Johnson Controls tyco CWS Manual
Text of the manual
Model CWS Specific Application
Concealed Pendent Vertical Sidewall
Window Sprinkler 5.6 K-factor
Page 1 of 8
DECEMBER 2019
TFP621
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Model CWS Specific Appli-
cation Concealed Pendent Vertical
Sidewall Window Sprinkler is a fast
response, solder-link type sprinkler
which delivers water to window glazing
in a horizontal pattern.
This sprinkler is the first concealed
window sprinkler to be specifically
Listed to provide complete wetting and
coverage for heat strengthened, tem-
pered, or ceramic glass windows using
closed sprinklers. As part of the testing,
the gas flow required to achieve the
time/temperature relationship speci-
fied in ASTM E119 was established in
a test furnace without sprinkler pro-
tection. A window assembly protected
with the Model CWS Window Sprinkler
was then installed in the test furnace,
and the same gas flow conditions were
maintained for a two-hour test period.
No cracking or visible damage to the
window was permitted during the test
period.
The success of the Model CWS Window
Sprinkler is based on its fast response
thermal sensitivity and on its specially
designed deflector which ensures the
spray pattern wets the entire surface
of the window.
Based on successful testing, the Model
CWS Window Sprinkler can be used
as interior protection for windows or
glazing in a sprinklered building or
non-sprinklered building in accordance
with Section 104 of the IBC (“Alternate
Materials, Design and Methods of Con-
struction and Equipment”).
As with any specific application sprin-
kler, the installation instructions
included in this data sheet must be pre-
cisely followed. If there are additional
local or jurisdictional installation stan-
dards/codes for window sprinklers on
glazed window systems, this document
does not relieve the designer/installer
from these requirements. Consult your
local jurisdiction to verify if or when
these additional guidelines must be
followed.
NOTICE
TYCO Model CWS Specific Applica-
tion Window Sprinkler described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
recognized by the approval agency, in
addition to the standards of any author-
ities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY3498
Technical
Data
Approvals
UL and C-UL Listed
Additional Recognition
ICC Evaluation Service (ESR-2397)
Pipe Thread Connection
1/2 in. NPT
Discharge Coefficient
K=5.6 GPM/psi½ (80,6 LPM/bar½)
Temperature Ratings
160°F (71°C) Sprinkler with
139°F (59°C) Cover Plate
212°F (100°C) Sprinkler with
165°F (74°C) Cover Plate
Finish
See Ordering Procedure section
Physical Characteristics
Body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Saddle . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Sealing Assembly . .Beryllium Nickel w/TEFLON
Soldered Link Halves . . . . . . . . . . . . . . . . Nickel
Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . Brass/Bronze
Guide Pin Housing . . . . . . . . . . . . . . . . . .Bronze
Guide Pins . . . . . . . . . . . . . . . . . Stainless Steel
Support Cup . . . . . . . . . . . . . . . . . . . . . . . Steel
Cover Plate . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Retainer . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Cover Plate Ejection Spring . . . . Stainless Steel
Page 2 of 8
SPRINKLER/SUPPORT CUP
ASSEMBLY
COVER PLATE/RETAINER ASSEMBLY
BODY
(1/2" NPT)
COVER
PLATE
EJECTION
SPRING
COVER PLATE
RETAINER
WITH THREAD
DIMPLES
SOLDER
TAB
SEALING
ASSEMBLY
COMPRESSION
SCREW
DEFLECTOR
(OPERATED
POSITION)
SPRINKLER
WRENCHING
AREA
SOLDER LINK
ELEMENT
SUPPORT
CUP WITH
ROLL FORMED
THREADS
GUIDE
PIN
GUIDE PIN
HOUSING
THREAD INTO
SUPPORT
CUP UNTIL
MOUNTING
SURFACE IS
FLUSH WITH
CEILING
LEVER
SADDLE
CAP
DEFLECTOR
3-3/16" DIA.
(81,0 mm)
2-1/2" DIA.
