Rotex R2CND035A4AA Installation Manual

Specifications

Brand: Rotex
Category: Boiler
Model: R2CND035A4AA (Installation Manual)
File Type: PDF
File Size: —
Pages: 28

Read Online

Read the Rotex R2CND035A4AA Installation Manual online using the built-in PDF viewer.

Text of the manual

Wall-mounted condensing boiler

English Installation manual Wall-mounted condensing boiler R2CND028A4AA R2CND035A4AA R2TND028A4AA R2TND035A4AA

R2TND012, R2TND018, R2CND024, R2TND024,

R2CND028, R2TND028, R2CND035, R2TND035, EN15502-1, EN60335-2-102, Low Voltage 2014/35/EU Boiler Efficiency 92/42/EEC Gas Appliances 2009/142/EC Electromagnetic Compatibility 2014/30/EU ** * CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI 01 02 03 04 05 06 07 08 declares under its sole responsibility that the equipment to which this declaration relates: erklärt auf seine alleinige Verantwortung daß die Ausrüstung für die diese Erklärung bestimmt ist: déclare sous sa seule responsabilité que l'équipement visé par la présente déclaration: verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft: declara bajo su única responsabilidad que el equipo al que hace referencia la declaración: dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione: δηλώνει με αποκλειστική της ευθύνη ότι ο εξοπλισμός στον οποίο αναφέρεται η παρούσα δήλωση: declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere: 09 10 11 12 13 14 15 16 заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление: erklærer under eneansvarlig, at udstyret, som er omfattet af denne erklæring: deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att: erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon innebærer at: ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet: prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje: izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi: teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik: 17 18 19 20 21 22 23 24 25 deklaruje na własną i wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy: declară pe proprie răspundere că echipamentele la care se referă această declaraţie: z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša: kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus: декларира на своя отговорност, че оборудването, за коeто се отнася тази декларация: visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija: ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija: vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie: tamamen kendi sorumluluǧunda olmak üzere bu bildirinin ilgili olduǧu donanımının aşaǧıdaki gibi olduǧunu beyan eder: 01 02 03 04 05 06 07 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions: der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß unseren Anweisungen eingesetzt werden: sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions: conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze instructies: están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras instrucciones: sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni: είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται σύμφωνα με τις οδηγίες μας: 08 09 10 11 12 13 14 15 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de acordo com as nossas instruções: соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим инструкциям: overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser: respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att användning sker i överensstämmelse med våra instruktioner: respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i henhold til våre instrukser: vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti: za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům: u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama: 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják: spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi instrukcjami: sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre: skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili: on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele: съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите инструкции: atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus: tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem: sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade s našim návodom: ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur: 01 02 03 04 05 06 07 08 09 following the provisions of: gemäß den Vorschriften der: conformément aux stipulations des: overeenkomstig de bepalingen van: siguiendo las disposiciones de: secondo le prescrizioni per: με τήρηση των διατάξεων των: de acordo com o previsto em: в соответствии с положениями: 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i: enligt villkoren i: gitt i henhold til bestemmelsene i: noudattaen määräyksiä: za dodržení ustanovení předpisu: prema odredbama: követi a(z): zgodnie z postanowieniami Dyrektyw: în urma prevederilor: 19 20 21 22 23 24 25 ob upoštevanju določb: vastavalt nõuetele: следвайки клаузите на: laikantis nuostatų, pateikiamų: ievērojot prasības, kas noteiktas: održiavajúc ustanovenia: bunun koşullarına uygun olarak: 01 02 03 04 05 06 07 08 09 Directives, as amended. Direktiven, gemäß Änderung. Directives, telles que modifiées. Richtlijnen, zoals geamendeerd. Directivas, según lo enmendado. Direttive, come da modifica. Οδηγιών, όπως έχουν τροποποιηθεί. Directivas, conforme alteração em. Директив со всеми поправками. 10 11 12 13 14 15 16 17 Direktiver, med senere ændringer. Direktiv, med företagna ändringar. Direktiver, med foretatte endringer. Direktiivejä, sellaisina kuin ne ovat muutettuina. v platném znění. Smjernice, kako je izmijenjeno. irányelv(ek) és módosításaik rendelkezéseit. z późniejszymi poprawkami. 18 19 20 21 22 23 24 25 Directivelor, cu amendamentele respective. Direktive z vsemi spremembami. Direktiivid koos muudatustega. Директиви, с техните изменения. Direktyvose su papildymais. Direktīvās un to papildinājumos. Smernice, v platnom znení. Değiştirilmiş halleriyle Yönetmelikler. 01 Note* 02 Hinweis* 03 Remarque* 04 Bemerk* 05 Nota* as set out in and judged positively by according to the Certificate . wie in aufgeführt und von positiv beurteilt gemäß Zertifikat . tel que défini dans et évalué positivement par conformément au Certificat . zoals vermeld in en positief beoordeeld door overeenkomstig Certificaat . como se establece en y es valorado positivamente por de acuerdo con el Certificado . 06 Nota* 07 Σημείωση* 08 Nota* 09 Примечание* 10 Bemærk* delineato nel e giudicato positivamente da  secondo il Certificato . όπως καθορίζεται στο και κρίνεται θετικά από το σύμφωνα με το Πιστοποιητικό . tal como estabelecido em e com o parecer positivo de de acordo com o Certificado . как указано в и в соответствии с положительным решением согласно Свидетельству . som anført i og positivt vurderet af i henhold til Certifikat . 11 Information* 12 Merk* 13 Huom* 14 Poznámka* 15 Napomena* enligt och godkänts av enligt Certifikatet . som det fremkommer i og gjennom positiv bedømmelse av ifølge Sertifikat . jotka on esitetty asiakirjassa ja jotka on hyväksynyt Sertifikaatin  mukaisesti. jak bylo uvedeno v a pozitivně zjištěno v souladu s osvědčením . kako je izloženo u i pozitivno ocijenjeno od strane prema Certifikatu . 16 Megjegyzés* 17 Uwaga* 18 Notă* 19 Opomba* 20 Märkus* a(z) alapján, a(z) igazolta a megfelelést, a(z)  tanúsítvány szerint. zgodnie z dokumentacją , pozytywną opinią i Świadectwem . aşa cum este stabilit în şi apreciat pozitiv de  în conformitate cu Certificatul . kot je določeno v in odobreno s strani v skladu s certifikatom . nagu on näidatud dokumendis ja heaks kiidetud järgi vastavalt sertifikaadile . 21 Забележка* 22 Pastaba* 23 Piezīmes* 24 Poznámka* 25 Not* както е изложено в и оценено положително от съгласно Сертификата . kaip nustatyta ir kaip teigiamai nuspręsta pagal Sertifikatą . kā norādīts un atbilstoši pozitīvajam vērtējumam saskaņā ar sertifikātu . ako bolo uvedené v a pozitívne zistené v súlade s osvedčením . ’da belirtildiği gibi ve  Sertifikasına göre tarafından olumlu olarak değerlendirildiği gibi. KIWA (NB0063) 94004/02, 94005/02 TCF.5.001.16 01** 02** 03** 04** 05** 06** Rotex GmbH is authorised to compile the Technical Construction File. Rotex GmbH hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen. Rotex GmbH est autorisé à compiler le Dossier de Construction Technique. Rotex GmbH is bevoegd om het Technisch Constructiedossier samen te stellen. Rotex GmbH está autorizado a compilar el Archivo de Construcción Técnica. Rotex GmbH è autorizzata a redigere il File Tecnico di Costruzione. 07** 08** 09** 10** 11** 12** Η Rotex GmbH είναι εξουσιοδοτημένη να συντάξει τον Τεχνικό φάκελο κατασκευής. A Rotex GmbH está autorizada a compilar a documentação técnica de fabrico. Компания Rotex GmbH уполномочена составить Комплект технической документации. Rotex GmbH er autoriseret til at udarbejde de tekniske konstruktionsdata. Rotex GmbH är bemyndigade att sammanställa den tekniska konstruktionsfilen. Rotex GmbH har tillatelse til å kompilere den Tekniske konstruksjonsfilen. 13** 14** 15** 16** 17** 18** Rotex GmbH on valtuutettu laatimaan Teknisen asiakirjan. Společnost Rotex GmbH má oprávnění ke kompilaci souboru technické konstrukce. Rotex GmbH je ovlašten za izradu Datoteke o tehničkoj konstrukciji. A Rotex GmbH jogosult a műszaki konstrukciós dokumentáció összeállítására. Rotex GmbH ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej. Rotex GmbH este autorizat să compileze Dosarul tehnic de construcţie. 19** 20** 21** 22** 23** 24** 25** Rotex GmbH je pooblaščen za sestavo datoteke s tehnično mapo. Rotex GmbH on volitatud koostama tehnilist dokumentatsiooni. Rotex GmbH е оторизирана да състави Акта за техническа конструкция. Rotex GmbH yra įgaliota sudaryti šį techninės konstrukcijos failą. Rotex GmbH ir autorizēts sastādīt tehnisko dokumentāciju. Spoločnosť Rotex GmbH je oprávnená vytvoriť súbor technickej konštrukcie. Rotex GmbH Teknik Yapı Dosyasını derlemeye yetkilidir. Georg Blümel Managing Director 3rd of July 2017

