Johnson Controls Series 20 J 15 DJ Technical Manual

Text of the manual

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TECHNICAL GUIDE SERIES 20 SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS J15, 18, 20 & 25 DJ 15 & 25 NOMINAL TONS 12.00 EER (15 TONS), 11.70 EER (17.5 TONS), 11.3 EER (20 TONS), 10.5 EER (25 TONS) DESCRIPTION Johnson Controls Series 20 J**DJ units are convertible single package high efficiency rooftops. All models have indepen- dent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. All units include: • Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards • Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats • Scroll compressors • Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic • Permanently lubricated motors • Bottom or side air discharge configuration capability (field convertible) • Belt Drive Blower Motor with high static drive option • Constant supply air volume (CV) with optional variable air volume (VAV) • Manufactured under the quality standards of ISO9001 • Zero-25% fixed air damper with hood • Copper tube/aluminum fin coils • Hinged filter access and tool free latched doors • Hinged tool free blower, blower motor, filters and electri- cal panel access • Rigging holes in base rails for lifting • Single point power connection • Complete factory package - tested, charged and wired • CSA agency approvals on all units WARRANTY • One-year parts warranty • A Five-year parts warranty on the compressors and electric heat elements • Ten-year parts warranty on the gas-fired heat exchangers

Johnson Controls Unitary Products

TABLE OF CONTENTS DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 7 GUIDE SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . 37 LIST OF FIGURES Fig. # Pg. # 1 UNIT CUTAWAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 ALTITUDE/TEMPERATURE CONVERSION FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 3 TYPICAL J**DJ FIELD WIRING DIAGRAM . . . . . . . . 29 4 FRONT VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . . 30 5 REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . . . 31 6 UNIT DIMENSIONS J15, 18, 20 & 25 DJ (RAINHOOD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 7 UNIT CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . 33 8 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . . 33 9 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 34 10 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . 35 11 ROOF CURB DUCT OPENINGS DIMENSION . . . . . 35 12 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . . 35 13 TYPICAL UNIT WIRING DIAGRAM . . . . . . . . . . . . . . 36 LIST OF TABLES Tbl. # Pg. # 1 SOUND POWER RATING. . . . . . . . . . . . . . . . . . . . . . . 9 2 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . . . . 9 3 GAS HEAT RATIINGS. . . . . . . . . . . . . . . . . . . . . . . . . . 9 4 COOLING CAPACITIES FOR J15DJ . . . . . . . . . . . . . 10 5 COOLING CAPACITIES FOR J18DJ . . . . . . . . . . . . . 11 6 COOLING CAPACITIES FOR J20DJ . . . . . . . . . . . . . 12 7 COOLING CAPACITIES FOR J25DJ . . . . . . . . . . . . . 13 Tbl. # Pg. # 8 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . 14 9 SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY 180 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 10 SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY 210 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 11 SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY 240 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 12 SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT 180 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 13 SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT 210 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 14 SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT 240 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 15 SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT 300 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 16 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 23 17 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 23 18 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . 23 19 J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET. . . . . . . . . . . . . . . . . . . . . . 24 20 J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET. . . . . . . . . . . . . . . . . . . . . . 26 21 J**DJ VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . 28 22 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 23 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . . . 29 24 ELECTRIC HEAT CORRECTION FACTORS. . . . . . . 29 25 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . 30 26 MINIMUM CLEARANCES. . . . . . . . . . . . . . . . . . . . . . 32 27 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 34

Johnson Controls Unitary Products

3 PRODUCT NOMENCLATURE D J J15 N24 A 2 A AA 1 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category A = Std. Drive Airflow B = Std. Drive/Single Input Econo. C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only) D = Std. Drive/Motorized Damper E = Std. Drive/Motorized Damper/Barometric Relief J = Std. Drive/Single Input Econo./Barometric Relief N = Hi Static Drive P = Hi Static Drive/Single Input Econo. Q = Hi Static Drive/Single Input Econo./Power Exhaust (Downflow Only) R = Hi Static Drive/Motorized Damper K = Hi Static Drive/Motorized Damper/Barometric Relief S = Hi Static Drive/Single Input Econo./Barometric Relief 1 = First Generation Product Generation 2 = Second Generation C00 = Cooling Only. No field installed electric heat Heat Type and Nominal Heat Capacity N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW Gas Heat Options Electric Heat Options J15 = 15 Ton Nominal Cooling Capacity J18 = 17.5 Ton J20 = 20 Ton J25 = 25 Ton Product Identifier J = 11.0+ EER A/C Voltage 2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60 Product Style A = Style A AA = None Standard Cabinet AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils BA = Hinged Filter Door & Tool Free Access Panels Additional Options Hinged Filter Door & Tool Free Access Cabinet BB = Phase Monitor, Hinged Filter Door & Tool Free Access Panels BC = Coil Guard, Hinged Filter Door & Tool Free Access Panels BD = Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels BE = Phase Monitor & Coil Guard, Hinged Filter Door & Tool Free Access Panels BF = Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels BG = Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels BH = Phase Monitor, Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels 15-25 Ton Series 20 Model Number Nomenclature ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be located in digits 15-18. A = No Options Installed Installation Options B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet Options N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5 SS Drain Pan Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed. Johnson Light Commercial Controls System (LCCS) Rtu Controller Johnson UNT 1126 Controller (N2 protocol), DFS, APS 2" Pleated filters 4" Pleated filters BAS Ready Economizer (2-10 V.D.C. Actuator without a controller) Double Wall Construction Hot Gas Bypass (Standard on VAV, Optional on CV) Variable Air Volume, VFD Variable Air Volume, VFD and Manual Bypass Variable Air Volume, VFD (BAS ready - for customer provided VFD controller) Variable Air Volume, VFD and Manual Bypass (BAS ready) Variable Air Volume, VFD Ready (for customer provided, field installed drive) For valid combinations of the above; see the equipment price pages or the Unitary Sales Tool program; all combinations are not available

Johnson Controls Unitary Products

FEATURES All Series 20 J**DJ models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All models are available with these “factory mounted” outdoor air damper options: • Single enthalpy economizer with or without power exhaust • BAS-ready economizer with or without power exhaust • Motorized outdoor air damper • Barometric Relief Damper A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an econo- mizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. A variable air vol- ume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor. All compressors include scroll compressors and internal pres- sure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications. • Advanced Controls - Unit control boards have stan- dardized a number of features previously available only as options or by utilizing additional controls. • Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis- tance. Optionally, the control board can be pro- grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available. • Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button. • Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board. • Fan Delays - Fan on and fan off delays are fully pro- grammable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat. • Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit con- trol board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. • Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor. • On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures. All models are CSA approved. • Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty. • Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger

Johnson Controls Unitary Products

5 with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit. • Electric Heat Operation - All electric heat models (fac- tory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to pro- vide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches. The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit. FACTORY-INSTALLED OPTIONS • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. • BAS-READY ECONOMIZER - Includes a slide-in / plug- in damper assembly with fully modulating spring-return motor actuator with zero to 95-degree rotation capable of introducing up to 100% outdoor air with nominal 1% leak- age type dampers. Actuator requires 2-10 VDC input from an external source, such as a field-installed or factory-installed BAS controller. BAS-ready actuators have an adjustable auxil- iary end-switch for optional power exhaust control. For units with optional VAV control, a factory-installed, dry bulb sensor determines if outdoor air temperature is low enough to provide free-cooling operation. (Field- installed humidity sensors for either outdoor air or out- door & return air streams are available for single enthalpy and differential enthalpy configurations, respec- tively). The rainhood is painted to match the basic unit and must be field-assembled before installing. FIGURE 1 - UNIT CUTAWAY UNIT

Johnson Controls Unitary Products

• POWER EXHAUST - Our economizer options are avail- able with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer opera- tion. BAS-ready economizer actuators have an adjust- able auxiliary end-switch to provide a range of damper positions available to energize power exhaust. The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field. The power exhaust option can only be used on bot- tom duct configurations. • MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is oper- ating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. • BAROMETRIC RELIEF DAMPER - This damper option can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. • PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that utilizes Technicoat 10-1" processes. Coating is applied by total immersion of the complete coil for maximum protection. • ELECTRIC HEATERS wired for single point power sup- ply. These nickel chromium heater elements are pro- vided with limit and automatic reset capability to prevent operation at excessive temperatures. • VARIABLE AIR VOLUME (VAV) - A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A pressure transducer and VAV control board are mounted inside the control box. The drive comes completely wired and pre-programmed from the factory. An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and oper- ate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes. Due to space limitations, VAV is not available with any of the factory-installed BAS options described below, but is available with ‘BAS-ready’ models. Terminal blocks are provided in the control box for field wiring of the cus- tomer-installed BAS. A ‘VFD-ready’ option provides the provisions for a cus- tomer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depend- ing on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are as follows: For 5-hp motor applications ........................13” H x 6” W x 7” D For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to exces- sive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclo- sure rated for outside installation to safeguard against moisture, dust and excessive heat. A terminal block located in the control box is provided for field connection of the VFD controls. • HOT GAS BYPASS - To allow for low cooling load oper- ation, a direct-acting pressure-modulating bypass control valve installed on the system #1 discharge line is used to divert high temperature, high pressure refrigerant around the TXV in order to maintain a desired minimum evapo- rator pressure. HGBP is standard on all units with VAV and optional with CV units. • FILTER OPTIONS - Standard units are shipped with 2” throw-away filters installed. 2” pleated and 4” pleated fil- ters are offered as a factory installed option. • CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or you may order the unit with a “non-powered” conve- nience outlet that can be wired in the field. • DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only. • DOUBLE WALL CONSTRUCTION - Optional double wall construction is available to provide smooth inner surfaces for easy and effective cleaning to reduce risk of dirt and bacterial accumulation. Fiberglass insulation is sandwiched between heavy gauge steel sheets to form a durable, rigid casing to withstand higher working pres- sures and impact forces. The heavy-duty construction provides excellent acoustic and thermal insulation and eliminates erosion of insulation material and contamina- tion of the air stream.

Johnson Controls Unitary Products

7 • SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. • STAINLESS STEEL HEAT EXCHANGER - For applica- tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly. • STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments. • PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition. • HIGH STATIC DRIVE - Includes a belt and blower pulley upgrade to enhance blower performance. • DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory. • HINGED FILTER DOOR/”TOOL FREE” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance. NOTE:Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed for tool free operation. • HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR, FILTER AND ELECTRIC ACCESS PANELS - This option allows for complete hinged and tool free access to the unit's blower, blower motor, filters and electrical panel sections. CONTROL OPTIONS • Johnson Light Commercial System (LCCS) - Provides rooftop system integration for LCCS single zone, change-over bypass and VAV systems. • Johnson UNT 1126 Rooftop Controller - N2 protocol with air proving and dirty filter sensors. Hardware con- tains generic application logic; field engineering and/or modification may be required. FIELD-INSTALLED ACCESSORIES • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. • MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. • ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports. • HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. • PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane. • HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti- tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit. • SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust. • BAROMETRIC RELIEF DAMPER - This damper acces- sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This Factory installed smoke detectors in the return air may be subjected to freezing temperatures during “off” times due to outside air infiltration. These smoke detectors have an operation limit of 32°F to 131°F. Smoke detectors installed in areas that could be outside those limitations will have to be moved to prevent having false alarms.