(63,5 mm)
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
DEFLECTOR IN
OPERATED POSITION
DISPOSABLE
PROTECTIVE CAP
1/2" (12,7 mm)
THREADED
ADJUSTMENT
3/16"
(4,8 mm)
3/32" GAP
(2,4 mm)
SPRINKLER-
SUPPORT CUP
ASSEMBLY
OPERATED
SPRINKLER
COVER
PLATE
RETAINER
1-1/8" (28,6 mm)
5/8" (15,9 mm)
TIP
SPRAY
1-15/16"±1/4"
FIGURE 1
MODEL CWS CONCEALED PENDENT VERTICAL SIDEWALL WINDOW SPRINKLER
ASSEMBLY
FIGURE 2
MODEL CWS CONCEALED PENDENT VERTICAL SIDEWALL WINDOW SPRINKLER
INSTALLATION
Page 3 of 8
Operation
When exposed to heat from a fire,
upon reaching the Cover Plate/Retainer
Assembly temperature rating, the
solder binding the Cover Plate to three
tabs of the Retainer melts, allowing
the Cover Plate to separate from the
Retainer and exposing the Sprinkler/
Support Cup Assembly. The Deflector,
supported by the Guide Pins, deploys
downward into the Operated Position.
As the temperature from the fire
reaches the Sprinkler temperature
rating, the solder binding the halves of
the Solder Link Element melts, allow-
ing the element to separate. With this
linkage no longer holding the Sealing
Assembly against the sprinkler orifice,
water is allowed to flow through the
waterway, spraying from the deflector
in a pattern toward the window glazing.
Design Criteria
The TYCO Model CWS Specific Appli-
cation Concealed Pendent Vertical
Sidewall Window Sprinkler is UL and
C-UL Listed.
This sprinkler is also Listed by Under-
writers Laboratories of Canada (ULC)
as providing a two-hour equivalency
for a fire separation assembly when
acceptable to the Authority Having
Jurisdiction and installed in accor-
dance with this code.
Area of Use
When acceptable to the authority
having jurisdiction, and unless modi-
fied by a local jurisdictional standard
or code mentioned previously, the
Model CWS Window Sprinkler may be
used in either a sprinklered or unsprin-
klered building to protect non-operable
window openings that are part of a fire
separation provided:
• in an interior fire separation, the win-
dow sprinklers are installed on both
sides of the window in the fire sepa-
ration (Figure 4A-1),
• in jurisdictions where exterior spatial
separation (that is, separation from
adjacent space) is defined as pro-
tecting an adjacent building from a
fire in your building, window sprin-
klers are installed on the interior side
of the building (Figure 4A-2).
System Protection Type
Interior: Wet Systems
Glass Type
The following types and thicknesses of
glass are recognized for use with the
Model CWS Window Sprinkler:
• Non-operable, heat-strengthened,
tempered, single-glazed (single
pane), not less than 1/4 in. (6 mm)
thick;
• Non-operable, heat-strengthened,
tempered, double-glazed (double
pane or insulated), not less than
1/4 in. (6 mm) thick;
• Non-operable, UL Classified and
labeled FIRELITE PLUS CWS
ceramic glass by TECHNICAL
GLASS PRODUCTS (TGP), not less
than 5/16 in. (8 mm) thick; or,
Note: Refer to FIRELITE PLUS CWS ceramic
glass technical data sheet for other classi-
fication limitations at www.fireglass.com.
• Non-operable, stronger glass win-
dow assemblies, not less than ¼ in.
(6 mm) thick.
Type of Window Frame/Mullion
Non-combustible Frame with a stan-
dard EPDM rubber gasket seal
Vertical joints of glass panes must be
connected by butt-joints using a sili-
cone sealant between the individual
panes or by Noncombustible Mullions.
(See Figures 4B-1 and 4B-2)
Maximum Length of
Window Assembly
Unlimited
Maximum Height of
Window Assembly
13 ft (3,96 m)
(See Figure 4B)
Maximum Distance Between
Window Sprinklers
8 ft (2,44 m)
(See Figures 4B-1 and 4B-2)
Minimum Distance Between
Window Sprinklers
6 ft (1,83 m) unless separated by a
baffle or mullion of sufficient depth to
act as a baffle.
