● Recommended phone brands: Huawei and Samsung.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
53
Figure 7-1 Connection over a WLAN module or a Bluetooth module
(A) SUN2000
(B) WLAN module or Bluetooth module
(C) Mobile phone
Figure 7-2 Connection over a USB data cable
(A) SUN2000
(B) USB data cable
(C) Mobile phone
NO TICE
● When you use the SUN2000 app to set parameters for the inverter, setting
items on certain parameter setting screens are not displayed if the AC switch
between the inverter and the power grid is turned on but the three DC switches
on the inverter are not in the ON position. Switch the three DC switches to the
ON position and then reset relevant parameters.
● If you change the grid code, some parameters may be restored to factory
defaults. After the grid code is changed, check whether the previously set
parameters are affected.
● Delivering a reset, factory reset, shutdown, or upgrade command to the solar
inverters may cause power grid connection failure, which affects the energy
yield.
● Only professionals are allowed to set the grid parameters, protection
parameters, feature parameters, and power adjustment parameters of the solar
inverters. If the grid parameters, protection parameters, and feature parameters
are incorrectly set, the solar inverters may not connect to the power grid. If the
power adjustment parameters are incorrectly set, the solar inverters may not
connect to the power grid as required. In these cases, the energy yield will be
affected.
NO TE
●
Configurable parameters vary depending on the grid code. The actual screen prevails.
●
The parameter names, value ranges, and default values are subject to change. The
actual display prevails.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
54
7.1.2 Downloading and Installing the App
●
FusionSolar app: Log in to Google Play, search for FusionSolar, and download
the app installation package. You can also scan the QR code to download the
installation package.
●
SUN2000 app: Log in to Huawei AppGallery (https://appstore.huawei.com),
search for SUN2000, and download the app installation package. You can also
scan the QR code (https://solar.huawei.com/~/media/Solar/APP/
SUN2000.apk) to download the installation package.
QR code:
7.1.3 Logging In to the App
Prerequisites
●
The DC or AC side of the SUN2000 has been energized.
●
Connection over a WLAN module or a Bluetooth module:
a.
The WLAN module or Bluetooth module is connected to the USB port at
the bottom of the SUN2000.
b.
The WLAN or Bluetooth function is enabled.
c.
Keep the mobile phone within 5 m from the SUN2000. Otherwise, the
communication between them would be affected.
●
Connection over a USB cable:
a.
The USB data cable is connected from the USB port at the bottom of the
SUN2000 to the port on the mobile phone.
b.
If the USB data cable is successfully connected, the message Connected
to USB Accessory will pop up on the phone. Otherwise, the cable is not
connected.
Procedure
Step 1 Run the app and select a connection mode.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
55
The screenshots in this document correspond to the SUN2000 app 3.2.00.003 (Android)
and FusionSolar app 2.5.7 (Android).
●
When the WLAN connection is used, scan the QR code of the WLAN module to access
the login screen.
●
When the WLAN connection is used, the initial name of the WLAN hotspot is Adapter-
WLAN module SN, and the initial password is Changeme. Use the initial password
upon first power-on and change it immediately after login. To ensure account security,
change the password periodically and keep the new password in mind. Not changing
the initial password may cause password disclosure. A password left unchanged for a
long period of time may be stolen or cracked. If a password is lost, devices cannot be
accessed. In these cases, the user is liable for any loss caused to the PV plant.
●
When the Bluetooth connection is used, the connected Bluetooth device is named after
last 8 digits of the SN barcode+HWAPP.
●
After you select Use by default for this USB accessory, a message that asks you to
confirm the USB access will not appear if you log in to the app again without removing
the USB data cable.
●
(Scenario in which the SUN2000 is connected to the FusionSolar hosting
cloud) Run the FusionSolar app and access the Device Commissioning
screen.
Figure 7-3 Selecting a connection mode (with network access)
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
56
Figure 7-4 Selecting a connection mode (without network access)
●
(Scenario in which the SUN2000 is connected to other management systems)
Run the SUN2000 app and access the operation screen.
Figure 7-5 Selecting a connection method
Step 2 Select a login user and enter the login password to access the quick settings
screen or the main menu screen.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
57
● The login password is the same as that for the SUN2000 connected to the app
and is used only when the SUN2000 connects to the app.
● The initial passwords for Common User, Advanced User, and Special User are
all 00000a.
● Use the initial password upon first power-on and change it immediately after
login. To ensure account security, change the password periodically and keep
the new password in mind. Not changing the initial password may cause
password disclosure. A password left unchanged for a long period of time may
be stolen or cracked. If a password is lost, devices cannot be accessed. In these
cases, the user is liable for any loss caused to the PV plant.
● During the login, if five consecutive invalid password entries are made (the
interval between two consecutive entries is less than 2 minutes), the account
will be locked for 10 minutes. The password should consist of six characters.
● If you log in to the SUN2000 app after the device connects to the app for the
first time or factory defaults are restored, the quick settings screen will be
displayed. If you do not set SUN2000 basic parameters on the quick settings
screen, the screen is still displayed when you log in to the app next time.
● To set SUN2000 basic parameters on the quick settings screen, switch to
Advanced User. If you log in as Common User or Special User, enter the
password of the advanced user to access the Quick Settings screen.
Figure 7-6 Login
NO TE
Set the correct grid code based on the application area and scenario of the SUN2000. On
the quick settings screen, you can set basic parameters. After settings, you can modify the
parameters by tapping Settings on the main menu screen.
