Trane Link UX360 Installation Manual
Read Online
Read the Trane Link UX360 Installation Manual online using the built-in PDF viewer.
Text of the manual
Trane® Link UX360
Smart Thermostat
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection
with the installation. Should further information be desired or should particular problems arise which are not covered
sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Model THUI2360A200U
With Link technology
TM
18-HD98D1-1B-EN
NOTE: Use 18-gauge color-coded thermostat
cable for proper wiring. Shielded cable is not
typically required.
Keep this wiring at least one foot away from
large inductive loads such as Electronic Air
Cleaners, motors, line starters, lighting ballasts
and large distribution panels.
Failure to follow these wiring practices may
introduce electrical interference (noise) which
can cause erratic system operation.
All unused thermostat wires should be grounded
at indoor unit chassis ground only. Shielded
cable may be required if the above wiring
guidelines cannot be met. Ground only one end
of the shield to the system chassis.
WARNING
!
This information is intended for use by
individuals possessing adequate backgrounds
of electrical and mechanical experience. Any
attempt to repair a central air conditioning
product may result in personal injury and/or
property damage. The manufacturer or seller
cannot be responsible for the interpretation of
this information, nor can it assume any liability
in connection with its use.
WARNING
!
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and
troubleshooting
of
this
product,
it
may
be necessary to work with live electrical
components. Failure to follow all electrical
safety precautions when exposed to live
electrical components could result in death or
serious injury.
1. Safety ...................................................................... 2
2. Product Specifications .......................................... 3
3. General Information ............................................... 3
3.1
What’s in the Box? ......................................... 3
3.2
Accessories ................................................... 3
4. Trane® Link Systems .............................................. 4
5. Placement & Installation ....................................... 5
5.1
Location ........................................................ 5
5.2
Network Connections .................................... 6
5.3
Mounting ....................................................... 6
5.4
Wiring ............................................................ 6
6. Field Wiring Connection Diagram Options ......... 7
7. CAN Low Voltage Troubleshooting ...................... 8
8. Configuration ......................................................... 9
8.1
General.......................................................... 9
8.2
Climate Control ............................................. 9
8.3
Energy ......................................................... 11
8.4
Environment ................................................ 11
8.5
Accessories ................................................. 12
9. Indoor Sensor Setup ............................................ 14
9.1
Available Sensors ........................................ 14
9.2
Sensor Details ............................................. 14
9.3
Assigning Sensors ...................................... 15
9.4
Unassigning Sensors .................................. 15
9.5
Adding Wireless Sensors ............................ 15
9.6
Removing Wireless Sensors ....................... 16
10. System Operation ................................................ 17
10.1 Power-Up Sequence ................................... 17
10.2 Service Reminders ...................................... 17
10.3 Software Updates ........................................ 17
10.4 System Mode .............................................. 17
10.5 Fan Mode .................................................... 17
10.6 Air Cleaner Mode ........................................ 17
11. Test Modes ........................................................... 18
12. Equipment Summary ........................................... 18
13. Alerts ..................................................................... 19
14. Troubleshooting ................................................... 19
UX360 Smart Thermostat
18-HD98D1-1B-EN
3
2. Product Specifications
Specification
Description
Model
THUI2360A200U
Product
UX360 Smart Thermostat
Size
7.125” x 4.725” x 1” (WxHxD)
Configurations
Heat Pump, Heat/Cool, Dual Fuel, Heat Only, Cooling Only
Maximum Number of Stages
5 Stages Heat, 2 Stages Cooling
Storage Temperature
-40°F to +167°F, RH non-condensing
Operating Temperature
32°F to 104°F, RH non-condensing
Input Power*
24VAC from HVAC System (Range: 18-30 VAC)
Power Consumption
2W (typical) / 5W (max)
Wire Usage
18 AWG NEC approved control wiring
Communications
Controller Area Network (CAN bus) 4-wire connection
System Modes
Auto, Heating, Cooling, Off, Emergency Heat
Fan Modes
Auto, On, Circulate
Cooling Setpoint Temperature Range
60°F to 99°F, 1°F resolution
Heating Setpoint Temperature Range
55°F to 90°F, 1°F resolution
Outdoor Temperature Display Range
Ambient Temperature: -40°F to 141°F (including dead band),
-38°F to 132°F (excluding dead band)
External Ambient Temperature: up to 136°F
Indoor Humidity Display Range
0% to 100%, 1% resolution
Minimum Cycle Off Time Delay
Compressor: 5 minutes, Indoor Heat: 1 minute
* On every application, 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized.
