Siemens FDOOT271 Technical Manual
Read Online
Read the Siemens FDOOT271 Technical Manual online using the built-in PDF viewer.
Text of the manual
Control Products and Systems
FDOOT271
Radio fire detector
Technical Manual
Technical specifications and availability subject to change without notice.
© Siemens Switzerland Ltd, 2011
Transmittal, reproduction, dissemination and/or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights created by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2015-03-11
Document ID: A6V10227635_g_en_--
Table of contents
1
About this document ......................................................................................5
1.1
Applicable documents .......................................................................................7
1.2
Download center...............................................................................................7
1.3
Technical terms ................................................................................................7
1.4
Revision history ................................................................................................8
2
Safety ..............................................................................................................9
2.1
Safety instructions ............................................................................................9
2.2
Safety regulations for the method of operation ................................................ 11
2.3
Standards and directives complied with .......................................................... 13
2.4
Release Notes ................................................................................................ 13
3
Structure and function ................................................................................. 14
3.1
Overview ........................................................................................................ 14
3.1.1
Details for ordering........................................................................... 15
3.1.2
Product version ES .......................................................................... 15
3.1.3
Features of fire detection functions ................................................... 16
3.1.4
Sensory ........................................................................................... 17
3.2
Power supply .................................................................................................. 18
3.3
Function ......................................................................................................... 19
3.3.1
Parameter sets ................................................................................ 19
3.3.2
Danger levels ................................................................................... 19
3.3.3
Diagnosis levels ............................................................................... 20
3.3.4
Internal alarm indicator..................................................................... 20
3.3.5
Renovation mode ............................................................................. 22
3.3.6
Test mode ....................................................................................... 23
3.3.7
Degraded mode in the FDnet/C-NET................................................ 23
3.3.8
Interface to service devices .............................................................. 23
3.4
Mechanical setup ............................................................................................ 24
3.5
Accessories .................................................................................................... 25
3.5.1
Detector base FDB271..................................................................... 25
3.5.2
Battery pack BAT3.6-10 ................................................................... 25
3.5.3
Detector locking device FDBZ293 .................................................... 25
3.5.4
Designation plate FDBZ291 ............................................................. 26
3.5.5
Detector dust cap FDZ291 ............................................................... 26
3.5.6
Detector base seal RS720 ............................................................... 26
Planning ........................................................................................................ 27
4.1
Compatibility FDnet/C-NET ............................................................................. 27
4.2
Ambient features ............................................................................................ 28
4.3
Parameter sets for FDOOT271 ....................................................................... 29
4.3.1
Sensor mode 0 'Neural fire detector' ................................................ 29
4.3.1.1
Description ...................................................................................... 29
4.3.1.2
Use .................................................................................................. 30
4.3.1.3
Specification .................................................................................... 30
4.3.2
Sensor mode 1 'Heat detector' ......................................................... 31
4.3.2.1
Description ...................................................................................... 31
4.3.2.2
Specification .................................................................................... 31
4.3.3
Sensor mode 2 'Smoke detector' ...................................................... 32
4.3.3.1
Description ...................................................................................... 32
4.3.3.2
Use .................................................................................................. 32
4.3.3.3
Specification .................................................................................... 32
4.4
Application examples ...................................................................................... 33
5
Mounting / Installation .................................................................................. 34
5.1
Required space .............................................................................................. 34
5.2
Detector base FDB271 ................................................................................... 35
5.3
Installing the radio fire detector FDOOT271 .................................................... 36
5.4
Detector locking device FDBZ293 ................................................................... 38
5.5
Designation plate FDBZ291 ............................................................................ 39
5.6
Detector dust cap FDZ291 .............................................................................. 40
5.7
Detector base seal RS720 .............................................................................. 41
6
Commissioning............................................................................................. 42
7
Maintenance / Repair .................................................................................... 43
7.1
Status query ................................................................................................... 43
7.2
Performance check ......................................................................................... 43
7.3
Testing detectors ............................................................................................ 44
7.4
Confirming the detector position...................................................................... 44
7.5
Establishing factory settings............................................................................ 45
7.6
Basic principles for replacing the battery pack ................................................. 46
7.7
Replacing the battery pack ............................................................................. 47
8
Specifications ............................................................................................... 49
8.1
Technical data ................................................................................................ 50
8.2
Dimensions .................................................................................................... 51
8.3
Environmental compatibility and disposal ........................................................ 51
Glossary ...................................................................................................................... 52
Index
....................................................................................................................... 53
About this document
1
Applicable documents
5
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
1
About this document
Goal and purpose
This document contains all information on the radio fire detector FDOOT271.
Following the instructions consistently will ensure that the product can be used
safely and without any problems.
Intended use
The radio fire detector FDOOT271 may only be used in a detector base FDB271
and together with a radio gateway FDCW241 in a fire detection system
FS20/FS720.
Target groups
The information in this document is intended for the following target groups:
Target group
Activity
Qualification
Product Manager
l
Is responsible for information passing
between the manufacturer and regional
company.
l
Coordinates the flow of information
between the individual groups of people
involved in a project.
l
Has obtained suitable specialist training
for the function and for the products.
l
Has attended the training courses for
Product Managers.
Project Manager
l
Coordinates the deployment of all
persons and resources involved in the
project according to schedule.
l
Provides the information required to run
the project.
l
Has obtained suitable specialist training
for the function and for the products.
l
Has attended the training courses for
Project Managers.
Project engineer
l
Sets parameters for product depending
on specific national and/or customer
requirements.
l
Checks operability and approves the
product for commissioning at the place
of installation.
l
Is responsible for trouble-shooting.
l
Has obtained suitable specialist training
for the function and for the products.
l
Has attended the training courses for
Product Engineer.
Installation personnel
l
Assembles and installs the product
components at the place of installation.
l
Carries out a performance check
following installation.
l
Has received specialist training in the
area of building installation technology
or electrical installations.
Maintenance personnel
l
Carries out all maintenance work.
l
Checks that the products are in perfect
working order.
l
Searches for and corrects malfunctions.
l
Has obtained suitable specialist training
for the function and for the products.
Source language and reference document
l The source/original language of this document is German (de).
l The reference version of this document is the international version in English.
The international version is not localized.
About this document
Applicable documents
6
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
Document identification
The document ID is structured as follows:
ID code
Examples
ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international
A6V10215123_a_de_DE
A6V10215123_a_en_--
A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
Conventions for text marking
Markups
Special markups are shown in this document as follows:
⊳
Requirement for a behavior instruction
1.
2.
