SME70, SME70-C, SME70-M-Manual-04-2020

SME70 SME70-C SME70-M DIRECTIONAL EARTH FAULT, SHORT-CIRCUIT AND VOLTAGE ELEMENTS MANUAL SME70 27V1 59 59V2 59N 51 67N SME70 27V1 59 59V2 59N 51 67N SME70 27V1 59 59V2 59N 51 67N

SME70, SME70-C, SME70-M-Manual-04-2020

I N T R O D U C T I O N — Scope and liability The functions, technical data, instructions for setting and commissioning of SME70, SME70-C, SME70-M (SME70 INDOOR FAMILY) devices are explained. This manual has been checked out, however, deviations from the description cannot be completely ruled out, so that no liability in a legal sense for correctness and completeness of the information or from any damage that might result from its use is formally disclaimed. The information given in this document is reviewed regularly; any corrections and integration will be included in subsequent editions that are identified by the date of revision. We appreciate any suggestions for improvement. We reserve the right to make technical improvements without notice. — Applicability This manual is valid for SME70 devices with firmware version 1.00 and following. — Conformity The product complies with the CEE directives: • EMC Council Directives 2014/30/EC • Low voltage Directives: 2014/35/EC • GICT-SGL_12_v01_OCS OT Security Guideline — Technical support Contact: THYTRONIC Technical Service www.thytronic.it — Copyright All right reserved; It is forbidden to copy, modify or store material (document and sw) protected by copyright without Thytronic consent. — Warranty Thytronic warrants devices against defects in materials and workmanship under normal use for a period of ONE (1) YEAR from the date of retail purchase by the original end-user purchaser (“War- ranty Period”). — Safety recommendations The warming contained in this document are all-important for safety; special attention must be paid to the following symbols: Installation and commissioning must be carried out by qualified person; Thytronic assumes no re- sponsibility for damages caused from improper use that does not comply all warning and caution in this manual. In particular the following requirements must be met: • Remove power before opening it. • Verify the voltage absence by means suitable instrumentation on relay connections; attention must be paid to all circuits supplied by external sources (binary input, analog inputs, etc...) • Care must be taken when handling metal parts (front panel, connectors). — Insulation tests After insulation tests, hazardous voltages (capacitor charges,...) may be arise; it is advisable to grad- ually reduce the test voltage avoiding to erase it abruptly. WARNING Death, severe personal injury or substantial property damage can result if proper precautions are not taken. CAUTION Minor personal injury or property damage can result if proper precautions are not taken

SME70, SME70-C, SME70-M-Manual-04-2020

G E N E R A L — Relay typology SME70 Suitable to install on MV cable lines connected with panels endowed with capacitor voltage divider transducer DJ1054 (approved by ENEL). The supplied device are: • SME70 • Cable for capacitor divider • Cable for UP connection SME70-C Suitable to install on MV cable lines connected with panels endowed with capacitor divider voltage transducer DJ1054 (approved by ENEL). The supplied device are: • SME70 • Rogowski current sensor • Cable for capacitor divider • Cable for UP connection SME70-M Suitable to install on MV cable lines connected with connected with busbar systems with bare con- ductors. The supplied device are: • SME70 • Rogowski current sensor • Cable for capacitor divider • Cable for UP connection • Capacitor voltage divider crossbar • Capacitor voltage divider transducer DJ1054 • Wiring and accessories for installation — General info SME70 INDOOR FAMILY fault detection systems are designed in conformity with the ENEL GSTP001 specification; they are installed in remote-controlled Secondary Stations in order to provide local and remote signalling of short circuit and earth faults that may occur in MV distribution networks. SME70, SME70-C, SME70-M quickly locate the line section affected by the fault thus reducing power outage. The SME70 INDOOR FAMILY can operate with: • insulated neutral • neutral earthed through an inductance with in parallel a resistor • neutral earthed through an resistor • neutral directly earthed The networks characteristics are: • Rated voltage: from 6 kV to 25kV ±10% • Maximum current of three-phase short circuit: 20 kA • Maximum value of time constant t of the phase unidirectional component decay: 2 ms • Maximum single phase ground fault current (insulated neutral earth): 500 A • Maximum single phase ground fault current (neutral earthed through a resistor): 1000 A • Maximum single phase ground fault current (neutral earthed through an inductance): 1000 A • Maximum single phase ground fault current (neutral directly earthed): 20 kA • Peak value of the unidirectional component of the current added to single phase ground fault cur- rent (neutral compensated ): 707A • Maximum value of time constant t of the residual unidirectional component decay: 150 ms • Zero sequence Voltage in healthy network condition: (0-5)% of Ph-E Voltage • Harmonic content in current: within prescribed limits by EN50160 • Rated frequency 50 Hz or 60 Hz • Frequency range fn=50 Hz 47,5Hz÷51,5 Hz • Frequency range fn=60 Hz 57,5Hz÷61,5 Hz SME70 INDOOR FAMILY devices detect faults between phases and earth failures both on insulated neutral networks and on compensated neutral networks, without any need of changing the settings between different configurations and regardless of the feeding direction. The correct detection of the fault direction also occurs in the presence of intermittent faults. SME70 INDOOR FAMILY devices check the voltage of the three phases of the MT line and indicates whether it is ON or OFF; a current converter is also available with an impressed current output of 4...20 mA for sending the phase current measurement to the remote control terminal. — Protective functions The following protective functions are provided: • 27V1 Direct sequence undervoltage (27Vd) • 51 Phase overcurrent • 51N Residual overcurrent • 59V2 Inverse sequence overvoltage (59Vi) • 67N Directional ground fault overcurrent • 59 Voltage presence • 59N Residual overvoltage (59V0)