3. General Information
3.1 What’s in the Box?
•
Literature
-
Installer Guide
-
User Guide
-
Warranty Card
•
UX360 Smart Thermostat
•
Wall Plate
•
Mounting Kit
3.2 Accessories
•
Wired Indoor Sensor (ZZSENSAL0400AA)
•
Wireless Indoor Sensor (ZSENS930AW00MA*)
* Wireless Indoor Sensor software version 1.70 or greater
is required.
4. Trane® Link Systems
•
Installation. Trane Link systems are built to
be “plug and play”. Once you’ve connected
the outdoor unit, indoor unit, SC360, and
UX360, turn on the system. The equipment
will communicate and configure the system
automatically to default settings.
•
Verification. You can easily verify all modes
of operation. Link can run and verify each
mode of operation as well as verify the
system is functioning properly. For example,
instruct the system to deliver 1200 CFM of
airflow, and the system will verify correct
operation. Once testing has been completed,
you can get a commissioning report that
documents the results.
•
Monitoring. With a homeowner’s
permission, you can monitor data from the
system remotely. This includes creating a
birth certificate that captures how the system
was operating on day one, and tracking
performance over time.
•
Upgrades. Connected systems can have
their software remotely upgraded through
the SC360, including pushing additional
features out to the installed communicating
equipment. No dealer visit or SD cards are
required.
Technical Advantages
•
Self-configuring system on startup
•
Automated verification simplifies charging
and airflow procedures, and automatically
goes through all modes of operation to verify
the system is operating properly and within
specifications
•
New sensors to easily monitor data, with
information shared wirelessly, either onsite
or in the cloud
•
Standardized and consistent wiring: four-wire
connection for all communicating equipment
simplifies installation
•
Faster, more robust communication protocol
•
Remotely control connected systems from
the Trane Home mobile app.
•
The system supports up to four indoor
temperature and humidity sensors in a
non-zoned system for averaging, including
ZSENS930AW00MA sensors.
•
With an Internet connection, full system
updates for installed communicating
equipment will occur automatically.
Download the Trane Diagnostics mobile app from the Google Play™ Store or App Store®.
All trademarks referenced are the trademarks of their respective owners. Google is a trademark of Google LLC.
TM
UX360 Smart Thermostat
18-HD98D1-1B-EN
5
5.1 Location
•
Install the UX360 in a centrally located
climate controlled living space with good air
circulation.
•
The UX360 MUST be at least 3 feet apart
from any other electronic device such as a
TV or speaker.
•
You MUST assign an indoor temperature
sensor that is installed in a controlled space.
See the Sensor Setup section for details.
•
If the UX360 and the SC360 must be in
close proximity (closer than 3 feet), always
install the UX360 diagonally above the
SC360. If top left and top right sides are not
possible, then install the SC360 to the right
or left side of the UX360.
•
Keep these 2 devices as far apart as
possible. Never install them on top of each
other.
•
The UX360 should be at least 3 feet away
from a corner where 2 walls meet. Corners
have poor circulation.
•
The UX360 should not be directly exposed to
air currents from supply air or ceiling fans.
•
Avoid exposing the UX360 to any radiant
heat source such as sun light or fireplaces.
5. Placement & Installation
Incorrect
Placement
3 Feet Min.
UX360
SC360
Preferred placement
(diagonally and above, in
same controlled space)
Acceptable placement
when space is limited
(SC360 to right or left, in
same controlled space)
Unacceptable placement
when space is limited
(Never install above/below,
same controlled space)
3 Feet Min.
3 Feet Min.
3 Feet Min.
3 Feet Min.
Incorrect
Placement
Problematic Air Patterns
Natural heat
dissipation
from the
Touch Screen
Onboard
Thermistor
5 FEET
Optimum
Zone
2 FEET
Correct
Placement
Locate the control in an
area with minimal air flow
patterns thereby avoiding
interuption of natural heat
dissipation
Figure 1. Placement of UX360 and SC360
5.2 Network Connections
To take advantage of the full range of features
on the UX360, the SC360 System Controller
should be connected to the Internet using a
wireless connection.