----End
7.1.4 Operations Related to the Advanced User
If you log in to the app asAdvanced User, you can set grid parameters, protection
parameters, and feature parameters for the SUN2000.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
58
7.1.4.1 Setting Grid Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Grid Parameters to access the parameters
setting screen.
Figure 7-7 Grid parameters (advanced user)
----End
Parameters
No.
Parameter
Description
1
Grid Code
Set this parameter based on the grid code of the country or
region where the inverter is used and the inverter application
scenario.
2
Isolation settings
Set the working mode of the inverter based on the grounding
status at DC side and the connection to the power grid.
7.1.4.2 Setting Protection Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Protect Parameters to go to the parameter
setting screen.
Figure 7-8 Protection parameters (advanced user)
----End
Parameter
No.
Parameter
Description
1
Insulation resistance
protection threshold (MΩ)
To ensure device safety, the inverter detects the insulation
resistance of the input side with respect to ground when it
starts a self-check. If the detected value is less than the
preset value, the inverter does not connect to the grid.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
59
7.1.4.3 Setting Feature Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Feature Parameters to access the settings
screen.
Figure 7-9 Feature parameters (advanced user)
----End
Parameters
No.
Parameter
Description
Remarks
1
MPPT multi-peak
scanning
When the inverter is used in
scenarios where PV strings are
greatly shaded, set this parameter
to Enable, and then the inverter
will perform MPPT scanning at
regular intervals to locate the
maximum power.
-
2
MPPT multi-peak
scan interval (min)
Specifies the MPPT scanning
interval.
This parameter is displayed
when MPPT multi-peak
scanning is set to Enable.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
60
RCD refers to the residual current
of the inverter to the ground. To
ensure device and personal safety,
RCD should be limited to the
specified value in the standard. If
an AC switch with a residual
current detection function is
installed outside the inverter, this
function should be enabled to
reduce the residual current
generated when the inverter is
running, thereby preventing the
AC switch from misoperations.
-
4
Night-time
reactive power
output
In some specific application
scenarios, a power grid company
requires that the inverter can
perform reactive power
compensation at night to ensure
that the power factor of the local
power grid meets requirements.
This parameter is displayed
when Isolation settings is set
to Input ungrounded, with
TF.
5
PID protection at
night
When the inverter outputs
reactive power at night and this
parameter is set to Enable, the
inverter will shut down
automatically if it detects
abnormal status of the PID
compensation.
-
6
Power quality
optimization mode
If this parameter is set to Enable,
the inverter output current
harmonics will be optimized.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
61
PV module type
This parameter is used to set
different types of PV modules and
the shutdown time of the
concentration PV module. If the
concentration PV modules are
shaded, the power drops
drastically to 0 and the inverter
shuts down. The energy yield
would be affected since it takes
too long for the power to resume
and inverter to restart. The
parameter does not need to be
set for crystalline silicon and filmy
PV modules.
● If this parameter is set to
Crystalline silicon or Film,
the inverter automatically
detects the power of PV
modules when they are
shaded and shuts down if
the power is too low.
● When concentration PV
modules are used:
–
If this parameter is set to
CPV 1, the inverter can
quickly restart in 60
minutes if the input
power of PV modules
drops drastically due to
shading.
–
If this parameter is set to
CPV 2, the inverter can
quickly restart in 10
minutes if the input
power of PV modules
drops drastically due to
shading.
8
Built-in PID
compensation
direction
When the external PID module
compensates the PID voltage for
the PV system, set Built-in PID
compensation direction to the
actual compensation direction of
the PID module so that the
inverter can output reactive
power at night.
-
9
String connection
mode
Specifies the connection mode of
PV strings.
● When PV strings connect to
the inverter separately (All
PV strings separated), there
is no need to set this
parameter. The inverter can
automatically detect the
connection mode of the PV
strings.
● When PV strings connect to
one another in parallel
outside the inverter and
then connect to it
independently (All PV
strings connected), set this
parameter to All PV strings
connected.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
62
The standards of certain countries
and regions require that the
inverter must shut down after the
communication is interrupted for
a certain time.
If Automatic OFF due to
communication interrupted is
set to Enable and the inverter
communication is interrupted
for a specified time (set by
Communication interruption
duration), the inverter will
automatically shut down.
11
Automatic ON due
to communication
resumed
If this parameter is set to Enable,
the inverter automatically starts
after communication recovers. If
this parameter is set to Disable,
the inverter needs to be started
manually after communication
recovers.
This parameter is displayed
when Automatic OFF due to
communication interrupted is
set to Enable.
12
Communication
interruption
duration (min)
Specifies the duration for
determining communication
interruption. Used for automatic
shutdown for protection in case of
communication interruption.
-
13
Soft start/boot
time (s)
Specifies the duration for the
power to gradually increase when
the inverter starts.
-
14
Shutdown gradient
(%/s)
Specifies the power change speed
when the inverter shuts down.
-
15
Night-time
hibernation
The inverter monitors PV strings
at night. If this parameter is set to
Enable, the monitoring function
of the inverter will hibernate at
night to reduce power
consumption.
-
16
MBUS
communication
For inverters that support RS485
communication and MBUS
communication, you are advised
to set this parameter to Disable
to reduce power consumption.