Johnson Controls Unitary Products

accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. • HIGH STATIC DRIVE - A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirements. • ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy. • BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work. • FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. • WOOD SKID - Allows unit to be handled with 90” forks. • CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits. • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. • PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

Johnson Controls Unitary Products

9 NOTE: All gas units are two-stage heating. First stage is 50% of total. S.S.E. = Steady State Efficiency (80%) - output divided by input. TABLE 1: SOUND POWER RATING1 UNIT SIZE CFM ESP BLOWER SOUND POWER (db 10-12 Watts) Octave Band Centerline Frequency (Hz) SWL dB(A) dB(A) @ 10Ft.2 IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000 J15DJ 6,000 1.00 1,080 4.60 99 99 89 82 84 77 72 67 89 56 J18, 20 DJ 8,000 1.00 1,120 6.65 102 102 92 85 87 80 75 70 92 59 J25DJ 10,000 1.30 1160 12.5 108 108 98 91 93 86 81 76 98 65 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower. TABLE 2: CAPACITY RATINGS - (ARI 360)1 1. Certified in accordance with the Unitary Large Equip- ment certification program which is based on ARI Stan- dard 340/360. MODEL MBH EER2 2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt). IPLV3 3. IPLV = Integrated Part Load Value. COOLING ONLY J15DJC/E00 178 12.0 12.5 J18DJC/E00 208 11.7 12.7 J20DJC/E00 230 11.3 12.0 J25DJC/E00 292 10.5 11.2 COOLING WITH GAS HEAT J15DJN/S 178 12.0 12.5 J18DJN/S 208 11.7 12.7 J20DJN/S 230 11.3 12.0 J25DJN/S 292 10.5 11.2 COOLING WITH ELECTRIC HEAT J15DJE18 178 12.0 12.5 J15DJE36 178 12.0 12.5 J15DJE54 176 11.8 12.2 J15DJE72 176 11.8 12.2 J18DJE18 208 11.7 12.7 J18DJE36 208 11.7 12.7 J18DJE54 206 11.5 12.4 J18DJE72 206 11.5 12.4 J20DJE18 230 11.3 12.0 J20DJE36 230 11.3 12.0 J20DJE54 228 11.1 11.7 J20DJE72 228 11.1 11.7 J25DJE18 292 10.5 11.2 J25DJE36 292 10.5 11.2 J25DJE54 290 10.3 11.0 J25DJE72 290 10.3 11.0 TABLE 3: GAS HEAT RATIINGS MODEL MBH INPUT MBH OUTPUT J15DJN/S24 300 240 J15DJN/S32 400 320 J18DJN/S24 300 240 J18DJN/S32 400 320 J20DJN/S24 300 240 J20DJN/S32 400 320 J25DJN/S24 300 240 J25DJN/S32 400 320 For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board. If there are VAV boxes present in the duct sys- tem, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across elec- tric heating elements or gas heat exchanger tubes.

Johnson Controls Unitary Products

TABLE 4: COOLING CAPACITIES FOR J15DJ Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68 4500 72 206.8 11.94 119.7 106.8 94.0 81.2 68.3 - - 196.1 12.98 115.7 102.9 90.1 77.3 64.4 - - 67 187.4 11.64 148.6 135.7 122.9 110.1 97.2 84.4 71.6 178.1 12.70 144.6 131.8 119.0 106.1 93.3 80.5 67.6 62 169.3 11.37 169.3 162.1 149.3 136.5 123.6 110.8 98.0 161.7 12.49 161.7 157.0 144.2 131.4 118.5 105.7 92.9 57 166.8 11.36 166.8 164.1 151.3 138.5 125.6 112.8 100.0 163.4 12.53 163.4 160.3 147.5 134.7 121.8 109.0 96.2 5250 72 212.8 12.00 132.2 117.0 101.8 86.7 71.5 - - 201.2 13.06 127.9 112.7 97.6 82.4 67.2 - - 67 192.8 11.70 163.5 148.3 133.2 118.0 102.8 87.7 72.5 182.8 12.78 159.2 144.0 128.8 113.7 98.5 83.3 68.2 62 174.2 11.43 174.2 170.7 161.7 146.6 131.4 116.3 101.1 166.0 12.57 166.0 163.6 156.2 141.0 125.9 110.7 95.5 57 171.6 11.42 171.6 170.3 163.9 148.8 133.6 118.4 103.3 167.7 12.61 167.7 166.2 159.8 144.6 129.4 114.3 99.1 6000 72 218.9 12.06 144.7 127.2 109.7 92.2 74.7 - - 206.4 13.14 140.0 122.5 105.1 87.6 70.1 - - 67 198.3 11.76 178.4 160.9 143.4 125.9 108.4 90.9 73.4 187.5 12.86 173.7 156.2 138.7 121.2 103.7 86.2 68.7 62 179.2 11.49 179.2 179.2 174.2 156.7 139.2 121.7 104.2 170.2 12.65 170.2 170.2 168.2 150.7 133.2 115.7 98.2 57 176.5 11.48 176.5 176.5 176.5 159.0 141.5 124.0 106.6 172.0 12.69 172.0 172.0 172.0 154.5 137.0 119.5 102.0 6600 72 224.3 12.14 156.2 136.7 117.2 97.8 78.3 - - 211.4 13.22 150.4 131.0 111.5 92.0 72.5 - - 67 203.2 11.83 192.2 172.8 153.3 133.8 114.3 94.9 75.4 192.0 12.93 185.1 166.7 147.2 127.7 108.2 88.8 69.3 62 183.6 11.57 183.6 183.6 181.1 161.7 142.2 122.7 103.2 174.3 12.72 174.3 174.3 173.3 153.8 134.4 114.9 95.4 57 180.9 11.56 180.9 180.9 180.9 161.4 141.9 122.5 103.0 176.2 12.76 176.2 176.2 176.2 156.7 137.2 117.7 98.3 7200 72 229.7 12.22 167.7 146.3 124.8 103.3 81.9 - - 216.4 13.30 160.8 139.4 117.9 96.4 75.0 - - 67 208.1 11.91 206.1 184.6 163.2 141.7 120.3 98.8 77.3 196.6 13.01 196.6 177.1 155.7 134.2 112.8 91.3 69.8 62 188.1 11.64 188.1 188.1 188.1 166.6 145.1 123.7 102.2 178.5 12.80 178.5 178.5 178.5 157.0 135.6 114.1 92.6 57 185.3 11.63 185.3 185.3 185.3 163.8 142.3 120.9 99.4 180.4 12.84 180.4 180.4 180.4 158.9 137.4 116.0 94.5 105°F 115°F 4500 72 184.9 14.46 111.3 98.5 85.6 72.8 60.0 - - 173.7 15.93 106.8 94.0 81.2 68.3 55.5 - - 67 167.9 14.19 140.0 127.2 114.3 101.5 88.7 75.9 63.0 157.7 15.68 135.4 122.6 109.7 96.9 84.1 71.2 58.4 62 152.9 14.00 152.9 149.0 136.2 123.4 110.5 97.7 84.9 144.1 15.50 144.1 141.0 128.2 115.4 102.5 89.7 76.9 57 155.3 14.03 155.3 152.1 139.3 126.5 113.6 100.8 88.0 147.3 15.53 147.3 143.9 131.1 118.3 105.4 92.6 79.8 5250 72 189.7 14.51 123.4 108.2 93.1 77.9 62.7 - - 178.3 15.95 118.9 103.7 88.6 73.4 58.2 - - 67 172.3 14.24 154.6 139.5 124.3 109.1 94.0 78.8 63.6 161.8 15.70 150.1 134.9 119.8 104.6 89.4 74.3 59.1 62 156.9 14.05 156.9 155.0 148.1 132.9 117.7 102.6 87.4 147.8 15.52 147.8 146.3 139.9 124.8 109.6 94.4 79.3 57 159.4 14.08 159.4 157.8 151.4 136.2 121.1 105.9 90.8 151.2 15.55 151.2 149.5 143.1 127.9 112.7 97.6 82.4 6000 72 194.6 14.56 135.5 118.0 100.5 83.0 65.5 - - 182.8 15.97 131.0 113.5 96.0 78.5 61.0 - - 67 176.7 14.29 169.2 151.7 134.2 116.7 99.3 81.8 64.3 166.0 15.72 164.8 147.3 129.8 112.3 94.8 77.3 59.8 62 160.9 14.09 160.9 160.9 159.9 142.4 124.9 107.4 89.9 151.6 15.54 151.6 151.6 151.6 134.1 116.6 99.1 81.6 57 163.5 14.13 163.5 163.5 163.5 146.0 128.5 111.0 93.5 155.0 15.56 155.0 155.0 155.0 137.5 120.0 102.6 85.1 6600 72 199.3 14.65 145.7 126.3 106.8 87.3 67.8 - - 187.1 16.07 141.1 121.6 102.1 82.6 63.1 - - 67 180.9 14.38 177.2 162.1 142.6 123.1 103.7 84.2 64.7 169.9 15.82 169.3 157.5 138.1 118.6 99.1 79.6 60.1 62 164.8 14.18 164.8 164.8 164.3 144.8 125.3 105.8 86.3 155.2 15.64 155.2 155.2 155.2 135.7 116.2 96.8 77.3 57 167.4 14.21 167.4 167.4 167.4 148.0 128.5 109.0 89.5 158.7 15.66 158.7 158.7 158.7 139.2 119.7 100.3 80.8 7200 72 203.9 14.74 156.0 134.5 113.1 91.6 70.1 - - 191.5 16.18 151.2 129.7 108.2 86.8 65.3 - - 67 185.2 14.47 185.2 172.5 151.0 129.5 108.1 86.6 65.2 173.8 15.93 173.8 167.8 146.3 124.9 103.4 81.9 60.5 62 168.6 14.27 168.6 168.6 168.6 147.2 125.7 104.2 82.8 158.8 15.74 158.8 158.8 158.8 137.3 115.9 94.4 72.9 57 171.4 14.30 171.4 171.4 171.4 149.9 128.4 107.0 85.5 162.4 15.77 162.4 162.4 162.4 140.9 119.4 98.0 76.5 125°F 4500 72 162.5 17.41 102.4 89.5 76.7 63.9 51.0 - - 67 147.5 17.18 130.8 118.0 105.1 92.3 79.5 66.6 53.8 62 135.2 17.00 135.2 133.0 120.2 107.4 94.5 81.7 68.9 57 139.2 17.02 139.2 135.7 122.9 110.1 97.2 84.4 71.6 5250 72 166.8 17.40 114.4 99.2 84.1 68.9 53.7 - - 67 151.3 17.17 145.5 130.4 115.2 100.1 84.9 69.7 54.6 62 138.8 16.99 138.8 137.7 131.8 116.6 101.5 86.3 71.1 57 142.9 17.01 142.9 141.1 134.7 119.6 104.4 89.2 74.1 6000 72 171.0 17.38 126.4 108.9 91.4 73.9 56.5 - - 67 155.2 17.16 155.2 142.8 125.3 107.8 90.3 72.8 55.3 62 142.3 16.98 142.3 142.3 142.3 125.9 108.4 90.9 73.4 57 146.6 17.00 146.6 146.6 146.6 129.1 111.6 94.1 76.6 6600 72 175.0 17.50 136.4 116.9 97.4 77.9 58.5 - - 67 158.8 17.27 158.8 153.0 133.5 114.0 94.5 75.0 55.6 62 145.6 17.10 145.6 145.6 145.6 126.7 107.2 87.7 68.2 57 150.0 17.12 150.0 150.0 150.0 130.5 111.0 91.5 72.0 7200 72 179.0 17.62 146.3 124.9 103.4 81.9 60.5 - - 67 162.4 17.38 162.4 162.4 141.7 120.2 98.7 77.3 55.8 62 148.9 17.21 148.9 148.9 148.9 127.5 106.0 84.5 63.1 57 153.4 17.23 153.4 153.4 153.4 131.9 110.4 89.0 67.5 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