Behavior instruction with at least two operation sequences
–
Version, option, or detailed information for a behavior instruction
⇨
Intermediate result of a behavior instruction
⇨
End result of a behavior instruction
l
Numbered lists and behavior instructions with an operation
sequence
[➙ X]
Reference to a page number
'Text'
Quotation, reproduced identically
Identification of keys
>
In addition to relation symbols and for identification between steps
in a sequence, e.g., 'Menu bar' > 'Help' > 'Help topics'
↑ Text
Identification of a glossary entry
Supplementary information and tips
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
About this document
1
Applicable documents
7
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
1.1
Applicable documents
Document ID
Title
001508
Guidelines Connection factors, line resistances and
capacitances for fire detection systems collective, AnalogPLUS,
interactive, FDnet
008331
List of compatibility (for 'Sinteso™' product line)
009409
Data sheet Colored detectors, bases and base attachment
FDO.., FDOOT…, FDT…, FDB…
010030
Application guideline Sinteso Fire detectors
A6V10208552
Installation Detector locking device FDBZ293
A6V10227631
Planning Radio fire detection system SWING
A6V10227637
Installation Radio fire detector FDOOT271, Detector base
FDB271
A6V10227639
Technical manual Radio gateway FDCW241
A6V10227643
User Guide SWING-Tool FXS2061
A6V10229261
List of compatibility (for 'Cerberus™ PRO' product line)
A6V10254740
Operating instructions Solo461 heat detector tester kit RE7T
A6V10271323
Data sheet SWING Neural radio fire detector FDOOT271,
FDCW241
A6V10367669
Open-Source Software (OSS) Licenses SWING
1.2
Download center
You can download various types of documents, such as data sheets, installation
instructions, and license texts via the following Internet address:
http://siemens.com/bt/download
l Enter the document ID in the 'Find by keyword' input box.
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
1.3
Technical terms
Term
Explanation
AI
Alarm indicator
Battery empty
Fault message in the event of a battery failing completely
Battery low
Fault message in the event that the spare battery is activated
FDnet/C-NET
Addressed detector line
LED
Light-emitting diode
About this document
Revision history
8
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
1.4
Revision history
The reference document's version applies to all languages into which the reference
document is translated.
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
Modification index
Edition date
Brief description
g
2015-03-11
l
Detector base seal RS720 added; mounting marking in 'Mechanical
setup' chapter removed
l
Flashing behavior table added
l
Editorial changes
f
2014-01-31
Changes in chapter: Parameter sets for FDOOT271; data sheet in
'Applicable documents' chapter added; reference to approvals added;
information on flashing pattern and sensory added; chapter with reference
to download center added; neural fire detector function added; value for
response sensitivity changed
e
2013-09-01
Changes in chapter: Planning, Technical data
Note on service devices added
d
2012-11-02
Parameter sets extended
c
2012-10-19
Value for permissible wind speed changed
b
2012-05-01
Editing
a
2011-11-01
First edition
The language versions and country variants produced by a local company have
the same modification index as the corresponding reference document. They are
not however included in the table below.
The table below shows the published language versions and country variants with
the corresponding modification index:
Modification index
en_--
de_--
fr_--
it_--
es_--
g
X
X
X
X
X
f
–
X
–
–
–
e
X
X
X
X
X
d
–
X
–
–
–
c
X
X
X
X
X
b
X
X
X
X
X
a
–
X
–
–
–
X = published
– = no publication with this modification index
The safety notices must be observed in order to protect people and property.
The safety notices in this document contain the following elements:
l Symbol for danger
l Signal word
l Nature and origin of the danger
l Consequences if the danger occurs
l Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury.
Follow all measures identified by this symbol to avoid injury or death.
Additional danger symbols
These symbols indicate general dangers, the type of danger or possible
consequences, measures and prohibitions, examples of which are shown in the
following table:
General danger
Explosive atmosphere
Voltage/electric shock
Laser light
Battery
Heat
Signal word
The signal word classifies the danger as defined in the following table:
Signal word
Danger level
DANGER
DANGER identifies a dangerous situation, which will result directly in death or
serious injury if you do not avoid this situation.
WARNING
WARNING identifies a dangerous situation, which may result in death or serious
injury if you do not avoid this situation.
CAUTION
CAUTION identifies a dangerous situation, which could result in slight to
moderately serious injury if you do not avoid this situation.
NOTICE
NOTICE identifies possible damage to property that may result from non-
observance.
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Nature and origin of the danger
Consequences if the danger occurs
●
Measures / prohibitions for danger avoidance
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
●
Measures / prohibitions for danger avoidance
Safety regulations for the method of operation
11
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
2.2
Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant
European and international safety standards. Should additional national or local
safety standards or legislation concerning the planning, mounting, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
●
Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
l Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
l Lock volt-free areas to prevent them being switched back on again by mistake.
l Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
l Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
l Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
l Produce earthing as stated in local safety regulations.
Mounting, installation, commissioning and maintenance
l If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
l When starting the fire control panel ensure that unstable conditions cannot
arise.
l Ensure that all points listed in the 'Testing the product operability' section below
are observed.
l You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Safety regulations for the method of operation
12
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
Testing the product operability
l Prevent the remote transmission from triggering erroneously.
l If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
l The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions must be observed:
–
Use the correct potential for activation; this is generally the potential of the
building installation.
–
Only check controls up to the interface (relay with blocking option).
–
Make sure that only the controls to be tested are activated.
l Inform people before testing the alarm devices and allow for possible panic
responses.
l Inform people about any noise or mist which may be produced.
l Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
l Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
l Only use fuses with the specified fuse characteristics.
l Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by
Siemens.
l Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrect application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
l Personal injuries or damage to property caused by improper use and incorrect
application
l Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
l Personal injury or damage to property caused by poor maintenance or lack of
maintenance
Standards and directives complied with
13
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
2.3
Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens
contact.
2.4
Release Notes
Limitations to the configuration or use of devices in a fire detection installation with
a particular firmware version are possible.
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
●
Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
●
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
●
Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
●
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
Structure and function
Overview
14
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3
Structure and function
In this document, the term 'detector' refers to an automatic fire detector that
communicates with a radio gateway and other radio devices in a radio cell using
radio signals. The detector is connected to a control panel FC20xx or FC72x via
the radio gateway and the detector line.
3.1
Overview
Properties
l Radio communication with:
–
Radio gateway
–
Other radio devices
l Signal processing with ASAtechnology and optional detection behavior
(application-specific ASA parameter sets)
l Software can be used to set as:
–
Neural fire detector
–
Heat detector
–
Wide-spectrum smoke detector
l Internal alarm indicator with status display (red and green):
–
identifies alarm
–
confirms positioning on detector base
–
confirms contact with the radio network
l Easy installation on the detector base
Structure and function
3
Overview
15
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.1.1
Details for ordering
Type
Order no.
