INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE
FOR THE UNITED KINGDOM AND EIRE
OPTIMAX HE 31 S
wall-mounted gas fired,
pre-mix
condensing system boiler
cod. 3540F441 - 04/2007 (Rev. 01)
G.C. No 41-267-26
OPTIMAX HE 31 S
2
Cod. 3540F441 - 03/2007 (Rev. 01)
• Read the warnings given in this manual thoroughly.
They provide important information for safe instal-
lation, use and maintenance
• By law the instruction manual must be left with the
end user.
• If the appliance is sold or transferred to another
owner or if the owner moves, leaving the appliance
behind, always ensure that the manual is kept with
the appliance for consultation by the new owner
and /or installer.
• Incorrect installation or poor maintenance absolves
the manufacturer from all liability for damage to
people or property.
• Installation and maintenance must be carried out
in conformity with current legislation, according
to the manufacturer’s instructions and by qualified
personnel.
• Before service or maintenance work is, carried out
isolate the appliance from the mains electricity
supply.
• In the event of malfunction or faulty operation, iso-
late the appliance. Do not attempt to repair or carry
out any other operation on the appliance directly.
Contact qualified personnel only.
• Repairs or the replacement of components must be
carried out exclusively by qualified personnel using
original spare parts only. Failure to respect the above
may compromise the safety of the appliance.
• To guarantee efficient operation, the appliance must
be serviced once a year by a corgi registered engi-
neer.
• The appliance may not be used for purposes other
than those for which it was explicitly designed. Any
other use is considered improper and therefore dan-
gerous.
• Incorrect installation and use or failure to follow the
instructions provided by the manufacturer absolve
the manufacturer from all liability for damage.
• After unpacking, check that the contents are complete
and undamaged.
• Keep the packaging out of reach of children as it is
potentially hazardous.
• To clean external parts, use a damp cloth moistened
with soapy water if necessary. Avoid using abrasive
cleaning products and solvents.
This symbol indicates “Caution” and is placed next to all safety information.
Strictly follow these instructions in order to avoid danger and damage to persons,
or property.
This symbols calls attention to a note or important information, please read thor-
oughly.
IMPORTANT
• Your "benchmark" Installation, Commissioning and Service Record Log Book is enclosed in the
last pages of this manual. “This record must be completed and left with the end user”.
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme.
Benchmark has been introduced to improve the standards of installation and commissioning of
central heating systems in the UK and to encourage the regular servicing of all central heating
systems to ensure safety and efficiency. Please see installation and servicing guidelines.
For EIRE ( Southern Ireland ) it is necessary to complete a “Declaration of Conformity “ to indicate
compliance to I.S. 813. An example of this is given in the current edition of I.S. 813. In addition
it is necessary to complete the “Benchmark” logbook
• "Ferroli declare that no substances harmful to health are contained in the appliance or used
during the appliance manufacture”.
OPTIMAX HE 31 S
3
Cod. 3540F441 - 03/2007 (Rev. 01)
1. OPERATING INSTRUCTIONS .................................................................4
1.1 Introduction ............................................................................................................4
1.2 Control panel ..........................................................................................................5
1.3 Turning ON and OFF ..............................................................................................6
1.4 Adjustments ............................................................................................................7
1.5 Maintenance ............................................................................................................8
1.6 Faults .......................................................................................................................8
2. INSTALLATION .......................................................................................9
2.1 General Instructions ................................................................................................9
2.2 Boiler location .......................................................................................................10
2.3 Boiler water connections ......................................................................................11
2.4 Connection to the gas system ..............................................................................13
2.5 Electrical Connections ..........................................................................................13
2.6 Flue system ...........................................................................................................16
2.7 Condensate outlet connection .............................................................................22
3. SERVICE AND MAINTENANCE ............................................................24
3.1 Adjustments ..........................................................................................................24
3.2 System start-up .....................................................................................................25
3.3 Maintenance ..........................................................................................................26
3.4 Troubleshooting ....................................................................................................28
4. TECHNICAL CHARACTERISTICS AND DATA ..........................................................30
4.1 Dimensions and connections ................................................................................30
4.2 General view and main components ....................................................................31
4.3 Hydraulic diagram .................................................................................................32
4.4 Technical data table ..............................................................................................33
4.5 Diagrams ...............................................................................................................34
4.6 Wiring diagram .....................................................................................................35
BENCHMARK ...........................................................................................37
OPTIMAX HE 31 S
4
Cod. 3540F441 - 03/2007 (Rev. 01)
1. OPERATING INSTRUCTIONS
1.1 Introduction
Dear Customer,
Thank you for choosing the OPTIMAX HE 31 S, a FERROLI wall-mounted boiler of the latest generation,
featuring advanced design and cutting-edge technology.
OPTIMAX HE 31 S is a high-efficiency condensing pre-mix appliance for heating with extremely low
emissions, running on natural gas or LPG.
The boiler consists of an aluminium laminar heat exchanger providing effective condensation of the
water vapour contained in the flue gases, permitting extremely high efficiency.
Above the heat exchanger, in the boiler, there is a pre-mix burner, with a large ceramic surface, equip-
ped with electronic ignition and ionization flame control, which achieves extremely low emissions while
ensuring high reliability and long life operation.
The boiler is totally room sealed from the installation room: the air needed for combustion is drawn
from outside. The boiler also includes a modulating speed fan, modulating gas valve, pump, expansion
vessel, safety valve, temperature sensors, a safety thermostat and a low water pressure sensor.
Thanks to the microprocessor control and adjustment system with advanced self-diagnosis, unit ope-
ration is for the most part automatic. The power for heating is automatically governed by the control
system.
The user only has to set the temperature desired inside the home by means of a room thermostat and
appliance temperature control. The adjustment and control system will provide optimum operation
throughout the year.
