Fire Alarm System EBL128

V1.1.x Author: Jan Pettersson Date of issue: 2008-07-11 Date of rev: 2010-05-28

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 1 Table of contents 1 Introduction________________________________ 7 2 Definitions / Explanations ____________________ 9 2.1 PEWF&STE AB ___________________________________ 9 2.2 Alarm point _______________________________________ 9 2.2.1 Smoke detector ________________________________ 9 2.2.2 Analog detector ________________________________ 9 2.2.3 Sensor _______________________________________ 9 2.2.4 (Analog) Sensor Base (ASB) _____________________ 9 2.2.5 Conventional detector ___________________________ 9 2.2.6 Conventional Detector Base (CDB) ________________ 9 2.2.7 Addressable ___________________________________ 9 2.2.8 Old detector __________________________________ 10 2.2.9 Conventional zone line _________________________ 10 2.2.10 Addressable zone interface ______________________ 10 2.3 Output unit ______________________________________ 10 2.4 Output / Control output _____________________________ 10 2.5 Short circuit isolator _______________________________ 10 2.6 Display unit (D.U.) ________________________________ 10 2.7 COM loop _______________________________________ 10 2.8 Control Unit (C.U.) / C.I.E. __________________________ 10 2.9 Fire Brigade Panel (FBP) ___________________________ 10 2.10 Control panel (CP) ________________________________ 11 2.11 LED ____________________________________________ 11 2.12 External Indicator (LED) ___________________________ 11 2.13 Display / LCD ____________________________________ 11 2.14 Door open / Key switch _____________________________ 11 2.15 SSD / Site Specific Data ____________________________ 11 2.16 S/W / Software / System program _____________________ 11 3 Overview _________________________________ 12 3.1 The EBL128 c.i.e. _________________________________ 12 3.2 S/W Versions ____________________________________ 12 3.3 Documents ______________________________________ 12 3.4 Applications _____________________________________ 12 3.5 PC S/W _________________________________________ 12 4 Control & Indicating Equipment _____________ 13 4.1 COM loop _______________________________________ 15 4.1.1 A single break (cut-off) on the COM loop __________ 16 4.1.2 Several breaks (cut-offs) on the COM loop _________ 17 4.1.3 Short-circuit on the COM loop ___________________ 18 4.2 Programmable voltage outputs (S0-S1) ________________ 18 4.3 Programmable relay output (R0) ______________________ 19 4.4 Relay output for routing equipment (fault tx) (R1) ________ 19

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 2 4.5 Programmable input (I0) ____________________________ 19 4.6 24 V DC power supply outputs _______________________ 20 4.7 RS232 interfaces __________________________________ 20 4.8 RS485 transceiver (option) __________________________ 20 4.9 Power supply _____________________________________ 20 4.10 Internal Power supply ______________________________ 21 5 Expansion boards 458x _____________________ 22 5.1 Expansion board address setting ______________________ 23 5.2 8 zones expansion board 4580 _______________________ 23 5.2.1 Type of zone line input _________________________ 24 5.2.2 Input states __________________________________ 24 5.3 8 relays expansion board 4581 _______________________ 25 5.4 Inputs and outputs expansion board 4583 _______________ 26 5.5 I/O Matrix board 4582 _____________________________ 27 5.5.1 Generic _____________________________________ 28 5.5.2 Fan control __________________________________ 29 5.5.3 Zone control _________________________________ 29 6 Peripheral devices __________________________ 30 6.1 COM loop units ___________________________________ 30 6.1.1 Input units ___________________________________ 31 6.1.2 Addressable I/O units __________________________ 39 6.1.3 Alarm devices (addressable sounders) _____________ 40 6.1.4 Short circuit isolators (addressable) _______________ 42 6.1.5 Units for Hazardous (Ex) areas ___________________ 43 6.1.6 Other COM loop units __________________________ 44 6.1.7 COM loop addresses for Base station and Wireless detectors 46 6.2 Units connected to the RS485 interface ________________ 46 6.2.1 External Fire Brigade Panels _____________________ 47 6.2.2 Alert Annunciation Units _______________________ 48 6.2.3 External Presentation Units ______________________ 49 6.2.4 German Fire Brigade Panels _____________________ 50 6.3 Units connected to the RS232 interface J5 ______________ 51 6.3.1 Web-servers __________________________________ 51 6.4 Units connected to the RS232 interface J3 ______________ 51 6.5 Other units _______________________________________ 51 6.5.1 Alert Annunciation Controllers ___________________ 51 6.5.2 External LEDs ________________________________ 52 6.5.3 Alarm devices (sounders, etc.) ___________________ 53 6.5.4 Door release magnets __________________________ 53 6.5.5 Boxes _______________________________________ 53 7 Programmable inputs _______________________ 54 7.1 Control unit Input I0 & Inputs and Outputs exp. board 4583, Input 0-4 ______________________________________________ 55 7.1.1 Not supervised ________________________________ 55

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 3 7.1.2 Supervised ___________________________________ 55 7.2 3361 unit Inputs In0 / Z & In1 _______________________ 56 8 Input programming ________________________ 57 8.1 Type (trigger conditions) ____________________________ 57 8.2 Logic ___________________________________________ 59 8.2.1 Not supervised (default) ________________________ 60 8.2.2 Supervised ___________________________________ 60 9 Programmable outputs ______________________ 61 9.1 Control unit outputs S0 – S1 _________________________ 62 9.2 Control unit output R0 _____________________________ 63 9.3 8 relay outputs expansion board 4581 Output 0 – Output 7 _ 63 9.4 Inputs and Outputs expansion board 4583 Output 0 – 1 ____ 63 9.5 The 3361 unit outputs Re0 – Re1 _____________________ 64 9.6 The 3364 unit outputs VO0, VO1 & VO2 ______________ 64 9.7 The 3377 unit output (siren) _________________________ 64 9.8 The 3378 unit output (sounder) _______________________ 64 9.9 The 3379 unit output (sounder) _______________________ 64 10 Output programming _______________________ 65 10.1 Type ___________________________________________ 65 10.2 Logic ___________________________________________ 66 10.3 Supervised _______________________________________ 66 10.4 Output signal period _______________________________ 66 10.5 Control expression ________________________________ 69 10.5.1 Trigger conditions _____________________________ 69 10.5.2 Logical operators ______________________________ 72 10.5.3 Control expression examples ____________________ 72 11 Interlocking function _______________________ 76 11.1 Interlocking programming __________________________ 76 11.1.1 Interlocking output ____________________________ 76 11.1.2 Interlocking input _____________________________ 76 11.1.3 Interlocking combination _______________________ 76 11.2 Interlocking indications _____________________________ 78 11.3 Information of interlocking combinations (H9) __________ 78 11.3.1 Display interlocking information (H9/C1) __________ 78 11.3.2 Activate interlocking output (H9/C2) ______________ 79 11.3.3 Reset interlocking output (H9/C3) ________________ 79 11.3.4 Disable interlocking output (H9/C4) _______________ 79 11.3.5 Re-enable interlocking output (H9/C5) _____________ 79 11.4 Interlocking control expressions ______________________ 79 12 Fire Door Closing function __________________ 80 13 Functions / Services / Features _______________ 81 13.1 Analog smoke detectors ____________________________ 81 13.1.1 Sensor value _________________________________ 81 13.1.2 Week average sensor value ______________________ 81

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 4 13.1.3 Decision value ________________________________ 82 13.1.4 Alarm algorithms for smoke detectors / Detection levels / Offsets 82 13.1.5 Alarm algorithm / Alternative alarm algorithm ______ 83 13.1.6 Filtering algorithm ____________________________ 84 13.1.7 Smouldering smoke algorithm ___________________ 86 13.1.8 Performance factor ____________________________ 88 13.2 Analog heat detectors ______________________________ 88 13.2.1 Class A1 algorithm ____________________________ 89 13.2.2 Class A2 S algorithm __________________________ 89 13.2.3 Class B S algorithm ____________________________ 89 13.3 Self verification ___________________________________ 90 13.4 Minimum / Maximum sensor values ___________________ 90 13.5 Two-unit dependence (co-incidence alarm) _____________ 90 13.6 Two-zone dependence (co-incidence alarm) _____________ 91 13.7 Delayed alarm ____________________________________ 92 13.8 Alarm Verification Facility __________________________ 92 13.9 Alert Annunciation ________________________________ 92 13.10 Alarm Acknowledgement Facility (AAF) _____________ 94 13.11 Quiet alarm ____________________________________ 96 13.12 Fire alarm type A and Fire alarm type B ______________ 96 13.12.1 Fire alarm type B ____________________________ 97 13.12.2 Fire alarm type A ___________________________ 97 13.13 Disable zones, alarm points, outputs, etc. _____________ 97 13.13.1 Disable zone _______________________________ 98 13.13.2 Disconnect / Re-connect zone line ______________ 98 13.13.3 Disable zone / address ________________________ 98 13.13.4 Disable control output ________________________ 98 13.13.5 Disable / Re-enable all control, exting. and ventilation outputs 98 13.13.6 Disable / Re-enable alarm devices ______________ 98 13.13.7 Disable outputs for routing equipment ___________ 98 13.13.8 Disable interlocking output ____________________ 99 13.13.9 Disconnect / Re-connect COM loop _____________ 99 13.14 Test mode _____________________________________ 99 13.15 Test alarm devices _______________________________ 99 13.16 Test of routing equipment ________________________ 100 13.17 Calibration of supervised outputs __________________ 100 13.18 Service signal _________________________________ 100 13.19 Fault signal (fault condition) ______________________ 100 13.20 Alarm texts ___________________________________ 101 13.20.1 Creating the alarm texts via Win128 ____________ 101 13.20.2 Downloading texts to the EPU 1728, AAUs 1735 / 1736 and ext. FBPs 1826 / 1828 ________________________ 103 13.21 Real time clock (RTC) __________________________ 103 13.21.1 Daylight saving time ________________________ 104

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 5 13.22 Time channels 1-4 ______________________________ 104 13.23 Time channels 5-12 _____________________________ 104 13.24 Event log _____________________________________ 105 13.25 Loss of main power source _______________________ 105 13.25.1 Fault: Loss of main power source ______________ 105 13.25.2 LCD backlight _____________________________ 105 13.26 Win128 Tools menu ____________________________ 105 14 Special New Zealand functions ______________ 108 14.1 Alarm devices ___________________________________ 108 14.1.1 Silence alarm devices (inside switch) _____________ 108 14.1.2 New Zealand FB Silence switch (outside switch) ____ 108 14.2 Battery faults ____________________________________ 109 14.2.1 FAULT: Battery _____________________________ 109 14.2.2 FAULT: Low battery capacity __________________ 109 14.3 Watchdog reset __________________________________ 110 14.4 Routing equipment isolate (disable) __________________ 110 14.5 Acknowledged alarm _____________________________ 110 15 Cyber sensor functions _____________________ 111 15.1 Pulse up – down counter ___________________________ 112 15.1.1 Pulse up – down counter for smoke ______________ 112 15.1.2 Pulse up – down counter for temperature __________ 112 15.1.3 Pulse up – down counter for smoke & temperature __ 112 15.2 Fire judgement __________________________________ 112 15.3 Alarm threshold levels ____________________________ 113 15.4 Learning function / Learning conditions _______________ 113 15.4.1 Learning conditions ___________________________ 113 15.5 Alarm delay time _________________________________ 115 15.6 Analog data output _______________________________ 116 15.7 Sensitivity compensation __________________________ 116 15.8 Self diagnosis of internal devices ____________________ 116 15.9 Address setting check _____________________________ 117 16 Control unit properties (settings) ____________ 118 16.1 Control Unit Properties ____________________________ 118 16.1.1 AAF times __________________________________ 118 16.1.2 Alert annunciation times _______________________ 118 16.2 Time Channels __________________________________ 119 16.3 Alarm Algorithms ________________________________ 121 16.3.1 Parameters for smoke algorithms ________________ 122 16.3.2 Parameters for heat algorithms __________________ 122 16.3.3 Parameters for combined decision algorithm _______ 123 16.4 National Holidays ________________________________ 123 16.5 Output Signal Periods _____________________________ 125 16.6 Advanced ______________________________________ 126 16.6.1 Main power loss fault _________________________ 126 16.6.2 Alarm reset _________________________________ 126

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 6 16.6.3 Door closing by time __________________________ 126 16.6.4 Zone line input alarm delay time _________________ 127 16.6.5 Miscellaneous _______________________________ 127 16.7 Statistics _______________________________________ 128 17 Cable types ______________________________ 129 17.1 COM loop cables_________________________________ 129 17.2 Ext. FBP / EPU / AAU cables _______________________ 129 17.3 Conventional zone line cables _______________________ 129 17.4 Alarm device cables ______________________________ 129 17.5 Other equipment cables ____________________________ 129 18 COM loop cable length _____________________ 131 19 Current consumption ______________________ 134 20 Power supply _____________________________ 137 20.1 Charger functions ________________________________ 137 20.1.1 Battery charging functions: _____________________ 138 20.1.2 Security functions ____________________________ 138 20.2 Current consumption calculations ____________________ 139 20.3 Main power source (Power Supply) __________________ 140 20.4 Second power source (Battery) ______________________ 140 20.5 Form / Table of current consumption _________________ 141 21 S/W versions _____________________________ 142 22 Technical data ____________________________ 143 23 Limitations_______________________________ 144 23.1 C.i.e. __________________________________________ 144 24 National regulations / requirements __________ 145 24.1 Conventions_____________________________________ 145 24.2 Language _______________________________________ 145 25 Drawings / connection diagrams _____________ 146 26 Revision history ___________________________ 147 Drawings according to the valid table of drawings.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 7 1 Introduction EBL128 Planning Instructions is a document1 with information of special interest for planning engineers as well as service / commissioning engineers. It should be read in conjunction with the EBL128 Operating Instructions, since most of the information in one of the documents is not found in the other document and vice versa. It should also be read in conjunction with the EBL128 drawings2, according to the valid Table of drawings. A Product Leaflet is also available at: http://www.panasonic-fire-security.com/pewfste/en/html (Data sheets) When planning a fire alarm installation the national regulations have to be obeyed. A lot of detector types can be used. Detector coverage area and detector placing in the room / building, etc. are matters for the planning engineers and are not described in this document. Due to continual development and improvement, different S/W versions are to be found. This document is valid for the EBL128 S/W version 1.1.x. On the date of this document is x=2. EBL128 S/W version 1.1.x support and some functions require the EBL128 main board 4556 with p.c.b. no. 9285-6A. S/W version 1.1.x also support main board with p.c.b. no. < 9285-6A (e.g. 9285-5A). EBL128 is produced for many countries, accordingly the look, the texts, the functions, etc. might vary from country to country. Products Products consists of one or more parts (H/W) according to a Product Parts List. A product has:  a type number (e.g. 4550)  an article number, often the same as the type no. but sometimes a country code is added (e.g. 4550SE)  a product name (e.g. EBL128 Control & Indicating Equipment, 128 addresses) H/W A H/W (e.g. a printed circuit board) has:  a type number (e.g. 1556)  an article number, often the same as the type no. but sometimes a country code is added (e.g. 1556SE)  a product name (e.g. Main Board 128 addr.) 1 File name: K:\PRO\FIRE\128\Doc\V1.1.x\MEW01090 (Rev 3).doc 2 Dimensions & overviews, connection diagrams, etc.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 8  a p.c.b. number (e.g. 9285-6A) and can also have a configuration (e.g. CFG: 1) and a revision (e.g. REV: 2)  sometimes is a S/W (software) downloaded. S/W A S/W has:  a version number (e.g. V1.1 or V1.1.0)  sometimes is additional information, such as Convention (different functions / facilities), Language, etc. added. PC S/W A PC S/W is a program used for programming, commissioning, etc. It has a version number.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 9 2 Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. 2.1 PEWN AB Panasonic Electric Works Nordic AB 2.2 Alarm point Unit, which can generate a fire alarm, i.e. an analog or conventional detector, a manual call point, etc. 2.2.1 Smoke detector Two types of analog and conventional smoke detectors are available: photo electric (optical) and ionization. 2.2.2 Analog detector Contains an A/D-converter. EBL128 picks up the digital values ("sensor values") for each detector individually. All evaluations and "decisions" are then made in EBL128, i.e. by advanced algorithms. Analog detectors are addressable – an address setting tool is used. An analog detector has to be plugged in an ASB. 2.2.3 Sensor Sensor = Analog detector 2.2.4 (Analog) Sensor Base (ASB) A sensor is plugged in an ASB, which is connected to a COM loop (see below). 2.2.5 Conventional detector Detector with two states, normal or fire alarm. The detector contains a closing contact and a series alarm resistor. Some types are plugged in a CDB (see below) but some types are water proof and are not plugged in any base. (Conventional detectors are normally plugged in a CDB (see below) and connected to a conventional zone line with end-of-line device.) 2.2.6 Conventional Detector Base (CDB) A conventional detector is plugged in a CDB and connected to a conventional zone line input. 2.2.7 Addressable A unit with a built-in address device (e.g. a manual call point). Each unit is individually identified, handled and indicated in EBL128. (The unit can consequently be an I/O unit, to which one or more conventional "alarm points" can be connected on the zone line.).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 10 2.2.8 Old detector Conventional detector with a closing contact (short circuit; no alarm resistor), or detector with two breaking contacts. 2.2.9 Conventional zone line Zone line input on e.g. an I/O unit, intended for one or more conventional alarm points. End-of-line device in the last alarm point. 2.2.10 Addressable zone interface Unit with a zone line input, intended for one or more conventional alarm points. End-of-line device in the last alarm point. 2.3 Output unit Addressable unit with programmable control outputs (e.g. an I/O unit). To be connected to a COM loop (see below). 2.4 Output / Control output Defined or programmable function. Relay or (supervised / monitored) voltage output, in EBL128 or an output unit. 2.5 Short circuit isolator Addressable unit for automatic isolation of a segment on a COM loop (see below) in case of short circuit on the loop. 2.6 Display unit (D.U.) Unit for fire alarm presentation (incl. alarm texts, if programmed). Connected to an RS485 line. 2.7 COM loop Loop = a cable (a twisted pair), to which all the addressable Panasonic COM loop units can be connected. It starts in EBL128 and it returns back to EBL128. 2.8 Control Unit (C.U.) / C.I.E. Control Unit = C.U. = Control and Indicating Equipment = A unit, e.g. EBL128, to which the alarm points are connected. Indicates fire alarm, fault condition, etc. on the front, i.e. on the Fire Brigade & Control Panel (see below). 2.9 Fire Brigade Panel (FBP) The Fire Brigade Panel is a part of the EBL128 front, intended for fire alarm presentation, etc. for the fire brigade personnel. A separate unit; an external FBP, can also be connected to EBL128. In the ext. FBP a printer can be included.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 11 2.10 Control panel (CP) The Control Panel is a part of the EBL128 front, intended for the building occupier, service personnel, etc. to "communicate" with EBL128 / the system. 2.11 LED LED (Light Emitting Diode) = Yellow, green or red optical indicator ("lamp"). 2.12 External Indicator (LED) A unit with an LED. Connected to an ASB, CDB or a detector with a built-in LED, for external indication. Lit when the built-in LED is lit. 2.13 Display / LCD LCD (Liquid Crystal Display) = Display for presentation of fire alarms, fault messages, etc. Normally alphanumeric characters and backlight. 2.14 Door open / Key switch A door / key switch, which has to be activated in order to get access to the push buttons on the front. Indicated by the LED "Door open". 2.15 SSD / Site Specific Data This data is unique for each installation. All alarm points, presentation numbers, alarm texts, programmable outputs, etc. are programmed (configured) in the PC program Win128 and has to be downloaded in EBL128. 2.16 S/W / Software / System program The S/W makes EBL128 (the microprocessor) work. It is factory downloaded but a new version can be downloaded in EBL128 on site.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 12 3 Overview 3.1 The EBL128 c.i.e. EBL128 is a microprocessor controlled intelligent fire alarm Control and Indicating Equipment (c.i.e.) intended for analog addressable smoke and heat detectors. Also conventional detectors and manual call points can be used. Programmable inputs, control outputs and I/O units are available. Up to 128 addresses can be connected to EBL128. EBL128 is fully compliant with the European standard EN54 parts 2 and 4 and the front is fully SS3654 compliant. 3.2 S/W Versions Due to continual development and improvement, different S/W versions can be found. The control unit S/W can be updated on site. 3.3 Documents The following documents are available:  Planning instructions  Drawings  Operating instructions Information found in one document is normally not to be found in another document, i.e. the documents complement each other. Product Leaflet for EBL128 and other units are available as pdf documents on our web site: http://www.panasonic-fire-security.com 3.4 Applications EBL128 is intended for small and medium installations. The intelligent control unit offer the system designer and end user a technically sophisticated range of facilities and functions. Programming (via PC S/W Win128) and commissioning is very easy. 3.5 PC S/W Win128 is used for programming and commissioning, i.e. to:  create / download / upload (backup) the site specific data (SSD)  download new S/W version, language (text file), EBL128 settings (e.g. convention), etc.  create / download the alarm texts shown in the display in EBL128, ext. FBP and/or AA units. The Win128 S/W shall have the same version number as the EBL128 S/W version number, e.g. 1.0.x. Only x may be different. Old SSD files can be used with a newer EBL128 S/W version. Open and save the old SSD file in the new Win128 version before the download. If a backup is required, use the same Win128 version as the EBL128 version.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 13 4 Control & Indicating Equipment Figure 1. The EBL128 Control & Indicating Equipment (4550). Depending on country, convention, configuration, etc. the look, language and functions might vary. Figure 1 shows an EBL128 with English front. The metal housing consists of a wall mounted chassis on which a removable skin, incl. the door, is attached. This makes the installation and service very easy. EBL128 is in its basic configuration equipped with:  Main board 4556 with: o One COM loop (0) to which the loop units are connected. Connections and more information, see drawing 128-21. o Two programmable supervised voltage outputs (S0-S1). Default programmed as outputs for alarm devices. Connections and more information, see drawing 128-22. o One programmable relay output (R0). Default programmed as output for routing equipment (Fire brigade tx). Connections and more information, see drawing 128-23. o One not programmable relay output for routing equipment (Fault tx). Connections and more information, see drawing 128-23. o One programmable input (I0). Supervised when required. Connections and more information, see drawing 128-22. o Two 24 V DC power supply outputs (for routing equipment and external equipment respectively). Connections and more information, see drawing 128-22.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 14 o A socket for an optional Communication module (RS485 transceiver component) 4552, which will provide an RS485 interface (serial line) for up to four Display Units (1735 / 1736 and/or 1826 / 1828 and/or 1728). Max. one 1826 with printer. Connections and more information, see drawing 128-23. On the RS485 serial line can as an alternative, up to four German Fire Brigade Control Panels (Feuerwehr-Bedienfeld) FBF 20033 and/or German Fire Brigade Indicator Panels (Feuerwehr-Anzeigetableau) FAT 20023 be connected. o RS232 interface ("D" connector) for a PC with Win128. Connections and more information, see drawing 128-25. o RS232 interface for a Web-server 1598. Connections and more information, see drawing 128-25. o 24 V DC power supply output for a Web-server 1598. Connections and more information, see drawing 128-25.  Built-in power supply (rectifier) and space for back-up batteries. Connections and more information, see drawing 128-24.  Space for optional expansion board holder (Expansion boards mounting kit 4551). Up to four expansion boards can be mounted in the holder.  Space for routing equipment.  DIN-rail (and space) for a Web-server 1598.  Cable inlets (rubber grommet / knock-outs) on the top, bottom and back sides. The door has a Plexiglas ahead of the front, see Figure 1. A key is required to open the door to get full access to the push buttons on the front, i.e. the Fire Brigade Panel (FBP) and the Control Panel (CP). Figure 2. The EBL128 front. The look might vary depending on the country (language), configuration, etc. (e.g. English texts as in the figure). LEDs & push buttons are described in the EBL128 Operating Instructions. 3 Manufacturer: IFAM GmbH, Erfurt, Germany. www.ifam-erfurt.de FBP CP

