NA20 - Manual - 04 - 2022

MANUAL NA20 PHASE, NEGATIVE SEQUENCE, RESIDUAL OVERCURRENT, THERMAL IMAGE PROTECTION RELAY

NA20 - Manual - 04 - 2022

T A B L E O F C O N T E N T S T A B L E O F C O N T E N T S 1 INTRODUCTION 5 Scope and liability ...........................................................................................................................................................................................5 Applicability ......................................................................................................................................................................................................5 Conformity ........................................................................................................................................................................................................5 Copyright ...........................................................................................................................................................................................................5 Warranty ...........................................................................................................................................................................................................5 Safety recommendations ...............................................................................................................................................................................5 Insulation tests ................................................................................................................................................................................................5 Product identification .....................................................................................................................................................................................6 Environment .....................................................................................................................................................................................................6 Graphical conventions ...................................................................................................................................................................................6 Glossary/definitions ........................................................................................................................................................................................6 2 GENERAL 10 Preface ........................................................................................................................................................................................................... 10 Photo .............................................................................................................................................................................................................. 10 Main features .................................................................................................................................................................................................11 3 TECHNICAL DATA 12 3.1 GENERAL ............................................................................................................................................................................................................12 Product standard for measuring relays .....................................................................................................................................................12 Mechanical data ...........................................................................................................................................................................................12 Insulation ........................................................................................................................................................................................................12 Voltage dip and interruption ........................................................................................................................................................................12 EMC tests for interference immunity .........................................................................................................................................................12 Emission ......................................................................................................................................................................................................... 13 Mechanical tests .......................................................................................................................................................................................... 13 Climatic tests ................................................................................................................................................................................................. 13 Safety ............................................................................................................................................................................................................. 13 Certifications ................................................................................................................................................................................................. 13 3.2 INPUT CIRCUITS ...............................................................................................................................................................................................14 Auxiliary power supply Uaux ......................................................................................................................................................................14 Phase current input circuits ........................................................................................................................................................................14 Residual current input circuit ......................................................................................................................................................................14 Binary input circuits ......................................................................................................................................................................................14 Block input (Logic selectivity) .....................................................................................................................................................................14 3.3 OUTPUT CIRCUITS ............................................................................................................................................................................................14 Relays ..............................................................................................................................................................................................................14 Block output (Logic selectivity) ...................................................................................................................................................................14 3.4 MMI .....................................................................................................................................................................................................................15 3.5 COMMUNICATION INTERFACES ...................................................................................................................................................................15 Local port ........................................................................................................................................................................................................15 Remote ports ..................................................................................................................................................................................................15 3.6 GENERAL SETTINGS ........................................................................................................................................................................................16 3.7 PROTECTIVE FUNCTIONS ...............................................................................................................................................................................16 Base current - IB ...........................................................................................................................................................................................16 Thermal protection with Pt100 probes - 26 ...............................................................................................................................................16 Undercurrent - 37 ..........................................................................................................................................................................................16 Negative sequence overcurrent - 46 .........................................................................................................................................................16 Negative sequence / positive sequence current ratio - I2 / I1 ..............................................................................................................17 Thermal image - 49 ....................................................................................................................................................................................... 18 Phase overcurrent - 50/51 ........................................................................................................................................................................... 18 Residual overcurrent - 50N/51N ................................................................................................................................................................ 19 Breaker failure - BF ...................................................................................................................................................................................... 20 3.8 CONTROL AND MONITORING ........................................................................................................................................................................21 Second harmonic restraint - 2ndh-REST ...................................................................................................................................................21 Trip Circuit Supervision - 74TCS ..................................................................................................................................................................21 Selective block - BLOCK2 ............................................................................................................................................................................21 Circuit Breaker supervision .........................................................................................................................................................................21 CT supervision - 74CT ...................................................................................................................................................................................21 Pilot wire diagnostic .....................................................................................................................................................................................21 Demand measures ........................................................................................................................................................................................21 Oscillography (DFR) ......................................................................................................................................................................................22 PLC (Programmable Logic Controller) .......................................................................................................................................................22

NA20 - Manual - 04 - 2022

3.9 METERING......................................................................................................................................................................................................... 23 Accuracy (type tests)................................................................................................................................................................................... 23 Measures ....................................................................................................................................................................................................... 23 4 FUNCTION CHARACTERISTICS 24 4.1 HARDWARE DESCRIPTION .............................................................................................................................................................................24 Power supply board ......................................................................................................................................................................................25 CPU board .......................................................................................................................................................................................................25 Input board .....................................................................................................................................................................................................25 MMI (keyboard, LED and display) ..............................................................................................................................................................25 4.2 SOFTWARE DESCRIPTION ..............................................................................................................................................................................26 Base software ................................................................................................................................................................................................26 Real-time operating system .........................................................................................................................................................................26 Task ..................................................................................................................................................................................................................26 Drivers .............................................................................................................................................................................................................27 Application Software ....................................................................................................................................................................................27 Data Base .......................................................................................................................................................................................................27 Self test (Application) ...................................................................................................................................................................................27 Development tools (Builder) ........................................................................................................................................................................27 4.3 I/O DESCRIPTION ............................................................................................................................................................................................. 28 Metering inputs ............................................................................................................................................................................................ 28 Signal processing ......................................................................................................................................................................................... 28 Conventions ....................................................................................................................................................................................................31 Use of measured values ...............................................................................................................................................................................32 Binary inputs ................................................................................................................................................................................................. 33 Output relays ................................................................................................................................................................................................. 38 LED indicators ............................................................................................................................................................................................... 40 Communication interfaces ...........................................................................................................................................................................42 4.4 PROTECTIVE ELEMENTS ................................................................................................................................................................................ 43 Rated values .................................................................................................................................................................................................. 43 Thermal protection with RTD thermometric probes - 26 ........................................................................................................................45 Undercurrent - 37 ..........................................................................................................................................................................................47 Negative sequence overcurrent - 46 ........................................................................................................................................................ 49 Negative sequence current / positive sequence current ratio - I2/I1 ..................................................................................................56 Thermal image - 49 ....................................................................................................................................................................................... 58 Phase overcurrent - 50/51 ........................................................................................................................................................................... 69 Residual overcurrent - 50N/51N ................................................................................................................................................................ 79 Breaker failure - BF ...................................................................................................................................................................................... 89 4.5 CONTROL AND MONITORING ........................................................................................................................................................................91 Logical block - BLOCK1 ................................................................................................................................................................................91 Selective block -BLOCK2 ............................................................................................................................................................................ 93 Remote tripping ............................................................................................................................................................................................ 98 Frequency tracking ...................................................................................................................................................................................... 99 Second Harmonic Restraint - 2ndh-REST .............................................................................................................................................. 100 Cold Load Pickup - CLP ..............................................................................................................................................................................101 CT supervision - 74CT ................................................................................................................................................................................ 103 Trip circuit supervision - 74TCS.................................................................................................................................................................104 Circuit breaker supervision .......................................................................................................................................................................107 Demand measures ..................................................................................................................................................................................... 110 Oscillography ............................................................................................................................................................................................. 110 5 MEASURES, LOGIC STATES AND COUNTERS 111 Measures ......................................................................................................................................................................................................111 Protection .....................................................................................................................................................................................................111 Delayed inputs .............................................................................................................................................................................................111 Internal states ..............................................................................................................................................................................................111 Relays ............................................................................................................................................................................................................112 Counters ........................................................................................................................................................................................................112 Self test .........................................................................................................................................................................................................112 Pilot wire diagnostic .................................................................................................................................................................................. 113 Selective Block - BLOCK2 ......................................................................................................................................................................... 113 Fault recording - SFR ................................................................................................................................................................................. 113 Event recording - SER ................................................................................................................................................................................ 113 Oscillography - DFR ....................................................................................................................................................................................114

NA20 - Manual - 04 - 2022

6 INSTALLATION 116 6.1 PACKAGING .....................................................................................................................................................................................................116 6.2 MOUNTING ......................................................................................................................................................................................................116 6.3 ELECTRICAL CONNECTIONS ....................................................................................................................................................................... 120 6.4 NOMINAL CURRENT In AND IEn SETTING ............................................................................................................................................... 130 6.5 LED ALLOCATION ............................................................................................................................................................................................134 6.6 FINAL OPERATIONS .......................................................................................................................................................................................134 7 PROGRAMMING AND SETTINGS 135 7.1 SW ThyVisor ....................................................................................................................................................................................................135 ThyVisor installation ....................................................................................................................................................................................135 ThyVisor use .................................................................................................................................................................................................135 7.2 MMI (Man Machine Interface) ....................................................................................................................................................................136 Reading variables (READ) ..........................................................................................................................................................................136 Setting modifying (SET) ..............................................................................................................................................................................136 TEST .............................................................................................................................................................................................................. 138 COMMUNICATION ..................................................................................................................................................................................... 138 Circuit breaker commands ....................................................................................................................................................................... 139 Enable / block changes via keyboard - Password ................................................................................................................................ 139 7.3 MODULES MANAGEMENT .......................................................................................................................................................................... 140 7.4 MAINTENANCE ...............................................................................................................................................................................................141 7.5 REPAIR ..............................................................................................................................................................................................................141 7.6 PACKAGING .....................................................................................................................................................................................................141 8 APPENDIX 142 8.1 APPENDIX A1 - Inverse time IEC curves ...................................................................................................................................................142 Mathematical formula ................................................................................................................................................................................142 Negative sequence overcurrent 46 - Standard inverse time curve (IEC 60255-3/BS142 type A) ................................................ 143 Negative sequence overcurrent 46 - Very inverse time curve (IEC 60255-3/BS142 type B) ..........................................................144 Negative sequence overcurrent 46 - Extremely inverse time curve (IEC 60255-3/BS142 type C) ................................................145 Phase overcurrent 50/51 - Standard inverse time curve (IEC 60255-3/BS142 type A) ....................................................................146 Phase overcurrent 50/51 - Very inverse time curve (IEC 60255-3/BS142 type B) ............................................................................147 Phase overcurrent 50/51 - Extremely inverse time curve (IEC 60255-3/BS142 type C) .................................................................. 148 Phase overcurrent 50/51 - long time inverse curve (IEC BS B LI) ..................................................................................................... 149 Residual overcurrent 50N/51N - Standard inverse time curve (IEC 60255-3/BS142 type A) ........................................................ 150 Residual overcurrent 50N/51N - Very inverse time curve (IEC 60255-3/BS142 type B) ..................................................................151 Residual overcurrent 50N/51N - Extremely inverse time curve (IEC 60255-3/BS142 type C) ........................................................152 Residual overcurrent 50N/51N - long time inverse curve (IEC BS B LI)........................................................................................... 153 8.2 APPENDIX A2 - Inverse time ANSI/IEEE curves .......................................................................................................................................154 Mathematical formula ................................................................................................................................................................................154 Negative sequence overcurrent 461 - Moderately inverse time curve (ANSI/IEEE type MI) .......................................................155 Negative sequence overcurrent 46 - Very inverse time curve (ANSI/IEEE type VI) .......................................................................156 Negative sequence overcurrent 46 - Extremely inverse time curve (ANSI/IEEE type EI)..............................................................157 Phase overcurrent 50/51 - Moderately inverse time curve (ANSI/IEEE type MI) ........................................................................... 158 Phase overcurrent 50/51 - Very inverse time curve (ANSI/IEEE type VI) ........................................................................................ 159 Phase overcurrent 50/51 - Extremely inverse time curve (ANSI/IEEE type EI) ............................................................................... 160 Residual overcurrent 50N/51N - Moderately inverse time curve (ANSI/IEEE type MI) .................................................................161 Residual overcurrent 50N/51N - Very inverse time curve (ANSI/IEEE type VI) ...............................................................................162 Residual overcurrent 50N/51N - Extremely inverse time curve (ANSI/IEEE type EI) ..................................................................... 163 8.3 APPENDIX A3 - Inverse time - RECTIFIER, I2t and EM curves ................................................................................................................164 Mathematical formula ................................................................................................................................................................................164 Phase overcurrent 50/51 - Rectifier curves ............................................................................................................................................165 Negative sequence overcurrent 46 - I2t inverse curves (I2t=K) .........................................................................................................166 Phase overcurrent 50/51 - I2t inverse curves (I2t=K) ............................................................................................................................167 Negative sequence overcurrent 46 - Electromechanical inverse curves (EM) .............................................................................. 168 Phase overcurrent 50/51 - Electromechanical inverse curves (EM) ................................................................................................. 169 Residual overcurrent 50N/51N - Electromechanical inverse curves (EM)....................................................................................... 170 8.4 APPENDIX B1 - I/O Diagram .........................................................................................................................................................................171 8.5 APPENDIX B2 - Interfaces ............................................................................................................................................................................172 8.6 APPENDIX B3- Connection diagrams ........................................................................................................................................................ 173 8.7 APPENDIX C - Dimensions ............................................................................................................................................................................176 8.8 APPENDIX D - Setting table ..........................................................................................................................................................................177 8.9 APPENDIX E - EC Declaration of conformity ............................................................................................................................................. 208

NA20 - Manual - 04 - 2022

1 I N T R O D U C T I O N 1 I N T R O D U C T I O N Scope and liability This document describes the functions, the technical data of NA20 devices; instructions for mount- ing, setting and commissioning are included. This manual has been checked out, however, deviations from the description cannot be completely ruled out, so that no liability in a legal sense for correctness and completeness of the information or from any damage that might result from its use is formally disclaimed. The information given in this document is reviewed regularly; any corrections and integration will be included in subsequent editions that are identified by the date of revision. We appreciate any suggestions for improvement. We reserve the right to make technical improvements without notice. Applicability This manual is valid for NA20 devices with firmware version 2.70 and following. Conformity The product complies with the CEE directives: • EMC Council Directives: 2014/30/EC • Low voltage Directives: 2014/35/EC Copyright All right reserved; It is forbidden to copy, modify or store material (document and sw) protected by copyright without Thytronic consent. Warranty Thytronic warrants devices against defects in materials and workmanship under normal use for a period of ONE (1) YEAR from the date of retail purchase by the original end-user purchaser (“War- ranty Period”). Safety recommendations The warming contained in this document are all-important for safety; special attention must be paid to the following symbols: Installation and commissioning must be carried out by qualified person; Thytronic assumes no re- sponsibility for damages caused from improper use that does not comply all warning and caution in this manual. In particular the following requirements must be met: • Remove power before opening it. • Verify the voltage absence by means suitable instrumentation on relay connections; attention must be paid to all circuits supplied by external sources (binary input, CT, etc...) • Care must be taken when handling metal parts. Insulation tests After insulation tests, hazardous voltages (capacitor charges,...) may be arise; it is advisable to grad- ually reduce the test voltage avoiding to erase it abruptly. DANGER Death, severe personal injury or substantial property damage will result if proper precautions are not taken WARNING Death, severe personal injury or substantial property damage can result if proper precautions are not taken. CAUTION Minor personal injury or property damage can result if proper precautions are not taken CAUTION Settings must be established on the basis of a coordination study. Numerical values inside examples have educational purpose only; they don’t be used, in no way, for actual applications.

NA20 - Manual - 04 - 2022

Product identification Each device is equipped with: • Identification label installed on the front side with following informations: code number, phase and residual nominal currents, auxiliary voltage range and CE mark: • Test label with following informations: data, serial number and test operator signature. Environment The NA20 device must be employed according to the environment conditions shown (see technical data). In case of different environment conditions, appropriate provisions must be provided (conditioning system, humidity control, etc...). If contaminants are present (dust, corrosive substances, etc...), filters must be provided. Graphical conventions The CEI/IEC and ANSI symbols is employed where possible: e.g.: 51 = ANSI code concerning the overcurrent element. Following text formats are used: The ThyVisor[1] menu: Phase overcurrent -50/51 The parameter description (measures, thresholds, operate time,...) and related value: I> element � � � � Definite�time I>def The display messages (MMI) are shown as: NA20 Notes are highlighted with cursive letters inside colored bar Note: Useful description note Glossary/definitions IEn Relay residual nominal current IEnp Residual CT primary nominal current In Relay phase nominal current Inp Phase CT primary nominal current IB Basic current: it represents the nominal current of the line or trans- former, referred to the nominal current of the CT’s for thermal image protection 37 Undercurrent ANSI code 46 Negative sequence overcurrent ANSI code 49 Thermal image ANSI code 50/51 Phase overcurrent ANSI code 50N/51N Residual overcurrent ANSI code BF Circuit breaker failure ANSI code 74CT CT supervision 74TCS Trip Circuit Supervision DFR Digital Fault Recorder (Oscillography) SER Sequential Event Recorder SFR Sequential Fault Recorder ANSI American National Standard Institute IEEE Institute of Electrical and Electronics Engineers IEC International Electrotechnical Commission CENELEC Comité Européen de Normalisation Electrotechnique 52 o CB (Circuit Breaker) Circuit Breaker 52a Auxiliary contact in the breaker that is in the same position as the breaker. It can be assigned to a binary input to locate the CB position (Breaker failure and/or CB diagnostic functions). (52a open = CB open) 52b Auxiliary contact in the breaker that is in the opposite position as the breaker (52b open = CB closed) K1...K6...K10 Output relays Pulse Output relay with pulse operation tTR Output relay minimum pulse width Latched Output relay with latched operation (manual reset) Output relay with latched operation (automatic reset) No-latched Output relay with no-latched operation (automatic reset) CT Current Transformer P1 IEC nomenclature for primary polarity mark of CTs (as an alternative to a ANSI dot) P2 IEC nomenclature for primary polarity mark of CTs (as an alternative to Note 1 The graphic interface and the operation of the ThyVisor software are described in the relative chapters

NA20 - Manual - 04 - 2022

a ANSI no-dot) S1 IEC nomenclature for secondary polarity mark of CTs (as an alternative to a ANSI dot) S2 IEC nomenclature for secondary polarity mark of CTs (as an alternative to a ANSI no-dot) Self test Diagnostic Start Leave an initial condition or reset condition (Pickup) Trip Operation (with operate time) Operating time Duration of time interval between the instant when the character- istic quantity in reset condition is changed, under specified condi- tions, and the instant when the relay operates Dropout ratio The ratio of a reset value to an operate value in well-specified con- ditions. The dropout ratio may be lower or greater than 1 according as an over or under element is considered Reset time Duration of the time interval between the instant when the charac- teristic quantity in operate condition is changed, under specified conditions, and the instant when the relay operates. The stated reset time is related to a step variation of characteristic quantity in operate condition to the reset condition. Overshoot time The critical impulse time for a relay which is in its reset condition, is the longest duration a specified change in the input energizing quantity(ies) (characteristic quantity), which will cause the relay to change to operate condition, can be applied without the relay switches. The overshoot time is the difference from the operate time and the critical impulse time. The declared values for the overshoot time are applicable with the lower setting value of the operation time. MMI (Man Machine Interface) Operator front panel ThyVisor Setting and monitoring software Log file A text file that lists actions that have occurred (ThyVisor). J2SE Java Platform Standard Edition Subnet Mask (Ethernet nomenclature) Sw Software Fw Firmware Upgrade Firmware upgrade XML eXtensible Markup Language

NA20 - Manual - 04 - 2022

Symbols.ai Symbols I>> Start I>> BF_OUT IPh Block2 Logic internal signal (output); may be a logical state (e.g.I>> Start) or a numerical value It is available for reading (ThySetter + communication interface) Logic external signal (intput); may be a command coming from a binary input or a sw command It is available for reading (ThySetter + communication interface) Internal signal (e.g. Breaker Failure output state concerning to the 2nd threshold of the 50 element) It is not available for reading (missing arrow) AND and NAND logic gates OR and NOR logic gates Limit block (I>> threshold). Computation block (Max phase current) Threshold setting (e.g. pickup I>>). The value is available for reading and is adjustable by means ThySetter + MMI. Switch ON delay timer with reset (tON delay) ON delay timer without reset (tON delay) OFF delay timer (dropout) without reset (tOFF delay) Curve type (definite/inverse time) 0 T I L3 Max[I L1 ,I L2 ,I L3 ] I L2 I L1 tON tON tON tON t RESET INPUT OUTPUT tOFF t tOFF INPUT OUTPUT tON tON tON t INPUT OUTPUT 0 T tON & & ≥1 ≥1 EXOR logic gate tOFF =1 I>> I I ≥ I>> tON RESET 0 T 0 T

NA20 - Manual - 04 - 2022

Symbols1 .ai t RESET INPUT OUTPUT tOFF tOFF tOFF tOFF Minimum pulse width operation for output relays (tTR) tTR t tTR INPUT OUTPUT tTR 0 T tTR t tTR INPUT OUTPUT Latched operating mode for output relays and LEDs Pulse operating mode for output relays t INPUT OUTPUT Latched tTR T 0 RESET OFF delay timer (dropout) with reset (tOFF delay)

NA20 - Manual - 04 - 2022

2 G E N E R A L 2 G E N E R A L Preface The relay type NA20 is typically used in HV, MV and LV radial networks as feeder or power trans- former protection. In solidly grounded systems the residual overcurrent protection can be used on feeders of any length, while in ungrounded or Petersen coil and/or resistance grounded systems, the residual overcurrent protection can be used on feeders of small length in order to avoid unwanted trippings due to the capacitive current contribution of the feeder on external ground fault. Beside to the phase and residual overcurrent protection, the following protective functions are pro- vided: • Thermal image protection of lines and power transformers. • Undercurrent protection for monitoring of CB opening. • Negative sequence protection against asymmetrical short circuits and unbalance loads. • I2/I1 protection against phase interruption under low-load condition. Following input circuits are available: • Three phase current and one residual current inputs with nominal currents independently select- able at 1 A or 5 A using dip-switch. • Two or five (optional) binary inputs. • One block input (logic selectivity). In addition to the main protection element, the breaker failure (BF), CT monitoring (74CT), Trip Circuit Supervision (TCS) and programmable logic (PLC) are also provided. Setting, programming and reading operations must be effected by means of Personal Computer with ThyVisor software or by means of remote communication interface (RS485 bus and Ethernet network or USB); all operations must be performed through MMI. According to the hardware configurations, the NA20 protection relay can be shipped in various case styles depending on the required mounting options: • Flush. • Projecting mounting. • Rack. • With separate operator panel. Other options are: • Auxiliary power supply operating range. • Communication protocols. Photo

NA20 - Manual - 04 - 2022

Main features • Metallic case. • Backlight LCD 4x16 Display. • Eight LEDs that may be joined with matrix criteria to many and various functions. • RESET key to clear LED indications and latched output relays. • Two free settable binary inputs. • Independently settable for start, trip, self-test and control six output relay (K1...K6) Each output relay may be set with normally energized or normally de-energized operating mode and manual or automatic reset (latched/no-latched). • Rear Ethernet communication port, with MODBUS TCP/IP® protocol, with RJ45 (copper wires) or FX (optical fiber) connection. • Rear RS485 port, with ModBus protocol. • USB front serial port (local communication for ThyVisor). • Real time clock with super capacitor. The most significant constructive features are: • Galvanically insulated input and output circuits (communication and binary circuits included). • Optimum filtering of input signals through combined use of analog and digital filters. • Traditional electromechanical-type final output contacts with continuous monitoring of control coil continuity. • Auxiliary supply comprising a switching-type voltage stabilizing circuit having a very wide working range and a very small power dissipation • Nominal frequency: 50 or 60 Hz. The most significant operating features are: • Programming of operating modes and parameters by means of the front keys and alphanumeric display, with a programming procedure based on carrying out guided selections and on explicit and immediate signalling of the operations being performed, so that such procedure can be carried out without coding tables or mnemonic informations. • The feature modification operations do not interrupt the normal functions of the relay. • Impossibility of programming unacceptable parameter values, thanks to the automatic limitation of top and bottom scale values for the relative setting ranges. • Currents are sampled 24 times per period and measured in the effective value (RMS) of the funda- mental component using the DFT (Discrete Fourier Transform) algorithm and digital filters. • The fault recorder (SFR) runs continuously capturing in circular mode the last twenty events upon trigger of binary input/output and/or element pickup (start-trip). • The event recorder (SER) runs continuously capturing in circular mode the last three hundred events upon trigger of binary input/output. • Digital fault recorder (DFR) in COMTRADE format (oscillography).

