Siemens SINAMICS S120 Function Manual
Read Online
Read the Siemens SINAMICS S120 Function Manual online using the built-in PDF viewer.
Text of the manual
Valid from: Firmware Version 4.4 SP1
(FHS), 07/2016
6SL3097-4AR00-0BP6
Preface
Fundamental safety
instructions
1
General information about
SINAMICS Safety Integrated
2
Overview of Safety
Integrated functions
3
Description of Safety
Integrated functions
4
Control of the safety
functions
5
Commissioning
6
Acceptance test
7
System features
8
Maintenance
9
Standards and regulations
10
Appendix
A
Division Digital Factory
Postfach 48 48
90026 NÜRNBERG
GERMANY
Document order number: 6SL3097-4AR00-0BP6
Ⓟ 06/2016 Subject to change
Copyright © Siemens AG 2008 - 2016.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury m ay result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
5
Preface
SINAMICS documentation
The SINAMICS documentation is organized in the following categories:
● General documentation/catalogs
● User documentation
● Manufacturer/service documentation
Additional information
You can find information on the following topics at the following address
(https://support.industry.siemens.com/cs/de/en/view/108993276):
● Ordering documentation/overview of documentation
● Additional links to download documents
● Using documentation online (find and search in manuals/information)
Please send any questions about the technical documentation (e.g. suggestions for
improvement, corrections) to the following e-mail address
(mailto:[email protected]).
Siemens MySupport/Documentation
At the following address (https://support.industry.siemens.com/My/ww/en/documentation),
you can find information on how to create your own individual documentation based on
Siemens' content, and adapt it for your own machine documentation.
Training
At the following address (http://www.siemens.com/sitrain), you can find information about
SITRAIN (Siemens training on products, systems and solutions for automation and drives).
FAQs
You can find Frequently Asked Questions in the Service&Support pages under Product
Support (https://support.industry.siemens.com/cs/de/en/ps/faq).
SINAMICS
You can find information about SINAMICS at the following address
(http://www.siemens.com/sinamics).
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Usage phases and their documents/tools (as an example)
Table 1
Usage phases and the available documents/tools
Usage phase
Document/tool
Orientation
SINAMICS S Sales Documentation
Planning/configuration
•
SIZER Engineering Tool
•
Configuration Manuals, Motors
Deciding/ordering
SINAMICS S120 catalogs
•
SIMOTION, SINAMICS S120 and Motors for Production Machines (Catalog PM 21)
•
SINAMICS and Motors for Single-axis Drives (Catalog D 31)
•
SINUMERIK & SINAMICS
Equipment for Machine Tools (Catalog NC 61)
•
SINUMERIK 840D sl Type 1B
Equipment for Machine Tools (Catalog NC 62)
Installation/assembly
•
SINAMICS S120 Manual for Control Units and Additional System Components
•
SINAMICS S120 Manual for Booksize Power Units
•
SINAMICS S120 Manual for Booksize Power Units C/D Type
•
SINAMICS S120 Manual for Chassis Power Units, Air-cooled
•
SINAMICS S120 Manual for Chassis Power Units, Liquid-cooled
•
SINAMICS S120 Manual for AC Drives
•
SINAMICS S120 Manual Combi
•
SINAMICS S120M Manual Distributed Drive Technology
•
SINAMICS HLA System Manual Hydraulic Drive
Commissioning
•
STARTER Commissioning Tool
•
SINAMICS S120 Getting Started with STARTER
•
SINAMICS S120 Commissioning Manual with STARTER
•
SINAMICS S120 CANopen Commissioning Manual
•
SINAMICS S120 Function Manual Drive Functions
•
SINAMICS S120 Safety Integrated Function Manual
•
SINAMICS S120/S150 List Manual
•
SINAMICS HLA System Manual Hydraulic Drive
•
Startdrive commissioning tool1)
•
SINAMICS S120 Getting Started with Startdrive1)
•
SINAMICS S120 Commissioning Manual with Startdrive1)
Usage/operation
•
SINAMICS S120 Commissioning Manual with STARTER
•
SINAMICS S120/S150 List Manual
•
SINAMICS HLA System Manual Hydraulic Drive
•
SINAMICS S120 Commissioning Manual with Startdrive1)
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
7
Usage phase
Document/tool
Maintenance/servicing
•
SINAMICS S120 Commissioning Manual with STARTER
•
SINAMICS S120/S150 List Manual
•
SINAMICS S120 Commissioning Manual with Startdrive1)
References
•
SINAMICS S120/S150 List Manual
1) available as of Startdrive V14 release
Target group
This documentation is intended for machine manufacturers, commissioning engineers, and
service personnel who use the SINAMICS drive system.
Benefits
This manual provides all of the information, procedures and operator actions required for the
particular usage phase.
Standard scope
The scope of the functionality described in this document can differ from that of the drive
system that is actually supplied.
● Other functions not described in this documentation might be able to be executed in the
drive system. However, no claim can be made regarding the availability of these functions
when the equipment is first supplied or in the event of service.
● The documentation can also contain descriptions of functions that are not available in a
particular product version of the drive system. The functionality of the supplied drive
system should only be taken from the ordering documentation.
● Extensions or changes made by the machine manufacturer must be documented by the
machine manufacturer.
For reasons of clarity, this documentation does not contain all of the detailed information on
all of the product types, and cannot take into consideration every conceivable type of
installation, operation and service/maintenance.
Technical Support
Country-specific telephone numbers for technical support are provided in the Internet at the
following address (https://support.industry.siemens.com/sc/ww/en/sc/2090) in the "Contact"
area.
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Notation
The following notation and abbreviations are used in this documentation:
Notation for faults and alarms (examples):
• F12345
Fault 12345
• A67890
Alarm 67890
• C23456
Safety message
Notation for parameters (examples):
• p0918
Adjustable parameter 918
• r1024
Display parameter 1024
• p1070[1]
Adjustable parameter 1070, index 1
• p2098[1].3
Adjustable parameter 2098, index 1 bit 3
• p0099[0...3]
Adjustable parameter 99, indices 0 to 3
• r0945[2](3)
Display parameter 945, index 2 of drive object 3
• p0795.4
Adjustable parameter 795, bit 4
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
9
Table of Contents
Preface................................................................................................................. 5
1
Fundamental safety instructions ................................................................................... 15
1.1
Fundamental safety instructions ..................................................................................... 15
1.1.1
General safety instructions ............................................................................................. 15
1.1.2
Industrial security .......................................................................................................... 16
1.2
Fundamental safety instructions for Safety Integrated ...................................................... 17
1.3
Residual risk ................................................................................................................. 21
2
General information about SINAMICS Safety Integrated ....................................................... 23
2.1
Drive products with integrated safety functions ................................................................ 23
2.2
Supported functions....................................................................................................... 24
2.3
Supported functions: HLA module................................................................................... 27
2.4
Examples of how the safety functions can be applied....................................................... 30
2.5
Drive monitoring with or without encoder ......................................................................... 32
3
Overview of Safety Integrated functions .......................................................................... 33
3.1
Safety Integrated Basic Functions................................................................................... 33
3.1.1
Safe Torque Off (STO)................................................................................................... 34
3.1.2
Safe Stop 1 (SS1) ......................................................................................................... 35
3.1.3
Safe Brake Control (SBC) .............................................................................................. 36
3.1.3.1
Hardware required for SBC ............................................................................................ 37
3.2
Safety Integrated Extended Functions............................................................................. 39
3.2.1
Preconditions for the Safety Extended Functions ............................................................. 39
3.2.2
Control possibilities........................................................................................................ 40
3.2.3
Safe Torque Off (STO)................................................................................................... 40
3.2.4
Safe Stop 1 (SS1) ......................................................................................................... 40
3.2.5
Safe Operating Stop (SOS) ............................................................................................ 43
3.2.6
Safe Stop 2 (SS2) ......................................................................................................... 45
3.2.6.1
How does SS2 function in detail? ................................................................................... 45
3.2.7
Safely Limited Speed (SLS) ........................................................................................... 47
3.2.8
Safe Speed Monitor (SSM)............................................................................................. 53
3.2.9
Safe Direction (SDI)....................................................................................................... 55
3.2.10
Safely-Limited Position (SLP) ......................................................................................... 57
3.2.11
Safe referencing ............................................................................................................ 58
3.2.12
Transferring safe position values (SP)............................................................................. 59
3.2.13
Safe Brake Test ............................................................................................................ 60
4
Description of Safety Integrated functions ........................................................................ 61
4.1
Safety Integrated basic functions .................................................................................... 62
4.1.1
Safe Torque Off (STO)................................................................................................... 62
4.1.1.1
Safe Torque Off (STO) for SINAMICS HLA ..................................................................... 66
Table of Contents
Safety Integrated
10
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1.2
Safe Stop 1 (SS1, time controlled)...................................................................................68
4.1.2.1
SS1 with OFF3...............................................................................................................68
4.1.2.2
SS1 with external stop ....................................................................................................69
4.1.2.3
Function diagrams and parameters .................................................................................70
4.1.3
Safe Brake Control (SBC) ...............................................................................................71
4.1.3.1
SBC for Motor Modules in the chassis format ...................................................................73
4.1.3.2
Function diagrams and parameters .................................................................................75
4.1.4
Safety faults ...................................................................................................................76
4.1.5
Forced dormant error detection (test stop) .......................................................................78
4.1.6
Function diagrams and parameters .................................................................................79
4.2
Safety Integrated Extended Functions .............................................................................80
4.2.1
License for Extended Functions ......................................................................................80
4.2.2
Differences between Extended Functions "with encoder" and "without encoder" .................80
4.2.3
Restrictions for Safety Integrated Functions "without encoder" ..........................................82
4.2.4
Safe Torque Off (STO) ...................................................................................................86
4.2.5
Safe Stop 1 (SS1) ..........................................................................................................87
4.2.5.1
Safe Stop 1 with encoder ................................................................................................87
4.2.5.2
Safe Stop 1 without encoder ...........................................................................................89
4.2.5.3
Safe Stop 1 with external stop .........................................................................................90
4.2.5.4
Function diagrams and parameters .................................................................................91
4.2.6
Safe Brake Control (SBC) ...............................................................................................91
4.2.7
Safe Operating Stop (SOS).............................................................................................92
4.2.8
Safe Stop 2 (SS2) ..........................................................................................................94
4.2.8.1
Interaction with EPOS.....................................................................................................95
4.2.8.2
SS2 with external stop (SS2E) ........................................................................................96
4.2.8.3
Overview of important parameters ...................................................................................98
4.2.9
Safely-Limited Speed (SLS) ............................................................................................99
4.2.9.1
Safely Limited Speed (SLS) .......................................................................................... 100
4.2.9.2
Safely Limited Speed without encoder ........................................................................... 103
4.2.9.3
Safely-Limited Speed without selection .......................................................................... 105
4.2.9.4
Function diagrams and parameters ............................................................................... 106
4.2.9.5
EPOS and safe setpoint velocity limitation ..................................................................... 107
4.2.10
Safe Speed Monitor (SSM) ........................................................................................... 108
4.2.10.1
Safe Speed Monitor with encoder .................................................................................. 109
4.2.10.2
Safe Speed Monitor without encoder ............................................................................. 111
4.2.10.3
Function diagrams and parameters ............................................................................... 114
4.2.11
Safe Direction (SDI) ..................................................................................................... 115
4.2.11.1
Safe Direction with encoder .......................................................................................... 115
4.2.11.2
Safe Direction without encoder...................................................................................... 117
4.2.11.3
Safe Direction without selection..................................................................................... 119
4.2.11.4
Function diagrams and parameters ............................................................................... 120
4.2.12
Safely-Limited Position (SLP) ........................................................................................ 121
4.2.12.1
Retraction .................................................................................................................... 124
4.2.12.2
Function diagrams and parameters ............................................................................... 126
4.2.13
Safe referencing........................................................................................................... 127
4.2.14
Transferring safe position values (SP) ........................................................................... 129
4.2.15
Safe Brake Test (SBT).................................................................................................. 132
4.2.15.1
Communication via SIC/SCC ........................................................................................ 139
4.2.15.2
Function diagrams and parameters ............................................................................... 141
4.2.16
Safe Acceleration Monitor (SAM)................................................................................... 142
4.2.17
Safe Brake Ramp (SBR) ............................................................................................... 144
Table of Contents
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
11
4.2.18
Safe actual value acquisition .........................................................................................147
4.2.18.1
Notes regarding safe actual value sensing using an encoder system ...............................147
4.2.18.2
Notes regarding setting parameters for safe actual value sensing without encoder ...........154
4.2.19
Safe gearbox stage switchover ......................................................................................157
4.2.20
Forced dormant error detection (test stop)......................................................................160
5
Control of the safety functions ................................................................................... 167
5.1
Control possibilities.......................................................................................................167
5.2
Control signals by way of terminals on the Control Unit and Motor / Power Module ...........168
5.2.1
Simultaneity and tolerance time of the two monitoring channels.......................................171
5.2.2
Bit pattern test ..............................................................................................................173
5.3
Activation via PROFIsafe ..............................................................................................174
5.3.1
Enabling of the control via PROFIsafe............................................................................175
5.3.2
Selecting a PROFIsafe telegram....................................................................................176
5.3.3
Telegram format ...........................................................................................................177
5.3.4
Process data ................................................................................................................179
5.3.4.1
S_STW1 and S_ZSW1 (Basic Functions) .......................................................................179
5.3.4.2
S_STW2 and S_ZSW2 (Basic Functions) .......................................................................181
5.3.4.3
S_STW1 and S_ZSW1 (Extended Functions) .................................................................183
5.3.4.4
S_STW2 and S_ZSW2 (Extended Functions) .................................................................185
5.3.4.5
Additional process data.................................................................................................188
5.3.5
Function diagrams and parameters................................................................................189
5.4
Control via TM54F ........................................................................................................190
5.4.1
Fault acknowledgment ..................................................................................................191
5.4.2
Overview of the F-DIs ...................................................................................................191
5.4.3
Overview of the F-DOs .................................................................................................193
5.5
Response for a communication failure via PROFIsafe or to the TM54F ............................196
5.5.1
STOP B as response to communication failure with PROFIsafe control ............................196
5.5.2
Initiating ESR for a communication failure ......................................................................197
5.6
Control of the Extended Functions via F-DI (for CU310-2) ...............................................199
5.6.1
Overview of the F-DIs ...................................................................................................200
5.6.2
Function of the F-DO ....................................................................................................202
5.7
Motion monitoring without selection ...............................................................................205
5.8
Safety Info Channel and Safety Control Channel ............................................................207
5.8.1
Safety Info Channel (SIC) .............................................................................................207
5.8.2
Safety Control Channel (SCC).......................................................................................207
5.8.3
Possible telegram configuration (700, 701).....................................................................207
5.8.4
Configuring ..................................................................................................................209
5.8.5
Applications .................................................................................................................210
5.8.6
Send data for SIC and SCC ..........................................................................................213
5.8.7
