isar + programmer
Your Ideal installation and servicing guide
ENGINEERED FOR PEACE OF MIND
When replacing any part on this appliance, use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
HE24, HE30, HE35
For details of document amendments, refer to page 3
For the very latest copy of literature for specification purposes please visit our website
www.idealboilers.com where you will be able to download the relevant information in pdf format.
October 2006 UIN 202851 A01
202851-1new.pmd
17/11/2006, 07:40
1
isar + programmer - Installation and Servicing
DOCUMENT AMENDMENTS
Relevant Installation changes implemented in this book from Mod Level .....................................A01 (Oct 06)
Caradon Ideal Limited reserve the right to vary specification without notice
202851-1new.pmd
17/11/2006, 07:40
3
isar + programmer - Installation and Servicing
GENERAL
isar
HE24+P
HE30+P
HE35+P
Gas supply
2H - G20 - 20mbar
Gas Supply Connection
Rc 1/2 (1/2” BSP female)
Injector Size
Stereomatic 5.6mm dia.
5.7mm dia
Inlet Connection
Domestic Hot Water
15mm copper compression
Outlet Connection
Domestic Hot Water
15mm copper compression
Flow Connection
Central Heating
22mm copper compression
Return Connection
Central Heating
22mm copper compression
Flue Terminal Diameter
mm (in)
100 (4)
Average Flue Temp-Mass Flow Rate
(DHW)
66oC-10g/s
74
oC - 12 g/s
82oC-14g/s
Maximum Working Pressure (Sealed Systems)
bar (lb/in2)
2.65 (38.5)
Maximum Domestic Hot Water Inlet Pressure
bar
(lb/in2)
10.0 (145)
Minimum Domestic Hot Water Inlet Pressure
bar
(lb/in2)
0.5 (7)
Electrical Supply
230 V ~ 50 Hz.
Power Consumption
148 W
148 W
152 W
Fuse Rating
External : 3A Internal : T3.15A L250 V
Water content
Central Heating
litre (gal)
2.0 (0.44)
Domestic Hot Water
0.5 (0.11)
Packaged Weight
kg (lb)
52 (115)
52 (115)
53 (117)
Maximum Installation Weight
kg (lb)
42.5 (94)
43 (95)
43.5 ( 96)
Boiler Casing Size
Height
mm (in)
687 (27)
Width
mm (in)
390 (15 3/8)
Depth
mm (in)
278 (11)
Table 1 - General Data
Note. Gas consumption is calculated using a
calorific value of 38.7 MJ/m3 (1038 Btu/ft3) gross
or 34.9 MJ/m3 (935 Btu/ft3) nett
To obtain the gas consumption at a different
calorific value:
a. For l/s- divide the gross heat input (kW) by
the gross C.V. of the gas (MJ/m3)
b. For ft
3/h - divide the gross heat input (Btu/h)
by the gross C.V. of the gas (Btu/ft3)
Key to symbols
GB =
United Kingdom
IE = Ireland
(Countries of destination)
PMS = Maximum operating pressure of water
C13 C33 C53 = A room sealed appliance designed for connection via ducts to a
horizontal or vertical terminal, which admits fresh air to the burner
and discharges the products of combustion to the outside through
orifices which, in this case, are concentric. The fan is up stream
of the combustion chamber.
I2H
= An appliance designed for use on 2nd Family gas, Group H only.
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which
it has been calculated have been certified by a notified body.
CAUTION. To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components
Table 2 - Performance Data - Central Heating
Maximum DHW Input :
HE24+P
HE30+P
HE35+P
Nett CV
kW
24.3
30.2
36.0
(Btu/h)
(82 900)
(103 000)
(122 800)
Gross CV
kW
27.0
33.5
39.9
(Btu/h)
(92 100)
(114 400)
(136 200)
Gas Consumption
l/s
0.7
0.87
1.03
(ft3/h)
(89.0)
(110)
(131)
Maximum
kW
23.4
29.3
35.2
DHW Output
(Btu/h)
(80 000)
(100 000)
(120 000)
DHW Flow Rate
l/min
9.6
12.0
14.4
at 35°C temp. rise.
(gpm)
(2.1)
2.6
(3.2)
DHW Specific Rate
l/min
11.2
14.0
16.8
(gpm)
(2.5)
(3.1)
(3.7)
Table 3 - Performance Data - Domestic Hot Water
Boiler Input :
Max.
Min.
Boiler Input ‘Q’
Nett CV
kW
24.4
9.1
(Btu/h)
(83 300)
(31 000)
Gross CV
kW
27.1
10.1
(Btu/h)
(92 500)
(34 400)
Gas Consumption
l/s
0.70
0.26
(ft3/h)
(89.0)
(33.1)
Boiler Output :
Non Condensing
kW
23.4
8.8
70oC Mean Water temp.
(Btu/h)
(80 000)
(30 000)
Condensing
kW
25.1
9.6
40oC Mean Water temp.
(Btu/h)
(85 700)
(32 800)
Seasonal efficiency*
(SEDBUK)
Band A [90.1]%
NOx Classification
Class 5
202851-1new.pmd
17/11/2006, 07:40
4
isar + programmer - Installation and Servicing
GENERAL
Boiler size
G.C. Appliance No.
PI No.
(Benchmark No.)
HE24+P
47 348 43
0063 BO 3317
HE30+P
47 348 44
0063 BO 3317
HE35+P
47 348 45
0063 BO 3317
CONTENTS
Air Supply ....................................................................... 8
Benchmark Commissioning Checklist ..................... 62
Boiler Clearances ......................................................... 9
Boiler Exploded Diagram ............................................ 13
Condensate Drain ........................................... 10, 21-22
Electrical Connections ............................................... 27
Electrical Supply ......................................................... 10
Extension Ducts - Fitting ............................................. 19
Fault Finding ........................................................... 52-56
Flow Wiring Diagram .................................................. 30
Flue Fitting .................................................................... 18
Flue Installation ............................................................. 8
Gas Safety Regulations ................................................ 7
Gas Supply ..................................................................... 8
Installation ............................................................. 12-33
Mandatory Requirements....................................... 7-10
Pump
.......................................................................... 49
Safe Handling ................................................................ 6
Servicing ................................................................ 34-38
Short List of Parts....................................................... 57
Thermostatic Radiator Valves ................................... 10
Water and Systems ........................................... 8,10-12
Water Connections ............................................... 24-25
Water Treatment ......................................................... 12
Wiring Diagrams ................................................... 27-30
isar HE +P
Natural Gas only
Destination Country: GB, IE
time
P R O G R A M M E R
prog
prog
select
select
+
-
Boiler
Page
Make and model .......................................................5
Appliance serial no. on data badge ...................... 13
SEDBUK No. % .........................................................4
Controls
Time and temperature control to heating ............. 28
Time and temperature control to hot water .......... 28
Heating zone valves ..............................................n/a
TRV's ...................................................................... 10
Auto bypass ........................................................... 10
Boiler interlock ....................................................... 10
For all boilers
Flushing to BS.7593 .............................................. 12
Inhibitor .................................................................. 12
Central heating mode
Heat input ................................................to be calculated
For assistance see Technical Helpline on the back page
Page
Burner operating pressure ....................................n/a
Central heating flow temp. ...... measure and record
Central heating return temp. ... measure and record
For combination boilers only
Scale reducer .........................................................n/a
Hot water mode
Heat input ..........................................to be calculated
Max. operating burner pressure ..............................n/a
Max. operating water pressure ........... measure & record
Cold water inlet temp ..................... measure & record
Hot water outlet temp. .................... measure & record
Water flow rate at max. setting ............ measure & record
For condensing boilers only
Condensate drain .................................................. 21
For all boilers:
complete, sign & hand over to customer
For GB, to comply with Building Regulations Part L1 (Section 6 in Scotland) the boiler should be fitted in accordance with the
manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be
demonstrated by completing and signing the Benchmark Commissioning Checklist.
BENCHMARK COMMISSIONING CHECKLIST DETAILS
NOTE TO THE INSTALLER: COMPLETE
THE BENCHMARK COMMISSIONING
CHECKLIST AND LEAVE THESE
INSTRUCTIONS WITH APPLIANCE
202851-1new.pmd
17/11/2006, 07:40
5
isar + programmer - Installation and Servicing
GENERAL
INTRODUCTION
The isar + programmer range of boilers is a wall mounted, full sequence,
automatic spark ignition, low water content, fanned flue, high efficiency,
condensing, combination gas boiler.
A seven day programmer is built into the boiler, capable of 3 timed periods
per day.
Note.Due to the high efficiency of the boiler a plume of water vapour will form
at the terminal during operation.
Central heating (CH) output is fully modulating with a range of 8.8 to 23.4kW
(30,000 to 80,000 Btu/h)
Instantaneous domestic hot water (DHW) output is also fully modulating with
a maximum of :
HE24 23.4kW (80,000 Btu/h)
HE30 29.3kW (100,000 Btu/h)
HE35 35.2kW (120,000 Btu/h)
The boiler is supplied fully assembled with DHW plate heat exchanger,
diverter valve, circulating pump, pressure gauge, safety valve and CH
expansion vessel.
Variable CH and DHW temperature controls are fitted on the user control and
the boiler features a DHW preheat facility.
The boiler casing is of white painted mild steel with the user controls
capable of being mounted remotely from the boiler if the option is required.
The boiler temperature controls are visible at the bottom RHS of the front panel.
The heat exchanger is of cast aluminium.
The boiler is suitable for connection to fully pumped, sealed water systems
ONLY. Adequate arrangements for completely draining the system by
provision of drain cocks MUST be provided in the installation pipework.
Pipework from the boiler is routed downwards as standard, but may be
routed upwards behind the boiler using the stand-off frame (supplied in a
separate kit).
OPERATION
With no demand for CH, the boiler fires only when DHW is drawn off, or
periodically for a few seconds without any DHW draw-off, in order to maintain
the DHW calorifier in a heated condition.
When there is a demand for CH, the heating system is supplied at the
selected temperature of between 30 oC and 82oC, until DHW is drawn off.
The full output from the boiler is then directed via the diverter valve to the
plate heat exchanger to supply a nominal DHW draw-off of
HE24 9.6 l/min at 35 oC temperature rise.
HE30 12 l/min at 35 oC temperature rise.
HE35 14.4 l/min at 35 oC temperature rise.
The DHW draw off rate specified above is the nominal that the boiler flow
regulator will give. Due to system variations and seasonal temperature
fluctuations DHW flow rates/temperature rise will vary, requiring adjustment
at the draw off tap.
At low DHW draw-off rate the maximum temperature is limited to 65 oC by the
modulating gas control.
Refer also to Frame 1 - 'Boiler Water Circuit Diagrams'
An additional feature incorporated within the boiler controls is boiler frost
protection.
If the flow temperature drops below 7
oC the pump will run. If the temperature
continues to drop and goes below 4
oC, the boiler will fire until the
temperature exeeds 7
oC.
The boiler features a comprehensive diagnostic system which gives detailed
information on the boiler status when operating, and performance of key
components to aid commissioning and fault finding.
SAFE HANDLING
This boiler may require 2 or more operatives to move it to its installation site,
remove it from its packaging base and during movement into its installation
location. Manoeuvring the boiler may include the use of a sack truck and
involve lifting, pushing and pulling.
Caution should be exercised during these operations.
1
BOILER WATER
CIRCUIT DIAGRAMS
Central Heating Circuit
Expansion
vessel
Automatic
air vent
Gas valve
Plate heat
exchanger
Pump
Safety
relief valve
Condensate
'S' trap
Diverter
valve
Water
pressure
gauge
Sump
Fan
Burner
CH Flow
Gas
Condensate
drain
Discharg
pipe
CH Return
Domestic Hot Water Circuit
Expansion
vessel
Automatic
air vent
Heat
exchanger
Gas valve
Pump
Safety
relief valve
Condensate
'S' trap
Diverter
valve
Water
pressure
gauge
Sump
Fan
Burner
DHW Hot out
Gas
Condensate drain
Discharge pipe
Ecl 2768
DHW Cold in
Plate heat
exchanger
Heat
exchanger
Operatives should be knowledgeable in handling
techniques when performing these tasks and the
following precautions should be considered:
•
Grip the boiler at the base.
•
Be physically capable.
•
Use PPE as appropriate, e.g. gloves, safety
footwear.
During all manoeuvres and handling actions, every
attempt should be made to ensure the following
unless unavoidable and/or the weight is light.
•
Keep back straight.
•
Avoid twisting at the waist.
•
Avoid upper body/top heavy bending.
•
Always grip with the palm of the hand.
•
Use designated hand holds.
•
Keep load as close to the body as possible.
•
Always use assistance if required.
202851-1new.pmd
17/11/2006, 07:40
6
isar + programmer - Installation and Servicing
GENERAL
SAFETY
Current Gas Safety (installation and use) regulations or rules
in force:
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance with
the relevant requirements of the:
•
Gas Safety (Installation and Use) Regulations
•
The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (northern Ireland).
•
The Water Fittings Regulations or Water byelaws in Scotland.
•
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent
Person and installed in accordance with the current edition of
I.S.813 "Domestic Gas Installations", the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
Detailed recommendations are contained in the following British
Standard Codes of Practice:
BS. 5440:1
Flues (for gas appliances of rated input not
exceeding 70 kW).
BS. 5440:2
Ventilation (for gas appliances of rated input not
exceeding 70 kW).
BS. 5449
Forced circulation hot water systems.
BS. 5546
Installation of gas hot water supplies for
domestic purposes (2nd Family Gases)
BS. 6798
Installation of gas fired hot water boilers of rated
input not exceeding 70 kW.
BS. 6891
Low pressure installation pipes.
Health & Safety Document No. 635.
The Electricity at Work Regulations, 1989.
The manufacturer’s notes must NOT be taken, in any way, as
overriding statutory obligations.
IMPORTANT. These appliances are CE certificated for safety
and performance. It is, therefore, important that no external
control devices, e.g. flue dampers, economisers etc., are
directly connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by Caradon Ideal Limited in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler or its
manufacture.
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable
of adequately supporting the weight of the boiler and any
ancillary equipment.