SME70, SME70-C, SME70-M-Manual-04-2020

M A I N F E A T U R E S SME70 INDOOR FAMILY panel The panel is suitable for projecting assembly. The front includes signalling LEDs, the RS232 commu- nication port is accessible by opening the front cover. Phase Current Sensors Only SME70-C, SME70-M devices use the signal provided by Rogowski sensors: • Two current sensors for measuring two-phase current and one current sensor for measuring re- sidual current or alternately • 3 Current sensors for measuring three-phase current, the residual current is derived through vec- torial sum from three-phase currents Voltage signals The voltage signals are derived from capacitors already arranged on MV panels using the plug of the fixed part of the voltage presence/absence device ENEL standard DY 1811. Residual voltage The residual voltage is computed through vector sum of phase voltages. Sensors connections The sensors must be connected to the MA connectors located inside the SME70 panel. Remote control unit Remote control unit connections are implemented according with ENEL specification; they are abut- ted to the terminal board MB at the factory according to the connection diagram inside the device cover. RS232 communication The device provides a serial interface to allow a PC connection for installation, configuration, moni- toring, firmware upgrade and diagnostic. X21 and X22 jumpers realise, according to Cyber Security requiremments, the RS232 access protec- tion against unwanted third parties manipulation. X21 X22 Action CLOSE CLOSE RS232 Read/Write ENABLE OPEN OPEN RS232 Read/Write DISABLE Binary input In Standard mode, the reversal of the direction of directional earth fault (67N) can be enabled; in voltage monitoring mode the binary input may be used as trigger to acquire the state of the line voltages. F U N C T I O N C H A R A C T E R I S T I C S SME70 INDOOR FAMILY devices perform its fault detection functions based on measure of line cur- rents and phase voltages. Earth single-phase fault directional detection function (67N) SME70-C, SME70-M ONLY The function detects the occurrence of earth faults both on insulated neutral networks and on com- pensated neutral networks, without any need of changing settings when changing type of network. The algorithm is based on the numerical analysis of signals (FFT) through fast sampling (64 samples per period) and phase locking algorithm (PLL); in this way the quantities are correctly measured in Through external signal from the remote control system, it is possible to control the reversal of the reference direction in case of line feeding from the opposed side (secondary station bar tripping directionality); the reversal signal is provided by the remote control system through the closing of a contact connected to terminals 8 and 9 of the MB terminal board. The fault signal (TS67AV) is provided to the remote control unit by the closing of a contact connected to terminal 5 of the MB terminal board. The sensitivity of the earth directional function depends on the extension of the line and on the neu- tral status (insulated or with Petersen coil). The setting is based on the adjusting of a V0> residual voltage[1] threshold and a I0 zero sequence current[2]. The protective element detects the directional earth fault if all the following conditions occur: • Residual voltage exceeds the V0> threshold, • Residual current exceeds the I0> threshold, • Residual current - residual voltage displacement inside the trip sector (I0 lags behind to V0 with reversed direction disabled), • All the above conditions were met for almost 80 ms. Note 1 The residual voltage V0 is the vector sum of the three phase voltages divided by three. Note 2 The residual current I0 is the vector sum of the three phase currents.

SME70, SME70-C, SME70-M-Manual-04-2020

Double earth single-phase or phase-phase (short circuit) fault detection function (51) SME70-C, SME70-M ONLY • The phase currents are measured and fault indication is provided when current in at least one phase exceeds the set threshold a: • 100...900 A for multi-phase faults (51) • 50...200 A for double earth-phase faults (51N). The fault signal (TS51A) is provided to the remote control unit by the closing of a contact connected to terminal 2 of the MB terminal board. Residual voltage detection function (59V0) FULL SME70 INDOOR FAMILY The residual voltage is calculate from the three phases voltages; when the voltage value overcomes the threshold the TS67AV information is provided to the remote control unit by the closing a contact connected to terminal 5 of the MB terminal board. Negative sequence overvoltage (59Vi) FULL SME70 INDOOR FAMILY The negative sequence voltage is calculate from the three phases voltages; when the voltage value overcomes the threshold the TS67AV information is provided to the remote control unit by the closing a contact connected to terminal 5 of the MB terminal board. Positive sequence overvoltage (59Vd) FULL SME70 INDOOR FAMILY The positive sequence voltage is calculate from the three phases voltages; when the voltage value overcomes the threshold the TS67AV information is provided to the remote control unit by the closing a contact connected to terminal 5 of the MB terminal board. Endesa Functionality SME70-C, SME70-M ONLY SME70 permit, setting in \Set\Base\Mode the endesa mode. to enable Endesa functionality. In this mode: • The command of the 51 relay is issued only when, after tripping of thresholds 51,51N or 67NS2, the condition of “Voltage Absent” is detected within a certain time (T1, programmable in \Set\Endesa, default setting: 0,5 s) • The command of 67 relay is issued only when, after triping of thresholds 67NS1. the condition of “Voltage Absent” is detected within a certain time (T1, programmable in \Set\Endesa, default set- ting: 0,5 s) • The return to quiescent mode of 51 and 67 relays occour when “Voltage Presence” condition is detected and hold to a certain time (T2, programmable in \Set\Endesa, default setting: 10s) • If there is no return of power within a certain time (T23 programmable in \Set\Endesa, default set- ting: 4 hours), outputs contacts 51 and 67 return to quiescent status anyway. According to this description of the Endesa Functionality, LED 51 and 67 must follow the state of re- spective relay and event logging also records the issuance of command to relay 51 and 67, in addition to tripping of various thresholds. Voltage presence FULL SME70 INDOOR FAMILY The three phases voltages are measured; when at least one voltage value is higher than 80% of the rated voltage the information (TSV) is provided to the remote control unit by the closing of a contact connected to terminal 3 of the MB terminal board. Current converter SME70-C, SME70-M ONLY The SME70 device is provided with an impressed current analogue output for sending the phase cur- rent measure to the remote control unit. Signal 4...20 mA is available for transfer to the remote control unit on terminals 4 (M1 connected to the positive auxiliary power) and 7 (M2 of terminal board MB). The rated primary current is adjustable inside the 100...1000 A range with 100 A step. Output relay commissioning • TS51A relay: phase fault (double single-phase earth fault), • TS67AV relay: directional earth fault - line side (with inversion command disabled), • TSV relay: voltage presence indication. The TS51A and TS 67AV output relays trip with faults that cause the circuit breaker open as for transient faults. The relays can be programmed with normally energized or de-energized mode (logic ENERGIZED / DE-ENERGIZED). The state of the relay is maintained for the duration of the fault and for a minimum of 150 ms. LED indicators management SME70 INDOOR FAMILY devices are provided with 8 indicator LEDs: • 3 green LEDs indicating that V4, V8, V12 phase voltages are ON, • 1 white LED indicating the direction reversal for the directional earth protection, • 1 orange LED indicating the multiphase, residual current or double single-phase function trip

