Kidde 1235CA Operation & User’s Manual

Text of the manual

M a n u a l

1235CA 1275CA PE120CA SINGLE AND/OR MULTIPLE STATION SMOKE ALARM For alarm models:

This unit is suitable as a Single Station and/or Multiple

Station alarm (interconnects with up to 24 devices), and has a five-year limited warranty. I M P O R TA N T: Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models of interconnect compatible alarms. Connection of Kidde

• Install smoke alarms on sloped, peaked or cathedral

ceilings at or within 0.9 m (3') of the highest point (measured horizontally). NFPA Standard 72 states: “Smoke alarms in rooms with ceiling slopes greater than 0.3 m in 2.4 m (1 foot in 8 feet) horizontally shall be located on the high side of the room.” NFPA Standard 72 states: “A row of detecto

Locations to Avoid

• Do not install within 0.9 m (3') of the following: The door to a kitchen, or a bathroom that contains a tub or shower, forced air ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high air-flow areas. • Do not place the alarm where drapes or other objects will block the sensor. Smoke must be able t

Mobile homes built in the past five to seven years have

been designed to be energy efficient. Install smoke alarms as recommended in Recommended Locations and Image 2A. In mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls