Viessmann Vitosol-F Service Instructions Manual

Text of the manual

For applicability, see the last page

VITOSOL-F 5692 808 GB 3/2009 Please keep safe.

Please follow these safety instructions closely to prevent accidents and mate-

rial losses. Safety instructions explained ! Please note This symbol warns against the risk of material losses and envi- ronmental pollution. Note Details identified by the word "Note" con- tain additional information. Target group These instructions are exclusively designed for qualified personnel. ■Work on electrical equipment must only be carried out by a qualified elec- trician. ■The system must be commissioned by the system installer or a qualified per- son authorised by the installer. Regulations Observe the following when working on this system ■all legal instructions regarding the pre- vention of accidents, ■all legal instructions regarding envi- ronmental protection, ■the Code of Practice of relevant trade associations. ■all current safety regulations as defined by DIN, EN, DVGW, VDE and all locally applicable standards Working on the system ■Isolate the system from the power sup- ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolator. ■Safeguard the system against unau- thorised reconnection. ! Please note Electronic modules can be dam- aged by electrostatic dis- charges. Touch earthed objects, such as heating or water pipes, to dis- charge static loads. Repair work ! Please note Repairing components that fulfil a safety function can compromise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts. Safety instructions Safety instructions 5692 808 GB

Ancillary components, spare and

wearing parts ! Please note Spare and wearing parts that have not been tested together with the heating system can com- promise its function. Installing non-authorised components and non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only orig- inal spare parts supplied or approved by Viessmann. Safety instructions Safety instructions (cont.) 5692 808 GB

Commissioning, inspection, maintenance

Steps - commissioning, inspection and maintenance.......................................... 5 Further details regarding the individual steps....................................................... 6 Parts lists Parts list Vitosol 200-F, 300-F.............................................................................. 11 Specification Vitosol 200-F........................................................................................................ 13 Vitosol 300-F........................................................................................................ 13 Solar-Divicon (accessory).................................................................................... 13 Heat transfer medium (accessory)....................................................................... 13 Certificates Declaration of conformity...................................................................................... 15 Index Index 5692 808 GB

For further information regarding the individual steps, see the page indicated

Commissioning steps Inspection steps Maintenance steps Page • 1. Flushing, testing for leaks and filling the solar thermal system............................................................................. 6 • • • 2. Checking the function of the safety equipment • • • 3. Checking the expansion vessel and the system pressure........................................................................... 7 • • • 4. Checking the electrical connections............................ 7 • • 5. Starting the system........................................................ 7 • • 6. Venting the solar thermal system................................. 8 • • • 7. Checking the switching function of the solar control unit................................................................................... 9 • • • 8. Checking the flow rate • 9. Shutting down the system............................................. 9 • • 10. Checking gaskets and seals • • 11. Checking the frost protection temperature and the pH value of the heat transfer medium................................ 10 • • 12. Checking the thermal insulation of the pipes.............. 10 • • 13. Checking circulation pumps • 14. Cleaning collectors Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance 5692 808 GB

Flushing, testing for leaks and filling the solar thermal system

■Never drain the system with a vacuum pump. ■Check the system for leaks: The collector in its cold state must be subject to a positive pressure of at least 1.0 bar. At a static head of 10 m, this would result in a system pressure of 2.0 bar. 1. Leave collectors covered or cover if necessary. Open any installed shut-off gates or valves by hand. Open the non-return valves when using a Solar-Divicon: Flow/return: Turn the thermometer clockwise through 45°. 2. Close the shut-off valve of the fill valve and open the drain valve. 3. Flush the system via the return con- nections. Fill and flush the system with heat transfer medium via the fill valve. Flush using a high speed pump over an open container and continue until no air remains in the collector system. Correct commissioning can only be guaranteed with a system that is completely free of air. Now close the drain valves on the fill valve, open the shut-off valve and check the system for leaks. Observe the permissible operating pressure. Pressure must not drop for at least 30 minutes. Notes ■A heat transfer medium containing gly- col can deteriorate if it is exposed to temperatures above 170 °C for pro- longed periods (stagnation). Temperatures in excess of 200 °C result in a slow thermal breakdown of the 1,2-propylene glycol that can be recognised by a darkening of the heat transfer medium. Furthermore, it can result in the solar circuit suffering from sludge and hard deposits, particularly in conjunction with other contaminants (cinder, swarf) and air. ■Ensure that the system is correctly flushed, filled and ventilated after installation. ■After filling the system with the heat transfer medium, ensure that the sys- tem is fully vented and that heat is transferred inside the system. ■Blow-off and drain lines must termi- nate in an open container, that is capa- ble of collecting the full collector con- tent. Commissioning, inspection, maintenance Further details regarding the individual steps 5692 808 GB

