Control Supplement and Gas Control Parts for Natural or Propane gas (tankless heater application optional) EG PEG EGH • Installation • Startup • Maintenance • Parts Boiler Manual Gas-Fired Boilers – Series 4 EG • PEG • EGH This manual must only be used by a qualified heating installer/service technician. Before installing, read all instructions, including this manual, the burner manual and any rela

Read this page first

Hazard definitions The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product. Indicates presence of hazards that will cause severe personal injury, death or substantial property damage. Indicates presence of hazards that can cause severe personal injury, death or substantial property damage. Indic

Weil-McLain EG Codes and Checklist . . . . . . . . . 4

Prepare boiler location . . . . . . . 5 Prepare the boiler . . . . . . . . . . . 9 Connect piping — water boilers 14 Connect piping — steam boilers 17 Install boiler controls . . . . . . . . 20 Connect piping — tankless heater 21 Connect gas supply piping . . . 22 Connect field wiring to boiler . 23 Start-up . . . . . . . . . . . . . . . . . . . 24 Ha

Weil-McLain EG Part Number 550-110-639/0512

4 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Installation must follow these codes: • Local codes, laws, provincial and national codes, laws, regulations and ordinances • National Fuel Gas Code ANSI Z223.1- latest edition • Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required • National Electric Code The equipment shall be installed in accord

Figure 1 Alcove installation (EG & PEG only)

1. For EGH boilers, See Table 1 for clearances to boiler and system components. EGH installations 1. Provide the clearances for service listed on this page. 2. Install in a space that is large in comparison to the size of the boiler (see National Fuel Gas Code for details). Part Number 550-110-639/0512 5 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Table 1 EG, PEG & EGH -Service and com

Weil-McLain EG Table 2 Minimum foundation size

Figure 2 Boiler foundation Part Number 550-110-639/0512 6 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Vent System Failure to follow all instructions can result in flue gas spill- age and carbon monoxide emissions, causing severe personal injury or death. Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe personal injury o

Weil-McLain EG Contaminants to avoid

Part Number 550-110-639/0512 7 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Products to avoid Spray cans containing chloro/fluorocarbons Permanent wave solutions Chlorinated waxes/cleaners Chlorine-based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic
Part Number 550-110-639/0512 8 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Air openings Provide adequate combustion and ventilation air to assure proper combustion and reduce the risk of severe personal injury, death or substantial prop- erty damage caused by flue gas spillage and carbon monoxide emissions. Combustion air and ventilation openings must comply with the National Fuel Gas Code, ANSI Z223.1 – latest edition, o

Handling split blocks

Part Number 550-110-639/0512 9 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Placing the boiler Block assembly is extremely heavy. Handle with caution to avoid personal injury. EGH boilers only — When an EGH block assembly is taken apart for handling: 1. Put a support under center of block. Support must be within ½ inch of block bottom. 2. Detach seal replacement kit from the draw rod. Remove sho
Part Number 550-110-639/0512 10 EG • PEG • EGH gas-fired boilers — series 4 — boiler manual Installation of optional indirect water heater 1. For a boiler ordered with internal type indirect water heater, remove heater opening cover plate (water boil- ers – round plate on left side; steam boilers – rectan- gular plate on front). 2. Install heater(s) as shown on page 18. Do not over tighten studs and nuts - damage to the gasket can occur. Hydr

Weil-McLain Boiler Owners Instructions:

Device Model Type of Document Pages Size Views Downloads Updated
GOLD CGt SERIES

Weil-McLain GOLD CGt SERIES User Guide (User's information manual), @GT4VOY

12 949 238 28-05-2026
Series 4

Series 4 (Boiler ePDF User Manual, #O2H1Z3)

32 241 58 05-09-2026
GV90+

GV90+ (Boiler ePDF Manual, #K9K8G4)

4 148 37 26-06-2026
EG 5 Series

Weil-McLain Boiler Manual  (File: PDF, 14-07-2026)

40 2.22 Mb 1115 235 14-07-2026

Boiler: Similar Manuals