Panasonic EBL128 Planning Instructions
Read Online
Read the Panasonic EBL128 Planning Instructions online using the built-in PDF viewer.
Text of the manual
Fire Alarm System EBL128
V1.1.x
Author:
Jan Pettersson
Date of issue: 2008-07-11
Date of rev:
2010-05-28
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
1
Table of contents
1
Introduction________________________________ 7
2
Definitions / Explanations ____________________ 9
2.1
PEWF&STE AB ___________________________________ 9
2.2
Alarm point _______________________________________ 9
2.2.1
Smoke detector ________________________________ 9
2.2.2
Analog detector ________________________________ 9
2.2.3
Sensor _______________________________________ 9
2.2.4
(Analog) Sensor Base (ASB) _____________________ 9
2.2.5
Conventional detector ___________________________ 9
2.2.6
Conventional Detector Base (CDB) ________________ 9
2.2.7
Addressable ___________________________________ 9
2.2.8
Old detector __________________________________ 10
2.2.9
Conventional zone line _________________________ 10
2.2.10
Addressable zone interface ______________________ 10
2.3
Output unit ______________________________________ 10
2.4
Output / Control output _____________________________ 10
2.5
Short circuit isolator _______________________________ 10
2.6
Display unit (D.U.) ________________________________ 10
2.7
COM loop _______________________________________ 10
2.8
Control Unit (C.U.) / C.I.E. __________________________ 10
2.9
Fire Brigade Panel (FBP) ___________________________ 10
2.10
Control panel (CP) ________________________________ 11
2.11
LED ____________________________________________ 11
2.12
External Indicator (LED) ___________________________ 11
2.13
Display / LCD ____________________________________ 11
2.14
Door open / Key switch _____________________________ 11
2.15
SSD / Site Specific Data ____________________________ 11
2.16
S/W / Software / System program _____________________ 11
3
Overview _________________________________ 12
3.1
The EBL128 c.i.e. _________________________________ 12
3.2
S/W Versions ____________________________________ 12
3.3
Documents ______________________________________ 12
3.4
Applications _____________________________________ 12
3.5
PC S/W _________________________________________ 12
4
Control & Indicating Equipment _____________ 13
4.1
COM loop _______________________________________ 15
4.1.1
A single break (cut-off) on the COM loop __________ 16
4.1.2
Several breaks (cut-offs) on the COM loop _________ 17
4.1.3
Short-circuit on the COM loop ___________________ 18
4.2
Programmable voltage outputs (S0-S1) ________________ 18
4.3
Programmable relay output (R0) ______________________ 19
4.4
Relay output for routing equipment (fault tx) (R1) ________ 19
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
2
4.5
Programmable input (I0) ____________________________ 19
4.6
24 V DC power supply outputs _______________________ 20
4.7
RS232 interfaces __________________________________ 20
4.8
RS485 transceiver (option) __________________________ 20
4.9
Power supply _____________________________________ 20
4.10
Internal Power supply ______________________________ 21
5
Expansion boards 458x _____________________ 22
5.1
Expansion board address setting ______________________ 23
5.2
8 zones expansion board 4580 _______________________ 23
5.2.1
Type of zone line input _________________________ 24
5.2.2
Input states __________________________________ 24
5.3
8 relays expansion board 4581 _______________________ 25
5.4
Inputs and outputs expansion board 4583 _______________ 26
5.5
I/O Matrix board 4582 _____________________________ 27
5.5.1
Generic _____________________________________ 28
5.5.2
Fan control __________________________________ 29
5.5.3
Zone control _________________________________ 29
6
Peripheral devices __________________________ 30
6.1
COM loop units ___________________________________ 30
6.1.1
Input units ___________________________________ 31
6.1.2
Addressable I/O units __________________________ 39
6.1.3
Alarm devices (addressable sounders) _____________ 40
6.1.4
Short circuit isolators (addressable) _______________ 42
6.1.5
Units for Hazardous (Ex) areas ___________________ 43
6.1.6
Other COM loop units __________________________ 44
6.1.7
COM loop addresses for Base station and Wireless
detectors 46
6.2
Units connected to the RS485 interface ________________ 46
6.2.1
External Fire Brigade Panels _____________________ 47
6.2.2
Alert Annunciation Units _______________________ 48
6.2.3
External Presentation Units ______________________ 49
6.2.4
German Fire Brigade Panels _____________________ 50
6.3
Units connected to the RS232 interface J5 ______________ 51
6.3.1
Web-servers __________________________________ 51
6.4
Units connected to the RS232 interface J3 ______________ 51
6.5
Other units _______________________________________ 51
6.5.1
Alert Annunciation Controllers ___________________ 51
6.5.2
External LEDs ________________________________ 52
6.5.3
Alarm devices (sounders, etc.) ___________________ 53
6.5.4
Door release magnets __________________________ 53
6.5.5
Boxes _______________________________________ 53
7
Programmable inputs _______________________ 54
7.1
Control unit Input I0 & Inputs and Outputs exp. board 4583,
Input 0-4 ______________________________________________ 55
7.1.1
Not supervised ________________________________ 55
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
3
7.1.2
Supervised ___________________________________ 55
7.2
3361 unit Inputs In0 / Z & In1 _______________________ 56
8
Input programming ________________________ 57
8.1
Type (trigger conditions) ____________________________ 57
8.2
Logic ___________________________________________ 59
8.2.1
Not supervised (default) ________________________ 60
8.2.2
Supervised ___________________________________ 60
9
Programmable outputs ______________________ 61
9.1
Control unit outputs S0 – S1 _________________________ 62
9.2
Control unit output R0 _____________________________ 63
9.3
8 relay outputs expansion board 4581 Output 0 – Output 7 _ 63
9.4
Inputs and Outputs expansion board 4583 Output 0 – 1 ____ 63
9.5
The 3361 unit outputs Re0 – Re1 _____________________ 64
9.6
The 3364 unit outputs VO0, VO1 & VO2 ______________ 64
9.7
The 3377 unit output (siren) _________________________ 64
9.8
The 3378 unit output (sounder) _______________________ 64
9.9
The 3379 unit output (sounder) _______________________ 64
10
Output programming _______________________ 65
10.1
Type ___________________________________________ 65
10.2
Logic ___________________________________________ 66
10.3
Supervised _______________________________________ 66
10.4
Output signal period _______________________________ 66
10.5
Control expression ________________________________ 69
10.5.1
Trigger conditions _____________________________ 69
10.5.2
Logical operators ______________________________ 72
10.5.3
Control expression examples ____________________ 72
11
Interlocking function _______________________ 76
11.1
Interlocking programming __________________________ 76
11.1.1
Interlocking output ____________________________ 76
11.1.2
Interlocking input _____________________________ 76
11.1.3
Interlocking combination _______________________ 76
11.2
Interlocking indications _____________________________ 78
11.3
Information of interlocking combinations (H9) __________ 78
11.3.1
Display interlocking information (H9/C1) __________ 78
11.3.2
Activate interlocking output (H9/C2) ______________ 79
11.3.3
Reset interlocking output (H9/C3) ________________ 79
11.3.4
Disable interlocking output (H9/C4) _______________ 79
11.3.5
Re-enable interlocking output (H9/C5) _____________ 79
11.4
Interlocking control expressions ______________________ 79
12
Fire Door Closing function __________________ 80
13
Functions / Services / Features _______________ 81
13.1
Analog smoke detectors ____________________________ 81
13.1.1
Sensor value _________________________________ 81
13.1.2
Week average sensor value ______________________ 81
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
4
13.1.3
Decision value ________________________________ 82
13.1.4
Alarm algorithms for smoke detectors / Detection levels /
Offsets 82
13.1.5
Alarm algorithm / Alternative alarm algorithm ______ 83
13.1.6
Filtering algorithm ____________________________ 84
13.1.7
Smouldering smoke algorithm ___________________ 86
13.1.8
Performance factor ____________________________ 88
13.2
Analog heat detectors ______________________________ 88
13.2.1
Class A1 algorithm ____________________________ 89
13.2.2
Class A2 S algorithm __________________________ 89
13.2.3
Class B S algorithm ____________________________ 89
13.3
Self verification ___________________________________ 90
13.4
Minimum / Maximum sensor values ___________________ 90
13.5
Two-unit dependence (co-incidence alarm) _____________ 90
13.6
Two-zone dependence (co-incidence alarm) _____________ 91
13.7
Delayed alarm ____________________________________ 92
13.8
Alarm Verification Facility __________________________ 92
13.9
Alert Annunciation ________________________________ 92
13.10
Alarm Acknowledgement Facility (AAF) _____________ 94
13.11
Quiet alarm ____________________________________ 96
13.12
Fire alarm type A and Fire alarm type B ______________ 96
13.12.1
Fire alarm type B ____________________________ 97
13.12.2
Fire alarm type A ___________________________ 97
13.13
Disable zones, alarm points, outputs, etc. _____________ 97
13.13.1
Disable zone _______________________________ 98
13.13.2
Disconnect / Re-connect zone line ______________ 98
13.13.3
Disable zone / address ________________________ 98
13.13.4
Disable control output ________________________ 98
13.13.5
Disable / Re-enable all control, exting. and ventilation
outputs
98
13.13.6
Disable / Re-enable alarm devices ______________ 98
13.13.7
Disable outputs for routing equipment ___________ 98
13.13.8
Disable interlocking output ____________________ 99
13.13.9
Disconnect / Re-connect COM loop _____________ 99
13.14
Test mode _____________________________________ 99
13.15
Test alarm devices _______________________________ 99
13.16
Test of routing equipment ________________________ 100
13.17
Calibration of supervised outputs __________________ 100
13.18
Service signal _________________________________ 100
13.19
Fault signal (fault condition) ______________________ 100
13.20
Alarm texts ___________________________________ 101
13.20.1
Creating the alarm texts via Win128 ____________ 101
13.20.2
Downloading texts to the EPU 1728, AAUs 1735 /
1736 and ext. FBPs 1826 / 1828 ________________________ 103
13.21
Real time clock (RTC) __________________________ 103
13.21.1
Daylight saving time ________________________ 104
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
5
13.22
Time channels 1-4 ______________________________ 104
13.23
Time channels 5-12 _____________________________ 104
13.24
Event log _____________________________________ 105
13.25
Loss of main power source _______________________ 105
13.25.1
Fault: Loss of main power source ______________ 105
13.25.2
LCD backlight _____________________________ 105
13.26
Win128 Tools menu ____________________________ 105
14
Special New Zealand functions ______________ 108
14.1
Alarm devices ___________________________________ 108
14.1.1
Silence alarm devices (inside switch) _____________ 108
14.1.2
New Zealand FB Silence switch (outside switch) ____ 108
14.2
Battery faults ____________________________________ 109
14.2.1
FAULT: Battery _____________________________ 109
14.2.2
FAULT: Low battery capacity __________________ 109
14.3
Watchdog reset __________________________________ 110
14.4
Routing equipment isolate (disable) __________________ 110
14.5
Acknowledged alarm _____________________________ 110
15
Cyber sensor functions _____________________ 111
15.1
Pulse up – down counter ___________________________ 112
15.1.1
Pulse up – down counter for smoke ______________ 112
15.1.2
Pulse up – down counter for temperature __________ 112
15.1.3
Pulse up – down counter for smoke & temperature __ 112
15.2
Fire judgement __________________________________ 112
15.3
Alarm threshold levels ____________________________ 113
15.4
Learning function / Learning conditions _______________ 113
15.4.1
Learning conditions ___________________________ 113
15.5
Alarm delay time _________________________________ 115
15.6
Analog data output _______________________________ 116
15.7
Sensitivity compensation __________________________ 116
15.8
Self diagnosis of internal devices ____________________ 116
15.9
Address setting check _____________________________ 117
16
Control unit properties (settings) ____________ 118
16.1
Control Unit Properties ____________________________ 118
16.1.1
AAF times __________________________________ 118
16.1.2
Alert annunciation times _______________________ 118
16.2
Time Channels __________________________________ 119
16.3
Alarm Algorithms ________________________________ 121
16.3.1
Parameters for smoke algorithms ________________ 122
16.3.2
Parameters for heat algorithms __________________ 122
16.3.3
Parameters for combined decision algorithm _______ 123
16.4
National Holidays ________________________________ 123
16.5
Output Signal Periods _____________________________ 125
16.6
Advanced ______________________________________ 126
16.6.1
Main power loss fault _________________________ 126
16.6.2
Alarm reset _________________________________ 126
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
6
16.6.3
Door closing by time __________________________ 126
16.6.4
Zone line input alarm delay time _________________ 127
16.6.5
Miscellaneous _______________________________ 127
16.7
Statistics _______________________________________ 128
17
Cable types ______________________________ 129
17.1
COM loop cables_________________________________ 129
17.2
Ext. FBP / EPU / AAU cables _______________________ 129
17.3
Conventional zone line cables _______________________ 129
17.4
Alarm device cables ______________________________ 129
17.5
Other equipment cables ____________________________ 129
18
COM loop cable length _____________________ 131
19
Current consumption ______________________ 134
20
Power supply _____________________________ 137
20.1
Charger functions ________________________________ 137
20.1.1
Battery charging functions: _____________________ 138
20.1.2
Security functions ____________________________ 138
20.2
Current consumption calculations ____________________ 139
20.3
Main power source (Power Supply) __________________ 140
20.4
Second power source (Battery) ______________________ 140
20.5
Form / Table of current consumption _________________ 141
21
S/W versions _____________________________ 142
22
Technical data ____________________________ 143
23
Limitations_______________________________ 144
23.1
C.i.e. __________________________________________ 144
24
National regulations / requirements __________ 145
24.1
Conventions_____________________________________ 145
24.2
Language _______________________________________ 145
25
Drawings / connection diagrams _____________ 146
26
Revision history ___________________________ 147
Drawings according to the valid table of drawings.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
7
1
Introduction
EBL128 Planning Instructions is a document1 with information of
special interest for planning engineers as well as service /
commissioning engineers.
It should be read in conjunction with the EBL128 Operating
Instructions, since most of the information in one of the documents is
not found in the other document and vice versa.
It should also be read in conjunction with the EBL128 drawings2,
according to the valid Table of drawings.
A Product Leaflet is also available at:
http://www.panasonic-fire-security.com/pewfste/en/html (Data sheets)
When planning a fire alarm installation the national regulations have
to be obeyed. A lot of detector types can be used. Detector coverage
area and detector placing in the room / building, etc. are matters for
the planning engineers and are not described in this document.
Due to continual development and improvement, different S/W
versions are to be found. This document is valid for the EBL128 S/W
version 1.1.x. On the date of this document is x=2.
EBL128 S/W version 1.1.x support and some functions require the
EBL128 main board 4556 with p.c.b. no. 9285-6A. S/W version 1.1.x
also support main board with p.c.b. no. < 9285-6A (e.g. 9285-5A).
EBL128 is produced for many countries, accordingly the look, the
texts, the functions, etc. might vary from country to country.
Products
Products consists of one or more parts (H/W) according to a Product
Parts List. A product has:
a type number (e.g. 4550)
an article number, often the same as the type no. but sometimes
a country code is added (e.g. 4550SE)
a product name (e.g. EBL128 Control & Indicating
Equipment, 128 addresses)
H/W
A H/W (e.g. a printed circuit board) has:
a type number (e.g. 1556)
an article number, often the same as the type no. but sometimes a
country code is added (e.g. 1556SE)
a product name (e.g. Main Board 128 addr.)
1 File name: K:\PRO\FIRE\128\Doc\V1.1.x\MEW01090 (Rev 3).doc
2 Dimensions & overviews, connection diagrams, etc.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
8
a p.c.b. number (e.g. 9285-6A) and can also have a configuration
(e.g. CFG: 1) and a revision (e.g. REV: 2)
sometimes is a S/W (software) downloaded.
S/W
A S/W has:
a version number (e.g. V1.1 or V1.1.0)
sometimes is additional information, such as Convention
(different functions / facilities), Language, etc. added.
PC S/W
A PC S/W is a program used for programming, commissioning, etc. It
has a version number.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
9
2
Definitions / Explanations
Definitions / explanations / abbreviations / etc. frequently used or not
explained elsewhere in the document.
2.1
PEWN AB
Panasonic Electric Works Nordic AB
2.2
Alarm point
Unit, which can generate a fire alarm, i.e. an analog or conventional
detector, a manual call point, etc.
2.2.1
Smoke detector
Two types of analog and conventional smoke detectors are available:
photo electric (optical) and ionization.
2.2.2
Analog detector
Contains an A/D-converter. EBL128 picks up the digital values
("sensor values") for each detector individually. All evaluations and
"decisions" are then made in EBL128, i.e. by advanced algorithms.
Analog detectors are addressable – an address setting tool is used. An
analog detector has to be plugged in an ASB.
2.2.3
Sensor
Sensor = Analog detector
2.2.4
(Analog) Sensor Base (ASB)
A sensor is plugged in an ASB, which is connected to a COM loop
(see below).
2.2.5
Conventional detector
Detector with two states, normal or fire alarm. The detector contains a
closing contact and a series alarm resistor. Some types are plugged in
a CDB (see below) but some types are water proof and are not
plugged in any base.
(Conventional detectors are normally plugged in a CDB (see below)
and connected to a conventional zone line with end-of-line device.)
2.2.6
Conventional Detector Base (CDB)
A conventional detector is plugged in a CDB and connected to a
conventional zone line input.
2.2.7
Addressable
A unit with a built-in address device (e.g. a manual call point). Each
unit is individually identified, handled and indicated in EBL128.
(The unit can consequently be an I/O unit, to which one or more
conventional "alarm points" can be connected on the zone line.).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
10
2.2.8
Old detector
Conventional detector with a closing contact (short circuit; no alarm
resistor), or detector with two breaking contacts.
2.2.9
Conventional zone line
Zone line input on e.g. an I/O unit, intended for one or more
conventional alarm points. End-of-line device in the last alarm point.
2.2.10
Addressable zone interface
Unit with a zone line input, intended for one or more conventional
alarm points. End-of-line device in the last alarm point.
2.3
Output unit
Addressable unit with programmable control outputs (e.g. an I/O unit).
To be connected to a COM loop (see below).
2.4
Output / Control output
Defined or programmable function. Relay or (supervised / monitored)
voltage output, in EBL128 or an output unit.
2.5
Short circuit isolator
Addressable unit for automatic isolation of a segment on a COM loop
(see below) in case of short circuit on the loop.
2.6
Display unit (D.U.)
Unit for fire alarm presentation (incl. alarm texts, if programmed).
Connected to an RS485 line.
2.7
COM loop
Loop = a cable (a twisted pair), to which all the addressable Panasonic
COM loop units can be connected. It starts in EBL128 and it returns
back to EBL128.
2.8
Control Unit (C.U.) / C.I.E.
Control Unit = C.U. = Control and Indicating Equipment = A unit,
e.g. EBL128, to which the alarm points are connected. Indicates fire
alarm, fault condition, etc. on the front, i.e. on the Fire Brigade &
Control Panel (see below).
2.9
Fire Brigade Panel (FBP)
The Fire Brigade Panel is a part of the EBL128 front, intended for fire
alarm presentation, etc. for the fire brigade personnel. A separate unit;
an external FBP, can also be connected to EBL128.
In the ext. FBP a printer can be included.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
11
2.10
Control panel (CP)
The Control Panel is a part of the EBL128 front, intended for the
building occupier, service personnel, etc. to "communicate" with
EBL128 / the system.
2.11
LED
LED (Light Emitting Diode) = Yellow, green or red optical indicator
("lamp").
2.12
External Indicator (LED)
A unit with an LED. Connected to an ASB, CDB or a detector with a
built-in LED, for external indication. Lit when the built-in LED is lit.
2.13
Display / LCD
LCD (Liquid Crystal Display) = Display for presentation of fire
alarms, fault messages, etc. Normally alphanumeric characters and
backlight.
2.14
Door open / Key switch
A door / key switch, which has to be activated in order to get access to
the push buttons on the front. Indicated by the LED "Door open".
2.15
SSD / Site Specific Data
This data is unique for each installation. All alarm points,
presentation numbers, alarm texts, programmable outputs, etc. are
programmed (configured) in the PC program Win128 and has to be
downloaded in EBL128.
2.16
S/W / Software / System program
The S/W makes EBL128 (the microprocessor) work. It is factory
downloaded but a new version can be downloaded in EBL128 on site.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
12
3
Overview
3.1
The EBL128 c.i.e.