The display continuously provides information on the unit’s operating status and it is easily possible
to obtain additional information on the sensor temperatures, set-points, etc. or configure them. Any
operating problems associated with the boiler or system is immediately signalled by the display and, if
possible, corrected automatically.
OPTIMAX HE 31 S
5
Cod. 3540F441 - 03/2007 (Rev. 01)
1.2 Control panel
fig. 1
1 = Domestic Hot Water temperature setpoint decreasing push button (not used)
2 = Domestic Hot Water temperature setpoint increasing push button (not used)
3 = Central Heating water temperature setpoint decreasing push button
4 = Central Heating water temperature setpoint increasing push button
5 = Display LCD
6 = Reset
7 = On-Off push button
8 = Domestic Hot Water symbol
11 = Multi-function indication
12 = Degrees indication
13 = Central Heating mode operation
14 = Central Heating symbol
15 = Burner on and actual load indication
Indication during boiler operation
Demand mode
The Boiler heat demand (generated by the Programmer, room thermostat and cylinder thermostat) is
indicated by the flashing of the Hot Air symbol over the radiator (part. 13 and 14 – fig. 1). The display
indicates the actual System water temperature (part. 11 – fig. 1).
fig. 2
OPTIMAX HE 31 S
6
Cod. 3540F441 - 03/2007 (Rev. 01)
1.3 Turning ON and OFF
Without main power supply
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all
water from the system.
Ignition
Ensure the power is on to the appliance.
For the first 120 seconds, the display shows FH that identifies the Air purge function.
During the first 5 seconds, the display shows the software version of the pcb.
Open the gas cock on the boiler and purge the air from the pipework upstream of the gas valve.
When the FH disappears, the boiler is ready to function automatically whenever the external controls
are calling for heat.
Turning off
Press the
(part. 7 - fig. 1) for 5 seconds.
•
•
•
•
fig. 3 - Boiler without main power supply
fig. 4 - Ignition
fig. 6 - Turning off
fig. 5 - Air purge
OPTIMAX HE 31 S
7
Cod. 3540F441 - 03/2007 (Rev. 01)
When the boiler is turned off with this key, the p.c.b is still powered, heating operation is disabled and
the display is off however the frost protection will still be active.
To totally isolate close the gas cock ahead of the boiler and disconnect electrical power.
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all
water from the system.
To turn the boiler on again, press
(part.7 - fig.1) for 5 seconds.
If there is no heat demand, the display shows the actual water pressure (bar/10).
The boiler is ready to function automatically whenever the external controls are calling for heat.
fig. 7
1.4 Adjustments
Heating temperature setting
To set the system flow temperature, use the CH push buttons
(Part. 3 and 4 – fig. 1). It can be
varied from a minimum of 20°C to a maximum of 90°C.
Room temperature adjustment (using a room thermostat )
Using the room thermostat, set the temperature desired in the rooms. Controlled by the room ther-
mostat, the boiler lights and heats the system water to the system delivery setpoint temperature. The
burner shuts down when the desired temperature in the room is reached.
A room thermostat and programmer are a mandatory requirement (Building regulations Doc ‘L’
2002).
fig. 8
It is strongly recommended to carry out annual maintenance of the boiler and heating system. Please
refer to the “maintenance” section in this manual.
The casing, the control panel and the aesthetic parts of the boiler can be cleaned using a soft and damp
cloth, do not use abrasives or solvents.
1.6 Faults
In the unlikely event of an operating problem, or component failure, the display flashes and a fault
identification code appears.
OPTIMAX HE 31 S
8
Cod. 3540F441 - 03/2007 (Rev. 01)
The boiler is equipped with an advanced self-diagnosis system that signals any faults on the display.
Some faults (“A“ indication) cause a boiler shutdown. In this case, operation must be reset manually by
pressing the
(Part. 6 – fig. 1) for 1 second.
Other faults (“F“ indication) cause temporary shutdowns that are automatically reset as soon as the
value causing the fault comes back within the boiler’s normal working range.
Listed below are some anomalies that can be caused by simple, user-solvable problems.
If the problem remains after two attempts at resetting, contact the Ferroli Service Centre.
For other faults, refer to section 3.4 “Troubleshooting”.
Fault
Cure
No burner ignition
Make sure that the gas cocks ahead of the boiler
and on the meter are open.
Press the RESET button (for 1 second).
In case of repeated shutdowns, contact the Ferroli
Service Department.
Low system pressure
Fill the ‘system to 1-1.5 bar.
Before calling a Ferroli service engineer, check that the problem is not due to there being no
gas or electricity, or low system pressure.
OPTIMAX HE 31 S
9
Cod. 3540F441 - 03/2007 (Rev. 01)
2. INSTALLATION
2.1 General Instructions
This device must only be used for the purpose for which it is specially designed. This unit is
designed to heat water to a temperature below boiling point and must be connected to a heat-
ing system and/or a water supply system for domestic use, compatible with its performance,
characteristics and its heating capacity. Any other use is considered improper.
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE
WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT
LAW, THE RECOMENDATION OF BS STANDARDS, ANY LOCAL REGULATIONS AND THE RULES OF
COMPETENT WORKMANSHIP.
IN IE, THE INSTALLATION MUST BE CARRIED OUT BY A COMPETENT PERSON IN ACCORDANCE
WITH THE CURRENT EDITION OF I.S. 813 “DOMESTIC GAS INSTALLATIONS”, THE CURRENT BUILD-
ING REGULATIONS AND REFERENCE SHOULD BE MADE TO THE CURRENT ETCI RULES FOR ELEC-
TRICAL INSTALLATIONS.
Incorrect installation can cause damage or physical injury for which the manufacturer declines any re-
sponsibility.
