NA10 - Manual - 04 - 2022
MANUAL
NA30
PHASE & RESIDUAL OVERCURRENT,
GROUND DIRECTIONAL, THERMAL IMAGE,
RESIDUAL OVERVOLTAGE
NA10 - Manual - 04 - 2022
T A B L E O F C O N T E N T S
T A B L E O F C O N T E N T S
1 INTRODUCTION
5
Scope and liability ...........................................................................................................................................................................................5
Applicability ......................................................................................................................................................................................................5
Conformity ........................................................................................................................................................................................................5
Copyright ...........................................................................................................................................................................................................5
Warranty ...........................................................................................................................................................................................................5
Safety recommendations ...............................................................................................................................................................................5
Insulation tests ................................................................................................................................................................................................5
Product identification .....................................................................................................................................................................................6
Environment .....................................................................................................................................................................................................6
Graphical conventions ...................................................................................................................................................................................6
Glossary/definitions ........................................................................................................................................................................................6
2 GENERAL
10
Preface ........................................................................................................................................................................................................... 10
Photo .............................................................................................................................................................................................................. 10
Main features .................................................................................................................................................................................................11
3 TECHNICAL DATA
12
3.1 GENERAL ............................................................................................................................................................................................................12
Technical data ................................................................................................................................................................................................12
Insulation ........................................................................................................................................................................................................12
EMC tests for interference immunity .........................................................................................................................................................12
Voltage dip and interruption ........................................................................................................................................................................12
EMC tests for interference immunity .........................................................................................................................................................12
Emission ......................................................................................................................................................................................................... 13
Mechanical tests .......................................................................................................................................................................................... 13
Climatic tests ................................................................................................................................................................................................. 13
Safety ............................................................................................................................................................................................................. 13
Certifications ..................................................................................................................................................................................................14
3.2 INPUT CIRCUITS ...............................................................................................................................................................................................14
Auxiliary power supply Uaux ......................................................................................................................................................................14
Phase current input circuits ........................................................................................................................................................................14
Residual current input circuit ......................................................................................................................................................................14
Residual voltage input circuit ......................................................................................................................................................................14
Binary input circuits ......................................................................................................................................................................................14
Block input (Logic selectivity) .....................................................................................................................................................................14
3.3 OUTPUT CIRCUITS ............................................................................................................................................................................................14
Relays ..............................................................................................................................................................................................................14
Block output (Logic selectivity) ...................................................................................................................................................................15
3.4 MMI .....................................................................................................................................................................................................................15
3.5 COMMUNICATION INTERFACES ...................................................................................................................................................................15
Local port ........................................................................................................................................................................................................15
Remote ports ..................................................................................................................................................................................................15
3.6 GENERAL SETTINGS ........................................................................................................................................................................................16
3.7 PROTECTIVE FUNCTIONS ...............................................................................................................................................................................16
Base current - IB ...........................................................................................................................................................................................16
Thermal protection with Pt100 probes - 26 ...............................................................................................................................................16
Thermal image - 49 ........................................................................................................................................................................................16
Phase overcurrent - 50/51 ............................................................................................................................................................................16
Residual overcurrent - 50N/51N ................................................................................................................................................................ 18
Residual overvoltage - 59N ......................................................................................................................................................................... 19
Directional earth fault overcurrent - 67N ................................................................................................................................................. 19
Breaker failure - BF .......................................................................................................................................................................................22
3.8 CONTROL AND MONITORING ....................................................................................................................................................................... 23
Second harmonic restraint - 2ndh-REST .................................................................................................................................................. 23
Trip Circuit Supervision - 74TCS ................................................................................................................................................................. 23
Selective block - BLOCK2 ........................................................................................................................................................................... 23
Internal selective block - BLOCK4 ............................................................................................................................................................. 23
Circuit Breaker supervision ........................................................................................................................................................................ 23
CT supervision - 74CT .................................................................................................................................................................................. 23
Pilot wire diagnostic .................................................................................................................................................................................... 23
Demand measures ....................................................................................................................................................................................... 23
Oscillography (DFR)) .....................................................................................................................................................................................24
PLC (Programmable Logic Controller) .......................................................................................................................................................24
NA10 - Manual - 04 - 2022
3.9 METERING..........................................................................................................................................................................................................25
Accuracy (type tests)....................................................................................................................................................................................25
Measures ........................................................................................................................................................................................................25
4 FUNCTION CHARACTERISTICS
26
4.1 HARDWARE DESCRIPTION .............................................................................................................................................................................26
Power supply board ......................................................................................................................................................................................27
CPU board .......................................................................................................................................................................................................27
Input board .....................................................................................................................................................................................................27
MMI (keyboard, LED and display) ..............................................................................................................................................................27
4.2 SOFTWARE DESCRIPTION ............................................................................................................................................................................. 28
Base software ............................................................................................................................................................................................... 28
Real-time operating system ........................................................................................................................................................................ 28
Task ................................................................................................................................................................................................................. 28
Drivers ............................................................................................................................................................................................................ 29
Application Software ................................................................................................................................................................................... 29
Data Base ...................................................................................................................................................................................................... 29
Self test (Application) .................................................................................................................................................................................. 29
Development tools (Builder) ....................................................................................................................................................................... 29
4.3 I/O DESCRIPTION ............................................................................................................................................................................................. 30
Metering inputs ............................................................................................................................................................................................ 30
Signal processing ......................................................................................................................................................................................... 30
Conventions ................................................................................................................................................................................................... 33
Use of measured values ...............................................................................................................................................................................34
Binary inputs ..................................................................................................................................................................................................35
Output relays ................................................................................................................................................................................................. 40
LED indicators ................................................................................................................................................................................................42
Communication interfaces ...........................................................................................................................................................................44
4.4 PROTECTIVE ELEMENTS .................................................................................................................................................................................45
Rated values ...................................................................................................................................................................................................45
Thermal protection with RTD thermometric probes - 26 ........................................................................................................................47
Thermal image - 49 ....................................................................................................................................................................................... 49
Phase overcurrent - 50/51 ........................................................................................................................................................................... 60
Residual overcurrent - 50N/51N ................................................................................................................................................................ 70
Residual overvoltage - 59N ......................................................................................................................................................................... 80
Ground directional overcurrent - 67N ........................................................................................................................................................84
Breaker failure - BF .....................................................................................................................................................................................107
4.5 CONTROL AND MONITORING ..................................................................................................................................................................... 109
Logical block - BLOCK1 ............................................................................................................................................................................. 109
Selective block - BLOCK2 ..........................................................................................................................................................................111
Internal selective block -BLOCK4 .............................................................................................................................................................116
Remote tripping ...........................................................................................................................................................................................117
Frequency tracking .................................................................................................................................................................................... 118
Second Harmonic Restraint - 2ndh-REST .............................................................................................................................................. 119
Cold Load Pickup - CLP ............................................................................................................................................................................. 120
CT supervision - 74CT .................................................................................................................................................................................122
Trip circuit supervision - 74TCS................................................................................................................................................................ 123
Circuit breaker supervision .......................................................................................................................................................................126
Demand measures ..................................................................................................................................................................................... 129
Oscillography ............................................................................................................................................................................................. 129
5 MEASURES, LOGIC STATES AND COUNTERS
130
Measures ..................................................................................................................................................................................................... 130
Protection .................................................................................................................................................................................................... 130
Delayed inputs ............................................................................................................................................................................................ 130
Internal states ............................................................................................................................................................................................. 130
Relays ............................................................................................................................................................................................................131
Counters ........................................................................................................................................................................................................131
Self test .........................................................................................................................................................................................................131
Pilot wire diagnostic ...................................................................................................................................................................................132
Selective Block - BLOCK2 ..........................................................................................................................................................................132
Fault recording - SFR ..................................................................................................................................................................................132
Event recording - SER ................................................................................................................................................................................ 133
Oscillography - DFR ................................................................................................................................................................................... 133
6 INSTALLATION
135
6.1 PACKAGING .....................................................................................................................................................................................................135
6.2 MOUNTING ......................................................................................................................................................................................................135
6.3 ELECTRICAL CONNECTIONS ....................................................................................................................................................................... 139
NA10 - Manual - 04 - 2022
6.4 NOMINAL CURRENT In AND IEn SETTING ............................................................................................................................................... 149
6.5 LED ALLOCATION ........................................................................................................................................................................................... 153
6.6 FINAL OPERATIONS ...................................................................................................................................................................................... 153
7 PROGRAMMING AND SETTINGS
154
7.1 SW ThyVisor ....................................................................................................................................................................................................154
ThyVisor installation ....................................................................................................................................................................................154
ThyVisor use .................................................................................................................................................................................................154
7.2 MMI (Man Machine Interface) ....................................................................................................................................................................155
Reading variables (READ) ..........................................................................................................................................................................155
Setting modifying (SET) ..............................................................................................................................................................................155
TEST ...............................................................................................................................................................................................................157
COMMUNICATION ......................................................................................................................................................................................157
Circuit breaker commands ....................................................................................................................................................................... 158
Enable / block changes via keyboard - Password ................................................................................................................................ 158
7.3 MODULES MANAGEMENT .......................................................................................................................................................................... 159
7.4 MAINTENANCE .............................................................................................................................................................................................. 160
7.5 REPAIR ............................................................................................................................................................................................................. 160
7.6 PACKAGING .................................................................................................................................................................................................... 160
8 APPENDIX
161
8.1 APPENDIX A1 - Inverse time IEC curves ...................................................................................................................................................161
Mathematical formula ................................................................................................................................................................................161
Phase overcurrent 50/51 - Standard inverse time curve (IEC 60255-3/BS142 type A) ....................................................................162
Phase overcurrent 50/51 - Very inverse time curve (IEC 60255-3/BS142 type B) ........................................................................... 163
Phase overcurrent 50/51 - Extremely inverse time curve (IEC 60255-3/BS142 type C) ...................................................................164
Residual overcurrent 50N/51N - Standard inverse time curve (IEC 60255-3/BS142 type A) .........................................................165
Residual overcurrent 50N/51N - Very inverse time curve (IEC 60255-3/BS142 type B) ..................................................................166
Residual overcurrent 50N/51N - Extremely inverse time curve (IEC 60255-3/BS142 type C) ........................................................167
Ground directional overcurrent 67N - Standard inverse time curve (IEC 60255-3/BS142 type A) ............................................... 168
Ground directional overcurrent 67N - Very inverse time curve (IEC 60255-3/BS142 type B) ....................................................... 169
Ground directional overcurrent 67N - Extremely inverse time curve (IEC 60255-3/BS142 type C) .............................................. 170
8.2 APPENDIX A2 - Inverse time ANSI/IEEE curves .......................................................................................................................................171
Mathematical formula ................................................................................................................................................................................171
Phase overcurrent 50/51 - Moderately inverse time curve (ANSI/IEEE type MI) ............................................................................172
Phase overcurrent 50/51 - Very inverse time curve (ANSI/IEEE type VI) ........................................................................................ 173
Phase overcurrent 50/51 - Extremely inverse time curve (ANSI/IEEE type EI) ................................................................................174
Residual overcurrent 50N/51N - Moderately inverse time curve (ANSI/IEEE type MI) .................................................................175
Residual overcurrent 50N/51N - Very inverse time curve (ANSI/IEEE type VI) ...............................................................................176
Residual overcurrent 50N/51N - Extremely inverse time curve (ANSI/IEEE type EI) ......................................................................177
Ground directional overcurrent 67N - Moderately inverse time curve (ANSI/IEEE type MI)....................................................... 178
Ground directional overcurrent 67N - Very inverse time curve (ANSI/IEEE type VI) .................................................................... 179
Ground directional overcurrent 67N - Extremely inverse time curve (ANSI/IEEE type EI) ........................................................... 180
8.3 APPENDIX A3 - Inverse time - RECTIFIER, I2t and EM curves ................................................................................................................181
Mathematical formula ................................................................................................................................................................................181
Phase overcurrent 50/51 - Rectifier curves ............................................................................................................................................182
Phase overcurrent 50/51 - I2t inverse curves (I2t=K) ........................................................................................................................... 183
Phase overcurrent 50/51 - Electromechanical inverse curves (EM) ..................................................................................................184
Residual overcurrent 50N/51N - Electromechanical inverse curves (EM)........................................................................................185
Ground directional overcurrent 67N - Electromechanical inverse curves (EM) ..............................................................................186
8.4 APPENDIX B1 - I/O Diagram .........................................................................................................................................................................187
8.5 APPENDIX B2 - Interfaces ........................................................................................................................................................................... 188
8.6 APPENDIX B3- Connection diagrams ........................................................................................................................................................ 189
8.7 APPENDIX C - Dimensions ............................................................................................................................................................................192
8.8 APPENDIX D - Setting table ......................................................................................................................................................................... 193
8.9 APPENDIX E - EC Declaration of conformity ..............................................................................................................................................237
NA30 - Manual - 04 - 2022
1 I N T R O D U C T I O N
1 I N T R O D U C T I O N
Scope and liability
This document describes the functions, the technical data of NA30 devices; instructions for mount-
ing, setting and commissioning are included.
This manual has been checked out, however, deviations from the description cannot be completely
ruled out, so that no liability in a legal sense for correctness and completeness of the information or
from any damage that might result from its use is formally disclaimed.
The information given in this document is reviewed regularly; any corrections and integration will be
included in subsequent editions that are identified by the date of revision.
We appreciate any suggestions for improvement.
We reserve the right to make technical improvements without notice.
Applicability
This manual is valid for NA30 devices with firmware version 1.60 and following.
Conformity
The product complies with the CE directives:
• EMC Council Directives:
2014/30/EC
• Low voltage Directives:
2014/35/EC
Copyright
All right reserved; It is forbidden to copy, modify or store material (document and sw) protected by
copyright without Thytronic consent.
Warranty
Thytronic warrants devices against defects in materials and workmanship under normal use for a
period of ONE (1) YEAR from the date of retail purchase by the original end-user purchaser (“War-
ranty Period”).
Safety recommendations
The warming contained in this document are all-important for safety; special attention must be paid
to the following symbols:
Installation and commissioning must be carried out by qualified person; Thytronic assumes no re-
sponsibility for damages caused from improper use that does not comply all warning and caution in
this manual.
In particular the following requirements must be met:
• Remove power before opening it.
• Verify the voltage absence by means suitable instrumentation on relay connections; attention must
be paid to all circuits supplied by external sources (binary input, CT, etc...)
• Care must be taken when handling metal parts (front panel, connectors).
Insulation tests
After insulation tests, hazardous voltages (capacitor charges,...) may be arise; it is advisable to grad-
ually reduce the test voltage avoiding to erase it abruptly.
DANGER
Death, severe personal injury or substantial property damage will result if proper precautions
are not taken
WARNING
Death, severe personal injury or substantial property damage can result if proper precautions
are not taken.
CAUTION
Minor personal injury or property damage can result if proper precautions are not taken
CAUTION
Settings must be established on the basis of a coordination study.
Numerical values inside examples have educational purpose only; they don’t be used, in no way,
for actual applications.
NA30 - Manual - 04 - 2022
Product identification
Each device is equipped with:
• Identification label installed on the front side with following informations: code number, phase and
residual nominal currents, auxiliary voltage range and CE mark:
• Test label with following informations: data, serial number and test operator signature.
Environment
The NA30 device must be employed according to the environment conditions shown (see technical
data).
In case of different environment conditions, appropriate provisions must be provided (conditioning
system, humidity control, etc...).
If contaminants are present (dust, corrosive substances, etc...), filters must be provided.
Graphical conventions
The CEI/IEC and ANSI symbols is employed where possible:
e.g.: 51 = ANSI code concerning the overcurrent element.
Following text formats are used:
The ThyVisor[1] menu:
Phase overcurrent -50/51
The parameter description (measures, thresholds, operate time,...) and related value:
I> element
�
�
�
�
Definite�time
I>def
The display messages (MMI) are shown as:
NA30
Notes are highlighted with cursive letters inside colored bar
Note: Useful description note
Glossary/definitions
IEn
Relay residual nominal current
IEnp
Residual CT primary nominal current
In
Relay phase nominal current
Inp
Phase CT primary nominal current
IB
Basic current: it represents the nominal current of the line or trans-
former, referred to the nominal current of the CT’s for thermal image
protection
UEn
Relay residual nominal voltage
UEnp
Residual primary nominal voltage (phase-to-phase) · √3
49
Thermal image ANSI code
50/51
Phase overcurrent ANSI code
50N/51N
Residual overcurrent ANSI code
59N
Residual overvoltage ANSI code
67N
Directional ground fault ANSI code
BF
Circuit breaker failure ANSI code
74CT
CT supervision
74TCS
Trip Circuit Supervision
DFR
Digital Fault Recorder (Oscillography)
SER
Sequential Event Recorder
SFR
Sequential Fault Recorder
ANSI
American National Standard Institute
IEEE
Institute of Electrical and Electronics Engineers
IEC
International Electrotechnical Commission
CENELEC
Comité Européen de Normalisation Electrotechnique
52 o CB (Circuit Breaker)
Circuit Breaker
Note 1 The graphic interface and the operation of the ThyVisor software are described in the relative chapters
NA30#0A2MMB0
In
5A
UAUX 110-230 Vac/dc
100V
IEn
UEn
1A 1A
5A 1A
5A
1
2
3
4
5
NA30 - Manual - 04 - 2022
52a
Auxiliary contact in the breaker that is in the same position as the
breaker. It can be assigned to a binary input to locate the CB posi-
tion (Breaker failure and/or CB diagnostic functions). (52a open = CB
open)
52b
Auxiliary contact in the breaker that is in the opposite position as the
breaker (52b open = CB closed)
K1...K6...K10
Output relays
Pulse
Output relay with pulse operation
tTR
Output relay minimum pulse width
Latched
Output relay with latched operation (manual reset) Output relay with
latched operation (automatic reset)
No-latched
Output relay with no-latched operation (automatic reset)
CT
Current Transformer
P1
IEC nomenclature for primary polarity mark of CTs (as an alternative to
a ANSI dot)
P2
IEC nomenclature for primary polarity mark of CTs (as an alternative to
a ANSI no-dot)
S1
IEC nomenclature for secondary polarity mark of CTs (as an alternative
to a ANSI dot)
S2
IEC nomenclature for secondary polarity mark of CTs (as an alternative
to a ANSI no-dot)
Self test
Diagnostic
Start
Leave an initial condition or reset condition (Pickup)
Trip
Operation (with operate time)
Operating time
Duration of time interval between the instant when the character-
istic quantity in reset condition is changed, under specified condi-
tions, and the instant when the relay operates
Dropout ratio
The ratio of a reset value to an operate value in well-specified con-
ditions. The dropout ratio may be lower or greater than 1 according
as an over or under element is considered
Reset time
Duration of the time interval between the instant when the charac-
teristic quantity in operate condition is changed, under specified
conditions, and the instant when the relay operates.
The stated reset time is related to a step variation of characteristic
quantity in operate condition to the reset condition.
Overshoot time
The critical impulse time for a relay which is in its reset condition,
is the longest duration a specified change in the input energizing
quantity(ies) (characteristic quantity), which will cause the relay
to change to operate condition, can be applied without the relay
switches. The overshoot time is the difference from the operate time
and the critical impulse time.
The declared values for the overshoot time are applicable with the
lower setting value of the operation time.
MMI (Man Machine Interface) Operator front panel
ThyVisor
Setting and monitoring software
Log file
A text file that lists actions that have occurred (ThyVisor).
J2SE
Java Platform Standard Edition
Subnet Mask
(Ethernet nomenclature)
Sw
Software
Fw
Firmware
Upgrade
Firmware upgrade
XML
eXtensible Markup Language
NA30 - Manual - 04 - 2022
Symbols.ai
Symbols
I>> Start
I>> BF_OUT
IPh Block2
Logic internal signal (output); may be a logical state (e.g.I>> Start) or a numerical value
It is available for reading (ThyVisor + communication interface)
Logic external signal (intput); may be a command coming from a binary input or a sw command
It is available for reading (ThyVisor + communication interface)
Internal signal (e.g. Breaker Failure output state concerning to the 2nd threshold of the 50 element)
It is not available for reading (missing arrow)
AND and NAND logic gates
OR and NOR logic gates
Limit block (I>> threshold).
Computation block (Max phase current)
Threshold setting (e.g. pickup I>>).
The value is available for reading and is adjustable by means ThyVisor + MMI.
Switch
ON delay timer with reset (tON delay)
ON delay timer without reset (tON delay)
OFF delay timer (dropout) without reset (tDROP delay)
Curve type (definite/inverse time)
0
T
I L3
Max[I L1 ,I L2 ,I L3 ]
I L2
I L1
tON
tON
tON
tON
t
RESET
INPUT
OUTPUT
tDROP
tON
tON
t
INPUT
OUTPUT
tON
tON
tON
t
INPUT
OUTPUT
0
T
tON
&
&
≥1
≥1
EXOR logic gate
tDROP
=1
I>>
I
I ≥ I>>
tON
RESET
0
T
0
T
NA30 - Manual - 04 - 2022
Symbols1 .ai
t
RESET
INPUT
OUTPUT
tOFF
tOFF
tOFF
tOFF
Minimum pulse width operation for output relays (tTR)
tTR
t
tTR
INPUT
OUTPUT
tTR
0
T
tTR
t
tTR
INPUT
OUTPUT
Latched operating mode for output relays and LEDs
Pulse operating mode for output relays
t
INPUT
OUTPUT
Latched
tTR
T
0
RESET
OFF delay timer (dropout) with reset (tOFF delay)
NA30 - Manual - 04 - 2022
2 G E N E R A L
2 G E N E R A L
Preface
The relay type NA30 can be used in radial networks as feeder or power transformer protection:
• On long feeders in ungrounded or Petersen coil and/or high resistance grounded systems.
• On the BT side of parallel connect transformers that are protected with differential element with
any grounded systems.
• As ground fault protection of parallel connected generators or generator-transformer unit on the
same Busbar.
Following input circuits are available:
• Three phase current and one residual current inputs with nominal currents independently select-
able at 1 A or 5 A using dip-switch.
• One residual voltage input with nominal voltage programmable in the range 50...130 V (UER=100V).
• Five binary inputs.
• One block input (logic selectivity).
In addition to the main protection element, the breaker failure (BF), CT monitoring (74CT)) and Trip
Circuit Supervision (TCS) are also provided.
Setting, programming and reading operations must be effected by means of Personal Computer with
ThyVisor software or by means of remote communication interface (RS485 bus,Ethernet network and
USB); all operations must be performed through MMI.
According to the hardware configurations, the NA30 protection relay can be shipped in various case
styles depending on the required mounting options:
• Flush.
• Projecting mounting.
• Rack.
• With separate operator panel.
Other options are:
• Auxiliary power supply operating range.
• Communication protocols.
Photo
NA30 - Manual - 04 - 2022
Main features
• Metallic case.
• Backlight LCD 4x16 Display.
• Eight LEDs that may be joined with matrix criteria to many and various functions.
• RESET key to clear LED indications and latched output relays.
• Five free settable binary inputs.
• Independently settable for start, trip, self-test and control six output relay (K1...K6) Each output
relay may be set with normally energized or normally de-energized operating mode and manual or
automatic reset (latched/no-latched).
• Rear Ethernet communication port, with MODBUS TCP/IP® protocol, with RJ45 (copper wires) or
FX (optical fiber) connection.
• Rear RS485 port, with ModBus protocol.
• USB front serial port (local communication for ThyVisor).
• Real time clock with super capacitor.
The most significant constructive features are:
• Galvanically insulated input and output circuits (communication and binary circuits included).
• Optimum filtering of input signals through combined use of analog and digital filters.
• Traditional electromechanical-type final output contacts with continuous monitoring of control coil
continuity.
• Auxiliary supply comprising a switching-type voltage stabilizing circuit having a very wide working
range and a very small power dissipation
• Nominal frequency: 50 or 60 Hz.
The most significant operating features are:
• Programming of operating modes and parameters by means of the front keys and alphanumeric
display, with a programming procedure based on carrying out guided selections and on explicit and
immediate signalling of the operations being performed, so that such procedure can be carried out
without coding tables or mnemonic informations.
• The feature modification operations do not interrupt the normal functions of the relay.
• Impossibility of programming unacceptable parameter values, thanks to the automatic limitation of
top and bottom scale values for the relative setting ranges.
• Currents are sampled 24 times per period and measured in the effective value (RMS) of the funda-
mental component using the DFT (Discrete Fourier Transform) algorithm and digital filters.
• The fault recorder (SFR) runs continuously capturing in circular mode the last twenty events upon
trigger of binary input/output and/or element pickup (start-trip).
• The event recorder (SER) runs continuously capturing in circular mode the last three hundred
events upon trigger of binary input/output.
• Digital fault recorder (DFR) in COMTRADE format (oscillography).
NA30 - Manual - 04 - 2022
3 T E C H N I C A L D ATA
3 T E C H N I C A L D ATA
3.1
GENERAL
� Technical data
Mounting:
• Flush.
• Projecting.
• Rack.
• Separated operator panel.
