Siemens SIMATIC PCS 7 Operating Manual
Text of the manual
Process Control System PCS 7
Help for SIMATIC PDM (V8.2)
Operating Manual
SIMATIC PDM V8.2
02/2014
A5E33203676-AA
Preface
1
Using SIMATIC PDM
2
Installation
3
PDM Exportfile Converter
4
Integrating devices into
SIMATIC PDM
5
Views
6
Functions
7
Menus and dialog boxes in
SIMATIC PDM
8
Menus and dialog boxes for
SIMATIC PDM in the
SIMATIC Manager
9
Menus and dialog boxes for
SIMATIC PDM in HW Config
10
PDM Web
11
Notes, Tips & Tricks
12
Appendix
A
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
A5E33203676-AA
Ⓟ 03/2014 Subject to change
Copyright © Siemens AG 2014.
All rights reserved
Table of contents
1
Preface.........................................................................................................................................................9
2
Using SIMATIC PDM..................................................................................................................................11
2.1
Introduction..................................................................................................................................11
2.2
Using the documentation.............................................................................................................11
2.3
Contact partner............................................................................................................................11
2.4
Basis for using intelligent field devices........................................................................................12
2.5
Establishing connections to field devices....................................................................................13
2.6
Product structure.........................................................................................................................18
2.6.1
Basic packages...........................................................................................................................18
2.6.2
Options........................................................................................................................................20
2.6.3
Delivery contents.........................................................................................................................22
3
Installation..................................................................................................................................................23
3.1
Preparing SIMATIC PDM............................................................................................................23
3.2
Installing SIMATIC PDM..............................................................................................................23
3.3
Setting the language...................................................................................................................26
3.4
Reinstalling / Removing SIMATIC PDM......................................................................................27
4
PDM Exportfile Converter...........................................................................................................................29
4.1
"PDM Exportfile Converter" dialog box........................................................................................29
5
Integrating devices into SIMATIC PDM......................................................................................................31
5.1
Device Integration Manager........................................................................................................31
5.2
"Device Integration Manager" main window................................................................................32
5.3
Views...........................................................................................................................................32
5.3.1
Title bar.......................................................................................................................................32
5.3.2
Menu bar.....................................................................................................................................33
5.3.3
Toolbar........................................................................................................................................34
5.3.4
Device list....................................................................................................................................35
5.3.5
Status bar....................................................................................................................................38
5.3.6
Source folder...............................................................................................................................38
5.3.7
Applying a filter............................................................................................................................38
5.3.8
Filter file/Project filter...................................................................................................................39
5.4
Working with the Device Integration Manager.............................................................................40
5.4.1
Integrating device descriptions....................................................................................................40
5.4.2
Completing a device description.................................................................................................41
5.4.3
Creating your own device library using the project filter..............................................................42
5.4.4
Creating your own device library from a collection of device descriptions..................................43
5.4.5
Removing device descriptions.....................................................................................................44
5.4.6
Update/upgrade of device descriptions (EDD update)................................................................44
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
3
Menus and dialog boxes.............................................................................................................45
5.5.1
File...............................................................................................................................................45
5.5.1.1
Read device descriptions from source directory.........................................................................45
5.5.1.2
Read device descriptions from compressed source....................................................................45
5.5.1.3
List of integrated device descriptions..........................................................................................46
5.5.1.4
List of device descriptions used..................................................................................................46
5.5.1.5
Save device list...........................................................................................................................47
5.5.1.6
Print device list............................................................................................................................47
5.5.1.7
Deleting the device list................................................................................................................48
5.5.1.8
Exit..............................................................................................................................................48
5.5.2
View.............................................................................................................................................48
5.5.2.1
Split device list window................................................................................................................48
5.5.3
Catalog........................................................................................................................................49
5.5.3.1
Complete device information.......................................................................................................49
5.5.3.2
Integrate......................................................................................................................................50
5.5.3.3
User-specific device DVD ...........................................................................................................50
5.5.3.4
Filter file.......................................................................................................................................51
5.5.3.5
Project filter.................................................................................................................................51
5.5.3.6
Messages....................................................................................................................................52
5.5.3.7
Find.............................................................................................................................................53
5.5.4
? (Help)........................................................................................................................................53
5.5.4.1
Help.............................................................................................................................................53
5.5.4.2
Info..............................................................................................................................................54
6
Views..........................................................................................................................................................55
6.1
Introduction..................................................................................................................................55
6.2
Views in SIMATIC Manager........................................................................................................55
6.2.1
Process devices plant view.........................................................................................................55
6.2.2
Process devices network view....................................................................................................56
6.2.3
Open SIMATIC PDM in the Process Devices - Plant View.........................................................57
6.2.4
Project synchronization...............................................................................................................57
6.3
Views in SIMATIC PDM..............................................................................................................58
6.3.1
Main Window "SIMATIC PDM"....................................................................................................58
6.3.2
Title bar.......................................................................................................................................59
6.3.3
Menu bar.....................................................................................................................................59
6.3.4
Toolbar........................................................................................................................................60
6.3.5
Structure view..............................................................................................................................60
6.3.6
Parameter table...........................................................................................................................61
6.3.6.1
"Parameter" column of the parameter table................................................................................62
6.3.6.2
"Value" column of the parameter table........................................................................................62
6.3.6.3
"Unit" column of the parameter table...........................................................................................63
6.3.6.4
"Status" column of the parameter table.......................................................................................63
6.3.7
Status bar....................................................................................................................................64
6.3.8
Display ........................................................................................................................................64
6.3.8.1
Display in the views.....................................................................................................................64
6.3.8.2
Stand-alone device view.............................................................................................................65
6.3.8.3
Multiple devices view...................................................................................................................66
6.3.9
Keyboard operation.....................................................................................................................66
Table of contents
Help for SIMATIC PDM (V8.2)
4
Operating Manual, 02/2014, A5E33203676-AA
"Settings" for the SIMATIC project..............................................................................................71
7.2.2
Setting the interface on the computer.........................................................................................73
7.2.3
Plant-wide communication by means of routing..........................................................................74
7.2.4
Checking the device integration..................................................................................................74
7.2.5
Print.............................................................................................................................................75
7.2.6
Cleaning the project (reorganization) .........................................................................................76
7.2.7
Saving the configuration..............................................................................................................77
7.3
Device management ..................................................................................................................77
7.3.1
Inserting devices.........................................................................................................................77
7.3.1.1
Inserting objects..........................................................................................................................77
7.3.1.2
"Insert Object - <...>" dialog box..................................................................................................78
7.3.1.3
"Insert Object - Assign Device Type" dialog box.........................................................................79
7.3.1.4
Integrating a device in HW Config...............................................................................................81
7.3.1.5
Setting the bus address in HW Config........................................................................................83
7.3.1.6
Integrating a HART device in a HART modem network..............................................................84
7.3.1.7
Integrating a MODBUS device in a MODBUS network...............................................................86
7.3.1.8
Integrating a HART server network.............................................................................................88
7.3.1.9
Compact PROFIBUS device (sensors and actuators)................................................................94
7.3.1.10 Modular PROFIBUS device (remote I/O)....................................................................................95
7.3.1.11 Connecting a field device to PROFINET.....................................................................................97
7.3.1.12 HART device on remote I/O........................................................................................................99
7.3.1.13 Inserting a HART device at a HART module.............................................................................102
7.3.1.14 Integrating an FF field device....................................................................................................102
7.3.2
Field devices with redundant bus connection ...........................................................................103
7.3.2.1
Connecting field devices to a redundant bus system................................................................103
7.3.2.2
"Select object" dialog box..........................................................................................................104
7.3.2.3
"Properties - Find object" dialog box.........................................................................................104
7.3.3
Using unspecified PROFIBUS PA devices as placeholders.....................................................104
7.3.4
Creating typicals for parameters (import without ID data) ........................................................105
7.3.5
Replacing devices.....................................................................................................................106
7.3.6
Inserting plant-specific documents for process mode...............................................................107
7.3.7
Operating modes of field devices..............................................................................................108
7.3.8
Deleting devices........................................................................................................................109
7.3.9
Assigning parameters and downloading to devices..................................................................110
7.3.10
Interconnecting and downloading FF devices...........................................................................110
7.3.10.1 “Interconnection Editor" dialog box...........................................................................................110
7.3.10.2 Downloading objects in the FF segment...................................................................................112
7.4
Communication.........................................................................................................................114
7.4.1
Saving/reading the device data.................................................................................................114
7.5
Export / Import...........................................................................................................................116
7.5.1
Introduction................................................................................................................................116
7.5.2
Exporting configuration and parameter assignment data..........................................................119
7.5.3
Importing configuration and parameter assignment data..........................................................120
7.6
Diagnostics................................................................................................................................122
7.6.1
Field device diagnostics............................................................................................................122
7.6.2
Overview of Device Icons..........................................................................................................124
Table of contents
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
5
Working with the LifeList...........................................................................................................127
7.7.2
Licensing...................................................................................................................................132
7.7.3
Menus and dialog boxes...........................................................................................................133
7.7.3.1
"File" menu................................................................................................................................133
7.7.3.2
"Edit" menu................................................................................................................................133
7.7.3.3
"Device" menu...........................................................................................................................134
7.7.3.4
"View" menu..............................................................................................................................136
7.7.3.5
"Options" menu.........................................................................................................................136
7.7.3.6
"Help" menu..............................................................................................................................136
7.7.4
Menu bar...................................................................................................................................137
7.7.5
Toolbar......................................................................................................................................137
7.7.6
Status bar..................................................................................................................................138
7.8
Logs...........................................................................................................................................138
7.8.1
Message log..............................................................................................................................138
7.9
Graphical displays.....................................................................................................................139
7.9.1
Graphical display of values.......................................................................................................141
7.9.2
Trend chart................................................................................................................................142
7.9.3
Bar chart....................................................................................................................................144
7.9.4
Tachometer chart......................................................................................................................145
7.9.5
Icons and buttons......................................................................................................................146
7.9.6
Work with trends........................................................................................................................147
7.9.7
Editing trends............................................................................................................................149
7.10
Asset management...................................................................................................................151
7.10.1
Asset management ..................................................................................................................151
7.10.2
Use with the PCS 7 Maintenance Station.................................................................................152
8
Menus and dialog boxes in SIMATIC PDM .............................................................................................155
8.1
"File" menu ...............................................................................................................................155
8.1.1
Save..........................................................................................................................................155
8.1.2
Exporting...................................................................................................................................155
8.1.2.1
"Export -
"Select object" dialog box..........................................................................................................169
8.3.4
Assign address and TAG..........................................................................................................169
8.3.4.1
"Assign address and TAG..." dialog box...................................................................................171
8.3.5
Object properties.......................................................................................................................172
8.3.5.1
"General" tab.............................................................................................................................173
8.3.5.2
"Device" tab...............................................................................................................................173
8.3.5.3
"Diagnostics" tab.......................................................................................................................174
8.3.5.4
"Communication" tab.................................................................................................................174
8.3.5.5
"Document Manager" tab..........................................................................................................176
8.3.6
Calibration log...........................................................................................................................176
8.3.6.1
Calibration log...........................................................................................................................176
8.3.6.2
Menus and dialog boxes...........................................................................................................178
8.3.6.3
Menu bar...................................................................................................................................183
8.3.6.4
Toolbar......................................................................................................................................183
8.3.7
Change log................................................................................................................................184
8.3.7.1
Show change log.......................................................................................................................184
8.3.7.2
Menus and dialog boxes...........................................................................................................185
8.3.7.3
Menu bar...................................................................................................................................187
8.3.7.4
Toolbar......................................................................................................................................187
8.4
"View" menu .............................................................................................................................188
8.4.1
Process variables / Measured value display (depends on device)............................................188
8.4.2
Start LifeList..............................................................................................................................189
8.4.3
Charts and trends (depends on device)....................................................................................189
8.4.3.1
Displaying process variables and measured values ................................................................190
8.5
"Diagnostics" menu...................................................................................................................191
8.5.1
Update diagnostics....................................................................................................................191
8.5.1.1
"Update diagnostics - <...>" dialog box.....................................................................................191
8.6
"Options" menu (depends on device)........................................................................................193
8.7
"Help" menu..............................................................................................................................193
8.7.1
Contents....................................................................................................................................193
8.7.2
Help for device parameters.......................................................................................................193
8.7.3
Info............................................................................................................................................193
8.7.4
Find...........................................................................................................................................194
8.7.5
Document Manager...................................................................................................................194
9
Menus and dialog boxes for SIMATIC PDM in the SIMATIC Manager....................................................195
9.1
"Edit" menu................................................................................................................................195
9.1.1
SIMATIC Manager > "Edit" menu..............................................................................................195
9.1.2
Object properties.......................................................................................................................195
9.1.2.1
"General" tab.............................................................................................................................196
9.1.2.2
"Device" tab...............................................................................................................................197
9.1.2.3
"Diagnostics" tab.......................................................................................................................197
9.1.2.4
"Communication" tab.................................................................................................................197
9.1.2.5
"Document Manager" tab..........................................................................................................199
9.1.3
SIMATIC PDM...........................................................................................................................200
9.1.3.1
Exporting...................................................................................................................................200
9.1.3.2
Importing...................................................................................................................................200
9.1.3.3
Download to device...................................................................................................................200
9.1.3.4
Upload to PG/PC.......................................................................................................................201
9.1.3.5
Update diagnostics....................................................................................................................202
Table of contents
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
7
Device selection (Reassign)......................................................................................................202
9.1.3.8
Show change log.......................................................................................................................204
9.2
"Insert" menu.............................................................................................................................205
9.2.1
Inserting an object.....................................................................................................................205
9.3
"View" menu .............................................................................................................................207
9.3.1
Process devices plant view.......................................................................................................207
9.3.2
Process devices network view..................................................................................................208
9.4
"Options" menu.........................................................................................................................208
9.4.1
Settings for SIMATIC PDM........................................................................................................210
9.4.1.1
Settings for SIMATIC PDM........................................................................................................210
9.4.1.2
"General" tab.............................................................................................................................211
9.4.1.3
"Communication" tab.................................................................................................................212
9.4.1.4
The "Load" tab...........................................................................................................................213
9.4.1.5
"Device Integration Manager" tab..............................................................................................213
9.4.1.6
"Maintenance Station" tab.........................................................................................................215
9.4.1.7
"Change Log" tab......................................................................................................................215
9.4.1.8
"Service" tab..............................................................................................................................215
9.4.2
Role management.....................................................................................................................217
9.4.3
HART server..............................................................................................................................218
10
Menus and dialog boxes for SIMATIC PDM in HW Config.......................................................................221
11
PDM Web.................................................................................................................................................223
11.1
Setting up SIMATIC PDM Web.................................................................................................223
11.2
PDM Web Server Configurator..................................................................................................225
11.3
Web login..................................................................................................................................227
11.4
Menus and dialog boxes for SIMATIC PDM in PDM Web........................................................227
11.4.1
"File" menu................................................................................................................................227
11.4.2
"Device" menu...........................................................................................................................228
11.4.3
"View" menu..............................................................................................................................228
11.4.4
"Diagnostics" menu...................................................................................................................228
11.4.5
"Help" menu..............................................................................................................................228
12
Notes, Tips & Tricks.................................................................................................................................229
12.1
Information on configuration and parameter assignment..........................................................229
12.2
Connecting field devices by means of Industrial Ethernet.........................................................230
12.3
HART applications.....................................................................................................................232
A
Appendix...................................................................................................................................................233
A.1
Communication Problems.........................................................................................................233
A.2
Message window.......................................................................................................................235
A.2.1
"Decision on error" dialog box...................................................................................................235
A.2.2
"Error history" dialog box...........................................................................................................235
A.2.3
"Error" dialog box......................................................................................................................235
A.2.4
"Multiple errors" dialog box........................................................................................................235
A.2.5
"Messages" Dialog Box.............................................................................................................235
Index.........................................................................................................................................................237
Table of contents
Help for SIMATIC PDM (V8.2)
8
Operating Manual, 02/2014, A5E33203676-AA
Purpose of the program
SIMATIC PDM (Process Device Manager) is a general-purpose, manufacturer-independent
tool for the configuration, parameter assignment, commissioning, diagnostics, and
maintenance of intelligent field devices (sensors and actuators) and field components (remote
I/O, multiplexers, control room devices, compact controllers).