Designation
FDOOT271
S54313-F1-A1
Radio fire detector
FDOOT271
S54313-F1-A2 +
RAL no.
Radio fire detector (colored)
The battery pack and detector base are not included in the scope of delivery. A
battery pack and detector base are required for commissioning and operation.
3.1.2
Product version ES
The product version ES provides the technical status of a device in terms of
software and hardware. The product version is provided as a two-digit number.
You will find the details of your device's product version:
l On the packaging label
l On the product label or the type plate
Product version on the packaging label
Details of the product version can be found directly on the packaging label in the
barcode:
ES
Example of a packaging label with details of the product version
Product version on the product label and the type plate
Details of the product version can be found after the device order number:
ES
04
Example of a product label with details of the product version
Depending on the product and various approvals, the product labels may differ in
terms of the information type and layout.
Look for your device's order number on the product label.
You will find the product version after the order number.
Structure and function
Overview
16
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.1.3
Features of fire detection functions
The FDOOT271 has the following features in terms of its fire detection functions:
l Dynamic influence on the parameter sets
l Pattern recognition
l Real time interpretation of the situation
l Process- and time-controlled switchover of the parameter sets
Signal processing is based on ASAtechnology (ASA = Advanced Signal Analysis).
ASAtechnology can also be characterized as second generation algorithms. Signal
processing with ASAtechnology allows for optimum adaptation of detector behavior
to the corresponding ambient conditions.
The detectors are characterized by their unique detection reliability and high
immunity to deceptive phenomena.
Operating mode: Signal processing with ASAtechnology
The figure below shows signal processing in the form of a diagram.
C
Dynamic influence
of parameter
Environment
Evaluation of the
situation
Danger
level
Result
Algorithms
Signal analysis
Sensory
Signal processing with ASAtechnology
Structure and function
3
Overview
17
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
Sensory
The signals captured by the sensory are transmitted to the algorithm. The
algorithms are set by selecting the parameter set.
Algorithms
In comparison to the detection algorithms, the individual parameters of the selected
parameter set can be adapted with ASAtechnology. A real time interpretation of the
situation leads to a dynamic influence on the algorithm. This results in a
broadening of the application range of the parameter set and thus of the detector.
The detector reacts more sensitively in the event of fire, and more robustly in the
event of deceptive phenomena.
Switching over the parameter set
In addition to selecting the parameter set, the detectors enable time- or process-
controlled switching over of the parameter sets (Manned/Unmanned switchover).
Thanks to this function, the detector can be used in places where the situation
changes significantly on a regular basis (e.g., kitchen, production hall).
3.1.4
Sensory
The radio fire detector has optical and thermal sensors. The radio fire detector can
be parameterized as a smoke detector or a heat detector.
1
2
3
4
Fire detector structure
1 Heat sensors
3 Forward scatterer
2 Backward scatterer
4 Labyrinth
The radio fire detector has a sophisticated opto-electronic measuring chamber with
two optical transmitters, an optical receiver, and two thermal sensors.
The transmitters illuminate the smoke particles from different angles. One sensor
acts as forward scatterer, the other as backward scatterer. The scattered light then
hits the receiver (photodiode) and generates a measurable electric signal.
The combination of a forward and backward scatterer facilitates an optimum
detection and the differentiation of light and dark particles, which leads to a
homogenous response behavior and optimizes the differentiation of wanted signals
and deceptive phenomena.
Structure and function
Power supply
18
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
The combination of optical and thermal sensor signals optimizes detection
reliability. This has the following advantages:
l Early detection of all types of fire, whether they generate light or dark smoke, or
no smoke at all.
l The neural fire detector can be operated at a lower sensitivity level and thus
achieves a higher immunity against false alarms which may otherwise be
caused by cold aerosols (e.g. by smoking, electrical welding, etc.). In the case
of an open fire, the smoke sensitivity is heightened by the temperature
increase, which means that a detection reliability level that is comparable to
that of the wide-spectrum smoke detector can be achieved.
In addition, the heat sensors make it possible to detect fires without smoke
generation.
The radio fire detector can be used purely as an optical smoke detector or purely
as a heat detector. This is determined by selecting one of the following sensor
modes (using the control panel):
l Sensor mode 0: Application as neural fire detector
l Sensor mode 1: Application as heat detector
l Sensor mode 2: Application as smoke detector
3.2
Power supply
The battery pack BAT3.6-10 supplies the radio devices with power. The battery
pack consists of lithium batteries plus a battery cable and a battery connector.
1
2
3
4
Battery pack BAT3.6-10
1
Battery pack consisting of:
l
4 lithium batteries for normal operation
l
1 lithium battery as a spare in the case of 'Battery low' operation
2
Label with area for filling in the commissioning date
3
Battery cable
4
Battery connector with protection against polarity reversal
Properties
l In normal operation: Can be used for the service life stated
l In 'Battery low' operation: subject to reduced operating life
l Connections cannot be reversed thanks to battery connector with protection
against polarity reversal
Structure and function
3
Function
19
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.3
Function
3.3.1
Parameter sets
The detection behavior of the detectors is influenced by the parameter sets, so that
it can be specifically adjusted to the fire phenomena and environmental conditions
to be expected in the environment to be monitored.
The parameter sets for smoke and heat detection are programmed in the
detectors. During commissioning, the optimum parameter set must be selected for
the conditions at the place of installation. This is carried out using the control panel.
3.3.2
Danger levels
The detector's signal processing efficiently distinguishes between fire events and
deceptive phenomena. The basis for reaching a danger level is not only given by
measured values exceeding a 'response threshold'; moreover, the smoke density
progression is observed over a longer period of time and assessed by the
algorithms.
Fire detectors can transmit the following danger levels to the control panel:
Danger level
Meaning
Comment
0
No danger
Normal condition
1
Check the situation.
A different parameter set should
potentially be selected (inappropriate
application)
2
Warning
Possible danger
3
Alarm
Fire
The evaluation of the danger level and the decisions to be taken (e.g. activation of
remote transmission) are configured in the control panel.
Structure and function
Function
20
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.3.3
Diagnosis levels
The detector monitors its operation largely autonomously. The signals of all
sensors are permanently monitored. In particular, the temperature sensors, light
emitters, and light receivers are monitored to ensure that they are functioning
correctly. Signal processing takes account of the monitoring results and adapts its
behavior accordingly.
The following diagnosis levels are derived from the different control measurements:
l Normal
l Observe information
l Replacement recommended
l Replacement necessary
l Fault
When an error occurs which impairs the correct functionality of the detector, a fault
message is reported to the control panel. To correct the cause of the fault,
additional information is available in the detector. The diagnosis levels can be read
out using the FXS2061 SWING tool. You will find more information in
document A6V10227643.