External dimensions (Flush mounting)
177 x 107 x 235 (high x width x depth)
Terminals
screw connection
Mass
(Flush mounting)
2.0 kg
Reference standards
EN 60529, EN 60529/A1
Degrees of protection provided by enclosures (IP Code)
• Front
IP52
• Terminals
IP20
� Insulation
Reference standards
EN 60255-5 IEC 60255-5
High voltage test (50 Hz 60 s)
• Auxiliary power supply
2 kV
• Input circuits
2 kV
• Output circuits
2 kV
• Output circuits (between open contacts)
1 kV
• Comunication Circuits
500 V
Impulse voltage withstand test (1.2/50 ms):
• Auxiliary power supply
5 kV
• Input circuits
5 kV
• Output circuits
5 kV
• Output circuits (between open contacts)
2.5 kV
Insulation resistance
>100 MW
� EMC tests for interference immunity
Reference standards
• Product standard for measuring relays
EN 50263
• Generic standards immunity for industrial environments
EN 61000-6-2
• Electromagnetic compatibility requirements for measuring relays and protection equipment
EN 60255-26
• Apparati di automazione e controllo per centrali e stazioni elettriche
• Compatibilità elettromagnetica - Immunità
ENEL REMC 02
• Normativa di compatibilità elettromeccanica per apparati e sistemi
ENEL REMC 01
� Voltage dip and interruption
Reference standards
EN 61000-4-29
IEC 60255-22-11
Voltage dips, short interruptions and voltage variations on dc input power port immunity tests
Auxiliary power supply in dc energizing quantity
• Interruption (UT=40%)
100 ms
• Interruption (UT=0%)
50 ms
• Voltage variations (UT=80...120%)
10 s
� EMC tests for interference immunity
Reference standards
EN 60255-22-1 IEC 60255-22-1
EN 61000-4-12 EN 61000-4-12
Damped oscillatory wave
• 0.1 MHz and 1 MHz common mode
2.5 kV
• 0.1 MHz and 1 MHz differential mode
1.0 kV
• Ring wave common mode
2.0 kV
• Ring wave differential mode
1.0 kV
Reference standards
EN 60255-22-2 IEC 60255-22-2
EN 61000-4-2 IEC 61000-4-2
Electrostatic discharge
• Contact discharge
6 kV
• Air discharge
8 kV
NA30 - Manual - 04 - 2022
Reference standards
EN 60255-22-3 IEC 60255-22-3
EN 61000-4-3 IEC 61000-4-3
Radiated radio-frequency fields
• 80...1000 MHz AM 80%
10 V/m
• 900 MHz Pulse modulated
10 V/m
Reference standards
EN 60255-22-4 IEC 60255-22-4
EN 61000-4-4 IEC 61000-4-4
Fast transient burst (5/50 ns)
• Auxiliary power supply
2 kV
• Input circuits
4 kV
Reference standards
EN 60255-22-5 IEC 60255-22-5
EN 61000-4-5 IEC 61000-4-5
High energy pulse
• Uaux (line-to-ground 10 ohm, 9 mF)
2 kV
• Uaux (line-to-line 0 ohm, 18 mF)
1 kV
• I/O ports (line-to-ground 40 ohm, 0.5 mF)
2 kV
• I/O ports (line-to-line 40 ohm, 0.5 mF)
1 kV
Reference standards
EN 60255-22-6 IEC 60255-22-6
EN 61000-4-6 IEC 61000-4-6
Conducted radio-frequency fields
• 0.15...80 MHz AM 80% 1kHz
10 V
Reference standards
EN 60255-22-7 IEC 60255-22-7
EN 61000-4-16 IEC 61000-4-16
Power frequency immunity tests
• Dc voltage
30 V
• 50 Hz continuously
30 V
• 50 Hz 1 s
300 V
• 0.015...150 kHz
30 V
Reference standards
EN 61000-4-8 IEC 61000-4-8
Magnetic field 50 Hz
• 50 Hz continuously
100 A/m
• 50 Hz 1 s
1 kA/m
Reference standards
EN 61000-4-10 IEC 61000-4-10
Damped oscillatory magnetic field
• Damped oscillatory wave 0.1 MHz
30 A/m
• Damped oscillatory wave 1 MHz
30 A/m
� Emission
Reference standards
EN 60255-25 IEC 60255-25
EN 61000-6-4 IEC 61000-6-4
EN 55011 CISPR 11
Electromagnetic emission tests
• Conducted emission auxiliary power supply 0.15...0.5 MHz
79 dB mV
• Conducted emission auxiliary power supply 0.5...30 MHz
73 dB mV
• Radiated emission 30...230 MHz
40 dB mV/m
• Radiated emission 230...1000 MHz
47 dB mV/m
� Mechanical tests
Reference standards
EN 60255-21-1 EN 60255-21-2 RMEC01
Vibration, shock, bump and seismic tests on measuring relays and protection equipment
• EN 60255-21-1 Vibration tests (sinusoidal)
Class 1
• EN 60255-21-2 Shock and bump test
Class 1
� Climatic tests
Reference standards
IEC 60068-x ENEL R CLI 01 CEI 50
Ambient temperature
-25...+70 °C
Storage temperature
-40...+85 °C
Relative humidity
10...95 %
Atmospheric pressure
70...110 kPa
� Safety
Reference standards
EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use
Pollution degree
3
Reference voltage
250 V
Overvoltage category
III
NA30 - Manual - 04 - 2022
� Certifications
Reference standards
Product standard for measuring relays
EN 50263
CE Conformity
• EMC Directive
2014/30/EC
• Low Voltage Directive
2014/35/EC
Type tests
IEC 60255-6
3.2
INPUT CIRCUITS
� Auxiliary power supply Uaux
Voltage
Nominal value (range)
24...48 V~/-
115...230 V~/110...220 V-
Operative range (each one of the above nominal values)
19...60 V~/-
85...265 V~/75...300 V-
Inrush current (max)
• 24 V-
6 A, 5 ms
• 48 V-
14 A, 5 ms
• 110 V-
20 A, 1 ms
• 230 V~
50 A, 1 ms
Frequency (for alternate voltage supply)
45...66 Hz
Max distortion factor ( for alternating voltage supply)
15%
Max alternating component (for dc voltage supply):
• Full wave rectified sine wave
100 %
• Sine wave
80 %
Power consumption:
• Maximum (energized relays, Ethernet TX)
10 W (20 VA)
• Maximum (energized relays, Ethernet FX)
15 W (25 VA)
� Phase current input circuits
Relay nominal phase current In
1 A or 5 A selectable by dip-switch
Permanent overload
25 A
Thermal overload (1 s)
500 A
Dynamic overload (half cycle)
1250 A
Rated consumption (for any phase)
≤ 0.002 VA with In=1 A
≤ 0.04 VA with In=5 A
� Residual current input circuit
Relay nominal residual current IEn
1 A or 5 A selectable by dip-switch
Permanent overload
25 A
Thermal overload (1 s)
500 A
Dynamic overload (half cycle)
1250 A
Rated consumption
≤ 0.006 VA with IEn=1 A
≤ 0.12 VA with IEn=5 A
� Residual voltage input circuit
Relay residual nominal voltage UEn
50...130 V
Permanent overload
130 V
Thermal overload (1 s)
200 V
Rated consumption
≤ 0.5 VA
� Binary input circuits
Quantity
5
Type
optocoupler
Operative range
24...265 V~/-
Min activation voltage UDIGmin
18 V
Max consumption, energized IDIG
3 mA
� Block input (Logic selectivity)
Quantity
1
Type
polarized wet input (powered by internal isolated supply)
Max consumption, energized
5 mA
3.3
OUTPUT CIRCUITS
� Relays
Quantity
6
Type of contacts K1, K2
changeover (SPDT, type C)
Type of contacts K3, K4, K5
make (SPST-NO, type A)
Type of contacts K6
break (SPST-NC, type B)
NA30 - Manual - 04 - 2022
Nominal current
8 A
Nominal voltage/max switching voltage
250 V~/400 V~
Breaking capacity:
• Direct current (L/R = 40 ms)
50 W
• Alternating current (l = 0,4)
1250 VA
Make
1000 W/VA
Short duration current (0,5 s)
30 A
Minimum switching load
300 mW (5 V/ 5 mA)
Life:
• Mechanical
106 operations
• Electrical
105 operations
� Block output (Logic selectivity)
Quantity
1
Type
optocoupler
3.4
MMI
Display
LCD alfanumerico 16x4
LEDs
Quantity
8
• ON/fail (green)
1
• Start (yellow)
1
• Trip (red)
1
• Freely allocatable (red)
5
Keyboard
8 keys
3.5
COMMUNICATION INTERFACES
� Local port
Connection
USB Type B
Protocol
Modbus RTU®
� Remote ports
RS485
• Connection
screw terminals
• Baud rate
1200...57600 bps
• Protocol
ModBus®RTU
IEC 60870-5-103
DNP3
Ethernet 100BaseT
• Connection
Optical fiber 1300 nm, ST
100 Base TX, RJ45
• Baud rate
100 Mbps
• Protocol
ModBus®TCP/IP
NA30 - Manual - 04 - 2022
3.6
GENERAL SETTINGS
Relay nominal frequency (fn)
50, 60 Hz
Relay phase nominal current (In)
1 A or 5 A [1]
Phase CT primary nominal current (Inp)
1 A...10 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...10000 A (step 100 A)
Relay residual nominal current (IEn)
1 A o 5 A [1]
Residual CT primary nominal current (IEnp)
1 A...10 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...10000 A (step 100 A)
Relay residual nominal voltage (UEn)
50...130 V (step 1 V)
Residual primary nominal voltage (phase-to-phase) ∙√3 (UEnp) 50 V...500 kV
50...499 V (step 1 V)
500...4990 V (step 10 V)
5000...49900 V (step 100 V)
50000...500000 V (step 1000 V)
3.7
PROTECTIVE FUNCTIONS
� Base current - IB[2]
Base current (IB)
0.10...2.50 In (step 0.01 In)
� Thermal protection with Pt100 probes - 26[3]
ThAL1...8 Alarm:
Alarm threshold 26 PT1...PT8 (ThAL1...8)
0...200 °C
Operating time ThAL1...8 (tThAL1...8)
0....100 s
Th>1...8 Trip:
Trip threshold 26 PT1...PT8 (Th>1...8)
0...200 °C
Operating time ThAL1...8 (tTh>1...8)
0....100 s
� Thermal image - 49
Common configuration:
Initial thermal image DqIN (DthIN)
0.0...1.0 DqB (step 0.1 DqB)[4]
Reduction factor at inrush (KINR)
1.0...3.0 (step 0.1)
Thermal time constant t (T)
1...200 min (step 1 min)
DthCLP activation time (tDthCLP)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
DthAL1 Element
49 First alarm threshold (DthAL1)
0.3...1.0 DqB (step 0.1 DqB)
DthAL2 Element
49 Second alarm threshold (DthAL2)
0.5...1.2 DqB (step 0.1 DqB)
Dth> Element
49 Trip threshold (Dth>)
1.100...1.300 DqB (step 0.001 DqB)
Pickup accuracy
± 1% with 0.1 In, ± 1% with 1 In
Operate time accuracy
5% or ± 10 ms
� Phase overcurrent - 50/51
I> Element
I> Curve type (I>Curve)
DEFINITE
IEC/BS A, B, C
ANSI/IEEE MI, VI, EI
RECTIFIER, I2t or EM
I CLP> Activation time (tCLP>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I> Reset time delay (t>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Note 1 The nominal current settings doesn’t concern the protection elements; they must agree with hardware setting (dip-switch 1 A or 5 A) .
Note 2 The basic current IB represents the nominal current of the line or transformer, referred to the nominal current of the CT’s for thermal image
protection. If the secondary rated current of the line CT’s equals the rated current of the NA30 relay, as usually happens, the IB value is the ratio
between the rated current of the protected element and the primary rated current of the CT’s
Note 3 The 26 element is available when the MPT module is connect on Thybus and enabled
Note 4 Dq is the thermal image (p.u. of the basic over temperature corresponding to the basic current IB).
Assuming that the secondary rated current of the line CT’s equals the rated current of the NA30 relay, as usually happens, the IB value is the
ratio between the rated current of the protected element and the primary rated current of the CT’s
NA30 - Manual - 04 - 2022
Definite time
50/51 First threshold definite time (I>def)
0.100...40.0 In
0.100...0.999 In (step 0.001 In)
1.00...9.99 In (step 0.01 In)
10.0...40.0 In (step 0.1 In)
I>def within CLP (ICLP>def)
0.100...40.0 In
0.100...0.999 In (step 0.001 In)
1.00...9.99 In (step 0.01 In)
10.0...40.0 In (step 0.1 In)
I>def Operating time (t>def)
0.04...200.00 s
0.04...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Inverse time[1]
50/51 First threshold inverse time (I>inv)
0.100...20.00 In
0.100...0.999 In (step 0.001 In)
1.00...20.00 In (step 0.01 In)
I>inv within CLP (ICLP>inv)
0.100...20.00 In
0.100...0.999 In (step 0.001 In)
1.00...20.00 In (step 0.01 In)
I>inv Operating time (t>inv)
0.02...60.0 s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
I>> Element
I>> Curve type (I>>Curve)
DEFINITE or I2t
I CLP>> Activation time (tCLP>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I>> Reset time delay (t>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50/51 Second threshold definite time (I>>def)
0.100...40.00 In
0.100...0.999 In (step 0.001 In)
1.00...9.99 In (step 0.01 In)
10.0...40.0 In (step 0.1 In)
I>>def within CLP (ICLP>>def)
0.100...40.00 In
0.100...0.999 In (step 0.001 In)
1.00...9.99 In (step 0.01 In)
10.0...40.0 In (step 0.1 In)
I>>def Operating time (t>>def)
0.03...10.00 s (step 0.01 s)
Inverse time
50/51 Second threshold inverse time (I>>inv)
0.100...20.00 In
0.100...0.999 In (step 0.001 In)
1.00...20.00 In (step 0.01 In)
I>>inv within CLP (ICLP>>inv)
0.100...20.00 In
0.100...0.999 In (step 0.001 In)
1.00...20.00 In (step 0.01 In)
I>>inv Operating time (t>>inv)
0.03...10.00 s (step 0.01 s)
I>>> Element
I CLP>>> Activation time (tCLP>>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I>>> Reset time delay (t>>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50/51 Third threshold definite time (I>>>def)
0.100...40.00 In
0.100...0.999 In (step 0.001 In)
1.00...9.99 In (step 0.01 In)
10.0...40.0 In (step 0.1 In)
Note 1 Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · t>inv / [(I/I>inv)0.02 - 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · t>inv / [(I/I>inv) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 · t>inv / [(I/I>inv)2 - 1]
Moderately Inverse (ANSI/IEEE type MI):
t = t>inv · {0.01 / [(I/I>inv)0.02 - 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t = t>inv · {3.922 / [(I/I>inv)2 - 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t = t>inv · {5.64 / [(I/I>inv)2 - 1] + 0.024}
I-squared-t (I 2t = K):
t = 16 · t>inv / (I/I>inv)2
Electromechanical (EM):
t = 0.28 · t>inv / [-0.236 · (I/I>inv)-1+ 0.339]
RECTIFIER (RI):
t = 2351 · t>inv / [(I/I>inv)5.6- 1]
t:
operate time
I>inv: pickup value
t>inv: operate time setting
Asymptotic reference value: 1.1 I>nv
Minimum operate time:
0.1 s
Equation is valid for 1.1 ≤ I/I>inv ≤ 20, with I>inv pickup ≥ 2.5 In, the upper limit is 50 In
NA30 - Manual - 04 - 2022
I>>>def within CLP (ICLP>>>def)
0.100...40.00 In
0.100...0.999 In (step 0.001 In)
1.00...9.99 In (step 0.01 In)
10.0...40.0 In (step 0.1 In)
I>>>def Operating time (t>>>def)
0.03...10.00 s (step 0.01 s)
Pickup time
≤ 0.03 s
Dropout ratio
0.95...0.98
Dropout time
≤ 0.05 s
Overshoot time
0.03 s
Pickup accuracy
± 0.5% with 0.1 In, ± 0.2% with 1 In
Operate time accuracy
5% or ± 10 ms
� Residual overcurrent - 50N/51N
IE> Element
IE> Curve type (IE>Curve)
DEFINITE
IEC/BS A, B, C
ANSI/IEEE MI, VI, EI - EM
IECLP> Activation time (tECLP>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IE> Reset time delay (tE>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50N/51N First threshold definite time (IE>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IE>def within CLP (IECLP>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 In (step 0.01 IEn)
IE>def Operating time (tE>def)
0.04...200 s
0.04...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Inverse time[1]
50N/51N First threshold inverse time (IE>inv)
0.010...2.00 IEn
0.010...0.999 IEn (step 0.001 IEn)
1.00...2.00 IEn (step 0.01 IEn)
IE>inv within CLP (IECLP>inv)
0.010...2.00 IEn
0.010...0.999 IEn (step 0.001 IEn)
1.00...2.00 IEn (step 0.01 IEn)
IE>inv Operating time (tE>inv)
0.02...60.0 s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
IE>> Element
IECLP>> Activation time (tECLP>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IE>> Reset time delay (tE>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50N/51N Second threshold definite time (IE>>def
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IE>>def within CLP (IECLP>>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IE>>def Operating time (tE>>def)
0.03...10.00 s (step 0.01 s)
Note 1 Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · tE>inv / [(IE/ IE>inv)0.02 - 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · tE>inv / [(IE/IE>inv) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 · tE>inv / [(IE/IE>inv)2 - 1]
Moderately Inverse (ANSI/IEEE type MI):
t = tE>inv · {0.01 / [(IE/IE>inv)0.02 - 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t = tE>inv · {3.922 / [(IE/IE>inv)2 - 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t = tE>inv · {5.64 / [(IE/IE>inv)2 - 1] + 0.024}
Electromechanical (EM):
t = 0.28 · tE>inv / [-0.236 · (IE/IE>inv)-1+ 0.339]
IE:
residual current input
t:
operate time
IE>inv: pickup value
tE>inv: operate time setting
Asymptotic reference value: 1.1 IE>
Minimum operate time:
0.1 s
Equation is valid for 1.1 ≤ IE/ IE>inv ≤ 20
With IE>inv pickup ≥ 0.5 IEn, the upper limit is 10 IEn
NA30 - Manual - 04 - 2022
IE>>> Element
IECLP>>> Activation time (tECLP>>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IE>>> Reset time delay (tE>>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50N/51N Third threshold definite time (IE>>>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IE>>>def within CLP (IECLP>>>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IE>>>def Operating time (tE>>>def)
0.03...10.00 s (step 0.01 s)
Pickup time
≤ 0.03 s
Dropout ratio
0.95...0.98
Dropout time
≤ 0.05 s
Overshoot time
0.03 s
Pickup accuracy
± 0.5% with 0.01 IEn, ± 0.2% with 1 IEn
Operate time accuracy
5% or ± 10 ms
� Residual overvoltage - 59N
Common configuration:
59N Operation from 74VT external (74VText59N)
ON/OFF
UE> Element
U> Curve type (U>Curve)
DEFINITE/INVERSE[1]
UE> Reset time delay (tUE>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
59N First threshold definite time (UE>def)
0.01...0.70 UEn (step 0.01 UEn)
UE>def Operating time (tUE>def)
0.07...100.0 s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59N First threshold inverse time (UE>inv)
0.01...0.50 UEn (step 0.01 UEn)
UE>inv Operating time (tUE>inv)
0.10...100.0 s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
UE>> Element
UE>> Reset time delay (tUE>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
59N Second threshold definite time (UE>>def)
0.01...0.70 UEn (step 0.01 UEn)
UE>>def Operating time (tUE>>def)
0.07...100.0 s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤ 0.03 s
Dropout ratio
0.95...0.98
Dropout time
≤ 0.04 s
Overshoot time
0.03 s
Pickup accuracy
± 4% ± 1% UEn
Operate time accuracy
5% or ± 10 ms
� Directional earth fault overcurrent - 67N
Common configuration:
67N Operating mode (Mode67N)
I/I∙cos
67N Multiplier of threshold for insensitive zone (M)
1.5...10.0 (step 0.1)
67N Operation from 74VT external (74VText67N)
OFF/Block/Not directional
IED> Element
IED> Curve type (IED>Curve)
DEFINITE
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
Note 1 The mathematical formula for INVERSE curve is t= (0.5 ∙ tUE>inv) / [(UE/UE>inv) - 1]
t:
operating time (in seconds)
tUE>inv: operating time setting (referred to UE/UE>inv = 1.5 )
UE:
residual input voltage (direct or calculated)
UE>inv: threshold setting
Asymptotic reference value: 1.1UE>inv
Minimum operate time:
0.1 s
Equation is valid for 1.1 ≤ UE/UE>inv ≤ 4
NA30 - Manual - 04 - 2022
IEDCLP> Activation time (tEDCLP>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IED> Reset time delay (tED>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
67N First threshold definite time (IED>def - UED>def)
Residual current pickup value
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
Residual voltage pickup value
0.004...0.500 UEn (step 0.001 UEn)
Characteristic angle
0...359° (step 1°)
Half operating sector
1...180° (step 1°)
IED>def within CLP (IEDCLP>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IED>def Operating time (tED>def)
0.05...200 s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Inverse time[1]
67N First threshold inverse time (IED>inv - UED>inv)
Residual current pickup value
0.002...2.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...2.00 IEn (step 0.01 IEn)
Residual voltage pickup value
0.004...0.500 UEn (step 0.001 UEn)
Characteristic angle
0...359° (step 1°)
Half operating sector
1...180° (step 1°)
IED>inv within CLP (IEDCLP>inv)
0.002...2.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...2.00 IEn (step 0.01 IEn)
IED>inv Operating time (tED>inv)
0.02...60.0 s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
IED>> Element
IED>> Curve type (IED>>Curve)
DEFINITE
IEC/BS A, B, C
ANSI/IEEE MI, VI, EI, EM
IEDCLP>> Activation time (tEDCLP>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IED>> Reset time delay (tED>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
67N Second threshold definite time (IED>>def - UED>>def)
Residual current pickup value
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
Residual voltage pickup value
0.004...0.500 UEn (step 0.001 UEn)
Characteristic angle
0...359° (step 1°)
Half operating sector
1...180° (step 1°)
IED>>def within CLP (IEDCLP>>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IED>>def Operating time (tED>>def)
0.05...10.00 s (step 0.01 s)
Note 1
Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · tED>inv / [(IE/IED>inv)0.02 - 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · tED> inv / [(IE/IED>inv) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 · tED>inv / [(IE/IED>inv)2 - 1]
Moderately Inverse (ANSI/IEEE type MI):
t = tED>inv · {0.01 / [(IE/IED>inv)0.02 - 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t = tED>inv · {3.922 / [(IE/IED>inv)2 - 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t = tED>inv · {5.64 / [(IE/IED>inv)2 - 1] + 0.024}
Electromechanical (EM):
t = 0.28 · tED>inv / [-0.236 · (IE/IED>inv)-1+ 0.339]
t: operate time
IED>inv: pickup value
tED>inv: operate time setting
Asymptotic reference value: 1.1 IED>inv
Minimum operate time:
0.1 s
Equation is valid for 1.1 ≤ IE/IED>inv ≤ 20
With IED>inv pickup ≥ 0.5 In, the upper limit is 10 IEn
NA30 - Manual - 04 - 2022
Inverse time[1]
67N Second threshold inverse time (IED>>inv - UED>>inv)
Residual current pickup value
0.002...2.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...2.00 IEn (step 0.01 IEn)
Residual voltage pickup value
0.004...0.500 UEn (step 0.001 UEn)
Characteristic angle
0...359° (step 1°)
Half operating sector
1...180° (step 1°)
IED>inv within CLP (IEDCLP>>inv)
0.002...2.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...2.00 IEn (step 0.01 IEn)
IED>>inv Operating time (tED>>inv)
0.02...10.00 s (step 0.01 s)
IED>>> Element
IEDCLP>>> Activation time (tEDCLP>>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IED>>> Reset time delay (tED>>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
67N Third threshold definite time (IED>>>def - UED>>>def)
Residual current pickup value
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
Residual voltage pickup value
0.004...0.500 UEn (step 0.001 UEn)
Characteristic angle
0...359° (step 1°)
Half operating sector
1...180° (step 1°)
IED>>>def within CLP (IEDCLP>>>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IED>>>def Operating time (tED>>>def)
0.05...10.00 s (step 0.01 s)
IED>>>> Element
IEDCLP>>>> Activation time (tEDCLP>>>>)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
IED>>>> Reset time delay (tED>>>>RES)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
67N Fourth threshold definite time (IED>>>>def - UED>>>>def)
Residual current pickup value
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
Residual voltage pickup value
0.004...0.500 UEn (step 0.001 UEn)
Characteristic angle
0...359° (step 1°)
Half operating sector
1...180° (step 1°)
IED>>>>def within CLP (IEDCLP>>>>def)
0.002...10.00 IEn
0.002...0.999 IEn (step 0.001 IEn)
1.00...10.00 IEn (step 0.01 IEn)
IED>>>>def Operating time (tED>>>>def)
0.05...10.00 s (step 0.01 s)
Pickup time
≤ 0.03 s
Dropout ratio
0.95...0.98
Dropout time
≤ 0.05 s
Overshoot time
0.03 s
Pickup accuracy (current thresholds)
± 1% with 0.1 In, ± 0.5% with 1 In
Pickup accuracy (voltage thresholds)
± 0.3% with 0.1Un, ± 0.1% with 1Un
Pickup accuracy (displacements)
± 2° with 0.1 In - 0.1Un
± 0.5° with 1In - 1 Un
Operate time accuracy
5% or ± 10 ms
Note 1 Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · tED>inv / [(IE/IED>inv)0.02 - 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · tED> inv / [(IE/IED>inv) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 · tED>inv / [(IE/IED>inv)2 - 1]
Moderately Inverse (ANSI/IEEE type MI):
t = tED>inv · {0.01 / [(IE/IED>inv)0.02 - 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t = tED>inv · {3.922 / [(IE/IED>inv)2 - 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t = tED>inv · {5.64 / [(IE/IED>inv)2 - 1] + 0.024}
Electromechanical (EM):
t = 0.28 · tED>inv / [-0.236 · (IE/IED>inv)-1+ 0.339]
t: operate time
IED>inv: pickup value
tED>inv: operate time setting
Asymptotic reference value: 1.1 IED>inv
Minimum operate time:
0.1 s
Equation is valid for 1.1 ≤ IE/IED>inv ≤ 20
With IED>inv pickup ≥ 0.5 In, the upper limit is 10 IEn
NA30 - Manual - 04 - 2022
� Breaker failure - BF
BF Phase current threshold (IBF>)
0.05...1.00 In (step 0.01 In)
BF Residual current threshold (IEBF>)
0.01...2.00 In (step 0.01 IEn)
BF Time delay(tBF)
0.06...10.00 s (step 0.01 s)
Dropout ratio
0.95...0.98
Dropout time
≤ 0.05 s
IBF>Pickup accuracy
± 0.5% con 0.1 InL
± 0.2% con 1 InL
IEBF>Pickup accuracy
± 0.5% con 0.01 IEn
± 0.2% con 1 IEn
Operate time accuracy
5% or ± 10 ms
NA30 - Manual - 04 - 2022
3.8
CONTROL AND MONITORING
� Second harmonic restraint - 2ndh-REST
Second harmonic restraint threshold (I2ndh>)
10...50 % (step 1 %)
I2ndh> reset time delay (t2ndh>RES)
0...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup accuracy I2ndh>
± 4% ± 1% In
Operate time accuracy
5% or ± 10 ms
� Trip Circuit Supervision - 74TCS
Operate time:
• One binary input supervision
40 s
• Two binary inputs supervision
2 s
Reset time delay:
• One binary input supervision
6 s
• Two binary inputs supervision
0.6 s
� Selective block - BLOCK2
Selective block IN:
• BLIN1 Selective block operating mode (ModeBLIN1)
OFF-ON IPh/IE-ON IPh-ON IE
• BLIN maximum activation time for phase protections (tB-IPh) 0.10...10.00 s (step 0.01 s)
• BLIN maximum activation time for ground protections (tB-IE) 0.10...10.00 s (step 0.01 s)
Selective block OUT:
• BLOUT1 Selective block operating mode (ModeBLOUT1)
OFF-ON IPh/IE-ON IPh-ON IE
• BLOUT Dropout time for phase protections (tF-IPh)
0.00...1.00 s (step 0.01 s)
• BLOUT Dropout time for ground protections (tF-IE)
0.00...1.00 s (step 0.01 s)
• BLOUT Dropout time for ground and phase protections (tF-IPh/IE) 0.00...1.00 s (step 0.01 s)
� Internal selective block - BLOCK4
Output internal selective block dropout time for phase protections (tFI-IPh)
0.00...10.00 s (step 0.01 s)
Output internal selective block dropout time for ground protections (tFI-IE)
0.00...10.00 s (step 0.01 s)
� Circuit Breaker supervision
Circuit breaker diagnostic
Number of CB trips threshold (N.Open)
0...10000 (step 1)
Cumulative CB tripping currents threshold (SumI)
0....5000 In (step 1 In)
Cumulative CB tripping I2t threshold (SumI^2t)
0....5000 (In)2∙s (step 1 In2∙s)
Circuit Breaker opening time for I^2t calculation (tbreak)
0.05...1.00 s (step 0.01 s)
Circuit Breaker maximum allowed opening time (tbreak>)
0.05...1.00 s (step 0.01 s)
� CT supervision - 74CT
74CT Threshold (S<)
0.10...0.95 (step 0.01)
74CT Overcurrent threshold (I*)
0.10...1.00 In (step 0.01 In)
S< Operating time delay (tS<)
0.03...200 s
0.03...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Dropout ratio for the I* pickup
0.95...0.98
Dropout time
≤ 0.05 s
Pickup accuracy S<
± 1% with 0.1 In , ± 0.5% with 1 In
Pickup accuracy I*
± 0.5% with 0.1 In , ± 0.2% with 1 In
Operate time accuracy
5% or ± 10 ms
� Pilot wire diagnostic
• BLOUT1 Diagnostic pulse period (PulseBLOUT1)
OFF-0.1-1-5-10-60-120 s
• BLIN1 Diagnostic pulse control time interval (PulseBLIN1)
OFF-0.1-1-5-10-60-120 s
� Demand measures
• Fix on demand period (tFIX)
1...60 min (step 1 min)
• Rolling on demand period (tROL)
1...60 min (step 1 min)
• Number of cycles for rolling on demand (N.ROL)
1...24 (step 1)
NA30 - Manual - 04 - 2022
� Oscillography (DFR))[1]
Format
COMTRADE
Recording mode
circular
Sampling rate
24 samples / cycle
Trigger setup:
• Pre-trigger time
0.05...1.00 s (step 0.01 s)
• Post-trigger time
0.05...60.00 s (step 0.05 s)
Set sample channels:
iL1, iL2, iL3, iE, uE
Set analog channels:
Analog 1...Analog 12
Frequency,IL1, IL2, IL3, IE, PhiE,
IL1-2nd, IL2-2nd, IL3-2nd, I-2nd /IL
T1...T8[2]
Set digital channels:
Digital 1...Digital 12
K1... K6, K7...K10,
IN1, IN2, IN3...IN42[3]
� PLC (Programmable Logic Controller)[4]
Reference standard
IEC 61131-3
Language[5]
IL (Instruction List)
Inputs:
Binary inputs
IN1, IN2 on board
IN8...IN10 with MRI module
IN11...IN26 with one MID16 module
IN27...IN42 with two MID16 modules
Delayed binary inputsi[6]
IN1, IN2 on board
IN8...IN10 with MRI module
IN11...IN26 with one MID16 module
IN27...IN42 with two MID16 modules
Start (all elements)
Start I>, Start I>>,...etc
Trip (all elements)
Trip I>, Trip I>>,...etc
Measures
IL1, IL2,...ecc
Temperature
Pt100
Block inputs
BLK2IN-Iph, BLK2IN-IE,...etc
Outputs:
Relays
K11...K6 on board
K7...K10 with MRI module
LEDs
START, TRIP, L1...L6 on board
L7...L10 with MRI module
Block outputs
BLK2OUT-Iph, BLK2OUT-IE,...etc
Current converter
DAC
Note 1 For the DFR function a licence is required; call Thytronic for purchasing.