EBL128 is a microprocessor controlled intelligent fire alarm Control
and Indicating Equipment (c.i.e.) intended for analog addressable
smoke and heat detectors. Also conventional detectors and manual
call points can be used. Programmable inputs, control outputs and I/O
units are available. Up to 128 addresses can be connected to EBL128.
EBL128 is fully compliant with the European standard EN54 parts 2
and 4 and the front is fully SS3654 compliant.
3.2
S/W Versions
Due to continual development and improvement, different S/W
versions can be found. The control unit S/W can be updated on site.
3.3
Documents
The following documents are available:
Planning instructions
Drawings
Operating instructions
Information found in one document is normally not to be found in
another document, i.e. the documents complement each other.
Product Leaflet for EBL128 and other units are available as pdf
documents on our web site: http://www.panasonic-fire-security.com
3.4
Applications
EBL128 is intended for small and medium installations. The
intelligent control unit offer the system designer and end user a
technically
sophisticated
range
of
facilities
and
functions.
Programming (via PC S/W Win128) and commissioning is very easy.
3.5
PC S/W
Win128 is used for programming and commissioning, i.e. to:
create / download / upload (backup) the site specific data (SSD)
download new S/W version, language (text file), EBL128 settings
(e.g. convention), etc.
create / download the alarm texts shown in the display in EBL128,
ext. FBP and/or AA units.
The Win128 S/W shall have the same version number as the EBL128
S/W version number, e.g. 1.0.x. Only x may be different. Old SSD
files can be used with a newer EBL128 S/W version. Open and save
the old SSD file in the new Win128 version before the download. If a
backup is required, use the same Win128 version as the EBL128
version.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
13
4
Control & Indicating Equipment
Figure 1. The EBL128 Control & Indicating Equipment (4550).
Depending on country, convention, configuration, etc. the look,
language and functions might vary. Figure 1 shows an EBL128 with
English front. The metal housing consists of a wall mounted chassis
on which a removable skin, incl. the door, is attached. This makes the
installation and service very easy.
EBL128 is in its basic configuration equipped with:
Main board 4556 with:
o One COM loop (0) to which the loop units are connected.
Connections and more information, see drawing 128-21.
o Two programmable supervised voltage outputs (S0-S1).
Default
programmed
as
outputs
for
alarm
devices.
Connections and more information, see drawing 128-22.
o One programmable relay output (R0). Default programmed as
output for routing equipment (Fire brigade tx). Connections
and more information, see drawing 128-23.
o One not programmable relay output for routing equipment
(Fault tx). Connections and more information, see drawing
128-23.
o One programmable input (I0). Supervised when required.
Connections and more information, see drawing 128-22.
o Two 24 V DC power supply outputs (for routing equipment and
external equipment respectively). Connections and more
information, see drawing 128-22.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
14
o A socket for an optional Communication module (RS485
transceiver component) 4552, which will provide an RS485
interface (serial line) for up to four Display Units (1735 / 1736
and/or 1826 / 1828 and/or 1728). Max. one 1826 with printer.
Connections and more information, see drawing 128-23.
On the RS485 serial line can as an alternative, up to four
German Fire Brigade Control Panels (Feuerwehr-Bedienfeld)
FBF 20033 and/or German Fire Brigade Indicator Panels
(Feuerwehr-Anzeigetableau) FAT 20023 be connected.
o RS232 interface ("D" connector) for a PC with Win128.
Connections and more information, see drawing 128-25.
o RS232 interface for a Web-server 1598. Connections and more
information, see drawing 128-25.
o 24 V DC power supply output for a Web-server 1598.
Connections and more information, see drawing 128-25.
Built-in power supply (rectifier) and space for back-up batteries.
Connections and more information, see drawing 128-24.
Space for optional expansion board holder (Expansion boards
mounting kit 4551). Up to four expansion boards can be
mounted in the holder.
Space for routing equipment.
DIN-rail (and space) for a Web-server 1598.
Cable inlets (rubber grommet / knock-outs) on the top, bottom and
back sides.
The door has a Plexiglas ahead of the front, see Figure 1. A key is
required to open the door to get full access to the push buttons on the
front, i.e. the Fire Brigade Panel (FBP) and the Control Panel (CP).
Figure 2. The EBL128 front. The look might vary depending on
the country (language), configuration, etc. (e.g. English texts as
in the figure). LEDs & push buttons are described in the
EBL128 Operating Instructions.
3 Manufacturer: IFAM GmbH, Erfurt, Germany. www.ifam-erfurt.de
FBP
CP
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
15
The FBP is used by the fire brigade personnel to see which alarm
point / zone having activated the fire alarm(s), silence alarm devices,
reset alarms, etc. In the display (LCD, 2x40 alphanumeric characters),
the information displayed on the first row is depending on how many
alarm points / zones having activated fire alarm, convention and
language.
On the second row is, for the activated alarm point / zone, an alarm
text shown, if programmed. For more detailed information regarding
the display information, see the EBL128 Operating instructions.
Required fire brigade personnel manoeuvres are performed via the
FBP in EBL128 or via an external FBP 1826 / 1828.
Instead of external FBPs 1826 / 1828, German Fire Brigade Control
Panels (Feuerwehr-Bedienfeld) FBF 2003 and/or German Fire
Brigade Indicator Panels (Feuerwehr-Anzeigetableau) FAT 2002 can
be used.
The CP is used by the EBL128 owner, service personnel, etc. to
"communicate" with EBL128, e.g. for monthly tests, disablements
commissioning, maintenance and service. Access codes for different
access levels are required. A keypad is used to get access to the menu
tree, i.e. main and sub menus for data input / output, manoeuvres, etc.
The CP also holds several system status LEDs.
4.1
COM loop
EBL128 has one COM loop (0), to which the loop units are connected.
Connections to "J1:1-4" according to drawing 128-21. On the COM
loop can theoretically 127 COM loop units be connected (i.e. address
1-127). The exact number of addresses that can be used and the cable
length are depending on the cable type (cable resistance) and the total
COM loop unit current consumption (i.e. the type and number of loop
units). See chapter "Current consumption", page 134 and drawing
128-11. Each COM loop unit has a technical address and each alarm
point and zone line input has a presentation number (zone-address).
See the EBL128 Operating Instructions for more information.
If one or more addressable Short Circuit Isolators (SCI 4313 / 4370)
are used, the loop will be divided into "segments", i.e. the part
between two isolators or between EBL128 and one isolator. In case of
short-circuit on the COM loop only the affected segment will be
isolated, which will minimise the number of units "disabled". See
Figure 9, page 43.
Break (cut-off) or short circuit on the COM loop
Normally EBL128 communicates with the units in the A-direction
only and is in the B-direction checking the COM loop voltage only,
which shall be > 12 V DC. There can be no one, one or up to eight
addressable Short Circuit Isolators, 4313 / 4370 (SCI), connected on
the COM loop.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
16
In case of short-circuit or a break (cut-off) on the COM loop, EBL128
will in order to localize it, do the following:
The COM loop voltage and communication will be turned off.
Because of that all isolators will also be turned off, i.e. the L
(SA) contact in each isolator will be "open".
The COM loop voltage and communication will be turned on
again.4 The isolators will now be turned on one after another
in the A-direction, until it is not possible to turn on any more
isolator, i.e. the isolator closest to a short-circuit will not be
turned on alt. the isolator closest to (just before) a break will
be turned on but the isolator after a break can of course not be
turned on.
The COM loop communication will now start in the B-
direction also and the isolators will be turned on one after
another, until it is not possible to turn on any more isolator,
i.e. the isolator closest to a short-circuit will not be turned on
alt. the isolator closest to (just before) a break will be turned
on.
In case of short-circuit on the COM loop, only the segment(s)
between the now turned off isolators will be isolated.
One or more fault messages will be shown in the EBL128
display, see below.
The fault messages will be different depending on if it is a single or
double break or short-circuit on the COM loop, as well as if there is
no one, one or several isolators connected on the COM loop, see
following chapters.
In any case, each unit not found by EBL128 will generate a fault:
FAULT: No reply xx-xx
Press "" to see the technical address.
FAULT: No reply techn. address xxx
Regarding
Fault
acknowledge,
see
the
EBL128
Operating
Instructions.
4.1.1
A single break (cut-off) on the COM loop
If not all units are found when communicating in the A-direction
only, but when communicating in both directions, it must be a single
break (cut-off) on the COM loop. One fault will be generated and the
following fault message will be shown:
4 Short-circuit on a COM loop with no isolators: The voltage and
communication will not be turned on.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
17
FAULT: Cut-off SCI n <-> SCI n
n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7 depending on if no one, one or several
isolators are used. A & B are the built-in control unit isolators in the
A- and B-direction respectively.
If no isolator is used the information will be: A<->B.
If one isolator (no. 0) is used: A<->0 or 0<->B
If two isolators (no. 0 and no. 1) are used: A<->0, 0<->1 or
1<->B
...and so on.
The break (cut-off) is found in the specified segment, e.g. A<->0.
Each 10th minute a new attempt is made to communicate in the A-
direction only.
When the fault is corrected (no break / cut-off) the communication
automatically returns to communicate in the A-direction only.5
4.1.2
Several breaks (cut-offs) on the COM loop
If not all units are found when communicating in the A-direction
only, and not when communicating in both directions, there must be
two or more breaks on the COM loop. A "no replay fault" (see
above) will be generated for each unit not found.
There will also the following fault message:
FAULT: Cut-off SCI n <-> SCI n
n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7 depending on if no one, one or several
isolators are used. A & B are the built-in control unit isolators in the
A- and B-direction respectively.
In case of a break (cut-off) in more than one segment there will also
be the following message:
FAULT: Several faults on COM loop
In case of "Several faults on COM loop": Correct the cut-off fault
shown in the display and the next cut-off fault will be shown, and so
on.
Each 10th minute a new attempt is made to communicate in the A-
direction only.
When all faults are corrected (no breaks / cut-offs) the communication
automatically returns to communicate in the A-direction only.5
5 NOTE! The fault has to be acknowledged and it can last up to 10 minutes
before the communication returns to communicate in the A-direction only.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
18
4.1.3
Short-circuit on the COM loop
Short-circuit between the L (SA) and C (SB) wires6 will generate a
fault with the following fault message:
FAULT: Short-circuit SCI n <-> SCI n
n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7 depending on if no one or several
isolators are used. A & B are the built-in control unit isolators in the
A- and B-direction respectively.
If no isolator is used the information will be: A<->B.
If one isolator (no. 0) is used: A<->0 or 0<->B
If two isolators (no. 0 and no. 1) are used: A<->0, 0<->1 or
1<->B
...and so on.
The short-circuit is in the specified segment, e.g. A<->0.
In case of short-circuit in more than one segment on the COM loop,
the fault messages will be similar to the message shown for several
breaks (cut-offs), FAULT: Several... (see above).
Each 10th minute a new attempt is made to communicate in the A-
direction only.
When the fault is corrected (no short-circuit) the communication
automatically returns to communicate in the A-direction only. 5
4.2
Programmable voltage outputs (S0-S1)
The outputs S0-S1 are normally supervised (monitored).7 One to five
33K resistors can be connected. Connections to "J1:5-8" according to
drawing 128-22. When the connections are finished, a calibration has
to be done.8 See also the EBL128 Operating Instructions chapter
"Calibration of supervised outputs (menu H5/A3)".
Each output has to be programmed (via Win128) regarding:
Type (Control, Fire ventilation, Alarm device, etc.)
Output signal period (steady, intermittent, pulse, delay, etc.)
Supervised / Not supervised
Logic, i.e. normally low (default) or normally high (24 V DC)9.
Control expression (containing one or more trigger conditions)
NOTE! The outputs S0-S1 are as default programmed as outputs for
alarm devices.
S0: max. 500 mA (Fuse F8).
6 Depending on the cable type / length and where the loop short-circuit is
located, it can take up to 10 seconds before the fault is generated.
7 A normally high output can not be supervised. The supervision voltage is
1.5 – 3.6 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to activated output.
8 The calibrated value has to be in the range 4K7 – 50K.
9 Regarding system voltage, see chapter "Technical data", page 143.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
19
S1: max. 200 mA (Fuse F6).
See also Win128 help or chapter "Programmable outputs", page 61.
4.3
Programmable relay output (R0)
Connections to "J1:17-19" according to drawing 128-23.
The output has to be programmed (via Win128) regarding:
Type (Control, Fire ventilation, Alarm device, etc.)
Output signal period (steady, intermittent, pulse, delay, etc.)
Logic, i.e. normally open or normally closed.10 11
Control expression (containing one or more trigger conditions).
NOTE! The output R0 is as default programmed as output for
Routing equipment (Fire brigade tx).12 Activated output is indicated
by the LED "Fire brigade tx".13 This output can be disabled via "door
open" or via menu H2/B9. This output can be tested via menu H1, see
the EBL128 Operating Instructions.
See also Win128 help or chapter "Programmable outputs", page 61.
4.4
Relay output for routing equipment (fault
tx) (R1)
Connections to "J1:20-22" according to drawing 128-23.
Not programmable relay output.11 This output for routing equipment
(Fault tx) is activated during normal operation and will be de-activated
when a fault is generated in EBL12814. De-activated output is also
indicated by the LED "Fault tx activated". This output can be tested
via menu H1, see the EBL128 Operating Instructions.
4.5
Programmable input (I0)
Connections to "J1:9-10" according to drawing 128-22.
The input has to be programmed (via Win128) regarding:
Type ("trigger condition")
Supervised / Not supervised
Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or Normally closed (low resistance, 680R, when supervised)
Additional information depending on selected type
10 In this case: Relay normally not activated / Relay normally activated.
11 Relay contact ratings (COM / NO / NC): max. 2 A @ 30 V DC.
12 A control expression is also required, i.e. Fire Brigade Tx.
Regarding "Fire brigade tx", see also chapters "Alert Annunciation", page 92
and "Fire alarm type A and Fire alarm type B", page 96.
13 It is possible to use a programmable input with trigger condition Activated
routing equipment, to turn on the LED instead.
14 Also if EBL128 becomes powerless (dead) and for "Watch-dog fault".
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
20
See also Win128 help or chapter "Programmable inputs", page 54.
4.6
24 V DC power supply outputs
The two 24 V DC15 outputs can be used for:
Power supply of routing equipment (fire brigade tx / fault tx).
Max. 200 mA (Fuse F7).
Power supply of external equipment, e.g. ext. FBP 1826 / 1828,
AAU 1735 / 1736, EPU 1728, etc. Max. 500 mA (Fuse F916).
Connections to "J1:11-12 & 13-14" according to drawing 128-22.
4.7
RS232 interfaces
The two interfaces can be used for:
Win128 (PC program). (9 ways female "D" connector)
Web-server II 1598. (3 ways Molex connector)
Connections to "J3" & "J5" according to drawing 128-25.
4.8
RS485 transceiver (option)
There is a socket on the main board 4556 where an optional RS485
transceiver communication module 4552 can be mounted. This
transceiver provides an interface (screw terminals J1:15-16) for up to
four Display Units, i.e. ext. FBP 182617 / 1828 and/or AAU 1735 /
1736 and/or EPU 1728 running in S/W mode xxxx – 158718. The
data rate in this mode is 9600 baud and max. cable length is 1200 m.
Connections to "J1:15-16" according to drawing 128-23.
On the RS485 serial line can as an alternative be connected up to four
German Fire Brigade Control Panels (Feuerwehr-Bedienfeld) FBF
20033 and/or German Fire Brigade Indicator Panels (Feuerwehr-
Anzeigetableau) FAT 20023.
4.9
Power supply
Connectors for the built-in power supply units:
Rectifier 230 V AC / 24 V DC (Two tab terminals, 6.35x0.8
mm, +24V / 0V)
Batteries19 (2 x 12 V, 16 Ah), 24 V (Two tab terminals,
6.35x0.8 mm, BATT + / BATT -)
15 Regarding system voltage, see chapter "Technical data", page 143.
16 Fuse F9 is also for the 24 V DC internal power supply output for Web-
server 1588 / 1598, see drawing 128-25.
17 Max. one with printer.
18 xxxx = type of display unit (e.g. 1826/28). For more information about
each type of unit, see chapter "Other units", page 51.
19 Batteries are not included in the c.i.e. type number, i.e. batteries have to be
ordered separately.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
21
Connections to "J2:1-5" according to drawing 128-24.
4.10
Internal Power supply
Connector for the Web-server II 1598 power supply:
24 V DC15 output (3 ways Molex connector).
Max. 500 mA (Fuse F920).
Connections to "J4" according to drawing 128-25.
20 Fuse F9 is also for the 24 V DC power supply output for external
equipment, see drawing 128-22.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
22
5
Expansion boards 458x
Inside EBL128, in an optional expansion board holder 4551, can up to
four optional expansion boards of types 4580, 4581 and 4583 be
mounted. A supplied ribbon cable is used for the connection of the
expansion board(s) to the main board. (Connector "J2" on the
expansion board respectively and "J13" on the main board 4556.) See
drawings 128-02 & -03.
Figure 3. 8 zones expansion board 4580, 8 relays expansion
board 4581 and Inputs and outputs expansion board 4583.
I/O Matrix board 458221 is a special type of expansion board
plugged as a "piggy back" to an Application board (Fan, Generic or
Zone). The Application board is connected to the COM loop and to
24 V DC. Up to four 4582 boards can always be used and up to eight
if no expansion board of type 4580, 4581 or 4583 are used.
Figure 4. I/O Matrix board 4582.
Each expansion board 4580-4583 has to have an expansion board
address (0-7) set via jumpers on the expansion board respectively. On
boards type 4580, 4581 and 4583 are the jumpers "JP2-JP4" used and
on board type 4582 are the jumpers "JP1-JP3" used, see Figure 5
below.
Win128 is used for all expansion board programming. For more
information see Win128 help.
21 The I/O Matrix board 4582 is available on the Australian market only,
since it requires an Application board not found in the Panasonic product
range.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
23
5.1
Expansion board address setting
The expansion board address is set via jumpers on the expansion
board respectively.
Board
address
4580, 4581 and 4583
4582
JP2
JP3
JP4
JP1
JP2
JP3
0
Open
Open
Open
Open
Open
Open
1
Shunted
Open
Open
Shunted
Open
Open
2
Open
Shunted
Open
Open
Shunted
Open
3
Shunted
Shunted
Open
Shunted
Shunted
Open
4
Open
Open
Shunted
Open
Open
Shunted
5
Shunted
Open
Shunted
Shunted
Open
Shunted
6
Open
Shunted
Shunted
Open
Shunted
Shunted
7
Shunted
Shunted
Shunted
Shunted
Shunted
Shunted
Figure 5. Expansion boards 4580 - 4583. Jumpers for
expansion board address setting.
5.2
8 zones expansion board 4580
NOTE! P.C.B. NO. 9287-2B and 9287-3A exists. When 9287-3A is
required is indicated below.
Each board has to be programmed via Win128 regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5 above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
an end-of-line device has to be connected, depending on the selected
"Type of zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing 128-30.
Each zone line input has to be programmed via Win128 regarding:
Type of zone line input (see below), depending on detectors / end-
of-line device (capacitor or resistor), i.e. different threshold levels
etc.
Alarm at short circuit / Not alarm at short circuit (i.e. if short-
circuit on the zone line shall generate a fault or a fire alarm)
Zone number (no address)
Fire alarm delay / No fire alarm delay
Text (Alarm text when required)
Alert annunciation time channel
Disablement time channel
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
24
For more information, see the Win128 help.
The terminal block terminals support a wire size up to 1.13 mm2 (1.2
mm).
5.2.1
Type of zone line input
Not used shall be selected for a not used input.
One of the following types can be selected.
5.2.1.1
Zone line input (EOL capacitor)
This type shall normally be used. It has the lowest zone line current
consumption since the end-of-line device is a capacitor, 470 nF (±10
%). Max. allowed cable resistance is 50 ohm. Max. allowed cable
capacitance is 50 nF. Max. allowed zone line current consumption is
1.5 mA.
5.2.1.2
EX zone line input (EOL resistor)
This type shall be used when units for Hazardous (Ex) areas shall be
connected, i.e. via the Galvanic isolator MTL5061 (2820). The end-
of-line device has to be a resistor, 10K (±5 %) with a body surface
area > 230 mm2 (supplied with the Galvanic isolator). Max. allowed
cable resistance is 40 ohm. Max. allowed cable capacitance is 70 nF.