Checking the expansion vessel and the system pressure

1. Drain the system. For this, close the cap valve on the expansion vessel (if installed) and reduce the pressure. 2. If the pre-charge pressure of the expansion vessel is lower than the set value, top up with nitrogen until the pre-charge pressure equals the set value. Static head (top edge of collector to expansion vessel): ........... m Set pre-charge pressure of the expansion vessel: 0.7 bar + 0.1 x static head in m 0.7 bar + 0.1 x ......... m = ........ bar 3. Top-up heat transfer medium until the system pressure is 0.3 to 0.5 bar higher than the set pre-charge pres- sure of the expansion vessel (create a safety water seal in the expansion vessel). The safety water seal should be 0.005 x liquid content of the complete system, but no less than 3 litres. Liquid content of the system = con- tent of pipes + content of collectors + content of the indirect coil of the DHW cylinder and safety water seal for the expansion vessel. Checking the electrical connections Check the tightness of the electrical plug-in connectors and cable grommets; check cables for damage. Starting the system Observe operating instructions of instal- led components. Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 5692 808 GB

Venting the solar thermal system

1. Open the air vent valve. Vent the circulation pumps. For this, adjust the circulation pumps to their maximum speed, switching the pump ON and OFF several times (a venti- lated pump runs almost silently) through a relay test (manual opera- tion). Repeat the ventilation process until the float in the flow meter of the Solar-Divicon holds a constant posi- tion when the pump is running (high- est pump rate). Note Air can be recognised in the flow rate indicator (float moves). 2. Set the required flow rate via the pump rate of the circulation pump (see following tables for approximate set values). Check the value underneath the float. 3. Repeat the venting process after the system has been operational for sev- eral days. Note If the system pressure drops, top-up the heat transfer medium in the cold state and vent again. 4. Always shut off the air vent valve after venting. Adjustable flow rates Vitosol 200-F, type 5DI Throughput 3 to 4 l/min Vitosol 200-F, 300-F The details in the following tables do not take the pipe pressure drop into account. Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 5692 808 GB

High-flow operation, 40 l/(h·m2)

Number of collectors Flow rate in l/min 2 3 3 4.5 4 6 5 7.5 6 9.5 7 10.5 8 12.5 9 14 10 15.5 11 17 12 18.5 13 20 14 21.5 15 23.5 Low-flow operation, 15 l/(h·m2) Number of collectors Flow rate in l/min 6 3.5 7 4 8 4.5 9 5 10 5.5 11 6.5 12 7 13 7.5 14 8 15 8.5 16 9 18 10.5 20 11.5 Checking the switching function of the solar control unit Solar control unit installation and service instructions Shutting down the system ! Please note To prevent equipment damage, cover the collectors before com- mencing any work on the compo- nents of the solar thermal sys- tem. Mixing the heat transfer medium with water reduces the frost and corrosion protection. Only flush the system with the specified heat transfer medium. Never mix "Tyfocor LS" with other heat transfer media. Electrically isolate the system (e.g. at a separate MCB/fuse or the main isolator) and safeguard against unauthorised reconnection. Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 5692 808 GB

Checking the frost protection temperature and the pH value of

the heat transfer medium Check the frost protection temperature of the "Tyfocor LS" heat transfer medium with a Viessmann antifreeze tester or the manual refractometer in the solar service case (accessory). Check the pH value using the pH strip in the solar service case (accessory). Solar service case operating instructions Checking the thermal insulation of the pipes Check the thermal insulation of the pipes for positioning and damage and adjust if required. Replace any damaged parts. Note The thermal insulation of external pipes must be resistant to temperature and UV rays. The insulation must be protected against attack from small animals and birds (e.g. metal sheath). Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 5692 808 GB

When ordering spare parts:

Quote the part and serial no. (see type plate) and the position no. of the required part (as per this parts list). Obtain standard parts from your local supplier. Parts 001 Connection pipe 002 Connection pipe (short) 003 Connection pipe (long) 004 Plug 005 Locking ring fitting with support sleeves 006 Elbow fitting with support sleeves 007 Clamping bracket, complete 008 Connecting part 009 Mounting bracket 010 Spacer plug 011 Retaining bracket 012 O-ring 013 Retaining screws 014 Profile clip 015 Diagonal sealing strip 016 Support sleeve 017 Resilient buffer 018 Mounting bracket Parts not shown 020 Special grease 021 Dismantling instructions 022 Operating instructions 023 Service instructions 025 Installation instructions for sloping roofs (pitched roofs), above roof installation with roof hooks 026 Installation instructions for sloping roofs (pitched roofs), roof integra- tion 027 Installation instructions for flat roofs or freestanding installation 028 Installation instructions for sloping roofs (pitched roofs), above roof installation with rafter anchors Parts lists Parts list Vitosol 200-F, 300-F 5692 808 GB

Parts list Vitosol 200-F, 300-F (cont.)

5692 808 GB

Thermal capacity c

kJ/(m2·K) 5.35 6.40 Max. idle temperature °C 202 185 Permiss. operating pressure bar 6 6 Content, heat transfer medium litres 1.83/2.48 4.2 Vitosol 300-F Type SV/SH Absorber area m2 2.32 Aperture area m2 2.33 Thermal capacity c kJ/(m2·K) 5.35 Max. idle temperature °C 212 Permiss. operating pressure bar 6 Content, heat transfer medium litres 1.83/2.48 Solar-Divicon (accessory) Safety valve 6 bar, 120 °C Max. operating tempera- ture 120°C Permiss. operating pres- sure 6 bar Heat transfer medium (accessory) The heat transfer medium provided is a liquid based on 1,2-propylene glycol with frost protection down to −28 °C. Monitor the operating condition of the medium as part of the annual service of the solar thermal system by the heating contractor. The solar service case (accessory) ena- bles, amongst others, the checking of the pH value and the frost protection tem- perature. In some cases the manufacturer of the heat transfer medium can carry out a laboratory test of the medium, subject to arrangement. Specification Vitosol 200-F 5692 808 GB

TYFOROP CHEMIE GmbH

Anton-Rée-Weg 7 D - 20537 Hamburg e-mail: [email protected] Internet: www.tyfo.de Specification Heat transfer medium (accessory) (cont.) 5692 808 GB

We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole respon-

sible body, that the products Vitosol 200-F and 300-F conform to the following standards: DIN 1055 EN 12975 to solar KEYMARK In accordance with the following directives, these products are designated _: 2006/95/EC 89/336/EEC 97/23/EC Details according to the Pressure Equipment Directive (97/23/EC): ■Heated pressure equipment ■Class I according to appendix II, diagram 5 ■Module A according to appendix III ■Identification of individual devices with a content of less than 2 litres as assembly according to article 3 (2), subject to the installation of at least one pair The pressure device was tested without fitted equipment (safety assembly). The pressure device must be equipped in accordance with current national regula- tions prior to installation and commissioning. The product characteristics determined as system values for the Vitosol prod- uct as part of EC type testing according to the Efficiency Directive (see speci- fication table) can be used for the energy assessment of heating and ventilation equipment to DIN V 4701-10. Allendorf, 1. March 2009 Viessmann Werke GmbH&Co KG pp. Manfred Sommer Certificates Declaration of conformity 5692 808 GB

Applicable to the following col-

lectors: Vitosol 200-F, type 5DI part no. 3004 363 Vitosol 200-F, type SV2 part no. 7248 237 Vitosol 200-F, type SH2 part no. 7248 238 Vitosol 200-F, type SV2A part no. 7374 162 Vitosol 200-F, type SH2A part no. 7374 161 Vitosol 200-F, type SV2B part no. 7417 763 Vitosol 200-F, type SH2B part no. 7417 764 Vitosol 300-F, type SV3 part no. 7248 611 Vitosol 300-F, type SH3 part no. 7248 612 Vitosol 300-F, type SV3A part no. 7374 164 Vitosol 300-F, type SH3A part no. 7374 163 Vitosol 300-F, type SV3B part no. 7417 765 Vitosol 300-F, type SH3B part no. 7417 766 Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: [email protected] Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com 5692 808 GB Subject to technical modifications. Printed on environmentally friendly, chlorine-free bleached paper