VENT-FREE PROPANE/LP GAS MINI-HEARTH ® HEATER OWNER’S OPERATION AND INSTALLATION MANUAL VMH3000TP Shown With Optional Mantel Which Features a Built-In Base WARNING: If the information in this manual is not fol- lowed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. — Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. — WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s in- structions. • If you cannot reach your gas supplier, call the fire department. — Installation and service must be performed by a qualified installer, service agency, or the gas supplier. WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For as- sistance or additional information consult a qualified installer, ser- vice agency, or the gas supplier. WARNING: This is an unvented gas-fired heater. It uses air (oxy- gen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation sec- tion on page 5 of this manual. ® 15,000 to 30,000 Btu/Hr with Thermostat This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases. *Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

VENT-FREE GAS RESIDENTIAL HEATERS

® LOCAL CODES Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANS Z223.1, also known as NFPA 54*. *Available from: American National Standards Institute, Inc. 1430 Broadway New York, NY 10018 National Fire Protection Association, Inc. Batterymarch Park Quincy, MA 02269 SAFETY INFORMATION Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes. Propane/LP Gas: Propane/LP gas is odor- less. An odor-making agent is added to gas. The odor helps you detect a gas leak. How- ever, the odor added to gas can fade. Gas may be present even though no odor exists. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater. DANGER: Carbon monoxide poisoning may lead to death! IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper- ate, or service this heater. Im- proper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning. WARNINGS WARNING: Any change to this heater or its controls can be dangerous. 1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases. 2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/ LP supply tank(s) outdoors. 3. If you smell gas • shut off gas supply • do not try to light any appliance • do not touch any electrical switch; do not use any phone in your building. • immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions • if you cannot reach your gas supplier, call the fire department WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this heater. 4. This heater shall not be installed in a bedroom or bathroom. 5. This heater needs fresh, outside air ven- tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air For Combustion and Ventilation, pages 5 through 7. 6. Before using furniture polish, wax, car- pet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white pow- der residue within burner box or on adjacent walls or furniture. 7. If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, have it serviced. 8. Do not run heater • where flammable liquids or vapors are used or stored. • under dusty conditions. 9. Do not use heater if any part has been under water. Immediately call a quali- fied service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water. 10. To prevent the creation of soot, follow the instructions in Cleaning and Main- tenance, page 19. 11. Turn off and unplug heater and let cool before servicing. Only a qualified service person should service and repair heater. 12. Operating heater above elevations of 4,500 feet could cause pilot outage. 13. To prevent performance problems, do not use a propane/LP fuel tank of less than 100 lbs. capacity. WARNING: Do not allow fans to blow directly into the heater. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting. Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater. Carefully supervise young chil- dren when they are in same room with heater. Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids. Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies. Surface of heater becomes very hot when running heater. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shut- down. Allow surfaces to cool be- fore touching. Make sure screen is in place be- fore running heater.

Figure 1 - Vent-Free Gas Log Propane/LP Gas Space Heater

UNPACKING 1. Remove heater from carton. 2. Remove all protective packaging ap- plied to heater for shipment. 3. Make sure your heater includes two hardware packets. 4. Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater. ASSEMBLY ASSEMBLING HEATER Tools Required: • Phillips screwdriver • 5/16" hex wrench • slotted screwdriver Removing Front Panel Of Heater 1. Remove two screws near bottom cor- ners of front panel with Phillips screw- driver. 2. Pull bottom of front panel forward, then down (see Figure 2) . Figure 2 - Removing Front Panel of Heater Piezo Ignitor Ignitor Cable Continued ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f SDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f SDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f ASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'fASDFKIGLFJI alskdidkoemkgo dkirlnfgpd'f Ignitor Button Screen Front Panel Heater Cabinet Log Lighting and Warning Plates Control Knob Installing Log Note: For easier installation, lay heater on its back. 1. Remove log from inside top of heater. Discard protective packaging. 2. Attach ignitor cable to piezo ignitor (see Figure 3). 3. With Phillips screwdriver, remove four screws holding screen in place. Re- move screen. 4. Gently slide log between log retaining brackets on deflector assembly (see Fig- ure 4, page 4). The log should fit firmly against bottom of log retaining brackets. 5. Reattach screen using four screws re- moved in step 3. PRODUCT FEATURES SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air. PIEZO IGNITION SYSTEM This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater. THERMOSTATIC HEAT CONTROL This heater has a thermostat sensing bulb and a control valve. This results in the great- est heater comfort. This can also result in lower gas bills. Note: Do not remove Lighting and Warning Plates from heater Figure 3 - Attaching Ignitor Cable to Piezo Ignitor