Max. allowed zone line current consumption is 1.0 mA.
5.2.2
Input states
Each input will be in one of six different states.
5.2.2.1
Normal state
This is the normal zone line input state, i.e. no alarm, no fault, etc. and
the nominal voltage is 24 V DC22. From this state any other state can
be reached / activated.
5.2.2.2
High current state
Max. current consumption limit23 for the zone line input is exceeded,
which is indicating that e.g. too many alarm points are connected.
This generates a fault condition in EBL128. From this state any other
state can be reached / activated except the open circuit state.
5.2.2.3
Alarm state
An alarm point on the zone line is in alarm state and the alarm limit23
for the zone line is exceeded, which activates fire alarm in EBL128.
In this state short-circuit, open circuit, high current and low voltage
states cannot be reached / activated. After alarm reset the zone line
input will return to the normal state.
22 Allowed voltage 15-28 V DC.
23 This limit is depending on the selected input mode.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
25
5.2.2.4
Short-circuit state
Short-circuit current limit23 is exceeded, indicating short-circuit on the
zone line, which generates a fault condition in EBL128.
5.2.2.5
Open circuit state
Open circuit current limit23 is passed, indicating no or too low zone
line current consumption, i.e. the end-of-line device is not detected,
which generates a fault condition in EBL128. From this state any
other state can be reached / activated.
5.2.2.6
Disconnected state
Via menu H5/A2 (Disconnect / Re-connect zone line) the zone line
input can be disconnected24, i.e. there is no voltage on the zone line.
From this state no other state can be reached / activated.
5.2.2.7
Low voltage state
Zone line low voltage limit (15 V DC) is passed without the high
current state is activated, indicating some H/W fault. This generates a
fault condition in EBL128. From this state any other state can be
reached / activated.
5.3
8 relays expansion board 4581
Each board has to be programmed via Win128 regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5, page 23.
The 4581 board has eight programmable relay outputs (Output 0-7).
Connections to "J1:1-16" and "J2" according to drawing 128-31.
Each output has to be programmed via Win128 regarding:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (NO) or normally closed (NC)
contacts25
Control expression (one or more trigger conditions)
For more information, see Win128 help and chapter "Programmable
outputs", page 61.
The terminals support a wire size up to 1.13 mm2 (1.2 mm).
5.4
Inputs and outputs expansion board 4583
Each board has to be programmed via Win128 regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5, page 23.
24 This indicated in EBL128 by the LED "Disablements".
25 Relay contact ratings: Max. 2A @ 30 V DC.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
26
The I/O expansion board 4583 has two programmable supervised or
not supervised voltage outputs (Output 0-1), one programmable
special output (Output 2) for German extinguishing system and five
programmable supervised or not supervised inputs (Input 0-4).
Connections to "J1:1-16" and "J2" according to drawing 128-03 sheet
2/2.
Output 0-1 has to be programmed via Win128 regarding:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Supervised / Not supervised26
Logic, i.e. normally low (default) or normally high (24 V DC)27.
Control expression (containing one or more trigger conditions)
One to five 33K resistors can be connected. When the connections are
finished, a calibration has to be done. Calibration value has to be in
the range 4K7-50K. See also the EBL128 Operating Instructions
chapter "Calibration of supervised outputs (menu H5/A3)".
Voltage Output 0 (J1:1-2): max. 200 mA (Fuse F1). "E"
(Brandmeldung)
Voltage Output 1 (J1:5-6): max. 200 mA (Fuse F2). "G" FSK öffnen
See also Win128 help or chapter "Programmable outputs", page 61.
Output 2 has to be programmed via Win128 regarding:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (default) or normally closed.
Control expression (containing one or more trigger conditions)
Output 2 (J1:11-12): Normally open (high resistance, 3K3, when
supervised) or Normally closed (low resistance, 680R, when
supervised). German extinguishing system (Löschanlage).
See also Win128 help or chapter "Programmable outputs", page 61.
Input 0-4 has to be programmed via Win128 regarding:
Type ("trigger condition")
Supervised / Not supervised
Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or Normally closed (low resistance, 680R, when supervised)
Additional information depending on selected type
26 A normally high output can not be supervised. The supervision voltage is
1.5 – 3.7 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to an activated output.
27 Regarding system voltage, see chapter "Technical data", page 143.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
27
Input 0 (J1:3-4): Fire alarm routing equipment fault (Melder
quittung)
Input 1 (J1:7-8): German key cabinet (FSK rückmeldung)
Input 2 (J1:9-10): German key cabinet (FSK überwachung)
Input 3 (J1:13-14): German extinguishing system (Löschanlage
ausgelöst)
Input 4 (J1:15-16): German extinguishing system (Löschanlage
quittung)
See also Win128 help or chapter "Programmable inputs", page 54.
5.5
I/O Matrix board 4582
A special type of expansion board that can only be used together with
an Application board (Fan, Generic or Zone).21
The I/O Matrix board makes it possible for any retailer to manufacture
and connect three different types of "Application boards" to EBL128
via the COM loop.
I/O
Matrix
board
4582
I/O
Matrix
board
4582
I/O
Matrix
board
4582
EBL512
C.i.e.
COM loop
24 V DC
Type:
Generic
Zone
Fan
Generic
c.i.p. board
Fan c.i.p. board
Zone c.i.p. board
Application
boards:
Fan c.i.p.
Mimic panel / New Zealand i.p.
Zone c.i.p.
No. 0
No. 1
No. 3
NOTE!
Up to 16 I/O Matrix board 4582 per EBL512 C.i.e.
Up to 4 (No. 0-3) I/O Matrix board 4582 per COM loop.
Up to 4 I/O Matrix boards type Generic and/or Zone per EBL512 C.i.e.
Figure 6. I/O Matrix board application overview. The COM
loop and 24 V DC are internally connected to the I/O Matrix
board.
The I/O Matrix board (80 x 63 mm) is plugged ("piggy back"
connection) to the Application board respectively and has 16 inputs
and 48 outputs. The COM loop and 24 V DC is connected to
Application board.
Three different application board types can be selected via jumpers
(JP4-JP5) on the I/O Matrix board:
Generic control and indicating panel (Mimic panel alt. New Zealand
indication panel), with 16 inputs (any input trigger condition can be
used) and 48 outputs (any output trigger condition can be used).
Fan control and indicating panel, for four Fan control panels, each
with six LED:s (On / Auto / Off / Running / Stopped / Fault) and three
push buttons (On / Auto / Off). One "Reset" switch. Can be used for
a "Supply air fan" or a "Standard fan".
Zone control and indicating panel, with outputs and inputs for 16 zone
LED:s (Alarm / Fault / Disabled) and 16 push buttons (Disable).
There is no COM loop address to be set. Instead, the expansion
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
28
board address (0-7) is set with jumpers (JP1-JP3) on the I/O Matrix
board respectively.
Up to four I/O Matrix boards can be used and up to eight if no
expansion boards of types 4580, 4581 and 4583 are used. but max.
two I/O Matrix boards of the types Generic and Zone respectively.
In EBL128 can totally up to 200 outputs be used, including all kinds
of outputs.
For more information (e.g. application board type selected via jumpers
JP4-JP5), see the I/O Matrix board 4582, Technical description
MEW00914.
Each I/O Matrix board has to be programmed via Win128
regarding:
Address, set via jumpers "JP1-JP3", see Figure 5, page 23.
Type of board (Generic / Fan control / Zone control)
LED test on Input 15 or no LED test on Input 15
The 4582 board has 48 LED outputs and 16 switch inputs (0-15).
Depending on if the Application board is of the type Generic, Fan or
Zone, the outputs and inputs are programmed differently.
5.5.1
Generic
Used for application board type Generic.
Each output (0-47) has to be added and programmed via Win128
regarding:
Output no. (0-47)
Properties like for any programmable relay output.
Each input (0-15) has to be added and programmed via Win128
regarding:
Input no. (0-15)
Type (of input)
Properties (e.g. zone-address, alarm text) like for any
programmable input.
5.5.2
Fan control
Used for application board type Fan control.
Each Fan control28 (0-3) has to be added programmed via Win128.
Each Fan control (0-3) contains four Fan control panels for control of
one fan each.
For each fan, one COM loop unit, I/O unit for fan control 3361, has
to be added and programmed via Win128 regarding:
28 The Fan control is only available on the Australian market.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
29
Technical address (COM loop address 1-127)
Fan control information
I/O Matrix fan control (Fan control 0-3)
Supervised or not supervised
Properties as for any programmable output
Normally stopped or Normally running
5.5.3
Zone control
Used for application board type Zone control.
Each input (0-15) has to be programmed via Win128 regarding:
Zone (control) no. (0-15)
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
30
6
Peripheral devices
Alarm points are connected to the COM loop.29
Wireless smoke detectors are "connected" to a Base station, which is
connected to the COM loop.
Short circuit isolators are connected to the COM loop.
I/O Matrix boards30 are plugged ("piggy back") to an Application
board (Fan, Generic or Zone), which is connected to the COM loop.
Sounders, door release magnets, etc. are connected to the
programmable outputs in EBL128 (S0-S1 and/or R0) and/or to output
units connected on the COM loop. Addressable sounders (alarm
devices) are connected directly on the COM loop.
Input devices as key cabinet, timer, external fault, etc. are connected
to programmable inputs, i.e. to input (I0) in EBL128 and/or to input
units connected to the COM loop.
Display units31 are connected to the RS485 interface in EBL128.
Alternatively, German Fire Brigade Control Panels (Feuerwehr-
Bedienfeld) FBF 20033 and/or German Fire Brigade Indicator Panels
(Feuerwehr-Anzeigetableau) FAT 20023 are connected to the RS485
interface in EBL128.
Routing equipment (Fire brigade tx / Fault tx) is normally connected
to the R0-R1 outputs in EBL128. Regarding the Fire brigade tx, see
chapter "Fire alarm type A and Fire alarm type B", page 96.
German routing equipment, key cabinet and extinguishing system are
connected to programmable inputs / outputs in EBL128 and
Expansion board 4583.
For more information, see the following chapters and/or the Product
Leaflets on our web site: http://www.panasonic-fire-security.com
6.1
COM loop units
The COM loop can handle up to 127 addressable COM loop units.32
NOTE!
Depending on the type of units and the number of units the total
current consumption will vary. This and the cable resistance will
affect the cable length.
See also chapter "Current consumption", page 134 and drawing 128-
11.
29 Directly (addressable) or via an input unit 3361. The programmable input
I0 in EBL128 can be used as a fire alarm input (NO/NC).
30 The I/O Matrix board 4582 is described in chapter "Expansion boards
458x", page 22.
31 External Presentation unit 1728, External Fire Brigade Panel 1826 / 1828
and Alert Annunciation unit 1735 / 1736
32 Conventional detectors can be connected to an 8 zones expansion board
4580 or to the zone line input (Z) on each addressable I/O unit 3361.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
31
The following units (in NORMAL mode) can be connected to the
COM loop:
Address setting / Technical address
Each COM loop unit has to have a unique technical address (001-
127). This address and the mode are set with an Address Setting Tool
3314. For EBL128 is always the NORMAL mode used (default).
NOTE! The technical address for Addressable Base station for
wireless units is set on a DIL-switch in the unit respectively.
The technical address for a wireless detector is depending on which
Base station it is "connected" to, see chapter "Other COM loop units",
page 44.
6.1.1
Input units
Each COM loop input unit is added and programmed via Win128.
Depending on type of unit, regarding:
Technical address (001-127)
Name (normally not changed)
Zone number and Address within the zone
Two-units-dependent fire alarm, i.e. co-incidence alarm (if you
wish / some units only)
Quiet alarm or not (Australian function)
Alert annunciation & Time Channel (if you wish / some units
only)
Disablement & Time Channel (if you wish / some units only)
Alarm text (if you wish)
Regular Alarm algorithm (some units only)
Alternative Alarm algorithm & Time Channel (if you wish / some
units only)
and 3339)
and 3379)
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
32
Figure 7. An example of a Win128 dialog box is the "Analog
photo electric smoke detector 4301" properties dialog box.
For more information, see Win128 help.
Connections, if nothing else is specified, see drawing 128-21.
6.1.1.1
Analog Sensor Bases (ASB)
3312 Analog Base. An analog detector (Sensor) is to be plugged in
3312. Terminals for ext. LED 2217 / 2218. Prepared for
mechanical lock of the detector. Recess for label holder 3391.
The base has an address label on which the plugged-in
detector's technical address is to be written.
3313 Analog Base. Like 3312 but instead of screw terminals for the
COM loop and ext. LED this base has fast connectors.
3314 Analog Base. Like 3312FL but no connector for ext. LED.
4313 Analog Base with isolator. An analog detector (Sensor) is to be
plugged in 4313. Terminals for ext. LED 2217 / 2218.
Prepared for mechanical lock of the detector. Recess for label
holder 3391. It has also a built-in short circuit isolator with the
same function as the Addressable short circuit isolator 4370
(see page 42). The isolator's technical address is set with an
Address setting tool (AST) 3314. The base has an address label
on which both the plugged-in detector's technical address and
the isolator's technical address are to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 4313 in EBL128.
3312FL
3312F
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
33
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
6.1.1.2
Addressable Manual Call Points
3333 Addressable Manual Call Point.33 Conforms to EN54-11. A
built-in LED will indicate that fire alarm is generated, i.e. the
glass is broken. Routine testing can be performed with a
supplied test key without breaking the glass. A hinged
polycarbonate flap is protecting the glass. The technical
address is set with an Address setting tool (AST) 3314. The
call point has an address label on which the programmed
technical address is to be written.
3333 is to be surface mounted in the supplied red backbox or
flush mounted in a Swedish 65mm circular mounting box. For
indoor use and in dry premises.
The Address setting tool 3314 is also used for mode setting.
NORMAL mode: Flashing or not flashing LED (see Product
leaflet MEW00097) is set via Win128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
3339 Enclosed Addressable Manual Call Point.33 Like the 3333 unit
but another type of front cover and backbox. For surface
mounting. For indoor use in premises where IP67 rating is
required.
6.1.1.3
Analog Detectors
3308 Analog heat detector. To be plugged in an ASB base 3312.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Prepared for mechanical lock (screw
attached). The technical address is set with an Address setting
tool (AST) 3314. The detector has an address label on which
the programmed technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: 3308 is in this mode via Win128 set to one
of three algorithms (static response temp. range) for class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
3309 Analog heat detector. Enclosed (IP67)34. Built-in LED that is
lit to indicate that the detector has generated fire alarm.
33 In all conventions the manual call points have a response time < 5 s.
34 As from January 2005, this detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 70°C), -20°C < Ta < 65°C.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
34
Terminals for ext. LED 2217 /2218. Recess for label holder
3391. The technical address is set with an Address setting tool
(AST) 3314. The Address setting tool 3314 is also used for
mode setting:
NORMAL mode: 3309 is in this mode via Win128 set to one
of three algorithms (static response temp. range) for class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
4300 Analog multi detector. A smoke detector and a heat detector
within one housing. Scattered light (i.e. reflection of infrared
light) is used to detect smoke and the heat sensing element is a
thermistor.
The detector has unleaded soldering.
To be plugged in an ASB base 3312. Built-in LEDs are lit to
indicate that the detector35 has generated fire alarm. Prepared
for mechanical lock (screw attached).
Via Win128 it is programmable how the detectors shall operate:
a)
Two presentation numbers (addresses): The detector
unit works as two separate detectors. The smoke detector is
programmed for one zone-address and the heat detector for
another zone-address36. (Can be used to disable one of the
detectors during working hours and in control expressions for
programmable outputs). The detector unit has one technical
address used for programming and fault presentation.
b)
One presentation number (address): The detector unit
works as one detector and is programmed for one zone-address.
The detector unit (actually the heat detector) can detect a
methylated spirits fire (EN54-9, test fire TF6; liquid fire), which
normally is impossible for a photo electric smoke detector to
detect. The detector unit has one technical address used for
programming and fault presentation.
It is, via Win128, programmable if the detectors in alt. b) shall
work with "OR-functionality" or with a "Decision algorithm":
b1)
OR-functionality: Either the heat detector or the
smoke detector will activate fire alarm. This alternative is
recommended in most cases. The detector unit has one
technical address used for programming and fault
presentation.
35 I.e. the heat detector and/or the smoke detektor.
36 The zone number has to be the same for both detectors. NOTE! When
counting alarm points these "two detectors" are regarded as two alarm points.
Zone-Addr.
001-01 (smoke)
001-02 (heat)
Techn. addr.
123
Zone-Addr.
001-01 (smoke
or heat)
Techn. addr.
123
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
35
b2)
Decision algorithm:
Fire alarm will be activated if:
temperature (°C) + adjusted smoke value 37 > 58.
Pre-warning will be activated if:
58 > temperature (°C) + adjusted smoke value37 > 50.
The "Decision algorithm" 38, see figure can be used to
reduce so called false alarms (nuisance alarms), because at
a normal room temperature, more smoke is required to
activate fire alarm than when the room temperature is high
(or is rising). By a real fire, the room temperature will rise
rather fast and less and less smoke is required to activate
fire alarm. Very little smoke require a "high" temperature
to activate fire alarm and very much smoke will activate
fire alarm also at a "low" temperature.
0
10
20
30
40
50
60
70
0
4
8 12 16 20 24 28 32 36 40 44 48 52 56 60
Smoke value
Temperature
Figure 8. When the calculated value in the decision algorithm
exceeds the lower graph, pre-warning will be activated. When it
exceeds the upper graph, fire alarm will be activated.
Temperature = °C. Smoke value = obscuration (%/m) x 10.
The technical address is set with an Address setting tool (AST)
3314. The detector has an address label on which the
programmed technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: 4300 in this mode is in Win128, for the
smoke detector, set to one of six algorithms H-15, H-35, L-15,
37 Adjusted smoke value = obscuration (%/m) x 10. Default heat alarm
levels (50°C / 58°C) and smoke alarm offsets (50 / 58) can be changed via
Win128. The temperature can not be lower than 0°C in the algorithm / graph.
38 The decision algorithm is a violation to the EN54-7 standard.
20°C => 3.8 %/m
↓ ↓
40°C => 1.8 %/m
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
36
L-35, N-15 or N-35 and for the heat detector set to one of three
algorithms for class A1 (static response temp. 54-65°C), A2 S
(54-70°C) or B S (69-85°C).
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
4301 Analog photo electric smoke detector. Scattered light (i.e.
reflection of infrared light) is used to detect smoke.
The detector has unleaded soldering.
To be plugged in an ASB base 3312. Built-in LEDs are lit to
indicate that the detector has generated fire alarm. Prepared for
mechanical lock (screw attached).
The technical address is set with an Address setting tool (AST)
3314. The detector has an address label on which the
programmed technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: 4301 in this mode is in Win128 set to one of
the six algorithms H-15, H-35, L-15, L-35, N-15 or N-35.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
6.1.1.4
Conventional Detector Bases (CDB)
2324 Base. A conventional detector is to be plugged in 2324. Built-
in LED that is lit to indicate that the detector plugged in the
base has generated fire alarm. Terminals for ext. LED 2217 /
2218.
6.1.1.5
Conventional Detectors
4318 Combination heat detector. Rate-of-rise and fixed temperature,
59°C, heat detector class A1 R. Static response temp. range 54-
65°C, ambient temp. min./typical/max. -10/+25/+50°C.
Has replaced 2318. To be plugged in a CDB 2324.
4350 Multi detector. A smoke detector and a heat detector within
one housing. Scattered light (i.e. reflection of infrared light) is
used to detect smoke and the heat sensing element is a
thermistor. In order to secure the fire detection and to prevent
false (nuisance) alarms, the AI function is used, i.e.
a: combined heat and smoke sensing
b: variable delay function
c: adaptive learning function
See also chapter "Cyber sensor functions", page 111.
The detector has unleaded soldering.
To be plugged in a CDB 2324.
4352 Photoelectric smoke detector. Scattered light (i.e. reflection of
infrared light) is used to detect smoke. An advanced alarm
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
37
algorithm is used to secure the smoke detection and to prevent
false (nuisance) alarms, e.g. a minimum of nine consecutive
readings over the fire alarm level are required, before the
detector goes into alarm. (One reading per sec.)