11 TABLE 5: COOLING CAPACITIES FOR J18DJ Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68 6000 72 238.9 14.24 142.6 125.5 108.4 91.3 74.2 - - 222.9 15.81 136.5 119.4 102.3 85.2 68.1 - - 67 221.2 13.83 178.6 161.5 144.4 127.3 110.2 93.1 76.0 207.1 15.38 172.8 155.7 138.6 121.5 104.4 87.2 70.1 62 207.4 13.57 207.4 192.8 175.7 158.5 141.4 124.3 107.2 197.6 15.09 197.6 181.0 163.8 146.7 129.6 112.5 95.4 57 197.6 13.52 197.6 195.7 178.6 161.4 144.3 127.2 110.1 186.0 15.06 186.0 181.8 164.7 147.6 130.5 113.4 96.3 6500 72 246.1 14.36 154.5 135.8 117.0 98.3 79.5 - - 231.8 15.91 149.7 130.9 112.2 93.4 74.6 - - 67 227.9 13.95 193.5 174.7 156.0 137.2 118.4 99.7 80.9 215.4 15.48 189.4 170.7 151.9 133.2 114.4 95.6 76.9 62 213.7 13.69 213.7 206.4 189.7 170.9 152.2 133.4 114.6 205.5 15.19 205.5 197.1 179.6 160.9 142.1 123.4 104.6 57 203.6 13.64 203.6 202.6 192.8 174.1 155.3 136.5 117.8 193.5 15.15 193.5 191.3 180.6 161.8 143.1 124.3 105.5 7000 72 253.4 14.48 166.5 146.1 125.7 105.3 84.9 - - 240.7 16.00 162.8 142.4 122.0 101.6 81.2 - - 67 234.6 14.06 208.3 187.9 167.5 147.1 126.7 106.3 85.9 223.6 15.57 206.1 185.7 165.3 144.8 124.4 104.0 83.6 62 220.0 13.80 220.0 220.0 203.7 183.3 162.9 142.5 122.1 213.3 15.28 213.3 213.3 195.4 175.0 154.6 134.2 113.8 57 209.6 13.75 209.6 209.6 207.1 186.7 166.2 145.8 125.4 200.9 15.24 200.9 200.9 196.4 176.0 155.6 135.2 114.8 7875 72 258.4 14.56 180.9 157.6 134.4 111.2 87.9 - - 243.3 16.09 176.8 153.6 130.3 107.1 83.8 - - 67 239.3 14.14 225.6 202.4 179.1 155.9 132.6 109.4 86.1 226.0 15.65 217.3 199.8 176.5 153.3 130.0 106.8 83.5 62 224.4 13.88 224.4 224.4 216.2 193.0 169.7 146.5 123.2 215.6 15.36 215.6 215.6 206.7 183.4 160.2 136.9 113.7 57 213.8 13.82 213.8 213.8 212.5 189.2 166.0 142.8 119.5 203.0 15.32 203.0 203.0 200.8 177.6 154.3 131.1 107.8 8750 72 263.5 14.63 195.3 169.2 143.1 117.0 91.0 - - 245.9 16.17 190.8 164.7 138.7 112.6 86.5 - - 67 243.9 14.21 242.9 216.8 190.7 164.7 138.6 112.5 86.4 228.4 15.73 228.4 213.9 187.8 161.7 135.6 109.5 83.5 62 228.7 13.95 228.7 228.7 228.7 202.6 176.6 150.5 124.4 217.9 15.43 217.9 217.9 217.9 191.8 165.8 139.7 113.6 57 217.9 13.90 217.9 217.9 217.9 191.8 165.8 139.7 113.6 205.2 15.40 205.2 205.2 205.2 179.1 153.0 126.9 100.9 105°F 115°F 6000 72 210.2 17.65 131.0 113.9 96.8 79.7 62.6 - - 197.6 19.49 125.5 108.3 91.2 74.1 57.0 - - 67 195.1 17.21 167.5 150.4 133.3 116.2 99.1 82.0 64.9 183.1 19.04 162.2 145.1 128.0 110.9 93.8 76.7 59.6 62 186.9 17.01 186.9 170.6 153.5 136.4 119.3 102.2 85.1 176.3 18.92 176.3 160.2 143.1 126.0 108.9 91.8 74.7 57 174.4 16.80 174.4 172.3 155.2 138.1 121.0 103.9 86.8 162.8 18.55 162.8 162.8 145.7 128.6 111.5 94.4 77.3 6500 72 218.3 17.77 143.8 125.0 106.3 87.5 68.7 - - 204.8 19.63 137.9 119.1 100.3 81.6 62.8 - - 67 202.6 17.33 183.9 165.1 146.4 127.6 108.8 90.1 71.3 189.9 19.18 178.3 159.5 140.8 122.0 103.3 84.5 65.8 62 194.1 17.12 194.1 186.0 168.5 149.8 131.0 112.2 93.5 182.8 19.06 182.8 174.8 157.4 138.6 119.9 101.1 82.4 57 181.1 16.92 181.1 180.1 170.4 151.7 132.9 114.1 95.4 168.8 18.69 168.8 168.8 160.3 141.5 122.8 104.0 85.2 7000 72 226.4 17.89 156.6 136.2 115.7 95.3 74.9 - - 212.1 19.77 150.3 129.9 109.5 89.0 68.6 - - 67 210.1 17.45 200.2 179.8 159.4 139.0 118.6 98.2 77.8 196.6 19.32 194.4 174.0 153.6 133.2 112.7 92.3 71.9 62 201.3 17.24 201.3 201.3 183.6 163.1 142.7 122.3 101.9 189.3 19.20 189.3 189.3 171.7 151.3 130.9 110.5 90.0 57 187.8 17.03 187.8 187.8 185.6 165.2 144.8 124.4 104.0 174.8 18.82 174.8 174.8 174.8 154.4 134.0 113.6 93.2 7875 72 228.5 17.97 171.3 148.0 124.8 101.5 78.3 - - 213.7 19.85 165.7 142.5 119.2 96.0 72.7 - - 67 212.1 17.53 207.1 193.3 171.9 148.6 125.4 102.2 78.9 198.1 19.40 197.0 186.8 167.3 144.0 120.8 97.5 74.3 62 203.2 17.32 203.2 203.2 194.3 171.0 147.8 124.5 101.3 190.7 19.28 190.7 190.7 181.9 158.6 135.4 112.1 88.9 57 189.6 17.11 189.6 189.6 188.5 165.2 142.0 118.7 95.5 176.1 18.90 176.1 176.1 176.1 152.9 129.6 106.4 83.1 8750 72 230.6 18.05 186.0 159.9 133.8 107.7 81.7 - - 215.2 19.94 181.1 155.1 129.0 102.9 76.8 - - 67 214.0 17.61 214.0 206.7 184.4 158.3 132.2 106.1 80.0 199.5 19.48 199.5 199.5 181.0 154.9 128.8 102.7 76.6 62 205.0 17.40 205.0 205.0 205.0 178.9 152.8 126.8 100.7 192.1 19.36 192.1 192.1 192.1 166.0 139.9 113.8 87.8 57 191.3 17.19 191.3 191.3 191.3 165.2 139.1 113.0 87.0 177.4 18.98 177.4 177.4 177.4 151.3 125.2 99.1 73.1 125°F 6000 72 184.9 21.33 119.9 102.8 85.7 68.6 51.5 - - 67 171.1 20.87 156.9 139.8 122.7 105.6 88.5 71.4 54.3 62 165.7 20.84 165.7 149.9 132.7 115.6 98.5 81.4 64.3 57 151.2 20.30 151.2 151.2 136.2 119.1 102.0 84.9 67.8 6500 72 191.4 21.49 132.0 113.2 94.4 75.7 56.9 - - 67 177.1 21.03 172.7 154.0 135.2 116.5 97.7 79.0 60.2 62 171.5 21.00 171.5 163.6 146.3 127.5 108.8 90.0 71.3 57 156.5 20.46 156.5 156.5 150.1 131.4 112.6 93.8 75.1 7000 72 197.8 21.65 144.0 123.6 103.2 82.8 62.3 - - 67 183.1 21.19 183.1 168.1 147.7 127.3 106.9 86.5 66.1 62 177.3 21.16 177.3 177.3 159.8 139.4 119.0 98.6 78.2 57 161.8 20.61 161.8 161.8 161.8 143.6 123.2 102.8 82.4 7875 72 198.9 21.74 160.2 136.9 113.7 90.4 67.2 - - 67 184.1 21.27 184.1 180.2 162.6 139.4 116.2 92.9 69.7 62 178.2 21.24 178.2 178.2 169.5 146.3 123.0 99.8 76.5 57 162.6 20.69 162.6 162.6 162.6 140.5 117.3 94.0 70.8 8750 72 199.9 21.82 176.3 150.2 124.2 98.1 72.0 - - 67 185.1 21.35 185.1 185.1 177.6 151.5 125.4 99.3 73.2 62 179.2 21.32 179.2 179.2 179.2 153.1 127.0 100.9 74.8 57 163.5 20.77 163.5 163.5 163.5 137.4 111.3 85.2 59.2 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

