Pro-face GP2500-TC11 Manual
Read Online
Read the Pro-face GP2500-TC11 Manual online using the built-in PDF viewer.
Text of the manual
Do not create GP touch panel switches that could possibly endanger the safety of equipment
and personnel. Damage to the GP, its I/O unit(s), cable(s), and other related equipment can
cause an output signal to remain continuously ON or OFF and possibly cause a major acci-
dent. Therefore, design all monitoring circuits using limit switches, etc. to detect incorrect
device movement. To prevent accidents related to incorrect signal output or operation, design
all switches used to control vital machine operations so they are operated via a separate
control system.
•
Do not create switches used to control machine safety operations, such as an emergency stop
switch, as a GP touch screen icon. Be sure to install these switches as separate hardware
switches, otherwise severe bodily injury or equipment damage can occur.
•
Please design your system so that equipment will not malfunction due to a communication
fault between the GP and its host controller. This is to prevent any possibility of bodily injury
or material damage.
•
Do not use the GP unit as a warning device for critical alarms that can cause serious operator
injury, machine damage or production stoppage. Critical alarm indicators and their control/
activator units must be designed using stand-alone hardware and/or mechanical interlocks.
•
The GP is not appropriate for use with aircraft control devices, aerospace equipment, central
trunk data transmission (communication) devices, nuclear power control devices, or medical
life support equipment, due to these devices’ inherent requirements of extremely high levels
of safety and reliability.
•
When using the GP with transportation vehicles (trains, cars and ships), disaster and crime
prevention devices, various types of safety equipment, non-life support related medical
devices, etc. redundant and/or failsafe system designs should be used to ensure the proper
degree of reliability and safety.
•
After the GP’s backlight burns out, unlike the GP’s “Standby Mode”, the touch panel is still
active. If the operator fails to notice that the backlight is burned out and touches the panel, a
potentially dangerous machine miss-operation can occur. Therefore, do not use GP touch
switches for the control of any equipment safety mechanisms, such as Emergency Stop
switches, etc. that protect humans and equipment from injury and damage. If your GP's
backlight suddenly turns OFF, use the following steps to determine if the backlight is actu-
ally burned out.
1) If your GP is not set to "Standby Mode" and the screen has gone blank, your backlight is
burned out.
2) Or, if your GP is set to "Standby Mode", but touching the screen does not cause the
display to reappear, your backlight is burned out.
Also, to prevent accidental machine miss-operation, Digital suggests you use the GP’s built-
in “USE TOUCH PANEL AFTER BACKLIGHT BURNOUT” feature, that will automati-
cally detect a burnout and disable the touch screen.
Installation
•
High voltage runs through the GP. Except for replacing the backlight, never disassemble the
GP, otherwise an electric shock can occur.
•
Do not modify the GP unit. Doing so may cause a fire or an electric shock.
•
Do not use the GP in an environment where flammable gasses are present, since operating
the GP may cause an explosion.
Wiring
•
To prevent an electric shock, be sure to confirm that the GP's power cord is not connected to
the main power when connecting any cords, cables or lines to the GP.
•
Be sure to replace the GP's plastic terminal block cover after wiring is completed, since
operating the GP without the cover may lead to an electric shock
•
Do not use power beyond the GP's specified voltage range. Doing so may cause a fire or an
electric shock.
Maintenance
•
The GP uses a lithium battery for backing up its internal clock data. If the battery is incor-
rectly replaced, the battery may explode. To prevent this, please do not replace the battery
yourself. When the battery needs to be replaced, please contact your local GP distributor.
Essential Safety Precautions
Be sure to securely connect all cable connectors to the GP. A loose connection may cause incorrect
input or output.
Wiring
•
Ground the GP's FG line separately from other units’ FG lines. Putting these FG lines too close
may cause an electric shock or unit malfunction. Be sure to use a grounding resistance of 100Ω or
less and a 2mm2 or thicker wire, or your country’s applicable standard.
•
Correctly wire the GP, be sure that the rated voltage and terminal layout are within the designated
range. If the voltage supplied differs from the rated voltage, or incorrect wiring or grounding is
performed, it may cause a fire or unit malfunction.
•
Use only the designated torque to tighten the GP's terminal block screws. If these screws are not
tightened firmly, it may cause a short-circuit, fire, or GP malfunction.
•
Be careful that metal filings and wiring debris do not fall inside the GP, since they can cause a fire,
GP malfunction, or incorrect operation.