-
17
Delay upgrade
This parameter is mainly used in
the upgrade scenarios where the
PV power supply is disconnected
at night due to no sunlight or
unstable at dawn or dusk due to
poor sunlight.
After the inverter starts to
upgrade, if Delay upgrade is
set to Enable, the upgrade
package is loaded first. After
the PV power supply recovers
and the activation conditions
are met, the inverter
automatically activates the
upgrade.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
63
If this parameter is set to Enable,
the RS485-2 port can be used. If
the port is not used, you are
advised to set this parameter to
Disable to reduce power
consumption.
-
19
Duration for
determining short-
time grid
disconnection (ms)
The standards of certain countries
and regions require that the
inverter should not disconnect
from the power grid if the power
grid experiences a short-time
failure. After the fault is rectified,
the inverter output power needs
to be quickly restored.
-
7.1.5 Operations Related to the Special User
If you log in to the app as Special User, you can set grid parameters, protection
parameters, feature parameters, and power adjustment parameters for the
SUN2000.
7.1.5.1 Setting Grid Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Grid Parameters to access the parameters
setting screen.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
64
Figure 7-10 Power grid parameters (special user)
----End
Parameters
No.
Parameter
Description
1
Grid Code
Set this parameter based on the grid code of the country
or region where the inverter is used and the inverter
application scenario.
2
Isolation settings
Set the working mode of the inverter based on the
grounding status at DC side and the connection to the
power grid.
3
Output mode
Specifies whether the inverter output has a neutral wire
based on the application scenario.
4
Automatically start upon
grid recovery
Specifies whether to allow the inverter to automatically
start after the power grid recovers.
5
Grid connected recovery
time from grid faults (s)
Specifies the time after which the inverter begins
restarting after the power grid recovers.
6
Startup voltage lower
threshold of grid
connection (V)
According to the standards of certain countries and
regions, after the inverter is powered on for the first time
for grid connection, if the power grid voltage is lower
than Startup voltage lower threshold of grid
connection, the inverter is not allowed to connect to the
grid.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
65
Startup frequency upper
threshold of grid
connection (Hz)
According to the standards of certain countries and
regions, after the inverter is powered on for the first time
for grid connection, if the power grid voltage is higher
than Startup frequency upper threshold of grid
connection, the inverter is not allowed to connect to the
grid.
8
Startup frequency lower
threshold of grid
connection (Hz)
According to the standards of certain countries and
regions, after the inverter is powered on for the first time
for grid connection, if the power grid voltage is lower
than Startup frequency lower threshold of grid
connection, the inverter is not allowed to connect to the
grid.
9
Grid reconnection voltage
upper limit (V)
The standards of certain countries and regions require
that after the inverter shuts down for protection due to a
fault, if the power grid voltage is higher than Grid
reconnection voltage upper limit, the inverter is not
allowed to reconnect to the grid.
10
Grid reconnection voltage
lower limit (V)
The standards of certain countries and regions require
that after the inverter shuts down for protection due to a
fault, if the power grid voltage is lower than Grid
reconnection voltage lower limit, the inverter is not
allowed to reconnect to the grid.
11
Grid reconnection frequency
upper limit (Hz)
The standards of certain countries and regions require
that after the inverter shuts down for protection due to a
fault, if the power grid frequency is higher than Grid
reconnection frequency upper limit, the inverter is not
allowed to reconnect to the grid.
12
Grid reconnection frequency
lower limit (Hz)
The standards of certain countries and regions require
that after the inverter shuts down for protection due to a
fault, if the power grid frequency is lower than Grid
reconnection frequency lower limit, the inverter is not
allowed to reconnect to the grid.
13
Reactive power
compensation (cosφ-P)
trigger voltage (%)
Specifies the voltage threshold for triggering reactive
power compensation based on the cosφ-P curve.
14
Reactive power
compensation (cosφ-P) exit
voltage (%)
Specifies the voltage threshold for exiting reactive power
compensation based on the cosφ-P curve.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
66
7.1.5.2 Setting Protection Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Protect Parameters to go to the parameter
setting screen.
Figure 7-11 Protection parameters (special user)
----End
Parameters
No.
Parameter
Description
1
Voltage unbalance protection
threshold (%)
Specifies the inverter protection threshold when the
power grid voltage is unbalanced.
2
Phase angle offset protection
The standards of certain countries and regions require
that the inverter needs to be protected when the
phase angle offset of the power grid three phases
exceeds a certain value.
3
10-min overvoltage protection
threshold (V)
Specifies the 10-minute overvoltage protection
threshold.
4
10-min overvoltage protection
duration (ms)
Specifies the 10-minute overvoltage protection
duration.
5
Level-N overvoltage protection
threshold (V)
Specifies the level-N grid overvoltage protection
threshold.
6
Level-N overvoltage protection
duration (ms)
Specifies the level-N grid overvoltage protection
duration.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
67
protection threshold (V)
Specifies the level-N grid undervoltage protection
threshold.
8
Level-N undervoltage
protection duration (ms)
Specifies the level-N grid undervoltage protection
duration.
9
Level-N overfrequency
protection threshold (Hz)
Specifies the level-N grid overfrequency protection
threshold.
10
Level-N overfrequency
protection duration (ms)
Specifies the level-N grid overfrequency protection
duration.
11
Level-N underfrequency
protection threshold (Hz)
Specifies the level-N grid underfrequency protection
threshold.