Purpose of the documentation
This documentation supports you in your work with SIMATIC PDM software. You are provided
with an overview of the following topics:
●
Installing SIMATIC PDM (Page 23)
●
Commissioning the software
●
Procedures for configuring networks and field devices
●
Procedures for commissioning and using the Runtime functions
Required basic knowledge
The documentation is intended for persons working in field engineering who are responsible
for configuration, commissioning and plant operation.
General knowledge in the area of field engineering is required to understand this
documentation.
Knowledge about the use of Windows operating systems is also required.
Activities using STEP 7 and PCS 7 require corresponding knowledge in the field of automation
technology and of SIMATIC S7.
Validity
This documentation is valid for the SIMATIC PDM V8.2 software package.
Device-specific help
This documentation only covers the basic functionality of PDM. For device-specific information,
refer to the documentation of the field device manufacturers.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
9
Readme for SIMATIC PDM
For details of the requirements for using SIMATIC PDM, of special functions, and of the various
applications, see file pdmbase-readme. You can locate the file as follows:
●
On the SIMATIC PDM product DVD in the main folder of the DVD
●
On the SIMATIC PCS 7 product DVD in the folder ...PDM...\PDMBASE\setup
●
After installation of SIMATIC PDM:
–
By selecting SIEMENS SIMATIC documentation in the Windows Start menu
–
The default folder for the file is ...\SIEMENS\SIMATIC_PDM\.
Online help
The SIMATIC PDM online help is a project-specific help feature, which contains the following
information:
●
Help for SIMATIC PDM
The PDF file is an extract of the HTML-based online help for SIMATIC PDM. The PDF file
does not contain any device-specific information.
●
Device-specific help
Device-specific information contained in the online help is derived from the device
descriptions (EDD) of the devices being used:
–
Information on device-specific functions (e.g. available online functions)
–
Help for device-specific menu commands (e.g. trend display options, device-specific
display functions and operating functions)
Note
Scope of the device-specific information
The scope of the device-specific information depends on what information can be
derived from the device descriptions.
The help system is integrated into the software by way of several interfaces:
●
The Help menu provides several menu commands: Help Topics opens the help for SIMATIC
PDM.
●
The context-sensitive help provides information with regard to the current context such as
open dialog boxes or active windows. The help is called by clicking the "Help" button or by
pressing the F1 key.
●
A tooltip is displayed for the toolbar icons when the user hovers the mouse pointer over the
icons.
If you would prefer to read a hardcopy of the help, you can print specific help topics or chapters,
or the entire help.
Preface
Help for SIMATIC PDM (V8.2)
10
Operating Manual, 02/2014, A5E33203676-AA
Using SIMATIC PDM
2
2.1
Introduction
SIMATIC PDM (Process Device Manager) is a general-purpose, manufacturer-independent
tool for configuration, parameter assignment, commissioning, diagnostics and maintenance of
intelligent field devices (sensors and actuators) and field components (remote I/Os,
multiplexers, control room units, compact controllers). These are simply referred to as devices
in the rest of this documentation.
With one software package, SIMATIC PDM enables processing of more than 2500 devices
from Siemens and 200 other manufacturers from around the world with an homogeneous user
interface.
2.2
Using the documentation
Scope
SIMATIC PDM operates within a SIMATIC STEP 7 / PCS 7 environment or in combination
with suitable function modules.
Conventions
The names of the user interfaces in this software are listed in accordance with the regional
language of this documentation. If you have installed an MUI operating system, certain
designations are still displayed in the base language of the operating system after a language
change and will, therefore, differ from those used in the documentation.
2.3
Contact partner
Your contact partner (not for demo version)
Questions on SIMATIC STEP 7 / SIMATIC PCS 7 / hardware / SIMATIC PDM / problems with
S7 communication
Mailing address:
SIEMENS AG
Customer Support
D-90475 Nuremberg, Germany
E-mail:
[email protected]
Internet:
http://www.siemens.com/automation/service&support (http://
www.siemens.com/automation/service&support)
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
11
Questions on devices and GSD files
Please get in touch with your contact partner at the device manufacturer.
For more information, refer to the "List of integrated devices". You will find this on the "SIMATIC
PDM Device Library 1#2014" DVD in the "\_manuals" directory.
Follow-up installations and additional information on SIMATIC PDM are available on the
Internet at "Auto-Hotspot".
See also
www.siemens.com/simatic-pdm (www.siemens.de/simatic-pdm)
2.4
Basis for using intelligent field devices
Integration of field devices from different manufacturers into control systems
Device descriptions had to be standardized In order to enable intelligent field devices from
different manufacturers to be integrated into different control systems. This standard (IEC
61804-2) was developed in collaboration with the following organizations:
●
PROFIBUS User Organization (PNO)
●
Hart Communication Foundation (HCF)
●
Fieldbus FOUNDATION (FF)
●
OPC Foundation
Device descriptions are based on EDDL (Electronic Device Description Language - standard
IEC 61804-3).
Finding the device description
You can obtain device descriptions in the following ways:
●
From the device manufacturer together with the device
●
On the Internet
●
In the device catalogs of applications that can evaluate data contained in device descriptions
Note
Device descriptions and EDD
Below, only the term "device description" will be used to refer to "EDD" (Electronic Device
Description) and "DD" (Device Description).
However, the terms EDD and DD appear in the user interface.
Using SIMATIC PDM
2.4 Basis for using intelligent field devices
Help for SIMATIC PDM (V8.2)
12
Operating Manual, 02/2014, A5E33203676-AA
Siemens explicitly declines any liability for damages resulting from the use of the following
device description files and use in conjunction with the associated devices:
●
For device-specific device description files for non-Siemens devices, the Siemens warranty
only applies up to the interface.
●
For non-device-specific device description files, such as those that correspond to the
PROFIBUS PA profiles or the HART universal or common practice commands
●
For device description files of the HCF library from the "Device Library" DVD
●
For device description files integrated through catalogs
NOTICE
Important note on the device description files included with the SIMATIC PDM
The device description files of non-Siemens field devices have not been developed by
Siemens and are included with the shipped products free of charge. The licensee is
entitled to use the device description files of these devices in the same manner as a trial
license in accordance with the general terms and conditions for the supply of software for
automation and drive technology. This right of use may be exercised by the licensee as
long as the right of use for the PDM software is in effect.
2.5
Establishing connections to field devices
Plants use field devices with different communication paths and protocols. The overview shows
a typical connection scenario for the field device groups that are supported by SIMATIC PDM.
Using SIMATIC PDM
2.5 Establishing connections to field devices
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
13
Network topologies for PROFIBUS DP
The following figure shows the access paths to field devices for SIMATIC PDM.
������������
�������������
�������������
�������������
�������������
�����������
�������
����������
����
�����
������������
�������
���
�����������
�����������
��������
�����������
�����������
�����������
�����������
�����������
�������������������
�������������������
�
Using SIMATIC PDM
2.5 Establishing connections to field devices
Help for SIMATIC PDM (V8.2)
14
Operating Manual, 02/2014, A5E33203676-AA
Network topologies for PROFINET
The following figure shows the access paths to field devices for SIMATIC PDM.
�������������
��������������������
�����������������
����������������
������������
�����������
����������
���������������
�������������
�������������
��������
��������
��������
��������
�����������
����������
����
�����
������������
�������
���
Communication paths
Note
Interface with SIMATIC PDM
The PC shown is always the interface to SIMATIC PDM.
In networks with routing capability, the PC can be connected to a linked network. You can
find information on this in the section "Plant-wide communication by means of routing
(Page 74)".
Using SIMATIC PDM
2.5 Establishing connections to field devices
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
15
HART modem network
The following figure shows the access paths to field devices for SIMATIC PDM.
���������������
MODBUS network
The following figure shows the access paths to field devices for SIMATIC PDM.
������
HART server network
The following figure shows the access paths to field devices for SIMATIC PDM.
Using SIMATIC PDM
2.5 Establishing connections to field devices
Help for SIMATIC PDM (V8.2)
16
Operating Manual, 02/2014, A5E33203676-AA
With this version of SIMATIC PDM, field devices are supported on the following networks:
●
PROFIBUS DP network (including subordinate Foundation Fieldbus)
●
PROFIBUS PA network
●
PROFINET
●
MODBUS network
●
HART modem network
●
HART server
Activating PDM functions
License keys are required in order to use SIMATIC PDM. You can expand the SIMATIC PDM
functions by adding optional packages. You can find information on this in the section "Basic
packages (Page 18)".
Using SIMATIC PDM
2.5 Establishing connections to field devices
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
17
Section "Inserting devices (Page 77)"
2.6
Product structure
2.6.1
Basic packages
The following product packages with different performance features are available for SIMATIC
PDM.
Product packages for SIMATIC PDM V8.2
Legend for the tables:
●:
Available
○:
Optionally available
-:
Not available
License key
SIMATIC PDM product package
Stand-alone
STEP 7
PCS 7
SIMATIC PDM Basic and Extended
-
●
●
SIMATIC PDM Single Point
●
-
-
Integration in STEP 7
-
●
●
TAGs
-
100
100
"SIMATIC PDM Routing (Page 20)"
optional package
-
○
●
SIMATIC Logon Service V1.5 SP2*
-
○
●
* The SIMATIC Logon Service option requires a license for the following applications:
●
SIMATIC PDM stand alone
●
SIMATIC PDM integrated in STEP 7
Within SIMATIC PCS 7, no separate license is necessary.
Note
Displaying devices subject to licensing
SIMATIC PDM will only display devices if a TAG license is installed for each device subject
to licensing.
●
Licenses are only required for devices that are subject to licensing.
●
No licenses are required for remote I/O modules and channels.
Using SIMATIC PDM
2.6 Product structure
Help for SIMATIC PDM (V8.2)
18
Operating Manual, 02/2014, A5E33203676-AA
Functions in product package
Functions
SIMATIC PDM
Single Point
STEP 7
PCS 7
Project functions
●
Create online
●
●
●
●
TAG options used
-
●
●
●
Network view
●
●
●
●
Plant view
●
●
●
●
Export / import devices
-
●
●
●
HW Config
-
●
●
●
Integration in STEP 7
-
●
●
Communication functions
●
PROFIBUS
●
●
●
●
PROFINET
●
●
●
●
FOUNDATION Fieldbus
-
○
○
●
MODBUS
●
●
●
●
S7 DSGW
-
○
●
●
HART modem
●
●
●
●
HART interface network
●
●
●
●
HCF HART server
-
○
○
●
HART SHC mode
(communication acceleration)
●
●
●
Device functions
●
Use of SIMATIC PDM options
-
●
●
●
Saving parameters
●
●
●
●
Log (audit trail)
-
●
●
LifeList functions
●
Scan from HW Config
-
●
●
●
Device diagnostics
-
●
●
●
Define scan area
●
●
●
●
Scan from network view
●
●
●
SIMATIC PDM Single Point
SIMATIC PDM Single Point can be used for a single device. SIMATIC PDM Single Point cannot
be extended with other options.
Using SIMATIC PDM
2.6 Product structure
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
19
Operating mode "PDM Demo"
The "PDM Demo" version is an operating mode especially for the product SIMATIC PDM. The
"PDM Demo" operating mode is activated automatically if necessary licenses are not
recognized or functions/options that are subject to licensing are present in a project.
●
Necessary licenses for SIMATIC PDM (license keys):
–
SIMATIC PDM Basic
●
Functions/options subject to licensing:
–
Options subject to licensing (for example SIMATIC PDM Extended)
Reaction
After starting SIMATIC PDM, you receive a message stating that demo mode is activated. In
addition, the status line displays the information "Demo".
Note
License conditions violated
If the license conditions are violated, the following applies:
●
The processing of the project with other editors is unrestricted.
●
Objects that are not affected by the infringement of the license conditions can be created.
●
The communication functions are locked.
●
Online dialog boxes of field devices can only be opened "offline".
2.6.2
Options
Program Add-ons for SIMATIC PDM
SIMATIC PDM Single Point can only be used for a single device. SIMATIC PDM Single Point
cannot be extended with other functional or TAG options.
For SIMATIC PDM, the following options can be purchased:
●
SIMATIC PDM Integration in STEP 7 (PCS 7)
It allows field devices and their associated networks to be configured using the STEP 7
hardware configurator (HW Config).
Note
The combination of SIMATIC PDM and the option "Integration in STEP 7" is referred SIMATIC
PDM integrated in the remainder of this documentation.
Using SIMATIC PDM
2.6 Product structure
Help for SIMATIC PDM (V8.2)
20
Operating Manual, 02/2014, A5E33203676-AA
SIMATIC PDM TAG
If you want to use more TAGs for each multiproject or project than those provided in the
standard package, the TAG options of SIMATIC PDM enable you to expand the TAGs to
the required number. By combining multiple license keys, you can reach the required
number of devices for licensing (TAG addition).
Available license keys:
–
10 TAG
–
100 TAG
–
1000 TAG
●
SIMATIC PDM Foundation Fieldbus
This option licenses and allows configuration and communication of field devices on the
Foundation Fieldbus in SIMATIC S 7 and SIMATIC PCS 7 projects.
●
SIMATIC PDM Routing
Licenses and enables the use of the following gateways:
–
Communication via an automation system which serves as a gateway
–
Communication between Ethernet and PROFIBUS
–
Communication between PROFINET and PROFIBUS
The option is not required for the following gateways:
–
PROFIBUS to PROFIBUS
–
PROFIBUS to HART
–
PROFINET to HART
●
SIMATIC PDM Extended
Licenses and enables the use of the following additional functions:
–
Import and export of parameter sets and project structures
–
Print
–
Document Manager
–
Extended functionality of the LifeList
–
Change log
–
Calibration log for each field device
–
Configuration of three time intervals (maintenance, servicing, calibration) for each field
device
●
SIMATIC PDM HART Server
Licenses and enables the use of the HCF HART Server and thereby the HART
multiplexers with connected HART field devices and and wireless HART field devices.
●
SIMATIC PDM Command Interface
The command interface enables the integration of SIMATIC PDM in other automation
systems. SIMATIC PDM projects and objects in these projects can be edited and operated
through this interface. The use of this interface requires advanced programming skills. It
should not be used in SIMATIC PCS 7 projects.