The detector has unleaded soldering.
To be plugged in a CDB 2324.
4375 Heat detector. Fixed temperature heat detector, 60°C, class
A2S (static response temp. range 54-70°C), latching.
Min./typical/max. ambient temp. -10/+25/+40°C.
The detector has unleaded soldering. Has replaced 6275.
To be plugged in a CDB 2324.
4376 Heat detector. Fixed temperature heat detector, 80°C, class BS
(static response temp. range 69-85°C), latching.
Min./typical/max. ambient temp. -10/+40/+60°C.
The detector has unleaded soldering. Has replaced 6276.
To be plugged in a CDB 2324.
6295 Heat detector: Enclosed (IP67)39. Fixed temperature (57°C)
heat detector, class A2 S (static response temp. range 54-70°C),
latching. Min./typical/max. ambient temp. -40/+25/+50°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6296 Heat detector: Enclosed (IP67)40. Fixed temperature (72°C)
heat detector, class B S (static response temp. range 69-85°C),
latching. Min./typical/max. ambient temp. -40/+40/+65°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6297 Heat detector: Enclosed (IP67). Fixed temperature (87°C) heat
detector, class C S (static response temp. range 84-100°C),
latching. Min./typical/max. ambient temp. -40/+55/+80°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6298 Heat detector: Enclosed (IP67). Fixed temperature (117°C) heat
detector, class E S (static response temp. range 114-130°C),
latching. Min./typical/max. ambient temp. -40/+85/+110°C.
Terminals for ext. LED 2217 / 2218 (to indicate that the
detector has generated fire alarm). NOTE! No built-in LED.
6.1.1.6
Accessories
3314 Address setting tool. Is used to write or read the COM loop
units' technical address (001-127). It is also used to write or
39 As from January 2005, this detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < Ta < 50°C.
40 As from January 2005, this detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < Ta < 65°C.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
38
read the mode, NORMAL or 2330 (see the unit respectively).
A connection cable (with crocodile clips and tab terminals) is
attached and can be used when required.
Put the ON/OFF switch in position ON and wait for a beep.
Plug the detector into 3314 (SA & SB terminals) or when
required, use the connection cable.41
How to read: Press "READ", wait for a beep and read the
address and mode.
How to write: Press "WRITE" and "READ" at the same time to
select the mode and/or write the address. Press "WRITE" and
wait for a beep. ("READ" again as a check.)
3390 Label holder. To be mounted on the analog base 331242.
Intended for a label with "zone-address", "technical address",
etc. to be read also when the detector is plugged in its base. 100
label holders per packet. Excl. labels.
3391 Labels for 3390. Packet with self-adhesive white labels for
label holder 3390. 10 A4-sheets à 132 labels for laser printer
usage. The print-out is done via Win128.
6.1.2
Addressable I/O units
3361 Addressable multipurpose I/O unit.43 Power supplied via the
COM loop. Up to 16 I/O units 3361 can be used.
The unit has two programmable inputs:
Monitored input
….used as zone line input (Z): End-of-line capacitor 470 nF
mounted in the last unit on the line. A short circuit can activate
fault or fire alarm (set via Win128). This input is intended for
conventional detectors.44
used as general input (In0): An input for NC or NO
contacts (set via Win128).
Isolated input (In1): An optocoupler input (external 24 V DC
/ 8 mA is required). Normally low or high (set via Win128).
41 Some units have flying leads for easier connection. After use they might
be disconnected and thrown away.
42 Also in the enclosed analog heat detector 3309.
43 The same physical unit (3361) is also used for the Australian Fan control
function and has a separate dialog box in Win128.
44 It is via Win128 possible to define this input functioning like a manual call
point ("Used as MCP"), i.e. it will not be collectively disabled via menu
"Disable zone, H2/B1", can not be included in two-unit dependence, it can
not use the "alarm delay" function and it can not be disabled via a time
channel.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
39
The unit has two programmable relay45 outputs:
Relay output (Re0): NC or NO contacts (set via Win128).
Relay output (Re1): NC or NO contacts (set via Win128).
Connections and examples, see drawings 128-21 & -26. The
unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required,
the unit can be mounted in a Waterproof box (IP66 / 67) 3362.
The unit has an LED to indicate communication to the unit or
alarm condition. For more information, see the Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The unit has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3361 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.
3364
Addressable 2 voltage outputs unit. The unit is connected
directly to the COM loop. External 24 V DC power supply is
required (via a 3366 unit or EBL128).
The unit has two programmable and supervised voltage outputs
(VO0-VO1), intended for alarm devices (e.g. sirens). An end-
of-line capacitor (470nF) is to be mounted in the last device
alt. a capacitor (470nF) in up to five alarm devices:
The unit also has a special voltage output (VO2) intended for
fire door closing only. The trigger condition "Fire door
closing" and the controlling detectors have to be programmed.
The "fire door closing function" is described on page 80 and
besides that function the output VO2 will also be powerless
approx. 30 sec. after:
- the "/Mains OK input" (terminal 8.) goes high, see below.
- the COM loop communication is interrupted = 3364 has no
connection / communication with EBL128.
The unit also has two inputs, i.e. one for power supply (24 V
DC) and one for "/Mains OK".
VO0: Normally low or high (set via Win128), 24 V DC, 1 A.46
VO1: Normally low or high (set via Win128), 24 V DC, 1 A.46
VO2: Normally high, 24 V DC, 1 A.46 (Fire door closing
function.)
24 V DC: From an external power supply (unit 3366 or
EBL128)
/Mains OK: From an external power supply unit (3366) when
45 Relay contacts: max. 2 A @ 30 V DC / 125 V AC.
46 Cont. 1 A, during 10 ms 1.4 A.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
40
the fire door closing function (ABDL) is to be used.
Normally low = The main power source (230 V AC) in the
External power supply unit is okay.
Connections and examples, see drawings 128-21 & -28. The
unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required, the
unit can be mounted in a Waterproof box (IP66 / 67) 3362.
For more information, see the Technical Description and the
Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The unit has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3364 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.
6.1.3
Alarm devices (addressable sounders)
3377 Addressable siren. The siren is connected directly to the COM
loop. It is power supplied via the COM loop, i.e. the number of
sirens is depending on the type and number of other units
connected to the COM loop.47 Red ABS plastic housing. Three
sound types (tones) and two priority levels are available. For
each level an output control expression and a sound type is
programmed (via Win128). For more technical data, see the
Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The siren has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3377 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.
3378 Addressable sounder base. 3378 consists of an analog base
(3312) mounted together with a sounder. The sounder is
mounted in the ceiling. Two flying leads from the base are
plugged in the sounder. The base is thereafter mounted on the
sounder, so that the detector can be plugged in the base. The
base is connected directly to the COM loop. (Like base 3312.)
It is power supplied via the COM loop, i.e. the number of
sounder bases is depending on the type and number of other
units connected to the COM loop47. Three sound types (tones)
47 The number of 3377 + 3378 units must be < 50.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
41
and two priority levels are available. For each level an output
control expression and a sound type is programmed (via
Win128). For more technical data, see the Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The unit has an address label on which the programmed
technical address is to be written. (The detector has its own
technical address set via the Address setting tool 3314.)
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3378 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.
3379 Addressable sounder base.48 3379 consists of an analog base
(3312) mounted together with a sounder. 3379 is mounted in
the ceiling. An analog detector can be plugged in the base,
which has screw terminals for the COM loop and an ext. LED
(2218). Prepared for mechanical lock of the detector - if
required. Recess for label holder (3391). 3379 is power
supplied via the COM loop, i.e. the number of sounder bases is
depending on the type and number of other units connected to
the COM loop47. Three sound types (tones) and two priority
levels are available. For each level an output control expression
and a sound type is programmed (via Win128). For more
technical data, see the Product Leaflet.
The COM loop address is set with the Address setting tool
(3314). The unit has an address label on which the programmed
COM loop address can be written. (The detector has its own
COM loop address set via the Address setting tool 3314.)
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3379 in system EBL128.
2330 mode: Not used in system EBL128.
2312 mode: Not used in system EBL128.
NOTE! See also chapter "Limitations", page 144.
6.1.4
Short circuit isolators (addressable)
Each COM loop short circuit isolator is to be programmed (via
Win128) regarding:
Technical address
Name (Normally not changed)
Sequence Number (Serial Number in the COM loop's A-
direction.)
Connections, see drawing 128-21. (See especially about the L wire!)
4313 Analog base with isolator. An analog base with a built-in short
circuit isolator with the same function as the Addressable short
circuit isolator 4370, see below. See also page 32.
48 This unit has replaced the Sounder base 3378.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
42
4370 Addressable short circuit isolator. In case of short circuit on the
COM loop, the number of disabled units will be minimised.
4370 is power supplied via the COM loop. The unit's
dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 128 x 72 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required, the
unit can be mounted in a Waterproof box (IP66 / 67) 3362. The
unit has an input to manually open the isolator ("isolated state")
and an input to manually close the isolator ("normal state"). An
LED will indicate the normal and isolated state respectively.
For more information, see the Product Leaflet. The technical
address is set with an Address setting tool (AST) 3314. The
unit has an address label on which the programmed technical
address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 4370 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
According to the EN54 standard, at least one short circuit isolator is
required per 32 alarm points on the COM loop. In the Australian and
New Zealand conventions at least one isolator per 40 alarm points.
Up to eight 4370 and/or 4313 can be used, which gives nine loop
segments. Each isolator has to be given a Sequence Number, 0-7.
The isolators have to be connected consecutively (Sequence Number
0-1-2-3-4-5-6-7) in the COM loop's A-direction. NOTE! EBL128
has one built-in isolator in the-A direction (no. "A") and one in the B-
direction (no. "B").
EBL128
4370
no. 0
4370
no. 1
A Dir.
B Dir.
Segment A
Segment B
Segment C
Figure 9. Two 4370 / 4313 isolators connected to the COM
loop gives three loop segments, i.e. Segment A (A-0), B (0-1)
and C (1-B). If one or more isolators are to be added the
sequence numbers have to be updated (via Win128), e.g. if one
isolator is to be put in between no. 0 and no. 1 in the figure, the
new isolator will be no. 1 and the old no. 1 will be no. 2.
Short circuit / cut-off (break) on the COM loop
See chapter "COM loop", page 15. See also chapter "Fault messages"
in the EBL128 Operating Instructions.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
43
6.1.5
Units for Hazardous (Ex) areas
In hazardous (Ex) areas, Intrinsically Safe (IS) and approved products
are required. The IS alarm points are connected to a detector
interface, i.e. a Galvanic isolator, which is connected to an expansion
board 4580 zone line input. See also drawings 128-32.
6.1.5.1
Galvanic isolators
MTL5061 Galvanic isolator. The isolator is used to connect the IS
detectors and manual call points to an expansion board 4580
zone line input. The isolator has two zone line inputs and two
outputs (Channel 1 & 2) and it is mounted in a Waterproof box
(IP66/67). Four compression glands for the cable entries and an
end-of-line resistor (10K) with an area >230 mm2 are supplied.
Box dimensions (L x W x H): 175 x 125 x 150 mm.
BASEEFA classification: EEx ia IIC.
6.1.5.2
Intrinsically Safe mounting bases
YBN-R / 4 IS
Intrinsically Safe mounting base. In the base can
be plugged an intrinsically safe conventional smoke or heat
detector. The base has terminals for the zone line (in/out) and
for an ext. LED.
6.1.5.3
Intrinsically Safe photoelectric smoke detectors
SLR-E-IS Intrinsically Safe photoelectric smoke detector.
A conventional photoelectric (optical) smoke detector, to be
plugged in the intrinsically safe mounting base. The detector
has two built-in LEDs that are lit to indicate that the detector
has generated fire alarm. Zone classification: 0, 1 or 2.
BASEEFA classification: EEx ia IIC T5, t (amb.)=50°C. Max
20 per zone.
6.1.5.4
Intrinsically Safe heat detectors
DCD-1E-IS Intrinsically Safe heat detector. A conventional Rate of
Rise heat detector, fixed temperature 60°C (class A1), to be
plugged in the intrinsically safe mounting base. Two built-in
LEDs that are lit to indicate that the detector has generated fire
alarm. Zone classification: Category 1 (incl. lower categories).
BASEEFA classification: II 1 G EEx ia IIC T5, t (amb.)=55°C.
Max 20 per zone.
6.1.5.5
Intrinsically Safe manual call points
6.1.6
Other COM loop units
3366 External power supply. Conforms to EN54-4. The unit is
connected to a COM loop, i.e. it is monitored from EBL128 and
e.g. loss of the main power source will generate a fault in
EBL128. It can be used as power supply for external
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
44
equipment requiring 24 V DC with battery backup, e.g. the
3364 unit. It also has a "/Mains OK" output (normally low),
intended to be connected to the corresponding input on the 3364
unit.
A light grey metal housing (HxWxD, 288 x 400 x 95 mm).
There is space for two maintenance-free sealed Lead-Acid
backup batteries, 2 x 12 V, 7.5 Ah as the second power source.
Batteries with higher capacity (up to 60 Ah) have to be placed
outside the housing. There are cable inlets on the top, bottom
and back sides of the housing. Two compression glands are
attached.
The unit has a 24 V DC49 power supply output for external
equipment with up to 2.1 A or 0.85 A continuous current
consumption, at the same time as the battery charging is in
progress.50 In case of no battery charging, the continuous
current consumption can be up to 4 A.
It has a number of security functions, e.g. against to high
current output and to low battery voltage etc. For more
information, see the Technical Description and the Product
Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The unit has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3366 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
4601 Wireless photoelectric smoke detector. The detector is plugged
in an attached base and the colour is white. Latest IC
technology will secure the highest reliability possible. The
smoke detection chamber contains an IR LED and a
photodiode. Scattered light (i.e. reflection of infrared light) is
used to detect smoke. The smoke enters the detection chamber
through an insect filter and an optical labyrinth. Fire alarm will
be activated after three values over the fire alarm threshold
level. The detector has sensitivity compensation for
contamination. Transmission distance between Detector and
Base station is min. 40 m in open air. The Wireless smoke
49 The rated output voltage for the main power source (rectifier) is 24 V ±
1%. Max. ripple 500 mVp-p. The rated output voltage for the second power
source (the backup battery) is 18 – 28 V DC. NOTE! The voltage will,
however, decrease to approx. 15 V when the output will be switched off in
order not to damage the battery.
50 A current consumption of 0.85-2.2 A allows only the "low current
charging mode", i.e. the battery capacity can be up to 27 Ah.
A current consumption < 0.85 A allows the "high current charging
mode", i.e. the battery capacity can be up to 60 Ah.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
45
detector is power supplied by three pieces of a 3 V Lithium
2400 mAh battery, type 4602. The battery life time is more
than three years.
Up to 16 Wireless photoelectric smoke detectors, type 4601,
can be "connected" to an Addressable Base station for
wireless units, type 4610. Each wireless detector shall be
programmed like the Analog photoelectric smoke detector, type
4301 regarding presentation number (Zone-Address), alarm
text, etc. For more information, see the Technical Description
and the Product Leaflet.
4610 Addressable Base station for wireless units. The Base station
consists of a p.c.b. mounted in a white plastic housing, which
has a great number of cable inlets and mounting holes. It has
fast connectors for the COM loop (in / out) and 24 V DC power
supply respectively. Up to four Base stations can be connected
to a COM loop in the EBL system and up to 16 Wireless
photoelectric smoke detectors (detector address 0-15) can be
"connected" to each Addressable Base station for wireless units,
type 4610. Each Base station shall have a transmission channel
(0-3) selected. The Base station's COM loop address is set on a
DIL-switch. The COM loop address for the wireless detector
respectively is depending on the Base station's COM loop
address, see below. Ext. 24 V DC power supply is required.
For more information, see the Technical Description and the
Product Leaflet.
AAFC Alarm Acknowledgement Facility Control.51 The AAFC is a
box with an alarm indication LED and a non-latching switch
"Press to acknowledge false alarm". One AAFC per AAFC
zone and up to 50 AAFC:s zones can be used. The COM loop
address is set with an Address setting tool (AST) 3314. See
also chapter "Alarm Acknowledgement Facility (AAF)", page
94.
6.1.7
COM loop addresses for Base station and Wireless
detectors
Each Base station takes one COM loop address (012 in the example
below).
Each wireless detector's COM loop address, will be as follows:
Detector
COM loop address
address
0
Base station's COM loop address +1 (e.g. 012+1=013)
1
Base station's COM loop address +2 (e.g. 012+2=014)
..and so on..
51 This unit is available on the Australian market only.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
46
15
Base station's COM loop address +16 (e.g. 012+16=028)
NOTE! Since the highest possible COM loop address is 127 the
highest possible COM loop address for a Base station is 111 if 16
Wireless smoke detectors shall be supported (111+16=127).
6.2
Units connected to the RS485 interface
Up to four Ext. FBPs (1826 / 1828) and/or Alert Annunciation Units
(1735 / 1736) and/or Ext. Presentation Units (1728) can be connected
to the RS485 interface52 (J1:15-16) in EBL128. Max one 1826 with
printer. (Power supply at J1:13-14.)
Address and S/W mode settings
The display and the push buttons (in the unit respectively) are used to
set the address, which also can be changed via EBL128. The S/W
mode shall be set to xxxx – 1587 (xxxx = type number). See the
Technical Description for the unit respectively.
The first unit shall have the address 00, the second unit address 01 and
so on53. Follow the Address setting instructions in the Technical
Description for the unit respectively.
Via Win128 can "Selective alarm presentation" be programmed, i.e.
you can select which alarms that shall be presented in each unit, see
the Technical Description for the unit respectively.
6.2.1
External Fire Brigade Panels
1826 External Fire Brigade Panel (ext. FBP). A light grey metal
housing (HxWxD, 288 x 400 x 95 mm) with a door. A key is
required to open the door, which has a Plexiglas ahead of the
FBP front. It has cable inlets on the top, bottom and back sides
and is intended to be wall mounted. Two compression glands
are attached.
LED indicators and push buttons on the front are like the
EBL128 FBP (upper black part of the front), see Figure 2, page
14. The front's designation texts are in Swedish. A neutral
front is available, where the designation texts, in any
language, are made separately and by production put into a
transparent "text slot" for the LED and push button respectively.
All or selected alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light. An
alarm text will also be presented together with each alarm, if
programmed in EBL128. Furthermore, at least 617 texts for
selected fire alarms can be stored in the unit and will in such a
case be shown, instead of the texts sent from EBL128 for these
alarms. These text messages will be downloaded to the unit via
EBL128. A built-in buzzer will sound like in EBL128. The
52 The RS485 transceiver 4552 is an option.
53 The connection order on the line is not dependent of the address.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
47
buzzer can be silenced and the alarm devices in the installation
can be silenced. They will re-sound for a new alarm. When
there are queued alarms in the system, you can scroll amongst
them and they can be reset. Any fault in the system will be
presented as "General fault in system" and the buzzer will
sound.54 A Printer 1835 can be mounted in ext. FBP 1826. It
will print all the alarms, including the alarm texts. New S/W
versions can be downloaded directly in the unit. The unit is
power supplied from EBL128 or an ext. power supply.
The unit shall run in S/W mode 1826/28 – 1587, which has the
highest performance with regard to functionality, response time,
ability to store fire alarms, etc. Up to 1200 m cable can be
used. For more information, see Technical description
MEW00249.
1828 External Fire Brigade Panel (FBP). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly but a key is required to
get access to the push buttons. They are disabled until they are
supposed to be used. The unit shall be wall mounted. Two
compression glands are attached. In all other respects it is like
1826, except that a printer can not be mounted in 1828.
The unit shall run in S/W mode 1826/28 – 1587, which has the
highest performance with regard to functionality, response time,
ability to store fire alarms, etc. Up to 1200 m cable can be
used. For more information, see Technical description
MEW00249.
1835 Printer. Can be mounted in the External Fire Brigade Panel
1826. It will print all the alarms, including the alarm texts.
6.2.2
Alert Annunciation Units
When the Alert Annunciation (AA) function shall be used in system
EBL128, a unit is required for the related manoeuvres, i.e. to
acknowledge / reset the AA alarms. For a detailed description of the
Alert Annunciation function, see chapter "Alert Annunciation", page
92.
1735 Alert Annunciation Unit (AAU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly but the push buttons are
disabled until they are supposed to be used. The unit shall be
wall mounted. Two compression glands are attached. The
front's designation texts are in Swedish.