VENT-FREE GAS RESIDENTIAL HEATERS

® Attaching Brass Front Trim to Front Panel 1. Locate brass front trim in brass trim package. 2. Slide the head of two truss-head screws from hardware packet into each end of brass front trim (see Figure 5). 3. Line up screws with holes in front panel (see Figure 4). Insert screws in holes. Attach nuts from inside of front panel. Tighten with wrench. 5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 6). 6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver. 7. Repeat steps 1 through 6 for other side. 8. Place the assembled trim on front of heater cabinet. Attach on top and sides with four brass screws included in hard- ware package (see Figure 7). 9. Reattach front panel to heater if you are going to mount the heater to the base. Do not reattach front panel at this time if you are going to mount heater to wall. Log Retaining Brackets Figure 4 - Assembling Heater Truss-Head Screw Nut Front Panel Figure 5 - Attaching Brass Front Trim to Front Panel Brass Front Trim Top Brass Trim Slot Mitered Edge Slot Set Screws Adjusting Plate Screws Assembled Brass Trim Shim Figure 6 - Assembling Brass Trim Figure 7 - Attaching Brass Trim to Heater WARNING: Always have burner shield and screen in place before operating heater. This pre- vents excessive temperatures on heater surfaces. Failure to position the parts in accordance with these diagrams or failure to use only parts spe- cifically approved with this heater may result in property damage or personal injury. Side Brass Trim ASSEMBLY Continued Burner Shield Screen Front Panel Deflector Log Truss- Head Screw Brass Front Trim Screw Screw Heater Cabinet Nut Assembling and Attaching Brass Trim 1. Remove packaging from three remain- ing pieces of brass trim. 2. Locate four brass screws, two adjust- ing plates with set screws, and two shims in the hardware packet. 3. Align shim under adjusting plate as shown in Figure 6. 4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 6).

FRESH AIR FOR

COMBUSTION AND VENTILATION Today’s homes are built more energy effi- cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible. While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com- bustion and ventilation. Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad- equate fresh air for these appliances. This will insure proper venting of vented fuel- burning appliances. Confined and Unconfined Space The National Fuel Gas Code, ANS Z223.1 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggre- gate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are con- sidered a part of the unconfined space. This heater shall not be installed in a con- fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. * Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them. WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven- tilation air. Read the following in- structions to insure proper fresh air for this and other fuel-burning appliances in your home. PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code, NFPA 54/ANS Z223.1, Sec- tion 5.3, Air for Combustion and Ventilation. All spaces in homes fall into one of the three following ventilation classifications: 1. Unusually Tight Construction 2. Unconfined Space 3. Confined Space The information on pages 5 through 7 will help you classify your space and provide adequate ventilation. Unusually Tight Construction The air that leaks around doors and win- dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air. Unusually tight construction is de- fined as construction where: a. walls and ceilings exposed to the outside atmosphere have a con- tinuous water vapor retarder with a rating of one perm (6x10-11 kg per pa-sec-m2) or less with open- ings gasketed or sealed and b. weather stripping has been added on openable windows and doors and c. caulking or sealants are applied to areas such as joints around window and door frames, be- tween sole plates and floors, be- tween wall-ceiling joints, be- tween wall panels, at penetra- tions for plumbing, electrical, and gas lines, and at other openings. If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 7. If your home does not meet all of the three criteria above, proceed to Determining Fresh- Air Flow For Heater Location, page 6. Continued

VENT-FREE GAS RESIDENTIAL HEATERS

® DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION Determining if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms. 1. Determine the volume of the space (length x width x height). Length x Width x Height = ____________________ cu. ft. (volume of space) Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space. 2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support. _____________________(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support) 3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater ___________________Btu/Hr Gas water heater* ___________________Btu/Hr Gas furnace ___________________Btu/Hr Vented gas heater ___________________Btu/Hr Gas fireplace logs ___________________Btu/Hr Other gas appliances* + ___________________Btu/Hr Total = ___________________Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors. 4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used. _________________ Btu/Hr (maximum the space can support) _________________ Btu/Hr (actual amount of Btu/Hr used) Example: 51,200 Btu/Hr (maximum the space can support) 60,000 Btu/Hr (actual amount of Btu/Hr used) The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined. If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation. AIR FOR COMBUSTION AND VENTILATION Continued Example: Gas water heater 30,000 Btu/Hr Vent-free heater + 30,000 Btu/Hr Total = 60,000 Btu/Hr WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Ventilation Air From Inside

Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 8). You can also remove door into adjoining room (see op- tion 3, Figure 8). Follow the National Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts. Figure 8 - Ventilation Air from Inside Building Figure 9 - Ventilation Air from Outdoors Or Remove Door into Adjoining Room, Option 3 Ventilation Grills Into Adjoining Room, Option 2 12" 12" Ventilation Grills into Adjoining Room, Option 1 Outlet Air Ventilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces. AIR FOR COMBUSTION AND VENTILATION Continued Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