Note 2 The measures of temperature are available only when the MPT module on Thybus is enabled (eigth Pt100 inputs)
Note 3 Output relay K7...K10 and binary input IN3...IN42 states are available only when the concerning I/O circuits are implemented (MRI and MID16
modules on Thybus)
Note 4 For the PLC function a licence is required; call Thytronic for purchasing.
Note5 With ThyVisor V3.4.3 release and compiler IEC 61131-3 V1.2.7 only the IL language is implemented (Instruction List);
other languages, according with IEC 61131 standard (ST (Structured Text)), LD (Ladder Diagram), FBD (Function Block Diagram), SFC (Sequential
Functional Chart), will be available soon
Note 6 The input state is acquired downstream the tON and tOFF timers
NA30 - Manual - 04 - 2022
3.9
METERING
More data are available inside Section 5 - MEASURES, LOGIC STATES AND COUNTERS
� Accuracy (type tests)
MEASURE
Reference values
Accuracy
Reference values
Accuracy
Phase current
0.1 In
0.2%
1 In
0.03%
Measured residual current
0.01 IEn
0.3%
1 IEn
0.02%
Measured residual voltage
0.01 UEn
0.02%
0.1 UEn
0.02%
Frequency
0.02 Un
3 mHz
1 Un
2 mHz
Phase
0.002 IEn - 0.004 UEn
1.5°
0.005 IEn - 0.01 UEn - 0.1 IEn - 0.5 UEn
0.2°
Positive/Negative sequence current
I1 = 0.5 In
0.5%
I1 = 1 In
0.5%
Pickup and operate time
1.5 x setting for fist element
5% ± 10 ms
2.5 x setting for other elements
5% ± 10 ms
� Measures
Direct
Frequency
(f )
RMS value of fundamental component for phase currents
(IL1, IL2, IL3)
RMS value of fundamental component for residual current
(IE)
RMS value of fundamental component for residual voltage
(UE)
Calculated
Thermal image
(DTheta)
Maximum current between IL1-IL2-IL3
(ILmax)
Minimum current between IL1-IL2-IL3
(ILmin)
Average current between IL1-IL2-IL3
(IL)
Sequence
Positive sequence current
(I1)
Negative sequence current
(I2)
Negative sequence current/positive sequence current ratio (I2/I1)
2nd harmonic
Second harmonic phase currents
(IL1-2nd, IL2-2nd, IL3-2nd)
Maximum of the second harmonic phase currents/
fundamental component percentage ratio I-2nd /IL
(I-2nd /IL)
3rd harmonic
Third harmonic phase currents
(IL1-3rd, IL2-3rd, IL3-3rd)
Third harmonic of residual current
(IE-3rd)
Third harmonic of residual voltage
(UE-3rd)
4th harmonic
Fourth harmonic phase currents
(IL1-4th, IL2-4th, IL3-4th)
5th harmonic
Fifth harmonic phase currents
(IL1-5th, IL2-5th, IL3-5th)
Demand phase
Phase fixed currents demand
(IL1FIX, IL2FIX, IL3FIX)
Phase rolling currents demand
(IL1ROL, IL2ROL, IL3ROL)
Phase peak currents demand
(IL1MAX, IL2MAX, IL3MAX)
Phase minimum currents demand
(IL1MIN, IL2MIN, IL3MIN)
PT100 [1]
Temperature PT1
(T1)
Temperature PT2
(T2)
Temperature PT3
(T3)
Temperature PT4
(T4)
Temperature PT5
(T5)
Temperature PT6
(T6)
Temperature PT7
(T7)
Temperature PT8
(T8)
Note 1 The measures of temperature are available only when the MPT module on Thybus is enabled (eigth Pt100 inputs)
NA30 - Manual - 04 - 2022
4 F U N C T I O N C H A R A C T E R I S T I C S
4 F U N C T I O N C H A R A C T E R I S T I C S
4.1
HARDWARE DESCRIPTION
The following figure illustrates the basic structure of the relay
hw.ai
RTC
EEprom
Flash
SRam
SRam
SPI
CPU
ETHERNET
CPU BOARD
POWER SUPPLY BOARD
INPUT MODULE
DSP
DUAL
PORT
1A/5A
≈
≈
≈
≈
EEprom
Thybus
RS485
RELAYS
K1...K6
Output contacts
USB
MMI
LCD
LEDs
BINARY INPUTS
IN1
Input
IN2
IN3
IN4
IN4
BLOCK I/O
BLKIN
Input
BLKOUT
POWER SUPPLY
+5 V
+10 V
0 V
+24 V
-10 V
POWER FAIL
RESET
Uaux
NA30 - Manual - 04 - 2022
Printed boards hold the circuit components arranged according to a modular allocation of the main
functions.
Power supply board
All the components necessary for conversion and stabilization functions are present.
Two versions are envisaged suited to the input ranges 24...48 V and 115...230 V.
The circuit provides stabilized voltages of +10 V and -10 V, required for the analogue measurement,
+24 V for relays and +5 V for supplying the digital circuits.
The circuit board additionally comprises:
INPUT CIRCUITS:
• Five binary input circuits,
• One block input circuit (BLIN1).
The logical input circuits and the block circuits include photo-couplers which provide for galvanic
separation.
OUTPUT CIRCUITS:
• One block output circuit (BLOUT 1),
• Six output relays (k1...K6).
CPU board
This circuit board contains all the circuits necessary for performing the analogue and digital pro-
cessing of the signals.
Analog processing
The following are envisaged:
• Anti aliasing filter circuits,
• Amplifier circuits for conditioning the input signals,
• Reference voltage adjustment circuits for the measurement A/D converter.
The Pro-n relays use a DSP processor operating at 40 MHz; it performs all the processing on the
analogue signals and furthermore coordinates management of the TX-RX signals to the CPU.
The input currents are sampled at a frequency of 24 samples per period by means of a dual conver-
sion system which allows the attainment of information pertaining to polarity and amplitude with high
resolution. The measurement criterion allows precise measurement of even those signals having a
unidirectional component, such as transient currents with overlapping exponential, which typically
appear during faults.
The circuit board also houses the output relays with the corresponding command and control cir-
cuits, communication circuits, buttons, LCD display, LEDs and the key switch.
CPU
A 32 bit CPU is provided.
The following are envisaged:
• Real Time Clock circuits with oscillator and super capacitor,
• USB communication port,
• RS485 communication port,
• Thybus communication circuits for external modules and MMI board,
• Network communication circuits (optional Ethernet).
Memories:
• SRam: high speed static memory, used for data and cache,
• Flash memory: used for fw storage and upgrade,
• EEprom memory: used for calibration data storage,
• Dual port Ram for data transfer between CPU and DSP.
Input board
• Three CTs committed for phase currents acquisition,
• One CT committed for residual current acquisition.
The input circuits are suitable for 1 A or 5 A external CTs.[1]
• Three VTs committed for phase voltages acquisition,
• One VT committed for residual voltage acquisition.
MMI (keyboard, LED and display)
The MMI module (Man Machine Interface) includes:
• An eight keys 8 keyboard,
• a backlight LCD display,
• Eight signalling LEDs,
The removable plug allows separation of the MMI module for free access to the CPU board when
DIP-switch setting is required.
Note 1 The phase and residual nominal currents must be adjusted by means dip-switch.
NA30 - Manual - 04 - 2022
4.2
SOFTWARE DESCRIPTION
The program which handles operation of the Pro-N relays is made up of three fundamental elements
shown in the following block diagram.
Base software
Single modules are application independent with modular and scalable structure.
The system can be assimilated to the PC BIOS (Basic Input-Output System); three main function are
provided:
• Start-up test execution;
• RAM loading of the operating system;
• Provide a suitable interface to access the relay hardware.
Real-time operating system
An embedded operative system is employed suitable for real-time applications (RTOS).
A multithread preemptive structure is able to menage several task with multiple priority levels .
The kernel represents the nucleus of the system: it includes the processing functions closest to the
electronic circuits.
In addition, the kernel manages a service communication protocol known as Basic Protocol (BP).
Task
The task (process e thread) are the base components.
Example are:
• Keyboard management
• RTC (Real Time Clock) updating
• RAM/EEPROM updating
• Diagnostic
• Input acquisition
• Output relay management
• MMI
• I/O updating
• DSP data processing
sw.ai
KEYS
PC com
Sync
Binary inputs
Output relays
LEDs
Fast devices
EEPROM
Slow devices
RTC refresh
EEPROM
update
Diagnostic
DSP
MMI
task
Oscillography
Measures
Drivers
sampling
RTOS timer
SIMBOLOGIA
Processo (task)
Libreria funzionale (Drivers)
Timer del sistema operativo
Interrupt
RTOS timer
I/O
I/O boards
KEYS
RTOS timer
RAM/EPROM
memory check
RTOS timer
RTOS timer
DATA BASE
TIMER
Ethernet
USB
RS485
Counters
Events
Data Base
Messages
Thybus
+
NA30 - Manual - 04 - 2022
DSP Firmware
By means of Discrete Fourier Transform calculation, based on 24 samples/period, information is de-
duced in relation to the amplitude and phase of all the current measurements; these are constantly
updated and at the disposal of all the protection and control application algorithms.
Drivers
Inside the driver library, all the specialized module for protection and control function are provided.
They are the link from kernel and application layer. Examples are:
• Data base management
• PC messages management
• TCP/IP messages management
• Basic Protocol management
• Counter management
• Event and fault management
• Measuring management
• Oscillography management
Application Software
The software acts the specialization of the base system; all protective and control elements are
inside it.
The main modules ate:
• Diagnostic function for application layer,
• Input management (binary inputs),
• Protective functions,
• Event recording,
• Output management (LEDs and relays)
Each element (Kernel, Drivers and Application) may, in turn, be split into modules:
Base protocol (kernel)
The module known as the Basic Protocol (BP) manages the service communication between the
kernel and the other modules through the communication buses with the following services:
• Data and information exchange,
• Calibration,
• Upgrade fw DSP,
• Upgrade application sw
Communication (drivers)
The ModBus TCP/IP protocol, with ethernet interface, the ModBus RTU, IEC 60870-5-103 and DNP3
protocol over RS485 interface and the ModBus RTU USB for ThyVisor are provided.
MMI (drivers)
The drivers deal with the menu management (MMi and/or communication messages).
Data Base
The data base is split into three main sections:
• RAM for volatile data,
• REE and PAR for non volatile data.
Self test (Application)
The main hw and sw function are permanently verified in background; no additional delay are intro-
duced.
In particular the following function are tested:
• Reference voltages;
• Output relays;
• Sw flow with execution time monitoring;
• REE and PAR data congruence.
Development tools (Builder)
For the development of the project, a CASE instrument has been developed, responsible for the opti-
mized production of software code for the management of collaboration, the database and the MMI
data and the Xml files used for communication. The automatic code generation criteria ensures the
quality of the result in terms of the reusability, verifiability and maintainability of the software life
cycle.
NA30 - Manual - 04 - 2022
4.3
I/O DESCRIPTION
Metering inputs
The following input are provided:
• Three phase current inputs.
• One residual current input.
• The nominal currents are independently adjustable at 1 A or 5 A through DIP-switches.
• One residual voltage input, with programmable nominal voltage within range 50...130 V (UER=100 V).
The input circuits are appropriately dimensioned in order to withstand the currents which arise
when a fault occurs, both in transient and steady state condition.
Signal processing
Various processing levels are involved:
• Acquisition (base level).
• Direct measures of physical channels (first level).
• Calculated measures (second level).
• Derived (third level).
The measures concerning a level are based on data worked out in the previous level.
For each level the required resources concerning the priority for tasks (conditioning circuits, DSP
and CPU) are on hand.
ACQUISITION (base level)
The input signals are sampled 24 times per period:
- iL1...iL3
Phase current instantaneous values
- iE
Residual current instantaneous value
- uE
Residual voltage instantaneous value
From the sampled quantities, several measures are computed for protection, monitoring and meter-
ing purposes.
sensori.ai
NA30
3 ingressi correnti di fase
1 ingresso di corrente residua
1 ingresso di tensione residua
acquisizione.ai
ACQUISITION
INSTANTANEOUS MEASURES
≈
NA30 - Manual - 04 - 2022
• Direct
• Calculated
• Phase
• Sequence
• Harmonic
• Demand
Direct
• Frequency. The measure of period is taken on the input phase currents.
Samples are processed by means DFT (Discrete Fourier Transform) algorithm and the phase and
amplitude of fundamental are computed:
• Phase currents IL1, IL2, IL3
• Residual current IE
• Residual voltage UE
Calculated
By means vector addition of direct measures the following are calculated (RMS value of fundamen-
tal components):
• Thermal image ∆θ
F.ai
(Hz)
ACQUISITION
IL1
IL2
CT
IL3
iL1
iL2
≈
≈
iL3
≈
f
T
IL1.ai
(In)
ACQUISITION
iL1, iL2, iL3
DFT
CT
≈
IL1, IL2, IL3
IE.ai
(IEn)
ACQUISITION
iE
DFT
CT
≈
IE
UE.ai
(UEn)
(UEn)
ACQUISITION
uE
DFT (fundamental)
VT
≈
UE
DFT (3rd harmonic)
UE3H
Theta.ai
IL1
I2
I2 = (IL1+ e-j120°IL2+ e+j120°IL3)
I1 = (IL1+ e+j120°IL2+ e-j120°IL3)
IL3
IL2
I1
Ith = √(I12+ K22∙I22)
∆θ
(∆θB)
2
d∆θ
dt
IB
Ith
∆θ
T+
T+
( )
+
=
NA30 - Manual - 04 - 2022
Phase
• Displacement angle of the residual current respect the corresponding measured residual voltage
(positive with current in lagging direction in respect to voltage): PhiE,
Sequence
• Fundamental RMS positive sequence current: I1
• Fundamental RMS negative sequence current: I2
Demand
• Fixed demand (IL1FIX, IL2FIX, IL3FIX, ±PFIX, ±QFIX)
Inside an adjustable time interval tFIX, an average magnitude is calculated for phase currents IL1, IL2,
IL3, active power ±P and reactive power ±Q of measures taken every second. The average values are
stored at the end of the same time interval.
• Rolling demand (IL1ROL, IL2ROL, IL3ROL, ±PROL, ±QROL)
Inside an adjustable time interval NROL∙tROL , an average magnitude is calculated for phase currents
IL1, IL2, IL3, active power ±P and reactive power ±Q of measures taken every second, where tROL is
the length of any time subinterval and NROL is the number of the time intervals. The average values
are stored at the end of the same time subinterval.
• Peak (IL1MAX, IL2MAX, IL3MAX, ±PMAX, ±QMAX)
Inside an adjustable time interval tROL, the maximum magnitude is calculated for phase currents IL1,
IL2, IL3, active power ±P and reactive power ±Q of measures taken every second. The average values
are stored at the end of the same time interval tROL (Rolling demand common parameter).
Fase.ai
PhiE
(° )
ϕE = ∠IE - ∠UE
UE
IE
I1-I2.ai
IL1
I2
I2 = (IL1+ e-j120°IL2+ e+j120°IL3) / 3
I1 = (IL1+ e+j120°IL2+ e-j120°IL3) / 3
IL3
IL2
(In)
I1
(In)
e-j120°= -
j √3
1
2
2
-
e+j120°= -
j √3
1
2
2
+
Fix-Demand.ai
1s
IL1FIX, IL2FIX,IL3FIX
tFIX
(In)
IL2
IL1
IL3
ILxFIX
ILxn
tFIX ∙ 60
tFIX ∙ 60
n=1
∑
1
tFIX
tFIX
tFIX
Rol-Demand.ai
Rolling demand example with NROL=4
IL1ROL
IL2ROL
IL3ROL
(In)
IL2
IL1
IL3
0
1
2
3
4
5
1s
tROL tROL
NROL
tROL tROL tROL
6
tROL
Average inside subinterval tROL
ILxROL=
ILxk
tROL∙60
tR OL∙60
k=1
∑
NR OL
n=1
n
∑
1
NROL
1
Max-Demand.ai
Maximum value of averages inside time interval tROL
Average inside time interval tROL
IL1MA X
IL2MA X
IL3MA X
(In)
IL2
IL1
IL3
1s
tROL tROL tROL tROL tROL tROL
ILxMA X= MAX
ILxn
tROL∙60
tR OL∙60
n=1
∑
1
NA30 - Manual - 04 - 2022
• Minimum (IL1MIN, IL2MIN, IL3MIN, ±PMIN, ±QMIN)
Inside an adjustable time interval tROL, the minimum magnitude is calculated for phase currents IL1,
IL2, IL3, active power ±P and reactive power ±Q of measures taken every second. The average values
are stored at the end of the same time interval tROL (Rolling demand common parameter).
Use of over-described measures is shown in the following tables.
Conventions
Phase rotation direction
The conventional rotation direction for the current phasors is counter-clockwise.
Cyclic phase sequence order
For three phase rotating currents, a direct cyclic sequence is defined when the three phases are
L1, L2, L3 ordered, while an inverse cyclic sequence is defined when the three phases are L1, L3, L2
ordered.
Min-Demand.ai
Minimum value of averaged inside time intervaltROL
Average inside time intervaltROL
Reset
IL1MIN
IL2MIN
IL3MIN
(In)
IL2
IL1
IL3
1s
tROL tROL tROL tROL tROL tROL
ILxMIN= MIN
ILxn
tROL∙60
tR OL∙60
n=1
∑
1
fasori.ai
fasori1.ai
UL1
UL3
UL2
UL1
UL2
UL3
Direct sequence cyclic order
Inverse sequence cyclic order
NA30 - Manual - 04 - 2022
Use of measured values
Usage of measured values for protection, control and monitoring
f
iL1, iL2, iL3
IL1, IL2, IL3
IL1-2nd, IL2-2nd, IL3-2nd
iE
IE
I1
I2
uE
UE
Temperature (PT1....PT8)
Binary input INx
START Relay K1...K6
TRIP) Relay K1...K6
START LEDs L1...L5
TRIP LEDs L1...L5
Selective block input BLIN1
Selective block output BLOUT1
Cold Load Pickup (CLP)
Seconda harmonic restraint
Logic block (Block1)
Logic selectivity (Block2)
Internal logic selectivity (Block4)
PROTECTIONS
Thermometric probes - 26
Thermal image - 49
Phase overcurrent - 50/51
Residual overcurrent - 50N/51N
Residual overvoltage - 59N
Directional earth fault overcurrent - 67N
Breaker failure - BF
CONTROL & MONITORING
CT Monitoring (74CT)
Trip Circuit Supervision TCS)
Second harminic restraint - 2NDH-REST
Logic block (Block1)
Selective block (Block2)
Internal Selective block (Block4)
Self-test
Functions state
Counters
Inputs state
Selective block state
Outputs state
MEASURES
Frequency
Phase currents
Residual current
Inverse sequence current
Direct sequence current
Thermal image
Residual voltage
UE - IE Displacement
Temperature (Pt100 with MPT module)
EVENT RECORDER
Event 0
Event 1
Event ...
Event 299
FAULT RECORDER
Fault 0
Fault 1
Fault ...
Fault 19
OSCILLOGRAPY
Record 1
Record 2
Record ...
NA30 - Manual - 04 - 2022
Binary inputs
Two binary inputs are available.
The dry inputs must be powered with an external voltage, (usually the auxiliary power supply).
The connections are shown in the schematic diagrams.
The following settings can be used to configure each input:
• Logic Active-ON (activated when powered), or Active-OFF (activated when power is turned off).
• ON Timer (OFF-to-ON time delay) and OFF Timer (ON-to-OFF time delay).
• Binary input allocation.
Adjustable debounce timer allows any transient to decay avoiding false activation of the input; the
positive transition is acquired if the input is permanently high for a time interval longer than the tON
setting delay; similarly for the negative transitions, the negative transition is acquired if the input is
permanently high for a time interval longer than the tOFF setting delay.
In the above shown diagram, INTERNAL STATE represents the logical state of the binary input used
in the following processing.
Each binary input may be matched to one of the following default functions.
