Siemens 5TC1585 Operating Instructions Manual
Read Online
Read the Siemens 5TC1585 Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Detector de movimiento
Détecteur de mouvement
Betriebsanleitung
Operating Instructions
Manual de instrucciones
Manuel d'utilisation
2516534149_01
• Passive infrared motion detector for wall mounting in device housing.
• Rectangular detection area (max. 14 m x 17 m).
• Mixed light measurement suitable for fluorescent lamps (FL/PL/ESL), halogen/incandescent lamps and LEDs
• Integrated button
• Different models:
•
5TC1585 Motion detector for normal requirements
•
5TC1586 For Master /Slave Switching.
Proper Use
• The detector controls the lighting.
• It is designed for wall mounting in an interior switch range, e.g. in a corridor, staircase, cellar, toilet, etc.
• For use in normal ambient conditions.
Connection
Use the same external conductor for all detectors.
Secure device with an upstream type B or type C circuit breaker (EN 60898-1) with a maximum of
(10 A L/L).
Individual switching (3 – wire detector)
As master, the detector detects presence and brightness and controls lighting.
2516534149_01
5TC1585
Master/slave parallel switching (3-wire detector)
If the detection area covered by a single detector is insufficient (in large rooms), then several detectors can be
operated in parallel by connecting the P terminals. The master 5TC1585 measures brightness and controls the
lighting. The other detectors, slaves 5TC1586, merely provide presence information.
A maximum of 6 detectors can be connected over a length of 50 m.
Installation
For installation in device housing, concealed housing size 1.
Observe the recommended installation height of 0.8 m – 1.2 m!
Ensure that there are no obstructions as infrared rays cannot pass through solid objects.
The detector is not suitable for intruder alarm systems!
Detection Area
5TC1585
5TC1586
5
2516534149_01
With a standard flush-mounting box, size 1 (see illustration)
Disconnect power source.
Connect detector according to the wiring diagram (see section connection)
Screw down the detector in the flush-mounted box
Position the button and frame on the detector
Position the adapter frame ④
Note: The frames should be ordered separately in function of the series Miro or Style.
The button and adapter frame ④ should be ordered separately according to the following table:
Description and settings
MLFBs
Description
5TG6278-5TW00
Adapter frame and button, titan white
5TG6278-5WH00
Adapter frame and button,polar white
5TG6278-5AM00
Adapter frame and button,aluminium metallic
5TG6278-5CM00
Adapter frame and button,carbon metallic
5TG6278-5SW00
Adapter frame and button,matt white
5TG6278-5SB00
Adapter frame and button,matt black
5TG6278-5AC00
Adapter frame and button,anthracite
5TG6278-5PM00
Adapter frame and button, platinum metallic
5TG6278-5CH00
Adapter frame and button, chocolate
2516534149_01
④
④
Setting the brightness (LUX)
You can set different brightness values with the brightness potentiometer (factory setting 500 lx).
Set potentiometer to desired switch-on brightness (5 to 1000 lux/on).
On the on setting the detector always responds to movement, regardless of the brightness.
Turn the potentiometer to Teach-in
; after 20 s (red LED flashes) the detector saves the current surrounding brightness
as the new switch-on brightness.
Setting the time delay (TIME)
If the detector detects no further movement, it switches off after the set time delay. If you want to change the preset time
(factory setting 10 min)
Set the potentiometer to the desired time (10 s, 1 min, 5 min, 10 min, 30 min).
If you wish to use the pulse function (e.g. for a staircase light timer switch)
Set the potentiometer to
. As long as motion is detected, the contact closes every 10 s for 0.5 s.
Test detection area (walking test)
The walking test is used to test the detection area and to restrict it if necessary.
Set the time potentiometer (TIME) to test
▻ The detector always responds to movements (regardless of brightness and configuration type).
▻ After the detector has detected a movement, the contact switches on for 2 s.
Performing the walking test using the button (only for slave devices)
Press the button for 10 s
▻ If motion is detected the red LED on the slave lights up.
▻ Test mode is activated for 10 min.
Briefly press the button
▻ The test mode is ended and the detector returns to normal operation.
Recommended guide values
2516534149_01
Setting the MODE (fully or semi-automatic) with staircase light function
Staircase light function – corridor off/corridor on
With the corridor off staircase light function the light can be switched on and off manually using the button at any time. With
corridor on it can be switched on manually but not switched off. The light will not be switched off again until after the set
time delay.
Configuration type – auto/man
auto = fully automatic
The lighting is switched on and off automatically (based on presence, absence and brightness)
man = semi-automatic
The lighting is always switched on manually. It is switched off by the detector.
Manual operation using the button (internal or external)
The button can be used to manually switch the lighting at any time.
Switching on manually
When the button is pressed briefly, the light switches on for a certain time (depending on the duration of motion and the set
time delay).
Switching off manually
If the light is switched on, it can be switched off for a certain time by briefly pressing the button (depending on the duration
of the motion
and the set time delay). Afterwards, the detector returns to normal operation.
Normal
Operation
Normal
Operation
> 30 s + set follow-up
time
> 30 s + set follow-up
time
2516534149_01
Flashes a 1 second
intervals
The detector is in the start -up phase
Flashes rapidly
Error flashing, the detector has found an error
Flickers for 20 s
Teach-in via potentiometer is activated
Lights up or flickers
irregularly
The detector is in walking test mode.
Troubleshooting
Fault
Cause
Light does not switch
on or off if presence
is detected and in
darkness
Lux value is set too low; detector set to semi-
automatic; light was switched off manually via button;
person not within detection area; obstruction(s)
interrupting detection;
time delay set too short
Light stays on with
detection
of presence despite
sufficient brightness
Lux value is set too high; light was briefly switched on
manually via button detector is in test mode
Light does not switch
off, or light switches on
spontaneously when
no one is present
Thermal sources of interference in the detection area:
fan heaters, incandescent lamps/halogen spotlights,
moving objects (e.g. curtains hanging in open
windows); load (EBs, relays) not cleared
Button does not work
Device still in the start-up phase
Device does not respond Short circuit or several phases in parallel switching!
Disconnect detector from the power supply for 5 min
(thermal fuse)
Error flashing
(4 x per second)
Error in self-test;
device not functional!
2516534149_01
230 V AC, + 10%/– 15%
Frequency:
50/60 Hz
Standby output:
0.4 W +/– 15%
Switching load:
L/L: 10 A with cos ϕ = 1, (not with 5TC1586)
Minimum load:
10 mA, (not with 5TC1586)
Contact type A:
µ contact, (not with 5TC1586)
Switching capacity A:
Incandescent/halogen
2300W, (not with 5TC1586)
Compact/fluorescent
lamps:
1150 VA, (not with 5TC1586)
LED lamps
< 2 W: type. 40 W
> 2 W: type. 450 W, (not with 5TC1586)
Protection rating:
IP 20 in accordance with EN 60529
Operating temperature:
–15 °C … +45 °C
Brightness setting range: 5 - 1000 lx, (not with 5TC1586)
Lighting time delay:
10 s (pulse) -30 min, (not with 5TC1586)
Installation height
0.8 – 1.2 m
Detection angle:
170°
Detection area:
– across
14 x 17 m
– frontal
12 x10 m
Dimensions
10 mm
5TC1585
5TC1586
Rigid cable
2516534149_01
* Note: for P terminal max 1,5mm2, solid rigid conductor.
*