Receive data for SCC ...................................................................................................216
5.8.8
Overview of important parameters .................................................................................217
6
Commissioning..................................................................................................... 219
6.1
Safety Integrated firmware versions ...............................................................................219
6.2
Parameters, checksum, version.....................................................................................220
6.3
Handling the Safety password .......................................................................................222
Table of Contents
Safety Integrated
12
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
6.4
DRIVE-CLiQ rules for Safety Integrated Functions.......................................................... 224
6.5
Forced dormant error detection (test stop) ..................................................................... 226
6.6
Commissioning Safety Integrated functions.................................................................... 229
6.6.1
General information ...................................................................................................... 229
6.6.2
Prerequisites for commissioning the Safety Integrated functions...................................... 231
6.6.3
Default settings for commissioning Safety Integrated functions without encoder ............... 232
6.6.4
Setting the sampling times ............................................................................................ 236
6.7
Commissioning: Basic procedure .................................................................................. 238
6.7.1
Basic Functions............................................................................................................ 238
6.7.1.1
Commissioning via direct parameter access................................................................... 238
6.7.1.2
Commissioning with STARTER ..................................................................................... 240
6.7.2
Commissioning of the Extended Functions with STARTER ............................................. 246
6.7.2.1
Extended Functions with encoder .................................................................................. 247
6.7.2.2
Extended Functions without encoder ............................................................................. 266
6.8
Commissioning CU310-2 using STARTER/SCOUT ........................................................ 282
6.8.1
Configuration start screen ............................................................................................. 283
6.8.2
F-DI/F-DO configuration................................................................................................ 284
6.8.3
Control interface of the drive ......................................................................................... 287
6.8.4
Forced dormant error detection (test stop) of the CU310-2 .............................................. 288
6.8.4.1
Test mode 1: Evaluation of internal diagnostic signal (passive load) ................................ 290
6.8.4.2
Test mode 2: Read back F-DO in DI (relay circuit) .......................................................... 291
6.8.4.3
Test mode 3: Read back F-DO into the DI (actuator with feedback signal) ....................... 292
6.8.4.4
Test stop mode parameters .......................................................................................... 293
6.9
Commissioning TM54F by means of STARTER/SCOUT................................................. 294
6.9.1
Basic sequence of commissioning ................................................................................. 294
6.9.2
Configuration start screen ............................................................................................. 295
6.9.3
Function diagrams and parameters ............................................................................... 296
6.9.4
TM54F configuration..................................................................................................... 297
6.9.5
F-DI/F-DO configuration................................................................................................ 300
6.9.6
Control interface of the drive group ................................................................................ 303
6.9.7
Forced dormant error detection (test stop) of the TM54F................................................. 305
6.9.7.1
Test mode 1: Evaluation of internal diagnostic signal (passive load) ................................ 307
6.9.7.2
Test mode 2: Read back F-DO in DI (relay circuit) .......................................................... 308
6.9.7.3
Test mode 3: Read back F-DO into the DI (actuator with feedback signal) ....................... 309
6.9.7.4
Parameter forced dormant error detection (test stop) ...................................................... 310
6.10
PROFIsafe communication ........................................................................................... 311
6.10.1
PROFIsafe via PROFIBUS ........................................................................................... 312
6.10.1.1
Configuring PROFIsafe via PROFIBUS ......................................................................... 312
6.10.2
PROFIsafe via PROFINET............................................................................................ 322
6.10.2.1
Assigning the IP address and the name ......................................................................... 322
6.10.2.2
Configuring PROFIsafe via PROFINET.......................................................................... 322
6.10.3
PROFIsafe configuration with STARTER ....................................................................... 330
6.10.3.1
Selecting a PROFIsafe telegram ................................................................................... 331
6.11
Commissioning a linear/rotary axis ................................................................................ 333
6.12
Modular machine concept Safety Integrated................................................................... 335
6.13
Information pertaining to series commissioning .............................................................. 336
6.14
Application examples.................................................................................................... 338
Table of Contents
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
13
7
Acceptance test .................................................................................................... 341
7.1
General information about the acceptance test ...............................................................344
7.2
Safety logbook .............................................................................................................346
8
System features.................................................................................................... 347
8.1
Latest information .........................................................................................................347
8.2
Certification ..................................................................................................................349
8.3
Probability of failure of the safety functions (PFH value) ..................................................350
8.4
Response times ...........................................................................................................351
8.4.1
Control of Basic Functions via terminals on the Control Unit and Motor Module
(CU310-2 and CU320-2) ...............................................................................................352
8.4.2
Control of Basic Functions via PROFIsafe (CU310-2 and CU320-2).................................353
8.4.3
Control of Basic Functions via TM54F ............................................................................354
8.4.4
Control of Extended Functions with encoder via PROFIsafe (CU310-2 and CU320-2) .......355
8.4.5
Control of Extended Functions with encoder via TM54F (CU310-2 and CU320-2).............356
8.4.6
Control of Extended Functions with encoder via terminals (only CU310-2) .......................357
8.4.7
Control of Extended Functions without encoder via PROFIsafe (CU310-2 and
CU320-2) .....................................................................................................................358
8.4.8
Control of Extended Functions without encoder via terminals (only CU310-2) ...................359
8.4.9
Control of Extended Functions without encoder via TM54F (CU310-2 and CU320-2) ........360
9
Maintenance........................................................................................................ 361
9.1
Information pertaining to component replacements .........................................................361
9.2
Note regarding firmware update ....................................................................................364
9.3
Safety faults .................................................................................................................365
9.3.1
Stop responses ............................................................................................................365
9.3.2
Stop response priorities ................................................................................................368
9.3.3
Acknowledging safety faults ..........................................................................................370
9.4
Message buffer ............................................................................................................371
10
Standards and regulations........................................................................................ 373
10.1
General information ......................................................................................................373
10.1.1
Aims ............................................................................................................................373
10.1.2
Functional safety ..........................................................................................................374
10.2
Safety of machinery in Europe.......................................................................................375
10.2.1
Machinery Directive ......................................................................................................375
10.2.2
Harmonized European Standards ..................................................................................376
10.2.3
Standards for implementing safety-related controllers .....................................................377
10.2.4
DIN EN ISO 13849-1 (replaces EN 954-1) .....................................................................379
10.2.5
EN 62061.....................................................................................................................380
10.2.6
Series of standards IEC 61508 (VDE 0803)....................................................................381
10.2.7
Risk analysis/assessment .............................................................................................382
10.2.8
Risk reduction ..............................................................................................................384
10.2.9
Residual risk ................................................................................................................384
10.2.10
EC declaration of conformity .........................................................................................384
Table of Contents
Safety Integrated
14
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
10.3
Machine safety in the USA ............................................................................................ 385
10.3.1
Minimum requirements of the OSHA.............................................................................. 385
10.3.2
NRTL listing ................................................................................................................. 385
10.3.3
NFPA 79...................................................................................................................... 386
10.3.4
ANSI B11 .................................................................................................................... 386
10.4
Machine safety in Japan ............................................................................................... 387
10.5
Equipment regulations .................................................................................................. 388
10.6
Other safety-related issues ........................................................................................... 389
10.6.1
Information sheets issued by the Employer's Liability Insurance Association .................... 389
10.6.2
Additional references .................................................................................................... 389
A
Appendix ........................................................................................................... 391
A.1
List of abbreviations ..................................................................................................... 391
A.2
Documentation overview............................................................................................... 401
A.3
Acceptance tests (recommendations) ............................................................................ 403
A.3.1
Contents and depth of the acceptance test .................................................................... 403
A.3.1.1
Content of the complete acceptance test ....................................................................... 403
A.3.1.2
Content of the partial acceptance test ............................................................................ 405
A.3.1.3
Test scope for specific measures .................................................................................. 407
A.3.1.4
Relevant checksums for the acceptance ........................................................................ 408
A.3.2
Acceptance reports ...................................................................................................... 409
A.3.2.1
Plant description - Documentation part 1........................................................................ 409
A.3.2.2
Description of safety functions - Documentation Part 2 ................................................... 411
A.3.3
Acceptance tests.......................................................................................................... 420
A.3.3.1
Acceptance tests – Basic Functions............................................................................... 422
A.3.3.2
Acceptance tests for Extended Functions (with encoder) ................................................ 426
A.3.3.3
Acceptance tests for Extended Functions (without encoder) ............................................ 481
A.3.3.4
Acceptance test for the transfer of F-DIs via PROFIsafe ................................................. 504
A.3.4
Completion of certificate ............................................................................................... 505
A.4
Stop variants................................................................................................................ 507
Index ................................................................................................................ 509
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
15
Fundamental safety instructions
1
1.1
Fundamental safety instructions
1.1.1
General safety instructions
WARNING
Danger to life if the safety instructions and residual risks are not observed
If the safety instructions and residual risks in the associated hardware documentation are
not observed, accidents involving severe injuries or death can occur.
• Observe the safety instructions given in the hardware documentation.
• Consider the residual risks for the risk evaluation.
WARNING
Danger to life or malfunctions of the machine as a result of incorrect or changed
parameterization
As a result of incorrect or changed parameterization, machines can malfunction, which in
turn can lead to injuries or death.
• Protect the parameterization (parameter assignments) against unauthorized access.
• Respond to possible malfunctions by applying suitable measures (e.g. EMERGENCY
STOP or EMERGENCY OFF).
Fundamental safety instructions
1.1 Fundamental safety instructions
Safety Integrated
16
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
1.1.2
Industrial security
Note
Industrial security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly
that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered. For more information about industrial security, visit this address
(http://www.siemens.com/industrialsecurity).
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. For more information, visit this address (http://support.automation.siemens.com).
WARNING
Danger as a result of unsafe operating states resulting from software manipulation
Software manipulation (e.g. by viruses, Trojan horses, malware, worms) can cause unsafe
operating states to develop in your installation which can result in death, severe injuries
and/or material damage.
• Keep the software up to date.
You will find relevant information and newsletters at this address
(http://support.automation.siemens.com).
• Incorporate the automation and drive components into a holistic, state-of-the-art
industrial security concept for the installation or machine.
You will find further information at this address
(http://www.siemens.com/industrialsecurity).
• Make sure that you include all installed products into the holistic industrial security
concept.
WARNING
Danger to life due to software manipulation when using exchangeable storage media
Storing files onto exchangeable storage media amounts to an increased risk of infection,
e.g. with viruses and malware. As a result of incorrect parameterization, machines can
malfunction, which in turn can lead to injuries or death.
• Protect files stored on exchangeable storage media from malicious software by taking
suitable protection measures, e.g. virus scanners.
Fundamental safety instructions
1.2 Fundamental safety instructions for Safety Integrated
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
17
1.2
Fundamental safety instructions for Safety Integrated
Note
Malfunctions as a result of withdrawing and inserting components
Malfunctions can occur when components are withdrawn or inserted that are used for Safety
Integrated. However, this does not mean that the fail-safe state is exited. For example,
PROFIsafe communication is not reestablished after this event.
• Withdrawing and inserting components used for Safety Integrated (power units, Sensor
Modules, TM54F) during operation and in the deactivated state is not permissible.
Activating the components always requires a POWER ON (see section "Modular machine
concept Safety Integrated (Page 335)").
Additional safety instructions and residual risks
Additional safety information and residual risks not specified in this section are included in
the relevant sections of this Function Manual.
DANGER
Risk minimization through Safety Integrated
Safety Integrated can be used to minimize the level of risk associated with machines and
plants.
Machines and plants can only be operated safely in conjunction with Safety Integrated,
however, when the machine manufacturer:
• Precisely knows and observes this technical user documentation - including the
documented limitations, safety information and residual risks.
• Carefully constructs and configures the machine/plant. A careful and thorough
acceptance test must then be performed by qualified personnel and the results
documented.
• Implements and validates all the measures required in accordance with the
machine/plant risk analysis by means of the programmed and configured Safety
Integrated functions or by other means.
The use of Safety Integrated does not replace the machine/plant risk assessment carried
out by the machine manufacturer as required by the EC machinery directive.
In addition to using Safety Integrated functions, further risk reduction measures must be
implemented.
NOTICE
Danger to life as a result of inactive Safety Integrated functions after powering up
The Safety Integrated functions are only activated after the system has completely powered
up. System startup is a critical operating state with increased risk. When accidents occur,
this can result in death or severe injury.
• Make sure that the machine is safe during the system start-up.
Fundamental safety instructions
1.2 Fundamental safety instructions for Safety Integrated
Safety Integrated
18
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
WARNING
Regulations from EN 60204-1
The Emergency Stop function must bring the machine to a standstill according to stop
category 0 or 1 (STO or SS1).
The machine must not restart automatically after EMERGENCY STOP.
When individual safety functions (Extended Functions) are deactivated, an automatic
restart is permitted under certain circumstances depending on the risk analysis (except
when Emergency Stop is reset). An automatic start is permitted when a protective door is
closed, for example.
WARNING
System power-up and drive activation after changing or replacing hardware and/or software
After hardware and/or software components have been modified or replaced, it is only
permissible for the system to run up and the drives to be activated with the protective
devices closed. Personnel shall not be present within the danger zone.
It may be necessary to carry out a partial or complete acceptance test or a simplified
functional test after having made certain changes or replacements.
Before personnel may re-enter the hazardous area, the drives should be tested to ensure
that they exhibit stable control behavior by briefly moving them in both the plus and minus
directions (+/–).
Please note the following during switch-on:
The Safety Integrated functions are only available and can only be selected after the
system has completely powered up.
WARNING
Danger to life when the drive coasts down for an STO or STOP A
The category 0 stop function in accordance with EN 60204-1 (STO or STOP A to Safety
Integrated) means that the drives are not decelerated but instead coast to standstill (the
time required to coast to standstill depends on the kinetic energy).
• Carefully take this response into account when designing the protective door
interlocking logic.
• For safety without encoder, you must apply other measures to ensure that the protective
door remains locked until the drive has come to a standstill.