VENT-FREE GAS RESIDENTIAL HEATERS

® WARNING: Never install the heater • in a bedroom or a bathroom • in a recreational vehicle • where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater • as a fireplace insert • in high traffic areas • in windy or drafty areas IMPORTANT: Vent-free heaters add mois- ture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Fresh Air for Com- bustion and Ventilation, pages 5 through 7. 36" 5" FLOOR CEILING Minimum Minimum To Top Surface Of Carpeting, Tile Or Other Combustible Material 6" Minimum From Sides Of Heater Left Side Right Side INSTALLATION CHECK GAS TYPE Use only propane/LP gas. If your gas supply is not propane/LP, do not install heater. Call dealer where you bought heater for proper type heater. INSTALLATION ITEMS Before installing heater, make sure you have the items listed below. • external regulator (supplied by installer) • piping (check local codes) • sealant (resistant to propane/LP gas) • equipment shutoff valve * • ground joint union • test gauge connection * • sediment trap • tee joint • pipe wrench * A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an ac- ceptable alternative to test gauge connec- tion. Purchase the optional CSA/AGA de- sign-certified equipment shutoff valve from your dealer. See Accessories, page 23. WARNING: A qualified ser- vice person must install heater. Follow all local codes. NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri- mary heating system. Do not in- stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu- late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source. CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls. LOCATING HEATER You can locate heater on floor. The op- tional hearth base is needed. You can also install optional decorative mantels on the heater (some mantels require the hearth base). IMPORTANT: Only use optional mantels and hearth base specified in this manual. Purchase the optional mantel and hearth base from your dealer. See Accesso- ries, page 23. The heater may also be mounted on a wall. You cannot use optional mantel if mounting heater on a wall. WARNING: Maintain the mini- mum clearances shown in Figure 10. If you can, provide greater clearances from floor, ceiling, and joining wall. Figure 10 - Mounting Clearances As Viewed From Front of Heater For convenience and efficiency, install heater • where there is easy access for operation, inspection, and service. • in coldest part of room. An optional fan kit is available from your dealer. See Accessories, page 23. If plan- ning to use fan, locate heater near an electri- cal outlet. CAUTION: If you install the heater in a home garage • heater pilot and burner must be at least 18 inches above floor. • locate heater where moving ve- hicle will not hit it.

The thermostat sensing bulb has been placed

inside the heater for protection during shipping. Locating Thermostat Sensing Bulb 1. Remove front panel of heater (see Fig- ure 2, page 3). 2. Locate thermostat sensing bulb just under burner assembly. IMPORTANT: Attach thermostat sensing bulb to back of heater for proper operation. Attaching Thermostat Sensing Bulb 1. Remove thermostat sensing bulb from holders inside heater. Route through slot opening in bottom of heater. 2. Place clamp on thermostat sensing bulb as shown in Figure 11. Clamp is pro- vided in hardware package. 3. Snap clamp into upper mounting hole as shown in Figure 11. Mounting hole is located on lower left edge on back of heater. Make sure the thermostat sensing bulb is pointing up. Figure 11 - Attaching Thermostat Sensing Bulb Mounting Bracket INSTALLATION OPTIONS There are three options for mounting this heater. A. Mounting heater to wall B. Mounting heater to optional hearth base C. Mounting heater to optional mantel (some mantels require the hearth base) A. MOUNTING HEATER TO WALL Mounting Bracket The mounting bracket is located on back panel of heater. It has been taped there for shipping. Remove mounting bracket from back panel. Figure 12 - Mounting Bracket Location Methods For Attaching Mounting Bracket To Wall Only use last hole on each end of mounting bracket to attach bracket to wall. These two holes are 16 inches apart from their centers. Attach mounting bracket to wall in one of two ways. 1. Attaching to wall stud 2. Attaching to wall anchor Attaching To Wall Stud: This method pro- vides the strongest hold. Insert mounting screws through mounting bracket and into wall studs. Attaching To Wall Anchor: This method allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry). Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket. Marking Screw Locations 1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level. Figure 13 - Mounting Bracket Clearances Attaching Mounting Bracket To Wall Note: Wall anchors, mounting screws, and spacers are in hardware package. The hard- ware package is provided with heater. Attaching To Wall Stud Method For attaching mounting bracket to wall studs 1. Drill holes at marked locations using 9/64" drill bit. 2. Place mounting bracket onto wall. Line up last hole on each end of bracket with holes drilled in wall. 3. Insert mounting screws through bracket and into wall studs. 4. Tighten screws until mounting bracket is firmly fastened to wall studs. Continued 20 3/4" Min. 11" Min. 16" Adjoining Wall Only Insert Mounting Screws Through Last Hole On Each End Floor INSTALLATION Continued WARNING: Maintain minimum clearances shown in Figure 13. If you can, provide greater clear- ances from floor and joining wall. 2. Mark screw locations on wall (see Fig- ure 13). Note: Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only. 3. Remove tape and mounting bracket from wall.