This appliance must be installed strictly in accordance with these instructions and
regulations:
The Gas Safety Regulations (Installations & Use).
The Local Building Regulations.
The Building Regulations (Part L).
The Buildings Standards (Scotland - Consolidated) Regulations.
British Standards Codes of Practice:
B.S. 5440 Part 1
Flues
B.S. 5440 Part 2
Air supply
B.S. 5449 FORCED CIRCULATION HOT WATER SYSTEMS
B.S. 6798 INSTALLATION OF GAS FIRED HOT WATER BOILERS
B.S. 6891 GAS INSTALLATIONS
B.S. 7671 IEE WIRING REGULATIONS
B.S. 4814 SPECIFICATION FOR EXPANSION VESSELS
B.S. 5482 INSTALLATION OF LPG
B.S. 7593 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS
B.S. 5546 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
I.S. 813 DOMESTIC GAS INSTALLATIONS (EIRE ONLY)
Model Water Bye Laws
B.S. 5955-8 PLASTIC PIPEWORK INSTALLATION
For Northern Ireland the rules in force apply
OPTIMAX HE 31 S
10
Cod. 3540F441 - 03/2007 (Rev. 01)
fig. 9
2.2 Boiler location
The unit’s combustion chamber is sealed off
from the installation room and therefore requi-
res no compartment ventilation.
The installation room must be sufficiently well
ventilated to prevent any dangerous condi-
tions from forming in the event of even slight
gas leakage. This safety standard is required
by the EEC Directive no. 90/396 for all gas
units, including those with a so-called sealed
chamber.
Therefore the place of installation must be
free of dust, flammable materials or objects
or corrosive gases. The room must be dry and
not subject to freezing.
The boiler is designed to be installed on a solid
wall. The wall fixing must ensure a stable and
effective support for the appliance, using the
bracket and fixings supplied.
If the unit is enclosed in a cupboard or moun-
ted alongside, there must be space for normal
maintenance work. Fig. 9 and tab. 1 give the
minimum clearances to leave around the unit.
Safe Handling of Substances
Care should be taken when handling the boiler
insulation panels, which can cause irritation to the skin. No asbestos, mercury or CFCs are included in
any part of the boiler.
Product Handling Advice
When handling or lifting always use safe techniques - keep your back straight, bend your knees, don’t
twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body
as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the
centre of gravity, repositioning yourself as necessary.
OPTIMAX HE 31 S
11
Cod. 3540F441 - 03/2007 (Rev. 01)
fig. 10
2.3 Boiler water connections
The heating capacity of the unit should be previously established by calculating the building’s heat requi-
rement according to current regulations. For good operation and long life of the boiler, the plumbing
system must be well proportioned and always complete with all those accessories that guarantee regular
operation and running, room thermostat, trv’s etc. The flow and return must be a minimum diameter of
22mm for the first 3 metres from the appliance.
If the flow and return pipes follow a path where air pockets could form in certain places, it is essential
to install vent valves at these points. Also, install type “A” drain cock device at the lowest points in the
system to allow complete draining.
The temperature differential between the flow manifold and the return to the boiler should not exceed
20° C.
A minimum flow of 6 litres/min is required through the heat exchanger, calibrated on site. An automatic
by-pass is fitted to the boiler which will provide this flow rate
in most circumstances.
Do not use the water system pipes to earth electrical
appliances.
Before installation, carefully flush all the pipes of the heating
system to remove residues or impurities that could affect the
unit’s operation (BS 7593 Building regs Doc L).
Make the connections to the appliance as shown in fig. 10.
Key
1
System flow (22 mm with isolation valve fitted)
3
Gas inlet (22 mm with isolation valve fitted)
5
System return - 22 mm with isolation valve fitted (c/w filter)
6
Pressure Relief Valve
7
Condense outlet
It is essential to install the isolation valves supplied between the boiler and heating system, allowing the
boiler to be isolated from the system if necessary.
The safety valve outlet must be connected to a 15mm diameter copper pipe, with a continual
fall from the boiler to allow system water out onto the ground in the event of over-pressure in
the heating circuit. If this is not done, and the drain valve trips and floods the room, the boiler
manufacturer is not to be held responsible. The outlet should face back against the outer bri-
ckwork or building face to prevent harm or injury from hot water discharging in the event of an
over-pressurising system.
Make the boiler connection in such a way that its internal pipes are free of stress.
OPTIMAX HE 31 S
12
Cod. 3540F441 - 03/2007 (Rev. 01)
fig. 11
Fig. 12
3
2
1
4
!" #
!"#
$
$%
&
'
'()
*(++,-
.+/(
The isolation valve kit shown in Fig. 11 is supplied as standard.
Make Up Water
Provision must be made for replacing water lost from the sealed system. Reference should be made
to BS6798, for methods of filling and making up sealed systems. There must be no direct connection
between the boiler's central heating system and the mains water supply. The use of mains water to
charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such
connection must be disconnected after use. Ensure the filling point is on the return pipe to the boiler.
Attention - is drawn to the Model Water Byelaws.
Key
1. C.H. filling valve.
2. Temporary connection.
3. Cold water supply valve.
4. Double check valve.
OPTIMAX HE 31 S
13
Cod. 3540F441 - 03/2007 (Rev. 01)
2.5 Electrical Connections
The unit must be installed in conformity with current national and local regulations.
Connection to the electrical Supply
The boiler must be connected to a single-phase, 230 Volt-50 Hz electric supply.
The unit’s electrical safety is only guaranteed when correctly connected to an efficient earthing
system executed according to current safety standards. Have the efficiency and suitability of the
earthing system checked by professionally qualified personnel. The manufacturer is not responsible
for any damage caused by failure to earth the system. Also make sure that the electrical system
is adequate for the maximum power absorbed by the unit, as specified on the boiler dataplate,
in particular ensuring that the cross sectional area of the system’s cables is suitable for the power
absorbed by the unit.
The boiler is prewired and provided with a cable and fitted with a 3 amp plug for connection to the
electricity supply.
Water treatment
If treatment is used ferroli limited recommended only the use of Fernox or Sentinel water treatment
products, which must be used in accordance with the manufactures instructions. for further information
contact:
Fernox Manufacturing Co. LTD.
Sentinel Performance Solutions Ltd
Cookson Electronics, Forsyth Road
The Heath Business & Technical Park
Sheerwater, Woking, surrey, GU21 5RZ
Runcorn, Cheshire WA7 4QX
Tel: 0870 8700362
Tel: 0151 424 5351
Note - If the boiler is installed on an existing system any unsuitable additives must be removed by tho-
rough cleansing. All systems should be cleansed according to B.S. 7593.
Note - In hard water areas treatment to prevent lime scale may be necessary.
Note - It is important that the correct concentration of the water treatment product is maintained in
accordance with the manufacturers instructions.
2.4 Connection to the gas system
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to
establish the availability of an adequate supply of gas.
An existing service pipe must not be used without prior consultation with the local Gas supplier.
A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor.
Installation pipes should be fitted in accordance with BS6891.
Appliance inlet working pressure must be 20mbar MINIMUM, for NG and 37 mbar minimum for LPG.
Do not use pipes of a smaller size than the boiler inlet gas connection (22 mm).
The complete installation must be tested for gas soundness and purged as described in BS689.
All pipework must be adquately supported. An isolating gas valve is provided and should be
fitted on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking
gas rate. Gas pressures should be checked after the boiler has operated for 10 minutes to reach
thermal equilibrium. This appliance has no facility to check the burner pressure and the gas
valve is sealed and should not be adjusted. A combustion test can be carried out (see page 28
combustion analyser testing).
The isolation kit shown in Fig. 11 is supplied as standard.
OPTIMAX HE 31 S
14
Cod. 3540F441 - 03/2007 (Rev. 01)
fig. 13
The user must never change the unit’s power cable. If the cable gets damaged, switch off the unit
and have it changed only by professionally qualified personnel. If changing the electric power cable,
use only “HAR H05 VV-F” 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
Access to the electrical terminal block
Follow the instructions given in fig. 13 to access the electrical connection terminal block. The layout of
the terminals for the various connections is given in the wiring diagram in the Technical Data chapter.
Key
62
Time Clock (optional)
fig. 14
Room thermostat
Remove connections 5 - 6 if external control fitted.
If using external controls the switched line can be connected into terminal 5 of the electrical
block ( see fig 15 and 16 ).
Warning: the
room thermo-
stat works at
230V
OPTIMAX HE 31 S
15
Cod. 3540F441 - 03/2007 (Rev. 01)
Central heating Demand
The heat demand can be controlled by the room thermostat (terminal 5-6) or by a switch line 230 V
(terminal 5).
Standard Systems
For a general pipe layout and wiring diagram on the “S” and “Y” plan systems please see fig.
15a, 15b, and 16a, 16b.
OPTIMAX “S” Plan
Wiring diagram
,012345
$('',+2
.,2+('
)676-6
89
676
89
!
(
+
"#$%&'&()
*+,+
)+
%,(
,(
()-+'
'&.)
/
%
/
'
1:
;<1:
(
+
9
= <
.',-
.+/(
&'(*
,'4&(
+
Fig. 15a
Fig. 15b
Remove
Link
between
terminals 5-6
Pipe layout
OPTIMAX HE 31 S
16
Cod. 3540F441 - 03/2007 (Rev. 01)
OPTIMAX “Y” Plan
fig. 16a
fig. 16b
,*&
0
)++,'&
,&')+
Wiring diagram
!
+
*+,+
)+
()-+'
'&.)
,(
%,(
%,
'-)
%&)
+)1
,+()
'
1:
;<1:
(
+
9
= <
7;%9 7
<
2%13,().'.)
"#$%&'&()
+
Remove
Link
between
terminals 5-6
Pipe layout
2.6 Flue system
The unit is “type C” with a sealed chamber and forced draught, the air inlet and flue outlet must be
connected to one of the following flue systems. With the aid of the tables and methods of calculation indi-
cated, before commencing installation, it is first necessary to check that the flue system does not exceed
the maximum permissible length. The current standards and local regulations must be observed.
It should be noted that only Ferroli flue system and accessories should be used on this appliance,
as per BS 5440 2000 and C.E. test certification.
OPTIMAX HE 31 S
17
Cod. 3540F441 - 03/2007 (Rev. 01)
>?%
>?%
>
>
@<<A-344
$B
0
@
)
@
>
+
@
>
0
+
)
@
45676
44
889
45676
44889
2
2
2
2
2
:
6
+
Side view
View from above
fig. 17a
Side Outlet
fig. 17b
Front view
View from above
P = S + 145 mm
Rear Outlet
L = S + D + 203 mm
Connection with concentric flue system
The unit can be connected to a concentric air/flue duct with a Horizontal or Vertical outlet as shown on
the following drawings. Numerous accessories are available on request to meet the various installation
requirements. Please refer to our “flue manual” or the price list.
Standard concentric flue installation
Horizontal flue installation
1. Define the position for installing the unit.
2. If using standard flue (1KWMA53A) this must be installed level, for non-standard flue lengths over
1mtr a fall of 3 mm per metre should be incorporated back to the boiler.
3. Make a hole of diameter 10 - 20 mm greater than the nominal diameter of the concentric pipe used.
4. If necessary, cut the terminal length to size, ensuring that the external pipe protrudes from the wall
by between 10 and 60 mm (fig. 17a and 17b). Remove the cutting burrs.
5. Connect the flue to the boiler, positioning the seals correctly. Seal the flue into the wall with silicone
or sand + cement and cover with wall seals provided.
Flue seals should be lubricated with a silicone type grease to prevent damage (grease not sup-
plied)
OPTIMAX HE 31 S
18
Cod. 3540F441 - 03/2007 (Rev. 01)
0:=
A-34/
A-34/
A-34 -
C6
!
C6
!
91
A-34/
2
:
6
+
Vertical Outlet
fig. 17c
+9
9
3C
<#:7D
;
<6=66
;
>6="
3C
<#:9
The total length in equivalent metres of the concentric flue must not exceed the maximum lengths stated
in the following table, note that each bend gives rise to the stated reduction. For example, a duct = 60/100
composed of 1 bend of 90° +1 horizontal metre + 2 bends of 45° + 1 horizontal metre has a total equivalent
length of 4 metres.
Vertical flueing
The installation of a concentric vertical flue can be carried out as follows,
Install the appliance as previously mentioned in this manual.
1. Connect onto the flue assembly at the top of the appliance a concentric vertical adaptor part number
1KWMA71W,
2. Use the required amount of 1mtr flue extensions (part number 1KWMA56U) inserting them spigot
down ensuring the seals are well lubricated with silicone grease (not supplied) and correctly located
into the sockets.
3. If required 45° bends (Part number1KWMA64A)
may be used with a resistance value of 0.5mtrs
each, the flue should be routed in such away
to avoid any unnecessary deviation and thus
minimise the amount of bends required.
4. The termination should be made through our
concentric flue outlet (part number 1KWMA83U)
in conjunction with a roof slate pitched (part
number 1KWMA82U) or flat roof (part number
1KWMA81U) The storm collar must be fixed on
using the three screws provided and sealed with
an external grade silicone (not supplied).
5. For longer flue lengths a 125mm concentric flue
system is available.
6. All flue installations must comply with BS5440
part 1 and must only be of Fèrroli manufacture.
The vertical flue must continually rise and be
supported throughout its length. The flue must
be inspected whilst commissioning the appliance
to ensure it is sound throughout its length.
This information is for guidance purposes and Fèr-
roli will in no way be held responsible for incorrect
installation following this guide.
OPTIMAX HE 31 S
19
Cod. 3540F441 - 03/2007 (Rev. 01)
+?
9E
9=E
E=A
8
)@
":
2
fig. 18
fig. 19
Connection with 80 mm pipe system
The unit can be connected to a system of separate air/flue
pipes for a Horizontal or Vertical outlet as shown fig 18 - 19
. Numerous accessories are available on request to meet
the various installation requirements. The components
used most frequently are stated in tables 4 - 5. Please
refer to the flue manual or the price list for additional
components.
To check you do not exceed the maximum permissible
flue length, it is necessary to make a simple calculation
before installation:
1. For each component, tables 4 - 5 provide an “equiva-
lent loss in linear metres”, depending on the position
of installation of the component (with air intake or flue
extraction, vertical or horizontal).
The loss is called “equivalent length” since it is compared
to the loss of one metre of flue (defined as equal to 1).
For example, a bend at 90° of Ø80 in flue extraction has
an equivalent loss of 2 linear metres, i.e. it has a loss
equal to that of 2 linear metres of flue length.
2. After completely defining the layout of the system of split
flues, add up the losses in equivalent metres, depending
on the installation position, of all the components and
accessories in the system.
3. Check that the total calculated loss is less than or equal
to 55 equivalent metres, i.e. the maximum permissible
for this model of boiler.
For complete flue options please contact ferroli or
check our comprehensive flue manual.
A-34-
A-34/
A-34/
A-3'4
E
&+
E
'-)
'
: #
A-3'4
2
:
6
+
OPTIMAX HE 31 S
20
Cod. 3540F441 - 03/2007 (Rev. 01)
A-344
A-344
A-34/
4
$
9
7D
9
7D
A-34-
A-34-
A-34-F
8
*8;>6
#
9:"A;>6
#
9B6A;>6
#
8
/
/
.
6
6
6
6
6
(G
4
$
9
7D
9
7D
(G
;>6
;>6
1
1
The stated loss values refer to genuine Ferroli flue accessories.
Terminal Position
0
)
(
H
H
.
4
&
$
+
I
7
7
A
3
3
H
fig. 20
Table of Ø80 flue and accessory
OPTIMAX HE 31 S
21
Cod. 3540F441 - 03/2007 (Rev. 01)
*
);%#
B
#%<%
6
4#
B
#%<%
6
7D;#
B
#%<%
6
.%#
<
.% =
.%
$
<
$
C
$
==#:
$
=#:
$
:%%:::
<
$
:=
4 %:=
7D;=
:
%
9;=
:
%
$
#:6#6<
%<%:<%#
4#<=;
!4
)
&
'
(
,
*
C
(,)
(=(88
2<<
:
:<:
=<<#:
#:<#==
<=:
=
<#J
: %<%=
6
< #1
0 K2=:=
<%
::
===:
<<6
1:
:<<
OPTIMAX HE 31 S
22
Cod. 3540F441 - 03/2007 (Rev. 01)
B
Connection to collective flues or single flues with natural draught
If you are then going to connect the OPTIMAX HE 31 S boiler to a collective flue or a single flue with
natural draught, the flue must be expressly designed by professionally qualified technical personnel in
conformity with the standards and rules in force.