Fundamental safety instructions
1.2 Fundamental safety instructions for Safety Integrated
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
19
WARNING
Danger to life as a result of a malfunction due to an acceptance test that has not been
carried out after changes to parameters have been made
Safety Integrated functions cannot detect parameter changes made by the machine builder
(OEM). Incorrect parameter changes for SI functions can result in accidents leading to
death or severe injury.
• After making a change to a parameter, always carry out an acceptance test and
document the values in an acceptance report.
• Only use the system or machine after the acceptance test has been successfully
completed.
WARNING
Danger to life as a result of different responses of the Safety Integrated functions when
replacing a Motor Module or a motor
Motor Modules or the motor must be replaced with a device of the same type, as the
parameter settings will otherwise lead to an incorrect response of the Safety Integrated
functions. Functionality that has been modified can result in accidents leading to death or
severe injury.
• Always replace a component by an identical component of precisely the same type.
• Readjust the drive involved when replacing an encoder.
• Carefully test the functionality after replacement.
WARNING
Danger to life as a result of parameterized safety functions, which are only available to a
restricted extent, when an internal or external fault occurs
If an internal or external fault occurs, none or only some of the parameterized safety
functions are available during the STOP F response triggered by the fault.
• Carefully take this into account when parameterizing a delay time between STOP F and
STOP B. This is especially true for vertical axes.
WARNING
Parameterizing the encoder system
Encoder faults are detected using different hardware and software monitoring functions.
• It is not permissible to disable these monitoring functions (i.e. the encoder monitoring in
the Sensor Module) and they must be parameterized carefully. Depending on the fault
type and the responding monitoring function, stop function category 0 or 1 in
accordance with EN 60204-1 (fault response functions STOP A or STOP B to Safety
Integrated) is selected (see table "Overview of stop responses" in Section "Safety
Integrated Extended Functions", in the section "Safety faults").
Fundamental safety instructions
1.2 Fundamental safety instructions for Safety Integrated
Safety Integrated
20
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Note
EDS switchover for safe motion monitoring
An encoder which is used for safety functions must not be switched over when a drive data
set (DDS) is switched over.
The safety functions check the safety-relevant encoder data for changes when data sets are
switched over. If a change is detected, fault F01670 is displayed with a fault value of 10,
which results in a non-acknowledgeable STOP A.
• The safety-relevant encoder data in the various data sets must therefore be identical.
WARNING
Converter operation despite active messages
With activated safety functions, there are a number of system messages that still permit the
drive to be traversed. In these cases, you must ensure that the causes of the messages are
corrected immediately. These messages include, among others, the following:
• A01774 SI Motion CU: Test stop required
A01697 SI Motion: Motion monitoring test required
Perform the required test stop.
• A13000 Insufficient license.
Purchase the license required for the operation of the Extended Functions.
• A01669 (F, N) SI Motion: Unsuitable combination of motor and power unit.
The motor / power unit combination can result in decreased robustness (incorrect
detection of errors) in the system when operating with SI Motion.
Fundamental safety instructions
1.3 Residual risk
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
21
1.3
Residual risk
The fault analysis enables machine manufacturers to determine the residual risk at their
machine with regard to the drive unit. The following residual risks are known:
WARNING
Residual risk through possible hardware faults: PFH value
Due to the intrinsic potential of hardware faults, electrical systems are subject to additional
residual risk, which can be expressed by means of the PFH value.
• Take into account these residual risks when designing your machine and where
necessary apply suitable countermeasures.
WARNING
Danger to life due to uncontrolled acceleration of the drive
Faults in the absolute track (C-D track), cyclic interchange of the drive phases (V-W-U
instead of U-V-W) and reversal of the control direction may cause acceleration of the drive.
Category 1 and 2 stop functions according to EN 60204-1 (fault response functions Stop B
to D according to Safety Integrated) that are provided are however not effective due to the
fault.
• Category 0 stop function according to EN 60204-1 (fault response function Stop A
according to Safety Integrated) is not activated until the transition or delay time set in the
parameter has expired. These faults are detected when SAM is selected (fault reaction
functions STOP B/C) and stop function category 0 according to EN 60204-1 (fault
reaction function STOP A according to Safety Integrated) is triggered as early as
possible regardless of this delay. Electrical faults (defective components or similar) may
also lead to the response stated above.
WARNING
Danger to life due to short, limited movements of the motor.
Simultaneous breakdown of 2 power transistors in the power unit can cause a short, limited
movement. This can cause accidents resulting in serious injuries or death.
• If there is a hazard due to unwanted movement in your application, take measures to
counter it, for example, by using a brake with safe monitoring. Further information can
be found in Section "Safe Brake Control (SBC) (Page 71)".
WARNING
Danger to life due to higher speeds of short duration when the limit value is exceeded
Violation of limits may briefly lead to a speed higher than the speed setpoint, or the axis
may pass the defined position to a certain extent, depending on the dynamic response of
the drive and on parameter settings.
• Take into account this situation when designing your machine and where necessary
apply suitable countermeasures.
Fundamental safety instructions
1.3 Residual risk
Safety Integrated
22
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
WARNING
Residual risk for a single-encoder system
Within a single-encoder system:
a) A single electrical fault in the encoder
b) A break of the encoder shaft (or loose encoder shaft coupling), or a loose encoder
housing will cause the encoder signals to remain static (that is, they no longer follow a
movement while still returning a correct level), and prevent fault detection while the drive is
in stop state (for example, drive in SOS state).
Generally, the drive is held by the active closed-loop control. Especially for drives with
suspended load, from a closed-loop control perspective, it is conceivable that drives such
as these move without this being detected.
The risk of an electrical fault in the encoder as described under a) is only present for few
encoder types employing a specific principal of operation.
• All of the faults described above must be included in the risk analysis of the machine
manufacturer. Additional safety measures have to be taken for drives with
suspended/vertical or pulling loads - e.g. in order to exclude faults under a):
– Use of an encoder with analog signal generation
– Use of a two-encoder system
• In order to exclude the fault described in b), for example:
– Perform an FMEA regarding encoder shaft breakage (or slip of the encoder shaft
coupling) as well as loose encoder housings and use a fault exclusion process
according to IEC 61800-5-2, or
– Implementation of a two-encoder system (the encoders must not be mounted on the
same shaft).
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
23
General information about SINAMICS Safety
Integrated
2
2.1
Drive products with integrated safety functions
General information about SINAMICS Safety Integrated
2.2 Supported functions
Safety Integrated
24
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
2.2
Supported functions
All of the Safety Integrated functions available under SINAMICS S120 are listed in this
section. SINAMICS makes a distinction between Safety Integrated Basic Functions and
Safety Integrated Extended Functions.
The safety functions listed here conform to:
● Safety Integrity Level (SIL) 2 according to IEC 61508
● Category 3 according to DIN EN ISO 13849-1
● Performance level (PL) d according to DIN EN ISO 13849-1
The safety functions correspond to the functions according to DIN EN 61800-5-2 (under the
assumption that they are defined there).
Safety Integrated Basic Functions
These functions are part of the standard scope of the drive and can be used without
requiring an additional license. These functions are always available. These functions do not
require an encoder and/or do not place any special requirements on the encoder used.
● Safe Torque Off (STO)
Safe Torque Off is a safety function to avoid unexpected startup in accordance with
EN 60204-1. STO prevents the supply of power to the motor, which can produce a
torque. This is equivalent to stop category 0.
● Safe Stop 1 (SS1, time-controlled)
Safe Stop 1 is based on the "Safe Torque Off" function. This means that a Category 1
stop according to EN 60204-1 can be implemented.
● Safe Brake Control (SBC)
Safe Brake Control is used to safely control a holding brake.1) 2)
1) Note regarding Power/Motor Modules in the chassis format: For the chassis format, SBC is
only supported by Power/Motor Modules with article number ...3 or higher. A Safe Brake
Adapter is also needed for this format.
2) Note regarding Power/Motor Modules in the blocksize format: Blocksize Power Modules
also require a Safe Brake Relay for this function.
Safety Integrated Extended Functions
These functions require an additional safety license. Extended Functions with encoder
require an encoder with safety capability (see Section "Notes regarding safe actual value
sensing using an encoder system (Page 147)").
● Safe Torque Off (STO)
Safe Torque Off is a safety function to avoid unexpected starting in accordance with
EN 60204-1.
● Safe Stop 1 (SS1, time and acceleration controlled)
Safe Stop 1 is based on the "Safe Torque Off" function. This means that a Category 1
stop in accordance with EN 60204-1 can be implemented.
General information about SINAMICS Safety Integrated
2.2 Supported functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
25
● Safe Brake Control (SBC)
Safe Brake Control is used to safely control a holding brake.1) 2)
● Safe Operating Stop (SOS)
Safe Operating Stop is used to protect against unintentional movement. The drive is in
closed-loop control mode and is not disconnected from the power supply.
● Safe Stop 2 (SS2)
Safe Stop 2 is used to safely brake the motor with a subsequent transition into the "Safe
Operating Stop" state (SOS). This means that a Category 2 stop in accordance with EN
60204-1 can be implemented.
● Safely Limited Speed (SLS)
Safely Limited Speed monitors that the drive does not exceed a preset speed/velocity
limit.
● Safe Speed Monitor (SSM)
Safe Speed Monitor is used for safely identifying when a speed limit is undershot in both
directions of motion, e.g. to identify zero speed. A fail-safe output signal is available for
further processing.
● Safe Direction (SDI)
Safe Direction is used to safely monitor the direction of motion.
● Safely Limited Position (SLP)
Safely Limited Position ensures that a freely definable traversing range is not left.
● Transferring safe position values (SP)
The "Transfer safe position values (SP)" function enables you to transfer a safe position
to the higher-level control via PROFIsafe.
● Safe gearbox stage switchover
The "Safe gearbox stage switchover" function facilitates reliable switching between
different gearbox stages. The switchover is only possible via PROFIsafe.
● Safe Brake Test (SBT)
The diagnostic function "Safe Brake Test" function (SBT) checks the required holding
torque of a brake (operating or holding brake).
1) Note regarding Power/Motor Modules in the chassis format: For the chassis format, SBC is
only supported by Power/Motor Modules with article number ...3 or higher. A Safe Brake
Adapter is also needed for this design.
2) Note regarding Power/Motor Modules in the blocksize format: Blocksize Power Modules
also require a Safe Brake Relay for this function.
Note
Parallel use of Safety Integrated Functions
All Safety Integrated Functions can be used simultaneously.
Exception: If SOS and SLS are activated simultaneously, SOS has higher priority and
overrides the SLS reaction.
General information about SINAMICS Safety Integrated
2.2 Supported functions
Safety Integrated
26
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
General information about SINAMICS Safety Integrated
2.3 Supported functions: HLA module
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
27
2.3
Supported functions: HLA module
SINAMICS HLA and Safety Integrated
SINAMICS HLA supports the following Safety Integrated functions:
● Basic Functions
These functions are part of the standard scope of the drive and can be used without
requiring an additional license. These functions are always available. These functions do
not require an encoder and/or do not place any special requirements on the encoder
used.
– Safe Torque Off (STO)
Safe Torque Off is a safety function to avoid unexpected startup in accordance with
EN 60204-1. STO prevents the supply of power to the valve, which can produce a
force. It is equivalent to stop category 0.
– Safe Stop 1 (SS1, time-controlled)
Safe Stop 1 is based on the "Safe Torque Off" function. This means that a Category 1
stop in accordance with EN 60204-1 can be implemented.
● Extended Functions
Note
Only Safety Integrated with encoder is possible
SINAMICS HLA only supports Safety Integrated Extended Functions with encoder.
These functions require an additional safety license. Extended Functions with encoder
require an encoder with safety capability.
Note
Encoder types for SINAMICS HLA
The following encoder types are permissible for SINAMICS HLA:
• Single-encoder systems
– DRIVE-CLiQ encoder with safety capability
– sin/cos encoder connected via SME20/25, SME120/125 or SMC20 (1Vss, pure
analog signal processing)
• 2-encoder systems
– Encoders with DRIVE-CLiQ connection
– sin/cos encoder connected via SME20/25, SME120/125 or SMC20 (1Vss, pure
analog signal processing)
– HTL/TTL encoder connected via SMC30 (not in connection with SINUMERIK)
– TTL encoder connected via the onboard interface of the HLA module (not in
connection with SINUMERIK)
– Safe Torque Off (STO)
Safe Torque Off is a safety function that prevents the drive from restarting
unexpectedly according to EN- 60204-1.
General information about SINAMICS Safety Integrated
2.3 Supported functions: HLA module
Safety Integrated
28
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
– Safe Stop 1 (SS1, time and acceleration controlled)
Safe Stop 1 is based on the "Safe Torque Off" function. This means that a Category 1
stop in accordance with EN 60204-1 can be implemented.
– Safe Operating Stop (SOS)
Safe Operating Stop provides protection against unwanted movements. The drive is in
closed-loop control mode and is not disconnected from the power supply.
– Safe Stop 2 (SS2)
Safe Stop 2 is used to safely brake the valve with a subsequent transition into the
"Safe Operating Stop" state (SOS). This means that a Category 2 stop in accordance
with EN 60204-1 can be implemented.
– Safely Limited Speed (SLS)
Safely Limited Speed ensures that the drive does not exceed a preset speed limit.
– Safe Speed Monitor (SSM)
Safe Speed Monitor is used for safely identifying when a speed limit is undershot in
both directions of motion, e.g. to identify zero speed. A fail-safe output signal is
available for further processing.
– Safe Direction (SDI)
Safe Direction is used to safely monitor the direction of motion.
– Safely Limited Position (SLP)
Safely Limited Position ensures that a freely definable traversing range is not left.
– Transferring safe position values (SP)
The "Transfer safe position values (SP)" function enables you to transfer a safe
position to a higher-level control via PROFIsafe.
Note
Only "linear" axis type permitted
For SINAMICS HLA, only the "linear" axis type is permitted.
General information about SINAMICS Safety Integrated
2.3 Supported functions: HLA module
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
29
Commissioning in STARTER
The Safety Integrated functions of SINAMICS HLA can be commissioned in STARTER as
follows:
Expert list
STARTER screen forms
Basic Functions
Yes
No
Extended Functions
Yes
Yes
Note
Comparison, description of electric ↔ hydraulic drives
In the Safety Integrated Function Manual, Safety Integrated functions are described from the
perspective of an electric drive. However, these descriptions essentially also apply in the
same way for hydraulic systems. You will find parameters and messages for the drive object
HLA in the SINAMICS S120/S150 List Manual.