Table of contents

Installation manual 3 R2CND028+035A4AA + R2TND028+035A4AA Wall-mounted condensing boiler 3P469346-6E – 2017.07 Table of contents 1 Introduction 3 1.1 About the documentation .......................................................... 3 1.1.1 Meaning of warnings and symbols.............................. 3 1.2 Identification label...................................................................... 3 1.3 Symbols on the package........................................................... 4 2 Safety instructions 4 3 About the unit 4 3.1 Safety systems .......................................................................... 4 3.2 Dimensions................................................................................ 5 3.3 Components .............................................................................. 6 3.4 Technical specifications ............................................................ 7 4 Installation 8 4.1 To open the unit ........................................................................ 8 4.2 Installation site requirements..................................................... 8 Minimum installation clearances................................. 9 4.3 To unpack the unit..................................................................... 9 4.4 To mount the unit ...................................................................... 10 4.5 Central heating system requirements........................................ 10 4.6 Underfloor heating requirements............................................... 11 4.7 Residual pump lift graph............................................................ 11 4.8 Connections .............................................................................. 11 4.8.1 Piping connections...................................................... 11 4.8.2 Guidelines when connecting the gas piping................ 12 4.8.3 Guidelines when connecting the water piping............. 12 4.8.4 Guidelines when connecting the electrical wiring ....... 13 4.8.5 Guidelines when connecting options to the boiler....... 13 4.8.6 Wiring diagram............................................................ 15 4.8.7 Guidelines when connecting the condensate piping... 16 4.8.8 Guidelines for condensate piping termination............. 16 4.8.9 Guidelines when connecting the boiler to the flue gas system......................................................................... 17 4.8.10 Applicable flue systems .............................................. 17 4.9 To fill the system with water ...................................................... 23 Method 1..................................................................... 23 Method 2..................................................................... 23 4.10 Converting for use with a different type of gas.......................... 23 4.10.1 To convert the system for use with a different type of gas .............................................................................. 23 4.10.2 To modify settings for gas conversion ........................ 24 5 Commissioning 24 5.1 To fill the condensate trap......................................................... 24 5.2 Gas-air ratio: No need to adjust ................................................ 24 5.3 To check for gas leakage .......................................................... 24 5.4 To commission the unit ............................................................. 24 5.4.1 To commission the central heating ............................. 25 5.4.2 To commission the central heating capacity setting ... 25 5.4.3 To commission the domestic hot water....................... 25 6 Hand-over to the user 25 Disposal Old units must be appropriately disposed of, in accordance with local and national regulations. The components are easy to separate and the plastics are marked. This allows the various components to be sorted for appropriate recycling or disposal. ▪ Units are marked with the following symbol: This means that electrical and electronic products may not be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority. 1 Introduction 1.1 About the documentation The instructions contained in this document are intended to guide you through the installation of the unit. Damage caused by non- observance of these instructions are not under the responsibility of ROTEX. ▪ The original documentation is written in English. All other languages are translations. ▪ The precautions described in this document are written for installers and they cover very important topics. Follow them carefully. ▪ Please read the operation manual and installation manual prior to use and keep them for future reference. 1.1.1 Meaning of warnings and symbols DANGER Indicates a situation that results in death or serious injury. WARNING Indicates a situation that could result in death or serious injury. CAUTION Indicates a situation that could result in minor or moderate injury. NOTICE Indicates a situation that could result in equipment or property damage. INFORMATION Indicates useful tips or additional information. 1.2 Identification label You can find data about the unit on its identification label, which is located at the bottom of the right cover of the unit.

2 Safety instructions

Installation manual 4 R2CND028+035A4AA + R2TND028+035A4AA Wall-mounted condensing boiler 3P469346-6E – 2017.07 Pn (80/60) Pn (50/30) Qn D (ΔT=30 K) PMS PMW Nox kW kW kW l/min bar MPa bar MPa / / XXXX-XX PIN: a b c d e f g h i j k l m n o p q r s t u v a Product number b Electrical supply c Maximum electrical power consumption d Degree of protection e Nominal heat output range @ 80/60 f Nominal heat output range @ 50/30 g Nominal heat input range h Hot water amount @ DT=30 i NOx class j Maximum central heating pressure (bar) k Maximum central heating pressure (MPa) l Maximum domestic hot water pressure (bar) m Maximum domestic hot water pressure (MPa) n Country of destination(s) o Country of origin p Serial number q Appliance type r Efficiency class s Gas category t Gas type and supply pressure u Product type v PIN number 1.3 Symbols on the package This is a fragile piece of equipment: Please provide a dry storage space for the unit. This is a fragile piece of equipment: Please be very careful not to drop. Store the unit in a flat position as indicated on the box. No more than five boxes should be stacked on top of each other. 2 Safety instructions These instructions are exclusively designed for qualified competent persons. ▪ Work on gas units must only be carried out by a qualified gas fitter. ▪ Work on electrical equipment must only be carried out by a qualified electrician. ▪ The system must be commissioned by a qualified competent person. WARNING A qualified person shall explain the operating principles and the use of the unit to the user. The user is not allowed to perform any modifications, maintenance or repairs on the unit, unless otherwise stated, or have the such performed by unauthorised third parties. Otherwise, the unit warranty becomes void. DANGER Isolate the boiler from the power mains before working on it. WARNING Unit installation, commissioning, repair, configuration and service must be performed by qualified competent persons in accordance with local standards and regulations. Incorrect installation of this unit may harm the user and his/ her surroundings. The manufacturer is not responsible for any malfunctions and/or damage that may occur this way. DANGER Flammable fluids and materials must be stored at least 1 metre away from the boiler. WARNING To ensure faultless operation, long term availability of all functions and long working life of the boiler only use original spares. 3 About the unit This ROTEX unit is a wall-mounted gas-fired condensing boiler that can supply heat to central heating systems, as well as supply domestic hot water. Depending on settings, it is possible to use the unit solely for hot water or solely for central heating. Hot water supply type can be instantaneous or by means of a hot water storage tank. The type of the boiler can be recognised from the model name written on the identification label. See table below: Model Type Domestic hot water supply Filling loop R2CND028A4AA R2CND028 Instantaneous External R2CND035A4AA R2CND035 Instantaneous External R2TND028A4AA R2TND028 Storage tank External R2TND035A4AA R2TND035 Storage tank External A control unit, which contains a user interface, controls the ignition, safety systems, and other actuators. User interaction is provided via that user interface, which is composed of an LCD screen, push buttons, and two dials, and which is located on the front cover of the unit. 3.1 Safety systems The unit is equipped with several safety systems, to protect it against dangerous conditions: Flue safety system: This is controlled by the flue gas temperature sensor located on the flue outlet part of the boiler. It is activated when the flue gas temperature exceeds safety limits. Overheating safety system: This is controlled by the safety limiting thermostat. It is located on the main heat exchanger and stops the unit when the flow temperature reaches 100°C, to avoid boiling of the water, which may damage the unit.

