Appendix A Specifications

6F8C1358 62 A.1 General specifications Table A-1 General specifications Specification Item EN811 Operating temperature range (product ambient temperature) 0 to 55°C Operating humidity range 10 to 95%RH (no condensation) Storage temperature range -40 to 70°C Storage humidity range 5 to 95%RH (no condensation) Power voltage range 4.75 to 5.25VDC (Rating: 5.0VDC) Current consumption (when rated power is fed) 2A or less (5.0VDC) Power consumption (when rated power is fed) 10W or less Dust 0.3mg/m3 or less (no conductive dust) Vibration resistance 5≤f<9: half ampl ...

Unified Controller nv series Ethernet (EN811) Module Operation Manual

81 Variable definition (TCP reception) VAR OPEN_COMPLETE: BOOL; OPEN_ERROR: BOOL; OPEN_REQ: BOOL; RX_COMPLETE: BOOL; RX_ERROR: BOOL; RX_REQ: BOOL; CLOSE_COMPLETE: BOOL; CLOSE_ERROR: BOOL; CLOSE_REQ: BOOL; RCV_STATUS: INT; CLOSE_STATUS1: INT; TR_DATA: ARRAY[0..512] OF WORD; T_O: typeTCP_OPEN; T_R: typeTCP_RCV; T_C: typeTCP_CLOSE; URCV_N_1: URCV_N; USEND_N_1: USEND_N; USEND_N_3: USEND_N; OPEN_STATUS1: INT; TR_DUMMY: WORD; T_SK_CMD: typeTCP_SEND; T_SOCKET: URCV_N; T_SK_REQ: BOOL; T_SK_COMP: BOOL; T_SK_ERR: BOOL; T_SK: INT; T_ ...

Chapter 1 Introducing the EN811 module

6F8C1358 4 1.2 Names and functions of the parts 1.2.1 Names of the parts Figure 1-2 shows the names of the parts of the EN811 module. Figure 1-2 Names of the parts of the EN811 module State display LED • RUN • ERR • L-A • HLTH Station address setting switch • STNH • STNL Operation mode setting switch • MODE Serial communication port • TOOL Ethernet modular connector Status display LED • LNK-A • ACT-A Transmission speed display LED • 1G-A • 100M-A ...

3.2 Network parameter setting

Unified Controller nv series Ethernet (EN811) Module Operation Manual 19 3.2.2 Station address Use the station address setting switches to set the station address. Any station address can be set; however, it must be unique within the system. The available setting range for station addresses is from 01(h) to FE(h)(1 to 254). When the IP address type is [Tool setting], it has precedence over the value of the station address setting switches. In this case, it is recommended matching the lowermost value of the specified IP address (5 in the case of 172.16.64.5) and ...

Appendix E Sample programs

6F8C1358 76 • Variation definition (UDP reception) VAR OPEN_COMPLETE: BOOL; OPEN_ERROR: BOOL; OPEN_REQ: BOOL; RX_COMPLETE: BOOL; RX_ERROR: BOOL; RX_REQ: BOOL; CLOSE_COMPLETE: BOOL; CLOSE_ERROR: BOOL; CLOSE_REQ: BOOL; RCV_STATUS: INT; CLOSE_STATUS1: INT; UR_DUMMY1: WORD; UR_DUMMY2: UINT; UR_SIZE: UNIT; UR_DATA: ARRAY[0..512] OF WORD; URCV_N_1: URCV_N; USEND_N_1: USEND_N; OPEN_STATUS1: INT; U_O: typeUDP_OPEN; U_R: typeUDP_RCV_BC; U_C: typeUDP_CLOSE; T_SK_CMD: typeTCP_SEND; T_SOCKET: URCV_N; T_SK_REQ: BOOL; T_SK_COMP: BOOL; T_SK_ERR: BOOL; T_SK: INT; T_SK_SOCKET: INT ...

Appendix A Specifications

6F8C1358 62 A.1 General specifications Table A-1 General specifications Specification Item EN811 Operating temperature range (product ambient temperature) 0 to 55°C Operating humidity range 10 to 95%RH (no condensation) Storage temperature range -40 to 70°C Storage humidity range 5 to 95%RH (no condensation) Power voltage range 4.75 to 5.25VDC (Rating: 5.0VDC) Current consumption (when rated power is fed) 2A or less (5.0VDC) Power consumption (when rated power is fed) 10W or less Dust 0.3mg/m3 or less (no conductive dust) Vibration resistance 5≤f<9: half ampl ...

Chapter 7 Application interface

6F8C1358 50 The EN811 module expands the state information by socket used by the user application as well as diagnosis information of the transmission path to the EN811 modules within the same network on the station bus. Information by socket includes information by single Ethernet socket. The configuration of application information on the station bus is as shown below. Access from the controller Reserved by the system EN state information (%MW13. CntBase + 130656) Reserved by the system Transmission path diagnosis result EN_NODEMAPA_* (%MW13. CntBase + 13091 ...

Appendix F Return code list

6F8C1358 86 The return codes related to EN811 are shown below. The return codes are outputted via the communication FB. For detailed explanation of the communication FB, refer to "Toshiba Integrated Controller V series/Unified Controller nv series Instruction Word Manual (LD/FBD/SFC/ST)(6F8C1226)." The following table shows the error codes that occur in the USND_N/URCV_N command request. Table F-1 USND_N/URCV_N command error code list Return value Description -5000 Communication command request count exceeded -5001 Command type error -5002 Reception timeout -5003 ...

Toshiba NV Series user guide recommended for: Satellite M35 Series, e-STUDIO 550, TCB-CC163TLE, Q7 Flow, 3000.

⚠️ Download Safety

The Controller Instruction manual (104 pages) is completely safe to download (last scan date: 08/05/2026).

Related PDF Instructions for Toshiba NV Series:

Controller Equipment: Frequently Requested

Have some Questions about Toshiba NV Series Device?

Get valuable and actionable advices from other Toshiba NV Series device users. Describe your problem or question, regarding the using of NV Series, in as much detail as possible, and other users will be able to answer you.