54 Not valid for the Swedish convention (SBF).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
48
All or selected fire alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light. An
alarm text will also be presented together with each alarm, if
programmed in EBL128. Furthermore, at least 617 texts can for
selected fire alarms be stored in the unit and will in such a case
be shown, instead of the texts sent out from EBL128 for these
alarms. These text messages will be downloaded to the unit via
EBL128. A built-in buzzer will sound to indicate a not
acknowledged AA alarm.
New software versions can be downloaded directly in the unit.
The unit is power supplied from EBL128 or an external power
supply.
The unit has the following LEDs:
Fire and Alarms queued, indicating fire / AA alarm.
Operation, indicating that the unit is in operation, i.e. the AA
function is enabled in the system. A time channel can be used
to enable the AA function.
Fire brigade alerted, indicating that the "Fire brigade tx"
output is activated in EBL128 because:
- the activated fire alarm is not an AA alarm
- the AA function has been ended, e.g. the acknowledge or
investigation time respectively has run out, etc.
Acknowledge, indicating that the AA alarm has been
acknowledged.
The unit has the following push buttons:
Alarms queued, used to scroll amongst the alarms.
Acknowledge, used to acknowledge an AA alarm and hereby
also silence the buzzer.
Reset, used to reset an AA alarm.
The unit shall run in S/W mode 1735 – 1587, which has the
highest performance with regard to functionality, response time,
ability to store alarms, etc. Up to 1200 m cable can be used.
For more information, see Technical description MEW00224.
1736 Alert Annunciation Unit (AAU). This unit is like 1735, except
it has a neutral front, where the designation texts, in any
language, are made separately and by production put into a
transparent "text slot" for the LED and push button respectively.
(This front also holds one extra LED & two extra push
buttons.).
The unit shall run in S/W mode 1736 – 1587, which has the
highest performance with regard to functionality, response time,
ability to store alarms, etc. Up to 1200 m cable can be used.
For more information, see Technical description MEW00224.
6.2.3
External Presentation Units
1728 External Presentation unit (EPU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
49
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly, when required. The
push buttons are disabled until they are supposed to be used.
The unit shall be wall mounted. Two compression glands are
attached. The front's designation texts are in Swedish. This
unit is intended for pre-warning, co-incidence55, fire (and heavy
smoke / heat) alarm presentation. If there are two or more
alarms in the system, you can scroll amongst them but the fire
alarms can not be reset via this unit.
All or selected alarms will be presented in a display (alpha-
numeric LCD, 2x40 characters), with back-light. An alarm text
will also be presented together with each alarm, if programmed
in EBL128. Furthermore, at least 617 texts can for selected fire
alarms be stored in the unit and will in such a case be shown,
instead of the texts sent out from EBL128 for these alarms.
These text messages will be downloaded to the unit via
EBL128.
Any fault in the system will be presented as "General fault in
system". The buzzer will sound.54 It can be silenced. Any
disablement in the system will be presented as "General
disablement in system".54
A built-in buzzer will sound like in EBL128. The buzzer can be
silenced but the alarm devices in the installation can not be
silenced via this unit. New software versions can be
downloaded directly in the unit. The unit is power supplied
from EBL128 or an external power supply. The unit shall run
in S/W mode 1728 – 1587, which has the highest performance
with regard to functionality, response time, ability to store fire
alarms, etc.
The number of units that can be power supplied via EBL128 (or
an external power supply) is depending on all other units
connected to the same c.i.e. / external power supply. Up to
1200 m cable can be used. For more information, see Technical
description MEW00290.
6.2.4
German Fire Brigade Panels
See also "…optional Communication module (RS485 transceiver
component) 4552", page 14.
FBF 2003 German
Fire
Brigade
Control
Panel
(Feuerwehr-
Bedienfeld). A grey metal housing (HxWxD, 185 x 255 x 58
mm) with a door. A key is required to open the door, which has
a Plexiglas ahead of the front. It has cable inlets on the top,
bottom and back sides and is intended to be wall mounted.
The function, LED indicators and push buttons on the front are
in accordance with DIN 14661. The front's designation texts
55 Two zone / address dependence.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
50
are in German. Serial RS485 interface for IHD protocol.
The unit is power supplied from EBL128 (or an ext. power
supply). Up to 1200 m cable can be used.
NOTE! Switch 1 on the DIP switch shall be set to "on".
FAT 2002 German Fire Brigade Indicator Panel (Feuerwehr-
Anzeigetableau). A grey metal housing (HxWxD, 185 x 255 x
58 mm) with a door. A key is required to open the door, which
has a Plexiglas ahead of the front. It has cable inlets on the top,
bottom and back sides and is intended to be wall mounted.
The function, Display information, LED indicators and push
buttons on the front are in accordance with DIN 14662. The
front's designation texts are in German. Serial RS485
interface for IHD protocol.
The unit is power supplied from EBL128 (or an ext. power
supply). Up to 1200 m cable can be used.
6.3
Units connected to the RS232 interface J5
6.3.1
Web-servers
1598
Web-server II. This unit has replaced 1588 and can be used:
a) for presentation of the actual c.i.e. status in a PC using the
web browser Microsoft Internet Explorer. It can also send e-
mails in case of pre-warning, fire alarm, fault, disablement,
test mode alarm and/or service signal.
b) for remote control with encrypted and safe two-way
communication and five different user (access) levels.
c) as a gateway to other PC systems etc. Three alternatives
are available today:
c1) EBL Talk is an open protocol, used to transmit and
present fire alarm information in a separate PC / system.
c2) Tateco, used to transmit and present fire alarm
information in an Ascom Tateco paging system.
c3) SIA, used to transmit and present fire alarm
information in a separate PC application.
A PC tool, Web128 II Config tool is used for the
configuration, which is downloaded to the web-server via
TCP/IP.
The Web-server II consists of a light grey plastic cabinet
(90x25x69.5 mm), which shall be vertically mounted on the
symmetric 35 mm DIN rail in the EBL128 c.i.e.
Web-server II has the following interfaces:
RS232 to connect the web-server to J5 in the EBL128 c.i.e.
RS232 to connect the web-server to other PC / system
RJ45 (10 BASE-T) to connect the web-server to Internet / an
intranet (LAN)
Molex 3.5 to connect the web-server to a power supply (24 V
DC, max. 65 mA), e.g. to J4 in the EBL128 c.i.e.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
51
6.4
Units connected to the RS232 interface J3
J3 is a 9 ways female "D" connector. This interface is used only for
connection of EBL128 to a PC with the PC program Win128, which is
used for download / backup of Site Specific Data (SSD), etc.
6.5
Other units
6.5.1
Alert Annunciation Controllers
1740
Alert Annunciation Controller (AAC). This unit has no
display, i.e. it has to be mounted close to EBL128 (or an ext.
FBP) where the fire alarms will be presented.
The compact size enclosure (HxWxD, 145 x 220 x 50 mm) is
made of grey high impact ABS. Fitted with a supplementary
"O" ring gasket, it will comply with IP61, in respect of dust
and moisture. The unit has no door, i.e. the front is accessed
directly but the push buttons are disabled until they are
supposed to be used. The front's designation texts are in
Swedish.
The unit shall be wall mounted. The LED "Acknowledge"
can be turned on by the push button "Acknowledge" or by an
input, i.e. a programmable output. This is set via a jumper
"JP1" in the unit. The unit is power supplied from EBL128 or
an external power supply. One supplementary compression
gland can be used for cable entry.
The unit has the following LEDs:
Fire, indicating fire / AA alarm.
Operation, indicating that the unit is in operation, i.e. the AA
function is enabled in the system. A time channel can be used
to enable this function.
Fire brigade alerted, indicating that the "Fire brigade tx"
output is activated in EBL128 because:
- the activated fire alarm is not an AA alarm
- the AA function has been ended, e.g. the acknowledge or
investigation time has run out, etc.
Acknowledge, indicating that the AA alarm has been
acknowledged.
The unit has the following push buttons:
Acknowledge, used to acknowledge an AA alarm.
Reset, used to reset an AA alarm.
Connections and more details are to be found in the Technical
Description MEW00283.
6.5.2
External LEDs
2217 Ext. LED (ext. indicator). Used when a detector is placed out
of view or hidden. The LED is lit at the same time as the LED
in the detector / base it is connected to. It has a "Burning
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
52
house" symbol instead of any text. 2217 can be connected to all
types of Panasonic detectors / bases. The input is polarised.
J1:1 (+5 to +24 V DC) / J1:2 (0 V). To be wall mounted with
the attached frame (84 x 84 mm) or flush mounted, e.g. with a
Swedish 65mm circular mounting box. 2217 is replaced with
2218, see below.
2218 Ext. LED (ext. indicator). Used when a detector is placed out
of view or hidden. The LED is lit at the same time as the LED
in the detector / base it is connected to. It has a "Burning
house" symbol instead of any text. 2218 can be connected to all
types of Panasonic detectors / bases. The input is polarised.
J2:1 (+5 to +35 V DC) for conventional detectors / bases
J2:2 (+; < 25 mA) for analog detectors / bases
J2:3 (0 V)
To be wall mounted (87 x 87 x 30 mm). 2218 has replaced
2217.
6.5.3
Alarm devices (sounders, etc.)
Regarding addressable alarm devices, see page 40.
In the Panasonic product range are no alarm device intended for a
supervised (monitored) voltage output (e.g. S0 or S1 in EBL128).
Connections of alarm devices according to drawing 128-22.
(For addressable sounders, see page 40.
6.5.4
Door release magnets
In the Panasonic product range is no Door release magnet. Door
release magnets shall always be provided with a "suppresion diode"
(e.g. 1N4004) in parallel with the coil, like in the alarm devices, see
drawing 128-22.
6.5.5
Boxes
3362 Waterproof box (IP66 / 67). A grey polycarbonate box with
ingress protection rating IP66 / 67. Four compression glands
are included for the cable entries. Dimensions (L x W x H):
175 x 125 x 75 mm. 3362 can be used for:
Addressable multipurpose I/O unit 3361
Addressable short circuit isolator 4370
Addressable 2 voltage outputs unit 3364
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
53
7
Programmable inputs
EBL128 has one programmable input (I0). In EBL128 can also be
mounted the Inputs and Outputs expansion board 4583, with five
programmable inputs (Input 0-4). See chapter "Expansion boards
458x", page 22. All these inputs can be supervised or not supervised.
On the COM loop can be connected up to 16 addressable multi
purpose I/O units 336156. Each 3361 unit has two programmable
inputs (In0/Z and In1), not supervised.
Each input is programmed (via Win128) regarding:
Name (Normally not changed, but used as Interlocking input it is
recommended to add some identification information)
Type ("Trigger condition")
Not supervised or Supervised. (Not valid for 3361.)
Logic, Normally open (high resistance, 3K3, when supervised) or
Normally closed (low resistance, 680R, when supervised)
Ext. Fault (Text; only for trigger cond. "External fault")
Ext. time channel Name (only for trigger cond. "External time
channel")
Activate output (Technical address and Output)
Zone, Address and Text (only for trigger cond. "General fire",
"Pre-warning" and "Zone line input").
Alert Annunciation time channel (only for trigger cond. "Zone
line input" – 3361 In 0).
Disablement time channel (only for trigger cond. "Zone line
input" – 3361 In 0).
Figure 10. The Win128 "Input" dialog box. The different trigger
conditions ("Type") require different additional information.
56 Units type 3361 + 3364 = max. 16.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
54
7.1
Control unit Input I0 & Inputs and Outputs
exp. board 4583, Input 0-4
7.1.1
Not supervised
Normally open (R > 2K)
or
Normally closed (R < 2K)
Activation time: >1 sec.
Connections, see drawing 128-22.
7.1.2
Supervised
Each supervised input can be in four different states:
Open circuit (cut-off)
Not activated (quiescent)
Activated
Short-circuit
Depending on the selected logic, Normally open (high resistance) or
Normally closed (low resistance), the following table is valid.
Line resistance R
Normally open
(high resistance)
Normally closed
(low resistance)
R > 6K8
Open circuit (cut-off)
Open circuit (cut-off)
6K8 > R > 2K
(nom. 3K3)
Not activated
Activated
2K > R > 70
(nom. 680)
Activated
Not activated
R < 70
Short-circuit
Short-circuit
7.1.2.1
Input line fault
If open circuit (cut-off) or short-circuit is detected on a supervised
input, a fault will be generated in EBL128 and the following fault
message will be displayed:
FAULT: Programmable input
alternatively
FAULT: Programmable input x exp. board x
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
55
7.2
3361 unit Inputs In0 / Z & In1
Connections, see drawing 128-26.
NOTE! The input In0 / Z can be used as a general input (In0) or as a
monitored zone line input (Z) requiring an end-of-line capacitor (470
nF).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
56
8
Input programming
Input programming is done via Win128. For more information, see
the Win128 help. Each input has to have an individual Trigger
condition ("Type") and Logic. Each input can be supervised or not
supervised. It is not recommended to let two or more inputs have the
same trigger condition.
8.1
Type (trigger conditions)
The following trigger conditions are available:
1. Not used
2. Alarm Key Cabinet (one input)
3. Alert Annunciation Acknowledge
4. Alert Annunciation Reset
5. Fault Signal External Power Supply (one input)
6. Fault Signal External Fuses (one input)
7. External Time Channel 5 - 12 (one input per time channel)
8. General Fire (max. 127)
9. Activated Routing Equipment (one input)
10. External Fault
11. Interlocking (max. 32 inputs)
12. Loss of main power source to external power supply (one
input)
13. Loss of battery charger to external power supply (one input)
14. Door Closing Test Input
15. Pre-warning
16. Activated fault routing equipment (one input)
17. Extinguishing system released
18. Extinguishing system fault
19. Extinguishing alarm
20. Fault warning routing equipment fault
21. Activate output
22. Silence alarms (one input)
23. Activated key cabinet
24. Evacuate
25. Zone Line Input 57
Comments to the trigger conditions:
57 Only valid for the Addressable multipurpose I/O unit 3361 input "In0",
used as zone line input (Z).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
57
1. Default. The input does not work.
2. Key cabinet, where the fire brigade store a key to the building.
Will activate a Key cabinet alarm. See the EBL128 Operating
Instructions for more information.
3. Alert annunciation, see the EBL128 Operating Instructions for
more information.
4. Like 2.
5. Ext. power supply equipment fault output will activate a fault in
EBL128.
The following fault message will be shown:
FAULT: External power supply
6. Ext. fuses (for the ext. power supply equipment) fault output will
activate a fault in EBL128.
The following fault message will be shown:
FAULT: External fuses
7. External clock, timer, key switch, switch, etc. can disable / re-
enable alarm points. The function Alert annunciation can be set
on / off by a time channel. Control outputs can be turned on
(activated) / off (de-activated) by a time channel.
8. A special detector, push button, etc. can activate a fire alarm in
EBL128. Zone no. and Address (+ user definable text).
9. "Activated Fire brigade tx" signal (feed-back) to EBL128 will
light up the LED "Fire brigade tx" on the front. (Normally the
LED will be lit when a corresponding output is activated58.)
Output with trigger condition "Indication Fire Brigade tx
Activated" will be activated.
10. Ext. fault will activate a fault in EBL128. A user definable fault
message ("text") with up to 40 characters will be shown.
11. A feed-back from the equipment activated by the corresponding
interlocking output. Activated input is shown in menu H9/C1.
See also chapter "Interlocking function", page 76.
12. Fault output "Loss of main power source to external power supply
equipment" will activate a fault in EBL128. It will have the same
time delay, as set for the Loss of main power source fault for
EBL128.
The following fault message will be shown:
FAULT: Mains, ext. power supply
13. Fault output "Loss of the battery charger to external power supply
equipment" will activate a fault in EBL128. It will have the same
time delay, as set for the "Loss of main power source" fault for
58 Type of output = Routing equipment (Fire brigade tx).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
58
EBL128.
The following fault message will be shown:
FAULT: Charging ext. power supply
14. "Fire door closing" outputs will be activated for 20 seconds by
this trigger condition.
15. Pre-warning, e.g. from a High Sensitive Smoke Detector's pre-
warning output. Zone no. and Address set to the same as the
corresponding fire alarm (from the same detector).
16. "Activated Fault routing equipment" signal (feed-back) to
EBL128 will light up the LED "Fault tx activated" on the front.
Output with trigger condition "Indication Fault tx Activated" will
be activated.
17. Activated input will light up the LED "Extinguishing" on the
front. (Normally the LED will be lit when a corresponding output
is activated.) Output with trigger condition "Extinguishing system
released" will be activated.
18. Activated input will generate a fault in EBL128. Output with
trigger condition "Extinguishing system fault" will be activated.
The following fault message will be shown:
FAULT: Extinguishing system fault
19. Activated input will activate a fire alarm in EBL128 (Zone no.)
from an extinguishing system. The alarm devices will not be
silenced by the "outside switch" (New Zealand FB Silence
switch).
20. Activated input will generate a fault in EBL128.
The following fault message will be shown:
FAULT: Fault warning routing equipment
21. Activated input will activate an output (Technical address /
output.)
22. Used for the "outside switch" (i.e. the New Zealand FB Silence
switch).
23. Output with trigger condition "Activated Key cabinet" will be
activated.
24. Activated input will activate all programmable outputs of type
"Alarm devices" steady (continuous).
25. The Addressable multipurpose I/O unit 3361 monitored input
"In0" used as zone line input (Z) for conventional detectors.
8.2
Logic
The logic has to be set (in the Win128 dialog box "Input Properties").
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
59
8.2.1
Not supervised (default)
(•) Normally open (low) Normally open contact / normally low
optocoupler input (3361).
( ) Normally closed (high) Normally closed contact / normally high
optocoupler input (3361).
8.2.2
Supervised
Valid for the c.i.e. programmable input I0 and the Inputs and Outputs
expansion board 4583 programmable inputs (Input 0-4).
(•) Normally open (high resistance)
( ) Normally closed (low resistance)
Depending on the selected logic, Normally open (high resistance,
3K3) or Normally closed (low resistance, 680R), the function will be
according to the table on page 55.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
60
9
Programmable outputs
EBL128 has two programmable voltage outputs (S0 and S1) and one
programmable relay output (R0). 8 relay outputs expansion board
4581 can be mounted in EBL128. Input and Output expansion board
4583 with three programmable outputs (Output 0-2) can be mounted
in EBL128. See chapter "Expansion boards 458x", page 22.
On the COM loop can be connected Addressable Multipurpose I/O
unit 3361 with two programmable relay outputs (Re0 and Re1) per
unit and Addressable 2 voltage outputs unit 3364 with two
programmable voltage outputs (VO0 and VO1) per unit. Addressable
siren 3377 and Addressable sounder base 3378 can also be connected
on the COM loop, i.e. these units have no physical output, only the
siren and sounder respectively.
NOTE! Units type 3361 + 3364 = max. 16.
Units type 3377 + 3378 = max. 50.
Each output is programmed (via Win128), when applicable, regarding:
Name (Normally not changed)
Type
Output signal period (continuous, pulse, delay, etc.)
Logic (NO / normally low or NC / normally high)
Supervised / Not Supervised (The EBL128 voltage outputs, Input
and Output expansion board 4583 voltage outputs (Output 0-1)
and Addressable 2 voltage outputs unit 3364.)
Control expression (with one or more trigger conditions).
If Enter arguments in dialog is selected a separate dialog box is
opened for easier entering of the required data (e.g. zone, address,
etc.). Current size gives a rough indication of how big the
control expression is. Normally it should be < 80 but it is
depending on the number and types of trigger conditions but also
the logical operators used in the control expression.
Figure 11. The Win128 dialog boxes "Voltage" & "Relay
Output" respectively.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
61
Each 3377 and 3378 unit is programmed (Win128) regarding:
Technical address
Name (Normally not changed)
Priority level (High / Low)
For each priority level:
Sound
type
(Steady/continuous,
Intermittent/pulsed
or
Alternating/two-tone)
Name
Type (Normally "Alarm device")
Output signal period (Normally "Steady")
Control expression (with one or more trigger conditions)
If Enter arguments in dialog is selected a separate dialog box
is opened for easier entering of the required data (e.g. zone,
address, etc.). Current size gives a rough indication of how
big the control expression is. Normally it should be < 80 but it
is depending on the number and types of trigger conditions but
also the logical operators used in the control expression.