TABLE 6: COOLING CAPACITIES FOR J20DJ Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68 6000 72 273.1 16.90 149.8 132.7 115.6 98.5 81.4 - - 257.3 18.45 150.2 133.1 116.0 98.9 81.8 - - 67 248.6 16.43 197.6 180.5 163.4 146.3 129.1 112.0 94.9 237.3 17.83 192.3 175.1 158.0 140.9 123.8 106.7 89.6 62 231.2 16.44 227.9 210.8 193.7 176.6 159.5 142.4 125.3 215.2 17.64 215.2 200.8 183.7 166.6 149.5 132.4 115.3 57 216.6 15.98 216.6 210.2 193.1 176.0 158.9 141.8 124.7 221.2 17.98 221.2 213.2 196.1 179.0 161.8 144.7 127.6 7000 72 278.7 16.96 165.8 145.6 125.4 105.1 84.9 - - 264.7 18.51 167.2 146.9 126.7 106.5 86.3 - - 67 253.8 16.49 217.5 197.3 177.1 156.9 136.7 116.5 96.2 244.2 17.89 213.1 192.9 172.7 152.4 132.2 112.0 91.8 62 236.0 16.50 234.4 225.8 210.0 189.8 169.6 149.4 129.2 221.5 17.70 221.5 214.3 200.7 180.5 160.3 140.0 119.8 57 221.1 16.04 221.1 217.9 209.3 189.1 168.9 148.7 128.5 227.6 18.04 227.6 223.6 214.2 194.0 173.8 153.5 133.3 8000 72 284.4 17.02 181.8 158.4 135.1 111.8 88.4 - - 272.2 18.58 184.1 160.8 137.4 114.1 90.8 - - 67 259.0 16.55 237.5 214.2 190.9 167.5 144.2 120.9 97.6 251.0 17.95 233.9 210.6 187.3 164.0 140.6 117.3 94.0 62 240.8 16.56 240.8 240.8 226.3 203.0 179.7 156.4 133.0 227.7 17.76 227.7 227.7 217.7 194.4 171.0 147.7 124.4 57 225.6 16.10 225.6 225.6 225.6 202.3 178.9 155.6 132.3 234.0 18.10 234.0 234.0 232.3 209.0 185.7 162.4 139.0 8700 72 291.0 17.43 193.1 167.5 141.8 116.1 90.4 - - 277.5 18.98 195.6 169.9 144.2 118.5 92.9 - - 67 265.0 16.95 251.7 226.0 200.3 174.7 149.0 123.3 97.6 256.0 18.33 247.4 222.2 196.5 170.8 145.2 119.5 93.8 62 246.4 16.96 246.4 246.4 237.6 211.9 186.2 160.5 134.9 232.2 18.14 232.2 232.2 227.2 201.5 175.8 150.1 124.5 57 230.8 16.49 230.8 230.8 230.8 205.2 179.5 153.8 128.1 238.6 18.50 238.6 238.6 237.7 212.1 186.4 160.7 135.0 9400 72 297.7 17.84 204.5 176.5 148.5 120.5 92.4 - - 282.9 19.38 207.0 179.0 151.0 123.0 94.9 - - 67 271.0 17.35 265.8 237.8 209.8 181.8 153.7 125.7 97.7 260.9 18.72 260.9 233.7 205.7 177.7 149.7 121.7 93.6 62 252.0 17.36 252.0 252.0 248.8 220.7 192.7 164.7 136.7 236.6 18.53 236.6 236.6 236.6 208.6 180.6 152.6 124.6 57 236.1 16.88 236.1 236.1 236.1 208.1 180.1 152.0 124.0 243.2 18.89 243.2 243.2 243.2 215.1 187.1 159.1 131.1 105°F 115°F 6000 72 244.1 20.09 146.5 129.4 112.3 95.2 78.1 - - 230.8 21.72 142.8 125.7 108.6 91.5 74.4 - - 67 225.3 19.63 186.7 169.6 152.5 135.4 118.3 101.2 84.1 213.4 21.43 181.2 164.1 147.0 129.9 112.8 95.7 78.6 62 202.7 19.37 202.7 194.9 177.7 160.6 143.5 126.4 109.3 190.2 21.09 190.2 188.9 171.8 154.7 137.6 120.5 103.4 57 211.7 19.63 211.7 205.7 188.6 171.5 154.4 137.3 120.2 202.2 21.28 202.2 198.2 181.1 164.0 146.9 129.8 112.7 7000 72 250.6 20.15 162.5 142.2 122.0 101.8 81.6 - - 236.4 21.79 157.8 137.5 117.3 97.1 76.9 - - 67 231.3 19.69 206.2 185.9 165.7 145.5 125.3 105.1 84.9 218.5 21.50 199.2 179.0 158.8 138.6 118.4 98.1 77.9 62 208.1 19.43 208.1 204.2 193.1 172.9 152.7 132.5 112.3 194.8 21.16 194.8 194.1 185.6 165.4 145.1 124.9 104.7 57 217.3 19.70 217.3 214.3 204.9 184.7 164.5 144.3 124.1 207.0 21.35 207.0 205.1 195.7 175.4 155.2 135.0 114.8 8000 72 257.0 20.22 178.4 155.1 131.7 108.4 85.1 - - 241.9 21.87 172.7 149.4 126.0 102.7 79.4 - - 67 237.3 19.76 225.6 202.3 178.9 155.6 132.3 109.0 85.6 223.6 21.58 217.3 193.9 170.6 147.3 123.9 100.6 77.3 62 213.5 19.50 213.5 213.5 208.5 185.2 161.9 138.5 115.2 199.4 21.24 199.4 199.4 199.4 176.0 152.7 129.4 106.1 57 222.9 19.77 222.9 222.9 221.3 197.9 174.6 151.3 128.0 211.9 21.43 211.9 211.9 210.2 186.9 163.5 140.2 116.9 8700 72 264.1 20.56 191.3 165.6 139.9 114.3 88.6 - - 250.6 22.15 187.0 161.3 135.6 110.0 84.3 - - 67 243.8 20.09 238.0 215.7 190.0 164.4 138.7 113.0 87.3 231.7 21.85 228.5 209.3 183.6 157.9 132.2 106.6 80.9 62 219.4 19.83 219.4 219.4 216.9 191.2 165.5 139.8 114.2 206.6 21.51 206.6 206.6 206.6 180.9 155.2 129.5 103.9 57 229.0 20.10 229.0 229.0 228.2 202.5 176.9 151.2 125.5 219.5 21.70 219.5 219.5 218.7 193.0 167.3 141.7 116.0 9400 72 271.1 20.91 204.1 176.1 148.1 120.1 92.1 - - 259.4 22.43 201.3 173.3 145.2 117.2 89.2 - - 67 250.3 20.43 250.3 229.2 201.1 173.1 145.1 117.1 89.1 239.7 22.13 239.7 224.6 196.6 168.6 140.5 112.5 84.5 62 225.2 20.16 225.2 225.2 225.2 197.2 169.2 141.1 113.1 213.8 21.78 213.8 213.8 213.8 185.7 157.7 129.7 101.7 57 235.2 20.43 235.2 235.2 235.2 207.1 179.1 151.1 123.1 227.2 21.98 227.2 227.2 227.2 199.2 171.1 143.1 115.1 125°F 6000 72 217.6 23.35 139.1 122.0 104.9 87.8 70.7 - - 67 201.4 23.23 175.7 158.6 141.5 124.4 107.3 90.2 73.1 62 177.7 22.82 177.7 177.7 165.8 148.7 131.6 114.5 97.4 57 192.7 22.93 192.7 190.8 173.7 156.5 139.4 122.3 105.2 7000 72 222.2 23.43 153.1 132.8 112.6 92.4 72.2 - - 67 205.6 23.31 192.3 172.1 151.9 131.7 111.4 91.2 71.0 62 181.5 22.90 181.5 181.5 178.0 157.8 137.6 117.4 97.1 57 196.8 23.01 196.8 195.8 186.4 166.2 146.0 125.7 105.5 8000 72 226.8 23.51 167.0 143.7 120.3 97.0 73.7 - - 67 209.9 23.39 208.9 185.6 162.3 138.9 115.6 92.3 68.9 62 185.2 22.98 185.2 185.2 185.2 166.9 143.5 120.2 96.9 57 200.8 23.09 200.8 200.8 199.1 175.8 152.5 129.1 105.8 8700 72 237.2 23.74 182.7 157.0 131.3 105.7 80.0 - - 67 219.5 23.61 219.0 202.8 177.1 151.5 125.8 100.1 74.4 62 193.7 23.19 193.7 193.7 193.7 170.6 144.9 119.2 93.6 57 210.0 23.30 210.0 210.0 209.2 183.5 157.8 132.1 106.5 9400 72 247.6 23.96 198.4 170.4 142.4 114.3 86.3 - - 67 229.1 23.84 229.1 220.0 192.0 164.0 136.0 107.9 79.9 62 202.3 23.41 202.3 202.3 202.3 174.3 146.3 118.2 90.2 57 219.2 23.52 219.2 219.2 219.2 191.2 163.2 135.1 107.1 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