General information about SINAMICS Safety Integrated
2.4 Examples of how the safety functions can be applied
Safety Integrated
30
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
2.4
Examples of how the safety functions can be applied
Safety function
Application examples
Possible solution
STO
It is only permissible to open a protective door if the
motor torque has been switched off.
•
Select STO in the converter via a terminal or
via PROFIsafe.
•
The pulses are suppressed and the motor
coasts to a standstill.
A central Emergency Stop button ensures that
several drives cannot unintentionally start.
Evaluating the Emergency Stop button in a cen-
tral controller, selecting STO in the converter via
PROFIsafe.
SS1
The drive must brake as quickly as possible after
the Emergency Stop button has been pressed. It is
not permissible that the stationary motor undesira-
bly accelerates.
Select SS1 in the converter using a fail-safe input
or via PROFIsafe .
SBC
Safe control of a motor holding brake must be
guaranteed to guarantee the motor is at a stand-
still.
SBC is (if configured) initiated together with STO.
The Motor Module / Safe Brake Relay / Safe
Brake Adapter then carries out the action and
safely controls the outputs for the brake.
SOS
The standstill position of the motor must be moni-
tored and ensured.
Select SOS, e.g. through SS2, in order to monitor
the standstill position of the motor after braking.
SS2
The drive must brake as quickly as possible after
the stop button has been pressed. The standstill
position of the motor must be monitored and en-
sured.
Select SS2in the converter using a fail-safe input
or via PROFIsafe.
SLS
The machine operator must be able to enter the
machine after the protective door has been opened
and slowly move a horizontal conveyor with an
acknowledgment button in the danger zone.
Selecting SLS in the converter. The converter
limits and monitors the velocity of the horizontal
conveyor.
A spindle drive, depending on the selection of the
cutting tool, must not exceed a specific maximum
speed.
Selecting SLS and the corresponding SLS level
in the converter via PROFIsafe.
SSM
A centrifuge may only be filled below a velocity
defined by the user.
If the Extended Functions are enabled, SSM is
always 1). The function does not have to be se-
lected.
The converter safely monitors the centrifuge
speed and enables the process to advance to the
next step using the "SSM status" bit.
1) Exception: Motion monitoring without selection
(Page 205)
SDI
A protective door must only be opened if a drive
moves in the safe direction (away from the opera-
tor).
Selecting SDI in the converter; enable the protec-
tive doors via status bit (PROFIsafe) of the con-
verter.
When replacing the pressure cylinders of the
plates, the drive must only move in the safe direc-
tion of rotation.
Selecting SDI in the converter. Disabling the
hazardous direction of rotation.
Once the protection against jamming has been
triggered, a roller shutter gate must only be able to
start moving in one direction.
At an operational limit switch, the trolley of a crane
must only start in the opposite direction.
General information about SINAMICS Safety Integrated
2.4 Examples of how the safety functions can be applied
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
31
Safety function
Application examples
Possible solution
SLP
The drive may not exit the specified position rang-
es.
Selection of SLP in the converter; inhibits the
range that is not permitted.
SP
It is necessary to transmit a "safe position," for
example, in the following use cases.
•
Safe cam sequencer
•
Calculation of the safe velocity
•
Safety concepts across axes
– Multi-dimensional protection areas
•
Zone concepts
– Safe response depending on the position of
the axes
– Different reaction to sensors
The selection of SP in the converter enables you
to transfer a safe position (i.e. absolute or relative
position) to the higher-level controller via
PROFIsafe.
SBT
The effect of a brake is reduced through wear.
The diagnostic function "Safe Brake Test SBT"
detects whether a brake is achieving the required
braking effect.
Safe gearbox
stage switchover
For a machine equipped with selector gearbox it
must be ensured that the switchover is actually
performed.
The "Safe gearbox stage switchover" function
ensures safe switchover between the gearbox
stages.
General information about SINAMICS Safety Integrated
2.5 Drive monitoring with or without encoder
Safety Integrated
32
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
2.5
Drive monitoring with or without encoder
If motors without a (safety-capable) encoder are being used, not all Safety Integrated
functions can be used.
Note
Definition: "Without encoder"
When "without encoder" is used in this manual, then this always means that either no
encoder or no safety-capable encoder is being used.
In operation without encoder the actual speed values are calculated from the measured
electrical actual values. Therefore, speed monitoring is also possible during operation
without encoder.
Table 2- 1
Overview of Safety Integrated functions
Functions
Abbr. With
encoder
Without
encoder
Brief description
Basic Functions Safe Torque Off
STO
Yes
Yes
Safe torque off
Safe Stop 1
SS1
Yes
Yes
Safe stopping process according to stop
category 1
Safe Brake Control
SBC
Yes
Yes
Safe brake control
Extended
Functions
Safe Torque Off
STO
Yes
Yes1)
Safe torque off
Safe Stop 1
SS1
Yes
Yes1)
Safe stop according to stop category 1
Safe Brake Control
SBC
Yes
Yes1)
Safe brake control
Safe Operating Stop
SOS
Yes
No
Safe monitoring of the standstill position
Safe Stop 2
SS2
Yes
No
Safe stop according to stop category 2
Safely Limited Speed
SLS
Yes
Yes1)
Safe monitoring of the maximum speed
Safe Speed Monitor
SSM
Yes
Yes1)
Safe monitoring of the minimum speed
Safe Direction
SDI
Yes
Yes1)
Safe monitoring of the direction of motion
Safely Limited Position
SLP
Yes
No
Safely limited position
Safe referencing
SR
Yes
No
Safe referencing
Transferring safe position
values
SP
Yes
Yes1)
Transferring safe position values
Safe Brake Test
SBT
Yes
No
Safe test of the required holding torque of a
brake
Safe Acceleration Monitor
SAM
Yes
Yes1)
Safe monitoring of drive acceleration
Safe Brake Ramp
SBR
Yes
Yes1)
Safe braking ramp
Safe gearbox stage switch-
over
–
Yes
No
–
1) The use of this safety function without encoder is permitted only for induction motors or synchronous motors of the
SIEMOSYN series.
The configuration of the Safety Integrated functions and the selection of monitoring with or
without encoder is realized in the safety screens of the STARTER or SCOUT tools.
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
33
Overview of Safety Integrated functions
3
3.1
Safety Integrated Basic Functions
Note
Basic functions do not require an encoder
The Safety Integrated Basic Functions are functions for safely stopping the drive. You do not
require an encoder.
Note
Application of the Basic Functions
The Basic Functions are available without any restrictions in all control modes, with and
without an encoder, for synchronous, induction, and reluctance motors.
Note
Control via TM54F
If you want to control the Safety Integrated Basic Functions via TM54F, set p9601.6 = 1.
This chapter should provide first users with a quick overview of the principle mode of
operation of safety functions.
The entry into the description of the safety functions is based on the definition according to
standard EN 61800-5-2 and some simple examples for using the function.
The description of the functions is simplified, as far as possible to clearly shown essential
properties and setting options.
More information about the functions can be found in the following sections,
e.g.: "Safety Integrated basic functions (Page 62)".
Overview of Safety Integrated functions
3.1 Safety Integrated Basic Functions
Safety Integrated
34
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
3.1.1
Safe Torque Off (STO)
Definition according to EN 61800-5-2:
"The STO function prevents energy from being
supplied to the motor, which can generate a
torque."
Examples of how the function can be used
Example
Possible solution
It is only permissible to open a protective door if the
motor torque has been switched off.
•
Select STO in the converter.
•
The pulses are suppressed and the motor
coasts to a standstill.
How does STO function in detail?
The converter recognizes the
selection of STO via a fail-safe
input or via the safe communi-
cation PROFIsafe.
The converter then safely
switches off the torque of the
connected motor.
Details and parameterization
For further details and information on how to parameterize this function, refer to Chapter
"Safe Torque Off (STO) (Page 62)".
Overview of Safety Integrated functions
3.1 Safety Integrated Basic Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
35
3.1.2
Safe Stop 1 (SS1)
Definition according to EN 61800-5-2:
"The function SS1 brakes the motor and
trips the function STO after a delay time."
Example of how the function can be used
Example
Possible solution
After an Emergency Stop button has been pressed,
the drive must be braked as quickly as possible and
brought into the STO state.
•
Wire the Emergency Stop button with a
fail-safe input.
•
Select SS1 via the fail-safe input.
A central Emergency Stop button ensures that sev-
eral drives are braked as quickly as possible and
brought into the STO state.
•
Evaluating an emergency stop pushbutton
in a central control.
•
Select SS1 via PROFIsafe.
How does SS1 function in detail?
Overview
The drive decelerates once "Safe Stop 1" has
been selected, and goes into the "Safe Torque
Off" state once the delay time has expired.
Select SS1
As soon as the converter identifies that SS1 has been selected via a terminal or via the
PROFIsafe safe communication, the following happens:
● If, when selecting SS1, the motor is already switched off, then until the SS1 delay time
expires, there is no response. STO becomes active after the time expires.
● If the motor is switched on when SS1 is selected, the inverter brakes the motor with the
OFF3 ramp-down time. After the delay time, STO is triggered automatically.
Overview of Safety Integrated functions
3.1 Safety Integrated Basic Functions
Safety Integrated
36
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Stop 1 (SS1, time controlled) (Page 68)".
3.1.3
Safe Brake Control (SBC)
Definition according to EN 61800-5-2:
"The SBC function supplies a safe output
signal to control a holding brake."
Safe Brake Control (SBC)
Example of how the function can be used
Example
Possible solution
The safe control of a motor holding
brake must be guaranteed in order to
guarantee the motor is at a standstill.
SBC is (if configured) initiated together with STO. The Motor
Module / Safe Brake Relay / Safe Brake Adapter then carries
out the action and safely controls the outputs for the brake.
How does SBC function in detail?
The converter recognizes the
selection of STO via a fail-safe
input or via the safe communi-
cation PROFIsafe.
The converter then safely
switches off the torque of the
connected motor.
SBC is (if configured) initiated
together with STO. The Motor
Module / Safe Brake Relay /
Safe Brake Adapter then car-
ries out the action and safely
controls the outputs for the
brake.
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Brake Control (SBC) (Page 71)".
Overview of Safety Integrated functions
3.1 Safety Integrated Basic Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
37
3.1.3.1
Hardware required for SBC
Hardware required for SBC
● Safe Brake Relay
The command for releasing or applying the brake is transferred to the Motor Module /
Power Module via DRIVE-CLiQ. The Motor Module / Safe Brake Relay then carries out
the action and appropriately activates the outputs for the brake.
Image 3-1
Interconnecting the Safe Brake Relay using Blocksize as an example
The brake cannot be directly connected to the Motor Module in the chassis format. The
connection terminals are only designed for 24 VDC with 150 mA; the Safe Brake Adapter is
required for higher currents and voltages.
Note
Additionally required hardware for other formats
A Safe Brake Relay is also required for the "Safe Brake Control" in the blocksize format.
With the chassis format (article numbers ending ...3 or higher), a Safe Brake Adapter is
required. The Safe Brake Adapter is available for a 230 V AC brake control voltage.
Overview of Safety Integrated functions
3.1 Safety Integrated Basic Functions
Safety Integrated
38
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Image 3-2
Interconnecting the Safe Brake Adapter
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
39
3.2
Safety Integrated Extended Functions
This chapter should provide first users with a quick overview of the principle mode of
operation of safety functions.
The entry into the description of the safety functions is based on the definition according to
standard EN 61800-5-2 and some simple examples for using the function.
The description of the functions is simplified, as far as possible to clearly shown essential
properties and setting options.
More information about the functions can be found in the following sections,
e.g.: "Safety Integrated Extended Functions (Page 80)".
3.2.1
Preconditions for the Safety Extended Functions
● For operation of the Safety Integrated Extended Functions, one license is required for
each axis.
● An activated current controller in the drive
● Overview of hardware components that support the Extended Functions:
– Control Unit CU320-2
– Control Unit CU310-2
– Motor Modules Booksize Compact
– Motor Modules Booksize with an article number ending: -...3 or higher
– Motor Modules Chassis with an article number ending: -...3 or higher
– Motor Modules Cabinet with an article number ending: -...2 or higher
– Power Modules Blocksize
– Control Unit Adapter CUA31 as of article number: 6SL3040-0PA00-0AA1
– Control Unit Adapter CUA32 as of article number: 6SL3040-0PA01-0AA0
– For the safety functions with encoder:
Motors with sin/cos encoder and encoder evaluation with DRIVE-CLiQ interface or via
Sensor Module SMC20, SME20/25/120/125
The list of approved encoders can be found on the Internet at:
http://support.automation.siemens.com
Enter the number 33512621 there as search term or contact your local Siemens office.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
40
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
3.2.2
Control possibilities
The following options are available for controlling Safety Integrated Extended Functions:
● PROFIsafe
● TM54F
● Onboard F-DI (CU310-2)
● Permanent selection (Safety Integrated functions without selection)
3.2.3
Safe Torque Off (STO)
For the control options and the functionality for "Safe Torque Off" (STO), see Section "Safe
Torque Off (STO) (Page 62)".
3.2.4
Safe Stop 1 (SS1)
Definition according to EN 61800-5-2:
"The function SS1 brakes the motor, moni-
tors the magnitude of the motor decelera-
tion within specified limits, and after a delay
time or violation of a speed threshold, initi-
ates the STO function."
Example of how the function can be used
Example
Possible solution
After an Emergency Stop button has been
pressed, the drive must be braked as quickly as
possible and brought into the STO state.
•
Wire the Emergency Stop button with a fail-
safe input.
•
Select SS1 via the fail-safe input.
•
SS1 brakes the drive and then brings it into
the STO state.
A central Emergency Stop button ensures that
several drives are braked as quickly as possible
and brought into the STO state.
•
Evaluating an emergency stop pushbutton in
a central control.
•
Select SS1 via PROFIsafe.
•
SS1 brakes the drives and then brings them
into the STO state.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
41
How does SS1 function in detail?
Overview
Using the SS1 function, the converter brakes
the motor and monitors the absolute speed.
If the motor speed is low enough or the delay
time has expired, the converter safely switches
off the motor torque using STO.
Select SS1
As soon as the converter identifies that SS1 has been selected via a fail-safe input or via
PROFIsafe safe communication, the following happens:
● If the motor has already been switched off when selecting SS1 then the converter safely
switches off the motor torque (STO).
● If the motor is switched on when SS1 is selected, the converter brakes the motor with the
AUS3 ramp-down time.