NA20 - Manual - 04 - 2022

3 T E C H N I C A L D ATA 3 T E C H N I C A L D ATA 3.1 GENERAL � Product standard for measuring relays Reference standards IEC 60255-1 Part 1: Common requirements � Mechanical data Mounting: • Flush. • Projecting. • Rack. • Separated operator panel. External dimensions (Flush mounting) 177 x 107 x 235 (high x width x depth) Terminals screw connection Mass (Flush mounting) 2.0 kg Reference standards EN 60529, EN 60529/A1 Degrees of protection provided by enclosures (IP Code) • Front IP52 • Terminals IP20 � Insulation Reference standards EN 60255-5, IEC 60255-27 High voltage test (50 Hz - 60 s) • Auxiliary power supply 2 kV • Input circuits 2 kV • Output circuits 2 kV • Output circuits (between open contacts) 1 kV • Comunication circuits 500 V Impulse voltage withstand test (1.2/50 µs): • Auxiliary power supply 5 kV (Common mode) - 2kV (Differential mode) • Input circuits 5 kV • Output circuits 5 kV • Output circuits (between open contacts) 1 kV Insulation resistance >100 MW � Voltage dip and interruption Reference standards EN 61000-4-29, IEC 60255-22-11 Voltage dips, short interruptions and voltage variations on dc input power port immunity tests • Interruption (UT=40%) 100 ms • Interruption (UT=0%) 50 ms • Voltage variations (UT=80...120%) 10 s � EMC tests for interference immunity Reference standards IEC 60255-26, EN 60255-26 Product standard for measuring relays Generic standards immunity for industrial environments EN 61000-6-2 • Electromagnetic compatibility requirements for measuring relays and protection equipment Apparati di automazione e controllo per centrali e stazioni elettriche • Compatibilità elettromagnetica - Immunità ENEL REMC 02 • Normativa di compatibilità elettromeccanica per apparati e sistemi ENEL REMC 01 Reference standards EN 60255-22-1 IEC 60255-22-1 EN 61000-4-12 EN 61000-4-12 Damped oscillatory wave • 0.1 MHz and 1 MHz common mode 2.5 kV • 0.1 MHz and 1 MHz differential mode 1.0 kV • Ring wave common mode 2.0 kV • Ring wave differential mode 1.0 kV Reference standards EN 60255-22-2 IEC 60255-22-2 EN 61000-4-2 IEC 61000-4-2 Electrostatic discharge • Contact discharge 6 kV • Air discharge 8 kV Reference standards EN 60255-22-3 IEC 60255-22-3 EN 61000-4-3 IEC 61000-4-3 Radiated radio-frequency fields • 80...1000 MHz AM 80% 10 V/m

NA20 - Manual - 04 - 2022

• 900 MHz Pulse modulated 10 V/m Reference standards EN 60255-22-4 IEC 60255-22-4 EN 61000-4-4 IEC 61000-4-4 Fast transient burst (5/50 ns) • Auxiliary power supply 2 kV • Input circuits 4 kV Reference standards EN 60255-22-5 IEC 60255-22-5 EN 61000-4-5 IEC 61000-4-5 High energy pulse • Uaux (line-to-ground 10 ohm, 9 mF) 2 kV • Uaux (line-to-line 0 ohm, 18 mF) 1 kV • I/O ports (line-to-ground 40 ohm, 0.5 mF) 2 kV • I/O ports (line-to-line 40 ohm, 0.5 mF) 1 kV Reference standards EN 60255-22-6 IEC 60255-22-6 EN 61000-4-6 IEC 61000-4-6 Conducted radio-frequency fields • 0.15...80 MHz AM 80% 1kHz 10 V Reference standards EN 60255-22-7 IEC 60255-22-7 EN 61000-4-16 IEC 61000-4-16 Power frequency immunity tests • Dc voltage 30 V • 50 Hz continuously 30 V • 50 Hz 1 s 300 V • 0.015...150 kHz 30 V Reference standards EN 61000-4-8 IEC 61000-4-8 Magnetic field 50 Hz • 50 Hz continuously 100 A/m • 50 Hz 1 s 1 kA/m Reference standards EN 61000-4-10 IEC 61000-4-10 Damped oscillatory magnetic field • Damped oscillatory wave 0.1 MHz 30 A/m • Damped oscillatory wave 1 MHz 30 A/m � Emission Reference standards EN 60255-25 IEC 60255-25 EN 61000-6-4 IEC 61000-6-4 EN 55011 CISPR 11 Electromagnetic emission tests • Conducted emission auxiliary power supply 0.15...0.5 MHz 79 dB mV • Conducted emission auxiliary power supply 0.5...30 MHz 73 dB mV • Radiated emission 30...230 MHz 40 dB mV/m • Radiated emission 230...1000 MHz 47 dB mV/m � Mechanical tests Reference standards EN 60255-21-1 EN 60255-21-2 RMEC01 Vibration, shock, bump and seismic tests on measuring relays and protection equipment • EN 60255-21-1 Vibration tests (sinusoidal) Class 1 • EN 60255-21-2 Shock and bump test Class 1 � Climatic tests Reference standards IEC 60068-x ENEL R CLI 01 CEI 50 Environmental testing Ambient temperature -25...+70 °C Storage temperature -40...+85 °C Relative humidity 10...95 % Atmospheric pressure 70...110 kPa � Safety Reference standards IEC 60255-27 Safety requirements for electrical equipment for measurement, control and laboratory use Pollution degree 3 Reference voltage 250 V Overvoltage category III � Certifications Reference standards Product standard for measuring relays EN 50263 CE Conformity • EMC Directive 2014/30/EC • Low Voltage Directive 2014/35/EC Type tests IEC 60255-1

NA20 - Manual - 04 - 2022

3.2 INPUT CIRCUITS � Auxiliary power supply Uaux Voltage Nominal value (range) 24...48 V~/- 115...230 V~/110...220 V- Operative range (each one of the above nominal values) 19...60 V~/- 85...265 V~/75...300 V- Inrush current (max) • 24 V- 6 A, 5 ms • 48 V- 14 A, 5 ms • 110 V- 20 A, 1 ms • 230 V~ 50 A, 1 ms Frequency (for alternate voltage supply) 45...66 Hz Max distortion factor ( for alternating voltage supply) 15% Max alternating component (for dc voltage supply): • Full wave rectified sine wave 100 % • Sine wave 80 % Power consumption: • Maximum (energized relays, Ethernet TX) 10 W (20 VA) • Maximum (energized relays, Ethernet FX) 15 W (25 VA) � Phase current input circuits Relay nominal phase current In 1 A or 5 A selectable by dip-switch Permanent overload 25 A Thermal overload (1 s) 500 A Dynamic overload (half cycle) 1250 A Rated consumption (for any phase) ≤ 0.002 VA with In=1 A ≤ 0.04 VA with In=5 A � Residual current input circuit Relay nominal residual current IEn 1 A or 5 A selectable by dip-switch Permanent overload 25 A Thermal overload (1 s) 500 A Dynamic overload (half cycle) 1250 A Rated consumption ≤ 0.006 VA with IEn=1 A ≤ 0.12 VA with IEn=5 A � Binary input circuits Quantity 2 or 5 (optional) Type optocoupler Operative range 24...265 V~/- Min activation voltage 18 V Max consumption, energized 3 mA � Block input (Logic selectivity) Quantity 1 Type polarized wet input (powered by internal isolated supply) Max consumption, energized 5 mA 3.3 OUTPUT CIRCUITS � Relays Quantity 6 Type of contacts K1, K2 changeover (SPDT, type C) Type of contacts K3, K4, K5 make (SPST-NO, type A) Type of contacts K6 break (SPST-NC, type B) Nominal current 8 A Nominal voltage/max switching voltage 250 V~/400 V~ Breaking capacity: • Direct current (L/R = 40 ms) 50 W • Alternating current (l = 0,4) 1250 VA Make 1000 W/VA Short duration current (0,5 s) 30 A Minimum switching load 300 mW (5 V/ 5 mA) Life: • Mechanical 106 operations • Electrical 105 operations � Block output (Logic selectivity) Quantity 1 Type optocoupler

NA20 - Manual - 04 - 2022

3.4 MMI Display 16 x 4 alphanumeric LCD LEDs Quantity 8 • ON/fail (green) 1 • Start (yellow) 1 • Trip (red) 1 • Freely allocatable (red) 5 Keyboard 8 keys 3.5 COMMUNICATION INTERFACES � Local port Connection USB Type B Protocol Modbus RTU® � Remote ports RS485 • Connection screw terminals • Baud rate 1200...57600 bps • Protocol[1] ModBus®RTU IEC 60870-5-103 DNP3[2] Ethernet 100BaseT • Connection[3] Optical fiber 1300 nm, ST 100 Base TX, RJ45 • Baud rate 100 Mbps • Protocol ModBus®TCP/IP Note 1 Different version must be selected at ordering Note 2 Extended list of reading variables (eg. ) Note 3 Different version must be selected at ordering

NA20 - Manual - 04 - 2022

3.6 GENERAL SETTINGS Relay nominal frequency (fn) 50, 60 Hz Relay phase nominal current (In) 1 A or 5 A [1] Phase CT primary nominal current (Inp) 1 A...10 kA 1...499 A (step 1 A) 500...4990 A (step 10 A) 5000...10000 A (step 100 A) Relay residual nominal current (IEn) 1 A or 5 A [1] Residual CT primary nominal current (IEnp) 1 A...10 kA 1...499 A (step 1 A) 500...4990 A (step 10 A) 5000...10000 A (step 100 A) 3.7 PROTECTIVE FUNCTIONS � Base current - IB[2] Base current (IB) 0.10...2.50 In (step 0.01 In) � Thermal protection with Pt100 probes - 26[3] ThAL1...8 Alarm: Alarm threshold 26 PT1...PT8 (ThAL1...8) 0...200 °C Operating time ThAL1...8 (tThAL1...8) 0....100 s Th>1...8 Trip: Trip threshold 26 PT1...PT8 (Th>1...8) 0...200 °C Operating time ThAL1...8 (tTh>1...8) 0....100 s � Undercurrent - 37 37 Operating logic (Logic37) AND/OR Definite time 37 First threshold definite time (I Element I2> Curve type (I2>Curve) DEFINITE IEC/BS A, B, C ANSI/IEEE MI, VI, EI I2t, EM I2CLP> Activation time (t2CLP>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) I2> Reset time delay (t2>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 46 First threshold definite time (I2>def) 0.100...10.00 In 0.100...0.999 In (step 0.001 In) 1.00...10.00 In (step 0.01 In) I2>def within CLP (I2CLP>def) 0.100...10.00 In 0.100...0.999 In (step 0.001 In) 1.00...10.00 In (step 0.01 In) I2>def Operating time (t2>def) 0.03...200 s 0.03...9.99 s (step 0.01 s) 10.0...99.9 s (step 0.1 s) 100...200 s (step 1 s) Note 1 The nominal current settings doesn’t concern the protection elements; they must agree with hardware setting (dip-switch 1 A or 5 A) . Note 2 The basic current IB represents the nominal current of the line or transformer, referred to the nominal current of the CT’s for thermal image protection. If the secondary rated current of the line CT’s equals the rated current of the NA20 relay, as usually happens, the IB value is the ratio between the rated current of the protected element and the primary rated current of the CT’s Note 3 The 26 element is available when the MPT module is connect on Thybus and enabled

NA20 - Manual - 04 - 2022

Inverse time [1] 46 First threshold inverse time (I2>inv) 0.100...10.00 In 0.100...0.999 In (step 0.001 In) 1.00...5.00 In (step 0.01 In) I2>inv within CLP (I2CLP>inv) 0.100...10.00 In 0.100...0.999 In (step 0.001 In) 1.00...10.00 In (step 0.01 In) I2>inv Operating time (t2>inv) 0.02...60.0 s 0.02...9.99 s (step 0.01 s) 10.0...60.0 s (step 0.1 s) I2>> Element I2CLP>> Activation time (t2CLP>>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) I2>> Reset time delay (t2>>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 46 Second threshold definite time (I2>>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...40.00 In (step 0.01 In) I2>>def within CLP (I2CLP>>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...40.00 In (step 0.01 In) I2>>def Operating time (t2>>def) 0.03...10.00 s (step 0.01 s) Pickup time ≤ 0.03 s Dropout ratio 0.95...0.98 Dropout time ≤ 0.05 s Overshoot time 0.03 s Pickup accuracy 1% with I2 ≥ 0.5 In Operate time accuracy 5% or ± 10 ms � Negative sequence / positive sequence current ratio - I2 / I1 I21> Element I21CLP> Activation time (t21CLP>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time I2 / I1> First threshold definite time (I21>def) 0.10...1.00 In (step 0.01 In) I2 / I1> within CLP ((I21CLP>def 0.10...1.00 In (step 0.01 In) I21>def Operating time (t21>def) 0.04...15000 s 0.04...9.99 s (step 0.01 s) 1...15000 s (step 1 s) Pickup time ≤ 0.03 s Dropout ratio 0.95...0.98 Dropout time ≤ 0.05 s Overshoot time 0.03 s Pickup accuracy 1% with I1 and I2 ≥ 0.5 In Operate time accuracy 5% or ± 10 ms Note 1 Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t2>inv / [(I2/I2>inv)0.02 - 1] Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t2>inv / [(I2/I2>inv) - 1] Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t2>inv / [(I2/I2>inv)2 - 1] Moderately Inverse (ANSI/IEEE type MI): t = t2>inv · {0.01 / [(I2/I2>inv)0.02 - 1] + 0.023} Very Inverse (ANSI/IEEE type VI): t = t2>inv · {3.922 / [(I2/I2>inv)2 - 1] + 0.098} Extremely Inverse (ANSI/IEEE type EI): t = t2>inv · {5.64 / [(I2/I2>inv)2 - 1] + 0.024} I-squared-t (I 2t = K): t = 16 · t2>inv / (I2/I2>inv)2 Electromechanical (EM): t = 0.28 · t2>inv / [-0.236 · (I2/I2>inv)-1+ 0.339] t: operate time I2>inv: pickup value t2>inv: operate time setting Asymptotic reference value: 1.1 I2>nv Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ I2/I2>inv ≤ 20 With I2>inv pickup ≥ 2.5 In, the upper limit is 50 In

NA20 - Manual - 04 - 2022

� Thermal image - 49 Common configuration: Initial thermal image DqIN (DthIN) 0.0...1.0 DqB (step 0.1 DqB)[1] Reduction factor at inrush (KINR) 1.0...3.0 (step 0.1) Thermal time constant t (T) 1...200 min (step 1 min) DthIN activation time (tdthCLP) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) DthAL1 Element 49 First alarm threshold (DthAL1) 0.3...1.0 DqB (step 0.1 DqB) DthAL2 Element 49 Second alarm threshold (DthAL2) 0.5...1.2 DqB (step 0.1 DqB) Dth> Element 49 Trip threshold (Dth>) 1.100...1.300 DqB (step 0.001 DqB) Pickup accuracy ± 1% with 0.1 In, ± 1% with 1 In Operate time accuracy 5% or ± 10 ms � Phase overcurrent - 50/51 I> Element I> Curve type (I>Curve) DEFINITE IEC/BS A, B, C, B-LI ANSI/IEEE MI, VI, EI RECTIFIER, I2t or EM I CLP> Activation time (tCLP>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) I> Reset time delay (t>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 50/51 First threshold definite time (I>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...40.0 In (step 0.1 In) I>def within CLP (ICLP>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...40.0 In (step 0.1 In) I>def Operating time (t>def) 0.04...200.00 s 0.04...9.99 s (step 0.01 s) 10.0...99.9 s (step 0.1 s) 100...200 s (step 1 s) Inverse time[2] 50/51 First threshold inverse time (I>inv) 0.100...20.00 In 0.100...0.999 In (step 0.001 In) 1.00...20.00 In (step 0.01 In) I>inv within CLP (ICLP>inv) 0.100...20.00 In 0.100...0.999 In (step 0.001 In) 1.00...20.00 In (step 0.01 In) I>inv Operating time (t>inv) 0.02...60.0 s 0.02...9.99 s (step 0.01 s) 10.0...60.0 s (step 0.1 s) Note 1 Dq is the thermal image (p.u. of the basic over temperature corresponding to the basic current IB). Assuming that the secondary rated current of the line CT’s equals the rated current of the NA20 relay, as usually happens, the IB value is the ratio between the rated current of the protected element and the primary rated current of the CTs Note 1 Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t>inv / [(I/I>inv)0.02 - 1] Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t>inv / [(I/I>inv) - 1] Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t>inv / [(I/I>inv)2 - 1] Long time Inverse Time (IEC 255-3/BS B LI): t = 120 · t>inv / [(I/I>inv) - 1] Moderately Inverse (ANSI/IEEE type MI): t = t>inv · {0.01 / [(I/I>inv)0.02 - 1] + 0.023} Very Inverse (ANSI/IEEE type VI): t = t>inv · {3.922 / [(I/I>inv)2 - 1] + 0.098} Extremely Inverse (ANSI/IEEE type EI): t = t>inv · {5.64 / [(I/I>inv)2 - 1] + 0.024} I-squared-t (I 2t = K): t = 16 · t>inv / (I/I>inv)2 Electromechanical (EM): t = 0.28 · t>inv / [-0.236 · (I/I>inv)-1+ 0.339] RECTIFIER (RI): t = 2351 · t>inv / [(I/I>inv)5.6- 1] t: operate time I>inv: pickup value t>inv: operate time setting Asymptotic reference value: 1.1 I>nv Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ I/I>inv ≤ 20 With I>inv pickup ≥ 2.5 In, the upper limit is 50 In

NA20 - Manual - 04 - 2022

I>> Element I>> Curve type (I>>Curve) DEFINITE or I2t I CLP>> Activation time (tCLP>>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) I>> Reset time delay (t>>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 50/51 Second threshold definite time (I>>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...40.0 In (step 0.1 In) I>>def within CLP (ICLP>>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...40.0 In (step 0.1 In) I>>def Operating time (t>>def) 0.03...10.00 s (step 0.01 s) Inverse time 50/51 Second threshold inverse time (I>>inv) 0.100...20.00 In 0.100...0.999 In (step 0.001 In) 1.00...20.00 In (step 0.01 In) I>>inv within CLP (ICLP>>inv) 0.100...20.00 In 0.100...0.999 In (step 0.001 In) 1.00...20.00 In (step 0.01 In) I>>inv Operating time (t>>inv) 0.02...10.00 s (step 0.01 s) I>>> Element I CLP>>> Activation time (tCLP>>>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) I>>> Reset time delay (t>>>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 50/51 Third threshold definite time (I>>>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...40.0 In (step 0.1 In) I>>>def within CLP (ICLP>>>def) 0.100...40.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...40.0 In (step 0.1 In) I>>>def Operating time (t>>>def) 0.03...10.00 s (step 0.01 s) Pickup time ≤ 0.03 s Dropout ratio 0.95...0.98 Dropout time ≤ 0.05 s Overshoot time 0.03 s Pickup accuracy ± 0.5% with 0.1 In, ± 0.2% with 1 In Operate time accuracy 5% or ± 10 ms � Residual overcurrent - 50N/51N IE> Element IE> Curve type (IE>Curve) DEFINITE IEC/BS A, B, C, B-LI ANSI/IEEE MI, VI, EI EM IECLP> Activation time (tECLP>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) IE> Reset time delay (tE>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 50N/51N First threshold definite time (IE>def) 0.002...10.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...10.00 IEn (step 0.01 IEn) IE>def within CLP (IECLP>def) 0.002...10.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...10.00 In (step 0.01 IEn) IE>def Operating time (tE>def) 0.04...200 s 0.04...9.99 s (step 0.01 s) 10.0...99.9 s (step 0.1 s) 100...200 s (step 1 s)

NA20 - Manual - 04 - 2022

Inverse time[1] 50N/51N First threshold inverse time (IE>inv) 0.002...2.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...2.00 IEn (step 0.01 IEn) IE>inv within CLP (IECLP>inv) 0.002...2.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...2.00 IEn (step 0.01 IEn) IE>inv Operating time (tE>inv) 0.02...60.0 s 0.02...9.99 s (step 0.01 s) 10.0...60.0 s (step 0.1 s) IE>> Element IECLP>> Activation time (tECLP>>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) IE>> Reset time delay (tE>>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 50N/51N Second threshold definite time (IE>>def) 0.002...10.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...10.00 IEn (step 0.01 IEn) IE>>def within CLP (IECLP>>def) 0.002...10.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...10.00 IEn (step 0.01 IEn) IE>>def Operating time (tE>>def) 0.03...10.00 s (step 0.01 s) IE>>> Element IECLP>>> Activation time (tECLP>>>) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) IE>>> Reset time delay (tE>>>RES) 0.00...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Definite time 50N/51N Third threshold definite time (IE>>>def) 0.002...10.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...10.00 IEn (step 0.01 IEn) IE>>>def within CLP (IECLP>>>def) 0.002...10.00 IEn 0.002...0.999 IEn (step 0.001 IEn) 1.00...10.00 IEn (step 0.01 IEn) IE>>>def Operating time (tE>>>def) 0.03...10.00 s (step 0.01 s) Pickup time ≤ 0.03 s Dropout ratio 0.95...0.98 Dropout time ≤ 0.05 s Overshoot time 0.03 s Pickup accuracy ± 0.5% with 0.01 IEn, ± 0.2% with 1 IEn Operate time accuracy 5% or ± 10 ms � Breaker failure - BF BF Phase current threshold (IBF>) 0.05...1.00 In (step 0.01 In) BF Residual current threshold (IEBF>) 0.01...2.00 IEn (step 0.01 IEn) BF Time delay(tBF) 0.06...10.00 s (step 0.01 s) Dropout ratio 0.95...0.98 Dropout time ≤ 0.05 s IBF>Pickup accuracy ± 0.5% with 0.1 InL ± 0.2% with 1 InL IEBF>Pickup accuracy ± 0.5% with 0.01 IEn ± 0.2% with 1 IEn Operate time accuracy 5% or ± 10 ms Note 1 Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · tE>inv / [(IE/ IE>inv)0.02 - 1] Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · tE>inv / [(IE/IE>inv) - 1] Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · tE>inv / [(IE/IE>inv)2 - 1] Long time Inverse Time (IEC 255-3/BS B LI): t = 120 · tE>inv / [(IE/IE>inv) - 1] Moderately Inverse (ANSI/IEEE type MI): t = tE>inv · {0.01 / [(IE/IE>inv)0.02 - 1] + 0.023} Very Inverse (ANSI/IEEE type VI): t = tE>inv · {3.922 / [(IE/IE>inv)2 - 1] + 0.098} Extremely Inverse (ANSI/IEEE type EI): t = tE>inv · {5.64 / [(IE/IE>inv)2 - 1] + 0.024} Electromechanical (EM): t = 0.28 · tE>inv / [-0.236 · (IE/IE>inv)-1+ 0.339] IE: residual current input t: operate time IE>inv: pickup value; tE>inv: operate time setting Asymptotic reference value: 1.1 IE> Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ IE/ IE>inv ≤ 20, with IE>inv pickup ≥ 0.5 IEn, the upper limit is 10 IEn