13 TABLE 7: COOLING CAPACITIES FOR J25DJ Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) Total Cap.1 (MBH) Total2 Input (kW) Sensible Capacity (MBH)* Return Dry Bulb (°F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68 7500 72 332.2 21.58 206.4 185.0 163.6 142.3 120.9 - - 324.4 25.42 191.5 170.2 148.8 127.4 106.0 - - 67 327.2 21.26 256.1 234.7 213.3 192.0 170.6 149.2 127.8 305.5 24.73 245.9 224.5 203.1 181.7 160.4 139.0 117.6 62 321.0 20.60 320.3 298.9 277.5 256.1 234.7 213.4 192.0 301.1 24.23 295.5 274.2 252.8 231.4 210.0 188.6 167.2 57 313.6 20.57 313.6 305.9 284.5 263.1 241.8 220.4 199.0 292.2 24.07 292.2 277.1 255.7 234.3 212.9 191.5 170.1 8750 72 329.6 22.39 217.2 191.9 166.6 141.4 116.1 - - 326.8 25.46 207.5 182.3 157.0 131.7 106.4 - - 67 324.6 22.06 267.8 242.5 217.3 192.0 166.7 141.4 116.2 307.7 24.76 264.9 239.6 214.4 189.1 163.8 138.5 113.3 62 318.4 21.37 318.0 307.3 282.6 257.3 232.0 206.8 181.5 303.3 24.26 300.5 289.8 266.7 241.5 216.2 190.9 165.7 57 311.1 21.34 311.1 307.2 289.7 264.5 239.2 213.9 188.6 294.3 24.10 294.3 286.7 269.8 244.5 219.3 194.0 168.7 10000 72 326.9 23.20 228.0 198.8 169.6 140.5 111.3 - - 329.1 25.49 223.5 194.4 165.2 136.1 106.9 - - 67 321.9 22.86 279.5 250.3 221.2 192.0 162.8 133.7 104.5 309.9 24.79 283.9 254.7 225.6 196.4 167.3 138.1 108.9 62 315.8 22.15 315.8 315.8 287.7 258.5 229.4 200.2 171.0 305.5 24.29 305.5 305.5 280.7 251.6 222.4 193.2 164.1 57 308.5 22.12 308.5 308.5 294.9 265.8 236.6 207.5 178.3 296.4 24.13 296.4 296.4 283.9 254.8 225.6 196.5 167.3 11250 72 333.6 23.42 241.2 208.0 174.8 141.6 108.4 - - 336.1 25.73 238.9 205.7 172.5 139.3 106.1 - - 67 328.6 23.07 294.3 261.1 227.9 194.7 161.5 128.3 95.1 316.4 25.02 302.0 268.8 235.5 202.3 169.1 135.9 102.7 62 322.3 22.35 322.3 322.3 296.5 263.3 230.0 196.8 163.6 311.9 24.52 311.9 311.9 293.1 259.9 226.7 193.5 160.3 57 314.9 22.32 314.9 314.9 304.0 270.7 237.5 204.3 171.1 302.7 24.36 302.7 302.7 296.5 263.2 230.0 196.8 163.6 12500 72 340.4 23.63 254.5 217.3 180.0 142.7 105.5 - - 343.1 25.96 254.3 217.1 179.8 142.5 105.3 - - 67 335.2 23.28 309.2 271.9 234.7 197.4 160.2 122.9 85.6 323.0 25.25 320.0 282.8 245.5 208.2 171.0 133.7 96.5 62 328.8 22.55 328.8 328.8 305.2 268.0 230.7 193.5 156.2 318.4 24.74 318.4 318.4 305.5 268.2 231.0 193.7 156.5 57 321.3 22.53 321.3 321.3 313.0 275.7 238.4 201.2 163.9 309.0 24.58 309.0 309.0 309.0 271.7 234.4 197.2 159.9 105°F 115°F 7500 72 301.8 27.73 184.5 163.2 141.8 120.4 99.0 - - 279.1 30.03 177.6 156.2 134.8 113.4 92.0 - - 67 289.0 27.27 238.8 217.4 196.0 174.6 153.2 131.9 110.5 272.6 29.81 231.6 210.3 188.9 167.5 146.1 124.7 103.3 62 283.6 26.57 280.8 259.7 238.3 216.9 195.5 174.1 152.7 266.0 28.91 266.0 245.2 223.8 202.4 181.0 159.6 138.3 57 271.5 26.43 271.5 260.3 238.9 217.6 196.2 174.8 153.4 250.9 28.79 250.9 243.6 222.2 200.8 179.4 158.1 136.7 8750 72 306.8 27.83 201.3 176.1 150.8 125.5 100.2 - - 286.9 30.20 195.1 169.8 144.6 119.3 94.0 - - 67 293.9 27.37 259.0 233.7 208.5 183.2 157.9 132.7 107.4 280.1 29.98 253.1 227.9 202.6 177.3 152.0 126.8 101.5 62 288.3 26.67 286.9 276.4 253.4 228.1 202.8 177.6 152.3 273.3 29.07 273.3 262.9 240.0 214.8 189.5 164.2 138.9 57 276.1 26.53 276.1 270.5 254.1 228.8 203.5 178.3 153.0 257.9 28.96 257.9 254.2 238.3 213.1 187.8 162.5 137.3 10000 72 311.8 27.93 218.1 188.9 159.8 130.6 101.5 - - 294.6 30.38 212.7 183.5 154.4 125.2 96.0 - - 67 298.7 27.47 279.3 250.1 220.9 191.8 162.6 133.5 104.3 287.6 30.16 274.6 245.5 216.3 187.1 158.0 128.8 99.7 62 293.1 26.77 293.1 293.1 268.5 239.3 210.2 181.0 151.9 280.7 29.24 280.7 280.7 256.3 227.1 198.0 168.8 139.6 57 280.6 26.63 280.6 280.6 269.2 240.0 210.9 181.7 152.6 264.8 29.13 264.8 264.8 254.5 225.3 196.2 167.0 137.8 11250 72 318.7 28.19 233.1 199.9 166.7 133.5 100.3 - - 301.4 30.66 227.3 194.1 160.9 127.7 94.5 - - 67 305.4 27.73 294.9 263.7 230.5 197.3 164.1 130.9 97.7 294.3 30.44 287.8 258.7 225.5 192.3 159.1 125.9 92.7 62 299.6 27.02 299.6 299.6 280.1 246.9 213.7 180.5 147.3 287.2 29.52 287.2 287.2 267.2 234.0 200.8 167.6 134.3 57 286.8 26.88 286.8 286.8 280.9 247.7 214.5 181.2 148.0 270.9 29.40 270.9 270.9 265.3 232.1 198.9 165.7 132.5 12500 72 325.6 28.46 248.2 210.9 173.6 136.4 99.1 - - 308.2 30.95 242.0 204.8 167.5 130.2 93.0 - - 67 312.0 27.99 310.5 277.4 240.1 202.8 165.6 128.3 91.1 300.9 30.72 300.9 272.0 234.7 197.4 160.2 122.9 85.7 62 306.0 27.27 306.0 306.0 291.8 254.5 217.3 180.0 142.8 293.6 29.79 293.6 293.6 278.1 240.8 203.6 166.3 129.0 57 293.0 27.13 293.0 293.0 292.5 255.3 218.0 180.8 143.5 277.0 29.68 277.0 277.0 276.1 238.9 201.6 164.3 127.1 125°F 7500 72 256.5 32.33 170.6 149.2 127.8 106.4 85.0 - - 67 256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2 62 248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8 57 230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0 8750 72 266.9 32.57 188.9 163.6 138.4 113.1 87.8 - - 67 266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6 62 258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6 57 239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5 10000 72 277.3 32.82 207.3 178.1 148.9 119.8 90.6 - - 67 276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0 62 268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4 57 249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1 11250 72 284.0 33.13 221.6 188.3 155.1 121.9 88.7 - - 67 283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6 62 274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4 57 255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9 12500 72 290.7 33.44 235.9 198.6 161.3 124.1 86.8 - - 67 289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3 62 281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3 57 261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

CFM, STATIC PRESSURE, AND POWER - ALTI- TUDE AND TEMPERATURE CORRECTIONS The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In order to use the indoor blower tables for high altitude applica- tions, certain corrections are necessary. A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 8 and Figure 2. The examples below will assist in determining the airflow per- formance of the product at altitude. Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP? Solution: At an elevation of 5,000 ft the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 8 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 8 shows the correction factor to be 0.832. Corrected static pressure = 1.5 x 0.832 = 1.248 IWC Corrected BHP = 4.0 x 0.832 = 3.328 Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit blower tables to select the blower speed and the BHP requirement. Solution: As in the example above, no temperature informa- tion is given so 70°F is assumed. The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions. Sea level static pressure = 1.5 / .832 = 1.80" Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft. Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation. BHP at 5,000 ft = 3.2 x .832 = 2.66 TABLE 8: ALTITUDE CORRECTION FACTORS AIR TEMP ALTITUDE (FEET) 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663 100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

Johnson Controls Unitary Products

15 FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR                         

Johnson Controls Unitary Products

NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY 180 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 4500 5250 6000 6750 7200 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 850 6.0** 0.9 2.4 2.2 0.7 3.0 2.7 0.5 3.2 2.9 - - - - - - 870 5.5 1.0 2.5 2.3 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - - 915 4.5 1.1 2.6 2.4 0.9 3.4 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0 965 3.5 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 4.9 4.4 980 3.0 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8. 4.3 0.5 5.1 4.6 1010 2.0 1.4 3.1 2.8 1.2 3.8 3.4 1.0 4.2 3.8 0.7 5.0 4.5 0.6 5.4 4.8 1040 1.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.2 4.7 0.7 5.7 5.1 208 VOLT AND HIGH STATIC DRIVE 965 6.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4 980 5.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6 1025 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.8 5.1 4.6 0.7 5.6 5.0 1065 3.5 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - - 1095 3.0 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - - 1130 2.0 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 - - - - - - 1170 1.0 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 - - - - - - 230/460/575 VOLT AND STANDARD DRIVE 870 6.0** 1.0 2.4 2.2 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - - 915 5.0 1.1 2.6 2.4 0.9 3.3 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0 965 4.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4 980 3.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6 1040 2.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1 1065 1.0 1.6 3.3 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - - 230/460/575 VOLT AND HIGH STATIC DRIVE 980 6.0 1.3 2.9 2.6 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6 1040 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1 1065 4.0 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - - 1095 3.5 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - - 1130 2.5 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 - - - - - - 1170 1.5 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 - - - - - - 1190 1.0 2.2 4.0 3.6 2.1 4.8 4.3 2.0 5.7 5.1 - - - - - -

Johnson Controls Unitary Products

17 NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY 210 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 6000 7000 8000 9000 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - 900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - 930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 208 VOLT AND HIGH STATIC DRIVE 950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - 230/460/575 VOLT AND STANDARD DRIVE 870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - 900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - 930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 230/460/575 VOLT AND HIGH STATIC DRIVE 950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - 1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - -

Johnson Controls Unitary Products

NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY 240 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 6000 7000 8000 9000 9400 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - - - - 900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - - 930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - - 950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - - 980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9 208 VOLT AND HIGH STATIC DRIVE 950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - - 980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 0.5 7.9 6.7 1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 0.6 8.3 7.0 1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3 1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - - 1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - - 1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - - 230/460/575 VOLT AND STANDARD DRIVE 870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - - - - 900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - - 930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - - 950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - - 980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9 1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 0.7 8.6 7.3 230/460/575 VOLT AND HIGH STATIC DRIVE 950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - - 980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9 1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3 1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - - 1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - - 1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - - 1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - - - - -

Johnson Controls Unitary Products

19 NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT 180 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 4500 5250 6000 6750 7200 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 850 6.0** 0.9 2.4 2.1 0.6 2.9 2.6 0.3 3.4 3.0 - - - - - - 870 5.5 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 - - - - - - 915 4.5 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - - 965 3.5 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.0 0.2 5.0 4.5 980 3.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1010 2.0 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8 1040 1.0 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0 208 VOLT AND HIGH STATIC DRIVE 965 6.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5 980 5.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1025 4.5 1.4 3.1 2.8 1.2 3.6 3.2 0.9 4.1 3.7 0.7 4.8 4.3 0.4 5.5 4.9 1065 3.5 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - - 1125 2.0 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - - 1170 1.0 2.1 3.9 3.5 1.9 4.7 4.2 1.6 5.5 4.9 - - - - - - 230/460/575 VOLT AND STANDARD DRIVE 870 6.0** 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 - - - - - - 915 5.0 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - - 965 4.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5 980 3.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1015 2.5 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8 1050 1.5 1.5 3.1 2.8 1.2 3.7 3.3 0.9 4.2 3.8 0.7 4.9 4.4 0.5 5.7 5.1 1065 1.0 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - - 230/460/575 VOLT AND HIGH STATIC DRIVE 980 6.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1045 4.5 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0 1065 4.0 1.7 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - - 1125 2.5 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - - 1170 1.5 2.1 3.9 3.5 1.8 4.7 4.2 1.6 5.5 4.9 - - - - - - 1190 1.0 2.2 4.0 3.6 1.9 4.8 4.3 1.7 5.6 5.0 - - - - - -

Johnson Controls Unitary Products

NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT 210 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 6000 7000 8000 9000 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - 900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - 930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6 208 VOLT AND HIGH STATIC DRIVE 950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - - 230/460/575 VOLT AND STANDARD DRIVE 870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - 900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - 930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 230/460/575 VOLT AND HIGH STATIC DRIVE 950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 - - - 1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 - - -

Johnson Controls Unitary Products

21 NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT 240 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 6000 7000 8000 9000 9400 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - - - - 900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - - - - 930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - - 950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - - 980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1 995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6 - - - 208 VOLT AND HIGH STATIC DRIVE 950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - - 980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1 995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - - 1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - - 1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - - 1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - - - - - 230/460/575 VOLT AND STANDARD DRIVE 870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - - - - 900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - - - - 930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - - 950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - - 965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1 995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - - 1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - - 230/460/575 VOLT AND HIGH STATIC DRIVE 950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - - 980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1 995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - - 1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - - 1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - - 1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - - 1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 - - - - - - 1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 - - - - -