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 15 The FBP is used by the fire brigade personnel to see which alarm point / zone having activated the fire alarm(s), silence alarm devices, reset alarms, etc. In the display (LCD, 2x40 alphanumeric characters), the information displayed on the first row is depending on how many alarm points / zones having activated fire alarm, convention and language. On the second row is, for the activated alarm point / zone, an alarm text shown, if programmed. For more detailed information regarding the display information, see the EBL128 Operating instructions. Required fire brigade personnel manoeuvres are performed via the FBP in EBL128 or via an external FBP 1826 / 1828. Instead of external FBPs 1826 / 1828, German Fire Brigade Control Panels (Feuerwehr-Bedienfeld) FBF 2003 and/or German Fire Brigade Indicator Panels (Feuerwehr-Anzeigetableau) FAT 2002 can be used. The CP is used by the EBL128 owner, service personnel, etc. to "communicate" with EBL128, e.g. for monthly tests, disablements commissioning, maintenance and service. Access codes for different access levels are required. A keypad is used to get access to the menu tree, i.e. main and sub menus for data input / output, manoeuvres, etc. The CP also holds several system status LEDs. 4.1 COM loop EBL128 has one COM loop (0), to which the loop units are connected. Connections to "J1:1-4" according to drawing 128-21. On the COM loop can theoretically 127 COM loop units be connected (i.e. address 1-127). The exact number of addresses that can be used and the cable length are depending on the cable type (cable resistance) and the total COM loop unit current consumption (i.e. the type and number of loop units). See chapter "Current consumption", page 134 and drawing 128-11. Each COM loop unit has a technical address and each alarm point and zone line input has a presentation number (zone-address). See the EBL128 Operating Instructions for more information. If one or more addressable Short Circuit Isolators (SCI 4313 / 4370) are used, the loop will be divided into "segments", i.e. the part between two isolators or between EBL128 and one isolator. In case of short-circuit on the COM loop only the affected segment will be isolated, which will minimise the number of units "disabled". See Figure 9, page 43. Break (cut-off) or short circuit on the COM loop Normally EBL128 communicates with the units in the A-direction only and is in the B-direction checking the COM loop voltage only, which shall be > 12 V DC. There can be no one, one or up to eight addressable Short Circuit Isolators, 4313 / 4370 (SCI), connected on the COM loop.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 16 In case of short-circuit or a break (cut-off) on the COM loop, EBL128 will in order to localize it, do the following:  The COM loop voltage and communication will be turned off. Because of that all isolators will also be turned off, i.e. the L (SA) contact in each isolator will be "open".  The COM loop voltage and communication will be turned on again.4 The isolators will now be turned on one after another in the A-direction, until it is not possible to turn on any more isolator, i.e. the isolator closest to a short-circuit will not be turned on alt. the isolator closest to (just before) a break will be turned on but the isolator after a break can of course not be turned on.  The COM loop communication will now start in the B- direction also and the isolators will be turned on one after another, until it is not possible to turn on any more isolator, i.e. the isolator closest to a short-circuit will not be turned on alt. the isolator closest to (just before) a break will be turned on.  In case of short-circuit on the COM loop, only the segment(s) between the now turned off isolators will be isolated.  One or more fault messages will be shown in the EBL128 display, see below. The fault messages will be different depending on if it is a single or double break or short-circuit on the COM loop, as well as if there is no one, one or several isolators connected on the COM loop, see following chapters. In any case, each unit not found by EBL128 will generate a fault: FAULT: No reply xx-xx Press "" to see the technical address. FAULT: No reply techn. address xxx Regarding Fault acknowledge, see the EBL128 Operating Instructions. 4.1.1 A single break (cut-off) on the COM loop If not all units are found when communicating in the A-direction only, but when communicating in both directions, it must be a single break (cut-off) on the COM loop. One fault will be generated and the following fault message will be shown: 4 Short-circuit on a COM loop with no isolators: The voltage and communication will not be turned on.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 17 FAULT: Cut-off SCI n <-> SCI n n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7 depending on if no one, one or several isolators are used. A & B are the built-in control unit isolators in the A- and B-direction respectively. If no isolator is used the information will be: A<->B. If one isolator (no. 0) is used: A<->0 or 0<->B If two isolators (no. 0 and no. 1) are used: A<->0, 0<->1 or 1<->B ...and so on. The break (cut-off) is found in the specified segment, e.g. A<->0. Each 10th minute a new attempt is made to communicate in the A- direction only. When the fault is corrected (no break / cut-off) the communication automatically returns to communicate in the A-direction only.5 4.1.2 Several breaks (cut-offs) on the COM loop If not all units are found when communicating in the A-direction only, and not when communicating in both directions, there must be two or more breaks on the COM loop. A "no replay fault" (see above) will be generated for each unit not found. There will also the following fault message: FAULT: Cut-off SCI n <-> SCI n n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7 depending on if no one, one or several isolators are used. A & B are the built-in control unit isolators in the A- and B-direction respectively. In case of a break (cut-off) in more than one segment there will also be the following message: FAULT: Several faults on COM loop In case of "Several faults on COM loop": Correct the cut-off fault shown in the display and the next cut-off fault will be shown, and so on. Each 10th minute a new attempt is made to communicate in the A- direction only. When all faults are corrected (no breaks / cut-offs) the communication automatically returns to communicate in the A-direction only.5 5 NOTE! The fault has to be acknowledged and it can last up to 10 minutes before the communication returns to communicate in the A-direction only.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 18 4.1.3 Short-circuit on the COM loop Short-circuit between the L (SA) and C (SB) wires6 will generate a fault with the following fault message: FAULT: Short-circuit SCI n <-> SCI n n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7 depending on if no one or several isolators are used. A & B are the built-in control unit isolators in the A- and B-direction respectively. If no isolator is used the information will be: A<->B. If one isolator (no. 0) is used: A<->0 or 0<->B If two isolators (no. 0 and no. 1) are used: A<->0, 0<->1 or 1<->B ...and so on. The short-circuit is in the specified segment, e.g. A<->0. In case of short-circuit in more than one segment on the COM loop, the fault messages will be similar to the message shown for several breaks (cut-offs), FAULT: Several... (see above). Each 10th minute a new attempt is made to communicate in the A- direction only. When the fault is corrected (no short-circuit) the communication automatically returns to communicate in the A-direction only. 5 4.2 Programmable voltage outputs (S0-S1) The outputs S0-S1 are normally supervised (monitored).7 One to five 33K resistors can be connected. Connections to "J1:5-8" according to drawing 128-22. When the connections are finished, a calibration has to be done.8 See also the EBL128 Operating Instructions chapter "Calibration of supervised outputs (menu H5/A3)". Each output has to be programmed (via Win128) regarding:  Type (Control, Fire ventilation, Alarm device, etc.)  Output signal period (steady, intermittent, pulse, delay, etc.)  Supervised / Not supervised  Logic, i.e. normally low (default) or normally high (24 V DC)9.  Control expression (containing one or more trigger conditions) NOTE! The outputs S0-S1 are as default programmed as outputs for alarm devices. S0: max. 500 mA (Fuse F8). 6 Depending on the cable type / length and where the loop short-circuit is located, it can take up to 10 seconds before the fault is generated. 7 A normally high output can not be supervised. The supervision voltage is 1.5 – 3.6 V DC (depending on the number of supervision resistors) and the polarity is reversed compared to activated output. 8 The calibrated value has to be in the range 4K7 – 50K. 9 Regarding system voltage, see chapter "Technical data", page 143.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 19 S1: max. 200 mA (Fuse F6). See also Win128 help or chapter "Programmable outputs", page 61. 4.3 Programmable relay output (R0) Connections to "J1:17-19" according to drawing 128-23. The output has to be programmed (via Win128) regarding:  Type (Control, Fire ventilation, Alarm device, etc.)  Output signal period (steady, intermittent, pulse, delay, etc.)  Logic, i.e. normally open or normally closed.10 11  Control expression (containing one or more trigger conditions). NOTE! The output R0 is as default programmed as output for Routing equipment (Fire brigade tx).12 Activated output is indicated by the LED "Fire brigade tx".13 This output can be disabled via "door open" or via menu H2/B9. This output can be tested via menu H1, see the EBL128 Operating Instructions. See also Win128 help or chapter "Programmable outputs", page 61. 4.4 Relay output for routing equipment (fault tx) (R1) Connections to "J1:20-22" according to drawing 128-23. Not programmable relay output.11 This output for routing equipment (Fault tx) is activated during normal operation and will be de-activated when a fault is generated in EBL12814. De-activated output is also indicated by the LED "Fault tx activated". This output can be tested via menu H1, see the EBL128 Operating Instructions. 4.5 Programmable input (I0) Connections to "J1:9-10" according to drawing 128-22. The input has to be programmed (via Win128) regarding:  Type ("trigger condition")  Supervised / Not supervised  Logic, i.e. Normally open (high resistance, 3K3, when supervised) or Normally closed (low resistance, 680R, when supervised)  Additional information depending on selected type 10 In this case: Relay normally not activated / Relay normally activated. 11 Relay contact ratings (COM / NO / NC): max. 2 A @ 30 V DC. 12 A control expression is also required, i.e. Fire Brigade Tx. Regarding "Fire brigade tx", see also chapters "Alert Annunciation", page 92 and "Fire alarm type A and Fire alarm type B", page 96. 13 It is possible to use a programmable input with trigger condition Activated routing equipment, to turn on the LED instead. 14 Also if EBL128 becomes powerless (dead) and for "Watch-dog fault".

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 20 See also Win128 help or chapter "Programmable inputs", page 54. 4.6 24 V DC power supply outputs The two 24 V DC15 outputs can be used for:  Power supply of routing equipment (fire brigade tx / fault tx). Max. 200 mA (Fuse F7).  Power supply of external equipment, e.g. ext. FBP 1826 / 1828, AAU 1735 / 1736, EPU 1728, etc. Max. 500 mA (Fuse F916). Connections to "J1:11-12 & 13-14" according to drawing 128-22. 4.7 RS232 interfaces The two interfaces can be used for:  Win128 (PC program). (9 ways female "D" connector)  Web-server II 1598. (3 ways Molex connector) Connections to "J3" & "J5" according to drawing 128-25. 4.8 RS485 transceiver (option) There is a socket on the main board 4556 where an optional RS485 transceiver communication module 4552 can be mounted. This transceiver provides an interface (screw terminals J1:15-16) for up to four Display Units, i.e. ext. FBP 182617 / 1828 and/or AAU 1735 / 1736 and/or EPU 1728 running in S/W mode xxxx – 158718. The data rate in this mode is 9600 baud and max. cable length is 1200 m. Connections to "J1:15-16" according to drawing 128-23. On the RS485 serial line can as an alternative be connected up to four German Fire Brigade Control Panels (Feuerwehr-Bedienfeld) FBF 20033 and/or German Fire Brigade Indicator Panels (Feuerwehr- Anzeigetableau) FAT 20023. 4.9 Power supply Connectors for the built-in power supply units:  Rectifier 230 V AC / 24 V DC (Two tab terminals, 6.35x0.8 mm, +24V / 0V)  Batteries19 (2 x 12 V, 16 Ah), 24 V (Two tab terminals, 6.35x0.8 mm, BATT + / BATT -) 15 Regarding system voltage, see chapter "Technical data", page 143. 16 Fuse F9 is also for the 24 V DC internal power supply output for Web- server 1588 / 1598, see drawing 128-25. 17 Max. one with printer. 18 xxxx = type of display unit (e.g. 1826/28). For more information about each type of unit, see chapter "Other units", page 51. 19 Batteries are not included in the c.i.e. type number, i.e. batteries have to be ordered separately.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 21 Connections to "J2:1-5" according to drawing 128-24. 4.10 Internal Power supply Connector for the Web-server II 1598 power supply: 24 V DC15 output (3 ways Molex connector). Max. 500 mA (Fuse F920). Connections to "J4" according to drawing 128-25. 20 Fuse F9 is also for the 24 V DC power supply output for external equipment, see drawing 128-22.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 22 5 Expansion boards 458x Inside EBL128, in an optional expansion board holder 4551, can up to four optional expansion boards of types 4580, 4581 and 4583 be mounted. A supplied ribbon cable is used for the connection of the expansion board(s) to the main board. (Connector "J2" on the expansion board respectively and "J13" on the main board 4556.) See drawings 128-02 & -03. Figure 3. 8 zones expansion board 4580, 8 relays expansion board 4581 and Inputs and outputs expansion board 4583. I/O Matrix board 458221 is a special type of expansion board plugged as a "piggy back" to an Application board (Fan, Generic or Zone). The Application board is connected to the COM loop and to 24 V DC. Up to four 4582 boards can always be used and up to eight if no expansion board of type 4580, 4581 or 4583 are used. Figure 4. I/O Matrix board 4582. Each expansion board 4580-4583 has to have an expansion board address (0-7) set via jumpers on the expansion board respectively. On boards type 4580, 4581 and 4583 are the jumpers "JP2-JP4" used and on board type 4582 are the jumpers "JP1-JP3" used, see Figure 5 below. Win128 is used for all expansion board programming. For more information see Win128 help. 21 The I/O Matrix board 4582 is available on the Australian market only, since it requires an Application board not found in the Panasonic product range.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 23 5.1 Expansion board address setting The expansion board address is set via jumpers on the expansion board respectively. Board address 4580, 4581 and 4583 4582 JP2 JP3 JP4 JP1 JP2 JP3 0 Open Open Open Open Open Open 1 Shunted Open Open Shunted Open Open 2 Open Shunted Open Open Shunted Open 3 Shunted Shunted Open Shunted Shunted Open 4 Open Open Shunted Open Open Shunted 5 Shunted Open Shunted Shunted Open Shunted 6 Open Shunted Shunted Open Shunted Shunted 7 Shunted Shunted Shunted Shunted Shunted Shunted Figure 5. Expansion boards 4580 - 4583. Jumpers for expansion board address setting. 5.2 8 zones expansion board 4580 NOTE! P.C.B. NO. 9287-2B and 9287-3A exists. When 9287-3A is required is indicated below. Each board has to be programmed via Win128 regarding:  Address (set via the jumpers "JP2-JP4", see Figure 5 above.) The 4580 board has eight conventional zone line inputs (0-7) intended for conventional detectors. In the last alarm point on each zone line, an end-of-line device has to be connected, depending on the selected "Type of zone line input", see below. Connections to "J1:1-16" and "J2" according to drawing 128-30. Each zone line input has to be programmed via Win128 regarding:  Type of zone line input (see below), depending on detectors / end- of-line device (capacitor or resistor), i.e. different threshold levels etc.  Alarm at short circuit / Not alarm at short circuit (i.e. if short- circuit on the zone line shall generate a fault or a fire alarm)  Zone number (no address)  Fire alarm delay / No fire alarm delay  Text (Alarm text when required)  Alert annunciation time channel  Disablement time channel