For more information, refer to the documentation for the command interface.
Using SIMATIC PDM
2.6 Product structure
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
21
Establishing connections to field devices (Page 13)
2.6.3
Delivery contents
Scope of delivery
Information about the software packages that are delivered with SIMATIC PDM can be found
in the pdmbase-readme file.
Device libraries
Information on the devices contained in the SIMATIC PDM device libraries can be found:
●
On the Internet pages of the device manufacturers
The updated versions of the device libraries and the HCF catalog are available in
publications on the Internet.
●
On the "Device Library" DVD in the _manuals\PI_Library_Documentation > folder in file
"index.html"
Liability
Note
Read the information in the section "Basis for using intelligent field devices (Page 12)".
Using SIMATIC PDM
2.6 Product structure
Help for SIMATIC PDM (V8.2)
22
Operating Manual, 02/2014, A5E33203676-AA
PDM V8.2 is compatible with STEP7 V5.5 SP4 and PCS7 V8.1.
PCS7 V8.0x (STEP7 V5.5.3 and prior versions) are not supported.
3.1
Preparing SIMATIC PDM
Requirement
●
SIMATIC PDM is installed.
You can find information on this in the section "Installing SIMATIC PDM (Page 23)"
●
Project settings have been made.
You can find information on this in the section ""Options" menu (Page 208)".
●
The settings have been made for the fieldbus interfaces.
●
Field device planning has been completed.
You can find information on this in the section "Establishing connections to field devices
(Page 13)"
●
The device description files for the field devices used within a plant have been integrated
into SIMATIC PDM. You can find information on this in the section "Integrating device
descriptions (Page 40)".
Recommendation:
Hardware has been prepared (configuration, power supply, network connections).
Additional information
●
For additional information on assigning a network, refer to the section "Setting the interface
on the computer (Page 73)".
●
For information on the particular issues relating to the distributed I/O, refer to the section
"Modular PROFIBUS device (remote I/O) (Page 95)".
3.2
Installing SIMATIC PDM
SIMATIC PDM must be installed before it can be started. The software package contains all
SIMATIC PDM software. Depending on the use case in question, you will only need to install
certain applications from the CD.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
23
In order to use the software you will need product-specific license keys (license agreements),
which you install with the Automation License Manager.
You can transfer the required license keys either prior to or following the installation. You can
find additional information on this in the online help for the Automation License Manager.
Requirements
●
The operating system has been installed.
●
No version of SIMATIC PDM has been installed.
●
All communications processors have been installed in the PC.
●
You have administrator rights on the PC station.
If you install the software in a domain, be aware of group policies or other restrictions that may
hinder the installation. Consult the appropriate Administrator as regards these settings and the
required approvals and permissions.
Note
Display of the dialog elements
Dialog elements of SIMATIC PDM are only displayed correctly when the display settings in
Windows are set to 100%. Bigger or smaller scaling lead to display errors.
Calling the setup program
1. Insert the program CD into the drive.
2. Double-click on "Setup.exe" to start the setup.
Note
Checking the installation requirements
The setup program automatically checks whether the software components needed for
the installation are already installed on the PC.
●
Read the latest information about installation and the software and hardware
requirements in the pdmbase-readme file on the program CD.
●
If any software components are missing, a message informs you of this. The setup
program is terminated after the message is confirmed . The setup will start again after
you have installed the missing software components.
Installation
3.2 Installing SIMATIC PDM
Help for SIMATIC PDM (V8.2)
24
Operating Manual, 02/2014, A5E33203676-AA
Settings in the setup
Below you will find information on the settings made in the setup dialog boxes, listed in the
order in which they are processed:
1. Setup language
–
For example, click "English" and "Next".
2. Welcome
–
"Next"
3. Product information
–
Read this if needed and "Next"
4. License agreement
–
Activate the check box "I accept the conditions of the licensing agreement as well as
the conditions of the Open Source Licensing Agreement".
–
"Next"
5. Setup type
–
Activate the "Install" check box and "Next".
6. User information
–
Enter the user information and click "Next".
7. Installation type
–
Package installation
–
Custom installation
–
You can specify the target folder for SIMATIC PDM.
–
"Next"
8. Programs
–
The software installed on the PC for this selection is listed in the display window. "Next"
Note
FOUNDATION Fieldbus
If you wish to configure or monitor devices on FOUNDATION Fieldbus, you must select
the "FOUNDATION Fieldbus" option.
Installation
3.2 Installing SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
25
9. System settings
System settings are required for problem-free operation of SIMATIC PDM.
Note
Required system settings
●
The settings in the exception list of the Windows firewall are applied to the area of the
local network (subnet). If your PC stations are located in different networks (subnets),
you need to change this area.
●
The settings in the exception list of the Windows firewall are made when the Windows
firewall is disabled.
●
You can open the "Security Controller" dialog box again. To do this, select the following
in the Start menu, Siemens SIMATIC programs: Security > Security Controller
10.Ready to install the selection.
"Install" - The installation is performed.
Close the dialog box when the installation is complete.
11.Reboot the PC.
Device descriptions of field devices used
Following the installation of SIMATIC PDM, integrate the required device descriptions (EDD)
for the field devices used.
You can find information on this in the following sections:
●
Section "Integrating devices into SIMATIC PDM (Page 31)"
●
Section "Integrating device descriptions (Page 40)"
3.3
Setting the language
Changing the language
1. In SIMATIC Manager, select the menu command Options > Settings…
.The "Settings" dialog box opens.
2. Open the "Language" tab. You can change the language on this tab page.
3. Select the language you want to work with in the "National language" field.
Note
SIMATIC PDM language versions
The drop-down list contains the languages in which SIMATIC Manager is installed.
If you select a language for which there is no matching SIMATIC PDM language version
installed on the given computer, "English" is set automatically.
Installation
3.3 Setting the language
Help for SIMATIC PDM (V8.2)
26
Operating Manual, 02/2014, A5E33203676-AA
Reinstalling / Removing SIMATIC PDM
Note
Observe the information on dealing with license keys, which can be found in:
●
File pdmbase-readme
●
Help for the Automation License Manager
Reinstalling
Reinstallation over the top of an existing SIMATIC PDM version is not possible. Remove
SIMATIC PDM prior to installing the new version.
Note
Device descriptions
Following a new installation, the required device description must be integrated again.
The device descriptions included with SIMATIC PDM are available on the "Device Library"
DVD.
You know the storage locations of additionally used device descriptions.
You can find information about integrating the device descriptions in the section "Integrating
devices into SIMATIC PDM (Page 31)".
Removing
To remove SIMATIC PDM, use the Windows system function for removing programs.
Installation
3.4 Reinstalling / Removing SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
27
PDM Exportfile Converter
4
4.1
"PDM Exportfile Converter" dialog box
In the "PDM Exportfile Converter" dialog, you can convert export files from older PDM versions,
enabling them to be imported into PDM again.
The export files from PDM versions V6.x and V7.x cannot be imported directly into PDM V8.
To enable importing of existing export files, the “old” export files are converted.
A structure file is generated in this process and stored along with the associated parameter
import files in the corresponding subdirectory generated by the converter. These files can then
be imported.
Source-File
Navigate to the desired directory in the file system containing the export files to be converted.
After the dialog is closed with OK and an export file is correctly selected, the structure it contains
is displayed in the converter.
Destination-Dir
Navigate to the desired directory in the file system where the converted files are to be stored.
"Convert" button
Click "Convert". The selected source file is converted.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
29
Integrating devices into SIMATIC PDM
5
5.1
Device Integration Manager
The field devices can only be configured if the device descriptions that are suitable for the field
devices have been integrated into SIMATIC PDM. The Device Integration Manager is the
SIMATIC PDM function for integrating device descriptions.
Liability
Siemens explicitly declines any liability for damages resulting from the use of the following
device descriptions and use in conjunction with the associated devices:
●
For device-specific device descriptions for non-Siemens devices, the Siemens warranty
only applies up to the interface.
●
For non-device-specific device descriptions,
such as device descriptions that correspond to the PROFIBUS PA profiles or the HART
universal or common practice commands.
●
For device descriptions of the HCF library, FF library, and PI library from the "Device
Library ..." DVD.
NOTICE
Important information about the device descriptions included with the SIMATIC PDM
The device descriptions of non-Siemens field devices were not developed by Siemens
and are included with the shipped products free of charge. The licensee is entitled to use
the device descriptions of these devices in the same manner as a trial license in
accordance with the general terms and conditions for the supply of software for automation
and drive technology. This right of use may be exercised by the licensee as long as the
right of use for the PDM software is in effect.
Starting the Device Integration Manager
1. In the Windows Start menu under the Siemens SIMATIC programs, select the SIMATIC
PDM > Device Integration Manager menu command.
The "Device Integration Manager" dialog opens.
2. Read the license agreement.
You must accept the license agreement in order to be able to work with the Device
Integration Manager .
3. Click the "I accept the license agreement" button.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
31
"Device Integration Manager" main window
Introduction
The "Device Integration Manager" main window remains on the screen throughout the work
session and is partially or totally covered by other activated dialog windows.
The main window has the following layout
Title bar (Page 32)
The product name is displayed.
Menu bar (Page 33)
You access the functions of the Device Integration Manager via the
menu bar.
Toolbar (Page 34)
The toolbar enables certain menu commands to be accessed
quickly.
Source folder (Page 38)
The "Source folder" box shows the storage location in which device
descriptions are or were searched for.
Applying a filter (Page 38)
You can apply filters to reduce the amount of information displayed
in the device list.
Applying a project filter
(Page 51) / Applying Filter File
(Page 51)
Only those devices that are used in the selected project and for
which an identical version has not yet been integrated are selected
for integration.
Device list (Page 35)
The device list displays information on devices that have been read
in or integrated.
Status bar (Page 38)
Contains information on processes currently being performed.
5.3
Views
5.3.1
Title bar
The title bar shows the name "Device Integration Manager".
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
32
Operating Manual, 02/2014, A5E33203676-AA
Below you will find an overview of the Device Integration Manager menus.
Menu
Submenu
Function
File
●
Read device descriptions
from source directory
(Page 45)
Select the storage location of the device descriptions to be read in.
Set the path to the device descriptions or navigate to the location.
●
Read device descriptions
from compressed source
(Page 45)
Select the storage location of the compressed device descriptions to be read in.
Set the path and the file name for compressed device descriptions or navigate
to the location.
●
List of integrated device
descriptions (Page 46)
The device descriptions integrated in the PC are read in to the device list.
●
List of device descriptions
used (Page 46)
The device descriptions used in the STEP 7 project are displayed.
●
Save device list (Page 47)
The displayed information of the current device list is saved.
Specify the storage location and file name for the file in which the device list is
to be saved.
●
Print device list (Page 47)
The device list is sent to the selected printer.
●
Deleting the device list
(Page 48)
The displayed device list is emptied.
Application example:
Clearing the device list before reading in device descriptions again.
●
Exit (Page 48)
Closes the Device Integration Manager.
View
●
Split device list window
(Page 48)
The device list window is split or the split is removed.
Catalog
●
Complete device
information (Page 49)
If the software detects that relevant information is missing in a device description
during its import, the "Device info incomplete" icon appears in the status column
of the device list.
If you select an affected device in the device list, you can then complete the
device information in a dialog.
●
Integrate (Page 50)
The device descriptions are integrated into SIMATIC PDM for those devices
selected in the device list.
Requirement:
The check box for the required device is selected in the "Path" column of the
device list.
●
Creating user-specific
device DVD (Page 50)
Your own device library is created.
Device libraries that were created in this way can be copied, compressed or
burned to DVD. These libraries can be read in and integrated with the Device
Integration Manager just like the SIMATIC PDM DVD "Device Library …".
●
Applying Filter File
(Page 51)
Select a filter file (previously saved device list) according to which the currently
displayed device list is to be filtered.
●
Applying a project filter
(Page 51)
Select a project or multiproject to filter the currently displayed device list for
components used in the project.
●
Remove Filter File/Project
Filter (Page 51)
Filtering by means of a filter file or project filter is stopped.
●
Messages (Page 52)
The "Messages" dialog box opens.
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
33
Find (Page 53)
The "Find" dialog window opens.
?
●
Help (Page 53)
Opens the help for SIMATIC PDM.
●
Info (Page 54)
The following information is displayed:
●
SIMATIC PDM version
●
Information about the "Device Integration Manager" component
Additional information
Use SIMATIC Manager to make the settings for the Device Integration Manager.
You can find information on this in the following sections:
●
Setting the language: Section Options > "Settings (Page 208)"
●
Section Options > SIMATIC PDM > Settings > "Device Integration Manager" tab
(Page 213)
5.3.3
Toolbar
The toolbar is located below the menu bar and contains a number of icons with which you can
quickly perform frequently used menu commands without having to open a menu and select
the command.
Icons
Meanings of the icons used:
Icon
Menu command
Description
Read device descriptions
from source directory
(Page 45)
Select the storage location of the device descriptions to
be read in.
Set the path to the device descriptions or navigate to the
location.
Read device descriptions
from compressed source
(Page 45)
Select the storage location of the compressed device
descriptions to be read in.
Set the path and the file name for compressed device
descriptions or navigate to the location.
Integrate (Page 50)
The device descriptions are integrated into SIMATIC PDM
for those devices selected in the device list.
Print device list (Page 47) The device list is sent to the selected printer.
Deleting the device list
(Page 48)
The displayed device list is emptied.
Application example:
Clearing the device list before reading in device
descriptions again.
List of integrated device
descriptions (Page 46)
The device descriptions integrated in the PC are read in
to the device list.
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
34
Operating Manual, 02/2014, A5E33203676-AA
List of device descriptions
used (Page 46)
The device descriptions used in the STEP 7 project are
displayed.
Creating user-specific
device DVD (Page 50)
Your own device library is created.
Save device list (Page 47) The displayed information of the current device list is
saved.
Specify the storage location and file name for the file in
which you want the device list to be saved.
Applying Filter File
(Page 51)
Select a filter file (previously saved device list) according
to which the currently displayed device list is to be filtered.
Applying a project filter
(Page 51)
Select a project or multiproject to filter the device list for
components used in the project.
Split device list window
(Page 48)
The device list window is split or the split is removed once
again.
Messages (Page 52)
The "Messages" dialog box opens.
Using the Find function
(Page 53)
The displayed device list is searched.
Open the "Find" dialog box. Enter a character string and
specify the search options.
Help (Page 53)
The SIMATIC PDM help opens.
5.3.4
Device list
The device list in the "Device Integration Manager" dialog window contains tabular information
on device descriptions and devices that can be interpreted by SIMATIC PDM with a device
description.
Columns
Column
Description
Path
Tree structure - The devices with device description are displayed in a hierarchical
structure (catalog path).
Flat structure - The devices with device description are displayed without a hierarchical
structure.
The devices are displayed in a hierarchical structure when you click the "Path" column
header for sorting.
The devices are displayed in a flat structure when you click the header of any other column
(except "Path").
●
Select the check boxes for the devices whose device descriptions are to be integrated.
Communication
Folder for device classes (actuator/sensor etc.)