Johnson Controls Unitary Products

NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT 300 MBH - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM 7500 8750 10000 11250 12500 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE 975 6.0 1.2 5.9 4.9 5.0 7.3 6.0 - - - - - - - - - 1005 5.0 1.4 6.2 5.1 0.7 7.7 6.3 - - - - - - - - - 1040 4.0 1.6 6.6 5.4 0.9 8.1 6.7 0.2 9.7 8.0 - - - - - - 1070 3.0 1.8 6.9 5.7 1.1 8.5 7.0 0.4 10.2 8.3 - - - - - - 1100 2.0 2.0 7.3 6.0 1.3 8.9 7.3 0.6 10.6 8.7 - - - - - - 1135 1.0 2.2 7.7 6.3 1.6 9.3 7.6 0.8 11.1 9.1 - - - - - - 1165 0.0 2.4 8.0 6.6 1.8 9.7 8.0 1.0 11.6 9.5 0.2 13.5 11.0 - - - 208 VOLT AND HIGH STATIC DRIVE 1140 6.0 2.2 7.7 6.3 1.6 9.4 7.7 0.9 11.2 9.2 - - - - - - 1180 5.0 2.5 8.2 6.7 1.9 9.9 8.1 1.2 11.8 9.7 0.3 13.7 11.2 - - - 1215 4.0 2.7 8.6 7.0 2.1 10.4 8.5 1.4 12.3 10.1 0.6 14.3 11.7 - - - 1255 3.0 3.0 9.1 7.4 2.4 11.0 9.0 1.7 12.9 10.6 0.9 15.0 12.3 - - - 1290 2.0 3.2 9.5 7.8 2.7 11.5 9.4 2.0 13.5 11.1 1.2 15.6 12.8 - - - 1330 1.0 3.5 10.0 8.2 3.0 12.0 9.9 2.3 14.1 11.6 1.5 16.4 13.4 - - - 1365 0.0 3.7 10.5 8.6 3.2 12.6 10.3 2.6 14.7 12.1 1.8 17.0 13.9 - - - 230/460/575 VOLT AND STANDARD DRIVE 975 6.0* 1.4 5.9 4.9 1.0 7.3 6.0 0.5 8.8 7.2 - - - - - - 1005 5.0 1.6 6.2 5.1 1.2 7.7 6.3 0.7 9.2 7.6 0.1 10.9 8.9 - - - 1040 4.0 1.8 6.6 5.4 1.4 8.1 6.7 0.9 9.7 8.0 0.3 11.4 9.4 - - - 1070 3.0 2.0 6.9 5.7 1.6 8.5 7.0 1.1 10.2 8.3 0.6 11.9 9.8 - - - 1100 2.0 2.1 7.3 6.0 1.8 8.9 7.3 1.3 10.6 8.7 0.8 12.4 10.2 0.2 14.3 11.7 1135 1.0 2.4 7.7 6.3 2.0 9.3 7.6 1.6 11.1 9.1 1.0 13.0 10.6 0.4 14.9 12.2 1165 0.0 2.6 8.0 6.6 2.2 9.7 8.0 1.8 11.6 9.5 1.3 13.5 11.0 0.7 15.5 12.7 230/460/575 VOLT AND HIGH STATIC DRIVE 1140 6.0 2.4 7.7 6.3 2.1 9.4 7.7 1.6 11.2 9.2 1.1 13.1 10.7 0.5 15.0 12.3 1180 5.0 2.7 8.2 6.7 2.3 9.9 8.1 1.9 11.8 9.7 1.4 13.7 11.2 0.8 15.8 12.9 1215 4.0 2.9 8.6 7.0 2.6 10.4 8.5 2.2 12.3 10.1 1.7 14.3 11.7 1.1 16.4 13.5 1255 3.0 3.2 9.1 7.4 2.9 11.0 9.0 2.5 12.9 10.6 2.0 15.0 12.3 1.4 17.2 14.1 1290 2.0 3.4 9.5 7.8 3.1 11.5 9.4 2.7 13.5 11.1 2.2 15.6 12.8 - - - 1330 1.0 3.7 10.0 8.2 3.4 12.0 9.9 3.0 14.1 11.6 2.6 16.4 13.4 - - - 1365 0.0 3.9 10.5 8.6 3.7 12.6 10.3 3.3 14.7 12.1 2.9 17.0 13.9 - - -

Johnson Controls Unitary Products

23 TABLE 16: BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLOWER RANGE (RPM) MOTOR1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT (NOTCHED) HP FRAME EFF. (%) DESIG- NATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIG- NATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIG- NATION PITCH LENGTH (IN.) QTY. 15 TON Standard 850/1065 5 184 T 83 1VP56 5.35 4.3-5.32 1-1/8 BK90 8.75 8.4 1 BX81 82.8 1 High Static 965/1190 BK80 7.75 7.4 1 BX78 79.8 1 17.5 & 20 TON Standard 870/1025 7.5 213 T 89 1VP68 6.75 5.5-6.52 1-3/8 BK120 11.75 11.4 1-3/16 BX83 84.8 1 High Static 950/1120 BK110 10.75 10.4 1-3/16 BX81 82.8 1 25 TON Standard 975/1165 15 254 T 91 1VP75X 7.5 6.2-7.42 1-5/8 1B5V110 11.3 11.1 1-7/16 5VX860 86.0 1 High Static 1140/1365 1B5V94 9.7 9.5 1-7/16 5VX840 84.0 1 1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heating device. 2. Do NOT close this pulley below 1 turn open. TABLE 17: STATIC RESISTANCES1 DESCRIPTION RESISTANCE, IWG CFM 15 TON 17.5 TON 20 TON 25 TON 4500 6000 7200 6000 7500 9000 6000 8000 9400 7500 10000 12500 WET INDOOR COIL 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 ELECTRIC HEAT OPTIONS 18 KW 0.3 0.4 0.4 0.4 0.4 0.5 0.4 0.4 0.5 0.4 0.5 0.6 36 KW 0.3 0.4 0.5 0.4 0.5 0.5 0.4 0.5 0.5 0.5 0.5 0.6 54 KW 0.4 0.5 0.5 0.5 0.5 0.6 0.5 0.5 0.6 0.5 0.6 0.7 72 KW 0.4 0.5 0.5 0.5 0.5 0.6 0.5 0.5 0.6 0.5 0.6 0.7 ECONOMIZER OPTION 0.1 0.1 0.1 0.1 0.1 0.2 0.1 0.1 0.2 0.1 0.2 0.3 HORIZONTAL DUCT CONNECTIONS2 0.1 0.2 0.3 0.2 0.3 0.5 0.2 0.3 0.5 0.3 0.5 0.6 1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for exception.) 2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the respective unit’s blower performance table. TABLE 18: POWER EXHAUST PERFORMANCE MOTOR SPEED1 STATIC RESISTANCE OF RETURN DUCTWORK, IWG 0.2 0.3 0.4 0.5 0.6 CFM kW CFM kW CFM kW CFM kW CFM kW HIGH2 5250 0.83 4500 0.85 4200 0.88 3750 0.93 3000 0.99 MEDIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - - LOW 4400 0.72 3700 0.74 3000 0.78 - - - - 1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection. 2. The factory setting.

Johnson Controls Unitary Products

NOTE 1: HACR Type per NEC. TABLE 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET MODEL (TON- NAGE) VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN. CIRCUIT AMPACITY (AMPS) MAX. FUSE/ BRKR1 SIZE (AMPS) RLA EACH LRA EACH MODEL KW STAGES AMPS J15 (15) 208 22.4 164 2.1 15.4 0.0 None 0.0 ~ ~ 74.2 90 E18 13.5 1 37.5 74.2 90 E36 27.0 2 75.1 112.9 125 E54 40.6 2 112.6 160.1 175 E72 54.1 2 150.1 169.4 200 230 22.4 164 2.1 15.4 0.0 None 0.0 ~ ~ 73.2 90 E18 18.0 1 43.3 73.2 90 E36 36.0 2 86.6 126.3 150 E54 54.0 2 129.9 147.9 175 E72 72.0 2 173.2 191.2 225 460 10.9 100 1.1 7.2 0.0 None 0.0 ~ ~ 36.1 45 E18 18.0 1 21.7 36.1 45 E36 36.0 2 43.3 63.1 70 E54 54.0 2 65.0 74.0 90 E72 72.0 2 86.6 95.6 110 575 8.3 78 0.9 5.9 0.0 None 0.0 ~ ~ 28.2 35 E18 18.0 1 17.3 29.0 35 E36 36.0 2 34.6 50.7 60 E54 54.0 2 52.0 59.3 70 E72 72.0 2 69.3 76.7 90 J18 (17 1/2) 208 25.6 190 2.1 20.0 0.0 None 0.0 ~ ~ 86.0 110 E18 13.5 1 37.5 86.0 110 E36 27.0 2 75.1 118.7 125 E54 40.6 2 112.6 165.9 175 E72 54.1 2 150.1 175.2 200 230 25.6 190 2.1 20.0 0.0 None 0.0 ~ ~ 86.0 110 E18 18.0 1 43.3 86.0 110 E36 36.0 2 86.6 133.3 150 E54 54.0 2 129.9 154.9 175 E72 72.0 2 173.2 198.2 225 460 12.8 95 1.1 10.0 0.0 None 0.0 ~ ~ 43.2 50 E18 18.0 1 21.7 43.2 50 E36 36.0 2 43.3 66.6 70 E54 54.0 2 65.0 77.5 90 E72 72.0 2 86.6 99.1 110 575 10.3 75 0.9 8.2 0.0 None 0.0 ~ ~ 35.0 45 E18 18.0 1 17.3 35.0 45 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90

Johnson Controls Unitary Products

25 NOTE 1: HACR Type per NEC. TABLE 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET (CONTINUED) MODEL (TON- NAGE) VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN. CIRCUIT AMPACITY (AMPS) MAX. FUSE/ BRKR1 SIZE (AMPS) RLA EACH LRA EACH MODEL KW STAGES AMPS J20 (20) 208 33.6 225 3.7 20.0 0.0 None 0.0 ~ ~ 110.4 125 E18 13.5 1 37.5 110.4 125 E36 27.0 2 75.1 118.7 125 E54 40.6 2 112.6 165.9 175 E72 54.1 2 150.1 175.2 200 230 33.6 225 3.7 20.0 0.0 None 0.0 ~ ~ 110.4 125 E18 18.0 1 43.3 110.4 125 E36 36.0 2 86.6 133.3 150 E54 54.0 2 129.9 154.9 175 E72 72.0 2 173.2 198.2 225 460 17.3 114 1.9 10.0 0.0 None 0.0 ~ ~ 56.5 70 E18 18.0 1 21.7 56.5 70 E36 36.0 2 43.3 66.6 70 E54 54.0 2 65.0 77.5 90 E72 72.0 2 86.6 99.1 110 575 13.5 80 1.5 8.2 0.0 None 0.0 ~ ~ 44.6 50 E18 18.0 1 17.3 44.6 50 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90 J25 (25) 208 47.1 245 3.7 38.6 0.0 None 0.0 ~ ~ 159.4 200 E18 13.5 1 37.5 159.4 200 E36 27.0 2 75.1 159.4 200 E54 40.6 2 112.6 189.1 200 E72 54.1 2 150.1 198.4 225 230 47.1 245 3.7 38.6 0.0 None 0.0 ~ ~ 159.4 200 E18 18.0 1 43.3 159.4 200 E36 36.0 2 86.6 159.4 200 E54 54.0 2 129.9 178.2 200 E72 72.0 2 173.2 221.5 250 460 19.6 125 1.9 19.3 0.0 None 0.0 ~ ~ 71.0 90 E18 18.0 1 21.7 71.0 90 E36 36.0 2 43.3 78.3 90 E54 54.0 2 65.0 89.1 100 E72 72.0 2 86.6 110.7 125 575 15.8 100 1.5 15.4 0.0 None 0.0 ~ ~ 57.0 70 E18 18.0 1 17.3 57.0 70 E36 36.0 2 34.6 62.6 70 E54 54.0 2 52.0 71.2 80 E72 72.0 2 69.3 88.5 100