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 24 For more information, see the Win128 help. The terminal block terminals support a wire size up to 1.13 mm2 (1.2 mm). 5.2.1 Type of zone line input Not used shall be selected for a not used input. One of the following types can be selected. 5.2.1.1 Zone line input (EOL capacitor) This type shall normally be used. It has the lowest zone line current consumption since the end-of-line device is a capacitor, 470 nF (±10 %). Max. allowed cable resistance is 50 ohm. Max. allowed cable capacitance is 50 nF. Max. allowed zone line current consumption is 1.5 mA. 5.2.1.2 EX zone line input (EOL resistor) This type shall be used when units for Hazardous (Ex) areas shall be connected, i.e. via the Galvanic isolator MTL5061 (2820). The end- of-line device has to be a resistor, 10K (±5 %) with a body surface area > 230 mm2 (supplied with the Galvanic isolator). Max. allowed cable resistance is 40 ohm. Max. allowed cable capacitance is 70 nF. Max. allowed zone line current consumption is 1.0 mA. 5.2.2 Input states Each input will be in one of six different states. 5.2.2.1 Normal state This is the normal zone line input state, i.e. no alarm, no fault, etc. and the nominal voltage is 24 V DC22. From this state any other state can be reached / activated. 5.2.2.2 High current state Max. current consumption limit23 for the zone line input is exceeded, which is indicating that e.g. too many alarm points are connected. This generates a fault condition in EBL128. From this state any other state can be reached / activated except the open circuit state. 5.2.2.3 Alarm state An alarm point on the zone line is in alarm state and the alarm limit23 for the zone line is exceeded, which activates fire alarm in EBL128. In this state short-circuit, open circuit, high current and low voltage states cannot be reached / activated. After alarm reset the zone line input will return to the normal state. 22 Allowed voltage 15-28 V DC. 23 This limit is depending on the selected input mode.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 25 5.2.2.4 Short-circuit state Short-circuit current limit23 is exceeded, indicating short-circuit on the zone line, which generates a fault condition in EBL128. 5.2.2.5 Open circuit state Open circuit current limit23 is passed, indicating no or too low zone line current consumption, i.e. the end-of-line device is not detected, which generates a fault condition in EBL128. From this state any other state can be reached / activated. 5.2.2.6 Disconnected state Via menu H5/A2 (Disconnect / Re-connect zone line) the zone line input can be disconnected24, i.e. there is no voltage on the zone line. From this state no other state can be reached / activated. 5.2.2.7 Low voltage state Zone line low voltage limit (15 V DC) is passed without the high current state is activated, indicating some H/W fault. This generates a fault condition in EBL128. From this state any other state can be reached / activated. 5.3 8 relays expansion board 4581 Each board has to be programmed via Win128 regarding:  Address (set via the jumpers "JP2-JP4", see Figure 5, page 23. The 4581 board has eight programmable relay outputs (Output 0-7). Connections to "J1:1-16" and "J2" according to drawing 128-31. Each output has to be programmed via Win128 regarding:  Type, i.e. output for Control, Alarm devices, etc.  Output signal period (steady, pulse, delay, etc.)  Logic, i.e. normally open (NO) or normally closed (NC) contacts25  Control expression (one or more trigger conditions) For more information, see Win128 help and chapter "Programmable outputs", page 61. The terminals support a wire size up to 1.13 mm2 (1.2 mm). 5.4 Inputs and outputs expansion board 4583 Each board has to be programmed via Win128 regarding:  Address (set via the jumpers "JP2-JP4", see Figure 5, page 23. 24 This indicated in EBL128 by the LED "Disablements". 25 Relay contact ratings: Max. 2A @ 30 V DC.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 26 The I/O expansion board 4583 has two programmable supervised or not supervised voltage outputs (Output 0-1), one programmable special output (Output 2) for German extinguishing system and five programmable supervised or not supervised inputs (Input 0-4). Connections to "J1:1-16" and "J2" according to drawing 128-03 sheet 2/2. Output 0-1 has to be programmed via Win128 regarding:  Type, i.e. output for Control, Alarm devices, etc.  Output signal period (steady, pulse, delay, etc.)  Supervised / Not supervised26  Logic, i.e. normally low (default) or normally high (24 V DC)27.  Control expression (containing one or more trigger conditions) One to five 33K resistors can be connected. When the connections are finished, a calibration has to be done. Calibration value has to be in the range 4K7-50K. See also the EBL128 Operating Instructions chapter "Calibration of supervised outputs (menu H5/A3)". Voltage Output 0 (J1:1-2): max. 200 mA (Fuse F1). "E" (Brandmeldung) Voltage Output 1 (J1:5-6): max. 200 mA (Fuse F2). "G" FSK öffnen See also Win128 help or chapter "Programmable outputs", page 61. Output 2 has to be programmed via Win128 regarding:  Type, i.e. output for Control, Alarm devices, etc.  Output signal period (steady, pulse, delay, etc.)  Logic, i.e. normally open (default) or normally closed.  Control expression (containing one or more trigger conditions) Output 2 (J1:11-12): Normally open (high resistance, 3K3, when supervised) or Normally closed (low resistance, 680R, when supervised). German extinguishing system (Löschanlage). See also Win128 help or chapter "Programmable outputs", page 61. Input 0-4 has to be programmed via Win128 regarding:  Type ("trigger condition")  Supervised / Not supervised  Logic, i.e. Normally open (high resistance, 3K3, when supervised) or Normally closed (low resistance, 680R, when supervised)  Additional information depending on selected type 26 A normally high output can not be supervised. The supervision voltage is 1.5 – 3.7 V DC (depending on the number of supervision resistors) and the polarity is reversed compared to an activated output. 27 Regarding system voltage, see chapter "Technical data", page 143.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 27 Input 0 (J1:3-4): Fire alarm routing equipment fault (Melder quittung) Input 1 (J1:7-8): German key cabinet (FSK rückmeldung) Input 2 (J1:9-10): German key cabinet (FSK überwachung) Input 3 (J1:13-14): German extinguishing system (Löschanlage ausgelöst) Input 4 (J1:15-16): German extinguishing system (Löschanlage quittung) See also Win128 help or chapter "Programmable inputs", page 54. 5.5 I/O Matrix board 4582 A special type of expansion board that can only be used together with an Application board (Fan, Generic or Zone).21 The I/O Matrix board makes it possible for any retailer to manufacture and connect three different types of "Application boards" to EBL128 via the COM loop. I/O Matrix board 4582 I/O Matrix board 4582 I/O Matrix board 4582 EBL512 C.i.e. COM loop 24 V DC Type: Generic Zone Fan Generic c.i.p. board Fan c.i.p. board Zone c.i.p. board Application boards: Fan c.i.p. Mimic panel / New Zealand i.p. Zone c.i.p. No. 0 No. 1 No. 3 NOTE! Up to 16 I/O Matrix board 4582 per EBL512 C.i.e. Up to 4 (No. 0-3) I/O Matrix board 4582 per COM loop. Up to 4 I/O Matrix boards type Generic and/or Zone per EBL512 C.i.e. Figure 6. I/O Matrix board application overview. The COM loop and 24 V DC are internally connected to the I/O Matrix board. The I/O Matrix board (80 x 63 mm) is plugged ("piggy back" connection) to the Application board respectively and has 16 inputs and 48 outputs. The COM loop and 24 V DC is connected to Application board. Three different application board types can be selected via jumpers (JP4-JP5) on the I/O Matrix board: Generic control and indicating panel (Mimic panel alt. New Zealand indication panel), with 16 inputs (any input trigger condition can be used) and 48 outputs (any output trigger condition can be used). Fan control and indicating panel, for four Fan control panels, each with six LED:s (On / Auto / Off / Running / Stopped / Fault) and three push buttons (On / Auto / Off). One "Reset" switch. Can be used for a "Supply air fan" or a "Standard fan". Zone control and indicating panel, with outputs and inputs for 16 zone LED:s (Alarm / Fault / Disabled) and 16 push buttons (Disable). There is no COM loop address to be set. Instead, the expansion

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 28 board address (0-7) is set with jumpers (JP1-JP3) on the I/O Matrix board respectively. Up to four I/O Matrix boards can be used and up to eight if no expansion boards of types 4580, 4581 and 4583 are used. but max. two I/O Matrix boards of the types Generic and Zone respectively. In EBL128 can totally up to 200 outputs be used, including all kinds of outputs. For more information (e.g. application board type selected via jumpers JP4-JP5), see the I/O Matrix board 4582, Technical description MEW00914. Each I/O Matrix board has to be programmed via Win128 regarding:  Address, set via jumpers "JP1-JP3", see Figure 5, page 23.  Type of board (Generic / Fan control / Zone control)  LED test on Input 15 or no LED test on Input 15 The 4582 board has 48 LED outputs and 16 switch inputs (0-15). Depending on if the Application board is of the type Generic, Fan or Zone, the outputs and inputs are programmed differently. 5.5.1 Generic Used for application board type Generic. Each output (0-47) has to be added and programmed via Win128 regarding:  Output no. (0-47)  Properties like for any programmable relay output. Each input (0-15) has to be added and programmed via Win128 regarding:  Input no. (0-15)  Type (of input)  Properties (e.g. zone-address, alarm text) like for any programmable input. 5.5.2 Fan control Used for application board type Fan control. Each Fan control28 (0-3) has to be added programmed via Win128. Each Fan control (0-3) contains four Fan control panels for control of one fan each. For each fan, one COM loop unit, I/O unit for fan control 3361, has to be added and programmed via Win128 regarding: 28 The Fan control is only available on the Australian market.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 29  Technical address (COM loop address 1-127)  Fan control information  I/O Matrix fan control (Fan control 0-3)  Supervised or not supervised  Properties as for any programmable output  Normally stopped or Normally running 5.5.3 Zone control Used for application board type Zone control. Each input (0-15) has to be programmed via Win128 regarding:  Zone (control) no. (0-15)

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 30 6 Peripheral devices Alarm points are connected to the COM loop.29 Wireless smoke detectors are "connected" to a Base station, which is connected to the COM loop. Short circuit isolators are connected to the COM loop. I/O Matrix boards30 are plugged ("piggy back") to an Application board (Fan, Generic or Zone), which is connected to the COM loop. Sounders, door release magnets, etc. are connected to the programmable outputs in EBL128 (S0-S1 and/or R0) and/or to output units connected on the COM loop. Addressable sounders (alarm devices) are connected directly on the COM loop. Input devices as key cabinet, timer, external fault, etc. are connected to programmable inputs, i.e. to input (I0) in EBL128 and/or to input units connected to the COM loop. Display units31 are connected to the RS485 interface in EBL128. Alternatively, German Fire Brigade Control Panels (Feuerwehr- Bedienfeld) FBF 20033 and/or German Fire Brigade Indicator Panels (Feuerwehr-Anzeigetableau) FAT 20023 are connected to the RS485 interface in EBL128. Routing equipment (Fire brigade tx / Fault tx) is normally connected to the R0-R1 outputs in EBL128. Regarding the Fire brigade tx, see chapter "Fire alarm type A and Fire alarm type B", page 96. German routing equipment, key cabinet and extinguishing system are connected to programmable inputs / outputs in EBL128 and Expansion board 4583. For more information, see the following chapters and/or the Product Leaflets on our web site: http://www.panasonic-fire-security.com 6.1 COM loop units The COM loop can handle up to 127 addressable COM loop units.32 NOTE! Depending on the type of units and the number of units the total current consumption will vary. This and the cable resistance will affect the cable length. See also chapter "Current consumption", page 134 and drawing 128- 11. 29 Directly (addressable) or via an input unit 3361. The programmable input I0 in EBL128 can be used as a fire alarm input (NO/NC). 30 The I/O Matrix board 4582 is described in chapter "Expansion boards 458x", page 22. 31 External Presentation unit 1728, External Fire Brigade Panel 1826 / 1828 and Alert Annunciation unit 1735 / 1736 32 Conventional detectors can be connected to an 8 zones expansion board 4580 or to the zone line input (Z) on each addressable I/O unit 3361.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 31 The following units (in NORMAL mode) can be connected to the COM loop: Address setting / Technical address Each COM loop unit has to have a unique technical address (001- 127). This address and the mode are set with an Address Setting Tool 3314. For EBL128 is always the NORMAL mode used (default). NOTE! The technical address for Addressable Base station for wireless units is set on a DIL-switch in the unit respectively. The technical address for a wireless detector is depending on which Base station it is "connected" to, see chapter "Other COM loop units", page 44. 6.1.1 Input units Each COM loop input unit is added and programmed via Win128. Depending on type of unit, regarding:  Technical address (001-127)  Name (normally not changed)  Zone number and Address within the zone  Two-units-dependent fire alarm, i.e. co-incidence alarm (if you wish / some units only)  Quiet alarm or not (Australian function)  Alert annunciation & Time Channel (if you wish / some units only)  Disablement & Time Channel (if you wish / some units only)  Alarm text (if you wish)  Regular Alarm algorithm (some units only)  Alternative Alarm algorithm & Time Channel (if you wish / some units only) and 3339) and 3379)

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 32 Figure 7. An example of a Win128 dialog box is the "Analog photo electric smoke detector 4301" properties dialog box. For more information, see Win128 help. Connections, if nothing else is specified, see drawing 128-21. 6.1.1.1 Analog Sensor Bases (ASB) 3312 Analog Base. An analog detector (Sensor) is to be plugged in 3312. Terminals for ext. LED 2217 / 2218. Prepared for mechanical lock of the detector. Recess for label holder 3391. The base has an address label on which the plugged-in detector's technical address is to be written. 3313 Analog Base. Like 3312 but instead of screw terminals for the COM loop and ext. LED this base has fast connectors. 3314 Analog Base. Like 3312FL but no connector for ext. LED. 4313 Analog Base with isolator. An analog detector (Sensor) is to be plugged in 4313. Terminals for ext. LED 2217 / 2218. Prepared for mechanical lock of the detector. Recess for label holder 3391. It has also a built-in short circuit isolator with the same function as the Addressable short circuit isolator 4370 (see page 42). The isolator's technical address is set with an Address setting tool (AST) 3314. The base has an address label on which both the plugged-in detector's technical address and the isolator's technical address are to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 4313 in EBL128. 3312FL 3312F

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 33 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 6.1.1.2 Addressable Manual Call Points 3333 Addressable Manual Call Point.33 Conforms to EN54-11. A built-in LED will indicate that fire alarm is generated, i.e. the glass is broken. Routine testing can be performed with a supplied test key without breaking the glass. A hinged polycarbonate flap is protecting the glass. The technical address is set with an Address setting tool (AST) 3314. The call point has an address label on which the programmed technical address is to be written. 3333 is to be surface mounted in the supplied red backbox or flush mounted in a Swedish 65mm circular mounting box. For indoor use and in dry premises. The Address setting tool 3314 is also used for mode setting. NORMAL mode: Flashing or not flashing LED (see Product leaflet MEW00097) is set via Win128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 3339 Enclosed Addressable Manual Call Point.33 Like the 3333 unit but another type of front cover and backbox. For surface mounting. For indoor use in premises where IP67 rating is required. 6.1.1.3 Analog Detectors 3308 Analog heat detector. To be plugged in an ASB base 3312. Built-in LED that is lit to indicate that the detector has generated fire alarm. Prepared for mechanical lock (screw attached). The technical address is set with an Address setting tool (AST) 3314. The detector has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: 3308 is in this mode via Win128 set to one of three algorithms (static response temp. range) for class: A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 3309 Analog heat detector. Enclosed (IP67)34. Built-in LED that is lit to indicate that the detector has generated fire alarm. 33 In all conventions the manual call points have a response time < 5 s. 34 As from January 2005, this detector holds the ATEX classification: Ex II 3GD EEx nA II T5 (T 70°C), -20°C < Ta < 65°C.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 34 Terminals for ext. LED 2217 /2218. Recess for label holder 3391. The technical address is set with an Address setting tool (AST) 3314. The Address setting tool 3314 is also used for mode setting: NORMAL mode: 3309 is in this mode via Win128 set to one of three algorithms (static response temp. range) for class: A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 4300 Analog multi detector. A smoke detector and a heat detector within one housing. Scattered light (i.e. reflection of infrared light) is used to detect smoke and the heat sensing element is a thermistor. The detector has unleaded soldering. To be plugged in an ASB base 3312. Built-in LEDs are lit to indicate that the detector35 has generated fire alarm. Prepared for mechanical lock (screw attached). Via Win128 it is programmable how the detectors shall operate: a) Two presentation numbers (addresses): The detector unit works as two separate detectors. The smoke detector is programmed for one zone-address and the heat detector for another zone-address36. (Can be used to disable one of the detectors during working hours and in control expressions for programmable outputs). The detector unit has one technical address used for programming and fault presentation. b) One presentation number (address): The detector unit works as one detector and is programmed for one zone-address. The detector unit (actually the heat detector) can detect a methylated spirits fire (EN54-9, test fire TF6; liquid fire), which normally is impossible for a photo electric smoke detector to detect. The detector unit has one technical address used for programming and fault presentation. It is, via Win128, programmable if the detectors in alt. b) shall work with "OR-functionality" or with a "Decision algorithm": b1) OR-functionality: Either the heat detector or the smoke detector will activate fire alarm. This alternative is recommended in most cases. The detector unit has one technical address used for programming and fault presentation. 35 I.e. the heat detector and/or the smoke detektor. 36 The zone number has to be the same for both detectors. NOTE! When counting alarm points these "two detectors" are regarded as two alarm points. Zone-Addr. 001-01 (smoke) 001-02 (heat) Techn. addr. 123 Zone-Addr. 001-01 (smoke or heat) Techn. addr. 123

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 35 b2) Decision algorithm: Fire alarm will be activated if: temperature (°C) + adjusted smoke value 37 > 58. Pre-warning will be activated if: 58 > temperature (°C) + adjusted smoke value37 > 50. The "Decision algorithm" 38, see figure can be used to reduce so called false alarms (nuisance alarms), because at a normal room temperature, more smoke is required to activate fire alarm than when the room temperature is high (or is rising). By a real fire, the room temperature will rise rather fast and less and less smoke is required to activate fire alarm. Very little smoke require a "high" temperature to activate fire alarm and very much smoke will activate fire alarm also at a "low" temperature. 0 10 20 30 40 50 60 70 0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60 Smoke value Temperature Figure 8. When the calculated value in the decision algorithm exceeds the lower graph, pre-warning will be activated. When it exceeds the upper graph, fire alarm will be activated. Temperature = °C. Smoke value = obscuration (%/m) x 10. The technical address is set with an Address setting tool (AST) 3314. The detector has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: 4300 in this mode is in Win128, for the smoke detector, set to one of six algorithms H-15, H-35, L-15, 37 Adjusted smoke value = obscuration (%/m) x 10. Default heat alarm levels (50°C / 58°C) and smoke alarm offsets (50 / 58) can be changed via Win128. The temperature can not be lower than 0°C in the algorithm / graph. 38 The decision algorithm is a violation to the EN54-7 standard. 20°C => 3.8 %/m ↓ ↓ 40°C => 1.8 %/m

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 36 L-35, N-15 or N-35 and for the heat detector set to one of three algorithms for class A1 (static response temp. 54-65°C), A2 S (54-70°C) or B S (69-85°C). 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 4301 Analog photo electric smoke detector. Scattered light (i.e. reflection of infrared light) is used to detect smoke. The detector has unleaded soldering. To be plugged in an ASB base 3312. Built-in LEDs are lit to indicate that the detector has generated fire alarm. Prepared for mechanical lock (screw attached). The technical address is set with an Address setting tool (AST) 3314. The detector has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: 4301 in this mode is in Win128 set to one of the six algorithms H-15, H-35, L-15, L-35, N-15 or N-35. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 6.1.1.4 Conventional Detector Bases (CDB) 2324 Base. A conventional detector is to be plugged in 2324. Built- in LED that is lit to indicate that the detector plugged in the base has generated fire alarm. Terminals for ext. LED 2217 / 2218. 6.1.1.5 Conventional Detectors 4318 Combination heat detector. Rate-of-rise and fixed temperature, 59°C, heat detector class A1 R. Static response temp. range 54- 65°C, ambient temp. min./typical/max. -10/+25/+50°C. Has replaced 2318. To be plugged in a CDB 2324. 4350 Multi detector. A smoke detector and a heat detector within one housing. Scattered light (i.e. reflection of infrared light) is used to detect smoke and the heat sensing element is a thermistor. In order to secure the fire detection and to prevent false (nuisance) alarms, the AI function is used, i.e. a: combined heat and smoke sensing b: variable delay function c: adaptive learning function See also chapter "Cyber sensor functions", page 111. The detector has unleaded soldering. To be plugged in a CDB 2324. 4352 Photoelectric smoke detector. Scattered light (i.e. reflection of infrared light) is used to detect smoke. An advanced alarm