A mullion will act as a baffle when the
mullion extends to the back of the
sprinkler deflector.
(See Figures 4B-1 and 4B-2)
Minimum Distance from
Standard Sprinklers
6 ft (1,83 m) unless separated by a
baffle
Sprinkler Location
• Mullioned Glazing Assemblies:
Locate window sprinklers within
each mullioned glazing segment.
See Figure 4B-1.
• Butt-Jointed Glazing Assem-
blies: Locate window sprinklers
on maximum 8 ft (2,44 m) centers.
See Figure 4B-2.
Maximum Distance from
Vertical Mullion
4 ft (1,22 m)
(See Figure 4B-1)
ACCEPTS 1/2" DRIVE
OR 7/8" OPEN-END
WRENCH
SUPPORT
CUP
SPRINKLER
WRENCHING
HEX
WRENCH HEX
RECESS
SPRAY
DEFLECTOR
ARROW INDICATES
SPRINKLER SPRAY
DIRECTION TOWARD
WINDOW GLAZING
WRENCH FULLY
ENGAGED ON
SPRINKLER
FIGURE 3
W-TYPE 39
SPRINKLER WRENCH
Page 4 of 8
Minimum Distance from
Vertical Mullions
4 in. (101,6 mm)
(See Figure 4B-1)
Intermediate Horizontal Mullions
Intermediate Horizontal Mullions
were not tested with the Model CWS
Window Sprinkler. Their use is outside
the scope of the Specific Application
Listing for the window sprinklers. See
Figure 4B-3.
Deflector Location
Sprinkler Deflectors must be located as
described below in order to ensure that
the entire surface of the glass window
is covered. Sprinkler Deflectors are
positioned with respect to the window
frame, not the ceiling.
• Model CWS Window Sprinkler:
Locate 6 in. to 12 in. (152,4 mm to
304,8 mm) from the face of the glass
and 2 in. ± 2 in. (50,8 mm ± 50,8
mm) above the top of exposed glass.
See Figure 4C.
Minimum Clearance from Face of
Glass to Combustible Materials
For glass types other than FIRELITE
PLUS CWS ceramic glass by TGP, all
combustible materials shall be kept
2 in. (50,8 mm) from the front face of
the glass. This can be accomplished
by a minimum 36 in. (914,4 mm) pony
wall or other method acceptable to the
authority having jurisdiction.
Recommended Hydraulic
Requirements
The authority having jurisdiction should
be consulted to determine the hydraulic
requirements for each installation.
Interior Protection Sprinklered
Building
Identify which compartmented area
has the most hydraulically demanding
window sprinklers. Calculate up to the
most demanding 46.5 linear feet (14,2
linear meters) of Model CWS Window
Sprinkler on one side of the glazing.
The 46.5 linear feet (14,2 linear meters)
is based upon 1.2 x the square root of
the system area of operation, when the
system area of operation is 1500 sq.
ft in accordance with NFPA 13 Light/
Ordinary Hazard density curves.
Where the area of Glazing is less than
46.5 linear feet (14.2 linear meters), all
window sprinklers on one side shall be
calculated.
FIGURE 4A-1 - INTERIOR FIRE SEPARATION
FIGURE 4A-2 - EXTERIOR FIRE SEPARATION - SPRINKLERS INSIDE
FIGURE 4A (A-1 AND A-2)
TYPICAL NON-OPERABLE WINDOW OPENINGS
If an area reduction for quick response
sprinklers is utilized, the linear length of
the calculated window sprinklers may
be reduced, but in no case shall be less
than 36 linear feet (1.2 x √900).
If a single fire can be expected to
operate Model CWS Window Sprinkler
and sprinklers within the design area of
a hydraulically calculated system, the
water demand of the window sprinklers
shall be added to the water demand of
the hydraulic calculations and shall
be balanced to the calculated area
demand.