FUNZIONI
Binary inputs
IN1
IN2
IN3
IN4
IN5
Reset LEDs
Set profile (switching setting A and B)
Fault trigger (fault recording)
Block2 IPh/IE (selective block from phase and/or ground elements)
Block2 IPh (selective block from phase elements)
Block2 IE (selective block from ground elements)
Block1 (logic block)
TCS1 (Trip Circuit Supervision)
TCS2 (Trip Circuit Supervision)
Trip ProtExt (trip from external protection relays)
Reset counters
Reset CB Monitor (clear CB monitoring data)
52a (CB auxiliary contact)
52b (CB auxiliary contact)
Open CB
Close CB
Preset DTheta (thermal image preset)
Remote trip
Reset on demand measures
74VT ext. (74VT from external protection relays)
BINARY INPUT
INTERNAL STATE
tON
tON
tOFF
tOFF
t
binary-timers.ai
NA30 - Manual - 04 - 2022
Reset LEDs
If the element tripped have gone back to rest condition, the latched LEDs and/or relays may be
reset.
Set profile
Inside Pro-N devices, two independent setting profiles (A and B) are available. Whereas different
settings are required, they are made in the setting profiles and stored in the non volatile memory of
relay. Applicable setting profile is activated usually via a binary input; when the programmed input is
activated, the profile B becomes operative as a replacement for the default profile A.[1]
Fault trigger
When the programmed input is activated, a trigger is issued for fault record SFR). Data storing takes
place with the same procedure resulting from a trip of any protective elements
Note 1 To enable the profile switching the “Input-selected” parameter must be set inside the “Profile selection” submenu.
If multiple setting groups are not required, Group A is the default selection
Reset-led.ai
TRIPPING MATRIX
(LED+RELAYS)
≥
≥
&
&
Set (ON≡turn on LED/relay)
S
Set-Reset latch
R
Reset (ON≡turn off LED/relay)
Reset LEDs
Binary input allocation for reset signalling (LEDs)
T
0
INx t ON
T
0
n.o.
n.c.
INx tON
Logic
INx tOFF
INx t OFF
Binary input INx (x=1,...5)
Switch-profile.ai
(A, B, from binary input)
OFF≡Profile A, ON≡Profile B
Binary input allocation for switching of setting profiles
Profile A
Profile B
Profile A
Profile selection
Profile B
Set profile
T
0
INx t ON
T
0
n.o.
n.c.
INx tON
Logic
INx tOFF
INx t OFF
Binary input INx (x=1,... 5)
Trigger-faults.ai
Binary input allocation for fault recorder trigger
Fault trigger
T
0
INx t ON
T
0
n.o.
n.c.
INx tON
Logic
INx tOFF
INx t OFF
Binary input INx (x=1,...5)
Fault recording
Protection
element
IL1->IL1r
IL2->IL2r
.....
DTheta->DTheta-r
Inputs
Outputs
Fault cause info
≥1
NA30 - Manual - 04 - 2022
Block2 IPh/IE
A change in status of a binary input effects a block[1] common for the following phase and ground
protective elements:
• I>, I>> and I>>> (50/51),
• DthAL1, DthAL2 and Dth (49),
• IPD>, IPD>>, IPD>>> and IPD>>>> (67),
and ground fault:
• IE>, IE>> and IE>>> (50N/51N),
• IED>, IED>>, IED>>> and IE>>>> (67N),
The application of the IN1 and IN2 binary inputs for the acquisition of Block2 (selective block) com-
ing from external protection relays is shown in the following figure (one phase overcurrent and one
phase and residual overcurrent protection).
Block2 IPh
A change in status of a binary input effects a block[2] for the following phase protective elements:
• I>, I>> and I>>> (50/51), DthAL1, DthAL2 and Dth> (49), IPD>, IPD >>, IPD >>> and IPD >>>> (67)
Block2 IE
A change in status of a binary input effects a block[1] for the following earth protective elements:
• IE>, IE>> and IE>>> (50N/51N), IED>, IED>>, IED>>> and IED>>>> (67N).
Block1
A change in status of a binary input effects a block for a length of time equal to the activation of the
input[3]; the element pickup that wish be blocked must be enabled (the Block1 parameter must be
set to ON in the concerning menu).[4]
The application of the IN1 binary input for the acquisition of the Block1 (logic block) coming from
external signal is shown in the following figure; in the example the block signal is ORed with Block2
(selective block) to block the generic (xxx) element.
Note 1 The exhaustive treatment of the Block 2 function is described in the “Logic selectivity” paragraph.
Note 2 The exhaustive treatment of the Block 2 function is described in the “Logic selectivity” paragraph.
The application of the inputs for the acquisition of Block2 (selective block) for Phase (Block2 Iph) and earth protective functions (Block2 IE) is
similar to that illustrated in the scheme concerning the Block2 IphIIE
Note 3 Unlike the Block2 (selective block), that houses a safety logic founded on programmable timers, the Block1 (logic block) keeps block of the
protection for the whole time when the input is active.
Note 4 The activation of one binary input produces indiscriminately a block of all protective elements programmed for being blocked from Block1
≥1
≥1
≥1
Block2IPh/IE
T
0
tB-Iph
BlockIph-Ie.ai
Binary input allocation for logic selectivity (Block2)
tB-Iph
tB-IE
xxxxx Trip Block2
Block2 input enable (ON≡Enable)
&
Block2 IN
towards reset timer
IPh Block2 input
IE Block2 input
Block2 IN diagnostic
Block2 input
FROM ANY PROTECTIONS
FROM OVERCURRENT PROTECTIONS
T
0
tB-IE
IPh/IE Block2
Binary input INx (x=1,... 5)
T
0
Logic
IN2 t ON
INx t ON
IN2 t OFF
T
0
n.o.
n.c.
INx t OFF
FROM EARTH FAULT PROTECTIONS
Block1.ai
xxxx Block1
Enable (ON≡Enable)
Block1 input (ON≡Block)
Block1
from Block2 (ON≡Block)
&
Block1
Block1
Binary input INx (x=1,... 5)
Binary input allocation for logic block (Block1)
Blocking
T
0
IN1 t ON
T
0
n.o.
n.c.
IN1 tON
Logic
IN1 tOFF
IN1 t OFF
≥1
NA30 - Manual - 04 - 2022
TCS1 and TCS2
Trip Circuit Supervision.
Supervision with one or two binary input can be performed.
The exhaustive treatment of the TCS function is described in the concerning paragraph.
Trip ProtExt
The binary input detects a trip coming from an external protective relay: the information is available
for the breaker failure function (BF).
Reset counters
A change in status of a binary input effects a reset of all start/trip partial counters.[1]
Reset CB Monitor
A change in status of a binary input effects a reset of all counters concerning the circuit breaker
diagnostic:
• Breaking Sum phase IL1, IL2, IL3
• Breaking SumI2t phase IL1, IL2, IL3
• CB Open counter
52a-52b
The CB position can be acquired by means of binary inputs connected to the auxiliary contacts: the
information is used in the following functions:
• CB position (open-closed)
• CB diagnostic (N. of operations, trip time)
• Breaker Failure (BF)
Note 1 The reset of the total counters is practicable by means ThyVisor command with Session Level 1 (available with password)
TCS2.ai
TRIP
+UAUX
Trip Circuit Supervision - 74TCS with two binary inputs
-UAUX
52a
52b
52
TCS1
TCS2
74TCS logic
74TCS logic
Binary input INx (x=1,... 5)
T
0
IN1 t ON
0
n.o.
n.c.
IN1 tON
Logic
IN1 tOFF
IN1 t OFF
Binary input INx (x=1,... 5)
T
0
IN1 t ON
0
n.o.
n.c.
IN1 tON
Logic
IN1 tOFF
IN1 t OFF
ExtProt.ai
Breaker failure (BF)
+UAUX
-UAUX
IN-
IN+
Trip ProtExt
Binary input INx (x=1,... 5)
T
0
IN1 t ON
T
0
n.o.
n.c.
IN1 tON
Logic
IN1 tOFF
IN1 t OFF
Binary input allocation for trip acquisition from external protection device
CB-pos.ai
CB position
CB diagnostic
Breaker failure (BF)
74VT
52a
52
52b
+UAUX
-UAUX
IN-
IN+
52a
IN-
IN+
52b
Binary input INx (x=1,... 5)
T
0
IN1 t ON
T
0
n.o.
n.c.
IN1 tON
Logic
IN1 tOFF
IN1 t OFF
Binary input INx (x=1,... 5)
T
0
IN2 t ON
T
0
n.o.
n.c.
IN2 tON
Logic
IN2 tOFF
IN2 t OFF
Binary input allocation for CB state acquisition
NA30 - Manual - 04 - 2022
Open CB
Close CB
The external acquisition of remote commands allows to drive CB remotely.
Preset DTheta
The input activation presets the thermal image (49).
The preset value can be adjusted by means the DθIN setting. The thermal image is initialized at the
DθIN value when the device is powered or when the binary input become active.
Remote trip
The input activation drives an expressly programmed output relay.
Reset demand measures
The input activation make a reset of all demand measures.
74TV ext
The external acquisition of 74TV allows to block or to change the operating mode of protective el-
ements where the residual voltage is employed; the information is available for residual voltage
protective elements (59N and 67N protections) that may operate inadvertently when an event cause
a loss of one or more voltages.
CB-com.ai
OPEN
Command
CLOSE
Command
+UAUX
+UAUX
-UAUX
IN-
IN+
IN-
IN+
Binary input INx (x=1,... 5)
T
0
IN1 t ON
T
0
n.o.
n.c.
IN1 tON
Logic
Open CB
Close CB
IN1 tOFF
IN1 t OFF
Binary input INx (x=1,... 5)
T
0
IN2 t ON
T
0
n.o.
n.c.
IN2 tON
Logic
IN2 tOFF
IN2 t OFF
Binary input allocation for CB remote command
TRIPPING MATRIX
(LED+RELAYS)
-UAUX
-UAUX
52 52a
O
I
52b
inhit-theta.ai
t = T+·ln{[(Ith/IB)2-DθP/DθB]/[(Ith/IB)2-1.2]
DθP = DθIN
Binary input allocationfor thernal image preset (49)
+UAUX
-UAUX
IN+
IN-
PresetDTheta
PresetDTheta
Binary input IN1, IN2
T
0
Logic
IN1 t ON
IN1 t ON
IN1 t OFF
0
n.o.
n.c.
IN1 t OFF
Remote-trip.ai
Remote trip
+UAUX
-UAUX
Remote trip
Binary input IN1, IN2
T
0
IN1 t ON
T
0
n.o.
n.c.
IN1 tON
Logic
IN1 tOFF
IN1 t OFF
TRIPPING MATRIX
(LED+RELAYS)
Binary input allocation for remote trip
NA30 - Manual - 04 - 2022
Output relays
Six output relays are available (K1...K6):[1]
• K1 and K2 have two changeover contacts (SPDT, type C).
• K3, K4 and K5 have one make contact (SPST-NO, type A).[2]
• K6 has one break contact (SPST-NC, type B).[3]
Each output relay may be programmed with following operating mode:
• Operation MODE (No latched, Pulse, Latched).
• Logic (Energized/De-energized).
To each output relay a programmable timer is matched (Minimum pulse width parameter).
All parameters are available inside the Set\Relays menu.
Any change to the settings can be affected at any time, also with the relay on duty, separately for
each relay.
Notes:
• When de-energized operating mode is set, the relay remains in rest condition if no trip command
is in progress.
• When energized operating mode is set, the relay remains in operating condition if no trip command
is in progress and the auxiliary supply is powered on.
• When no-latched operating mode is set (Operation MODE No latched), the output relay reset
at the end of the trip condition. To each output relay a programmable timer is matched (minimum
pulse width operation).
• When latched operating mode is set (Operation MODE Latched), the output relay doesn’t reset
at the end of the trip condition; it stays ON until a reset command is issued (RESET key, ThyVisor or
communication command).
• When pulse operating mode is set (Operation MODE Pulse), the output relay reset after a tTR
programmable delay regardless of the trip condition.
• It is advisable to make sure that the output contact technical data are suitable for load (Nominal
current, breaking capacity, make current, switching voltage,...).
Matching every output relay to any protective element is freely programmable inside the Setpoints
submenus according a tripping matrix structure.[4][5]
Note 1 Schematic diagram are shown inside APPENDIX B1.
Note 2 K3 and K4 have a common terminal (A10)
Note 3 K5 and K6 have a common terminal (A13)
Note 4 Matching of the output relay to the protective and control functions can be defined so that any collision from other function is avoided.
All output relay are unassigned in the default setting.
Note 5 Self test relay: it is advisable to plan the following settings:
- Energized operating mode,
- No-latched ,
in order that it stays ON for normal conditions and the other way round it goes OFF if any fault is detected and/or the auxiliary supply turns OFF.
Input
No-latched operation
Latched operation
Pulse operation
Output relay operation
Minimum pulse width
Relay-operation-timers.ai
t
Minimum pulse width
tTR
tTR
NA30 - Manual - 04 - 2022
FUNCTIONS
RELAYS
K1 K2 K3 K4 K5 K6
Self-test relay
DthAL1 Alarm relays (DthAL1-K)
DthAL2 Alarm relays (DthAL2-K)
Dth> Trip relays (Dth>-K)
I> Start relays (I>ST-K)
I> Trip relays (I>TR-K)
I>> Start relays (I>>ST-K)
I>> Trip relays (I>>TR-K)
I>>> Start relays (I>>>ST-K)
I>>> Trip relays (I>>>TR-K)
IE> Start relays (IE>ST-K)
IE> Trip relays (IE>TR-K)
IE>> Start relays (IE>>ST-K)
IE>> Trip relays (IE>>TR-K)
IE>>> Start relays (IE>>>ST-K)
IE>>> Trip relays (IE>>>TR-K)
UE> Start relays (UE> ST-K)
UE> Trip relays (UE> TR-K)
UE>> Start relays (UE>> ST-K)
UE>> Trip relays (UE>>TR-K)
IED> Start relays (IED>ST-K)
IED> Trip relays (IED>TR-K)
IED>> Start relays (IED>>ST-K)
IED>> Trip relays (IED>>TR-K)
IED>>> Start relays (IED>>>ST-K)
IED>>> Trip relays (IED>>>TR-K)
IED>>>> Start relays (IED>>>>ST-K)
IED>>>> Trip relays (IED>>>>TR-K)
I2ndh> Start relays (I2ndh>ST-K)
I2ndh> Trip relays (I2ndh>TR-K)
S< Trip relays (S
NA30 - Manual - 04 - 2022
LED indicators
Eight LEDs are available.
• One green LED “ON”: if turned on it means that the device is properly working, if flashing the inter-
nal self-test function has detected an anomaly.
• One yellow LED “START” tagged for START of one or more protective elements.[1]
• One red LED “TRIP” tagged for TRIP of one or more protective elements.[1]
• Five red LEDs “1...5” for highlight the activation of one or more user defined function.
Each output relay may be programmed with following operating mode:
• No-latched: the LED reset at the end of the trip condition.
• Latched: the LED doesn’t reset at the end of the trip condition; it stays ON until a manual reset
command is issued (RESET key, ThyVisor or communication command).
Any change to the settings can be affected at any time, also with the relay on duty, separately for
each LED.
Free allocation of each LED may be set according to the matrix structure shown in the following
page.[2]
Note 1 The START and the TRIP LED are user assignable to any function; other than starting and tripping information can be assigned to them too, just
the same for L1...L5
Note 2 All LEDs are unassigned in the default setting.
Led
CB Open
CB Close
NA30 - Manual - 04 - 2022
FUNCTIONS
LEDs
START TRIP L1
L2
L3
L4
L5
DthAL1 Alarm LEDs (DthAL1-L)
DthAL2 Alarm LEDs (DthAL2-L)
Dth> Trip LEDs (Dth>-L)
I> Start LEDs (I>ST-L)
I> Trip LEDs (I>TR-L)
I>> Start LEDs (I>>ST-L)
I>> Trip LEDs (I>>TR-L)
I>>> Start LEDs (I>>>ST-L)
I>>> Trip LEDs (I>>>TR-L)
IE> Start LEDs (IE>ST-L)
IE> Trip LEDs (IE>TR-L)
IE>> Start LEDs (IE>>ST-L)
IE>> Trip LEDs (IE>>TR-L)
IE>>> Start LEDs (IE>>>ST-L)
IE>>> Trip LEDs (IE>>>TR-L)
UE> Start LEDs (UE> ST-L)
UE> Trip LEDs (UE> TR-L)
UE>> Start LEDs (UE>> ST-L)
UE>> Trip LEDs (UE>>TR-L)
IED> Start LEDs (IED>ST-L)
IED> Trip LEDs (IED>TR-L)
IED>> Start LEDs (IED>>ST-L)
IED>> Trip LEDs (IED>>TR-L)
IED>>> Start LEDs (IED>>>ST-L)
IED>>> Trip LEDs (IED>>>TR-L)
IED>>>> Start LEDs (IED>>>>ST-L)
IED>>>> Trip LEDs (IED>>>>TR-L)
I2ndh> Start LEDs (I2ndh>ST-L)
I2ndh> Trip LEDs (I2ndh>TR-L)
S< Trip LEDs (S
NA30 - Manual - 04 - 2022
Communication interfaces
Several communication ports are provided:
• USB port on the front side for local communication (ThyVisor).
• RS485 port on the rear side for bus communication.
• Ethernet port on the rear side for bus communication.
USB
To connect the local port you need to use a cable USB Type B - Type A; the Thytronic cable code
L10042 can be supplied.
The serial port is the simplest access for setting by means the ThyVisor software.
RS485
Several protocol are implemented[1]:
• ModBus RTU. Modbus is a serial communications protocol. It is a de facto standard communica-
tions protocol in industry, and is now the most commonly available means of connecting industrial
electronic devices also inside electric utilities and substation.
• IEC 60870-5. The IEC 60870-5 suite of protocol is used for communications from master station to
substation, as well within the substation; the IEC 60870-5-103 (Protection equipment) is available
together the Modbus protocol on some version of Pro-n devices (code NAxx#xxxxC x).
Ethernet
It is provided (optionally) a communication board useful for Ethernet communication with ModBus
TCP/IP protocol.[2]
Modbus/TCP basically embeds a Modbus frame into a TCP frame in a simple manner. This is a con-
nection-oriented transaction which means every query expects a response.
This query/response technique fits well with the master/slave nature of ModBus, adding to the de-
terministic advantage that Switched Ethernet offers industrial users.
In the same way as the RS485 base Modbus, every device is identified by a personal address and the
communication goes in “client-server” mode with answering request from the recipient.
The protective relay can be directly connect to the Ethernet network (no gateway, protocol converter
are needed).
Two port can be implemented:
• 100BASE-TX with RJ45 connector (copper).
• 100BASE-FX with FX connector (optical fiber)[2]
For both modules no hw preset are required.
Two LEDs are on board (RJ45):
• LINK - (green): The LED lights up if the connection is active.
• TX - (yellow): The LED lights up when data transmission is active.
Note 1 The RS485 port is not implemented on the Pro-N devices endowed with Ethernet FX port
Note 2 Information about the ModBus map may be find inside the “Remote programming manual”
ethernet-sch.ai
RX
FX Ethernet (no RS485 port)
TX
1 TX+
2 TX-
3 RX+
4
5
6 RX-
7
8
RJ45 Ethernet+RS485 ports
RS485
F1
F2
F3
F4
F5
A+
B-
NA30 - Manual - 04 - 2022
4.4
PROTECTIVE ELEMENTS
Rated values
Inside the Base menu the following parameters can be set:
• Relay reference name.
• Relay nominal currents (phase and residual), to which the regulation are related.
• Primary nominal values, employed for measures relative to primary values.
• Measurements reading mode.
Information for settings:
• Relay reference name.
Alphanumeric mnemonic string (max 16 characters) useful for identification of protected plant.
• Relay nominal frequency fn
This nominal value must be set same as the frequency of the grid.
Example: grid frequency fn = 50 Hz
Relay nominal frequency fn = 50 Hz
• Relay phase nominal current In
This nominal value must be set by means dip-switch to 1 A or 5 A, same as the secondary CTs
nominal current.
Dip-switches are located on board of the CPU module; the exhaustive treatment of Dip setup is
described in the “6.5 SETTING NOMINAL CURRENTS In AND IEn” paragraph.
• Relay residual nominal current IEn
This nominal value must be set by means dip-switch to 1 A or 5 A, same as the secondary CT nomi-
nal current.
Dip-switch is located on board of the CPU module; the exhaustive treatment of Dip setup is de-
scribed in the “6.5 SETTING NOMINAL CURRENTS In AND IEn” paragraph.
• Phase CT primary current Inp
This parameter affects the measure of the phase currents when the primary measurement read-
ing mode is selected. It must be programmed to the same value of the phase CT primary nominal
current.
Example
The phase CT primary current Inp must be set as: Inp = 500 A
• Residual CT primary current IEnp
This parameter affects the measure of the residual current when the primary measurement reading
mode is selected. It must be programmed to the same value of the residual CT(s) primary nominal
current.
Example 1
The residual CT primary current IEnp must be set as: IEnp = 100 A
Es-In.ai
KCT = 500A/5A=100
52
In
NA30
Es1-IEn.ai
1x
KCT = 100 A /1 A
52
IEn= 1 A
NA30
NA30 - Manual - 04 - 2022
Example 2
The residual CT primary current IEnp must be set as: IEnp = 100 A
• Relay residual nominal voltage UEn
The residual nominal voltage UEn may be estimated by means of the following general formula (ef-
fective for insulated neutral or impedance-ground connected grids):
If open delta VT with primary nominal voltage balances to the grid voltage divided by √3, the follow-
ing streamlined calculus may be used:
UEn = 3 · VT open delta secondary nominal voltage [V] for insulated or impedance-ground neutral
grids.
Example A1
The relay residual nominal voltage UEn must be estimated by means of the following general for-
mula:
UEn = √3 · Ung /KVT = √3 · 6900 / (√3 · 100) = 69 V
Example A2
The relay residual nominal voltage UEn must be indifferently estimated by means of the following
general formula:
UEn = √3 · Ung /KVT = √3 · 6000 / (√3 · 60) = 100 V
or by means the following streamlined formula:
UEn = 3 · Uns = 3 · 100 / 3 = 100 V
The Unp setting must be adjusted to: Unp = Ung = 6.9 kV
• Measurement reading mode
Measures may be displayed according the following operating modes:
- With RELATIVE setting all measures are related to the nominal value,
- With PRIMARY setting all measures are related to the primary value.
Es2-IEn.ai
3x
KCT = 100A / 5A
52
IEn= 5 A
NA30
VT ratio KVT
UEn = Grid nominal voltage Ung where the VTs [V] x √3 are connected
/
Es1-UEn.ai
KVT =
/
/
V
V
10000
3
100 3
3
= 100 ·
= 100 · 3
/
/
V
V
10000
3
100 3
Grid nominal voltage Ung = 6.9 kV
VT ratio: KVT =
Insulated or impedance-ground neutral
/
Ung = 6.9 kV
UEn
52
NA30
Es2-UEn.ai
KVT =
/
V
V
6000
3
100 / 3
3
= 60 ·
Insulated or impedance-ground neutral
Unp = 6 kV
UEn
52
NA30
= 60 · 3
/
/
V
V
6000
3
100 3
Grid nominal voltage Ung = 6 kV
VT ratio: KVT =
/
NA30 - Manual - 04 - 2022
Thermal protection with RTD thermometric probes - 26
Preface
The measure of temperature is acquired by means of Pt100 (RTD Resistive Temperature sensing
Devices) probed, connected to the MPT module.[1]
A direct thermal protection element with eight PT100 thermometric probes (RTD Resistive Thermal
Device) provides protection against premature ageing or breakdown of the insulating materials
through overheating.
Thermal protection using thermometric probes offers greater reliability than Thermal overload-based
indirect protection, since it is not influenced by inaccuracies in the time constant for the thermal
model of the machinery and by variations in the surrounding temperature.
For each thermometric probe an alarm (ThALx, where x=1...8 points one of the eight probes) and one
trip adjustable threshold is provided (Th>x), with adjustable operating time (tThALx and tTh>x>);if the
measured temperature overcomes the threshold, the relative alarm and/or trip is issued when the
timer expires.
The adjustments are operable in °C.
The probes should be placed in strategic points around the machinery susceptible to the greatest
overheating, such as for example:
- near the generator stator windings, near the step-up transformer windings and/or in the oil, with the
aim of detecting overheating produced by the overload currents,
- near the generator bearings, with the aim of detecting localised overheating due to worn or non-
lubricated bearings.
The Pt100 probes detect the temperature in the range -50 °C...+250 °C (at 0 °C its resistance is 100
ohm); an alarm indicates any interruption or short-circuiting of the probe or related connections to
the MPT module; the information is available inside the Read \ PT100 menu:
• Ptx probe ON to point a measure inside the range
• Ptx probe LOW to point a measure lower the range (short circuit of probe and/or wires)
• Ptx probe HIGH ao point a measure higher the range (breaking of probe and/or wires).
Self reset is performed when faults are cleared.
The measure of each probe is updated at 2 s time intervals.
Note 1 The 26 menu is available when the MPT module is enabled
t-int-F26.ai
T (°C)
t
General operation time characteristic for thermal protection with RTD thermometric probes (26)
Th>x
tTh>x
tThALx
TRIP
all-F26.ai
General logic diagram of the thermal elements - (26)
Pt100
Thybus
MPT
AL ARM
TRIP
Trip Element
Alarm Element
ThALx enable
Th>x enable
ThALx
Th>x
t ThALx
t Th>x
Th>xBF
Trip Th>x
&
Th>xBF
t-refresh-F26.ai
t
Pt1...8 update
Pt1
Pt2
Pt3
Pt4
Pt5
Pt6
Pt7
Pt8
Pt1
0.25s
0.25s
0.25s
0.25s
0.25s
0.25s
0.25s
0.25s
2.0s
NA30 - Manual - 04 - 2022
All alarm and/or trip elements can be enabled or disabled by setting ON or OFF the ThALx Enable
e Th>x Enable parameters inside the Set \ Profile A(or B) \ Thermal protection with RTD thermo-
metric probes - 26 \ PTx Probe \ ThALx Alarm (ThALx Trip) where x = 1...8.