12
Level-N underfrequency
protection duration (ms)
Specifies the level-N grid underfrequency protection
duration.
7.1.5.3 Setting Feature Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Feature Parameters to access the settings
screen.
Figure 7-12 Feature parameters (special user)
----End
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
68
LVRT is short for low voltage ride-through.
When the grid voltage is abnormally low for a
short time, the inverter cannot disconnect from
the power grid immediately and has to work for
some time.
-
2
Threshold for
triggering
LVRT (V)
Specifies the threshold for triggering LVRT. The
threshold settings should meet the local grid
standard.
This parameter is
displayed when LVRT
is set to Enable.
3
LVRT reactive
power
compensation
factor
During LVRT, the solar inverter needs to
generate positive-sequence reactive power to
support the power grid. This parameter is used
to set the positive-sequence reactive power
generated by the solar inverter.
For example, if you set LVRT reactive power
compensation factor to 2, the positive-
sequence reactive current generated by the
solar inverter is 20% of the rated current when
the AC voltage decreases by 10% during LVRT.
4
LVRT
compensation
power factor
of reactive
power in
negative
sequence
During LVRT, the solar inverter needs to
generate negative-sequence reactive power to
support the power grid. This parameter is used
to set the negative-sequence reactive power
generated by the solar inverter.
For example, if you set LVRT compensation
power factor of reactive power in negative
sequence to 2, the negative-sequence reactive
current generated by the solar inverter is 20%
of the rated current when the AC voltage
decreases by 10% during LVRT.
5
Percentage of
LVRT reactive
current
limiting
During LVRT, the solar inverter needs to limit
the reactive current.
For example, if you set Percentage of LVRT
reactive current limiting to 50, the reactive
current upper limit of the solar inverter is 50%
of the rated current during LVRT.
6
Threshold of
LVRT zero-
current mode
When Zero current due to power grid fault is
enabled, if the power grid voltage is less than
the value of Threshold of LVRT zero-current
mode during LVRT, the zero current mode is
used. Otherwise, the mode configured in LVRT
mode is used.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
69
Sets LVRT mode. The options are Zero-current
mode, Constant current mode, Reactive
power priority mode, and Active power
priority mode.
8
LVRT
characteristic
curve
Specifies the low voltage ride-through
capability of the inverter.
9
HVRT
HVRT is short for high voltage ride-through.
When the grid voltage is abnormally high for a
short time, the inverter cannot disconnect from
the power grid immediately and has to work for
some time.
-
10
Threshold for
triggering
HVRT (V)
Specifies the threshold for triggering HVRT. The
threshold settings should meet the local grid
standard.
This parameter is
displayed when HVRT
is set to Enable.
11
HVRT reactive
power
compensation
factor
During HVRT, the solar inverter needs to
generate positive-sequence reactive power to
support the power grid. This parameter is used
to set the positive-sequence reactive power
generated by the solar inverter.
For example, if you set HVRT reactive power
compensation factor to 2, the positive-
sequence reactive current generated by the
solar inverter is 20% of the rated current when
the AC voltage increases by 10% during HVRT.
12
HVRT
compensation
power factor
of reactive
power in
negative
sequence
During HVRT, the solar inverter needs to
generate negative-sequence reactive power to
support the power grid. This parameter is used
to set the negative-sequence reactive power
generated by the solar inverter.
For example, if you set HVRT compensation
power factor of reactive power in negative
sequence to 2, the negative-sequence reactive
current generated by the solar inverter is 20%
of the rated current when the AC voltage
increases by 10% during HVRT.
13
Grid voltage
protection
shield during
VRT
Specifies whether to shield the undervoltage
protection function during LVRT or HVRT.
This parameter is
displayed when LVRT
or HVRT is set to
Enable.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
70
Specifies the LVRT/HVRT recovery threshold.
● This parameter is
displayed when
LVRT or HVRT is
set to Enable.
● LVRT recovery
threshold =
Threshold for
triggering LVRT +
VRT exit hysteresis
threshold
● HVRT recovery
threshold =
Threshold for
triggering HVRT +
VRT exit hysteresis
threshold
15
Grid voltage
jump
triggering
threshold (%)
Specifies the LVRT or HVRT threshold for
triggering a transient voltage jump of a power
grid. A transient voltage jump indicates that the
inverter cannot immediately disconnect from
the power grid when the power grid is
abnormal due to transient changes.
-
16
Zero current
due to power
grid fault
Certain countries and regions have
requirements on the output current during
high/low voltage ride-through. In this case, set
this parameter to Enable. After this parameter
is set to Enable, the output current is less than
10% of the rated current during high/low
voltage ride-through.
This parameter is
displayed when LVRT
or HVRT is set to
Enable.
17
Active
islanding
protection
Specifies whether to enable the active islanding
protection function.
-
18
Automatic
OFF due to
communicati
on
interrupted
The standards of certain countries and regions
require that the inverter must shut down after
the communication is interrupted for a certain
time.
-
19
Automatic
ON due to
communicati
on resumed
If this parameter is set to Enable, the inverter
automatically starts after communication
recovers. If this parameter is set to Disable, the
inverter needs to be started manually after
communication recovers.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
71
Specifies the duration for determining
communication interruption. Used for
automatic shutdown for protection in case of
communication interruption.
-
21
Soft start/
boot time (s)
Specifies the duration for the power to
gradually increase when the inverter starts.