Refer to the UX360 User Guide for additional
information on connecting to the Internet.
5.3 Mounting
Follow these steps to mount the UX360 to the
wall. See Figures 2 and 3.
1. Turn OFF all power to heating and cooling
equipment.
2. Route the wires through the opening on the
Sub-base.
3. Place the Sub-base against the wall in the
desired location and mark the wall through
the center of each mounting hole.
4. Drill the holes in the wall where marked.
5. Mount the Sub-base to the wall using
included mounting screws and drywall
anchors. Make sure all wires extend through
the Sub-base.
Wires
Mounting Hole
Mounting Hole
Figure 2. Mark The Mounting Holes
Wall
Wiring
Figure 3. Mount The Sub-Base To The Wall
5.4 Wiring
1. Adjust the length and position of each wire to
reach the proper terminal on the connector
block of the Sub-base. Strip 1/4” of insulation
from each wire. Do not allow adjacent
wires to short together when connected. If
stranded thermostat cable is used, one or
more strands will have to be cut to allow
the cable to fit connector. For use with solid
conductor 18 ga. thermostat wire.
2. Match and connect control wires to the
proper terminals on the connector block.
Refer to the Field Wiring Connection
Diagrams shown later in this document.
3. Push excess wire back into the wall and seal
the hole to prevent air leaks.
NOTE: Air Leaks in the wall behind the
UX360 can cause improper operation.
4. Attach the UX360 to the Sub-base.
5. Turn ON power to the heating and cooling
equipment.
UX360 Smart Thermostat
18-HD98D1-1B-EN
7
6. Field Wiring Connection Diagram Options
R
DH
DL
B
SYSTEM
CONTROLLER
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
THERMOSTAT
(UX360)
DISTRIBUTION
BOARD
(4x or 8x)
(SC360)
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
COMMUNICATING
INDOOR UNIT
COMMUNICATING
OUTDOOR UNIT
R
DH
DL
B
RED
WHITE
GREEN
BLUE
WIRE COLORS
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
THERMOSTAT
(UX360)
DISTRIBUTION
BOARD
(4x or 8x)
R
DH
DL
B
R
DH
DL
B
R
DH
DL
B
COMMUNICATING
INDOOR UNIT
COMMUNICATING
OUTDOOR UNIT
COMMUNICATING INDOOR AND OUTDOOR
SYSTEM
CONTROLLER
(SC360)
7. CAN Low Voltage Troubleshooting
•
24 VAC is required to power up the SC360 and UX360
•
24 VAC is required at the outdoor unit for Smart Charge
automatic charging
•
24 VAC is required at the outdoor unit if Load Shed is desired
Troubleshooting steps
Description
Bus Idle
Expected Measurement
2 - 4 VDC between DH and GND
2 - 4 VDC between DL and GND
Voltage measured from DH to DL will vary depending on bus
traffic
Resistance Between DH and DL1
Appropriate range can vary depending on the communicating equipment installed on the system
Expected Measurement
60 +/- 10 ohms can be expected when the SC360,
communicating indoor unit and communicating variable speed
outdoor unit are installed.
90 +/- 10 ohms can be expected with no communicating outdoor
unit installed
Lower than appropriate range
Possible short on the bus between DH and DL
Higher than appropriate range
Possible open circuit on the bus
Resistance Between DH and GND2
Expected Measurement
1 Mohms or greater
1 All power to the system must be turned OFF.
2 Device must be powered OFF and disconnected from the CAN bus.
UX360 Smart Thermostat
18-HD98D1-1B-EN
9
8. Configuration
Certain menu selections may or may not be present depending on other menu settings and equipment
installed.
8.1 General
8.2 Climate Control
Menu
Selection
Options
Description
System
Name
Manual
keypad entry
Enter a custom name for the system.
Dealer Code
Manual
keypad entry
When the system is connected to Trane Home, a Dealer Code can be
entered to populate the dealer’s contact information and logo. The code
is the dealer’s registered phone number listed on ComfortSite. A dealer
can upload a logo by selecting Tech Support from the Home page of
ComfortSite, then select Dealer Logo Management and upload logo. File
size should not exceed 3MB.
Factory
System
Restore
Full Restore
Erases all user and installer settings and restores the system to factory
default settings.
Partial
Restore
HVAC configuration will be set to factory default values. Zoning
configuration, indoor sensor settings, and user settings will be retained.