Each trip threshold (Th>x) may be associated with the breaker failure (BF) function by setting ON
the Th>xBF parameters inside the Set \ Profile A(or B) \ Thermal protection with RTD thermometric
probes - 26 \ PTx Probe \ ThALx Trip where x = 1...8.[1]
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu.
Fun-F26.ai
Logic diagram for thermal protection with RTD thermometric probes (26)
T° ≤ +245.0°C
T° > Pt x>
Ptx
Pt1
Pt2
Pt3
Pt4
Pt5
Pt6
Pt7
Pt8
0
T
TRIPPING MATRIX
(LED+RELAYS)
T° > ThALx
Pt100-x Trip
Pt100-xAlarm
t Th>x
t ThALx
BF Enable (ON≡Enable)
Pt100 OK
Pt100 FAULT
Th>xBF
TOWARDS BF LOGIC
Th>x BF_OUT
TOWARDS DIAGNOSTIC
Pt x> Diagnostic
TRIP
&
&
&
T° ≥ -49.0°C
0
T
ThALx-K
ThALx-L
Th>x-K
Th>x-L
ThALx
Th>x
t ThALx
t Th>x
Pro_N
E1
THYBUS
THYBU I S NPUT
HYBU S OUTPUT
T
MPT
8
T1
PT1
PT8
MPT1
MPT8
PT7
MPT7
PT6
MPT6
PT5
MPT5
PT2
MPT2
PT3
MPT3
PT4
MPT4
T8
7
6
T7
T6
T5
11
T2
12
13
15
T3
16
17
20
T4
21
22
49
48
47
44
43
42
40
39
38
35
34
33
Pt100 probes (Pt1...Pt8)
NA30 - Manual - 04 - 2022
Thermal image - 49
Preface
It is a overload protection with memory capability and three setpoints, used to protect lines and
transformers against thermal overload.
The phase currents are used into an algorithm reproducing a thermal replica according the IEC
60255-8 standard taking into account the Joule losses and the cooling effect due to the load reduc-
tion; in this way the previous history and the overload are taken into account.
The thermal protection can be adapted to the different features of motors by setting the thermal
heating t+ and cooling t- constants ( the t+ constant refers to motor running condition, while the
t- constant, always higher than t+, refers to stop condition).
The trip element has an adjustable threshold; with 1.2 DθB setting (ie 1.2 times the overtemperature
corresponding to the nominal operation condition) the corresponding tripping current IB is 1.1 since
the temperature rise is proportional to the square of the current.
The 49 element is provided with two further thresholds DθAL1 and DθAL2, lower than the previous one.
These thresholds, both adjustable, provide an alarm signal to draw attention in the event of anoma-
lous heating, without disconnect the protected device. One of the above thresholds can be used to
prevent refeeding of the system when heating approaches the trip conditions since the additional
heating brought on by the inrush currents would cause the protection to operate.
Operation and settings
The thermal current used for thermal image calculation is:
Ith = max (IL1, IL2, IL3)
If the second harmonic restraint is enabled, the thermal current used for thermal image calculation
becomes:
Ith = ILMAX/KINR = max (IL1, IL2, IL3) / KINR
where KINR is an adjustable parameter (1.0...3.0), useful to reduce the thermal current during the
transformer energization (inrush).
According to a single-body thermal model, the thermal image is based on the differential equation:
dDθ/dt+Dθ/T=(Ith/IB)2/T
where Dθ is the system thermal state as a percentage of base thermal capacity DθB corresponding
to the base current IB[1] and T is the thermal time constant (the same for heating and cooling).
When the thermal image Dθ overcomes the threshold a trip is issued.
The operating characteristic (IEC 60255-8) is:
t=T*ln{[(Ith/IB)2-Dθp/DθB)]/[(Ith/IB)2-1.2]}=T*ln{[(Ith/IB)2-(Ip/IB)2]/[(Ith/IB)2-1.2]=
T*ln{[(Ith/IB)2-p2]/[(Ith/IB)2-1.2]} [1]
where:
• t: operating time,
• ln: natural logarithm,
• Dθp and Ip are the thermal image and the corresponding equivalent thermal current before the
overload occurs.
• p=Ip/IB=√(Dθp/DθB: prior load.
Following data applies:
• Range where the equation is valid: 1.1IB ≤ Ith ≤ 10IB
• If 10IB ≤ Ith ≤ 20IB, the operating time is fixed to a value corresponding to the 10IB
• The upper limit is 20IB.
Note 1 Assuming that the secondary rated current of the line CT’s equals the rated current of the NA20 relay, as usually happens, the IB value is the
ratio between the rated current of the protected component (line, transformer,...) and the primary rated current of the CT’s.
t-int-F49.ai
Ith/IB
p=0
p=1
Dth>
t
TRIP
General operation time characteristic for the thermal image elements - 49
NA30 - Manual - 04 - 2022
If the CLP function (Cold Load Pick-up) is enabled for blocking 49, the thermal image is blocked for an
adjustable time interval, starting from the circuit breaker closure.[1] The operating mode parameter
may be select by setting ON-Element blocking the DThCLP Mode parameter inside the Set\Pro-
file A(or B)\Thermal image-49\ Common configuration menu.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the equivalent ther-
mal current may be decreased by means a KINR factor for an adjustable time interval, starting
from the circuit breaker closure.[2] The operating mode parameter may be select by setting ON-
Change setting the DThCLP Mode parameter inside the Set\Profile A(or B)\Thermal image-49\
Common configuration menu.
For the Dth> threshold, a block from the second harmonic restraint may be set by set-
ting ON the DTh>2ndh-REST parameter inside the Set\Profile A(or B)\Thermal image-49\
Common configuration menu.
All elements can be enabled or disabled by setting ON or OFF the DThetaAL1 Enable, DTheta-
AL2 Enable and/or DTheta> Enable parameters inside the Set\Profile A(or B)\Thermal image-49\
DthAL1 Element (DthAL2 Element, Dth> Element) menus.
The trip element (Dth>) may be inhibited when a start of at least one of the overcurrent element
(50/51) is active, if the Dth>disby50-51 parameter is set ON inside the Set\Profile A(or B)\Thermal
image-49\ Dth> Element menu.
The DθIN parameter sets a minimum level of previous thermal image Dθp when the protection relay
is powered or when a remote (binary input) or local (keyboard or ThyVisor) command is issued.
The DthIN parameter may be adjusted inside the Set \ Profile A(or B) \ Thermal image-49\
Common configuration menu.
To active the DθIN preset value remotely, a binary input must be programmed as Init DTheta func-
tion inside the Set \ Inputs \ Binary input IN1, Binary input IN2 menu.
The trip element can produce the Breaker Failure output if the Dth> BF parameters is set to ON.
The parameter is available inside the Set\Profile A(or B)\Thermal image-49 \ Dth> Element menu.[3]
The IB setting is adjustable inside the Set\Profile A(or B)\Base current IB menu.
Note 1 The CLP function (Cold Load Pick-up) with blocking of the 49 element has priority compared with the second harmonic restraint function, so, if
the equivalent thermal current is enabled, the latter is not reduced when a second harmonic restraint is active.
Note 2 The CLP function (Cold Load Pick-up) with threshold change of the 49 element has priority compared with the second harmonic restraint func-
tion, so, if the equivalent thermal current is enabled, the latter is not reduced when a second harmonic restraint is active.
Note 3 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu.
all-F49.ai
KINR
T
DthIN
DthCLP Mode
Dth2ndh REST
tDthCLP
Common configuration
Ith
Dth> Element
Trip DTh>
DTh> Enable
DTh>
Trip DTh>
Dth>BF
&
Dth>BF
BLK4OUT
Dth>BLK4
Start I>
&
BLK2OUT
Dth>BLK2OUT
&
Trip Dth>
Trip Dth>
BLK2INDth>
Block2
&
Dth>BLK2IN
&
DthAL1 Element
DThAL1
DThAL1
DThAL1
DThAL1 Enable
Ith
BLK4OUT
DthAL1BLK4
&
BLK2OUT
DthAL1BLK2OUT
&
Trip Dth>
Block1
BLK1DthAL1
&
DthAL1BLK1
&
Dth>AL1
DthAL1
BLK2INDthAL1
Block2
&
DthAL1BLK2IN
&
DthAL2
BLK2INDthAL2
Block2
&
DthAL2BLK2IN
&
DthAL2 Element
DThAL2
DThAL2
DThAL2 Enable
Ith
BLK4OUT
DthAL2BLK4
&
BLK2OUT
DthAL2BLK2OUT
&
Block1
BLK1DthAL2
&
DthAL2BLK1
&
Dth>AL2
Dth>AL2
Dth>AL2
Block1
BLK1Dth>
&
Dth>BLK1
Trip Dth> &
&
50-51 inhibition
Dth>disby50-51
General logic diagram of the thermal image elements - 49
NA30 - Manual - 04 - 2022
For every threshold the following block criteria are available:
Logical block (Block1)
If the DthAL1BLK1, DthAL2BLK1 and/or Dth>BLK1 enabling parameters are set to ON and a bi-
nary input is designed for logical block (Block1), the concerning element is blocked off whenever the
given input is active.[1] The enabling parameters are available inside the Set\Profile A(or B)\Thermal
image-49\ DthAL1 Element (DthAL2 Element, Dth> Element) menus, while the Block1 function must
be assigned to the selected binary input inside the Set\Inputs\Binary input IN1(2) menus.
Selective block (Block2)
All along the protective elements the selective block may be set.
The logic selectivity function may be performed by means any combination of the following I/O:
• One committed pilot wire input (BLIN1).
• One or more binary inputs designed for input selective block.
• One committed pilot wire output (BLOUT1).
• One or more output relays designed for output selective block.
Only when the committed pilot wire are used the continuity check of the pilot wire link is active.
Use of committed pilot wire input BLIN1:
• The protection is blocked off according the selectivity block criteria when the input BLIN1 is active.
The information about phase or phase+earth block may be select programming the ModeBLIN1
parameter inside the Set\Profile A(or B)\Selective block-BLOCK2 \ Selective block IN menus.
Use of binary inputs:
• If the DthAL1BLK2IN, DthAL2BLK2IN and/or Dth>BLK2IN parameter are are set to ON and
a binary input is designed for selective block (Block2), the protection is blocked off by phase ele-
ments (Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block
criteria.[2] The enable DthAL1BLK2IN, DthAL2BLK2IN and/or Dth>BLK2IN parameters
are available inside the Set\Profile A(or B)\Thermal image-49\ DthAL1 Element, DthAL2 Element,
Dth> Element menus, while the Block2 Iph and Block2 Iph/IE functions must be assigned to the
selected binary inputs inside the Set \ Inputs \ Binary input IN1(2) menus (IN1 or IN2 matching).
Use of committed pilot wire output BLOUT1:
• The information about phase or phase+earth block may be select programming the ModeBLOUT1
parameter inside Set\Profile A(or B)\Selective block-BLOCK2\ Selective block OUT menus.
Use of output relay (K1...K6):
• If the DthAL1BLK2OUT, DthAL2BLK2OUT and/o Dth>BLK2OUT enable parameters are set
to ON and a output relay is designed for selective block (Block2), the protection issues a block
output by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), when-
ever the given element (DthAL1, DthAL2 e/o Dth>) becomes active. The enable DthAL1BLK2OUT,
DthAL2BLK2OUT and/or Dth>BLK2OUT parameters are available inside the Set\Profile A(or
B)\Thermal image-49\ DthAL1 Element (DthAL2 Element, Dth> Element) menus, while the BLK-
2OUT-Iph-K, BLK2OUT-Iph/IE-K and/or BLK2OUT-IE-K output relays must be set inside the
Set\Profile A(or B)\Selective block-BLOCK2 \ Selective block OUT menus.
Internal selective block (Block4)
As well as to send or transmit a selective block toward other protective relays, each protective
element may be enabled for receive or transmit a selective block from/to other internal protective
elements.[3]
The internal selective block of one or more element concerning the thermal image function may
be enabled/disabled by means the DthAL1BLK4, DthAL2BLK4, and/or Dth>BLK4 parameters
(virtual input and output common to all protective thresholds); the following operating modes are
available:
• IN - the element is enabled to receive the selective block from an internal input.
• OUT - the element is enabled to send the selective block to an internal output.
• OFF - the element is disabled to send/receive the internal selective block.
Transmission and reception for the same element is not allowed, so any stall situation due to wrong
setting is avoided.
The internal selective block can work together with an external selective block from other protective
relays (Block2).
Note 1 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR-
ING section
Note 2 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND
MONITORING section
Nota 3 The exhaustive treatment of the internal selective block (Block 4) function may be found in the “Internal selective block” paragraph inside
CONTROL AND MONITORING section.
NA30 - Manual - 04 - 2022
Fun_49_AL1.ai
Common configuration
&
dDθ/dt + Dθ/T = (Ith/IB)2/T
Init DTheta
Dθ ≥ DthAL1
DthAL1
Binary input INx (x=1...8-16)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Ith
≥1
KINR
DthAL1
CB-State
Start I2ndh>
ON≡Enable element
(Pickup within CLP)
(Pickup outside CLP)
Pickup - CLP setting change
Block1, Block2, Block4
T
0
tDthCLP
&
2nd harmonic restraint enable (ON≡Enable)
Dth2ndh-REST
DthCLPMode
t DthCLP
Ith ∙ KINR
TRIPPING MATRIX
(LED+RELAYS)
A
B
C
A =“1”
A =“0 or OFF”
Output tDthCLP
DthAL1 Enable
DThhAL1 thermal image (49) block diagram
tDthCLP
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tDthCLP
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
DthAL1-L
DthAL1-K
≥1
CLP Dth
T
DthIN
Thermal image (49) - Logic diagram of the first alarm threshold
NA30 - Manual - 04 - 2022
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
DthAL1BLK2OUT
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
49AL1_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1DthAL1
BLK4INDthAL1
&
&
BLK2IN DthAL1
&
&
Enable (ON≡Enable)
DthAL1BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
DThAL1BLK2IN
Block1
BLK2IN-Iph
DthAL1
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
DthAL1 Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
IPD>Block4 I/O
IPD>>Block4 I/O
IPD>>>Block4 I/O
IPD>>>>Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IPD>Block2 OUT
IPD>>Block2 OUT
IPD>>>Block2 OUT
IPD>>>>Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
DthAL1BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
DthAL1BLK4
A
DthAL1
DthAL1
Thermal image (49) - Logic diagram of the blocking signals concerning the first alarm element
NA30 - Manual - 04 - 2022
Fun_49_AL2.ai
Common configuration
&
dDθ/dt + Dθ/T = (Ith/IB)2/T
Init DTheta
Dθ ≥ DthAL2
DthAL2
Binary input INx (x=1...8-16)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Ith
≥1
KINR
DthAL2
CB-State
Start I2ndh>
ON≡Enable element
(Pickup within CLP)
(Pickup outside CLP)
Pickup - CLP setting change
Block1, Block2, Block4
T
0
tDthCLP
&
2nd harmonic restraint enable (ON≡Enable)
Dth2ndh-REST
DthCLPMode
t DthCLP
Ith ∙ KINR
TRIPPING MATRIX
(LED+RELAYS)
A
B
C
A =“1”
A =“0 or OFF”
Output tDthCLP
DthAL2 Enable
DThhAL1 thermal image (49) block diagram
tDthCLP
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tDthCLP
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
DthAL2-L
DthAL2-K
≥1
CLP Dth
T
DthIN
Thermal image (49) - Logic diagram of the second alarm threshold
NA30 - Manual - 04 - 2022
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
DthAL2BLK2OUT
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
49AL2_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1DthAL2
BLK4INDthAL2
&
&
BLK2IN DthAL2
&
&
Enable (ON≡Enable)
DthAL2BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
DThAL2BLK2IN
Block1
BLK2IN-Iph
DthAL2
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
DthAL2 Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
IPD>Block4 I/O
IPD>>Block4 I/O
IPD>>>Block4 I/O
IPD>>>>Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IPD>Block2 OUT
IPD>>Block2 OUT
IPD>>>Block2 OUT
IPD>>>>Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
DthAL2BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
DthAL2BLK4
A
DthAL2
DthAL2
Thermal image (49) - Logic diagram of the blocking signals concerning the second alarm element
NA30 - Manual - 04 - 2022
Fun_49_Dth.ai
Common configuration
&
dDθ/dt + Dθ/T = (Ith/IB)2/T
Init DTheta
Dθ ≥ Dth>
Dth>
Binary input INx (x=1...8-16)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Ith
≥1
KINR
Dth>
CB-State
Start I2ndh>
ON≡Enable element
(Pickup within CLP)
(Pickup outside CLP)
Pickup - CLP setting change
Block1, Block2, Block4
T
0
tDthCLP
&
2nd harmonic restraint enable (ON≡Enable)
Dth2ndh-REST
DthCLPMode
t DthCLP
Ith ∙ KINR
BF Enable (ON≡Enable)
Dth>BF
towards BF logic
Dth> BF
&
Trip Dth>
TRIPPING MATRIX
(LED+RELAYS)
A
B
C
A =“1”
A =“0 or OFF”
Output tDthCLP
Dth> Enable
DTh> thermal image (49) block diagram
tDthCLP
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tDthCLP
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
Dth>-L
Dth>-K
≥1
CLP Dth
from 50/51 element (ON≡Inhibit)
50/51 inhibition
&
50/51block enable (ON≡Enable)
Dth>disby50-51
T
DthIN
Thermal image (49) - Logic diagram of the trip threshold
NA30 - Manual - 04 - 2022
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
Dth>BLK2OUT
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
49_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1Dth>
BLK4INDth>
&
&
BLK2IN Dth>
&
&
Enable (ON≡Enable)
Dth>BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
DTh>BLK2IN
Block1
BLK2IN-Iph
Dth>
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
Dth> Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
IPD>Block4 I/O
IPD>>Block4 I/O
IPD>>>Block4 I/O
IPD>>>>Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IPD>Block2 OUT
IPD>>Block2 OUT
IPD>>>Block2 OUT
IPD>>>>Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
Dth>BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
Dth>BLK4
A
Dth>
Dth>
Thermal image (49) - Logic diagram of the blocking signals concerning the trip element
NA30 - Manual - 04 - 2022
F_49-1min-Char.ai
Operating characteristic concerning the thermal image element (49) - T=1 min
1
1.1
2
3
4
5
6
7
8 9 10
20
Ith /IB
0.01
0.1
1
10
100
1000
10000
1.0
p =
0.0
0.8
0.6
t [s]
NA30 - Manual - 04 - 2022
F_49-200min-Char.ai
Operating characteristic concerning the thermal image element (49) - T = 200 min
1
1.1
2
3
4
5
6
7
8 9 10
20
Ith /IB
t [s]
0.1
1
10
100
1000
10000
100000
1.0
p =
0.0
0.8
0.6
NA30 - Manual - 04 - 2022
Phase overcurrent - 50/51
Preface
Three operation thresholds, independently adjustable (I>, I>>, I>>>) with adjustable delay
(t>, t>>, t>>>).
The first one may be programmed with definite or inverse time according the IEC and ANSI/IEEE
standard, as well as with rectifier, I2t or EM curve.
The second threshold may be programmable with independent or dependent time according to the
I2t curve and the third threshold with independent time.
For each threshold a reset time can be set (t>RES, t>>RES, t>>>RES) useful to reduce the clearing time
for intermittent faults.
The first threshold trip may be inhibited by start of the second and/or third threshold (I>>, I>>>).
Similarly the second threshold trip may be inhibited by start of the third threshold (I>>>).
Operation and settings
Each phase fundamental frequency current is compared with the setting value. Currents above the
associated pickup value are detected and a start is issued. After expiry of the associated operate
time a trip command is issued; if instead the current drops below the threshold, the element is re-
stored.
The first threshold (I>) may be programmed with definite or inverse time according the following
characteristic curves:
• Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t>inv / [(I/I>inv)0.02 - 1]
• Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · t>inv / [(I/I>inv) - 1]
• Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t>inv / [(I/I>inv)2 - 1]
• Moderately Inverse (ANSI/IEEE type MI):
t = t>inv · {0.01 / [(I/I>inv)0.02 - 1] + 0.023}
• Very Inverse (ANSI/IEEE type VI):
t = t>inv · {3.922 / [(I/I>inv)2 - 1] + 0.098}
• Extremely Inverse (ANSI/IEEE type EI):
t = t>inv · {5.64 / [(I/I>inv)2 - 1] + 0.024}
• Rectifier (RI):
t = 2351 · t>inv / [(I/I>inv)5.6 - 1]
• I-squared-t (I 2t = K):
t = 16 · t>inv / (I/I>inv)2
• Electromechanical (EM):
t = t>inv · {0.28 / [-0236 · (I/I>inv)-1 + 0.339]}
Where:
t:
operate time
I>inv:
threshold setting
t>inv:
operate time setting
The second threshold (I>>) may be programmable with definite or inverse time according to the I2t
curve:
t = 16 · t>inv / (I/I>inv)2
The third threshold (I>>>) with definite time.
For all inverse time characteristics, following data applies:
• Asymptotic reference value (minimum pickup value): 1.1 I>inv
• Minimum operate time:
0.1 s
• Range where the equation is valid:[1] 1.1 ≤ I/I>inv ≤ 20
• If I>inv pickup ≥ 2.5 In, the upper limit is 50 In
For all definite time elements the upper limit for measuring is 50 In.
All overcurrent elements can be enabled or disabled by setting ON or OFF the I> Enable, I>>
Enable and/or I>>> Enable parameters inside the Set \ Profile A(or B) \ Phase overcurrent-50/51
\ I> Element (I>> Element, I>>> Element) \ Setpoints menus.
The first overcurrent element can be programmed with definite or inverse time characteristic by
setting the I>Curve parameter (DEFINITE, IEC/BS A, IEC/BS B, IEC/BS C, ANSI/IEE MI,
ANSI/IEE VI, ANSI/IEE EI, RECTIFIER, I2t, EM) available inside the Set \ Profile A(or B) \
Phase overcurrent-50/51 \ I> Element \ Setpoints menu.
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
t-int-F50-51.ai
I
I>>
I>>>
t>
t>>
t>>>
I>
t
TRIP
General operation time characteristic for the phase overcurrent elements - 50/51
NA30 - Manual - 04 - 2022
The second overcurrent element can be programmed with definite or inverse time characteristic by
setting the I> Time characteristic (I>>Curve) parameter (DEFINITE, I2t) available inside the Set
\Profile A(or B) \ Phase overcurrent-50/51 \ I>> Element \ Setpoints menu.
The trip of I> element may be inhibited by the start of the second and/or third element (I>>, I>>>) by set-
ting ON the Disable I> by start I>>, Disable I>> by start I>>> (I>disbyI>>, I>disbyI>>>) parameters
available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I>> Element (I>>> Element) \ Setpoints
menus.
Similarly the trip of the I>> element may be inhibited by start of the third element (I>>>) by setting
ON the Disable I>> by start I>>> (I>>disbyI>>>) parameter available inside the Set \ Profile A(or
B) \ Phase overcurrent-50/51 \ I>>> Element \ Setpoints menu.
All the named parameters can be set separately for Profile A and Profile B (Set \ Profile A(or B)\
Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus).
An adjustable reset time delay is provided for every threshold (t>RES, t>>RES, t>>>RES).
Each overcurrent element can produce the Breaker Failure output if the I> BF, I>> BF and/or
I>>> BF parameters are set to ON. The parameters are available inside the Set \ Profile A(or B)
\Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus.[1]
For all overcurrent elements, a block from the second harmonic restraint may be set by setting ON
the I>2ndh-REST, I>>2ndh-REST, I>>>2ndh-REST parameters inside the Set \ Profile A(or
B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus.
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting ON-Element blocking the ICLP> Mode, ICLP>>
Mode and/or ICLP>>> Mode parameters.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting ON-Change setting the ICLP> Mode, ICLP>>
Mode and/or ICLP>>> Mode parameters, whereas the operating thresholds within the CLP
may be adjusted inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element,(I>> Element,
I>>> Element) \ Definite time (Inverse time) menus.
For both operating modes the CLP Activation time parameters (tCLP>, tCLP>>, tCLP>>>) may
be adjusted inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element,
I>>> Element) \ Setpoints menus.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu.
Timers-F50-51.ai
I> Start
I> Trip
t>
t>
RESET
INPUT
t>RES
t>RES
t>RES
t
I> element phase overcurrent timers - 50/51
NA30 - Manual - 04 - 2022
all-F50-51.ai
General logic diagram of the phase overcurrent elements - 50/51
IL1
IL2
IL3
IL1
IL2
IL3
IL1
IL2
IL3
≥
I>> inhibition
BLK1I>>>
I>>>BF
I>>> Element
Start I>>>
Start I>>>
Start I>>>
Trip I>>>
Trip I>>>
&
I>> disbyI>>>
&
I>>>BLK2IN
&
I> disbyI>>>
t>>> def
ICLP>>> def
I>>> def
ICLP>>>Mode
tCLP>>>
t>>>RES
BLK1I>>
I>> Element
BLK2OUT
Start I>>
Start I>>
Trip I>>
&
I> disbyI>>
&
I>>BLK1
&
I>>BLK2IN
t>> def
ICLP>> def
I>> def
t>> inv
ICLP>> inv
I>> inv
I>>Curve
ICLP>>Mode
tCLP>>
t>>RES
I>> Enable
I>>> Enable
I> inhibition
Block1
BLK1I>
CLPI>
CLPI>>
CLPI>>>
I> Element
BLK2OUT
BLK4OUT
BLK4OUT
BLK2INI>
BLK2INI>>
Start I>
Trip I>
&
I>BLK1
Block2
&
I>BLK2IN
Start I2ndh>
&
I>2ndh-REST
I>BLK2OUT
Start I2ndh>
&
I>>2ndh-REST
Start I2ndh>
&
I>>>2ndh-REST
&
I>>>BF
I>>BF
I>> Trip
&
I>>BF
I>BF
Trip I>
&
I>BF
Start I>
&
I>>BLK2OUT
Start I>>
&
BLK2OUT
I>>>BLK2OUT
Start I>>> &
I>BLK4
Start I>
&
I>>BLK4
Start I>>
&
BLK4OUT
I>>>BLK4
Start I>>> &
Block1
Block2
&
I>>>BLK1
Block1
Block2
t> def
ICLP> def
I> def
t> inv
ICLP> inv
I> inv
I>Curve
ICLP>Mode
tCLP>
t>RES
I> Enable
Start I>
&
Start I>>
&
Start I>>>
&
Start I>>
&
BLK2INI>>>
Start I>>>
&
Start I>
&
NA30 - Manual - 04 - 2022
For every of the three thresholds the following block criteria are available:
Logical block (Block1)
If the I>BLK1, I>>BLK1 and/or I>>>BLK1 enabling parameters are set to ON and a binary in-
put is designed for logical block (Block1), the concerning element is blocked off whenever the given
input is active.[1] The enabling parameters are available inside the Set\Profile A(or B)\Phase over-
current-50/51\ I> Element (I>> Element, I>>> Element) \Setpoints menus, while the Block1 function
must be assigned to the selected binary input inside the Set\Inputs\Binary input IN1(2) menus.