NA20 - Manual - 04 - 2022

3.8 CONTROL AND MONITORING � Second harmonic restraint - 2ndh-REST Second harmonic restraint threshold (I2ndh>) 10...50 % (step 1 %) I2ndh> reset time delay (t2ndh>RES) 0...100.0 s 0.00...9.99 s (step 0.01 s) 10.0...100.0 s (step 0.1 s) Dropout ratio 0.95...0.98 Dropout time ≤ 0.04 s Pickup accuracy I2ndh> ± 4% ± 1% In Operate time accuracy 5% or ± 10 ms � Trip Circuit Supervision - 74TCS Operate time: • One binary input supervision 40 s • Two binary inputs supervision 2 s Reset time delay: • One binary input supervision 6 s • Two binary inputs supervision 0.6 s � Selective block - BLOCK2 Selective block IN: • BLIN1 Selective block operating mode (ModeBLIN1) OFF-ON IPh/IE-ON IPh-ON IE • BLIN maximum activation time for phase protections (tB-IPh) 0.10...10.00 s (step 0.01 s) • BLIN maximum activation time for ground protections (tB-IE) 0.10...10.00 s (step 0.01 s) Selective block OUT: • BLOUT1 Selective block operating mode (ModeBLOUT1) OFF-ON IPh/IE-ON IPh-ON IE • BLOUT Dropout time for phase protections (tF-IPh) 0.00...1.00 s (step 0.01 s) • BLOUT Dropout time for ground protections (tF-IE) 0.00...1.00 s (step 0.01 s) • BLOUT Dropout time for ground and phase protections (tF-IPh/IE) 0.00...1.00 s (step 0.01 s) � Circuit Breaker supervision Circuit breaker diagnostic Number of CB trips threshold (N.Open) 0...10000 (step 1) Cumulative CB tripping currents threshold (SumI) 0....5000 In (step 1 In) Cumulative CB tripping I2t threshold (SumI^2t) 0....5000 (In)2∙s (step 1 In2∙s) Circuit Breaker opening time for I^2t calculation (tbreak) 0.05...1.00 s (step 0.01 s) Circuit Breaker maximum allowed opening time (tbreak>) 0.05...1.00 s (step 0.01 s) � CT supervision - 74CT 74CT Threshold (S<) 0.10...0.95 (step 0.01) 74CT Overcurrent threshold (I*) 0.10...1.00 In (step 0.01 In) S< Operating time delay (tS<) 0.03...200 s 0.03...9.99 s (step 0.01 s) 10.0...99.9 s (step 0.1 s) 100...200 s (step 1 s) Dropout ratio for the I* pickup 0.95...0.98 Dropout time ≤ 0.05 s Pickup accuracy S< ± 1% with 0.1 In , ± 0.5% with 1 In Pickup accuracy I* ± 0.5% with 0.1 In , ± 0.2% with 1 In Operate time accuracy 5% or ± 10 ms � Pilot wire diagnostic • BLOUT1 Diagnostic pulse period (PulseBLOUT1) OFF-0.1-1-5-10-60-120 s • BLIN1 Diagnostic pulse control time interval (PulseBLIN1) OFF-0.1-1-5-10-60-120 s � Demand measures • Fix on demand period (tFIX) 1...60 min (step 1 min) • Rolling on demand period (tROL) 1...60 min (step 1 min) • Number of cycles for rolling on demand (N.ROL) 1...24 (step 1)

NA20 - Manual - 04 - 2022

� Oscillography (DFR)[1] Format COMTRADE Recording mode circular Sampling rate 24 samples / cycle Trigger setup: • Pre-trigger time 0.05...1.00 s (step 0.01 s) • Post-trigger time 0.05...60.00 s (step 0.05 s) Set sample channels: iL1, iL2, iL3, iE Set analog channels: Analog 1...Analog 12 Frequency, IL1, IL2, IL3, IE, I1, I2, I2/I1, IL1-2nd, IL2-2nd, IL3-2nd, I-2nd /IL, T1...T8[2] Set digital channels: Digital 1...Digital 12 K1... K6, K7...K10, IN1, IN2, IN3...IN42[3] � PLC (Programmable Logic Controller)[4] Reference standard IEC 61131-3 Language[5] IL (Instruction List) Inputs: Binary inputs IN1, IN2 on board IN8...IN10 with MRI module IN11...IN26 with one MID16 module IN27...IN42 with two MID16 modules Delayed binary inputs[6] IN1, IN2 on board IN8...IN10 with MRI module IN11...IN26 with one MID16 module IN27...IN42 with two MID16 modules Start (all elements) Start I>, Start I>>,...etc Trip (all elements) Trip I>>, Trip I>>,...etc Measures IL1, IL2,...ecc Temperature Pt100 Block inputs BLK2IN-Iph, BLK2IN-IE,...etc Outputs: Relays K11...K6 on board K7...K10 with MRI module LEDs START, TRIP, L1...L6 on board L7...L10 with MRI module Block outputs BLK2OUT-Iph, BLK2OUT-IE,...etc Current converter DAC Note 1 For the DFR function a licence is required; call Thytronic for purchasing. Note 2 The measures of temperature are available only when the MPT module on Thybus is enabled (eigth Pt100 inputs) Note 3 Output relay K7...K10 and binary input IN3...IN42 states are available only when the concerning I/O circuits are implemented (MRI and MID16 modules on Thybus) Note 4 For the PLC function a licence is required; call Thytronic for purchasing. Note5 With ThyVisor and compiler IEC 61131-3 V1.2.7 only the IL language is implemented (Instruction List); other languages, according with IEC 61131 standard (ST (Structured Text)), LD (Ladder Diagram), FBD (Function Block Diagram), SFC (Sequential Functional Chart), will be available soon Note 6 The input state is acquired downstream the tON and tOFF timers

NA20 - Manual - 04 - 2022

3.9 METERING More data (range and accuracy) are available inside Section 5 - MEASURES, LOGIC STATES AND COUNTERS � Accuracy (type tests) MEASURE Reference values Accuracy Reference values Accuracy Phase current 0.1 In 0.2% 1 In 0.03% Measured residual current 0.01 IEn 0.3% 1 IEn 0.02% Calculated residual current 0.1...1 IECn 2% 1 IECn 0.3% Frequency 0.02 Un 3 mHz 1 Un 2 mHz Positive/Negative sequence current I1 = 0.5 In 0.5% I1 = 1 In 0.5% Pickup and operate time 1.5 x setting for fist element 5% ± 10 ms 2.5 x setting for other elements 5% ± 10 ms � Measures Direct Frequency (f ) RMS value of fundamental component for phase currents (IL1, IL2, IL3) RMS value of fundamental component for residual current (IE) Calculated Thermal image (DTheta) Maximum current between IL1-IL2-IL3 (ILmax) Minimum current between IL1-IL2-IL3 (ILmin) Average current between IL1-IL2-IL3 (IL) Sequence Positive sequence current (I1) Negative sequence current (I2) Negative sequence current/positive sequence current ratio (I2/I1) 2nd harmonic Second harmonic of phase currents (IL1-2nd, IL2-2nd, IL3-2nd) Maximum of the second harmonic phase currents/ fundamental component percentage ratio I-2nd /IL (I-2nd /IL) 3rd harmonic Third harmonic of phase currents (IL1-3rd, IL2-3rd, IL3-3rd) Third harmonic of residual current (IE-3rd) 4th harmonic Fourth harmonic of phase currents (IL1-4th, IL2-4th, IL3-4th) 5th harmonic Fifth harmonic of phase currents (IL1-5th, IL2-5th, IL3-5th) On demand Phase fixed currents demand (IL1FIX, IL2FIX, IL3FIX) Phase rolling currents demand (IL1ROL, IL2ROL, IL3ROL) Phase peak currents demand (IL1MAX, IL2MAX, IL3MAX) Phase minimum currents demand (IL1MIN, IL2MIN, IL3MIN) PT100 [1] Temperature PT1 (T1) Temperature PT2 (T2) Temperature PT3 (T3) Temperature PT4 (T4) Temperature PT5 (T5) Temperature PT6 (T6) Temperature PT7 (T7) Temperature PT8 (T8) Note 1 The measures of temperature are available only when the MPT module on Thybus is enabled (eigth Pt100 inputs)

NA20 - Manual - 04 - 2022

4 F U N C T I O N C H A R A C T E R I S T I C S 4 F U N C T I O N C H A R A C T E R I S T I C S 4.1 HARDWARE DESCRIPTION The following figure illustrates the device layout. Printed boards hold the circuit components arranged according to a modular allocation of the main functions. hw.ai RTC EEprom Flash SRam SRam SPI CPU ETHERNET CPU BOARD POWER SUPPLY BOARD INPUT MODULE DSP DUAL PORT 1A/5A ≈ ≈ ≈ ≈ EEprom Thybus RS485 RELAYS K1...K6 Output contacts USB MMI LCD LEDs BINARY INPUTS IN1 Input IN2 BLOCK I/O BLKIN Input BLKOUT POWER SUPPLY +5 V +10 V 0 V +24 V -10 V POWER FAIL RESET Uaux

NA20 - Manual - 04 - 2022

Power supply board All the components necessary for conversion and stabilization functions are present. Two versions are envisaged suited to the input ranges 24...48 V and 115...230 V. The circuit provides stabilized voltages of +10 V and -10 V, required for the analogue measurement, +24 V for relays and +5 V for supplying the digital circuits. The circuit board additionally comprises: INPUT CIRCUITS: • Two binary input circuits, • One block input circuit (BLIN1). The logical input circuits and the block circuits include photo-couplers which provide for galvanic separation. OUTPUT CIRCUITS: • One block output circuit (BLOUT 1), • Six output relays (k1...K6). CPU board This circuit board contains all the circuits necessary for performing the analogue and digital pro- cessing of the signals. Analog processing The following are envisaged: • Anti aliasing filter circuits, • Amplifier circuits for conditioning the input signals, • Reference voltage adjustment circuits for the measurement A/D converter. The Pro-n relays use a DSP processor operating at 40 MHz; it performs all the processing on the analogue signals and furthermore coordinates management of the TX-RX signals to the CPU. The input currents are sampled at a frequency of 24 samples per period by means of a dual conver- sion system which allows the attainment of information pertaining to polarity and amplitude with high resolution. The measurement criterion allows precise measurement of even those signals having a unidirectional component, such as transient currents with overlapping exponential, which typically appear during faults. The circuit board also houses the output relays with the corresponding command and control cir- cuits, communication circuits, buttons, LCD display, LEDs and the key switch. CPU A 32 bit CPU is provided. The following are envisaged: • Real Time Clock circuits with oscillator and super capacitor, • USB communication port, • RS485 communication port, • Thybus communication circuits for external modules and MMI board, • Network communication circuits (optional Ethernet). Memories: • SRam: high speed static memory, used for data and cache, • Flash memory: used for fw storage and upgrade, • EEprom memory: used for calibration data storage, • Dual port Ram for data transfer between CPU and DSP. Input board • Three CTs committed for phase currents acquisition, • One CT committed for residual current acquisition. The input circuits are suitable for 1 A or 5 A external CTs.[1] • Three VTs committed for phase voltages acquisition, • One VT committed for residual voltage acquisition. MMI (keyboard, LED and display) The MMI module (Man Machine Interface) includes: • An eight keys 8 keyboard, • a backlight LCD display, • Eight signalling LEDs, The removable plug allows separation of the MMI module for free access to the CPU board when DIP-switch setting is required. Note 1 The phase and residual nominal currents must be adjusted by means dip-switch.

NA20 - Manual - 04 - 2022

4.2 SOFTWARE DESCRIPTION The program which handles operation of the Pro-N relays is made up of three fundamental elements shown in the following block diagram. Base software Single modules are application independent with modular and scalable structure. The system can be assimilated to the PC BIOS (Basic Input-Output System); three main function are provided: • Start-up test execution; • RAM loading of the operating system; • Provide a suitable interface to access the relay hardware. Real-time operating system An embedded operative system is employed suitable for real-time applications (RTOS). A multithread preemptive structure is able to menage several task with multiple priority levels . The kernel represents the nucleus of the system: it includes the processing functions closest to the electronic circuits. In addition, the kernel manages a service communication protocol known as Basic Protocol (BP). Task The task (process e thread) are the base components. Example are: • Keyboard management • RTC (Real Time Clock) updating • RAM/EEPROM updating • Diagnostic • Input acquisition • Output relay management • MMI • I/O updating • DSP data processing sw.ai KEYS PC com Sync Binary inputs Output relays LEDs Fast devices EEPROM Slow devices RTC refresh EEPROM update Diagnostic DSP MMI task Oscillography Measures Drivers sampling RTOS timer SIMBOLOGIA Processo (task) Libreria funzionale (Drivers) Timer del sistema operativo Interrupt RTOS timer I/O I/O boards KEYS RTOS timer RAM/EPROM memory check RTOS timer RTOS timer DATA BASE TIMER Ethernet USB RS485 Counters Events Data Base Messages Thybus +

NA20 - Manual - 04 - 2022

DSP Firmware By means of Discrete Fourier Transform calculation, based on 24 samples/period, information is de- duced in relation to the amplitude and phase of all the current measurements; these are constantly updated and at the disposal of all the protection and control application algorithms. Drivers Inside the driver library, all the specialized module for protection and control function are provided. They are the link from kernel and application layer. Examples are: • Data base management • PC messages management • TCP/IP messages management • Basic Protocol management • Counter management • Event and fault management • Measuring management • Oscillography management Application Software The software acts the specialization of the base system; all protective and control elements are inside it. The main modules ate: • Diagnostic function for application layer, • Input management (binary inputs), • Protective functions, • Event recording, • Output management (LEDs and relays) Each element (Kernel, Drivers and Application) may, in turn, be split into modules: Base protocol (kernel) The module known as the Basic Protocol (BP) manages the service communication between the kernel and the other modules through the communication buses with the following services: • Data and information exchange, • Calibration, • Upgrade fw DSP, • Upgrade application sw Communication (drivers) The ModBus TCP/IP protocol, with ethernet interface, the ModBus RTU, IEC 60870-5-103 and DNP3 protocol over RS485 interface and the ModBus RTU USB for ThyVisor are provided. MMI (drivers) The drivers deal with the menu management (MMi and/or communication messages). Data Base The data base is split into three main sections: • RAM for volatile data, • REE and PAR for non volatile data. Self test (Application) The main hw and sw function are permanently verified in background; no additional delay are intro- duced. In particular the following function are tested: • Reference voltages; • Output relays; • Sw flow with execution time monitoring; • REE and PAR data congruence. Development tools (Builder) For the development of the project, a CASE instrument has been developed, responsible for the opti- mized production of software code for the management of collaboration, the database and the MMI data and the Xml files used for communication. The automatic code generation criteria ensures the quality of the result in terms of the reusability, verifiability and maintainability of the software life cycle.

NA20 - Manual - 04 - 2022

4.3 I/O DESCRIPTION Metering inputs The following input are provided: • Three phase current inputs. • One residual current input. • The nominal currents are independently adjustable at 1 A or 5 A through DIP-switches. The input circuits are appropriately dimensioned in order to withstand the currents which arise when a fault occurs, both in transient and steady state condition. Signal processing Several processing levels are involved: • Acquisition (base level). • Direct measures of physical channels (first level). • Calculated measures (second level). • Derived (third level). The measures concerning a level are based on data worked out in the previous level. For each level the required resources concerning the priority for tasks (conditioning circuits, DSP and CPU) are on hand. ACQUISITION (base level) The input signals are sampled 24 times per period: - iL1...iL3 Phase current instantaneous values - iE Residual current instantaneous value From the sampled quantities, several measures are computed for protection, monitoring and meter- ing purposes. • Direct • Calculated • Phase • Sequence • Harmonic • Demand Direct • Frequency. The measure of period is taken from current inputs. sensori.ai NA20 3 phase current inputs 1 residual current input acquisizione.ai ACQUISITION INSTANTANEOUS MEASURES ≈ F.ai (Hz) ACQUISITION IL1 IL2 CT IL3 iL1 iL2 ≈ ≈ iL3 ≈ f T

NA20 - Manual - 04 - 2022

Samples are processed by means DFT (Discrete Fourier Transform) algorithm and the phase and amplitude of fundamental are computed: • Phase currents IL1, IL2, IL3 • Residual current IE Calculated By means vector addition of direct measures the following are calculated (RMS value of fundamen- tal components): • Thermal image ∆θ Sequence • Fundamental RMS positive sequence current: I1 • Fundamental RMS negative sequence current: I2 On demand • Fixed demand (IL1FIX, IL2FIX, IL3FIX, ±PFIX, ±QFIX) Inside an adjustable time interval tFIX, an average magnitude is calculated for phase currents IL1, IL2, IL3, active power ±P and reactive power ±Q of measures taken every second. The average values are stored at the end of the same time interval. IL1.ai (In) ACQUISITION iL1, iL2, iL3 DFT CT ≈ IL1, IL2, IL3 IE.ai (IEn) ACQUISITION iE DFT CT ≈ IE Theta.ai IL1 I2 I2 = (IL1+ e-j120°IL2+ e+j120°IL3) I1 = (IL1+ e+j120°IL2+ e-j120°IL3) IL3 IL2 I1 Ith = √(I12+ K22∙I22) ∆θ (∆θB) 2 d∆θ dt IB Ith ∆θ T+ T+ ( ) + = I1-I2.ai IL1 I2 I2 = (IL1+ e-j120°IL2+ e+j120°IL3) / 3 I1 = (IL1+ e+j120°IL2+ e-j120°IL3) / 3 IL3 IL2 (In) I1 (In) e-j120°= - j √3 1 2 2 - e+j120°= - j √3 1 2 2 + Fix-Demand.ai 1s IL1FIX, IL2FIX,IL3FIX tFIX (In ) IL2 IL1 IL3 ILxFIX ILxn tFIX ∙ 60 tFIX ∙ 60 n=1 ∑ 1 tFIX tFIX tFIX

NA20 - Manual - 04 - 2022

• Rolling demand (IL1ROL, IL2ROL, IL3ROL, ±PROL, ±QROL) Inside an adjustable time interval NROL∙tROL , an average magnitude is calculated for phase currents IL1, IL2, IL3, active power ±P and reactive power ±Q of measures taken every second, where tROL is the length of any time subinterval and NROL is the number of the time intervals. The average values are stored at the end of the same time subinterval. • Peak (IL1MAX, IL2MAX, IL3MAX, ±PMAX, ±QMAX) Inside an adjustable time interval tROL, the maximum magnitude is calculated for phase currents IL1, IL2, IL3, active power ±P and reactive power ±Q of measures taken every second. The average values are stored at the end of the same time interval tROL (Rolling demand common parameter). • Minimum (IL1MIN, IL2MIN, IL3MIN, ±PMIN, ±QMIN) Inside an adjustable time interval tROL, the minimum magnitude is calculated for phase currents IL1, IL2, IL3, active power ±P and reactive power ±Q of measures taken every second. The average values are stored at the end of the same time interval tROL (Rolling demand common parameter). Use of over-described measures is shown in the following tables. Rol-Demand.ai Esempio media mobile con NROL=4 IL1ROL IL2ROL IL3ROL (In ) IL2 IL1 IL3 0 1 2 3 4 5 1s tROL tROL NROL tROL tROL tROL 6 tROL Media aritmetica nell’inervallo tROL ILxROL= ILxk tROL∙60 tR OL∙60 k=1 ∑ NR OL n=1 n ∑ 1 NROL 1 Max-Demand.ai Massimo valore delle medie nell’inervallo tROL Media aritmetica nell’inervallo tROL IL1MA X IL2MA X IL3MA X (In ) IL2 IL1 IL3 1s tROL tROL tROL tROL tROL tROL ILxMA X= MAX ILxn tROL∙60 tR OL∙60 n=1 ∑ 1 Min-Demand.ai Minimo valore delle medie nell’inervallo tROL Media aritmetica nell’inervallo tROL Reset IL1MIN IL2MIN IL3MIN (In ) IL2 IL1 IL3 1s tROL tROL tROL tROL tROL tROL ILxMIN= MIN ILxn tROL∙60 tR OL∙60 n=1 ∑ 1

NA20 - Manual - 04 - 2022

Conventions Phase rotation direction The conventional rotation direction for the current phasors is counter-clockwise. Cyclic phase sequence order For three phase rotating currents, a direct cyclic sequence is defined when the three phases are L1, L2, L3 ordered, while an inverse cyclic sequence is defined when the three phases are L1, L3, L2 ordered. fasori.ai fasori1.ai UL1 UL3 UL2 UL1 UL2 UL3 Direct sequence cyclic order Inverse sequence cyclic order

NA20 - Manual - 04 - 2022

Use of measured values f iL1, iL2, iL3 IL1, IL2, IL3 IL1-2nd, IL2-2nd, IL3-2nd IL1-3rd, IL3-3rd, IL3-3rd IL1-4th, IL2-4th, IL3-4th IL1-5th, IL2-5th, IL3-5th iE IE IE-3rd I1 I2 Temperature (PT1....PT8) Binary inputs IN1, IN2...INx Start (START) Relays K1...K6 Trip (TRIP) Relè K1...K6...K10 Start (START) LEDs L1...L5 Trip (TRIP) LEDs L1...L5 Selective block input BLIN1 Selective block output BLOUT1 Cold Load Pickup (CLP) Second harmonic restraint Logic block - BLOCK1 Breaker failure (BF) PROTECTION Thermal with Pt100 probes (26)  Undercurrent (37)        Negative sequence overcurrent (46)            Negative sequence-positive current ratio         Thermal image (49)              Phase overcurrent (50/51)            Residual overcurrent (50N/51N)            Breaker failure (BF)         CONTROL and MONITORING CT Monitoring (74CT)   Trip Circuit Supervision (TCS)  Second harmonic restraint (2NDH-REST)  Logic block (BLOCK1)  Selective block (BLOCK2)    Diagnostic    Element states  Binary input states  Selective block state (Block2)   Output relay states     MEASURES Frequency  Phase currents  Residual current  Positive sequence current  Negative sequence current  Harmonic currents      Thermal image  Temperature (Pt100 on MPT module)  EVENT RECORDER Event 0      Event 1      Event ...      Event 299      FAULT RECORDER Fault 0        Fault 1        Fault ...        Fault 19        OSCILLOGRAPHY Record 1              Record 2              Record ...             