VENT-FREE GAS RESIDENTIAL HEATERS

® Attaching To Wall Anchor Method For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry) 1. Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1" deep. 2. Fold wall anchor as shown in Figure 14. 3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall. 4. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to “pop” open anchor wings. IMPORTANT: Do not hammer key! For thick walls (over 1/2" thick) or solid walls, do not pop open wings. 5. Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors. 6. Insert mounting screws through bracket and into wall anchors. 7. Tighten screws until mounting bracket is firmly fastened to wall. INSTALLATION Continued Figure 16 - Mounting Heater Onto Mount- ing Bracket Installing Bottom Mounting Screws 1. Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see Figure 17). 2. Mark screw locations on wall. 3. Remove heater from mounting bracket. 4. If installing bottom mounting screws into hollow or solid wall, install wall anchors. Follow steps 1 through 4 un- der Attaching To Wall Anchor Method. If installing bottom mounting screw into wall stud, drill holes at marked lo- cations using 9/64" drill bit. 5. Replace heater onto mounting bracket. 6. Place spacers between bottom mount- ing holes and wall anchor or drilled hole. 7. Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole. 8. Tighten both screws until heater is firmly secured to wall. Do not over tighten. Note: Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 12 and 13). Figure 17 - Installing Bottom Mounting Screws B. MOUNTING HEATER ON OPTIONAL HEARTH BASE Tools needed: • #2 Phillips screwdriver • slotted screwdriver • electric drill (if securing base to floor) The optional hearth base kit includes the following: • Hearth Base • 4 Wood Screws • 4 Sheet Metal Screws • Brass Base Trim • Hearth Insert • 4 Anchors • 2 Brass Screws Note: It is an option to secure “A” model hearth base to floor. You must secure the “B” and “C” model hearth base to floor. To secure hearth base to floor, follow instruc- tions under Securing Hearth Base to Floor, page 11. If not securing hearth base to floor, proceed to Mounting Heater to Optional Hearth Base, page 11. Figure 14 - Folding Anchor Figure 15 - Popping Open Anchor Wings For Thin Walls Placing Heater On Mounting Bracket 1. Locate two horizontal slots on back panel of heater. 2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket. Horizontal Slots Mounting Bracket (attached to wall) Stand-Out Tab

Mounting Heater to Optional

Hearth Base 1. Lay heater on its back on a table with the bottom of heater overhanging the edge of the table. 2. Remove 2 shipping screws in bottom of heater. Discard shipping screws. 3. Line up mounting holes on top of hearth base with holes in bottom of heater (see Figure 18). 4. Using a Phillips screwdriver, secure hearth base to heater with four sheet metal screws (see Figure 18). 5. Stand heater up on base. 6. Place hearth insert in hearth base as shown in Figure 19. 7. Assemble brass trim (see steps 1 through 7 under Assembling and At- taching Brass Trim, page 4). 8. Slide base trim on heater base. Attach brass trim to base with two brass screws included as shown in Figure 19. Figure 18 - Attaching Heater to Hearth Base Base Holes for Securing Heater to Floor Shipping Screw Bottom of Heater Sheet Metal Screw Mounting Holes Brass Base Trim Hearth Insert Screw Figure 19 - Placing Hearth Insert on Heater Base and Attaching Brass Base Trim Securing Hearth Base to Floor 1. Position hearth base in desired location. Mark holes for drilling (See Figure 18). Remove hearth base. 2. For carpeted floor, make a small cut with a sharp knife at marked locations before drilling. If securing to a wood floor, drill a 3/4" deep hole using a 1/8" diameter drill bit. Do not use anchors in wood floors. If securing to a concrete floor, drill a 1 3/8" deep hole using a 1/4" diameter concrete drill bit. Completely insert anchors into each hole. 3. Mount heater to hearth base following steps under Mounting Heater to Op- tional Hearth Base. After mounting heater, position heater and hearth base over drilled holes. With slotted screw- driver, secure hearth base to floor with four wood screws. C. MOUNTING HEATER TO OPTIONAL MANTEL. See Instructions Included With Mantel Kit. IMPORTANT: Only use the optional man- tels specified in this manual. See Accesso- ries, page 23 for proper mantel kits. This heater is only approved for use with models GMF800/GMU801 series, GM900F/ GM901U series, GM902F/GM903U series, GM700F/GM701U, and GM702F/ GM703U series mantel kits. Using any other mantel will void the CSA/AGA approval for this heater. Only use models GMF800/ GMU801 series, GM900F/GM901U series, GM902F/GM903U series, GM700F/ GM701U, and GM702F/GM703U series mantels with this heater. Do not use these mantels with any other product. Continued

VENT-FREE GAS RESIDENTIAL HEATERS

® Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 21). IMPORTANT: Install an equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance. Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves. Tee Joint Reducer Bushing to 1/8" NPT 1/8" NPT Plug Tap Test Gauge Connection * Tee Joint Pipe Nipple Cap Sediment Trap Figure 21 - Gas Connection * A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design-certified equipment shutoff valve from your dealer. See Accessories, page 23. Pressure Regulator 3/8" NPT Pipe Nipple Ground Union Joint Heater Cabinet 3" Minimum Note: Burner bracket not shown for clarity Equipment Shutoff Valve * CONNECTING TO GAS SUPPLY Figure 20 - External Regulator with Vent Pointing Down CAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas. Propane/LP Supply Tank Vent Pointing Down External Regulator From External Regulator (11" W.C. to 14" W.C. Pressure) The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom- ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 20. Pointing the vent down protects it from freezing rain or sleet. INSTALLATION Continued CAUTION: Use only new, black iron or steel pipe. Inter- nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" or greater diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur. We recommend that you install sediment trap in supply line as shown in Figure 21. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sedi- ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly. IMPORTANT: Hold pressure regulator with wrench when connecting it to gas pip- ing and/or fittings. WARNING: This appliance re- quires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator. WARNING: A qualified service person must connect heater to gas supply. Follow all local codes. WARNING: Never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

