Process Meter K3MA-J

1 Process Meter K3MA-J Highly Visible LCD Display with 2-color (Red and Green) LEDs • Multi-range DC voltage/current input. • Front-panel key operation for easy setting. • Average processing function suppresses flicker. • Scaling, front-panel forced-zero, zero-limit functions. • Easy confirmation of max/min display. • Short 80-mm depth (measured from edge of face plate). • Finger protective cover (standard equipment) guards against electric shock. • Water- and dust-proof NEMA4X (IP66 equivalent) front panel. • Recognized to U.S. and Canadian requirements under the Component Recognition Program of UL. • CE marking. Model Number Structure ■ Model Number Legend 1. Input Type J: DC voltage/current 2. Output Type None: No output A2: 2 relay contact outputs (SPST-NO) 3. Supply Voltage 100-240VAC: 100 to 240 VAC 24VAC/VDC: 24 VAC/VDC Ordering Information ■ List of Models ■ Accessories (Order Separately) K3MA-J-@ 1 2 3 Input type Supply voltage Output Model DC voltage/current 100 to 240 VAC None K3MA-J 100-240VAC 2 relay contact outputs (SPST-NO) K3MA-J-A2 100-240VAC 24 VAC/VDC None K3MA-J 24VAC/VDC 2 relay contact outputs (SPST-NO) K3MA-J-A2 24VAC/VDC Name Shape Model Splash-proof Soft Cover K32-49SC Hard Cover K32-49HC

Process Meter K3MA-J

Specifications ■ Ratings Model K3MA-J 100-240VAC, K3MA-J-A2 100-240VAC K3MA-J 24VAC/VDC, K3MA-J-A2 24VAC/VDC Supply voltage 100 to 240 VAC 24 VAC/VDC Operating voltage range 85% to 110% of the rated supply voltage Power consumption (under maximum load) 6 VA max. 4.5 VA max. (24 VAC) 4.5 W max. (24 VDC) Insulation resistance 20 MΩ min. (at 500 VDC) between external terminal and case. Insulation provided between inputs, outputs, and power supply. Dielectric strength 2,000 VAC for 1 min between external terminal and case. Insulation provided between inputs, outputs, and power supply. Noise immunity ±1,500 V on power supply terminals in normal or com- mon mode. ±1 µs, or 100 ns for square-wave noise with 1 ns. ±480 V on power supply terminals in normal mode. ±1,500 V in common mode. ±1 µs, or 100 ns for square-wave noise with 1 ns. Vibration resistance Vibration: 10 to 55 Hz, Acceleration: 50 m/s2 5 min each in X, Y, and Z directions for 10 sweeps. Shock resistance 150 m/s2 (100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions. Ambient temperature Operating: −10°C to 55°C (with no condensation or icing) Storage: −25°C to 65°C (with no condensation or icing) Ambient humidity Operating: 25% to 85% (with no condensation) Approved safety standards UL3121-1, conforms to EN61010-1 (Pollution degree 2/overvoltage category II) Conforms to VDE0106/P100 (finger protection) EMC (EMI) EN61326+A1 Industry Emission Enclosure: CISPR 11 Group 1 class A: CISRP16-1/-2 Emission AC Mains: CISPR 11 Group 1 class A: CISRP16-1/-2 (EMS) EN61326+A1 Industry Immunity ESD: EN61000-4-2: 4 kV contact discharge 8 kV air discharge Immunity RF-interference: EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz) Electrical Fast Transient Noise: EN61000-4-4: 2 kV (power line) Immunity Burst Noise: 1 kV line to line (I/O signal line) Immunity Surge: EN61000-4-5: 1 kV (power line) 2 kV line to ground (power line) Immunity Conducted Disturbance: EN61000-4-6: 3 V (0.15 to 80 MHz) Immunity Voltage Dip/Interrupting: EN61000-4-11: 0.5 cycle, 0, 180°, 100% (rated voltage) Weight Approx. 200 g