NA20 - Manual - 04 - 2022

Binary inputs Two or five binary inputs are available on board, up to 40 binary inputs may be added with auxiliary modules. The dry inputs must be powered with an external voltage, (usually the auxiliary power supply). The connections are shown in the schematic diagrams. The following settings can be used to configure each input: • Logic Active-ON (activated when powered), or Active-OFF (activated when power is turned off). • ON Timer (OFF-to-ON time delay) and OFF Timer (ON-to-OFF time delay). • Binary input allocation. Adjustable debounce timer allows any transient to decay avoiding false activation of the input; the positive transition is acquired if the input is permanently high for a time interval longer than the tON setting delay; similarly for the negative transitions, the negative transition is acquired if the input is permanently high for a time interval longer than the tOFF setting delay. In the above shown diagram, INTERNAL STATE represents the logical state of the binary input used in the following processing. Each binary input may be matched to one of the following default functions. FUNCTIONS Binary inputs IN1 IN2 INx Reset LEDs    Set profile (switching setting A and B)    Fault trigger (fault recording)    Block2 IPh/IE (selective block from phase and/or ground elements)    Block2 IPh (selective block from phase elements)    Block2 IE (selective block from ground elements)    Block1 (logic block)    TCS1 (Trip Circuit Supervision)    TCS2 (Trip Circuit Supervision)    Trip ProtExt (trip from external protection relays)    Reset counters    Reset CB Monitor (clear CB monitoring data)    52a (CB auxiliary contact)    52b (CB auxiliary contact)    Open CB    Close CB    Preset DTheta (thermal image preset)    Remote trip    Reset on demand measures    BINARY INPUT INTERNAL STATE tON tON tOFF tOFF t binary-timers.ai

NA20 - Manual - 04 - 2022

Reset LEDs If the element tripped have gone back to rest condition, the latched LEDs and/or relays may be reset. Set profile Inside Pro-N devices, two independent setting profiles (A and B) are available. Whereas different settings are required, they are made in the setting profiles and stored in the non volatile memory of relay. Applicable setting profile is activated usually via a binary input; when the programmed input is activated, the profile B becomes operative as a replacement for the default profile A.[1] Fault trigger When the programmed input is activated, a trigger is issued for fault record SFR). Data storing takes place with the same procedure resulting from a trip of any protective elements Note 1 To enable the profile switching the “Input-selected” parameter must be set inside the “Profile selection” submenu. If multiple setting groups are not required, Group A is the default selection Reset-led.ai TRIPPING MATRIX (LED+RELAYS) ≥ ≥ & & Set (ON≡turn on LED/relay) S Set-Reset latch R Reset (ON≡turn off LED/relay) Reset LEDs Binary input allocation for reset signalling (LEDs) T 0 INx t ON T 0 n.o. n.c. INx tON Logic INx tOFF INx t OFF Binary input INx Switch-profile.ai (A, B, from binary input) OFF≡Profile A, ON≡Profile B Binary input allocation for switching of setting profiles Profile A Profile B Profile A Profile selection Profile B Set profile T 0 INx t ON T 0 n.o. n.c. INx tON Logic INx tOFF INx t OFF Binary input INx Trigger-faults.ai Binary input allocation for fault recorder trigger Fault trigger T 0 INx t ON T 0 n.o. n.c. INx tON Logic INx tOFF INx t OFF Binary input INx Fault recording Protection element IL1->IL1r IL2->IL2r ..... DTheta->DTheta-r Inputs Outputs Fault cause info ≥1

NA20 - Manual - 04 - 2022

Block2 IPh/IE A change in status of a binary input effects a block[1] common for the following phase and ground protective elements: • I>, I>> and I>>> (50/51), • DthAL1, DthAL2 and Dth (49), • I2>, I2>> (46), • IE>, IE>> and IE>>> (50N/51N), The application of the binary inputs for the acquisition of Block2 (selective block) coming from ex- ternal protection relays is shown in the following figure (one phase overcurrent and one phase and residual overcurrent protection). Block2 IPh A change in status of a binary input effects a block[2] for the following phase protective elements: • I>, I>> and I>>> (50/51), DthAL1, DthAL2 and Dth> (49), I2>, I2 >> (46) Block2 IE A change in status of a binary input effects a block[1] for the following earth protective elements: • IE>, IE>> and IE>>> (50N/51N)). Block1 A change in status of a binary input effects a block for a length of time equal to the activation of the input[3]; the element pickup that wish be blocked must be enabled (the Block1 parameter must be set to ON in the concerning menu).[4] The application of the binary input for the acquisition of the Block1 (logic block) coming from external signal is shown in the following figure; in the example the block signal is ORed with Block2 (selective block) to block the generic (xxx) element. Note 1 The exhaustive treatment of the Block 2 function is described in the “Logic selectivity” paragraph. Note 2 The exhaustive treatment of the Block 2 function is described in the “Logic selectivity” paragraph. The application of the inputs for the acquisition of Block2 (selective block) for Phase (Block2 Iph) and earth protective functions (Block2 IE) is similar to that illustrated in the scheme concerning the Block2 IphIIE Note 3 Unlike the Block2 (selective block), that houses a safety logic founded on programmable timers, the Block1 (logic block) keeps block of the protection for the whole time when the input is active. Note 4 The activation of one binary input produces indiscriminately a block of all protective elements programmed for being blocked from Block1 ≥1 ≥1 ≥1 Block2IPh/IE T 0 tB-Iph BlockIph-Ie.ai Binary input allocation for logic selectivity (Block2) tB-Iph tB-IE xxxxx Trip Block2 Block2 input enable (ON≡Enable) & Block2 IN towards reset timer IPh Block2 input IE Block2 input Block2 IN diagnostic Block2 input FROM ANY PROTECTIONS FROM OVERCURRENT PROTECTIONS T 0 tB-IE IPh/IE Block2 Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF FROM EARTH FAULT PROTECTIONS Block1.ai xxxx Block1 Enable (ON≡Enable) Block1 input (ON≡Block) Block1 from Block2 (ON≡Block) & Block1 Block1 Binary input INx Binary input allocation for logic block (Block1) Blocking T 0 IN1 t ON T 0 n.o. n.c. INx tON Logic INx tOFF IN1 t OFF ≥1

NA20 - Manual - 04 - 2022

TCS1 and TCS2 Trip Circuit Supervision. Supervision with one or two binary input can be performed. The exhaustive treatment of the TCS function is described in the concerning paragraph. Trip ProtExt The binary input detects a trip coming from an external protective relay: the information is available for the breaker failure function (BF). Reset counters A change in status of a binary input effects a reset of all start/trip partial counters.[1] Reset CB Monitor A change in status of a binary input effects a reset of all counters concerning the circuit breaker diagnostic: • Breaking Sum phase IL1 • Breaking Sum phase IL2 • Breaking Sum phase IL3 • Breaking SumI2t phase IL1 • Breaking SumI2t phase IL2 • Breaking SumI2t phase IL3 • CB Open counter 52a and 52b The CB position can be acquired by means of binary inputs connected to the auxiliary contacts: the information is used in the following functions: • CB position (open-closed) • CB diagnostic (N. of operations, trip time) • Breaker Failure (BF) Note 1 The reset of the total counters is practicable by means ThyVisor command with Session Level 1 (available with password) TCS2.ai TRIP +UAUX Trip Circuit Supervision - 74TCS with two binary inputs -UAUX 52a 52b 52 TCS1 TCS2 74TCS logic 74TCS logic Binary input INx T 0 IN1 t ON 0 n.o. n.c. IN1 tON Logic IN1 tOFF IN1 t OFF Binary input INx T 0 IN1 t ON 0 n.o. n.c. IN1 tON Logic IN1 tOFF IN1 t OFF ExtProt.ai Binary input allocation for trip acquisition from external protection device Breaker failure (BF) +UAUX -UAUX IN- IN+ Trip ProtExt Binary input INx T 0 INx t ON T 0 n.o. n.c. IN1 tON Logic IN1 tOFF INx t OFF CB-pos.ai CB position CB diagnostic Breaker failure (BF) 74VT 52a 52 52b UAUX UAUX INx INx 52a 52b Binary input INx T 0 IN1 t ON T 0 n.o. n.c. INx tON Logic INx tOFF IN1 t OFF Binary input INx T 0 IN2 t ON T 0 n.o. n.c. INx tON Logic INx tOFF IN2 t OFF Binary input allocation for CB state acquisition

NA20 - Manual - 04 - 2022

Open CB Close CB The external acquisition of remote commands allows to drive CB remotely. Preset DTheta The input activation presets the thermal image (49). The preset value can be adjusted by means the DθIN setting. The thermal image is initialized at the DθIN value when the device is powered or when the binary input become active. Remote trip The input activation drives an expressly programmed output relay. Reset on demand measures The input activation make a reset of all demand measures. CB-com.ai OPEN Command CLOSE Command UAUX +UAUX UAUX INx INx Binary input INx T 0 INx t ON T 0 n.o. n.c. INx tON Logic Open CB Close CB INx tOFF INx t OFF Binary input INx T 0 IN2 t ON T 0 n.o. n.c. INx tON Logic INx tOFF IN2 t OFF Binary input allocation for CB remote command TRIPPING MATRIX (LED+RELAYS) -UAUX -UAUX 52 52a O I 52b inhit-theta.ai t = T+·ln{[(Ith/IB)2-DθP/DθB]/[(Ith/IB)2-1.2] DθP = DθIN Binary input allocation for thernal image preset (49) UAUX UAUX INx PresetDTheta PresetDTheta Binary input INx T 0 Logic INx t ON IN1 t ON INx t OFF 0 n.o. n.c. IN1 t OFF Remote-trip.ai Remote trip UAUX UAUX Remote trip Binary input INx INx T 0 INx t ON T 0 n.o. n.c. INx tON Logic INx tOFF INx t OFF TRIPPING MATRIX (LED+RELAYS) Binary input allocation for remote trip

NA20 - Manual - 04 - 2022

Output relays Six output relays are available on board (K1...K6):[1] • K1 and K2 have two changeover contacts (SPDT, type C). • K3, K4 and K5 have one make contact (SPST-NO, type A).[2] • K6 has one break contact (SPST-NC, type B).[3] Each output relay may be programmed with following operating mode: • Operation�MODE (No latched, Pulse, Latched). • Logic (Energized/De-energized). To each output relay a programmable timer is matched (Minimum�pulse�width parameter). All parameters are available inside the Set\Relays menu. Any change to the settings can be affected at any time, also with the relay on duty, separately for each relay. Notes: • When de-energized operating mode is set, the relay remains in rest condition if no trip command is in progress. • When energized operating mode is set, the relay remains in operating condition if no trip command is in progress and the auxiliary supply is powered on. • When no-latched operating mode is set (Operation�MODE No latched), the output relay reset at the end of the trip condition. To each output relay a programmable timer is matched (minimum pulse width operation). • When latched operating mode is set (Operation�MODE Latched), the output relay doesn’t reset at the end of the trip condition; it stays ON until a reset command is issued (RESET key, ThyVisor or communication command). • When pulse operating mode is set (Operation�MODE Pulse), the output relay reset after a tTR programmable delay regardless of the trip condition. • It is advisable to make sure that the output contact technical data are suitable for load (Nominal current, breaking capacity, make current, switching voltage,...). Matching every output relay to any protective element is freely programmable inside the Setpoints� submenus according a tripping matrix structure.[4][5] Note 1 Schematic diagram are shown inside APPENDIX B1; more relays (K7...K10) are available with MRI auxiliary module Note 2 K3 and K4 have a common terminal (A10) Note 3 K5 and K6 have a common terminal (A13) Note 4 Matching of the output relay to the protective and control functions can be defined so that any collision from other function is avoided. All output relay are unassigned in the default setting. Note 5 Self test relay: it is advisable to plan the following settings: - Energized operating mode, - No-latched , in order that it stays ON for normal conditions and the other way round it goes OFF if any fault is detected and/or the auxiliary supply turns OFF. Input No-latched operation Latched operation Pulse operation Output relay operation Minimum pulse width Relay-operation-timers.ai t Minimum pulse width tTR tTR

NA20 - Manual - 04 - 2022

FUNCTIONS RELAYS K1 K2 K3 K4 K5 K6 Self-test relay       ThALx Alarm relays (ThAL1-K...ThAL8-K)       ThALx Trip relays (Th>1-K...Th>8-K)       I< Start relays (I< ST-K)       I< Trip relays (I< TR-K)       U<< Start relays (U<< ST-K)       U<< Trip relays (U<< TR-K)       I2> Start relays (I2>ST-K)       I2> Trip relays (I2>TR-K)       I2>> Start relays (I2>>ST-K)       I2>> Trip relays (I2>>TR-K)       DthAL1 Alarm relays (DthAL1-K)       DthAL2 Alarm relays (DthAL2-K)       Dth> Trip relays (Dth>-K)       I> Start relays (I>ST-K)       I> Trip relays (I>TR-K)       I>> Start relays (I>>ST-K)       I>> Trip relays (I>>TR-K)       I>>> Start relays (I>>>ST-K)       I>>> Trip relays (I>>>TR-K)       IE> Start relays (IE>ST-K)       IE> Trip relays (IE>TR-K)       IE>> Start relays (IE>>ST-K)       IE>> Trip relays (IE>>TR-K)       IE>>> Start relays (IE>>>ST-K)       IE>>> Trip relays (IE>>>TR-K)       I2/I1 Start relays (I1/I2>ST-K)       I2/I1 Trip relays (I1/I2> TR-K)       I2ndh> Start relays (I2ndh>ST-K)       S< Trip relays (S

NA20 - Manual - 04 - 2022

LED indicators Eight LEDs are available. • One green LED “ON”: if turned on it means that the device is properly working, if flashing the inter- nal self-test function has detected an anomaly. • One yellow LED “START” tagged for START of one or more protective elements.[1] • One red LED “TRIP” tagged for TRIP of one or more protective elements.[1] • Five red LEDs “1...5” for highlight the activation of one or more user defined function. Each output relay may be programmed with following operating mode: • No-latched: the LED reset at the end of the trip condition. • Latched: the LED doesn’t reset at the end of the trip condition; it stays ON until a manual reset command is issued (RESET key, ThyVisor or communication command). Any change to the settings can be affected at any time, also with the relay on duty, separately for each LED. Free allocation of each LED may be set according to the matrix structure shown in the following page.[2] Note 1 The START and the TRIP LED are user assignable to any function; other than starting and tripping information can be assigned to them too, just the same for L1...L5 Note 2 All LEDs are unassigned in the default setting. Led CB Open CB Close

NA20 - Manual - 04 - 2022

FUNCTIONS LEDs START TRIP 1 2 3 4 5 ThALx Alarm LEDs (ThAL1-L...ThAL8-L)        ThALx Trip LEDs (Th>1-L...Th>8-L)        I< Start LEDs (I< ST-L)        I< Trip LEDs (I< TR-L)        I2> Start LEDs (I2>ST-L)        I2> Trip LEDs (I2>TR-L)        I2>> Start LEDs (I2>>ST-L)        I2>> Trip LEDs (I2>>TR-L)        DthAL1 Alarm LEDs (DthAL1-L)        DthAL2 Alarm LEDs (DthAL2-L)        Dth> Trip LEDs (Dth>-L)        I> Start LEDs (I>ST-L)        I> Trip LEDs (I>TR-L)        I>> Start LEDs (I>>ST-L)        I>> Trip LEDs (I>>TR-L)        I>>> Start LEDs (I>>>ST-L)        I>>> Trip LEDs (I>>>TR-L)        IE> Start LEDs (IE>ST-L)        IE> Trip LEDs (IE>TR-L)        IE>> Start LEDs (IE>>ST-L)        IE>> Trip LEDs (IE>>TR-L)        IE>>> Start LEDs (IE>>>ST-L)        IE>>> Trip LEDs (IE>>>TR-L)        I2/I1 Start LEDs (I1/I2>ST-L)        I2/I1 Trio LEDs (I1/I2>TR-L)        I2ndh> Start LEDs (I2ndh>ST-L)        I2ndh> Trip LEDs (I2ndh>TR-L)        S< Trip LEDs (S

NA20 - Manual - 04 - 2022

Communication interfaces Several communication ports are provided: • USB port on the front side for local communication (ThyVisor). • RS485 port on the rear side for bus communication. • Ethernet port on the rear side for bus communication. USB To connect the local port you need to use a cable USB Type B - Type A; the Thytronic cable code L10042 can be supplied. The serial port is the simplest access for setting by means the ThyVisor software. RS485 Several protocol are implemented[1]: • ModBus RTU. Modbus is a serial communications protocol. It is a de facto standard communica- tions protocol in industry, and is now the most commonly available means of connecting industrial electronic devices also inside electric utilities and substation. • IEC 60870-5. The IEC 60870-5 suite of protocol is used for communications from master station to substation, as well within the substation; the IEC 60870-5-103 (Protection equipment) is available together the Modbus protocol on some version of Pro-n devices (code NAxx#xxxxC x). Ethernet It is provided (optionally) a communication board useful for Ethernet communication with ModBus TCP/IP protocol.[2] Modbus/TCP basically embeds a Modbus frame into a TCP frame in a simple manner. This is a con- nection-oriented transaction which means every query expects a response. This query/response technique fits well with the master/slave nature of ModBus, adding to the de- terministic advantage that Switched Ethernet offers industrial users. In the same way as the RS485 base Modbus, every device is identified by a personal address and the communication goes in “client-server” mode with answering request from the recipient. The protective relay can be directly connect to the Ethernet network (no gateway, protocol converter are needed). Two port can be implemented: • 100BASE-TX with RJ45 connector (copper). • 100BASE-FX with FX connector (optical fiber)[2] For both modules no hw preset are required. Two LEDs are on board (RJ45): • LINK - (green): The LED lights up if the connection is active. • TX - (yellow): The LED lights up when data transmission is active. Note 1 The RS485 port is not implemented on the Pro-N devices endowed with Ethernet FX port Note 2 Information about the ModBus map may be find inside the “Remote programming manual” ethernet-sch.ai RX FX Ethernet (no RS485 port) TX 1 TX+ 2 TX- 3 RX+ 4 5 6 RX- 7 8 RJ45 Ethernet+RS485 ports RS485 F1 F2 F3 F4 F5 A+ B-

NA20 - Manual - 04 - 2022

4.4 PROTECTIVE ELEMENTS Rated values Inside the Base menu the following parameters can be set: • Relay reference name. • Relay nominal currents (phase and residual), to which the regulation are related. • Primary nominal values, employed for measures relative to primary values. • Measurements reading mode. Information for settings: • Relay reference name. Alphanumeric mnemonic string (max 16 characters) useful for identification of protected plant. • Relay nominal frequency fn This nominal value must be set same as the frequency of the grid. Example: grid frequency fn = 50 Hz Relay nominal frequency fn = 50 Hz • Relay phase nominal current In This nominal value must be set by means dip-switch to 1 A or 5 A, same as the secondary CTs nominal current. Dip-switches are located on board of the CPU module; the exhaustive treatment of Dip setup is described in the “6.5 SETTING NOMINAL CURRENTS In AND IEn” paragraph. • Relay residual nominal current IEn This nominal value must be set by means dip-switch to 1 A or 5 A, same as the secondary CT nomi- nal current. Dip-switch is located on board of the CPU module; the exhaustive treatment of Dip setup is de- scribed in the “6.5 SETTING NOMINAL CURRENTS In AND IEn” paragraph. • Phase CT primary current Inp This parameter affects the measure of the phase currents when the primary measurement read- ing mode is selected. It must be programmed to the same value of the phase CT primary nominal current. Example The phase CT primary current Inp must be set as: Inp = 500 A • Residual CT primary current IEnp This parameter affects the measure of the residual current when the primary measurement reading mode is selected. It must be programmed to the same value of the residual CT(s) primary nominal current. Example 1 The residual CT primary current IEnp must be set as: IEnp = 100 A Es-In.ai KCT = 500A/5A=100 52 In NA20 Es1-IEn.ai 1x KCT = 100 A /1 A 52 IEn= 1 A NA20

NA20 - Manual - 04 - 2022

Example 2 The residual CT primary current IEnp must be set as: IEnp = 100 A • Measurement reading mode Measures may be displayed according the following operating modes: - With RELATIVE setting all measures are related to the nominal value, - With PRIMARY setting all measures are related to the primary value. Es2-IEn.ai 3x KCT = 100A / 5A 52 IEn= 5 A NA20

NA20 - Manual - 04 - 2022

Thermal protection with RTD thermometric probes - 26 Preface The measure of temperature is acquired by means of Pt100 (RTD Resistive Temperature sensing Devices) probed, connected to the MPT module.[1] A direct thermal protection element with eight PT100 thermometric probes (RTD Resistive Thermal Device) provides protection against premature ageing or breakdown of the insulating materials through overheating. Thermal protection using thermometric probes offers greater reliability than Thermal overload-based indirect protection, since it is not influenced by inaccuracies in the time constant for the thermal model of the machinery and by variations in the surrounding temperature. For each thermometric probe an alarm (ThALx, where x=1...8 points one of the eight probes) and one trip adjustable threshold is provided (Th>x), with adjustable operating time (tThALx and tTh>x>);if the measured temperature overcomes the threshold, the relative alarm and/or trip is issued when the timer expires. The adjustments are operable in °C. The probes should be placed in strategic points around the machinery susceptible to the greatest overheating, such as for example: - near the generator stator windings, near the step-up transformer windings and/or in the oil, with the aim of detecting overheating produced by the overload currents, - near the generator bearings, with the aim of detecting localised overheating due to worn or non- lubricated bearings. The Pt100 probes detect the temperature in the range -50 °C...+250 °C (at 0 °C its resistance is 100 ohm); an alarm indicates any interruption or short-circuiting of the probe or related connections to the MPT module; the information is available inside the Read \ PT100 menu: • Ptx probe ON to point a measure inside the range • Ptx probe LOW to point a measure lower the range (short circuit of probe and/or wires) • Ptx probe HIGH ao point a measure higher the range (breaking of probe and/or wires). Self reset is performed when faults are cleared. The measure of each probe is updated at 2 s time intervals. Note 1 The 26 menu is available when the MPT module is enabled t-int-F26.ai T (°C) t General operation time characteristic for thermal protection with RTD thermometric probes (26) Th>x tTh>x tThALx TRIP all-F26.ai General logic diagram of the thermal elements - (26) Pt100 Thybus MPT AL ARM TRIP Trip Element Alarm Element ThALx enable Th>x enable ThALx Th>x t ThALx t Th>x Th>xBF Trip Th>x & Th>xBF t-refresh-F26.ai t Pt1...8 update Pt1 Pt2 Pt3 Pt4 Pt5 Pt6 Pt7 Pt8 Pt1 0.25s 0.25s 0.25s 0.25s 0.25s 0.25s 0.25s 0.25s 2.0s