-
22
Soft start
time after
grid failure
(s)
Specifies the time for the power to gradually
increase when the inverter restarts after the
power grid recovers.
-
23
TCP
heartbeat
interval (s)
Specifies the TCP link timeout period for the
solar inverter to connect to the management
system.
-
24
TCP frame
length
Specifies the maximum length of the TCP frame
sent by the northbound device to the solar
inverter.
-
25
Heartbeat
period at
application
layer (min)
Specifies the timeout period for the solar
inverter to connect to the management system.
-
7.1.5.4 Setting Power Adjustment Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Power Adjustment to go to the parameter
setting screen.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
72
Figure 7-13 Power adjustment parameters (special user)
----End
Parameters
No.
Parameter
Description
Remarks
1
Remote power
schedule
If this parameter is set to Enable,
the inverter responds to the
scheduling instruction from the
remote port. If this parameter is
set to Disable, the inverter does
not respond to the scheduling
instruction from the remote port.
-
2
Schedule instruction
valid duration (s)
Specifies the time for maintaining
the scheduling instruction.
When this parameter is set
to 0, the scheduling
instruction takes effect
permanently.
3
Maximum active
power (kW)
Specifies the output upper
threshold for the maximum active
power to adapt to different market
requirements.
-
4
OFF at 0% power
limit
If this parameter is set to Enable,
the inverter shuts down after
receiving the 0% power limit
command. If this parameter is set
to Disable, the inverter does not
shut down after receiving the 0%
power limit command.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
73
Specifies the change speed of the
inverter active power.
-
6
Derated by fixed
active power (kW)
Adjusts the active power output of
the inverter by fixed value.
-
7
Derated by active
power % (%)
Adjusts the active power output of
the inverter by percentage.
If this parameter is set to
100, the inverter outputs
based on the maximum
output power.
8
Night-time reactive
power output
In some specific application
scenarios, a power grid company
requires that the inverter can
perform reactive power
compensation at night to ensure
that the power factor of the local
power grid meets requirements.
-
9
Enable reactive
power parameters
at night
When this parameter is set to
Enable, the inverter outputs
reactive power based on the
setting of Reactive power
compensation at night.
Otherwise, the inverter executes
the remote scheduling command.
This parameter is displayed
when Night-time reactive
power output is set to
Enable.
10
Night-time reactive
power
compensation
(kVar)
During the reactive power
compensation at night, the
reactive power is scheduled by
fixed value.
This parameter is displayed
when Night-time reactive
power output and Enable
reactive power parameters
at night are set to Enable.
11
Reactive power
change gradient
(%/s)
Specifies the change speed of the
inverter reactive power.
-
12
Plant active power
gradient (min/
100%)
Specifies the rate of active power
rise due to sunlight changes.
-
13
Average active
power filtering time
(ms)
Specifies the period of active
power rise due to sunlight
changes. This parameter is used
with Plant active power gradient.
-
14
Power factor
Specifies the power factor of the
inverter.
-
15
Reactive power
compensation (Q/S)
Specifies the reactive power output
by the inverter.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
74
If this parameter is set to Enable,
the active power of the inverter
will be derated according to a
certain slope when the grid
frequency exceeds the frequency
that triggers overfrequency
derating.
-
17
Frequency for
triggering
overfrequency
derating (Hz)
The standards of certain countries
and regions require that the
output active power of inverters be
derated when the power grid
frequency exceeds a certain value.
● This parameter is
displayed when
Overfrequency derating
is set to Enable.
● When setting this
parameter, ensure that
the following condition is
met: Frequency for
exiting overfrequency
derating ≤ Frequency
for triggering
overfrequency derating
< Cutoff frequency of
overfrequency derating.
18
Frequency for
exiting
overfrequency
derating (Hz)
Specifies the frequency threshold
for exiting overfrequency derating.
19
Cutoff frequency of
overfrequency
derating (Hz)
Specifies the frequency threshold
for cutting off overfrequency
derating.
20
Cutoff power of
overfrequency
derating (%)
Specifies the power threshold for
cutting off overfrequency derating.
21
Power recovery
gradient of
overfrequency
derating (%/min)
Specifies the recovery rate of the
overfrequency derating power.
22
PF (U) voltage
detection filtering
time (s)
Specifies the time for filtering the
grid voltage in the PF-U curve.
-
23
Apparent power
baseline (kVA)
Adjust the apparent output
baseline of the inverter.
-
24
Active power
baseline (kW)
Adjusts the active output baseline
of the inverter.
-
25
Power percentage
for triggering Q-U
scheduling
Specifies the reference apparent
power, in percentage. When the
actual apparent power of the
inverter is greater than the value
of this parameter, the Q-U
characteristic curve scheduling
function is enabled.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
75
The inverter adjusts Q/S (the ratio
of the output reactive power to
apparent power) in real time
based on U/Un(%) (the ratio of
the actual power grid voltage to
the rated power grid voltage).
-
27
Q-P characteristic
curve
The inverter adjusts Q/Pn (the
ratio of the output reactive power
to the rated active power) in real
time based on P/Pn(%) (the ratio
of the actual active power to the
rated active power).
-
28
Cosφ-P/Pn
characteristic curve
The inverter adjusts the output
power factor cosφ in real time
based on P/Pn(%).
-
7.2 Operations with a USB Flash Drive
USB flash drives of SanDisk, Netac, and Kingston are recommended. Other brands
may be incompatible.