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 37 algorithm is used to secure the smoke detection and to prevent false (nuisance) alarms, e.g. a minimum of nine consecutive readings over the fire alarm level are required, before the detector goes into alarm. (One reading per sec.) The detector has unleaded soldering. To be plugged in a CDB 2324. 4375 Heat detector. Fixed temperature heat detector, 60°C, class A2S (static response temp. range 54-70°C), latching. Min./typical/max. ambient temp. -10/+25/+40°C. The detector has unleaded soldering. Has replaced 6275. To be plugged in a CDB 2324. 4376 Heat detector. Fixed temperature heat detector, 80°C, class BS (static response temp. range 69-85°C), latching. Min./typical/max. ambient temp. -10/+40/+60°C. The detector has unleaded soldering. Has replaced 6276. To be plugged in a CDB 2324. 6295 Heat detector: Enclosed (IP67)39. Fixed temperature (57°C) heat detector, class A2 S (static response temp. range 54-70°C), latching. Min./typical/max. ambient temp. -40/+25/+50°C. Built-in LED that is lit to indicate that the detector has generated fire alarm. Terminals for ext. LED 2217 / 2218. 6296 Heat detector: Enclosed (IP67)40. Fixed temperature (72°C) heat detector, class B S (static response temp. range 69-85°C), latching. Min./typical/max. ambient temp. -40/+40/+65°C. Built-in LED that is lit to indicate that the detector has generated fire alarm. Terminals for ext. LED 2217 / 2218. 6297 Heat detector: Enclosed (IP67). Fixed temperature (87°C) heat detector, class C S (static response temp. range 84-100°C), latching. Min./typical/max. ambient temp. -40/+55/+80°C. Built-in LED that is lit to indicate that the detector has generated fire alarm. Terminals for ext. LED 2217 / 2218. 6298 Heat detector: Enclosed (IP67). Fixed temperature (117°C) heat detector, class E S (static response temp. range 114-130°C), latching. Min./typical/max. ambient temp. -40/+85/+110°C. Terminals for ext. LED 2217 / 2218 (to indicate that the detector has generated fire alarm). NOTE! No built-in LED. 6.1.1.6 Accessories 3314 Address setting tool. Is used to write or read the COM loop units' technical address (001-127). It is also used to write or 39 As from January 2005, this detector holds the ATEX classification: Ex II 3GD EEx nA II T5 (T 100°C), -40°C < Ta < 50°C. 40 As from January 2005, this detector holds the ATEX classification: Ex II 3GD EEx nA II T5 (T 100°C), -40°C < Ta < 65°C.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 38 read the mode, NORMAL or 2330 (see the unit respectively). A connection cable (with crocodile clips and tab terminals) is attached and can be used when required. Put the ON/OFF switch in position ON and wait for a beep. Plug the detector into 3314 (SA & SB terminals) or when required, use the connection cable.41 How to read: Press "READ", wait for a beep and read the address and mode. How to write: Press "WRITE" and "READ" at the same time to select the mode and/or write the address. Press "WRITE" and wait for a beep. ("READ" again as a check.) 3390 Label holder. To be mounted on the analog base 331242. Intended for a label with "zone-address", "technical address", etc. to be read also when the detector is plugged in its base. 100 label holders per packet. Excl. labels. 3391 Labels for 3390. Packet with self-adhesive white labels for label holder 3390. 10 A4-sheets à 132 labels for laser printer usage. The print-out is done via Win128. 6.1.2 Addressable I/O units 3361 Addressable multipurpose I/O unit.43 Power supplied via the COM loop. Up to 16 I/O units 3361 can be used. The unit has two programmable inputs: Monitored input ….used as zone line input (Z): End-of-line capacitor 470 nF mounted in the last unit on the line. A short circuit can activate fault or fire alarm (set via Win128). This input is intended for conventional detectors.44 used as general input (In0): An input for NC or NO contacts (set via Win128). Isolated input (In1): An optocoupler input (external 24 V DC / 8 mA is required). Normally low or high (set via Win128). 41 Some units have flying leads for easier connection. After use they might be disconnected and thrown away. 42 Also in the enclosed analog heat detector 3309. 43 The same physical unit (3361) is also used for the Australian Fan control function and has a separate dialog box in Win128. 44 It is via Win128 possible to define this input functioning like a manual call point ("Used as MCP"), i.e. it will not be collectively disabled via menu "Disable zone, H2/B1", can not be included in two-unit dependence, it can not use the "alarm delay" function and it can not be disabled via a time channel.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 39 The unit has two programmable relay45 outputs: Relay output (Re0): NC or NO contacts (set via Win128). Relay output (Re1): NC or NO contacts (set via Win128). Connections and examples, see drawings 128-21 & -26. The unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic protection cover is attached. The cover's dimensions: (L x W x H) 129 x 73 x 45 mm. The unit is intended to be surface mounted and for indoor use in dry premises. When required, the unit can be mounted in a Waterproof box (IP66 / 67) 3362. The unit has an LED to indicate communication to the unit or alarm condition. For more information, see the Product Leaflet. The technical address is set with an Address setting tool (AST) 3314. The unit has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 3361 in EBL128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. NOTE! See also chapter "Limitations", page 144. 3364 Addressable 2 voltage outputs unit. The unit is connected directly to the COM loop. External 24 V DC power supply is required (via a 3366 unit or EBL128). The unit has two programmable and supervised voltage outputs (VO0-VO1), intended for alarm devices (e.g. sirens). An end- of-line capacitor (470nF) is to be mounted in the last device alt. a capacitor (470nF) in up to five alarm devices: The unit also has a special voltage output (VO2) intended for fire door closing only. The trigger condition "Fire door closing" and the controlling detectors have to be programmed. The "fire door closing function" is described on page 80 and besides that function the output VO2 will also be powerless approx. 30 sec. after: - the "/Mains OK input" (terminal 8.) goes high, see below. - the COM loop communication is interrupted = 3364 has no connection / communication with EBL128. The unit also has two inputs, i.e. one for power supply (24 V DC) and one for "/Mains OK". VO0: Normally low or high (set via Win128), 24 V DC, 1 A.46 VO1: Normally low or high (set via Win128), 24 V DC, 1 A.46 VO2: Normally high, 24 V DC, 1 A.46 (Fire door closing function.) 24 V DC: From an external power supply (unit 3366 or EBL128) /Mains OK: From an external power supply unit (3366) when 45 Relay contacts: max. 2 A @ 30 V DC / 125 V AC. 46 Cont. 1 A, during 10 ms 1.4 A.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 40 the fire door closing function (ABDL) is to be used. Normally low = The main power source (230 V AC) in the External power supply unit is okay. Connections and examples, see drawings 128-21 & -28. The unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic protection cover is attached. The cover's dimensions: (L x W x H) 129 x 73 x 45 mm. The unit is intended to be surface mounted and for indoor use in dry premises. When required, the unit can be mounted in a Waterproof box (IP66 / 67) 3362. For more information, see the Technical Description and the Product Leaflet. The technical address is set with an Address setting tool (AST) 3314. The unit has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 3364 in EBL128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. NOTE! See also chapter "Limitations", page 144. 6.1.3 Alarm devices (addressable sounders) 3377 Addressable siren. The siren is connected directly to the COM loop. It is power supplied via the COM loop, i.e. the number of sirens is depending on the type and number of other units connected to the COM loop.47 Red ABS plastic housing. Three sound types (tones) and two priority levels are available. For each level an output control expression and a sound type is programmed (via Win128). For more technical data, see the Product Leaflet. The technical address is set with an Address setting tool (AST) 3314. The siren has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 3377 in EBL128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. NOTE! See also chapter "Limitations", page 144. 3378 Addressable sounder base. 3378 consists of an analog base (3312) mounted together with a sounder. The sounder is mounted in the ceiling. Two flying leads from the base are plugged in the sounder. The base is thereafter mounted on the sounder, so that the detector can be plugged in the base. The base is connected directly to the COM loop. (Like base 3312.) It is power supplied via the COM loop, i.e. the number of sounder bases is depending on the type and number of other units connected to the COM loop47. Three sound types (tones) 47 The number of 3377 + 3378 units must be < 50.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 41 and two priority levels are available. For each level an output control expression and a sound type is programmed (via Win128). For more technical data, see the Product Leaflet. The technical address is set with an Address setting tool (AST) 3314. The unit has an address label on which the programmed technical address is to be written. (The detector has its own technical address set via the Address setting tool 3314.) The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 3378 in EBL128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. NOTE! See also chapter "Limitations", page 144. 3379 Addressable sounder base.48 3379 consists of an analog base (3312) mounted together with a sounder. 3379 is mounted in the ceiling. An analog detector can be plugged in the base, which has screw terminals for the COM loop and an ext. LED (2218). Prepared for mechanical lock of the detector - if required. Recess for label holder (3391). 3379 is power supplied via the COM loop, i.e. the number of sounder bases is depending on the type and number of other units connected to the COM loop47. Three sound types (tones) and two priority levels are available. For each level an output control expression and a sound type is programmed (via Win128). For more technical data, see the Product Leaflet. The COM loop address is set with the Address setting tool (3314). The unit has an address label on which the programmed COM loop address can be written. (The detector has its own COM loop address set via the Address setting tool 3314.) The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 3379 in system EBL128. 2330 mode: Not used in system EBL128. 2312 mode: Not used in system EBL128. NOTE! See also chapter "Limitations", page 144. 6.1.4 Short circuit isolators (addressable) Each COM loop short circuit isolator is to be programmed (via Win128) regarding:  Technical address  Name (Normally not changed)  Sequence Number (Serial Number in the COM loop's A- direction.) Connections, see drawing 128-21. (See especially about the L wire!) 4313 Analog base with isolator. An analog base with a built-in short circuit isolator with the same function as the Addressable short circuit isolator 4370, see below. See also page 32. 48 This unit has replaced the Sounder base 3378.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 42 4370 Addressable short circuit isolator. In case of short circuit on the COM loop, the number of disabled units will be minimised. 4370 is power supplied via the COM loop. The unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic protection cover is attached. The cover's dimensions: (L x W x H) 128 x 72 x 45 mm. The unit is intended to be surface mounted and for indoor use in dry premises. When required, the unit can be mounted in a Waterproof box (IP66 / 67) 3362. The unit has an input to manually open the isolator ("isolated state") and an input to manually close the isolator ("normal state"). An LED will indicate the normal and isolated state respectively. For more information, see the Product Leaflet. The technical address is set with an Address setting tool (AST) 3314. The unit has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 4370 in EBL128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. According to the EN54 standard, at least one short circuit isolator is required per 32 alarm points on the COM loop. In the Australian and New Zealand conventions at least one isolator per 40 alarm points. Up to eight 4370 and/or 4313 can be used, which gives nine loop segments. Each isolator has to be given a Sequence Number, 0-7. The isolators have to be connected consecutively (Sequence Number 0-1-2-3-4-5-6-7) in the COM loop's A-direction. NOTE! EBL128 has one built-in isolator in the-A direction (no. "A") and one in the B- direction (no. "B"). EBL128 4370 no. 0 4370 no. 1 A Dir.  B Dir.  Segment A Segment B Segment C Figure 9. Two 4370 / 4313 isolators connected to the COM loop gives three loop segments, i.e. Segment A (A-0), B (0-1) and C (1-B). If one or more isolators are to be added the sequence numbers have to be updated (via Win128), e.g. if one isolator is to be put in between no. 0 and no. 1 in the figure, the new isolator will be no. 1 and the old no. 1 will be no. 2. Short circuit / cut-off (break) on the COM loop See chapter "COM loop", page 15. See also chapter "Fault messages" in the EBL128 Operating Instructions.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 43 6.1.5 Units for Hazardous (Ex) areas In hazardous (Ex) areas, Intrinsically Safe (IS) and approved products are required. The IS alarm points are connected to a detector interface, i.e. a Galvanic isolator, which is connected to an expansion board 4580 zone line input. See also drawings 128-32. 6.1.5.1 Galvanic isolators MTL5061 Galvanic isolator. The isolator is used to connect the IS detectors and manual call points to an expansion board 4580 zone line input. The isolator has two zone line inputs and two outputs (Channel 1 & 2) and it is mounted in a Waterproof box (IP66/67). Four compression glands for the cable entries and an end-of-line resistor (10K) with an area >230 mm2 are supplied. Box dimensions (L x W x H): 175 x 125 x 150 mm. BASEEFA classification: EEx ia IIC. 6.1.5.2 Intrinsically Safe mounting bases YBN-R / 4 IS Intrinsically Safe mounting base. In the base can be plugged an intrinsically safe conventional smoke or heat detector. The base has terminals for the zone line (in/out) and for an ext. LED. 6.1.5.3 Intrinsically Safe photoelectric smoke detectors SLR-E-IS Intrinsically Safe photoelectric smoke detector. A conventional photoelectric (optical) smoke detector, to be plugged in the intrinsically safe mounting base. The detector has two built-in LEDs that are lit to indicate that the detector has generated fire alarm. Zone classification: 0, 1 or 2. BASEEFA classification: EEx ia IIC T5, t (amb.)=50°C. Max 20 per zone. 6.1.5.4 Intrinsically Safe heat detectors DCD-1E-IS Intrinsically Safe heat detector. A conventional Rate of Rise heat detector, fixed temperature 60°C (class A1), to be plugged in the intrinsically safe mounting base. Two built-in LEDs that are lit to indicate that the detector has generated fire alarm. Zone classification: Category 1 (incl. lower categories). BASEEFA classification: II 1 G EEx ia IIC T5, t (amb.)=55°C. Max 20 per zone. 6.1.5.5 Intrinsically Safe manual call points 6.1.6 Other COM loop units 3366 External power supply. Conforms to EN54-4. The unit is connected to a COM loop, i.e. it is monitored from EBL128 and e.g. loss of the main power source will generate a fault in EBL128. It can be used as power supply for external