Process Meter K3MA-J

3 ■ Characteristics ■ Measuring Ranges Process Voltage/Current Inputs ■ Input/Output Ratings Relay Contact Output Input signal DC voltage/current (0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V, ±5 V, ±10 V) A/D conversion Double integral method Sampling period 250 ms Display refresh period Sampling period (sampling times multiplied by number of measurements for averaging if average pro- cessing is selected.) Max. displayed digits 5 digits (−19999 to 99999) Display 7-segment digital display, Character height: 14.2 mm Polarity display “−” is displayed automatically with a negative input signal. Zero display Leading zeros are not displayed. Scaling function Programmable with front-panel key inputs (range of display: −19999 to 99999). The decimal point po- sition can be set as desired. Hold function Max. hold (maximum value), Min. hold (minimum value) Hysteresis setting Programmable with front-panel key inputs (0001 to 9999). Other functions Forced-zero (with front-panel key) Zero-limit Scaling teach function Display color change (green (red), green, red (green), red) OUT type change (upper limit, lower limit, upper/lower limit) Average processing (simple average) Output Relays: 2 SPST-NO Delay in comparative outputs 750 ms max. Degree of protection Front panel: NEMA4X for indoor use (equivalent to IP66) Rear case: IEC standard IP20 Terminals: IEC standard IP00 + finger protection (VDE0106/100) Memory protection Non-volatile memory (EEPROM) (possible to rewrite 100,000 times) Input Measuring range Measuring accuracy Input impedance Displayable range DC voltage 1.000 to 5.000 V ±0.1% FS ±1 digit max. (at 23±3°C) 1 MΩ min. –19999 to 99999 (with scaling function) 0.000 to 5.000 V –5.000 to 5.000 V ±0.1% FS ±1 digit max. (at 23±5°C) –10.00 to 10.00 V DC current 4.00 to 20.00 mA/ 0.00 to 20.00 mA ±0.1% FS ±1 digit max. (at 23±3°C) 45 Ω Item Resistive load (cosφ = 1) Inductive load (cosφ = 0.4, L/R=7 ms) Rated load (UL ratings) 5 A at 250 VAC, 5 A at 30 VDC 1.5 A at 250 VAC, 1.5 A at 30 VDC Rated carry current 5 A max. (at COM terminal) Max. contact voltage 250 VAC, 150 VDC Max. contact current 5 A (at COM terminal) Max. switching capacity 1,250 VA, 150 W 250 VA, 30 W Min. permissible load (P level, reference value) 10 mA at 5 VDC Mechanical life 5,000,000 times min. (at a switching frequency of 1,200 times/min) Electrical life (at an ambient temperature of 20°C) 100,000 times min. (at a rated load switching frequency of 10 times/min)

Process Meter K3MA-J

Connections ■ Terminal Arrangement ■ Block Diagram ■ Input Circuits Analog Input (DC Voltage/Current) Power supply Output terminals Input terminals A1 A2 E1 E2 E3 E4 E5 E6 E4 E5 E6 100- to 240-VAC type or 24-VAC/ VDC type (No polarity for 24-VDC connection.) Models with comparative output Voltage input For voltage input For current input OUT1 OUT2 COM COM Current input Terminal No. Name Description Operation power Connects the operation power supply. Analog input Connects the voltage or current analog input. Outputs Outputs the relay outputs. A1 A2 - E4 , E6 E5 - E1 , E2 E3 - X 5 V 12 V Input Input circuit Micro- computer Key Display Output circuit Contact output (See note.) Constant voltage circuit Power supply circuit EEPROM Note: Relay output models only. 45 Ω 4 5 6 5 A B Voltage input Current input COM To A/D A+B=1 MΩ COM To A/D