SME70, SME70-C, SME70-M-Manual-04-2020

T E C H N I C A L D A T A GENERAL — Measuring relays and protection equipment Reference standards IEC 60255-1, GSTP001 rev.01 — Mechanical data • Phase current/voltage sensor GSTP001 • SME70 device mounting Projecting Reference standards EN 60529, EN 60529/A1 Protection degree IP31 Mass: • Phase current about 0.3 kg • SME70 device (with remote control cable) 1.2 kg — Insulation test Reference standards EN 60255-5, IEC 60255-27 High voltage test (50 Hz 60 s) • Auxiliary power supply 2 kV • Input circuits 2 kV • Output circuits 2 kV • Output circuits (between open contacts) 1 kV Impulse voltage withstand test (1.2/50 µs): • Auxiliary power supply 5 kV (common mode)-2 kV (differential mode) • Input circuits 5 kV (common mode)-2 kV (differential mode) • Output circuits 5 kV (common mode)-2 kV (differential mode) Insulation resistance >100 MW — EMC tests for interference immunity Reference standards IEC 60255-26, EN 60255-26 Electromagnetic compatibility requirements for measuring relays and protection equipment Electromagnetic compatibility (EMC) - Generic standards EN 61000-6-2 Apparati di automazione e controllo per centrali e stazioni elettriche (ENEL utility standard) • Compatibilità elettromagnetica - Immunità ENEL REMC 02 • Normativa di compatibilità elettromeccanica per apparati e sistemi ENEL REMC 01 Reference standards EN 60255-22-1 IEC 60255-22-1 EN 61000-4-12 EN 61000-4-12 EN61000-4-18 Damped oscillatory wave • 0.1 MHz and 1 MHz common mode 1.0 kV • 0.1 MHz and 1 MHz differential mode 0.5 kV • Ring wave common mode 2.0 kV • Ring wave differential mode 1.0 kV Reference standards EN 60255-22-2 IEC 60255-22-2 EN 61000-4-2 IEC 61000-4-2 Electrostatic discharge • Contact discharge 6 kV • Air discharge 8 kV Reference standards EN 60255-22-3 IEC 60255-22-3 EN 61000-4-3 IEC 61000-4-3 Radiated radio-frequency fields • 80...3000 MHz AM 80% 10 V/m • 900, 1890 MHz Pulse modulated 10 V/m Reference standards EN 60255-22-4 IEC 60255-22-4 EN 61000-4-4 IEC 61000-4-4 (51/51N), • 1 red LED indicating the earth fault function trip downstream of the device (67), • 1 red LED indicating the device fail status, • 1 green LED indicating auxiliary power (fix ON). The fault indicator LEDs light up when a fault occurs (circuit breaker open), and they remain lit (latched) until the phase voltages return (circuit breaker closed); latch may be extended for a pro- grammable time (0 ... 238 hours) counted from the closing of the circuit breaker. The Trip Led Reset Delay may be adjusted inside the Set \ Base menu. The V4, V8, V12 LEDs, light up if the voltage of the relative phase is greater than 0.8 Vn and go OFF when the voltage is less than 0.2 Vn; in Voltage monitoring mode voltage presence is indicated by a flashing / LED relative to the corresponding phase.

SME70, SME70-C, SME70-M-Manual-04-2020

Fast transient burst (5/50 ns) • Auxiliary power supply 4 kV • Input circuits 4 kV Reference standards EN 60255-22-5 IEC 60255-22-5 EN 61000-4-5 IEC 61000-4-5 High energy pulse • Uaux (line-to-ground 10 ohm, 9 mF) 2 kV • Uaux (line-to-line 0 ohm, 18 mF) 1 kV • I/O ports (line-to-ground 40 ohm, 0.5 mF) 2 kV • I/O ports (line-to-line 40 ohm, 0.5 mF) 1 kV Reference standards EN 60255-22-6 IEC 60255-22-6 EN 61000-4-6 IEC 61000-4-6 Conducted radio-frequency fields • 0.15...80 MHz AM 80% 1kHz 10 V Reference standards EN 60255-22-7 IEC 60255-22-7 EN 61000-4-16 IEC 61000-4-16 Power frequency • DC voltage 30 V • 50 Hz continuously 30 V • DC voltage 1 s 300 V • 50 Hz 1 s 300 V • 0.015...150 kHz 10-1-1-10 V Reference standards EN 61000-4-8 IEC 61000-4-8 Magnetic field 50 Hz • 50 Hz continuously 100 A/m • 50 Hz 1 s 1 kA/m Reference standards EN 61000-4-10 IEC 61000-4-10 Damped oscillatory magnetic field • Damped oscillatory wave 0.1 MHz 30 A/m • Damped oscillatory wave 1 MHz 30 A/m — Mechanical tests Reference standards EN 60255-21-1 EN 60255-21-2 RMEC01 Vibration, shock, bump and seismic tests on measuring relays and protection equipment • EN 60255-21-1 Vibration tests (sinusoidal) Class 1 • EN 60068-2-64 Vibration tests broad band (random) Class 1 — IP protection grade tests Reference standards EN 60529 • IP grade (case) IP31 — Climatic tests Reference standards IEC 60068-x ENEL R CLI 01 CEI 50 Environmental testing Ambient temperature -25...+70 °C Storage temperature -40...+85 °C Relative humidity 10...95 % Atmospheric pressure 70...110 kPa — Safety Reference standards IEC 60255-27 Pollution degree 3 Reference voltage 250 V Overvoltage category III — Certifications Product standards EN 50263 CE Conformity • EMC Directive 2014/30/EC • Low Voltage Directive 2014/35/EC Type tests IEC 60255-1 — Cyber Security • Security Guideline GICT-SGL_12_v01_OCS OT