NO TE
Delete the script file immediately after use to reduce information disclosure risks.
7.2.1 Exporting Configurations
Procedure
1.
Click Local maintenance script on the app to generate a boot script file, see
the FusionSolar APP and SUN2000 APP User Manual.
2.
Import the boot script file to a PC.
(Optional) The boot script file can be opened as a .txt file.
Figure 7-14 Boot script file
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
76
● Advanced user: engineer
● Special user: admin
2
Ciphertext
The ciphertext varies depending on the login
password of the SUN2000 app or entering the
Device Commissioning screen on the FusionSolar
app.
3
Script
validity
period
-
4
Command
Different command settings can produce different
commands.
● Configuration export command: export param.
● Configuration import command: import param.
● Data export command: export log。
● Upgrade command: upgrade.
3.
Import the boot script file to the root directory of a USB flash drive.
4.
Connect the USB flash drive to the USB port. The system automatically
identifies the USB flash drive and executes all commands specified in the boot
script file. View the LED indicator to determine the operating status.
NO TICE
Ensure that the ciphertext in the boot script matches the login password for
logging into the SUN2000 app or entering the Device Commissioning screen
on the FusionSolar app. Otherwise, the user account will be locked for 10
minutes after the USB flash drive is inserted for five consecutive times.
Table 7-1 LED indicator description
LED Indicator
Status
Meaning
Green off
There is no operation
with a USB flash drive.
Blinking green slowly
There is an operation
with a USB flash drive.
Blinking green fast
An operation with a
USB flash drive has
failed.
Steady green
An operation with a
USB flash drive is
successful.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
77
Insert the USB flash drive into a computer and check the exported data.
NO TE
When the configuration export is complete, the boot script file and exported file are in
the root directory of the USB flash drive.
7.2.2 Importing Configurations
Prerequisites
A complete configuration file has been exported.
Procedure
1.
Click Local maintenance script on the app to generate a boot script file, see
the FusionSolar APP and SUN2000 APP User Manual.
2.
Import the boot script file to a PC.
3.
Replace the exported boot script file in the root directory of the USB flash
drive with the imported one.
NO TICE
Replace the boot script file only and keep the exported files.
4.
Connect the USB flash drive to the USB port. The system automatically
identifies the USB flash drive and executes all commands specified in the boot
script file. View the LED indicator to determine the operating status.
NO TICE
Ensure that the ciphertext in the boot script matches the login password for
logging into the SUN2000 app or entering the Device Commissioning screen
on the FusionSolar app. Otherwise, the user account will be locked for 10
minutes after the USB flash drive is inserted for five consecutive times.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
78
Table 7-2 LED indicator description
LED Indicator
Status
Meaning
Green off
There is no operation
with a USB flash drive.
Blinking green slowly
There is an operation
with a USB flash drive.
Blinking green fast
An operation with a
USB flash drive has
failed.
Steady green
An operation with a
USB flash drive is
successful.
7.2.3 Exporting Data
Procedure
1.
Click Local maintenance script on the app to generate a boot script file, see
the FusionSolar APP and SUN2000 APP User Manual.
2.
Import the boot script file to the root directory of a USB flash drive.
3.
Connect the USB flash drive to the USB port. The system automatically
identifies the USB flash drive and executes all commands specified in the boot
script file. View the LED indicator to determine the operating status.
NO TICE
Ensure that the ciphertext in the boot script matches the login password for
logging into the SUN2000 app or entering the Device Commissioning screen
on the FusionSolar app. Otherwise, the user account will be locked for 10
minutes after the USB flash drive is inserted for five consecutive times.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
79
Table 7-3 LED indicator description
LED Indicator
Status
Meaning
Green off
There is no operation
with a USB flash drive.
Blinking green slowly
There is an operation
with a USB flash drive.
Blinking green fast
An operation with a
USB flash drive has
failed.
Steady green
An operation with a
USB flash drive is
successful.
7.2.4 Upgrading
Procedure
1.
Download the required software upgrade package from the technical support
website.
2.
Decompress the upgrade package.
NO TE
If the login password for logging into the SUN2000 app or entering the Device
Commissioning screen on the FusionSolar app is the initial password, you do not need
to perform steps 3 to 5. If not, perform steps 3 to 7.
3.
Click Local maintenance script on the app to generate a boot script file, see
the FusionSolar APP and SUN2000 APP User Manual.
4.
Import the boot script file to a PC.
5.
Replace the boot script file (sun_lmt_mgr_cmd.emap) in the upgrade package
with the one generated by the app.
6.
Copy the extracted files to the root directory of the USB flash drive.
7.
Connect the USB flash drive to the USB port. The system automatically
identifies the USB flash drive and executes all commands specified in the boot
script file. View the LED indicator to determine the operating status.
NO TICE
Ensure that the ciphertext in the boot script matches the login password for
logging into the SUN2000 app or entering the Device Commissioning screen
on the FusionSolar app. Otherwise, the user account will be locked for 10
minutes after the USB flash drive is inserted for five consecutive times.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
80
Table 7-4 LED indicator description
LED Indicator
Status
Meaning
Green off
There is no operation
with a USB flash drive.
Blinking green slowly
There is an operation
with a USB flash drive.
Blinking green fast
An operation with a
USB flash drive has
failed.
Steady green
An operation with a
USB flash drive is
successful.
8.
