Lightolier LPTC series Specification
Read Online
Read the Lightolier LPTC series Specification online using the built-in PDF viewer.
Text of the manual
FLUORESCENT LIGHTING TRANSFER CIRCUIT
Page 1 of 2
Job Information
Type:
Job Name:
Cat. No.:
Notes:
Features
Illumination: Emergency
illumination is provided
to designated fluorescent
fixtures by transferring
backup generator or inverter
power to the AC ballast. The
designated emergency fixture
can be locally switched, and
will provide full-rated light
output when operating from
emergency power.
Housing: Housing and cover
are constructed of 24 gauge
galvanized steel. Low profile
housing allows mounting in
most low-profile fluorescent
fixtures with low-profile AC
ballast.
Operating Temperature
Range:
32°F (0°C) to 131°F (55°C)
Electronics: 120/277 VAC
dual input voltage with all
inputs fused to 3 A.
Electrical Specifications:
(120/277 VAC) .27 mA, 1.48 W
All inputs fused to 3 A
Code Compliance
UL 924 “Auxiliary Power and
Lighting Equipment” listed. UL
damp location listing standard.
NFPA 101, NEC, BOCA,
OSHA and IBC illumination
standards.
Warranty
Five years full warranty.
LPTC
1.17"
(2.97 cm)
8.0"
(20.32 cm)
1.1"
(2.79 cm)
FLUORESCENT LIGHTING TRANSFER CIRCUIT
Page 2 of 2
Philips Lightolier
e: [email protected]
t: (508) 679-8131
w: www.lightolier.com
LPTC Series August 11, 2011
Specifications are subject to change without notice.
© Koninklijke Philips Electronics N.V., 2011. All rights reserved.
Job Information
Type:
Ordering Information
Series
LPTC = Auxiliary
Power Transfer Circuit
LPTC
Typical Wiring Diagram
Shown with utility power present
BLUE
WALL SWITCH
ORANGE
BLACK
WHITE
RED
WHITE/RED
NORMAL POWER
DIST. PANEL
HOT
N
TRANSFER
SWITCH
HOT
N
AUXILIARY
POWER
AUXILIARY
POWER
EMER. POWER
DIST. PANEL
CONTROL
MODULE
AUXILIARY POWER
TRANSFER UNIT
BROWN
WHT/BLK
AC
BALLAST
HOT
N
277 V
120 V
N
Shown with programmable circuit breakers (generator off-line)
BLUE
ORANGE
BLACK
WHITE
RED
WHITE/RED
PROGRAMMABLE
CIRCUIT BKR PANEL
HOT
N
HOT
N
AUXILIARY
POWER
AUXILIARY
POWER
EMER. POWER
DIST. PANEL
CONTROL
MODULE
AUXILIARY POWER
TRANSFER UNIT
BROWN
WHT/BLK
AC
BALLAST
HOT
N
277 V
120 V
N