Process Meter K3MA-J

5 Operation ■ Main Functions Input Types and Ranges Note: The initial value for the input range is “4 to 20 mA (4-20).” Scaling • Analog (Process) Inputs The K3MA-J converts input signals into desired physical values. INPUT2: Any input value DISPLAY2: Displayed value corresponding to INPUT2 INPUT1: Any input value DISPLAY1: Displayed value corresponding to INPUT1 When DISPLAY1 is set for INPUT1, and DISPLAY2 is set for INPUT2, a line will be displayed joining the two points. (Raise shift, reverse scaling, plus/minus display, etc., can be adjusted as desired.) Input type (setting parameter) Function Input range (setting parameters) Setting range Input range (in-t) Selects DC voltage/current signal input 0 to 20 mA (0-20) Displayable from −19999 to 99999 with scaling function. The position of the decimal point can be set as desired. 4 to 20 mA (4-20) 0 to 5 V (0-5) 1 to 5 V (1-5) ±5 V (5) ±10 V (10) Parameter Setting value Meaning Parameter Setting value Meaning inp.1 -19999 to 99999 Input value for dsp.1 dp %.%%%% Display four digits after decimal point dsp.1 -19999 to 99999 Display value for inp.1 %%.%%% Display three digits after decimal point inp.2 -19999 to 99999 Input value for dsp.2 %%%.%% Display two digits after decimal point dsp.2 -19999 to 99999 Display value for inp.2 %%%%.% Display one digit after decimal point %%%%% No decimal point ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) Reverse scaling also possible. Input value Input value Display value Display value DISPLAY 2 DISPLAY 1 DISPLAY 1 DISPLAY 2 INPUT 1 INPUT 2 INPUT 1 INPUT 2 Teaching with actual values is possible. Instead of setting by inputting with the Up Key and Shift Key, current values can be input as scaling input values for teaching. This is useful for making settings while checking the operation status of the K3MA-J. The decimal point can be optionally displayed. When displaying the decimal point, consider the number of digits to follow the decimal point prior to setting the scaling display value. Reverse scaling, where the display value decreases as the input value increases, is also possible.

Process Meter K3MA-J

Convenient Functions Scaling Teach The parameters (inp.1, inp.2) for the K3MA-J’s initial setting level can be set using actual input values with the teaching function. After displaying the parameters, the actual input settings can be made with the following operation. OUT Types (Comparative Output Models Only) OUT 1 and OUT 2 can be set to operate in one of the three following modes in accordance with the compared values: • Upper limit (High Acting): The output is turned ON when the measurement value is greater than its set value. • Lower limit (Low Acting): The output is turned ON when the measurement value is less than its set value. • Upper and lower limits (Outside Band Acting): An upper limit (H set value) and lower limit (L set value) can be set independently. The output is turned ON when the measurement value is greater than upper-limit set value or less than the lower-limit set value. The three types of output operations shown above can be combined as desired. The following are examples of possible combinations. “T” lights to indicate that the parameter is valid for teaching. Monitor mode Teaching mode “T” flashes. Normal change “T” turns OFF. Use to register and shift to monitor mode. Use to shift to the next parameter without registering. Next parameter Upper Limit (High Acting) Lower Limit (Low Acting) OUT1/2 value Measurement value ON OFF Output ON OFF Output ON OFF Output OUT1/2 value Measurement value Measurement value Hysteresis Hysteresis Hysteresis Hysteresis Upper and Lower Limits (Outside Band Acting) OUT1/2 upper-limit value OUT1/2 lower-limit value Upper Limit 2-stage Output Threshold Output Combination of Upper Limit and Upper/Lower Limits OUT2 value OUT1 value OUT2 OUT1 ON OFF OFF ON OUT2 OUT1 ON OFF OFF ON OUT2 OUT1 ON OFF OFF ON Measurement value Measurement value Measurement value OUT2 upper-limit value OUT1 upper-limit value OUT1 lower-limit value OUT2 lower-limit value OUT2 Upper-limit value OUT1 value OUT2 Lower-limit value

Process Meter K3MA-J

7 Parameter Initialization This function returns all of the parameters to their initial values. Use this to reset the K3MA-J after returning it to its factory-set condi- tion. Average Processing Average processing stabilizes displayed values to minimize flicker by averaging the fluctuating input signals. Average processing can be performed for the measurement values in either of four steps (OFF, 2 times, 4 times, or 8 times). This is useful for ignoring rapid fluctuations, e.g., eliminating spike noise. Hysteresis (Comparative Output Models Only) The hysteresis of comparative outputs can be set to prevent chatter- ing in the output when the measurement value fluctuates finely near the OUT value. Zero-limit Function The zero-limit function changes any value below the set value to zero. This is useful when you want to change negative values to zero rather than display them, or when you want to make the display in the smallest part of the input range zero. Changing the Display Color The color of the value displayed can be set to either red or green. For comparative output models, the display color can be set to change from green to red, or from red to green, according to the status of the comparison criterion. Display Auto-return Time This function automatically returns the display to the operation level’s current value if no keys are pressed for a preset time (called the dis- play auto-return time). Move-to-Protect-Level Time The time required to shift to the protect level can be set as desired. Forced-zero Function It is possible to shift from a value to the zero point with one touch of the Up Key on the front panel (for example, when adjusting reference values). Note: Used only for releasing the forced-zero with the Protect menu. MAX/MIN Display The maximum and minimum measurement (display) values from the time the power is turned ON until the current time can be stored and displayed. This is useful, for example, when measuring the maximum value. Parameter Setting value Meaning init off --- on Initializes all parame- ters. Parameter Setting value Meaning =-lim off OFF: No zero-limit on ON: Zero-limit lim-p 0 to 99 0 to 99: Zero-limit value Upper limit (high acting) Set value Measurement value Hysteresis Output ON OFF Display Zero-limit setting value Input 8.781 100.05 113.36 OUT1 value OUT2 value Green Red Red UP MAX/MIN LEVEL MODE SHIFT Current value MAX value MIN value MAX/MIN MAX/MIN MAX/MIN Max Min MAX/MIN LEVEL MODE SHIFT UP MAX/MIN LEVEL MODE SHIFT UP MAX/MIN LEVEL MODE SHIFT UP

Process Meter K3MA-J

Nomenclature Dimensions Name Functions 1. Main indicator Displays current values, parameters, and set values. 2. Opera- tion indica- tors 1 Lit when output 1 is ON. 2 Lit when output 2 is ON. SV Lit when a set value is being displayed or changed. Max Lit when the main indicator is showing the MAX value. Min Lit when the main indicator is showing the MIN value. Z Lit during the forced-zero operation. T Lit when the teaching function is operable. Blinks while the teaching function is operating. 3. Level indicator Displays the current level that the K3MA-J is in. (See below for details.) 4. MAX/MIN Key Used to display the MAX and MIN values when a measurement value is being displayed. 5. Level Key Used to change the level. 6. Mode Key Used to allow the main indicator to indicate parameters sequentially. 7. Shift Key Used to enable a set value to be changed. When changing a set value, this key is used to move along the digits. 8. Up Key Used to change a set value. Used to set or clear a forced-zero function when a measurement value is being displayed. Level indicator Level p Protect Not lit Operation s Initial setting f Advanced-function setting 2 1 MAX/MIN LEVEL MODE SHIFT UP Max Min SV Z T 2. Operation indicators 3. Level indicator 4. MAX/MIN key 5. Level key 6. Mode key 7. Shift key 8. Up key 1. Main indicator A B C D E UP SHIFT MODE LEVEL MAX/MIN 101.2 91 96 48 1.3 12 97 85 80 44.8 45 +0.5 0 92 +0.5 0 Finger protective cover (provided) Main indicator character size Panel cut-out 7.6 mm 14.2 mm 75 min. 120 min. The K3MA-J uses M3 terminals.

Process Meter K3MA-J

9 Application Examples Installation 1. Insert the K3MA-J into the panel cut-out hole. 2. For a waterproof installation, insert the rubber gasket onto the body of the K3MA-J. 3. Fit the adaptor into the grooves on the left and right sides of the rear case, then push it until it contacts the panel to secure the K3MA-J. ■ Wiring Precautions • Use crimp terminals. • Tighten the terminal screws to a torque of approximately 0.5 N⋅m. • To avoid the influence of noise, route signal lines and power lines separately. ■ Wiring • Use the following M3 crimp terminals. ■ Unit Labels (Provided) • The unit labels are not attached to the K3MA-J. Select the desired labels from the provided sheet. Note: For scales and gauges, use the unit labels that are specified by the relevant laws or regulations. Flowrate sensor Displaying/outputting liquid level Monitoring interior tank pressure E8AA Pressure Sensor 4 to 20 mA K3MA-J Tank Discharge valve Pump E4PA Ultra- sonic Dis- placement Sensor 4 to 20 mA or 0 to 10 V K3MA-J Pump K3MA-J 4 to 20 mA Flowrate Sensor m/min mm Pa • Monitoring gas pressure • Inspection instruments in food or phar- maceutical plants • Monitoring liquid level in cleaning tanks • Monitoring sendout flowrate • Water processing devices, etc. • Water tanks, devices using chemicals, etc. 5.8 mm max. 5.8 mm max.

Process Meter K3MA-J

Precautions WARNING Do not touch any of the terminals while the power is being sup- plied. Doing so may result in electric shock. !Caution !Caution Do not disassemble the product or touch the internal components of the product while the power is being supplied. Doing so may re- sult in electric shock. !Caution !Caution Do not allow metal objects or wire cuttings to enter the product. Doing so may result in electric shock, fire, or malfunction. !Caution !Caution Perform correct settings for the product according to the control application. Failure to do so may cause unexpected operation, re- sulting in damage to the product or injury. !Caution !Caution Take safety measures, such as installing a separate monitoring system, to ensure safety even if the product fails. Product failure may prevent comparative outputs from being generated, resulting in serious accidents. Observe the following precautions to ensure safety. 1. Maintain the power supply voltage within the range specified in the specifications. 2. Maintain the load within the ratings specified in the specifications. 3. Check each terminal for correct number and polarity before con- necting it. Incorrect or reverse connections may damage or burn out internal components in the product. 4. Tighten the terminal screws securely. The recommended tighten- ing torque is 0.43 to 0.58 N⋅m. Loose screws may cause fire or malfunction. 5. Do not connect anything to unused terminals. 6. Provide a switch or circuit breaker so that operators can easily turn OFF the power supply when necessary. Also provide appro- priate indications of such devices. 7. Do not attempt to disassemble, repair, or modify the product. 8. Do not use the product where flammable or combustible gases are present. Application General Precautions 1. Do not use the product in the following locations: • Locations subject to direct radiant heat from heating equip- ment. • Locations subject to exposure to water, oil, or chemicals. • Locations subject to direct sunlight. • Locations subject to dust or corrosive gases (particularly sul- furic gas or ammonia gas). • Locations subject to severe changes in temperature. • Locations subject to icing or condensation. • Locations subject to shock or vibration. 2. Do not block heat dissipation around the product, i.e., provide suf- ficient space for heat dissipation. 3. Ensure that the rated voltage is reached within two seconds after the power is turned ON. 4. Conduct aging for 15 minutes min. after power is turned ON for correct measurement. 5. Do not touch the slit sections or terminals while the power is being supplied to prevent the product from being affected by static electricity. 6. Do not lay heavy objects on the product during use or storage. Doing so may deform or deteriorate the product. 7. Do not use paint thinner for cleaning. Use commercially available alcohol. Mounting • Mount the product to a panel that is 1 to 8 mm thick. • Install the product in a horizontal position. • Use crimp terminals that match screw sizes. Noise Prevention • Install the product as far as possible from devices that generate strong, high-frequency fields (such as high-frequency welders or sewing machines) or surges. • Install surge absorbers or noise filters on nearby devices that gen- erate noise (particularly, motors, transformers, solenoids, magnet coils, and other devices that have a high inductance component). • To prevent inductive noise, separate the terminal block wiring for the product from high-voltage or high-current power lines. Do not route the wiring for the product in parallel with or tie it in a bundle with power lines. Take the following countermeasures against inductive noise in input lines. Analog Signal Inputs • When using a noise filter for the power supply, check for the voltage and current and install it as close as possible to the Process Meter. • Do not install the product near radios, television sets, or wireless devices. Doing so may cause reception interference. Increasing Service Life • Do not use the product in locations where the temperature or humidity exceeds the ratings or where condensation may occur. When installing the product in a panel, be sure that the temperature around the product (not the temperature around the panel) does not exceed the ratings. The product service life depends on the ambient temperature. The higher the ambient temperature, the shorter the service life. To extend the product service life, lower the temperature inside the Process Meter. • Use and store the product within the temperature and humidity ranges given in the specifications. When gang-mounting Process Meters or arranging them vertically, heat generated by the Process Meters will cause the internal temperature to rise, reducing the ser- vice life. In such cases, consider forced cooling methods, such as using a fan to circulate air around the Process Meters. Do not, how- ever, allow only the terminals to be cooled. Doing so will increase measurement error. • The life of the output relays is greatly affected by the switching capacity and switching conditions. Use these relays within their rated load and electrical life. The contacts may fuse or burn if they are used past their electrical life. + − Line filter Power supply input Process Meter Signal input Process Meter Power supply input Surge absorber + − Signal input 2-conductor shielded cable Process Meter

Process Meter K3MA-J

11 Operating Procedures ■ Levels “Level” refers to a grouping of parameters. The following table lists the operations that are possible in each of the levels, and the diagram tells how to move between levels. There are some parameters that are not displayed for certain models. Note: The move-to-protect-level time can be set in the advanced-function setting level. Level name Function Measurement Protect Setting lockouts. Continue Operation Displaying current values, setting/clearing forced-zero function, and setting OUT 1/2 values. Continue Initial setting Making initial settings of input type, scaling, output operating action, and other parameters. Stopped Advanced-function setting Setting average processing, display color settings, and other ad- vanced-function parameters. Stopped + -1234.5 + Power ON Operation level Protect level Initial setting level Advanced-function setting level Time set by user (See note.) 1 s min. 1 s min. 1 s min. Flashing stops if key is released. Continue to press the key for 2 s min. 1 s min. Password "−0169" Indicates change of level.

Process Meter K3MA-J

■ Parameters − − − − − − For models with the comparative output function MODE MODE MODE MODE MODE MODE MODE Set one of these. Set one of these. Current value OUT1 value OUT1 upper-limit value OUT1 lower-limit value OUT2 upper-limit value OUT2 lower-limit value OUT2 value Note: 1. Some parameters are not displayed for certain models. 2. The K3MA-J will stop measurement if the level is changed to the initial setting level or the advanced-function setting level. 3. If the input range is changed, some parameters are set to default values. Therefore, set the input range first. 4. Settings displayed in reversed colors are defaults. Power ON Operation level

Process Meter K3MA-J

13 − / / / / / − − − − − − − − − − − / / / / − − − − Press Level Key for more than 3 s. Press Level Key for more than 1 s. Initial setting level Input type MODE MODE MODE MODE MODE MODE MODE MODE MODE OUT2 type Move to advanced- function setting level OUT1 type Decimal point position Scaling display value 2 Scaling input value 2 Scaling display value 1 Scaling input value 1 Press Level Key for more than 1 s. Advanced-function setting level Enter password "−0169" Parameter initialization Average processing OUT1 hysteresis OUT2 hysteresis Models with the compar- ative output function MODE MODE MODE MODE MODE MODE MODE MODE MODE Zero-limit Zero-limit value Display color change Display auto-return time Move-to- protect- level time Unit: times Zero-limit Green (red) Green Red (green) Red Unit: s Unit: s Upper Limit Lower Limit Upper/Lower Limits Upper Limit Lower Limit Upper/Lower Limits When zero- limit is ON

Process Meter K3MA-J

Operation/Adjustment Lockouts Restricts key operations for operation level and adjustment level. • Initial setting is 0. • This cannot be displayed on models not equipped with the compar- ative output function. Setting Level Lockout Restricts shifting to initial setting level or advanced-function setting level. Setting Change Lockout Restricts setting changes by key operation. When this lockout is set, it is no longer possible to shift to a setting change mode. However, all protect level parameters can still be changed. Forced-zero Lockout Restricts the setting or release of a forced-zero by front-panel key operation. ■ Initial Settings / / / / / / Press Level Key + Mode Key for more than 1 s. Operation level Protect level Press Level Key + Mode Key for more than preset time. MODE MODE MODE MODE Operation/adjustment lockouts Setting level lockout Setting change lockout Forced-zero shift lockout Parameter Setting Operation level Current value display Set value display oapt 0 Allowed Allowed 1 Allowed Allowed 2 Allowed Prohibited Parameter Setting Shift to initial setting level Shift to advanced- function setting level icpt 0 Allowed Allowed 1 Allowed Prohibited 2 Prohibited Prohibited Parameter Setting Setting change by key operation wtpt off Allowed on Prohibited Parameter Setting Setting/release of forced-zero by key operation =rpt off Allowed on Prohibited If required, shift to the advanced-function setting level to set the number of measurements for averaging, hysteresis values, auto-zero limit value, display color change, display auto-return time, or move-to-protect-level time. Press the Level Key for less than 1 s min. to return to the operation level. Specify set value of OUT 1 and 2. Select the input type. Set the scaling values and specify output operating action as required. Press the Level Key for 3 s min. to move to the initial setting level. Power ON Measurement starts.

Process Meter K3MA-J

15 ■ Setting Example Initial Settings The settings for the following example are shown here. Example: Tank pressure display Here, the pressure inside the tank is to be displayed in units of 0.1 kPa. • Pressure Sensor: E8AA-M10 Measuring range: 0 to 980 kPa, output 4 to 20 mA 1. Set the K3MA-J input type to the 4 to 20 mA input range. Parameter: in-t (input type), Setting value: 4-20 2. Set the display values for the corresponding input values. Set the scaling as shown below for the following correspondence: input 4 mA-->display 0.0, input 20 mA-->display 980.0 Parameter Setting value inp.1 (scaling input value 1) 4.00 dsp.1 (scaling display value 1) 00000 inp.2 (scaling input value 2) 20.00 dsp.2 (scaling display value 2) 09800 dp (decimal point position) %%%%.% Note: The decimal point position here refers to the position in the number after scaling. When setting the scaling display value, it is necessary to consider the number of digits to be displayed past the decimal point. ■ Troubleshooting When an error occurs, error details will be displayed on the main indicator. Confirm the error from the main indicator and take the appropriate coun- termeasures. 1 2 0 to 980 kPa 4 to 20 mA E8AA-M10 Pressure Sensor K3MA-J-A2 24VAC/VDC Max Min SV MAX/MIN LEVEL MODE SHIFT UP ( ) ( ) ( ) ( ) Display value DISPLAY 2 DISPLAY 1 INPUT 1 INPUT 2 Input value Level display Main indicator Error contents Countermeasures Not lit e111 RAM memory error Repair is necessary. Consult your OMRON sales representative. 5 e111 EEPROM memory error When this error is displayed, press the Level Key for 3 sec- onds, and the settings will be restored to the factory set- tings. If the error cannot be recovered, repair is necessary. Con- sult your OMRON sales representative. Not lit Flashes s.err You will see this indication when turning ON the product the first time after purchase. This is be- cause the input signal value is 0 mA at that time even though the range is factory set to 4 to 20 mA. At the initial setting level, set the input type and other pa- rameters according to your application. Input error Promptly change the input voltage/current to a value that falls within the measurement range. If the error cannot be recovered, repair is necessary. Con- sult your OMRON sales representative. Not lit Flashes 99999 The scaling display value exceeds 99999. Promptly change the input to a value that falls within the specified range. The scaling value may be inappropriate. Review the scal- ing value at the initial setting level. Not lit Flashes The scaling display value is lower than −19999. Promptly change the input to a value that falls within the specified range. The scaling value may be inappropriate. Review the scal- ing value at the initial setting level. 19999 -

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. N108-E1-04A OMRON Corporation Industrial Automation Company Industrial Devices and Components Division H.Q. Measuring Components Department Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7080/Fax: (81)75-344-7189 Printed in Japan 0903-0.4M (1001) (B) Warranty and Limitations of Liability ■ WARRANTY OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DIS- CLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. ■ LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMER- CIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLI- GENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations ■ SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the custom- er’s application or use of the products. At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products. • Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. • Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. • Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.