Pressure Testing Gas Supply

Piping System Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) 1. Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage heater regulator. 2. Cap off open end of gas pipe where equipment shutoff valve was connected. 3. Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve. 4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak. 5. Correct all leaks at once. 6. Reconnect fireplace and equipment shutoff valve to gas supply. Check re- connected fittings for leaks. Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa) 1. Close equipment shutoff valve (see Fig- ure 22). 2. Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve. 3. Check all joints from propane/LP sup- ply tank to equipment shutoff valve (see Figure 23). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak. 4. Correct all leaks at once. Open Closed Equipment Shutoff Valve Figure 23 - Checking Gas Joints Equipment Shutoff Valve Propane/LP Supply Tank Thermostat Gas Valve Location Figure 22 - Equipment Shutoff Valve Pressure Testing Heater Gas Connections 1. Open equipment shutoff valve (see Fig- ure 22). 2. Open propane/LP supply tank valve. 3. Make sure control knob of heater is in the OFF position. 4. Check all joints from equipment shutoff valve to thermostat gas valve (see Fig- ure 23). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak. 5. Correct all leaks at once. 6. Light heater (see Operating Heater, pages 14 and 15). Check all other in- ternal joints for leaks. 7. Turn off heater (see To Turn Off Gas to Appliance, page 14). 8. Replace front panel. CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply, page 12. WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once. WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once. INSTALLATION Continued

VENT-FREE GAS RESIDENTIAL HEATERS

® PILOT LO OFF HI IGNITOR OPERATING HEATER FOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS Figure 24 - Control Knob In The OFF Position Control Knob Ignitor Button 1. STOP! Read the safety information, column 1. 2. Make sure equipment shutoff valve is fully open. 3. Turn control knob clockwise to the OFF position. 4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety in- formation. If you don’t smell gas, go to the next step. 5. Turn control knob counterclockwise C-clockwise to the PILOT position. Press in control knob for five (5) seconds (see Figure 24). Note: You may be running this heater for the first time after hook- ing up to gas supply. If so, the con- trol knob may need to be pressed in for 30 seconds. This will allow air to bleed from the gas system. 6. With control knob pressed in, push down and release ignitor button. This will light pilot. The pilot is at- tached to the front of burner. If needed, keep pressing ignitor but- ton until pilot lights. Note: If pilot does not stay lit, refer to Troubleshooting, pages 16 through 18. Also contact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with match. To light pilot with match, see Manual Lighting Procedure, page 15. Pilot Burner Thermocouple Figure 25 - Pilot Ignitor Electrode CAUTION: Do not try to adjust heating levels by using the equip- ment shutoff valve. TO TURN OFF GAS TO APPLIANCE Shutting Off Heater 1. Turn control knob clockwise to the OFF position. 2. Turn off all electric power to the ap- pliance if service is to be performed. Shutting Off Burner Only (pilot stays lit) Turn control knob clockwise to the PILOT position. A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. • If you cannot reach your gas sup- plier, call the fire department. C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been un- der water. WARNING: If you do not fol- low these instructions exactly, a fire or explosion may result caus- ing property damage, personal injury or loss of life. 7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. • If control knob does not pop up when released, contact a quali- fied service person or gas sup- plier for repairs. Note: If pilot goes out, repeat steps 3 through 7. This heater has a safety interlock system. Wait one (1) minute before lighting pilot again. 8. Turn control knob counterclockwise C-clockwise to desired heating level. The main burner should light. Set control knob to any heat level between HI and LO.