SME70, SME70-C, SME70-M-Manual-04-2020

INPUT CIRCUITS — Auxiliary power supply Uaux Rated voltage 24 V- Nominal value (range) 19.2...28.8 V- Max alternating component 10% Maximum time at power ON 0.10 s Power consumption at rest condition 2.5 W Max power consumption <3 W — Rated frequency fn Rated value 50, 60 Hz (sw setting) Range 47.5...51.5 Hz (fn = 50 Hz) 57.5...61.5 Hz (fn = 60 Hz) — Sensor inputs Current transformers Type Rogowski open core Coupling Bayonet Inside diameter 95 mm Rated transformation ratio 1000 A/0.100 V Bandwidth 40 Hz...20 kHz Connection to SME70 • type bipolar shielded wires • section 0.15 mm2 • length 3.5 m Voltage inputs Type Capacitive voltage dividers Plug DY811 MV rated voltage 6...36 kV Capacitive reactance (MTV side) 100...700 MΩ Connection to SME70 • type shielded wires • section 0.5 mm2 • length 3.0 m — Binary input Quantity 1 Type optocoupler Operative range rated Uaux Max consumption, energized 3 mA OUTPUT CIRCUITS — Relays Quantity 3 Type of contacts make (SPST-NO, type A) Nominal current 2 A Nominal voltage 250 V Breaking capacity (24 V, L/R = 40 ms) 0.2 A Minimum switching load 300 mW (5 V/5 mA) Each output relay is independently programmable as normally energized or de-energized (ENER- GIZED/DE-ENERGIZED) — Current converter Operating range 100...900 A (step 10 A) Output current 4...20 mA With 67N element active inside the no trip sector 0 mA Accuracy 10% Max load 750 Ω Maximum response time 300 ms CONNECTION TO THE REMOTE CONTROL UNIT Type 9 wires multipolar cable Section 1 mm2 Length 8 m

SME70, SME70-C, SME70-M-Manual-04-2020

LEDs — Signalling LEDs Voltage presence (V4) green LED Voltage presence (V8) green LED Voltage presence (V12) green LED 67N trip direction (INV 67) white LED Trip 51/51N (51A) orange LED Tripe 67N (67AV) red LED Device fail (FAIL) red LED Run (ON) green LED COMMUNICATION INTERFACE — Local port Connection 9 pin Rate 9600 Bps Parity None Protocol ModBus RTU® PROTECTION AND CONTROL FUNCTIONS — Positive sequence undervoltage - 27V1 (27Vd) U1< threshold 0.2...1.10 En (step 0.01 En) t1< operate time (inverse time characteristic) 0.0...60.0 s (step 0.1 s) Start time 0.045 s Operation The positive sequence voltage is compared with the threshold. If voltage under the pickup value is detected a start is issued and, after expiry of the associated operate time, a trip command (67N relay) is issued; if however the voltage increases beyond the threshold the element is restored. — Negative sequence overvoltage - 59V2 (59Vi) U2> threshold 0.01...0.40 En (step 0.01 En) t2> operate time (inverse time characteristic) 0.0...60.0 s (step 0.1 s) Start time 0.045 s Operation The positive sequence voltage is compared with the threshold. If voltage over the pickup value is detected a start is issued and, after expiry of the associated operate time, a trip command (67N relay) is issued; if however the voltage drop below the threshold the element is restored. U1 U1< t tU1< TRIP General operation time characteristic for the positive sequence undervoltage element - 27V1 U2 U2> t tU2> General operation time characteristic for the negative sequence overvoltage element - 59V2 TRIP

SME70, SME70-C, SME70-M-Manual-04-2020

— Residual overvoltage - 59VN (59V0) UE> threshold 0.01...0.40 En (step 0.01 En) tE> operate time 0.0...60.0 s (step 0.1 s) Start time 0.045 s Operation The residual voltage is compared with the threshold. If voltage over the pickup value is detected a start is issued and, after expiry of the associated operate time, a trip command (67N relay) is issued; if however the voltage drop below the threshold the element is restored. — Voltage presence Two thresholds are provided: • 80% of rated voltage for trip (4% accuracy), • 20% of rated voltage for reset (4% accuracy). The transition between the states of presence / absence voltage is described: • Starting from the no voltage condition (Voltage Presence OFF), the logic state of supply voltage is detected when, for at least 250 ms the following condition is true: (V4>80%Vn) OR (V8>80%Vn) OR (V12>80%Vn) • Starting from the condition of Voltage Presence ON, the logic state is no longer recognized if the following condition is true: (V4<20%Vn) AND (V8<20%Vn) AND (V12<20%Vn) without intentional delay. U> threshold 0.80 En Voltage absence threshold 0.20 En Operate time 0.25 s Operation The voltage presence is indicated by through the TSV relay and the corresponding LED (V4, V8, V12) t-int-F59N.ai UE tUE> UE> t TRIP General operation time characteristic for the residual overvoltage element - 59V0 0.2 Un 0.8 Un Voltage presence (59) Voltage presence (59) LED V4 V4, V8, V12 V8 V12 t V4 0.25s LED V8 LED V12