See also
2 Applicable documents [➙ 7]
3.3.4
Internal alarm indicator
The internal alarm indicator's LED has two colors and shows the operating
condition of the radio fire detector.
1
1 Internal alarm indicator
The table below describes the flashing behavior of the internal alarm indicator in
the radio fire detector FDOOT271:
Several flashing patterns are available for normal operation. The flashing pattern
is selected using the software 'FXS2002'.
Structure and function
3
Function
21
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
Operating condition
Flashing mode
Graphic
Alarm
IAI flashes red
once a second
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
Alarm in test mode
IAI flashes green
twice every
four seconds and
red every second
in-between
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
Fault
There is an error.
IAI flashes red
four times every
second
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
Commissioni
ng
The radio fire detector
has not yet been
logged on to a radio
gateway.
And
The radio fire detector
is not installed on a
detector base.
And
There is no contact
with the radio network.
IAI flashes red
once every two
seconds
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
The radio fire detector
has already been
logged on to a radio
gateway.
And
The radio fire detector
is not installed on a
detector base.
And
There is no contact
with the radio network.
IAI flashes green
once every two
seconds
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
The radio fire detector
is installed on the
base but has not yet
been logged on to the
radio network.
IAI flashes green
twice every two
seconds
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
Normal
Configuration 1
IAI flashes green
once every 30
seconds
t
0
1
2
3
4
5
6
7
8
9
31
30
[s]
Configuration 2
IAI off
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
Test
IAI flashes green
twice every four
seconds
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
New battery
IAI lights up once
for five seconds
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
x1
Battery is flat
IAI off
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
Structure and function
Function
22
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
Several operating conditions may be indicated at the same time. This may lead to
the flashing patterns overlapping one another. The red LED indicator has priority
over the green LED indicator.
Flashing patterns with a higher frequency will overlap those with a lower
frequency, which means that the latter may no longer be discernible.
Not all fire control panels support the flashing patterns described.
Please also observe the documentation for your fire detection system.
3.3.5
Renovation mode
Renovation mode is set using the control panel.
Renovation mode can be used under the following conditions:
l If there is a large amount of dust in the air around the radio fire detector
temporarily
l If there are aerosols in the air around the radio fire detector temporarily
The radio fire detector does not issue alarms in renovation mode until a
temperature of 80 °C has been exceeded for 20 seconds.
You will find more detailed information in the fire detection system documentation.
Structure and function
3
Function
23
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.3.6
Test mode
In test mode the radio fire detectors react faster and with a higher sensitivity level.
For testing purposes, the radio fire detectors can be set to test mode using the
control panel or the FXS2061 SWING tool.
The following tests can be performed:
l Test of optical detector function using test gas
l Test of heat detector function using hot air
You will find more detailed information in the fire detection system documentation.
3.3.7
Degraded mode in the FDnet/C-NET
When the main processor of the fire control panel fails, the control panel is in
degraded mode operation. Depending on the control panel type, the fire control
panel can continue to perform the most important alarming and signaling functions
in degraded mode operation.
l There are no restrictions on the function of the detector when it is in degraded
mode operation.
l Degraded mode operation does not affect radio cell communication.
l A fault message is transmitted to the fire control panel via the radio gateway.
The fire control panels support degraded mode operation in different ways.
During planning, therefore, you must observe the information in the 'List of
compatibility' document and the fire control panel documentation. See the
'Applicable documents [➙ 7]' chapter.
You will find more detailed information in the fire detection system documentation.
3.3.8
Interface to service devices
The fire control panel or the software FXS2061 SWING tool is used to read out and
set the parameter sets.
The detector exchanger and tester FDUD292 and the intelligent detector tester
FDUD293 cannot be used to read out or set the parameter sets.
See also
2 Applicable documents [➙ 7]
Structure and function
Mechanical setup
24
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.4
Mechanical setup
An installed detector base FDB271 is required to install the detector.
Once the detector is ready for use, twist it onto the detector base either manually or
using the detector exchanger.
new
2
3
1
8
4
5
6
7
Mechanical setup
1
Battery connector
5
Fixing screws
2
Battery pack
6
Detector
3
Switch
7
Internal alarm indicator
4
Detector base
8
'new' button
See also
2 Accessories [➙ 25]
Structure and function
3
Accessories
25
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.5
Accessories
3.5.1
Detector base FDB271
l
For installing radio fire detectors
l
Directly attached to the mounting surface
l
Fastened with two screws
l
Compatible with:
–
Radio fire detector FDOOT271
–
Wireless alarm sounder FDS271
l
Order no. FDB271-W: S54319-F12-A1
l
Order no. FDB271-R: S54xxx-Fx-Ax
See also
2 Detector base FDB271 [➙ 35]
3.5.2
Battery pack BAT3.6-10
l
For supplying radio devices and the radio gateway
with power
l
Lithium batteries
–
BAT3.6-10 LI-SOCl2 battery pack 3.6 V, 10 Ah
l
Batteries with battery cable
l
Connector system with protection against polarity
reversal
l
Inscription field for commissioning date
l
Compatible with:
–
Radio gateway FDCW241
–
Radio manual call point FDM273
–
Radio fire detector FDOOT271
l
Order no.: S54370-Z11-A1
3.5.3
Detector locking device FDBZ293
l
For protection against theft
l
Compatible with:
–
Point detectors from the 'Sinteso' product line
–
Alarm sounder FDS221
–
Alarm sounder with supplementary optical
indication FDS229
–
Interbase FDSB22x
l
Order no.: A5Q00005035
See also
2 Detector locking device FDBZ293 [➙ 38]
Structure and function
Accessories
26
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.5.4
Designation plate FDBZ291
l
To identify the location
l
Compatible with:
–
Detector base FDB2xx/-AA
–
Detector base FDB271
–
Sounder base FDSB29x
–
Base attachment FDB291
–
Interbase FDSB22x
l
Order no.: A5Q00002621
See also
2 Designation plate FDBZ291 [➙ 39]
3.5.5
Detector dust cap FDZ291
l
To protect the point detector from dust
l
Compatible with:
–
Point detectors from the 'Sinteso' product line
l
Order no.: A5Q00004814
See also
2 Detector dust cap FDZ291 [➙ 40]
3.5.6
Detector base seal RS720
l
For mounting in wet rooms
l
Protection category IP42
l
Compatible with:
–
Detector base (collective) DB110
–
Detector base (collective) DB110x
–
Detector base (collective) DB110xx
–
Detector base FDB271
–
Detector base FDB271-R
l
Not compatible with:
–
Designation plate FDBZ291
l
Order no.: S54319-F8-A1
The radio connection means that there is no need to wire the radio devices,
such as the radio fire detector, radio manual call point, etc., in the usual way.
Together with the radio gateway, the radio devices form a radio cell. The control
panel treats this radio cell as a loop or a stub. It is used for the 'Sinteso' and
'Cerberus PRO' product lines.
In the 'Planning' document (A6V10227631), you will find detailed information about
the components of the radio fire detection system as well as the necessary devices
and device combinations.
You will find more information in the 'List of compatibility'.
See also
2 Applicable documents [➙ 7]
2 Applicable documents [➙ 7]
4.1
Compatibility FDnet/C-NET
Compatible with control panels that support the FDnet/C-NET detector line.
Detector line
Control panel
FC20xx
FC72x
SIGMASYS
AlgoRex
FDnet
X
From MP5
–
–
–
C-NET
–
X
From IP5
–
–
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
In selecting the optimum parameter set, the following factors must be taken into
account:
l Risk of damage to persons
l Value concentration
l Room geometry
l Deceptive phenomena
l Risk of fire
l Critical fire size
Risk of injury to persons
People's lives are severely at risk in venues such as concert halls, nursing homes,
and hospitals. The risk of damage to persons is therefore very high in such places.
In canteen kitchens the situation is different. Few people work in such facilities and
are able to save themselves in the event of timely alarms. The risk of damage to
persons is thus rather low in this case.
Value concentration
Irreplaceable cultural assets are often on display in museums. Computer centers
house servers with large data volumes. The concentration of valuable items is
rather high. In a normal hotel room the concentration of valuable items must be
classified as low.
Room geometry
High ceilings, complex room shapes or well-ventilated rooms have a complex room
geometry. This aggravates early fire detection, as it is difficult for the fire
phenomenon to reach the fire detector. An office room with normal ceiling height
has a simple room geometry.
Deceptive phenomena
Deceptive phenomena can deceive a fire detector and bring about a false alarm.
The deceptive phenomena differ depending on the fire detector. Examples of
deceptive phenomena include steam, cigarette smoke, dust, dry ice in
discotheques, exhaust fumes, aerosols occurring during welding, and heat sources
such as radiant heaters or hot engines.
In a small hotel room with a rather low ceiling where vapor from the bathroom may
penetrate the room, or in operating facilities where a lot of dust is generated, many
deceptive phenomena must be taken into consideration. In a clean room where
electronic modules are fabricated the risk of deceptive phenomena is rather low.
Risk of fire
In production facilities where highly combustible materials such as flammable
liquids, cotton, paper, etc., are processed and where electrical machines are
operated, the risk of fire is very high. Minor overheating or sparks may cause a fire.
In a storehouse where steel is stored and where no electrical installation is
provided with the exception of lighting, the fire risk is very low.
Critical fire size
When a waste paper basket in a metal-processing facility catches fire, the
consequential damage is usually rather low. Here we are talking about a critical,
medium fire size that can still be tolerated. The situation is completely different in
pharmaceutical production facilities where even the lowest smoke concentration
may impair the process and where combustible materials are processed. Even the
smallest fire must be detected immediately. Therefore, we need to define what is
termed a small admissible critical fire size.
Parameter sets for FDOOT271
29
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
4.3
Parameter sets for FDOOT271
4.3.1
Sensor mode 0 'Neural fire detector'
4.3.1.1
Description
(Parameter set numbers in brackets)
Robust (0)/(2):
The priority of the 'Robust' parameter set is to a robust response. The sensitivity is
the same as with the 'Suppression' parameter set; however, deceptive phenomena
are not explicitly analyzed and suppressed. It is thus particularly suited to
application in rooms where deceptive phenomena such as cigarette smoke or dust
can be expected. The 'Robust (2)' parameter set is suitable for higher rooms in
comparison to the 'Suppression (5)' parameter set.
Balanced (4):
The 'Balanced' parameter set reveals a balanced response behavior regarding
reaction to fires and robustness to deceptive phenomena. It reacts faster with open
fires. It reacts slower with vapor, cigarette smoke or smoldering fires.
Suppression (5):
Thanks to its very robust behavior, the 'Suppression' parameter set is particularly
suitable for rooms where deceptive phenomena such as cigarette smoke or
exhaust fumes can be expected. It reacts in a very robust way to the deceptive
phenomenon vapor.
Fast Response (6):
This parameter set reacts in a fast and highly sensitive manner. It is thus especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
High Sensitive Fast (9):
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response'.
This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Download 1 (14) / download 2 (15):
Application-specific parameter sets that can be loaded on site (depending on the
control panel).
Parameter sets for FDOOT271
30
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
4.3.1.2
Use
No. Name
Risk of damage
to persons
Concentration
of valuable
items
Room
geometry
Deceptive
phenomena
Risk of fire
Critical fire size
small…
large
low…
high
simple…
complex
few…
many
small…
large
small…
medium
0
Robust
2
Robust
4
Balanced
5
Suppression
6
Fast Response
9
High Sensitive
Fast
The 'High Sensitive Fast' parameter set is only suitable for special applications.
4.3.1.3
Specification
The following table displays the properties and fields of application of the
parameter sets of radio fire detector FDOOT271 in sensor mode 0.
No.
Name
Optical
Thermal
Typ. Response
time
from - typ. - to
Sensitivity,
open fire
Sensitivity,
smoldering fire
Static
activation
temperature
Differential activation
temperature 1
Differential
activation
possible from:
[s]
[%/m]
[%/m]
[°C]
∆T [K]
[°C]
0
Robust
80
3.2
11.4
80
29
30
2
Robust
80
3.2
11.4
80
29
30
4
Balanced
40 - 64 - 300
2.3
8
80
25
30
5
Suppression
90 -160 - 760
3.2
11.4
80
29
30
6
Fast Response
20 - 30
1.6
5.6
80
22
3
9
High Sensitive Fast
20 - 30
0.8
2.8
60
16
3
14
Application-specific parameter sets
15
1 Applicable with fast temperature increases >10 K/min.
All parameter sets except for 14 and 15 comply with standards EN 54-7 and
CEA 4021.
Parameter sets for FDOOT271
31
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
4.3.2
Sensor mode 1 'Heat detector'
4.3.2.1
Description
This sensor mode is especially suited for applications where the detector should
only react thermally.
The heat detector FDOOT271 has the following parameter sets:
l A1R (1)
l A1S (3)
Notes on A1 designations
l A1 parameter sets should be operated at a room temperature of around 25 °C.
However, they can be applied at temperatures up to 50 °C. The static response
temperature is 60 °C.
Notes on the designations R and S
Compared with S parameter sets, R parameter sets also trigger an alarm when the
temperature increases (e.g. from 20 °C to 50 °C within a few minutes).
4.3.2.2
Specification
No.
Name
Operating
temperature
typ. / max.
Static activation
temperature 1
Differential activation
temperature 2
Differential activation
possible from:
[°C]
[°C]
∆T [K]
[°C]
1
A1R
60 °C rate of
rise
25 / 50
60
25
3
3
A1S
60 °C
maximum
25 / 50
60
–
–
1 Applicable with slow temperature increases <1 K/min.
2 Applicable with fast temperature increases of >10 K/min. When there is a slow
temperature increase of < 10 K/min, this value rises by a few degrees.
This parameter set meets the criteria of standard EN 54-5.
Parameter sets for FDOOT271
32
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
4.3.3
Sensor mode 2 'Smoke detector'
4.3.3.1
Description
This sensor mode should be selected if fast temperature changes that are not
caused by fire may occur (e.g. in the case of radiant heaters, hot engines). In this
sensor mode the detector only reacts optically; this is comparable with a wide-
spectrum smoke detector. Having to a second optical sensor, however, it reveals a
balanced response behavior in relation to the different types of fire.
Universal (1):
With 'Universal' the sensitivity and response time to aerosols are between 'Robust'
and 'Sensitive'.
Robust (2):
This parameter set responds to aerosols in a similar way as the neural fire detector
FDOOT271 in sensor mode 0 with the 'Robust' parameter set, without taking into
account the temperature.
Sensitive (3):
With regard to aerosols, this parameter set reacts in a way that is comparable to
'Fast Response' in sensor mode 0 without temperature influence.
4.3.3.2
Use
No.
Name
Risk of damage
to persons
Concentration
of valuable
items
Room
geometry
Deceptive
phenomena
Risk of fire
Critical fire size
small…
large
low…
high
simple…
complex
few…
many
small…
large
small…
medium
1
Universal
2
Robust
3
Sensitive
4.3.3.3
Specification
No.
Name
Response time [s]
Sensitivity
open fire/smoldering fire
[%/m]
1
Universal
50
2.3 / 8
2
Robust
80
2.3 / 8
3
Sensitive
30
1.6 / 5.6
All parameter sets meet the criteria of standard EN 54-7.
Please refer to document 010030 for application recommendations, such as
choosing the detector type and its settings for various applications.
See also
2 Applicable documents [➙ 7]
Mounting / Installation
Required space
34
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5
Mounting / Installation
5.1
Required space
l Upon insertion of the detector, the detector base is stressed by compression,
tension and torsion. The fixing must thus be designed accordingly.
l Detector bases must be placed flat on the ceiling.
l Avoid mounting on steps, concrete ribs, etc.
l When selecting the installation position, take into account any structures that
may impair radio reception.
l There must be at least 50 cm of free space below and at least 2 cm to the
sides of the detector, so that the detector can be removed with the detector
exchanger.
l Contorted detector bases complicate or even impede the insertion of the
detectors with the detector exchanger.
* = min. 2 cm
min. 50 cm
Minimum spacing when installing detector bases
Mounting / Installation
5
Detector base FDB271
35
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5.2
Detector base FDB271
The detector base must be securely connected to the substructure.
Screw the detector base securely onto the substructure using two screws.
2
2
11
2
4
2
3
46 mm
90 mm
Installing the detector base
1 Detector base
2 Screws with max. Ø of 4 mm
3 Holder for detector locking device
4 Switching cam
See also
2 Detector base FDB271 [➙ 25]
Mounting / Installation
Installing the radio fire detector FDOOT271
36
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5.3
Installing the radio fire detector FDOOT271
The action of inserting the radio fire detector into the detector base activates it;
the detector then logs on to other radio devices immediately. Therefore, start from
the radio gateway and work outwards to install the individual radio fire detectors.
1
2
4
5
3
Installing the radio fire detector
1
Battery pack BAT3.6-101
4
Battery cable
2
Inserting the battery pack
5
Battery connector
3
Holder
1 not included in the scope of delivery
The flashing behavior of the internal alarm indicator is described in the technical
manual A6V10227635 provided by the manufacturer in the 'Internal alarm
indicator [➙ 20]' chapter.
w The radio gateway has been activated and switched to maintenance mode.
w The radio fire detector is set to the factory settings.
w You have the battery pack and the required accessories to hand.
w The detector base FDB271 is installed [➙ 35].
Mounting / Installation
5
Installing the radio fire detector FDOOT271
37
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
1.
Install the accessories you require.
2.
Label the new battery pack (1) with the current date.
3.
Connect the battery connector (5) of the new battery pack.
4.
Insert the new battery pack (1), paying attention to the position of the battery
cable (arrows at 4).
5.
Make sure that the holder (3) latches into place correctly.
a When the battery connector is connected, the internal alarm indicator lights
up red for 5 seconds.
a After a further 10 seconds, the radio fire detector signals that it is not
installed on the detector base and the internal alarm indicator flashes. If it
flashes red, this indicates the factory settings. If it flashes green, this
indicates that the radio fire detector has already been logged on to a radio
gateway.
a If this does not happen, this means the battery pack is defective and must
not be used.
6.
Insert the radio fire detector into the detector base.
a The internal alarm indicator flashes green and the radio fire detector is
logged on to the radio gateway.
a If the process of logging on to the radio gateway is successful, the internal
alarm indicator stops flashing.
a The radio fire detector is now installed and is ready for commissioning.
See also
2 Detector base FDB271 [➙ 35]
2 Establishing factory settings [➙ 45]
2 Internal alarm indicator [➙ 20]
2 Establishing factory settings [➙ 45]
2 Internal alarm indicator [➙ 20]
Mounting / Installation
Detector locking device FDBZ293
38
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5.4
Detector locking device FDBZ293
The detector can be protected against theft with the detector locking device
FDBZ293.
Mounting of detector locking device FDBZ293
1 Detector base
4 Detector
2 Set screw with a hexagon socket
5 Allen key
3 Hole
1.
Place the 'set screw with a hexagon socket' (2) in the hole (3) on the
detector (4).
2.
Insert the detector (4) into the detector base (1).
3.
Using the Allen key provided (5), insert the 'set screw with a hexagon
socket' (2) through the hole in the detector base (1) and tighten.
a The detector can no longer be removed from the base without tools.
See also
2 Detector locking device FDBZ293 [➙ 25]
Mounting / Installation
5
Designation plate FDBZ291
39
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5.5
Designation plate FDBZ291
Designation plate FDBZ291 is used to assign a location address to the detector.
1.
Label the designation plate.
2.
Slide the designation plate into the detector base from the side.
AB 134 E
FDBZ291
FDB271
1
2
Installing the designation plate
1 Designation plate
2 Detector base
See also
2 Designation plate FDBZ291 [➙ 26]
Mounting / Installation
Detector dust cap FDZ291
40
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5.6
Detector dust cap FDZ291
During the construction phase the detector may be covered with a detector dust
cap FDZ291 to protect it from dust and dirt.
FDZ291
1
2
3
Mounting / removal of detector dust cap FDZ291
1
Detector
2
Detector dust cap
3
Removing detector dust cap by turning it to the right
The detector dust cap can be put on or removed either manually or using the
detector exchanger, e.g., FDUD291.
See also
2 Detector dust cap FDZ291 [➙ 26]
Mounting / Installation
5
Detector base seal RS720
41
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
5.7
Detector base seal RS720
l Use the detector base seal RS720 to install point detectors in wet rooms.
Protection category: IP42.
l Not compatible with designation plate FDBZ291.
Installing the detector base seal
1. NOTICE! Excessively large holes in the detector base seal will impair the
potential IP protection category. Do not cut or drill holes in the detector base
seal.
2.
Fit the detector base seal RS720 between the ceiling and the detector base or
the sounder base.
Installing the detector base seal RS720
When the battery connector is connected, the radio fire detector FDOOT271 is
activated. Once inserted into the detector base, the radio fire detector automatically
looks for radio devices within range in the vicinity and automatically integrates itself
into the radio network.
You will find the procedure for logging on and creating a radio cell in document
A6V10227639.
You must fully commission a radio cell before establishing the connection to the
FDnet/C-NET.
Insert the battery packs into the devices at the location where they are going to be
used just before commissioning the fire detection installation.
The device is commissioned via the control panel. The exact procedure is
described in the control panel documentation.
Conduct a performance check once commissioning is complete.
See also the following documents for more information:
l Document A6V10227639
l Document A6V10227631
See also
2 Applicable documents [➙ 7]
Maintenance / Repair
7
Status query
43
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
7
Maintenance / Repair
Check the detector on a regular basis, but at least once a year.
To do this, look for/check the following and resolve any problems you identify:
l Mechanical damage
l Soiling
l Correct fastening
l Detector function by means of test activation
7.1
Status query
The query is issued from the control panel, via the radio gateway.
The following queries may be issued:
l Danger level
l Detector fault
l Radio status
Depending on the authorization level of the user and the control panel type, the
following actions can be performed:
l Device test (Go/No Go or detailed by status polling)
l Activation of a test alarm
l Reading out the identification number, customer text and measure text
l Localizing and setting the parameters of the detector
l Switching off the detector
See also
2 Diagnosis levels [➙ 20]
2 Internal alarm indicator [➙ 20]
7.2
Performance check
The selftest automatically subjects the detectors to an extensive electrical
performance check. Regular performance checks of the detectors are required
nonetheless. These can be performed using test gas or hot air.
Recommendation:
l Perform a visual inspection on all detectors every year. Detectors that are
heavily soiled or mechanically damaged must be replaced.
l All detectors should be replaced after 6 to 8 years of service, depending on the
ambient conditions.
Maintenance / Repair
Testing detectors
44
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
7.3
Testing detectors
Depending on the sensor mode, testing may be performed with one or more of the
following tools:
l Test gas
–
Detector tester RE6 for smoke detectors
–
Test gas REF8-S (recommended)
–
Test gas REF8
l Hot air
–
Solo461 heat detector tester kit RE7T
The following table shows which mode may be tested with which test aid.
Mode
Test gas
Hot air
SWING tool
Sensor mode 1
–
X
Communication
Sensor mode 2
X
–
Communication
The fire detectors are highly resistant to deceptive phenomena. This means that
optical fire detectors, for example, will recognize the immediate occurrence of
smoke (such as that which occurs during testing with test gas) as a deceptive
phenomenon and will not trigger an alarm. This is desirable in normal operation;
however, it does make testing with test gas problematical.
To enable detector testing with test gas or hot air, the detector must be switched to
test mode. Testing with test gas or hot air is performed differently on addressed
detector lines and collective detector lines.
Proceed as follows:
1.
First switch the zone to 'Test' on the control panel.
2.
Then perform the test using test gas.
To trigger a detector using test gas, normally 2…4 gas discharges at intervals of
approx. 2 seconds are required. When the detector is in test mode, activation
takes place after approximately 10 seconds.
7.4
Confirming the detector position
The procedures in 'Testing detectors [➙ 44]' may also be used to confirm the
position of the detector.
l The corresponding status display on the radio gateway is cleared.
l The 'Device localization error' display on the control panel disappears.
See also
2 Testing detectors [➙ 44]
Maintenance / Repair
7
Establishing factory settings
45
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
7.5
Establishing factory settings
All existing settings are deleted and reset to the factory settings.
new
1
2
Establishing factory settings
1 Internal alarm indicator
2 'new' opening with button
To create the factory settings on the radio fire detector, proceed as follows:
w The radio fire detector is being supplied with power.
w You have a slim pen or pencil to hand.
1.
Remove the radio fire detector from the detector base.
2.
Wait until the internal alarm indicator (1) flashes green (2-second interval).
a The detector is 'out of base'.
3.
Press the pen or pencil into the 'new' opening (2) for 5 seconds.
a The internal alarm indicator flashes red (2-second interval).
a The radio fire detector is set to the factory settings.
See also
2 Internal alarm indicator [➙ 20]
Maintenance / Repair
Basic principles for replacing the battery pack
46
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
7.6
Basic principles for replacing the battery pack
CAUTION
Risk of explosion due to fire or short-circuit, even if the battery pack is empty
Injuries caused by flying parts
●
To prevent the connection wires short-circuiting, insulate the connections and
stick the battery cable to the battery pack.
●
Do not allow the battery pack to come into contact with water.
●
Do not extinguish a burning battery pack with water.
●
Do not recharge the battery pack.
●
Do not damage or dismantle the battery pack.
●
Do not heat the battery pack to more than 100 °C.
CAUTION
Disposing of damaged or leaky battery packs
Lithium can burn the skin and produce toxic vapors.
●
Avoid direct contact with the body. Wear appropriate protective clothing
(safety gloves, safety goggles, etc.). Use appropriate means of transportation
to move damaged batteries around.
●
Do not breathe in vapors. Ensure that there is sufficient ventilation.
Always observe the following information:
l When the control panel issues the message 'Battery low', replace the battery
pack.
l Use the control panel to identify the location of the radio device.
l Only use battery pack BAT3.6-10.
l The battery pack must be new and free from damage. The battery cable is
attached to the battery pack with an adhesive label.
l Store, transport, and dispose of the battery pack in accordance with local
regulations, guidelines, and laws.
l Label the battery pack with the commissioning date.