In particular, flues must have the following characteristics:
• Be sized according to the method of calculation stated in the standard
• Be airtight to the products of combustion, resistant to the fumes and heat and waterproof for the
condensate
• Have a circular or square cross-section (some hydraulically equivalent sections are permissible), with
a vertical progression and with no constrictions
• Have the flue conveying the hot fumes adequately distanced or isolated from combustible mate-
rials
• Be connected to just one unit per floor, for at most 6 units in all (8 if there is a compensation duct or
opening)
• Have no mechanical suction devices in the main ducts
• Be at a lower pressure, all along their length, under conditions of stationary operation
• Have at their base a collection chamber for solid materials or condensation of at least 0.5 m, equipped
with a metal door with an airtight closure.
2.7 Condensate outlet connection
The boiler is equipped with an internal air-trap to drain off the condensate. Fit the inspection coupling
A and the hose B, pushing it on for approximately 3 cm and securing it with a clamp.
Fill the air-trap with approximately 0.5 ltrs of water and connect the hose to the waste system, or
soakaway.
6
A
fig. 21
OPTIMAX HE 31 S
23
Cod. 3540F441 - 03/2007 (Rev. 01)
)!
!
@%<%B
)
.
<
+
:#
&<:!,
7<:
'% =
C
7
&
J
fig. 22
Condensate discharge
Where possible the condensate should discharge into an internal soil pipe or waste system. The minimum
pipe diameter required is 22 mm, a trap has already been fitted to the appliance with a flexible tail to
facilitate the connection to the condensate discharge pipe.
The pipe should be a solvent weld plastic, not copper, as the condensate has a ph value of 4 (slightly
acidic).
Where it is not possible to terminate internally, the condensate discharge pipe may be run outside (see
below drawing).
Any external run is subject to freezing, in severe weather conditions. To avoid this the pipework should
be installed to dispose of the condensate quickly, with as much as possible run internally, before passing
through the wall.
Pipework external to the building should be increased in diameter to 32 or 40 mm solvent weld. It should
be run to a external drain or soakaway, with a maximum length of 3 metres.
When a soakaway (condensate absorption point) is used, it should be constructed as shown below, or
use a specifically designed unit, for example Mc Alpine SOAK1GR available from most plumbing and
heating stockists.
OPTIMAX HE 31 S
24
Cod. 3540F441 - 03/2007 (Rev. 01)
fig. 23
&D;
(
E
'*
@:<
3. SERVICE AND MAINTENANCE
3.1 Adjustments
All adjustment and conversion operations must be carried out by Qualified Personnel such as ferroli
Technical Service.
FERROLI declines any responsibility for damage or physical injury caused by unqualified and unauthorized
persons tampering with the device.
Gas supply conversion
The unit can function with either Natural Gas or LPG (commercial propane)and is factory-set for use with
one of the two gases, as clearly shown on the packing and on the unit’s dataplate. Whenever a different
gas to that for which the unit is preset has to be used, a conversion kit will be required, proceeding as
follows:
1
Remove the casing.
2
Open the airtight chamber.
3
Unscrew the gas coupling A on the air/gas mixer.
4
Replace the injector in the mixer with the one contained in the conversion kit.
5
Refit the coupling A and check the connection is gastight.
6
Apply the sticker, contained in the conversion kit, near the dataplate.
7 Fit the airtight chamber and casing back on.
8 Adjust the parameter for the specific type of gas to be used:
- Turn the boiler onto standby
- Press the DHW buttons
(part. 1, 2 - fig. 1) for 10 seconds: the display will show “P01”
blinking
- Press the DHW buttons
(part. 1, 2 - fig. 1) to set parameter 00 (for natural gas operation)
or 01 (for LPG operation)
- Press the DHW buttons
(part. 1, 2 - fig. 1) for 10 seconds
- The boiler will go back onto standby
9 Check working pressure.
10 Check CO2 mixture as detailed (page 27 combustion analyser testing).
OPTIMAX HE 31 S
25
Cod. 3540F441 - 03/2007 (Rev. 01)
3.2 System start-up
Commissioning must be performed by Qualified Personnel.
Checks to be made at first ignition, and after all maintenance operations that involved discon-
necting from the systems or an intervention of a safety device.
Before lighting the boiler:
• Open any isolation valves between the boiler and the system.
• Check the tightness of the gas system, proceeding with caution and use gas leak detection fluid to
detect any leaks in connections.
• Check the pre-filling of the expansion tank (ref. sec.4.4)
• Fill the water system and make sure that all air contained in the boiler and the system has been vented
by opening the air vent valve on the boiler and any vent valves on the system.
• Make sure there are no water leaks in the system, hot water circuits, connections or boiler.
• Make sure the electrical system is properly connected.
• Make sure that the unit is connected to a good earthing system.
• Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.
• Vent and spin the pump.
• Ensure the flue system is correctly fitted, including terminal locations.
Ignition
• Open the gas valve upstream of the boiler.
• Purge the air from the installation pipework to the appliance.
• Switch on the boiler electrical supply.
• Press the
key on the boiler for 5 seconds (part. 7 - fig. 1).
• The boiler is now ready to function automatically whenever the external controls call for a demand.
In case of an electrical power failure while the boiler is working, the burner will go out. When
power returns, the boiler will run the self-test cycle again, after which the burner will automatically
re-ignite (if there is still demand for heat).
Checks during operation
• Check the tightness of the gas circuit and water systems.
• Check the efficiency of the flue and air-flue ducts while the boiler is working.
• Check that the water is circulating properly between the boiler and the system.
• Make sure that the gas valve modulates correctly.
• Check the proper ignition of the boiler by performing various tests, turning it on and off with the
room thermostat or remote control.
• Make sure that the fuel consumption indicated on the meter corresponds to that given in the technical
data table in section 4.4 page 33
Turning off
Press the
key for 5 seconds (part. 7 - fig. 1).