Johnson Controls Unitary Products

NOTE 1: HACR Type per NEC. TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET MODEL (TON- NAGE) VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN. CIRCUIT AMPACITY (AMPS) MAX. FUSE/ BRKR1 SIZE (AMPS) RLA EACH LRA EACH MODEL KW STAGES AMPS J15 (15) 208 22.4 164 2.1 15.4 10.0 None 0.0 ~ ~ 84.2 100 E18 13.5 1 37.5 84.2 100 E36 27.0 2 75.1 125.4 150 E54 40.6 2 112.6 172.6 175 E72 54.1 2 150.1 181.9 200 230 22.4 164 2.1 15.4 10.0 None 0.0 ~ ~ 83.2 100 E18 18.0 1 43.3 84.6 100 E36 36.0 2 86.6 138.8 150 E54 54.0 2 129.9 160.4 175 E72 72.0 2 173.2 203.7 225 460 10.9 100 1.1 7.2 5.0 None 0.0 ~ ~ 41.1 50 E18 18.0 1 21.7 42.3 50 E36 36.0 2 43.3 69.4 70 E54 54.0 2 65.0 80.2 90 E72 72.0 2 86.6 101.9 110 575 8.3 78 0.9 5.9 4.0 None 0.0 ~ ~ 32.2 40 E18 18.0 1 17.3 34.0 40 E36 36.0 2 34.6 55.7 60 E54 54.0 2 52.0 64.3 70 E72 72.0 2 69.3 81.7 90 J18 (17 1/2) 208 25.6 190 2.1 20.0 10.0 None 0.0 ~ ~ 96.0 110 E18 13.5 1 37.5 96.0 110 E36 27.0 2 75.1 131.2 150 E54 40.6 2 112.6 178.4 200 E72 54.1 2 150.1 187.7 200 230 25.6 190 2.1 20.0 10.0 None 0.0 ~ ~ 96.0 110 E18 18.0 1 43.3 96.0 110 E36 36.0 2 86.6 145.8 150 E54 54.0 2 129.9 167.4 175 E72 72.0 2 173.2 210.7 225 460 12.8 95 1.1 10.0 5.0 None 0.0 ~ ~ 48.2 60 E18 18.0 1 21.7 48.2 60 E36 36.0 2 43.3 72.9 80 E54 54.0 2 65.0 83.7 90 E72 72.0 2 86.6 105.4 110 575 10.3 75 0.9 8.2 4.0 None 0.0 ~ ~ 39.0 45 E18 18.0 1 17.3 39.0 45 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90

Johnson Controls Unitary Products

27 NOTE 1: HACR Type per NEC. TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED) MODEL (TON- NAGE) VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN. CIRCUIT AMPACITY (AMPS) MAX. FUSE/ BRKR1 SIZE (AMPS) RLA EACH LRA EACH MODEL KW STAGES AMPS J20 (20) 208 33.6 225 3.7 20.0 10.0 None 0.0 ~ ~ 120.4 150 E18 13.5 1 37.5 120.4 150 E36 27.0 2 75.1 131.2 150 E54 40.6 2 112.6 178.4 200 E72 54.1 2 150.1 187.7 200 230 33.6 225 3.7 20.0 10.0 None 0.0 ~ ~ 120.4 150 E18 18.0 1 43.3 120.4 150 E36 36.0 2 86.6 145.8 150 E54 54.0 2 129.9 167.4 175 E72 72.0 2 173.2 210.7 225 460 17.3 114 1.9 10.0 5.0 None 0.0 ~ ~ 61.5 70 E18 18.0 1 21.7 61.5 70 E36 36.0 2 43.3 72.9 80 E54 54.0 2 65.0 83.7 90 E72 72.0 2 86.6 105.4 110 575 13.5 80 1.5 8.2 4.0 None 0.0 ~ ~ 48.6 60 E18 18.0 1 17.3 48.6 60 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90 J25 (25) 208 47.1 245 3.7 38.6 10.0 None 0.0 ~ ~ 169.4 200 E18 13.5 1 37.5 169.4 200 E36 27.0 2 75.1 169.4 200 E54 40.6 2 112.6 201.6 225 E72 54.1 2 150.1 210.9 225 230 47.1 245 3.7 38.6 10.0 None 0.0 ~ ~ 169.4 200 E18 18.0 1 43.3 169.4 200 E36 36.0 2 86.6 169.4 200 E54 54.0 2 129.9 190.7 225 E72 72.0 2 173.2 234.0 250 460 19.6 125 1.9 19.3 5.0 None 0.0 ~ ~ 76.0 90 E18 18.0 1 21.7 76.0 90 E36 36.0 2 43.3 84.5 90 E54 54.0 2 65.0 95.3 110 E72 72.0 2 86.6 117.0 125 575 15.8 100 1.5 15.4 4.0 None 0.0 ~ ~ 61.0 70 E18 18.0 1 17.3 61.0 70 E36 36.0 2 34.6 67.6 70 E54 54.0 2 52.0 76.2 90 E72 72.0 2 69.3 93.5 100

Johnson Controls Unitary Products

TABLE 21: J**DJ VOLTAGE LIMITATIONS1 1. Utilization Range “A” in accordance with ARI Standard 110. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE MIN. MAX. VOLTAGE LIMITATIONS 208/230-3-60 187 253 460-3-60 414 506 575-3-60 518 630 TABLE 22: PHYSICAL DATA MODELS J15DJ J18DJ J20DJ J25DJ EVAPORATOR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd.) 15x15 18x15 18x15 18x15 FAN MOTOR HP 5.0 7.5 7.5 15 EVAPORATOR COIL ROWS DEEP 4 FINS PER INCH 13.5 FACE AREA (Sq. Ft.) 25 CONDENSER FAN (Four Per Unit) PROPELLER DIA. (In.) (Each) 24 24 30 30 FAN MOTOR HP (Each) 1/3 1/3 3/4 3/4 NOM. CFM TOTAL (Each) 4,000 4,000 5,000 5,000 CONDENSER COIL ROWS DEEP 2 FINS PER INCH 20 FACE AREA (Sq. Ft.) 63.8 COMPRESSOR (Qty. Per Unit) SCROLL 2 FILTERS QUANTITY PER UNIT (12" X 24" X 2" 12 TOTAL FACE AREA (Sq. Ft.) 24 CHARGE REFRIGERANT 22 (Lb./Oz.) SYSTEM No.1 23/0 24/0 23/8 23/8 SYSTEM No. 2 23/8 24/0 23/8 23/8 OPERATING WEIGHTS (LBS.) BASIC UNIT COOLING ONLY 2260 2540 2560 2660 GAS / ELECTRIC N24 2460 2740 2760 2860 N32 2500 2780 2800 2900 OPTIONS DOUBLE WALL 260 ECONOMIZER 160 ECONOMIZER WITH POWER EXHAUST 245 MOTORIZED DAMPER 150 ELECTRIC HEATER 18 KW 25 36 KW 30 54 KW 35 72 KW 40 HOT GAS BYPASS 10 SUPPLY FAN VFD See Table 23 ACCESSORIES ROOF CURB 185 BAROMETRIC DAMPER 45 ECONOMIZER / MOTORIZED DAMPER RAIN HOOD 55 ECONOMIZER / POWER EXHAUST RAIN HOOD 90 WOOD SKID 220

Johnson Controls Unitary Products

29 TABLE 23: SUPPLY FAN VFD WEIGHTS, IN LBS. SUPPLY FAN MOTOR 230V 460V 575V W/O MANUAL BYPASS 5.0 hp 25 25 30 7.5 hp 30 30 30 10.0 hp 30 30 35 15.0 hp 30 30 40 W/MANUAL BYPASS 5.0 hp 30 30 35 7.5 hp 35 35 35 10.0 hp 35 35 40 15.0 hp 40 35 45 TABLE 24: ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAGE kW CAP. MULTI- PLIER 208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92 FIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAM                                                    !"#$%!"&!'((') *!("+ '  ,$#-.++-))'+/0 !($#')"1 2"' ."#!'3)"'!.$#24" + $"#"5 *-#$ "# !")"60 "#.+ '&*' $#&$+#" !7-$!."#-#$ +8$ *'+$#&+ '& !$*' !0 !($#'+'#.%!"4$.'!'3"- %-  ""+ *"- .""!"#"($9!.'(%!+ 8*# * *!("+ ' +8$ *+ " *+ 2)'1%"+$ $"#0                    :      ;        5! " *    ')+ "+$9 * %"8!8$!$#&< * 5-++'#. * .$+"## +8$ *0 :      =  ,:  /            ;  :" *!("+ ' "!> ,8$ *-))'+ /0 !($#'+ !$% 2"' ."#!'3)"'!.$#24" + $"# "5 *-#$ "# !")"60 "#.+ '&*' $#&$+#" !7-$!."#-#$ +8$ *'+$#&+ '&  !$*' !0         ;     ,:  / :          ?@    ?@    ?@ 

Johnson Controls Unitary Products

FIGURE 4 - FRONT VIEW DIMENSIONS TABLE 25: UTILITIES ENTRY DATA HOLE OPENING SIZE (DIA.) USED FOR A 1-1/8” KO Control Wiring Side 3/4” NPS (Fem.) Bottom B 3-5/8” KO Power Wiring Side 3” NPS (Fem.) Bottom C 2-3/8” KO Gas Piping (Front)1 1. One-inch gas piping NPT required. D 1-11/16” Hole Gas Piping (Bottom)1, 2 2. Opening in the bottom of the unit can be located by the slice in the insulation. NOTE: All entry holes should be field sealed to prevent rain water entry into the building. 11-1/2 (A) CONTROL WIRING ENTRY COIL GUARD KIT CONDENSER COILS All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. (B) POWER WIRING ENTRY 5 9-3/4 21.00 6-3/8 7-1/8 35 5-7/8 136-1/4 GAS OR ELECTRIC HEAT ACCESS DOT PLUG (For pressure drop reading) BLOWER COMPARTMENT ACCESS (Auxiliary) (C) GAS SUPPLY ENTRY CONTROL BOX ACCESS VENT AIR OUTLET HOODS BLOWER MOTOR ACCESS (Location of Optional VFD Bypass) BLOWER ACCESS (Location of Optional VFD) 52-5/8 180-19/32 COMPRESSOR ACCESS DISCONNECT SWITCH LOCATION ECONOMIZER / MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail Y) 92 46-5/8 35-1/4 33 2-3/4 3-3/4 (B) POWER WIRING ENTRY BOTTOM SUPPLY AND RETURN AIR OPENINGS (See Note) (A) CONTROL WIRING ENTRY 21-1/2 11-1/8 (D) GAS SUPPLY ENTRY UNIT BASE RAILS Shown separately to illustrate RETURN AIR Bottom Duct openings. Power and Gas Piping Connection location. NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for proper size of the supply and return air duct connections. 12-1/2 9-1/4 8-1/8 46-5/8 9-3/4 COMBUSTION AIR INLET HOOD SUPPLY AIR

Johnson Controls Unitary Products

31 FIGURE 5 - REAR VIEW DIMENSIONS NOTE:Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. 2. Remove and discard the bottom duct covers. Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition. 3. Replace the side supply and return air compartment panels. For side duct applications: 1. Replace the side panels on the supply and return air compartments with the side duct flange accessory kit panels. 2. Connect ductwork to the flanges on those panels. SUPPLY AIR RETURN AIR OUTDOOR AIR 5-1/8" 18-5/8" 27-3/4" 39-5/8" 40-1/2" OUTDOOR AIR COMPARTMENT ACCESS FILTER ACCESS 1" NPT FEMALE COND. DRAIN CONNECTION DOT PLUG (For pressure drop reading) EVAPORATOR SECTION 40-3/8" COMPRESSOR ACCESS SUPPLY AIR ACCESS RETURN AIR ACCESS REAR VIEW Dimensions listed are for side duct flange openings; see Field Accessories for Side Duct Flange Kit.