SME70, SME70-C, SME70-M-Manual-04-2020

— Overcurrent - 51 I> threshold (1) 100...900 A (step 10 A) t> otime delay 0.000....1.000 s (step 0.005 s) Start time 0.045 s Dropout ratio > 0.95 Reset delay 0.02 s Duration of the fault not detected 0.04 s Duration of the fault detected 0.08 s Threshold accuracy ±10% Operate time accuracy ± 10 ms Operation Each phase fundamental frequency current is compared with the setting threshold. Currents above the pickup value are detected and a start is issued. After expiry of the associated operate time a trip command is issued (51 relay); if instead the current drops below the threshold, the element it is restored. — Residual overcurrent - 51N IE> threshold (1) 10...200 A (step 2 A) tE> time delay 0.000....1.000 s (step 0.005 s) Start time 0.045 s Dropout ratio > 0.95 Reset delay 0.02 s Duration of the fault not detected 0.04 s Duration of the fault detected 0.08 s Threshold accuracy ±10% Operate time accuracy ± 10 ms Operation The residual current is compared with the setting threshold. Currents above the pickup value are detected and a start is issued. After expiry of the associated operate time a trip command is issued (51 relay); if instead the current drops below the threshold, the element it is restored. I I> t TRIP 0.045 General operation time characteristic for the phase overcurrent element - 51 t-int-F51N.ai IE 0.045 (s) IE> t General operation time characteristic for the residual overcurrent element - 51N TRIP

SME70, SME70-C, SME70-M-Manual-04-2020

— Directional earth fault - 67N SME70 permit, using a software flag, to choose instead of the zero sequence Voltage Vo,the negative sequence Voltage Vi as reference for intervention sectors. 67NS1 threshold Io threshold [1] 1.0...20.0 A (step 0.5 A) Vo,Vi threshold 0.01...0.32 Vn (step 0.01 Vn) tED> time delay 0.000....1.000 s (step 0.005 s) Trip sector (Inversion OFF) 60...255° Trip sector (Inversion ON) 240...75° 67NS2 threshold Io threshold 1.0...20.0 A (step 0.5 A) Vo,Vi threshold 0.01...0.32 Vn (step 0.01 Vn) tED>> time delay 0.000....1.000 s (step 0.005 s) Trip sector (Inversion OFF) 60...120° Trip sector (Inversion ON) 240...300° Start time ≤ 0.04 s Reset ratio 0.95...0.98 Reset time ≤ 0.1 s Accuracy (residual voltage) ±1% Accuracy (residual current) ±15% Angular sectors accuracy (UE = 1...120%; IE =1...150 A) ±2° (I0=1...150 A - V0=1...120% En) Hysteresis on output by sector ≤ 3° Operate time accuracy ±3% ± 20 ms Operating characteristic voltage-residual current for directional earth fault element (67N) Operating characteristic time to voltage-residual current for directional earth fault element (67N) Fig.1 67NS1 (INV=OFF) 67NS2 (INV=OFF) I0> I0>, V0>,Vi> TRIP TRIP I0 V0 V0>,Vi> I0,V0,Vi t 120° 60° V0,Vi & I0 255° 60° V0,Vi V0,Vi & I0 Fig.2 67NS1 (INV=ON) 67NS2 (INV=ON) 300° 240 V0,Vi & I0 240° 75° V0,Vi & I0 TRIP TRIP TRIP TRIP NO TRIP NO TRIP NO TRIP NO TRIP tED>, tED>> V0,Vi V0,Vi V0,Vi

SME70, SME70-C, SME70-M-Manual-04-2020

• V0Operation The start of any 67N element becomes active when the following conditions are contemporaneously active: • The residual current fundamental component (I0) overcomes the threshold • The residual voltage fundamental component (V0) or the negative sequence voltage (Vi ) over- comes the threshold • The residual current phasor (I0) is located inside the trip angular sector. Each directional earth fault overcurrent elements can be enabled or disabled by setting ON or OFF the 67NS1 Enable, 67NS2 Enable parameters inside the Set \ 67 menu. The setting in which both thresholds are disabled is indicated by a flashing LED 67N. Depending on the type of fault the relays 51 and 67N and the LED 67N are driven. • The trip of the 67NS1 threshold (60 ... 255°), with the 67NS2 threshold disabled, drives the relay 67N and 67N LED • The trip of the 67NS2 threshold (60 ... 120°), with the 67NS1 threshold disabled, drives the 51 and 67N relays and 67N LED • A fault inside the 120...255° sector with the 67NS1 and 67NS2 threshold enabled, drives the 67N relay and 67N LED • A fault inside the 60...120° sector with the 67NS1 and 67NS2 threshold enabled, drives the 51 and 67N relays and 67N LED Operate times: • Duration of the fault not detected 0.04 s • Duration of the fault detected (voltage present) 0.08 s • Duration of the fault detected (voltage not present) 0.15 s • Max operate time (voltage present) 0.15 s • Max operate time (voltage not present) 0.17 s 67NS1 threshold ENABLED 67NS2 threshold DISABLED Relay 67N ON Relay 51 OFF LED 67N ON 255° 60° V0,Vi 120° 60° NO TRIP NO TRIP TRIP TRIP 67NS1 threshold DISABLED 67NS2 threshold ENABLED Relay 67N ON Relay 51 ON LED 67N ON 255° 60° 120° 60° NO TRIP NO TRIP TRIP TRIP 67NS1 threshold ENABLED 67NS2 threshold ENABLED Relay 67N ON Relay 51 OFF with fault inside the 120...255° sector Relay 51 ON with fault inside the 60...120° sector LED 67N ON 255° 60° 120° 60° NO TRIP NO TRIP TRIP TRIP V0,Vi V0,Vi V0,Vi V0,Vi V0,Vi 67N logic Circuit breaker closing on fault with voltage ON before fault 67N logic Circuit breaker closing on fault with voltage OFF before fault 40 ms Fault TRIP 67N V4,V8,V12 Circuit breaker CLOSED CLOSED Voltage presence ON Voltage ON Voltage OFF OPEN OPEN ≥80 ms ≤ 150 ms 40 ms ≥150 ms ≤ 170 ms