Figure 12. The Win128 dialog box "Addressable siren 3377"
(The dialog box "Addressable sounder base 3378" is similar).
9.1
Control unit outputs S0 – S1
EBL128 has two programmable, supervised (monitored)59 voltage
outputs:
59 Supervised as default but via Win128 it is possible to set each output
individually as not supervised (not monitored). A normally high output can
not be supervised.
Supervised outputs have to be calibrated via menu H5/A3, see the EBL128
Operating Instructions. 1-5 supervision resistors 33K can be used. The
calibrated value has to be in the range 4K7-50K. A fault will be generated
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
62
S0
Supervised (monitored) voltage output, 24V DC60, max. 500
mA (Fuse F8).
S1
Supervised (monitored) voltage output, 24V DC60, max. 200
mA (Fuse F6).
As default S0-S1 are set to type "Alarm device", "Intermittent 0.8 /
0.8, normally low, supervised and trigger condition "General fire".
Connections and more information, see drawing 128-22.
See also chapter "Programmable voltage outputs (S0-S1)", page 18.
9.2
Control unit output R0
EBL128 has one programmable relay output:
R0
Relay output, NO or NC contacts61 programmable.
As default R0 is set to type "Routing equipment" (Fire brigade tx),
Steady (cont.), normally open and trigger condition "Fire brigade tx".
Connections and more information, see drawing 128-23.
9.3
8 relay outputs expansion board 4581
Output 0 – Output 7
Each 4581 board has eight programmable relay outputs:
Output 0
Relay output, NO or NC contacts programmable
Output 1
Relay output, NO or NC contacts programmable
Output 2
Relay output, NO or NC contacts programmable
Output 3
Relay output, NO or NC contacts programmable
Output 4
Relay output, NO or NC contacts programmable
Output 5
Relay output, NO or NC contacts programmable
Output 6
Relay output, NO or NC contacts programmable
Output 7
Relay output, NO or NC contacts programmable
Relay contact ratings: Max. 2A @ 30 V DC.
Connections and more information, see dwg. 128-30.
9.4
Inputs and Outputs expansion board 4583
Output 0 – 1
Expansion
board
4583
has
two
programmable,
supervised
(monitored)59 voltage outputs:
Output 0
Supervised (monitored) voltage output, 24V DC60, max.
200 mA (Fuse F1).
Output 1
Supervised (monitored) voltage output, 24V DC60, max.
200 mA (Fuse F2).
Connections and more information, see drawing 128-33.
See also chapter "Inputs and outputs expansion board 4583", page 26.
for a value outside this range. A normally high output will be low for a few
seconds during restart of EBL128.
60 See chapter "Technical data", page 143, regarding system voltage.
61 Relay contacts: max. 1 A @ 30 V DC.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
63
9.5
The 3361 unit outputs Re0 – Re1
Each 3361 unit has two programmable relay outputs:
Re0 Relay output, NO or NC contacts programmable
Re1 Relay output, NO or NC contacts programmable
Relay contacts: max. 2 A @ 30 V DC / 125 V AC (60W).
Connections and more information, see drawings 128-21 & -26.
9.6
The 3364 unit outputs VO0, VO1 & VO2
Each 3364 unit has two programmable, supervised (monitored)59
voltage outputs:
VO0 Supervised (monitored) voltage output, 24V DC, max. 1A62
VO1 Supervised (monitored) voltage output, 24V DC, max. 1A62
VO2 is a voltage output, 24V DC, max. 1A62, intended for fire door
closing. Normally high. For more information see the
Technical Description MEW00529.
24 V DC required from an external power supply unit (e.g. 3366).
Connections, see drawing 128-21 & -28.
9.7
The 3377 unit output (siren)
Each 3377 unit has one programmable output:
Output
Siren, with two priority levels and three sound types.
Connections and more information, see drawing 128-21.
9.8
The 3378 unit output (sounder)
Each 3378 unit has one programmable output:
Output
Sounder, with two priority levels and three sound types.
Connections and more information, see drawing 128-21.
9.9
The 3379 unit output (sounder)
Each 3379 unit has one programmable output:
Output
Sounder, with two priority levels and three sound types.
Connections and more information, see drawing 128-21.
62 Cont. 1 A, during 10 ms 1.4 A.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
64
10
Output programming
Output programming is done via Win128. See the Win128 dialog box
respectively. For more information see also Win128 help.
10.1
Type
The following output types are available (see also comments below):
0. Control
1. Fire Ventilation
2. Extinguishing
3. Alarm Device
4. Routing Equipment (Fire brigade tx)
5. Control, neutral
6. Interlocking Output
Comments to the types:
0. Default. General (normal) control output63
1. Used to activate fire ventilation equipment64
2. Used to activate extinguishing equipment65
3. Used for sounders, etc.66
4. Used for fire alarm tx67
5. General (normal) control output. No collective disablement and
no LED indication.
6. Output used together with a corresponding interlocking input.
See chapter "Interlocking function", page 76. Activated outputs
are shown in menu H9/C1.
63 Collectively disabled via menu H2/B4 (all control outputs). Re-enabled
via menu H2/B8.
64 Collectively disabled via menu H2/B4 (all ventilation outputs). Re-
enabled via menu H2/B8. LED "Ventilation" is indicating activated output.
65 Collectively disabled via menu H2/B4 (all extinguishing outputs). Re-
enabled via menu H2/B8. LED "Extinguishing" is indicating activated
output.
66 Collectively disabled via menu H2/B4 (all alarm device outputs). Re-
enabled via menu H2/B8. Controlled by push button "Silence alarm
devices". Fault on / disabled output is indicated by LED "Fault /
Disablements Alarm devices" blinking (fault) / continuous (disablement).
67 Disabled / Re-enabled via menu H2/B9 (Fire and/or fault outputs).
Controlled via open door (if programmed so). Used together with trigger
condition Fire brigade tx. LED "Fire brigade tx" is indicating activated
output. (Fire brigade tx feedback via a programmable input can light up the
LED instead). Fault on / disabled output is indicated by LED "Fault /
Disablements Fire brigade tx" blinking (fault) / continuous (disablement).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
65
10.2
Logic
The logic is set in the Win128 dialog box "Voltage or Relay Output".
(•) Normally open / low Normally open relay contacts / normally
low voltage output.
( ) Normally closed / high Normally closed relay contacts / normally
high voltage output (24V DC).
10.3
Supervised
A voltage output is normally supervised (default). By un-marking this
checkbox the voltage output will be not supervised.
NOTE! A normally high output is not supervised.
See also chapter "Programmable voltage outputs (S0-S1)", page 18.
10.4
Output signal period
Each output uses an "Output signal period", which controls the
output's activation. The following are available:
Steady (continuous)
Intermittent 0.8s/0.8s
User defined 1
User defined 2
User defined 3
User defined 4
User defined 5
User defined 6
User defined 7
User defined 8
User defined 1-8 can be built up with type and time.
The following types are available:
Steady (continuous)
Intermittent
One pulse
Steady Delayed Activation
Intermittent Delayed Activation
One pulse Delayed Activation
Steady Delayed De-Activation
The following times are available:
Delay time (when required)
Pulse length time (when required)
Pulse off time (when required)
De-activation time (when required)
See also chapter "Output Signal Periods", page 125.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
66
Figure 13. Delay time, Pulse length, Pulse off and/or De-
Activation, have to be set for the "Signal period" respectively.
For types 1 & 4 the x and y times must be equal and max. 5.6s.
For types 2 & 5 the x time must be max. 5.6s.
NOTE! There are limitations according to the following table:
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
67
In EBL128
COM loop units
Output
Type
S0-S1
R0
4581
board
4583
board
I/O unit
3361
Unit
3364
Siren &
S/B
3377 &
3378
4582
board
Inter
locking
0 Steady (continuous)
X
X
X
X
X
X
X
X
X
1 Intermittent
X
X
XXX
--
--
XX
--
--
--
2 One pulse
X
X
XXX
--
--
--
--
--
--
3 Steady (continuous),
delayed activation
X
X
X
X
X
X
X
X
X
4 Intermittent,
delayed activation
X
X
XXX
--
--
XX
--
--
--
5 One pulse,
delayed activation
X
X
XXX
--
--
--
--
--
--
6 Steady (continuous),
delayed de-activation
X
X
X
X
X
X
X
X
--
Figure 14. The types that can be used in the "Output signal
period" for the programmable output respectively
X = Output type can be used. XX = Output type can be used
but only 0.8s/0.8s. XXX = Output type can be used but max.
5.6s/5.6s and the pulse max. 5.6s respectively.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
68
10.5
Control expression
Each programmable output has to be given a control expression (with
one or more trigger conditions), made by so called Boolean algebra.
Trigger conditions (displayed a list by clicking the right mouse
button), logical "Operators" (AND, OR, NOT) and parentheses are
used to build up a "control expression" containing up to 40 trigger
conditions. See also chapter "Control expression examples" page 72
and the Win128 help.
10.5.1
Trigger conditions
Some trigger conditions require additional information, see
parentheses (+nnnnn) after the trigger condition respectively.
Consecutive trigger conditions includes a "Quantity" that shows the
number of alarm points within the sequence that have to be activated
to fulfil the trigger condition. (Quantity = 1-10. "1" is normal.)
The following trigger conditions are available:
1
Fire Alarm Zone (+Zone no.)
2
Fire Alarm Zone Address (+Zone no.+Address)
3
General Fire Alarm
4
Consecutive Fire Alarm (sequence) (+start Zone no. and
address +stop Zone no. and address +Quantity)
5
Pre Warning Zone (+Zone no.)
6
Pre Warning Zone Address (+Zone no.+Address)
7
General Pre Warning
8
Consecutive Pre Warning (+start Zone no. and address
+stop Zone no. and address +Quantity)
9
Heavy Smoke Alarm Zone (+Zone no.)
10
Heavy
Smoke
Alarm
Zone
Address
(+Zone
no.+Address)
11
General Heavy Smoke Alarm
12
Consecutive Heavy Smoke Alarm (sequence) (+start
Zone no. and address +stop Zone no. and address
+Quantity)
13
Two Address Dependent Fire Alarm (+Zone no.
+Address)
14
Interlocking Input Area Activated (+Area no.)
15
Interlocking Input Area Point Activated (+Area no.
+Point)
16
General Interlocking Input Activated
17
Consecutive Interlocking Input Activated (sequence)
(+start Area no. and point +stop Area no. and point
+Quantity)
18
Indication Fire Brigade Tx Activated
19
Indication Fault Tx Activated
20
Fire Brigade Tx Disabled
21
Zone Disabled (+Zone no.)
22
Zone Address Disabled (+Zone no. +Address)
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
69
23
General Zone Address Disabled
24
General Fault
25
General Charge Fault
26
Reset Pulse Zone Address (+Zone no. +Address) 68
27
Time Channel Activated (+Time channel no.)
28
Alert Annunciation Activated
29
Alert Annunciation Acknowledged
30
Door Open
31
Key Cabinet Open
32
General Control Disabled
33
General Alarm Device Disabled
34
Fire Door Closing (+Zone no. +Address)
35
General Service Signal
36
Fire Brigade tx
37
AAF Zone Alarm (+AAF Zone no.)
38
Quiet Alarm Zone (+Zone no.)
39
Quiet Alarm Zone Address (+Zone no. +Address)
40
Extinguishing System Fault
41
Extinguishing System Released
42
Activated Key Cabinet
43
Multiple Detector Alarm
44
One Detector Alarm
Comments to the trigger conditions (functions):
1
Fire alarm from a Zone.
2
Fire alarm from a Zone-Address.
3
Fire alarm from any alarm point in the system.
4
Fire alarm from any alarm point within the specified
range. "Quantity" is the number of alarm points required
to activate the output.
5
Pre-warning,69 else see 1.
6
Pre-warning, else see 2.
7
Pre-warning, else see 3.
8
Pre-warning, else see 4.
9
Heavy smoke / heat alarm, else see 1.
10
Heavy smoke / heat alarm, else see 2.
11
Heavy smoke / heat alarm, else see 3.
12
Heavy smoke / heat alarm, else see 4.
13
Only one address (in two-unit-dependence) is in fire
alarm state. For more information, see EBL128
Operating Instructions.
68 Only valid for EBL128 outputs (S0-S1 and R0), 4581 outputs and 3361
outputs (i.e. not 3364 outputs).
69 The trigger condition is true as long as the pre-warning level is exceeded.
It is also true as long as the fire alarm level is exceeded.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
70
14
One or more interlocking inputs, in the specified
interlocking area, are activated.
15
The interlocking input, in the specified interlocking
area/point, is activated.
16
One or more interlocking inputs are activated.
17
One or more interlocking inputs, in the specified range,
are activated (from interlocking area no./point to
interlocking area no./point).
18
Output activated when input trigger condition "Activated
routing equipment" is true.70 The output is activated until
the alarm has been reset.
19
Routing equipment output "Fault tx" is activated or input
trigger condition "Activated fault routing equipment" is
true.71
20
Routing equipment output (Fire brigade tx) is disabled.72
21
The specified zone is disabled.
22
The specified alarm point (zone/address) is disabled.
23
One or more alarm points (zone/address) are disabled. 73
24
One or more faults are generated in the system.74
25
Loss of mains (in a c.i.e.). NOTE! The output(s) will be
activated immediately but the corresponding fault is
normally delayed.
26
This control expression is true for 5 seconds, whenever a
reset pulse is sent to the specified zone/address.
27
The programmed time channel (1-12) is activated.
28
Alert annunciation activated (by any alarm point set to
activate this function). Valid until the AA alarm is reset
or becomes a normal fire alarm. For more information,
see EBL128 Operating Instructions.
29
Alert annunciation activated (by any alarm point set to
activate this function) and acknowledged. Valid until the
AA alarm is reset or becomes a normal fire alarm. For
more information, see EBL128 Operating Instructions.
30
Door open in EBL128 / ext. FBP.75
31
Key cabinet alarm. For more information, see EBL128
Operating Instructions.
32
General control disabled (via menu H2/B7). 73
33
General alarm device disabled (via menu H2/B876 or via
"Silence alarm devices).
70 Indicated by LED "Fire brigade tx". Output can be tested via menu H1.
71 Indicated by LED "Fault tx activated". Output can be tested via menu H1.
72 Indicated by LED "Fault/Disablements Fire brigade tx".
73 Indicated by LED "Disablements".
74 Indicated by LED "General fault" and/or LED "Fault tx activated".
75 Or ext FBPs connected to the control unit.
Indicated by LED "Door open".
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
71
34
This trigger condition plus the OR operator shall be used
for each detector (zone-address) controlling a fire door
(normally > two detectors). Type of output is normally
"Control, neutral".77 See also chapter "Fire Door Closing
function", page 80.
35
Service signal is activated (by any sensor).78
36
Used for routing equipment (Fire brigade tx) output only.
Has to be type Routing Equipment (Fire brigade tx).
NOTE! The Alert Annunciation function is working
with this trigger cond. (If this function shall not be used,
use trigger cond. "General fire alarm" instead.)
37
"Alarm Acknowledgement Facility" alarm activated in
the specified AAF Zone. Required "AAF Control" unit is
available on the Australian market only.
38
Any "Quiet alarm" in the specified zone will activate the
output. Used e.g. for the Australian fan control function.
39
One specified "Quiet alarm" in the specified zone will
activate the output. Used e.g. for the Australian fan
control function.
40
Output
activated
when
input
trigger
condition
"Extinguishing system fault" is true.
41
Output
activated
when
input
trigger
condition
"Extinguishing system released" is true.
42
Output activated when input trigger condition "Activated
key cabinet" is true.
43
Output activated when input trigger condition "Multiple
detector alarm" is true, i.e. fire alarm type A.79
44
Output activated when input trigger condition "One
detector alarm" is true, i.e. fire alarm type B.79
10.5.2
Logical operators
The logical operators available in Win128 are in priority order:
( )
parentheses, changes priority order
NOT
not-function (inverts), is written NOT in Win128
AND
and-function, is written AND in Win128
OR
or-function, is written OR in Win128
10.5.3
Control expression examples
In order to understand the possibilities to create control expressions,
here follow some AND, OR, NOT and ( ) examples and also some
control expression examples.
76 Indicated by LED "Fault / Disablements Alarm devices".
77 In Danish convention (DBI), must only EBL128 outputs R0, S0-S1 and
the COM loop unit 3364 be used. The type has to be "control neutral".
78 Indicated by LED "Service".
79 See chapter "Fire alarm type A and Fire alarm type B", page 96.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
72
10.5.3.1
AND
a AND b AND c=y
y is true (=1) when all the conditions a, b, c are true, i.e. a=1 and b=1
and c=1 makes y=1. All other combinations makes y=0.
This is also shown in the following table:
a
b
c
y
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
10.5.3.2
OR
a OR b OR c=y
y is true if at least one of the conditions a, b, c is true, i.e. a=1 or b=1
or c=1 makes y=1.
This is also shown in the following table:
a
b
c
y
0
0
0
0
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
1
10.5.3.3
NOT
Inverts a condition, e.g. NOT b=NOT 0=1.
A OR NOT b AND c=y
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
73
This is shown in the following table:
a
b
c
y
0
0
0
0
0
0
1
1
0
1
0
0
0
1
1
0
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
1
10.5.3.4
Parentheses
Changes priority order.
a OR NOT (b AND c)=y (This is same as the previous but parentheses
are added, which makes a differance.)
This is shown in the following table:
a
b
c
y
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
0
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
1
10.5.3.5
Control expressions
The AND operator has priority, i.e. a AND b OR c = (a AND b) OR c.
This is perhaps more obvious if you write it: a · b + c.
NOTE! a AND b OR c ≠ a AND (b OR c).
Here follows some examples (and explanations) to show how to build
a control expression with trigger conditions and logical operators:
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
74
Example 1
Output:
Voltage output S0
Control expression:
Pre Warning Zone (10)
Explanation:
Pre-warning activated in zone no. 10 will
activate the output S0.
Example 2
Output:
Relay output R0
Control expression:
General Control disabled AND NOT Door
Open
Explanation:
Controls disabled via menu H2/B7 will
activate the output R0 when the door in
EBL128 is not open (i.e. when it is closed).
Example 3
Output:
Voltage output VO0
Control expression:
Fire Alarm Zone (23) AND Fire Alarm Zone
(24) AND NOT General Fault
Explanation:
Fire alarm activated in zone 23 and zone 24
will activate the output VO0 only if there are
no faults in the system at the same time.
Example 4
Output:
Voltage output S1
Control expression:
Consecutive Fire Alarm (10,10,10,19,1) OR
Consecutive Fire Alarm (10,21,10,40,1)
Explanation:
Fire alarm activated by one of the alarm
points in zone 10 addresses 10-19 or by one
of the alarm points in zone 10 addresses
21-40 will activate the output S1 (i.e. the
alarm point in zone 10 address 20 will not
activate the output S1).
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
75
11
Interlocking function
The interlocking function is used to verify that an output really is
activated, i.e. by "combining" an output with an input (feed-back from
the equipment controlled by the corresponding interlocking output).
11.1
Interlocking programming
Win128 is used for the programming. Up to 32 Interlocking
Combinations can be used.
NOTE! Each interlocking input and each interlocking output can
only be used in one interlocking combination.
11.1.1
Interlocking output
The "Voltage Output" / "Relay Output" dialog boxes are to be used.
Type: "Interlocking" is to be selected.
Output signal period: Steady (continuous) or Steady, delayed
activation is to be selected.
Control Expression is to be programmed for the output, i.e. for the
equipment to be controlled.
Activated output will be indicated in menu H9/C1.
Name: It is recommended to add information, e.g. the interlocking
combination's presentation number (Area-Point).
11.1.2
Interlocking input
The "Input" dialog box is to be used.
Triggered by: "Interlocking Input" is to be selected.
Activated input will be indicated in menu H9/C1.
Name: It is recommended to add information, e.g. the interlocking
combination's presentation number (Area-Point).
11.1.3
Interlocking combination
One interlocking output and one interlocking input are programmed in
one interlocking combination to get the interlocking functions.
NOTE!
The interlocking outputs and inputs have to be programmed before the
programming of an interlocking combination is possible to do.80
An interlocking combination can have only an output or only an input
programmed, e.g. when a text shall indicate an activated output or
input.
80 In the "Interlocking Combination" dialog box are listed all the outputs and
inputs previously programmed for interlocking, see Figure 15.