Maintenance
•
The liquid crystal panel contains a powerful irritant and if for any reason the panel is damaged and
this liquid contacts any part of your body, be sure to wash that area with running water for 15
minutes. If any of this liquid enters your eye, flush your eye for 15 minutes with running water and
contact a physician.
•
Prior to inserting or removing a CF Card, be sure to turn the GP’s CF Card ACCESS switch OFF
and to confirm that the ACCESS lamp is not lit. If you do not, CF Card internal data may be
damaged or lost.
•
While a CF Card is being accessed, NEVER turn OFF or reset the GP, or insert or remove the CF
Card. Prior to performing these operations, create and use a special GP application screen that will
prevent access to the CF Card.
Unit Disposal
•
When this unit is disposed of, it should be done so according to your country's regulations for
similar types of industrial waste.
General Safety Precautions
•
Do not strike the touch panel with a hard or pointed object, or press on the touch panel with too
much force, since it may damage the touch panel or the display.
•
Do not install the GP where the ambient temperature can exceed the allowed range. Doing so may
cause the GP to malfunction or shorten its operation life.
•
Do not restrict or limit the GP’s naturally occurring rear-face ventilation, or storing or using the GP
in an environment that is too hot.
•
Do not use this unit in areas where large, sudden temperature changes can occur. These changes
can cause condensation to form inside the unit, possibly causing the unit to malfunction.
•
Do not allow water, liquids, metal or charged particles to enter inside the GP’s case, since they can
cause either a GP malfunction or an electrical shock. The allowable pollution degree is 2.
•
Do not use or store the GP in direct sunlight, or in excessively dusty or dirty environments.
•
Do not store or use the unit where strong jolting or excessive vibration can occur.
•
Do not store or use the GP where chemicals (such as organic solvents, etc.) and acids can evapo-
rate, or where chemicals and acids are present in the air.
Corrosive chemicals:
Acids, alkalines, liquids containing salt
Flammable chemicals:
Organic Solvents
•
Do not use paint thinner or organic solvents to clean the GP.
•
Do not store or operate the LCD display in areas receiving direct sunlight, since the sun's UV rays
may cause the LCD display’s quality to deteriorate.
•
Storing this unit in areas at a temperature lower than is recommended in this manual’s specifica-
tions may cause the LCD display’s liquid to congeal, which may damage the panel. Conversely, if
the storage area’s temperature becomes higher than the allowed level, the LCD’s liquid will be-
come isotropic, causing irreversible damage to the LCD. Therefore, be sure to store the panel only
in areas where temperatures are within those specified in this manual.
•
After turning the GP OFF, be sure to wait a few seconds before turning it ON again. If the GP
started too soon, it may not start up correctly.
•
Due to the possibility of unexpected accidents, be sure to back up the GP’s screen data regularly.
The GP2500-TC11*1 and the GP2600-TC11*1 are UL/c-UL(CSA) recognized
components. (UL file No. E231702)
This Unit conforms as a component to the following standards:
�����UL1604
Electrical Equipment for Use in Class I and II Division 2 and Class III Hazard-
ous (Classified) Locations
�����UL60950
Safety Standard for Information Technology Equipment (3rd Edition, issued
December 1, 2001)
�����CAN/CSA-C22.2, No.60950-00
Safety Standard for Information Technology Equipment (3rd Edition, issued
December 1, 2001)
�����CAN/CSA-C22.2, No.213-M1987
Safety Standard for Information Technology and Electrical Business Equipment
GP2500-TC11 (UL Registration Model : 3180021-01)
GP2600-TC11 (UL Registration Model : 3180021-02)
• The GP must be used as a built-in component of an end-use product.
• The GP units must be used indoors only.
• The GP should be installed in the front face of a metal panel.
• If the GP is installed so as to cool itself naturally, be sure to install it in a verti-
cal panel. Also, be sure that the GP is mounted at least 100mm away from
adjacent structures and other equipment, otherwise, the heat generated by the
GP's internal components may become higher than that allowed by UL stan-
dard requirements.
• Make sure to set up a switch to turn off the power to the GP in an accessible
position on the end-use product that the GP unit is built-in. Make sure to
consider the current and voltage when selecting the switch.
• Make sure that the frame of the product to which the GP unit is built-in con-
forms to UL60950 standard requirements.