NA20 - Manual - 04 - 2022

All alarm and/or trip elements can be enabled or disabled by setting ON or OFF the ThALx�Enable� e Th>x�Enable�parameters inside the Set \ Profile A(or B) \ Thermal protection with RTD thermo- metric probes - 26 \ PTx Probe \ ThALx Alarm (ThALx Trip) where x = 1...8. Each trip threshold (Th>x) may be associated with the breaker failure (BF) function by setting ON the Th>xBF�parameters inside the Set \ Profile A(or B) \ Thermal protection with RTD thermometric probes - 26 \ PTx Probe \ ThALx Trip where x = 1...8.[1] Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. Fun-F26.ai Logic diagram for thermal protection with RTD thermometric probes (26) T° ≤ +245.0°C T° > Pt x> Ptx Pt1 Pt2 Pt3 Pt4 Pt5 Pt6 Pt7 Pt8 0 T TRIPPING MATRIX (LED+RELAYS) T° > ThALx Pt100-x Trip Pt100-xAlarm t Th>x t ThALx BF Enable (ON≡Enable) Pt100 OK Pt100 FAULT Th>xBF TOWARDS BF LOGIC Th>x BF_OUT TOWARDS DIAGNOSTIC Pt x> Diagnostic TRIP & & & T° ≥ -49.0°C 0 T ThALx-K ThALx-L Th>x-K Th>x-L ThALx Th>x t ThALx t Th>x

NA20 - Manual - 04 - 2022

Undercurrent - 37 Preface One operation threshold, adjustable (I

NA20 - Manual - 04 - 2022

Fun-F37_S1.ai Logic diagram concerning the threshold (I<) of the undercurrent element - 37 RESET t

NA20 - Manual - 04 - 2022

Negative sequence overcurrent - 46 Preface Two operation thresholds, independently adjustable (I2>, I2>>) with adjustable delay (t2>, t2>>). The first one may be programmed with definite or inverse time according the IEC and ANSI/IEEE standard, as well as with I2t or EM curve. The second threshold has a definite time characteristic. For each threshold a reset time can be set (t2>RES, t2>>RES) useful to reduce the clearing time for intermittent faults. The first threshold trip may be inhibited by start of the second threshold (I2>>). Operation and settings The negative sequence current is computed as: I2=(IL1+e-j120°·IL2+e+j120°·IL3)/3 where e-j120°=-1/2-j√3/2, ej120°=-1/2+j√3/2. The negative sequence current is compared with the setting values. Currents above the associated pickup value are detected and a start is issued. After expiry of the associated operate time (t2>, t2>>) a trip command is issued; if instead the current drops below the threshold, the element is restored. The first threshold (I2>) may be programmed with definite or inverse time according the following characteristic curves: • Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t2>inv / [(I2/I2>inv)0.02 - 1 • Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t2>inv / [(I2/I2>inv) - 1] • Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t2>inv / [(I2/I2>inv)2 - 1] • Moderately Inverse (ANSI/IEEE type MI): t = t2>inv · {0.01 / [(I2/I2>inv)0.02 - 1] + 0.023} • Very Inverse (ANSI/IEEE type VI): t = t2>inv · {3.922 / [(I2/I2>inv)2 - 1] + 0.098} • Extremely Inverse (ANSI/IEEE type EI): t = t2>inv · {5.64 / [(I2/I2>inv)2 - 1] + 0.024} • I-squared-t (I 2t = K): t = 16 · t2>inv / (I2/I2>inv)2 • Electromechanical (EM): t = t2>inv · {0.28 / [-0236 · (I2/I2>inv)-1 + 0.339]} Where: t: operate time I2>inv: threshold setting t2>inv: operate time setting The second threshold has a definite time characteristic. For all inverse time characteristics, following data applies: • Asymptotic reference value (minimum pickup value): 1.1 I2>inv • Minimum operate time: 0.1 s • Range where the equation is valid:[1] 1.1 ≤ I2/I2>inv ≤ 20 For all definite time elements the upper limit for measuring is 50 In. All overcurrent elements can be enabled or disabled by setting ON or OFF the I2>�Enable and/or I2>>�Enable�parameters inside the Set \ Profile A(or B) \ Negative sequence overcurrent - 46 \ I2> Element (I2>> Element) \ Setpoints menus. The first overcurrent element can be programmed with definite or inverse time characteristic by setting the I2>Curve parameter (DEFINITE,�IEC/BS�A,�IEC/BS�B,�IEC/BS�C,�ANSI/IEE�MI,� ANSI/IEE�VI,�ANSI/IEE�EI,�I2t,�EM) available inside the Set \ Profile A(or B) \ Negative sequence overcurrent - 46 \ I2> Element \ Setpoints menu. The trip of I2> element may be inhibited by the start of the second element (I2>>) by set- ting ON the Disable I2> by start I2>> (I2>disbyI2>>) parameter available inside the Set \ Profile A(or B) \ Negative sequence overcurrent-46 \ I2>> Element \ Setpoints menu. Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point t-int-F46.ai I2 I2>> t2> t2>> I2> t TRIP General operation time characteristic curve for the negative sequence overcurrent element - 46

NA20 - Manual - 04 - 2022

All the parameters can be set separately for Profile A and Profile B (Set \ Profile A(or B) \ Negative sequence overcurrent - 46 \ I2> Element (I2>> Element) \ Setpoints menus). An adjustable reset time delay is provided for every threshold (t2>RES, t2>>RES). Each element can produce the Breaker Failure output if the I2> BF and/or I2>> BF parameters are set to ON. The parameters are available inside the Set \ Profile A(or B) \ negative sequence overcurrent - 46 \ I2> Element (I2>> Element) \ Setpoints menus.[1] If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may be blocked for an adjustable time interval, starting from the circuit breaker closure. Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. Timers-F46.ai I2> Start I2> Trip t2> t2> RESET INPUT t2>RES t2>RES t2>RES t I2> element timers - 46 all-F46.ai IL1 IL2 IL3 IL1 IL2 IL3 BLK1I2>> I2>> Element BLK2OUT Start I2>> Start I2>> Trip I2>> & I2> disbyI>> & I2>>BLK1 & I2>>BLK2IN t2>> def I2CLP>> def I2>> def t2CLP>> t2>>RES I2>> Enable I2> inhibition Block1 BLK1I2> CLPI2> CLPI2>> I2> Element BLK2OUT BLK2INI2> BLK2INI>> Start I2> Trip I2> & I2>BLK1 Block2 & I2>BLK2IN I2>BLK2OUT I2>>BF I2>> Trip & I2>>BF I2>BF Trip I2> & I2>BF Start I2> & I2>>BLK2OUT Start I2>> & Block1 Block2 t2> def I2CLP> def I2> def t2> inv I2CLP> inv I2> inv I2>Curve t2CLP> t2>RES I2> Enable Start I2> & Start I2>> & Start I2>> & Start I2> & General logic diagram of the negative sequence overcurrent elements - 46 I2CLP>Mode Change setting Element blocking OFF I2CLP>>Mode Change setting Element blocking OFF

NA20 - Manual - 04 - 2022

This operating mode may be select by setting ON-Element�blocking�the I2CLP>�Mode�and/or I2CLP>>�Mode parameters. If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may be changed for an adjustable time interval, starting from the circuit breaker closure. This operating mode may be select by setting ON-Change�setting�the I2CLP>�Mode�and/or I2CLP>>�Mode parameters, whereas the operating thresholds within the CLP may be adjusted in- side the Set \ Profile A(or B) \ Negative sequence overcurrent - 46\ I2> Element,(I2>> Element) \ Defi- nite time (Inverse time) menus. For both operating modes the CLP Activation time parameters (t2CLP>, t2CLP>>) may be ad- justed inside the Set \ Profile A(or B) \ Negative sequence overcurrent - 46 \ I2> Element (I2>> Ele- ment) \ Setpoints menus. For both thresholds the following block criteria are available: Logical block (Block1) If the I2>BLK1 and/or I2>>BLK1 enabling parameters are set to ON and a binary input is de- signed for logical block (Block1), the concerning element is blocked off whenever the given input is active.[1] The enabling parameters are available inside the Set \ Profile A(or B) \ Negative sequence overcurrent - 46 \ I2> Element (I2>> Elemen) \ Setpoints menus, while the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input INx menus. Selective block (Block2) All along the protective elements the selective block may be set. The logic selectivity function may be performed by means any combination of the following I/O: • One committed pilot wire input (BLIN1). • One or more binary inputs designed for input selective block. • One committed pilot wire output (BLOUT1). • One or more output relays designed for output selective block. Only when the committed pilot wire are used the continuity check of the pilot wire link is active. Use of committed pilot wire input BLIN1: • The protection is blocked off according the selectivity block criteria when the input BLIN1 is active. The information about phase or phase+earth block may be select programming the ModeBLIN1 parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus. Use of binary inputs: • If the I2>BLK2IN and/or I2>>BLK2IN parameters are set to ON and a binary input is de- signed for selective block (Block2), the protection is blocked off by phase elements (Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block criteria.[2] The enable I2>BLK2IN and/or I2>>BLK2IN parameters are available inside the Set \ Profile A(or B) \ Neg- ative sequence overcurrent - 46 \ I2> Element (I2>> Element) \ Setpoints menus, while the Block2 Iph and�Block2�Iph/IE functions must be assigned to the selected binary inputs inside the Set \ Inputs \ Binary input INx menus (IN1... matching). Use of committed pilot wire output BLOUT1: • The information about phase or phase+earth block may be select programming the ModeBLOUT1 parameter (OFF�-�ON�IPh�-�ON�IPh/IE�-�ON�IE) inside Set \ Profile A(or B) \ Selective block- BLOCK2 \ Selective block OUT menus. Use of output relay (K1...K6): • If the I2>BLK2OUT�and/or�I2>>BLK2OUT enable parameters are set to ON and a output relay is designed for selective block (Block2), the protection issues a block output by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), whenever the given element (Start I>, Start I>> e/o Start I>>>) becomes active. The enable I2>BLK2OUT�and/or�I2>>BLK2OUT� parameters (ON or OFF) are available inside the Set \ Profile A(or B) \ Negative sequence overcur- rent - 46 \ I2> Element (I2>> Element) \ Setpoints menus, while the BLK2OUT-Iph-K,�BLK2OUT- Iph/IE-K�and/or BLK2OUT-IE-K�output relays and LEDs (BLK2OUT-Iph-L,�BLK2OUT-Iph/ IE-L�e/o BLK2OUT-IE-L) must be select inside the Set \ Profile A(or B) \ Selective block-BLOCK2\ Selective block OUT menu. Note 1 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR- ING section Note 2 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND MON- ITORING section

NA20 - Manual - 04 - 2022

46S1-diagram.ai I2 t2>RES T 0 RESET t2> 0 T ≥1 t2>def t2>inv t2>RES Start I2> Trip I2> ON≡Inhibit (from I2>> element) ON≡Enable I2> overcurrent element (Pickup within CLP) (Pickup outside CLP) I2> inhibition & I2CLP>Mode I2CLP>def I2CLP>inv I2 ≥ I2CLP>def (inv) BF Enable (ON≡Enable) I2>BF towards BF logic I2> BF & Trip I2> TRIPPING MATRIX (LED+RELAYS) I2> Curve 0 T I2> Enable I2> Negative sequence overcurrent element (46) block diagram Output t2CLP> t2CLP> Output t2CLP> I2>TR-K I2>TR-L I2>ST-L I2>ST-K I2>inv I2 ≥ I2>def I2 ≥ I2>inv I2>def Negative sequence overcurrent (46) - Logic diagram of the first threshold (I2>) T 0 t2CLP> t2CLP> Block1, Block2 A B C A = ON - Change setting B = OFF C = ON - Element blocking ≥1 ≥1 A B C A = ON - Change setting A B C C = ON - Element blocking A B C B = OFF CB State CB OPEN CB CLOSED CB OPEN t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK CB-State

NA20 - Manual - 04 - 2022

Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 46S1_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1I2> & & BLK2IN I2> & & Enable (ON≡Enable) I2>BLK1 Block2 input enable (ON≡Enable) Pilot wire input & I2>BLK2IN Block1 BLK2IN-Iph Start I2> Trip I2> Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM ANY PROTECTIONS FROM PHASE PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 I2> Block2 OUT I2>> Block2 OUT Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 Negative sequence overcurrent (46) - Logic diagram of the blocking signals concerning the first element (I2>) Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 & Block2 output (ON≡Enable) I2>BLK2OUT Start I2> ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L FROM EARTH FAULT PROTECTIONS I>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

46S2-diagram.ai I2 t2>>RES T 0 RESET t2>>def 0 T t2>>def t2>>RES Start I2>> Trip I2>> ON≡Enable I2>> overcurrent element (Pickup within CLP) (Pickup outside CLP) & I2CLP>>def I2 ≥ I2>> BF Enable (ON≡Enable) I2>>BF towards BF logic I2>> BF & Trip I2>> TRIPPING MATRIX (LED+RELAYS) I2>> Enable I2>>TR-K I2>>TR-L I2>>ST-L I2>>ST-K I2 ≥ I2>>def I2>>def Negative sequence overcurrent (46) - Logic diagram of the second threshold (I2>>) Output t2CLP>> t2CLP>> I2CLP>>Mode I2>> Negative sequence overcurrent element (46) block diagram Output t2CLP>> T 0 t2CLP>> t2CLP>> Block1, Block2 A B C A = ON - Change setting B = OFF C = ON - Element blocking ≥1 ≥1 A B C A = ON - Change setting A B C C = ON - Element blocking A B C B = OFF CB State CB OPEN CB CLOSED CB OPEN t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK CB-State

NA20 - Manual - 04 - 2022

Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 46S2_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1I2>> & & BLK2IN I2>> & & Enable (ON≡Enable) I2>>BLK1 Block2 input enable (ON≡Enable) Pilot wire input & I2>>BLK2IN Block1 BLK2IN-Iph Start I2>> Trip I2>> Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM ANY PROTECTIONS FROM PHASE PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 I2> Block2 OUT I2>> Block2 OUT Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 Negative sequence overcurrent (46) - Logic diagram of the blocking signals concerning the second element (I2>>) Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 & Block2 output (ON≡Enable) I2>>BLK2OUT ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L FROM EARTH FAULT PROTECTIONS I>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT Start I2>>

NA20 - Manual - 04 - 2022

Negative sequence current / positive sequence current ratio - I2/I1 Preface One adjustable operation threshold (I2/I1)> with definite time adjustable delay (t21>). Operation and settings The negative and positive sequence currents are computed as: I1=(IL1+e+j120°·IL2+e-j120°·IL3)/3 I2=(IL1+e-j120°·IL2+e+j120°·IL3)/3 where e-j120°=-1/2-j√3/2, ej120°=-1/2+j√3/2. The negative sequence-positive sequence currents ratio is compared with the setting value. Ratio above the associated pickup value is detected and a start is issued. After expiry of the associated operate time (t21>) a trip command is issued; if instead the it drops below the threshold, the element is restored. The element can be enabled or disabled by setting ON or OFF the State parameter inside the Set \ Profile A(or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ Def- inite time menu. The element can produce the Breaker Failure output if the (I2/I1)> BF parameter is set to ON. The parameter is available inside the Set \ Profile A(or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ Setpoints menus.[1] A block from the second harmonic restraint may be set by setting ON the parameter inside the Set \ Profile A(or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ Set- points menu. If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may be blocked for an adjustable time interval, starting from the circuit breaker closure. This operating mode may be select by setting ON-Element�blocking�the I2/I1)CLP>�Mode�pa- rameter. If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may be changed for an adjustable time interval, starting from the circuit breaker closure. This operating mode may be select by setting ON-Change�setting�the I2/I1)CLP>�Mode�param- eter, whereas the operating thresholds within the CLP may be adjusted inside the Set \ Profile A(or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ Definite time menu. For both operating modes the CLP Activation time parameter (t21CLP>) may be adjusted in- side the Set \ Profile A(or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ Setpoints menu. Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. t-int-I2-I1.ai I2/I1 t21> (I2/I1)> t TRIP General operation time characteristic for Negative sequence-positive sequence ratio element - I2/I1 General logic diagram of the negative sequence-positive sequence ratio element - I2/I1 all-FI2-I1.ai (I2/I1) (I2/I1)> Element Start (I2/I1)> Start (I2/I1)> Trip (I2/I1)> t21>def (I2/I1)>def Enable (I2/I1)> Block1 BLK1(I2/I1)> & I< & (I2/I1)>2ndh-REST

NA20 - Manual - 04 - 2022

The element may be blocked when the CT supervision function become active to avoid unwanted trips following any faults on CTs an amperometric input circuits;[1]the 74CT�Enable�parameter may be set to ON inside the Set \ CT supervision TA-74CT menù The following block criteria is available: Logical block (Block1) If the I2/I1)>BLK1 enabling parameter are set to ON and a binary input is designed for logical block (Block1), the protection is blocked off whenever the given input is active. The trip timer is held in reset condition, so the operate time counting starts when the input block goes down.[2] The enabling parameter is available inside the Set \ Profile A(or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ Setpoints menu, while the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input INx) menus (INx matching). The parameter may be adjusted independently for both profiles A or B. Note 1 The setting may be found in the “CT supervision ” paragraph inside CONTROL AND MONITORING section Note 2 The description of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITORING section I2-I1S1.ai (I2/I1) RESET t2 > 0 T ≥1 t21>def Start (I2/I1)> Trip (I2/I1)> CB-State Start I2ndh> ON≡Enable (I2/I1)> overcurrent element (Pickup within CLP) (Pickup outside CLP) Block1, Block2 & T 0 t21CLP> & 2nd harmonic restraint enable (ON≡Enable) (I2/I1)>2ndh-REST (I2/I1)>CLP>Mode t 21CLP> BF Enable (ON≡Enable) (I2/I1)>BF towards BF logic (I2/I1)> BF & Trip (I2/I1)> TRIPPING MATRIX (LED+RELAYS) A B C A =“1” A =“0 or OFF” Output t21CLP> (I2/I1)> Enable (I2/I1)> overcurrent element block diagram t21CLP> CB State CB OPEN CB CLOSED CB OPEN Output t21CLP> t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking (I2/I1)>TR-K (I2/I1)>TR-L (I2/I1)>ST-K (I2/I1)>ST-L ≥1 CLP (I2/I1)> (I2/I1) ≥ (I2/I1)>def (I2/I1)>def (I2/I1) ≥ (I2/I1)CLP>def (I2/I1)>def Negative sequence-positive sequence ratio element (I2/I1) - Logic diagram

NA20 - Manual - 04 - 2022

Thermal image - 49 Preface It is a overload protection with memory capability and three setpoints, used to protect lines and transformers against thermal overload. The phase currents are used into an algorithm reproducing a thermal replica according the IEC 60255-8 standard taking into account the Joule losses and the cooling effect due to the load reduc- tion; in this way the previous history and the overload are taken into account. The thermal protection can be adapted to the different features of motors by setting the thermal heating t+ and cooling t- constants ( the t+ constant refers to motor running condition, while the t- constant, always higher than t+, refers to stop condition). The trip element has an adjustable threshold; with 1.2 DqB setting (ie 1.2 times the overtemperature corresponding to the nominal operation condition) the corresponding tripping current IB is 1.1 since the temperature rise is proportional to the square of the current. The 49 element is provided with two further thresholds DqAL1 and DqAL2, lower than the previous one. These thresholds, both adjustable, provide an alarm signal to draw attention in the event of anoma- lous heating, without disconnect the protected device. One of the above thresholds can be used to prevent refeeding of the system when heating approaches the trip conditions since the additional heating brought on by the inrush currents would cause the protection to operate. Operation and settings The thermal current used for thermal image calculation is: Ith = max (IL1, IL2, IL3) If the second harmonic restraint is enabled, the thermal current used for thermal image calculation becomes: Ith = ILMAX/KINR = max (IL1, IL2, IL3) / KINR where KINR is an adjustable parameter (1.0...3.0), useful to reduce the thermal current during the transformer energization (inrush). According to a single-body thermal model, the thermal image is based on the differential equation: dDq/dt+Dq/T=(Ith/IB)2/T where Dq is the system thermal state as a percentage of base thermal capacity DqB corresponding to the base current IB[1] and T is the thermal time constant (the same for heating and cooling). When the thermal image Dq overcomes the threshold a trip is issued. The operating characteristic (IEC 60255-8) is: t=T*ln{[(Ith/IB)2-Dqp/DqB)]/[(Ith/IB)2-1.2]}=T*ln{[(Ith/IB)2-(Ip/IB)2]/[(Ith/IB)2-1.2]= T*ln{[(Ith/IB)2-p2]/[(Ith/IB)2-1.2]} [1] where: • t: operating time, • ln: natural logarithm, • Dqp and Ip are the thermal image and the corresponding equivalent thermal current before the overload occurs. • p=Ip/IB=√(Dqp/DqB: prior load. Following data applies: • Range where the equation is valid: 1.1IB ≤ Ith ≤ 10IB • If 10IB ≤ Ith ≤ 20IB, the operating time is fixed to a value corresponding to the 10IB • The upper limit is 20 IB. Note 1 Assuming that the secondary rated current of the line CT’s equals the rated current of the NA20 relay, as usually happens, the IB value is the ratio between the rated current of the protected component (line, transformer,...) and the primary rated current of the CT’s. t-int-F49.ai Ith/IB p=0 p=1 Dth> t TRIP General operation time characteristic for the thermal image elements - 49