3 About the unit

Installation manual 5 R2CND028+035A4AA + R2TND028+035A4AA Wall-mounted condensing boiler 3P469346-6E – 2017.07 Pump anti-blockage system: The pump operates for 30 seconds every 24 hours during long periods of inactivity to ensure it does not get stuck. To enable this function, the unit must be connected to the power supply. Three-way valve anti-blockage system: In cases where the unit is non-operational for prolonged periods of time, the three-way valve switches its position every 24 hours to prevent it from getting stuck. To enable this function, the unit must be connected to the power supply. Safety against dry operation: This is controlled by the pressure sensor. It turns off the unit and ensures system safety when the water pressure of the heating installation falls below 0.6 bar for any reason. Flame ionisation control: This is controlled by the ionisation electrode. It checks whether a flame forms on the burner surface or not. If there is no flame, it turns the unit off to stop gas flow and warns the user. High pressure protection: ▪ Pressure sensor: When heating system pressure reaches 2.8  bar, control unit stops heating operation thus preventing the pressure from rising. ▪ Safety valve: When the water pressure of the heating circuit exceeds 3  bar, some water is automatically drained from the safety valve to keep the pressure below 3 bar thus protecting the boiler and heating installation. Automatic air vents: There are two air vents; one on the pump, other on the heat exchanger. They help discharging the air inside the installation and heating circuit to avoid air traps and consequent operational problems. Frost protection safety system: This function protects the unit and heating installation from frost damages. It is controlled by the flow temperature sensor, which is located at the outlet of the main heat exchanger. This protection activates the boiler pump when the water temperature drops below 13°C and it activates the burner when the water temperature drops below 8°C. The unit keeps running until the temperature reaches 20°C. To enable this function, the unit must be connected to the power supply and its main gas valve must be open. Any damage caused by frost is not covered by the warranty. Low voltage safety system: This is controlled by the control unit. When the supply voltage drops below 170 Volt, the boiler goes to error mode. It is a blocking error and the boiler will operate without reset after supply voltage is above 180 Volt. It is recommended to use a voltage regulator of suitable power and type in locations with voltage fluctuations below this limit for faultless operation. High electric supply current protection system: A fuse on the control unit protects equipment and wiring against the damaging effects of electrical faults which is caused by excess currents, and disables equipment which is faulty. The fuse "blows" (opens) when the current carried exceeds the rated value for an excessive time. Automatic by-pass system: This ensures that the flow is at all times continued, to avoid overheating of the heat exchanger. This system is also supported with a special by-pass function in the control unit software. Combustion control safety system: Boiler control unit monitors the flame to avoid bad combustion and risky conditions. It also makes self-inspection against its own malfunctioning and to keep emissions always at a low level. 3.2 Dimensions Top view Front view and right side view 784.5 695.5 294.4 Bottom view of model R2CND028A4AA and R2CND035A4AA 90 65 65 68 65 37.5 125 132 180 Bottom view of models R2TND028A4AA and R2TND035A4AA 90 30 100 103 30 125.7 72 132 180 182.5

3 About the unit

Installation manual 6 R2CND028+035A4AA + R2TND028+035A4AA Wall-mounted condensing boiler 3P469346-6E – 2017.07 3.3 Components Components of model R2CND028A4AA and R2CND035A4AA a b c d e f g h i j k z l m n o p q r s t u v w x y a Automatic air vent (heat exchanger) b Flow temperature sensor c Expansion vessel (10 litres) d Gas valve e Heat exchanger f 3-way valve stepper motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve (3 bar) j Condensate trap k Ignition transformer l Flue gas temperature sensor m Burnerhood n Ignition electrode o Ionisation electrode p High limit thermostat q Fan r Return temperature sensor s Silencer t Automatic air vent (pump) u Water pressure sensor v By-pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Flue gas adapter Components of models R2TND028A4AA and R2TND035A4AA a b c d e w f i j k o v p q r s t g h l m n u a Automatic air vent (heat exchanger) b Flow temperature sensor c Expansion vessel (10 litres) d Gas valve e Heat exchanger f 3-way valve stepper motor g Safety valve (3 bar) h Condensate trap i Flue gas temperature sensor j Burnerhood k Ignition electrode l Ionisation electrode m High limit thermostat n Fan o Return temperature sensor p Silencer q Automatic air vent (pump) r Water pressure sensor s By-pass t Boiler pump u Flue gas adapter v Condensate sump w Flue gas pipe

3 About the unit

Installation manual 7 R2CND028+035A4AA + R2TND028+035A4AA Wall-mounted condensing boiler 3P469346-6E – 2017.07 3.4 Technical specifications Technical specifications Unit R2CND028A*AA R2CND035A*AA R2TND028A4AA R2TND035A4AA Heat Input Range(Qn) kW 4.8~27.0 4.8~34.0 4.8~27.0 4.8~34.0 Nominal Heat Output Range (Pn) at 80-60°C kW 4.6~26.3 4.6~33.2 4.6~26.3 4.6~33.2 Nominal Heat Output Range (Pn) at 50-30°C kW 5.2~28.2 5.2~35.0 5.2~28.2 5.2~35.0 Efficiency (30% partial load at 30°C return temperature) % 108.9 108.7 108.9 108.7 Central Heating Circuit Operating Pressure (min./max.) bar 0.6 / 3.0 Heating Circuit Temperature Interval (min./max.) °C 30 / 80 Domestic Hot Water Circuit Hot Water Amount DT: 30°C l/min 14 16 — Hot Water Amount DT: 35°C l/min 12 14 — Water Installation Pressure (min./max.) bar 0.5 / 10.0 — Domestic Hot Water Temperature Interval (min./max.) °C 35 / 60 Domestic Hot Water Circuit Type — instantaneous storage tank General Expansion Vessel Initial Pressure bar 1 Expansion Vessel Capacity l 10 Electrical Connection V AC/Hz 230/50 Electrical Power Consumption (max.) W 92 112 92 112 Standby Electrical Power Consumption W 2.7 Electrical Protection Class — IPX5D Boiler Weight kg 37 35.5 Boiler Dimensions (Height x Width x Depth) mm 695 x 440 x 295 Flue outlet diameter mm 60 / 100 Combustion specifications Unit R2CND028A*AA R2CND035A*AA R2TND028A4AA R2TND035A4AA Gas Category — II2N3P Nominal Gas Inlet Pressure (G20/G25/G31) mbar 20 / 37 G20 Gas Inlet Pressure (min./max.) mbar 17 / 25(a) G25 Gas Inlet Pressure (min./max.) mbar 20 / 31 G31 Gas Inlet Pressure (min./max.) mbar 25 / 45 Natural Gas (G20) Consumption (min./max.) m³/h 0.51 / 2.89 0.51 / 3.63 0.51 / 2.89 0.51 / 3.63 Natural Gas (G25) Consumption (min./max.) m³/h 0.59 / 3.32 0.59 / 4.19 0.59 / 3.32 0.59 / 4.19 LPG (G31) Consumption (min./max.) m³/h 0.2 / 1.09 0.2 / 1.38 0.2 / 1.09 0.2 / 1.38 Combustion products mass flow rate (min./max.) (G20) g/s 2.2 / 12.35 2.2 / 15.47 2.2 / 12.35 2.2 / 15.47 Combustion products mass flow rate (min./max.) (G31) g/s 2.2 / 12.02 2.2 / 15.22 2.2 / 12.02 2.2 / 15.22 Combustion products temperature (min./max.) (G20) °C 57.5 / 76.4 57.5 / 81.7 57.5 / 76.4 57.5 / 81.7 Combustion products temperature (min./max.) (G31) °C 57.5 / 74.5 57.2 / 80.2 57.5 / 74.5 57.2 / 80.2 CO2 Emission at nominal and minimum heat input (G20) % 8.8±0.8 CO2 Emission at nominal and minimum heat input (G31) % 11.3 / 10.2±1.0 NOx Class — 6 (a) 20 / 30 for Hungary Energy-related products (ErP) specifications Symbol Unit R2CND028A*AA R2CND035A*AA R2TND028A4AA R2TND035A4AA Model — — R2CND028 R2CND035 R2TND028 R2TND035 Condensing boiler — — YES YES YES YES Low-temperature(b) boiler — — NO NO NO NO B1 boiler — — NO NO NO NO Cogeneration space heater — — NO NO NO NO Combination heater — — YES YES NO NO Central heating efficiency class — — ****/A Rated heat output Prated kW 26 33 26 33 Useful heat output at rated heat output and high-temperature regime(a) P4 kW 26.3 33.2 26.3 33.2 Useful heat output at 30% of rated heat output and low-temperature regime(b) P1 kW 8.8 11.1 8.8 11.1 Seasonal space heating energy efficiency ηs % 93 Useful efficiency at rated heat output and high-temperature regime(a) η4 % 87.8 87.9 87.8 87.9 Useful efficiency at 30% of rated heat output and low-temperature regime(b) η1 % 98.1 97.9 98.1 97.9 Auxiliary electricity consumption At full load elmax kW 0.0356 0.0547 0.0356 0.0547 At part load elmin kW 0.0098 0.0111 0.0098 0.0111 In standby mode PSB kW 0.0026 Other items Standby heat loss Pstby kW 0.0651 Ignition burner power consumption Pign kW — Annual energy consumption QHE GJ 48 58 48 58 Sound power level, indoors (at maximum heat input) LWA dB 49 52 49 52 Emissions of nitrogen oxides NOx mg/kWh 36 35 36 35 Domestic hot water parameters Declared load profile — — XL —