The system automatically restarts when the upgrade is completed. All LED
indicators are off during the restart. After the restart, the indicator is blinking
green slowly for 1 minute and then it becomes steady green, which indicates
that the upgrade is successful.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
81
8.1 System Power-Off
Precautions
WARNING
● If two inverters share the same AC switch on the AC side, power off the two
inverters.
● After the inverter powers off, the remaining electricity and heat may still cause
electric shocks and body burns. Therefore, put on personal protective
equipment (PPE) and begin servicing the inverter fifteen minutes after power-
off.
Procedure
Step 1 Run a shutdown command on the SUN2000 app, SmartLogger, or network
management system (NMS).
For details, see the user manual of the corresponding product.
Step 2 Turn off the AC switch between the inverter and the power grid.
Step 3 Set the three DC switches to OFF.
----End
8.2 Power-Off for Troubleshooting
Context
To prevent personal injury and equipment damage, perform the following
procedure to power off the solar inverter for troubleshooting or replacement.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
82
● When a solar inverter is faulty, try to avoid standing in front of the solar
inverter.
● Do not operate the DC switch on the solar inverter before you finish Step 3 to
Step 5.
● If the AC switch between the solar inverter and the power grid has
automatically disconnected, do not turn on the switch before the fault is
rectified.
● Before power-off for troubleshooting, do not touch the energized components
of the solar inverter. Otherwise, electric shocks or arcing may occur.
Procedure
Step 1 Wear proper personal protective equipment (PPE).
Step 2 If the solar inverter is not shut down due to a fault, send a shutdown command
on the SUN2000 app, SmartLogger, or management system. If the solar inverter
has shut down due to a fault, go to the next step.
Step 3 Turn off the AC switch between the solar inverter and the power grid.
Step 4 Measure the DC current of each PV input string using a clamp meter that is set to
the DC position.
●
If the current is less than or equal to 0.5 A, go to the next step.
●
If the current is higher than 0.5 A, wait until the solar irradiance decreases
and the PV string current decreases below 0.5 A at night, and then go to the
next step.
Step 5 Open the maintenance compartment door, install a support bar, and use a
multimeter to measure the voltage between the AC terminal block and the
ground. Ensure that the AC side of the solar inverter is disconnected.
Step 6 Turn off all DC input switches of the solar inverter.
Figure 8-1 Power-off for maintenance
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
83
Step 7 Wait for 15 minutes and troubleshoot or repair the inverter.
WARNING
● Do not open the host panel for maintenance if the solar inverter is emitting
odor or smoke, or has obvious exceptions.
● If the solar inverter does not emit odor or smoke and is intact, repair or restart
it based on the alarm handling suggestions. Do not stand in front of the solar
inverter during the restart.
----End
8.3 Routine Maintenance
Maintenance Item
To ensure that the inverter can operate properly for a long term, you are advised
to perform routine maintenance on it as described in this chapter.
CA UTION
● Before cleaning the system, connecting cables, and maintaining the grounding
reliability, power off the system and ensure that the three DC switches on the
inverter are OFF.
● If you need to open the maintenance compartment door in rainy or snowy
days, take protective measures to prevent rain or snow entering the
maintenance compartment. If unavoidable, do not open the maintenance
compartment door.
Maintenance list
Item
Check Method
Maintenance
Interval
● Cleanness of
air intake and
exhaust vents
● Fans
● Check whether there is dust on
the air intake and exhaust vents.
If necessary, remove the baffle
of the air intake vent.
● Check whether the fans produce
abnormal sounds during
operation.
Once every 6 to 12
months
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
84
● The inverter is not damaged or
deformed.
● The inverter operates with no
abnormal sound.
● When the inverter is running,
check whether all inverter
parameters are correctly set.
Once every 6 months
Electrical
connections
● Cables are securely connected.
● Cables are intact, and in
particular, the parts touching
the metallic surface are not
scratched.
● Check whether the sealing caps
of idle DC input terminals fall
off.
● Check that the idle COM and
USB ports are locked by
waterproof caps.
The first inspection is
6 months after the
initial commissioning.
From then on, the
interval can be 6 or
12 months.
Grounding
reliability
Ground cables are securely
connected.
The first inspection is
6 months after the
initial commissioning.
From then on, the
interval can be 6 or
12 months.
Removing the baffle of the air intake vent
Figure 8-2 Removing the baffle
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
85
8.4 Replacing a Fan
CA UTION
● Before replacing a fan, power off the inverter.
● When replacing a fan, use insulation tools and wear personal protective
devices.
NO TE
If the fan tray gets stuck when being pulled or pushed, slightly lift it.
Step 1 Remove the screw on the fan tray and save it. Pull out the fan tray until the fan
baffle plate aligns with the inverter chassis.
Figure 8-3 Pulling out fan tray (1)
Step 2 Remove the cable ties shared by the cables, unscrew the connectors, and
disconnect the cables.
Figure 8-4 Disconnecting cables
Step 3 Pull out the fan tray.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
86
Figure 8-5 Pulling out fan tray (2)
Step 4 Remove cable ties from the faulty fan.
●
FAN 1 Faulty
Figure 8-6 Removing the FAN 1 cable ties
●
FAN 2 Faulty
Figure 8-7 Removing the FAN 2 cable ties
●
FAN 3 Faulty
Figure 8-8 Removing the FAN 3 cable ties
Step 5 Remove the faulty fan (FAN 1 is used as an example).