NA20 - Manual - 04 - 2022

If the CLP function (Cold Load Pick-up) is enabled for blocking 49, the thermal image is blocked for an adjustable time interval, starting from the circuit breaker closure.[1] The operating mode parameter may be select by setting ON-Element�blocking�the DThCLP�Mode parameter inside the Set \ Profile A(or B) \ Thermal image-49 \ Common configuration menu. If the CLP function (Cold Load Pick-up) is enabled for threshold change, the equivalent thermal cur- rent may be decreased by means a KINR factor for an adjustable time interval, starting from the circuit breaker closure.[2] The operating mode parameter may be select by setting ON-Change� setting� the DThCLP� Mode parameter inside the Set \ Profile A(or B) \ Thermal image-49 \ Common configuration menu. For the Dth> threshold, a block from the second harmonic restraint may be set by setting ON the DTh>2ndh-REST parameter inside the Set \ Profile A(or B) \ Thermal image-49 \ Common configuration menu. All elements can be enabled or disabled by setting ON or OFF the DThetaAL1�Enable, DTheta- AL2�Enable�and/or DTheta>�Enable�parameters inside the Set \ Profile A(or B) \ Thermal image- 49 \ DthAL1 Element (DthAL2 Element, Dth> Element) menus. The trip element (Dth>) may be inhibited when a start of at least one of the overcurrent element (50/51) is active, if the Dth>disby50-51 parameter is set ON inside the Set \ Profile A(or B) \Ther- mal image-49 \ Dth> Element menu. The DqIN parameter sets a minimum level of previous thermal image Dqp when the protection relay is powered or when a remote (binary input) or local (keyboard or ThyVisor) command is issued. The DthIN parameter may be adjusted inside the Set \ Profile A(or B) \ Thermal image-49\ Common configuration menu. To active the DqIN preset value remotely, a binary input must be programmed as Init�DTheta func- tion inside the Set \ Inputs \ Binary input IN1, Binary input INx menu. The trip element can produce the Breaker Failure output if the Dth> BF parameters is set to ON. The parameter is available inside the Set \ Profile A(or B) \ Thermal image-49 \ Dth> Element menu.[3] The IB setting is adjustable inside the Set \ Profile A(or B) \ Base current IB menu. Note 1 The CLP function (Cold Load Pick-up) with blocking of the 49 element has priority compared with the second harmonic restraint function, so, if the equivalent thermal current is enabled, the latter is not reduced when a second harmonic restraint is active. Note 2 The CLP function (Cold Load Pick-up) with threshold change of the 49 element has priority compared with the second harmonic restraint func- tion, so, if the equivalent thermal current is enabled, the latter is not reduced when a second harmonic restraint is active. Note 3 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. all-F49.ai KINR T DthIN DthCLP Mode Dth2ndh REST tDthCLP Common configuration Ith Dth> Element Trip DTh> DTh> Enable DTh> Trip DTh> Dth>BF & Dth>BF BLK2OUT Dth>BLK2OUT & Trip Dth> Trip Dth> BLK2INDth> Block2 & Dth>BLK2IN & DthAL1 Element DThAL1 DThAL1 DThAL1 DThAL1 Enable Ith BLK2OUT DthAL1BLK2OUT & Block1 BLK1DthAL1 & DthAL1BLK1 & Dth>AL1 DthAL1 BLK2INDthAL1 Block2 & DthAL1BLK2IN & DthAL2 BLK2INDthAL2 Block2 & DthAL2BLK2IN & DthAL2 Element DThAL2 DThAL2 DThAL2 Enable Ith BLK2OUT DthAL2BLK2OUT & Block1 BLK1DthAL2 & DthAL2BLK1 & Dth>AL2 Dth>AL2 Block1 BLK1Dth> & Dth>BLK1 Trip Dth> & & 50-51 inhibition Dth>disby50-51 General logic diagram of the thermal image elements - 49

NA20 - Manual - 04 - 2022

For every threshold the following block criteria are available: Logical block (Block1) If the DthAL1BLK1,�DthAL2BLK1�and/or Dth>BLK1 enabling parameters are set to ON and a bi- nary input is designed for logical block (Block1), the concerning element is blocked off whenever the given input is active.[1] The enabling parameters are available inside the Set \ Profile A(or B)\Ther- mal image-49 \ DthAL1 Element (DthAL2 Element, Dth> Element) menus, while the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input IN1(x) menus. Selective block (Block2) All along the protective elements the selective block may be set. The logic selectivity function may be performed by means any combination of the following I/O: • One committed pilot wire input (BLIN1). • One or more binary inputs designed for input selective block. • One committed pilot wire output (BLOUT1). • One or more output relays designed for output selective block. Only when the committed pilot wire are used the continuity check of the pilot wire link is active. Use of committed pilot wire input BLIN1: • The protection is blocked off according the selectivity block criteria when the input BLIN1 is active. The information about phase or phase+earth block may be select programming the ModeBLIN1 parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus. Use of binary inputs: • If the DthAL1BLK2IN,�DthAL2BLK2IN�and/or Dth>BLK2IN parameter are are set to ON and a binary input is designed for selective block (Block2), the protection is blocked off by phase ele- ments (Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block criteria.[2] The enable DthAL1BLK2IN,�DthAL2BLK2IN�and/or Dth>BLK2IN parameters are available inside the Set \ Profile A(or B) \ Thermal image-49 \ DthAL1 Element, DthAL2 Element, Dth> Element menus, while the Block2 Iph and�Block2�Iph/IE functions must be assigned to the selected binary inputs inside the Set \ Inputs \ Binary input IN1(2) menus (IN1 or IN2 matching). Use of committed pilot wire output BLOUT1: • The information about phase or phase+earth block may be select programming the ModeBLOUT1 parameter inside Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block OUT menus. Use of output relay (K1...K6): • If the DthAL1BLK2OUT,�DthAL2BLK2OUT�and/o�Dth>BLK2OUT enable parameters are set to ON and a output relay is designed for selective block (Block2), the protection issues a block output by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), when- ever the given element (DthAL1, DthAL2 e/o Dth>) becomes active. The enable DthAL1BLK2OUT,� DthAL2BLK2OUT�and/or�Dth>BLK2OUT�parameters are available inside the Set \ Profile A(or B) \ Thermal image-49 \ DthAL1 Element (DthAL2 Element, Dth> Element) menus, while the BLK- 2OUT-Iph-K,�BLK2OUT-Iph/IE-K�and/or BLK2OUT-IE-K�output relays must be set inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block OUT menus. Note 1 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR- ING section Note 2 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND MONITORING section

NA20 - Manual - 04 - 2022

Thermal image (49) - Logic diagram of the first alarm threshold Fun_49_AL1.ai Common configuration & dDθ/dt + Dθ/T = (Ith/IB)2/T Init DTheta Dθ ≥ DthAL1 DthAL1 Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Ith ≥1 KINR DthAL1 CB-State Start I2ndh> ON≡Enable element (Pickup within CLP) (Pickup outside CLP) Pickup - CLP setting change Block1, Block2 T 0 tDthCLP & 2nd harmonic restraint enable (ON≡Enable) Dth2ndh-REST DthCLPMode t DthCLP Ith ∙ KINR TRIPPING MATRIX (LED+RELAYS) A B C A =“1” A =“0 or OFF” Output tDthCLP DthAL1 Enable DThhAL1 thermal image (49) block diagram tDthCLP CB State CB OPEN CB CLOSED CB OPEN Output tDthCLP t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking DthAL1-L DthAL1-K ≥1 CLP Dth T DthIN

NA20 - Manual - 04 - 2022

Thermal image (49) - Logic diagram of the blocking signals concerning the first alarm element Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 49AL1_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1DthAL1 & BLK2IN DthAL1 & & Enable (ON≡Enable) DthAL1BLK1 Block2 input enable (ON≡Enable) Pilot wire input & DThAL1BLK2IN Block1 BLK2IN-Iph DthAL1 Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 & Block2 output (ON≡Enable) DthAL1BLK2OUT DthAL1 Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Thermal image (49) - Logic diagram of the second alarm threshold Fun_49_AL2.ai Common configuration & dDθ/dt + Dθ/T = (Ith/IB)2/T Init DTheta Dθ ≥ DthAL2 DthAL2 Binary input INx (x=1,2) T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Ith ≥1 KINR DthAL2 CB-State Start I2ndh> ON≡Enable element (Pickup within CLP) (Pickup outside CLP) Pickup - CLP setting change Block1, Block2 T 0 tDthCLP & 2nd harmonic restraint enable (ON≡Enable) Dth2ndh-REST DthCLPMode t DthCLP Ith ∙ KINR TRIPPING MATRIX (LED+RELAYS) A B C A =“1” A =“0 or OFF” Output tDthCLP DthAL2 Enable DThhAL2 thermal image (49) block diagram tDthCLP CB State CB OPEN CB CLOSED CB OPEN Output tDthCLP t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking DthAL2-L DthAL2-K ≥1 CLP Dth T DthIN

NA20 - Manual - 04 - 2022

Thermal image (49) - Logic diagram of the blocking signals concerning the second alarm element Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 49AL2_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1DthAL2 & BLK2IN DthAL2 & & Enable (ON≡Enable) DthAL2BLK1 Block2 input enable (ON≡Enable) Pilot wire input & DThAL2BLK2IN Block1 BLK2IN-Iph DthAL2 Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 & Block2 output (ON≡Enable) DthAL2BLK2OUT DthAL2 Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Thermal image (49) - Logic diagram of the trip threshold Fun_49_Dth.ai Common configuration & dDθ/dt + Dθ/T = (Ith/IB)2/T Init DTheta Dθ ≥ DthAL1 Dth> Binary input INx (x=1,2) T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Ith ≥1 KINR Dth> CB-State Start I2ndh> ON≡Enable element (Pickup within CLP) (Pickup outside CLP) Pickup - CLP setting change Block1, Block2 T 0 tDthCLP & 2nd harmonic restraint enable (ON≡Enable) Dth2ndh-REST DthCLPMode t DthCLP Ith ∙ KINR BF Enable (ON≡Enable) Dth>BF towards BF logic Dth> BF & Trip Dth> TRIPPING MATRIX (LED+RELAYS) A B C A =“1” A =“0 or OFF” Output tDthCLP Dth> Enable DTh> thermal image (49) block diagram tDthCLP CB State CB OPEN CB CLOSED CB OPEN Output tDthCLP t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking Dth>-L Dth>-K ≥1 CLP Dth from 50/51 element (ON≡Inhibit) 50/51 inhibition & 50/51block enable (ON≡Enable) Dth>disby50-51 T DthIN

NA20 - Manual - 04 - 2022

Thermal image (49) - Logic diagram of the blocking signals concerning the trip element Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 49_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1Dth> & BLK2IN Dth> & & Enable (ON≡Enable) Dth>BLK1 Block2 input enable (ON≡Enable) Pilot wire input & DTh>BLK2IN Block1 BLK2IN-Iph Dth> Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 & Block2 output (ON≡Enable) Dth>BLK2OUT Dth> Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

F_49-1min-Char.ai Operating characteristic concerning the thermal image element (49) - T=1 min 1 1.1 2 3 4 5 6 7 8 9 10 20 Ith /IB 0.01 0.1 1 10 100 1000 10000 1.0 p = 0.0 0.8 0.6 t [s]

NA20 - Manual - 04 - 2022

F_49-200min-Char.ai Operating characteristic concerning the thermal image element (49) - T = 200 min 1 1.1 2 3 4 5 6 7 8 9 10 20 Ith /IB t [s] 0.1 1 10 100 1000 10000 100000 1.0 p = 0.0 0.8 0.6

NA20 - Manual - 04 - 2022

Phase overcurrent - 50/51 Preface Three operation thresholds, independently adjustable (I>, I>>, I>>>) with adjustable delay (t>, t>>, t>>>). The first one may be programmed with definite or inverse time according the IEC and ANSI/IEEE standard, as well as with rectifier, I2t or EM curve. The second threshold may be programmable with independent or dependent time according to the I2t curve and the third threshold with independent time. For each threshold a reset time can be set (t>RES, t>>RES, t>>>RES) useful to reduce the clearing time for intermittent faults. The first threshold trip may be inhibited by start of the second and/or third threshold (I>>, I>>>). Similarly the second threshold trip may be inhibited by start of the third threshold (I>>>). Operation and settings Each phase fundamental frequency current is compared with the setting value. Currents above the associated pickup value are detected and a start is issued. After expiry of the associated operate time a trip command is issued; if instead the current drops below the threshold, the element is re- stored. The first threshold (I>) may be programmed with definite or inverse time according the following characteristic curves: • Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t>inv / [(I/I>inv)0.02 - 1] • Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t>inv / [(I/I>inv) - 1] • Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t>inv / [(I/I>inv)2 - 1] • Long Time Inverse (IEC 255-3/BS type B LTI): t = 120 · t>inv / [(I/I>inv) - 1] • Moderately Inverse (ANSI/IEEE type MI): t = t>inv · {0.01 / [(I/I>inv)0.02 - 1] + 0.023} • Very Inverse (ANSI/IEEE type VI): t = t>inv · {3.922 / [(I/I>inv)2 - 1] + 0.098} • Extremely Inverse (ANSI/IEEE type EI): t = t>inv · {5.64 / [(I/I>inv)2 - 1] + 0.024} • Rectifier (RI): t = 2351 · t>inv / [(I/I>inv)5.6 - 1] • I-squared-t (I 2t = K): t = 16 · t>inv / (I/I>inv)2 • Electromechanical (EM): t = t>inv · {0.28 / [-0236 · (I/I>inv)-1 + 0.339]} Where: t: operate time I>inv: threshold setting t>inv: operate time setting The second threshold (I>>) may be programmable with definite or inverse time according to the I2t curve: t = 16 · t>inv / (I/I>inv)2 The third threshold (I>>>) with definite time. For all inverse time characteristics, following data applies: • Asymptotic reference value (minimum pickup value): 1.1 I>inv • Minimum operate time: 0.1 s • Range where the equation is valid:[1] 1.1 ≤ I/I>inv ≤ 20 • If I>inv pickup ≥ 2.5 In, the upper limit is 50 In For all definite time elements the upper limit for measuring is 50 In. All overcurrent elements can be enabled or disabled by setting ON or OFF the I>�Enable, I>> Enable�and/or I>>>�Enable�parameters inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus. The first overcurrent element can be programmed with definite or inverse time characteristic by set- ting the I>Curve parameter (DEFINITE,�IEC/BS�A,�IEC/BS�B,�IEC/BS�C,�IEC/BS�B�LI,�ANSI/ IEE�MI,�ANSI/IEE�VI,�ANSI/IEE�EI,�RECTIFIER,�I2t,�EM) available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element \ Setpoints menu. Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point t-int-F50-51.ai I I>> I>>> t> t>> t>>> I> t TRIP General operation time characteristic for the phase overcurrent elements - 50/51

NA20 - Manual - 04 - 2022

The second overcurrent element can be programmed with definite or inverse time characteristic by setting the I> Time characteristic (I>>Curve) parameter (DEFINITE,�I2t) available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I>> Element \ Setpoints menu. The trip of I> element may be inhibited by the start of the second and/or third element (I>>, I>>>) by set- ting ON the Disable I> by start I>>, Disable I>> by start I>>> (I>disbyI>>,�I>disbyI>>>) parameters available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I>> Element (I>>> Element) \ Setpoints menus. Similarly the trip of the I>> element may be inhibited by start of the third element (I>>>) by setting ON the Disable I>> by start I>>> (I>>disbyI>>>) parameter available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I>>> Element \ Setpoints menu. All the named parameters can be set separately for Profile A and Profile B (Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus). An adjustable reset time delay is provided for every threshold (t>RES, t>>RES, t>>>RES). Each overcurrent element can produce the Breaker Failure output if the I> BF, I>> BF and/or I>>> BF parameters are set to ON. The parameters are available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus.[1] For all overcurrent elements, a block from the second harmonic restraint may be set by setting ON the I>2ndh-REST,�I>>2ndh-REST,�I>>>2ndh-REST parameters inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus. If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may be blocked for an adjustable time interval, starting from the circuit breaker closure. This operating mode may be select by setting ON-Element�blocking�the ICLP>�Mode,�ICLP>>� Mode�and/or �ICLP>>>�Mode parameters. If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may be changed for an adjustable time interval, starting from the circuit breaker closure. This operating mode may be select by setting ON-Change�setting�the ICLP>�Mode,�ICLP>>� Mode�and/or �ICLP>>>�Mode parameters, whereas the operating thresholds within the CLP may be adjusted inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element,(I>> Element, I>>> Element) \ Definite time (Inverse time) menus. For both operating modes the CLP Activation time parameters (tCLP>, tCLP>>, tCLP>>>) may be adjusted inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus. Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. Timers-F50-51.ai I> Start I> Trip t> t> RESET INPUT t>RES t>RES t>RES t I> element phase overcurrent timers - 50/51

NA20 - Manual - 04 - 2022

General logic diagram of the phase overcurrent elements - 50/51 all-F50-51.ai IL1 IL2 IL3 IL1 IL2 IL3 IL1 IL2 IL3 ≥ I>> inhibition BLK1I>>> I>>>BF I>>> Element Start I>>> Start I>>> Start I>>> Trip I>>> Trip I>>> & I>> disbyI>>> & I>>>BLK2IN & I> disbyI>>> t>>> def ICLP>>> def I>>> def ICLP>>>Mode tCLP>>> t>>>RES BLK1I>> I>> Element BLK2OUT Start I>> Start I>> Trip I>> & I> disbyI>> & I>>BLK1 & I>>BLK2IN t>> def ICLP>> def I>> def t>> inv ICLP>> inv I>> inv I>>Curve ICLP>>Mode tCLP>> t>>RES I>> Enable I>>> Enable I> inhibition Block1 BLK1I> CLPI> CLPI>> CLPI>>> I> Element BLK2OUT BLK2INI> BLK2INI>> Start I> Trip I> & I>BLK1 Block2 & I>BLK2IN Start I2ndh> & I>2ndh-REST I>BLK2OUT Start I2ndh> & I>>2ndh-REST Start I2ndh> & I>>>2ndh-REST & I>>>BF I>>BF I>> Trip & I>>BF I>BF Trip I> & I>BF Start I> & I>>BLK2OUT Start I>> & BLK2OUT I>>>BLK2OUT Start I>>> & Block1 Block2 & I>>>BLK1 Block1 Block2 t> def ICLP> def I> def t> inv ICLP> inv I> inv I>Curve ICLP>Mode tCLP> t>RES I> Enable Start I> & Start I>> & Start I>>> & Start I>> & BLK2INI>>> Start I>>> & Start I> &

NA20 - Manual - 04 - 2022

For every of the three thresholds the following block criteria are available: Logical block (Block1) If the I>BLK1, I>>BLK1 and/or I>>>BLK1 enabling parameters are set to ON and a binary in- put is designed for logical block (Block1), the concerning element is blocked off whenever the given input is active.[1] The enabling parameters are available inside the Set \ Profile A(or B) \ Phase over- current-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus, while the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input IN1(x) menus. Selective block (Block2) All along the protective elements the selective block may be set. The logic selectivity function may be performed by means any combination of the following I/O: • One committed pilot wire input (BLIN1). • One or more binary inputs designed for input selective block. • One committed pilot wire output (BLOUT1). • One or more output relays designed for output selective block. Only when the committed pilot wire are used the continuity check of the pilot wire link is active. Use of committed pilot wire input BLIN1: • The protection is blocked off according the selectivity block criteria when the input BLIN1 is active. The information about phase or phase+earth block may be select programming the ModeBLIN1 parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus. Use of binary inputs: • If the I>BLK2IN, I>>BLK2IN and/or I>>>BLK2IN parameters are set to ON and a binary input is designed for selective block (Block2), the protection is blocked off by phase elements (Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block criteria.[2] The enable I>BLK2IN, I>>BLK2IN and/or I>>>BLK2IN parameters are available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus, while the Block2 Iph and�Block2�Iph/IE functions must be assigned to the selected binary inputs inside the Set \ Inputs \ Binary input IN1(x) menus (IN1 or INx matching). Use of committed pilot wire output BLOUT1: • The information about phase or phase+earth block may be select programming the ModeBLOUT1 parameter (OFF�-�ON�IPh�-�ON�IPh/IE�-�ON�IE) inside Set \ Profile A(or B) \ Selective block- BLOCK2 \ Selective block OUT menus. Use of output relay (K1...K6): • If the I>BLK2OUT,�I>>BLK2OUT�and/or�I>>>BLK2OUT enable parameters are set to ON and a output relay is designed for selective block (Block2), the protection issues a block output by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), whenever the given element (Start I>, Start I>> e/o Start I>>>) becomes active. The enable I>BLK2OUT,� I>>BLK2OUT�and/or�I>>>BLK2OUT�parameters (ON or OFF) are available inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus, while the BLK2OUT-Iph-K,�BLK2OUT-Iph/IE-K�and/or BLK2OUT-IE-K�output relays and LEDs (BLK2OUT-Iph-L,�BLK2OUT-Iph/IE-L�e/o BLK2OUT-IE-L) must be select inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block OUT menu. Note 1 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR- ING section Note 2 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND MONITORING section

NA20 - Manual - 04 - 2022

Phase overcurrent (50/51) - First element logic diagram (I>) Fun_50-51S1.ai IL1 IL2 t >RES T 0 RESET t > 0 T ≥1 ≥1 ≥1 t >def t >inv t >RES Start I> Trip I> CB-State Start I2ndh> ON≡Inhibit (from I>> and/or I>>> overcurrent element) ON≡Enable I> overcurrent element (Pickup within CLP) (Pickup outside CLP) I> inhibition Block1, Block2 & T 0 tCLP> & 2nd harmonic restraint enable (ON≡Enable) I>2ndh-REST ICLP>Mode ICLP>def t CLP> ICLP>inv IL1 ≥ I> BF Enable (ON≡Enable) I>BF towards BF logic I> BF & Trip I> TRIPPING MATRIX (LED+RELAYS) I> Curve 0 T A B C A =“1” A =“0 or OFF” Output tCLP> IL3 I> Enable I> overcurrent element (50/51) block diagram tCLP> CB State CB OPEN CB CLOSED CB OPEN Output tCLP> t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking I>TR-K I>TR-L I>ST-L I>ST-K ≥1 CLP I> & State I>inv IL1 ≥ I>def IL1 ≥ I>inv I>def & State