Monitoring modes
For the Extended Functions with or without encoder, you can choose between 2 different
monitoring modes of the function SS1:
● Safe Brake Ramp (SBR)
● Safe Acceleration Monitor (SAM)
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
42
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Brake ramp monitoring
(with or without encoder)
Acceleration monitoring
(with or without encoder)
•
Using the SBR (Safe Brake Ramp) function,
the converter monitors whether the motor
speed decreases.
•
The gradient of the SBR function can be set
via the reference velocity and the ramp-down
time. The SBR function only starts after the
"Delay for braking ramp".
•
The SBR function starts with the speed set-
point, which was present at the instant in
time that SS1 was selected.
•
If the converter detects that the speed has
fallen below the speed threshold (standstill
monitoring), it safely switches off the motor
torque (STO).
•
The converter monitors the speed of the motor
with the SAM function.
•
The converter prevents the motor from accel-
erating again by having the monitoring function
continuously track the speed as it decreases.
•
The converter reduces the monitoring thresh-
old until the "Shutdown speed" has been
reached.
•
The converter safely switches off the motor
torque (STO), if one of the following conditions
is fulfilled:
– The speed has fallen below the shutdown
speed SS1.
– The maximum time until the torque is
switched off has expired.
Note
SS1 with external stop (SS1E)
If you use SS1E, neither of the two monitoring functions (SBR, SAM) is active. The drive
must be shut down in SS1E within the delay time, for example, by a user program of a CPU.
STO becomes active after the delay time expires.
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Stop 1 (SS1) (Page 87)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
43
3.2.5
Safe Operating Stop (SOS)
Definition according to EN 61800-5-2:
"This SOS function is used for safe monitor-
ing of the standstill position of a drive."
Example of how the function can be used
Example
Possible solution
A protective door must only be
opened if a motor is in the safe
standstill state.
•
Select SOS
•
A higher-level controller brakes the axis (e.g. position-
controlled) down to standstill within the configured time be-
tween the selection of SOS and when it becomes active.
•
Standstill is then safely monitored via the SOS function.
The protected machine areas can be entered without having to shut down the machine as
long as SOS is active.
After SOS has been selected it becomes active after the parameterizable delay time has
expired. The drive must be braked to standstill within this delay time (e.g. by the controller).
Drive stopping is monitored using an SOS tolerance window. At the instant this function
becomes active, the current actual position is stored as the comparison position until SOS is
deselected again. Any delay time is cleared after SOS is deselected and the drive can be
immediately moved.
The drive is stopped with SS1 when the standstill tolerance window is violated.
Note
Contrary to SS1 and SS2, SOS does not automatically brake the drive
The control still enters the setpoint.
This means that in the user program of the control system, the system must respond to the
"SOS selected" bit so that the control system brings the drive to a standstill within the delay
time.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
44
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Image 3-3
Standstill tolerance
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Operating Stop (SOS) (Page 92)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
45
3.2.6
Safe Stop 2 (SS2)
Definition according to EN 61800-5-2:
"The function SS2 brakes the motor, moni-
tors the magnitude of the motor decelera-
tion, and after a delay time, initiates the
SOS function."
Example of how the function can be used
Example
Solution
A protective door must only be opened
if a motor is in the safe standstill state.
•
Select SS2 in the converter via a terminal or via
PROFIsafe .
•
After braking, the converter goes into the SOS state.
Only then may the protective door be released.
3.2.6.1
How does SS2 function in detail?
Overview
The safety function SS2 monitors the
load speed and initiates the SOS function
if the SS2 delay time has expired.
With SS2, braking is monitored on the
OFF3 ramp. A faulty acceleration is de-
tected and the drive then shuts down
with STO.
If you are operating the motor with closed-loop torque control, the converter switches to the
closed-loop speed control mode when SS2 is selected.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
46
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Detailed description
The fail-safe logic (e.g. F-CPU) selects the SS2 safety function via a fail-safe input or via the
PROFIsafe safe communication.
● If, when selecting SS2, the motor is already at a standstill, after a delay time, the
converter activates the Safe Operating Stop function (SOS).
● If the drive is not at standstill when SS2 is selected, it is braked along the OFF3 ramp.
Braking is monitored with one of the following functions, depending on the setting in
p9506:
– "Safe Acceleration Monitor (SAM)"
A faulty acceleration is therefore detected.
– "Safe Brake Ramp (SBR)"
In this way, a violation of the braking ramp is detected.
After a delay time, the converter activates the Safe Operating Stop function (SOS). This
function monitors the safe standstill of the drive.
Braking behavior
Image 3-4
Braking behavior and diagnostics of the safety function SS2 (example of SS2 with SAM)
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
47
Note
SS2 with external stop (SS2E)
If you use SS2E, neither of the two monitoring functions (SBR, SAM) is active. The drive
must be shut down in SS2E within the delay time, for example, by a user program of a CPU.
SOS becomes active after the delay time expires.
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Stop 2 (SS2) (Page 94)".
3.2.7
Safely Limited Speed (SLS)
Definition according to EN 61800-5-2:
"The SLS function prevents the motor from
exceeding the specified speed limit."
Examples of how the function can be used
Example
Possible solution
The machine operator must be able to enter the
machine after the protective door has been opened
and slowly move a horizontal conveyor with an ac-
knowledgment button in the danger zone.
•
Select SLS in the converter via a fail-safe
input or PROFIsafe .
•
The converter limits and monitors the
velocity of the horizontal conveyor.
A spindle drive, depending on the selection of the
cutting tool, must not exceed a specific maximum
velocity.
•
Select SLS and the corresponding
SLSlevel in the converter via PROFIsafe.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
48
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
How does SLS function in detail?
Overview
1. The inverter recognizes the
selection of SLS via a fail-safe
input or via the PROFIsafe safe
communication.
2. SLS allows a motor to reduce its
possibly inadmissibly high speed
within a defined time.
3. SLS monitors the absolute value
of the actual velocity.
The SLS setpoint limit can be
transferred to the higher-level
motion controller (e.g.
SIMOTION), where the velocity
setpoint can be limited.
In addition, you can configure the
setpoint limit provided by SLS as
maximum speed in the ramp-
function generator. In this case,
SLS limits the speed setpoint.
Note
SLS without selection
As an alternative to controlling via terminals and/or PROFIsafe, there is also the option to
parameterize the SLS function without selection. In this case, the SLS function is
permanently active after POWER ON. You can find details about this in Section "Safely-
Limited Speed without selection (Page 105)".
Selecting SLS when the motor is switched on
As soon as the converter detects the selection of SLS via a fail-safe input or via PROFIsafe
safe communication, the following happens:
● To avoid a limit value being violated, the setpoint limit can be transferred to the higher-
level motion controller (e.g. SIMOTION). The higher-level motion controller can then limit
the velocity setpoint.
● If the speed setpoint limitation is interconnected to the ramp-function generator, the
converter limits the speed to a value below the SLS monitoring.
● For SLS without encoder, you can select whether the converter monitors motor braking
using the function SBR (Safe Brake Ramp) or not. For SLS with encoder, the SBR
function cannot be selected.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
49
With braking ramp monitoring1)
(only without encoder)
Without braking ramp monitoring
(with or without encoder)
•
After the adjustable "delay time for the brak-
ing ramp", using the SBR (Safe Brake Ramp)
function, the converter monitors whether the
velocity decreases.
•
The converter switches from SBR to SLS as
soon as one of the following two conditions is
fulfilled:
– The SBR monitoring ramp has reached
the value of the SLS monitoring.
This case is shown in the diagram above.
– After the actual velocity has reached the
value of the SLS monitoring threshold, the
system again waits for the "delay time for
braking ramp" until SLS becomes active.
•
The converter monitors the load velocity after
the "delay time for SLS switchover" has ex-
pired.
Advantages:
•
Already when braking, the converter detects
as to whether the load velocity decreases too
slowly.
•
The feedback signal "SLS active" generally
comes earlier than without acceleration moni-
toring.
Advantage:
•
Commissioning is simplified, because instead
of the subfunction SBR or SAM of the alterna-
tive brake ramp monitoring, you only have to
set the delay time.
1) The automatic reduction of the speed only takes effect when the ramp-function generator is inter-
connected to the speed setpoint limitation.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
50
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Selecting SLS at low velocities
If the motor velocity when selecting SLS is less than the SLSlimit, then the drive responds as
follows:
Deselecting SLS
If the higher-level controller deselects SLS , then the converter deactivates limiting and
monitoring.
Switching over the monitoring limits
When SLS is active, you can switchover between 4 different speed levels. An exception is
"SLS without selection": In this case, there is only one limit.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
51
Switching to a lower speed level
With braking ramp monitoring1)
(only without encoder)
Without braking ramp monitoring
(with or without encoder)
•
Once the "delay time for braking ramp" has
elapsed, the converter monitors the motor ve-
locity using the function SBR (Safe Brake
Ramp).
•
The converter switches over from SBR moni-
toring to level 2 of SLS monitoring as soon as
one of the following conditions is fulfilled:
– The SBR monitoring ramp has reached
the value of the SLS monitoring.
This case is shown in the diagram above.
– The load velocity has decreased down to
the value SLS monitoring and the "delay
time for braking ramp" has expired.
•
The converter monitors the velocity with the
lower SLS level after the "delay time for SLS
changeover" has expired (this is the same de-
lay time that applies after selecting the func-
tion SLS).
1) The automatic reduction of the speed only takes effect when the ramp-function generator is inter-
connected to the speed setpoint limitation.
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
52
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Switching to a higher speed level
If you switch over from a lower to a higher speed level, the converter immediately monitors
the actual velocity against the higher velocity.
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safely-
Limited Speed (SLS) (Page 99)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
53
3.2.8
Safe Speed Monitor (SSM)
Definition according to EN 61800-5-2:
"The SSM function supplies a safe
output signal to indicate whether the
motor speed is below a specified limit
value."
Note
SSM is a pure signaling function
Unlike other Safety Integrated functions, exceeding the SSM limit value does not result in a
drive-autonomous stop response.
Example of how the function can be used
Example
Possible solution
A centrifuge may only be filled below a
velocity defined by the user.
•
SSM is activated by configuring the Safety Integrated
Extended Functions.
•
The converter safely monitors the centrifuge speed
and enables the process to advance to the next step
using the "Status SSM" status bit.
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Speed Monitor (SSM) (Page 108)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
54
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
How does SSM function in detail?
Requirements
The safety function SSM cannot be selected or deselected using external control signals.
SSM is active when you have set a monitoring velocity > 0 for SSM .
Evaluating the speed
The converter compares the load speed with the speed limit and signals if the limit value is
undershot to the high-level control.
Parameterizable hysteresis
The parameterizable hysteresis ensures that the SSM output signal does not jump between
the values "0" and "1" in the limit range.
Image 3-5
Time response of the safety function SSM (Safe Speed Monitor)
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
55
3.2.9
Safe Direction (SDI)
Definition according to EN 61800-5-2:
"The SDI function prevents the motor shaft mov-
ing in the wrong direction."
Examples of how the function can be used
Example
Possible solution
A protective door must only be opened if a drive
moves in the safe direction (away from the operator).
•
Select SDI in the converter using a fail-
safe input or PROFIsafe .
•
Enable the locking mechanism of the
protective doors via the PROFIsafe status
bit of the converter.
When replacing the pressure cylinders of the plates,
the drive must only move in the safe direction of
rotation.
•
Select SDI in the converter using a fail-
safe input or PROFIsafe .
•
In the converter, inhibit the direction of
rotation that is not permitted.
Once the protection against jamming has been trig-
gered, a roller shutter gate must only be able to start
moving in one direction.
At an operational limit switch, the trolley of a crane
must only be able to start in the opposite direction.
How does SDI function in detail?
SDI monitors the actual direction of
rotation.
The SDI setpoint limit can be transmit-
ted to the higher-level motion control-
ler (e.g. SIMOTION) to enable
limitation of the velocity setpoint there.
In addition, you can configure the
setpoint limit provided by SDI as max-
imum speed in the ramp-function
generator. In this case, SDI limits the
speed setpoint to the permissible di-
rection.
You can select to block either the positive or the negative direction of rotation via 2 fail-safe
signals (F-DIs or PROFIsafe).
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
56
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Selecting and deselecting SDI
As soon as the converter identifies that SDI has been selected via a fail-safe input or via
PROFIsafe safe communication, the following happens:
● You can also set a delay time, within which you can ensure that the converter moves in
the enabled (safe) direction.
● You can also set a tolerance, within which the converter tolerates movement in the
direction that has not been enabled (unsafe). You can avoid the triggering of faults during
braking (overshoot) as well as in controlled standstill.
● After the delay time has expired, the converter monitors the direction of rotation of the
motor.
● If the converter now moves in the blocked direction by more than the configured
tolerance, a message will be output and the defined stop response will be initiated.
Image 3-6
Time response of the safety function SDI (Safe Direction)
Note
SDI without selection
As an alternative to controlling via terminals and/or PROFIsafe, there is also the option of
parameterizing SDI without selection. In this case, SDI will be permanently active after
POWER ON. You will find details of this in Chapter "Safe Direction without selection
(Page 119)."
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Direction (SDI) (Page 115)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
57
3.2.10
Safely-Limited Position (SLP)
Definition according to EN 61800-5-2:
"The SLP function prevents the motor shaft
from exceeding the specified position limit(s)."
The Safely Limited Position function (SLP) is used to safely monitor the limits of two
traversing and/or positioning ranges, which are toggled between using a safe signal.
Examples of how the function can be used
Example
Possible solution
The drive must not exit the
specified position ranges.
•
Selection of SLP in the converter; inhibiting the range that is not
permitted.
•
After the enabled range has been exited, a parameterizable stop
response is initiated.
Features
● Selection via terminals or PROFIsafe
● 2 position ranges, each defined by a limit switch pair
● Safe switchover between the two position ranges
● Adjustable stop response
● To run the motor out of the prohibited range, you must perform a special sequence (see
Chapter "Retraction (Page 124)").
Requirements
● The function is only available with a suitable encoder.
● The drive has to be safely referenced (see Chapter "Safe referencing (Page 58)").
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safely-
Limited Position (SLP) (Page 121)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
58
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
3.2.11
Safe referencing
The "safe referencing" function allows a safe absolute position to be defined. This safe
position is used for the following functions:
● Safely-Limited Position (SLP) (Page 57)
● Transferring safe position values (SP) (Page 59)
General description
In most cases, an external control performs referencing to an absolute position. The
converter only performs this task in special cases (for example, EPOS).
● Referencing using an external control
Requirement: No movement of the drive
The reference position determined by the control is entered into parameter p9572 and is
declared to be valid using p9573 = 89.
● Referencing by EPOS
The SINAMICS EPOS function transfers, when referencing, the determined position
directly to Safety Integrated. This can also take place during motion.
● User agreement
The user agreement must be set (p9726 = p9740 = AC hex) within 2 seconds after
referencing.
Safety Integrated only evaluates the reference position if this is required by a function that
has been enabled (e.g. SLP). Using diagnostics bit r9723.17, Safety Integrated indicates
whether the drive has been referenced. Safety Integrated indicates the position of the drive
in diagnostic parameters r9708 and r9713. Bit r9722.23 is set when the axis is safely
referenced.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2821
SI Extended Functions - Safe referencing
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
referencing (Page 127)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
59
3.2.12
Transferring safe position values (SP)
The "Safe Position (SP)" function enables you
to transfer safe position values to the higher-
level fail-safe controller (F-CPU) via PROFIsafe
(telegram 901 or 902).
From the position change over time, the F-CPU
can also calculate the current velocity. In tele-
gram 902, the values are transferred in 32-bit
format, in telegram 901, in 16-bit format.
After parameter assignment, release and POWER ON, the function is automatically selected
and the values transferred. Please observe the following:
● For use as the safe absolute position, the "Absolute position" must also be enabled and
then safely referenced.
● In order that the transferred position can be used, the actual position value must be valid.
Using the time stamp that is also transferred, you can also calculate the velocity from the
position values. If you only want to calculate the velocity, it is sufficient to enable the
"Transfer of safe position values" without the "Absolute position."
Details and parameterization
For further details and information on how to parameterize this function, see Section
"Transferring safe position values (SP) (Page 129)".
Overview of Safety Integrated functions
3.2 Safety Integrated Extended Functions
Safety Integrated
60
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
3.2.13
Safe Brake Test
The diagnostic function "Safe Brake Test" function (SBT) checks the required holding torque
of a brake (operating or holding brake). You can test linear and rotary brakes. The drive
purposely generates a force/torque against the applied brake. If the brake is operating
correctly, the axis motion remains within a parameterized tolerance. If, however, a larger axis
motion is detected, it must be assumed that the braking force/torque has deteriorated and
maintenance is required.
The "Safe Brake Test" function allows a safe test of up to two brakes:
● 1 motor holding brake and 1 external brake
● 2 external brakes
● 1 motor holding brake
● 1 external brake
The Safe Brake Test (SBT) diagnostic function meets the requirements for Category 2
according to EN ISO 13849-1.
Details and parameterization
For further details and information on how to parameterize this function, see Section "Safe
Brake Test (SBT) (Page 132)".
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
61
Description of Safety Integrated functions
4
Two-channel parameterization
Parameterization of the Safety Integrated functions must be performed in two channels; i.e.
there is one parameter each for the 1st and 2nd channel. These two parameters must be
identically parameterized.
For safety reasons, when using the STARTER commissioning tool (or SCOUT), you can only
set the safety-related parameters of the first channel offline.
To set the safety-related parameters of the second channel, proceed as follows:
● Activate the "Copy parameters after download" checkbox and then establish an online
connection to the drive unit. Perform the download and then adapt the checksums.
Execute the "Copy RAM to ROM" command and then a POWER ON.
● Or establish an online connection to the drive unit first and then duplicate the parameters
by clicking the "Copy parameters" button on the start screen of the configuration.
Because, in STARTER, you can set the safety-related parameters of the 2nd channel by
copying, only the parameters of the 1st channel are stated in this manual. You will find the
relevant parameters of the 2nd channel in the parameter description, e.g. in SINAMICS
S120/S150 List Manual.
On faults and alarms, only the error number of the 1st channel is stated.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
62
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1
Safety Integrated basic functions
Note
Basic functions do not require an encoder
The Safety Integrated Basic Functions are functions for safely stopping the drive. You do not
require an encoder.
Note
Application of the Basic Functions
The Basic Functions are available without any restrictions in all control modes, with and
without an encoder, for synchronous, induction, and reluctance motors.
Note
Control via TM54F
If you want to control the Safety Integrated Basic Functions via TM54F, set p9601.6 = 1.
Note
PFH values
The PFH values of the individual SINAMICS S120 safety components can be found at:
http://support.automation.siemens.com/WW/view/de/76254308
4.1.1
Safe Torque Off (STO)
In conjunction with a machine function or in the event of a fault, the "Safe Torque Off" (STO)
function is used to safely disconnect the torque-generating energy supply to the motor.
A restart is prevented by the two-channel pulse suppression. The switching on inhibited
prevents an automatic restart after deselection of STO.
The two-channel pulse suppression function integrated in the Motor Modules / Power
Modules is the basis for this function.
Functional features of "Safe Torque Off"
● The function is completely integrated in the drive. It can be selected via terminals, TM54F
or PROFIsafe from an external source.
● The function is drive-specific, i.e. it is available for each drive and must be individually
commissioned.
● The function must be enabled via parameter.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
63
● When the "Safe Torque Off" function is selected, the following applies:
– The motor cannot be started accidentally.
– The pulse suppression safely disconnects the torque-generating energy supply to the
motor.
– The power unit and motor are not electrically isolated.
● The selection/deselection of the STO function also acknowledges the safety faults when
the Basic Functions are used. The standard acknowledgment mechanism must also be
performed.
● Extended acknowledgement:
The selection/deselection of STO can also acknowledge the safety messages of the
extended safety functions. This requires that the extended message acknowledgement is
configured (p9507.0 = 1).
If in addition to the "Extended Functions", the "Basic Functions via terminals" are also
enabled, in addition to selection/deselection of STO via PROFIsafe or TM54F,
acknowledgement is also possible by selection/deselection of STO via terminals.
● The status of the "Safe Torque Off" function is displayed using parameters (r9772, r9872,
r9773 and r9774).
WARNING
Danger to life as a result of undesirable motor movement
After the energy feed has been disconnected (STO active) the motor can undesirably move
(e.g. the motor can coast down), therefore presenting risk to persons.
• Take suitable measures to prevent undesirable movement, e.g. by using a brake with
safety-relevant monitoring. For additional information, see Section "Safe Brake Control
(SBC) (Page 71)".
WARNING
Danger to life as a result of undesirable motor movement
Undesirable motor motion can occur if 2 power transistor simultaneously become defective
(breakdown of the depletion layer). This can result in accidents leading to death or severe
injury.
• Take suitable measures to prevent undesirable movement, e.g. by using a brake with
safety-relevant monitoring. For additional information, see Section "Safe Brake Control
(SBC) (Page 71)".
1) The maximum movement can involve:
● Synchronous rotary motors: Max. movement = 180° / no. of pole pairs
● Synchronous linear motors: Max. movement = pole width
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
64
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Enabling the "Safe Torque Off" function
The "Safe Torque Off" function is enabled via parameter p9601:
● STO for the Safety Integrated Basic Functions:
– p9601 = 1 hex (Basic Functions via onboard terminals)
– p9601 = 8 hex (Basic Functions via PROFIsafe)
– p9601 = 9 hex (Basic Functions via PROFIsafe and onboard terminals)
– p9601 = 40 hex (basic functions via TM54F)
– p9601 = 41 hex (basic functions via TM54F and onboard terminals)
● STO in the Safety Integrated Extended Functions (EF):
– p9601 = 4 hex (EF via TM54F)
– p9601 = 5 hex (EF via TM54F and basic functions via onboard terminals)
– p9601 = C hex (EF via PROFIsafe)
– p9601 = D hex (EF via PROFIsafe via onboard terminals)
– p9601 = 25 hex (EF without selection and basic functions via onboard terminals)
Selecting/deselecting "Safe Torque Off"
The following is executed when "Safe Torque Off" is selected:
● Each monitoring channel triggers safe pulse suppression via its switch-off signal path.
● A motor holding brake is closed (if connected and configured).
Deselecting "Safe Torque Off" represents an internal safety acknowledgment. The following
is executed if the cause of the fault has been removed:
● Each monitoring channel cancels safe pulse suppression via its switch-off signal path.
● The Safety requirement "Close motor holding brake" is canceled.
● Any pending STOP F or STOP A commands are canceled (see r9772).
● The messages in the fault memory must also be reset using the general acknowledgment
mechanism.
Note
No message for selection/deselection within the tolerance time (p9650)
If "Safe Torque Off" is selected and deselected through one channel within the tolerance
time p9650, the pulses are suppressed without a message being output.
However, if you want a message to be displayed, then you must reconfigure N01620 as
an alarm or fault using p2118 and p2119.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
65
Restart after the "Safe Torque Off" function has been selected
1. Deselect the function.
2. Set drive enables.
3. Cancel the "switching on inhibited" and switch the drive back on.
– 1/0 edge at input signal "ON/OFF1" (cancel "switching on inhibited")
– 0/1 edge at input signal "ON/OFF1" (switch on drive)
Status for "Safe Torque Off"
The status of the function STO is displayed via r9772, r9872, r9773, and r9774. Alternatively,
you can display the status of the function via the configurable message N01620
(configuration via p2118 and p2119).
Response time for the "Safe Torque Off" function
For the response times when the function is selected/deselected via input terminals, see the
table in Section "Response times (Page 351)".
Internal armature short-circuit with the "Safe Torque Off" function
The function "internal armature short-circuit" can be configured together with the "STO"
function.
The "STO" safety function has the higher priority when simultaneously selected. If the "STO"
function is initiated, then an activated "internal armature short-circuit" is disabled.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2810
SI Basic Functions - STO (Safe Torque Off), SS1 (Safe Stop 1)
• 2811
SI Basic Functions - STO (Safe Torque Off), safe pulse suppression
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p9601
SI enable functions integrated in the drive (Control Unit)
• r9720
CO/BO: SI Motion drive-integrated control signals
• r9722
CO/BO: SI Motion drive-integrated status signals
• r9772
CO/BO: SI Status (Control Unit)
• r9773
CO/BO: SI Status (Control Unit + Motor Module)
• r9774
CO/BO: SI Status (group STO)
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
66
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1.1.1
Safe Torque Off (STO) for SINAMICS HLA
For the HLA module, safe torque off (STO) corresponds to shutting off a safety-relevant
shutoff valve.
Special features of STO for HLA
● The shutoff valve controls the infeed to the hydraulic circuit. The shutoff valve is
controlled via an F-DO of SINAMICS HLA.
● For Safety Integrated functions, it is absolutely necessary that a shutoff valve is
connected with the associated feedback signals.
● You configure the feedback signal contacts of the shutoff valve using parameter p9626.
● You can take into account the response times of the feedback signals using parameter
p9625.
● The shutoff valve is safely closed by selecting STO. If the shutoff valve signals a safe
state via the feedback signal(s), the "STO active/Power removed" state is displayed, and
is output at the configured safety-relevant output (PROFIsafe feedback signal telegram,
F-DO on TM54F).
Image 4-1
Interconnecting the shutoff valve (for an axis)
● F-DO is dynamized each time that STO is selected/deselected: "Diag DO+" and "Diag
DO-" are checked when switching F-DO+ and F-DO-.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
67
● This makes it unnecessary to select forced dormant error detection (test stop) explicitly.
● If an error occurs in forced dormant error detection (test stop), the converter will issue the
fault F01632 or F30632.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2810
SI Basic Functions - STO (Safe Torque Off), SS1 (Safe Stop 1)
• 2811
SI Basic Functions - STO (Safe Torque Off), safe pulse suppression
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p9625[0...1]
SI HLA shutoff valve wait time (CU)
• p9626
SI HLA shutoff valve feedback contacts configuration (CU)
• r9773
CO/BO: SI Status (Control Unit + Hydraulic Module)
• r9774
CO/BO: SI Status (group STO)
• r9780
SI monitoring cycle (Control Unit)
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
68
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1.2
Safe Stop 1 (SS1, time controlled)
4.1.2.1
SS1 with OFF3
The "Safe Stop 1" (SS1) function allows the drive to be stopped in accordance with
EN 60204-1, Stop Category 1. The drive decelerates with the OFF3 ramp (p1135) once
"Safe Stop 1" is selected and switches to "Safe Torque Off" once the delay time set in p9652
has elapsed.
Note
Selection via terminals
The selection of the "Safe Stop 1" (time-controlled) function via terminals is parameterized
by setting a delay > 0 in p9652. In this case, the STO function can no longer be selected
directly via terminals, i.e. either STO or SS1 can be selected via terminals.
If the "Safe Stop 1" (time-controlled) function has been selected by parameterizing a delay
time in p9652, STO can no longer be selected directly via terminals.
Functional features of Safe Stop 1
SS1 is enabled by p9652 (delay time) ≠ 0.
● Setting parameter p9652 has the following effect:
– p9652 = 0
SS1 is not enabled. Only STO can be selected via TM54F, the onboard terminals
and/or PROFIsafe.
– p9652 > 0
SS1 is enabled. Only SS1 can be selected via the onboard terminals; with PROFIsafe,
a selection of SS1 and STO is possible.
● When SS1 is selected, the drive is braked along the OFF3 ramp (p1135) and STO/SBC is
automatically initiated after the delay time has expired (p9652).
After the function has been selected, the delay timer runs down - even if the function is
deselected during this time. In this case, after the delay time has expired, the STO/SBC
function is selected and then again deselected immediately.
Note
Setting the delay time
So that the drive is able to travel down the OFF3 ramp completely and any motor holding
brake present can be applied, before the pulses have been safely deleted, the delay time
should be set as follows:
• Motor holding brake parameterized: Delay time p9652 ≥ p1135 + p1228 + p1217
• Motor holding brake not parameterized: Delay time p9652 ≥ p1135 + p1228
• The setting of parameter p1135 must be oriented towards the actual braking capability
of the drive.
● The timer (p9652) after whose expiration STO is activated, is implemented with two
channels, although deceleration along the OFF3 ramp is only one channel.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
69
Requirement
● The Basic Functions are enabled via terminals and/or PROFIsafe:
– p9601 = 1, 8 or 9 (hex)
● Enabling Basic Functions via TM54F
– p9601.6 = 1
● In order that the drive can brake down to a standstill even when selected through one
channel, the time in p9652 must be shorter than the sum of the parameters for the data
cross-check (p9650 and p9658). Otherwise the drive will coast down after the time p9650
+ p9658 has elapsed.
Status of Safe Stop 1
The status of the "Safe Stop 1" (SS1) function is displayed using the parameters r9772,
r9872, r9773 and r9774.
As an alternative, the status of the function can be displayed using the configurable message
N01621 (configured using p2118 and p2119).