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 Energy-related products (ErP) specifications Symbol Unit R2CND028A*AA R2CND035A*AA R2TND028A4AA R2TND035A4AA Daily electricity consumption Qelec kWh 0.153 0.204 — Annually electricity consumption AEC kWh 33 44 — Water heating energy efficiency ηwh % 84 83 — Water heating energy efficiency class — — A — Daily fuel consumption Qfuel kWh 23.25 30.26 — Annual fuel consumption AFC GJ 18 23 — (a) High-temperature regime means 60°C return temperature at heater inlet and 80°C flow temperature at heater outlet. (b) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet). 4 Installation 4.1 To open the unit WARNING Only qualified competent persons are allowed to open the unit. Certain actions explained in this document, such as gas conversion, optional equipment connection, require that the front cover is opened. 1 Loosen the screw that holds the right mounting clips (1). 2 Dismantle the two mounting clips that hold the front cover (2). 3 Remove the front cover forwards (3). 3 a 2 1 a Front cover 4 Loosen the two screws of the control panel (4). 4 a a Control panel 5 Pull the control panel forwards (5). 5 4.2 Installation site requirements WARNING The boiler must be installed by a qualified installer in accordance with local and national regulations. WARNING The following instructions shall be observed when determining the installation site. ▪ Mount this unit on vertical, flat walls only.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 a a Vertical, flat wall ▪ The boiler can be installed outdoors in a partially protected location. A partially protected location is a place where the boiler is not exposed to the direct action and to the penetration of atmospheric precipitation (rain, snow, hail,...). The boiler can also be installed inside of an outside wall using the appropriate in‑wall kit. In case of outdoor installation, use the antifreeze kit (DRANTIFREEZAA) to prevent the piping and condensate trap from freezing. ▪ Flammable fluids and materials must be stored at least 1  metre away from the boiler. ▪ The wall on which the unit is mounted should be strong enough to carry the unit's weight. Build a reinforcement if necessary. ▪ The following minimum clearances are required for servicing: 180 mm above the casing*, 200 mm below, and 10 mm at each side. 500 mm at the front clearance may be realised by opening a cupboard door. See "Minimum installation clearances"  on page 9. ▪ For easier use of control panel, it is recommended that boiler bottom is 1500 mm from the floor, for easier part replacement side clearances should be 50  mm where applicable. See "Minimum installation clearances" on page 9. ▪ If the boiler is installed in a room or compartment, it does not require a dedicated ventilation for combustion air. If however installed in a room containing a bath or a shower, then particular reference is drawn to the current I.E.E. Wiring Regulations, local Building Regulations or any other local regulations currently in service. ▪ The intake air must not include chemicals that may cause corrosion, toxic gas formation and even risk of explosion. ▪ If the wall on which the unit is mounted, is flammable, a non- flammable material must be placed between the wall and the unit and also at all locations through where the flue piping passes. Minimum installation clearances a a d f c e d b Minimum allowable clearances a, sides 10 mm b, Above the casing* 180 mm c, below 255 mm f, in front 500 mm Recommended clearances for easy servicing d, sides 50 mm e, below (from the floor) 1500 mm * 180 mm is for the case that 60/100 90° elbow is connected to the flue outlet of the boiler. b = 270 mm in case that 60/100 to 80/80 adapter + 90° elbow 80 are connected to the flue outlet of the boiler. b = 280 mm in case that 60/100 to 80/125 adapter + 90° elbow 80/125 are connected to the flue outlet of the boiler. 4.3 To unpack the unit 1 Unpack the unit as shown on top of the packing case. The following items must be included in the package: a k b c d e f g h i j a Combi boiler b Operation manual c Installation manual d Wall-mounting bracket e Installation template f Dowels and screws g Condensate hose h Cable glands 2×PG 7, 1×PG 9 i Energy label j Storage tank temperature sensor (only for models R2TND028A4AA and R2TND035A4AA) k Condensate trap 2 Check the contents of the package. If any of them is damaged or missing, contact your dealer. CAUTION Store the remaining parts of the package (cardboard, plastic, etc.) in a place children cannot reach. The manufacturer is not responsible for any accidents and/or damage that may occur this way.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 4.4 To mount the unit 1 The mounting template shows the position for the horizontal flue. If there is no hole in the wall for the flue piping, drill one. If there is already a hole in the wall for the flue piping, you can use this hole as a starting point to determine the position of the mounting bracket, according to the template. Flue duct must incline 3° away from the unit, to allow the condensate to drain back to the boiler. 220 220 148 DN100 >3° >3° 2 Drill holes for the mounting bracket (Ø10  mm). Fasten the mounting bracket to the wall according to mounting template. d=10 mm 3 Hang the unit on the bracket. Make sure the unit is latched to the bracket. 4.5 Central heating system requirements Expansion vessel sizing The boiler is equipped with an 10  litre expansion vessel that has initial charge pressure of 1 bar. Sufficiency of the incorporated expansion vessel for the central heating circuit that the boiler is to be connected to depends on system charge pressure and water temperature circulating in the circuit. Determination of system water height and related system charge pressure are given below: h p ≤6 m 0.8 bar 7 m 0.9 bar 8 m 1.0 bar 9 m 1.1 bar 10 m 1.2 bar 11 m 1.3 bar 12 m 1.4 bar 13 m 1.5 bar h h System water height (m) p System charge pressure (bar) According to the graph below, there is no need to install an additional expansion vessel for the systems with a water volume in the area below the operating temperature curve. If water volume is above the curve, additional vessel must be installed, preferably on the return to the boiler. 600 500 400 300 200 100 0 0,8 B (bar) 0,9 1,0 1,1 1,2 1,3 1,4 1,5 50°C - 30°C 50°C - 40°C 60°C - 40°C 70°C - 50°C 80°C - 60°C A (l) A System water volume (l) B System charge pressure (bar) * 50°C-40°C temperature regime is given for underfloor heating systems Water treatment Inappropriate central heating circuit water reduces functionality and efficiency of the boiler over time. Appropriate water should have: ▪ pH degree between 6.5 and 8.5 ▪ Hardness less than 15°fH and 8.4°dH Appropriate additives can be used for water treatment. If antifreeze is needed for the system, the chosen antifreeze should not interact with rubber, commercial plastic and metal parts of the boiler that are in contact with the central heating water. For use of any additive in the central heating system, please refer to the instructions of their manufacturers to ensure above functionality and compatibility. WARNING Mixing inappropriate additives with the central heating circuit water can result in efficiency loss in the boiler or damage to the boiler and the other central heating circuit elements. ROTEX accepts no liability for any such damage or ineffectiveness caused by using inappropriate additive.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 4.6 Underfloor heating requirements Underfloor heating systems apparently require higher flow rate and lower ΔT. This boiler can be connected to an underfloor heating system without use of a second pump and low loss header because of its high pump capacity. Direct connection is possible when the system is well designed and pressure loss is low enough. When the boiler is connected to underfloor heating installation, the maximum central heating set temperature must be limited to 50°C and the pump operation temperature difference must be adjusted to 10 Kelvin in the service settings menu. To change this setting, refer to the servicing instructions. WARNING Make sure parameter changes explained above are done to avoid discomfort of the user. 4.7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift (mbar) that remains for the central heating circuit. 0 0 100 200 300 400 500 600 700 800 200 400 600 800 1000 1200 1400 1600 1800 A (mbar) B (l/h) A Residual pump lift (mbar) B Flow (l/h) 4.8 Connections 4.8.1 Piping connections Piping connections of model R2CND028A4AA and R2CND035A4AA Below, find the piping connections of the unit. A B D E G C F A Central heating return connection, 3/4" B Domestic cold water inlet connection, 1/2" C Condensate trap discharge D Domestic hot water outlet connection, 1/2" E Central heating supply connection, 3/4" F Gas inlet connection, 3/4" G Safety valve discharge B F D a b E A Valve Strainer Tee connection Double check valve + filling hose Disconnector a Isolation valve on domestic hot water supply pipe is tentative. b External filling group used with model R2CND028A4AA and R2CND035A4AA. Use a disconnector or a double check valve according to local regulations. Isolation valves and strainers should be used just before the appliance piping inlet as shown in figure above. Ensure that necessary gaskets are placed. Note: Optional ROTEX connection kit can be used and it is recommended to use it. Piping connections of models R2TND028A4AA and R2TND035A4AA Below, find the piping connections of the unit. B D C A E G F A Central heating return connection, 3/4" B Storage tank return connection, 3/4" C Condensate trap discharge D Storage tank supply connection, 3/4" E Central heating supply connection, 3/4" F Gas inlet connection, 3/4" G Safety valve discharge

