4009-9812 Class A Adapter

Option Card Installation Instructions  2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA All specifications and other information shown were current as of publication, and are subject to change without notice. IDNet and TrueAlert are trademarks of Simplex Time Recorder Company. Suffix “C” or “CA” following an

An aftermarket SLC option card is available to convert the three SLCs found on

the TrueAlert Addressable Controller system board to three Class A (Style 6) hardwired SLCs. Each TrueAlert Addressable Controller supports one Class A Adapter Option Card. Figure 1 is an illustration of the Class A Adapter Option Card. CLASS A CLASS A 4009T TRIPLE-T CLASS A BD

The Class A return wiring for system board SLC 1 is terminated at TB1 on the

Class A card. The other two SLCs must be terminated to complete the Style 6 loops (SLC2 to TB2 and SLC3 to TB3), regardless of whether or not those circuits are used. Refer to the 842-158 Field Wiring Diagram for complete wiring, compatible appliances, current, and line distance

Install the 4009-9812 Class A Adapter Option Card piggy-backed onto the

Addressable Controller. Use the following steps and Figure 3 to mount the card. 1. Disconnect the battery and then AC power from the Addressable Controller. 2. Place one of the supplied insulating washers over the threaded end of each of the three metal standoffs. Screw t