UL1604 Conditions of Acceptability and Handling Cautions:
1. Power, input and output (I/O) wiring must all be in accordance with Class I,
Division 2 wiring methods, Article 501-4 (b) of the National Electrical Code,
NFPA 70, or as specified in Section 18-152 of the Canadian Electrical Code
for units installed within Canada, and in accordance with that location's au-
thority.
2. Suitable for use in Class I, Division2, GroupsA, B, C and D hazardous loca-
tion.
3. WARNING: Explosion hazard - substitution of components may impair
suitability for Class I, Division2.
4. WARNING: Explosion hazard - when in hazardous locations, turn the power
off before replacing or wiring modules.
5. WARNING: Explosion hazard - do not disconnect equipment unless power
has been switched off or the area is known to be nonhazardous.
6. WARNING: Explosion hazard - do not connect/ disconnect equipment unless
area is known to be nonhazardous. Port is for system set up and diagnostics.
UL/c-UL(CSA) Approval
The GP2500-TC11*1 and GP2600-TC11*1 are CE marked products that con-
form to EMC directives and the Low-voltage directive. These units also con-
form to EN55011 ClassA, EN61000-3-2, EN-61000-3-3, EN61000-6-2,
EN60950 directives.
For detailed CE marking information, please contact your local distributor.
CE Marking
DIGITAL ELECTRONICS CORP.
REV ABC*EFGHIJKLMNOPQRSTUVWXYZ**345
Revision Version
• The GP must be used as a built-in component of an end-use product.
• The GP units must be used indoors only.
• The GP should be installed in the front face of a metal panel.
• If the GP is installed so as to cool itself naturally, be sure to install it in a verti-
cal panel. Also, be sure that the GP is mounted at least 100mm away from
adjacent structures and other equipment, otherwise, the heat generated by the
GP's internal components may become higher than that allowed by the stan-
dard requirements.
• Make sure to set up a switch to turn off the power to the GP in an accessible
position on the end-use product that the GP unit is built-in. Make sure to
consider the current and voltage when selecting the switch.
• Make sure that the frame of the product to which the GP unit is built-in con-
forms to EN60950 standard requirements.
The revision version can be determined by the identification label or revision
stickers that are placed on the main unit of the GP. The characters and numer-
als in the "REV" area that are replaced with asterisks (*), or marked with a
marker indicate the revision version.
In the example below, the asterisks "*" are placed at positions "D", "1", and
"2", which indicates the revision version as "D, 1, 2".
Identification Label
Revision Sticker
*1
The products on which Revision "3" is marked conform to the stan-
dard requirements. For more information on how to determine the
revision version, refer to section "Revision Version".
The following items are included in the GP's package. Before using the GP, please
confirm that all items listed here are present.
This unit has been carefully packed, with special attention to quality. However, should
you find anything damaged or missing, please contact your local GP distributor im-
mediately.
Package Contents
� GP Unit (1)
(GP2500-TC11/
GP2600-TC11)
� Installation Guide (1)
� Installation Gasket
(1, attached to the GP unit)
� Installation Fasteners (4/set)
� Screw Lock Terminal Block
(1, attached to the GP unit)
D : Power Input Terminal Block
E : Expansion Unit Interface 1
F : Expansion Unit Interface 2
G : CF Card Expansion Interface
H : CF Card Cover
I : CF Card Access Lamp
J : CF Card Slot
K : Serial Interface (HOST-I/F 25-pin)
L : Serial Interface (SUB-SIO 9-pin)
M: Printer Interface
(Half Pitch 20-pin)
N : Ethernet Interface (10BASE-T)
O : Screw Lock Terminal Block
(12 pin)
P : Tool Connector
Connects a Data Transfer Cable or
bar code reader
LED
GP Status
Not Lit
Power is OFF.
Green
Normal operation
Orange
Backlight is not functioning.
(Refer to 10.Replacing the
Backlight. )
A : Display
B : Touch Panel
C : Status LED
These switches are located inside the CF Card's cover.
The factory settings for these switches are OFF.
Dip Switches
Rear View of GP
Dip Switch
Function
ON
OFF
Note
1
This Dip switch
setting controls
the startup from a
CF Card.
Startup from
CF Card is
enabled.
Startup from
CF Card is
disabled.
CF Card with
startup data
required.
2
Reserved
3
Reserved
4
This setting
controls the forced
closing of the CF
Card cover.
Forced close
enabled.
Forced close
disabled.
Used when CF
Card cover is
damaged.