After the partial restore, HVAC configuration may need to be reconfigured.
Sub Menu
Menu Selection
Options [Default]
Description
General
System
Operation
Cooling Sensible Load
Value (Btu/h)
[0] Btu/h
Range of values is based on system
configuration.
Heating Sensible Load
Value (Btu/h)
[0] Btu/h
Range of values is based on system
configuration.
Aggressive Recovery
by Temp Error
Enabled/[Disabled]
Select whether to disable the
15-minute staging inhibit during
heating mode when Temp Error is
greater than 2°F.
Cannot be enabled when Heating
Aggressive Recovery by ODT is
enabled.
Heating Aggressive
Recovery by ODT
Enabled/[Disabled]
Select whether to require/[bypass]
outdoor temperature to fall below
the selected Heating Aggressive
Recovery Setting in order to disable
the 15-minute staging inhibit during
heating mode when Temp Error is
greater than 2°F.
Cannot be enabled when Heating
Aggressive Recovery by Temp Error
is enabled.
Outdoor temperature sensor must be
connected and enabled to allow this
setting to be selected.
Recovery Setting (°F)
0°F -70°F [40°F]
Select the outdoor temperature for
Heating Aggressive Recovery.
Smart Control Fan
Enable Status
Enabled/[Disabled]
Select to enable or disable Smart
Continuous Fan.
System
Controller
SC360 Installed in
Conditioned Space
Yes/[No]
Enable if the SC360 was installed in a
conditioned space and can be used as an
indoor temperature and humidity sensor.
Indoor Heat
Heater Type
[None]/Electric/
Hydronic
Select the type of indoor unit
installed. Value is pre-populated for
communicating equipment.
Heater Size
Electric: [Empty List]/
25KW, 1-Phase/
20KW, 1-Phase/
15KW, 3-Phase/
15KW, 1-Phase/
10KW, 3-Phase/
10KW, 1-Phase/
8KW, 1-Phase/ 4KW,
1-Phase/
5KW, 1-Phase
Hydronic:
100Kbtu/80Kbtu/
70Kbtu/50Kbtu
Select the size of the indoor unit based
on tonnage and heater type. Options
vary depending on heater type.
Value is pre-populated for
communicating equipment.
Heater Model Number
[NOMODELNUM]
Value is pre-populated based on heater
size, but can also be manually configured.
Heater Serial Number
[NOSERNUM]
Enter the 10-digit serial number of the
indoor unit.
Cycles Per Hour
2-6 CPH [5]
Electric Heat Airflow
[Low]/Med/High
Blower On Delay
No delay/15/30/45/[60]
seconds
Select to enable or disable the blower
on delay in hydronic heating.
Blower Off Delay
No delay/30/[50]/70/90
seconds
Select to enable or disable the blower
off delay in hydronic heating.
Compressor
Operation
Minimum System
Speed
[Factory]/
30%/40%/50%
Compressor
Cooling
Cycles Per Hour
2-6 CPH [3]
Blower Off Delay
[No Delay]/Auto/
30 seconds
Select to enable or disable the blower
off delay in compressor cooling.
Blower On Delay
[No Delay]/Auto/
30 seconds
Select to enable or disable the blower
on delay in compressor cooling.
Minimum Indoor Coil
Temp (°F)
28°F -60°F [30°F]
Maximum Indoor Coil
Temp (°F)
28°F -60°F [55°F]
UX360 Smart Thermostat
18-HD98D1-1B-EN
11
Sub Menu
Menu Selection
Options [Default]
Description
Compressor
Cooling
System Control
More Efficient/Efficient/
Balanced/ Comfort/
[More Comfort]
Minimum CFM Per Ton
200-500 [250]
Maximum CFM Per Ton
200-500 [500]
Minimum value based on Minimum
CFM Per Ton setting. Maximum value
based on Comp Cooling Maximum
Airflow setting.
Cooling Maximum
Airflow (CFM)
[0]
Range varies per system settings.
Compressor
Heating
Cycles Per Hour
2-6 CPH [3]
Blower Off Delay
[No delay]/30/60/90
seconds
Blower On Delay
[No delay]/15/30
seconds
Heating Maximum RPM
[High]/Med/Low
System Control
[Comfort]/Efficiency
Comp Heat CFM Per Ton
290-450 [400]
8.3 Energy
8.4 Environment
Sub Menu
Menu Selection
Options [Default]
Description
Indoor Heat
Auxiliary Heat Lockout
Enabled/[Disabled]
Enable auxiliary heat lockout
(10° minimum separation when
enabling auxiliary heat lockout and
compressor heat lockout).