The boiler may be fitted on a combustible wall and insulation
between the wall and the boiler is not necessary, unless
required by the local authority.
For electrical safety reasons there must be no access available
from the back of the boiler.
The boiler must not be fitted outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should
be fitted in accordance with the Institute of Gas Engineering
document IGE/UP/7:1998.
Bathroom Installations
This appliance is rated IP20.
The boiler may be installed in any room or internal space,
although particular attention is drawn to the requirements of the
current IEE (BS.7671) Wiring Regulations and, in Scotland, the
electrical provisions of the building regulations applicable in
Scotland, with respect to the installation of the boiler in a room
or internal space containing a bath or shower. For IE reference
should be made to the current ETCI rules for electrical
installations and I.S. 813:2002.
If the appliance is to be installed in a room containing a bath or
shower then, providing water jets are not going to be used for
cleaning purposes (as in communal baths/showers), the
appliance can be installed in Zone 3, as detailed in BS.7671.
Compartment Installations
A compartment used to enclose the boiler should be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, provided
that it is modified for the purpose.
In both cases, details of essential features of cupboard /
compartment design, including airing cupboard installation,
are to conform to the following:
z
BS 6798 (No cupboard ventilation is required - see ‘Air
Supply’ for details).
z
The position selected for installation MUST allow adequate
space for servicing in front of the boiler.
OPTIONAL EXTRA KITS
z
Flue Extension Ducts (1000mm long).
HE24-up to 6m
HE30-up to 6m
HE35-up to 3m
z
Flue Finishing Kit
z
90
o Elbow Kit (maximum per installation).
HE24-upto 4 elbows
HE30-upto 4 elbows
HE35-upto 2 elbows
z
45
o Elbow Kit (maximum per installation).
HE24-upto 4 elbows
HE30-upto 4 elbows
HE35-upto 2 elbows
z
Roof Flue Kit (to a maximum of 8m).
HE24-upto 8m
HE30-upto 8m
HE35-upto 5m
z
Powered Vertical Flue Kit (to a maximum primary flue
length of 8m + a maximum secondary flue length of 6m)
HE24
HE30
HE35
Primary flue (m)
8
8
5
4
3
2
1
Secondary flue (m)
6
6
3
6
6
6
6
z
Twin Fluing Kit (up to a maximum of 46m combined total
flue and airducts)
z
Remote User Controls Kit
z
Boiler Stand-off Kit
z
Siphon Kit
z
Valve Cover Kit
z
System Frost Stat Fitting Kit
202851-1new.pmd
17/11/2006, 07:40
7
isar + programmer - Installation and Servicing
GENERAL
z
For the minimum clearances required for safety and
subsequent service, see the wall mounting template and
Frame 2. In addition, sufficient space may be required to
allow lifting access to the wall mounting plate.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an
adequate supply of gas. An existing service pipe must NOT be
used without prior consultation with the local gas supplier.
The boiler MUST be installed on a gas supply with a governed
meter only.
A gas meter can only be connected by the local gas supplier or
by a CORGI registered engineer. In IE by a competent person.
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the
rate of gas supply required.
N.B.
The principle of the 1:1 gas valve ensures that the isar
HE range is able to deliver it’s full output at inlet pressures
down to 14mb. However if dynamic pressures below 20mb are
experienced ensure this is adequate for ALL other gas
appliances in the property.
IMPORTANT.
Installation pipes must be fitted in accordance with BS.6891. In
IE refer to IS.813:2002. Pipework from the meter to the boiler
MUST be of an adequate size, i.e. no longer than 20m and not
less than 15mm O.D.
The complete installation MUST be tested for gas soundness
and purged as described in the above code.
FLUE INSTALLATION
Pluming will occur at the terminal so terminal positions where
this could cause a nuisance should be avoided.
The flue must be installed in accordance with the
recommendations of BS. 5440-1: 2000.
In IE refer to I.S. 813:2002.
The following notes are intended for general guidance:
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in
Table 4.
4. Where the lowest part of the terminal is fitted less than 2m
(6'6") above a balcony, above ground or above a flat roof to
which people have access then the terminal MUST be
protected by a purpose designed guard.
Terminal guards are available from boiler suppliers. (Ask for
TFC flue guard model no. K6 - round, plastic coated). In
case of difficulty contact:
Grasslin (UK) Ltd.
Tel. + 44 (0) 01732 359 888
Tower House, Vale Rise
Fax. + 44 (0) 01732 354 445
Tonbridge. Kent TN9 1TB
www.tfc-group.co.uk
Ensure that the guard is fitted centrally.
5. The flue assembly shall be so placed or shielded as to
prevent ignition or damage to any part of any building.
6. The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1") to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS. 5440-1:2000.
IMPORTANT. It is absolutely essential to ensure, in practice,
that products of combustion discharging from the terminal
cannot re-enter the building or any other adjacent building
through ventilators, windows, doors, other sources of natural
air infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF,
labelled as 'unsafe' until corrective action can be taken.
TERMINAL
The terminal assembly can be adapted to accommodate
various wall thicknesses. Refer to Frame 12 .
AIR SUPPLY
It is NOT necessary to have a purpose-provided air vent in the
room or internal space in which the boiler is installed. Neither
is it necessary to ventilate a cupboard or compartment in which
the boiler is installed, due to the low surface temperatures of
the boiler casing during operation; therefore the requirements
of BS 6798, Clause 12, and BS 5440:2 may be disregarded.
WATER CIRCULATION SYSTEM
IMPORTANT.
A minimum length of 1 metre of copper pipe MUST be fitted to
both flow and return connections from the boiler before
connection to any plastic piping.
The central heating system should be in accordance with
BS.6798 and, in addition, for smallbore and microbore
systems, BS.5449.
WATER TREATMENT - see Frame 6
Flue Terminal Positions
Min. Spacing*
1.
Directly below,above or alongside an opening
window, air vent or other ventilation opening.
300mm (12")
2.
Below guttering, drain pipes or soil pipes.
25mm ( 1")*
BS5440-1 2000
75mm (3")
3.
Below eaves.
25mm (1")*
BS5440-1 2000
200mm (8")
4.
Below balconies or a car port roof.
25mm (1")*
BS5440-1 2000
200mm (8")
5.
From vertical drain pipes or soil pipes.
25mm (1")*
BS5440-1 2000
150mm (6")
6.
From an internal or external corner or to a
25mm (1")*
boundary along side the terminal.
BS5440-1 2000
300mm (12")
7.
Above adjacent ground, roof or balcony level.
300mm (12")
8.
From a surface or a boundary facing the terminal.
600mm (24")
9.
From a terminal facing a terminal.
1,200mm (48")
10. From an opening in a car port
(e.g. door or window) into dwelling.
1,200mm (48")
11. Vertically from a terminal on the same wall.
1,500mm (60")
12. Horizontally from a terminal on the wall.
300mm (12")
Vertical Terminals
13. Above the roof pitch with roof slope of all angles.
300mm (12")
Above flat roof.
300mm (12")
14. From a single wall face.
600mm (24")
From corner walls.
1000mm (40")
Twin Flue Applications
15. Centre distance between air inlet and flue
outlet ducts.
120mm (5")
Table 4 - Balanced Flue Terminal Position
* Only one reduction down to 25mm is allowable per installation
otherwise BS5440-1 2000 dimensions must be followed.
202851-1new.pmd
17/11/2006, 07:40
8
isar + programmer - Installation and Servicing
GENERAL
time
P R O G R A M M E R
prog
select
+
-
time
P R O G R A M M E R
prog
select
+
-
time
P R O G R A M M E R
prog
select
+
-
nm8426
2
BOILER DIMENSIONS, SERVICES & CLEARANCES
all dimensions in mm (in)
The boiler connections are made on the boiler piping frame.
Refer to Frames 27-29.
The following minimum clearances must be maintained for
operation and servicing.
Additional space will be required for installation, depending
upon site conditions.
Side and Rear Flue
a. Provided that the flue hole is cut accurately, e.g. with a core
drill, the flue can be installed from inside the building
where wall thicknesses do not exceed 600mm (24").
Front clearance
The minimum front clearance when built in to a cupboard is 5mm
(1/4") from the cupboard door but 450mm (17 3/4") overall
clearance is still required, with the cupboard door open, to allow for
servicing.
N.B. The boiler will not fit into a standard depth wall unit. In order for
it to do so the plastic fascia should be removed. See Frame 39.
*
Bottom clearance
Bottom clearance after installation can be reduced to 5mm.
However, 100mm must be available for servicing.
Where the space into which the boiler is going to be
installed is less than the length of flue required the flue
must be fitted from the outside.
Installation from inside ONLY
b. If a core boring tool is to be used inside the building the
space in which the boiler is to be installed must be at least
wide enough to accommodate the tool.
REAR FLUE ONLY
MIN. Top clearance required = 145 mm (5 3/4")
SIDE FLUE ONLY
Horizontal length of flue
Top clearance
from centre line of boiler
required (MIN.)
to outside wall
Dim. A
HE24
HE30
HE35
0.5 m
0.5 m
0.5 m
160 mm
(6 5/16")
1.0 m
1.0 m
1.0 m
170 mm
(6 11/16)
1.5 m
1.5 m
1.5 m
185 mm
(7 1/4")
1.5 m
1.5 m
1.5 m
200 mm
( 7 7/8")
2.5 m
2.5 m
2.5 m
210 mm
(8 1/4")
3.0 m
3.0 m
3.0 m
225 mm
(8 7/8")
3.5 m
3.5 m
N/A
250 mm
(9 7/8")
4.0 m
4.0 m
N/A
260 mm
(10 1/4")
4.5 m
4.5 m
N/A
265 mm
(10 7/16")
5.0 m
5.0 m
N/A
275 mm
(10 13/16")
5.5 m
5.5 m
N/A
290 mm
(11 3/8")
6.0 m
6.0 m
N/A
300 mm
(11 13/16")
202851-1new.pmd
17/11/2006, 07:40
9
isar + programmer - Installation and Servicing
GENERAL
General
1. The installation must comply with all relevant national and
local regulations.
2. The installation should be designed to work with flow
temperatures of up to 82
oC.
3. All components of the system must be suitable for a working
pressure of 3 bar and temperature of 110
oC. Extra care should
be taken in making all connections so that the risk of leakage
is minimised.
The following components are incorporated within the
appliance:
a.
Circulating pump.
b.
Safety valve, with a non-adjustable preset lift pressure of
3 bar.
c.
Pressure gauge, covering a range of 0 to 6 bar.
d.
An 8-litre expansion vessel, with an initial charge pressure
of 0.75 bar.
4. 'Make-up' Water. Provision must be made for replacing water
loss from the system, either :
a.
From a manually filled 'make-up' vessel with a readily
visible water level. The vessel should be mounted at
least 150mm above the highest point of the system and
be connected through a non-return valve to the system,
fitted at least 150mm below the 'make-up' vessel on the
return side of the radiators.
Notes
a. The method of filling, refilling, topping up or flushing
sealed primary hot water circuits from the mains via a
temporary hose connection is only allowed if acceptable
to the local water authority.
b. Antifreeze fluid, corrosion and scale inhibitor fluids
suitable for use with boilers having aluminium heat
exchangers may be used in the central heating system.
Advice should be sought from a local water treatment
company.
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems
utilising full thermostatic radiator valve control of temperature
in individual rooms should also be fitted with a room
thermostat controlling the temperature in a space served by
radiators not fitted with such a valve as stated in BS. 5449.
Central heating systems controls should be installed to
ensure the boiler is switched off when there is no demand
for heating or hot water.
When thermostatic radiator valves are used, the space
heating temperature control over a living / dining area or
hallway having a heating requirement of at least 10% of the
boiler heat output should be achieved using a room
thermostat, whilst other rooms are individually controlled by
thermostatic radiator valves. However, if the system employs
thermostatic radiator valves on all radiators, or two port
valves without end switches, then a bypass circuit must be
fitted with an automatic bypass valve to ensure a flow of
water should all valves be in the closed position.
ELECTRICAL SUPPLY
WARNING.
This appliance must be earthed.
Wiring external to the appliance MUST be in accordance with
the current I.E.E. (BS.7671) Wiring Regulations and any local
regulations which apply. For IE reference should be made to
the current ETCI rules for electrical installations.
The point of connection to the mains should be readily
accessible and adjacent to the boiler.
CONDENSATE DRAIN Refer to Frames 22 & 49.
A condensate drain is provided on the boiler. This drain must be
connected to a drainage point on site. All pipework and fittings in
the condensate drainage system MUST be made of plastic - no
other materials may be used.
IMPORTANT.
Any external runs must be insulated
The drain outlet on the boiler is standard 21.5mm (3/4”) overflow
pipe.
3
SYSTEM REQUIREMENTS - Central Heating
Safety valve setting
bar
3.0
Vessel charge pressure
bar
0.5 to 0.75
System pre-charge pressure bar
None
1.0
System volume
Expansion vessel
(litres)
volume (litres)
25
1.6
1.8
50
3.1
3.7
75
4.7
5.5
100
6.3
7.4
125
7.8
9.2
150
9.4
11.0
175
10.9
12.9
190
11.9
14.0
200
12.5
14.7
250
15.6
18.4
300
18.8
22.1
For other system volumes
multiply by the factor across
0.063
0.074
or
b.
Where access to a 'make-up' vessel would be difficult,
by pre-pressurisation of the system.
The maximum cold water capacity of the system
should not exceed 143 litres, if not pressurized.
However, if the system is to be pressurized, the
efficiency of the expansion vessel will be reduced and
a larger vessel (or smaller system volume) may be
necessary. If the capacity of the vessel is not
considered sufficient for this, or for any other reason,
202851-1new.pmd
17/11/2006, 07:40
10
isar + programmer - Installation and Servicing
GENERAL
4
SYSTEM REQUIREMENTS - CH (continued) and Hot Water
an additional vessel MUST be installed on the return
to the boiler.
Guidance on vessel sizing is given in Frame 3.
5. Filling. The system may be filled by the following method:
a.
Through a temporary hose connection from a 'draw-off'
tap, supplied from a service pipe under mains pressure.
Where the mains pressure is excessive a pressure
reducing valve must be used to facilitate filling.
When installing the filling device it must be connected as
shown below, to fully comply with the water regulations.
This may involve the fitting of an additional WRAS
approved isolator valve to the mains supply.
i. Thoroughly flush out the whole system with
cold water.
ii. Fill and vent the system until the pressure
gauge registers 1.5 bar and examine for leaks.
iii. Check the operation of the safety valve by
raising the water pressure until the valve lifts.
This should occur within 0.3 bar of the preset lift
pressure.
iv. Release water from the system until the
minimum system design pressure is reached;
1.0 bar if the system is to be pre-pressurised.
Water Flow Rate and Pressure Loss
Max CH Output
kW
23.4
(Btu/h)
(80 000)
Water flow rate
l/sec
0.37
(gal/min)
4.8
Temperature Differential
oC
15
(
oF)
(27)
Head available for
m.w.g.
2.3
system pump.
(ft.w.g.)
7.5
DOMESTIC HOT WATER
1. The domestic hot water service must be in accordance
with BS 5546 and BS 6700.
2. Refer to Table 1 for minimum and maximum working
pressures.
3. The boilers are suitable for connection to most types of
washing machine and dishwasher appliances.
4. When connecting to suitable showers, ensure that:
a.
The cold inlet to the boiler is fitted with an approved
anti-vacuum or syphon non-return valve.
b.
Hot and cold water supplies to the shower are of equal
pressure.
CH Return
Ecl 6053
Hose unions
Mains
water supply
Temporary hose
(disconnect after filling)
Additional
stop valve
Double check valve
assembly
(note direction of flow)
The boiler does not normally need a bypass but at least some
radiators on the heating circuit, of load of at least 10% of the
minimum boiler output, must be provided with twin lockshield
valves so that this minimum heating load is always available.
See note regarding thermostatic radiator valves on page 10.
Note. Systems incorporating zone valves which could
completely cut off the flow through the system must also
include a bypass.
BALANCING
1. Set the programmer to ON.
Close the manual or thermostatic valves on all radiators,
leaving the twin lockshield valves (on the radiators referred
to above) in the OPEN position.
5
SYSTEM BALANCING
Turn up the room thermostat and adjust these lockshield
valves to give boiler flow and return temperatures not
more than 20 oC apart.
These valves should now be left as set.
2. Open all manual or thermostatic radiator valves and
adjust the lockshield valves on the remaining radiators,
to give around 15 oC temperature drop at each radiator.
3. Adjust the room thermostat and programmer to
NORMAL settings.
5. Hard Water Areas
Where the water hardness exceeds 200mg/litre, it is
recommended that a proprietary scale reducing device is
fitted into the boiler cold supply within the requirements of
the local water company.
IMPORTANT
Provision MUST be made to accommodate the expansion of
DHW contained within the appliance, if a non-return valve is
fitted to the DHW inlet.
202851-1new.pmd
17/11/2006, 07:40
11
isar + programmer - Installation and Servicing
6
WATER TREATMENT
CENTRAL HEATING
The isar range of boilers have an ALUMINIUM alloy heat
exchanger.
IMPORTANT.
The application of any other treatment to this product
may render the guarantee of Caradon Ideal Limited.
Caradon Ideal Limited recommend Water Treatment in
accordance with the Benchmark Guidance Notes on
Water Treatment in Central Heating Systems.
If water treatment is used Caradon Ideal Limited recommend
only the use of FERNOX-COPAL or MB1, GE BETZ SENTINEL X100
or Salamander Corrosion Guard inhibitors and associated
water treatment products, which must be used in accordance
with the manufacturers' instructions.
Notes.
1. It is most important that the correct concentration of the
water treatment products is maintained in accordance with
the manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing. BS
7593:1992 details the steps necessary to clean a domestic
heating system.
3. In hard water areas, treatment to prevent lime scale may be
necessary - however the use of artificially softened water is
NOT permitted.
4. Under no circumstances should the boiler be fired before
the system has been thoroughly flushed.
DOMESTIC HOT WATER
In hard water areas where main water can exceed 200ppm
Total Hardness (as defined by BS 7593:1993 Table 2) a
scale reducing device should be fitted into the boiler cold
supply within the requirements of the local water company.
The use of artificially softened water, however, is not
permitted.
Caradon Ideal Limited recommend the use of Fernox
Qantomat, GE Betz Sentinel Combiguard and Calmag
CalPhos I scale reducing devices, which must be used in
accordance with the manufacturers' instructions.
19.
Gas control valve.
20.
Fan bracket.
21.
Orifice plate.
23.
Control thermistor (flow/return)
24.
Overheat thermostat.
25.
Ignition electrode.
26.
Flame detection electrode.
32.
Kit - Trap and seal.
35.
User control.
36.
Primary controls (PCB).
39.
Mains switch.
44.
Piping frame.
51.
Mains connector.
53.
Turret gasket kit.
54.
Spark generator.
55.
Ignition lead.
57.
CH stub pipe.
1.
Front casing panel.
2.
Boiler sealing panel.
3.
Sump cover.
4.
Bottom casing panel.
5.
Flue sensing nipple.
6.
Return pipe.
8.
Flue manifold.
9.
Flue manifold fixing.
10.
Interpanel.
11.
Burner.
12.
Combustion chamber insulation.
13.
Heat exchanger.
14.
Injector and housing.
15.
Venturi assembly.
16.
Fan assembly.
17.
Automatic air vent.
18.
Gas service cock.
7
BOILER ASSEMBLY - Exploded View Legend
59.
Flow restrictor.
60.
DHW inlet/outlet pipe.
61.
Pressure relief valve.
62.
Expansion vessel.
63.
Expansion vessel pipe.
64.
Pressure gauge.
65.
DHW thermistor.
66.
*Diverter valve head.
67.
*Diverter valve.
68.
*Diverter valve manifold.
69.
*Pump (Wilo pump shown).
70.
Pump manifold.
71.
DHW plate heat exchanger.
75.
Control box clamp.
103.
Dry fire thermistor.
For further information contact:
Fernox Manufacturing Co. Ltd
Cookson Electronics
Forsyth Road
Sheerwater
Woking
Surrey GU21 5RZ
+44 (0) 1799 521133
Sentinel Performance Solutions
The Heath Business & Technical Park
Runcorn
Cheshire WA7 4QXD
Tel: 0800 389 4670
www.sentinel-solutions.net
Salamander Engineering Ltd
Unit 24 Reddicap Trading Estate
Sutton Coldfield
West Midlands B75 7BU
Tel: +44 (0) 121 3780952
Calmag Ltd.
Unit 4-6, Crown Works
Bradford Road
Sandbeds, Keighley
West Yorkshire BD20 5LN
Tel: +44 (0) 1535 210 320
*Note. Two waterset assemblies are used on this appliance, WILO and CP. These units are not interchangeable.
202851-1new.pmd
17/11/2006, 07:40
12
isar + programmer - Installation and Servicing
8
BOILER ASSEMBLY - Exploded View
8
5
44
53
14
13
15
62
59
18
64
4
75
35
36
66
67
23
23
68
24
71
17
26
25
3
19
57
60
6
11
12
40
103
39
32
21
16
69
70
61
57
60
51
65
10
9
20
2
63
1
nm8423
Data badge
94
WILO
pump
shown
time
P R O G R A M M E R
prog
prog
select
select
+
-
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
13
isar + programmer - Installation and Servicing
9
UNPACKING
The boiler is supplied fully assembled in one Pack A, together with a standard flue
assembly for lengths up to 650mm, rear or side flue outlet, in Pack B.
Unpack and check the contents.
Pack A Contents
A
Boiler
B
Hardware Pack Box
C
Pre-piping Frame
D
These Installation/Users
Instructions
E
Wall Mounting Template
F
1 Year Guarantee
Pack B Contents
Flue turret.
Flue terminal.
Flue support cutting aid.
Ecl 2354
Flue terminal
Flue turret
nm8424
B
C
E
A
D
F
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm8452
A
B
C
D
E
F
G
H
I
J
K
L
R
M
N
O
P
Q
Hardware Pack Contents
A
Isolation valve c/w pressure gauge - 1 off
B
Isolation valve c/w drain - 1 off
C
Bulkhead connector - 1 off
D
Restrictor valve - 1 off
E
Compression gas cock - 1 off
F
Valve securing clip 22mm - 2 off
G Valve securing clip 15mm - 3 off
H
Pre-piping frame support bracket - 1 off
I
S-trap hose - 1 off
J
15mm olive - 1 off
K
Pressure relief valve nut - 1 off
L
No. 14x2in woodscrew - 4 off
M Wallplug - 4 off
N
Fibre washer 19 ID x 26 OD - 3 off
O 12mm sealing washer - 3 off
P
Gas line sealing washer - 1 off
Q Hole plug white - 6 off
R
Mains connector - 1 off
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
14
isar + programmer - Installation and Servicing
1. Ensure the boiler is on a sound flat
surface.
2. Carefully remove the strapping.
3. Fold back the top flaps to gain access to:
z
Instructions.
z
Wall mounting template.
z
1 year guarantee.
z
Pre-piping frame.
4. Remove the instructions and read
thoroughly before unpacking the product.
5. When ready for installation lift off the
cardboard carton.
10
PACKAGING REMOVAL
11
BOTTOM AND FRONT PANEL REMOVAL
1. Remove the screws from the
underside of the boiler.
2. Pull the RHS of the panel
down, slide it to the right and
withdraw.
3. Remove the screws from
bottom of the front panel.
4. Lift panel up and off top
pegs.
Boiler
Hardware
pack box
Pre-piping
frame
nm8425
Retaining
clip
2
1
3
time
P R O G R A M M E R
prog
select
+
-
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
15
isar + programmer - Installation and Servicing
FLUE KITS
Pack B - supplied as standard
Pack D - optional extension kit for side flue or rear flue outlet.
Finishing Kit - Supplied as an optional extra.
Refer to 'Flue Extension Ducts'
IMPORTANT. The boiler MUST be installed in a vertical position
Dimension X -
Wall thickness.
Dimension L
-
Wall thickness plus boiler spacing.
Dimension S -
Stand-off frame depth = 33mm
12
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED
Notes.
1. The flue duct MUST be inclined at 1.5 degrees
to the horizontal to allow condensate to drain
back into the boiler and out through the
condensate drain.
2. If the boiler is to be installed with upward piping
routed behind the boiler then the optional
stand-off kit should be used. Care must be
taken when cutting the ducts and marking the
wall to suit this condition.
Note. MAXIMUM FLUE LENGTHS:
HE24 AND 30
- 6M (HORIZONTAL FLUE)
HE35
- 3M (HORIZONTAL FLUE)
HE24 AND 30
- 8M (ROOF FLUE)
HE35
- 5M (ROOF FLUE)
HE 24 AND 30
- 14M TOTAL (POWERED VERTICAL FLUE)
HE 35
- 8M TOTAL (POWERED VERTICAL FLUE)
HE24 AND HE30
- 20M TOTAL (AIR PLUS FLUE DUCT-60/60 TWIN FLUE KIT)
HE24, HE30 AND HE35 - 46M TOTAL (AIR PLUS FLUE DUCT - 80/80 TWIN FLUE KIT)
90O ELBOW KIT 60/100 (EQUIVALENT FLUE LENGTH RESISTANCE = 1M)
45O ELBOW KIT 60/100 (EQUIVALENT FLUE LENGTH RESISTANCE = 0.6M)
Total Flue length dimension
Flue
Rear flue
Side flue
Extra packs
Boiler
dim. X+160
dim. L+195
required
size
Up to
650 mm
Up to
650 mm
none
HE24,30 & 35
Up to 1600 mm
Up to
1600 mm
Pack D - 1 off
HE24,30 & 35
Up to 2550 mm
Up to
2550 mm
Pack D - 2 off
HE24,30 & 35
Up to 3500 mm
Up to
3500 mm
Pack D - 3 off
HE24 & 30
Up to 4450 mm
Up to
4450 mm
Pack D - 4 off
HE24 & 30
Up to 5400 mm
Up to
5400 mm
Pack D - 5 off
HE24 & 30
Up to 6000 mm
Up to
6000 mm
Pack D - 6 off
HE24 & 30
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
16
isar + programmer - Installation and Servicing
FLUE OUTLET
Note.
The template shows the positions of the fixing holes and
the flue hole centres for standard installation and for using
the stand-off kit. Care MUST be taken to ensue the correct
holes are drilled.
1. Separate the templates.
2. Tape template A into the selected position.
3. Ensure squareness by hanging a plumbline as shown. If
fitting a side flue extend the flue centre line onto the side
wall and tape template B into the selected position.
4. Mark onto the wall the following:
a The piping frame screw positions (choose one from
each group).
b. The position of the flue duct hole (see diagram below
and template).
Note. Mark the centre of the hole as well as the
circumference
5. Remove the template from the wall.
14
WALL MOUNTING TEMPLATE
13
FLUE ASSEMBLY - Exploded View
An optional flue duct extension kit is required for
wall thicknesses greater than :
Side
455mm (18").
Rear
490mm (19 1/4").
Rear flue arrangement shown
Ecl 2360
V
A
B
Extended centre line
LEGEND
1. Duct assembly.
2. Flue turret.
3. Turret gasket.
4. M5 x 10 pozi screw.
5. Turret clamp.
202851-1new.pmd
17/11/2006, 07:40
17
isar + programmer - Installation and Servicing
FLUE OUTLET
15
PREPARING THE WALL
IMPORTANT.
Ensure that, during the cutting operation, masonry
falling outside of the building does not cause damage
or personal injury.
1. Cut the flue hole (preferably with a 5" core boring
tool), ensuring that the hole is square to the wall.
Both wall faces immediately around the cut hole
should be flat.
2. Drill 4 holes with a 7.5mm / 8mm masonry drill
and insert the plastic plugs, provided, for the
piping frame.
3. Locate 4 No.14 x 50mm screws in the piping
frame (one at each side, in any of the 3 holes
provided at each side) and screw home.
16 CUTTING THE FLUE - REAR Wall thicknesses of 114 to 490mm
Notes.
a. If using the extension ducts go to Frame 18.
b. If the stand-off frame is used it is essential add 33mm to
'X' the measured wall thickness when marking the flue
(this will allow for the fitted frame).
1. Measure and note wall thickness X. Refer to Frame 12.
2. Add 90mm (3 1/2") to dimension X and, measuring from
the ring, cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all the way
around.
4. Cut the inner tube to a length 20mm (3/4") longer to aid
engagement, using the cardboard support.
17 CUTTING THE FLUE - SIDE Wall thicknesses of 114 to 455mm
Note. If using the extension ducts go to Frame 18.
1. Measure and note side flue length L. Refer to
Frame 12.
2. Add 125mm (5") to dimension L and, measuring
from the ring, cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all
the way around.
4. Cut the inner tube to a length 20mm (3/4") longer to
aid engagement, using the cardboard support.
2011
X
Section
through wall
Note. Check all of the hole
positions before drilling.
Side flue only
5" diameter hole
Rear flue only
5" diameter hole
202851-1new.pmd
17/11/2006, 07:40
18
isar + programmer - Installation and Servicing
FLUE OUTLET
1. A maximum of 6 extension ducts for the HE24/
HE30 and a maximum of 3 extension ducts for
the HE35 (one suitably cut) plus the standard
flue duct may be used together.
2. Flue extensions of greater length than 1m (39")
should be supported with the bracket provided,
suitably adjusted. Refer to Frames 18 and 25.
19
FLUE EXTENSION DUCTS - continued
1. Remove the cardboard support aid from the flue and place
safely to one side.
2. Fit the inner flue extension duct onto the inner flue duct.
3. Fit the outer flue extension duct onto the outer air duct.
4. Using the clamp provided clamp the flue lengths together.
5. Repeat steps 1-4 if a second flue extension is required.
6. Measure and mark the flue length required onto the flue,
measuring from the ring near the terminal.
7. To ensure a square cut, mark the flue all the way around.
8. Cut to length using the cardboard support aid.
9. Remove the cardboard and deburr the metal edges.
20
FITTING THE KIT
18
FLUE EXTENSION DUCTS - For flue lengths greater than 650mm
Pack D Flue extension duct kit contents
Note. Side flue shown
General arrangement
Flue duct support
Flue support cutting aid
(shown folded up)
Wall plugs - 4 off
Extension duct & clamp
1.0m (39") long
No. 10 x2" wood screw - 4 off
Ecl 1244
Use a maximum of 6m extended flue ONLY (HE24 & 30)
Measure from
this RING
2
3
9
Ecl 2540
Use a maximum of 3m extended flue ONLY (HE35)
202851-1new.pmd
17/11/2006, 07:40
19
isar + programmer - Installation and Servicing
FLUE OUTLET
21
FITTING THE PIPING FRAME AND VALVES
(Rear Flue outlet shown)
TO FIT THE PRE-PIPING FRAME DIRECTLY TO THE WALL
•
Insert wall plugs.
•
Put the screws into the wall plugs and leave 10mm proud
•
Hang the frame onto the screws (take care to use the
same hole position from each group as previously chosen
with the wall template) and tighten up.
•
Locate the support bracket on the piping frame.
Note. Service connections may be made now, before mounting the boiler, if required. Refer to Frames 27-29.
Piping
frame
Wall
plug
Screw
(10mm proud)
Support
bracket
nm8443
Note.
Isolating valves are supplied separately in the hardware pack box.
Fit to the piping frame BEFORE mounting the boiler.
Piping
frame
Wall
plug
Screw
(10mm proud)
Support
bracket
nm8444
TO FIT THE PRE-PIPING FRAME USING THE STAND-OFF FRAME
OPTION KIT (To allow pipework to be taken upwards)
•
Put the screws into the wall plugs and leave 10mm proud.
•
Hang the stand-off frame onto the screws and tighten up.
•
Fasten the piping frame to the stand-off frame with the
6mm screws provided.
•
Locate the support bracket on the piping frame.
Note.
If the clearances above and below the boiler are less than
the length of the pipes it will be necessary to position the
pipes behind the wall mounting plate BEFORE the plate is
screwed to the wall.
nm8453
Valve securing
clip 15mm
Valve securing
clip 22mm
Valve securing
clip 22mm
Isolation valve
c/w pressure
gauge
Bulkhead
connector
Compression
gas cock
Restrictor
valve
Isolation valve
c/w drain
1. Remove valves and clips from
the hardware pack box.
2. Assemble valves to the frame
and secure in place with clips
provided.
3. Make sure to fit valves in
correct order shown.
202851-1new.pmd
17/11/2006, 07:40
20
isar + programmer - Installation and Servicing
22
CONDENSATE DRAIN
Refer also to the British Gas document: 'Guidance Notes for
the Installation of Domestic Gas Condensing Boilers' (1989).
Before mounting the boiler on the wall, the condensate drain
(provided in the h/ware pack) must be connected from the
boiler ‘S’ trap to a drainage point, preferably within the
building.
Ensure that the condensate trap is full of water before
commissioning the boiler . Refer to Frame 26.
The routing of the drain must be made to allow a minimum
fall of 1 in 20 away from the boiler, throughout its length.
The drainage pipework must be arranged so that obstruction
(e.g. through freezing) of external drainage pipe does not give
rise to spillage within the dwelling.
IMPORTANT.
If excessive external pipework cannot be avoided an
additional siphon kit and insulation are recommended to
prevent possible freezing.
All pipework and fittings in the condensate drain system
must be made of plastic. No other materials may be used.
The drain outlet on the boiler is standard 21.5mm overflow
pipe. This size must not be reduced in any part of its length.
BOILER
cla7771
75mm trap
Sink constitutes
air break
DRAIN
Ground Level
Open end of pipe
direct into gulley
below grating but
above water level
BOILER
cla7772
75mm trap
DRAIN
Sink
Ground Level
Open end of pipe
direct into gulley
below grating but
above water level
1. INTERNAL TO SINK WASTE
UPSTREAM OF SINK WASTE
TRAP
2. INTERNAL TO SINK WASTE
DOWNSTREAM OF SINK
WASTE TRAP (PREFERRED
METHOD)
* If drain termination is to soil
stack, a 75mm trap will be
required
Note. ALL EXTERNAL PIPE RUNS MUST BE INSULATED
23
CONDENSATE PIPE TERMINATION CONFIGURATIONS
continued . . . .
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
21
isar + programmer - Installation and Servicing
24
CONDENSATE PIPE TERMINATION CONFIGURATIONS . . . continued
BOILER
cla7773
3. INTERNAL CONNECTION TO SOIL AND VENT STACK
* Make connection to SVP using a solvent welded saddle
BOILER
External
wall
Ground Level
Termination
to Soak away
cla7774
minimum
500mm
BOILER
External
wall
Ground Level
Open end of pipe
direct into gulley
below grating but
above water level
DRAIN
cla7775
4. TERMINATION TO SOAK AWAY
5. TERMINATION TO DRAIN / GULLEY
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
22
isar + programmer - Installation and Servicing
25
MOUNTING THE BOILER
IMPORTANT.
1. Before mounting the boiler on the wall place it on
its left hand side, fit the 'S' trap hose moulding/nut
and fold the hose to facilitate fitting into pre-piping
frame.
2. Ensure that the plastic plugs are removed from
both the CH and DHW pipes before mounting.
N.B. Some spillage of water may occur from the
pipework when mounting the boiler to the frame.
3. Lift the boiler onto the wall mounting frame,
locating it over the tabs at the top of the frame.
4. Lower the boiler into position, engaging it onto the
support bracket.
Note. Ensure the condensate drain pipe is correctly
positioned through the hole in the pre-piping
frame before continuing.
5. Using the fibre washers supplied in the hardware
pack box, engage and then tighten the 4 water
unions.
6. Engage and tighten the gas union, ensuring that
the blue fibre washer is in place. DO NOT
overtighten.
7. Connect a pipe to the safety drain outlet using the
nut and olive supplied in the boiler hardware pack
box.
nm8024
time
P R O G R A M M E R
prog
select
+
-
1
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
23
isar + programmer - Installation and Servicing
C.H. FLOW
C.H. RETURN
nm8454
22mm copper pipe
Isolating valve
(shown in the
open position)
Piping frame
Drain
point
22mm copper pipe
Isolating valve
(shown in the
open position)
Pressure gauge
Condensate drain pipe located here.
Compression
gas cock
27
WATER CONNECTIONS - CH
Notes.
1. For heating loads in excess of
60,000 Btu/h use 28mm x 22mm
connectors to connect the boiler
flow and return pipes to 28mm
system pipework.
2. Do not subject any of the isolating
valves to heat as the seals may be
damaged.
nm7898
2
1
3
26
CONNECTING THE FLUE TO THE BOILER
Note.
Before fitting the flue turret fill the condensate trap within the
boiler by pouring a cupful of water into the flue outlet A.
Take care to ensure that the water is only poured into the flue
outlet, and does not spill into the boiler casing.
1. Locate the flue into the turret.
2. Insert the flue assembly
through the prepared hole
in the wall.
3. Locate the flue turret on
the top of the boiler,
ensuring that the turret
gasket is in place.
Check that the flue seal
‘A’ located in the top of
the flue manifold is secure
and giving an effective
seal.
4. Secure the flue turret on top of
the boiler by inserting the open
ends of the turret clamp under the 2
studs and fixing it in the middle with
the single M5 x 10mm pozi-hex screw
provided.
5. Flues over 1 metre long.
Fix the flue support bracket to the wall, using the 4 wall
plugs and wood screws.
NB. The space bracket will utilise one fixing hole only
whilst used in conjunction with the stand-off option.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
24
isar + programmer - Installation and Servicing
nm8456
Piping
frame
Blue fibre washer
Compression
gas cock
(shown in the
open position)
GAS IN
D.H.W. Inlet
D.H.W. Outlet
nm8455
15mm copper pipe
15mm copper pipe
Regulator / Filter
'O' Ring
Piping frame
Isolating valve
(shown in the
open position)
Compression
gas cock
Outlet
connector
Retaining
screw
Cross bar
IMPORTANT. The gas service cock is sealed
with a non-metallic blue fibre washer so must
not be overheated when making capillary
connections.
Refer to Frame 2 for details of the position of
the gas connection.
N.B.
The principle of the 1:1 gas valve
ensures that the isar HE range is able to
deliver it’s full output at inlet pressures
down to 14mb. However if dynamic
pressures below 20mb are experienced
ensure this is adequate for ALL other gas
appliances in the property.
A boiler gas supply pipe length of 20m and
not less than 15mm O.D. can be connected
to the boiler via the gas service cock union.
Ensure that the gas supply pipe does not
foul the boiler casing.
Refer to Frame 38 or 'Servicing' for details of
the pressure test point position.
29
GAS CONNECTION
28
WATER CONNECTIONS - DHW
Note. The DHW inlet
isolating valve incorporates
a flow regulator / filter. It should
be inspected to ensure no blockage
is evident.
1. To remove, turn off the valve, undo the
retaining screw and pull out the filter
by grasping the crossbar with pliers.
2. Reassemble in reverse order,
inserting in the direction of the arrow.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
25
isar + programmer - Installation and Servicing
31
FILLING
Central Heating
1. Remove the sealing panel. Refer to Frames 44 & 45.
2. Swing the control box down into the servicing position.
Refer to Frame 46.
3. Ensure that the CH isolating valves are open.
4. Fill and vent the system. Check for water soundness.
Note.
The domestic hot water flow rate is
automatically regulated to a maximum:
HE24 =
9.6 l/m (2.1 gpm)
HE30 = 12.0 l/m (2.6 gpm)
HE35 = 14.4 l/m (3.2 gpm)
The safety valve is located at the bottom RHS of the boiler.
The discharge pipe should be positioned so that the discharge of water or steam cannot create a hazard to the occupants
of the premises or damage the electrical components and wiring.
30
SAFETY VALVE DRAIN
IMPORTANT - when filling:
a. Remove the diverter valve actuator (refer to Frame 62)
and depress the spindle several times during filling.
Replace diverter valve actuator.
b. When filling, there may be a slight water leak from the air
vent therefore electrical connections should be
protected.
c. Bleed any air from the pump and ensure that it is free to
rotate.
For Wilo Pump:
To ensure the pump is free to rotate:
i.
Remove the vent plug
ii.
Using a screwdriver, rotate the shaft several times
For CP Pump:
To ensure the pump is free to rotate:
i.
Unscrew the central cap.
ii.
Gently pull the cap out to engage with the shaft.
iii. Rotate the cap and spindle.
Note. Some slight water leakage will occur.
Domestic Hot Water
1. Fully open all DHW taps and ensure that water flows freely
from them.
2. Close all taps.
To vent the pump:
Repeat steps i. and ii. Move the fitting from side to side to
allow air to vent. Ensure the cap is fully retightened.
iii. Replace the vent plug.
Note. Some slight water leakage will occur.
Pump
Automatic
air vent
Central
Cap
nm8412
c.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
26
isar + programmer - Installation and Servicing
32
ELECTRICAL CONNECTIONS
Wiring should be 3 core PVC insulated cable, not less than
0.75 mm2 (24 x 0.2mm), and to BS 6500 Table 16. For IE
reference should be made to the current ETCI rules for
electrical installations.
Connection must be made in a way that allows complete
isolation of the electrical supply such as a double pole
switch having a 3mm (1/8") contact separation in both
poles, or a plug and socket, serving only the boiler and
system controls. The means of isolation must be
accessible to the user after installation.
WARNING. This appliance MUST be earthed.
A mains supply of 230 V ~ 50 Hz is required.
The fuse rating should be 3A. All external controls and wiring
must be suitable for mains voltage.
Wiring external to the boiler MUST be in accordance with the
current I.E.E. (BS.7671) Wiring Regulations and any local
regulations.
1. Route the mains cable into the bottom rear centre of
the boiler.
2. Wire the permanent live supply into the 5-way
remote plug terminals, L3, N &
.
IMPORTANT.
A permanent live is ESSENTIAL in order for the
advanced diagnostic controls to function correctly.
33
INTERNAL WIRING
3. Wire the normal room thermostat switched live supply into
L2 or connect L1 and L2 via external control switching as
shown in Frame 34. In either case remove the wire link
fitted to L1 to L2.
4. Secure the mains lead with the cable clamp.
5. Connect the mains lead connector. Ensure it is fully
located.
L3
N
L2
L1
Mains Connector
(supplied in hardware pack)
Socket
(fixed to boiler)
Remove link when connecting external programmer.
nm8071
Ecl 1542
A pictorial wiring diagram is shown in Frame 35.
Note.
Ensure that the lengths of the current carrying conductors
are shorter than the earth conductor so that if the cable
slips in its anchorage the current carrying conductors
become taut before the earth conductor.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
27
isar + programmer - Installation and Servicing
34
EXTERNAL ELECTRICAL CONTROLS
Wiring External to the Boiler
The fuse rating should be 3A.
Wiring external to the boiler MUST be in accordance with the
current I.E.E. (BS.7671) Wiring Regulations and any local
regulations.
Room Thermostat
If the thermostat has a neutral connection, use it (it provides
for more energy efficient operation by reducing switching
temperature differentials).
Frost Protection
If parts of the pipework run outside the house or if the boiler
will be left off for more than a day or so then a frost thermostat
should be wired into the system.
The frost thermostat should be sited in a cold place but
where it can sense heat from the system.
L3
L2 L1
N
Room 'stat
N
if required
nm8428
A
Mains in
System
controls
System
Controls
L
N
nm8429
Diagram A
shows an application to boilers fitted with a room
thermostat only.
Diagram B
shows the fitting of a frost thermostat. An option kit
must be purchased to allow this.
Earths are not shown for clarity but must never be omitted.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
28
isar + programmer - Installation and Servicing
nm8413
Dry fire
thermistor
Diverter
Valve
Permanent
black
link
br
b
bk
y/g
y/g
35
PICTORIAL WIRING DIAGRAM
LEGEND
b
- blue
bk - black
br - brown
gy - grey
or - orange
pk - pink
r
- red
v
- violet
w - white
y
- yellow
y/g - yellow/green
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
29
isar + programmer - Installation and Servicing
Dry fire thermistor
nm8414
Diverter
Valve
36
FUNCTIONAL FLOW WIRING DIAGRAM
WARNING. Whilst effecting the required gas soundness test and purging air from the gas installation,
open all windows and doors, extinguish naked lights and DO NOT SMOKE.
A. Electrical Installation
1. Checks to ensure electrical safety should be carried out by
a competent person.
2. ALWAYS carry out the preliminary electrical system checks,
i.e. earth continuity, polarity, resistance to earth and short
circuit, using a suitable test meter.
B. Gas Installation
1. The whole of the gas installation, including the meter,
should be inspected and tested for soundness and purged
in accordance with the recommendations of BS. 6891.
In IE refer to IS.813:2002.
2. Purge air from the gas installation by the approved
methods only.
37
COMMISSIONING AND TESTING
LEGEND
b
- blue
bk - black
br - brown
gy - grey
or - orange
pk - pink
r
- red
v
- violet
w - white
y
- yellow
y/g - yellow/green
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
30
isar + programmer - Installation and Servicing
nm8430
time
P R O G R A M M E R
prog
prog
select
select
+
-
B
T
S
K
H
E
D
G
J
L
M
N
Q
F
R
P
C
38
INITIAL LIGHTING
1. Check that the system has been filled and that the boiler is
not airlocked. Ensure the automatic air vent cap (K) is open.
Note.
It is important the burner is not operated before the system is
fully vented of air. If it is necessary to operate the appliance
pump to assist venting of the air this must be done with the
gas service cock turned off.
2. Refit the boiler sealing panel. Refer to Frame 45.
3. Check that all the drain cocks are closed and that the CH
and DHW isolating valves (P, R and N) are OPEN.
4. Check that the electrical supply is OFF.
5. Check that the boiler on/off switch (A) is off.
6. Carefully align the user control and push gently into place.
Secure with the single screw located underneath.
7. Check that the gas service cock (F) is OPEN.
8. Slacken the screw in the inlet pressure test point (E) and
connect a gas pressure gauge via a flexible tube.
9. Swing the control box to the working position and secure
with the clamp.
10. Connect the low voltage electrical lead from the user control
to the control box (refer to Frame 46).
11. Screw the control into position.
12. Switch the electricity supply ON and check all external controls
are calling for heat.
13. CENTRAL HEATING
Switch the boiler on/off switch (A) to ON. The boiler control
should now go through its ignition sequence until the burner
is established.
LEGEND
A. Boiler On/Off switch
B. LED display
C. Select (reset) button
D. Injector pressure test point
E. Inlet pressure test point
F.
Gas service cock
G. Casing pressure test point
H. Overheat thermostat
J. Control thermistor (flow)
K. Automatic air vent
L. Control box (Servicing
position)
M. Pressure gauge
N. CH Flow isolating valve
P.
CH Return isolating valve
Q. DHW outlet
R. DHW inlet
S. Spark generator
T.
Condensate drain
14. If the boiler does not light after 3 attempts the fault code
“LF” will be displayed, Press the select button (C) and
the boiler will repeat its ignition sequence.
When the burner is established the flame 'Burner On'
indicator will be illuminated, the LED display will show
the radiator status symbol.
The itime programmer display
The LCD display has a number of indicators to show the
operation of the boiler. In stand-by mode there are no
additional indicators other than the time of day. Each channel,
CH and DHW, status is shown as OFF, ON, TIMED or
ADVANCE (see users guide). In a timed on period the status
of the boiler is:
Radiator symbol indicats CH demand.
Tap symbol indicates DHW or preheat demand.
Flame symbol indicates burner status.
In error conditions the following indicates the error:
Blocking error is proceeded by “H” on the LCD display.
Locking out error is proceeded by a “L” on the LCD display.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
31
isar + programmer - Installation and Servicing
40
GENERAL CHECKS
39
INITIAL LIGHTING - continued
15. DOMESTIC HOT WATER
Ensure programmer is in an ‘ON’ DHW period. With the
boiler firing, fully open a DHW tap.
The boiler should continue to run and the LED display
should show the tap status symbol.
16. Ensure that with the boiler operating the dynamic gas
pressure is able to obtain maximum output. Refer to
Table 2.
N.B. The principle of the 1:1 gas valve ensures that the
isar HE range is able to deliver it’s full output at inlet
pressures down to 14mb. However if dynamic pressures
below 20mb are experienced ensure this is adequate for
ALL other gas appliances in the property.
IMPORTANT
The gas input to the burner is regulated by the gas valve
according to the air flow produced by the fan. It is NOT
user-adjustable. Any interference to sealed settings on
the gas valve will adversely affect operation and render
our warranty void.
DOMESTIC HOT WATER (DHW) MODE
1. With no call for CH or DHW the boiler should fire for a
short period to preheat the DHW plate heat exchanger.
The LCD display symbol will be:
returning to
none
when the burner switches off.
Notes.
a.
If no DHW is drawn off, the boiler will fire periodically
for a short time, to maintain the plate heat exchanger
temperature.
b.
DHW pre-heat will be inhibited during programmed
DHW off periods.
2. Fully open all DHW taps in turn and ensure that water
flows freely from them.
The LCD display symbols will be:
then
when the burner lights.
Make the following checks for correct operation in:
3. Close all taps except the furthest one from the boiler and
check that the boiler is firing at maximum rate.
This is factory set to give a DHW temperature rise of
approximately 35oC at the flow rate stated on page 6 under
“operation”.
4. Reduce the DHW draw-off rate to about 3 l/min (0.7gpm)
and check that the boiler modulates to deliver DHW at
approximately 65oC.
5. Close the DHW tap and check that the main burner
extinguishes. The pump should overrun for a few seconds
and the display symbols should read:
When the pump stops the display symbols clear
Note. On systems in excess of 2 bar inlet pressure a water
pressure governor may be required to prevent water
noise.
17. Turn off the DHW tap.
18. Set the boiler on/off switch (A) to OFF.
19. Swing the control box into the servicing position. Refer to
Frame 46.
20. Remove the pressure gauge and tube. Tighten the sealing
screw in the pressure test point. Ensure a gas tight seal is
made.
21. Swing the control box back into its working position and
secure. Reconnect the ignition lead.
22. Refit the user control.
23. Fit the boiler front and bottom panels.
24. THE FASCIA
a.
To remove the plastic fascia, prise off the retaining star
washers using a pair of pliers and place to one side.
b.
Fill the remaining fixing holes with the white push in
caps provided.
25. Switch the boiler on again.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
32
isar + programmer - Installation and Servicing
WATER TEMPERATURES
Temperatures can be selected via the CH and DHW
temperature settings (see users guide).
41
GENERAL CHECKS - continued
Setting
CH Flow
DHW Outlet
Temp
Temp
oC (
oF)
oC (
oF)
Max
82 (180)
65 (150)
Min
30 (86)
42 (110)
CENTRAL HEATING (CH) & DOMESTIC HOT WATER (DHW)
MODE.
1. Ensure that the CH external controls are calling for heat.
The LCD display symbols should be:
2. Fully open a DHW tap and check that hot water is
delivered.
The LCD display symbols should be:
3. Gas Rate
Check the boiler gas rate when the boiler is at full DHW
output.
Check at the gas meter, with no other appliance in use.
Refer to Table 3 for gas rates.
4. Close the DHW tap. The burner should go off and the
pump continue to run.
The LCD display symbol should be:
then
After 15 seconds the burner should relight, to supply
central heating.
The LCD display symbols should be:
5. Set the central heating external controls to OFF. The
burner should go off and the pump continue to run for a
few seconds.
The LCD display symbols should be:
returning to none when the pump stops.
6. Check the correct operation of the programmer (if fitted)
and all other system controls. Operate each control
separately and check that the main burner responds.
WATER CIRCULATION SYSTEM
1. With the system COLD, check that the initial pressure is
correct to the system design requirements.
For pre-pressurised systems, this should be 1.0 bar.
2. With the system HOT, examine all water connections for
soundness. The system pressure will increase with
temperature rise but should not exceed 2.5 bar.
3. With the system still hot, turn off the gas, water and
electricity supplies to the boiler and drain down to
complete the flushing process.
Note.A flushing solution should be used during the flushing
procedure. Flushing solutions: Fernox Superfloc,
Sentinel X300 (new systems) or X400 (existing
systems). Refer to Frame 6.
4. Refill and vent the system, add inhibitor (see Frame 6),
clear all air locks and again check for water soundness.
Affix the water treatment warning label, supplied in the
hardware pack, in a prominent position on the system, to
prevent the use of incorrect water treatment additives.
5. Reset the system initial pressure to the design
requirement.
6. Balance the system. Refer to Frame 5.
7. Check the condensate drain for leaks and check that it is
discharging correctly.
8. Finally, set the controls to the User's requirements.
Note.The pump will operate briefly as a self-check once
every 24 hours in the absence of any system demand.
INSTALLATION
202851-1new.pmd
17/11/2006, 07:40
33
isar + programmer - Installation and Servicing
43
SERVICING SCHEDULE
To ensure the continued safe and efficient operation of the
appliance it is recommended that it is checked at regular
intervals and serviced as necessary. The frequency of
servicing will depend upon the installation condition and
usage but should be carried out at least annually.
It is the law that any service work must be carried out by a
CORGI registered installer. In IE service work must be carried
out by a competent person.
1. Light the boiler and carry out a pre-service check, noting
any operational faults.
2. Check the gas consumption.
3. Connect a suitable gas analyser to the sampling point on
the top of the boiler (refer to Frame 45) or into the flue
terminal if access is possible (optional test).
For correct boiler operation, the CO/CO2 content of the flue
gas should not be greater than 0.004 ratio.
If this is the case, and the gas input is at least 90% of the
nominal, then no further action need be taken. If not,
proceed to Step 5 but see note above.
4. Clean the main burner.
5. Clean the heat exchanger & ‘S’ trap.
6. Check the condition of the combustion chamber insulation.
Any cracked or damaged pieces should be replaced.
7. Check the main injector for blockage or damage.
8. Wherever possible remove and clean the condensate ‘S’
trap (refer to Frame 49) and check the drain for blockage.
9. Check that the flue terminal is unobstructed and that the
flue system is sealed correctly.
10. Check the DHW filter for blockage. Refer to Frame 28.
The servicing procedures are covered more fully in Frames
44-51 and MUST be carried out in sequence.
Note.
In order to carry out either servicing or replacement of
components the boiler front panel and sealing panel
must be removed. Refer to Frames 44 and 45.
WARNING.
Always turn OFF the gas supply at the gas
service cock, and switch OFF and disconnect the electricity
supply to the appliance before servicing.
IMPORTANT.
11. After completing the servicing or exchange of components
always test for gas soundness and carry out functional
checks in 2 and 3 above.
12. When work is complete the sealing panel MUST be
correctly refitted, ensuring that a good seal is made.
Do NOT OPERATE the boiler if the sealing
panel is not fitted.
13. If, for any reason, the condensate ‘S’ trap has been
removed ensure the trap is refilled with water before
reassembling.
14. Complete the service section in the Benchmark
Commissioning Checklist.
42
HANDING OVER
6. Explain and demonstrate the function of time and
temperature controls, radiator valves etc., for the economic
use of the system.
7. Draw attention to the Programmer Users Instructions and
hand them to the householder.
8. Loss of system water pressure
Explain that the dial underneath the boiler indicates the
central heating system pressure and that if the normal COLD
pressure of the system is seen to decrease over a period of
time then a water leak is indicated. Explain the re-
pressurising procedure and if unable to repressurise or if the
pressure continues to drop a registered local heating
installer should be consulted.
WARNING.
Do not fire the boiler if the pressure has reduced to zero from
the original setting.
9. After installation and commissioning please complete the
Commissioning Checklist before handover to
the customer.
For IE, its is necessary to complete a “Declaration of
Conformity” to indicate compliance to I.S. 813:2002.
10. IMPORTANT
A comprehensive service should be carried out ANNUALLY.
Stress the importance of regular servicing by a CORGI
registered installer. In IE servicing work must be carried out
by a competent person.
11. As the installer you may wish to undertake the service
contract yourself or alternatively offer to the customer the
benefits of the Ideal Care Scheme, details of which are
outlined in the householder pack supplied with this boiler.
1. Hand the User Instructions and Quick Reference Guide
to the householder and explain his/her responsibilities
under the relevant national regulations.
2. Explain and demonstrate the lighting and shutting
down procedures.
3. The operation of the boiler and the use and adjustment
of all system controls should be fully explained to the
householder, to ensure the greatest possible fuel
economy consistent with the household requirements
of both heating and hot water consumption.
Advise the User of the precautions necessary to prevent
damage to the system and to the building, in the event
of the system remaining inoperative during frosty
conditions.
4. Explain the function and the use of the boiler heating
and domestic hot water controls.
Explain that due to system variations and seasonal
temperature fluctuations DHW flow rates/temperature
rise will vary, requiring adjustment at the draw off tap. It
is therefore necessary to draw the users attention to the
section in the Users Instructions titled “Control of Water
Temperature” and the following statement:
“Additionally, the temperature can be controlled by
the user via the draw-off tap: the lower the rate the
higher the temperature, and vice versa”.
5. Explain the function of the boiler fault mode.
Emphasise that if a fault is indicated, the boiler should
be turned off and a CORGI registered local heating
installer consulted. In IE contact a competent person.
After completing the installation and commissioning of the system the
installer should hand over to the householder by the following actions:
SERVICING
202851-1new.pmd
17/11/2006, 07:40
34
isar + programmer - Installation and Servicing
45
BOILER SEALING PANEL / BOTTOM PANEL REMOVAL
44
BOILER FRONT PANEL REMOVAL
1. Remove the 2 screws from the
underside of the boiler.
2. Pull the panel forward at the bottom and
lift to disengage it from the top lugs.
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm8431
1. To remove the sealing panel remove
the 4 screws.
2. Remove the panel.
3. To remove the bottom panel remove
the 2 screws.
4. Pull the right hand side of the panel
down. Slide it to the right and
withdraw.
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm8432
SERVICING
202851-1new.pmd
17/11/2006, 07:40
35
isar + programmer - Installation and Servicing
46
THE CONTROL BOX IN THE SERVICING POSITION
1. Remove the 2 screws and withdraw the user
control.
2. Unplug the low voltage electrical lead from the
back of the user control.
3. Turn the clamp, swing the control box down and
pull slightly forward.
nm8433
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm7540
SERVICING
202851-1new.pmd
17/11/2006, 07:40
36
isar + programmer - Installation and Servicing
2
3
1
4
Ecl 6073
47
FAN AND VENTURI ASSEMBLY REMOVAL AND CLEANING
48
BURNER REMOVAL AND CLEANING
1. Remove the 6 screws securing the
burner (the 3 screws at the rear are
extended to ease access).
2. Lift off the burner from the combustion
chamber.
IMPORTANT
The burner head is a ceramic plaque
construction. Care must be taken to
ensure that the burner is not placed
down upon its face as this may cause
damage to the ceramic.
3. Brush off any deposits that may be on
the ceramic with a SOFT brush.
4. Inspect the sealing gasket around the
burner and combustion chamber
insulation for any signs of damage.
Replace as necessary.
Note.
Take care not to disturb the ionisation
probes at the front and rear of the
combustion chamber.
1. Disconnect the electrical leads from the
fan.
2. Undo the gas pipe union connection to the
injector housing.
3. Undo the screw on the fan mounting
bracket.
4. Lift off fan and venturi assembly.
5. Inspect the injector for blockage or
damage.
nm7400
Ionisation
Probes
1
2
4
SERVICING
202851-1new.pmd
17/11/2006, 07:40
37
isar + programmer - Installation and Servicing
50
CLEANING THE HEAT EXCHANGER
Reassemble the boiler in the following order:
1. Refit the condensate ‘S’ trap, ensuring that it is full of water.
2. Refit the sump cover.
3. Refit the electrodes. (Check dimensions; Frames 58 & 59).
4. Refit the burner.
5. Refit the fan / venturi assembly.
6. Reconnect the fan electrical lead.
1. Remove ignition and flame detection electrodes.
Refer to Frames 58 & 59.
2. Remove the 3 screws retaining the sump cover and
remove.
3. Using a suitable tool as supplied in the standard
British Gas Flue brush kit, clean between the heat
exchanger fins from the top of the heat exchanger.
4. Access to the base of the heat exchanger is now
possible. Brush clean any deposits from the base of
the heat exchanger and remove any loose deposits
from the sump.
5. Inspect the ignition and detection electrodes. Ensure
that they are clean and in good condition - replace if
necessary.
6. Check the condition of the combustion chamber
insulation. Any cracked or damaged pieces must be
replaced.
Note. Take care not to disturb the ionisation probes at the
front and rear of the combustion chamber.
7. Check that the ignition and detection gaps are
correct. Refer to Frames 58 & 59.
7. Refit the boiler sealing panel.
IMPORTANT.
Ensure that the boiler sealing panel is correctly fitted and
that a good seal is made.
8. Swing the control box back into its working position and
secure.
9. Refit the display unit.
10. Refit the boiler front and bottom panels.
11. Turn on the gas supply at the gas service cock.
12. Reconnect the electrical supply.
51
REASSEMBLY
1. Swing the control box down into the
servicing position. Refer to Frame 46.
2. Disconnect the condensate drain pipe.
3. Remove the screw and elongated bolt,
pull the trap down and forward to
remove.
4. Flush out any deposits with clean
water.
49
CLEANING THE CONDENSATE 'S' TRAP
nm7401
2
Sump cover
3
Ionisation
probes
Heat exchanger
SERVICING
202851-1new.pmd
17/11/2006, 07:40
38
isar + programmer - Installation and Servicing
Gasket
Orifice plate
Ecl 2373
5
3
7
4
52
REPLACEMENT OF COMPONENTS
GENERAL
When replacing ANY component
1. Isolate the electricity supply.
2. Turn off the gas supply.
3. Remove the boiler front panel. Refer to Frame 44.
After replacing ANY component check operation of the boiler,
including gas soundness, gas rate and combustion test.
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to
Frames 44 & 45.
3. Drain down the boiler. Refer to Frame 72.
4. Unplug the electrical lead.
5. Unscrew the thermistor.
6. Fit the new thermistor using the sealing washer
provided.
7. Reassemble in the reverse order.
8. Check the operation of the boiler.
53
DRY FIRE THERMISTOR REPLACEMENT
54
FAN REPLACEMENT
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to Frames
44 & 45.
3. Disconnect the electrical leads from the fan.
4. Undo the gas pipe union connection to the injector housing.
5. Remove the screw retaining the fan mounting bracket.
6. Remove the fan and venturi assembly. Refer to
Frame 47.
7. Unscrew the 3 screws and remove the venturi
assembly, noting the orientation of the venturi in
relation to the fan body.
8. Transfer the venturi assembly to the new fan,
replacing the gasket if evidence of damage or
deterioration is visible.
9. Fit the new fan / venturi assembly.
10. Reassemble the boiler in reverse order, taking care not to
overtighten the screw on the fan mounting bracket.
11. Check the operation of the boiler. Refer to Frame 52.
IMPORTANT.
When work is complete, the sealing panel, if removed, must
be correctly refitted - ensuring that a good seal is made.
Notes.
1. In order to assist fault finding, the control panel has an
LED diagnostic display. The key to boiler fault conditions
is shown in Frame 79.
2. In order to replace components in Frames 69-77 it is
necessary to drain the boiler. Refer to Frame 72.
THE BOILER MUST NOT BE OPERATED WITHOUT THE SEALING PANEL FITTED
nm8027
SERVICING
202851-1new.pmd
17/11/2006, 07:40
39
isar + programmer - Installation and Servicing
56
BURNER REPLACEMENT
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to
Frames 44 & 45.
3. Remove the fan assembly. Refer to Frame 54.
4. Remove the 6 screws securing the burner (the 3 screws at
the rear are extended to ease access).
5. Lift off the burner from the combustion chamber.
6. Fit the new burner, replacing any damaged or deteriorating
sealing gasket.
7. Reassemble in reverse order.
8. Check the operation of the boiler. Refer to Frame 52.
Note.
Take care not to disturb the ionisation probes at the
front and rear of the combustion chamber.
55
BURNER INJECTOR REPLACEMENT
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to Frames
44 & 45.
3. Disconnect the electrical leads from the fan.
4. Undo the gas pipe union connection to the injector housing.
5. Remove the screw retaining the fan mounting bracket.
6. Remove the fan and venturi assembly
7. Remove the 2 injector housing screws.
8. Withdraw the injector housing.
9. Fit the new injector housing complete with injector.
10. Reassemble in reverse order, ensuring that the new gas seal
supplied is located correctly in the injector housing.
11. Check operation of the boiler. Refer to Frame 52.
Mounting bracket
7
Ecl 2400
5
Injector
Fan
Gas pipe union
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm8434
57
CONTROL THERMISTOR, RETURN THERMISTOR & OVERHEAT ‘STAT REPLACEMENT
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels.
Refer to Frames 44 & 45.
3. Unclip the thermistor / thermostat from the flow / return pipe and
withdraw it from the controls compartment.
4. Disconnect the electrical leads from the
thermistor / thermostat.
5. Reconnect the electrical leads and
reassemble in reverse order, ensuring that the
spring clip is securely on the pipe.
6. Check the operation of the boiler. Refer to
Frame 52.
nm7402
Ionisation
Probes
4
5
6
SERVICING
202851-1new.pmd
17/11/2006, 07:40
40
isar + programmer - Installation and Servicing
58
IGNITION ELECTRODE REPLACEMENT
59
FLAME DETECTION ELECTRODE REPLACEMENT
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to
Frames 44 & 45.
3. Unplug the ignition lead from the electrode.
4. Remove the earth lead from the ignition electrode.
5. Remove the remaining screw holding the ignition
electrode to the combustion chamber.
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to
Frames 44 & 45.
3. Unplug the flame detection lead from the electrode.
4. Remove the 2 screws holding the flame detection
electrode to the combustion chamber.
6. Remove the electrode.
7. Fit the new ignition electrode, using the new gasket
supplied. Check dimensions as shown.
8. Reassemble in reverse order, and check that no damage
to the combustion chamber insulation has occurred
during the electrode replacement.
9. Check the operation of the boiler. Refer to Frame 52.
5. Remove the electrode.
6. Fit the new flame detection electrode, using the new gasket
supplied. Check dimensions as shown.
7. Reassemble in reverse order, and check that no damage to
the combustion chamber insulation has occurred during the
electrode replacement.
8. Check the operation of the boiler. Refer to Frame 52.
60
SPARK GENERATOR REPLACEMENT
1. Refer to Frame 52.
2. Disconnect the leads from the spark generator and bracket.
3. Remove the M5 screw securing the spark generator bracket
to the flue casting.
4. Remove the 2 M4 screws securing the spark generator to the
bracket.
5. Fit the new spark generator and re-assemble in reverse
order.
6. Check operation of the boiler. Refer to Frame 52.
4
2
3
nm7548
SERVICING
202851-1new.pmd
17/11/2006, 07:40
41
isar + programmer - Installation and Servicing
61
GAS CONTROL VALVE REPLACEMENT
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Swing the control box down into the servicing
position. Refer to Frame 46.
4. Unplug the electrical lead from the gas control
valve and disconnect the earth wire.
5. Remove the sensing tube from the gas control
valve.
6. Undo the gas inlet pipe union at the gas
service cock.
7. Undo the union nut on the outlet of the gas
control valve.
8. Slacken the screw securing the valve
mounting bracket and withdraw the valve,
complete with bracket and inlet pipe.
9. Transfer the mounting bracket and gas inlet
pipe to the new gas control valve.
10. Fit the new gas control valve, ensuring that
any seals showing damage or deterioration
are replaced. Reassemble in reverse order.
11. Ensure the sensing tube is correctly replaced
and not kinked or blocked in any way.
12. Check operation of the boiler. Refer to Frame
52.
62
DIVERTER VALVE ACTUATOR REPLACEMENT
1. Refer to Frame 52.
2. Remove the casing front & bottom
panel.
Refer to Frames 44 & 45.
3. Squeeze the tab and unplug the
electrical lead from the valve
actuator.
4. Rotate the actuator anticlockwise
and pull forward to remove.
5. Fit new actuator and reassemble in
reverse order.
6. Check operation of the boiler. Refer
to Frame 52.
2040
Electrical
lead
Tab
Diverter
valve actuator
SERVICING
202851-1new.pmd
17/11/2006, 07:41
42
isar + programmer - Installation and Servicing
Rear
Front
Combustion
chamber
LH Side
RH Side
nm8033
7
6
5
63
COMBUSTION CHAMBER INSULATION REPLACEMENT
The insulation boards used in the combustion chamber of
this product are made of high temperature glass fibres with a
binder of organic and inorganic materials.
Caradon Ideal Limited recommend that, for your own comfort
and safety and to comply with good working practice, the
procedure described below is followed:
1. Refer to Frame 52.
2. Remove the boiler front and sealing panels. Refer to
Frames 44 & 45.
3. Remove the fan / venturi assembly. Refer to Frame 47.
4. Remove the burner. Refer to Frame 48.
5. Remove the ignition electrode. Refer to Frame 58.
6. Remove the flame detection electrode. Refer to Frame 59.
7. Remove the front and rear ionisation probes.
Prior to removal of the board the following protective
equipment should be worn:
z
Face mask supplied with the spare part.
z
Gloves supplied with the spare part.
8. Damp down the combustion chamber area containing the
insulation boards.
9. Remove the split pin and washer from the RHS of the
combustion chamber.
10. Remove the insulation boards. The replacement boards
are supplied in a plastic bag. This bag should be retained
and the discarded boards should now be placed into it.
11. Sweep any dampened particles and place in the plastic
bag.
12. Fit new insulation boards.
Note.
The boards are designed to be interlocking and should be
fitted as shown.
13. Fit the new split pin and washer in the RHS of the chamber.
14. Remove the gloves and face mask and place them in the
plastic bag.
15. Wash your hands and any areas of skin which may have
come into contact with any of the particles from the
insulation board.
Note. Seal the plastic bag and dispose of it and its contents
into a commercial tip.
16. Reassemble in reverse order, remembering to re-fit the
ionisation probes first.
17. Check operation of the boiler. Refer to Frame 52.
Fit insulation in the following order:
1.
Rear.
2.
Left Hand Side.
3.
Front.
4.
Right Hand Side.
SERVICING
202851-1new.pmd
17/11/2006, 07:41
43
isar + programmer - Installation and Servicing
64
CONDENSATE 'S' TRAP REPLACEMENT
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Swing the control box down into the servicing
position. Refer to Frame 46.
4. Disconnect the condensate drain pipe.
5. Remove the securing screw and elongated bolt,
pull the trap down and forward to remove.
6. Transfer the drain pipe to the new trap and
reassemble in reverse order.
7. When reassembling ensure the trap is full of water.
8. Check operation of the boiler. Refer to Frame 52.
65
DHW THERMISTOR REPLACEMENT
1. Refer to Frames 52 & 72 for draining the appliance.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Remove the 4 screws securing the support plate and
withdraw the plate.
Note.
The M4 screws fit the casing and the self-tapping
screws fit the plastic pump and valve housings.
4. Withdraw the securing pin.
5. Disconnect the electrical lead.
6. Ease out the sensor and discard.
7. Fit the new sensor, ensuring silicone grease is applied
to the 'O' ring.
8. Refit the securing pin.
9. Reassemble in reverse order, ensuring correct location
of screws in support plate, and that tabs on the pump
and valve housings engage in slots.
10. Check operation of the boiler. Refer to Frame 52.
Support plate
Discharge pipe
M4 screw
2055
M4 screw
Self tapper
screw
Sensor
Electrical lead
Securing pin
2042
SERVICING
202851-1new.pmd
17/11/2006, 07:41
44
isar + programmer - Installation and Servicing
Screws
C.
B .
A.
Hinge arms
Control box mounting bracket
Electrical lead
Control box
Control box
Control
box
nm7541
Low voltage lead
Clamp
3
nm8435
itime
programmer
unit
User control
time
P R O G R A M M E R
prog
prog
select
select
+
-
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Remove the 2 screws and allow the user control to lower.
4. Push out the mains switch from the rear, as shown.
5. Fit the new switch, ensuring that the electrical leads are
67
MAINS SWITCH REPLACEMENT
66
CONTROL BOX REPLACEMENT
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Swing the control box down into the servicing position.
Refer to Frame 46.
4. Unplug the user control electrical lead and low voltage
lead from the control box and remove the control. Refer
to diagram A.
5. Return the control box to the working position and
secure with the clamp. Unscrew the mounting bracket
screws to remove the bracket. Refer to diagram B.
6. Release the clamp and carefully remove the control
box from the hinge arms. Refer to diagram C.
7. Unplug all the electrical wiring from the control box and
remove.
8. Transfer mounting bracket and hinge arms to the new
control box.
9. Reassemble in reverse order, ensuring that the control box
is located correctly in the housing before reconnecting the
electrical wiring.
10. Check operation of the boiler. Refer to Frame 52.
nm8436
itime programmer
unit
replaced on the correct terminals (refer to Frame 36) and
the key on the switch is correctly aligned with the slot in the
plastic moulding.
6. Reassemble in reverse order.
7. Check operation of the boiler. Refer to Frame 52.
SERVICING
202851-1new.pmd
17/11/2006, 07:41
45
isar + programmer - Installation and Servicing
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm8437
itime
programmer
unit
2
itime
programmer
unit
nm8438
time
P R O G R A M M E R
prog
prog
select
select
+
-
Note. Only the display unit is replaced.
1. Refer to Frame 52.
2. Loosen the screw on the underside of the user control.
3. Pull the display unit forward to remove.
4. Push the new display unit into position.
5. Reassemble in reverse order.
6. Check operation of the boiler. Refer to Frame 52.
68
USER CONTROL REPLACEMENT
69
PRESSURE GAUGE REPLACEMENT
1. Refer to Frame 52.
2. Drain the boiler. Refer to Frame 72.
3. Unscrew the pressure gauge and discard.
4. Fit the new pressure gauge, using a suitable jointing
compound.
5. Refill the boiler. Refer to Frame 31.
6. Check operation of the boiler. Refer to Frame 52.
2041
Pressure gauge
Flow isolation valve
(shown in the open position)
SERVICING
202851-1new.pmd
17/11/2006, 07:41
46
isar + programmer - Installation and Servicing
70
SAFETY RELIEF VALVE REPLACEMENT
1. Refer to Frame 52.
2. Remove the casing front and bottom panels. Refer to
Frames 44 & 45.
3. Drain the boiler. Refer to Frame 72.
4. Remove the discharge pipe.
5. Remove the 4 screws retaining the rear support plate and
withdraw the plate.
Note.The M4 screws fit the casing and the self -tapping screws
fit the plastic pump and valve housings, as shown.
6. Withdraw the securing pin.
71
AUTOMATIC AIR VENT REPLACEMENT
1. Refer to Frame 52
2. Remove the boiler front and sealing panels. Refer to
frames 44 and 45.
3. Drain the boiler. Refer to frame 72.
4. Remove the turret from the boiler. Refer to frame 26.
5. Release the silicon tubing from the sample point.
6. Release the electrical connections from the dry fire
thermistor.
7. Release the electrical connections from the spark
generator.
8. Remove the M5 nut retaining the flue casting spring clip
and remove the spring clip.
9. Undo the 2 M5 x 10 flue spring clip retaining bracket
screws and remove the bracket.
10. Remove the M5 x 10 screw retaining the flue casting.
11. Remove the flue casting.
12. Remove the screw and rear bracket. Pull the air vent and
plug assembly from the heat exchanger and replace with
the parts supplied in the air vent kit.
13. Re assemble the boiler in reverse order.
14. Refill the boiler. Refer to frame 31. Check for leaks around
the new air vent joint.
15. Check the operation of the boiler. Refer to frame 52.
7. Remove the safety valve.
8. Fit the new safety valve and refit the securing pin.
9. Reassemble in reverse order, ensuring correct
location of screws in the support plate and that tabs
on the pump and valve housings engage in slots.
10. Reconnect the discharge pipe.
11. Refill the boiler. Refer to Frame 31.
12. Check operation of the boiler. Refer to Frame 52.
Support plate
M4 screw
2012
M4 screw
Self tapper
screw
Discharge pipe
Safety relief valve
Securing pin
2039
nm8028
10
9
8
6
Air vent
Plug
SERVICING
202851-1new.pmd
17/11/2006, 07:41
47
isar + programmer - Installation and Servicing
72
DRAINING THE BOILER
1. Refer to frame 52.
2. Remove the boiler bottom panel. Refer to Frame 45.
3. Close all the water isolating (CH and DHW) valves on
the piping frame.
4. To drain the central heating circuit, attach a length of
hose to the drain point and open the drain valve.
However it must be noted that some residual water
may be experienced during the replacement of
components.
5. As there is no direct drain for the domestic hot water
circuit, depending on the location of the boiler, opening
the lowest hot water tap may drain this circuit.
However it must be noted that some residual water
will be experienced during replacement of
components.
6. After replacing any component on the boiler, close
the drain valve, remove the hose and open all
system isolating valves (re-pressurise as
appropriate) before proceeding to check operation
of the boiler.
7. Check operation of the boiler. Refer to Frame 52.
73
DIVERTER VALVE MECHANISM REPLACEMENT
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Drain the boiler. Refer to Frame 72.
4. Remove the 4 screws retaining the rear support
plate and withdraw the plate. Refer to Frame 70.
Note.
The M4 screws fit the casing and the self-
tapping screws fit the plastic pump and
valve housings.
5. Remove the valve actuator head. Refer to Frame
62.
6. Remove the 4 Allen screws and remove the valve
mechanism.
7. Fit the new valve mechanism and gasket,
ensuring correct fit over the location pin.
8. Reassemble in reverse order, ensuring correct
location of screws in the support plate and that
tabs on the pump and valve housings engage in
slots.
9. Refill the boiler. Refer to Frame 31.
10. Check operation of the boiler. Refer to
Frame 52.
isolating valve
(shown closed)
Isolating valves
Drain point
Drain valve
nm8457
TO OPEN
Compression
gas cock
nm7546
Valve
mechanism
Allen
screws
Locating
pin hole
Gasket
SERVICING
202851-1new.pmd
17/11/2006, 07:41
48
isar + programmer - Installation and Servicing
75
PUMP HEAD REPLACEMENT (Wilo and CP)
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Drain the boiler. Refer to Frame 72.
4. Swing the control box down into the
servicing position. Refer to Frame 46.
5. Disconnect the electrical lead from the
pump.
6. Remove the 4 Allen screws retaining the
pump head.
7. Remove the pump head.
8. Fit the new pump head.
9. Reassemble in reverse order.
10. Refill the boiler. Refer to Frame 31
11. Check operation of the boiler. Refer to
Frame 52.
74
DHW PLATE HEAT EXCHANGER REPLACEMENT (WILO AND CP)
1. Refer to Frame 52.
2. Remove the casing front & bottom panel.
Refer to Frames 44 & 45.
3. Drain the boiler. Refer to Frame 72.
4. Remove the 4 screws securing the rear
support plate and withdraw the plate. Refer
to Frame 70.
Note.
The M4 screws fit the casing and the
self-tapping screws fit the plastic pump
and valve housings.
5. Remove the 2 Torx screws (allen screws on
the CP waterset) securing the plate heat
exchanger from the valve and pump
housings.
6. Raise the RH side of the heat exchanger,
lower the LH side through the bottom of the
boiler and remove.
7. Fit the new heat exchanger, using the new
gaskets supplied.
8. Reassemble in reverse order ,ensuring
correct location of screws in the support
plate and that tabs on the pump and valve
housings engage in slots.
9. Refill the boiler. Refer to Frame 31.
10. Check operation of the boiler. Refer to
Frame 52.
Wilo pump shown
SERVICING
202851-1new.pmd
17/11/2006, 07:41
49
isar + programmer - Installation and Servicing
nm8029
Refer also to Frame 8 - 'Boiler Exploded View'.
IMPORTANT
Before starting the removal procedure, protect the gas and
electrical controls with a waterproof sheet or plastic bag.
1. Refer to Frame 52.
2. Remove the boiler front, bottom and sealing panels.
Refer to Frames 44 & 45.
3. Drain the boiler. Refer to Frame 72.
4. Remove the control box and place on one side. Refer to
Frame 66.
5. Remove the fan / venturi assembly and place on one
side. Refer to Frame 47.
6. Remove the burner and place on one side. Refer to
Frame 48.
7. Remove the ignition and detection electrodes. Refer to
Frames 58 & 59.
8. Remove the spark generator. Refer to Frame 60.
9. Release the flue from the turret. Refer to Frame 26.
10. Remove the turret from the boiler. Refer to Frame 26.
11. Release the silicone tubing from the sampling point.
12. Release the electrical connection to the dry fire
thermistor.
13. Remove the M5 nut retaining the flue casting spring clip
and remove the spring clip.
14. Undo the 2 M5 x 10 flue spring clip retaining bracket
screws and remove the bracket.
15. Remove the M5 x 10 screw retaining the flue casting.
16. Remove the flue casting.
76
HEAT ENGINE REPLACEMENT
17. Remove the automatic air vent. Refer to Frame 71.
18. Remove the edge clip securing the dry fire thermistor
wiring.
19. Remove the blind grommet to gain access to the return
pipe securing bracket.
20. Remove the M5 screw and remove the return pipe
securing bracket by sliding forwards.
21. Remove the overheat thermostat and the control
thermistor. Refer to Frame 57.
22. Remove the securing pin to release the flow pipe.
23. Remove the condensate ‘S’ trap. Refer to Frame 64.
24. Remove the 2 M5 screws securing the interpanel to the
back panel.
25. Slide the heat exchanger and interpanel assembly upward
to disengage and remove from the casing, complete with
the flow pipe.
26. Remove the 2 M6 countersunk screws, remove the
interpanel and transfer to the new heat exchanger.
27. Remove the M5 screw and remove the flow pipe securing
bracket.
28. Remove the flow pipe and transfer to the new heat
exchanger.
29. Reassemble in reverse order, replacing gaskets or seals
if any sign of damage or deterioration is evident.
Note.The heat exchanger is supplied with new combustion
chamber insulation boards. These should be fitted (refer
to Frame 63 before the burner and fan / venturi
assembly and before the ignition and detection
electrodes are replaced).
30. Refill the boiler. Refer to Frame 31.
31. Check operation of the boiler. Refer to Frame 52.
SERVICING
202851-1new.pmd
17/11/2006, 07:41
50
isar + programmer - Installation and Servicing
time
P R O G R A M M E R
prog
prog
select
select
+
-
nm8439
78
BOILER SEALING PANEL SEAL REPLACEMENT
1. Refer to Frame 52.
2. Remove the boiler front and sealing
panels. Refer to Frames 44 & 45 .
3. Remove the old seal from the casing
and thoroughly clean the casing
surfaces.
4. Fit the new adhesive seals, note that
they are supplied to the correct length
for the relevant sides.
5. Reassemble in reverse order.
6. Check operation of the boiler. Refer to
Frame 52.
Note.
Ensure that the boiler sealing
panel is correctly sealed,
compressing the seal to make an
airtight joint.
77
EXPANSION VESSEL REPLACEMENT
1. Refer to Frame 52.
2. Drain the boiler. Refer to Frame 72.
3. Unscrew all the gas and water connection unions on the
boiler side of the valves.
4. Remove the screw from the turret clamp and remove.
5. Remove the turret.
6. Lift the complete boiler from the wall mounting frame
and place on a flat surface, face down, to expose the
expansion vessel.
7. Unscrew the union nut on the vessel water connection
pipe.
8. Unscrew the 2 screws from the securing clamp and
remove.
9. Remove the expansion vessel.
10. Fit the new expansion vessel.
11. Reassemble in reverse order.
12. Refill the boiler. Refer to Frame 31.
13. Check operation of the boiler. Refer to Frame 52.
Note.
If preferred, and for convenience, a new expansion vessel
may be installed elsewhere in the heating system, providing
it ensures equivalent system protection.
SERVICING
202851-1new.pmd
17/11/2006, 07:41
51
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
isar + programmer - Installation and Servicing
79
FAULT FINDING CHART MAIN MENU
'L' 'F'
GO TO FRAME 80
'L' 'E'
GO TO FRAME 81
'L' 'A'
GO TO FRAME 82
'L' '8'
GO TO FRAME 83
'H' '1'
GO TO FRAME 84
'H' '2'
GO TO FRAME 85
'H' '3'
GO TO FRAME 86
'H' '4'
GO TO FRAME 87
'H' 'F'
GO TO FRAME 88
In order to assist fault finding the boiler has an LED diagnostic display. The key to the display codes is as follows:
'H' 'n'
GO TO FRAME 89
'H' 'E'
GO TO FRAME 81
'H' '9'
GO TO FRAME 87
'L' '9'
GO TO FRAME 87
202851-1new.pmd
17/11/2006, 07:41
52
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
isar + programmer - Installation and Servicing
80
L.....F.....
(FLAME DETECTION ERROR)
Check the ignition electrode and associated harness
for: continuity, visual condition, position
(Refer to Frame 58).
Are these functioning correctly ?
Check gas valve
wiring for
continuity
YES
Check the detection electrode and
associated harness for:
continuity, visual condition, position
(Refer to Frame 59).
Replace as necessary.
If the boiler select (reset) button
is pressed does the boiler ignite
for a short time then extinguish?
Is 200V DC supply available
at the gas valve ?
(see Note)
NO
YES
YES
Is gas pressure available at
the boiler inlet ?
Replace PCB
Check gas supply
and rectify fault
Replace ignition electrode and associated
harness as necessary
NO
Replace gas valve
YES
NO
NO
81
L.....E.....
or
H.....E..... (PCB ERROR)
Note. Due to the wave form of the rectified voltage, the reading will vary depending on the type of meter used to
measure the value (some may measure the possible peak voltage of 339V). In general terms a reading greater
than 150V indicates that the correct voltage is supplied to the gas valve. As an alternative to a meter, a mains
voltage checking device may be used. E.g. an electrical screwdriver or mains tester.
Check spark generator and associated
harness for continuity and visual condition.
(Refer to Frame 60).
Are these functioning correctly ?
Replace spark
generator
YES
NO
Internal fault within the PCB
Replace PCB
Press and hold boiler select
(reset) button for 2 seconds.
Does boiler operate correctly?
Turn boiler off and wait for 5
seconds. Turn boiler on.
Does boiler operate correctly?
NO
NO
YES
OK
YES
OK
Check syphon
and condensate
drain pipework
for blockage
202851-1new.pmd
17/11/2006, 07:41
53
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
isar + programmer - Installation and Servicing
Does the pump setting give a differential across
the boiler in excess of 25
oC ?
Can the overheat condition be reset by pressing the
boiler select (reset) button when the system is cold ?
Replace the system pump
Set CH control knob to maximum.
If the overheat trips again measure the flow temp:
Over 90
oC
Check control thermistor
(Refer to Frame 84)
Under 90
oC
Replace overheat 'stat
YES
YES
Check that the pump is rotating freely.
Is differential now below 25
oC ?
NO
NO
82
L.....A.....
(OVERHEAT ERROR)
Fill and vent the system and open all
isolation valves
YES
Is the boiler and CH system filled with
water and all isolation valves open ?
OK
NO
YES
NO
Replace overheat thermostat
83
L....8.....
(FAN ERROR)
Is nominal 330 V DC present across
red and blue at the fan connector as
boiler select (reset) button is pressed?
Replace fan
YES
NO
Replace harness
84
H.....1.....
(CONTROL THERMISTOR [FLOW] ERROR)
YES
Is there continuity between the
PCB and the thermistor ?
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25
oC
expect
9,700 - 10,300
Ohms
At 60
oC
expect
2,400 -
2,600
Ohms
At 85
oC
expect
1,000 -
1,100
Ohms
Remove the boiler control thermistor from the
CH flow pipe and disconnect thermistor wires.
Are the thermistor values correct ?
Replace the thermistor
NO
NO
YES
Replace PCB
Check and replace wiring as necessary
Replace PCB
YES
Is 14V DC present across
yellow and pink at the fan
connector?
Check wiring harness for continuity.
Is there continuity?
NO
YES
NO
202851-1new.pmd
17/11/2006, 07:41
54
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
isar + programmer - Installation and Servicing
85
H.....2..... (CONTROL THERMISTOR [RETURN] ERROR)
YES
Is there continuity between the
PCB and the thermistor ?
Remove the boiler return thermistor from the
CH return pipe.
Are the thermistor values correct ?
Replace the thermistor
NO
NO
YES
Replace PCB
Check and replace wiring as necessary
86
H.....3.....
(DHW THERMISTOR ERROR)
YES
Is there continuity between the
PCB and the thermistor ?
Remove the boiler DHW thermistor from the plate
heat exchanger and disconnect thermistor wires.
Are the thermistor values correct ?
Replace the thermistor
NO
NO
YES
Replace PCB
Check and replace wiring as necessary
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25
oC
expect
9,700 - 10,300
Ohms
At 60
oC
expect
2,400 -
2,600
Ohms
At 85
oC
expect
1,000 -
1,100
Ohms
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25
oC
expect
9,700 - 10,300
Ohms
At 60
oC
expect
2,400 -
2,600
Ohms
At 85
oC
expect
1,000 -
1,100
Ohms
202851-1new.pmd
17/11/2006, 07:41
55
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
isar + programmer - Installation and Servicing
87
H.....4.... (DRY FIRE THERMISTOR ERROR)
Check wiring for continuity from the
PCB to the dry fire thermistor
Can the fault condition be reset by switching off
the mains supply to the boiler ?
Is the system filled and vented and all
isolation valves open ?
Is the pump operating correctly?
Ensure flow through system.
NO
Are thermistor values correct ?
Replace PCB
Replace thermistor
Fill and vent the
system and open all
isolating valves
YES
Are thermistor values correct ?
Inspect heat
exchanger for
blockage or damage
in the flueways.
Clean or replace as
necessary
Replace thermistor
NO
89
H......n..... (PHASE REVERSAL ERROR)
Check wiring to the boiler for
reversed live and neutral
YES
NO
YES
NO
88
H......F..... (FLAME DETECTION ERROR)
Replace flame detection electrode
Is there continuity between the 2 terminal pins ?
NO
YES
Remove flame detection electrode terminal from PCB
Replace PCB
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25
oC
expect
9,700 - 10,300
Ohms
At 60
oC
expect
2,400 -
2,600
Ohms
At 85
oC
expect
1,000 -
1,100
Ohms
Check resistance using a suitable multimeter
connected across the dry fire thermistor’s
terminal pins
At 25
oC
expect
9,700 - 10,300
Ohms
At 60
oC
expect
2,400 -
2,600
Ohms
At 85
oC
expect
1,000 -
1,100
Ohms
H9/L9
(HEAT EXCHANGER OVERHEAT)
202851-1new.pmd
17/11/2006, 07:41
56
SHORT LIST OF PARTS
isar + programmer - Installation and Servicing
When ordering spares please quote:
1. Boiler model
2. Appliance G.C. No.
3. Description.
4. Quantity.
5. Product number.
The following are parts commonly required due to damage or
expendability. Their failure or absence is likely to affect safety or
performance of this appliance.
The list is extracted from the British Gas List of Parts, which
contains all available spare parts.
The full list is held by British Gas Services, Caradon Ideal Limited
distributors and merchants.
Key No.
G.C. Part No.
Description
Qty.
Product Number
1
Front casing panel
1
173 509
4
E69-384
Bottom casing panel
1
171 027
11
E67-489
Burner
1
170 905
12
Combustion chamber insulation
1
173 520
14
E67-492
Injector and housing
HE24/30
1
170 908
HE35
1
173 522
16
E85-097
Fan assembly
HE24/30
1
172 625
HE35
1
173 525
17
E69-286
Automatic air vent
1
170 988
19
E69-288
Gas control valve
1
171 035
23
E67-501
Control thermistor (flow/return)
2
170 917
24
E67-502
Overheat thermostat
1
170 918
25
Ignition electrode kit
1
173 528
26
Flame detection electrode kit
HE24/30
1
173 529
HE35
1
170 984
32
H40-140
Kit - Trap and Seal
1
174 244
35
itime user control programmer
1
174 487
36
V9 PCB primary ctrls (includes plastic housing)
HE24/30/35
1
174 486
37
E67-519
Fuse PCB (3.15A L250V)
1
170 931
39
Mains switch c/w harness
1
173 537
40
Spark generator assy.
1
173 538
45
E67-527
Gasket kit (servicing)
1
170 938
52
E68-376
Seal kit (sealing panel)
1
171 014
53
E68-380
Turret gasket
1
171 022
61
E69-338
Pressure relief valve - Wilo *
1
170 992
Pressure relief valve - CP *
1
173 977
62
Expansion vessel
1
173 066
64
E69-341
Pressure gauge
1
170 991
65
E69-403
DHW thermistor - Wilo *
1
170 996
DHW thermistor - CP *
1
173 974
66
Diverter valve motor head - Wilo / CP*
1
173 628
67
Diverter valve body - Wilo / CP*
1
173 624
69
E69-342
Pump - Wilo *
1
170 990
Pump Head - CP *
1
173 963
71
E69-408
Plate heat exchanger - Wilo *
HE24
1
173 544
HE30
1
170 995
HE35
1
173 545
Plate heat exchanger - CP *
HE24
1
174 207
HE30
1
173 957
HE35
1
174 208
94
Ignition lead
1
173 510
95
Detection lead
1
173 512
103
Dry Fire Thermistor
1
173 617
When replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
(* Refer to boiler serial letter code on data plate to identify correct spare. Serial letter codes: Wilo= VU, CP= VX)
202851-1new.pmd
17/11/2006, 07:41
57
SHORT LIST OF PARTS
isar + programmer - Installation and Servicing
90
SHORT LIST
nm8440
103
time
P R O G R A M M E R
prog
prog
select
select
+
-
202851-1new.pmd
17/11/2006, 07:41
58
LIST OF PARTS
isar + programmer - Installation and Servicing
Ecl 1598
91
BOILER CASING ASSEMBLY
1. Front casing panel with screws.
2. Sealing panel with screws.
4. Bottom panel with screws.
92
CONTROLS ASSEMBLY
33.
Controls assy with screws.
34.
Controls hinge bracket.
35.
User controls (without item 38).
36.
PCB (primary controls).
38.
User controls housing
39.
Mains switch.
54.
Jumper link (not shown)
93
BURNER ASSEMBLY
11. Burner assembly with screws and gasket.
nm8441
36
34
39
38
35
time
P R O G R A M M E R
prog
prog
select
select
+
-
202851-1new.pmd
17/11/2006, 07:41
59
isar + programmer - Installation and Servicing
INSTALLER NOTIFICATION GUIDELINES
IT IS A REQUIREMENT OF CORGI MEMBERSHIP TO REGISTER EVERY GAS APPLIANCE
In addition a change to Building Regulations (England and Wales) requires the installer to notify
when installing a heating appliance, as from 1st April 2005.
Competent Person's
SELF CERTIFICATION SCHEME
BUILDING CONTROL
Install and commission
this appliance to
manufacturers' instructions
Complete the
Benchmark Checklist
Choose
Buildings Regulations
notification route
Contact your relevant
Local Authority
Building Control (LABC) who
will arrange an inspection
or contact a government
approved inspector
LABC will record the data
and will issue a
certificate of compliance
If you notify via CORGI Scheme,
CORGI will then notify the
relevant Local Authority Building
Control (LABC) scheme
on members behalf
Scheme members only:
Call CORGI on 0870 88 88 777
or log onto:
www.corgi-notify.com
within 10 days
You must ensure that the
notification number
issued by CORGI is written
onto the Benchmark Checklist
CORGI will record the data and
will send a certificate of
compliance to the property
IT IS A CONDITION OF THE
MANUFACTURERS WARRANTY
THAT THE BENCHMARK
COMMISSIONING CHECKLIST IS
FULLY COMPLETED AND LEFT
WITH THE APPLIANCE
202851-1new.pmd
17/11/2006, 07:41
61
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING
ROOM T/STAT & PROGRAMMER/TIMER
PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER
CYLINDER T/STAT & PROGRAMMER/TIMER
COMBI BOILER
HEATING ZONE VALVES
FITTED
NOT REQUIRED
HOT WATER ZONE VALVES
FITTED
NOT REQUIRED
THERMOSTATIC RADIATOR VALVES
FITTED
AUTOMATIC BYPASS TO SYSTEM
FITTED
NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURERÕS INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE
ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE)
mbar
CENTRAL HEATING FLOW TEMPERATURE
oC
CENTRAL HEATING RETURN TEMPERATURE
oC
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE
ft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)
mbar
COLD WATER INLET TEMPERATURE
oC
HOT WATER OUTLET TEMPERATURE
oC
WATER FLOW RATE
lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS?
YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING?
N/A
YES
CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER'S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
m3/hr
m3/hr
COMMISSIONING ENG'S NAME PRINT
CORGI ID No.
SIGN
DATE
BOILER SERIAL No.
NOTIFICATION No.
BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
C O L L E C T I V E M A R K
N/A
N/A
202851-1new.pmd
17/11/2006, 07:41
62
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer's instructions. Always use the manufacturer's specified spare part when replacing all controls
SERVICE 1 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 2 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 7 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 8 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
202851-1new.pmd
17/11/2006, 07:41
63
Ideal Boilers, P.O. Box 103, National Ave, Kingston upon Hull,
HU5 4JN. Telephone: 01482 492 251 Fax: 01482 448 858.
Registration No. London 322 137.
Technical Training
Caradon Ideal Limited pursues a policy of continuing
improvement in the design and performance of its products.
The right is therefore reserved to vary specification without
notice.
The Ideal Boilers Technical Training Centre offers a series
of first class training courses for domestic, commercial
and industrial heating installers, engineers and system
specifiers.
For details of courses please ring: .......... 01482 498 432
CERTIFIED PRODUCT
Manufactured under a BS EN ISO 9001:
2000 Quality System accepted by BSI
The code of practice for the installation,
commissioning & servicing of central heating systems
Ideal Installer/Technical Helpline: 01482 498 663
www.idealboilers.com
202851-1new.pmd