Selective block (Block2)
All along the protective elements the selective block may be set.
The logic selectivity function may be performed by means any combination of the following I/O:
• One committed pilot wire input (BLIN1).
• One or more binary inputs designed for input selective block.
• One committed pilot wire output (BLOUT1).
• One or more output relays designed for output selective block.
Only when the committed pilot wire are used the continuity check of the pilot wire link is active.
Use of committed pilot wire input BLIN1:
• The protection is blocked off according the selectivity block criteria when the input BLIN1 is active.
The information about phase or phase+earth block may be select programming the ModeBLIN1
parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus.
Use of binary inputs:
• If the I>BLK2IN, I>>BLK2IN and/or I>>>BLK2IN parameters are set to ON and a binary
input is designed for selective block (Block2), the protection is blocked off by phase elements
(Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block criteria.[2]
The enable I>BLK2IN, I>>BLK2IN and/or I>>>BLK2IN parameters are available inside the
Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints
menus, while the Block2 Iph and Block2 Iph/IE functions must be assigned to the selected
binary inputs inside the Set \ Inputs \ Binary input IN1(x) menus (IN1 or IN2 matching).
Use of committed pilot wire output BLOUT1:
• The information about phase or phase+earth block may be select programming the ModeBLOUT1
parameter (OFF - ON IPh - ON IPh/IE - ON IE) inside Set \Profile A(or B) \ Selective block-
BLOCK2 \ Selective block OUT menus.
Use of output relay (K1...K6):
• If the I>BLK2OUT, I>>BLK2OUT and/or I>>>BLK2OUT enable parameters are set to ON
and a output relay is designed for selective block (Block2), the protection issues a block output
by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), whenever
the given element (Start I>, Start I>> e/o Start I>>>) becomes active. The enable I>BLK2OUT,
I>>BLK2OUT and/or I>>>BLK2OUT parameters (ON or OFF) are available inside the Set
\ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints
menus, while the BLK2OUT-Iph-K, BLK2OUT-Iph/IE-K and/or BLK2OUT-IE-K output relays
and LEDs (BLK2OUT-Iph-L, BLK2OUT-Iph/IE-L e/o BLK2OUT-IE-L) must be select inside the
Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block OUT menu.
Internal selective block (Block4)
As well as to send or transmit a selective block toward other protective relays, each protective
element may be enabled for receive or transmit a selective block from/to other internal protective
elements.[3]
The internal selective block of one or more element concerning the phase overcurrent function may
be enabled/disabled by means the I>BLK4, I>>BLK4, and/or I>>>BLK4 parameters (virtual
input and output common to all protective thresholds); the following operating modes are available:
• IN - the element is enabled to receive the selective block from an internal input.
• OUT - the element is enabled to send the selective block to an internal output.
• OFF - the element is disabled to send/receive the internal selective block.
Transmission and reception for the same element is not allowed, so any stall situation due to wrong
setting is avoided.
The internal selective block can work together with an external selective block from other protective
relays (Block2).
Note 1 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR-
ING section
Note 2 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND
MONITORING section
Nota 3 The exhaustive treatment of the internal selective block (Block 4) function may be found in the “Internal selective block” paragraph inside
CONTROL AND MONITORING section.
NA30 - Manual - 04 - 2022
Fun_50-51S1.ai
IL1
IL2
t >RES
T
0
RESET
t >
0
T
≥1
≥1
≥1
t >def
t >inv
t >RES
Start I>
Trip I>
CB-State
Start I2ndh>
ON≡Inhibit (from I>> and/or I>>> overcurrent element)
ON≡Enable I> overcurrent element
(Pickup within CLP)
(Pickup outside CLP)
I> inhibition
Block1, Block2, Block4
&
T
0
tCLP>
&
2nd harmonic restraint enable (ON≡Enable)
I>2ndh-REST
ICLP>Mode
ICLP>def
t CLP>
ICLP>inv
IL1 ≥ I>
BF Enable (ON≡Enable)
I>BF
towards BF logic
I> BF
&
Trip I>
TRIPPING MATRIX
(LED+RELAYS)
I> Curve
0
T
A
B
C
A =“1”
A =“0 or OFF”
Output tCLP>
IL3
I> Enable
I> overcurrent element (50/51) block diagram
tCLP>
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tCLP>
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
I>TR-K
I>TR-L
I>ST-L
I>ST-K
≥1
CLP I>
&
State
I>inv
IL1 ≥ I>def
IL1 ≥ I>inv
I>def
&
State
Phase overcurrent (50/51) - First element logic diagram (I>)
NA30 - Manual - 04 - 2022
Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the first element (I>)
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
I>BLK2OUT
Start I>
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
50-51S1_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1I>
BLK4IN I>
&
&
&
BLK2IN I>
&
&
Enable (ON≡Enable)
I>BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
I>BLK2IN
Block1
BLK2IN-Iph
Start I>
Trip I>
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
I> Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
I>BLK4
Start I>
C
B
A
“0”
“0”
B
“0” C
“0”
I>BLK4
A
NA30 - Manual - 04 - 2022
Fun_50-51S2.ai
t >>RES
T
0
RESET
t >>
0
T
≥1
t >>def
t >>inv
t >>RES
Start I>>
Trip I>>
CB-State
Start I2ndh>
ON≡Inhibit (from I>>> overcurrent element)
ON≡Enable I>> overcurrent element
I>> inhibition
Block1, Block2, Block4
I>>TR-K
I>>TR-L
I>>ST-L
I>>ST-K
T
0
tCLP>>
&
&
2nd harmonic restraint enable (ON≡Enable)
I>>2ndh-REST
ICLP>>Mode
t CLP>>
BF Enable (ON≡Enable)
I>>BF
towards BF logic
I>> BF
&
Trip I>>
TRIPPING MATRIX
(LED+RELAYS)
I>> Curve
0
T
A
B
C
Output tCLP>>
I>> Enable
I>> overcurrent element (50/51) Block diagram
tCLP>>
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tCLP>>
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
&
(ON≡Inhibit)
Start I>>
I> inhibition
I> disbyl>>
≥1
CLP I>>
IL1
IL2
≥1
≥1
(Pickup within CLP)
(Pickup outside CLP)
ICLP>>def
ICLP>>inv
IL1 ≥ I>>
A =“1”
A =“0 or OFF”
IL3
&
State
I>>inv
IL1 ≥ I>>def
IL1 ≥ I>>inv
I>>def
&
State
Phase overcurrent (50/51) - Second element logic diagram (I>>)
NA30 - Manual - 04 - 2022
Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the second element (I>>)
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
I>>BLK2OUT
Start I>>
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
50-51S2_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1I>>
BLK4IN I>>
&
&
&
BLK2IN I>>
&
&
Enable (ON≡Enable)
I>>BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
I>>BLK2IN
Block1
BLK2IN-Iph
Start I>>
Trip I>>
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
I>> Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
I>>BLK4
Start I>>
C
B
A
“0”
“0”
B
“0” C
“0”
I>>BLK4
A
NA30 - Manual - 04 - 2022
Fun_50-51S3.ai
t >>>RES
T
0
RESET
t >>>def
0
T
≥1
t >>>def
t >>>RES
Start I>>>
Trip I>>>
CB-State
Start I2ndh>
ON≡Enable 3rd overcurrent element
Block1, Block2, Block4
&
I>>>TR-K
I>>>TR-L
I>>>ST-L
I>>>ST-K
T
0
tCLP>>>
&
2nd harmonic restraint enable (ON≡Enable)
I>>>2ndh-REST
ICLP>>>Mode
t CLP>>>
BF Enable (ON≡Enable)
I>>>BF
towards BF logic
I>>> BF
&
Trip I>>>
TRIPPING MATRIX
(LED+RELAYS)
A
B
C
Output tCLP>>>
I>>> Enable
I>>> overcurrent element (50/51) Block diagram
tCLP>>>
Output tCLP>>>
CB State
CB OPEN
CB CLOSED
CB OPEN
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
&
(ON≡Inhibit)
Start I>>>
Start I>>>
Start I>>>
(ON≡Inhibit)
I> inhibition
I> disbyl>>>
&
I>> inhibition
I>> disbyl>>>
≥1
CLP I>>>
IL1
IL2
≥1
(Pickup within CLP)
(Pickup outside CLP)
ICLP>>def
ICLP>>inv
IL1 ≥ I>>>
A =“1”
A =“0 or OFF”
IL3
&
State
IL1 ≥ I>>>def
I>>>def
Phase overcurrent (50/51) - Third element logic diagram (I>>>)
NA30 - Manual - 04 - 2022
Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the third element (I>>>)
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
I>>>BLK2OUT
Start I>>>
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
50-51S3_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1I>>>
BLK4IN I>>>
&
&
&
BLK2IN I>>>
&
&
Enable (ON≡Enable)
I>>>BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
I>>>BLK2IN
Block1
BLK2IN-Iph
Start I>>>
Trip I>>>
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
I>>> Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
I>>>BLK4
Start I>>>
C
B
A
“0”
“0”
B
“0” C
“0”
I>>>BLK4
A
NA30 - Manual - 04 - 2022
Residual overcurrent - 50N/51N
Preface
Three operation thresholds, independently adjustable (IE>, IE>>, IE>>>) with adjustable delay (tE>,
tE>>, tE>>>).
The first one (IE>) may be programmed with definite or inverse time according the IEC and ANSI/IEEE
standard, as well as with EM curve.
The second and third thresholds (IE>>, IE>>>) with independent time.
For each threshold a reset time can be set (tE>RES, tE>>RES, tE>>>RES) useful to reduce the clearing
time for intermittent faults.
The first threshold trip may be inhibited by start of the second and/or third threshold (IE>>, IE>>>).
Similarly the second threshold trip may be inhibited by start of the third threshold (IE>>>).
Operation and settings
The residual fundamental frequency current is compared with the setting value. Current above the
associated pickup value is detected and a start is issued. After expiry of the associated operate time
a trip command is issued; if instead the current drops below the threshold, the element is restored.
The first threshold (IE>) may be programmed with definite or inverse time according the following
characteristic curves:
• Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · tE>inv / [(IE/IE>inv)0.02 - 1]
• Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · tE>inv / [(IE/IE>inv) - 1]
• Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · tE>inv / [(IE/IE>inv)2 - 1]
• Moderately Inverse (ANSI/IEEE type MI):
t = tE>inv · {0.01 / [(IE/IE>inv)0.02 - 1] +
0.023}
• Very Inverse (ANSI/IEEE type VI):
t = tE>inv · {3.922 / [(IE/IE>inv)2 - 1] + 0.098}
• Extremely Inverse (ANSI/IEEE type EI):
t = tE>inv · {5.64 / [(IE/IE>inv)2 - 1] + 0.024}
• Electromechanical (EM):
t = tE>inv · {0.28 / [-0236 · (IE/IE>inv)-1 + 0.339]}
Where:
t:
operate time
IE >:
pickup value
tE >inv:
operate time setting
For all inverse time characteristics, following data applies:
• Asymptotic reference value (minimum pickup value): 1.1 IE>
• Minimum operate time:
0.1 s
• Range where the equation is valid:[1] 1.1 ≤ IE/IE>inv ≤ 20
• If IE>inv pickup ≥ 2.5 IEn, the upper limit is 10 IEn
For all definite time elements the upper limit for measuring is 10 IEn.
All residual overcurrent elements can be enabled or disabled by setting ON or OFF the IE> En-
able, IE>> Enable and/or IE>>> Enable parameters inside the Set \ Profile A(or B)\ Residual
overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus.
The first overcurrent element can be programmed with definite or inverse time characteristic by
setting the IE>Curve parameter (DEFINITE, IEC/BS A, IEC/BS B, IEC/BS C, ANSI/IEE MI,
ANSI/IEE VI, ANSI/IEE EI, EM) available inside the Set \ Profile A(or B) \ Residual overcurrent-
50N/51N \ IE> Element \ Setpoints menu.
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
t-int-F50N-51N.ai
IE
IE>>
IE>>>
tE>
tE>>
tE>>>
IE>
t
TRIP
General operation time characteristic for the residual overcurrent elements - 50N/51N
NA30 - Manual - 04 - 2022
The trip of IE> element may be inhibited by the start of the second and/or third el-
ement (IE>>, IE>>>) by setting ON the Disable IE> by start IE>>, Disable IE> by
start
IE>>>
(IE>disbyIE>>,
IE>disbyIE>>>)
parameters
available
inside
the
Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE>> Element (IE>>> Element) \ Setpoints
menus.
Similarly the trip of the IE>> element may be inhibited by start of the third element (IE>>>) by setting
ON the Disable IE>> by start IE>>> (IE>>disbyIE>>>) parameter available inside the Set \ Profile
A(or B) \ Residual overcurrent-50N/51N \ IE>>> Element \Setpoints menu.
All the named parameters can be set separately for Profile A and Profile B (Set \ Profile A(or B) \
Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus).
An adjustable reset time delay is provided for every threshold tE>RES, tE>>RES, tE>>>RES).
Each residual overcurrent element can produce the Breaker Failure output if the IE> BF, IE>> BF
and/or IE>>> BF parameters are set to ON. The parameters are available inside the Se \ Profile
A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints
menus.[1]
For all overcurrent elements, a block from the second harmonic restraint may be set by setting ON
the IE>2ndh-REST, IE>>2ndh-REST, IE>>>2ndh-REST parameters inside the Set \ Profile
A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints
menus.
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting ON-Element blocking the IECLP> Mode, IECLP>>
Mode, IECLP>>> Mode parameters.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure.
This operating mode (ON-Change setting = IECLP> Mode, IECLP>> Mode, IECLP>>>
Mode) and the concerning operating time within the CLP (tECLP>, tECLP>>, tECLP>>>) may be
adjusted inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element,
IE>>> Element) \ Setpoints menus, whereas the operating thresholds within the CLP ( IECLP>def,
IECLP>inv,....) may be adjusted inside the Set \ Profile A(or B)\ Residual overcurrent-50N/51N \
IE> Element (IE>> Element, IE>>> Element) \ Definite time (Inverse time) menus.
For every of the four thresholds the following block criteria are available:
Logical block (Block1)
If the IE>BLK1, IE>>BLK1 and/or IE>>>BLK1 enabling parameters are set to ON and a bi-
nary input is designed for logical block (Block1), the concerning element is blocked off whenever
the given input is active.[2] The enabling parameters are available inside the Set \ Profile A(or B)\
Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus, while
the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary
input IN1(x) menus.
Selective block (Block2)
All along the protective elements the selective block may be set.
The logic selectivity function may be performed by means any combination of the following I/O:
• One committed pilot wire input (BLIN1).
• One or more binary inputs designed for input selective block.
• One committed pilot wire output (BLOUT1).
• One or more output relays designed for output selective block.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu.
Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR-
ING section
Timers-F50N-51N.ai
IE> element residual overcurrent (50N/51N) - Timers
IE> Start
IE> Trip
tE>
tE>
RESET
INPUT
tE>RES
tE>RES
tE>RES
t
NA30 - Manual - 04 - 2022
IE
IE
IE
tE>> def
IECLP>> def
IE>> def
IECLP>>Mode
tECLP>>
tE>>RES
IE>> Enable
tE>>> def
IECLP>>> def
IE>>> def
IECLP>>>Mode
tECLP>>>
tE>>>RES
IE>>> Enable
tE> def
IECLP> def
IE> def
tE> inv
IECLP> inv
IE> inv
IE>Curve
IECLP>Mode
tECLP>
tE>RES
IE> Enable
all-F50N-51N.ai
General logic diagram of the residual overcurrent elements - 50N/51N
≥
IE>> inhibition
BLK1IE>>>
IE>>>BF
IE>>> Element
Start IE>>>
Start IE>>>
Start IE>>>
Trip IE>>>
Trip IE>>>
&
IE>> disbyIE>>>
&
IE>>>BLK2IN
&
IE> disbyIE>>>
BLK1IE>>
IE>> Element
BLK2OUT
Start IE>>
Start IE>>
Trip IE>>
&
IE> disbyIE>>
&
IE>>BLK1
&
IE>>BLK2IN
IE> inhibition
Block1
BLK1IE>
CLPIE>
CLPIE>>
CLPIE>>>
IE> Element
BLK2OUT
BLK4OUT
BLK4OUT
BLK2INIE>
BLK2INIE>>
Start IE>
Trip IE>
&
IE>BLK1
Block2
&
IE>BLK2IN
Start I2ndh>
&
IE>2ndh-REST
IE>BLK2OUT
Start I2ndh>
&
IE>>2ndh-REST
Start I2ndh>
&
IE>>>2ndh-REST
&
IE>>>BF
IE>>BF
IE>> Trip
&
IE>>BF
IE>BF
Trip I>
&
IE>BF
Start IE>
&
IE>>BLK2OUT
Start IE>> &
BLK2OUT
IE>>>BLK2OUT
Start IE>>> &
IE>BLK4
Start IE>
&
IE>>BLK4
Start IE>> &
BLK4OUT
IE>>>BLK4
Start IE>>> &
Block1
Block2
&
IE>>>BLK1
Block1
Block2
Start I>
&
Start IE>>
&
Start IE>>>
&
Start IE>>
&
BLK2INIE>>>
Start IE>>>
&
Start I>
&
NA30 - Manual - 04 - 2022
Only when the committed pilot wire are used the continuity check of the pilot wire link is active.
Use of committed pilot wire input BLIN1:
• The protection is blocked off according the selectivity block criteria when the input BLIN1 is active.
The information about phase or phase+earth block may be select programming the ModeBLIN1
parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus.
Use of binary inputs:
• If the IE>BLK2IN, IE>>BLK2IN and/or IE>>>BLK2IN parameters are set to ON and a
binary input is designed for selective block (Block2), the protection is blocked off by phase ele-
ments (Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block
criteria.[1] The enable IE>BLK2IN, IE>>BLK2IN and/or IE>>>BLK2IN parameters are avail-
able inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element,
IE>>> Element) \ Setpoints menus, while the Block2 Iph and Block2 Iph/IE functions must be
assigned to the selected binary inputs inside the Set \ Inputs \ Binary input IN1(x) menus (IN1 or
IN2 matching).
Use of committed pilot wire output BLOUT1:
• The information about phase or phase+earth block may be select programming the ModeBLOUT1
parameter (OFF - ON IPh - ON IPh/IE - ON IE) inside Set \ Profile A(or B) \ Selective block-
BLOCK2 \ Selective block OUT menus.
Use of output relay (K1...K6):
• If the IE>BLK2OUT, IE>>BLK2OUT and/or IE>>>BLK2OUT enable parameters are set to
ON and a output relay is designed for selective block (Block2), the protection issues a block output
by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), whenever the
given element (Start IED>, Start IED>>, Start IED>>> and/or Start IED>>>>) becomes active. The
enable IED>BLK2OUT, IED>>BLK2OUT, IED>>>BLK2OUT and/or IED>>>>BLK2OUT
parameters (ON or OFF) are available inside the Set \ Profile A(or B) \ Residual overcurrent-
50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus, while the BLK2OUT-
Iph-K, BLK2OUT-Iph/IE-K and/or BLK2OUT-IE-K output relays and LEDs (BLK2OUT-Iph-L,
BLK2OUT-Iph/IE-L e/o BLK2OUT-IE-L) must be select inside the Set \ Profile A(or B) \ Selec-
tive block-BLOCK2 \ Selective block OUT menu.
Internal selective block (Block4)
As well as to send or transmit a selective block toward other protective relays, each protective
element may be enabled for receive or transmit a selective block from/to other internal protective
elements.[2]
The internal selective block of one or more element concerning the residual overcurrent function
may be enabled/disabled by means the IE>BLK4, IE>>BLK4 and/or IE>>>BLK4 parameters
(virtual input and output common to all protective thresholds); the following operating modes are
available:
• IN - the element is enabled to receive the selective block from an internal input.
• OUT - the element is enabled to send the selective block to an internal output.
• OFF - the element is disabled to send/receive the internal selective block.
Transmission and reception for the same element is not allowed, so any stall situation due to wrong
setting is avoided.
The internal selective block can work together with an external selective block from other protective
relays (Block2).
Note 1 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND
MONITORING section
Nota 2 The exhaustive treatment of the internal selective block (Block 4) function may be found in the “Internal selective block” paragraph inside
CONTROL AND MONITORING section.
NA30 - Manual - 04 - 2022
0
T
RESET
tE>
0
T
Fun_50N-51NS1.ai
t >RES
T
0
≥1
tE>def
tE>inv
tE>RES
Start IE>
Trip IE>
CB-State
Start I2ndh>
ON≡Inhibit
(from IE>> and/or IE>>> residual overcurrent element)
ON≡Enable IE> residual overcurrent element
IE> inhibition
Block1, Block2, Block4
&
T
0
tECLP>
&
2nd harmonic restraint enable (ON≡Enable)
IE>2ndh-REST
IECLP>Mode
tECLP>
BF Enable (ON≡Enable)
IE>BF
towards BF logic
IE> BF
&
Trip IE>
TRIPPING MATRIX
(LED+RELAYS)
IE> Curve
A
B
C
A =“1”
A =“0 or OFF”
Output tECLP>
IE> Enable
IE> residual overcurrent element (50N/51N) Block diagram
tECLP>
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tECLP>
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
IE>TR-K
IE>TR-L
IE>ST-L
IE>ST-K
≥1
CLP IE>
IE
≥1
(Pickup within CLP)
(Pickup outside CLP)
IECLP>def
IECLP>inv
IE ≥ IECLP>
&
State
IE>inv
IE ≥ IE>def
IE ≥ IE>inv
IE>def
&
State
Residual overcurrent (50N/51N) - First element logic diagram (IE>)
NA30 - Manual - 04 - 2022
Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the first element (IE>)
IE>BLK1
Start IE>
Start IE>
Start IE>
Trip IE>
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
IE>BLK2OUT
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
50N-51NS1_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1IE>
BLK4IN IE>
&
&
&
BLK2IN IE>
&
&
Enable (ON≡Enable)
Block2 input enable (ON≡Enable)
Pilot wire input
&
IE>BLK2IN
Block1
BLK2IN-Iph
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
IE> Block4 OUT
Block4
Block4
Phase elements
≥1
I>> Block4 I/O
I> Block4 I/O
Phase elements
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
IE>BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
IE>BLK4
A
NA30 - Manual - 04 - 2022
Fun_50N-51NS2.ai
tE>>RES
T
0
RESET
tE>>def
0
T
≥1
tE>>def
tE>>RES
Start IE>>
Trip IE>>
CB-State
Start I2ndh>
IE>> inhibition
Block1, Block2, Block4
&
IE>>TR-K
IE>>TR-L
IE>>ST-L
IE>>ST-K
T
0
tECLP>>
&
2nd harmonic restraint enable (ON≡Enable)
IE>>2ndh-REST
IECLP>>Mode
tECLP>>
BF Enable (ON≡Enable)
IE>>BF
towards BF logic
IE>> BF
&
Trip IE>>
TRIPPING MATRIX
(LED+RELAYS)
A
B
C
Output tECLP>>
IE>> Enable
IE>> residual overcurrent element (50N/51N) Block diagram
tECLP>>
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tECLP>>
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
&
(ON≡Inhibit)
Start IE>>
Start IE>>
IE> inhibition
IE> disbylE>>
≥1
CLP IE>>
ON≡Inhibit
(from IE>>> residual overcurrent element)
ON≡Enable IE>> residual overcurrent element
IE>>def
A =“1”
A =“0 or OFF”
IE
(Pickup within CLP)
(Pickup outside CLP)
IECLP>>def
IE ≥ IECLP>>def
&
State
IE ≥ IE>>def
Residual overcurrent (50N/51N) - Second element logic diagram (IE>>)
NA30 - Manual - 04 - 2022
Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the second element (IE>>)
IE>>BLK1
Start IE>>
Start IE>>
Start IE>>
Trip IE>>
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
IE>>BLK2OUT
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
50N-51NS2_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1IE>>
BLK4IN IE>>
&
&
&
BLK2IN IE>>
&
&
Enable (ON≡Enable)
Block2 input enable (ON≡Enable)
Pilot wire input
&
IE>>BLK2IN
Block1
BLK2IN-Iph
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
IE>> Block4 OUT
Block4
Block4
Phase elements
≥1
I>> Block4 I/O
I> Block4 I/O
Phase elements
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
IE>>BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
IE>>BLK4
A
NA30 - Manual - 04 - 2022
Fun_50N-51NS3.ai
tE>>>RES
T
0
RESET
tE>>>def
0
T
≥1
tE>>>def
tE>>>RES
Start IE>>>
Trip IE>>>
CB-State
Start I2ndh>
ON≡Enable IE>>> residual overcurrent element
Block1, Block2, Block4
&
IE>>>TR-K
IE>>>TR-L
IE>>>ST-L
IE>>>ST-K
T
0
tECLP>>>
&
2nd harmonic restraint enable (ON≡Enable)
IE>>>2ndh-REST
IECLP>>>Mode
tECLP>>>
BF Enable (ON≡Enable)
IE>>>BF
towards BF logic
IE>>> BF
&
Trip IE>>>
TRIPPING MATRIX
(LED+RELAYS)
A
B
C
A = ON - Change setting
B = OFF
C = ON - Element blocking
Output tECLP>>>
IE>>> Enable
IE>>> residual overcurrent element (50N/51N) Block diagram
tECLP>>>
CB State
CB OPEN
CB CLOSED
CB OPEN
Output tECLP>>>
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
&
(ON≡Inhibit)
Start IE>>>
Start IE>>>
Start IE>>>
(ON≡Inhibit)
IE> inhibition
IE>disbylE>>>
&
IE>> inhibition
IE>>disbylE>>>
≥1
CLP IE>>>
IE>>>def
A =“1”
A =“0 or OFF”
IE
(Pickup within CLP)
(Pickup outside CLP)
IECLP>>>def
IE ≥ IECLP>>>def
&
State
IE ≥ IE>>>def
Residual overcurrent (50N/51N) - Third element logic diagram (IE>>>)
NA30 - Manual - 04 - 2022
Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the third element (IE>>>)
IE>>>BLK1
Start IE>>>
Start IE>>>
Start IE>>>
Trip IE>>>
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON≡Enable)
IE>>>BLK2OUT
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
50N-51NS3_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1IE>>>
BLK4IN IE>>>
&
&
&
BLK2IN IE>>>
&
&
Enable (ON≡Enable)
Block2 input enable (ON≡Enable)
Pilot wire input
&
IE>>>BLK2IN
Block1
BLK2IN-Iph
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
IE>>> Block4 OUT
Block4
Block4
Phase elements
≥1
I>> Block4 I/O
I> Block4 I/O
Phase elements
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
IE>>>BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
IE>>>BLK4
A
NA30 - Manual - 04 - 2022
Residual overvoltage - 59N
Preface
Two operation thresholds, independently adjustable (UE>, UE>>) with adjustable delay (tUE>, tUE>>).
