Text of Weil-McLain GOLD CGi-4E Manual
Part No. 550-110-711/1108
This manual must only be used by a qualified heating installer/service technician. Before installing, read all
instructions, including this manual, the burner manual and any related supplements. Perform steps in the order
given. Failure to comply could result in severe personal injury, death or substantial property damage.
• Installation
• Startup
Boiler Manual
• Maintenance
• Parts
Gas-Fired Water Boiler
DO NOT USE BOILER
Weil-McLain GOLD CGi-4E GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual
2
Part Number 550-110-711/1108
How it works . . .
①
Control module
The control module responds to signals from the room thermostat, air pressure switch and boiler limit circuit to operate
the boiler circulator, pilot burner, gas valve and inducer. When room thermostat calls for heat, the control module starts the
system circulator and inducer.
The control module runs the inducer long enough to purge th
Part Number 550-110-711/1108
3
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual
GOLD CGi-4E Gas-Fired Induced-Draft Water Boiler
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual 4
Part Number 550-110-711/1108
Contents
How it works.....................................................2–3
Hazard definitions................................................ 4
Please read before proceeding............................. 5
1
Prepare boiler location....................................6–11
2
Prepare boiler................................................12–13
3
Venting...........
Part Number 550-110-711/1108 5
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual
Please read before proceeding
Failure to adhere to the guidelines on this page can result in severe personal injury, death
or substantial property damage.
•
Continual fresh makeup water will reduce
boiler life. Mineral buildup in sections re-
duces heat transfer, overheats cast iron, and
causes section failure. Addition of oxygen
and other gases can cause internal corrosi
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual 6
Part Number 550-110-711/1108
Prepare boiler location — codes & checklist
1a
Installations must follow these codes:
•
Local, state, provincial, and national codes, laws, regulations and ordinances.
•
National Fuel Gas Code, ANSI Z223.1–latest edition.
•
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/
ASME CSD-1, when required.
•
National Electrical Code.
•
F
Part Number 550-110-711/1108 7
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual
Prepare boiler location — clearances
1b
Figure 1b
Required MINIMUM clearances
Figure 1a
Recommended
SERVICE clearances
(see WARNING
below)
Recommended SERVICE clearances
(Fig. 1a)
1. Provide clearances for cleaning and servicing the boiler and for
access to controls and components. See Figure 1a for recommen-
dations.
2. Provide at least screwdriver clearance to jacke
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual 8
Part Number 550-110-711/1108
Prepare boiler location — vent system
1c
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe
personal injury or death.
When removing boiler from an
existing common vent system:
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining con-
nected to the com
Part Number 550-110-711/1108 9
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual
Prepare boiler location — air contamination
Table 1 Corrosive or destructive contaminants and likely locations
1d
Please review the following information on potential
combustion air contamination problems.
Refer to Table 1 for products and areas which may cause
contaminated combustion air.
CONSTRUCTION DUST HAZARD — Airborne particulates, such as drywall dust or
fibe
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual 10
Part Number 550-110-711/1108
Figure 5
Air from outdoors — horizontal ducts
Figure 4
Air from outdoors — vertical ducts
Figure 2
Air openings to interior spaces
Figure 3
Air directly through outside wall
Air opening options
Two openings — Air supply from inside the building ✷
1. If the building is of unusually tight construction (see definition, next
page), the building must also be provided w
Part Number 550-110-711/1108 11
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual
Unusually tight construction
Unusually tight construction means (per ANSI Z223.1)
buildings in which:
a. Walls and ceilings exposed to the outside atmo-
sphere have a continuous water vapor retarder with
a rating of 1 perm or less with openings gasketed,
and . . .
b. Weather-stripping has been added on openable
windows and doors, and . . .
c. Caulking or sealants are app
GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual 12
Part Number 550-110-711/1108
Prepare boiler — placement & setup
2a
Table 2 Manifold orifice sizing at sea level and altitudes to 4,500 feet
Location
Natural gas
Propane gas
U. S.
0-2,000 ft
over 2,000 ft
0-2,000 ft
over 2,000 ft
2.55 mm
(Note 1)
1.60 mm
(Note 1)
Canada
0-2,000 ft
2,000-4,500
0-2,000 ft
2,000-4,500
2.55 mm
#41
1.60 mm
1.45 mm
Note 1: For elevations above 2,000 feet, contact your l
Weil-McLain Boiler Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated |
|---|---|---|---|---|---|---|
Evergreen EVG 220 |
Evergreen EVG 220 Manual - 24164Q |
136 | 1281 | 231 | 20-06-2026 | |
Gold GV 3 Series |
Gold GV 3 Series Manual - 7A988C |
95 | 820 | 132 | 11-07-2026 | |
HE (Series 2) |
Weil-McLain HE (Series 2) User Guide (Manual ), @WS9LOQ |
132 | 1129 | 170 | 19-04-2026 | |
WTGO |
WTGO Manual - 352BR9 |
44 | 3.36 Mb | 1047 | 231 | 09-08-2026 |
GV90+3 |
#Z2J35M: GV90+3 Boiler Brochure & specs |
4 | 0.77 Mb | 503 | 101 | 07-06-2026 |
SGO SERIES |
Boiler #SF9SZ2 |
12 | 559 | 140 | 05-08-2026 |