Manufacturer
Device type, Component, Device version, Variant
Device name
Device name
Manufacturer
Manufacturer
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
35
Communication type for the connection to the field device
Device class
Catalog position (object name)
New version
Version of the device description which was read in from a device description library
Integrated version
EDD source version
Integrated on
Installation date of the installed EDD
Description
Attribute from device file
Type ID
ID of the device type
GSD file
Names of the GSD files
New DD revision
Revision of the device description file of the imported device package
Integrated DD revision
Revision of the device description file of the integrated device package
New device revision
Device revision of the device with which the imported device package is compatible.
Integrated device revision
Device revision of the device with which the integrated device package is compatible.
Device library
Version number of the device DVD from which the device package was imported during
integration
If the device package was supplied as a single package, this column is empty.
Additional information may be displayed.
●
You can select the columns to be displayed in the SIMATIC Manager using the following menu command: Options >
SIMATIC PDM > Settings... .
●
You will find additional information on this topic in section "Device Integration Manager" tab (Page 213).
Status icons of the device description
Meaning of icons before the status of the device description integration
Icon
Meaning
Not (yet) integrated
Device info incomplete
An identical or newer device description is integrated.
The device description is in the process of being integrated.
The device description has been integrated successfully.
The device description is used in the project but neither read in nor integrated.
Error; Observe the error details in the message window.
Warning; Observe the warning details in the message window.
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
36
Operating Manual, 02/2014, A5E33203676-AA
Meaning of icons after the device descriptions have been read in and before they have been
integrated
Icon
Meaning
The device description has been read in without any errors but has not yet been
integrated.
The device information is incomplete in the imported device description. The device
description cannot be integrated correctly.
You can find information on correcting this in the section "Completing a device
description (Page 41)".
An identical or newer version of the device description is integrated.
The device description is in the process of being integrated.
The device description has been integrated successfully.
Errors occurred while reading in the device description. The device description cannot
be integrated.
For details regarding the error messages, see the message window.
Warnings generated. The device description has been read in and can be integrated.
Meaning of the icons after integration of the device description
Icon
Meaning
The device description has not been integrated because the user did not select it for
integration.
The device description was not integrated because an identical or a newer version was
already installed.
The device description has been successfully integrated without errors.
The device description has been successfully integrated without errors. Warnings
occurred during the semantic check.
The device description has been successfully integrated without errors. Errors occurred
during the semantic check.
An attempt was made to integrate the device description. The device description could
not be integrated due to an error.
●
Error messages:
For details, please refer to the message window.
●
Potential cause: Device information incomplete during integration.
The device description has been integrated. The warnings indicate potential
inconsistencies.
Sorting
You can sort the contents of the table. Click on the cell in the header of the column based on
which the contents should be sorted. Clicking on this cell again changes the sorting direction
(ascending/descending).
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
37
The status bar is located at the bottom of the main window. It displays the number of read in
or integrated device descriptions.
5.3.6
Source folder
The Source folder box is located underneath the toolbar. You use this box to select the path
in which the device descriptions are located. The device list is created based on the device
descriptions.
The source can be:
Icon
Meaning
Folder
Compressed file (*.zip)
Device description file (*.xml)
The Source folder box gives you the option to display the history of the directories so far. Click
the drop-down list icon on the right side of the box to display the last ten sources.
Changing the source folder
Procedure
1. Click the "Find folder" icon.
The "Change source folder" dialog box opens.
2. Navigate to the required directory in the file system.
3. Click "OK".
Alternatively, you can enter the path in the text box.
All compressed files included in the selected source directory are searched for the device
descriptions. Compressed files within a compressed file are also taken into consideration.
5.3.7
Applying a filter
The "Filter" box is located underneath the "Source folder" box. You can filter for up to three
strings of your choice (filters 1, 2 and 3) simultaneously. When the filter is applied, all devices
that include all specified strings in their device description are displayed. A distinction is not
made between uppercase and lowercase letters.
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
38
Operating Manual, 02/2014, A5E33203676-AA
1. Click in the text box "Filter 1", "Filter 2" or "Filter 3".
2. Enter the required search term.
3. Confirm your entry with the "Enter" key.
The device list is searched for the search terms and updated.
Each input box gives you the option to display the history of the search terms so far.
●
Click the drop-down list icon to the right of the text box to display the history.
●
To disable individual filters, click on the
of the respective filter.
Note
The filter (text boxes, filter files, project filter) does not only affect the display. The selections
of all devices excluded by the filter are removed and no longer set when the filter is disabled.
See also
Applying a project filter (Page 51)
Remove Filter File/Project Filter (Page 51)
Applying Filter File (Page 51)
5.3.8
Filter file/Project filter
The "Filter file/Project filter" box is located underneath the "Source folder" box. It is only
displayed when you use a filter file or the project filter.
The devices that match the data of the filter file or are contained in the project file are displayed
when the filter is applied.
Applying a filter
The procedure for applying a filter file or a project filter is described under Filter file (Page 51)
or Project filter (Page 51).
See also
Remove Filter File/Project Filter (Page 51)
Integrating devices into SIMATIC PDM
5.3 Views
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
39
Working with the Device Integration Manager
5.4.1
Integrating device descriptions
The Device Integration Manager is the SIMATIC PDM function for integrating device
descriptions.
Device descriptions of the "Device Library" DVD
Make sure the device descriptions are always integrated in SIMATIC PDM from the "Device
Library" DVD provided with your version of SIMATIC PDM. Changes in the device descriptions
and the catalog structure may exist between the different versions.
Note
FOUNDATION Fieldbus
The SIMATIC PDM option "FOUNDATION Fieldbus" must be installed to integrate device
descriptions for devices on FOUNDATION Fieldbus.
You can find information on this in section "Installing SIMATIC PDM (Page 23)"
Upgrading SIMATIC PDM
Note
Checking for all device types used in the project
After integrating the device descriptions, you need to check the assignment of the device
description (by opening the parameter assignment interface once).
Procedure
1. Close all SIMATIC programs that are open on the PDM PC.
2. Go to the Windows Start menu and select the menu command SIMATIC PDM > Device
Integration Manager under the Siemens SIMATIC programs.
You must accept the license agreement to be able to use the Device Integration Manager .
3. Select the File > Read device descriptions from source directory... or File > Read device
descriptions from compressed source... menu command.
4. Navigate to the folder with the device descriptions in the tree structure.
Note
"Device Library" DVD
The "Device Library" DVD is supplied with SIMATIC PDM. Select the drive containing the
DVD.
Integrating devices into SIMATIC PDM
5.4 Working with the Device Integration Manager
Help for SIMATIC PDM (V8.2)
40
Operating Manual, 02/2014, A5E33203676-AA
5. Click the "OK" button.
The device descriptions found are displayed in the "Devices" list.
You can find additional information on this in the section "Device list (Page 35)".
6. Select the check boxes for the devices whose device descriptions are to be integrated. The
check box is automatically selected for devices that have not been integrated or have been
integrated with an older version. You can work with a split device list window (Page 48).
7. Select the Catalog > Integration... menu command.
The device descriptions are transferred to the PC.
Note
During the device description integration
Do not open any SIMATIC programs until the device description integration has completed.
Completing the information for a device description
If information is missing from a device description, e.g., regarding the classification, you can
add this information yourself. You can find information on this in the section "Completing a
device description (Page 41)".
Additional information
●
Section "Delivery contents (Page 22)"
●
Section "Messages (Page 44)"
●
Section "Checking the device integration (Page 74)"
●
Section "Replacing devices (Page 106)"
5.4.2
Completing a device description
If the software detects that information is missing in a device description during its import, the
"Device info incomplete" icon appears in the status column of the device list.
Recommendation:
Each device description marked in this way should be completed before it is integrated in
SIMATIC PDM.
Note
Completing device information at a later date
If you need to complete any device information at a later date then please follow the procedure
below.
Integrating devices into SIMATIC PDM
5.4 Working with the Device Integration Manager
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
41
1. Select an incomplete device description and then select the Complete device
information... command in the shortcut menu.
2. Complete the device description.
3. Click "OK".
Note
Saving the changes
●
If the device description is located on a read-only medium, changes cannot be made.
In this case, copy the device description to a medium that is not write-protected and
start the process again.
●
The changes will remain available in the Device Integration Manager until the dialog
box is closed. When you click the "OK" button, the changes are applied to the device
description.
4. Click "Integrate".
The integration of the device description is performed.
Additional information
You can find information on the device list entries in the section "Device list (Page 35)".
5.4.3
Creating your own device library using the project filter
Introduction
You use the following procedure to create your own device library using the project filter.
Project filter
Information on the project filter and its application is available in the section "Applying a project
filter (Page 51)".
Procedure
1. Read in the device descriptions of a standard library.
2. Apply a project filter.
3. Select the Catalog > Creating user-specific device DVD... menu command.
4. Enter the destination path in the "Create own device library... " dialog box.
5. Enter the device library name or the version identification of the device library.
Integrating devices into SIMATIC PDM
5.4 Working with the Device Integration Manager
Help for SIMATIC PDM (V8.2)
42
Operating Manual, 02/2014, A5E33203676-AA
Devices without help files
If you are using a device without help files, you can integrate the help files at a later time. To
do this, answer the "Missing Help Files" dialog box with "Yes".
Additional information
Section "Integrating device descriptions (Page 40)"
See also
Basis for using intelligent field devices (Page 12)
5.4.4
Creating your own device library from a collection of device descriptions
You use the following procedure to create your own device library from a collection of device
descriptions.
Collection of device descriptions
You can find information about the availability of device descriptions and their application in
the section "Basis for using intelligent field devices (Page 12)".
Procedure
1. Read in the device descriptions of a standard library.
2. Select the check box for the device descriptions that you need in your own device library.
3. Select the Catalog > Creating user-specific device DVD... menu command.
4. Enter the destination path in the "Create own device library... " dialog box.
5. Enter the device library name or the version identification of the device library.
Note
Devices without help files
If you are using a device without help files, you can integrate the help files at a later time. To
do this, answer the "Missing Help Files" dialog box with "Yes".
Additional information
Section "Integrating device descriptions (Page 40)"
Integrating devices into SIMATIC PDM
5.4 Working with the Device Integration Manager
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
43
Removing device descriptions
Shortcut menu
If you select objects in the list of integrated device descriptions, you can use the shortcut menu
to remove the device description:
Removing integrated device descriptions
Delete the selected objects from the list of integrated device descriptions via this menu
command. The selected objects are also deleted from the catalog.
5.4.6
Update/upgrade of device descriptions (EDD update)
Procedure
1. Check the version of the integrated device descriptions.
You can find information on this in the section "Device list (Page 35)".
2. Read in the new device descriptions and compare the new version with the integrated
version.
You can find information on this in the section "Read device descriptions from source
directory (Page 45)".
3. Select the required device descriptions and integrate the device descriptions. The check
box is automatically selected for devices that have not been integrated or have been
integrated with an older version.
Information on this is available in the section "Integrating device descriptions (Page 40)".
See also
Download to device (Page 200)
5.4.7
Messages
Message log
If errors occur during the actions or in the application of the Device Integration Manager, they
are shown in the message log. The message log opens automatically when a warning or an
error has occurred, but it can also be opened manually from any node in the device list. In this
case, all messages of the nodes under this in the hierarchical order are displayed.
Additional information
Section "Message log (Page 138)"
Integrating devices into SIMATIC PDM
5.4 Working with the Device Integration Manager
Help for SIMATIC PDM (V8.2)
44
Operating Manual, 02/2014, A5E33203676-AA
Menus and dialog boxes
5.5.1
File
5.5.1.1
Read device descriptions from source directory
Before devices can be configured in SIMATIC PDM, the associated device description files
need to be read in using the Device Integration Manager.
Requirement
The storage paths of the device description files can be accessed.
Procedure
1. Select the menu command File > Read device description files from source directory ....
In the tree structure, navigate to the storage path where the device description files are
saved.
2. Click "OK".
The device description files are read in.
Note
If the compressed file is password-protected, a dialog appears for entering a password.
Shortcut menu
If you select objects in the list of read in device descriptions, you will find the following via the
object-dependent shortcut menu commands below:
●
Messages (Page 44)
Open the message log via this menu command.
●
Complete device information (Page 49)
Open the "Complete device information..." dialog via this menu command.
5.5.1.2
Read device descriptions from compressed source
Introduction
Before devices can be configured in SIMATIC PDM, the associated device description files
need to be read in using the Device Integration Manager.
Requirement
The storage paths of the device description files can be accessed.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
45
1. Select the File > Read device description files from compressed source ... menu command.
2. In the tree structure, navigate to the storage path of the device description files.
3. Click "OK".
The device description files are read in.
Note
If the compressed file is password-protected, a dialog appears for entering a password.
Shortcut menu
If you select objects in the list of read in device descriptions, you will find the following object-
dependent shortcut menu commands:
●
Messages (Page 44)
You use this menu command to open the message log.
●
Complete device information (Page 49)
You use this menu command to open the "Complete device information..." dialog.
5.5.1.3
List of integrated device descriptions
Displaying the device list
Displays the devices for which a device description file is saved on the PC.
Shortcut menu
If you select objects in the list of integrated device descriptions, you will find the following object-
dependent shortcut menu commands:
●
Messages (Page 52)
You use this menu command to open the message log.
●
Remove integrated device description(s) (Page 44)
You use this menu command to delete selected objects from the list of integrated device
descriptions.
See also
Complete device information (Page 49)
5.5.1.4
List of device descriptions used
Displaying the device list
Display of the devices used in the project.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
46
Operating Manual, 02/2014, A5E33203676-AA
The status column (Page 35) indicates whether or not the corresponding device description is
integrated on the computer.
If you select a STEP 7 multiproject, all projects are always displayed, even when only a
subproject is selected in the dialog box.
Shortcut menu
If you select objects in the list of integrated device descriptions, you will find the following object-
dependent shortcut menu commands:
●
Messages (Page 52)
You use this menu command to open the message log.
●
Remove integrated device description(s) (Page 44)
You use this menu command to delete selected objects from the list of integrated device
descriptions.
See also
Complete device information (Page 49)
5.5.1.5
Save device list
Saving the device list
Specify the storage location and file name for the file in which you want the device list to be
saved.
5.5.1.6
Print device list
You can print the device list that is currently being displayed.
Setting the printer options
Note
●
The printer options depend on your computer's operating system and on the printer being
used.
●
The file is sent to the default printer.
●
If the printout has more than one page, two periods are printed after the page number in
the bottom right corner of the page. The last page does not have these periods, indicating
no more pages are to follow.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
47
1. Select the menu command File > Print device list or click the "Print" button.
The "Print" dialog box opens.
2. Select the required options.
3. Click "OK".
5.5.1.7
Deleting the device list
Clearing the displayed device list.
Example of application
Clearing the device list before reading in device descriptions again.
5.5.1.8
Exit
Exits the "Device Integration Manager".
5.5.2
View
5.5.2.1
Split device list window
The device list window is split or the split is removed.
When you select the menu command, the device list window is cut in half vertically. The right
half shows an additional device list window with the same structure. This window includes all
devices selected in the left device list window (check boxes are selected).
Note
The line selected with the mouse is displayed with a blue background in the active window.
In the inactive window, the line is displayed with a gray background.