The first one (UE>) may be programmed with definite or inverse time, while the second threshold
operates with definite time characteristic.
Each threshold may be separately enabled or disabled.
The first threshold trip (UE>) may be inhibited by start of the second threshold (UE>>).
Operation and settings
The residual voltage (UE) is compared with the setting values (UE>, UE>>); a start is issued when the
residual voltage overcomes the adjustable threshold (START); after expiry of the associated operate
time (tUE>, tUE>>) a trip command is issued; if instead the voltage drops below the threshold, the
element is restored.
The first threshold (UE>) may be programmed with definite or inverse time according the following
characteristic curve:
t=0.5 tUE> / [(UE/UE>inv) - 1] or
Where:
UE:
measured residual voltage
t:
operate time
UE>inv:
threshold setting
tUE>inv:
operate time setting
For the inverse time characteristic, following data applies:
• The operate time setting is referred to an input voltage equal to 1.5 of the pickup value.
• Asymptotic reference value (minimum pickup value): 1.1 UE>inv
• Minimum operate time:
0.1 s
• Range where the equation is valid: 1.1 ≤ UE/UE>inv ≤ 4
• If UE>inv pickup ≥ 0.5 UEn, the upper limit is 2 UEn.
The first residual overvoltage element can be programmed with definite or inverse time character-
istic by setting the UE> Curve parameter (DEFINITE, INVERSE) available inside the Set \ Profile
A(or B) \ Residual overvoltage-59N \ UE> Element \ Setpoints menu.
Each element can be enabled or disabled by setting ON or OFF the UE> Enable parameter inside
the Set \ Profile A(or B) \ Residual overvoltage-59N \ UE> Element \ Setpoints menu and/or the State
parameter inside the Set \ Profile A(or B) \ Residual overvoltage-59N \ UE>> Element \ Definite time.
For both elements, a block of the UE> and UE>> threshold may be select when the 74VT function is
active (external). The blocking enabling parameters 74VText59N is available inside the Set \ Pro-
file A(or B) \ Residual overvoltage-59N \ Common configuration menu.[1]
The first threshold trip (UE>) may be inhibited by start of the second threshold (UE>>) by setting ON
the UE> Disabling by UE>> start (UE>disbyUE>>) parameter available inside the Set \ Profile A(or
B) \ Residual overvoltage-59N \ UE>> Element \ Setpoints menu.
Note 1 The operating time must be adjusted to a greater value than the 74VT activation time (internal or binary input)
t-int-F59N.ai
UE
UE>>
tUE>
tUE>>
UE>
t
TRIP
General operation time characteristic for the residual overvoltage elements - 59N
NA30 - Manual - 04 - 2022
An adjustable reset time delay is provided for every threshold tUE>RES, tUE>>RES, tUE>>>RES).
Both residual overvoltage elements (UE>, UE>>) can produce the Breaker Failure output if the
UE>BF and UE>>BF parameters are set to ON.
The parameters are available inside the Set \ Profile A(or B) \ Residual overvoltage - 59N \
UE> Element (UE>> Element) \ Setpoints menus.[1]
For every of the two thresholds the following block criteria are available:
Logical block (Block1)
If the UE>BLK1 and/or UE>>BLK1 enabling parameters are set to ON and a binary input is de-
signed for logical block (Block1), the protection is blocked off whenever the given input is active.
The trip timer is held in reset condition, so the operate time counting starts when the input block
goes down.[2] The enabling parameters are available inside the Set \ Profile A(or B) \ Residual over-
voltage - 59N \ UE> Element (UE>> Element) \ Setpoints menus, while the Block1 function must be
assigned to the selected binary input inside the Set \ Inputs \ Binary input IN1(x) menus (IN1 or INx
matching).
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu.
Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR-
ING section.
Timers-F59N.ai
UE> Start
UE> Trip
tUE>
tUE>
RESET
INPUT
tUE>RES
tUE>RES
tUE>RES
t
Teimers concerning the first element of residual overvoltage protection- 59N
Logic diagram concerning the residual overvoltage element - 59N
all-F59N.ai
UE
UE> Element
UE>> Element
Start U>>
Start UE>>
Start UE>
Trip UE>
Trip UE>>
&
UE> disbyUE>>
U> inhibition
tUE> def
tUE> inv
UE>def
tUE>> def
tUE>>RES
tUE>RES
UE>>def
UE> inv
UE> Curve
UE> Enable
State
Block1
BLK1UE>
&
UE>BLK1
Start UE>
&
Block1
BLK1UE>>
&
UE>>BLK1
Start UE>>
&
UE>BF
Trip UE>
&
UE>BF
&
UE
&
74VText-Block
74VText-Block
74VText-Block
&
74VText
Common configuration
74VText59 N
NA30 - Manual - 04 - 2022
Logic diagram concerning the first threshold (UE>) of the residual overvoltage element - 59N
Fun-F59N_S1.ai
≥1
UE> Inhibition
(ON≡Inhibit)
Block 74VTExt59N
(ON≡Inhibit)
&
UE> Curve
0
T
RESET
tUE>
0
T
TRIPPING MATRIX
(LED+RELAYS)
tUE>def
tUE>inv
Start UE>
UE>ST-K
UE>ST-L
Start UE>
Trip UE>
UE>TR-K
UE>TR-L
Trip UE>
Block1 UE>
74VT ext.
Trip UE>
BF Enable (ON≡Enable)
UE>BF
towards BF logic
&
UE> BF
&
&
&
Enable (ON≡Enable)
Block1 input (ON≡Block)
Block1
Block1
Block1
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
74VText.
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
t UE>RES
T
0
t UE>RES
ON≡Enable UE> residual overvoltage element
UE> Enable
UE
UE>def
UE>inv
≥1
&
State
UE ≥ UE>def
UE ≥ UE>inv
&
State
Logic diagram concerning the second threshold (UE>>) of the residual overvoltage element - 59N
Fun-F59N_S2.ai
≥1
&
RESET
tUE>>
0
T
TRIPPING MATRIX
(LED+RELAYS)
tUE>>def
Start UE>>
UE>>ST-K
UE>>ST-L
Start UE>>
Trip UE>>
UE>>TR-K
UE>>TR-L
Trip UE>>
Trip UE>>
BF Enable (ON≡Enable)
UE>>BF
towards BF logic
&
Block1 UE>>
74VT ext.
UE>> BF
&
&
&
Enable (ON≡Enable)
Block1 input (ON≡Block)
Block1
Block1
Block1
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
74VText.
Binary input INx (x=1,...5)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
t UE>>RES
T
0
t UE>>RES
UE
UE>>def
&
State
UE ≥ UE>>def
&
(ON≡Inhibit)
UE> Inhibition
UE>disbyUE>>
Block 74VTExt59N
(ON≡Inhibit)
NA30 - Manual - 04 - 2022
Inverse time operating characteristic concerning the first threshold (UE>) of the residual overvoltage element - 59N
F_59N-Char.ai
1.1
2
3
4
t UE>= 100 s
t UE>= 10 s
t UE>= 1 s
t UE>= 0.1 s
1.5
0.01
0.1
1
10
100
1000
10000
t [s]
Note: match of operating and setting time takes place when UE /UE>inv = 1.5
t =tUE>inv · [(UE /UE>inv) - 1]
0.5
UE /UE>inv
NA30 - Manual - 04 - 2022
Ground directional overcurrent - 67N
Preface
Four operation thresholds, independently adjustable (IED>, IED>>, IED>>> ,IED>>>>) with adjustable delay
(tED>, tED>>, tED>>>, tED>>>>).
Each element can be enabled or disabled.
The first two may be programmed with definite or inverse time according the IEC and ANSI/IEEE
standard, as well as with rectifier, EM curve.
The third and fourth thresholds with independent time.
Moreover several predefined blocking criteria are implemented (threshold trip may be inhibited by
start of the other thresholds, logic selectivity with internal and/or external elements, etc.).
Operation and settings
The first and second threshold (IED>, IED>>) may be programmed with definite or inverse time ac-
cording the following characteristic curves:
• Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · tED>inv / [(IED/IED>inv)0.02 - 1]
• Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · tED>inv / [(IPD/IED>inv) - 1]
• Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · tPD>inv / [(IED/IED>inv)2 - 1]
• Moderately Inverse (ANSI/IEEE type MI):
t = tED>inv · {0.01 / [(IED/IED>inv)0.02 - 1] + 0.023}
• Very Inverse (ANSI/IEEE type VI):
t = tED>inv · {3.922 / [(IED/IED>inv)2 - 1] + 0.098}
• Extremely Inverse (ANSI/IEEE type EI):
t = tED>inv · {5.64 / [(IED/IED>inv)2 - 1] + 0.024}
• Electromechanical (EM):
t = tED>inv · {0.28 / [-0236 · (IED/IED>inv)-1 + 0.339]}
Where:
t:
operate time
IED>inv:
first and second threshold setting (IED>inv, IED>>inv)
tED>inv:
first and second threshold operate time setting (tPD>inv, tPD>>inv)
Third and fourth threshold (IED>>>def, IED>>>>def) with definite time.
For all inverse time characteristics, following data applies:
• Asymptotic reference value (minimum pickup value): 1.1 IED> or IED>>
• Minimum operate time:
0.1 s
• Range where the equation is valid:[1] 1.1 ≤ IED/IED>inv (or IED>>inv) ≤ 20
• If IED>inv (or IED>>inv) pickup ≥ 0.5 IEn, the upper limit is 10 IEn
For all definite time elements the upper limit for measuring is 50 In.
Two different criteria may be selected:
• Residual current threshold overcoming (module)
• Projection residual current threshold overcoming (projection)
The operating mode may be selected by setting the Mode67N parameter, located inside the Set \
Profile A(or B) \ Directional earth fault overcurrent-67N \ Common configuration menu.
The settable operating mode is I (module) or I*cos (projection).
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
t-int-F67N.ai
IED
IED>>
IED>>>
IED>>>>
tED>
tED>>
tED>>>
tED>>>>
IED>
t
TRIP
General operation time characteristic for the ground directional overcurrent elements - 67N
NA30 - Manual - 04 - 2022
For both the operating modes, the measured UE voltage is employed as polarizing reference for
displacement measure of the residual current.
The displacement of the residual current phasor IE and the residual voltage phasor (UE), positive for
lagging current compared with voltage (ΦE=(∠IE - ∠UE).
For each of the four thresholds (IED>, IED>>, IED>>>, IED>>>>) , the characteristic angle (ϑE>, ϑE>>,
ϑE>>>, ϑE>>>>) may be adjusted (setting range 0…359° common for the three phases).
The the characteristic angle setting (positive when clockwise compared the polarizing voltage)
specifies the angular displacement of the characteristic axis standing for the trip bisector of the
tripping zone.
For isolated neutral systems with a 90° characteristic angle setting, faults towards the LINE are
detected, while with a 270° characteristic angle setting, faults towards the BUS are detected.
All the named parameters can be set separately for the four thresholds and for definite or inverse
time settings menu
For each of the four thresholds (IED>, IED>>, IED>>>, IED>>>>), the half operating sector may be ad-
justed (setting range 0…180° simmetrically regarding the characteristic axis).
All the named parameters can be set separately for the four thresholds and for definite or inverse
time settings menu.
For all the four thresholds (IED>, IED>>, IED>>>, IED>>>>), the operating mode when the 74VT function is
active may be defined:
• OFF: no action are issued by 74VT.
• Block: all the four thresholds are blocked when the 74VT function is active.
• Not directional: all the four thresholds are switched from directional to not directional criteria
when the 74VT function is active.
The 74VT information may be issued from an external signal acquired by means a binary input.
If a binary input is designed for 74VText, for all the four thresholds, the operating mode when the 74VT
function is active may be defined:
char-F67N-mode.ai
Operating characteristics of the earth fault overcurrent element - 67N
with module operating mode (I)
Operating characteristics of the earth fault overcurrent element - 67N
with projection operating mode ( I∙cos)
IE
UE
UEC
Characteristic axis
Characteristic axis
ΦE o ΦEC
Half operating sector
(βE>, βE>>, βE>>>, βE>>>>)
Half operating sector
(βE>, βE>>, βE>>>, βE>>>>)
Half operating sector
(βE>, βE>>, βE>>>, βE>>>>)
Half operating sector
(βE>, βE>>, βE>>>, βE>>>>)
Threshold (IED threshold):
(IED>, IED>>, IED>>>, IED>>>>)
(M∙IED>, M∙IED>>, M∙IED>>>, M∙IED>>>>)
Threshold (IED threshold):
(IED>, IED>>, IED>>>, IED>>>>)
(M∙IED>, M∙IED>>, M∙IED>>>, M∙IED>>>>)
IE
ΦE o ΦEC
Characteristic angle
Characteristic angle
(ΘE>, ΘE>>, ΘE>>>, ΘE>>>>)
(ΘE>, ΘE>>, ΘE>>>, ΘE>>>>)
UE
UEC
IE ≥ IED threshold
IED threshold
IE
I
I∙cos
Mode67N
IE∙COS(ϑE-ΦE) ≥ IED threshold
IED threshold
IE
I
I∙cos
Mode67N
ΦE o ΦEC
UE
UEC
3Votype67N
NA60
BUSBAR
IE
UE
RESIDUAL
VOLTAGE INPUT
B7 terminal
C7 terminal
RESIDUAL
CURRENT INPUT
Trip sector
(toward line)
Trip sector
(toward line)
No trip sector
(toward busbar)
No trip sector
(toward busbar)
Operating characteristics of the ground directional overcurrent elements - 67N
LINE
NA30 - Manual - 04 - 2022
• OFF: no action are issued by 74VT.
• Block: all the four thresholds are blocked when the 74VT external signal is active.
• Not directional: all the four thresholds are switched from directional to not directional criteria
when the 74VT external signal is active.
Malfunctioning of the directional overcurrent elements can be avoided when VTs secondary fault
will arise (fuse or MCB tripping) by switching the overcurrent directional to non directional overcur-
rent protection
The 74VText67N parameter may be set as OFF, Block, Not directional inside the Set \ Profile
A(or B) \ Directional earth fault overcurrent-67N \ Common configuration menu, while the 74VText
function must be assigned to the selected binary inputs inside the Set \ Inputs \ Binary input IN1(...x)
menus (IN1 or ...INx matching).
For all the four thresholds (common for all thresholds) an insensibility zone may be enabled in the
voltage-current plane.
If enabled, the insensibility zone is user adjustable by means the M multiplier (common for all thresh-
olds); the rectangle defined by the current and voltage thresholds and the same multiplied by M
becomes a No trip zone.
Such insensibility zone may be useful to avoid unwanted trip in the presence of some fixed residual
current and/or voltage (e.g. CT and or VT errors in the residual measurements).
The Insens-Zone (OFF, ON) and M parameters may be adjusted inside the Set \ Profile A(or B)\Di-
rectional earth fault overcurrent-67N \ Common configuration menu.
Module
If the module principle and the operation mode is not switched to “not directional” (by the 74VT
function), the start of any 67N threshold becomes active when the following A) and B) conditions
are contemporaneously active:
A) in the “Insens-Zone=OFF” operating mode:
- The residual current (IE) fundamental component overcomes the threshold (IED>, IED>>, IED>>>, IED>>>>)
AND
- The residual voltage (UE or UEC) fundamental component overcomes the threshold (UED>, UED>>,
UED>>>, UED>>>>),
while in the “Insens-Zone=ON” operating mode:
- The residual current (IE) fundamental component overcomes the threshold (IED>, IED>>, IED>>>, IED>>>>)
AND
- The residual current (IE) fundamental component overcomes the threshold (M∙UED>, M∙UED>>,
M∙UED>>>, M∙UED>>>>)
OR
- The residual current (IE) fundamental component overcomes the threshold (M∙IED>, M∙IED>>, M∙IED>>>,
M∙IED>>>>)
char-F67N-IeUe.ai
Voltage/current characteristic concerning the earth fault overcurrent element - 67N
with insensibility zone disabled
Voltage/current characteristic concerning the ground directional overcurrent - 67N
with insensibility zone enabled
IE
IED>, IED>>, IED>>>, IED>>>>
M∙IED>, M∙IED>>, M∙IED>>>, M∙IED>>>>
M∙UED>, M∙UED>>, M∙UED>>>, M∙UED>>>>
TRIP
UE
UEC
IE
IED>, IED>>, IED>>>, IED>>>>
TRIP
UE
UEC
UED>, UED>>, UED>>>, UED>>>>
UED>, UED>>, UED>>>, UED>>>>
NA30 - Manual - 04 - 2022
AND
The residual voltage (UE) fundamental component overcomes the threshold (UED>, UED>>, UED>>>,
UED>>>>).
B) The residual current phasor (IE) is located inside the angular sector defined by own characteristic
angle (βE>, βE>>, βE>>>, βE>>>>) and half operating sector (ΘE>, ΘE>>, ΘE>>>, ΘE>>>>), that is the
-βE ≤ (ΘE-ΦE) ≤ +βE condition is fulfilled.
If the operation mode is switched to “not directional” (by the 74VT function), the start of any 67N
threshold becomes active when the following is complied:
- The residual current (IE) fundamental component overcomes the threshold (IED>, IED>>, IED>>>,
IED>>>>)
The operating mode (Mode67N), the residual voltage measurement type (Type67N), the insensi-
bility zone enabling (Insens-Zone), the threshold multiplier for the insensibility zone (M) and the
operation from 74VT (74VText67N) may be selected by setting the concerning parameters, located
inside the Set \ Profile A(or B) \ Directional earth fault overcurrent-67N \ Common configuration
menu.
The settable operating mode is I (module) or I*cos (projection).
Projection
If the projection principle and he operation mode is not switched to “not directional” (by the 74VT
function), the start of any 67N threshold becomes active when the following C) condition is active:
C) in the “Insens-Zone=OFF” operating mode:
- Residual current projection on the characteristic axis IE∙cos(ΦE-ΘE) > 0
AND
- The residual current projection on the characteristic axis IE∙cos(ΦE-ΘE) overcomes the threshold
(IED>, IED>>, IED>>>, IED>>>>)
AND
- The residual voltage (UE) fundamental component overcomes the threshold (UED>, UED>>, UED>>>,
UED>>>>).
AND
The residual current phasor (IE) is located inside the angular sector defined by own characteristic
angle (βE>, βE>>, βE>>>, βE>>>>) and half operating sector (ΘE>, ΘE>>, ΘE>>>, ΘE>>>>), that is the
-βE ≤ (ΘE-ΦE) ≤ +βE condition is fulfilled.[1]
While in the “Insens-Zone=ON” operating mode:
- Residual current projection on the characteristic axis IE∙cos(ΦE-ΘE) > 0
AND
- The residual current projection on the characteristic axis IE∙cos(ΦE-ΘE) overcomes the threshold
(IED>, IED>>, IED>>>, IED>>>>)
AND
- The residual voltage (UE) fundamental component overcomes the threshold (M∙UED>, M∙UED>>,
M∙UED>>>, M∙UED>>>>)
OR
The residual current projection on the characteristic axis IE∙cos(ΦE-ΘE) overcomes the threshold
(M∙IED>, M∙IED>>, M∙IED>>>, M∙IED>>>>)
AND
- The residual voltage (UE or UEC) fundamental component overcomes the threshold (UED>, UED>>,
UED>>>, UED>>>>).
AND
The residual current phasor (IE) is located inside the angular sector defined by own characteristic
angle (βE>, βE>>, βE>>>, βE>>>>) and half operating sector (ΘE>, ΘE>>, ΘE>>>, ΘE>>>>), that is the
-βE ≤ (ΘE-ΦE) ≤ +βE condition is fulfilled.[2]
If the operation mode is switched to “not directional” (by the 74VT function), the start of any 67N
threshold becomes active when the following is complied:
- The residual current (IE) fundamental component overcomes the threshold (IED>, IED>>, IED>>>,
IED>>>>)
For both the operating mode (module or projection), when the start signal goes ON a concerning
counter starts; after expiry of the associated operate time (tED>, tED>>, tED>>>, tED>>>>) a trip command
is issued, if instead the above conditions don’t remain valid, the element it is restored.
All the parameters are located inside the menus concerning the four elements, separately for defi-
nite and inverse time characteristics.
Example: the operate time concerning the first threshold with definite time characteristic (IED>def)
is available inside the Set \ Profile A(or B) \ Directional earth fault overcurrent-67N \ IED> Element
\ Definite time menu.
Note 1 For each threshold the projection of the residual current phasor on the characteristic axis is: IEcos(ΘE>-ΦE), IEcos(ΘE>>-ΦE), IEcos(ΘE>>>-ΦE),
IEcos(ΘE>>>>-ΦE) when “direct” residual voltage is selected (UE), or
IEcos(ΘE>-ΦEC), IEcos(ΘE>>-ΦEC), IEcos(ΘE>>>-ΦEC), IEcos(ΘE>>>>-ΦEC) when “calculated” residual voltage is selected (UEC).
The ΘE , βE and ΦEC symbols are not used inside the ThyVisor and MMI menus.
Note 2 For each threshold the projection of the residual current phasor on the characteristic axis is: IEcos(ΘE>-ΦE), IEcos(ΘE>>-ΦE), IEcos(ΘE>>>-ΦE),
IEcos(ΘE>>>>-ΦE) when “direct” residual voltage is selected (UE), or
IEcos(ΘE>-ΦEC), IEcos(ΘE>>-ΦEC), IEcos(ΘE>>>-ΦEC), IEcos(ΘE>>>>-ΦEC) when “calculated” residual voltage is selected (UEC).
The ΘE , βE and ΦEC symbols are not used inside the ThyVisor and MMI menus.
NA30 - Manual - 04 - 2022
All directional earth fault overcurrent elements can be enabled or disabled by setting ON or OFF the
IED> Enable, IED>> Enable, , IED>>> Enable e/o IED>>>> Enable parameters inside
the Set \ Profile A(or B) \ Directional earth fault overcurrent-67N \ IED> Element (IED>> Element,
IED>>> Element, IED>>> Element) \ Setpoints menus.
The first and second overcurrent element can be programmed with definite or inverse time charac-
teristic by setting theIED>Curve and/or IED>>Curve (DEFINITE, IEC/BS A, IEC/BS B, IEC/
BS C, ANSI/IEE MI, ANSI/IEE VI, ANSI/IEE EI, EM) available inside the Set \ Profile A(or B) \
Directional earth fault overcurrent-67N \ IED> Element (IED>> Element) \ Setpoints menus.
The trip of IED> element may be inhibited by the start of the second, third and/or fourth element (IED>>,
IED>>>, IED>>>>) by setting ON the Disable IED> by start IED>>, Disable IED> by start IED>>>, Dis-
able IED> by start IED>>>> (IED>disbyIED>>, IED>disbyIED>>>, IED>disbyIED>>>>)
parameters available inside the Set \ Profile A(or B) \ Directional earth fault overcurrent-67N
\ IED>> Element (IED>>> Element, IED>>>> Element) \ Setpoints menus.
Similarly the trip of the:
• IED>> element may be inhibited by start of the third and/or fourth element (IED>>> and/or IED>>>>)
by setting ON the Disable IED>> by start IED>>>, start IED>>>> (IED>>disbyIED>>>,
IED>>disbyIED>>>>) parameter available inside the Set \ Profile A(or B) \ Directional earth
fault overcurrent-67N \ IED>>> Element (IED>>>> Element) \S etpoints menus.
• IED>>> element may be inhibited by start of the fourth element (IED>>>>) by setting ON the Dis-
able IED>>> by start IED>>>> (IED>>>disbyIED>>>>) parameter available inside the Set \
Profile A(or B) \ Directional earth fault overcurrent-67N \ IED>>>> Element \ Setpoints menu.
All the named parameters can be set separately for Profile A and Profile B.
An adjustable reset time delay is provided for every threshold (tED>RES, tED>>RES, tED>>>RES, tED>>>RES).
Each directional earth fault element can produce the Breaker Failure output if the IED> BF, IED>>
BF, IED>>> BF and/or IED>>>> BF parameters are set to ON. The parameters are available
inside the Set \ Profile A(or B) \ Directional earth fault overcurrent-67N \ IED> Element (IED>> Ele-
ment, IED>>> Element, IED>>> Element) \ Setpoints menus.[1]
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting ON-Element blocking the IEDCLP> Mode, IED-
CLP>> Mode, IEDCLP>>> Mode, IEDCLP>>>> Mode parameters.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure.
This operating mode (ON-Change setting = IEDCLP> Mode, IEDCLP>> Mode, IED-
CLP>>> Mode, IEDCLP>>>> Mode) and the concerning operating time within the CLP (tED-
CLP>, tEDCLP>>, tEDCLP>>>, tEDCLP>>>>) may be adjusted inside the Set \ Profile
A(or B) \ Directional earth fault overcurrent-67N \ IED> Element (IED>> Element, IED>>> Element,
IED>>> Element) \ Setpoints menus, whereas the operating thresholds within the CLP ( IEDCLP>def,
IEDCLP>inv,....) may be adjusted inside the Set \ Profile A(or B) \ Directional earth fault overcur-
rent-67N \ IED> Element (IED>> Element, IED>>> Element, IED>>> Element) \ Definite time (Inverse
time) menus.
For every of the four thresholds the following block criteria are available:
Logical block (Block1)
If the IED>BLK1, IED>>BLK1, IED>>>BLK1 and/or IED>>>>BLK1 enabling parameters
are set to ON and a binary input is designed for logical block (Block1), the concerning element
is blocked off whenever the given input is active.[2] The enabling parameters are available inside
the Set \ Profile A(or B) \ Directional earth fault overcurrent-67N \ IED> Element (IED>> Element,
IED>>> Element, IED>>> Element) \ Setpoints menus, while the Block1 function must be assigned
to the selected binary input inside the Set \ Inputs \ Binary input IN1(x) menus.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu.
Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR-
ING section
Timers-F67N.ai
IED> Start
IED> Trip
tED>
tED>
RESET
INPUT
tED>RES
tED>RES
tED>RES
t
IED> element timers - 67N
NA30 - Manual - 04 - 2022
General logic diagram of the ground directional overcurrent elements - 67N
all-F67N.ai
Start IED>>
&
IED> disbyIED>>
tED>> def
IEDCLP>>def
IED>>def
tED>> inv
IEDCLP>>inv
IED>>inv
IED>>Curve
IEDCLP>>Mode
tEDCLP>>
tED>>RES
IED>> Enable
CLPIED>
CLPIED>>
IED> Element
IED>> Element
Start IED>
Trip IED>
Start IED>>
Trip IED>>
IED>>BF
&
IED>>BF
Trip IED>>
IED>BF
Trip IED>
&
IED>BF
BLK2OUT
IED>BLK2OUT
Start IED>
&
BLK2OUT
IED>>BLK2OUT
Start IED>>
&
BLK4OUT
IED>BLK4
Start IED>
&
BLK4OUT
IED>>BLK4
Start IED>>
&
tED> def
IEDCLP> def
IED> def
tED> inv
IEDCLP> inv
IED> inv
IED>Curve
IEDCLP>Mode
tEDCLP>
tED>RES
IED> Enable
≥
IED> inhibition
≥
IED>> inhibition
IED>>> inhibition
Block1
BLK1IED>
&
IED>BLK1
Start IED> &
&
IED>>BLK2IN
BLK2INIED>>
Block2
Start IED>>
&
BLK2INIED>
Block2
&
IED>BLK2IN
Start IED>
&
BLK1IED>>
&
IED>>BLK1
Block1
Start IED>>
&
IE
UE
UE
UE
UE
tED>>> def
IEDCLP>>>def
IED>>>def
IEDCLP>>>Mode
tEDCLP>>>
tED>>>RES
IED>>> Enable
Start IED>>>
&
IED> disbyIED>>>
Start IED>>>
&
IED>> disbyIED>>>
CLPIED>>>
CLPIED>>>>,
IED>>> Element
Start IED>>>
Trip IED>>>
Start I2ndh>
IED>>>BF
IED>>>>BF,
&
IED>>>BF
Trip IED>>>
BLK2OUT
BLK2OUT, BLK4OUT
IED>>>BLK2OUT
Start IED>>>
&
BLK4OUT
IED>>>BLK4
Start IED>>>
&
&
IED>>>BLK2IN
BLK2INIED>>>
BLK2INIED>>>>,
Block2
Start IED>>>
&
BLK1IED>>>
BLK1IED>>>>,
&
IED>>>BLK1
Block1
Block1
Block2
Start IED>>>
&
tED>>>>def
IEDCLP>>>>def
IED>>>>def
IEDCLP>>>>Mode
tEDCLP>>>>
tED>>>>RES
IED>>>> Enable
Start IED>>>>
&
IED> disIED>>>>
Start IED>>>>
&
IED>> disIED>>>>
IED>>>> Element
Start IED>>>>
Trip IED>>>>
Start IED>>>>
&
IED>>> disIED>>>>
IE
IE
IE
Common configurations
Insens-Zone
OFF
ON
IE
I
I∙cos
Mode67N
≥ M∙threshold
M
NA30 - Manual - 04 - 2022
Selective block (Block2)
All along the protective elements the selective block may be set.
The logic selectivity function may be performed by means any combination of the following I/O:
• One committed pilot wire input (BLIN1).
• One or more binary inputs designed for input selective block.
• One committed pilot wire output (BLOUT1).
• One or more output relays designed for output selective block.
Only when the committed pilot wire are used the continuity check of the pilot wire link is active.
Use of committed pilot wire input BLIN1:
• The protection is blocked off according the selectivity block criteria when the input BLIN1 is active.
The information about phase or phase+earth block may be select programming the ModeBLIN1
parameter inside the Set\Profile A(or B)\Selective block-BLOCK2\ Selective block IN menus.
Use of binary inputs:
• If the IED>BLK2IN, IED>>BLK2IN, IED>>>BLK2IN and/or IED>>>>BLK2IN parameters
are set to ON and a binary input is designed for selective block (Block2), the protection is blocked
off by phase elements (Block2 Iph) or by any protection element (Block2 Iph/IE) according the se-
lectivity block criteria.[1] The enable IED>BLK2IN, IED>>BLK2IN, IED>>>BLK2IN and/or
IED>>>>BLK2IN parameters are available inside the Set\Profile A(or B)\Directional earth fault
overcurrent-67N \ IED> Element (IED>> Element, IED>>> Element, IED>>>> Element) \Setpoints
menus, while the Block2 Iph and Block2 Iph/IE functions must be assigned to the selected
binary inputs inside the Set \ Inputs \ Binary input IN1(2) menus (IN1 or IN2 matching).
Use of committed pilot wire output BLOUT1:
• The information about phase or phase+earth block may be select programming the ModeBLOUT1
parameter (OFF - ON IPh - ON IPh/IE - ON IE) inside Set\Profile A(or B)\Selective block-
BLOCK2\ Selective block OUT menus.
Use of output relay (K1...K6):
• If the IED>BLK2OUT, IED>>BLK2OUT, IED>>>BLK2OUT and/or IED>>>>BLK2OUT
enable parameters are set to ON and a output relay is designed for selective block (Block2), the
protection issues a block output by phase elements (BLK2OUT-Iph) or by any protection element
(BLK2OUT-Iph/IE), whenever the given element (Start IED>, Start IED>>, Start IED>>> and/or Start
IED>>>>) becomes active. The enable IED>BLK2OUT, IED>>BLK2OUT, IED>>>BLK2OUT
and/or IED>>>>BLK2OUT parameters (ON or OFF) are available inside the Set\Profile
A(or B)\Directional earth fault overcurrent-67 \ IED> Element (IED>> Element, IED>>> Element,
IED>>>> Element) \Setpoints menus, while the BLK2OUT-Iph-K, BLK2OUT-Iph/IE-K and/or
BLK2OUT-IE-K output relays and LEDs (BLK2OUT-Iph-L, BLK2OUT-Iph/IE-L e/o BLK2OUT-
IE-L) must be select inside the Set\Profile A(or B)\Selective block-BLOCK2\ Selective block OUT
menu.
Internal selective block (Block4)
As well as to send or transmit a selective block toward other protective relays, each protective
element may be enabled for receive or transmit a selective block from/to other internal protective
elements.[2]
The internal selective block of one or more element concerning the directional earth fault overcur-
rent function may be enabled/disabled by means the IED>BLK4, IED>>BLK4, IED>>>BLK4
and/or IED>>>>BLK4 parameters (virtual input and output common to all protective thresholds);
the following operating modes are available:
• IN - the element is enabled to receive the selective block from an internal input.
• OUT - the element is enabled to send the selective block to an internal output.
• OFF - the element is disabled to send/receive the internal selective block.
Transmission and reception for the same element is not allowed, so any stall situation due to wrong
setting is avoided.
The internal selective block can work together with an external selective block from other protective
relays (Block2).
Note 1 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND
MONITORING section
Nota 2 The exhaustive treatment of the internal selective block (Block 4) function may be found in the “Internal selective block” paragraph inside
CONTROL AND MONITORING section.
NA30 - Manual - 04 - 2022
67NS1-module.ai
IE
IE
3Vo
3Vo
3Vo
3Vo
3Vo
≥1
&
&
IEDCLP>def
IEDCLP>inv
≥ IEDCLP>
sheet 3
Insens-Zone OFF
Insens-Zone ON
M
A
A
A
&
State
IED>inv
≥ IED>inv
≥ IED>def
IED>def
Angle
Semisector
&
State
OFF
ON
Insens-Zone
ΦE inside trip sector
IE
ΦE inside trip sector
≥1
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
≥1
&
State
UED>inv
≥ UED>def
≥ UED>inv
UED>def
&
State
IE
≥1
&
IEDCLP>def
IEDCLP>inv
≥ IEDCLP>
&
State
IED>inv
≥ IED>def
≥ IED>inv
IED>def
&
State
≥1
&
State
UED>inv
≥ M∙UED>def
≥ M∙UED>inv
UED>def
&
State
IE
≥1
&
IEDCLP>def
IEDCLP>inv
≥ M∙IEDCLP>
&
State
IED>inv
≥ M∙IED>def
≥ M∙IED>inv
IED>def
&
State
≥1
&
State
UED>inv
≥ UED>def
≥ UED>inv
UED>def
&
State
3Vo
IE
TRIP
3Vo
IE
TRIP
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Ground directional overcurrent (67N) - First element logic diagram (IED>) - Module operating mode (sheet 1 of 4)
NA30 - Manual - 04 - 2022
67NS1-proiezione.ai
IE
IE
3Vo
3Vo
3Vo
3Vo
IE
≥1
&
&
IEDCLP>def
IEDCLP>inv
sheet 3
P
A
&
State
IED>inv
IE∙cosϕ ≥ IED>inv
IE∙cosϕ ≥ IEDCLP>
IE∙cosϕ ≥ 0
IED>def
Angle
Semisector
&
State
IE∙cosϕ ≥ IED>def
IE
≥1
IEDCLP>def
IEDCLP>inv
A
&
State
IED>inv
IE∙cosϕ ≥ IED>inv
IE∙cosϕ ≥ IEDCLP>
IED>def
&
State
IE∙cosϕ ≥ IED>def
IE
≥1
IEDCLP>def
IEDCLP>inv
A
&
State
IED>inv
IE∙cosϕ ≥M∙IED>inv
IE∙cosϕ ≥ IEDCLP>
IED>def
&
State
IE∙cosϕ ≥M∙IED>def
OFF
ON
Insens-Zone
ΦE inside trip sector
IE
ΦE inside trip sector
≥1
A = ON - Change setting within CLP
A =“ON”
A =“OFF”
≥1
&
State
UED>inv
≥ UED>def
≥ UED>inv
UED>def
&
State
3Vo
IE
IE∙cosϕ ≥ 0
&
≥1
&
State
UED>inv
≥ M∙UED>def
≥ M∙UED>inv
UED>def
&
State
&
≥1
&
State
UED>inv
≥ UED>def
≥ UED>inv
UED>def
&
State
3Vo
IE
TRIP
3Vo
IE
TRIP
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Insens-Zone OFF
Insens-Zone ON
Ground directional overcurrent (67N) - First element logic diagram (IED>) - Projecting operating mode (sheet 2 of 4)
Characteristic axis
Half
operating sector
Half
operating sector
IED threshold
IE
ΦE o ΦEC
Characteristic angle
UE
UEC
Trip sector
(toward
No trip sector
(toward busbar)
NA30 - Manual - 04 - 2022
Fun_67NS1-3.ai
ON≡Enable IED> directional earth fault
&
BF Enable (ON≡Enable)
IED>BF
towards BF logic
IED>BF
&
Trip IED>
A
B
Non-directional
(from 74VT)
Non-directional
A = Directional
B = Non-directional
IED> Enable
≥1
CB-State
Block1, Block2, Block4
T
0
tCLP>
IEDCLP>Mode
t EDCLP>
A
B
C
A =“1”
A =“0 or OFF”
IED> overcurrent directional element (67N) block diagram (sheet 4)
A = ON - Change setting within CLP
B = OFF - CLP disabled
C = ON - Element blocking within CLP
≥1
CLP IED>
IE
IEDCLP>def
≥ IEDCLP>def
&
State
≥ IED>def
IED>def
Block by 74VT (ON≡Block)
Internal or external
OFF
74VT
74VTint/ext67N
tED>RES
T
0
RESET
t ED>def/inv
0
T
tED>RES
Start IED>
Trip IED>
TRIPPING MATRIX
(LED+RELAYS)
IED> Curve
0
T
IED>TR-K
IE>TR-L
IED>ST-L
IED>ST-K
t ED>def
t ED>inv
A
B
(sheet 1)
D =“modulo”
Mode67N
C
D
D =“modulo” C =“proiezione”
C
D
M
(sheet 2)
C =“proiezione”
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Ground directional overcurrent (67N) - First element logic diagram (IED>) (sheet 3 of 4)
NA30 - Manual - 04 - 2022
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
67NS1_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1IED>
BLK4IN IED>
&
&
&
BLK2IN IED>
&
&
Enable (ON≡Enable)
IED>BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
IED>BLK2IN
Block1
BLK2IN-Iph
Start IED>
Trip IED>
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
FROM PHASE PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
IED> Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
IPD>Block4 I/O
IPD>>Block4 I/O
IPD>>>Block4 I/O
IPD>>>>Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IPD>Block2 OUT
IPD>>Block2 OUT
IPD>>>Block2 OUT
IPD>>>>Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
IED>BLK4
C
B
A
“0”
“0”
B
“0” C
“0”
IPD>BLK4
A
Start IED>
IED>BLK2OUT
&
Block2 output
(ON≡Enable)
Start IED>
Ground directional overcurrent (67N) - Logic diagram of the blocking signals concerning the first element (IED>) (sheet 4 of 4)
NA30 - Manual - 04 - 2022
67NS2-module.ai
IE
IE
3Vo
3Vo
3Vo
3Vo
3Vo
≥1
&
&
IEDCLP>>def
IEDCLP>>inv
≥ IEDCLP>>
sheet 3
Insens-Zone OFF
Insens-Zone ON
M
A
A
A
&
State
IED>>inv
≥ IED>>def
≥ IED>>inv
IED>>def
Angle
Semisector
&
State
OFF
ON
Insens-Zone
ΦE inside trip sector
IE
ΦE inside trip sector
≥1
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
≥1
&
State
UED>>inv
≥ UED>def
≥ UED>>inv
UED>>def
&
State
IE
≥1
&
IEDCLP>>def
IEDCLP>>inv
≥ IEDCLP>>
&
State
IED>>inv
≥ IED>def
≥ IED>>inv
IED>>def
&
State
≥1
&
State
UED>>inv
≥ M∙UED>def
≥ M∙UED>>inv
UED>>def
&
State
IE
≥1
&
IEDCLP>>def
IEDCLP>>inv
≥ M∙IEDCLP>>
&
State
IED>>inv
≥ M∙IED>def
≥ M∙IED>>inv
IED>>def
&
State
≥1
&
State
UED>>inv
≥ UED>>def
≥ UED>>inv
UED>>def
&
State
3Vo
IE
TRIP
3Vo
IE
TRIP
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Ground directional overcurrent (67N) - Second element logic diagram (IED>>) - Module operating mode (sheet 1 of 4)
NA30 - Manual - 04 - 2022
67NS2-proiezione.ai
IE
IE
3Vo
3Vo
3Vo
3Vo
IE
≥1
&
&
IEDCLP>>def
IEDCLP>>inv
sheet 3
P
A
&
State
IED>>inv
IE∙cosϕ ≥ IED>>inv
IE∙cosϕ ≥ IEDCLP>>
IE∙cosϕ ≥ 0
IED>>def
Angle
Semisector
&
State
IE∙cosϕ ≥ IED>>def
IE
≥1
IEDCLP>>def
IEDCLP>>inv
A
&
State
IED>>inv
IE∙cosϕ ≥ IED>>inv
IE∙cosϕ ≥ IEDCLP>>
IED>>def
&
State
IE∙cosϕ ≥ IED>def
IE
≥1
IEDCLP>>def
IEDCLP>>inv
A
&
State
IED>>inv
IE∙cosϕ ≥M∙IED>>inv
IE∙cosϕ ≥ IEDCLP>>
IED>>def
&
State
IE∙cosϕ ≥M∙IED>>def
OFF
ON
Insens-Zone
ΦE inside trip sector
IE
ΦE inside trip sector
≥1
A = ON - Change setting within CLP
A =“ON”
A =“OFF”
≥1
&
State
UED>>inv
≥ UED>>def
≥ UED>>inv
UED>>def
&
State
3Vo
IE
IE∙cosϕ ≥ 0
&
≥1
&
State
UED>>inv
≥ M∙UED>>def
≥ M∙UED>>inv
UED>>def
&
State
&
≥1
&
State
UED>>inv
≥ UED>>def
≥ UED>>inv
UED>>def
&
State
3Vo
IE
TRIP
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Insens-Zone OFF
3Vo
IE
TRIP
Insens-Zone ON
Ground directional overcurrent (67N) - Second element logic diagram (IED>>) - Projecting operating mode (sheet 2 of 4)
Characteristic axis
Half
operating sector
Half
operating sector
IED threshold
IE
ΦE o ΦEC
Characteristic angle
UE
UEC
Trip sector
(toward
No trip sector
(toward busbar)
NA30 - Manual - 04 - 2022
Fun_67NS2-3.ai
ON≡Enable IED>> directional earth fault
&
BF Enable (ON≡Enable)
IED>>BF
towards BF logic
IED>>BF
&
Trip IED>>
A
B
Non-directional
(from 74VT)
Non-directional
A = Directional
B = Non-directional
IED>> Enable
≥1
CB-State
Block1, Block2, Block4
T
0
tCLP>>
IEDCLP>>Mode
t EDCLP>>
A
B
C
A =“1”
A =“0 or OFF”
IED>> overcurrent directional element (67N) block diagram (sheet 4)
A = ON - Change setting within CLP
B = OFF - CLP disabled
C = ON - Element blocking within CLP
≥1
CLP IED>>
IE
IEDCLP>>def
≥ IEDCLP>>def
&
State
≥ IED>>def
IED>>def
Block by 74VT (ON≡Block)
Internal or external
OFF
74VT
74VTint/ext67N
tED>>RES
T
0
RESET
t ED>>def/inv
0
T
tED>>RES
Start IED>>
Trip IED>>
TRIPPING MATRIX
(LED+RELAYS)
IED>> Curve
0
T
IED>>TR-K
IE>>TR-L
IED>>ST-L
IED>>ST-K
t ED>>def
t ED>>inv
A
B
(sheet 1)
D =“modulo”
Mode67N
C
D
D =“modulo” C =“proiezione”
C
D
M
(sheet 2)
C =“proiezione”
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Ground directional overcurrent (67N) - Second element logic diagram (IED>>) (sheet 3 of 4)
NA30 - Manual - 04 - 2022
Pilot wire output
TRIPPING MATRIX
(LED+RELAYS)
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
≥1
tF-IPh
tF-IPh/IE
tF-IE
ST-Iph BLK2
ST-IE BLK2
≥1
T
0
tF-IPh/IE
T
0
tF-IPh
T
0
tF-IE
I> Block2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Binary input INx (x=1,2)
T
0
Logic
INx t ON
INx t ON
INx t OFF
T
0
n.o.
n.c.
INx t OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
T
0
tB-Iph
67NS2_BL-diagram.ai
≥1
≥1
≥1
≥1
tB-Iph
tFI-Iph
tB-IE
BLK1IED>>
BLK4IN IED>>
&
&
&
BLK2IN IED>>
&
&
Enable (ON≡Enable)
IED>>BLK1
Block2 input enable (ON≡Enable)
Pilot wire input
&
IED>>BLK2IN
IED>>BLK2OUT
Block1
BLK2IN-Iph
Start IED>>
Trip IED> >
ST-IE BLK4
ST-Iph BLK4
Iph Block2
IE Block2
Block4 enable
BLK2IN-IE
tB timeout
Block2 input
tB-K
tB-L
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
FROM PHASE PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
≥1
≥1
tFI-IE
Block4 OUT
≥1
T
0
tFI-Iph
T
0
tFI-IE
I>> Block4 I/O
I> Block4 I/O
IED>> Block4 OUT
Block4
Block4
I>>> Block4 I/O
DthAL1 Block4 I/O
DthAL2 Block4 I/O
Dth Block4 I/O
IPD>Block4 I/O
IPD>>Block4 I/O
IPD>>>Block4 I/O
IPD>>>>Block4 I/O
I>> Block2 OUT
I>>> Block2 OUT
DthAL1 Block2 OUT
DthAL2 Block2 OUT
Dth Block2 OUT
IPD>Block2 OUT
IPD>>Block2 OUT
IPD>>>Block2 OUT
IPD>>>>Block2 OUT
IE>> Block4 I/O
IE> Block4 I/O
IE>>> Block4 I/O
IED>> Block4 I/O
IED> Block4 I/O
IED>>> Block4 I/O
IED>>>> Block4 I/O
≥1
IE>> Block2 OUT
IE> Block2 OUT
IE>>> Block2 OUT
IED>> Block2 OUT
IED> Block2 OUT
IED>>> Block2 OUT
IED>>>> Block2 OUT
Block4
Block1
T
0
tB-IE
Block2 IE
≥1
Block1, Block2, Block4
TRIPPING MATRIX
(LED+RELAYS)
≥1
≥1
A = IN
B = OFF
C = OUT
A = IN
B = OFF
C = OUT
C
B
A
“0”
“0”
B
“0” C
“0”
IED>>BLK4
A
IPD>>BLK4
&
Block2 output
(ON≡Enable)
Start IED>>
Start IED>>
Ground directional overcurrent (67N) - Logic diagram of the blocking signals concerning the second element (IED>>) (sheet 4 of 4)
NA30 - Manual - 04 - 2022
67NS3-module.ai
IE
3Vo
3Vo
&
&
sheet 3
Insens-Zone OFF
Insens-Zone ON
M
Angle
Semisector
OFF
ON
Insens-Zone
ΦE inside trip sector
IE
ΦE inside trip sector
≥1
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
3Vo
&
State
≥ UED>>>def
UED>>>def
&
3Vo
&
State
UED>>>def
≥ M∙UED>>>def
3Vo
&
State
UED>>>def
≥ M∙UED>>>def
&
3Vo
IE
TRIP
3Vo
IE
TRIP
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
IE
IEDCLP>>>def
≥ IEDCLP>>>def
A
&
State
≥ IED>>>def
IED>>>def
IE
IEDCLP>>>def
≥ IEDCLP>>>def
A
&
State
≥ IED>>>def
IED>>>def
IE
IEDCLP>>>def
≥ M∙IEDCLP>>def
A
&
State
≥ M∙IED>>>def
IED>>>def
Ground directional overcurrent (67N) - Third element logic diagram (IED>>>) - Module operating mode (sheet 1 of 4)
NA30 - Manual - 04 - 2022
67NS3-proiezione.ai
IE
IE
3Vo
IE
&
&
IEDCLP>>>def
sheet 3
P
A
&
State
IE∙cosϕ ≥ IEDCLP>>>def
IE∙cosϕ ≥ 0
IED>>>def
Angle
Semisector
IE∙cosϕ ≥ IED>>>def
OFF
ON
Insens-Zone
ΦE inside trip sector
IE
ΦE inside trip sector
≥1
A = ON - Change setting within CLP
A =“ON”
A =“OFF”
A = ON - Change setting within CLP
A =“ON”
A =“OFF”
3Vo
IE
IE∙cosϕ ≥ 0
&
&
3Vo
IE
TRIP
A = ON - Change setting within CLP
A =“ON”
CLP
A =“OFF”
IE
Common configurations
Insens-Zone
OFF
ON
UE
UEC
3Votype67N
3Vo
I
I∙cos
Mode67N
≥ M∙threshold
M
Insens-Zone OFF
3Vo
IE
TRIP
Insens-Zone ON
3Vo
&
State
UED>>>def
≥ M∙UED>>>def
3Vo
&
State
UED>>>def
≥ UED>>>def
3Vo
&
State
UED>>>def
≥ UED>>>def
IE∙cosϕ ≥M∙IED>>>def
IE
IEDCLP>>>def
A
&
State
IE∙cosϕ ≥M∙IEDCLP>>>def
IED>>>def
IE∙cosϕ ≥IED>>>def
IE
IEDCLP>>>def
A
&
State
IE∙cosϕ ≥IEDCLP>>>def
IED>>>def
Ground directional overcurrent (67N) - Third element logic diagram (IED>>>) - Projecting operating mode (sheet 2 of 4)
Characteristic axis
Half
operating sector
Half
operating sector
IED threshold
IE
ΦE o ΦEC
Characteristic angle
UE
UEC
Trip sector
(toward
No trip sector
(toward busbar)