OPTIMAX HE 31 S
26
Cod. 3540F441 - 03/2007 (Rev. 01)
3.3 Maintenance
The following operations are strictly reserved for Qualified Personnel, such as corgi registered
engineers or Ferroli engineers.
Seasonal inspection of the boiler and flue
It is advisable to carry out the following checks at least once a year:
• The control and safety devices (gas valve, flow meter, thermostats, etc.) must function correctly.
• The flue terminal end piece and ducts must be free of obstructions and leaks.
• The gas and water systems must be sound.
• The burner and exchanger must be clean.
• The electrodes must be free of scale and correctly positioned.
• The system pressure when cold must be approx 1 bar; otherwise, bring it to that value.
• The expansion vessel must be filled to 1 bar cold with zero system pressure.
• The gas flow and pressure must correspond to that given in table 10 section 4.4 page 33.
• The circulating pump must be vented and free of debris.
• The returned filter cleaned.
• The condensate trap inspection bowl should be cleaned and free of debris.
OPTIMAX HE 31 S
27
Cod. 3540F441 - 03/2007 (Rev. 01)
fig. 24
2
:
6
+
2
:
6
+
4
$#
4 $#
fig. 25
Opening the casing
To open the boiler casing, you need to follow the sequence given below
and the instructions of fig. 24.
1 Using a screwdriver, fully unscrew and remove the 2 screws “A ”
2 Open by lowering the panel “B ”
3 Lift and take off the casing “C ”
Cleaning the boiler and burner
The body and burner must not be cleaned with chemical products or wire brushes. Special care must
be taken over all the sealing systems pertaining to the sealed chamber (gaskets, cable clamps, etc.). In
addition, it is necessary to pay attention after performing all these operations to check and carry out all
the phases of ignition and thermostat operation, the gas valve and circulation pump.
After these checks, make sure there are no gas leaks.
Combustion analysis
It is possible to analyse the combustion
through the air and flue sampling points
shown in fig. 25.
To make the measurement, it is necessary
to:
1) Open the flue sampling point
2) Insert the probe;
3) Press CH button
(part. 3, 4 - fig. 1)
for 5 seconds to turn on TEST mode;
4) Wait 10 minutes for the boiler to stabilize
5) Take the measurement.
NAT GAS; CO2 reading should be 8.7 to 9.0%
L.P.G; CO2 reading should be 9.5 to 10%
Readings taken with an unstabilized boiler will cause measurement errors.
OPTIMAX HE 31 S
28
Cod. 3540F441 - 03/2007 (Rev. 01)
3.4 Troubleshooting
Fault Diagnosis
In the event of operating problems or trouble, the display will flash and a fault identification code
appears.
There are faults that in order to restore operation the RESET button must be pressed (ref.6 - fig. 1); or
if the boiler fails to start, it will be necessary to repair the fault (code nos. F1 to F24). Other faults cause
temporary shutdowns that are automatically reset as soon as the value comes back within the boiler’s
normal working range (codes from 25 to 47).
When the boiler starts functioning normally again, the display stops flashing and the fault code disap-
pears.
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas fl ow to the boiler and the air
has been purged from the pipes.
Detection or ignition electrode fault
Check that the electrodes are correctly positioned
and free of any deposits
Defective gas valve
Check and change the gas valve
Incorrect inlet gas pressure
Check inlet gas pressure
Siphon obstructed
Check and if necessary change the siphon
A02
Flame detected with the burner off
Ionisation electrode defective
Check the ionizing electrode wiring
Main board defective
Check the PCB
A03
High limit protection
Flow sensor not active or correctly
located
Check the correct positioning and operation of the
fl ow sensor
No system circulation
Check the pump and radiator valves present in the
system and automatic by-pass
A04
Flue gas fault
Fault F07 happened 3 times in the
last 24 hours
Check the fl ue
A05
Fan problem
Tachometer signal interruped for
1 hour
Check the wiring and the fan
A06
No fl ame after the ignition phase (6
times in 4 min.)
Detection electrode fault
Check that the electrode is correctly positioned and
if necessary change it
Flame unstale
Check the burner
Incorrect valve gas Offset
Check Offset at the minimum power
Flue gas circuit obstructed
Check if fl ue gas circuit is free
Siphon obstructed
Check and if necessary change the siphon
A41
Flow sensor disconnected
Sensor disconnected
Check the correct position and operation of the fl ow
sensor
F07
Flue gas fault
The exhaust gases temperature
becomes higher than 95°C for 2
minutes longer.
Check the fl ue
F10
Flow sensor fault
Sensor damaged or short circuited
Check the wiring or change the sensor
Sensor damaged or wiring broken
Check the wiring or change the sensor
F11
Return sensor fault
Sensor damaged or wiring shorted
Check the wiring or change the sensor
Sensor damaged or wiring broken
Check the wiring or change the sensor
OPTIMAX HE 31 S
29
Cod. 3540F441 - 03/2007 (Rev. 01)
Fault
Possible cause
Cure
F13
Flue sensor fault
Sensor damaged or wiring shorted
Check the wiring or change the sensor
Sensor damaged or wiring broken
Check the wiring or change the
sensor
F14
Flow sensor fault
Sensor damaged or short circuited
Check the wiring or change the sensor
Sensor damaged or wiring broken
Check the wiring or change the sensor
F15
Fan problem
Tachometer signal interrupted, fan
connection
Check the wiring and fan
Fan damaged, debris in fan
Check the fan, clean debris
F34
Supply voltage under 180V.