Auxiliary Heat Lockout
Temp (°F)
32°F -70°F [45°F]
Select an outdoor temperature to
prevent auxiliary heat above the
selected outdoor temperature.
Compressor
Heating
Compressor Heat
Lockout
Enabled/[Disabled]
Enable compressor heat lockout (10°
minimum separation when enabling
auxiliary heat lockout and compressor
heat lockout)
Lockout Temperature
(°F)
5°F -70°F [30°F]
Select an outdoor temperature to
prevent compressor heating below the
selected outdoor temperature.
Outdoor Unit
Power Factor
Correction
Enabled/[Disabled]
Sub Menu
Menu Selection
Options [Default]
Description
Outdoor Unit
Reduce Electrical
Interference
Enabled/[Disabled]
Defrost Termination
Temp (°F)
[Factory]/Medium/High
& 2 Input
Accessory Type
[None], Air Cleaner,
Powered/Bypass,
Steam, Ext Dehum,
Ventilator
Select the accessory type.
Humidifier Action
[With Active Heat Call],
Without Active Heat
Call
Disabled for Air Cleaner accessory.
Airflow During
Humidifier Only Mode
35%-100% [50%]
Select the desired airflow when the
humidifier is operating without an
active call for heat.
Dehum Type
[With Cool]/Stand alone
Defaulted to [With Cool] for Ext Dehum
accessory.
Dehum Fan Action
[Force Fan]/Normal
Minimum Ventilation
Run Time (mins)
1-60 [5]
Ventilator Fan Action
[Ventilate With Blower]/
Ventilate Without
Blower
Outdoor Temperature
Ventilation Override
[Disabled]/Enabled
Max Outdoor
Temperature
80°F - 110°F [85°F]
Min Outdoor
Temperature
-10°F to 50°F [0°F]
Accumulate
Overridden Run Time
[Disabled]/Enabled
Accumulate Period
[4 hrs - Recover
based on OD
Conditions]/4 hrs -
Recover to maintain
Min Ventilation/24 hrs
- Recover based on
OD Conditions/24 hrs
- Recover to maintain
Min Ventilation
Humidifier Control
[RH Control]/Frost
Control
Not available for Ext Dehum accessory.
Available accessory menu selections will vary based on the accessory type.
UX360 Smart Thermostat
18-HD98D1-1B-EN
13
Sub Menu
Menu Selection
Options [Default]
Description
ID External
Switch Input
1 & 2
Accessory Type
[None], Condensate-
Cooling, Smoke
Detector
Select the accessory type.
Disable Compressor
Cooling
[Disabled]/Enabled
Enabled by default for Condensate-
Cooling and Smoke Detector
accessories.
Disable Compressor
Heating
[Disabled]/Enabled
Enabled by default for Smoke Detector
accessory.
Disable Indoor
Heating
[Disabled]/Enabled
Enabled by default for Smoke Detector
accessory.
Disable Fan
Circulation
[Disabled]/Enabled
Enabled by default for Smoke Detector
accessory.
Limit Compressor
Speed
[Disabled]/Enabled
Outdoor Load
Shed
Accessory Type
[None], Load Shed,
Generator Backup
Disable Compressor
Cooling
[Disabled]/Enabled
Enabled by default for the Load Shed
accessory.
Disable Compressor
Heating
[Disabled]/Enabled
Enabled by default for the Load Shed
accessory.
Disable Indoor
Heating
[Disabled]/Enabled
Enabled by default for the Load Shed
and Generator Backup accessories.
Disable Fan
Circulation
Disabled/[Enabled]
Limit Compressor
Speed
[Disabled]/Enabled
9. Indoor Sensor Setup
9.1 Available Sensors
A list of all available sensors for the system will be
displayed at the top of the Indoor Sensor Setup
screen. Once a sensor has been assigned, it will
be removed from the list of available sensors. The
sensors from the communicating equipment will
show up in the list automatically, but the wireless
sensors must be added one by one.