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 44 equipment requiring 24 V DC with battery backup, e.g. the 3364 unit. It also has a "/Mains OK" output (normally low), intended to be connected to the corresponding input on the 3364 unit. A light grey metal housing (HxWxD, 288 x 400 x 95 mm). There is space for two maintenance-free sealed Lead-Acid backup batteries, 2 x 12 V, 7.5 Ah as the second power source. Batteries with higher capacity (up to 60 Ah) have to be placed outside the housing. There are cable inlets on the top, bottom and back sides of the housing. Two compression glands are attached. The unit has a 24 V DC49 power supply output for external equipment with up to 2.1 A or 0.85 A continuous current consumption, at the same time as the battery charging is in progress.50 In case of no battery charging, the continuous current consumption can be up to 4 A. It has a number of security functions, e.g. against to high current output and to low battery voltage etc. For more information, see the Technical Description and the Product Leaflet. The technical address is set with an Address setting tool (AST) 3314. The unit has an address label on which the programmed technical address is to be written. The Address setting tool 3314 is also used for mode setting: NORMAL mode: Used for 3366 in EBL128. 2330 mode: Not used in EBL128. 2312 mode: Not used in EBL128. 4601 Wireless photoelectric smoke detector. The detector is plugged in an attached base and the colour is white. Latest IC technology will secure the highest reliability possible. The smoke detection chamber contains an IR LED and a photodiode. Scattered light (i.e. reflection of infrared light) is used to detect smoke. The smoke enters the detection chamber through an insect filter and an optical labyrinth. Fire alarm will be activated after three values over the fire alarm threshold level. The detector has sensitivity compensation for contamination. Transmission distance between Detector and Base station is min. 40 m in open air. The Wireless smoke 49 The rated output voltage for the main power source (rectifier) is 24 V ± 1%. Max. ripple 500 mVp-p. The rated output voltage for the second power source (the backup battery) is 18 – 28 V DC. NOTE! The voltage will, however, decrease to approx. 15 V when the output will be switched off in order not to damage the battery. 50 A current consumption of 0.85-2.2 A allows only the "low current charging mode", i.e. the battery capacity can be up to 27 Ah. A current consumption < 0.85 A allows the "high current charging mode", i.e. the battery capacity can be up to 60 Ah.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 45 detector is power supplied by three pieces of a 3 V Lithium 2400 mAh battery, type 4602. The battery life time is more than three years. Up to 16 Wireless photoelectric smoke detectors, type 4601, can be "connected" to an Addressable Base station for wireless units, type 4610. Each wireless detector shall be programmed like the Analog photoelectric smoke detector, type 4301 regarding presentation number (Zone-Address), alarm text, etc. For more information, see the Technical Description and the Product Leaflet. 4610 Addressable Base station for wireless units. The Base station consists of a p.c.b. mounted in a white plastic housing, which has a great number of cable inlets and mounting holes. It has fast connectors for the COM loop (in / out) and 24 V DC power supply respectively. Up to four Base stations can be connected to a COM loop in the EBL system and up to 16 Wireless photoelectric smoke detectors (detector address 0-15) can be "connected" to each Addressable Base station for wireless units, type 4610. Each Base station shall have a transmission channel (0-3) selected. The Base station's COM loop address is set on a DIL-switch. The COM loop address for the wireless detector respectively is depending on the Base station's COM loop address, see below. Ext. 24 V DC power supply is required. For more information, see the Technical Description and the Product Leaflet. AAFC Alarm Acknowledgement Facility Control.51 The AAFC is a box with an alarm indication LED and a non-latching switch "Press to acknowledge false alarm". One AAFC per AAFC zone and up to 50 AAFC:s zones can be used. The COM loop address is set with an Address setting tool (AST) 3314. See also chapter "Alarm Acknowledgement Facility (AAF)", page 94. 6.1.7 COM loop addresses for Base station and Wireless detectors Each Base station takes one COM loop address (012 in the example below). Each wireless detector's COM loop address, will be as follows: Detector COM loop address address 0 Base station's COM loop address +1 (e.g. 012+1=013) 1 Base station's COM loop address +2 (e.g. 012+2=014) ..and so on.. 51 This unit is available on the Australian market only.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 46 15 Base station's COM loop address +16 (e.g. 012+16=028) NOTE! Since the highest possible COM loop address is 127 the highest possible COM loop address for a Base station is 111 if 16 Wireless smoke detectors shall be supported (111+16=127). 6.2 Units connected to the RS485 interface Up to four Ext. FBPs (1826 / 1828) and/or Alert Annunciation Units (1735 / 1736) and/or Ext. Presentation Units (1728) can be connected to the RS485 interface52 (J1:15-16) in EBL128. Max one 1826 with printer. (Power supply at J1:13-14.) Address and S/W mode settings The display and the push buttons (in the unit respectively) are used to set the address, which also can be changed via EBL128. The S/W mode shall be set to xxxx – 1587 (xxxx = type number). See the Technical Description for the unit respectively. The first unit shall have the address 00, the second unit address 01 and so on53. Follow the Address setting instructions in the Technical Description for the unit respectively. Via Win128 can "Selective alarm presentation" be programmed, i.e. you can select which alarms that shall be presented in each unit, see the Technical Description for the unit respectively. 6.2.1 External Fire Brigade Panels 1826 External Fire Brigade Panel (ext. FBP). A light grey metal housing (HxWxD, 288 x 400 x 95 mm) with a door. A key is required to open the door, which has a Plexiglas ahead of the FBP front. It has cable inlets on the top, bottom and back sides and is intended to be wall mounted. Two compression glands are attached. LED indicators and push buttons on the front are like the EBL128 FBP (upper black part of the front), see Figure 2, page 14. The front's designation texts are in Swedish. A neutral front is available, where the designation texts, in any language, are made separately and by production put into a transparent "text slot" for the LED and push button respectively. All or selected alarms will be presented in a display (alphanumeric LCD, 2x40 characters), with back-light. An alarm text will also be presented together with each alarm, if programmed in EBL128. Furthermore, at least 617 texts for selected fire alarms can be stored in the unit and will in such a case be shown, instead of the texts sent from EBL128 for these alarms. These text messages will be downloaded to the unit via EBL128. A built-in buzzer will sound like in EBL128. The 52 The RS485 transceiver 4552 is an option. 53 The connection order on the line is not dependent of the address.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 47 buzzer can be silenced and the alarm devices in the installation can be silenced. They will re-sound for a new alarm. When there are queued alarms in the system, you can scroll amongst them and they can be reset. Any fault in the system will be presented as "General fault in system" and the buzzer will sound.54 A Printer 1835 can be mounted in ext. FBP 1826. It will print all the alarms, including the alarm texts. New S/W versions can be downloaded directly in the unit. The unit is power supplied from EBL128 or an ext. power supply. The unit shall run in S/W mode 1826/28 – 1587, which has the highest performance with regard to functionality, response time, ability to store fire alarms, etc. Up to 1200 m cable can be used. For more information, see Technical description MEW00249. 1828 External Fire Brigade Panel (FBP). A compact size enclosure (HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS. Fitted with a supplementary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly but a key is required to get access to the push buttons. They are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached. In all other respects it is like 1826, except that a printer can not be mounted in 1828. The unit shall run in S/W mode 1826/28 – 1587, which has the highest performance with regard to functionality, response time, ability to store fire alarms, etc. Up to 1200 m cable can be used. For more information, see Technical description MEW00249. 1835 Printer. Can be mounted in the External Fire Brigade Panel 1826. It will print all the alarms, including the alarm texts. 6.2.2 Alert Annunciation Units When the Alert Annunciation (AA) function shall be used in system EBL128, a unit is required for the related manoeuvres, i.e. to acknowledge / reset the AA alarms. For a detailed description of the Alert Annunciation function, see chapter "Alert Annunciation", page 92. 1735 Alert Annunciation Unit (AAU). A compact size enclosure (HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS. Fitted with a supplementary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly but the push buttons are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached. The front's designation texts are in Swedish. 54 Not valid for the Swedish convention (SBF).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 48 All or selected fire alarms will be presented in a display (alphanumeric LCD, 2x40 characters), with back-light. An alarm text will also be presented together with each alarm, if programmed in EBL128. Furthermore, at least 617 texts can for selected fire alarms be stored in the unit and will in such a case be shown, instead of the texts sent out from EBL128 for these alarms. These text messages will be downloaded to the unit via EBL128. A built-in buzzer will sound to indicate a not acknowledged AA alarm. New software versions can be downloaded directly in the unit. The unit is power supplied from EBL128 or an external power supply. The unit has the following LEDs: Fire and Alarms queued, indicating fire / AA alarm. Operation, indicating that the unit is in operation, i.e. the AA function is enabled in the system. A time channel can be used to enable the AA function. Fire brigade alerted, indicating that the "Fire brigade tx" output is activated in EBL128 because: - the activated fire alarm is not an AA alarm - the AA function has been ended, e.g. the acknowledge or investigation time respectively has run out, etc. Acknowledge, indicating that the AA alarm has been acknowledged. The unit has the following push buttons: Alarms queued, used to scroll amongst the alarms. Acknowledge, used to acknowledge an AA alarm and hereby also silence the buzzer. Reset, used to reset an AA alarm. The unit shall run in S/W mode 1735 – 1587, which has the highest performance with regard to functionality, response time, ability to store alarms, etc. Up to 1200 m cable can be used. For more information, see Technical description MEW00224. 1736 Alert Annunciation Unit (AAU). This unit is like 1735, except it has a neutral front, where the designation texts, in any language, are made separately and by production put into a transparent "text slot" for the LED and push button respectively. (This front also holds one extra LED & two extra push buttons.). The unit shall run in S/W mode 1736 – 1587, which has the highest performance with regard to functionality, response time, ability to store alarms, etc. Up to 1200 m cable can be used. For more information, see Technical description MEW00224. 6.2.3 External Presentation Units 1728 External Presentation unit (EPU). A compact size enclosure (HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 49 Fitted with a supplementary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly, when required. The push buttons are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached. The front's designation texts are in Swedish. This unit is intended for pre-warning, co-incidence55, fire (and heavy smoke / heat) alarm presentation. If there are two or more alarms in the system, you can scroll amongst them but the fire alarms can not be reset via this unit. All or selected alarms will be presented in a display (alpha- numeric LCD, 2x40 characters), with back-light. An alarm text will also be presented together with each alarm, if programmed in EBL128. Furthermore, at least 617 texts can for selected fire alarms be stored in the unit and will in such a case be shown, instead of the texts sent out from EBL128 for these alarms. These text messages will be downloaded to the unit via EBL128. Any fault in the system will be presented as "General fault in system". The buzzer will sound.54 It can be silenced. Any disablement in the system will be presented as "General disablement in system".54 A built-in buzzer will sound like in EBL128. The buzzer can be silenced but the alarm devices in the installation can not be silenced via this unit. New software versions can be downloaded directly in the unit. The unit is power supplied from EBL128 or an external power supply. The unit shall run in S/W mode 1728 – 1587, which has the highest performance with regard to functionality, response time, ability to store fire alarms, etc. The number of units that can be power supplied via EBL128 (or an external power supply) is depending on all other units connected to the same c.i.e. / external power supply. Up to 1200 m cable can be used. For more information, see Technical description MEW00290. 6.2.4 German Fire Brigade Panels See also "…optional Communication module (RS485 transceiver component) 4552", page 14. FBF 2003 German Fire Brigade Control Panel (Feuerwehr- Bedienfeld). A grey metal housing (HxWxD, 185 x 255 x 58 mm) with a door. A key is required to open the door, which has a Plexiglas ahead of the front. It has cable inlets on the top, bottom and back sides and is intended to be wall mounted. The function, LED indicators and push buttons on the front are in accordance with DIN 14661. The front's designation texts 55 Two zone / address dependence.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 50 are in German. Serial RS485 interface for IHD protocol. The unit is power supplied from EBL128 (or an ext. power supply). Up to 1200 m cable can be used. NOTE! Switch 1 on the DIP switch shall be set to "on". FAT 2002 German Fire Brigade Indicator Panel (Feuerwehr- Anzeigetableau). A grey metal housing (HxWxD, 185 x 255 x 58 mm) with a door. A key is required to open the door, which has a Plexiglas ahead of the front. It has cable inlets on the top, bottom and back sides and is intended to be wall mounted. The function, Display information, LED indicators and push buttons on the front are in accordance with DIN 14662. The front's designation texts are in German. Serial RS485 interface for IHD protocol. The unit is power supplied from EBL128 (or an ext. power supply). Up to 1200 m cable can be used. 6.3 Units connected to the RS232 interface J5 6.3.1 Web-servers 1598 Web-server II. This unit has replaced 1588 and can be used: a) for presentation of the actual c.i.e. status in a PC using the web browser Microsoft Internet Explorer. It can also send e- mails in case of pre-warning, fire alarm, fault, disablement, test mode alarm and/or service signal. b) for remote control with encrypted and safe two-way communication and five different user (access) levels. c) as a gateway to other PC systems etc. Three alternatives are available today: c1) EBL Talk is an open protocol, used to transmit and present fire alarm information in a separate PC / system. c2) Tateco, used to transmit and present fire alarm information in an Ascom Tateco paging system. c3) SIA, used to transmit and present fire alarm information in a separate PC application. A PC tool, Web128 II Config tool is used for the configuration, which is downloaded to the web-server via TCP/IP. The Web-server II consists of a light grey plastic cabinet (90x25x69.5 mm), which shall be vertically mounted on the symmetric 35 mm DIN rail in the EBL128 c.i.e. Web-server II has the following interfaces: RS232 to connect the web-server to J5 in the EBL128 c.i.e. RS232 to connect the web-server to other PC / system RJ45 (10 BASE-T) to connect the web-server to Internet / an intranet (LAN) Molex 3.5 to connect the web-server to a power supply (24 V DC, max. 65 mA), e.g. to J4 in the EBL128 c.i.e.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 51 6.4 Units connected to the RS232 interface J3 J3 is a 9 ways female "D" connector. This interface is used only for connection of EBL128 to a PC with the PC program Win128, which is used for download / backup of Site Specific Data (SSD), etc. 6.5 Other units 6.5.1 Alert Annunciation Controllers 1740 Alert Annunciation Controller (AAC). This unit has no display, i.e. it has to be mounted close to EBL128 (or an ext. FBP) where the fire alarms will be presented. The compact size enclosure (HxWxD, 145 x 220 x 50 mm) is made of grey high impact ABS. Fitted with a supplementary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly but the push buttons are disabled until they are supposed to be used. The front's designation texts are in Swedish. The unit shall be wall mounted. The LED "Acknowledge" can be turned on by the push button "Acknowledge" or by an input, i.e. a programmable output. This is set via a jumper "JP1" in the unit. The unit is power supplied from EBL128 or an external power supply. One supplementary compression gland can be used for cable entry. The unit has the following LEDs: Fire, indicating fire / AA alarm. Operation, indicating that the unit is in operation, i.e. the AA function is enabled in the system. A time channel can be used to enable this function. Fire brigade alerted, indicating that the "Fire brigade tx" output is activated in EBL128 because: - the activated fire alarm is not an AA alarm - the AA function has been ended, e.g. the acknowledge or investigation time has run out, etc. Acknowledge, indicating that the AA alarm has been acknowledged. The unit has the following push buttons: Acknowledge, used to acknowledge an AA alarm. Reset, used to reset an AA alarm. Connections and more details are to be found in the Technical Description MEW00283. 6.5.2 External LEDs 2217 Ext. LED (ext. indicator). Used when a detector is placed out of view or hidden. The LED is lit at the same time as the LED in the detector / base it is connected to. It has a "Burning

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 52 house" symbol instead of any text. 2217 can be connected to all types of Panasonic detectors / bases. The input is polarised. J1:1 (+5 to +24 V DC) / J1:2 (0 V). To be wall mounted with the attached frame (84 x 84 mm) or flush mounted, e.g. with a Swedish 65mm circular mounting box. 2217 is replaced with 2218, see below. 2218 Ext. LED (ext. indicator). Used when a detector is placed out of view or hidden. The LED is lit at the same time as the LED in the detector / base it is connected to. It has a "Burning house" symbol instead of any text. 2218 can be connected to all types of Panasonic detectors / bases. The input is polarised. J2:1 (+5 to +35 V DC) for conventional detectors / bases J2:2 (+; < 25 mA) for analog detectors / bases J2:3 (0 V) To be wall mounted (87 x 87 x 30 mm). 2218 has replaced 2217. 6.5.3 Alarm devices (sounders, etc.) Regarding addressable alarm devices, see page 40. In the Panasonic product range are no alarm device intended for a supervised (monitored) voltage output (e.g. S0 or S1 in EBL128). Connections of alarm devices according to drawing 128-22. (For addressable sounders, see page 40. 6.5.4 Door release magnets In the Panasonic product range is no Door release magnet. Door release magnets shall always be provided with a "suppresion diode" (e.g. 1N4004) in parallel with the coil, like in the alarm devices, see drawing 128-22. 6.5.5 Boxes 3362 Waterproof box (IP66 / 67). A grey polycarbonate box with ingress protection rating IP66 / 67. Four compression glands are included for the cable entries. Dimensions (L x W x H): 175 x 125 x 75 mm. 3362 can be used for: Addressable multipurpose I/O unit 3361 Addressable short circuit isolator 4370 Addressable 2 voltage outputs unit 3364

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 53 7 Programmable inputs EBL128 has one programmable input (I0). In EBL128 can also be mounted the Inputs and Outputs expansion board 4583, with five programmable inputs (Input 0-4). See chapter "Expansion boards 458x", page 22. All these inputs can be supervised or not supervised. On the COM loop can be connected up to 16 addressable multi purpose I/O units 336156. Each 3361 unit has two programmable inputs (In0/Z and In1), not supervised. Each input is programmed (via Win128) regarding:  Name (Normally not changed, but used as Interlocking input it is recommended to add some identification information)  Type ("Trigger condition")  Not supervised or Supervised. (Not valid for 3361.)  Logic, Normally open (high resistance, 3K3, when supervised) or Normally closed (low resistance, 680R, when supervised)  Ext. Fault (Text; only for trigger cond. "External fault")  Ext. time channel Name (only for trigger cond. "External time channel")  Activate output (Technical address and Output)  Zone, Address and Text (only for trigger cond. "General fire", "Pre-warning" and "Zone line input").  Alert Annunciation time channel (only for trigger cond. "Zone line input" – 3361 In 0).  Disablement time channel (only for trigger cond. "Zone line input" – 3361 In 0). Figure 10. The Win128 "Input" dialog box. The different trigger conditions ("Type") require different additional information. 56 Units type 3361 + 3364 = max. 16.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 54 7.1 Control unit Input I0 & Inputs and Outputs exp. board 4583, Input 0-4 7.1.1 Not supervised Normally open (R > 2K) or Normally closed (R < 2K) Activation time: >1 sec. Connections, see drawing 128-22. 7.1.2 Supervised Each supervised input can be in four different states:  Open circuit (cut-off)  Not activated (quiescent)  Activated  Short-circuit Depending on the selected logic, Normally open (high resistance) or Normally closed (low resistance), the following table is valid. Line resistance R Normally open (high resistance) Normally closed (low resistance) R > 6K8 Open circuit (cut-off) Open circuit (cut-off) 6K8 > R > 2K (nom. 3K3) Not activated Activated 2K > R > 70 (nom. 680) Activated Not activated R < 70 Short-circuit Short-circuit 7.1.2.1 Input line fault If open circuit (cut-off) or short-circuit is detected on a supervised input, a fault will be generated in EBL128 and the following fault message will be displayed: FAULT: Programmable input alternatively FAULT: Programmable input x exp. board x

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 55 7.2 3361 unit Inputs In0 / Z & In1 Connections, see drawing 128-26. NOTE! The input In0 / Z can be used as a general input (In0) or as a monitored zone line input (Z) requiring an end-of-line capacitor (470 nF).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 56 8 Input programming Input programming is done via Win128. For more information, see the Win128 help. Each input has to have an individual Trigger condition ("Type") and Logic. Each input can be supervised or not supervised. It is not recommended to let two or more inputs have the same trigger condition. 8.1 Type (trigger conditions) The following trigger conditions are available: 1. Not used 2. Alarm Key Cabinet (one input) 3. Alert Annunciation Acknowledge 4. Alert Annunciation Reset 5. Fault Signal External Power Supply (one input) 6. Fault Signal External Fuses (one input) 7. External Time Channel 5 - 12 (one input per time channel) 8. General Fire (max. 127) 9. Activated Routing Equipment (one input) 10. External Fault 11. Interlocking (max. 32 inputs) 12. Loss of main power source to external power supply (one input) 13. Loss of battery charger to external power supply (one input) 14. Door Closing Test Input 15. Pre-warning 16. Activated fault routing equipment (one input) 17. Extinguishing system released 18. Extinguishing system fault 19. Extinguishing alarm 20. Fault warning routing equipment fault 21. Activate output 22. Silence alarms (one input) 23. Activated key cabinet 24. Evacuate 25. Zone Line Input 57 Comments to the trigger conditions: 57 Only valid for the Addressable multipurpose I/O unit 3361 input "In0", used as zone line input (Z).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 57 1. Default. The input does not work. 2. Key cabinet, where the fire brigade store a key to the building. Will activate a Key cabinet alarm. See the EBL128 Operating Instructions for more information. 3. Alert annunciation, see the EBL128 Operating Instructions for more information. 4. Like 2. 5. Ext. power supply equipment fault output will activate a fault in EBL128. The following fault message will be shown: FAULT: External power supply 6. Ext. fuses (for the ext. power supply equipment) fault output will activate a fault in EBL128. The following fault message will be shown: FAULT: External fuses 7. External clock, timer, key switch, switch, etc. can disable / re- enable alarm points. The function Alert annunciation can be set on / off by a time channel. Control outputs can be turned on (activated) / off (de-activated) by a time channel. 8. A special detector, push button, etc. can activate a fire alarm in EBL128. Zone no. and Address (+ user definable text). 9. "Activated Fire brigade tx" signal (feed-back) to EBL128 will light up the LED "Fire brigade tx" on the front. (Normally the LED will be lit when a corresponding output is activated58.) Output with trigger condition "Indication Fire Brigade tx Activated" will be activated. 10. Ext. fault will activate a fault in EBL128. A user definable fault message ("text") with up to 40 characters will be shown. 11. A feed-back from the equipment activated by the corresponding interlocking output. Activated input is shown in menu H9/C1. See also chapter "Interlocking function", page 76. 12. Fault output "Loss of main power source to external power supply equipment" will activate a fault in EBL128. It will have the same time delay, as set for the Loss of main power source fault for EBL128. The following fault message will be shown: FAULT: Mains, ext. power supply 13. Fault output "Loss of the battery charger to external power supply equipment" will activate a fault in EBL128. It will have the same time delay, as set for the "Loss of main power source" fault for 58 Type of output = Routing equipment (Fire brigade tx).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 58 EBL128. The following fault message will be shown: FAULT: Charging ext. power supply 14. "Fire door closing" outputs will be activated for 20 seconds by this trigger condition. 15. Pre-warning, e.g. from a High Sensitive Smoke Detector's pre- warning output. Zone no. and Address set to the same as the corresponding fire alarm (from the same detector). 16. "Activated Fault routing equipment" signal (feed-back) to EBL128 will light up the LED "Fault tx activated" on the front. Output with trigger condition "Indication Fault tx Activated" will be activated. 17. Activated input will light up the LED "Extinguishing" on the front. (Normally the LED will be lit when a corresponding output is activated.) Output with trigger condition "Extinguishing system released" will be activated. 18. Activated input will generate a fault in EBL128. Output with trigger condition "Extinguishing system fault" will be activated. The following fault message will be shown: FAULT: Extinguishing system fault 19. Activated input will activate a fire alarm in EBL128 (Zone no.) from an extinguishing system. The alarm devices will not be silenced by the "outside switch" (New Zealand FB Silence switch). 20. Activated input will generate a fault in EBL128. The following fault message will be shown: FAULT: Fault warning routing equipment 21. Activated input will activate an output (Technical address / output.) 22. Used for the "outside switch" (i.e. the New Zealand FB Silence switch). 23. Output with trigger condition "Activated Key cabinet" will be activated. 24. Activated input will activate all programmable outputs of type "Alarm devices" steady (continuous). 25. The Addressable multipurpose I/O unit 3361 monitored input "In0" used as zone line input (Z) for conventional detectors. 8.2 Logic The logic has to be set (in the Win128 dialog box "Input Properties").