The thermostatic control used on this

heater differs from standard thermostats. Standard thermostats simply turn on and off the burner. The thermostat used on this heater senses the room temperature. The thermostat adjusts the amount of gas flow to the burner. This increases or de- creases the burner flame height. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temperature. The control knob can be set to any heat level between HI and LO. Note: The thermostat sensing bulb mea- sures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installation loca- tion, room size, open air temperatures, etc.). Frequent use of your heater will let you determine your own comfort levels. MANUAL LIGHTING PROCEDURE 1. Remove front panel (see Figure 2, page 3). 2. Follow steps 1 through 5 under Light- ing Instructions, page 14. 3. With control knob pressed in, strike match. Hold match to pilot until pi- lot lights. 4. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow step 8 under Lighting Instruc- tions, page 14. 5. Replace front panel. Figure 26 - Correct Pilot Flame Pattern Thermocouple Thermocouple INSPECTING BURNER Figure 27 - Incorrect Pilot Flame Pattern Pilot Burner Pilot Burner Check pilot flame pattern and burner flame pattern often. PILOT FLAME PATTERN Figure 26 shows a correct pilot flame pattern. Figure 27 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touch- ing the thermocouple. This will cause the thermocouple to cool. When the thermo- couple cools, the heater will shut down. If pilot flame pattern is incorrect, as shown in Figure 27 • turn heater off (see To Turn Off Gas to Appliance, page 14) • see Troubleshooting, pages 16 through 18 BURNER FLAME PATTERN Figure 28 shows a correct burner flame pattern. Figure 29 shows an incorrect burner flame pattern. The incorrect burner flame pattern shows yellow tipping of the flame. It also shows the flame higher than one inch above the log. Note: When using the heater the first time, the flame will be yellow for approximately one hour until the log cures. NOTICE: Do not mistake orange flames with yellow tipping. Dirt or other fine particles enter the heater and burn causing brief patches of orange flame. WARNING: If yellow tipping occurs, your heater could pro- duce increased levels of carbon monoxide. If burner flame pat- tern shows yellow tipping, follow instructions, bottom of this page. Yellow Tipping Top of Flame About One Inch Above Logs If burner flame pattern is incorrect, as shown in Figure 29 • turn heater off (see To Turn Off Gas to Appliance, page 14) • see Troubleshooting, pages 16 through 18 Figure 29 - Incorrect Burner Flame Pattern Figure 28 - Correct Burner Flame Pattern

VENT-FREE GAS RESIDENTIAL HEATERS

® TROUBLESHOOTING WARNING: Turn off and un- plug heater and let cool before servicing. Only a qualified ser- vice person should service and repair heater. REMEDY 1. Replace ignitor 2. Replace ignitor 3. Reconnect ignitor cable 4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry 5. Tighten nut holding piezo ignitor to heater cabinet. Nut is located inside heater cabinet at top 6. Replace ignitor cable 7. Replace piezo ignitor 1. Turn on gas supply or open equipment shutoff valve 2. Turn control knob to PILOT position 3. Press in control knob while in PILOT position 4. Continue holding down control knob. Re- peat igniting operation until air is removed 5. Contact local propane/LP gas company 6. Clean ODS/pilot (see Cleaning and Maintenance, page 19) or replace ODS/ pilot assembly 7. Replace gas regulator 1. Press in control knob fully 2. After ODS/pilot lights, keep control knob pressed in 30 seconds 3. Wait one minute for safety interlock sys- tem to reset. Repeat ignition operation 4. Fully open equipment shutoff valve 5. Hand tighten until snug, then tighten 1/4 turn more 6. A) Contact local propane/LP company B) Clean ODS/pilot (see Cleaning and Maintenance, page 19) or replace ODS/ pilot assembly 7. Replace thermocouple 8. Replace control valve POSSIBLE CAUSE 1. Ignitor electrode positioned wrong 2. Ignitor electrode broken 3. Ignitor electrode not connected to igni- tor cable 4. Ignitor cable pinched or wet 5. Piezo ignitor nut is loose 6. Broken ignitor cable 7. Bad piezo ignitor 1. Gas supply turned off or equipment shutoff valve closed 2. Control knob not in PILOT position 3. Control knob not pressed in while in PILOT position 4. Air in gas lines when installed 5. Depleted gas supply 6. ODS/pilot is clogged 7. Gas regulator setting is not correct 1. Control knob not fully pressed in 2. Control knob not pressed in long enough 3. Safety interlock system has been trig- gered 4. Equipment shutoff valve not fully open 5. Thermocouple connection loose at con- trol valve 6. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob- lem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged ODS/pilot 7. Thermocouple damaged 8. Control valve damaged OBSERVED PROBLEM When ignitor button is pressed, there is no spark at ODS/pilot When ignitor button is pressed, there is spark at ODS/pilot but no ignition ODS/pilot lights but flame goes out when control knob is released CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit. Note: For additional help, visit DESA International’s technical service web site at www.desatech.com. Note: All troubleshooting items are listed in order of operation. www.desatech.com