Figure 8-9 Removing the fan
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
87
Step 6 Install the new fan (FAN 1 is used as an example).
Figure 8-10 Installing a new fan
Step 7 Bind the fan cables.
●
Binding positions for fan 1
Figure 8-11 Binding the FAN 1 cables
●
Binding positions for fan 2
Figure 8-12 Binding the FAN 2 cables
●
Binding positions for fan 3
Figure 8-13 Binding the FAN 3 cables
Step 8 Push the fan tray into the slot until the fan baffle plate aligns with the inverter
chassis.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
88
Figure 8-14 Pushing the fan tray in
Step 9 Connect the cables correctly according to the cable labels and bind the cables.
Figure 8-15 Reconnecting and binding the cables
Step 10 Push the fan tray into the slot and tighten the screw.
Figure 8-16 Reinstalling the fan tray
----End
8.5 Troubleshooting
Alarm severities are defined as follows:
●
Major: The inverter is faulty. As a result, the output power decreases or the
grid-tied power generation is stopped.
●
Minor: Some components are faulty without affecting the grid-tied power
generation.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
89
Warning: The inverter works properly. The output power decreases or some
authorization functions fail due to external factors.
Table 8-1 Common alarms and troubleshooting measures
Alarm
ID
Alarm Name
Alarm
Severity
Cause
Troubleshooting Suggestions
2001
High String
Input Voltage
Major
The PV array is not
properly configured.
Excessive PV modules are
connected in series to a PV
string, and therefore the
PV string open-circuit
voltage exceeds the
maximum operating
voltage of the inverter.
● Cause ID 1: PV strings 1
and 2
● Cause ID 2: PV strings 3
and 4
● Cause ID 3: PV strings 5
and 6
● Cause ID 4: PV strings 7
and 8
● Cause ID 5: PV strings 9
and 10
● Cause ID 6: PV strings
11 and 12
● Cause ID 7: PV strings
13 and 14
● Cause ID 8: PV strings
15 and 16
● Cause ID 9: PV strings
17 and 18
Reduce the number of PV
modules connected in series in
the PV string until the PV
string open-circuit voltage is
not greater than the
maximum operating voltage
of the inverter. After the PV
array configuration is
corrected, the alarm
disappears.
2011
String Reverse
Connection
Major
The PV string is reversely
connected.
Cause ID 1–18: PV strings
1–18
Check whether the PV string is
reversely connected to the
inverter. If yes, wait until the
PV string current drops below
0.5 A. Then, set all DC
switches to OFF and correct
the PV string connection.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
90
1. Only a few PV modules
are connected in series
in the PV string.
Therefore, the end
voltage is lower than
that of other PV strings.
2. The PV string is shaded.
Cause ID 1–18: PV strings
1–18
1. Check whether the number
of PV modules connected
in series in the PV string is
less than that in other PV
strings connected in
parallel with this PV string.
If yes, wait until the PV
string current drops below
0.5 A, set all DC switches to
OFF, and adjust the
number of PV modules in
the PV string.
2. Check whether the open-
circuit voltage of the PV
string is normal.
3. Check whether the PV
string is shaded.
2015
PV String Loss
Warning
This alarm is generated
when the PV string status
is abnormal in the
following conditions:
● A single PV string is
lost.
● Both 2-in-1 PV strings
are lost.
● Either of the 2-in-1 PV
strings is lost.
Cause ID 1–8: PV strings
1–18
1. If the PV string access type
is manually set, check
whether it is consistent
with the actual access
status.
2. Check whether the inverter
terminals are properly
connected.
3. Check whether the PV
string terminals are
properly connected.
4. If a 2-in-1 terminal is used,
check whether it is normal.
2031
Phase Wire
Short-Circuited
to PE
Major
Cause ID=1
The impedance of the
output phase wire to PE is
low or the output phase
wire is short-circuited to
PE.
Check the impedance of the
output phase wire to PE,
locate the position with lower
impedance, and rectify the
fault.
2032
Grid Loss
Major
Cause ID=1
1. The power grid
experiences an outage.
2. The AC circuit is
disconnected or the AC
switch is off.
1. The alarm is automatically
cleared after the power
grid is restored.
2. Check whether the AC
circuit is disconnected or
the AC switch is off.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
91
The grid voltage is below
the lower threshold or the
undervoltage duration has
exceeded the time that
triggers LVRT.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers
after detecting that the
power grid becomes
normal.
2. If the alarm occurs
frequently, check whether
the power grid voltage is
within the acceptable
range. If not, contact the
local power operator. If yes,
modify the grid
undervoltage protection
threshold through the
mobile app, SmartLogger,
or network management
system (NMS) with the
consent of the local power
operator.
3. If the fault persists for a
long time, check the AC
circuit breaker and AC
output power cable.
2034
Grid
Overvoltage
Major
Cause ID=1
The grid voltage is beyond
the upper threshold or the
overvoltage duration has
exceeded the time that
triggers HVRT.
1. Check whether the grid
connection voltage exceeds
the upper threshold. If yes,
contact the local power
operator.
2. If you have confirmed that
the grid-tied voltage
exceeds the upper
threshold and have
obtained the consent of the
local power operator,
modify the overvoltage
protection threshold
through the mobile app,
SmartLogger, or NMS.
3. Check whether the peak
grid voltage exceeds the
upper threshold.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
92