SME70, SME70-C, SME70-M-Manual-04-2020

By means a SW flag, the negative sequence voltage can be select as reference vector for the direc- tional earth fault element. The start of any 67N element becomes active when the following conditions are contemporaneously active: • The residual current fundamental component (I0) overcomes the threshold (1...200 A primary val- ues) with a step of 0,5 A (±15% accuracy on the set value) • The negative sequence voltage fundamental component (Vi) overcomes the threshold 1...40%, with a step of 1% (±15% accuracy on the set value) • The residual current phasor (I0) is located inside the trip angular sector. — Voltage monitoring Operation logic By sw setting the operation mode can be switched from standard to voltage monitoring. In voltage monitoring mode all the protective functions are disabled and the operation of binary inputs and logic outputs is modified as specified below. Following an external trigger command, connected to the input used in standard mode to reverse the directional earth function 67N (UD), the SME70 device verifies the voltage presence. With UD input ON, the SME70 device checks for voltage presence; if the voltage presence is ON, the relay contact “TSV” is operated in a pulse mode (pulse duration time adjustable from 0 ms to 5000 ms at 10 step). The “TSV” contact is normally open when the voltage is OFF. The operating logic (“voltage presence” of the OR type for the three phases, “voltage absence” of the AND type for the three phases), is described in the “Voltage presence” paragraph. Along with TSV control relay and in the same operating mode (impulsive) the relay 51 is also driven. The 67N relay, used in standard configuration to signal trip of the 67N protection, unlike the 51 and 59 relays, keeps the bistable operation mode (output contact open when voltage is OFF, closed when voltage is ON). In the absence of the trigger signal (low signal on UD input) the relay 59 “TSV” is driven to open instantaneously. Only the voltage measure is always active, even when the binary signal is OFF, only the signaling functions are blocked. Operate times: • 51 and 59 output time 0...5000 ms (step 10 ms) • 51 e 59 pulse 0...5000 ms (step 10 ms) Vi I0 Vi> & I0> TRIP NO TRIP Operating mode MV Voltage At least one voltage ≥ 80% Un STANDARD VOLTAGE MONITORING STANDARD INV (UD) Relay 51 (pulse) Relay 59 (pulse) Relay 67N (bistable) delay pulse delay pulse

SME70, SME70-C, SME70-M-Manual-04-2020

— Optional timers signalling Operation logic Some timers are provided; when enabled through sw flag the timing concerning the output relays is modified: • The command of relay 51 is issued only when, after tripping of the 51, 51N or 67NS2 element, the condition of “Voltage Absent” is detected within a T1 adjustable time (default setting: 0.5 s). • The command of relay 67 is issued only when, after tripping of the 67NS1 or 67NS2 element, the condition of “Voltage Absence” is detected within a T1 adjustable time (default setting: 0.5 s). • The return to quiescent status of relays 51 and 67 occur when “Voltage Presence” condition is detected and the condition holds for a T2 adjustable time (default setting: 10 s). • If there is no return of power within a T3 adjustable time (default setting: 4 hours), output contacts 51 and 67 return to quiescent status anyway. According to the previous points: • LEDs 51 and 67 follow the state of the 51 and 67 relay. • Event logging also records the commands to relays 51 and 67, in addition to tripping of various elements. RECORDINGS — Faults recording The recordings are activated (trigger)[1] by a trip of a protective function. The last 20 faults are stored in a FIFO memory circular buffer (First In, First Out).[2] The following data are automatically recorded (Read \ Faults \ Info menu): • Faults stored[3] • Last fault For every record the following data are recorded (Read \ Faults \ Fault menu): • Fault number (F-Number) • Fault cause (F-Cause) • Faulted phase (F-Phases) • Current phase 4 (F-I4) • Current phase 8 (F-I8) • Current phase 12 (F-I12) • Residual current (F-I0) • Phase voltage V4 (F-V4) • Phase voltage V8 (F-V8) • Phase voltage V12 (F-V12,) • Residual voltage V0 (F-V0) • I0-V0 displacement (F-Theta) • Residual voltage V0 (F-Vo Sequence) • Positive sequence voltage Vd (F-Vd Sequence) • Negative sequence voltage Vi (F-Vi Sequence) • Data and time (F-Year) • Data and time (F-Month) • ... • Data and time (F-Millisecond) The fault memory can be erased by means of the command inside the Read \ Faults \ Reset menu. — Events recording The recordings are activated (trigger) by a trip of a protective function. The last 20 events are stored in a FIFO memory circular buffer (First In, First Out).[4] The following data are automatically recorded (Read \ Events \ Info menu): • Events stored[5] • Last Event For every record the following data are recorded (Read \ Events \ Event menu): • Event cause (E-Cause) • Data and time (E-Year) • Data and time (E-Month) • ... • Data and time (E-Millisecond) The event memory can be erased by means of the command inside the Read \ Events \ Reset Note 1 Data are stored in non volatile memory; they are held in spite of power down Note 2 Data concerning the most recent fault is stored in the record indicated by the Last fault parameter (1...50) Note 3 The counter is increased on each next fault; it can be reset by ThySetter command Note 4 Data concerning the most recent event is stored in the record indicated by the Last event parameter (1...200) Note 5 The counter is increased on each next event; it can be reset by ThySetter command