Electric mains fault
Check the electrical system
F35
Irregular mains frequency
Electric mains fault
Check the electrical system
F37
Incorrect system water pressure
Pressure too low
Fill the system
Sensor damaged
Check the sensor
F40
Incorrect system water pressure
Pressure too high above 3 - 5 bar
Check the fi lling loop is not passing and discon-
nected
Check the wiring and sensor
Check the safety valve
Check the expansion vessel
F42
Flow sensor fault
Sensor damaged
Change the sensor
F47
N/A for UK
OPTIMAX HE 31 S
30
Cod. 3540F441 - 03/2007 (Rev. 01)
4. TECHNICAL CHARACTERISTICS AND
DATA
4.1 Dimensions and connections
6
Pressure Relief Valve
7
Condense outlet
Key
1
System flow (22 mm with isolation valve fitted)
3
Gas inlet (22 mm with isolation valve fitted)
5
System return - 22 mm with isolation valve fitted
(c/w filter)
E!L
E!L
E!L
2
<
"
F
E
2
:
6
+
fig. 26
OPTIMAX HE 31 S
31
Cod. 3540F441 - 03/2007 (Rev. 01)
4.2 General view and main components
fig. 27
5
Room sealed compartment
7
Gas inlet
10
CH flow
11
CH return
14
Heating safety valve
16
Premix fan assembly
19
Combustion compartment
21
Main injector
22
Main burner
29
Flue Collar
32
Pump
36
Automatic air vent
44
Gas valve
56
Expansion vessel
82
Ionisation electrode
145
System pressure gauge
154
Condensate outlet pipe
161
Heat exchanger
186
Return sensor
188
Ignition electrode
191
Flue gas temperature sensor
196
Condensate collector
201
Fan Venturi
241
Automatic by-pass
246
System pressure sensor
278
Double sensor (Safety + Heating)
OPTIMAX HE 31 S
32
Cod. 3540F441 - 03/2007 (Rev. 01)
4.3 Hydraulic diagram
fig. 28
Key
7
Gas inlet
10
CH flow
11
CH return
14
Pressure Relief valve
16
Premix fan assembly
32
Pump
36
Automatic air vent
44
Gas valve
56
Expansion vessel
154
Condensate outlet pipe
161
Heat exchanger
186
Return sensor
193
Siphon
201
Fan Venturi
241
Automatic by-pass
246
System pressure sensor
278
Double sensor (Safety + Heating)
OPTIMAX HE 31 S
33
Cod. 3540F441 - 03/2007 (Rev. 01)
4.4 Technical data table
E
7#
G
>3
#G
O=$('',+2 ;
)85
88
3C% <
-
(%<%;:@<2J22J222
-
J
6
E
E
JJ
,
8
!=
77
& =%&
& ; &
+0&=%&
+0& ; &
*!
*
B-
!:
B#!:
/ =:NJN
/ =:NJN
,&J&
P
,&J0
P
$#
NJN
N
$#
NJN
N
$# =%
B#!:
*!
*
B-
B-
,C
(#;
B#!((<
6
& DD&J&
& DD&J0
(#
20
0%#!=G;
9!7D
5)
!
@ (==;@()./A
OPTIMAX HE 31 S
34
Cod. 3540F441 - 03/2007 (Rev. 01)
4.5 Diagrams
Head available for the system
fig. 29
)
*
+
,
-
.
/
0
)
.))
*)))
*.))
+))) 123
1
%+3
,
*
+
Key
1 - 2 - 3 = Pump selector positions
A = Boiler losses of head
OPTIMAX HE 31 S
35
Cod. 3540F441 - 03/2007 (Rev. 01)
Key
16
Fan
32
Central heating pump
44
Combination gas valve
62
Time clock (optional)
81
Spark Electrode
82
Ionisation electrode
101 Main p.c.b.
103 Relay
104 Fuse
186 Return temperature sensor
191 Exhaust temperature sensor
202 Transformer 230V-24V
203 Supply lead and 3 Amp plug
246 Water Pressure Sensor
278 Double sensor (Safety + Heating)
fig. 30
4.6 Wiring diagram
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING
ROOM T/STAT & PROGRAMMER/TIMER
PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER
CYLINDER T/STAT & PROGRAMMER/TIMER
COMBI BOILER
HEATING ZONE VALVES
FITTED
NOT REQUIRED
HOT WATER ZONE VALVES
FITTED
NOT REQUIRED
THERMOSTATIC RADIATOR VALVES
FITTED
AUTOMATIC BYPASS TO SYSTEM
FITTED
NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE
ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE)
mbar
CENTRAL HEATING FLOW TEMPERATURE
°C
CENTRAL HEATING RETURN TEMPERATURE
°C
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE
ft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)
mbar
COLD WATER INLET TEMPERATURE
°C
HOT WATER OUTLET TEMPERATURE
°C
WATER FLOW RATE
lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS?
YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING?
N/A
YES
CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
m3/hr
m3/hr
COMMISSIONING ENG’S NAME PRINT
CORGI ID No.
SIGN
DATE
BOILER SERIAL No.
NOTIFICATION No.
BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
C O L L E C T I V E M A R K
N/A
N/A
2 6 7
Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No.
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 2 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 7 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 8 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
FERROLI TECHNICAL HELPLINE - 08707 282 885
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS
MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
ALL SPECIFICATIONS SUBJECT TO CHANGE
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this is not caused by lack of electricity supply, gas supply or low water pressure before calling our
Customer Service Helpline.
Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HD
Tel. 08707 282 885 - Fax 08707 282 886
EIRE only:
HEATOVENT Greenhills Industrial Estate,
Greenhills Road, Walkinstown, Dublin 12, IRELAND
Tel 014508166 - Fax 014508501
Should you require any assistance during the installation
call our Technical Service Helpline on
08707 282 885 option 1
Should you require a service engineer to visit
call our service centre on
08707 282 885 option 2
(For U.K. and Northern Ireland)
For EIRE only call HEATOVENT on
014508166