TEREN DPTR Operation Manual

Specifications

Brand: TEREN
Category: Transmitter
Model: DPTR (Operation Manual)
File Type: PDF
File Size: —
Pages: 2

Read Online

Read the TEREN DPTR Operation Manual online using the built-in PDF viewer.

Text of the manual

DPTR Rail Mount Differential Pressure Transmitter-Operation Manual Edition: A/3

1 DPTR Rail Mount Differential Pressure Transmitter Applications & Features  Mount on standard 35mm DIN rail, small enough for compact installation in equipments and instruments  Apply high accuracy MEMS sensor and digital technologies, can measure differential pressure on equipment such as isolators and clean benches for pharmaceutical production, biological and medicine research, microelectronics, hazardous chemicals operations, and general laboratories  Multiple ranges, engineering units and outputs  Good performance, accuracy 1.0% or 0.5%FS selectable  Function keys: zero reset, unit select, response time set, etc Specifications Medium: non-combustible, non-corrosive air, insensitive to moisture, dust, condensation and oil Temp.: Working,-20~70°C; Medium, 0~60°C; Compensation, 0~50°C Storage: -30~70°C Working Pressure: overload 10xFS, burst 15xFS Performance: Accuracy %FS ±1.0% ±0.5% Thermal effect %FS/°C(Zero/FS) ±0.05/0.08 ±0.03/0.04 Stability %FS/Year ±0.5 ±0.3 Response Time: 0.5/1/2/5s, can be set by keys Process Connection: 5mm ID tubing Output: 0~10V, 4~20mA (2 wires), RS485 selectable Output Load: ≤500Ω (current), ≥2kΩ (voltage) Power: Current: 18.5~35VDC (RL=500Ω)8.5~35VDC (RL=0Ω) Voltage: 16~28VAC/ 16~35VDC Zero reset: outside key to operate easily Materials: Fire-proof ABS+PC Protection: IP30 Weight: 110g Approval: CE Models Model DPTR Rail Mount DP Transmitter Accuracy 0 ±1%FS 1 ±0.5%FS Range x Range selection(See table) Output 1 0~10V 2 4~20mA(2 wires) 8 RS485/Modbus Measuring ranges Note: For zero center models, add “Z” at the end of the model. For example, DPTR*1*Z, means the range is -30-0-30.Only 1~6 have this selection. Connection Different models have different electrical terminals. Please wire specific model according to the wiring diagram on the front cover. Setting 1. The zero-reset button is for resetting zero drift. Press and hold the button for 5 seconds to complete the operation. 2. The RS485 terminating resistor (120Ω) is selected by the toggle switch. When “J8” is ON, the resistor (120Ω) is applied. 3. Response Time select: switch the S2 to different positions for 0.5s,1s, 2s and 5s according to the diagram below. Note: since the time is not fully synchronized, the actual response time is 1~2 times set time. Code Pa Code Pa 0 0~25 5 0~1000 1 0~60 6 0~2500 2 0~125 7 0~5000 3 0~250 8 0~10000 4 0~500 RS485 9600,8,N,1 Slave Add.= 1 3 4 A 1 2 POWER SUPPLY B 24VDC/AC V 3 4 POWER SUPPLY 24VDC A 3 4 POWER SUPPLY 1 2 Current Output 4-20mA Voltage Output 0-10V RS485/Modbus RTU Output 24VDC/AC ON 1 2 ON 1 2 ON 1 2 ON 1 2 0.5S 1S 2S 5S S2 RS485 terminal resistance (inside product) ON 1 J8 zero-reset

DPTR Rail Mount Differential Pressure Transmitter-Operation Manual Edition: A/3

2 Installation: Figure 1 Figure 2 Figure 3 Figure 4 ● Install into the DIN rail: it is recommended that the pressure ports to be installed vertically downwards, as shown in above figures. As Figure 1 and 2, insert the transmitter’s upper hook into DIN-rail, then buckle the lower white plastic hook into DIN- rail, as Figure 3. The plastic hook can be pulled down to help. ● Pressure connection: connect the tube to the two pressure ports correctly, making sure to air-tighten to prevent leakage. ● Electrical connection: As figure 4, unplug the terminals of the transmitter and wire correctly, then plug back. Zero reset & Calibration ● Due to different environment and sensor characteristics, after long term of using, the sensor’s accuracy maybe drift. The transmitter should be zero reset after initial installed to meet the specified accuracy. It is better to be “zero reset” after the initial 7 days continuous working. Usually it need to be zero reset periodically in every 6-12 months’ working. ● Zero reset: keep the high (+) and low (-) pressure ports unconnected in stable air, or directly connect the two, press the button “ZERO” for 5s. It means to remove the zero drift of the transmitter in order to improve the accuracy. It is recommended that this operation to be done periodically. ● Initial zero reset: when initial power on, it should be zero reset after fully warm-up and stable, to meet the specified accuracy. ● Long term zero drift & reset: It may have long term zero drift after continuous working; customers can reset it periodically. ● Re-calibration & zero reset: when re-calibration needed, zero reset should be done first. A qualified standard manometer is needed for re-calibration operation. Attention It should be power OFF during installing and wiring. When using 24VAC, it is strongly recommended to power the unit with independent transformer. If sharing a 24VAC transformer with other equipments such as controllers, transmitters or actuators, please make sure the terminals 24V and GND are connected correctly. Otherwise, it may reduce serious damages. Warranty ● It has limited warranty for eighteen (18) months after the production date. ● It does not extend to any unit that has been subjected to misuse or accident. ● It is, in any event, strictly limited to the replacement or repair of the product itself. Shenzhen TEREN Control Technology Co. Ltd. Add: 3F, 2nd Industrial Zone, Nankeng, Longgang District, Shenzhen,Guangdong,P.R.CHINA Tel: 0755-23935155 Fax: 0755-23935156 web: www.teren.com.cn TEREN website Alibaba shop

Other Transmitter Manuals