Supported Indoor Sensors:
•
UX360 Thermostat (Onboard Sensor)
•
SC360 System Controller (Onboard Sensor)
•
Wireless Indoor Sensor (ZSENS930AW00MA)
•
Wired Indoor Sensor (ZZSENSAL0400AA)
NOTE: The SC360 will only be included as
an available sensor if it has been configured
and installed in controlled space. This setting
can be modified from Technician Access >
Configuration > Climate Control > SC360
System Controller.
9.2 Sensor Details
Select a specific sensor to view more details
about the sensor and to assign it to the system.
The details displayed may be different for
different sensor types.
Sensor Details May Include:
•
Assigned Status: if the sensor has been
assigned to the system or not
•
Use Temperature: enables/disables the use
of the temperature sensor on the device
•
Use Humidity: enables/disables the use of
the humidity sensor on the device
•
Battery: battery % on battery powered
sensors
•
Status: communicating status with the
system
•
Serial Number: serial number of the sensor
•
Model Number: model number of the
sensor
•
Sensor Name: sensor name can be
changed to a default or custom name
•
Temperature Weight: weight of the
temperature sensor when being averaged
with other sensors
View, edit and assign temperature and humidity sensors for the system.
UX360 Smart Thermostat
18-HD98D1-1B-EN
15
Select Custom to
manually enter a sensor
name
Assign or Unassign
the sensor
Enable/Disable
temperature
Enable/Disable
humidity sensing
Select a custom or predefined sensor name
9.3 Assigning Sensors
To assign a sensor to the system:
1. Select the corresponding sensor under
Available Sensors.
2. On the Sensor Details screen, select
Assigned Status.
3. Select Assign and then Done.
4. The sensor will be assigned to the system and
removed from the Available Sensors list.
5. Up to four sensors can be assigned to the
system at a time.
9.4 Unassigning Sensors
To unassign a sensor:
1. Select the corresponding sensor under
Available Sensors.
2. On the Sensor Details screen, select
Assigned Status.
3. Select Unassign and then Done.
4. The sensor will be unassigned from the
system and will be added back to the
Available Sensors list.
9.5 Adding Wireless Sensors
ZSENS930 wireless sensors must be added
to the system one at a time.
Follow these steps to add new wireless sensor:
1. Select Add Wireless Sensor under the list
of available sensors.
2. Press and release the INSTALL button on
the back of the wireless sensor.
3. The LED on the back of the sensor will begin
flashing.
4. Once successfully added, select a pre-
defined name or enter a custom name and
then select BACK.
5. Select Assign to assign the sensor to the system.
9.6 Removing Wireless Sensors
ZSENS930 wireless sensors must be removed
from the system one at a time. The sensors
must be online to be removed by the steps listed
below.
Follow these steps to remove a wireless sensor:
1. From the list of Assigned Sensors, select
the wireless sensor to be removed.
2. Scroll to the bottom of the Sensor Details
screen and select Remove Wireless
Sensor.
3. Press and release the INSTALL button on
the back of the wireless sensor.
4. The LED on the back of the sensor will begin
flashing.
5. When successfully removed, the sensor will
no longer be in the Assigned Sensors list
or the Available Sensors list.
NOTE: After being removed, the wireless
sensor would have to be added back to the
system before it can be assigned as a sensor.
UX360 Smart Thermostat
18-HD98D1-1B-EN
17
10.1 Power-Up Sequence
When the UX360 is connected to the sub-
base, the thermostat initiates an 80 to 200
second power-up sequence. During the power-
up sequence, the screen will remain dark for
approximately 20 seconds and will then display
‘Initializing...’ above a progress bar for up to
three minutes.
10.2 Service Reminders
Reminders can be enabled to send a notification
when the configured reminder expires. A
message will be displayed across the top of the
display. The reminder is time-based and can be
configured on system run time or calendar days.
Reminders can be configured for humidifiers,
filters, ventilation systems, UV lights and HVAC
system maintenance. The type of reminders
available are based on the accessories enabled
in the installer settings.
10.3 Software Updates
To take full advantage of the features and
benefits of the UX360 Smart Thermostat, the
latest software revision should be installed.
An Internet connection to the SC360 System
Controller is required for software updates.
When the SC360 is connected to the Internet,
software updates to the installed communicating
equipment will occur automatically and do not
require user intervention.