4.1.2.2
SS1 with external stop
In drive line-ups (e.g. drives that are mechanically connected via the material), the drive-
independent braking on the respective OFF3 ramp can cause problems. If the SS1E function
is used, the safe delay time (p9562) is started when the function is selected, but no OFF3 is
triggered. The higher-level controller still enters the setpoint. The controller receives the
information that SS1E has been selected via the Safety Info Channel.
WARNING
Danger to life due to unsupervised axis motion
During the unsupervised delay time, for "Safe Stop 1 (time-controlled) with external stop",
unsupervised axis motion is possible.
• If there is a hazard due to unwanted movement in your application, take measures to
counter it, for example, by using a brake with safe monitoring. For more information, see
Chapter "Safe Brake Control (SBC) (Page 71)".
Differences between "SS1 with OFF3" and "SS1 with external stop"
"SS1 with OFF3" and "SS1 with external stop" have the following differences:
● In order to activate "Safe Stop 1 with external stop", additionally set p9653 to 1.
● When SS1E is selected, the drive is not braked along the OFF3 ramp, but after the delay
time has expired (p9652), only STO/SBC is automatically initiated.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
70
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1.2.3
Function diagrams and parameters
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2810
SI Basic Functions - STO (Safe Torque Off), SS1 (Safe Stop 1)
• 2811
SI Basic Functions - STO (Safe Torque Off), safe pulse cancellation
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p1135[0...n]
OFF3 ramp-down time
• p1217
Motor holding brake closing time
• p1228
Pulse suppression delay time
• p9601
SI enable functions integrated in the drive (Control Unit)
• p9652
SI Safe Stop 1 delay time (Control Unit)
• r9772.0...23
CO/BO: SI Status (Control Unit)
• r9773.0...31
CO/BO: SI Status (Control Unit + Motor Module)
• r9774.0...31
CO/BO: SI Status (group STO)
Only for "Safe Stop 1 (time-controlled) with external stop"
• p9653
SI Safe Stop 1 drive-based braking response
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
71
4.1.3
Safe Brake Control (SBC)
The "Safe Brake Control" function (SBC) is used to safely control holding brakes that
function according to the closed-circuit principle (e.g. motor holding brake).
The opening and closing of the brake is controlled by the Motor Module / Power Module.
Terminals are available for this on the device in booksize format. A Safe Brake Relay is also
required for the "Safe Brake Control" in the blocksize format. A Safe Brake Adapter is
required in the chassis format (starting with article numbers ending with ...3). When the
Power Module is configured automatically, the Safe Brake Relay is detected and the motor
holding brake type is defaulted (p1278 = 0).
Brake activation via the brake connection on the Motor Module / Safe Brake Relay (SBR) /
Safe Brake Adapter (SBA) involves a safe, two-channel method.
Note
No SBC for SINAMICS HLA
SINAMICS HLA does not support Safe Brake Control.
Note
Controlling the brake via a relay for "Safe Brake Control":
If you use the "Safe Brake Control (SBC)" function, the use of relays/contactors can cause
faults in the brake control when brakes are switched. For this reason, this type of control is
not generally enabled.
WARNING
Danger to life as a result of undesirable motor motion due to defective brake
"Safe Brake Control" does not detect mechanical defects of the brake.
A cable break or a short-circuit in the brake winding is only detected when the state
changes, i.e. when the brake either opens and/or closes. In SINAMICS S120M, a cable
break is only identified when opening the brake.
For devices in chassis format with connected Safe Brake Adapter, the connecting cable
between the Safe Brake Adapter and the motor brake is not monitored for cable break or
short-circuit.
The aforementioned defects may trigger unwanted motor motion, which may result in
physical injury or death.
• In particular, ensure the brake is not powered from an external source. Information on
this topic can be found in EN 61800-5-2:2007, Appendix D.
• During commissioning, test the brake using the Safety Integrated Extended Function
"Safe Brake Test (SBT)" (for further information, see Section "Safe Brake Test (SBT)
(Page 132)").
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
72
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Functional features of "Safe Brake Control"
● SBC is executed when "Safe Torque Off" (STO) is selected.
● In contrast to conventional brake control, SBC is executed via two channels.
● SBC is executed regardless of the brake control or mode set in p1215. However, SBC
does not make sense for 1215 = 0 or 3.
● The function must be enabled using parameters.
● When the state changes, electrical faults, such as a short circuit in the brake winding or
wire breakage can be detected.
Enabling the "Safe Brake Control" function
The "Safe Brake Control" function is enabled via parameter p9602.
The SBC function can be used only together with STO. The selection of SBC alone is not
possible.
Two-channel brake control
Note
Connecting the brake
The brake cannot be directly connected to the Motor Module in chassis format: A Safe Brake
Adapter is also required.
The brake is controlled from the Control Unit. Two signal paths are available for applying the
brake.
Image 4-2
Two-channel brake control, blocksize (example)
For the "Safe Brake Control" function, the Motor/Power Module assumes a monitoring
function to ensure that when the Control Unit fails or malfunctions, the brake current is
interrupted therefore closing the brake.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
73
The brake diagnosis can only reliably detect a malfunction in either of the switches
(TB+, TB-) when the status changes, i.e. when the brake is released or applied.
If the Motor Module or Control Unit detects a fault, the brake current is switched off. The
brake then closes and a safe state is reached.
4.1.3.1
SBC for Motor Modules in the chassis format
To be able to set higher power in the brakes of devices of this format, an additional Safe
Brake Adapter (SBA) module is needed. For more information about connecting and wiring
the Safe Brake Adapter, refer to the "SINAMICS G130/G150/S120 Chassis/S120 Cabinet
Modules/S150 Safety Integrated" Function Manual.
Using parameter p9621, you can define via which digital input the relay (NO contacts)
feedback signal of the Safe Brake Adapter is routed to the Control Unit.
To evaluate the feedback signal contacts, you must maintain the wait times caused by the
SBA. Parameter p9622 is pre-assigned with the SBA-relay wait times:
● p9622[0] ≙ wait time, switching on
● p9622[1] ≙ wait time, switching off
Further functionality and the activation of the brake, i.e. reaching the safe status, are in this
case the same as the above described procedure for booksize devices.
Safe Brake Control with power units in a parallel connection
Note
SBC for parallel connection of power units
Safe Brake Control with power units in a parallel connection is available if r9771.14 = 1.
If you wish to use SBC with SBA for chassis format power units connected in parallel, then it
is only permissible that you connect precisely one SBA to a power unit in the parallel
connection. The Safe Brake Adapter and therefore the brake are controlled via this power
unit.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
74
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
There are two options for registering this power unit with the system:
● Automatic brake identification when commissioning the system for the first time
– Requirements:
- No Safety Integrated functions enabled
- p1215 = 0 (no motor holding brake available)
– During the first commissioning, SINAMICS checks at which power unit an SBA is
connected. If precisely one SBA is found, the number of the power unit is entered into
parameter p7015.
If several SBAs are found at the parallel-connected power units, message "F07935
drive: Motor holding brake configuration error" is output.
– For devices in the chassis format, if the SBA feedback signal (SBA_DIAG) is read in
via an input of the power unit, then in addition, this digital input is automatically
entered into parameter p9621.
● Manually defining the power unit
– Enter the component number of the power unit, to which the SBA is connected, into
parameter p7015. If no SBA is connected to the power unit, faults are detected when
controlling the motor holding brake and fault F01630 is output.
– In parameter p9621 (p9621 = BICO interconnection to r9872.3), enter the digital input
of the power unit to which the SBA is connected and via which the SBA feedback
signal (SBA_DIAG) is read in.
Note
Disconnecting the brake cable for service purposes
As long as the brake is permanently released and not actuated, it is possible to briefly
disconnect the brake cable, e.g. for service purposes, and not receive fault messages. In the
case of a fault, message F07935 is only output when the brake is controlled.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
75
4.1.3.2
Function diagrams and parameters
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2814
SI Basic Functions - SBC (Safe Brake Control), SBA (Safe Brake Adapter)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p0799
CU inputs/outputs, sampling time
• p1215
Motor holding brake configuration
• p7015
Par_circuit holding brake power unit data set
• p9602
SI enable safe brake control (Control Unit)
• p9621
BI: SI Safe Brake Adapter signal source (Control Unit)
• p9622[0...1]
SI SBA relay wait times (Control Unit)
• r9771.14
SI common functions (Control Unit): SBC supported for parallel connection
• r9780
SI monitoring cycle (Control Unit)
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
76
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1.4
Safety faults
The fault messages of the Safety Integrated Basic Functions are saved in the standard
message buffer and can be read out from there. By contrast, the fault messages of the
Safety Integrated Extended Functions are stored in a separate Safety message buffer (see
Chapter "Message buffer (Page 371)").
When faults associated with Safety Integrated Basic Functions occur, the following stop
responses can be initiated:
Table 4- 1
Stop responses for Safety Integrated Basic Functions
Stop response
Triggered ...
Action
Effect
STOP A cannot
be acknowledged
For all Safety faults with pulse
suppression that cannot be
acknowledged.
Trigger safe pulse suppres-
sion via the switch-off signal
path for the relevant monitor-
ing channel. During operation
with SBC:
Apply motor holding brake.
The motor coasts to a standstill
or is braked by the holding brake.
STOP A
For all acknowledgeable Safety
faults
As a follow-up reaction of STOP F
STOP A corresponds to Stop Category 0 in accordance with EN 60204-1.
With STOP A, the motor is switched directly to zero torque via the "Safe Torque Off (STO)" function.
A motor at standstill cannot be started again accidentally.
A moving motor coasts to standstill. This can be prevented by using external braking mechanisms, e.g.
holding or operating brake.
When STOP A is present, "Safe Torque Off" (STO) is active.
STOP F
If an error occurs in the data cross-
check.
Transition to STOP A.
Follow-up response STOP A
with adjustable delay (factory
setting without delay) if one of the
safety functions is selected
STOP F is permanently assigned to the data cross-check (DCC). In this way, errors are detected in the
monitoring channels.
After STOP F, STOP A is triggered.
When STOP A is present, "Safe Torque Off" (STO) is active.
WARNING
Danger to life due to an uncontrolled movement of the axis
With a vertical axis or a pulling load, there is a danger of uncontrolled movement of the axis
when STOP A/F if triggered.
This can cause serious injury or death to persons in the danger zone.
• If there is a hazard due to unwanted movement in your application, take measures to
counter it, for example, by using a brake with safe monitoring. For additional information,
see Section "Safe Brake Control (SBC) (Page 71)".
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
77
Acknowledging the Safety faults
There are several ways to acknowledge Safety faults:
● Acknowledgment through deselection of STO or SS1:
– Remove the cause of the fault.
– Deselect "Safe Torque Off" (STO) or "Safe Stop 1" (SS1).
– Acknowledge the fault.
If the Safety commissioning mode is excited when the Safety functions are switched off
(p0010 ≠ 95 when p9601 = 0), all Safety faults can be acknowledged.
Once safety commissioning mode has been selected again (p0010 = 95), all the faults
that were previously present reappear.
● The higher-level controller sets the signal "Internal Event ACK" via the PROFIsafe
telegram (STW bit 7). A falling edge in this signal resets the status "Internal Event" and so
acknowledges the fault.
● Acknowledgment by switching the drive unit off/on
Safety faults can also be acknowledged (as with all other faults) by switching the drive
unit off and then on again (POWER ON). If this action has not eliminated the fault cause,
the fault is displayed again immediately after power-up.
Description of faults and alarms
Note
References
The faults and alarms for SINAMICS Safety Integrated functions are described in the
following document:
References: SINAMICS S120/S150 List Manual
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
78
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.1.5
Forced dormant error detection (test stop)
Forced dormant error detection or test of the switch-off signal paths (test stop) for Safety Integrated
Basic Functions
The forced dormant error detection function (test stop) at the switch-off signal paths is used
to detect software/hardware faults at both monitoring channels in time and is automated by
means of activation/deactivation of the "Safe Torque Off" (STO) or "Safe Stop 1" (SS1)
function.
To fulfill the requirements of ISO 13849-1 regarding timely error detection, the two switch-off
signal paths must be tested at least once within a defined time to ensure that they are
functioning properly. This functionality must be implemented by means of forced dormant
error detection (test stop), triggered either in manual mode or by the automated process.
A timer ensures that forced dormant error detection (test stop) is carried out in a timely
fashion.
● p9659 SI forced dormant error detection, timer.
A forced dormant error detection (test stop) must be performed on the switch-off signal paths
at least once during the time set in this parameter.
Once this time has elapsed, an alarm is output and remains active until forced dormant error
detection (test stop) is carried out.
The timer returns to the set value each time the STO/SS1 function is deactivated.
When the appropriate safety devices are implemented (e.g. protective doors), it can be
assumed that running machinery will not pose any risk to personnel. As a consequence, the
user is only made aware of the forced checking procedure (test stop) that is required using
an alarm, and is requested to perform the forced checking procedure (test stop) at the next
possible opportunity. This alarm does not affect machine operation.
The user must set the time interval for carrying out forced dormant error detection (test stop)
to between 0.00 and 9000,00 hours depending on the application (factory setting: 8.00
hours).
Examples of when forced dormant error detection (test stop) must be performed:
● When the drives are at a standstill after the system has been switched on (POWER ON).
● When the protective door is opened.
● At defined intervals (e.g. every 8 hours).
● In automatic mode (time and event dependent).
● The maximum time interval is one year (8760 hours).
Forced dormant error detection (test stop) can be automatically executed at POWER ON.
● If the forced dormant error detection (test stop) as well as the test of the F-DO for the
CU310-2 are to be executed automatically, then set p9507.6 = 1. When testing the FD-O
of the CU310-2, you must parameterize p10042 and activate the test in p10046.
● If the forced dormant error detection (test stop) of the F-DI and F-DO of the TM54F is to
be executed automatically, then set p10048 = 1.
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
79
● If you have parameterized the forced dormant error detection (test stop) for POWER ON,
you can still initiate a forced dormant error detection (test stop) at any time through the
application.
● If the automatically initiated function cannot be correctly completed as a result of a
problem (e.g. communication failure), then after the problem has been resolved, the
function is automatically restarted.
● After the forced dormant error detection (test stop) has been successfully executed, the
converter goes into the "Ready" state.
● Timer p9659 is automatically reset as a result of the forced dormant error detection (test
stop).
● The automatic forced dormant error detection (test stop) for POWER ON does not
influence the Safety Integrated functions.