Keep these
switches OFF
Send Data (RS-232C)
3
RD
Receive Data (RS-232C)
4
RS
Request to Send (RS-232C)
5
CS
Clear to Send (RS-232C)
6
DR
Data Set Ready (RS-232C)
7
SG
Signal Ground
8
CD
Carrier Detect (RS-232C)
9
TRMX
Termination (RS-422)
10
RDA
Receive Data A (RS-422)
11
SDA
Send Data A (RS-422)
12
NC
No Connection(Reserved)
13
NC
No Connection(Reserved)
14
VCC
5V±5% Output 0.25A
15
SDB
Send Data B (RS-422)
16
RDB
Receive Data B (RS-422)
17
RI
Ring Indicate (RS-232C)
18
CSB
Clear to Send B (RS-422)
19
ERB
Enable Receive B (RS-422)
20
ER
Enable Receive (RS-232C)
21
CSA
Clear to Send A (RS-422)
22
ERA
Enable Receive A (RS-422)
23
NC
No Connection(Reserved)
24
NC
No Connection(Reserved)
25
NC
No Connection(Reserved)
4
Interfaces
Recommended Connector: Dsub 25 pin plug XM2A-2501
Recommended Cover
: Dsub 25 pin Cover XM2S-2511
Jack Screw XM2Z-0071
Recommended Cable
: CO-MA-VV-SB5P x 28AWG
• This GP unit’s serial port is not isolated. When the host (PLC) unit is
also not isolated, and to reduce the risk of damaging the RS-422 circuit,
be sure to connect the #7 SG (Signal Ground) terminal.
• Pin #14 (VCC) DC 5V Output is not protected. To prevent damage or unit
malfunction, use only the designated level of current.
• Inside the GP2500/2600 unit, the SG (Signal Ground) and FG (Frame
Ground) terminals are connected to each other.
• When connecting an external device to the GP with the SG terminal,
ensure that no short-circuit loop is created when you setup the system.
Use rough metric type M2.6 x 0.45p threads to hold the cable’s set
(fastening) screws in place.
� Serial Interface (HOST-I/F)
This interface is used to connect the GP to the host (PLC), via an RS-232C or RS-
422 cable.
1
14
13
25
When creating a cable, please be aware of the following:
� Screw Lock Terminal Block (12 pin)
This interface performs external reset, alarm output, buzzer output and sound output.
� Ethernet Interface
This interface complies with the IEEE802.3 standard for Ethernet (10BASE-T)
connections. This interface uses an RJ-45 type modular jack connector (8 points).
� CF Card Interface
This slot accepts a CF Card.
� Expansion CF Card Interface
This interface is for connecting the Front Maintenance CF Card Unit.
� Expansion Unit Interface 1
This interface is used to connect an expansion unit that can transmit data over a
Fieldbus or similar type of network.
� Expansion Unit Interface 2
Provides expanded features.
1
12
5
Installation
• Before installing the GP into a cabinet or panel, check that the
installation gasket is securely attached to the unit.
• Be sure the gasket's seam is not inserted into any of the unit's
corners, only in the straight sections of the groove. Inserting it
into a corner may lead to its eventually tearing.
• A gasket which has been used for a long period of time may have
scratches or dirt on it, and could have lost much of its dust and
drip resistance. Be sure to change the gasket periodically (or
when scratches or dirt become visible).
� Confirm the Installation Gasket's Positioning
It is strongly recommended that you use the gasket. It absorbs vibration in addition
to repelling water.
Place the GP on a level surface with the display panel facing downward. Check
that the GP’s installation gasket is seated securely into the gasket’s groove, which
runs around the perimeter of the panel’s frame.
Gasket
Rear face
Pin Arrangement
I/F
Pin No. Signal Name
Description
External Reset
1
AUXCOM
External Reset Common
2
AUXRESET External Reset Input
AUX
3
RUN
Online
4
ALARM
System Alarm Output
5
OUTCP
24VDC
6
BUZZ
External Buzzer Output
7
RESERVE
Reserved
8
OUTCN
0V
9
RESERVE
Reserved
Sound I/F
10
SP OUT
Speaker Output
11
GND
Ground
12
LINE OUT
Sound Line Out Output
• To avoid an electric shock, when connecting the GP's power cord
terminals to the power terminal block, confirm that the GP's power
supply is completely turned OFF, via a breaker, or similar unit.