SME70, SME70-C, SME70-M-Manual-04-2020

I N S T A L L A T I O N RESIDUAL CURRENT SENSOR The residual current sensort must be crossed in the same direction by all active conductors and hence, also by the neutral conductor if distributed, with the exception of the ground connection protective conductor. The drawing below shows cases of assembly of the residual current sensor on unscreened and screened cables; prior to proceeding with assembly, it is necessary to check that there are no screen-to-ground connections upstream of the sensor. In order to ensure a linear response from the sensor, the cables must be positioned in the centre of it so that the magnetic effect of the three cables is perfectly compensated in the absence of residual current (Fig.2a). Hence, the assembly indicated in the following drowing, in which phase L3 causes local magnetic saturation whereby the vectorial sum of the three currents would be non-null, should be avoided. The same considerations also apply when the sensor is positioned near bends in the cabling. It is recommended that the transformer be placed away from bends in the conductors). Armoring Load Load Source Source Insulated cables Shielded cables Armoring L1 L3 L2 L1 L3 L2

SME70, SME70-C, SME70-M-Manual-04-2020

SME70-M equipment composition: - n.1 SME70 - n.1 UP connection cable - n.1 Capacitive divider connection cable - n.2 Phase currenr sensors - n.1 Residual current sensor - n.1 Crossbar for capacitive insulators - n.3 Copper braids 50mm2 - n.3 Shielded interconnecting cables (capacitive insulators voltmetric socket) - n.1 Voltmetric socket - n.3 10pF capacitive voltage dividers - n.1 Mechanical support for RGDAT and voltmetric socket - n.4 Plastic straps - n.1 3m rilsan sheath - n.4 Screws - n.4 Shakery washers - n.4 Assembly nuts EARTH PHASE 4 8 12 82 Ø5.5 2 220 200 20 120 120 20 280 max 45 SME70-M SME70-M 300 300 49 50 250 50 250 50 49 740 4 65 30 80 400 225 300 748 Ø10 Ø10 N.6 HOLES Ø15 Copper braids Copper braids Copper braids Capacitive insulator Capacitive insulator Capacitive insulator

SME70, SME70-C, SME70-M-Manual-04-2020

C O M M I S S I O N I N G ATTENTION - CLOSE JUMPER X21 and JUMPER X22 For start up, apply the auxiliary power voltage fitting the connector in the remote control outlet. Upon start up, all of the eight leds are controlled to light up for a short time; afterwards, they turn off except for led ON and V4, V8, V12, if voltage on the corresponding phases is ON. The settings must be made by Personal Computer with sw Thyvisor THYVISOR The Thyvisor sw is a “browser” of data (setting, measure, etc..); it implements an engine that is afford to rebuild the menu set up and the relationships to data concerning all Thytronic protective relays by means of XML files. Following operations are performed by means Thyvisor: • Open-store of setting files; • Create network of relays • Configuration of communication based on protocol IEC 61850 • ASCII or Excel export reports; • Open/close communication; • Send settings, read settings; • Firmware upgrades; • Session level selection and log enabling (log files); After the device selection Thyvisor allows to: • Set the relay reference data; • Read info, measures, etc... ; • Store settings. — Thyvisor installation The latest release of ThySetter can be downloaded free of charge from the www.thytronic.it site (Products / Software / Thyvisor - DOWNLOAD AREA). Setup Once the release you want to install is available, just run both files (ie: ThyVisorSetup_V1.4.8.33.exe and ThytronicTemplates_V1211_IT_US.exe). If an older version is already present, a suitable message will ask user to remove the oldest before proceeding. This chapter is a short description of the main commands of Thyvisor software.

SME70, SME70-C, SME70-M-Manual-04-2020

Working with Thyvisor The below window is shown Two operating modes are available: • On line (with device connection), • Off line (building of setting file without connection to SME70 device). ON LINE Communication The following operation may be performed when the communication with device is active: • In standing connection mode an automatic communication session is activated; the configuration file stays open until the “Save” or “Close” commands are issued. • In Upload or Download data an automatic communication session is activated only for a short time required for send or receive data to/from device; at the end of the data transfer all the files are closed. Standing connection The communication must be open with the Auto open command in the Network tab. The Serial must be activated; the communication parameters can be set (using the button “Serial Port” in the tab “Network”) - baud rate, parity, number of data bits, number of stop bits, Modbus ad- dress, as well as various parameters of timers useful for serial communication. Moreover, inside the Auto Open upper panel, is possible to select (tick on the Reading settings) if the settings must be updated.[1] • With “Reading settings” selection the communication session starts and the reading progress is shown with a status bar; at last the device type is highlighted (left side on the bottom of desktop); by means of the Windows commands the menu may be resized as much you like.[2] • Without “Reading settings” selection the communication session starts without reading the set- tings; they are updated when the relative menus are accessed. This operating mode is very fastest and so it is advantageous when the settings updating is not needed. Note 1 To change the setting you need to work at session level 1; at level 0 (user) reading settings can not be disabled Note 2 The shown images explain some menu levels; all examples are indicatives and unrealistic.