If the window sprinklers are located in
an area other than the hydraulic design
area, the demand of the window sprin-
klers is not required to be added to the
demand of the remote hydraulic design
area. However, it is necessary to prove
hydraulically the simultaneous opera-
tion of the Model CWS Window Sprin-
kler and the ceiling sprinklers adjacent
to the window sprinklers.
Interior Protection
Non-Sprinklered Building
Calculate all sprinklers on the most
demanding side of the glazing assem-
bly within the enclosure.
Duration of Water Supply
Duration of water supply must comply
with requirements of NFPA. If window
sprinklers are used to provide the
equivalency of a fire rating, the water
supply must be capable of supplying
water for the required rating period.
Minimum Flow per Sprinkler
20 GPM (75,7 LPM) for sprinkler
spacing of 6 ft to 8 ft (1,83 m to 2,44
m) or 15 GPM (56,8 LPM) for sprinkler
spacing less than 6 ft (1,83 m).
Maximum Pressure per Sprinkler
175 psi (12,07 bar)
INSIDE
INSIDE
When acceptable to the Authority Having Jurisdiction the Model CWS Specifc Application
Window Sprinkler may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are in an interior fre separation, the window sprinklers
are installed on both sides of the window in the fre separation.
INSIDE
OUTSIDE
EXPOSURE
SIDE
When acceptable to the Authority Having Jurisdiction the Model CWS Specifc Application
Window Sprinkler may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a fre separation provided in jurisdictions
where exterior spatial separation is defned as protecting an adjacent building from a fre
in your building, window sprinklers are installed on the interior side of the glass.
Page 5 of 8
MULLION
BUTT JOINT
4'-0" (1,22 m) MAXIMUM
0'-4" (101,6 mm) MINIMUM
8'-0" (2,44 m)
MAXIMUM
MODEL CWS
CONCEALED
SPRINKLER
6'-0" (1,83 m)
MINIMUM
Window Sprinklers are NOT
required to be located with
respect to horizontal or
vertical butt joints.
MODEL CWS
CONCEALED
SPRINKLER
MULLION
INTERMEDIATE
MULLION
Window Sprinklers are NOT
listed to protect windows
when intermediate horizontal
mullions are present.
4'-0" (1,22 m) MAXIMUM
0'-4" (101,6 mm) MINIMUM
8'-0" (2,44 m)
MAXIMUM
MODEL CWS
CONCEALED
SPRINKLER
6'-0" (1,83 m)
MINIMUM
MULLION
Minimum distance between
Window Sprinklers is 6'-0"
(1,83 m) unless separated
by a baffe or mullion of
suffcient depth to act as a
baffe.
*
*
FIGURE 4B (B-1 TO B-3)
WINDOW MULLIONS AND BUTT JOINTS
FIGURE 4B-1 - MULTIPLE WINDOWS SEPARATED BY MULLIONS
FIGURE 4B-2 - MULTIPLE WINDOWS SEPARATED BY BUTT JOINTS
FIGURE 4B-3 - WINDOWS WITH HORIZONTAL MULLIONS
Page 6 of 8
INSTALLATION
NOTE:
BUILDING
STRUCTURE
NON-OPERABLE
GLASS WINDOW
ORIENT SPRINKLER
WITH GUIDE PINS
ALIGNED PARALLEL
TO GLAZING AND
DEFLECTOR SPRAY
ARROW POINTED
TOWARD GLAZING
NO
MAXIMUM
HEIGHT
6" to 12"
(152 to
305 mm)
CENTERLINE
OF SPRINKLER
WATERWAY
13'-0"
(3,96 m)
MAXIMUM
EXPOSED
GLAZING
HEIGHT
SPRAY
FLUSH
OR EXPOSED
WINDOW
FRAME
2"±2"
(50,8 mm
±50,8 mm)
MODEL CWS
SPRINKLER
SHOWN ON ONE
SIDE OF GLAZING
FOR CLARITY
FOR GLASS
TYPES OTHER
THAN FIRELITE
PLUS CWS
CERAMIC GLASS
BY TGP, ALL
COMBUSTIBLE
MATERIALS
SHALL BE KEPT