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 A a B F D E Valve Strainer Tee connection Double check valve + filling hose Disconnector a External filling group used with models R2TND028A4AA and R2TND035A4AA. Use a disconnector or a double check valve according to local regulations. Isolation valves and strainers should be used just before the appliance piping inlet as shown in figure above. Boiler is filled with external fresh water supply. Ensure that necessary gaskets are placed. Note: Optional ROTEX connection kit can be used and it is recommended to use it. 4.8.2 Guidelines when connecting the gas piping This unit is designed to be operated with natural gas or LPG. The preset gas type and the designated gas inlet pressure are indicated on the boiler's identification label. WARNING Only qualified persons are allowed to connect the gas piping. The gas inlet pipe diameter must be selected according to the applicable legislation, standards, and regulations. Connect the gas piping according to applicable legislation of the country of destination and the regulations of the gas supply company. Connect the gas supply piping without tension to the gas pipe connection ("Connection F", see "4.8.1  Piping connections"  on page 11). WARNING After the gas connection is made, the gas line must be tested for leakage while the gas line to the boiler is open (see "5.3 To check for gas leakage" on page 24). In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with an elbow, enough space for taking out the condensate trap must be left. This can be done in two ways: 1 Elbow must be placed crosswise so it will not block the condensate trap when it is being taken out. 2 Elbow must be placed 200 mm below the gas piping connection of the boiler. 4.8.3 Guidelines when connecting the water piping When connecting the piping to the boiler, observe the following instructions: WARNING Ignoring the rules explained below may result in serious damages in installation or boiler or cause discomfort of the user. The manufacturer is not responsible for any damage that may occur this way. ▪ The installation of the boiler should be in compliance with the applicable legislation, standards, and regulations. ▪ The materials used in the installation must be in compliance with the applicable legislation, standards, and regulations. ▪ Heating installation piping material must not allow oxygen diffusion according to DIN4726. ▪ The central heating/domestic hot water installation should be flushed and visually inspected. Wastes, dust, rubbers, and metal pieces generated during the installation and mounting of the boiler must be removed in order not to cause any damage. ▪ The central heating circuit must be able to withstand a pressure of at least 6 bar. ▪ Cross connection must be preferred in the radiators longer than 1.5 metres. ▪ The safety valve piping should be connected to a water outlet with an additional hose or piping. This outlet should not be installed in places where there is risk of freezing, nor in the rain gutter, it should not end to dry floor without available drainage to avoid damaging of floor coating like parquet. ▪ The maximum pressure in the domestic hot water circuit is 10 bar. Inspect the piping taking this in to consideration. If the water pressure of the main water supply is excessive, use an appropriate pressure reducer. Installation must comply with EN 15502-2-2. ▪ As the condensing boilers generate condensate, the condensate trap outlet should be connected to an open drain. Piping and elements of the drain line must be made of acid-resistant material like plastics. Metals like steel or copper are not allowed. ▪ The system must be air-free to protect the boiler. There are two automatic air vents on the boiler, one at heat exchanger, the other on the pump. Ensure air is discharged completely at each water filling. Bleed the radiators if necessary. ▪ If the boiler will be connected to an old central heating/domestic hot water installation, then first visually inspect the old installation. The installation must be in compliance with the capacity of the boiler and must not prevent the efficient running of it. Dirt in old system and piping must be flushed, and filters must be inspected.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 ▪ If old piping material does not have oxygen barrier, then it must be separated from the boiler circuit via a plate heat exchanger and a second pump has to be installed for necessary circulation. ▪ If the pressure reading on the boiler user interface is dropping repeatedly, most probably there is a leakage in the installation. Inspect the installation to repair. ▪ In case of solar preheating of the domestic hot water from a solar tank, install the thermostatic mixing valve at the domestic hot water outlet and inlet. 4.8.4 Guidelines when connecting the electrical wiring DANGER Before working on the electrical circuit always isolate the unit from the power mains. WARNING Only qualified persons are allowed to make electrical connections on the unit. Failure to observe this warning will void the warranty. The manufacturer is not responsible for any damage that may occur this way. WARNING Use a dedicated power circuit. Never use a power supply cable shared by another unit. The unit runs on 230 V AC 50 Hz power. A power cable is delivered with the package. The power cable must be connected to the power supply by an electrician and in accordance with the applicable legislation. a b 3×0.75 TTR / 230 V H05RN 1~ 230 V 50 Hz Cat. III a Safety breaker (2 A) b Earth leakage safety breaker Cat. III Overvoltage category III ▪ Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice. ▪ Insufficient capacity or incomplete electrical work may cause electrical shock or fire. ▪ A main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III, shall be installed in the fixed wiring. ▪ Be sure to establish an earth. Do not earth the unit to a utility pipe, lightning arrester, or telephone earth. Incomplete earth may cause electrical shock and fire. ▪ While the electrical connections are being done, energy should not be on the main power supply cable and the main switch should be closed. ▪ During the electrical connections, make sure that the cables are well-fixed and are connected firmly and tightly. ▪ Power supply cable must be equivalent to H05RN-F (2451EC57) as minimum requirement. Observe the point mentioned below when wiring to the power supply terminal board. b a L N a

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 PG9 PG7 PG7 PG9 Holes on the bottom sheet that are reserved for cable glands are covered with insulation material. The insulation material must be bored if glands are to be used. Note: Unit must be opened to mount cable glands. See "4.1 To open the unit" on page 8 to reach the inside of the boiler.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 4.8.6 Wiring diagram DANGER: RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Model R2CND028A4AA and R2CND035A4AA Models R2TND028A4AA and R2TND035A4AA 7 8

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 Symbols: Item Description Option Wiring depending on model Switch box PCB X4M Main terminal Earth wiring 15 Wire number 15 Field supply 1 Several wiring possibilities Legend: Part Connector Description PCB1 — Main PCB PCB2 X3 Status indicator PCB PCB3 X9 LAN (var iCAN) adapter P1 X2-X11 Boiler pump F1 X1-X11 Fan GV1 X11 Gas valve IT1 X1 Ignition transformer 3WV1 X13 Central heating / domestic hot water diverter valve stepper motor WPS1 X4 Water pressure sensor DHW FS1 X4 Domestic hot water flow sensor (for models R2CND*) IE1 X5 Ionisation input K1 X2M Solar stop contact K2 X2M On/OFF room thermostat HE1 X11 Overheat thermostat NTC1 X1M Outdoor temperature sensor NTC2 X4 Flow temperature sensor NTC3 X4 Return temperature sensor NTC4 X4 Flue temperature sensor NTC5 X4 Domestic hot water temperature sensor (for models R2CND*) NTC5 X1M Domestic hot water storage tank sensor (for models R2TND*) NTC6 X1M Solar domestic hot water temperature sensor Ext1 X8 BCC (Boiler Chip Card) Ext2 X10 Personal computer production interface Ext3 X1M Opentherm room thermostat Ext4 X2M External power output (230 V AC) Ext5 X2M Reserved, not in use X1M X4-X11-X12 Low voltage terminal strip X2M X1-X2 High voltage terminal strip 4.8.7 Guidelines when connecting the condensate piping DANGER In order to prevent escape of flue gases and so poisoning, the condensate trap must be mounted to its place before commissioning. Condensate trap must be connected to a drain via an open connection. Precautions that should be taken about condensate piping are: ▪ Horizontal pipe runs must fall a minimum of 45 mm/metre. ▪ External piping should be kept as short as possible or thermally insulated to prevent freezing, depending on the installation winter climate condition. ▪ Make sure that the condensate disposal system, the piping, and the fittings are made of acid resistant material like plastics. WARNING The condensate trap outlet shall not be modified or blocked. CAUTION The condensate discharge piping diameter must be large enough so as not to restrain the condensate water flow. WARNING If the discharge pipe is located outdoors, take measures against frost. 4.8.8 Guidelines for condensate piping termination Condensate piping can be connected to a termination in different ways shown below:

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 Terminating into an internal soil and vent stack b a ≥450 mm a Air breaker b Internal soil and vent stack Terminating into an external waste system a a Open end direct into gully, below ground but above water level Terminating into an external purpose made soakaway a b a Open end direct into gully, below ground but above water level b Sink, basin, bath or shower NOTICE Use of a condensate drain pump is necessary where termination of condensate line is below a soakaway. 4.8.9 Guidelines when connecting the boiler to the flue gas system DANGER Risk of poisoning due to flue gas escaping within enclosed rooms that are inadequately ventilated. CAUTION Connected flue type must be identified on the identification label. Approved flue systems Choose a flue type according to the installation site. Approved flue types are written on the identification label. Flue termination The positions of the terminals in the roof or in the wall with respect to openings for ventilation must be in accordance with national regulations. ▪ The boiler must be installed so that the terminal is exposed to external air. ▪ Position of the terminal must allow the free passage of air across it at all times. ▪ Pluming may occur at the flue terminal. Positions where this could be a nuisance should be avoided. ▪ For single wall flue pipe, the minimum distance to a combustible material must be 25 mm. For air intake pipe and concentric systems, the distance to a combustible material is 0 (zero) mm. ▪ It is essential to ensure that products of combustion discharging from the terminal cannot re-enter the building or other buildings, through ventilators, windows, doors, other sources of natural air infiltration or forced ventilation. ▪ Minimum flue duct length must be 50 cm. 4.8.10 Applicable flue systems In this part, information about different flue systems are given. The mounting instructions for correct installation of the flue systems are included in the packaging of the flue parts as well as flue cutting instructions where needed. NOTICE Optional parts shown in rectangular area are used where needed. Type C13x (concentric flue system) The boiler draws combustion air from outside via a concentric coaxial pipe fitted to the external wall and expels flue gas to the outside via the external wall. a b c d e L f a Wall terminal kit 60/100 Optional: b 90° elbow 60/100 c 45° elbow 60/100