• GP2500-TC11 and GP2600-TC11 units that are not marked as REV
"3" are designed for use only with 100 VAC input.
• Since there is no power switch on the GP unit, be sure to attach a
breaker-type switch to its power cord.
under 4-R3
Panel
Unit: mm [in]
Installation
fastener
� Create a Panel Cut and insert the GP into the panel from the front
� Attach the Installation Fasteners from Inside the Panel
The following figures show the four(4) fastener insertion slot locations. Insert
each fastener's hook into the slot and tighten it with a screwdriver.
Panel
GP
• Tightening the screws with too much force can damage the GP's
plastic case.
• The necessary torque is 0.5 N•m.
• Depending on the installation panel's thickness, etc., the number of
installation fasteners used may need to be increased to provide the
desired level of moisture resistance.
Insertion Slots
Insertion Slots
Top
Bottom
301.5 [11.87 ]
+1
0
+0.04
0
227.5
[8.96 ]
+0.04
0
GP
WARNINGS
+1
0
• To avoid a short caused by loose ring terminals, be sure to use
ring terminals with an insulating sleeve.
• When the FG terminal is connected, be sure the wire is grounded.
Not grounding the GP unit will result in excess noise and vibra-
tion.
• Wherever possible, use thick wires (max. 2 mm2) for power termi-
nals, and twist the wire ends before attaching the ring terminals.
• Be sure to use the following size ring terminals.*1
Power Input
Terminal Block
Rear of GP
Ring Terminals*1
����� Connecting the GP Power Cord
When connecting the power cord, be sure to follow the procedures given below.
1. Confirm that the GP's Power Cord is unplugged from the power supply.
2. Use a screwdriver to remove the Power Input Terminal Block's clear plastic
cover.
3. Unscrew the screws from the middle three (3) terminals, align the Ring Terminals
and re-attach the screws.
4. Replace the Power Input Terminal Block's clear plastic cover.
• Confirm that the ring terminal wires are connected correctly.
• The torque required to tighten these screws is 0.5 to 0.6 N•m.
*1
L=AC Input Live Line
N=AC Input Neutral Line
FG=Grounding Terminal connected to the GP chassis.
Suggested Ring Terminal : equivalent to V2-MS3 (made by JST)
10 Replacing the Backlight
9
Input/Output Signal Line Cautions
• All GP Input and Output signal lines must be separated from all operating
circuit (power) cables.
• If this is not possible, use a shielded cable and ground the shield.
The GP unit's backlight is user replacable.
Use of a different model backlight may cause a GP malfunc-
tion or breakdown.
For an explanation of how to replace the GP's backlight, please refer to the User
Manual or the Installation Guide which comes with the replacement backlights (sold
separately).
Corresponding Replacement Backlights
• When grounding to the GP's rear face FG terminal, (on the Power Input
Terminal Block), be sure to create an exclusive ground.*1
• Inside the GP2500/GP2600 unit, the SG (Signal Ground) and FG
(Frame Ground) terminals are connected to each other.
• When connecting an external device to the GP with the SG terminal,
ensure that no short-circuit loop is created when you setup the system.
• When attaching an expansion unit to the GP, be sure to read the expan-
sion unit's Installation Guide.
Please pay special attention to the following instructions when connecting the
power cord terminals to the GP unit.
• If the power supply voltage exceeds the GP's specified range, connect a
voltage transformer.
• Between the line and the ground, be sure to use a low noise power
supply. If there is still an excessive amount of noise, connect a noise
reducing transformer.
• Input and Output signal lines must be separated from the power control
cables for operational circuits.
• To increase the noise resistance, be sure to twist the ends of the power
cord wires before connecting them to the GP unit.
• The GP's power supply cord should not be bundled with or kept close to
main circuit lines (high voltage, high current), or input/output signal lines.
• Connect a surge absorber to handle power surges.
• To reduce noise, make the power cord as short as possible.
7
Power Supply Cautions
*1 Use a grounding resistance of 100Ω, a wire of 2mm2 or
thicker, or your country's applicable standard.
*2 For GP-2600 Series, the backlight differs depending on a
Rev. For the correct backlight and how to distinguish Rev.,
refer to the User Manual carried in the Pro-face Web Site
(http://www.pro-face.com/).
GP Unit
Rev.
Backlight Model
GP2500-TC11
-
GP577RT-BL00-MS
Rev.4 is marked
CA3-BLU12-01
The others
PS600-BU00
GP2600-TC11
*2