1. Clean burner (see Cleaning and Mainte-

nance, page 19) or replace burner orifice 2. Replace burner orifice 3. Contact local propane/LP company 1. Contact local propane/LP company 2. Clean burner (see Cleaning and Mainte- nance, page 19) or replace burner orifice 1. Clean burner (see Cleaning and Mainte- nance, page 19) or replace burner orifice 2. Replace burner 3. Replace gas regulator 1. Check burner for dirt and debris. If found, clean burner (see Cleaning and Maintenance, page 19) 2. Replace gas regulator 1. Problem will stop after a few hours of operation 1. Turn control knob to LO position and let warm up for a minute 2. Operate burner until air is removed from line. Have gas line checked by local pro- pane/LP company 3. Observe minimum installation clear- ances (see Figure 10, page 8) 4. Clean burner (see Cleaning and Mainte- nance, page 19) or replace burner orifice 1. Turn heater off when using furniture polish, wax, carpet cleaners, or similar products TROUBLESHOOTING Continued OBSERVED PROBLEM Burner does not light after ODS/pilot is lit Delayed ignition of burner Burner backfiring during combustion Yellow flame during burner combustion Slight smoke or odor during initial operation Heater produces a whistling noise when burner is lit White powder residue forming within burner box or on adjacent walls or furniture POSSIBLE CAUSE 1. Burner orifice is clogged 2. Burner orifice diameter is too small 3. Inlet gas pressure is too low 1. Manifold pressure is too low 2. Burner orifice is clogged 1. Burner orifice is clogged or damaged 2. Burner damaged 3. Gas regulator defective 1. Not enough air 2. Gas regulator defective 1. Residues from manufacturing processes 1. Turning control knob to HI position when burner is cold 2. Air in gas line 3. Air passageways on heater blocked 4. Dirty or partially clogged burner orifice 1. When heated, vapors from furniture pol- ish, wax, carpet cleaners, etc. turn into white powder residue Continued www.desatech.com

VENT-FREE GAS RESIDENTIAL HEATERS

® TROUBLESHOOTING Continued WARNING: If you smell gas • Shut off gas supply. • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. • If you cannot reach your gas supplier, call the fire department. IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors. OBSERVED PROBLEM Heater produces a clicking/ticking noise just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use (ODS operates) Gas odor even when control knob is in OFF position Gas odor during combustion POSSIBLE CAUSE 1. Metal expanding while heating or con- tracting while cooling 1. Heater burning vapors from paint, hair spray, glues, etc. (see IMPORTANT statement above) 2. Gas leak. See Warning statement at top of page 1. Not enough fresh air is available 2. Low line pressure 3. ODS/pilot is partially clogged 1. Gas leak. See Warning statement at top of page 2. Control valve defective 1. Foreign matter between control valve and burner 2. Gas leak. See Warning statement at top of page REMEDY 1. This is common with most heaters. If noise is excessive, contact qualified ser- vice person 1. Ventilate room. Stop using odor caus- ing products while heater is running 2. Locate and correct all leaks (see Check- ing Gas Connections, page 13) 1. Open window and/or door for ventilation 2. Contact local propane/LP company 3. Clean ODS/pilot (see Cleaning and Maintenance, page 19) 1. Locate and correct all leaks (see Check- ing Gas Connections, page 13) 2. Replace control valve 1. Take apart gas tubing and remove for- eign matter 2. Locate and correct all leaks (see Check- ing Gas Connections, page 13) www.desatech.com

• Use a vacuum cleaner or pressurized air

to clean. Exterior • Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabi- net to remove dust. CAUTION: You must keep control areas, burner, and circu- lating air passageways of heater clean. Inspect these areas of heater before each use. Have heater inspected yearly by a quali- fied service person. Heater may need more frequent cleaning due to excessive lint from carpeting, pet hair, bedding material, etc. WARNING: Turn off heater and let cool before cleaning. CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. Keep these holes clear of dust, dirt, and lint. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We rec- ommend that you clean the unit every 2,500 hours of operation or every three months. We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recom- mend using compressed air no greater than 30 PSI. Your local computer store, hard- ware store, or home center may carry com- pressed air in a can. You can use a vacuum cleaner in the blow position. If using com- pressed air in a can, please follow the direc- tions on the can. If you don't follow direc- tions on the can, you could damage the pilot assembly. 1. Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes. 2. Inspect burner, pilot, and primary air inlet holes on injector holder for dust and dirt (see Figure 30). 3. Blow air through the ports/slots and holes in the burner. Figure 30 - Injector Holder On Outlet Burner Tube 4. Check the injector holder located at the end of the burner tube again. Remove any large particles of dust, dirt, lint, or pet hairs with a soft cloth or vacuum cleaner nozzle. 5. Blow air into the primary air holes on the injector holder. 6. In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4. Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 31). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available. Burner Tube Injector Holder Primary Air Inlet Holes Figure 31 - Pilot Inlet Air Hole Pilot Assembly Pilot Air Inlet Hole Ports/Slots REPLACEMENT PARTS Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty. PARTS UNDER WARRANTY Contact authorized dealers of this product. If they can’t supply original replacement part(s), call DESA International’s Techni- cal Service Department at 1-800-323-5190 for referral information. When calling DESA International, have ready • your name • your address • model and serial numbers of your heater • how heater was malfunctioning • type of gas used (propane/LP or natural gas) • purchase date Usually, we will ask you to return the defec- tive part to the factory. PARTS NOT UNDER WARRANTY Contact authorized dealers of this product. If they can’t supply original replacement part(s), call DESA International’s Parts Department at 1-800-972-7879 for referral information. When calling DESA International, have ready • model number of your heater • the replacement part number

VENT-FREE GAS RESIDENTIAL HEATERS

® 12-1 12-2 1 2 9 10 10 11 12 13 14 15 17 19 20 23 24 25 8 6 6 21 7 1 3 5 18 16 4 22 26 1 ILLUSTRATED PARTS BREAKDOWN VMH3000TP

This list contains replaceable parts used in your heater. When ordering parts, follow the

instructions listed under Replacement Parts on page 19 of this manual. KEY VMH3000TP NO. PART NO. DESCRIPTION QTY. 1 098304-01 Screw, #10 x 3/8" 6 2 100566-01CK Front Panel 1 3 100573-01BR Screen Assembly 1 4 100568-02BR Burner Shield 1 5 100903-04 Log, Service Kit 1 6 098303-02 Screw, #8 x 3/8" 6 7 099066-01 Mounting Bracket 1 8 M11084-26 Screw, #10 x 3/8" 8 9 100571-03BR Deflector Unit 1 10 098271-03 Ignitor Cable 1 11 098249-01 Nut, M5 2 12 099440-06 ODS/Pilot Assembly 1 12-1 098514-01 Thermocouple 1 12-2 098594-01 Ignitor Electrode 1 13 103447-01 Burner 1 14 099387-03 3/16" Pilot Tubing 1 15 103845-07 Injector 1 16 NJF-8C Nut, Hex 1 17 099415-06 Pressure Regulator 1 18 103408-01 Burner Bracket 2 19 103255-01 3/8" Outlet (Burner) Tubing 1 20 103256-01 3/8" Inlet Tubing 1 21 103837-03 Bracket Support 1 22 101046-01 Log Strap 2 23 098522-13 Thermostat Gas Valve 1 24 098529-07 Cabinet 1 25 097159-04 Piezo Ignitor 1 26 098304-03 Screw, #8 x 3/8" 5 PARTS AVAILABLE — NOT SHOWN 100562-01 Lighting Instructions Plate 1 100563-01 Warning Plate 1 101899-01 Brass Trim Assembly 1 100769-02 Brass Trim Hardware 1 100642-01 Hardware Package 1 100565-01 Warning Plate Fastener Kit 1 101416-30 Instructional Video 1

VENT-FREE GAS RESIDENTIAL HEATERS

® TECHNICAL SERVICE You may have further questions about in- stallation, operation, or troubleshooting. If so, contact DESA International’s Technical Service Department at 1-800-323-5190. You can also visit DESA International’s technical service web site at www.desatech.com. SPECIFICATIONS Btu (Variable) 15,000/30,000 Type Gas Propane/LP Only Ignition Piezo Pressure Regulator Setting 8" W.C. Inlet Gas Pressure (in. of water) * Maximum 14" Minimum 11" Dimensions, Inches (H x W x D) Heater 23.75 x 25.9 x 8.5 Carton 25.8 x 28.7 x 10.1 Weight (pounds) Heater 29 Shipping 35 * For purposes of input adjustment SERVICE HINTS When Gas Pressure Is Too Low • pilot will not stay lit • burner(s) will have delayed ignition • heater will not produce specified heat • propane/LP gas supply may be low When Gas Quality Is Bad • pilot will not stay lit • burner(s) will produce flames and soot • heater will backfire when lit You may feel your gas pressure is too low or gas quality is bad. If so, contact your local propane/LP supplier.

VALVE - GA5010

Equipment shutoff valve with 1/8" NPT tap. HEARTH BASE - GHB802 SERIES For locating heater on the floor. Includes brass trim. Complete installation instruc- tions included. ACCESSORIES Purchase these heater accessories from your local dealer. If they can not supply these accessories call DESA International’s Sales Department at 1-800-458-2472 for infor- mation. You can also write to the address listed on the back page of this manual. FAN KITS GA3100A - Manually-Controlled GA3200TA - Thermostatically- Controlled Provides better heat distribution. Makes heater more efficient. Complete installation and operating instructions included. PREMIER MANTEL Unfinished - GM903U Series Finished - GM902F Series White Lacquer - GM904W Series For use with heater. Features a built-in base. Sturdy hardwood construction with classic styling and attractive molding. Available in white lacquer, walnut finish or an unfin- ished hardwood, ready to stain or paint. Complete assembly and installation instruc- tions included. Note: White lacquer mantel features differ slightly from illustration. CORNER MANTEL Unfinished - GM703U Series Finished - GM702F Series For use with heater. Features a built-in base. Space-saving corner design featuring clean, classic lines. Available in a walnut finish or an unfinished hardwood, ready to stain or paint. Complete assembly and installation instructions included.

2701 Industrial Drive

P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com INTERNATIONAL LIMITED WARRANTY VENT-FREE PROPANE/LP GAS HEATERS DESA International warrants this product to be free from defects in materials and components for four (4) years and five (5) years on stainless steel burners from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented. This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit. This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner. TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO FOUR (4) YEARS ON ALL COMPONENTS AND FIVE (5) YEARS ON STAINLESS STEEL BURNERS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state. For information about this warranty write: KEEP THIS WARRANTY Model Serial No. Date Purchased Always specify model and serial numbers when communicating with the factory. We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied. WARRANTY INFORMATION NOT A UPC 104432-01 Rev. D 03/00 104432 01