The check boxes in the left device list window are visible but cannot be operated.
You can move the dividing line between the two device list windows with the mouse.
The buttons for adding or removing selected individual devices or sub-trees are located
between the two windows.
The selection of devices in the device list window is used for
• Integrating and
• Creating your own device library.
With a device list window that is not split, a selection can be made by setting the check boxes
in the line of the device.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
48
Operating Manual, 02/2014, A5E33203676-AA
By selecting a line in the left device list window and clicking the
button, you add individual
devices or sub-trees to the right device list window.
By selecting a line in the right device list window and clicking the
button, you remove the
individual devices or sub-trees added previously from the right device list window.
Keyboard operation
Use the "SHIFT + >" and "SHIFT + <" shortcuts to add or remove the selected devices to and
from the right window.
Rules for working with split device list windows
When a filter is used, it acts on both device list windows.
Sorting can take place independently in each window.
Searches are only conducted in the active window with the selected line having a blue
background.
An export only includes the contents of the left window (with selection information).
Only one device list window is displayed after the Device Integration Manager is restarted.
Note
You cannot split the device list window when the list of integrated or used devices is displayed.
5.5.3
Catalog
5.5.3.1
Complete device information
Modifying the information in a device description file
The table below shows the information that can be completed in the "Device Integration
Manager" dialog box using the "Complete device information" function.
Column
Explanation
Device name
You can modify the device name in this input box.
Name of the device
version
You can modify the version of the device description in this input field.
Manufacturer
Manufacturer of the field device
Type ID
Identifier for a device type in hexadecimal format
You can find information on this in IEC 61804-3.
Device revision
Identifier for a device revision
Communication
Communication type for the connection to the field device
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
49
Class of the device - name of the object (e.g., SENSOR - FLOW -
ULTRASONIC)
DD revision
Version of the device description file
You can find information on this in IEC 61804-3.
EDD
Name of the device version
You can find information on this in IEC 61804-3.
5.5.3.2
Integrate
Use the menu command Catalog > Integrate to integrate the device description files of the
devices into the device catalog of SIMATIC PDM for those devices with selected check boxes
in the "Path" column of the device list.
Compiling device description files for SIMATIC PDM
You can find information about the possible settings in the description of the PDM setting in
the section ""Device Integration Manager" tab (Page 213)".
Remove integrated device description(s)
Section "List of integrated device descriptions (Page 46)"
5.5.3.3
User-specific device DVD
Creating user-specific device DVD
You can use the Catalog > Creating user-specific device DVD... menu command to create
your own device library. You can copy created device libraries, save them as compressed
archive or burn them on DVD and read in and integrate them with the Device Integration
Manager just like the SIMATIC PDM DVD "Device Library …".
Additional information
Information on creating a device library from a collection of device descriptions is available
here (Page 43).
Information on creating a device library using a project filter is available here (Page 42).
"Creating user-specific device DVD" dialog
Procedure
1. Select the Catalog > Creating user-specific device DVD... menu command.
The "Create own device library ..." dialog box opens.
2. Enter the destination path, the name and a version identification of the device library.
3. Click "OK".
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
50
Operating Manual, 02/2014, A5E33203676-AA
Applying Filter File
You can use the Catalog > Applying Filter File... menu command to apply predefined filter files
(device lists in XML format saved in the Device Integration Manager beforehand) to the device
library.
The "Filter file" box is displayed underneath the "Source folder" box if a filter file is loaded.
"Apply Filter File..." dialog box
Procedure
1. Select the Catalog > Applying Filter File... menu command.
The "Applying Filter File..." dialog box opens.
2. Select a file with an exported device list.
3. Click "OK".
The currently displayed device list is filtered as follows:
• Only devices that are read in and are included in the filter file are displayed.
• Only devices that are selected in the filter file can be selected for integration.
Remove Filter File/Project Filter
The Catalog > Remove Filter File/Project Filter menu command is used to stop the application
of the filter file or a project filter. The complete device list is displayed once again when you
revoke the filter.
5.5.3.5
Project filter
Applying a project filter
You can use the Catalog > Apply Project Filter… menu command to select a STEP 7 project
or STEP 7 multiproject to filter the device list for the components used in the project.
The "Project filter" box is displayed underneath the "Source folder" box if a project is loaded.
By combining the "Create own device library" and "Apply Project Filter" functions, you can
create a device DVD that is perfectly adapted to your project.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
51
If you select a STEP 7 multiproject, all projects are always selected, even when only a
subproject is selected in the dialog box.
Note
Object status
Make sure that the status of each device contained in the project file is also integrated in the
device library before you apply the project filter. You can determine this by the status icon in
the "Icon" column of the device list. You can find a list of the icons under Device list
(Page 35).
Additional information
Information on creating a device library using a project filter is available here (Page 42).
"Apply project filter..." dialog box
Requirement
A device list has been read in.
Applying a project filter
Procedure
1. Click the "Apply Project Filter..." icon in the menu bar.
The "Open Project" dialog box opens.
2. Select the required project in the "User project" tab.
If you want to open a multiproject, select the "Multiproject" tab.
3. If the required project file is located on an external source, click the "Browse" button and
navigate to the required path.
4. Confirm your entry by pressing "Enter".
The device list is searched and updated.
To revoke the filter, click the
button.
Remove Filter File/Project Filter
The Catalog > Remove Filter File/Project Filter menu command is used to stop the application
of the filter file or a project filter. The complete device list is displayed once again when you
revoke the filter.
5.5.3.6
Messages
Opens the "Messages" dialog box.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
52
Operating Manual, 02/2014, A5E33203676-AA
Section "Message log (Page 138)"
5.5.3.7
Find
Using the Find function
You can use the Catalog > Find menu command to find device description files.
"Find" dialog box
Procedure
1. Select the menu command Catalog > Find.
The "Find" dialog box opens.
2. Enter a string and define search options.
3. Click "Find".
Settings in the "Find" dialog box
●
Entry field with drop-down list
You can enter any string. You can search for this string.
●
Check boxes
–
Match case
The writing style of the string entered for an object in the device list is observed.
–
Match entire cell contents
The entire string must match for an object in the device list.
–
Search up
If this option is enabled, the search begins at the selected point and continues until the
start of the device list.
If this option is disabled, the search begins at the selected point and continues until the
end of the device list.
●
"Find" button
The system searches through the displayed device list.
5.5.4
? (Help)
5.5.4.1
Help
This menu command displays the Help on SIMATIC PDM.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
53
You can navigate to different help topics from the Table of Contents. The "Index" and "Find"
functions enable you to display information on specific terms.
5.5.4.2
Info
This menu command displays information about the version and the copyright.
Integrating devices into SIMATIC PDM
5.5 Menus and dialog boxes
Help for SIMATIC PDM (V8.2)
54
Operating Manual, 02/2014, A5E33203676-AA
PDM objects are displayed in the following views in SIMATIC Manager:
●
Process Device Plant View
The process device plant view provides an overview of all configured devices in all
configured networks.
●
Process Device Network View
The plant topology is reproduced in the process device network view. The depicted objects
are links to the objects in the plant view.
●
PDM objects can be configured with HW Config. Open the SIMATIC PDM shortcut menu
to assign parameters.
●
The network links to the PDM objects are also listed in NetPro.
Working with SIMATIC PDM
License keys are required to use SIMATIC PDM. You will find information about this in the
pdmbase-readme file.
Recommendation: Before you assign parameters to a field device with SIMATIC PDM, check
whether you can reach the required device.
Additional information
Section "Settings" for the SIMATIC project (Page 71)"
6.2
Views in SIMATIC Manager
6.2.1
Process devices plant view
In SIMATIC Manager, you call the process devices plant view using the menu command View
> Process devices plant view.
The process devices plant view provides an overview of all configured devices in all configured
networks. This view is used to obtain a quick overview of the configured devices. You cannot
configure new networks in this view.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
55
Section ""Settings" for the SIMATIC project (Page 71)"
6.2.2
Process devices network view
In SIMATIC Manager, you call the process devices network view using the menu command
View > Process devices network view.
The process devices network view displays the devices in groups according to the network
topology. You can configure smaller projects directly in the process devices network view, for
example, for end-to-end connections between a PC and a device in the factory.
Views
6.2 Views in SIMATIC Manager
Help for SIMATIC PDM (V8.2)
56
Operating Manual, 02/2014, A5E33203676-AA
Section ""Settings" for the SIMATIC project (Page 71)"
6.2.3
Open SIMATIC PDM in the Process Devices - Plant View
Procedure
1. Select the View > Process devices plant view menu command in SIMATIC Manager.
The process devices plant view opens.
2. Select the "Devices" object in the S7 project.
All available devices are displayed.
3. Double-click the desired object.
The desired object opens in SIMATIC PDM.
6.2.4
Project synchronization
HW Config
In the course of device configuration in HW Config, an image of the plant structure, including
all devices which can be configured using SIMATIC PDM, is transferred from HW Config to
the process devices network view.
After saving in HW Config, the changes made to the devices are applied in the following views:
●
Process devices network view
●
Process devices plant view
Changes cannot be incorporated into the process devices view if the higher-level objects are
linked with HW Config to an existing S7 station.
Views
6.2 Views in SIMATIC Manager
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
57
Views in SIMATIC PDM
6.3.1
Main Window "SIMATIC PDM"
Introduction
The "SIMATIC PDM" main window remains on the screen throughout the work session and is
partially or totally covered by other activated dialog windows.
The main window is structured as follows:
Title bar (Page 59): The title bar shows the project name or the name of the object which was selected
before SIMATIC PDM was called.
Menu bar (Page 59): The menu bar can be used to call SIMATIC PDM functions and manufacturer-
specific device functions.
Toolbar (Page 60): The toolbar enables certain menu commands to be accessed quickly.
Structure view (Page 60): The objects
displayed depend on the object which was
selected before SIMATIC PDM was started.
Parameter table (Page 61): The parameters for the
object selected in the structure view are displayed in a
table.
Status bar (Page 64): Contains information on processes currently being performed.
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
58
Operating Manual, 02/2014, A5E33203676-AA
The title bar shows the name of the object which was selected before SIMATIC PDM was
called.
6.3.3
Menu bar
Structure
Below is an overview of the SIMATIC PDM menus.
Menu
Submenu in parameter assignment mode
File
●
Save (Page 155)
●
Exporting (Page 200)
●
Importing (Page 200)
●
Print (Page 161)
●
Exit (Page 162)
Device
●
Download to device (Page 163)
●
Upload to PG/PC (Page 165)
●
Assign address and TAG (Page 171)
●
Value comparison (Page 168)
●
Object properties (Page 172)
●
Calibration log (Page 176)
●
Change log (Page 184)
View
●
Process variables (Page 188)
●
Start LifeList (Page 127)
●
Trends (Page 189) (depends on device)
Diagnostics
●
Update diagnostics (Page 191)
Help
●
Contents (Page 193)
●
Help for device parameters (Page 193)
●
Info (Page 193)
●
Find (Page 194)
●
Document Manager (Page 194)
●
Device manual (depends on device)
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
59
The toolbar is located below the menu bar and contains a number of icons with which you can
quickly perform frequently used menu commands without having to open a menu and select
the command.
SIMATIC PDM mode
Icons
Parameter assignment mode
Icons
The icons are linked to the following commands:
Parameter assignment mode
Menu command
Save (Page 155)
Print (Page 161)
Download to device (Page 200)
Upload to PG/PC (Page 201)
Value comparison (Page 168)
Change log (Page 184)
Process variables / Measured value display (depends on device)
(Page 188)
Update diagnostics (Page 191)
Start LifeList (Page 127)
Find (Page 194)
Contents (Page 193)
6.3.5
Structure view
The left-hand section of the main window in the structure view contains a tree structure. The
objects displayed depend on the object which was selected before SIMATIC PDM was started.
●
If a single field device was selected, it will be displayed in the structure view. You can find
information on this in the section "Stand-alone device view (Page 65)".
●
If a network or gateway (e.g., DP/PA-Link) was selected, the tree structure is displayed with
the associated devices in the structure view. You can find information on this in the section
"Multiple devices view (Page 66)".
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
60
Operating Manual, 02/2014, A5E33203676-AA
You will see the following status icons in front of the objects in the tree view:
Icon
Meaning
The device has been loaded.
At least one parameter of the object has been changed.
The object is already open at another location (window or computer).
The object is locked for editing in the current view.
The object is already open at another location (window or computer).
Another user is making changes to the object.
At least one parameter of the object is defective.
Display
The following are displayed in the structure view:
●
Objects with associated parameter groups
●
Any available lower-level objects
The selected parameter group is displayed on a blue background. The parameter table shows
the parameters of the selected parameter group.
Objects that contain lower-level objects can be identified by the check boxes next to the object
icon:
●
Check box "+"
●
Check box "-"
Note
Generally speaking, the table is only opened down to the structure view.
Move the parameter table in order to view all the general information for a device.
6.3.6
Parameter table
The right pane of the main window is filled by the parameter table.
The parameter table shows a device's parameters in the order in which they are listed in the
structure view. Unlike in the structure tree, no hierarchy is displayed here.
Device parameters
The parameters which can be edited depend on the device in question. Fields with a gray
background cannot be edited.
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
61
Refer to the manufacturer device description for information on how to set the device
parameters.
Display of the parameter table
The following columns are displayed in the parameter table:
●
Parameter (Page 62)
●
Value (Page 62)
●
Unit (Page 63)
●
Status (Page 63)
Each parameter group starts with a header with the name of the group on a gray background.
The indented header text indicates the classification level of the header. The parameter lines
are positioned underneath the header.
Operator input
Any entries and changes made must be loaded to the devices in order for them to take effect.
If you click an object in the structure view, the associated parameters are displayed in the
parameter table.
Additional information
●
Section "Display in the views (Page 64)"
6.3.6.1
"Parameter" column of the parameter table
The names of the individual parameters are listed in the "Parameter" column.
6.3.6.2
"Value" column of the parameter table
This column displays the value of the parameter whose name is in the "Name" (Page 62)
column. This can be a numerical value, a physical unit, a status, or a designation.
The "Value" box can only be edited if it has a white background. A box with a gray background
indicates that the parameter is read-only and cannot be modified or written.
●
Right-click on the value to display a list of possible value settings for selection, provided
that these value settings are specified in the device description.
●
Enter a new value here or select a new setting from the drop-down list box.
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
62
Operating Manual, 02/2014, A5E33203676-AA
Right-click inside the parameter table to open one of the following fields:
●
An information box is shown for static fields if the cursor is located over a parameter in the
"Parameter" column.
Information is displayed to explain the meaning of the field or to explain the associated
entry in the "Value" column.
●
Selection of values from drop-down lists
The drop-down lists open when you select a corresponding value with the cursor and click
on it.
Select the correct setting for your plant- and device-specific conditions.
●
Shortcut menu for input boxes
Menu command
Explanations/operating instructions
Minimum value ...
Displays the minimum permitted value of the parameter. *) **)
Maximum value ...
Displays the maximum permitted value of the parameter. *) **)
Default value ...
Displays the default value of the parameter. *) **)
*) Click the value to transfer it to the parameter table.
**) There can be several minimum, maximum and default values.
6.3.6.3
"Unit" column of the parameter table
The "Unit" column displays the engineering unit of the numerical value present in the "Value"
(Page 62) column.
6.3.6.4
"Status" column of the parameter table
The "Status" column displays the status of the parameter whose name is in the "Name"
(Page 62) column.
The table below shows the icons that can be displayed here:
Icon
Meaning
Action that can trigger the
status
- empty -
Value (Page 62) corresponds to the offline data storage
system.
Save
Initialization running or status "OK".
Value was never changed.
Open new PDM object
The parameter has been changed by means of operator
input, import, or internal methods.
Value was changed by user.
●
Edit
●
Dialogs
The parameter could not be converted.
Value could not be converted following a change in the
unit.
Edit
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
63
Action that can trigger the
status
A parameter's value is defective.
An illegal value was detected the validity check (e.g.,
value too high or too low)
Validity check of value
The parameter has been successfully loaded.
There is no difference between the loaded and the
configured parameter.
●
Download to device
●
Upload to PG/PC
The parameter cannot be loaded, as a communication
error is present.
●
Error message when downloading to the device
●
Error message when uploading to PG/PC
●
Download to device
●
Upload to PG/PC
6.3.7
Status bar
The status bar is located at the bottom of the main window.
Display
The following information is provided in the status bar:
●
User that is currently using SIMATIC PDM
●
PDM object for which information is currently being displayed in the parameter list
●
Diagnostics activated / deactivated
●
Identity check activated / deactivated
●
Processing status
●
Connection status for the object currently selected in the tree structure
6.3.8
Display
6.3.8.1
Display in the views
Operating principle
You can open SIMATIC PDM for a device from SIMATIC Manager or HW Config.
After you open SIMATIC PDM, the table displays the values saved in the project. These values
are projected values and default values of the object, which was selected before SIMATIC
PDM was started.
All objects for which parameters can be assigned are displayed in the structure view, including
the lower-level objects. Only the parameter table of the root object is initially displayed and
can be edited (fields on white background).
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
64
Operating Manual, 02/2014, A5E33203676-AA
Select an object in the structure view; its parameters are then shown in the parameter table,
where they can be edited.
●
If an object has already been opened by a different user, a message is displayed that
identifies the user who opened the object and the PC from which the object was opened.
All fields of the parameter table then have a gray background and cannot be modified.
Note
Changes made to an object opened in SIMATIC PDM only take effect when you select
the menu command File > Save.
The displays in the status bar and title bar depend on the object you have currently selected.
Setting options for SIMATIC PDM
You can find information on this in the section "Settings for SIMATIC PDM (Page 210)".
6.3.8.2
Stand-alone device view
SIMATIC PDM is opened in the stand-alone device view if a device was selected before
SIMATIC PDM was started. The device represents the base of the tree in the structure view.
The main window is structured as follows:
Title bar
Menu bar
Toolbar
Parameter table (on the right in the main
window)
Status bar
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
65
Section "Main Window "SIMATIC PDM" (Page 58)"
6.3.8.3
Multiple devices view
SIMATIC PDM is opened in the multiple device view if an object with lower-level objects was
selected before SIMATIC PDM was started, e.g. an ET 200 station with connected field
devices. The object represents the base of the tree in the structure view.
The main window is structured as follows:
Title bar
Menu bar
Toolbar
Parameter table (on the right in the main
window)
Status bar
Display
When the multiple device view is opened, only the parameter table of the root object is
displayed at first. You can edit all the displayed objects and their lower-level objects without
opening SIMATIC PDM again.
Additional information
●
Section "Main Window "SIMATIC PDM" (Page 58)"
6.3.9
Keyboard operation
Key shortcuts
The tables below list the key shortcuts.
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
66
Operating Manual, 02/2014, A5E33203676-AA
Selecting menus via keys
Key shortcut
Function
Save (File menu) (Page 155)
Print... (File menu) (Page 161)
For the menu which contains the underscored letter X
Underscored letter in
the menu command
Assigned menu command
Key operation in dialog boxes
Key shortcut
Function
To the next input field, from left to right and from top to bottom
Arrow keys
Selected in the drop-down list
Spacebar
Selects an object or cancels a selection
Key operation in help programs
Key shortcut
Function
Closes the help window, return to the tool window
Selecting menu commands using shortcut keys
You can execute many menu commands by pressing the associated ALT key shortcut. Press
the following keys in succession:
1. key
2. The underscored letter of the required menu (e.g. , for the File menu - if the menu
bar contains a File command). The menu opens.
3. Letter that is underlined in the desired menu command.
The submenus of the corresponding menu commands will be opened in the next steps.
Repeat these actions until you have selected the entire menu command by typing in the
relevant letters.
You trigger the menu command as soon as you have entered the last letter of the shortcut
keys.
Example
Menu
Key shortcut
File
+
Help
+
Views
6.3 Views in SIMATIC PDM
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
67
Before you can work with SIMATIC PDM, a project containing at least one PDM object must
have been created in SIMATIC Manager. In the following, the term "PDM object" is used to
refer to those objects that can be configured, have parameters assigned, or be diagnosed with
SIMATIC PDM. PDM objects include:
●
Field devices
●
Remote I/O stations (with/without modules or field devices)
●
Networks containing field devices
Information about the creation process
●
For information on creating a project, refer to the PCS 7/STEP 7 help.
●
For information on creating PDM objects, please refer to the section "Inserting devices
(Page 77)".
Requirements for working with SIMATIC PDM
●
SIMATIC PDM is installed.
●
The necessary license keys are available.
●
The device descriptions have been integrated.
●
For online functions to work there must be a connection to the corresponding network. You
can find additional information on this in the section "Establishing connections to field
devices (Page 13)".
Calling SIMATIC PDM
Where
Requirement
Function
SIMATIC Manager
●
Process device network view
●
Process device plant view
Project containing PDM object has
been created.
Select object
Edit > Open object
HW Config
Device is created.
Double-click device
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
69
Scope of functions
●
Configuration and parameter assignment
–
Integrating field devices into plants and networks
–
Making project engineering settings for and configuring connections
–
Making project engineering settings for and configuring devices
●
Mini control and monitoring system for field devices
–
Controlling and monitoring field devices
●
Diagnostics
–
Performing diagnostics on field device functions
–
Performing diagnostics on networks
–
Evaluating logs
Hardware configurations
Integration into a SIMATIC project enables you to create SIMATIC stations and field devices
in HW Config. You can open SIMATIC PDM directly on the networks and subordinate field
devices listed below:
●
PROFIBUS DP
●
PROFIBUS PA
●
PROFINET IO
●
Ethernet
●
HART modem
●
FOUNDATION Fieldbus
Assigning parameters and loading
In the case of offline parameter assignment, data relating to entries and changes made in
SIMATIC PDM is saved in the project data.
The inputs and changes will only become active after uploading the project data to the device.
The option for online parameter assignment depends on the device and must be stored in the
device description.
Entries and changes made in SIMATIC PDM must be loaded into the project.
Functions
7.1 Introduction
Help for SIMATIC PDM (V8.2)
70
Operating Manual, 02/2014, A5E33203676-AA
"Settings" for the SIMATIC project
You will find the following views in SIMATIC Manager after the installation of SIMATIC PDM:
●
Process device plant view
●
Process device network view
Project settings
The project settings are made in the SIMATIC Manager. These settings apply to the SIMATIC
project and SIMATIC PDM.
●
Language for the menus and dialog boxes
●
Default project view
●
Display
●
Details in the columns
You make the project settings in SIMATIC Manager using the following menu command:
Options > Settings...
Settings
Tab
Meaning
Language selection
"Language" tab
Language displayed in the menus and dialog
boxes in the SIMATIC Manager and SIMATIC
PDM
Default project view
"View" tab
Start view for the SIMATIC Manager;
available views for SIMATIC PDM:
●
Process device plant view
●
Process device network view
Details in the columns
"Columns" tab
Views and object types in the parameter table
"Columns" tab
On the "Columns" tab, you can select the columns that you want to be displayed in a PDM
view.
Select an object type in the tree structure. Then go to the "Visible Columns" list and activate
the check boxes for the entries you want to be displayed for the selected object type.
Object types
Functions
7.2 Project editing
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
71
Type 1 in the tree structure
–
Process device plant view
–
Process device network view
●
Type 2 in the tree structure
–
Process device plant view > Devices
●
Type 3
–
Process device network view > Networks
●
Type 4
–
Process device network view > Networks > PC
●
Type 5
–
Process device network view > Networks > Communication network
–
Process device network view > Networks > Communication network > Object(on all
subordinate levels)
Visible columns
Object type
Type 1
Type 2
Type 3
Type 4
Type 5
Object name
Standard
Standard
Standard
Standard
Standard
Picture Name For OS
Standard
-
-
-
-
LID
(Location identifier denotes the
installation position of a device)
-
Standard
-
-
-
Address
-
x
-
Standard
Standard
Description
Standard
Standard
Standard
Standard
Standard
Message
Standard
Standard
Standard
Standard
Standard
Device status
-
Standard
-
-
Standard
Last communication
-
Standard
-
-
Standard
Text1
x
x
x
x
x
Text2
x
x
x
x
x
Text3
x
x
x
x
x
Device
-
Standard
x
x
Standard
PLT ID*
-
Standard
-
-
x
Manufacturer
-
Standard
-
-
Standard
Serial number
-
x
-
-
x
Installation date
-
x
-
-
x
Hardware version
-
x
-
-
x
Software version
-
x
-
-
x
Article number
-
x
-
-
x
Object status
-
Standard
-
-
Standard
DD revision
-
x
-
-
x
Author
x
x
x
x
x
Functions
7.2 Project editing
Help for SIMATIC PDM (V8.2)
72
Operating Manual, 02/2014, A5E33203676-AA
*Process control ID generated internally by PDM for identification of an object for connections
to the Asset Management System (PCS 7 Maintenance Station and PDM Maintenance
Station).
●
Type 6
–
Settings for a multiproject
Process device plant view (multiproject)
Process device network view (multiproject)
Object name
Standard
Standard
Project language
Standard
Standard
UNC path
Standard
Standard
Path to "Computer"
Standard
Standard
Computer
Standard
Standard
Computer after removal
Standard
Standard
Path after removal
Standard
Standard
See also
Settings for SIMATIC PDM (Page 210)
Menus and dialog boxes for SIMATIC PDM in the SIMATIC Manager (Page 195)
7.2.2
Setting the interface on the computer
Use the interface settings of the project (SIMATIC PCS 7 or SIMATIC STEP 7).
The following interface types are used in SIMATIC PCS 7 and SIMATIC STEP 7:
●
PROFIBUS DP interface
●
Ethernet interface
●
COM interface
Alternative communication channels in the case of redundant S7-400 stations
If SIMATIC PDM signals a connection failure due to a fault in the communication channel, an
attempt is made to automatically establish a connection using the redundant S7-400 station
via an alternative communication channel.
Functions
7.2 Project editing
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
73
Plant-wide communication by means of routing
Overview
In most automation systems, the programming device can only be operated via the bus cable
(subnet) connected directly to the automation system. On larger networked plants you must
connect the programming device to different bus cables (subnets) before you can go online to
a remote automation system.
Routing function
The routing function allows you to reach automation systems online across subnet boundaries
from a central point (Engineering Station) with the programming device or PC, in order, for
example, to download user programs or a hardware configuration or to perform test functions.
Requirements
The following conditions must be met for S7 routing:
●
STEP 7 as of version 5.5 and SIMATIC PDM, i.e., SIMATIC PDM, are integrated.
●
The communication-capable modules (CPUs or CPs) which establish gateways between
subnets must support "S7 routing".
●
All the automation devices or communications partners that can be reached in a plant
network are configured and downloaded within an S7 project.
●
The SIMATIC S7 station required is networked and can be reached via the network nodes.
●
The last communication interface (CPU, CP) supports the "Dataset gateway" function.
●
The modules are downloaded together with the configuration information, which contains
the current "knowledge" on the complete network configuration of the project.
Reason: All the modules involved in the gateway must receive information on which subnets
can be reached over which routes (routing tables).
●
The programming device or PC to which you want to establish an online connection via a
gateway is configured in the network configuration and assigned to your programming
device.
Additional information
SIMATIC documentation; SIMATIC PDM; pdm-readme
7.2.4
Checking the device integration
You can check in a project whether the required device descriptions are integrated for all
objects to be displayed in SIMATIC PDM.
These situations serve as examples for this:
Functions
7.2 Project editing
Help for SIMATIC PDM (V8.2)
74
Operating Manual, 02/2014, A5E33203676-AA
A project has been copied to the PDM computer.
●
Device descriptions have been deleted on the computer.
●
A computer has been reinstalled and the device descriptions were not integrated.
Requirement
SIMATIC PDM is installed.
Procedure
1. Open the process devices plant view in SIMATIC Manager.
2. Open the "Devices" folder in the tree view.
3. Check whether devices are there that are labeled as follows:
Icon
Meaning
Note
Deactivated
No device description is integrated in SIMATIC PDM for the
device.
4. If deactivated devices have been found, select the View > Details menu command.
5. Check the information in the "Object name" column.
Information in the "Object
name" column
Meaning
Further procedure
"TAG" or "Default"
A device description from the
device catalog has not yet
been assigned to the device.
Assign the required device description to
the device.
Section "Device selection (Reassign)
(Page 202)"
Plant-specific object
name
The device description that has
been assigned to the device
cannot be found or is no longer
functional (e.g. accidentally
deleted).
Integrate the required device description.
Section "Integrating device descriptions
(Page 40)"
Additional information
●
Section "Overview of Device Icons (Page 124)"
●
Section "Replacing devices (Page 106)"
●
Section "Completing a device description (Page 41)"
●
Section "Cleaning the project (reorganization) (Page 76)"
7.2.5
Print
You can print out the parameter list for a device.
Functions
7.2 Project editing
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
75
Setting the printer options
Note
Note the following:
●
The printer options depend on your computer's operating system and on the printer being
used.
●
The file is sent to the default printer.
●
If the printout has more than one page, two periods are printed after the page number in
the bottom right corner of the page. The last page does not have these periods, indicating
no more pages are to follow.
Requirements
●
SIMATIC PDM is open.
●
In the structure view, an object is selected in the root folder of a device.
You can find information on the structure view in the section "Stand-alone device view
(Page 65)".
Procedure
1. Select the menu command File > Print or click the "Print" button
.
The "Print" dialog box opens.
2. Select the required options.
3. Click "OK".
7.2.6
Cleaning the project (reorganization)
PDM objects can be contained in copied SIMATIC projects. If SIMATIC PDM will no longer be
used in the project, you can remove the requirement for TAG licenses in the project using the
"Reorganize" function.
Note
SIMATIC PDM must be closed before you use the "Reorganize" function.
The time it takes to perform reorganization depends on the data movement required, and it
can be a long time. The function is therefore not carried out automatically (for example, when
closing a project).
Procedure
In SIMATIC Manager, select the menu command File > Reorganize.
Functions
7.2 Project editing
Help for SIMATIC PDM (V8.2)
76
Operating Manual, 02/2014, A5E33203676-AA
Saving the configuration
Changes that are made with SIMATIC PDM are always stored in the SIMATIC project.
Save the SIMATIC project to save the changes. Stop SIMATIC PDM before you save an entire
SIMATIC project.