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 d 30° elbow 60/100 e Tee 60/100 with measurement point f Extension 60/100 L = 500-1000 mm Allowable flue length for C13x Concentric 60/100 mm(a) 7.0 m Concentric 80/125 mm(a) 33.6 m (a) Including 1 90° elbow Equivalent length of options 90° elbow 60/100 mm 1.5 m 45° elbow 60/100 mm 1.0 m 30° elbow 60/100 mm 1.0 m 90° elbow 80/125 mm 1.5 m 45° elbow 80/125 mm 1.0 m 30° elbow 80/125 mm 1.0 m 60/100 flue length can be increased up to 19.9  metres by adjusting the parameter C3 to 5. Refer to servicing instructions for this operation. 80/125 flue length can be increased up to 99  metres by adjusting the parameter C3 to 5. Refer to servicing instructions for this operation. Subtract equivalent length value of bends from the allowable flue length value. DANGER Flue duct must incline 3° away from the unit, to allow the condensate to drain back to the boiler and out of the condensate drain. Flue length determination Flue duct length (L) is measured from lip of the elbow to end of the flue terminal. L a L Flue duct length a Distance of outer lip of terminal to outer wall, a≤50 mm Note: Flue ducts are inserted 45 mm into elbows and extensions. Type C33x (concentric flue system) The boiler draws combustion air from the outside and expels flue gas to the outside through a concentric coaxial pipe via the roof. The terminal outlets from separate combustion and air supply circuits shall fit inside a square of 50 cm and the distance between the planes of the two orifices shall be less than 50 cm. a b e c c d d f g h L i a Roof terminal 60/100 b Tile roof outlet kit Optional: c 45° elbow 60/100 d Extension 60/100 mm e Flat roof outlet kit f 90° elbow 60/100 g 45° elbow 60/100 h 30° elbow 60/100 i Extension 60/100 L = 500-1000 mm Allowable flue length for C33x Concentric 60/100 mm 7.6 m Concentric 80/125 mm 34.4 m Equivalent length of options 90° elbow 60/100 mm 1.5 m 45° elbow 60/100 mm 1.0 m 30° elbow 60/100 mm 1.0 m 90° elbow 80/125 mm 1.5 m 45° elbow 80/125 mm 1.0 m 30° elbow 80/125 mm 1.0 m 60/100 Vertical flue length can be increased up to 20.7 metres by adjusting the parameter C3 to 5 from the user interface. Refer to servicing instructions for this operation.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 80/125 Vertical flue length can be increased up to 99  metres by adjusting the parameter C3 to 5 from the user interface. Refer to servicing instructions for this operation. Subtract equivalent length value of bends from the allowable flue length value. 80/125 mm flue system To increase the maximum allowable flue duct length, 80/125  mm concentric flue ducts can be used instead of 60/100  mm. In this case, C13x and C33x flue systems should start with a 60/100 to 80/125 adapter coupled to the flue outlet. a a 60/100 to 80/125 adapter 80/125 flue parts to be used are shown below: a b c d e f a 80/125 wall terminal kit (type C13) b 80/125 roof terminal kit (type C33) c 90° elbow 80/125 d 45° elbow 80/125 e 30° elbow 80/125 f Extension 80/125 L = 500-1000 mm Type C43x (concentric flue system) Several heat sources draw combustion air from the outside through the annular gap of the room sealed balanced flue system and expel flue gas to the outside via the roof, through a moisture-resistant internal pipe. The multi-served chimney is a system that is part of the building and has a separate CE marking. The connection between the boiler and the shaft and, the connection between the boiler and the air intake system must be obtained via ROTEX. e f g h L i a b c d a Tee flex boiler connection set 100 or 130 b Extension 60 mm c Chimney connection 60/100 d Elbow 60/100 90° Optional: e 90° elbow 60/100 f 45° elbow 60/100 g Tee 60/100 with measurement point h 30° elbow 60/100 i Extension 60/100 L = 500-1000 mm Maximum allowable length of the flue duct up to common chimney is 2 metres + 1 60/100 90° elbow. In C43x type units, condensate flow into the unit is not allowed. Type C63x (concentric flue system) To install the boiler as a C63x option the following data must be used to determine the correct diameters and lengths of the flue system. for R2C/TND028 ▪ Nominal combustion products temperature: 83.4°C ▪ Combustion products mass flow rate: 12.35 g/s ▪ Overheat combustion products temperature: 92.2°C ▪ Minimum combustion products temperature: 30.8°C ▪ Maximum allowable pressure difference between combustion air inlet and flue gas outlet (including wind pressures): 135 Pa for R2C/TND035 ▪ Nominal combustion products temperature: 88.4°C ▪ Combustion products mass flow rate: 15.47 g/s ▪ Overheat combustion products temperature: 99.5°C ▪ Minimum combustion products temperature: 31.2°C ▪ Maximum allowable pressure difference between combustion air inlet and flue gas outlet (including wind pressures): 185 Pa for R2C/TND028 and R2C/TND035 ▪ Minimum combustion products mass flow rate: 2.2 g/s ▪ CO2 content at nominal heat input: 8.8% ▪ Maximum allowable draught: 50 Pa ▪ The boiler must be connected to a system with the following characteristics: T120 P1 W ▪ Maximum allowable temperature of combustion air: 50°C ▪ Maximum allowable recirculation rate under wind conditions is 10% ▪ The terminals for the supply of combustion air and for the evacuation of combustion products shall not be installed on opposite walls of the building. ▪ Condensate flow into the unit is allowed.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 Type C53x (twin pipes flue system) Air supply and flue gas discharge from / to atmosphere in areas of different pressure. The boiler draws combustion air from outside via a horizontal pipe fitted to the external wall and expels flue gas to the outside via the roof. The terminals for the supply of combustion air and for the evacuation of combustion products shall not be installed on opposite walls of the building. h i L j f g b c a c d e a Roof terminal 80 mm b Flat roof outlet kit c Extension 80 mm d Air intake 80 mm e 60/100 to 80 80 adapter f 90° elbow 80 mm Optional: g Tile roof outlet kit h 45° elbow 80 mm i 90° elbow 80 mm j Extension 80 mm L = 500-1000-2000 mm Allowable flue length for C53x Air intake duct 80 mm 54 m Flue outlet duct 80 mm 54 m Equivalent length of options 45° elbow 80 mm 1.0 m Equivalent length of options 90° elbow 80 mm 2.0 m Subtract equivalent length value of bends from the allowable flue length value. Note: The air intake length is 3 metres. In case of longer air intake use, flue outlet duct length must be shortened with the same length. Type C83x (twin pipes flue system) The boiler draws combustion air from outside via a separate supply pipe routed through the external wall, and expels flue gas to a shared flue system. The multi served chimney is a system that is part of the building and has a separate CE marking. The connection between the boiler and the shaft and, the connection between the boiler and the air intake system must be obtained via ROTEX. In C83x type units, condensate flow into the unit is not allowed. a b d c d f g L h e a Wall plate b Extension 80 mm c 60/100 to 80 80 adapter d 90° elbow 80 mm e Air intake 80 mm Optional: f 45° elbow 80 mm g 90° elbow 80 mm h Extension 80 mm L = 500-1000-2000 mm Type C93x The boiler draws combustion air from the outside through the annular gap in the shaft (chimney) and expels the flue gas via the flue pipe to above the roof.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 g h L i j a b c b d e f a Flex kit PP Dn 60-80 or Dn 80 b Spacer c Extension Flex PP 80 mm d Connector Flex-Flex PP 80 mm e Chimney connection 60/100 or 80/125 f 90° elbow 60/100 Optional: g Tee 60/100 with measurement point h 30° elbow 60/100 i 45° elbow 60/100 j Extension 80/125 L = 500-1000 mm Instead of 60/100, 80/125 flue ducts can be used at the outlet of the boiler. In that case, the parts below are used: a b c d e a 60/100 to 80/125 adapter b 90° elbow 80/125 c 45° elbow 80/125 d 30° elbow 80/125 e Extension 80/125 L = 500-1000 mm Allowable flue length for C93x Shaft Chimney cross- section Parameter C3 “3” “5” 60-100 Concentric circular and smooth 100 8.0 21 DN 60 Flex circular and rough 106 3.7 9.8 DN 60 Flex circular and rough 100 2.7 7.0 DN 60 Flex square and rough 95 3.8 9.9 DN 60 Flex square and rough 90 2.8 7.4 80-125 Concentric circular and smooth 124 34 100 DN 80 Flex circular and rough 140 18.2 53.5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11.6 34.1 DN 80 Flex circular and rough 120 4.4 13.0 DN 80 Flex square and rough 140 23.8 69.9 DN 80 Flex square and rough 130 20.6 60.6 DN 80 Flex square and rough 120 14.8 43.5 DN 80 Star square and rough 140 58 169.5 DN 80 Star square and rough 120 40.7 119.0 Equivalent length of options 45° elbow 60/100 mm 1.0 m 90° elbow 60/100 mm 1.5 m 45° elbow 80/125 mm 1.0 m 90° elbow 80/125 mm 1.5 m Maximum allowable length of the flue duct up to common chimney is 2 metres + 1 60/100 90° elbow. Subtract equivalent length value of bends from the allowable flue length value. Type B53 (open flue system) The boiler draws combustion air from the installation room and expels flue gas through the flue to above the roof (1). The boiler draws combustion air from the installation room and routes flue gas through the moisture-resistant chimney to above the roof (2). Allowable flue length for B53 Flue duct 60 mm 15.0 m Flue duct 80 mm 100.0 m Equivalent length of options 90° elbow 60 mm 1.5 m 45° elbow 60 mm 1.0 m 90° elbow 80 mm 2.0 m 45° elbow 80 mm 1.0 m Subtract equivalent length value of bends from the allowable flue length value.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 a c d e L b a 90° elbow 60 mm b Extension 60 mm Optional: c 90° elbow 60 mm d 45° elbow 60 mm e Extension 60 mm L= 250-500-1000-1500-2000 mm Type B33 (open flue system) The multi served chimnet is a system that is a part of the building and has a separate CE marking. The connection between the boiler and the shaft must be obtained via ROTEX. b c a d L a B33 flue kit Optional: b 90° elbow 60 mm c 45° elbow 60 mm d Extension 60 mm L = 500 mm Flue parts order codes Required flue kits and/or additional parts can be ordered from ROTEX with the order codes given in the table below: Flue part Order code Wall terminal kit 60/100 (C13x) DRWTER60100AA Wall terminal kit 80/125 (C13x) EKFGW6359 Flue part Order code Roof terminal kit 60/100 (C33x) EKFGP6837 Roof terminal kit 80/125 (C33x) EKFGP6864 Tee 60/100 with measurement point EKFGP4667 90° elbow 60/100 with measurement point DRMEEA60100BA 90° elbow 60/100 EKFGP4660 90° elbow 80/125 EKFGP4810 45° elbow 60/100 EKFGP4661 45° elbow 80/125 EKFGP4811 30° elbow 60/100 EKFGP4664 30° elbow 80/125 EKFGP4814 Extension duct 60/100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80/125 500 mm EKFGP4801 1000 mm EKFGP4802 Tile roof outlet kit 60/100 18°/22° EKFGS0518 23°/27° EKFGS0519 25°/45° EKFGP7910 43°/47° EKFGS0523 48°/52° EKFGS0524 53°/57 EKFGS0525 Tile roof outlet kit 80/125 18°/22° EKFGT6300 23°/27° EKFGT6301 25°/45° EKFGP7909 43°/47° EKFGT6305 48°/52° EKFGT6306 53°/57° EKFGT6307 Flat roof outlet kit 60/100 EKFGP6940 80/125 EKFGW5333 Wall bracket DN.100 EKFGP4631 DN.125 EKFGP4481 60/100 to 80/125 adapter DRDECO80125BA Tee flex boiler connection set 100 mm EKFGP6368 130 mm EKFGP6215 Flex + support elbow 60/100 EKFGP6354 60/130 EKFGS0257 Chimney connection 60/100 EKFGP4678 80/125 EKFGS4828 Roof terminal kit 80 mm EKFGP6864 90° elbow 80 mm EKFGW4085 45° elbow 80 mm EKFGW4086 Extension duct 80 mm 500 mm EKFGW4001 1000 mm EKFGW4002 2000 mm EKFGW4004 60/100 to 80/80 adapter DRDECOP8080BA Air intake 80 mm (C53 kit) EKFGV1102 Air intake 80 mm (C83 kit) EKFGV1101 Flex kit PP DN.80 (C93 kit) EKFGP2520 Flex kit PP DN.60/80 (C93 kit) EKFGP1856 Extension flex PP 80 mm 10 m EKFGP6340 15 m EKFGP6344 25 m EKFGP6341 50 m EKFGP6342 Connector flex - flex PP 80 EKFGP6324 Spacer PP 80 to 100 mm EKFGP6333