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 59 8.2.1 Not supervised (default) (•) Normally open (low) Normally open contact / normally low optocoupler input (3361). ( ) Normally closed (high) Normally closed contact / normally high optocoupler input (3361). 8.2.2 Supervised Valid for the c.i.e. programmable input I0 and the Inputs and Outputs expansion board 4583 programmable inputs (Input 0-4). (•) Normally open (high resistance) ( ) Normally closed (low resistance) Depending on the selected logic, Normally open (high resistance, 3K3) or Normally closed (low resistance, 680R), the function will be according to the table on page 55.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 60 9 Programmable outputs EBL128 has two programmable voltage outputs (S0 and S1) and one programmable relay output (R0). 8 relay outputs expansion board 4581 can be mounted in EBL128. Input and Output expansion board 4583 with three programmable outputs (Output 0-2) can be mounted in EBL128. See chapter "Expansion boards 458x", page 22. On the COM loop can be connected Addressable Multipurpose I/O unit 3361 with two programmable relay outputs (Re0 and Re1) per unit and Addressable 2 voltage outputs unit 3364 with two programmable voltage outputs (VO0 and VO1) per unit. Addressable siren 3377 and Addressable sounder base 3378 can also be connected on the COM loop, i.e. these units have no physical output, only the siren and sounder respectively. NOTE! Units type 3361 + 3364 = max. 16. Units type 3377 + 3378 = max. 50. Each output is programmed (via Win128), when applicable, regarding:  Name (Normally not changed)  Type  Output signal period (continuous, pulse, delay, etc.)  Logic (NO / normally low or NC / normally high)  Supervised / Not Supervised (The EBL128 voltage outputs, Input and Output expansion board 4583 voltage outputs (Output 0-1) and Addressable 2 voltage outputs unit 3364.)  Control expression (with one or more trigger conditions). If Enter arguments in dialog is selected a separate dialog box is opened for easier entering of the required data (e.g. zone, address, etc.). Current size gives a rough indication of how big the control expression is. Normally it should be < 80 but it is depending on the number and types of trigger conditions but also the logical operators used in the control expression. Figure 11. The Win128 dialog boxes "Voltage" & "Relay Output" respectively.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 61 Each 3377 and 3378 unit is programmed (Win128) regarding:  Technical address  Name (Normally not changed)  Priority level (High / Low) For each priority level:  Sound type (Steady/continuous, Intermittent/pulsed or Alternating/two-tone)  Name  Type (Normally "Alarm device")  Output signal period (Normally "Steady")  Control expression (with one or more trigger conditions) If Enter arguments in dialog is selected a separate dialog box is opened for easier entering of the required data (e.g. zone, address, etc.). Current size gives a rough indication of how big the control expression is. Normally it should be < 80 but it is depending on the number and types of trigger conditions but also the logical operators used in the control expression. Figure 12. The Win128 dialog box "Addressable siren 3377" (The dialog box "Addressable sounder base 3378" is similar). 9.1 Control unit outputs S0 – S1 EBL128 has two programmable, supervised (monitored)59 voltage outputs: 59 Supervised as default but via Win128 it is possible to set each output individually as not supervised (not monitored). A normally high output can not be supervised. Supervised outputs have to be calibrated via menu H5/A3, see the EBL128 Operating Instructions. 1-5 supervision resistors 33K can be used. The calibrated value has to be in the range 4K7-50K. A fault will be generated

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 62 S0 Supervised (monitored) voltage output, 24V DC60, max. 500 mA (Fuse F8). S1 Supervised (monitored) voltage output, 24V DC60, max. 200 mA (Fuse F6). As default S0-S1 are set to type "Alarm device", "Intermittent 0.8 / 0.8, normally low, supervised and trigger condition "General fire". Connections and more information, see drawing 128-22. See also chapter "Programmable voltage outputs (S0-S1)", page 18. 9.2 Control unit output R0 EBL128 has one programmable relay output: R0 Relay output, NO or NC contacts61 programmable. As default R0 is set to type "Routing equipment" (Fire brigade tx), Steady (cont.), normally open and trigger condition "Fire brigade tx". Connections and more information, see drawing 128-23. 9.3 8 relay outputs expansion board 4581 Output 0 – Output 7 Each 4581 board has eight programmable relay outputs: Output 0 Relay output, NO or NC contacts programmable Output 1 Relay output, NO or NC contacts programmable Output 2 Relay output, NO or NC contacts programmable Output 3 Relay output, NO or NC contacts programmable Output 4 Relay output, NO or NC contacts programmable Output 5 Relay output, NO or NC contacts programmable Output 6 Relay output, NO or NC contacts programmable Output 7 Relay output, NO or NC contacts programmable Relay contact ratings: Max. 2A @ 30 V DC. Connections and more information, see dwg. 128-30. 9.4 Inputs and Outputs expansion board 4583 Output 0 – 1 Expansion board 4583 has two programmable, supervised (monitored)59 voltage outputs: Output 0 Supervised (monitored) voltage output, 24V DC60, max. 200 mA (Fuse F1). Output 1 Supervised (monitored) voltage output, 24V DC60, max. 200 mA (Fuse F2). Connections and more information, see drawing 128-33. See also chapter "Inputs and outputs expansion board 4583", page 26. for a value outside this range. A normally high output will be low for a few seconds during restart of EBL128. 60 See chapter "Technical data", page 143, regarding system voltage. 61 Relay contacts: max. 1 A @ 30 V DC.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 63 9.5 The 3361 unit outputs Re0 – Re1 Each 3361 unit has two programmable relay outputs: Re0 Relay output, NO or NC contacts programmable Re1 Relay output, NO or NC contacts programmable Relay contacts: max. 2 A @ 30 V DC / 125 V AC (60W). Connections and more information, see drawings 128-21 & -26. 9.6 The 3364 unit outputs VO0, VO1 & VO2 Each 3364 unit has two programmable, supervised (monitored)59 voltage outputs: VO0 Supervised (monitored) voltage output, 24V DC, max. 1A62 VO1 Supervised (monitored) voltage output, 24V DC, max. 1A62 VO2 is a voltage output, 24V DC, max. 1A62, intended for fire door closing. Normally high. For more information see the Technical Description MEW00529. 24 V DC required from an external power supply unit (e.g. 3366). Connections, see drawing 128-21 & -28. 9.7 The 3377 unit output (siren) Each 3377 unit has one programmable output: Output Siren, with two priority levels and three sound types. Connections and more information, see drawing 128-21. 9.8 The 3378 unit output (sounder) Each 3378 unit has one programmable output: Output Sounder, with two priority levels and three sound types. Connections and more information, see drawing 128-21. 9.9 The 3379 unit output (sounder) Each 3379 unit has one programmable output: Output Sounder, with two priority levels and three sound types. Connections and more information, see drawing 128-21. 62 Cont. 1 A, during 10 ms 1.4 A.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 64 10 Output programming Output programming is done via Win128. See the Win128 dialog box respectively. For more information see also Win128 help. 10.1 Type The following output types are available (see also comments below): 0. Control 1. Fire Ventilation 2. Extinguishing 3. Alarm Device 4. Routing Equipment (Fire brigade tx) 5. Control, neutral 6. Interlocking Output Comments to the types: 0. Default. General (normal) control output63 1. Used to activate fire ventilation equipment64 2. Used to activate extinguishing equipment65 3. Used for sounders, etc.66 4. Used for fire alarm tx67 5. General (normal) control output. No collective disablement and no LED indication. 6. Output used together with a corresponding interlocking input. See chapter "Interlocking function", page 76. Activated outputs are shown in menu H9/C1. 63 Collectively disabled via menu H2/B4 (all control outputs). Re-enabled via menu H2/B8. 64 Collectively disabled via menu H2/B4 (all ventilation outputs). Re- enabled via menu H2/B8. LED "Ventilation" is indicating activated output. 65 Collectively disabled via menu H2/B4 (all extinguishing outputs). Re- enabled via menu H2/B8. LED "Extinguishing" is indicating activated output. 66 Collectively disabled via menu H2/B4 (all alarm device outputs). Re- enabled via menu H2/B8. Controlled by push button "Silence alarm devices". Fault on / disabled output is indicated by LED "Fault / Disablements Alarm devices" blinking (fault) / continuous (disablement). 67 Disabled / Re-enabled via menu H2/B9 (Fire and/or fault outputs). Controlled via open door (if programmed so). Used together with trigger condition Fire brigade tx. LED "Fire brigade tx" is indicating activated output. (Fire brigade tx feedback via a programmable input can light up the LED instead). Fault on / disabled output is indicated by LED "Fault / Disablements Fire brigade tx" blinking (fault) / continuous (disablement).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 65 10.2 Logic The logic is set in the Win128 dialog box "Voltage or Relay Output". (•) Normally open / low Normally open relay contacts / normally low voltage output. ( ) Normally closed / high Normally closed relay contacts / normally high voltage output (24V DC). 10.3 Supervised A voltage output is normally supervised (default). By un-marking this checkbox the voltage output will be not supervised. NOTE! A normally high output is not supervised. See also chapter "Programmable voltage outputs (S0-S1)", page 18. 10.4 Output signal period Each output uses an "Output signal period", which controls the output's activation. The following are available:  Steady (continuous)  Intermittent 0.8s/0.8s  User defined 1  User defined 2  User defined 3  User defined 4  User defined 5  User defined 6  User defined 7  User defined 8 User defined 1-8 can be built up with type and time. The following types are available:  Steady (continuous)  Intermittent  One pulse  Steady Delayed Activation  Intermittent Delayed Activation  One pulse Delayed Activation  Steady Delayed De-Activation The following times are available:  Delay time (when required)  Pulse length time (when required)  Pulse off time (when required)  De-activation time (when required) See also chapter "Output Signal Periods", page 125.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 66 Figure 13. Delay time, Pulse length, Pulse off and/or De- Activation, have to be set for the "Signal period" respectively. For types 1 & 4 the x and y times must be equal and max. 5.6s. For types 2 & 5 the x time must be max. 5.6s. NOTE! There are limitations according to the following table:

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 67 In EBL128 COM loop units Output Type S0-S1 R0 4581 board 4583 board I/O unit 3361 Unit 3364 Siren & S/B 3377 & 3378 4582 board Inter locking 0 Steady (continuous) X X X X X X X X X 1 Intermittent X X XXX -- -- XX -- -- -- 2 One pulse X X XXX -- -- -- -- -- -- 3 Steady (continuous), delayed activation X X X X X X X X X 4 Intermittent, delayed activation X X XXX -- -- XX -- -- -- 5 One pulse, delayed activation X X XXX -- -- -- -- -- -- 6 Steady (continuous), delayed de-activation X X X X X X X X -- Figure 14. The types that can be used in the "Output signal period" for the programmable output respectively X = Output type can be used. XX = Output type can be used but only 0.8s/0.8s. XXX = Output type can be used but max. 5.6s/5.6s and the pulse max. 5.6s respectively.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 68 10.5 Control expression Each programmable output has to be given a control expression (with one or more trigger conditions), made by so called Boolean algebra. Trigger conditions (displayed a list by clicking the right mouse button), logical "Operators" (AND, OR, NOT) and parentheses are used to build up a "control expression" containing up to 40 trigger conditions. See also chapter "Control expression examples" page 72 and the Win128 help. 10.5.1 Trigger conditions Some trigger conditions require additional information, see parentheses (+nnnnn) after the trigger condition respectively. Consecutive trigger conditions includes a "Quantity" that shows the number of alarm points within the sequence that have to be activated to fulfil the trigger condition. (Quantity = 1-10. "1" is normal.) The following trigger conditions are available: 1 Fire Alarm Zone (+Zone no.) 2 Fire Alarm Zone Address (+Zone no.+Address) 3 General Fire Alarm 4 Consecutive Fire Alarm (sequence) (+start Zone no. and address +stop Zone no. and address +Quantity) 5 Pre Warning Zone (+Zone no.) 6 Pre Warning Zone Address (+Zone no.+Address) 7 General Pre Warning 8 Consecutive Pre Warning (+start Zone no. and address +stop Zone no. and address +Quantity) 9 Heavy Smoke Alarm Zone (+Zone no.) 10 Heavy Smoke Alarm Zone Address (+Zone no.+Address) 11 General Heavy Smoke Alarm 12 Consecutive Heavy Smoke Alarm (sequence) (+start Zone no. and address +stop Zone no. and address +Quantity) 13 Two Address Dependent Fire Alarm (+Zone no. +Address) 14 Interlocking Input Area Activated (+Area no.) 15 Interlocking Input Area Point Activated (+Area no. +Point) 16 General Interlocking Input Activated 17 Consecutive Interlocking Input Activated (sequence) (+start Area no. and point +stop Area no. and point +Quantity) 18 Indication Fire Brigade Tx Activated 19 Indication Fault Tx Activated 20 Fire Brigade Tx Disabled 21 Zone Disabled (+Zone no.) 22 Zone Address Disabled (+Zone no. +Address)

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 69 23 General Zone Address Disabled 24 General Fault 25 General Charge Fault 26 Reset Pulse Zone Address (+Zone no. +Address) 68 27 Time Channel Activated (+Time channel no.) 28 Alert Annunciation Activated 29 Alert Annunciation Acknowledged 30 Door Open 31 Key Cabinet Open 32 General Control Disabled 33 General Alarm Device Disabled 34 Fire Door Closing (+Zone no. +Address) 35 General Service Signal 36 Fire Brigade tx 37 AAF Zone Alarm (+AAF Zone no.) 38 Quiet Alarm Zone (+Zone no.) 39 Quiet Alarm Zone Address (+Zone no. +Address) 40 Extinguishing System Fault 41 Extinguishing System Released 42 Activated Key Cabinet 43 Multiple Detector Alarm 44 One Detector Alarm Comments to the trigger conditions (functions): 1 Fire alarm from a Zone. 2 Fire alarm from a Zone-Address. 3 Fire alarm from any alarm point in the system. 4 Fire alarm from any alarm point within the specified range. "Quantity" is the number of alarm points required to activate the output. 5 Pre-warning,69 else see 1. 6 Pre-warning, else see 2. 7 Pre-warning, else see 3. 8 Pre-warning, else see 4. 9 Heavy smoke / heat alarm, else see 1. 10 Heavy smoke / heat alarm, else see 2. 11 Heavy smoke / heat alarm, else see 3. 12 Heavy smoke / heat alarm, else see 4. 13 Only one address (in two-unit-dependence) is in fire alarm state. For more information, see EBL128 Operating Instructions. 68 Only valid for EBL128 outputs (S0-S1 and R0), 4581 outputs and 3361 outputs (i.e. not 3364 outputs). 69 The trigger condition is true as long as the pre-warning level is exceeded. It is also true as long as the fire alarm level is exceeded.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 70 14 One or more interlocking inputs, in the specified interlocking area, are activated. 15 The interlocking input, in the specified interlocking area/point, is activated. 16 One or more interlocking inputs are activated. 17 One or more interlocking inputs, in the specified range, are activated (from interlocking area no./point to interlocking area no./point). 18 Output activated when input trigger condition "Activated routing equipment" is true.70 The output is activated until the alarm has been reset. 19 Routing equipment output "Fault tx" is activated or input trigger condition "Activated fault routing equipment" is true.71 20 Routing equipment output (Fire brigade tx) is disabled.72 21 The specified zone is disabled. 22 The specified alarm point (zone/address) is disabled. 23 One or more alarm points (zone/address) are disabled. 73 24 One or more faults are generated in the system.74 25 Loss of mains (in a c.i.e.). NOTE! The output(s) will be activated immediately but the corresponding fault is normally delayed. 26 This control expression is true for 5 seconds, whenever a reset pulse is sent to the specified zone/address. 27 The programmed time channel (1-12) is activated. 28 Alert annunciation activated (by any alarm point set to activate this function). Valid until the AA alarm is reset or becomes a normal fire alarm. For more information, see EBL128 Operating Instructions. 29 Alert annunciation activated (by any alarm point set to activate this function) and acknowledged. Valid until the AA alarm is reset or becomes a normal fire alarm. For more information, see EBL128 Operating Instructions. 30 Door open in EBL128 / ext. FBP.75 31 Key cabinet alarm. For more information, see EBL128 Operating Instructions. 32 General control disabled (via menu H2/B7). 73 33 General alarm device disabled (via menu H2/B876 or via "Silence alarm devices). 70 Indicated by LED "Fire brigade tx". Output can be tested via menu H1. 71 Indicated by LED "Fault tx activated". Output can be tested via menu H1. 72 Indicated by LED "Fault/Disablements Fire brigade tx". 73 Indicated by LED "Disablements". 74 Indicated by LED "General fault" and/or LED "Fault tx activated". 75 Or ext FBPs connected to the control unit. Indicated by LED "Door open".

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 71 34 This trigger condition plus the OR operator shall be used for each detector (zone-address) controlling a fire door (normally > two detectors). Type of output is normally "Control, neutral".77 See also chapter "Fire Door Closing function", page 80. 35 Service signal is activated (by any sensor).78 36 Used for routing equipment (Fire brigade tx) output only. Has to be type Routing Equipment (Fire brigade tx). NOTE! The Alert Annunciation function is working with this trigger cond. (If this function shall not be used, use trigger cond. "General fire alarm" instead.) 37 "Alarm Acknowledgement Facility" alarm activated in the specified AAF Zone. Required "AAF Control" unit is available on the Australian market only. 38 Any "Quiet alarm" in the specified zone will activate the output. Used e.g. for the Australian fan control function. 39 One specified "Quiet alarm" in the specified zone will activate the output. Used e.g. for the Australian fan control function. 40 Output activated when input trigger condition "Extinguishing system fault" is true. 41 Output activated when input trigger condition "Extinguishing system released" is true. 42 Output activated when input trigger condition "Activated key cabinet" is true. 43 Output activated when input trigger condition "Multiple detector alarm" is true, i.e. fire alarm type A.79 44 Output activated when input trigger condition "One detector alarm" is true, i.e. fire alarm type B.79 10.5.2 Logical operators The logical operators available in Win128 are in priority order: ( ) parentheses, changes priority order NOT not-function (inverts), is written NOT in Win128 AND and-function, is written AND in Win128 OR or-function, is written OR in Win128 10.5.3 Control expression examples In order to understand the possibilities to create control expressions, here follow some AND, OR, NOT and ( ) examples and also some control expression examples. 76 Indicated by LED "Fault / Disablements Alarm devices". 77 In Danish convention (DBI), must only EBL128 outputs R0, S0-S1 and the COM loop unit 3364 be used. The type has to be "control neutral". 78 Indicated by LED "Service". 79 See chapter "Fire alarm type A and Fire alarm type B", page 96.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 72 10.5.3.1 AND a AND b AND c=y y is true (=1) when all the conditions a, b, c are true, i.e. a=1 and b=1 and c=1 makes y=1. All other combinations makes y=0. This is also shown in the following table: a b c y 0 0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1 1 10.5.3.2 OR a OR b OR c=y y is true if at least one of the conditions a, b, c is true, i.e. a=1 or b=1 or c=1 makes y=1. This is also shown in the following table: a b c y 0 0 0 0 0 0 1 1 0 1 0 1 0 1 1 1 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1 1 10.5.3.3 NOT Inverts a condition, e.g. NOT b=NOT 0=1. A OR NOT b AND c=y

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 73 This is shown in the following table: a b c y 0 0 0 0 0 0 1 1 0 1 0 0 0 1 1 0 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1 1 10.5.3.4 Parentheses Changes priority order. a OR NOT (b AND c)=y (This is same as the previous but parentheses are added, which makes a differance.) This is shown in the following table: a b c y 0 0 0 1 0 0 1 1 0 1 0 1 0 1 1 0 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1 1 10.5.3.5 Control expressions The AND operator has priority, i.e. a AND b OR c = (a AND b) OR c. This is perhaps more obvious if you write it: a · b + c. NOTE! a AND b OR c ≠ a AND (b OR c). Here follows some examples (and explanations) to show how to build a control expression with trigger conditions and logical operators:

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 74 Example 1 Output: Voltage output S0 Control expression: Pre Warning Zone (10) Explanation: Pre-warning activated in zone no. 10 will activate the output S0. Example 2 Output: Relay output R0 Control expression: General Control disabled AND NOT Door Open Explanation: Controls disabled via menu H2/B7 will activate the output R0 when the door in EBL128 is not open (i.e. when it is closed). Example 3 Output: Voltage output VO0 Control expression: Fire Alarm Zone (23) AND Fire Alarm Zone (24) AND NOT General Fault Explanation: Fire alarm activated in zone 23 and zone 24 will activate the output VO0 only if there are no faults in the system at the same time. Example 4 Output: Voltage output S1 Control expression: Consecutive Fire Alarm (10,10,10,19,1) OR Consecutive Fire Alarm (10,21,10,40,1) Explanation: Fire alarm activated by one of the alarm points in zone 10 addresses 10-19 or by one of the alarm points in zone 10 addresses 21-40 will activate the output S1 (i.e. the alarm point in zone 10 address 20 will not activate the output S1).