10.4 System Mode
The system has five System Modes which can
be selected:
•
Heating: system only operates in heating
mode
•
Cooling: system only operates in the cooling
mode
•
Off: system will not operate in heating or
cooling mode
•
Emergency Heating: system will run the
indoor heat source only (only available when
the outdoor unit type is a heat pump)
•
Auto: Mode of operation is automatically
selected based on the following rules:
a. Heating - Indoor temperature is equal or
less than heating setpoint
b. Cooling – Indoor temperature is equal to
or greater than cooling setpoint or within
1°F of cooling setpoint
There is a minimum deadband between heating
and cooling setpoints of 3°F (4°F when zoning is
applied).
10.5 Fan Mode
The system has three fan mode options:
•
Auto: fan only runs with a call for heating or
cooling
•
On: fan runs continuously
•
Circ: fan runs a user-selected minimum
amount of time each hour
10.6 Air Cleaner Mode
When an air cleaner is installed, the system has
three Air Cleaner modes:
•
Auto: air cleaner operates only with a call for
fan operation
•
Quick: air cleaner operates for 3-hours with
blower at 100%
•
Allergy: air cleaner operates for 24-hours
with blower at 100%
10. System Operation
11. Test Modes
12. Equipment Summary
Certain tests may or may not be present depending on other menu settings and equipment installed.
Select the Start button to run each test.
The Equipment summary table is based on the installed communicating equipment and differs from
system to system.
The following information per device is displayed:
•
Status: identifies if the device is currently communicating on the system
•
Description: name of the device
•
Model: model number of the device
•
Serial: serial number of the device
Menu Selection
Options
Description
Test Blower
300-1580 CFM
Energize indoor blower at the selected CFM.
Range of values varies per Air Handler model.
Test
Compressor
Cool
Minimum-100%
Adjust % demand for compressor operation. Indoor blower will
operate at the speed required for the selected % demand. Range of
values is based on system configuration and ambient conditions.
Test
Compressor
Heat
Minimum-100%
Adjust % demand for compressor operation. Indoor blower will
operate at the speed required for the selected % demand. Range of
values is based on system configuration and ambient conditions.
Test Indoor
Heat
Stage 1/
Stage 2/
Stage 3
Energize the selected stage of indoor heating. Indoor blower will
operate at the speed required for the selected stage.
Indoor heat test will run at maximum airflow for hydronic heat.
Charge Mode –
Cooling
N/A
Energizes system to set/verify system charge. Use sub-cooling tables
in the outdoor Service Facts to determine correct charge levels.
Check Charge
Mode – Heating
N/A
Energizes system to compare actual performance to typical
performance. Use the pressure curves in the outdoor unit Service
Facts for comparison.
Pump Down
mode – Cooling
N/A
Pulses the latching switchover valve to cooling position and runs at
full compressor speed. Outdoor EEV will remain open and indoor
EEV (if installed) will continue to control superheat.
Pump Down
Mode - Heating
N/A
Pulses the latching switchover valve to heating position and runs
at full compressor speed. Outdoor EEV will control superheat and
indoor EEV (if installed) will remain open.
Test Aux Relay
N/A
Enabled when Aux1/Aux2 accessories are configured for the system.
Installed accessories will be displayed.
UX360 Smart Thermostat
18-HD98D1-1B-EN
19
13. Alerts
14. Troubleshooting
The UX360 displays two sets of alerts:
•
Current Alerts: alerts which are currently
active
•
Alert History: alerts that have been cleared
in the last 30 days
Each alert in the history will display the date the
alert was cleared. Current alerts will display the
date when the alert was triggered.
Select an alert code to view additional
information on that alert as well as a list of
possible causes.
All alerts are categorized by severity:
Critical
•
Loss of heating/cooling operation
•
Service call is required
•
Alert notifications are displayed on the home
screen
Major
•
Reduced functionality - minimum operation is
possible
•
Service call is not immediately required
•
Alert notifications are not displayed on the
home screen
Normal
•
Functionality may be lost but should recover
or the information is for diagnostic purposes/
performance monitoring
•
Service call is not required
•
Alert notifications are not displayed on the
home screen
Symptom
Possible Causes
Action
UX360 displays an
alert on the screen
A critical or major alert is present.
Navigate to the Alerts screen for a problem
description and possible cause.
Menu > System Info > Alerts
Display will not
come on
Loss of 24VAC between R & B at
the UX360 Control.