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 Flue part Order code 90° elbow 60 mm DR90ELBOW60AA 45° elbow 60 mm DR45ELBOW60AA Extension duct 60 mm 500 mm DREXDUC0500AA 1000 mm DREXDUC1000AA B33 flue kit DRB33FLUKITAA 4.9 To fill the system with water CAUTION Water filling must be done while the boiler is in standby mode. Method 1 (For models R2TND028A4AA and R2TND035A4AA) a 1 2 3 4 6 7 5 E D F B A a Use a disconnector or a double check valve according to local regulations. After all system connections are performed with care, perform the following steps: 1 Connect the appliance to the main power supply. Due to low pressure, error code "Err HJ-09" will appear on the user interface and the status indicator light will be red. 2 Open all radiator valves. 3 Set all isolating valves to closed position. 4 Connect fresh water supply pipe to valve 5. 5 Open valves 1, 2, 3, 4, 5, 6. 6 Slowly turn the valve 7 to open position until pressure reaches a value around 0.8 bar for system heights up to 6 metres. For longer system heights, see "4.5  Central heating system requirements" on page 10 to determine filling pressure. Filling operation should be done slowly. When pressure exceeds 0.8 bar, error code will disappear and the status indicator light will turn to blue. Turn the valve 7 off. 7 Turn the valve 5 off. Remove the filling loop if it is required by local regulations. 8 Check the central heating circuit - especially the couplings of the circuit - for leakage. 9 Make sure the automatic air vent valves located on the pump and heat exchanger are opened. Vent the air from the installation with the manual air vent screws on the radiators. Make sure screws are tightened after venting. 10 If after the venting the pressure decreases below 0.8 bar, refill with water until the pressure reaches 0.8 bar again. 11 Isolate the appliance from power mains. Method 2 (For model R2CND028A4AA and R2CND035A4AA) E 1 2 4 3 6 5 D F B 7 a 8 A a Use a disconnector or a double check valve according to local regulations. After all system connections are performed with care, perform the following steps: 1 Connect the appliance to the main power supply. Due to low pressure, error code "Err HJ-09" will appear on the user interface and the status indicator light will be red. 2 Open all radiator valves. 3 Set all isolating valves to closed position. 4 Connect the filling loop to the valve 7 and valve 8. 5 Set valves 1, 3, 5, 6 and 8 to open position. 6 Slowly open the valve 7 until pressure reaches a value around 0.8 bar for system heights up to 6 metres. For longer system heights, see "4.5  Central heating system requirements"  on page  10 to determine filling pressure. Filling operation should be done slowly. When pressure exceeds 0.8 bar, error code will disappear and the status indicator light will turn to blue. Turn the valve 7 off. 7 You can monitor the system pressure value from the user interface. 8 Make sure the automatic air vent valves located on the pump and heat exchanger are opened. Vent the air from the installation with the manual air vent screws on the radiators. Make sure screws are tightened after venting. 9 If after the venting the pressure decreases below 0.8 bar, refill with water until the pressure reaches 0.8 bar again. 10 Set valve 8 to off position. Remove the filling loop if it is required by local regulations. 11 Check the central heating circuit - especially the couplings of the circuit - for leakage. 12 Isolate the boiler from power mains. 4.10 Converting for use with a different type of gas WARNING Gas conversion operation can only be carried out by qualified competent persons. DANGER Isolate the boiler from the power mains before gas conversion operation. 4.10.1 To convert the system for use with a different type of gas 1 Open the front cover of the unit as described in this manual.

R2CND028+035A4AA + R2TND028+035A4AA

Wall-mounted condensing boiler 3P469346-6E – 2017.07 2 To set natural gas, adjust screw on the gas valve to position "1". 3 To set LPG, adjust the screw to position "2". 4 Mount the front cover, connect the unit to the main power supply. 4.10.2 To modify settings for gas conversion 1 Enter the menu section from the user interface. Select service settings by using the left dial. 2 Press the "Enter" button and choose the password by using the right dial and press the "Enter" button again. 3 Choose "C" parameters via left dial and press the "Enter" button. 4 Choose "CE" and press the "Enter" button. It will ask for password again. Choose the password and press the "Enter" button. 5 Choose "C0" and press the "Enter" button. 6 To convert to LPG, choose "1" with the right dial and press the "Enter" button, To convert to Natural gas, choose "0" with the right dial and press the "Enter" button. 7 Leave the menu screen and go back to the home screen by using the "Back" button. INFORMATION Only qualified persons have access to servicing parameters. The passwords needed to access service parameters are written in servicing instructions. 5 Commissioning WARNING Only qualified persons should conduct commissioning. CAUTION Preliminary electrical system checks such as earth continuity, polarity, resistance to earth and short circuit must be carried out by using a suitable test meter by a competent person. 5.1 To fill the condensate trap INFORMATION Water must be poured into the inner tube. Fill the condensate trap by pouring 0.2 litres of water from the boiler flue outlet. 5.2 Gas-air ratio: No need to adjust The installer does not have to adjust the gas-air ratio, because the boiler has an electronic gas adaptive feature. 5.3 To check for gas leakage DANGER Before passing next steps, this control must be fulfilled. 1 Before connecting the unit to power mains, close valves 1, 2 and 3. 2 Connect a manometer to gas counter. 3 Open valves 1, 2 and 3. 4 Close valve 1. 5 Note the manometer measurement and wait for 10 minutes. 6 After 10  minutes, compare the manometer measurement with the initial value. If the pressure is decreased, it means there is gas leakage. Check the gas line and fittings. 7 Repeat this process until being sure that there is no leakage. 8 Close valve 1, remove the manometer and open valve 1 again. 1 2 3 5.4 To commission the unit Legend - User interface:

6 Hand-over to the user

Installation manual 25 R2CND028+035A4AA + R2TND028+035A4AA Wall-mounted condensing boiler 3P469346-6E – 2017.07 a e f g c b d a Left dial b LCD screen c Right dial d Mode / Reset e Status indicator f Cancel / Back g Menu / Enter 1 Make sure the system is filled with water and fully vented as described in this manual. 2 Check that the central heating and domestic hot water isolating valves are open. 3 Check that gas service valve is open. 4 Connect the unit to the main power supply. The user interface will be energised. 5.4.1 To commission the central heating 1 Set mode to winter mode via "Mode" button on the user interface. ( and icons are displayed on the screen.) 2 Set central heating set temperature to maximum value via left dial. If connected, make sure all external controls such as outdoor sensor and room thermostat are calling for heat. 3 The boiler control now go through its ignition sequence. The status indicator will glow constantly in blue if flame is established. icon will blink when central heating is active. INFORMATION After first power ON, the boiler does not increase its capacity above a preset value for about 12 minutes, even if there is demand. ▪ First 0~2 minutes: The electronic gas adaptive system calibrates itself. ▪ Next 8~10 minutes: The boiler performs the low water temperature function. You can skip this function by pressing the "Cancel" button for 5 seconds. 4 Press "Cancel" and "Menu" buttons together 5  seconds to activate the sweeper mode. With sweeper mode, boiler can be operated at maximum and minimum capacity independent of heat demand. 5 "tst - 100" caption will appear on the screen. This means boiler is operating at nominal capacity. Check nominal capacity operation. 6 To quit sweeper mode, again press "Cancel" and "Menu" buttons together five seconds. Sweeper mode will be deactivated and boiler will return to normal operation mode. Sweeper mode also finishes automatically after 15 minutes. 5.4.2 To commission the central heating capacity setting The boiler's central heating capacity can be adjusted form the control panel. If the heat loss of installation is much less than that of the boiler nominal capacity, it is recommended to reduce the boiler nominal capacity to the installation capacity. Refer to service instructions for this operation. 5.4.3 To commission the domestic hot water (Only for models R2CND028 and R2CND035 ) 1 Set domestic hot water set temperature to its maximum value via right dial. 2 Open hot water taps fully and ensure that water flows freely from them. 3 icon will blink when domestic water heating is active. 4 Measure the domestic hot water inlet temperature. (Cold water drawn off from taps) 5 Check that domestic hot water temperature rise is around 34°C. 6 Hand-over to the user After completing the installation and commissioning of the system the installer should hand over to the householder. ▪ Hand the operation manual to the householder and inform them about his/her responsibilities under the relevant national regulations. ▪ Explain and demonstrate the lighting and shutting down procedures. ▪ Explain the function and the use of the boiler heating and domestic hot water controls. ▪ Explain and demonstrate the function of temperature controls, radiator valves etc., for the economic use of the system. ▪ Explain the function of the boiler error mode. Emphasise that if an error is indicated refer to "Error codes" in the operation manual. ▪ Inform the user about frost protection function and advise never to cut off the electric supply to the boiler. ▪ Emphasise that a comprehensive service should be carried out annually, especially before winter. ▪ Inform the householder of the guarantee and the requirement to register it to receive the full benefit of the warranty.

ROTEX Heating Systems GmbH

Langwiesenstraße 10 D-74363 Güglingen www.rotex-heating.com Unsere Partner im Ausland Our partners abroad • Unsere Partner im Ausland Nos partenaires à l’étranger • Le nostre sedi all'estero Neustros representantes en el extranjero Nasi partnerzy za granicą • Naši partneři v zahraničí http://de.rotex-heating.com > ueber-rotex > international 3P469346-6E 2017.07 © ROTEX ∙ Subject to change and correction