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 75 11 Interlocking function The interlocking function is used to verify that an output really is activated, i.e. by "combining" an output with an input (feed-back from the equipment controlled by the corresponding interlocking output). 11.1 Interlocking programming Win128 is used for the programming. Up to 32 Interlocking Combinations can be used. NOTE! Each interlocking input and each interlocking output can only be used in one interlocking combination. 11.1.1 Interlocking output The "Voltage Output" / "Relay Output" dialog boxes are to be used. Type: "Interlocking" is to be selected. Output signal period: Steady (continuous) or Steady, delayed activation is to be selected. Control Expression is to be programmed for the output, i.e. for the equipment to be controlled. Activated output will be indicated in menu H9/C1. Name: It is recommended to add information, e.g. the interlocking combination's presentation number (Area-Point). 11.1.2 Interlocking input The "Input" dialog box is to be used. Triggered by: "Interlocking Input" is to be selected. Activated input will be indicated in menu H9/C1. Name: It is recommended to add information, e.g. the interlocking combination's presentation number (Area-Point). 11.1.3 Interlocking combination One interlocking output and one interlocking input are programmed in one interlocking combination to get the interlocking functions. NOTE! The interlocking outputs and inputs have to be programmed before the programming of an interlocking combination is possible to do.80 An interlocking combination can have only an output or only an input programmed, e.g. when a text shall indicate an activated output or input. 80 In the "Interlocking Combination" dialog box are listed all the outputs and inputs previously programmed for interlocking, see Figure 15. Input EBL128 Output Controlled equipment Feed-back signal

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 76 Figure 15. The Win128 dialog box "Interlocking Combination". Logical Name: Displayed in the Win128 Tree and List views. Default is "Interlocking Combination" that can be changed when wanted / required. Area and Point: Each "Interlocking Combination" is presented as Area-Point (compare with Zone-Address). Area numbers 1-31 are possible to use and Point numbers 1-63 are possible to use. Available interlocking outputs list displays all the previous programmed outputs, Type = "Interlocking Output". Available interlocking inputs list displays all the previous programmed inputs with the Triggered by alternative (trigger condition) 10 = "Interlocking Input". Select one output and one input in the list respectively.81 Press Select and the selected output and input will be shown in the Selected output and Selected input field respectively. Text = Interlocking text to be shown in the menu H9/C1. Can be written in this field or in the "Texts" dialog box, see chapter "Creating the alarm texts via Win128", page 101. Buzzer checked = activated interlocking input will turn on the EBL128 buzzer (0.8 / 0.8 sec.)82. The buzzer can be silenced. It will be automatically turned on again, if a new interlocking input is activated. 81 Output / Input parent will then show in which unit the output / input respectively is situated. 82 Priority order: Fire alarm – Pre-warning - Interlocking - Fault.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 77 Latched output checked = Output reset has to be performed via menu H9/C3. (Automatically output reset will not take place when the control expression becomes false.). Fault checked = Fault detection ON. Fault Detection Time: If the input is not activated within 5-255 seconds after the output is activated83, a fault will be generated: FAULT: Interlocking input AA/PP Date: MM-DD Time: HH:MM 11.2 Interlocking indications One or more activated Interlocking Combinations (interlocking output and/or input) are indicated in the display in EBL12884: Interlocking input/output activated See menu H9/C1 Disabled interlocking output is indicated by the LED "Disablements". 11.3 Information of interlocking combinations (H9) Menu H9 has the following sub menus. 11.3.1 Display interlocking information (H9/C1) See also chapter "Interlocking indications", page 78. In menu H9/C1 information will be shown as follows: Output AA/PP activated at HH:MM Interlocking text.. .. .. or Output AA/PP act HH:MM, input act HH:MM Interlocking text.. .. .. or Input AA/PP activated at HH:MM Interlocking text.. .. .. AA = Interlocking combination Area PP = Interlocking combination Point within the Area HH = Hours MM = Minutes Use "↑" "↓" to scroll between several interlocking combinations. 83 After the end of the delay time (if used). 84 This indication has low priority and will only be shown in the display if there are no fire alarms, faults, disablements, etc.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 78 11.3.2 Activate interlocking output (H9/C2) Even if the control expression for an interlocking output is not fulfilled (true), the output can be manually activated via this menu. The "Interlocking Combination" (Area / Point) is to be entered to activate the output. The corresponding interlocking input will be "monitored" in the same way as if the output was activated by its control expression. Reset has to be performed via menu H9/C3. 11.3.3 Reset interlocking output (H9/C3) Activated interlocking outputs are listed here. Use "↑" "↓" to scroll between the "Interlocking Combinations" (Area / Point). Interlocking output activated via its control expression and latching output selected: The output has to be reset via this menu. Interlocking output activated via its control expression and latching output not selected: The output can be reset via this menu. Interlocking output activated via menu H9/C2: The output has to be reset via this menu. 11.3.4 Disable interlocking output (H9/C4) Interlocking outputs (i.e. Output Type = Interlocking) can be disabled via menu H9/C4. A disabled output will stay in (or return to) the normal condition for the output respectively. The "Interlocking Combination" (i.e. Area / Point) is to be entered to disable the output. If "00/00" is entered, all interlocking outputs will be disabled. 11.3.5 Re-enable interlocking output (H9/C5) Interlocking outputs (i.e. Output Type = Interlocking) can be re- enabled via menu H9/C5. Disabled interlocking outputs are listed in menu H9/C5. Use "↑" "↓" to scroll between the "Interlocking Combinations" (i.e. Area / Point) or type it via the key-pad. If "00/00" is entered, all interlocking outputs, disabled via menu H9/C4 and "00/00", will be re-enabled. 11.4 Interlocking control expressions A programmable output control expression can contain "interlocking" trigger conditions ("Functions") numbers 14-17 (see chapter "Control expression", page 69), i.e. one or more outputs can be activated when one or more interlocking inputs are activated.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 79 12 Fire Door Closing function Programmable outputs85 can be used for fire door closing. A special trigger condition is available (no. 34 = Fire Door Closing). Type of output shall normally be "Control, neutral". One or more alarm points can control the output, e.g. the detectors on both sides of the fire door. M S S 01-01 01-02 Programmable output Door release magnet Smoke detector Fire door Fire Door Closing function (ABDL) In case of one of the following events, the output will be "activated" (i.e. powerless) and the fire door will close:  Fire alarm (any of the programmed detectors)  Fire alarm in "Test mode" (any of the programmed detectors)  Fault (i.e. "no answer" from any of the programmed detectors86)  Disablement (any of the programmed detectors, the involved zone(s) or the COM loop).  A definite time every day, if programmed via Win128. (The output will be activated for 20 seconds.)  Via a programmable input (trigger condition no. 17 = Door Closing Test Input). (The output will be activated for 20 seconds.) NOTE! For safety reasons should an I/O unit 3361 output not be used.85 If there is a short-circuit or a double break on the COM loop, the I/O unit can not be "ordered" to activate the output, i.e. the door will not be closed. If a magnet contact is available, it is possible to get a "closed fire door verification" via the Interlocking function. In this case, Type of in- /output has to be "Interlocking in-/output". See also chapter "Interlocking function", page 76. 85 In the DBI (Danish) convention, must only EBL128 outputs R0 and S0-S1 as well as the 3364 unit be used and "Type of output" has to be "Control neutral". 86 E.g. a faulty detector, two breaks or short-circuit on the COM loop.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 80 13 Functions / Services / Features Some Functions / Services / Features require programming via Win128, see chapter "PC S/W", page 12. For more information see also the EBL128 Operating Instructions and Win128 help. How to connect the PC and more information, see the EBL128 Operating Instructions chapter "SSD programming and download" and "Software (S/W) download". 13.1 Analog smoke detectors 13.1.1 Sensor value The basic working principle and some expressions are described below. Regarding the analog smoke detectors 430x in NORMAL mode, see chapter "Alarm algorithms for smoke detectors / Detection levels / Offsets", page 82. An analog smoke detector is like a "sensor". It detects its environment at all times. The detected analog values are, in the detector, converted to digital "sensor values", which are for each individual detector, continuously (each 3.4th sec.) picked up and evaluated by EBL128. In Figure 16 the (digital) sensor values are represented by the graph "Working level". 13.1.2 Week average sensor value Each hour, one sensor value is stored (in EBL128) and each week are these stored sensor values used to calculate a "week average sensor value".87 This is done for each analog smoke detector individually. In Figure 16 the (digital) week average sensor values are represented by the graph "Week average". Each analog smoke detector has a default sensor value = 1 (i.e. the "Working level" at Time = 0). A "fire alarm offset" (value) is added to get each detector's "Fire alarm level", i.e. the fire alarm level will be adjusted in relation to each new week average sensor value in order to keep the detector's fire alarm sensitivity constant. The fire alarm level is in Figure 16 represented by the graph "Fire alarm level" (being parallel with the graph "Week average"). Service signal will be given when the week average sensor value for a detector has reached a fixed level, see "Service level" in Figure 16. 87 The very first week average sensor value will be calculated within 2 minutes after any restart, i.e. also after SSD download. During these "2 min." all analog smoke detector fire alarms are suppressed.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 81 Figure 16. The basic working principle for one analog smoke detector ("sensor"). Sensor value, working level, week average sensor value, fire alarm offset / level and service level. "Sensor Information" is available via menu H4/U3. Via Win128 and a PC connected to EBL128 you can get "Sensor Information" for all analog detectors on the COM loop or an individual detector. For an individual detector you can also get continuous information. Also via the Web-server II 1598 you can get "Sensor Information" for all analog detectors on the COM loop. The smoke detector sensor values are presented as obscuration in % per meter (%/m) and heat detector sensor values as °C. The following is valid for the analog smoke detector types 430x in NORMAL mode. In order to secure real alarms and reduce nuisance alarms, advanced algorithms are used and a decision value is calculated, see below. 13.1.3 Decision value The decision value is used to decide if it is normal state, pre-warning, fire alarm or heavy smoke alarm. It is also used in the smouldering smoke algorithm (see page 86). The decision value is calculated, see chapter "Filtering algorithm, page 84. 13.1.4 Alarm algorithms for smoke detectors / Detection levels / Offsets Each detector uses an alarm algorithm and each detector has three different detection levels for: 1. fire alarm88 88 The fire alarm level for each analog detector (sensor) = the current week average sensor value + a fixed fire alarm offset (value), i.e. when the current

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 82 2. pre-warning will be activated at a lower level (smaller offset) than for fire alarm, i.e. pre-warning will be activated before fire alarm will be activated. 3. heavy smoke alarm will be activated at a higher level (bigger offset) than for fire alarm, i.e. heavy smoke alarm will be activated after fire alarm has been activated. Heavy smoke alarm will be saved in the event log.89 The pre-warning offset and the heavy smoke alarm level can, for all detectors, be set in Win128, see chapter "Alarm Algorithms", page 121. See also Win128 help. The fire alarm offset can, for all detectors, be set in Win128, see chapter "Alarm Algorithms", page 121. See also Win128 help. NOTE! Changing these parameters will affect the sensitivity and detection time and should be done by authorised personnel only!!!!! In addition, a special password is required to change the fire alarm parameters. "Pre-warning", "Fire Alarm" and "Heavy Smoke Alarm" can activate programmable outputs respectively, see chapter "Control expression", page 69. See also the EBL128 Operating Instructions. 13.1.5 Alarm algorithm / Alternative alarm algorithm Alarm algorithm In order to secure real alarms and reduce nuisance alarms90, six different alarm algorithms are available. See Figure 17., page 85. The alarm algorithms are based on:  Normal, high or low sensitivity  Normal (15 sec.) or slow (35 sec.) detection time (alarm delay) Normal sensitivity. 3.0 % smoke obscuration per meter is required to activate fire alarm (i.e. fire alarm offset=30). This is default in the N-15 algorithm and should normally not be changed. High sensitivity. 2.4 % smoke obscuration per meter is required to activate fire alarm, i.e. less fire alarm offset than for normal sensitivity. High sensitivity can be used when an "early" fire alarm is wanted. Low sensitivity. 3.6 % smoke obscuration per meter is required to activate fire alarm, i.e. a higher fire alarm offset than for normal sensitivity. Low sensitivity can be used to get an extra delay time in order to reduce nuisance alarms90 but might not fulfil the EN54-7 specifications. week average sensor value is re-calculated (and adjusted) the fire alarm level will also be adjusted. The detector sensitivity is accordingly constant. 89 No other heavy smoke alarm information if not an ext. FBP with printer is available. If so, the heavy smoke alarm information will also be printed out. 90 So called false / unnecessary alarms.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 83 Normal detection time (15 sec.) If it was possible to completely fill up a detector with smoke within 1 sec. there will nevertheless be 15 seconds alarm delay. This alarm delay is a "filter" to reduce nuisance alarms. Slow detection time (35 sec.). If it was possible to completely fill up a detector with smoke within 1 sec. there will nevertheless be 35 seconds alarm delay. This alarm delay is an "extra filter" to reduce the nuisance alarms90 but might not fulfil the EN54-7 specifications. Alternative alarm algorithm Each analog smoke detector can have two alarm algorithms programmed (via Win128). One alarm algorithm that is normally used (N-15 is default) and one alternative alarm algorithm turned on / off by a time channel (internal or external). Normal sensitivity can for example be used during the night-time and low sensitivity and/or slow detection time can be used during the daytime, i.e. the alternative alarm algorithm can be used to reduce nuisance alarms90 during working hours. The actual (current) alarm algorithm is shown in menu H4/U3. The alarm algorithm parameters can, for all detectors, be set in Win128, see chapter "Alarm Algorithms", page 121. See also Win128 help. 13.1.6 Filtering algorithm In order to secure a fast detection of real fire alarms and to reduce nuisance alarms to a minimum, the filtering algorithm is used in the six different alarm algorithms. The filtering algorithm uses the sensor value to calculate a decision value depending on which alarm algorithm that is selected. The decision value starts at zero. Each time a new sensor value is picked up (sampled) from an analog smoke detector, this new sensor value is compared with the actual decision value, which will be adjusted, see below. If the difference, between the new sensor value and the actual decision value is < "X", the decision value is set equal to the new sensor value. If the difference, between the new sensor value and the actual decision value is > "X", the decision value is increased (or decreased) by "X". The decision value will consequently not be increased / decreased with a value exceeding the "X" value even if the sensor value is much higher / lower, see Figure 18. "X" = The Step Value, is depending on which alarm algorithm that is used, see Figure 17. Analog detector Normal detection time (15sec.) Slow detection time (35sec.)

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 84 H-15 (High sensitivity, 2.4%) N-15 (Normal sensitivity, 3%) L-15 (Low sensitivity, 3.6%) H-35 (High sensitivity, 2.4%) N-35 (Normal sensitivity, 3%) L-35 (Low sensitivity, 3.6%) 4301 X=4 X=5 X=6 X=2 X=2 X=2 4300 X=8 X=10 X=12 X=4 X=4 X=4 Figure 17. The six alarm algorithms. Default is alarm algorithm N-15, i.e. normal detection time (15 sec.) and normal sensitivity (3%). "X" is the step value. (NOTE! The L-15, H-35, N-35 and L-35 algorithms might not fulfil the EN54-7 specifications.) Figure 18. An example showing the alarm algorithm "N-15", i.e. the step value X = 5. The detector polling time t ≈ 3.4 sec. Explanations to the figure: One analog smoke detector 430x using alarm algorithm "N-15", i.e. normal detection time (15sec.) and normal sensitivity (3.0 %/m). This gives X = 5. The week average sensor value has in this example been adjusted (due to contamination) and is now "10"91, i.e. the pre-warning level is 10+offset 22=32 and the fire alarm level is 10+offset 30=40, which is the same as 4.0 %/m. The sensor values and decision values are approx. equal ("10"), until the polling when the sensor value increases to approx. "27". Since 27-10 > X=5, the decision value is increased by "5" to "15" (10+5). 91 "10" = 1.0 %/m. A new / clean detector has approx. 0.1 %/m, i.e. this detector is probably mounted in a very "dirty" environment. A detector mounted in a normal office would after 8-10 years have approx. 0.3 %/m.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 85 Next polling the sensor value is approx. "45". 45-15 > 5, i.e. the decision value "15" is increased by 5 to "20", and so on. In this example the sensor value starts to decrease before the decision value reaches the fire alarm level. When the sensor value has decreased to approx. "25" the decision value is set to "30", because 35-25=10 > 5, i.e. the decision value "35" is decreased by 5 to "30", and so on. 1. The sensor value has reached the pre-warning level but nothing will happen since the decision value has not yet reached the pre- warning level. 2. The sensor value has reached the fire alarm level but nothing will happen since the decision value has not yet reached the fire alarm level. 3. The decision value has reached / passed the pre-warning level and pre-warning is activated. 4. The sensor values have started to decrease and the decision value is now below the pre-warning level and the pre-warning is automatically reset. NOTE! In case of a real fire, the sensor values would have stayed at a "high" value (> 40) for a long time and consequently the decision value would have increased and reached / passed the fire alarm level approx. 15 sec. after the sensor value reached the fire alarm level. 13.1.7 Smouldering smoke algorithm The smoke from a smouldering fire brings the sensor value to rise very slowly. This might last for hours and sometimes days. To be able to detect such a smouldering fire at an "early" stage, a smouldering smoke algorithm is used. The smouldering smoke algorithm is depending on and is always working parallel with the selected alarm algorithm, i.e. the smouldering smoke algorithm will affect the pre-warning and fire alarm levels, see below. If the decision value has been over the smouldering level (1) for 7 minutes, the pre-warning and fire alarm levels will be lowered (2): - The pre-warning level will be lowered to a level right between the original pre-warning level and the smouldering level. - The fire alarm level will be lowered to a level right between the original fire alarm level and the pre-warning level. If the decision value has reached the pre-warning level (3), but not the fire alarm level, after additional 90 minutes, the pre-warning and fire alarm levels will be lowered again (4): - The pre-warning level will be lowered to the original smouldering level. - The fire alarm level will be lowered to the original pre-warning level.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 86 The smouldering smoke algorithm will be aborted and the pre- warning and fire alarm levels restored to their original values if: - The decision value becomes lower than the smouldering level. - The decision value, after the 90 minutes, has not reached the pre- warning level. - The decision value, after the 90 minutes and additional 120 minutes, has not reached the fire alarm level. The smouldering offset can be set in Win128, see chapter "Alarm Algorithms", page 121. Figure 19. An example with the smouldering smoke algorithm. Explanations to the figure: Analog smoke detector 430x. The week average sensor value has in this example been adjusted and is now "10"91, i.e. the smouldering level is 10+offset 14=24, the pre-warning level is 10+offset 22=32 and the fire alarm level is 10+offset 30=40. When a smouldering fire starts, the sensor values and the decision values will increase very slowly from "10" and upwards. 1. The decision value has reached the smouldering level. A 7 minutes timer is started. 2. After the 7 minutes the decision value is still over the smouldering level. The pre-warning level and the fire alarm level are therefore lowered. A 90 minutes timer is started. 3. The decision value has reached the pre-warning level and pre- warning is activated. 4. After the 90 minutes the decision value is still over the pre- warning level but has not reached the fire alarm level. The pre- warning level and the fire alarm level are therefore lowered again. A 120 minutes timer is started. 5. The decision value has reached the fire alarm level and fire alarm is activated.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 87 6. The decision value has reached the original fire alarm level "40". This happens approx. 90 minutes after the fire alarm has been activated by the smouldering algorithm!! 13.1.8 Performance factor To find out the environment conditions where an analog smoke detector 430x is mounted, the Performance factor (Pf) can be studied via menu H4/U3 or via Win128. The performance factor is calculated for each detector individually. Each momentary sensor value is compared with the week average sensor value. The absolute difference is saved and each twenty-four hour (at midnight) an "average value" is calculated, i.e. the performance factor. (25412 = samples per 24 hours.) If the detector is mounted in a very "stable" environment (like an office) the performance factor will be low, i.e. min. 0 %/m. If the detector is mounted in a very "unstable" environment (like in a factory) the performance factor might be high, i.e. max. 2.55 %/m. An "unstable" environment where the sensor values vary a lot can cause nuisance alarms (unnecessary alarms). Perhaps should another type of detector be used, another alarm algorithm92 or other actions be taken, e.g. alert annunciation or two-unit-dependence (co-incidence alarm). The performance factor is shown in menu H4/U3 or via Win128 together with the min. and max. sensor values. These values should be studied together. (E.g. one or two high sensor values will not result in a high performance factor, like many high sensor values will.) 13.2 Analog heat detectors The following is valid for the analog heat detector types 330x in NORMAL mode. The detectors conforms to a class (see EN54-5:2000, clause 4.2) according to the requirements of the tests specified in EN54-5:2000, clause 5. Each analog heat detector can have two alarm algorithms programmed (via Win128). One alarm algorithm that is normally used (default) and one alternative alarm algorithm turned on / off by a time channel (internal or external). E.g. class A1 can be used during night-time and class B can be used during daytime. The alternative alarm algorithm can be used to reduce nuisance alarms during working hours. The actual algorithm is shown in menu H4/U3. When EBL128 has picked up a sensor value above the fire alarm level for a detector, the next two values from the same detector also 92 E.g. an alternative alarm algorithm during working hours. 25412 Σ |Xm-Xwa| m=0 --------------------------- = Pf 25412 Xm = momentary sensor values for 24 hours. Xwa = weak average sensor value