SME70, SME70-C, SME70-M-Manual-04-2020

Once SME70 has been added to network, it will appear a windows that let to make modification of the main parameters, read measuremente from the device and select mode of the relay. The communication session may be closed by means the Stop command in the Network tab Send or Receive data The operating mode allows the automatic data transfer from and towards the linked device. The operations described below are enabled only when the communication is closed. Receive data The operating procedure is started with the Receive Data command in the IED tab. Send Data The operating procedure is started with the Send data command in the IED tab; at the end of the data transfer, the new setting data must be confirmed OFFLINE In off-line mode (without link to device), it is possible to modify settings through the generating one or more files containing the desired settings, which can then be transferred over the relay by means of the Send data command. The file may be constructed by creating it from scratch, by starting from a file already present on a Personal Computer, or from a file taken from a relay by means of the Receive data command which can be activated from the IED tab. The window for easy configuration can be accessed anytime clicking on the Protection command in the IED tab. THYVISOR SOFTWARE Some information are provided about the different tabs of the Thyvisor sw. — Home Inside of the tab Home is possible to find all commands related to customization of the user-expe- rience with Thyvisor. From the Home tab is also possible to switch to Session Level 1 (password “level1”) to enable some hidden function, such as “Set default PAR” and “Set default REE” — Network Inside the tab Network is possible to find all commands to add protections relay to the network, configure serial port, start and stop a network and configure functions of the relay clicking on the command Protections. Change session level Activation of optional functions Setting of serial port Add/Load offline device Auto add online device Save network

SME70, SME70-C, SME70-M-Manual-04-2020

Add Device Insert an offline relay to the network so that is possible to change it’s configuration for a later upload to the device. Auto open Providing the right configuration of the serial port, Thyvisor is able to auto-recognize the connected relay and add it to the network. Once SME70 has been added to the network, a window with main parameters is shown to the User. — Draw Inside this tab is possible to find instrument to personalize the graphical side of the network just created with Thyvisor. — IED In IED tab is possible to find command to send and to receive data to the protection relay, open Pro- tections window, syncronize clock and update firmware of the protection relay. Protection To manually open configuration window, in case of Off-line programmation, User can click on the “Pro- tection” command. From that window is possible to change all main parameters. They will be stored in memory of SME70 and then become operational only after that the “OK” button has been pressed. Manually open configuration window Send and receive data Update firmware

SME70, SME70-C, SME70-M-Manual-04-2020

FIRMWARE UPDATE The command allows upgrading of the firmware. The operating procedure is scheduled in the following steps: • Connect device to the personal computer by means of a RS232 cable • Start ThyVisor • Press “Auto Open” from Network tab, add SME70 and then from tab Network press the command Stop (or press F3) • From IED tab press the command Firmware Device, confirm the procedure. • Select the new firmware file (.s19) and enable the transfer by clicking the Start button. • Status bar progress is displayed by status bar. If power goes OFF within this stage the firmware is lost and the device must be returned to the factory for repair. If the data base on the updated version has not been changed all settings are preserved: vice versa if the new database is not compatible with the previous, the default settings must be send to device with the operations described in the next paragraph (Data base restoring). Data base restoring If the data base of the up-to-date release is not compatible with the former, the default data must be send to the device. Typically the data base must be restored after significant upgrades. Following operations must be performed: • Switch to Level 1 session (Level command from Home tab) • Send the following commands (Commands \ Option menu) right clicking and pressing “Execute” (be sure to Start network from Home tab or press F2) • Set default PAR • Set default REE WARNING The procedure should only be activated in case of real need in accordance with the instructions provided by Thytronic. Incorrect operation can cause serious damage to the operation of the device!

SME70, SME70-C, SME70-M-Manual-04-2020

CONNECTION DIAGRAM SME-70 MB terminal block TRIP capacitive divider normal direction of power MA terminal block SME70 0 8 7 1 2 3 4 6 5 Link to remote control unit [UP] + COM TS (+24 V) TS 51A TS PRES V M1 TS 67AV M2 UD K1 K2 K3 D/A COM UD -24 V 1 2 3 4 5 6 7 8 9 10 RS232 Ground Spacer

SME70, SME70-C, SME70-M-Manual-04-2020

MB terminal block I> current sensor I> current sensor IE> current sensor TRIP capacitive divider normal direction of power MA terminal block SME70-C SME70-M 0 8 7 1 2 3 S1 P1 4 6 5 Link to remote control unit [UP] + COM TS (+24 V) TS 51A TS PRES V M1 TS 67AV M2 UD K1 K2 K3 D/A COM UD -24 V 1 2 3 4 5 6 7 8 9 10 RS232 Ground Spacer CONNECTION DIAGRAM SME70-C, SME70-M

SME70, SME70-C, SME70-M-Manual-04-2020

EXTERNAL VIEW - SME70 INDOOR FAMILY 135 175 max40 RS232 ON FAIL 67AV 51A INV. 67 V12 V8 V4 To Remote control unit [UP] 165

SME70, SME70-C, SME70-M-Manual-04-2020

INTERNAL VIEW - SME70 INDOOR FAMILY 165 173 100 Ø5.5 150 POWER SUPPLY MA TERMINAL BOARD (SENSORS) MB TERMINAL BOARD (REMOTE CONTROL UNIT) RELAY RELAY RELAY RS232 PE X22 X21 CYBER SECURITY PRESET

SME70, SME70-C, SME70-M-Manual-04-2020

CURRENT SENSORS (SME70-C, SME70-M ONLY) Phase Current Residual Current Residual sensor 0 Connect to MA according to the terminal tag Phase sensors Connect to MA according to the terminal tag Connect to the ground spacer CAPACITIVE INSULATORS (SME70-M ONLY)

SME70, SME70-C, SME70-M-Manual-04-2020

VOLMETRIC SOCKET (SME70-M ONLY) CROSSBAR FOR CAPACITIVE INSULATORS (SME70-M ONLY)

SME70, SME70-C, SME70-M-Manual-04-2020

SHIELDED INTERCONNECTING CABLE (SME70-M ONLY) UP CONNECTION CABLE (FULL SME70 INDOOR FAMILY)