Input
EBL128
Output
Controlled
equipment
Feed-back signal
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
76
Figure 15. The Win128 dialog box "Interlocking Combination".
Logical Name: Displayed in the Win128 Tree and List views.
Default is "Interlocking Combination" that can be changed when
wanted / required.
Area and Point: Each "Interlocking Combination" is presented as
Area-Point (compare with Zone-Address). Area numbers 1-31 are
possible to use and Point numbers 1-63 are possible to use.
Available interlocking outputs list displays all the previous
programmed outputs, Type = "Interlocking Output".
Available interlocking inputs list displays all the previous
programmed inputs with the Triggered by alternative (trigger
condition) 10 = "Interlocking Input".
Select one output and one input in the list respectively.81 Press Select
and the selected output and input will be shown in the Selected
output and Selected input field respectively.
Text = Interlocking text to be shown in the menu H9/C1. Can be
written in this field or in the "Texts" dialog box, see chapter "Creating
the alarm texts via Win128", page 101.
Buzzer checked = activated interlocking input will turn on the
EBL128 buzzer (0.8 / 0.8 sec.)82. The buzzer can be silenced. It will
be automatically turned on again, if a new interlocking input is
activated.
81 Output / Input parent will then show in which unit the output / input
respectively is situated.
82 Priority order: Fire alarm – Pre-warning - Interlocking - Fault.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
77
Latched output checked = Output reset has to be performed via menu
H9/C3. (Automatically output reset will not take place when the
control expression becomes false.).
Fault checked = Fault detection ON.
Fault Detection Time: If the input is not activated within 5-255
seconds after the output is activated83, a fault will be generated:
FAULT: Interlocking input AA/PP
Date: MM-DD Time: HH:MM
11.2
Interlocking indications
One or more activated Interlocking Combinations (interlocking output
and/or input) are indicated in the display in EBL12884:
Interlocking input/output activated
See menu H9/C1
Disabled interlocking output is indicated by the LED "Disablements".
11.3
Information of interlocking combinations
(H9)
Menu H9 has the following sub menus.
11.3.1
Display interlocking information (H9/C1)
See also chapter "Interlocking indications", page 78.
In menu H9/C1 information will be shown as follows:
Output AA/PP activated at HH:MM
Interlocking text.. .. ..
or
Output AA/PP act HH:MM, input act HH:MM
Interlocking text.. .. ..
or
Input AA/PP activated at HH:MM
Interlocking text.. .. ..
AA = Interlocking combination Area
PP = Interlocking combination Point within the Area
HH = Hours
MM = Minutes
Use "↑" "↓" to scroll between several interlocking combinations.
83 After the end of the delay time (if used).
84 This indication has low priority and will only be shown in the display if
there are no fire alarms, faults, disablements, etc.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
78
11.3.2
Activate interlocking output (H9/C2)
Even if the control expression for an interlocking output is not
fulfilled (true), the output can be manually activated via this menu.
The "Interlocking Combination" (Area / Point) is to be entered to
activate the output. The corresponding interlocking input will be
"monitored" in the same way as if the output was activated by its
control expression.
Reset has to be performed via menu H9/C3.
11.3.3
Reset interlocking output (H9/C3)
Activated interlocking outputs are listed here. Use "↑" "↓" to scroll
between the "Interlocking Combinations" (Area / Point).
Interlocking output activated via its control expression and latching
output selected: The output has to be reset via this menu.
Interlocking output activated via its control expression and latching
output not selected: The output can be reset via this menu.
Interlocking output activated via menu H9/C2: The output has to be
reset via this menu.
11.3.4
Disable interlocking output (H9/C4)
Interlocking outputs (i.e. Output Type = Interlocking) can be disabled
via menu H9/C4. A disabled output will stay in (or return to) the
normal condition for the output respectively. The "Interlocking
Combination" (i.e. Area / Point) is to be entered to disable the output.
If "00/00" is entered, all interlocking outputs will be disabled.
11.3.5
Re-enable interlocking output (H9/C5)
Interlocking outputs (i.e. Output Type = Interlocking) can be re-
enabled via menu H9/C5.
Disabled interlocking outputs are listed in menu H9/C5. Use "↑" "↓"
to scroll between the "Interlocking Combinations" (i.e. Area / Point)
or type it via the key-pad.
If "00/00" is entered, all interlocking outputs, disabled via menu
H9/C4 and "00/00", will be re-enabled.
11.4
Interlocking control expressions
A programmable output control expression can contain "interlocking"
trigger conditions ("Functions") numbers 14-17 (see chapter "Control
expression", page 69), i.e. one or more outputs can be activated when
one or more interlocking inputs are activated.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
79
12
Fire Door Closing function
Programmable outputs85 can be used for fire door closing. A special
trigger condition is available (no. 34 = Fire Door Closing). Type of
output shall normally be "Control, neutral". One or more alarm points
can control the output, e.g. the detectors on both sides of the fire door.
M
S
S
01-01
01-02
Programmable output
Door release magnet
Smoke detector
Fire
door
Fire Door Closing function (ABDL)
In case of one of the following events, the output will be "activated"
(i.e. powerless) and the fire door will close:
Fire alarm (any of the programmed detectors)
Fire alarm in "Test mode" (any of the programmed
detectors)
Fault (i.e. "no answer" from any of the programmed
detectors86)
Disablement (any of the programmed detectors, the involved
zone(s) or the COM loop).
A definite time every day, if programmed via Win128. (The
output will be activated for 20 seconds.)
Via a programmable input (trigger condition no. 17 = Door
Closing Test Input). (The output will be activated for 20
seconds.)
NOTE!
For safety reasons should an I/O unit 3361 output not be used.85 If
there is a short-circuit or a double break on the COM loop, the I/O
unit can not be "ordered" to activate the output, i.e. the door will not
be closed.
If a magnet contact is available, it is possible to get a "closed fire door
verification" via the Interlocking function. In this case, Type of in-
/output has to be "Interlocking in-/output". See also chapter
"Interlocking function", page 76.
85 In the DBI (Danish) convention, must only EBL128 outputs R0 and S0-S1
as well as the 3364 unit be used and "Type of output" has to be "Control
neutral".
86 E.g. a faulty detector, two breaks or short-circuit on the COM loop.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
80
13
Functions / Services / Features
Some Functions / Services / Features require programming via
Win128, see chapter "PC S/W", page 12. For more information see
also the EBL128 Operating Instructions and Win128 help.
How to connect the PC and more information, see the EBL128
Operating Instructions chapter "SSD programming and download" and
"Software (S/W) download".
13.1
Analog smoke detectors
13.1.1
Sensor value
The basic working principle and some expressions are described
below. Regarding the analog smoke detectors 430x in NORMAL
mode, see chapter "Alarm algorithms for smoke detectors / Detection
levels / Offsets", page 82.
An analog smoke detector is like a "sensor". It detects its environment
at all times. The detected analog values are, in the detector, converted
to digital "sensor values", which are for each individual detector,
continuously (each 3.4th sec.) picked up and evaluated by EBL128. In
Figure 16 the (digital) sensor values are represented by the graph
"Working level".
13.1.2
Week average sensor value
Each hour, one sensor value is stored (in EBL128) and each week are
these stored sensor values used to calculate a "week average sensor
value".87 This is done for each analog smoke detector individually.
In Figure 16 the (digital) week average sensor values are represented
by the graph "Week average".
Each analog smoke detector has a default sensor value = 1 (i.e. the
"Working level" at Time = 0). A "fire alarm offset" (value) is added
to get each detector's "Fire alarm level", i.e. the fire alarm level will
be adjusted in relation to each new week average sensor value in order
to keep the detector's fire alarm sensitivity constant. The fire alarm
level is in Figure 16 represented by the graph "Fire alarm level"
(being parallel with the graph "Week average").
Service signal will be given when the week average sensor value for a
detector has reached a fixed level, see "Service level" in Figure 16.
87 The very first week average sensor value will be calculated within 2
minutes after any restart, i.e. also after SSD download. During these "2 min."
all analog smoke detector fire alarms are suppressed.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
81
Figure 16. The basic working principle for one analog smoke
detector ("sensor"). Sensor value, working level, week average
sensor value, fire alarm offset / level and service level.
"Sensor Information" is available via menu H4/U3. Via Win128 and a
PC connected to EBL128 you can get "Sensor Information" for all
analog detectors on the COM loop or an individual detector. For an
individual detector you can also get continuous information. Also via
the Web-server II 1598 you can get "Sensor Information" for all
analog detectors on the COM loop.
The smoke detector sensor values are presented as obscuration in %
per meter (%/m) and heat detector sensor values as °C.
The following is valid for the analog smoke detector types 430x in NORMAL
mode.
In order to secure real alarms and reduce nuisance alarms, advanced
algorithms are used and a decision value is calculated, see below.
13.1.3
Decision value
The decision value is used to decide if it is normal state, pre-warning,
fire alarm or heavy smoke alarm. It is also used in the smouldering
smoke algorithm (see page 86). The decision value is calculated, see
chapter "Filtering algorithm, page 84.
13.1.4
Alarm algorithms for smoke detectors / Detection
levels / Offsets
Each detector uses an alarm algorithm and each detector has three
different detection levels for:
1. fire alarm88
88 The fire alarm level for each analog detector (sensor) = the current week
average sensor value + a fixed fire alarm offset (value), i.e. when the current
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
82
2. pre-warning will be activated at a lower level (smaller offset)
than for fire alarm, i.e. pre-warning will be activated before fire
alarm will be activated.
3. heavy smoke alarm will be activated at a higher level (bigger
offset) than for fire alarm, i.e. heavy smoke alarm will be
activated after fire alarm has been activated. Heavy smoke alarm
will be saved in the event log.89
The pre-warning offset and the heavy smoke alarm level can, for all
detectors, be set in Win128, see chapter "Alarm Algorithms", page
121. See also Win128 help.
The fire alarm offset can, for all detectors, be set in Win128, see
chapter "Alarm Algorithms", page 121. See also Win128 help.
NOTE! Changing these parameters will affect the sensitivity and
detection time and should be done by authorised personnel only!!!!!
In addition, a special password is required to change the fire alarm
parameters.
"Pre-warning", "Fire Alarm" and "Heavy Smoke Alarm" can activate
programmable outputs respectively, see chapter "Control expression",
page 69. See also the EBL128 Operating Instructions.
13.1.5
Alarm algorithm / Alternative alarm algorithm
Alarm algorithm
In order to secure real alarms and reduce nuisance alarms90, six
different alarm algorithms are available. See Figure 17., page 85.
The alarm algorithms are based on:
Normal, high or low sensitivity
Normal (15 sec.) or slow (35 sec.) detection time (alarm delay)
Normal sensitivity. 3.0 % smoke obscuration per meter is required to
activate fire alarm (i.e. fire alarm offset=30). This is default in the
N-15 algorithm and should normally not be changed.
High sensitivity. 2.4 % smoke obscuration per meter is required to
activate fire alarm, i.e. less fire alarm offset than for normal
sensitivity. High sensitivity can be used when an "early" fire alarm is
wanted.
Low sensitivity. 3.6 % smoke obscuration per meter is required to
activate fire alarm, i.e. a higher fire alarm offset than for normal
sensitivity. Low sensitivity can be used to get an extra delay time in
order to reduce nuisance alarms90 but might not fulfil the EN54-7
specifications.
week average sensor value is re-calculated (and adjusted) the fire alarm level
will also be adjusted. The detector sensitivity is accordingly constant.
89 No other heavy smoke alarm information if not an ext. FBP with printer is
available. If so, the heavy smoke alarm information will also be printed out.
90 So called false / unnecessary alarms.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
83
Normal detection time (15 sec.) If it was possible to completely fill
up a detector with smoke within 1 sec. there will nevertheless be 15
seconds alarm delay. This alarm delay is a "filter" to reduce nuisance
alarms.
Slow detection time (35 sec.). If it was possible to completely fill up
a detector with smoke within 1 sec. there will nevertheless be 35
seconds alarm delay. This alarm delay is an "extra filter" to reduce
the nuisance alarms90 but might not fulfil the EN54-7 specifications.
Alternative alarm algorithm
Each analog smoke detector can have two alarm algorithms
programmed (via Win128). One alarm algorithm that is normally
used (N-15 is default) and one alternative alarm algorithm turned on
/ off by a time channel (internal or external). Normal sensitivity can
for example be used during the night-time and low sensitivity and/or
slow detection time can be used during the daytime, i.e. the alternative
alarm algorithm can be used to reduce nuisance alarms90 during
working hours. The actual (current) alarm algorithm is shown in
menu H4/U3.
The alarm algorithm parameters can, for all detectors, be set in
Win128, see chapter "Alarm Algorithms", page 121. See also Win128
help.
13.1.6
Filtering algorithm
In order to secure a fast detection of real fire alarms and to reduce
nuisance alarms to a minimum, the filtering algorithm is used in the
six different alarm algorithms.
The filtering algorithm uses the sensor value to calculate a decision
value depending on which alarm algorithm that is selected.
The decision value starts at zero. Each time a new sensor value is
picked up (sampled) from an analog smoke detector, this new sensor
value is compared with the actual decision value, which will be
adjusted, see below.
If the difference, between the new sensor value and the actual decision
value is < "X", the decision value is set equal to the new sensor value.
If the difference, between the new sensor value and the actual decision
value is > "X", the decision value is increased (or decreased) by "X".
The decision value will consequently not be increased / decreased
with a value exceeding the "X" value even if the sensor value is much
higher / lower, see Figure 18.
"X" = The Step Value, is depending on which alarm algorithm that is
used, see Figure 17.
Analog
detector
Normal detection time (15sec.)
Slow detection time (35sec.)
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
84
H-15
(High
sensitivity,
2.4%)
N-15
(Normal
sensitivity,
3%)
L-15
(Low
sensitivity,
3.6%)
H-35
(High
sensitivity,
2.4%)
N-35
(Normal
sensitivity,
3%)
L-35
(Low
sensitivity,
3.6%)
4301
X=4
X=5
X=6
X=2
X=2
X=2
4300
X=8
X=10
X=12
X=4
X=4
X=4
Figure 17. The six alarm algorithms. Default is alarm algorithm
N-15, i.e. normal detection time (15 sec.) and normal sensitivity
(3%). "X" is the step value. (NOTE! The L-15, H-35, N-35 and
L-35 algorithms might not fulfil the EN54-7 specifications.)
Figure 18. An example showing the alarm algorithm "N-15", i.e.
the step value X = 5. The detector polling time t ≈ 3.4 sec.
Explanations to the figure:
One analog smoke detector 430x using alarm algorithm "N-15", i.e.
normal detection time (15sec.) and normal sensitivity (3.0 %/m). This
gives X = 5. The week average sensor value has in this example been
adjusted (due to contamination) and is now "10"91, i.e. the pre-warning
level is 10+offset 22=32 and the fire alarm level is 10+offset 30=40,
which is the same as 4.0 %/m.
The sensor values and decision values are approx. equal ("10"), until
the polling when the sensor value increases to approx. "27". Since
27-10 > X=5, the decision value is increased by "5" to "15" (10+5).
91 "10" = 1.0 %/m. A new / clean detector has approx. 0.1 %/m, i.e. this
detector is probably mounted in a very "dirty" environment. A detector
mounted in a normal office would after 8-10 years have approx. 0.3 %/m.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
85
Next polling the sensor value is approx. "45". 45-15 > 5, i.e. the
decision value "15" is increased by 5 to "20", and so on.
In this example the sensor value starts to decrease before the decision
value reaches the fire alarm level. When the sensor value has
decreased to approx. "25" the decision value is set to "30", because
35-25=10 > 5, i.e. the decision value "35" is decreased by 5 to "30",
and so on.
1. The sensor value has reached the pre-warning level but nothing
will happen since the decision value has not yet reached the pre-
warning level.
2. The sensor value has reached the fire alarm level but nothing will
happen since the decision value has not yet reached the fire alarm
level.
3. The decision value has reached / passed the pre-warning level and
pre-warning is activated.
4. The sensor values have started to decrease and the decision value
is now below the pre-warning level and the pre-warning is
automatically reset.
NOTE! In case of a real fire, the sensor values would have stayed at a
"high" value (> 40) for a long time and consequently the decision
value would have increased and reached / passed the fire alarm level
approx. 15 sec. after the sensor value reached the fire alarm level.
13.1.7
Smouldering smoke algorithm
The smoke from a smouldering fire brings the sensor value to rise
very slowly. This might last for hours and sometimes days. To be
able to detect such a smouldering fire at an "early" stage, a
smouldering smoke algorithm is used.
The smouldering smoke algorithm is depending on and is always
working parallel with the selected alarm algorithm, i.e. the
smouldering smoke algorithm will affect the pre-warning and fire
alarm levels, see below.
If the decision value has been over the smouldering level (1) for 7
minutes, the pre-warning and fire alarm levels will be lowered (2):
- The pre-warning level will be lowered to a level right between the
original pre-warning level and the smouldering level.
- The fire alarm level will be lowered to a level right between the
original fire alarm level and the pre-warning level.
If the decision value has reached the pre-warning level (3), but not the
fire alarm level, after additional 90 minutes, the pre-warning and fire
alarm levels will be lowered again (4):
- The pre-warning level will be lowered to the original smouldering
level.
- The fire alarm level will be lowered to the original pre-warning
level.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
86
The smouldering smoke algorithm will be aborted and the pre-
warning and fire alarm levels restored to their original values if:
- The decision value becomes lower than the smouldering level.
- The decision value, after the 90 minutes, has not reached the pre-
warning level.
- The decision value, after the 90 minutes and additional 120
minutes, has not reached the fire alarm level.
The smouldering offset can be set in Win128, see chapter "Alarm
Algorithms", page 121.
Figure 19. An example with the smouldering smoke algorithm.
Explanations to the figure:
Analog smoke detector 430x. The week average sensor value has in
this example been adjusted and is now "10"91, i.e. the smouldering
level is 10+offset 14=24, the pre-warning level is 10+offset 22=32 and
the fire alarm level is 10+offset 30=40.
When a smouldering fire starts, the sensor values and the decision
values will increase very slowly from "10" and upwards.
1. The decision value has reached the smouldering level. A 7
minutes timer is started.
2. After the 7 minutes the decision value is still over the smouldering
level. The pre-warning level and the fire alarm level are therefore
lowered. A 90 minutes timer is started.
3. The decision value has reached the pre-warning level and pre-
warning is activated.
4. After the 90 minutes the decision value is still over the pre-
warning level but has not reached the fire alarm level. The pre-
warning level and the fire alarm level are therefore lowered again.
A 120 minutes timer is started.
5. The decision value has reached the fire alarm level and fire alarm
is activated.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
87
6. The decision value has reached the original fire alarm level "40".
This happens approx. 90 minutes after the fire alarm has been
activated by the smouldering algorithm!!
13.1.8
Performance factor
To find out the environment conditions where an analog smoke
detector 430x is mounted, the Performance factor (Pf) can be studied
via menu H4/U3 or via Win128.
The performance factor is calculated for each detector individually.
Each momentary sensor value is compared with the week average
sensor value. The absolute difference is saved and each twenty-four
hour (at midnight) an "average value" is calculated, i.e. the
performance factor. (25412 = samples per 24 hours.)
If the detector is mounted in a very "stable" environment (like an
office) the performance factor will be low, i.e. min. 0 %/m.
If the detector is mounted in a very "unstable" environment (like in a
factory) the performance factor might be high, i.e. max. 2.55 %/m.
An "unstable" environment where the sensor values vary a lot can
cause nuisance alarms (unnecessary alarms). Perhaps should another
type of detector be used, another alarm algorithm92 or other actions be
taken, e.g. alert annunciation or two-unit-dependence (co-incidence
alarm).
The performance factor is shown in menu H4/U3 or via Win128
together with the min. and max. sensor values. These values should
be studied together. (E.g. one or two high sensor values will not result
in a high performance factor, like many high sensor values will.)
13.2
Analog heat detectors
The following is valid for the analog heat detector types 330x in NORMAL
mode.
The detectors conforms to a class (see EN54-5:2000, clause 4.2)
according to the requirements of the tests specified in EN54-5:2000,
clause 5. Each analog heat detector can have two alarm algorithms
programmed (via Win128).