2" (50,8 mm)
MINIMUM FROM
SPRINKLERED
FACE OF
GLAZING. THIS
MAY BE DONE
THROUGH USE
OF 3'-0" (0,9 m)
MINIMUM
PONY WALL
INSTALLATION
NOTE:
MODEL CWS
SPRINKLER
SHOWN ON ONE
SIDE OF GLAZING
FOR CLARITY
FOR GLASS
TYPES OTHER
THAN FIRELITE
PLUS CWS
CERAMIC GLASS
BY TGP, ALL
COMBUSTIBLE
MATERIALS
SHALL BE KEPT
2" (50,8 mm)
MINIMUM FROM
SPRINKLERED
FACE OF
GLAZING. THIS
MAY BE DONE
THROUGH USE
OF 3'-0" (0,9 m)
MINIMUM
PONY WALL
BUILDING
STRUCTURE
TYPICAL
WINDOW
COVERING
NON-OPERABLE
GLASS WINDOW
INSTALL MODEL
CWS SPRINKLERS
INTO RECESSED
CEILING SPACES.
DO NOT PLACE
BLINDS, CURTAINS
OR OTHER WINDOW
COVERINGS
BETWEEN
SPRINKLER
AND GLAZING
FLUSH
OR EXPOSED
WINDOW
FRAME
SPRAY
FIGURE 4C
MODEL CWS CONCEALED PENDENT
VERTICAL SIDEWALL WINDOW SPRINKLER
TYPICAL INSTALLATION
FIGURE 4D
MODEL CWS CONCEALED PENDENT
VERTICAL SIDEWALL WINDOW SPRINKLER
TYPICAL INSTALLATION WITH WINDOW COVERING
Page 7 of 8
Installation
The TYCO Model CWS Specific
Application Window Sprinkler must
be installed in accordance with this
section.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 14
lb-ft (9,5 to 19,0 N∙m). Higher levels of
torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Sprinkler
by under- or over-tightening the Sprin-
kler/Support Cup Assembly. Re-adjust
the position of the sprinkler fitting to
suit.
Step 1. Install the Model CWS Window
Sprinkler only in the pendent position
with the center-line of the sprinkler
parallel to the glass surface. Orient the
sprinkler so that the direction of flow
indicated on the sprinkler deflector is
facing the window.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant
applied to the pipe threads, and using
the W-Type 39 Wrench, as shown in
Figure 3, install and tighten the Sprin-
kler/Support Cup Assembly into the
fitting. The W-Type 39 Wrench will
accept a 1/2 in. ratchet drive.
Step 4. Replace the Protective Cap by
pushing it upwards until it bottoms
out against the Support Cup
(see Figure 2). The Protective Cap
helps prevent damage to the Deflector
and Guide Pin Housing during ceiling
installation and/or finish. You can also
use the Protective Cap to locate the
center of the clearance hole by gently
pushing the ceiling material up against
the center point of the Protective Cap.
NOTICE
As long as the Protective Cap remains
in place, the system is considered “Out
of Service”.
Step 5. After the ceiling has been
completed with the 2 1/2 in. (63,5 mm)
diameter clearance hole and in prep-
aration for installing the Cover Plate/
Retainer Assembly, remove and
discard the Protective Cap. Verify that
the Deflector moves up and down
freely. If the Sprinkler is damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler. Do not attempt to modify or repair
a damaged sprinkler.
Step 6. Push on the Cover Plate
Assembly until its flange comes in
contact with the ceiling.
Do not continue to push on the Cover
Plate Assembly such that it lifts a
ceiling panel out of its normal position.
If the Cover Plate Assembly cannot
be engaged with the Mounting Cup
or the Cover Plate Assembly cannot
be engaged sufficiently to contact the
ceiling, the Sprinkler Fitting must be
repositioned.