1. Check wiring between R & B.
2. Check transformer for 24VAC output.
3. Check for broken or shorted thermostat
wire.
Indoor temperature
display is incorrect
1. Indoor temperature display
needs calibration.
2. Surrounding air flow affecting
sensed temperature of the
UX360.
Calibrate temperature sensor from UX360
menu.
Indoor humidity
display is incorrect
Indoor humidity display needs
calibration.
Calibrate humidity sensor from the UX360
menu.
Heating will not
come on
1. System mode is not set to Heat/
Auto or setpoint is set too low.
2. Minimum off time delay is being
enforced.
3. Heating system may require
service.
1. Set mode to heat and raise the setpoint
above the room temperature.
2. Wait 5 minutes and recheck heating
equipment.
3. Check/repair system.
Cooling will not
come on
1. System mode is not set to Cool/
Auto or the setpoint is too high.
2. Minimum off time delay is being
enforced.
3. Cooling system may require
service.
1. Set mode to cool and lower the setpoint
below the room temperature.
2. Wait 5 minutes and recheck cooling
equipment.
3. Check/repair system.
Heating or Cooling
is displayed, but no
warm or cool air is
coming from the
registers
1. Fan delay as the heating or
cooling equipment turns on.
2. Equipment is not working
properly.
1. Wait a minute for blower delays and
recheck registers.
2. Check/repair system.
Fan runs all the time
1. Fan mode is set to On,
Circulate or Clean mode.
2. There is a failure in the indoor
unit.
1. Check UX360 settings to see if fan is
set to On, Circulate or Clean mode.
2. Check indoor unit for failures (such as
tripped heating limit).
“+” symbol appears
on Home Screen
beneath Indoor
Temperature readout
Both compressor heat and
indoor heat are being called
simultaneously
No action required. Symbol is for
informational purposes only.
Fan is set to ON but
not running
1. Smart Control Fan feature has
been is engaged.
2. Blower motor is not functioning.
1. If indoor humidity is higher than desired
setpoint, the blower will cycle off with
the equipment. A humidity icon will
be displayed on the Fan Mode button
when the blower operation is being
inhibited due too high humidity.
2. Check/repair system.
Cooling or Heating
cycles too fast or too
slow (narrow or wide
temperature swings)
1. Check the location of the
UX360 for drafts.
2. Cycles per hour or aggressive
recovery is improperly set.
1. Seal air leaks behind UX360. Relocate
UX360 or apply remote indoor
temperature sensor.
2. Adjust cycle rates and aggressive
recovery features in the advanced
installer set up.
Heat pump is not
turning on; only
furnace or electric
heat strips are
running
1. Outdoor temperature is
below compressor lockout
temperature setting.
2. Compressor heating lockout
is enabled and outdoor temp
sensor is out of calibration or
failed.
3. The outdoor unit is not
reporting.
1. Adjust the compressor lockout
temperature setting if desired.
2. Check/repair outdoor sensor or wiring.
3. Check communication status of outdoor
unit.
Cannot change
system mode to
desired setting
Equipment is not configured
properly.
Check the Configuration screen to ensure
equipment is properly configured.
Screen does not
respond properly to
a button press
1. Internal UX360 hardware
failure.
2. Screen Lock has been enabled.
1. Remove UX360 from sub-base and
reset.
2. Press and hold the Menu button for 5
seconds to override screen lock.
UX360 Smart Thermostat
18-HD98D1-1B-EN
21
Symptom
Possible Causes
Action
Screen goes blank
after a period time of
inactivity
Screen Saver mode set to “Black”
which turns off screen back light
after a user-selected period of
inactivity.
Normal operation. User may change
screen saver from “Black” to “Indoor
Temperature” or increase the time before
the screen saver is activated.
Time set on UX360
changes every 24
hours.
UX360 is connected to Trane Home
and the time zone set from the
Trane Home account is incorrect.
Correct the time zone from the Trane Home
account.
Representative-only illustrations included in this document.
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor
environments for commercial and residential applications. For more information, please visit trane.com or
tranetechnologies.com.
Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed
to using environmentally conscious print practices.
6200 Troup Highway
Tyler, TX 75707
© 2022 Trane
18-HD98D1-1B-EN 24 Feb 2022
Supersedes 18-HD98D1-1A-EN (August 2021)