One alarm algorithm that is normally used (default) and one
alternative alarm algorithm turned on / off by a time channel
(internal or external). E.g. class A1 can be used during night-time and
class B can be used during daytime. The alternative alarm algorithm
can be used to reduce nuisance alarms during working hours. The
actual algorithm is shown in menu H4/U3.
When EBL128 has picked up a sensor value above the fire alarm
level for a detector, the next two values from the same detector also
92 E.g. an alternative alarm algorithm during working hours.
25412
Σ |Xm-Xwa|
m=0
--------------------------- = Pf
25412
Xm = momentary sensor values
for 24 hours.
Xwa = weak average sensor value
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
88
have to be above the fire alarm level to activate fire alarm in EBL128.
(This results in approx. 7 seconds alarm delay).
The same is valid for pre-warning only it is a lower level than for fire
alarm.
The same is valid for heavy heat alarm only it is a higher level than
for fire alarm. Heavy heat alarm will be saved in the event log.93
The fire alarm, pre-warning and heavy heat alarm level respectively
can be set via Win128, see chapter "Alarm Algorithms", page 121.
"Pre-warning", "Fire Alarm" and "Heavy Smoke Alarm" can activate
programmable outputs respectively, see chapter "Control expression",
page 69. See also the EBL128 Operating Instructions for more
information.
13.2.1
Class A1 algorithm
Conforms to Class A1.
Typical / max. application temperature 25 / 50° C.
Max. / min. static response temperature 54 / 65° C.
The algorithm is as follows:
For a rate-of-rise < 4° C per minute:
Fire alarm level is 56° C.
Pre-warning level is 46° C.
Heavy heat alarm level is 90° C.
For a rate-of-rise > 4° C per minute:
Fire alarm level is 46° C.
Pre-warning level is 36° C.
Heavy heat alarm level is 90° C.
The biggest difference between the class A1 and A2 algorithms is that
the class A1 algorithm will detect a fast temperature rise (rate-of-rise
> 4° C per minute) faster than the class A2 algorithm.
13.2.2
Class A2 S algorithm
Conforms to Class A2 S.
Typical / max. application temperature 25 / 50° C.
Max. / min. static response temperature 54 / 70° C.
The algorithm is as follows:
Fire alarm level is 60° C.
Pre-warning level is 50° C.
Heavy heat alarm level is 90° C.
13.2.3
Class B S algorithm
Conforms to Class B S.
Typical / max. application temperature 40 / 50° C.
Max. / min. static response temperature 69 / 85° C.
93 No other heavy heat alarm information if not an ext. FBP with printer is
available. If so, the heavy heat alarm information will also be printed out.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
89
The algorithm is as follows:
Fire alarm level is 74° C.
Pre-warning level is 64° C.
Heavy heat alarm level is 90° C.
The class B S algorithm shall be used when the typical application
temperature is "high" compared with the class A1 and A2 algorithms.
13.3
Self verification
The analog detectors in NORMAL mode have a built-in self
verification function. The detector's H/W is always supervised by the
detector's S/W and CPU. Every minute, each detector will receive a
question from EBL128. If the self verification function has detected
any fault it will be reported back to EBL128. A fault will be activated
in EBL128 and the following fault message will be shown:
FAULT: Detector xx-xx →
FAULT: Detector techn. address nnn ←
13.4
Minimum / Maximum sensor values
To find out how the environment is, where an analog detector in
NORMAL mode is mounted, the minimum and maximum sensor
values can be studied. The sensor values are continuously picked up
and evaluated by EBL128 for each detector individually. Every value
is checked if it is a new minimum or maximum value for that detector
and if so, the value will be stored. At midnight every day a memory
will be updated and the new minimum and maximum sensor values94
can be read in menu H4/U3 or via Win128.
For analog smoke detectors the minimum and maximum sensor values
are shown as XX.X % (obscuration) per meter.
For analog heat detectors the values are shown as XX°C.
13.5
Two-unit dependence (co-incidence alarm)
In some premises two-unit-dependent fire alarm (co-incidence alarm)
can be used to avoid unwanted false alarms (nuisance alarms).
Each analog or addressable detector (alarm point) and addressable
multi purpose I/O unit (3361) monitored input (Z)95 can be
programmed for two-unit-dependent fire alarm activation. (Heat
detectors should not and manual call points must not be 2-unit
dependent).
94 I.e. the min. / max. sensor values are from the previous day.
95 In this case only one alarm point is recommended on the zone line.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
90
Function: Two or more two-unit-dependent alarm points in the same
zone have to be in "fire alarm state" (i.e. over the fire alarm level)96 at
the same time to activate fire alarm in EBL128. If only one such
alarm point is in "fire alarm state" it is indicated in EBL128 as a co-
incidence alarm:
The buzzer sounds 0.8 sec. each 5th sec. (like pre-warning).
In the display is the following text shown:
Co-incidence alarm detector ZZ/AA
Programmable outputs can be activated by the trigger condition "Two
Address Dependent Fire Alarm" but no other outputs will be activated.
A co-incidence alarm can be manually reset ("Reset" button on the
front) and will be automatically reset 5 min. after it is no longer in
"fire alarm state" (i.e. below the fire alarm level).
13.6
Two-zone dependence (co-incidence alarm)
This function is valid only for the 4580 board zone line inputs. Two
specified zones must be in fire alarm state at the same time to activate
fire alarm in EBL128.
In some premises two-zone-dependent fire alarm (co-incidence alarm)
can be used to avoid unwanted false alarms (nuisance alarms).
NOTE! It is not recommended to use heat detectors and/or manual
call points in a zone with this function.
If only one two-zone-dependent zone is in "fire alarm state" it is
indicated in EBL128 as a co-incidence alarm:
The buzzer sounds 0.8 sec. each 5th sec. (like pre-warning).
In the display is the following text shown:
Co-incidence alarm zone ZZ
Programmable outputs can be activated by the trigger condition "Two
Zone Dependent Fire Alarm" but no other outputs will be activated.
A co-incidence alarm can be manually reset ("Reset" button on the
front) and will be automatically reset 5 min. after it is no longer in
"fire alarm state".
13.7
Delayed alarm
In some premises delayed fire alarm activation can be used to avoid
unwanted false alarms (nuisance alarms). Note, this function is a
violation to the EN54-2 standard.
This function is valid only for the 4580 board zone line inputs.
96 A not two-unit dependent alarm point would in this state have activated a
fire alarm in EBL128.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
91
NOTE! It is not recommended to use heat detectors and/or manual
call points in a zone with this function.
The delay time can via Win128 be set to 30 or 60 seconds. (The
selected time is valid for all zones.)
The function "Delayed" is selected in the dialog box for the zone line
input respectively.
Function: A zone in "fire alarm state"97 will be recorded in EBL128
but a fire alarm will not be activated. When the delay time has run out
the zone will be automatically reset and if the zone is still in "fire
alarm state", a fire alarm will be activated in EBL128, else nothing
will happen until the next time the zone is in "fire alarm state" and a
new time delay will start.
13.8
Alarm Verification Facility
In some premises AVF can be used to avoid unwanted false alarms
(nuisance alarms). Note, this function is a violation to the EN54-2
standard.
This function is valid for any zone line input but only in the
Australian and New Zealand convention respectively.
In these conventions the function "Delayed alarm" (see above) is not
valid.
The function "Delayed" is selected in the dialog box for the zone line
input respectively.
Function: A zone in "fire alarm state"98 will be recorded in EBL128
but a fire alarm will not be activated. After 15 seconds the zone will
be automatically reset and if the zone comes in "fire alarm state" again
within 110 seconds, a fire alarm will be activated in EBL128, else
nothing will happen until the next time the zone is in "fire alarm state"
and so on.
13.9
Alert Annunciation
In some installations the Alert Annunciation function can be used to
avoid unwanted false alarms (nuisance alarms) to the fire brigade.
Trained personnel on site have to locate the "alarming" detector and
take the correct actions depending on if there is a fire or not.
Normally analog or addressable smoke detectors and zones with
smoke detectors only, should come in question for the AA function.
Heat detectors and manual call points should normally not come in
question for the AA function. A manual call point can only activate
the AA function if there are no other fire alarms activated, i.e. the
second fire alarm will turn OFF the AA function and the "Fire brigade
97 A not delayed zone would in this state activate a fire alarm in EBL128.
98 A zone with the AVF not selected would in this state activate a fire alarm
in EBL128.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
92
tx" output will be activated.
The AA function is normally ON (enabled) during daytime only (i.e.
working hours). The time channels 2-4 or the external time channels
5-12 are used to turn ON / OFF (enable / disable) the AA function.99
Figure 20. Alert Annunciation function flow chart.
AA Function: Indications, actions, etc. as for a normal fire alarm
except that the output for routing equipment (Fire brigade tx) 100
will not be activated directly.
The AA alarm has to be acknowledged within an acknowledge time
and the AA alarm has to be reset within an investigation time,
otherwise the output for routing equipment (Fire brigade tx) will be
activated.
During the acknowledge & investigation times the output for routing
equipment (Fire brigade tx) will be activated if:
fire alarm is activated by another detector not programmed for
alert annunciation
fire alarm is activated in another zone
fire alarm is activated by a manual call point
AA alarm is activated by a second detector within the same zone
programmed for alert annunciation and "Multiple alarms allowed
within same zone" is not selected101 via Win128.
Acknowledge and Reset is done on the Alert annunciation unit 1735 /
1736 (or Alert annunciation controller 1740). Programmable output
("Alert Announcement Activated" for indication and programmable
inputs
("Alert
Announcement
Acknowledge"
and
"Alert
Announcement Reset") can also be used.
99 The alert annunciation function ON (enabled) is indicated by the LED
"Fire brigade tx delay". Normally is only one time channel used for this
function but two or more channels can be used. The AA function can, as an
alternative, be continuously "on". NOTE! The AA function can be de-
activated (disabled) via menu H2/B10 and will stay so until re-activated (re-
enabled) again via menu H2/B10.
100 NOTE! As default it is the relay output "R0" in EBL128. If another
output shall be used it has to be programmed as type Routing Equipment
(Fire brigade tx) and the trigger condition has to be "Fire brigade tx".
101 Default the Check box is un-marked = Multiple alarms are not allowed
within same zone.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
93
The Acknowledge time can be set to 5-60 seconds.
The Investigation time can be set to 1-9 minutes.
NOTE! According to EN54-2, the total delay of fire alarm routing
equipment must not exceed 10 minutes (i.e. Acknowledge time +
Investigation time < 10 min.).
13.10
Alarm Acknowledgement Facility (AAF)
This function is similar to the "Alert Annunciation Function"
(described above) and used on the Australian market only.
One AAF zone can be one to five analog smoke detectors (4300 /
4301), one AAF buzzer (e.g. Sounder base 3378) and one AAF
Control (AAFC)102. All connected on the COM loop.
Sounder Base 3378
Smoke detector (4300, 4301)
COM loop
AAF
Non-latching switch
LED
PRESS TO ACKNOWLEDGE
FALSE ALARM
AAFC
Figure 21. Alarm Acknowledgement Facility units.
Function (see also the flow chart in the following figure):
- One of the detectors in an AAF zone reaches its fire alarm level.
The AA Process starts and the AAF buzzer sounds.
- An Acknowledgement Period starts
(AP=10-60 sec. -- programmable).
- If it is a false alarm, acknowledge the alarm on the AAFC before
the AP is ended.
- After acknowledgement an Investigation Period starts and the AAF
buzzer is silent
(IP=0-3 min. -- programmable).
If all the detectors in the AAF zone becomes normal again (i.e. goes
below the fire alarm level respectively) during the IP, the AAP ends.
If the AP or the IP runs out during the AAP and any detector in the
AAF zone still is over its fire alarm level, normal fire alarm(s) will be
activated.
102 This unit is available on the Australian market only.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
94
Quiscent state
AP timer starts
Count down
AAFC
button
pressed?
AP time
remains?
No
No
Yes
Yes
IP timer starts
Buzzer ON
Detector LED ON
AAFC LED ON
Buzzer OFF
All detectors
normal?
Count down
IP time
remains?
No
Yes
Yes
No
Fire Alarm
in the C.I.E.
Any detector
in alarm?
Yes
No
Detector LED OFF
AAFC LED OFF
AAFC LED OFF
Figure 22. Alarm Acknowledgement Facility (AAF) flow chart.
During the AAF process, an AAF alarm will be indicated in the c.i.e.
display ….
…. during the acknowledgement period (AP):
AAF zone xx, activated
…. during the investigation period (IP):
AAF zone xx, investigation in progress
If more than one AAF zones have been activated only the first is
shown in the display.
The detectors in an AAF zone can be one to five and not be
programmed as 2-unit-dependent and not be controlled by the Alert
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
95
Annunciation function. Only Analog photo electric smoke detector
4301 and Analog multi detector 4300 can be used for AAF. If the
Analog multi detector 4300 is used, it must be programmed as type
"Two addresses", so that only the "smoke part" of the detector can be
used for AAF.
Max. 50 AAF zones can be used.
The AAF buzzer (e.g. Sounder base 3378) has to be programmed with
the output trigger condition "AAF zone alarm".
13.11
Quiet alarm
Quiet alarm is e.g. used in conjunction with the I/O Matrix board
4582103, an application board for fan control and an I/O unit 3361 for
fan control.
NOTE! These units are available on the Australian market only.
Smoke detectors, programmed for quiet alarm, can be used e.g. for
controlling fans (stop / start depending on the type of fan).
Indications and actions:
In the c.i.e. display: Quiet alarm detector ZZ/AA and a
user definable text message (alarm text) if programmed.
LED:s "Fire" in the c.i.e. are blinking (0.4 / 0.4 sec.).
Buzzer in the c.i.e. sounding (0.8 / 5 sec.).
Programmable outputs for quiet alarm, e.g. 3361 outputs
controlling supply air fans and standard fans i.e. any output
with a control expression containing trigger conditions "Quiet
Alarm Zone" or "Quiet Alarm Zone Address".
Quiet alarms are non-latching, i.e. they will be automatically reset
when the alarm point / zone is no longer above alarm level.
NOTE! Quiet alarm can also be programmed for a 3361 unit "zone
line input". In such a case only non-latching detectors can be used.
13.12
Fire alarm type A and Fire alarm type B
Normally the c.i.e. relay output "R0" is used as an output for Routing
equipment (Fire brigade tx).
The output shall be programmed (via Win128) as type "Routing
equipment" and have the trigger condition "Fire brigade tx". The
output will then be activated for fire alarm from any alarm point or
zone line input.
If the fire alarm routing equipment has provision for transmission of
several fire alarm signals and the alarm receiver has provision for
reception of several fire alarm signals, a fire alarm type B will indicate
that only one detector is activated, which could be a nuisance alarm.
103 See "I/O Matrix board 4582", page 22.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
96
If a fire alarm type A is received, the probability of a real fire is higher
than for a fire alarm type B. The alarm receiver can take different
actions depending on if it is a fire alarm type A or B.
13.12.1
Fire alarm type B
The output will be activated for fire alarm from one analog
addressable smoke, heat or multi104 detector only.
The output shall be programmed (via Win128) as type "Routing
equipment" and have the trigger condition "One detector alarm".
13.12.2
Fire alarm type A
The output will be activated for fire alarm from:
Two or more analog addressable smoke, heat or multi
detectors.
Any manual call point
Any zone line input
Any programmable input with the trigger condition "General
Fire"
The output shall be programmed (via Win128) as type "Routing
equipment" and have the trigger condition "Multiple detector
alarm".
13.13
Disable zones, alarm points, outputs, etc.
Temporary disablements are made via the menu H2 sub menus B1-B3
& B7-B9. For more information see the EBL128 Operating
Instructions, chapter "Disable or re-enable (H2)".
Regular disablements are made via time channels, see chapter "Time
Channels", page 119.
Disabled alarm points and outputs are indicated by LED
"Disablements" and listed in menu H4/U1.
Fire alarm, pre-warning and fault signal can not be activated by a
disabled alarm point / zone.
13.13.1
Disable zone
A whole zone (all addressable alarm points within one zone, including
the manual call points) can be disabled via menu H2/B1. This menu is
also used to disable a conventional zone, i.e. a 3361 unit's zone line
input (Z) and expansion board 4580 zone line inputs.
Re-enable via menu H2/B4 or automatic re-enabling at a specified
time.
104 NOTE! A multi detector can have one presentation number (Zone-
Address) or two presentation numbers depending on how it is programmed
via Win128. One presentation number = one detector and two presentation
numbers = two detectors regarding fire alarm types A and B.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
97
A time channel can instead be used to disable and re-enable
automatically.
13.13.2
Disconnect / Re-connect zone line
Disconnect a zone line (on a 4580 board) via menu H5/A2.
Disconnected zone line will stay disconnected until re-connected.
Re-connect via menu H5/A2.
For more information see EBL128 Operating Instructions.
13.13.3
Disable zone / address
Individual alarm points can be disabled via menu H2/B2.
Re-enable via menu H2/B5 or automatic re-enabling at a specified
time.
A time channel can instead be used to disable and re-enable
automatically.
13.13.4
Disable control output
Individual control outputs can be disabled via menu H2/B3. Disabled
output will stay in (or return to) the normal condition for the output
respectively until re-enabled.
Re-enable via menu H2/B6.
13.13.5
Disable / Re-enable all control, exting. and ventilation
outputs
The control outputs of type "Control (general)", "Fire ventilation" and
"Extinguishing system" can be collective disabled via menu H2/B7.
Disabled outputs will stay in (or return to) the normal condition for the
output respectively until re-enabled.
Re-enable via menu H2/B7.
13.13.6
Disable / Re-enable alarm devices
The control outputs of type "Alarm device (sounder)" can be
collective disabled via menu H2/B8. Disabled outputs will stay in (or
return to) the normal condition for the output respectively until re-
enabled.
Re-enable via menu H2/B8.
13.13.7
Disable outputs for routing equipment
The control outputs of type "Routing equipment (Fire brigade tx and
Fault tx)" can be collective disabled via menu H2/B9. Disabled
outputs will stay in (or return to) the normal condition for the output
respectively until re-enabled.
Re-enable via menu H2/B9.
13.13.8
Disable interlocking output
The control outputs of type "Interlocking output" can be disabled via
menu H9/C4, see chapter "Disable interlocking output (H9/C4)", page
79.
Re-enable via menu H9/C5.
Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
EBL128 Planning Instructions V1.1.x
98
13.13.9
Disconnect / Re-connect COM loop
Disconnect the COM loop via menu H5/A1. Disconnected COM loop
will stay disconnected until re-connected.
Re-connect via menu H5/A1.
For more information see EBL128 Operating Instructions.
13.14
Test mode
Up to four zones can be set in Test mode at the same time.105 Alarm
points / zones can be tested during the Monthly test (via menu H1) or
separately (via menu H7). For more information see the EBL128
Operating Instructions. The LED "Test mode" indicates one or more
zones in Test mode. Zones in Test mode are also simultaneously
shown in the EBL128 display.106 In order to shorten the testing time,
any time delay for the detectors / zones in test mode will be
"disabled", i.e. fire alarm will be activated faster than normally.
13.15
Test alarm devices
The programmable outputs type "Alarm device" can be collectively
activated via menu H8/S3, which make it possible to test the alarm
devices. (The test can not be started if a fire alarm already is
activated.) When the test starts the alarm devices will be turned "ON"
for 5 seconds (±1s), "off" for 25 seconds (±1s), "on" for 5 seconds and
so on.107
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test will continue for one hour if it is not stopped via menu H8/S3
or if a fire alarm is activated in the system.
13.16
Test of routing equipment
Via menu H1 it is possible to test the fault and fire alarm outputs for
routing equipment (Fault tx & Fire brigade tx).
In menu H1, press "Accept" to start the test. The fault output will be
activated108, indicated by LED "Fault tx activated". After 30 seconds
will also the fire output be activated, indicated by LED "Fire brigade
tx". After additional 30 seconds will the test be ended and the outputs
and LEDs will go back to "normal" status.
105 In DBI (Danish) convention, one zone only.
106 Disablements, faults and fire alarms have higher priority, i.e. the
presentation of zones in Test mode will be suppressed during such a
condition.
107 The output activation will be continuously (steady). For the alarm
devices 3377 and 3378, the tone with the highest priority level (and type
"alarm device") will be automatically selected.
108 NOTE! The Fault tx output is activated in "normal" state, i.e. it will in
this test be de-activated.