Care and
Maintenance
The TYCO Model CWS Specific Appli-
cation Window Sprinkler must be main-
tained and serviced in accordance with
this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the Cover Plate Assem-
bly may delay sprinkler operation in a
fire situation. When properly installed,
there is a nominal 3/32 in. (2,4 mm) air
gap between the lip of the Cover Plate
and the ceiling, as shown in Figure 2.
This air gap is necessary for proper
operation of the sprinkler. If the ceiling
is to be repainted after the installation
of the Sprinkler, care must be exercised
to ensure that the new paint does not
seal off any of the air gap.
Factory painted Cover Plates must not
be repainted. They should be replaced,
if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a fire.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers
damaged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. See the Installation section
for additional information.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this doc-
ument, as well as with the applicable
standards recognized by the Approval
agency, such as NFPA 25, in addition
to the standards of any authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Page 8 of 8
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TECHNICAL GLASS PRODUCTS and TGP are registered trademarks of Technical Glass Products;
FIRELITE and FIRELITE PLUS are registered trademarks of Nippon Electric Glass Co., Ltd.; TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Model CWS Specific Applications
Concealed Pendent Vertical
Sidewall Window Sprinkler
Specify: Model CWS Specific Applica-
tion Concealed Pendent Vertical Side-
wall Window Sprinkler, SIN TY3498,
(specify) temperature rating, and P/N
(specify):
160°F (71°C). . . . . . . . . . . . . . . . . .50-630-0-160
212°F (100°C) . . . . . . . . . . . . . . . . .50-630-0-212
Note: Sprinkler and Cover Plates are sepa-
rately sold. See Cover Plate Assemblies
subsection for ordering information.
Cover Plate Assemblies
Specify: Model CWS Concealed Sprin-
kler Cover Plate Assembly, (specify)
temperature rating, (specify) finish,
P/N (specify):
139°F (59°C)a
Ivory (RAL1015) . . . . . . . . . . . . . . . 56-214-0-135
Bright Chrome . . . . . . . . . . . . . . . . 56-214-1-135
Beige (RAL1001) . . . . . . . . . . . . . . 56-214-2-135
Pure White (RAL9010)* . . . . . . . . . 56-214-3-135
Signal White (RAL9003)** . . . . . . . 56-214-4-135
Grey White (RAL9002). . . . . . . . . . 56-214-5-135
Brown (RAL8028). . . . . . . . . . . . . . 56-214-6-135
Black (RAL9005) . . . . . . . . . . . . . . 56-214-7-135
Brushed Brass . . . . . . . . . . . . . . . . 56-214-8-135
Brushed Chrome . . . . . . . . . . . . . . 56-214-9-135
Custom Paint . . . . . . . . . . . . . . . . . 56-214-X-135
165°F (74°C)b
Ivory (RAL1015) . . . . . . . . . . . . . . . 56-214-0-165
Bright Chrome . . . . . . . . . . . . . . . . 56-214-1-165
Beige (RAL1001) . . . . . . . . . . . . . . 56-214-2-165
Pure White (RAL9010)* . . . . . . . . . 56-214-3-165
Signal White (RAL9003)** . . . . . . . 56-214-4-165
Grey White (RAL9002). . . . . . . . . . 56-214-5-165
Brown (RAL8028). . . . . . . . . . . . . . 56-214-6-165
Black (RAL9005) . . . . . . . . . . . . . . 56-214-7-165
Brushed Brass . . . . . . . . . . . . . . . . 56-214-8-165
Brushed Chrome . . . . . . . . . . . . . . 56-214-9-165
Custom Paint . . . . . . . . . . . . . . . . . 56-214-X-165
a. For use with 160°F (71°C) sprinklers
b. For use with 212°F (100°C) sprinklers
* Eastern Hemisphere sales only
** Previously known as Bright White
Sprinkler Wrench
Specify: W-Type 39 Sprinkler Wrench,
P/N 56-000-1-950