Procedure
Select the menu command File > Save As in the SIMATIC Manager.
Additional information
●
STEP 7 Online Help
●
PCS 7 Online Help
7.3
Device management
7.3.1
Inserting devices
7.3.1.1
Inserting objects
You can use the "Insert New Object" function to perform the following:
●
Create networks, including network components
●
Insert objects into a configured network:
–
Insert an individual device or module
–
Insert multiple devices or modules at the same time
Note
This function is only available for the following devices:
●
PROFIBUS devices
●
PROFINET devices
●
HART modem devices
●
HART devices downstream of a remote I/O
Configure FOUNDATION Fieldbus devices in HW Config.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
77
The project is open in the process device network view.
●
The PDM folder called "Networks" is available in the tree structure.
If the folder structure has not yet been created, select the menu command Insert New Object
followed by Networks.
Note
Licenses for SIMATIC PDM are required for further processing.
Without license keys, you can configure a maximum of 4 devices (demo mode).
Inserting a network, a header module, modules, and a field device
Follow the steps below to insert objects into higher-level objects one after the other. You will
find more information on object types that can be inserted in an object in the section ""Insert
Object - Assign Device Type" dialog box (Page 79) ".
Procedure
1. Select the higher-level object in the tree structure in the window on the left.
2. In the shortcut menu, select the menu command Insert New Object > Object.
The "Insert Object - <...>" dialog box opens.
3. Make the relevant settings for the inserted object. You can find information on this in the
section ""Insert Object - <...>" dialog box (Page 78)"
–
"Object name" input box
–
"" input box (e.g., PROFIBUS address or PROFINET IP address)
–
"Number" input box
4. Click the "Assign Device Type" button.
The "Insert Object - Assign Device Type" dialog box opens.
You can find additional information on this in the section ""Insert Object - Assign Device
Type" dialog box (Page 79)".
5. Select the object to be added from the tree structure.
6. Click "OK".
The objects are inserted.
7. Correct the assigned addresses if necessary.
You can find additional information on this in the section "Setting the bus address in HW
Config (Page 83)".
Additional information
Section "Device selection (Reassign) (Page 202)".
7.3.1.2
"Insert Object - <...>" dialog box
Make the settings for inserted objects in the "Insert Object - <...>" dialog box.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
78
Operating Manual, 02/2014, A5E33203676-AA
You must set the following parameters in order to insert objects:
●
Object name
Specify the name of the inserted object.
The entered name is the base name when creating several objects.
●
(e.g., PROFIBUS address or PROFINET IP address)
Note
This setting cannot be changed when HART devices are added.
–
Enter the address for the inserted object.
–
If you wish to create multiple objects, enter the first address of the objects to be inserted.
●
Number
Note
This setting cannot be changed when HART devices are added.
Adjust the number of objects to be added when adding several objects. Please note that
the value depends on the network being used and other factors.
A certain number (n) of objects of one type is created in accordance with these parameters.
The object name is generated as follows:
–
If the number is equal to 1, the address does not appear in the object name that is
generated ().
–
If the number is greater than 1:
PROFIBUS devices and modules
Channels of remote I/O
...
...
*: n corresponds to the number of objects to be inserted
"Assign Device Type" button
The "Insert Object - Assign Device Type" dialog box opens.
Assign a specific object type to the object you want to insert in the project. The possible object
types are listed in the tree structure. The object types displayed depend on the location at
which an object was inserted.
7.3.1.3
"Insert Object - Assign Device Type" dialog box
Select the device description file of the desired device in this dialog box.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
79
The devices are structured by the device types in a tree structure.
Note
Integrated devices
You can only select devices for which a device description file has been integrated via the
Device Integration Manager.
Object types
When assigning objects, select the object type. The following object types can be assigned,
depending on the nature of the higher-level object:
Higher-level object
Object to be inserted
PDM "Networks" folder
Communications network
●
As part of the assignment process, select the
communications network via which the PDM objects
are to be connected.
●
Selection:
–
PROFIBUS DP network
–
PROFIBUS link
–
PROFINET network
–
MODBUS
–
Ethernet
–
HART modem network
–
HART server
–
Foundation Fieldbus network
Header module
●
Selection:
–
Remote I/O
–
PROFIBUS Link
–
PROFIBUS DP device
–
PROFIBUS PA device
–
HART device
Remote I/O
Modules
●
Selection:
–
Module
Modules
●
Selection:
–
Module
Field device
●
HART device
"Device identification" Button
When you click this button, a connection to the device is established and an attempt is made
to read the information from the device. If not all the required information could be read out,
only the structures necessary for the device will remain in the tree structure. Make your
selection from these structures.
Device identification procedure:
●
For PA devices:
Select the "PROFIBUS PA" folder and then press the "Device identification" button
●
For DP devices:
Select the "PROFIBUS DP" folder and then press the "Device identification" button
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
80
Operating Manual, 02/2014, A5E33203676-AA
For MODBUS devices:
Select the "MODBUS" folder and press the "Device identification" button
●
For HART devices:
Select the "HART" folder and then press the "Device identification" button
Additional information
●
Section "Integrating devices into SIMATIC PDM (Page 31)"
7.3.1.4
Integrating a device in HW Config
Below, you will learn how to insert devices in the project using HW Config:
●
Inserting a DP device
●
Inserting a DP remote I/O system (distributed I/O)
●
Inserting a PA device at a DP/PA coupler
●
Inserting a PA device at a DP/PA-Link
●
Inserting a PA remote I/O system (distributed I/O)
●
Inserting a remote I/O system (PROFINET)
Requirement
PROFIBUS DP master system or PROFINET IO system
Options for creating the PROFIBUS DP master system:
●
In HW Config:
If the DP master system is not displayed, select the menu command Insert > Master
system at the required PROFIBUS module.
●
In the process device network view:
–
Open the process device network view in SIMATIC Manager.
–
Double-click the "Networks" object in the right window to insert a PROFIBUS DP
network. Select "Networks" in the left window, and select the menu command Insert
New Object > Object in the shortcut menu.
–
Click the "Assign Device Type" button.
The "Insert object - Assign device type" dialog box opens.
You can find additional information on this in the section ""Insert Object - Assign Device
Type" dialog box (Page 79)".
–
Select the PROFIBUS DP network from the tree structure.
–
Click "OK".
The PROFIBUS DP network is inserted.
Note
Representation in HW Config
Objects created in the process device network view are not displayed in HW Config.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
81
Inserting a DP device
PROFIBUS devices can be inserted directly into the PROFIBUS DP master system.
1. Select the device you require under "PROFIBUS DP" in the hardware catalog and drag it
onto the DP master system.
Inserting a DP remote I/O system (distributed I/O)
Integration is described based on the example of ET 200iSP .
1. Place the head-end station "IM152-1" you have selected from the hardware catalog under
"PROFIBUS DP > ET200iSP" at the DP master system.
The slots of the head-end station are displayed in the detail view in the table below the
graphic.
2. You can insert the required analog and digital modules in slot 4 and higher.
Inserting a PA device at a DP/PA coupler
1. Select a device in the PROFIBUS-PA folder of the hardware catalog.
This can be, for example, a SITRANS P pressure transmitter listed under "PROFIBUS-PA
> Siemens > Sensors > Pressure > SITRANS P" or a device profile listed under "PROFIBUS-
PA > Other".
2. Position it at the PROFIBUS DP master system.
You have to select the device for some objects. You can find information on this in the
section ""Insert Object - Assign Device Type" dialog box (Page 79)".
Note
The DP/PA coupler does not need to be configured; you only need to set an appropriate
bus transmission rate (for example, 45.45 kbps for the Siemens coupler) for the DP master
system.
Inserting a PA device at a DP/PA-Link
1. Place the "IM 153-2" you have selected from the hardware catalog under "PROFIBUS DP
> DP/PA-Link" at the DP master system. (The IM 153-2 replaces the IM 157, but both types
can be used as PROFIBUS-Link ).
HW Config creates a PA master system for the DP/PA-Link .
2. Drag-and-drop the PA devices to this PA master system.
For certain objects it is necessary to select the device. You can find information on this in
the section ""Insert Object - Assign Device Type" dialog box (Page 79)".
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
82
Operating Manual, 02/2014, A5E33203676-AA
Inserting a PA remote I/O system (distributed I/O)
Integration is described based on the Pepperl+Fuchs example.
1. You can find the "RSD-GW-EX1.PA" head-end station in the hardware catalog under
"PROFIBUS-PA\REMOTE I/O\PEPPERL+FUCHS GmbH\ P+F I/O System".
Place the head-end station on the DP master system (with DP/PA coupler, see above) or
on the PA master system (with DP/PA-Link, see above).
The slots of the head-end station are displayed in the detail view in the table below the
graphic.
2. Place one of the modules listed in the hardware catalog under "PROFIBUS-PA > P+F I/
O SYSTEM > RSD-GW-EX1.PA" in a free slot.
Inserting a remote I/O system (PROFINET)
The integration is described using ET 200M as an example.
1. Place the head-end station "IM153-4" you have selected from the hardware catalog under
"PROFINET IO > I/O > ET200M" at the IO system.
2. The slots of the head-end station are displayed in the detail view in the table below the
graphic. You can insert the required analog and digital modules in slot 4 and higher.
7.3.1.5
Setting the bus address in HW Config
Make sure the bus addresses of all field devices are entered correctly in HW Config.
Bus addresses can only be set for field devices on a PROFIBUS network.
Procedure
Proceed as follows to edit the settings:
1. Select a field device in HW Config. In the shortcut menu, select the menu command Object
Properties.
The "Properties - ..." dialog box opens.
2. Click the button for the associated bus system in the "Node/ ...system" area.
The "Properties - ...Interface " dialog box opens.
3. Enter the desired bus address.
HW Config automatically assigns addresses in the order in which objects are created. You
may need to correct these addresses, depending on the device used (refer to the device
manual).
Click the "OK" button to save the address.
4. Click "OK" to close the "Properties - ..." dialog boxes.
5. Save the project with the menu command Station > Save.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
83
Integrating a HART device in a HART modem network
���������������
Figure 7-1
HART modem
The following describes how to integrate a HART device in a HART modem network.
Requirements
●
A project has been created.
●
The device description files (EDD) for planned or already installed field devices are available
in SIMATIC PDM.
●
An access point of the computer is set to the COM port to which the HART modem network
is connected.
Integrating a HART device in a HART modem network
1. Open the project in the process device network view.
2. Right-click the "Networks" object in the tree structure. In the shortcut menu that opens,
select the menu command Insert New Object > Communication network.
The "Insert Object(s) - <...>" dialog box opens.
3. Click the "Assign Device Type" button.
The "Insert Object(s) - Assign Device Type" dialog box opens. You can find additional
information in the section "Insert Object - Assign Device Type" dialog box (Page 79).
4. To set the network properties, select the inserted HART modem network in the right window
and right-click. Select the Object Properties command in the displayed shortcut menu.
5. Enter the device-specific information in the "Communication" tab of the Properties dialog
for the HART modem network.
Set the master type (primary or secondary, usually secondary):
Here, you can select the "Prefer 'Long address'" check box.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
84
Operating Manual, 02/2014, A5E33203676-AA
6. To check if the correct network and the correct port are assigned to the COM interface,
double-click the "PC" object in the right window. Select the "COM interface" object in HW
Config, and select the Object Properties menu command in the shortcut menu.
Note
The COM port is almost always "1" for notebooks. Since most PCs have two COM ports,
you must specify the port to which the HART modem is connected in this tab. Check
whether the settings for the FIFO buffer of the COM port are suitable, or immediately use
a USB HART modem.
7. To insert the HART device, select the "HART modem network" object in the right window
and right-click. In the displayed shortcut menu, select the Insert New Object > Object
command.
In the displayed dialog box, enter the name of the HART device.
8. To set the device address, select the inserted HART device in the right window and right-
click. Select the Object Properties command in the displayed shortcut menu.
9. Enter the device-specific information (long address) in the "Communication" tab of the
Properties dialog for the HART device.
Note
Address with HART
The information must correspond to the connected device.
●
The short address must be entered for HART devices. This address must correspond
to the connected HART device. The short address is always "0", unless the device is
in the multi-drop function.
●
For a HART interface, enter the long address. This address contains the following
device-specific information:
–
Manufacturer
–
Device type
–
Device name
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
85
10.To change the device address, select the inserted HART device in the right window and
then select the Object properties menu command in the shortcut menu. Select the
"Communication" tab in the displayed dialog and enter the new short address.
Note
The address must correspond to the connected device. The short address for HART
devices is always "0" unless the device is in the multi-drop function.
11.Start SIMATIC PDM by double-clicking the newly inserted HART device in the right window.
Select the relevant device in the menu tree (only required for the first call), and assign
parameters for the device.
Note
Multiple PCs in one project
If there are several PCs in your project, you have to define one of them as the current
one. To do this, select the desired "PC" object in the left window and then select the menu
command Options > Define Current PC.
7.3.1.7
Integrating a MODBUS device in a MODBUS network
������
The following paragraph describes how you integrate a MODBUS device in a MODBUS
network.
Requirements
●
A project has been created.
●
The device description files (EDD) for planned or already installed field devices are available
in SIMATIC PDM.
Integrating a MODBUS device in a MODBUS network
1. Open the project in the process device network view.
2. Right-click the "Networks" object in the tree structure. In the shortcut menu that opens,
select the menu command Insert New Object > Communication network.
The "Insert Object(s) - <...>" dialog box opens.
3. Click the "Assign Device Type" button.
The "Insert Object(s) - Assign Device Type" dialog box opens. You can find additional
information in the section "Insert Object - Assign Device Type" dialog box (Page 79).
4. To set the network properties, select the inserted MODBUS network in the right window
and right-click. Select the Object Properties command in the displayed shortcut menu.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
86
Operating Manual, 02/2014, A5E33203676-AA
5. Enter the device-specific information in the "Communication" tab of the Properties dialog
for the MODBUS network.
MODBUS communication type: Serial or IrDA (infrared)
Serial
The interface must be set accordingly on the PC station.
IrDA
No additional setting required.
Once the device is within range, it is available for MODBUS communication.
Only one infrared device can be coupled to MODBUS at a given time. Several devices
can be coupled under Windows.
Response
time
General timeout within which the device is allowed to report. If the timeout is too long, the
communication is slowed. If it is too short, some devices may not be found.
6. To check if the correct network and the correct port are assigned to the COM interface,
double-click the "PC" object in the right window. Select the "COM interface" object in HW
Config, and select the Object Properties menu command in the shortcut menu.
Note
The COM port is almost always "1" for notebooks. Since most PCs have two COM ports,
you have to specify which port the device is connected to in this tab.
7. To insert the MODBUS device, select the "MODBUS network" object in the right window
and right-click. In the displayed shortcut menu, select the Insert New Object > Object
command.
In the displayed dialog box, enter the name of the MODBUS device.
8. To set the device address, select the inserted MODBUS device in the right window and
right-click. Select the Object Properties command in the displayed shortcut menu.
9. Enter the device-specific information (MODBUS address 0-247) in the "Communication"
tab of the Properties dialog for the MODBUS device.
