Thermon Terminator ZS Installation Procedures
Read Online
Read the Thermon Terminator ZS Installation Procedures online using the built-in PDF viewer.
Text of the manual
For In-Line Splice Connection and End Termination Applications
Terminator
TM ZS/ZE
In Line Splice/End Termination Kit
INSTALLATION PROCEDURES
Support Base with O-Ring
2
1
Splice Cap
3
1
Banding Guide
4
1
Banding
Terminator
TM ZS/ZE
INSTALLATION PROCEDURES
Kit Contents
Order Separately for End Termination
PETK Power and End Termination Kits (per cable)
PETK-1
for BSX, RSX, VSX, VSX-HT
PETK-2
for KSX, HTSX,
PETK-3
for FP, HPT
Item
Quantity
Description
1
1
RTV Tube
2
1
Power Connection Boot
3
1
End Cap
4
1
Tape Strip Teflon 6" (PETK-3 only)
5
1
End Termination Caution Label
6
1
GRW-G Grommet (PETK-3 only)
Order Separately for Inline Splice
SCTK Splice Connection Termination Kits (per cable)
SCTK-1
for BSX, RSX, VSX, VSX-HT
SCTK-2
for KSX, HTSX,
SCTK-3
for FP, HPT
Item
Quantity
Description
1
3
Splice Connection Boots
2
2
Small Crimps
3
1
Large Crimp
4
2
Small Crimp Insulators
5
2
Silicone Caps
6
3
Ground Sleeves
7
1
RTV Tube
Certifications/Approvals
1725 II 2 GD Ex eb IIC T6...T4, Ex tb IIIC T85°C...T135°C
FM 10ATEX0058X
IP66 -60°C ≤ Ta ≤ +55°C
Ordinary & Hazardous Locations
FMG 10.0022X Ex eb IIC T6...T4
Ex tb IIIC T85°C...T135°C
Warnings
• Due to the risk of electrical shock, arcing and fire caused
by product damage or improper usage, installation or
maintenance, a ground-fault protection device is required.
• Installation must comply with Thermon requirements and be
installed in accordance with the regulations as per the norm
EN IEC 60079-14 for hazardous areas (where applicable), or
any other applicable national and local codes.
• Component approvals and performance ratings are based on
the use of Thermon specified parts only.
• De-energize all power sources before opening enclosure.
• Avoid electrostatic charge. Clean only with a damp cloth.
• Keep ends of heating cable and kit components dry before
and during installation.
• Minimum bending radius of heating cable is 32 mm (except
HPT is 57 mm and FP is 19 mm).
• Individuals installing these products are responsible for
complying with all applicable safety and health guidelines.
Proper Personal Protective Equipment (PPE) should be
utilized during installation. Contact Thermon if you have any
additional questions.
Tcode Instructions
Temperature code is based on the rating of the electrical heat
tracing cables for which the connection kits are intended to
be used.
Dimensions
A
inch (mm)
B
inch (mm)
C
inch (mm)
D
inch (mm)
Terminator
ZS/ZE
3” (75 mm)
3” (75 mm)
3-1/2”
(90 mm)
7-3/4”
(200 mm)
D
B
C
A
Terminator has additional hazardous area approvals including:
• GGTN • Kazakhstan
The following installation procedures are guidelines for the
installation of the In Line Splice/End Termination Kit. For
translations other than English and local language translation
provided here, please contact Thermon. The English language
installation procedure shall govern.
1
2
4
3
2
4
3
5
1
6
2
4
3
5
6
1
7
1. Locate bus connection (HPT and FP only) and
cable as shown. Cut end of cable at angle to
aid in piercing grommet. Leave additional
cable for expansion loop. See page 4 for
multiple cable installation tips.
2. Insert cable into expediter. If mounted on
bottom or side of pipe, punch out weep hole.
Note: For HPT and FP cable, exchange
grommet in Terminator with GRW-G provided
in PETK-3.
3. Slide expediter toward pipe and route cable
through support base entry.
4. Insert banding guide into expediter and snap
into place..
5. Mount expediter to pipe using pipe band. Do
not band over cable.
6. Cut off end of cable. .
7. Terminate cable with appropriate PETK
termination kit. Refer to PETK installation
instructions.
8. Push excess cable back through expediter.
Tighten cap securely. Tape cable expansion
loop to pipe.
9. Connect bus wires using small crimps and
connect ground wires using large crimp. See
page 9 for wiring details. Trim excess wire if
necessary.
European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The Netherlands • Phone: +31 (0) 15-36 15 370
Corporate Headquarters:100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . . www.thermon.com
© Thermon, Inc. • Printed in U.S.A. • Information subject to change.
10. Snap on crimp insulators
11. Slide silicone caps over crimp insulators.
13. Completed splice kit. Make sure latch
mechanism is in the locked position.
14. To remove cap, lift latch mechanism and
unscrew cap.
12. Tighten cap securely.
In-Line Splice
Wiring Details
Form PN50816U-0718
Terminator
TM ZS/ZE
INSTALLATION PROCEDURES