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 88 have to be above the fire alarm level to activate fire alarm in EBL128. (This results in approx. 7 seconds alarm delay). The same is valid for pre-warning only it is a lower level than for fire alarm. The same is valid for heavy heat alarm only it is a higher level than for fire alarm. Heavy heat alarm will be saved in the event log.93 The fire alarm, pre-warning and heavy heat alarm level respectively can be set via Win128, see chapter "Alarm Algorithms", page 121. "Pre-warning", "Fire Alarm" and "Heavy Smoke Alarm" can activate programmable outputs respectively, see chapter "Control expression", page 69. See also the EBL128 Operating Instructions for more information. 13.2.1 Class A1 algorithm Conforms to Class A1. Typical / max. application temperature 25 / 50° C. Max. / min. static response temperature 54 / 65° C. The algorithm is as follows: For a rate-of-rise < 4° C per minute: Fire alarm level is 56° C. Pre-warning level is 46° C. Heavy heat alarm level is 90° C. For a rate-of-rise > 4° C per minute: Fire alarm level is 46° C. Pre-warning level is 36° C. Heavy heat alarm level is 90° C. The biggest difference between the class A1 and A2 algorithms is that the class A1 algorithm will detect a fast temperature rise (rate-of-rise > 4° C per minute) faster than the class A2 algorithm. 13.2.2 Class A2 S algorithm Conforms to Class A2 S. Typical / max. application temperature 25 / 50° C. Max. / min. static response temperature 54 / 70° C. The algorithm is as follows: Fire alarm level is 60° C. Pre-warning level is 50° C. Heavy heat alarm level is 90° C. 13.2.3 Class B S algorithm Conforms to Class B S. Typical / max. application temperature 40 / 50° C. Max. / min. static response temperature 69 / 85° C. 93 No other heavy heat alarm information if not an ext. FBP with printer is available. If so, the heavy heat alarm information will also be printed out.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 89 The algorithm is as follows: Fire alarm level is 74° C. Pre-warning level is 64° C. Heavy heat alarm level is 90° C. The class B S algorithm shall be used when the typical application temperature is "high" compared with the class A1 and A2 algorithms. 13.3 Self verification The analog detectors in NORMAL mode have a built-in self verification function. The detector's H/W is always supervised by the detector's S/W and CPU. Every minute, each detector will receive a question from EBL128. If the self verification function has detected any fault it will be reported back to EBL128. A fault will be activated in EBL128 and the following fault message will be shown: FAULT: Detector xx-xx → FAULT: Detector techn. address nnn ← 13.4 Minimum / Maximum sensor values To find out how the environment is, where an analog detector in NORMAL mode is mounted, the minimum and maximum sensor values can be studied. The sensor values are continuously picked up and evaluated by EBL128 for each detector individually. Every value is checked if it is a new minimum or maximum value for that detector and if so, the value will be stored. At midnight every day a memory will be updated and the new minimum and maximum sensor values94 can be read in menu H4/U3 or via Win128. For analog smoke detectors the minimum and maximum sensor values are shown as XX.X % (obscuration) per meter. For analog heat detectors the values are shown as XX°C. 13.5 Two-unit dependence (co-incidence alarm) In some premises two-unit-dependent fire alarm (co-incidence alarm) can be used to avoid unwanted false alarms (nuisance alarms). Each analog or addressable detector (alarm point) and addressable multi purpose I/O unit (3361) monitored input (Z)95 can be programmed for two-unit-dependent fire alarm activation. (Heat detectors should not and manual call points must not be 2-unit dependent). 94 I.e. the min. / max. sensor values are from the previous day. 95 In this case only one alarm point is recommended on the zone line.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 90 Function: Two or more two-unit-dependent alarm points in the same zone have to be in "fire alarm state" (i.e. over the fire alarm level)96 at the same time to activate fire alarm in EBL128. If only one such alarm point is in "fire alarm state" it is indicated in EBL128 as a co- incidence alarm:  The buzzer sounds 0.8 sec. each 5th sec. (like pre-warning).  In the display is the following text shown: Co-incidence alarm detector ZZ/AA Programmable outputs can be activated by the trigger condition "Two Address Dependent Fire Alarm" but no other outputs will be activated. A co-incidence alarm can be manually reset ("Reset" button on the front) and will be automatically reset 5 min. after it is no longer in "fire alarm state" (i.e. below the fire alarm level). 13.6 Two-zone dependence (co-incidence alarm) This function is valid only for the 4580 board zone line inputs. Two specified zones must be in fire alarm state at the same time to activate fire alarm in EBL128. In some premises two-zone-dependent fire alarm (co-incidence alarm) can be used to avoid unwanted false alarms (nuisance alarms). NOTE! It is not recommended to use heat detectors and/or manual call points in a zone with this function. If only one two-zone-dependent zone is in "fire alarm state" it is indicated in EBL128 as a co-incidence alarm:  The buzzer sounds 0.8 sec. each 5th sec. (like pre-warning).  In the display is the following text shown: Co-incidence alarm zone ZZ Programmable outputs can be activated by the trigger condition "Two Zone Dependent Fire Alarm" but no other outputs will be activated. A co-incidence alarm can be manually reset ("Reset" button on the front) and will be automatically reset 5 min. after it is no longer in "fire alarm state". 13.7 Delayed alarm In some premises delayed fire alarm activation can be used to avoid unwanted false alarms (nuisance alarms). Note, this function is a violation to the EN54-2 standard. This function is valid only for the 4580 board zone line inputs. 96 A not two-unit dependent alarm point would in this state have activated a fire alarm in EBL128.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 91 NOTE! It is not recommended to use heat detectors and/or manual call points in a zone with this function. The delay time can via Win128 be set to 30 or 60 seconds. (The selected time is valid for all zones.) The function "Delayed" is selected in the dialog box for the zone line input respectively. Function: A zone in "fire alarm state"97 will be recorded in EBL128 but a fire alarm will not be activated. When the delay time has run out the zone will be automatically reset and if the zone is still in "fire alarm state", a fire alarm will be activated in EBL128, else nothing will happen until the next time the zone is in "fire alarm state" and a new time delay will start. 13.8 Alarm Verification Facility In some premises AVF can be used to avoid unwanted false alarms (nuisance alarms). Note, this function is a violation to the EN54-2 standard. This function is valid for any zone line input but only in the Australian and New Zealand convention respectively. In these conventions the function "Delayed alarm" (see above) is not valid. The function "Delayed" is selected in the dialog box for the zone line input respectively. Function: A zone in "fire alarm state"98 will be recorded in EBL128 but a fire alarm will not be activated. After 15 seconds the zone will be automatically reset and if the zone comes in "fire alarm state" again within 110 seconds, a fire alarm will be activated in EBL128, else nothing will happen until the next time the zone is in "fire alarm state" and so on. 13.9 Alert Annunciation In some installations the Alert Annunciation function can be used to avoid unwanted false alarms (nuisance alarms) to the fire brigade. Trained personnel on site have to locate the "alarming" detector and take the correct actions depending on if there is a fire or not. Normally analog or addressable smoke detectors and zones with smoke detectors only, should come in question for the AA function. Heat detectors and manual call points should normally not come in question for the AA function. A manual call point can only activate the AA function if there are no other fire alarms activated, i.e. the second fire alarm will turn OFF the AA function and the "Fire brigade 97 A not delayed zone would in this state activate a fire alarm in EBL128. 98 A zone with the AVF not selected would in this state activate a fire alarm in EBL128.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 92 tx" output will be activated. The AA function is normally ON (enabled) during daytime only (i.e. working hours). The time channels 2-4 or the external time channels 5-12 are used to turn ON / OFF (enable / disable) the AA function.99 Figure 20. Alert Annunciation function flow chart. AA Function: Indications, actions, etc. as for a normal fire alarm except that the output for routing equipment (Fire brigade tx) 100 will not be activated directly. The AA alarm has to be acknowledged within an acknowledge time and the AA alarm has to be reset within an investigation time, otherwise the output for routing equipment (Fire brigade tx) will be activated. During the acknowledge & investigation times the output for routing equipment (Fire brigade tx) will be activated if:  fire alarm is activated by another detector not programmed for alert annunciation  fire alarm is activated in another zone  fire alarm is activated by a manual call point  AA alarm is activated by a second detector within the same zone programmed for alert annunciation and "Multiple alarms allowed within same zone" is not selected101 via Win128. Acknowledge and Reset is done on the Alert annunciation unit 1735 / 1736 (or Alert annunciation controller 1740). Programmable output ("Alert Announcement Activated" for indication and programmable inputs ("Alert Announcement Acknowledge" and "Alert Announcement Reset") can also be used. 99 The alert annunciation function ON (enabled) is indicated by the LED "Fire brigade tx delay". Normally is only one time channel used for this function but two or more channels can be used. The AA function can, as an alternative, be continuously "on". NOTE! The AA function can be de- activated (disabled) via menu H2/B10 and will stay so until re-activated (re- enabled) again via menu H2/B10. 100 NOTE! As default it is the relay output "R0" in EBL128. If another output shall be used it has to be programmed as type Routing Equipment (Fire brigade tx) and the trigger condition has to be "Fire brigade tx". 101 Default the Check box is un-marked = Multiple alarms are not allowed within same zone.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 93 The Acknowledge time can be set to 5-60 seconds. The Investigation time can be set to 1-9 minutes. NOTE! According to EN54-2, the total delay of fire alarm routing equipment must not exceed 10 minutes (i.e. Acknowledge time + Investigation time < 10 min.). 13.10 Alarm Acknowledgement Facility (AAF) This function is similar to the "Alert Annunciation Function" (described above) and used on the Australian market only. One AAF zone can be one to five analog smoke detectors (4300 / 4301), one AAF buzzer (e.g. Sounder base 3378) and one AAF Control (AAFC)102. All connected on the COM loop. Sounder Base 3378 Smoke detector (4300, 4301) COM loop AAF Non-latching switch LED PRESS TO ACKNOWLEDGE FALSE ALARM AAFC Figure 21. Alarm Acknowledgement Facility units. Function (see also the flow chart in the following figure): - One of the detectors in an AAF zone reaches its fire alarm level. The AA Process starts and the AAF buzzer sounds. - An Acknowledgement Period starts (AP=10-60 sec. -- programmable). - If it is a false alarm, acknowledge the alarm on the AAFC before the AP is ended. - After acknowledgement an Investigation Period starts and the AAF buzzer is silent (IP=0-3 min. -- programmable). If all the detectors in the AAF zone becomes normal again (i.e. goes below the fire alarm level respectively) during the IP, the AAP ends. If the AP or the IP runs out during the AAP and any detector in the AAF zone still is over its fire alarm level, normal fire alarm(s) will be activated. 102 This unit is available on the Australian market only.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 94 Quiscent state AP timer starts Count down AAFC button pressed? AP time remains? No No Yes Yes IP timer starts Buzzer ON Detector LED ON AAFC LED ON Buzzer OFF All detectors normal? Count down IP time remains? No Yes Yes No Fire Alarm in the C.I.E. Any detector in alarm? Yes No Detector LED OFF AAFC LED OFF AAFC LED OFF Figure 22. Alarm Acknowledgement Facility (AAF) flow chart. During the AAF process, an AAF alarm will be indicated in the c.i.e. display …. …. during the acknowledgement period (AP): AAF zone xx, activated …. during the investigation period (IP): AAF zone xx, investigation in progress If more than one AAF zones have been activated only the first is shown in the display. The detectors in an AAF zone can be one to five and not be programmed as 2-unit-dependent and not be controlled by the Alert

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 95 Annunciation function. Only Analog photo electric smoke detector 4301 and Analog multi detector 4300 can be used for AAF. If the Analog multi detector 4300 is used, it must be programmed as type "Two addresses", so that only the "smoke part" of the detector can be used for AAF. Max. 50 AAF zones can be used. The AAF buzzer (e.g. Sounder base 3378) has to be programmed with the output trigger condition "AAF zone alarm". 13.11 Quiet alarm Quiet alarm is e.g. used in conjunction with the I/O Matrix board 4582103, an application board for fan control and an I/O unit 3361 for fan control. NOTE! These units are available on the Australian market only. Smoke detectors, programmed for quiet alarm, can be used e.g. for controlling fans (stop / start depending on the type of fan). Indications and actions:  In the c.i.e. display: Quiet alarm detector ZZ/AA and a user definable text message (alarm text) if programmed.  LED:s "Fire" in the c.i.e. are blinking (0.4 / 0.4 sec.).  Buzzer in the c.i.e. sounding (0.8 / 5 sec.).  Programmable outputs for quiet alarm, e.g. 3361 outputs controlling supply air fans and standard fans i.e. any output with a control expression containing trigger conditions "Quiet Alarm Zone" or "Quiet Alarm Zone Address". Quiet alarms are non-latching, i.e. they will be automatically reset when the alarm point / zone is no longer above alarm level. NOTE! Quiet alarm can also be programmed for a 3361 unit "zone line input". In such a case only non-latching detectors can be used. 13.12 Fire alarm type A and Fire alarm type B Normally the c.i.e. relay output "R0" is used as an output for Routing equipment (Fire brigade tx). The output shall be programmed (via Win128) as type "Routing equipment" and have the trigger condition "Fire brigade tx". The output will then be activated for fire alarm from any alarm point or zone line input. If the fire alarm routing equipment has provision for transmission of several fire alarm signals and the alarm receiver has provision for reception of several fire alarm signals, a fire alarm type B will indicate that only one detector is activated, which could be a nuisance alarm. 103 See "I/O Matrix board 4582", page 22.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 96 If a fire alarm type A is received, the probability of a real fire is higher than for a fire alarm type B. The alarm receiver can take different actions depending on if it is a fire alarm type A or B. 13.12.1 Fire alarm type B The output will be activated for fire alarm from one analog addressable smoke, heat or multi104 detector only. The output shall be programmed (via Win128) as type "Routing equipment" and have the trigger condition "One detector alarm". 13.12.2 Fire alarm type A The output will be activated for fire alarm from:  Two or more analog addressable smoke, heat or multi detectors.  Any manual call point  Any zone line input  Any programmable input with the trigger condition "General Fire" The output shall be programmed (via Win128) as type "Routing equipment" and have the trigger condition "Multiple detector alarm". 13.13 Disable zones, alarm points, outputs, etc. Temporary disablements are made via the menu H2 sub menus B1-B3 & B7-B9. For more information see the EBL128 Operating Instructions, chapter "Disable or re-enable (H2)". Regular disablements are made via time channels, see chapter "Time Channels", page 119. Disabled alarm points and outputs are indicated by LED "Disablements" and listed in menu H4/U1. Fire alarm, pre-warning and fault signal can not be activated by a disabled alarm point / zone. 13.13.1 Disable zone A whole zone (all addressable alarm points within one zone, including the manual call points) can be disabled via menu H2/B1. This menu is also used to disable a conventional zone, i.e. a 3361 unit's zone line input (Z) and expansion board 4580 zone line inputs. Re-enable via menu H2/B4 or automatic re-enabling at a specified time. 104 NOTE! A multi detector can have one presentation number (Zone- Address) or two presentation numbers depending on how it is programmed via Win128. One presentation number = one detector and two presentation numbers = two detectors regarding fire alarm types A and B.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 97 A time channel can instead be used to disable and re-enable automatically. 13.13.2 Disconnect / Re-connect zone line Disconnect a zone line (on a 4580 board) via menu H5/A2. Disconnected zone line will stay disconnected until re-connected. Re-connect via menu H5/A2. For more information see EBL128 Operating Instructions. 13.13.3 Disable zone / address Individual alarm points can be disabled via menu H2/B2. Re-enable via menu H2/B5 or automatic re-enabling at a specified time. A time channel can instead be used to disable and re-enable automatically. 13.13.4 Disable control output Individual control outputs can be disabled via menu H2/B3. Disabled output will stay in (or return to) the normal condition for the output respectively until re-enabled. Re-enable via menu H2/B6. 13.13.5 Disable / Re-enable all control, exting. and ventilation outputs The control outputs of type "Control (general)", "Fire ventilation" and "Extinguishing system" can be collective disabled via menu H2/B7. Disabled outputs will stay in (or return to) the normal condition for the output respectively until re-enabled. Re-enable via menu H2/B7. 13.13.6 Disable / Re-enable alarm devices The control outputs of type "Alarm device (sounder)" can be collective disabled via menu H2/B8. Disabled outputs will stay in (or return to) the normal condition for the output respectively until re- enabled. Re-enable via menu H2/B8. 13.13.7 Disable outputs for routing equipment The control outputs of type "Routing equipment (Fire brigade tx and Fault tx)" can be collective disabled via menu H2/B9. Disabled outputs will stay in (or return to) the normal condition for the output respectively until re-enabled. Re-enable via menu H2/B9. 13.13.8 Disable interlocking output The control outputs of type "Interlocking output" can be disabled via menu H9/C4, see chapter "Disable interlocking output (H9/C4)", page 79. Re-enable via menu H9/C5.

Panasonic Electric Works Nordic AB

MEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x 98 13.13.9 Disconnect / Re-connect COM loop Disconnect the COM loop via menu H5/A1. Disconnected COM loop will stay disconnected until re-connected. Re-connect via menu H5/A1. For more information see EBL128 Operating Instructions. 13.14 Test mode Up to four zones can be set in Test mode at the same time.105 Alarm points / zones can be tested during the Monthly test (via menu H1) or separately (via menu H7). For more information see the EBL128 Operating Instructions. The LED "Test mode" indicates one or more zones in Test mode. Zones in Test mode are also simultaneously shown in the EBL128 display.106 In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled", i.e. fire alarm will be activated faster than normally. 13.15 Test alarm devices The programmable outputs type "Alarm device" can be collectively activated via menu H8/S3, which make it possible to test the alarm devices. (The test can not be started if a fire alarm already is activated.) When the test starts the alarm devices will be turned "ON" for 5 seconds (±1s), "off" for 25 seconds (±1s), "on" for 5 seconds and so on.107 NOTE! Also disabled (and silenced) alarm devices will be tested. The test will continue for one hour if it is not stopped via menu H8/S3 or if a fire alarm is activated in the system. 13.16 Test of routing equipment Via menu H1 it is possible to test the fault and fire alarm outputs for routing equipment (Fault tx & Fire brigade tx). In menu H1, press "Accept" to start the test. The fault output will be activated108, indicated by LED "Fault tx activated". After 30 seconds will also the fire output be activated, indicated by LED "Fire brigade tx". After additional 30 seconds will the test be ended and the outputs and LEDs will go back to "normal" status. 105 In DBI (Danish) convention, one zone only. 106 Disablements, faults and fire alarms have higher priority, i.e. the presentation of zones in Test mode will be suppressed during such a condition. 107 The output activation will be continuously (steady). For the alarm devices 3377 and 3378, the tone with the highest priority level (and type "alarm device") will be automatically selected. 108 NOTE! The Fault tx output is activated in "normal" state, i.e. it will in this test be de-activated.