Johnson Controls Unitary Products

NOTE: ELEC / ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters. GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit. The products of combustion must not be allowed to accumulate within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least: • Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit). • Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building. • Four (4) feet from electric and gas meters, regulators and relief equipment. FIGURE 6 - UNIT DIMENSIONS J15, 18, 20 & 25 DJ (RAINHOOD) TABLE 26: MINIMUM CLEARANCES LOCATION CLEARANCE Front 36” Rear 24” (Less Economizer) 49” (With Economizer) Left Side (Filter Access) 24” (Less Economizer) 36” (With Economizer)3 Right Side (Cond. Coil) 36” Below Unit1 1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 0” Above Unit2 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. 3. If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of evapora- tor coil, or in the outdoor air compartment, prior to final installa- tion. 72” With 36” Maximum Horizontal Overhang (For Condenser Air Discharge) REAR VIEW DETAIL “Y” UNIT WITH RAIN HOODS LH VIEW 28-3/16” 92” 36-5/8” 5” 16-1/8” SUPPLY AIR COMPARTMENT POWER EXHAUST RAIN HOOD (on Return Air Compartment) ECONOMIZER MOTORIZED DAMPER RAIN HOOD (on Outdoor Air Compartment) ECONOMIZER / MOTORIZED DAMPER AND POWER EXHAUST RAIN HOODS FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment) 1“ CONDENSATE DRAIN (Must be trapped)

Johnson Controls Unitary Products

33 FIGURE 7 - UNIT CENTER OF GRAVITY FIGURE 8 - TYPICAL UNIT APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION

Johnson Controls Unitary Products

Note: These weights are with economizer and high option heat (gas or electric). FIGURE 9 - FOUR AND SIX POINT LOADS A D C E B F A D B C TABLE 27: FOUR AND SIX POINT LOADS Unit Size Total Shipping Weight 4 Point Loads (lbs) A B C D J15DJ Gas 2660 454 847 885 474 J18DJ Gas 2928 510 954 954 510 J20DJ Gas 2960 516 964 964 516 J25DJ Gas 3046 531 992 992 531 J15DJ Elec 2460 419 784 819 438 J18DJ Elec 2728 476 888 888 476 J20DJ Elec 2760 481 899 899 481 J25DJ Elec 2846 496 927 927 496 Unit Size Total Shipping Weight 6 Point Loads (lbs) A B C D E F J15DJ Gas 2660 302 316 453 590 565 434 J18DJ Gas 2928 340 340 488 636 636 488 J20DJ Gas 2960 344 344 493 643 643 493 J25DJ Gas 3046 354 354 508 661 661 508 J15DJ Elec 2460 280 292 419 546 523 401 J18DJ Elec 2728 317 317 455 592 592 455 J20DJ Elec 2760 321 321 460 599 599 460 J25DJ Elec 2846 331 331 474 618 618 474

Johnson Controls Unitary Products

35 1. The 2” space between the ducts allows for “jumping” an existing roof joist. 2. The 58-1/2” overall dimension of the ducts allows duct- work penetration between roof joists that are spaced on 72” centers. Note: Ducts can be installed into the curb from the roof. All electrical and gas line connections can be made inside the curb. FIGURE 10 - UNIT ROOF CURB DIMENSIONS 25-1/4" FIGURE 11 - ROOF CURB DUCT OPENINGS DIMENSION FIGURE 12 - CUT AWAY OF ROOF CURB

Johnson Controls Unitary Products

FIGURE 13 - TYPICAL UNIT WIRING DIAGRAM W1 W2 Y1 G OCC P P1 Y2 X R SD C C SD SD R OCC C RC G Y2 Y1 W2 W1 Jumper Smoke Detector 24 VAC Class 2 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units. Second stage cooling not required on single stage cooling units. Jumper is required if there is no Smoke Detector circuit. Jumper is required for any combination of R, RC, or RH. 6 5 5 6 OCC is an output from the thermostat to indicate the Occupied condition. X is an input to the thermostat to display Error Status conditions.

Johnson Controls Unitary Products

37 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by Johnson Controls in an ISO 9001 certified facility. Series 20 J**DJ units are convertible single package units. All models have dual independent refrigerant circuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every applica- tion. All units are self-contained and assembled on full perim- eter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. Each unit shall have 4 condenser fan motors. All compres- sors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compres- sor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.All models are CSA approved. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty. DESCRIPTION Units shall be factory-assembled, single packaged, J**DJN Electric Cooling/Gas Heat, J**DJC/E Electric Cooling/ Optional Electric Heat, designed for outdoor mounted instal- lation. The 15,17.5, and 20 ton units shall have minimum EER ratings of 11.1. The 25 ton unit shall have a minimum EER rating of 10.5. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to ship- ment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSIZ21.47 standards, UL 1995/ CAN/CSA No. 236-M90 conditions. UNIT CABINET Unit cabinet shall be constructed of a combination of G60 and G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per ASTMB117 standards. Indoor blower sec- tion shall be insulated with a minimum 1/2" thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be "large" size, easily removable for ser- vicing and maintenance. Full perimeter base rails shall be pro- vided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 2" fil- ters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1" or 2" filters. Fan performance mea- suring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan perfor- mance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate con- nection shall be a minimum of 1" I.D. female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit. INDOOR (EVAPORATOR) FAN ASSEMBLY Fan shall be a belt drive assembly and include an adjustable- pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with for- ward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. A variable air volume (VAV) option using a variable frequency drive (VFD) is available for applications requiring a constant supply duct static pressure. Units equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. The VAV control board shall operate using factory-installed Sup- ply Air, Return Air and Outside Air Temperature Sensors.

Johnson Controls Unitary Products

Units equipped with VFD’s shall have factory-installed man- ual bypass as an option. OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider brackets and shall be dynami- cally balanced for smooth operation. The 4 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently. REFRIGERANT COMPONENTS Compressors: a. Shall be Scroll compressors internally protected with internal high-pressure relief and over temperature protection. b. Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting. Coils: a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option. b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design. Refrigerant Circuit and Refrigerant Safety Components shall include: a. Balance-port thermostatic expansion valve with independent circuit feed system. b. Filter drier/strainer to eliminate any moisture or for- eign matter. c. Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge. d. The refrigeration system shall provide at least 15° F of sub-cooling at design conditions. e. All models shall have two independent circuits. f. Hot gas bypass option shall be factory-installed on compressor #1 discharge line to provide cooling in low-load applications. HGBP shall be a standard feature on VAV models and an optional feature on CV models. UNIT CONTROLS a. Unit shall be complete with self-contained low-volt- age control circuit protected by a resetable circuit breaker on the 24-volt transformer side. b. Unit shall incorporate a lockout circuit which pro- vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor. c. Loss-of-charge/Low-pressure switch. 1. High-pressure switch. 2. Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped. d. Unit shall incorporate "AUTO RESET" compressor over temperature, over current protection. e. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up. f. Unit control board shall have on-board diagnostics and fault code display. g. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 °F. h. Control board shall monitor each refrigerant safety switch independently. i. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss. GAS HEATING SECTION (J**DJN MODELS) Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redun- dant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25° F. Burners shall be of the in- shot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol- lowing minimum protection:

Johnson Controls Unitary Products

39 a. Primary and auxiliary high-temperature limit switches. b. Induced draft motor speed sensor. c. Flame roll out switch (automatic reset). d. Flame proving controls. Unit shall have two inde- pendent stages of capacity. ELECTRIC HEATING (J**DJC/E MODELS) Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required). UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0° F. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only). ELECTRICAL REQUIREMENTS All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. STANDARD LIMITED WARRANTIES • Compressor 5 Years • Heat Exchanger 10 Years • Electric Heat Element 5 Years • Other Parts 1 Year OPTIONAL OUTDOOR AIR (Shall be made available by either/or): • ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER - Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring- return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi- tioned space during normal operation. During econo- mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss. • BAS-READY ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully- modulating, spring return damper actuator. The maxi- mum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. For units with optional VAV control, free-cooling shall be available while the outdoor dry bulb temperature (OAT) remains below a programmable set-point of the control- ler. Field-installed humidity sensors for either outdoor air or outdoor & return air streams are available to provide free-cooling based on single-enthalpy or dual-enthalpy configurations, respectively. If free-cooling is available, a call for cooling shall modulate the economizer in order to maintain a supply air temperature (SAT) programmable set-point. With the use of a field-installed indoor air qual- ity sensor, the controller shall provide Demand Ventila- tion by modulating the economizer dampers to allow more outside airflow upon detection of elevated indoor CO2 concentrations above a programmable set-point. With an additional field-installed outdoor air quality sen- sor, Differential Demand Ventilation shall be provided. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water elimina- tor/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. • MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maxi- mum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi- tions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

Subject to change without notice. Printed in U.S.A.

349687-JTG-A-1007 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069 OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE • ROOF CURB - 14" high, full perimeter curb with wood nailer (shipped knocked-down). • 100% BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mount- ing hardware. Used to relieve internal air pressure through the unit. • PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required. • HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. • HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit. • BURGLAR BARS - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings. • SIDE DUCT FLANGE - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust. • HIGH STATIC DRIVE - Includes blower pulley and belt for higher CFM and/or static pressure requirements. • WOOD SKID - Allows unit to be handled with 90" forks. • ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (J25DJN/E/C only) - Contains all hood panels and the hardware for assembling. • ANTI-RECYCLE TIMER - Assures 5-minute off time between compressor cycles. • LOW AMBIENT KIT - Provides unit cooling operation down to 0°F. • COIL GUARD KIT - Guard for cooling coil. OTHER FACTORY INSTALLED OPTIONS • POWER EXHAUST OPTION - To work in conjunction with economizers. • STAINLESS STEEL HEAT EXCHANGER • STAINLESS STEEL DRAIN PAN • TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL • ELECTRONIC SINGLE ENTHALPY ECONOMIZER • DIRTY FILTER SWITCH • DOUBLE WALL • PHASE MONITOR • COIL GUARD • POWERED GFI CONVENIENCE OUTLET • NON-POWERED GFI CONVENIENCE OUTLET • BAS READY ECONOMIZER (2-10 V.D.C. ACTUATOR WITHOUT A CONTROLLER) • HINGED FILTER DOOR ACCESS AND TOOL FREE ACCESS PANELS • HINGED TOOL FREE BLOWER, BLOWER MOTOR, FILTER AND ELECTRICAL ACCESS PANELS • HIGH STATIC DRIVE • 2" PLEATED FILTERS • 4" THROW AWAY FILTERS • DISCONNECT SWITCH • SUPPLY AIR SMOKE DETECTOR • RETURN AIR SMOKE DETECTOR CONTROLS • JOHNSON LIGHT COMMERCIAL SYSTEM (LCCS) - Provides rooftop system integration for LCCS single zone, change-over bypass and VAV systems. • JOHNSON UNT 1126 ROOFTOP CONTROLLER - N2 protocol with air proving and dirty filter sensors. Hard- ware contains generic application logic; field engineering and/or modification may be required.