NA20 - Manual - 04 - 2022

Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the first element (I>) Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 50-51S1_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1I> & & BLK2IN I> & & Enable (ON≡Enable) I>BLK1 Block2 input enable (ON≡Enable) Pilot wire input & I>BLK2IN Block1 BLK2IN-Iph Start I> Trip I> Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 & Block2 output (ON≡Enable) I>BLK2OUT Start I> Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Phase overcurrent (50/51) - Second element logic diagram (I>>) Fun_50-51S2.ai t >>RES T 0 RESET t >> 0 T ≥1 t >>def t >>inv t >>RES Start I>> Trip I>> CB-State Start I2ndh> ON≡Inhibit (from I>>> overcurrent element) ON≡Enable I>> overcurrent element I>> inhibition Block1, Block2 I>>TR-K I>>TR-L I>>ST-L I>>ST-K T 0 tCLP>> & & 2nd harmonic restraint enable (ON≡Enable) I>>2ndh-REST ICLP>>Mode t CLP>> BF Enable (ON≡Enable) I>>BF towards BF logic I>> BF & Trip I>> TRIPPING MATRIX (LED+RELAYS) I>> Curve 0 T A B C Output tCLP>> I>> Enable I>> overcurrent element (50/51) Block diagram tCLP>> CB State CB OPEN CB CLOSED CB OPEN Output tCLP>> t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking & (ON≡Inhibit) Start I>> I> inhibition I> disbyl>> ≥1 CLP I>> IL1 IL2 ≥1 ≥1 (Pickup within CLP) (Pickup outside CLP) ICLP>>def ICLP>>inv IL1 ≥ I>> A =“1” A =“0 or OFF” IL3 & State I>>inv IL1 ≥ I>>def IL1 ≥ I>>inv I>>def & State

NA20 - Manual - 04 - 2022

Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the second element (I>>) Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 50-51S2_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1I>> & & BLK2IN I>> & & Enable (ON≡Enable) I>>BLK1 Block2 input enable (ON≡Enable) Pilot wire input & I>>BLK2IN Block1 BLK2IN-Iph Start I>> Trip I>> Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 & Block2 output (ON≡Enable) I>>BLK2OUT Start I>> Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Phase overcurrent (50/51) - Third element logic diagram (I>>>) Fun_50-51S3.ai t >>>RES T 0 RESET t >>>def 0 T ≥1 t >>>def t >>>RES Start I>>> Trip I>>> CB-State Start I2ndh> ON≡Enable 3rd overcurrent element Block1, Block2 & I>>>TR-K I>>>TR-L I>>>ST-L I>>>ST-K T 0 tCLP>>> & 2nd harmonic restraint enable (ON≡Enable) I>>>2ndh-REST ICLP>>>Mode t CLP>>> BF Enable (ON≡Enable) I>>>BF towards BF logic I>>> BF & Trip I>>> TRIPPING MATRIX (LED+RELAYS) A B C Output tCLP>>> I>>> Enable I>>> overcurrent element (50/51) Block diagram tCLP>>> Output tCLP>>> CB State CB OPEN CB CLOSED CB OPEN t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking & (ON≡Inhibit) Start I>>> Start I>>> Start I>>> (ON≡Inhibit) I> inhibition I> disbyl>>> & I>> inhibition I>> disbyl>>> ≥1 CLP I>>> IL1 IL2 ≥1 (Pickup within CLP) (Pickup outside CLP) ICLP>>def ICLP>>inv IL1 ≥ I>>> A =“1” A =“0 or OFF” IL3 & State IL1 ≥ I>>>def I>>>def

NA20 - Manual - 04 - 2022

Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the third element (I>>>) Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 50-51S3_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1I>>> & & BLK2IN I>>> & & Enable (ON≡Enable) I>>>BLK1 Block2 input enable (ON≡Enable) Pilot wire input & I>>>BLK2IN Block1 BLK2IN-Iph Start I>>> Trip I>>> Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 & Block2 output (ON≡Enable) I>>>BLK2OUT Start I>>> Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Residual overcurrent - 50N/51N Preface Three operation thresholds, independently adjustable (IE>, IE>>, IE>>>) with adjustable delay (tE>, tE>>, tE>>>). The first one (IE>) may be programmed with definite or inverse time according the IEC and ANSI/IEEE standard, as well as with EM curve. The second and third thresholds (IE>>, IE>>>) with independent time. For each threshold a reset time can be set (tE>RES, tE>>RES, tE>>>RES) useful to reduce the clearing time for intermittent faults. The first threshold trip may be inhibited by start of the second and/or third threshold (IE>>, IE>>>). Similarly the second threshold trip may be inhibited by start of the third threshold (IE>>>). Operation and settings The residual fundamental frequency current is compared with the setting value. Current above the associated pickup value is detected and a start is issued. After expiry of the associated operate time a trip command is issued; if instead the current drops below the threshold, the element is restored. The first threshold (IE>) may be programmed with definite or inverse time according the following characteristic curves: • Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · tE>inv / [(IE/IE>inv)0.02 - 1] • Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · tE>inv / [(IE/IE>inv) - 1] • Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · tE>inv / [(IE/IE>inv)2 - 1] • Long Time Inverse (IEC 255-3/BS type B LTI): t = 120 · tE>inv / [(tE/tE>inv) - 1] • Moderately Inverse (ANSI/IEEE type MI): t = tE>inv · {0.01 / [(IE/IE>inv)0.02 - 1] + 0.023} • Very Inverse (ANSI/IEEE type VI): t = tE>inv · {3.922 / [(IE/IE>inv)2 - 1] + 0.098} • Extremely Inverse (ANSI/IEEE type EI): t = tE>inv · {5.64 / [(IE/IE>inv)2 - 1] + 0.024} • Electromechanical (EM): t = tE>inv · {0.28 / [-0236 · (IE/IE>inv)-1 + 0.339]} Where: t: operate time IE >: pickup value tE >inv: operate time setting For all inverse time characteristics, following data applies: • Asymptotic reference value (minimum pickup value): 1.1 IE> • Minimum operate time: 0.1 s • Range where the equation is valid:[1] 1.1 ≤ IE/IE>inv ≤ 20 • If IE>inv pickup ≥ 0.5 IEn, the upper limit is 10 IEn For all definite time elements the upper limit for measuring is 10 IEn. All residual overcurrent elements can be enabled or disabled by setting ON or OFF the IE>�En- able, IE>>�Enable�and/or IE>>>�Enable�parameters inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus. The first overcurrent element can be programmed with definite or inverse time characteristic by setting the IE>Curve parameter (DEFINITE,�IEC/BS�A,�IEC/BS�B,�IEC/BS�C,�IEC/BS�B�LI,� ANSI/IEE�MI,�ANSI/IEE�VI,�ANSI/IEE�EI,�EM) available inside the Set \ Profile A(or B) \ Re- sidual overcurrent-50N/51N \ IE> Element \ Setpoints menu. Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point t-int-F50N-51N.ai IE IE>> IE>>> tE> tE>> tE>>> IE> t TRIP General operation time characteristic for the residual overcurrent elements - 50N/51N

NA20 - Manual - 04 - 2022

The trip of IE> element may be inhibited by the start of the second and/or third el- ement (IE>>, IE>>>) by setting ON the Disable IE> by start IE>>, Disable IE> by start IE>>> (IE>disbyIE>>,� IE>disbyIE>>>) parameters available inside the Set \Profile A(or B) \ Residual overcurrent-50N/51N \ IE>> Element (IE>>> Element) \ Setpoints menus. Similarly the trip of the IE>> element may be inhibited by start of the third element (IE>>>) by setting ON the Disable IE>> by start IE>>> (IE>>disbyIE>>>) parameter available inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE>>> Element \ Setpoints menu. All the named parameters can be set separately for Profile A and Profile B (Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus). An adjustable reset time delay is provided for every threshold tE>RES, tE>>RES, tE>>>RES). Each residual overcurrent element can produce the Breaker Failure output if the IE>�BF, IE>>�BF� and/or IE>>>�BF�parameters are set to ON. The parameters are available inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus.[1] For all overcurrent elements, a block from the second harmonic restraint may be set by setting ON the IE>2ndh-REST,�IE>>2ndh-REST,�IE>>>2ndh-REST parameters inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus. If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may be blocked for an adjustable time interval, starting from the circuit breaker closure. This operating mode may be select by setting ON-Element�blocking�the IECLP>�Mode,�IECLP>>� Mode,�IECLP>>>�Mode parameters. If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may be changed for an adjustable time interval, starting from the circuit breaker closure. This operating mode (ON-Change� setting� = IECLP>� Mode,� IECLP>>� Mode,� IECLP>>>� Mode) and the concerning operating time within the CLP (tECLP>,�tECLP>>,�tECLP>>>) may be adjusted inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus, whereas the operating thresholds within the CLP ( IECLP>def,� IECLP>inv,....) may be adjusted inside the Set\Profile A(or B)\ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Definite time (Inverse time) menus. For every of the four thresholds the following block criteria are available: Logical block (Block1) If the IE>BLK1,�IE>>BLK1�and/or�IE>>>BLK1 enabling parameters are set to ON and a bi- nary input is designed for logical block (Block1), the concerning element is blocked off whenever the given input is active.[2] The enabling parameters are available inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus, while the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input IN1(x) menus. Selective block (Block2) All along the protective elements the selective block may be set. The logic selectivity function may be performed by means any combination of the following I/O: • One committed pilot wire input (BLIN1). • One or more binary inputs designed for input selective block. • One committed pilot wire output (BLOUT1). • One or more output relays designed for output selective block. Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR- ING section Timers-F50N-51N.ai IE> element residual overcurrent (50N/51N) - Timers IE> Start IE> Trip tE> tE> RESET INPUT tE>RES tE>RES tE>RES t

NA20 - Manual - 04 - 2022

General logic diagram of the residual overcurrent elements - 50N/51N IE IE IE tE>> def IECLP>> def IE>> def IECLP>>Mode tECLP>> tE>>RES IE>> Enable tE>>> def IECLP>>> def IE>>> def IECLP>>>Mode tECLP>>> tE>>>RES IE>>> Enable tE> def IECLP> def IE> def tE> inv IECLP> inv IE> inv IE>Curve IECLP>Mode tECLP> tE>RES IE> Enable all-F50N-51N.ai ≥ IE>> inhibition BLK1IE>>> IE>>>BF IE>>> Element Start IE>>> Start IE>>> Start IE>>> Trip IE>>> Trip IE>>> & IE>> disbyIE>>> & IE>>>BLK2IN & IE> disbyIE>>> BLK1IE>> IE>> Element BLK2OUT Start IE>> Start IE>> Trip IE>> & IE> disbyIE>> & IE>>BLK1 & IE>>BLK2IN IE> inhibition Block1 BLK1IE> CLPIE> CLPIE>> CLPIE>>> IE> Element BLK2OUT BLK2INIE> BLK2INIE>> Start IE> Trip IE> & IE>BLK1 Block2 & IE>BLK2IN Start I2ndh> & IE>2ndh-REST IE>BLK2OUT Start I2ndh> & IE>>2ndh-REST Start I2ndh> & IE>>>2ndh-REST & IE>>>BF IE>>BF IE>> Trip & IE>>BF IE>BF Trip I> & IE>BF Start IE> & IE>>BLK2OUT Start IE>> & BLK2OUT IE>>>BLK2OUT Start IE>>> & Block1 Block2 & IE>>>BLK1 Block1 Block2 Start I> & Start IE>> & Start IE>>> & Start IE>> & BLK2INIE>>> Start IE>>> & Start I> &

NA20 - Manual - 04 - 2022

Only when the committed pilot wire are used the continuity check of the pilot wire link is active. Use of committed pilot wire input BLIN1: • The protection is blocked off according the selectivity block criteria when the input BLIN1 is active. The information about phase or phase+earth block may be select programming the ModeBLIN1 parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus. Use of binary inputs: • If the IE>BLK2IN,� IE>>BLK2IN� and/or� IE>>>BLK2IN parameters are set to ON and a binary input is designed for selective block (Block2), the protection is blocked off by phase ele- ments (Block2 Iph) or by any protection element (Block2 Iph/IE) according the selectivity block criteria.[1] The enable IE>BLK2IN,�IE>>BLK2IN�and/or�IE>>>BLK2IN�parameters are avail- able inside the Set \ Profile A(or B) \ Residual overcurrent-50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus, while the Block2 Iph and�Block2�Iph/IE functions must be assigned to the selected binary inputs inside the Set \ Inputs \ Binary input IN1(x) menus (IN1 or INx matching). Use of committed pilot wire output BLOUT1: • The information about phase or phase+earth block may be select programming the ModeBLOUT1 parameter (OFF�-�ON�IPh�-�ON�IPh/IE�-�ON�IE) inside Set \ Profile A(or B) \ Selective block- BLOCK2 \ Selective block OUT menus. Use of output relay (K1...K6): • If the IE>BLK2OUT,�IE>>BLK2OUT�and/or�IE>>>BLK2OUT enable parameters are set to ON and a output relay is designed for selective block (Block2), the protection issues a block output by phase elements (BLK2OUT-Iph) or by any protection element (BLK2OUT-Iph/IE), whenever the given element (Start IED>, Start IED>>, Start IED>>> and/or Start IED>>>>) becomes active. The enable IED>BLK2OUT,�IED>>BLK2OUT,�IED>>>BLK2OUT�and/or�IED>>>>BLK2OUT� parameters (ON or OFF) are available inside the Set \ Profile A(or B) \ Residual overcurrent- 50N/51N \ IE> Element (IE>> Element, IE>>> Element) \ Setpoints menus, while the BLK2OUT- Iph-K,�BLK2OUT-Iph/IE-K�and/or BLK2OUT-IE-K�output relays and LEDs (BLK2OUT-Iph-L,� BLK2OUT-Iph/IE-L�e/o BLK2OUT-IE-L) must be select inside the Set \ Profile A(or B) \ Selec- tive block-BLOCK2 \ Selective block OUT menu. Note 1 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND MONITORING section

NA20 - Manual - 04 - 2022

Residual overcurrent (50N/51N) - First element logic diagram (IE>) Fun_50N-51NS1.ai t >RES T 0 RESET tE> 0 T ≥1 tE>def tE>inv tE>RES Start IE> Trip IE> CB-State Start I2ndh> ON≡Inhibit (from IE>> and/or IE>>> residual overcurrent element) ON≡Enable IE> residual overcurrent element IE> inhibition Block1, Block2 & T 0 tECLP> & 2nd harmonic restraint enable (ON≡Enable) IE>2ndh-REST IECLP>Mode tECLP> BF Enable (ON≡Enable) IE>BF towards BF logic IE> BF & Trip IE> TRIPPING MATRIX (LED+RELAYS) IE> Curve 0 T A B C A =“1” A =“0 or OFF” Output tECLP> IE> Enable IE> overcurrent element (50/51) Block diagram tECLP> CB State CB OPEN CB CLOSED CB OPEN Output tECLP> t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking IE>TR-K IE>TR-L IE>ST-L IE>ST-K ≥1 CLP IE> IE ≥1 (Pickup within CLP) (Pickup outside CLP) IECLP>def IECLP>inv IE ≥ IECLP> & State IE>inv IE ≥ IE>def IE ≥ IE>inv IE>def & State

NA20 - Manual - 04 - 2022

Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the first element (IE>) IE>BLK1 Start IE> Trip IE> Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 50N-51NS1_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1IE> & & BLK2IN IE> & & Enable (ON≡Enable) Block2 input enable (ON≡Enable) Pilot wire input & IE>BLK2IN Block1 BLK2IN-Iph Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 Start IE> & Block2 output (ON≡Enable) IE>BLK2OUT Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Fun_50N-51NS2.ai tE>>RES T 0 RESET tE>> 0 T ≥1 tE>>def tE>>RES Start IE>> Trip IE>> CB-State Start I2ndh> IE>> inhibition Block1, Block2 & IE>>TR-K IE>>TR-L IE>>ST-L IE>>ST-K T 0 tECLP>> & 2nd harmonic restraint enable (ON≡Enable) IE>>2ndh-REST IECLP>>Mode tECLP>> BF Enable (ON≡Enable) IE>>BF towards BF logic IE>> BF & Trip IE>> TRIPPING MATRIX (LED+RELAYS) A B C Output tECLP>> IE>> Enable IE>> overcurrent element (50/51) Block diagram tECLP>> CB State CB OPEN CB CLOSED CB OPEN Output tECLP>> t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK A = ON - Change setting B = OFF C = ON - Element blocking & (ON≡Inhibit) Start IE>> Start IE>> IE> inhibition IE> disbylE>> ≥1 CLP IE>> ON≡Inhibit (from IE>>> residual overcurrent element) ON≡Enable IE>> residual overcurrent element IE>>def A =“1” A =“0 or OFF” IE (Pickup within CLP) (Pickup outside CLP) IECLP>>def IE ≥ IECLP>>def & State IE ≥ IE>>def Residual overcurrent (50N/51N) - Second element logic diagram (IE>>)

NA20 - Manual - 04 - 2022

Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the second element (IE>>) IE>>BLK1 Start IE>> Trip IE>> Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 50N-51NS2_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1IE>> & & BLK2IN IE>> & & Enable (ON≡Enable) Block2 input enable (ON≡Enable) Pilot wire input & IE>>BLK2IN Block1 BLK2IN-Iph Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 Start IE>> & Block2 output (ON≡Enable) IE>>BLK2OUT Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Residual overcurrent (50N/51N) - Third element logic diagram (IE>>>) Fun_50N-51NS3.ai tE>>>RES T 0 RESET tE>>>def 0 T ≥1 tE>>>def tE>>>RES Start IE>>> Trip IE>>> CB-State Start I2ndh> ON≡Enable IE>>> residual overcurrent element Block1, Block2 & IE>>>TR-K IE>>>TR-L IE>>>ST-L IE>>>ST-K T 0 tECLP>>> & 2nd harmonic restraint enable (ON≡Enable) IE>>>2ndh-REST IECLP>>>Mode tECLP>>> BF Enable (ON≡Enable) IE>>>BF towards BF logic IE>>> BF & Trip IE>>> TRIPPING MATRIX (LED+RELAYS) A B C A = ON - Change setting B = OFF C = ON - Element blocking Output tECLP>>> IE>>> Enable IE>>> residual overcurrent element (50/51) Block diagram tECLP>>> CB State CB OPEN CB CLOSED CB OPEN Output tECLP>>> t 0.1 s HIGH THRESHOLD/ BLOCK LOW THRESHOLD/ UNBLOCK HIGH THRESHOLD/ BLOCK & (ON≡Inhibit) Start IE>>> Start IE>>> Start IE>>> (ON≡Inhibit) IE> inhibition IE>disbylE>>> & IE>> inhibition IE>>disbylE>>> ≥1 CLP IE>>> IE>>>def A =“1” A =“0 or OFF” IE (Pickup within CLP) (Pickup outside CLP) IECLP>>>def IE ≥ IECLP>>>def & State IE ≥ IE>>>def

NA20 - Manual - 04 - 2022

Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the third element (IE>>>) IE>>>BLK1 Start IE>>> Trip IE>>> Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 T 0 tB-Iph 50N-51NS3_BL-diagram.ai ≥1 ≥1 ≥1 ≥1 tB-Iph tB-IE BLK1IE>>> & & BLK2IN IE>>> & & Enable (ON≡Enable) Block2 input enable (ON≡Enable) Pilot wire input & IE>>>BLK2IN Block1 BLK2IN-Iph Iph Block2 IE Block2 BLK2IN-IE tB timeout Block2 input tB-K tB-L Block1 FROM GROUND PROTECTIONS FROM PHASE PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block1 T 0 tB-IE Block2 IE ≥1 Block1, Block2 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 Start IE>>> & Block2 output (ON≡Enable) IE>>>BLK2OUT Pilot wire output TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D BLOUT1 Block2 output ≥1 tF-IPh tF-IPh/IE tF-IE ST-Iph BLK2 ST-IE BLK2 ≥1 T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE I> Block2 OUT BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT ≥1 IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT

NA20 - Manual - 04 - 2022

Breaker failure - BF Preface When the protection issues a trip command but, because an anomaly, the circuit breaker cannot open, the breaker failure protection issues a back-up trip command to trip adjacent circuit breakers. The breaker failure function may be started by internal protective function (if associated with BF) or by external protections. Operation and settings The starting of the timer occurs if both the following conditions are filled: A) Start and trip of internal protective elements (trip of elements matched with BF protection) or, trip of external protections acquired by means binary input, if enabled; B) The CB is closed (the CB state may be acquired by means two binary inputs connected to the auxiliary contacts 52a and 52b) or the fundamental component of at least one phase current IL1, IL2, IL3 is greater than the IBF> adjustable threshold or the fundamental component of the residual current IE is greater than the IEBF> adjustable threshold. The breaker failure protection reliability is improved by means of the CB position control or phase or residuaI current measure; the trip can arise also for wrong auxiliary contacts state (if the current is greater than the adjustable threshold ) or for trip of external protections (frequency, voltage,..) without current (with CB closed information supplied from state of auxiliary contacts). If the information concerning the CB position is not achievable (for instance the auxiliary contacts are unavailable), such control must be disabled. If both conditions are held along the set operate time tBF, the BF element trips at deadline, vice versa the timer is cleared and the function is restored. To the purpose to restore the BF element as quickly as possible, with start of the same protection (see A condition), additionally to the trip of some internal protections, their starts are required (start reset is faster than trip reset). The element may be enabled or disabled by setting ON the BF�Enable parameter available inside the Set \ Profile A(or B) \ Breaker failure-BF menu. All the IBF>, IEBF and tBF parameters can be set separately for Profile A and Profile B; they are avail- able inside the Set \ Profile A(or B) \ Breaker failure-BF menu. BF start from Circuit breaker If the CB Input parameter (BF Start from circuit breaker) is set to ON, and two binary inputs are designed for acquire the 52a and 52b auxiliary contacts[1], the control of the CB position is enabled. If the information concerning the CB position is not available, such control must be disabled by setting OFF the CB Input parameter. The parameter is available inside the Set \ Profile A(or B) \ Breaker failure-BF menu, the 52a�and�52b function must be assigned to the selected binary inputs inside Set \ Inputs \ Binary input IN1(x) menus (IN1 or INx matching). To enable the breaker failure protection to operate with trips coming from external protections, one binary input must be designed to acquire the relative contacts. The TripProtExt function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input IN1(2...) menus (IN1 or IN... matching). Logical block (Block1) If the BF-BLK1 parameter (BF logical block) is set to ON, and a binary input is designed for logical block (Block1), the breaker failure protection is blocked off whenever the given input is active. The trip timer is held in reset condition, so the operate time counting starts when the input block goes down.[2] The enabling parameter is available inside the Set \ Profile A(or B) \ Breaker failure-BF menu, while the Block1 function must be assigned to the selected binary input inside the Set \ Inputs \ Binary input IN1(x) menus (IN1 or INx matching). Note 1 Both auxiliary contact state 52a and 52b must be acquired (two binary inputs are required) with Fw version previous to 1.60; with later versions, giving up an inconsistency occurs, one logical input for the acquisition of a contact (52nd or 52b ) may suffice Note 2 The exhaustive treatment of the logic block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITORING section all-FBF.ai General logic diagram of the breaker failure element - BF Block1 BLK1 BF IL1...IL3 IE 52b 52a Trip ProtExt Start BF Trip BF Block1 & BF-BLK1 BF Enable IBF> IEBF> t BF