See also
2 Environmental compatibility and disposal [➙ 51]
Maintenance / Repair
7
Replacing the battery pack
47
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
7.7
Replacing the battery pack
Each radio device stores its contact data in the event of an interruption in the
power supply lasting two minutes. The stored contact data enables the radio
device to reintegrate itself into the radio network without delay and without any
problems. If the power supply for a radio device is interrupted for more than two
minutes, the contact data will be lost and this radio device will not be detected. If
this happens to multiple radio devices at the same time, this means there is a
fault in the radio cell.
l Do not interrupt the power supply for longer than 2 minutes.
l Do not interrupt the power supply to multiple radio devices simultaneously.
Replace the battery pack for one radio device as described below before
replacing the battery pack for the next radio device. This will prevent mix-ups
and will ensure the devices can be reintegrated into the radio cell without any
problems.
2
3
4
5
11
2
3
4
5
Replacing the detector battery pack
1
Battery pack BAT3.6-10
4
Holder
2
Removing the battery pack
5
Battery cable
3
Inserting the battery pack
6
Battery connector
w You have a new, undamaged battery pack to hand.
w You have tools for removing the detector to hand.
Maintenance / Repair
Replacing the battery pack
48
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
1.
Remove the detector from the detector base.
2.
Wait until the internal alarm indicator flashes green (interval: 2 seconds).
a The detector is 'out of base'.
3.
Push the holder (4) to the side and remove the battery pack (1).
4.
Release the battery connector (6).
5.
Dispose of the old battery pack.
6.
Label the new battery pack with the current date.
7.
Connect the battery connector (6) of the new battery pack.
8.
Insert the new battery pack, paying attention to the position of the battery cable
(arrows at 5).
9.
Make sure that the holder (4) latches into place correctly.
a When the battery connector is connected, the internal alarm indicator lights
up red for 5 seconds (flashing pattern number 1 Internal alarm indicator
[➙ 20]).
a After a further 10 seconds, the detector signals that it is not installed on the
detector base and the internal alarm indicator flashes green (flashing
pattern number 3).
a If this does not happen, this means the battery pack is defective and must
not be used.
10. Insert the detector into the detector base.
a The internal alarm indicator flashes green (flashing pattern number 4) and
the detector is logged on to the radio gateway.
a If the process of logging on to the radio gateway is successful, the internal
alarm indicator stops flashing.
11. Following the successful logon, replace the battery pack of the next radio
device.
12. Check the status display on the radio gateway or the 'Device localization error'
display on the control panel.
–
If there is a 'Device localization error' message on the radio gateway or the
control panel, the detector will need to be assigned again. Assign the
detector by following the information in Confirming the detector position
[➙ 44].
a The battery pack has now been replaced.
See also
2 Internal alarm indicator [➙ 20]
2 Battery pack BAT3.6-10 [➙ 25]
2 Applicable documents [➙ 7]
2 Environmental compatibility and disposal [➙ 51]
Replacing the battery pack
49
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
8
Specifications
See also
2 Applicable documents [➙ 7]
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
l Document A6V10271323
Device characteristics
Response sensitivity
2.3…12 %/m
Compensation speed
≤1/45 voltage increase for detection/h
Detector diagnosis
With SWING tool
Radio
Sending/receiving aerials
Dual band aerial
Frequency range
868…870 MHz SRD band
433…435 MHz
Channel grid
50 kHz
Number of channels
27 in 868-MHz band
20 in 433-MHz band
Transmitting power
<10 mW ERP
Range
See document 'A6V10227631'
Battery pack BAT3.6-10
Lithium battery pack
BAT3.6-10 LI-SOCl2 battery pack 3.6 V,
10 Ah
Battery service life
At least 3 years depending on the ambient
conditions
Service life in 'battery low' operation
>3 months
Battery voltage monitored
Yes
Weight
0,093 kg
Ambient conditions
Operating temperature:
-10…+55 °C
Storage temperature
-30…+75 °C
Air humidity
≤95 % rel.
Protection category (IEC 60529):
IP30
Electromagnetic compatibility:
100 kHz…2.5 GHz
30 V/m
Permissible wind speed:
Max. 5 m/s
Mechanical data
Color
∼RAL 9010 pure white
Weight without accessories
0,132 kg
Standards
European standards
l
EN 54-11
l
EN 54-25
l
EN 300220-2
l
EN 301489-3
l
EN 60950
See also
2 Applicable documents [➙ 7]
Radio fire detector FDOOT271 with detector base FDB271
64
23
117
100
8.3
Environmental compatibility and disposal
This equipment is manufactured using materials and procedures which
comply with current environmental protection standards as best as
possible. More specifically, the following measures have been
undertaken:
l Use of reusable materials
l Use of halogen-free plastics
l Electronic parts and synthetic materials can be separated
Larger plastic parts are labeled according to ISO 11469 and ISO 1043.
The plastics can be separated and recycled on this basis.
Electronic parts and batteries must not be disposed of with domestic
waste.
l Take electronic parts and batteries to local collection points or
recycling centers.
l Contact local authorities for more information.
l Observe national requirements for disposing of electronic parts
and batteries.
Basic settings present at the time of delivery
Radio cell
Unit comprising all radio devices connected to
the radio gateway
Radio device
Any device that the radio gateway monitors
Radio network
Within a radio cell, bidirectional radio
connections are established between the radio
devices. Together with the radio gateway
connections, these create a radio network.
Replacing the battery pack, 46
C
CE marking, 50
Compatibility, 27
Compatibility with control panels, 27
Control panel, 42
D
Danger level
Signal processing of the detector, 19
Degraded mode operation
Fire control panel failure, 23
Detection behavior of the detector
Parameter set, 19
Detector base seal
Mounting, 41
Diagnosis levels, 20
Disposal, 51
Documentation for fire detection system, 22
Download center
URL, 7
E
Environmental compatibility, 51
ES
Product version, 15
EU directives, 50
F
Fire control panel failure
Degraded mode operation, 23
Flashing mode
Internal alarm indicator, 20
Flashing pattern
Configuration, 20
Internal alarm indicator, 20
I
Intended use, 5
L
List of compatibility, 23, 27
O
Original language
Source language, 5
P
Packaging label
Product version, 15
Parameter set
Detection behavior of the detector, 19
Product label
Product version, 15
R
Recycling, 51
S
Signal processing of the detector
Danger level, 19
Source language, 5
Standards, 50
T
Type plate
Product version, 15
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2011
Technical specifications and availability subject to change without notice.
Document ID
A6V10227635_g_en_--
Manual FD20/FD720
Edition
2015-03-11
Register 3