Foster LC125 Service Manual
Read Online
Read the Foster LC125 Service Manual online using the built-in PDF viewer.
Text of the manual
Tel: 01553 691122
Fax: 01553 691447
Website: www.fosterrefrigerator.co.uk
Email: [email protected]
a Division of ‘ITW (UK) Ltd’
LC125 /SM/07/04
If not disposed of properly all refrigerators have components that can be harmful to the environment. All old
refrigerators must be disposed of by appropriately registered and licensed waste contractors, and in accordance
with UK laws and regulations.
Contents
Page
Introduction
1
Technical Information
1
Temperature Controller
1
Controller Parameters
2
Alarms and Warnings
2
Electrical Connections
2
Wiring Diagram
3
Introduction
Top loading meatwell for the storage of frozen
products
One piece foam shell with skin evaporator and
bottom
mount condensing system.
R 134A refrigerant
Fitted with corner bumpers to each side.
Front smash bar as an option, fitted as standard for
Burger King.
Fitted with 4 x 60mm castors.
Technical Information
Temperature Set Point
-21°C
Refrigerant
R134A
Refrigerant Charge
180 gms
Capillary
4.5mts x 042
Power supply
230/50/1
Temperature Controller
When the controller is switched on a single line appears on the display for 3 seconds to indicate the autotest
period.
After this period the air temperature measured by the T1 probe is displayed.
It is strongly advised that before adjusting any Service Parameters a thorough understanding of the
following instructions should be obtained.
LDU 15 Controller
Check temperature set point.
Check set point by pressing the
button
To increase set point press
+
To decrease set point press
+
Factory Temperature Set Point -21°C.
Exit from set up occurs after 10 seconds if no button is pressed.
Controller Set Up.
The parameters are accessed by pressing the following keys in succession
+
+
and keeping them pressed for 3 seconds.
Access to the parameters has been achieved with the first parameter SCL being displayed.
To pass from one parameter to the next press either the
or
key.
To display the value press.
To change the value press
+
to increase, or
+
to decrease.
aux
lae
set
aux
set
set
set
set
set
set
set
Minimum Temperature Set Point
05
-25
SPH
Maximum Temperature Set Point
01
-15
SP
Effective Temperature Set Point
03
-21
HYS
Hysteresis
3
+3
CRT
Compressor Rest Time (minutes)
10
0
CDC
Compressor Regulation with T1 Fail
20
7
DFR
Defrosting Frequency (/24 hours)
4
0
DTO
Defrosting Duration (minutes)
20
20
DDY
Defrost Display Control
1
1
ATL
Low Alarm Differential
-5
-10
ATH
High Alarm Differential
5
10
ATD
Temperature Alarm Delay (minutes)
60
90
ACC
Condenser Clean Interval
05
0
OAU
Auxiliary Output Mode of Operation
30
NON
BAU
Auxiliary Button Mode of Operation
05
NON
OS1
T1 Offset
00
00
SIM
Display Slowdown
00
00
ADR
Address
01
01
Alarms and Warnings
HI
High Temperature Alarm
LO
Low Temperature Alarm
E1
T1 Probe Failure
DF
Defrosting in Progress
CLN
Condenser
LDU 151E-BG Electrical Connections
PARTS LIST
ITEM
Description
Part Number
Temperature Controller
LDU 151E-BG
00-555357
Air Probe
T1
POA
Rocker Switch
15243562
Rocker Switch Cover
15243609
Capillary
4.5 mts X 042"
16010654 (sold in 5m lengths)
Compressor
GL60AA
15427002
Drier
1/4 DBL ENT1/4 OUT R134
15480908
Condenser
15432001
Condenser Fan Motor
Grid Mount 5W
15470032
Corner Bumpers
15260653
Front Smash Bar
00-744880-01
Castor
60mm Swivel
00-555335
Castor
60mm Swivel Braked
00-555336
PWR
1 2 3 4 5 6 7 8 9 10 11
AUX
T1
DATA