NA20 - Manual - 04 - 2022

Logic diagram concerning the breaker failure element -BF Fun-BF_Pro-n.ai TRIPPING MATRIX (LED+RELAYS) Start BF Start IBF> Trip BF Trip int-prot & & & & Block1 input (ON≡Block) BLK1 BF Trip Int/Ext Block1 Start BF ON≡CB Closed Start BF Trip BF Trip BF Trip ProtExt 52a & Block1 enable (ON≡Enable) BF-BLK1 Block1 52a IBF> Max IL1...IL3 ≥ IBF> IL1 IL2 IL3 IEBF> IE ≥ IEBF> IE ≥1 RESET tBF 0 T t BF ≥1 Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF 52b Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF 52b Start IEBF> “0” CB Input CB Input OFF CB Input ON

NA20 - Manual - 04 - 2022

4.5 CONTROL AND MONITORING Logical block - BLOCK1 To the purpose to block off the trip of one protection element, the logical block function (Block1) may be matched with binary inputs.[1] The binary-matching may be set inside the Inputs submenu; to the purpose the Block1 parameter must be selected for INx�matching (x=1, 2) A protective element, where the logical block is enabled, is blocked off whenever the given input is ON. For a given protective element, the logical block state is reading available (ThyVisor and communi- cation interfaces); it is ON the following condition are at the same time observed: • Binary input ON, • Element start ON, • Element Trip OFF. The logical block it is not liable for any inhibition time-out, so the protective element is disabled for the whole time when the input is ON.[2] Note 1 In the following treatment, the logical block is defined as “Logical block” or “Block1” Note 2 The Block 1 signal forces a timer reset Blocco_L.ai RESET Operate time 0 T Generic protective element Measure Input TRIPPING MATRIX (LED+RELAYS) BLK1xxx Operate time Threshold Start Start Trip Trip & & & Enable (ON≡Enable) Block1 input (ON≡Block) Customized Block1 info Block1 info (internal state) xxxBLK1 Block1 Block1 Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF General logic diagram of the logic block - Block1 Start Block1 (input) Block1 (output) Trip Operate time t Timers-Block1.ai Logic block timers - Block1 Activation of any binary input assigned ti logic block (Block1) function effects a block of all the protective elements where the logic block is enabled CAUTION

NA20 - Manual - 04 - 2022

Logic diagram concerning the logic block element -Block1 Block1_L.ai Start Trip & & & Enable (ON≡Enable) (ON≡element inhibition) Customized Block1 info Reset timers Block1 info (internal state) xxxBLK1 Block1 IBLK1 50-51 element I>>BLK1 I2>BLK1 (I2/I1)> element (I2/I1)>BLK1 I2>>BLK1 50-51 element I>>>BLK1 50-51 element IE>BLK1 50N-51N element IE>>BLK11 50N-51N element IE>>>BLK1 50N-51N1 element

NA20 - Manual - 04 - 2022

Selective block -BLOCK2 Preface The logic selectivity function has been developed to the purpose to reduce the clearing times for faults closes to the source. The output blocking circuits of one or several Pro_N relays, shunted together, must be connected to the input blocking circuit of the protection relay, which is installed upwards in the electric plant. The output circuit works as a simple contact, whose condition is detected by the input circuit of the upwards protection relay. The logic selectivity function can be realized through any combination of the following I/O circuits: • One committed pilot wire input BLIN1...ON Iph, ON...Iph/IE, ON...IE. • One committed pilot wire output BLOUT1...ON Iph, ON...Iph/IE, ON...IE. • One or more than one independent binary inputs programmed with Block2 Iph, Block2�Iph/IE or Block2�IE. • One or more than one independent output relays programmed with BLK2OUT-Iph-K, BLK2OUT- Iph/IE-K or BLK2OUT-IE-K. In reference to the following schematic diagram, the some protection functions of the relay placed on the feeder may be blocked by downstream protective relays. Input selective block Use of committed pilot wire input BLIN1 The input is a polarized wet type powered by internal isolated supply; it must be drive by an output block signal coming from a Pro-N device or by a free voltage contact. The protection is blocked off according the selectivity block criteria by phase elements (Block2 Iph), by earth elements (Block2�IE) or by any protection element (Block2�Iph/IE) when the input BLIN1 is active. The information about phase or phase+earth block may be select programming the ModeBLIN1 parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block IN menus. Use of binary inputs If the xxBLK2IN parameters (enable) are set to ON and a binary input is designed for selective block (Block2), the protection is blocked off by phase elements (Block2 Iph), by earth elements (Block2�IE) or by any protection element (Block2�Iph/IE), according the selectivity block criteria, when the input (IN1 and/or INx) is active. The Block2�Iph,�Block2�IE�and�Block2�Iph/IE matching must be assigned to the selected binary inputs inside the Set \ Inputs \ Binary input 1 and Set \ Inputs \ Binary input x menus. When a binary input is programmed for selective block input, the IN1 tON, INx tON, IN1 tOFF and INx tOFF time delays must be reset to zero; the Logic parameters (ON/OFF) must be programmed in the same way of the related output relay connected with-it. Logic selectivity Pro_N Pro_N Pro_N Pro_N logica_acc.ai BLIN1 BLK2OUT-Iph-K INx=Blocco selettivo Iph BLOUT1 BLOUT1 BLOUT1 BLIN1 BLIN1 TRIP TRIP TRIP TRIP TRIP Any device Never connect power to the block input circuit; the electronic circuit can be demaged WARNING

NA20 - Manual - 04 - 2022

Operation For any protective element, three main conditions can arise: A) Start = OFF: the element is at rest (no trip) regardless of the input/output blocks. B) Start = ON: the element trips if no selective block input becomes active during the operate time. C) Start = ON: if the selective block input (BLIN1 and/or binary input) becomes active, the element goes in selective block state wherein the operate timer is forced to reset, so the element cannot trip. After an adjustable time tB-Iph (common for phase protection elements) or tB-IE (common for earth protection elements), the selective block input is disregarded and the operate timer can start again. Information about tB-Iph and or tB-IE expired is available for reading (tB�timeout data inside Read \ Selective block - BLOCK2 \ Block2 input menu) and can drive an output relay and or a LED (tB-K�and or tB-K�parameters inside Set \ Profile A(or B) \ Selective block - BLOCK2 \ Selective block IN submenu). With a setting other than 0.00 s, the tB-Iph and tB-IE timers may be used to have a backup protection available against pilot wire short circuit.[1] The tB-Iph and/or tB-IE timers must be adjusted according the following rule (example for tB-Iph): tB-Iph = tFv + et + es where tFv is the value of block output timer related to the downstream relay (example tF-Iph), et is a chronometric selectivity margin to apply in comparison to the tB-Iph time related to the downstream relay (does not take into account if such margin has been considered for the tF-Iph setting), es is a safety margin. The chronometric selectivity applied among the tB-x times of the relays in accelerated logic system allows to avoid more the contemporary circuit breaker opening after the clearing of a fault in a line of concomitant plant to the short-circuit of the pilot wires concerning the same line. Note 1 In the absence of suitable provisions, a short circuit on a pilot wire causes the block of the receiving relay, so a possible fault (contemporary or following) inside the protected zone, cannot be cleared that being the case the protective relay blocked. Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Binary input INx T 0 Logic INx t ON INx t ON INx t OFF T 0 n.o. n.c. INx t OFF Block2 IPh Block2 IPh/IE ModeBLIN1 PulseBLIN1 T 0 Pilot wire Diagnostic Pulse BLIN1 Block2-in-diagram.ai ≥1 ≥1 ≥1 ≥1 BLK2IN xx & & & Pilot wire input No pulses Permanently “ON” xxBLK2IN BLK2IN-Iph Start xx Trip xx BLK2IN I> & & Block2 input enable (I> element) Block2 input enable (I>, I>>, I>>>, IE>, IE>>, IE>>>, elements) (ON≡Enable) & I>BLK2IN Start I> Trip I> Iph Block2 IE Block2 BLK2IN-IE tB timeout FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS FROM PHASE PROTECTIONS OFF ON IPh ON IPh/IE ON IE BLIN1 Block2 IE Breaked BLIN1 TRIPPING MATRIX (LED+RELAYS) ≥1 ≥1 Shorted BLIN1 Logic diagram concerning the selective block intput - Block2 input T 0 tB-Iph tB-Iph tB-IE T 0 tB-IE

NA20 - Manual - 04 - 2022

To enable the selectivity logic input for a generic xx element, the xxBLK2IN parameters must be set to ON inside the Set \ Parametri di configurazione A (o B) \ xxx \ Setpoints menus concerning all element where the selective block is available, eg: I>BLK2IN inside the Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I> Element \ Setpoints menu. Output selective block Use of output relays If the xxBLK2OUT,�xxBLK2OUT�and/or�xxBLK2OUT enable parameters are set to ON and a output relay is designed for selective block (Block2), the protection issues a block output by phase elements (BLK2OUT-Iph), by ground elements (BLK2OUT-IE) or by any protection element (BLK2OUT- Iph/IE), whenever the given start is active. The BLK2OUT-Iph-K,�BLK2OUT-Iph/IE-K�and/or BLK2OUT-IE-K�output relays must be set in- side the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block OUT menu; the same for ad- dressing the LED indicators (BLK2OUT2-Iph-L,�BLK2OUT2-IE-L�and�BLK2OUT2-Iph/IE_L). When output relays are programmed for selective block output, the tTR time delays must reset to zero; the operation mode must be set with self reset (No-latched inside Set \ Relays submenu) and the Logic parameters (Energized/De-energized) must be programmed in the same way of the related binary input connected with-it. Use of committed pilot wire output BLOUT1 The output is a dry static relay. The information about phase (ON IPh), earth (ON�IE), or phase+earth (ON�IPh/IE) concerning the sending block out signal may be select by means of the ModeBLOUT1 parameter inside the Set \ Profile A(or B) \ Selective block-BLOCK2 \ Selective block OUT menu. The parameters can be set separately for A and B profiles. Operation The selective block outputs go ON at the same time of the xx element start; they hold steady (even if the start reset to zero) for along the tF-IPh, tF-IE and tF-IPh/IE adjustable times for phase, earth and phase+earth functions. The timers starts when one or more selective block function goes ON; when a timer expires, the selective block outputs are disregarded (even if the start holds steady). The tF-IPh and tF-IE counters start when the output selective block becomes active. When the coun- ters expire the block selective output is forced off (despite the start xxx remain active). If the tF-IPh, tF-IE e tF-IPh/IE timers are cleared the selective block output state is freeze up to the start xxx remain active. With a setting other than 0.00 s, the tF-IPh, tF-IE e tF-IPh/IE timers may be used to provide a backup protection against breaker failure inside a selectivity logic system, as well as to hold blocked up- stream protective relays up after the fault is cleared with CB opening to provide solution against unwanted trips because of a larger reset time compared with the downstream relay (the selectivity will be lost). TB-timer.ai t tB-Iph/tB-IE BLIN2IN-Iph/BLIN2IN-IE tB timeout INPUT BLOCK (binary input and/or BLIN1) tB timer TF-timer.ai t tF-IPh, tF-IE, tF-IPh/IE tF-IPh, tF-IE, tF-IPh/IE Start xx (internal elements) tF timers BLK2OUT-Iph BLK2OUT-IE BLK2OUT-Iph/IE

NA20 - Manual - 04 - 2022

With traditional selective logic systems, in the absence of suitable cares, the event of a circuit breaker failure causes the block of the receiving relays situated upstream the circuit breaker, so the fault cannot be cleared. When using the Pro-N devices inside the selective logic systems, the answer to the circuit breaker failure problem can be solved by means of, (as well as the BF-Breaker Failure element) or by means of a threshold adjusted for time selectivity, through use of the output block reset timer too with the intent that avoid permanently block of all upstream relays by downstream block signals (the only one unblocked relays deals to the fault breaker). The tF-IPh, tF-IE, tF-IPh/IE timers must be adjusted according the following rule (example for tF-Iph): tF-Iph = t + TAP + trip + et + es where t is the larger phase protection operate time, TAP is the circuit breaker operate time (with arc extinction), trip is the larger reset time of all protective relays inside the selective logic system, et is an potential selectivity margin relative to the tF-x time of the downstream relays, es is a safety margin need to include timers errors (tolerances). Diagnostic To guarantee maximum fail-safety, the relay performs a run time monitoring for pilot wire continuity and pilot wire shorting.[1] Exactly the output blocking circuit periodically produces a pulse, having a small enough width in order to be ignored as an effective blocking signal by the input blocking circuit of the upstream protection, but suitable to prove the continuity of the pilot wire. Furthermore a permanent activation (or better, with a duration longer than a preset time) of the blocking signal is identified, as a warning for a possible short circuit in the pilot wire or in the output circuit of the downstream protection. The periodic pulses that are sent by output circuit may be enabled or disabled by means the Pulse- BLOUT1� parameter available inside the Set \ Pilot wire diagnostic menu; with OFF setting the pulses are disabled.[2] If no pulses are received inside an adjustable time window at the selective block input circuit, a break pilot wire alarm is issued; the information is available for reading (Breaked BLIN1 data inside Read \ Pilot wire diagnostic submenu) and can drive an output relay and or a LED (PulseBLIN-K and or a PulseBLIN-L parameters inside Set \ Pilot wire diagnostic submenu). Note 1 Full diagnostic of pilot wires is only available when committed pilot wire input/outputs are employed Note 2 When several outputs are parallel linked the pulse emission must be enabled inside one device only, sooner inside the outermost device Pilot wire output Pilot wire link ≥1 Pulse generator BLOCK OUT BLOCK IN T 0 Pilot wire Diagnostic Pilot wire input No pulses Permanently “ON” BLIN1 BLOUT1 Breaked BLIN TRIPPING MATRIX (LED+RELAYS) Shorted BLIN Pulse BLIN1 Pulse BLIN1 Pulse BLOUT1 Pulse BLOUT1 Block2-diagram.ai Pilot wire output BLOUT1 TRIPPING MATRIX (LED+RELAYS) ModeBLOUT1 A B C D ≥1 ST-Iph BLK2 ST-IE BLK2 & Block2 output (ON≡Enable) I>BLK2OUT Start I> BLK2OUT-Iph BLK2OUT-Iph/IE BLK2OUT-IE A = OFF B = ON IPh C = ON IPh/IE D = ON IE BLK2OUT-IPh-K BLK2OUT-IPh-L BLK2OUT-IPh/IE-K BLK2OUT-IPh/IE-L BLK2OUT-IE-K BLK2OUT-IE-L ≥1 Start IE>>> & Block2 output (ON≡Enable) IE>>>BLK2OUT IE>> Block2 OUT IE> Block2 OUT IE>>> Block2 OUT Logic diagram concerning the selective block output - Block2 output ≥1 I> Block2 OUT I>> Block2 OUT I2> Block2 OUT I2>> Block2 OUT I>>> Block2 OUT DthAL1 Block2 OUT DthAL2 Block2 OUT Dth Block2 OUT tF-IPh tF-IPh/IE tF-IE T 0 tF-IPh/IE T 0 tF-IPh T 0 tF-IE

NA20 - Manual - 04 - 2022

The control window may be programmed for OFF (no control) - 0.1 -1 - 5 - 10 - 60 - 120 s; the Pulse BLIN1 parameter is available inside the Set \ Pilot wire diagnostic menu; with OFF setting of the the PulseBLIN1 parameter the pulse control is disabled. The same setting must be for input and output (PulseBLIN1 and PulseBLOUT1). In the following example the output pulses must be enabled inside the device B only (2nd logic se- lectivity level) and D (1st logic selectivity level). Setting example In reference to the above shown schematic diagram, the logic selectivity is performed by means of the dedicated I/O for the short circuit elements of A, B and C protective relays, so that if a fault arises in (2), the open order or circuit breaker CB2 is issued and no trip is issued by A device. A command must be issued for the main circuit breaker CB1 by the A relay with a fault in (1). A Protection I>> element with definite time set to 4.5 In with operate time to 0.10 s blocked by start of B and/or C protection. Settings: • I>>def = 4.5 In • t>>def = 0.100 s • PulseBLOUT1 = OFF • PulseBLIN1 = 1 s • I>>BLK2IN = ON • I>>BLK2OUT = OFF • tB-IPh = 0.30 s B Protection I>> element with definite time set to 4.0 In with operate time to 0.10 s with emission of block output toward A protection relay. Settings: • I>>def = 4.0 In • t>>def = 0.100 s • I>>BLK2IN = OFF • I>>BLK2OUT = ON • PulseBLIN1 = OFF • PulseBLOUT1 = 1 s • tF-IPh = 0.25 s C Protection I>> element with definite time set to 4.0 In with operate time to 0.10 s with emission of block output toward A device and block input from D protection relay. Settings: • I>>def = 4.0 In • t>>def = 0.100 s • I>>BLK2IN = ON • I>>BLK2OUT = ON • PulseBLIN1 = 1 s • PulseBLOUT1 = OFF • tF-IPh = 0.25 s • tB-IPh = 0.30 s LOAD Pro_N Pro_N Pro_N CB1 CB2 CB3 CB4 Pro_N logica_acc-esempio.ai Logic selectivity BLIN1 BLOUT1 BLOUT1 BLOUT1 BLIN1 BLIN1 TRIP TRIP TRIP 2nd logic selectivity level 1st logic selectivity level TRIP 1 2 B C D A

NA20 - Manual - 04 - 2022

Remote tripping Preface Some output relays may be programmed for remote trip function resulting from a command coming from a binary input. If a binary input is designed for remote trip acquisition, an output relay allocated to the same function is triggered when the input (IN1 and/or IN2) is active. Operation and settings The Remote�trip�matching must be assigned to the selected binary inputs inside the Set \ Inputs \Binary input1 or Set \ Inputs \ Binary inputx menus. When a binary input is programmed for remote trip acquisition, the IN1 tON, IN2 tON, IN1 tOFF and IN2 tOFF time delays must be reset to zero; the Logic parameters (ON/OFF) must be pro- grammed in the same way of the related circuit connected with-it. The RemTrip-K matching must be assigned to the selected output relays inside the Set \ Remote tripping submenu; the same for addressing the LED indicators (RemTrip-L). When output relays are programmed for remote tripping, the tTR time delays must reset to zero; the operation mode must be set with self reset (No-latched inside Set \ Relays submenu) and the Logic parameters (Energized/De-energized) must be programmed in the same way of the related binary input connected with-it. All the parameters are common for A and B Profiles. Remote tripping logic diagram Fun-Remote-trip.ai Remote trip +UAUX -UAUX Remote trip Binary input INx RemTrip-K RemTrip-L T 0 INx t ON T 0 n.o. n.c. INx tON Logic INx tOFF INx t OFF TRIPPING MATRIX (LED+RELAYS) Remote trip

NA20 - Manual - 04 - 2022

Frequency tracking Within the frequency range 45...55 Hz (fn = 50 Hz). or 54...63 Hz (fn = 60 Hz), a frequency tracking al- gorithm adjusts the currents sampling frequency, so as to keep the number of samples in any given period constant. With 24 samples for periods the sampling rate is adjusted from 1.08 kHz with f = 45 Hz to 1.512 kHz with f= 63 Hz For a frequency step change the tracking response time is 10 Hz/s. The frequency measure is based on the largest phase current. • If the larger phase input current is lower than 25% In the sampling frequency is fixed to fn (50 or 60 Hz). • If the measured frequency is outside the locking range, the sampling frequency is fixed to the lower or upper value (45 or 55 Hz with fn = 50 Hz, 54 or 63 Hz with fn = 63 Hz). All protective elements are always operative; accuracy is guaranteed inside locked frequency band. Displayed value Locked frequency Locked frequency (Displayed value) Displayed value Locked frequency Locked frequency (Displayed value) Frequency tracking IF.ai Frequency tracking 0.25 In 0.25 In 40 45 60 55 f (Hz) 50 Hz (0 Hz) Nominal frequency fn = 50 Hz Max IL1...L3 40 Hz 45 Hz 60 Hz 55 Hz 40 54 70 63 f (Hz) 60 Hz (0 Hz) Nominal frequency fn = 60 Hz Max IL1...L3 40 Hz 54 Hz 70 Hz 63Hz IL1 IL2 IL3 Max IL1...L3 > 0.25 In

NA20 - Manual - 04 - 2022

Second Harmonic Restraint - 2ndh-REST Preface When a power transformer is energized, as well know an inrush current flow in the side that have been energized with an amount and duration that depend by many factors which: • Instantaneous value of the supply voltage at the time where the transformer is energized • Transformer design, magnetization characteristic and size • Residual flux The maximum amount of the inrush current is produced by energizing the transformer at the zero point of the voltage wave, when it increase or decrease with the residual flux respectively positive or negative. Moreover the ratio between the maximum amount of the inrush current and the nominal current of the transformer decrease if the size of transformer increase, whereas the duration of the inrush current increase with the size of transformer. Some types of instantaneous protections as overcurrent, residually connected ground fault and dif- ferentials, are affected by this inrush current and their unwanted tripping can occur on transformer energizing. The second harmonic restraint is available to restraint any selected threshold of NA21 protective relay: • Negative sequence overcurrent - 46 • Negative sequence-positive sequence current ratio - I2/I1 • Thermal image - 49 • Phase overcurrent - 50/51 • Residual overcurrent - 50N/51N Moreover one or more output contacts may be allocated to the 2NDH-REST function in order to block any external protection relays where second harmonic restraint is not available. Operation and settings Each second harmonic component of phase currents (IL1-2nd, IL2-2nd, IL3-2nd) is compared with the I2ndh> adjustable threshold. When one or more currents overcome the setting threshold a start is issued. The start may be employed to block-off one or more 50/51/50N/51N elements or to block-off external protections by means output relays (this can be usefully used in order to restraint external protection relays where second harmonic restraint is not available). For the purpose to keep in block state the selected elements, an adjustable t2ndh>RES reset delay is provided. The setting of I2ndh> and t2ndh>RES parameters are available inside the Set \ Profile A(B) \ Second Harmonic Restraint menu. The second harmonic element may be enabled or disabled; to enable it, the Statee parameter must be set to ON inside the Set \ Profile A(B) \ Second Harmonic Restraint menu. All the parameters can be set separately for Profile A and Profile B. The output may be assigned to the selected I2ndh>-ST-K output relays inside the Set \ Profile A(B) \ Second Harmonic Restraint menu; the same for addressing the LED indicators (I2ndh>-ST-L). When output relays are programmed for second harmonic element output, the tTR time delays must reset to zero; the operation mode must be set with self reset (No-latched inside Set \ Relays menu) and the Logic parameters (Energized/De-energized) must be programmed in the same way of the related binary input connected with-it. Logic diagram concerning the second harmonic restraint function - 2NDH/REST 2NDH-REST-diagram.ai IL1-nd t2ndh>RES T 0 ≥1 t2ndh>RES Start I2ndh> ON≡Enable State & I2ndh>ST-K I2ndh>ST-L I2ndh> IL1-nd ≥ I2ndh> IL2-nd IL2-nd ≥ I2ndh> IL3-nd IL3-nd ≥ I2ndh> TRIPPING MATRIX (LED+RELAYS)