10.To change the device address, select the inserted MODBUS device in the right window
and then select the Object Properties menu command in the shortcut menu. Select the
"Communication" tab in the displayed dialog and enter the new short address.
11.Start SIMATIC PDM by double-clicking the newly inserted MODBUS device in the right
window. Select the relevant device in the menu tree (only required for the first call), and
assign parameters for the device.
Note
Multiple PCs in one project
If there are several PCs in your project, you have to define one of them as the current
one. To do this, select the desired "PC" object in the left window and then select the menu
command Options > Define Current PC.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
87
Integrating a HART server network
You can use SIMATIC PDM to configure HART devices for the following networks:
●
Multiplexer networks
–
Multiplexer network with panel (for example, MTL multiplexer)
–
Multiplexer network without panel (for example, P+F multiplexer)
●
Wireless Hart gateway
You configure a wireless HART gateway as a HART multiplexer.
You need a HART server application in the project to integrate and manage these networks.
You can find detailed information on the HART server in the description or the online help for
this product.
●
You can address multiplexers using the HART server. You can obtain more information
from the device manufacturers.
●
The HART server of SIMATIC PDM does not support multimaster operation. Jobs have to
be coordinated to avoid conflicts. This coordination has to take place on the multiplexer
network level.
Requirement
●
A HART server is installed on the computer.
●
A multiplexer network has been integrated in the HART server.
●
A project has been created in the SIMATIC Manager.
●
The HART network is physically connected to the PC station.
Note
Integrating a HART multiplexer network
In the HART server, a project has to be created for the multiplexer in order for the
configuration data of the multiplex to be available in the process device network view.
Starting the HART server application
Note
HART server
The HART server application should always be open before you configure or integrate HART
devices.
You have the following options for starting the HART server application:
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
88
Operating Manual, 02/2014, A5E33203676-AA
In SIMATIC Manager, select the menu command Options > SIMATIC PDM > HART server.
●
In the Windows taskbar, select the menu command Start > Programs > HART server >
HART server (path of the HART server created by SIMATIC PDM setup).
Note
Network address of the HART multiplexer
Enter the network address of the HART multiplexer in the HART server application when
you create an I/O system in the HART network.
Starting the HART server application for the first time
To configure communication between SIMATIC PDM and the HART server, proceed as follows:
1. Select the HART server project. Select the menu command File > Preferences.
The "HART Server Preferences" dialog box opens.
2. In the "New Configuration Will Use" section, select the check box according to your settings
in SIMATIC PDM.
3. Apply this setting also to the existing project, if required. After it has been applied to an
existing project, the devices must be read in again with "Learn".
Note
SIMATIC PDM default settings
The default settings for HART communication in SIMATIC PDM correspond to the "8 char
(HART 5), 32 char (HART 6 +)" check box.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
89
Configuring the HART server
1. Select the HART server project. Right-click and select the shortcut menu command Add
Network. In the dialog box that opens, select the type of network through which the objects
are connected:
–
Single Port RS485
–
Single Serial Port
–
TCP/UDP
2. Enter a name in the "Network Properties" field.
SIMATIC Manager later identifies the network based on this name.
Set the properties of the interface under "Properties" and confirm your entries with "OK".
The network is inserted in the project.
Note
TAG names
Ensure that the TAG names of the components do not contain a "." (dot) character.
3. You can read in the multiplexer data automatically or configure them manually.
–
Automatic reading:
Select the higher-level object. Right-click and select the shortcut menu command Learn.
All data (multiplexers and devices) of the selected object are read out. A dialog box
indicates the progress.
While the addresses (multiplexer, etc.) are being checked, the status of all assigned
addresses changes from "not responding" to "responding". If this does not happen, there
is a connection error, such as incorrect polarity.
Note
Learning process in a HART server project
You can start the learning process on any level.
●
When you select a network, you start the learning process for the entire
configuration tree.
●
If you select a panel, you start the learning process for the selected partial
configuration, meaning for the instruments below the panel level.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
90
Operating Manual, 02/2014, A5E33203676-AA
Example 1: HART server project with serial multiplexers
Figure 7-3
Example 2: HART server project with wireless HART gateway
–
Manual configuration:
If you want to create the configuration manually, select the project, followed by the
shortcut menu command Add Device (or Add IO-System for Ethernet networks). Enter
the required information in the dialog box.
Continue this procedure until all the devices have been configured.
The HART server immediately checks whether a HART multiplexer is available at the
selected address: If a HART multiplexer is reached, its properties are displayed.
Otherwise, a message is generated indicating that no connection could be established.
HART multiplexer with panel: Configure the address information for the panel before
you configure the HART devices.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
91
Inserting a HART server in a multiplexer network
1. Check whether the HART server is started.
2. Open the project in the process device network view.
3. Right-click and select the following shortcut menu command: Insert New Object >
Communication network.
The "Insert Object - " dialog box opens.
4. Click the button "Assign Device Type" > Object.
The "Insert Object - " dialog box opens. Select "HART server" as the network
type and click the "Assign Device Type" button.
5. Select the following shortcut menu command: SIMATIC PDM > Synchronize.
If you select the "Object with all subordinate objects and networks" option, all devices and
multiplexers detected in the HART server are automatically applied to the project.
The hierarchy is transferred to the SIMATIC Manager. The levels displayed in the SIMATIC
Manager depend on the selected multiplexer (e.g. single-stage or two-stage).
6. In the process device network view of SIMATIC Manager, insert the HART server in the
HART multiplexer network and edit the individual devices.
Configuring the devices
Note the following:
●
You can start a learning process for identification of the devices on the multiplexer and
assign the device description files (EDD) automatically.
●
You can manually configure the multiplexer and the devices. For this purpose, the devices
and the computer must be connected and the device names and addresses must be known.
Changing the configuration
If, for example, you change an existing multiplexer network by inserting a new device or
replacing a device (must be followed by reconfiguration in the HART server), you can compare
the changes in the HART server with the menu command Edit > SIMATIC PDM >
Synchronize. The comparative function takes the following into consideration:
●
New hierarchy and devices are inserted.
●
Hierarchies and devices that no longer exist are removed.
●
Renamed devices are also renamed in PDM.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
92
Operating Manual, 02/2014, A5E33203676-AA
Wireless HART device on a Wireless HART gateway
Wireless HART devices are integrated into HART multiplexer networks the same way as HART
devices.
IE/WSN-
PA LINK
SITRANS
AW210
SITRANS
AW200
SITRANS
AW210
SITRANS
TF280
SITRANS
P280
Wireless
HART
PDM
Ethernet
Renaming devices downstream from a HART server project
If you want to rename a device on a HART multiplexer, observe the order in which the actions
must be performed:
1. Open the device with SIMATIC PDM.
2. Enter new TAG in PDM.
3. Select the following shortcut menu command: SIMATIC PDM > Download to device...
4. Save in PDM
Saving automatically applies the changes to the HART server.
Additional information
Information on configuring the HART server application supplied with PDM can be found in
the online help HART Server Help(Start > Programs > HART Server > HART Server Help).
For information on the structure, configuration, and commissioning of wireless HART devices
on an IE/WSN PA link (WSN-PA Link link), refer to the following documentation:
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
93
Operating instructions titled SIMATIC NET; IE/WSN PA Link
●
Operating instructions titled SIMATIC NET; IE/WSN PA Link (Compact)
7.3.1.9
Compact PROFIBUS device (sensors and actuators)
Procedure
To integrate a PROFIBUS device (PROFIBUS DP device, PROFIBUS PA device or
PROFIBUS remote I/O), proceed as follows:
�����������
�����������
�����������
�����������
�����������
�����������
��������
Creating a network
1. Open the process device network view in SIMATIC Manager.
2. Select the "Networks" folder in the tree structure in the left window and select the Insert
New Object > Object command from the shortcut menu.
The "Insert Object" dialog box opens.
3. Click the "Assign Device Type" button.
Inserting a PROFIBUS device or remote I/O
Follow the steps below to insert objects into higher-level objects one after the other.
Higher-level object
Object to be inserted
"Networks" folder
Type of network via which the field devices are connected
to the automation system (e.g., PROFIBUS DP network).
PROFIBUS DP network
PROFIBUS DP device / PROFIBUS PA device
Header module (selection: remote I/O)
Modules (selection: module)
Modules (selection: module)
Field device (selection: HART device)
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
94
Operating Manual, 02/2014, A5E33203676-AA
1. Select the higher-level object in the tree structure in the window on the right.
2. In the shortcut menu, select the menu command Insert New Object > Object.
The dialog box "<... SIMATIC PDM – Insert Object(s)" opens.
3. In the dialog box that opens, enter the name of the process tag.
Note
Configure the PROFIBUS PA devices directly on the PROFIBUS network if you are using
a PROFIBUS DP/PA coupler. The coupler itself is not configured (the DP/PA couplers
with diagnostic capability as of 6ES7157-0AC84-0XA0 can be configured as a stand-alone
device).
4. Alternatively, you can add a PROFIBUS-Link (Y-Link or DP/PA-Link) to a PROFIBUS DP
network. Downstream of the PROFIBUS-Link , you can then insert PROFIBUS devices,
but not another PROFIBUS-Link .
Note
The address of the PROFIBUS device that you set in the "Insert SIMATIC PDM Object(s)"
dialog box can be changed afterwards on the "Communication" tab of the "Object
Properties" dialog box.
Configuring devices with SIMATIC PDM
1. Select the inserted PROFIBUS device in the process device network view.
2. Select the Open object command in the shortcut menu.
SIMATIC PDM opens. The PROFIBUS device is shown in the structure view.
3. Set the required parameters for the function in the parameter table.
4. Make the necessary settings and save the object.
7.3.1.10
Modular PROFIBUS device (remote I/O)
Creating a network
1. Open the process device network view in SIMATIC Manager.
2. Double-click the "Networks" object in the right window to insert a PROFIBUS DP network.
Select the "Networks" folder in the left window, and select the Insert New Object >
Communications Network command in the shortcut menu.
The "Insert Object(s) - <...>" dialog box opens.
3. Click the "Assign device type" button.
The "Insert Object - Assign Device Type" dialog box opens.
You can find additional information on this in the section ""Insert Object - Assign Device
Type" dialog box (Page 79)".
4. Select the PROFIBUS DP network from the tree structure.
5. Click "OK".
The PROFIBUS DP network is inserted.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
95
Adding remote I/O, module, and PROFIBUS device
Follow the steps below to insert objects into higher-level objects one after the other.
Higher-level object
Object to be inserted
PROFIBUS DP network
Header module (selection: remote I/O)
Header module (selection: remote I/O)
Modules (selection: module)
Modules (selection: module)
Field device (selection: PROFIBUS device)
1. Select the higher-level object in the tree structure in the window on the left.
2. In the shortcut menu, select the menu command Insert New Object > Object.
The "Insert Object(s) - <...>" dialog box opens.
3. Make the following settings for the inserted object.
You can find additional information on this in the section "Inserting objects (Page 77)".
4. Select the object. Select the Object properties command in the shortcut menu.
The "Properties - " dialog box opens.
5. Select the "Communication" tab.
6. Make the necessary settings depending on the inserted object in the input fields:
–
Remote I/O: Enter the PROFIBUS address.
–
Module (device module): Enter the slot.
–
PROFIBUS devices: Do not make changes to the channel settings.
7. Repeat these steps until all remote I/O, modules, and PROFIBUS devices have been added.
Configuring devices with SIMATIC PDM
1. Select the PROFIBUS DP network in the process device network view, which is of a higher
level than the added PROFIBUS devices.
2. Select the Open object command in the shortcut menu.
SIMATIC PDM opens. The PROFIBUS DP network is represented in the structure view.
You can find the remote I/O, modules, and PROFIBUS devices by opening the tree
structure.
3. Assign a function individually to the added objects (corresponding with the actual
configuration in HW Config and the connected equipment):
–
Open the object by selecting its icon in the structure view.
–
Select the parameters required for the function in the parameter table.
Make the required settings and save the object.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
96
Operating Manual, 02/2014, A5E33203676-AA
To transfer the configuration and parameters, select the "" object and then select
the Device > Upload to PC/PG... menu command.
Note
The automatic detection of the depends on the type of , the
, and the device description.
7.3.1.11
Connecting a field device to PROFINET
To integrate distributed I/O devices (e.g., ET 200M) or links for connecting intelligent DP or
PA field devices (e.g., IE/PB link) via PROFINET, follow these steps:
Creating a network
1. Open the process device network view in SIMATIC Manager.
2. Select the "Networks" folder in the tree structure in the left window and select the Insert
New Object > Object command from the shortcut menu.
The "Insert Object" dialog box opens.
3. Click the "Assign Device Type" button.
Inserting a field device or remote I/O
Follow the steps below to insert objects into higher-level objects one after the other.
Higher-level object
Object to be inserted
"Networks" folder
Type of network via which the field devices are connected
to the automation system (e.g., PROFINET network).
PROFINET network
Header module (selection: remote I/O)
Header module (selection: remote I/O)
Modules (selection: module)
Modules (selection: module)
Field device (selection:HART device)
1. Select the higher-level object in the tree structure in the window on the right.
2. In the shortcut menu, select the menu command Insert New Object > Object.
The dialog box "<... SIMATIC PDM – Insert Object(s)" opens.
3. In the dialog box that opens, enter the name of the process tag.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
97
Alternatively, you can add a IE/PB-Link to a PROFINET network. Downstream of the IE/PB-
Link , you can then insert PROFIBUS devices. IE/PB-Links are only supported in HW Config
in V8.0.
Note
The address of the PROFINET device that you set in the "Insert SIMATIC PDM Object(s)"
dialog box can be changed afterwards on the "Communication" tab of the "Object Properties"
dialog box.
Network topology
�����������
�����������
�����������
��������
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
98
Operating Manual, 02/2014, A5E33203676-AA
Configuring devices with SIMATIC PDM
1. Select the inserted PROFINET device in the process device network view.
2. Select the Open Object command from the shortcut menu.
SIMATIC PDM opens and the PROFINET device is shown in the structure view.
3. Set the required parameters for the function in the parameter table.
4. Make the necessary settings and save the object.
7.3.1.12
HART device on remote I/O
You can connect the HART devices to a suitable remote I/O module.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
99
Remote I/O with HART devices (PROFIBUS DP)
�����������
��������
Creating the PDM basic folder called "Networks"
1. Open the process device network view in SIMATIC Manager.
2. If the "Networks" object has not been inserted in the tree structure, select the menu
command Insert New Object and select the "Networks" object.
Note
PDM basic folder called "Networks"
SIMATIC PDM licenses must be available in the project when this folder is created.
Creating a communications network
1. Open the process device network view in SIMATIC Manager.
2. Select the "Networks" folder in the tree structure in the left window and select the Insert
New Object > Object command from the shortcut menu.
The "Insert Object - <...>" dialog box opens.
3. Click the "Assign Device Type" button.
Inserting an object (creating a communications network; remote I/O, module, and HART device)
Follow the steps below to insert objects into higher-level objects one after the other.
Higher-level object
Object to be inserted
"Networks" folder
Type of network via which the field devices are connected
to the automation system (e.g., PROFIBUS DP network or
PROFINET).
PROFIBUS DP network
Header module (selection: remote I/O)
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
100
Operating Manual, 02/2014, A5E33203676-AA