Note
Resetting the timer of the basic functions
• If the Extended Functions and the associated forced dormant error detection (test stop)
are used at the same time, the timer of the Basic Functions is also reset.
Discrepancy is not checked at the terminals used to select the Basic Functions as long as
STO is set by the Extended Functions. This means that the forced dormant error
detection (test stop) of the basic functions must be performed by the Extended Functions
without simultaneous selection of STO or SS1. It is otherwise not possible to verify the
correct control through the terminals.
• The timer is also reset if you first select "Change settings" and then "Activate settings" in
the start screen of the configuration in STARTER.
4.1.6
Function diagrams and parameters
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2800
SI Basic Functions - Parameter manager
• 2802
SI Basic Functions - Monitoring functions and faults/alarms
• 2890
SI TM54F - Overview
• 2891
SI TM54F - Parameter manager
• 2900
SI TM54F - Basic Functions control interface (p9601.2/3 = 0, p9601.6 = 1)
• 2901
SI TM54F - Basic Functions Safe State selection
• 2902
SI TM54F - Basic Functions assignment (F-DO 0 ... F-DO 3)
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
80
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2
Safety Integrated Extended Functions
Note
PFH values
The PFH values of the individual SINAMICS S120 safety components can be found at:
http://support.automation.siemens.com/WW/view/de/76254308
4.2.1
License for Extended Functions
● For operation of the Safety Integrated Extended Functions, one license is required for
each axis. You enter the associated license key with the "License Key" button in
STARTER. Then activate the license key using Activate.
As an alternative, you can enter the license key into parameter p9920 in the ASCII code.
The license key is activated using parameter p9921 = 1.
● For information on how to generate the license key for the product "SINAMICS Safety
Integrated Extended Functions", read the section "Licensing" in the SINAMICS S120
Function Manual. An insufficient license is indicated via the following alarm and LED:
– A13000 --> License not sufficient
– LED RDY --> Flashes greed/red at 0.5 Hz
● When purchasing your drive, you can already decide to use Safety Integrated functions,
and you will then be provided with the required license(s) on the memory card supplied.
In this case, you do not have to explicitly activate the licenses.
4.2.2
Differences between Extended Functions "with encoder" and "without encoder"
If motors without a (safety-capable) encoder are being used, not all Safety Integrated
functions can be used. You will find general information on this distinction in Chapter "Drive
monitoring with or without encoder (Page 32)."
Activation
For activation of the Safety Integrated Extended Functions "with encoder" and "without
encoder", set the parameters p9306 and p9506 (factory setting = 0). You can also make this
setting by selecting "with encoder" or "without encoder" on the Safety Integrated STARTER
screen. You will find this STARTER screen in every drive under "Functions > Safety
Integrated."
● Operation with encoder
p9506 = 0 or p9506 = 2
● Operation without encoder
p9506 = 1 or p9506 = 3
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
81
Monitoring with an encoder
The Safety Integrated Functions with encoder are configured with p9506 = 0 (factory setting)
or p9506 = 2 in the expert list or by selecting "with encoder" in the Safety screen.
● If p9506 = 0:
Braking is monitored with the "Safe Acceleration Monitor" function.
● If p9506 = 2:
Here, also for SS1, the monitoring function "Safe Brake Ramp" is active.
More detailed information on actual value acquisition with encoder can be found in Section
"Notes regarding safe actual value sensing using an encoder system (Page 147)".
Monitoring without an encoder
The Safety Integrated functions without encoder are configured in the expert list using p9506
= 1 or p9506 = 3 or by selecting "without encoder" in the Safety screen form.
● For p9506 = 1, the following applies:
Here, also for SS1, the monitoring function "Safe Brake Ramp" is active.
● For p9506 = 3, the following applies:
Braking is monitored with the "Safe Acceleration Monitor" function. The behavior
corresponds to "monitoring with encoder".
Taking into account the slip of an induction motor
For Safety Integrated without encoder (depending on the drive load), as a result of slip
(deviations between electrical and mechanical speed), deviations can occur between the
safely determined electrical speed and the mechanical speed at the motor shaft.
Note
Sudden changes in the current and voltage curve (e.g. sudden change in the setpoint setting
and load) and very small absolute values with a high proportion of noise generally result in
faults of the safe encoderless actual value acquisition and must be avoided.
More detailed information on actual value acquisition without encoder can be found in
Section "Notes regarding setting parameters for safe actual value sensing without encoder
(Page 154)".
Note
Scope of functions
There are fewer Safety Integrated Extended Functions available "without encoder" than "with
encoder" (see Section "Drive monitoring with or without encoder (Page 32)").
Note
Safety Integrated functions "without encoder" for group drives
The Safety Integrated functions "without encoder" are also permitted for group drives
(several motors connected to one power unit).
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
82
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
"Parking" state for Safety Integrated Extended Functions with encoder
Note
Extended Functions with encoder and "parking"
When a drive object, for which Safety Integrated Extended Functions with encoder are
enabled, is switched to "Park" mode, the Safety Integrated software responds by selecting
STO without generating a separate message. This internal STO selection is displayed in
parameter r9772.19.
4.2.3
Restrictions for Safety Integrated Functions "without encoder"
Basic Functions
The Basic Functions are available without any restrictions in all control modes, with and
without an encoder, for synchronous, induction, and reluctance motors.
A safety-related encoder is not required for Basic Functions.
The Safety Integrated functions "without encoder" are also permitted for group drives
(several motors connected to one power unit).
Extended Functions
Extended Functions SS1, SLS, SDI and SSM "without encoder" do not require safety-related
speed actual value sensing. If an encoder is used for the drive control, this has no influence
on the sensorless safety functions. They can be used with induction motors in all control
modes, as well as with SIEMOSYN synchronous motors with U/f control.
The Safety Integrated functions "without encoder" are also permitted for group drives
(several motors connected to one power unit).
Note
The slip of an induction motor must be taken into account
For Safety Integrated without encoder (depending on the drive load), as a result of slip for
induction motors (deviations between electrical and mechanical speed), deviations can occur
between the safely determined electrical speed and the mechanical speed at the motor
shaft.
When using Extended Functions, observe the following restrictions.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
83
Inadmissible operating modes for Safety Integrated Functions "without encoder"
● No operation with SINAMICS Hydraulic Drive (HLA)
● Current controller clock cycles 31.25 µs and 62.5 μs (for Double Motor Modules with two
configured safety drives) are not permissible.
● For the independent setting of current controller clock cycle and pulse frequency in
conjunction with Safety Integrated "without encoder", the following system clock cycles
are not permitted:
– Double Motor Module: <125 μs
– All other components: <62.5 μs
– p9589 must be set = 3300 to allow the current controller clock cycle and pulse
frequency to be independently set.
● For chassis format devices, the following also applies:
– For chassis format devices, operation without encoder is only permissible for induction
motors, however not for synchronous motors.
– No operation involving parallel connections
– Optimized pulse patterns cannot be selected for SIMOTICS FD
– Only using parameter p1810 = factory setting, this includes:
- No wobbling
- No fine setting of the pulse frequency
● No "shaft generator" functionality
● Induction motors up to 1000 kW
On very large machines, it may also be necessary to adjust the parameter p9585.
Critical operating modes for Safety Integrated Functions "without encoder"
When the safety functions are deactivated, the following technology functions are not
negatively influenced.
When using the following operating modes with the Safety Integrated functions activated
without encoder, this can result in errors in the encoderless safe actual value sensing (see
messages C01711, C30711 with fault values 1040 ff.).
Safe, encoderless actual value sensing is based on the measurement of current and voltage
variables, which can influence the following functions. This does not result in unsafe states.
However, this fault can be expected to have a negative impact on availability.
Note
Irregular operating states
Note that in irregular operating states (e.g. "stalled motor"), the converter can fail with safety
faults. However, under no circumstances is an unsafe state reached.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
84
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
● Current limiting of the power unit
When the current limitation of the power unit responds, a fault of the encoderless safe
actual value acquisition and a consequent stop response can be expected.
Note
When engineering the drive and when the parameterizing the current and torque limits, it
must be ensured that the power unit current limiting does not respond.
● Operation with pulling loads
It is not permissible that the converter is forced into regenerative operation as a result of
external forces.
Note
If a coupled drive comprises an electric drive that motors and one that regenerates (e.g. a
test stand), and the speeds of both drives are safely monitored, safety functions without
encoder can be used. This is because in the case of a fault, the motoring drive
recognizes when a limit value is violated. If, in this example, the motoring drive is an
internal combustion engine, which is not safely monitored, then it is not permissible to use
safety functions without encoder for the braking drive.
Winders with a motoring and a braking drive can be assessed in the same way (both
drives are monitored).
● Motor data identification
When using the measuring functions (stationary and rotating measurement) to determine
the motor data, then it can be assumed that the encoderless safe actual value sensing
will have an error.
Note
The motor data identification should always be performed before commissioning the
Safety Integrated Functions.
● Data set switchover
The motor and drive data switchover can always be used for safety functions without
encoder. It is not possible to switch over between induction and synchronous motors (this
is interlocked). For several motor data sets it must be ensured that all motors have the
same number of pole pairs. If the number of pole pairs in r0313 is not the same value that
was taken into account when configuring the safe actual value sensing (gearbox), then
the calculated, safe actual speed no longer corresponds to the mechanical speed of the
shaft.
When SLS is activated, the shaft can rotate faster than the configured limits.
● Alternating acceleration/deceleration
For alternating acceleration and deceleration, it must be ensured that the following
conditions are maintained.
– Within 1 s, only one acceleration and one braking ramp are permitted.
Therefore, for a cycle 0 → +nset → -nset → 0 – one period of at least 2 s is required.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
85
● This also applies to positioning operation; it may be necessary that the position control
settings and traversing profiles must be adapted so that no overshoots occur in the speed
characteristic (e.g. reduce the dynamic response, use flatter braking ramps).
● Flying restart
A flying restart should not be performed in operation with the Safety Integrated Functions
active.
Note
If you must use this function, then before the flying restart, you can deactivate the Safety
Integrated Functions, and then reactivate them again after the flying restart has been
completed.
In this case, the user must check as to whether it is permissible that the safety functions
are deactivated during the flying restart.
It is only permissible to activate and deactivate Safety Integrated Functions using fail-safe
signals.
● DC brake
When using this function, DC current is impressed to brake the drive: This can result in a
fault of the encoderless safe actual value acquisition and a consequent stop response.
Note
If you must use this function, then before braking, you can deactivate the Safety
Integrated Functions, and then reactivate them again after braking has been completed.
In this case, the user must check as to whether it is permissible that the safety functions
are deactivated during braking.
It is only permissible to activate and deactivate Safety Integrated Functions using fail-safe
signals.
Recommendations for stable operation with active Extended Functions without encoder
The following preconditions must be fulfilled to avoid fault messages from the safe actual
value sensing without encoder:
● The motor and the power unit are adequately dimensioned for this application.
● Motor and power unit should fulfill the following condition: The ratio between the rated
power unit current (r0207[0]) and rated motor current (p0305) should be less than 5.
● Before commissioning the safety functions, we recommend that the motor data are
identified at standstill and a rotating measurement is carried out.
● For the basic commissioning, i.e. before the safety commissioning, the closed-loop
control should be optimally set. The following effects should be avoided:
- speed overshoots
- current peaks and/or discontinuous/unsteady current actual value over time
- voltage peaks and/or discontinuous/unsteady voltage actual value over time
- the lowest possible amount of noise in the current and voltage
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
86
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Safety Integrated Extended Functions without encoder for Control Unit Adapter CUA31 and CUA32
In the case of the control unit adapters CUA31 and CUA32, the Safety Integrated Extended
Functions without encoder with SINAMICS firmware version 4.5 (or higher) are available as
follows:
Control Unit
Adapter
Article number
Safety Integrated without encoder
SINAMICS firm ware version 4.5 (or higher)
Not available for
Available for
CUA31
6SL3040-0PA01-0AA1
Version (function states) A, B and C
Version D or newer
CUA32
6SL3040-0PA01-0AA0
Version (function states) A and B
Version C or newer
4.2.4
Safe Torque Off (STO)
For the control options and the functionality for "Safe Torque Off" (STO), see Section "Safe
Torque Off (STO) (Page 62)".
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
87
4.2.5
Safe Stop 1 (SS1)
4.2.5.1
Safe Stop 1 with encoder
For function SS1 of the Extended Safety Functions, braking monitoring is included.
● If p9506 = 0:
Braking is monitored with the "Safe Acceleration Monitor" function (see Chapter "Safe
Acceleration Monitor (SAM) (Page 142)").
In this case, we also talk about "SS1 (time and acceleration controlled)".
● If p9506 = 2:
Here, also for SS1, the monitoring function "Safe Brake Ramp" is active (see Chapter
"Safe Brake Ramp (SBR) (Page 144)").
In this case, we also talk about "SS1 (speed controlled)".
The "Safe Stop 1" (SS1) function allows the drive to be stopped according to EN 60204-1,
Stop Category 1. The drive brakes with the OFF3 ramp (p1135) once "Safe Stop 1" is
selected and switches to "Safe Torque Off" (STO) once the delay time has elapsed (p9556)
or when the shutdown speed is fallen below (p9560).
Functional features of Safe Stop 1 with encoder
● The delay time starts after the function has been selected. If SS1 is deselected within this
time, after the delay time has elapsed or after the velocity has fallen below the shutdown
speed, the STO function is selected and deselected again immediately; i.e. the SS1
function is ended completely normally. It cannot be interrupted.
● Selection and monitoring of the acceleration (SAM) or the monitoring function "Safe
Brake Ramp" are implemented in two channels, but braking along the OFF3 ramp is only
implemented in one channel.
Note
Interrupting the ramp function with OFF2 by the higher-level controller
Activating SS1 can mean that the higher-level controller (PLC, motion controller), which
specifies the speed setpoint, interrupts the ramp function (e.g. with OFF2). The device
behaves in this way as a result of a fault reaction triggered by OFF3 activation. This fault
reaction must be avoided by assigning appropriate parameters or configurations.
Note
No OFF2 with SS1 and EPOS
If you use SS1 together with EPOS, the fault reaction to F07490 (EPOS: enable withdrawn
while traversing) OFF2 is not permitted. The response to this error message (OFF1, OFF2 or
OFF3) can be configured via p2100/p2101.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
88
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Commissioning
The delay time (SS1 time) is set by entering parameter p9556. The wait time until safe pulse
suppression (STO) can be shortened by specifying a shutdown speed in p9560.
To enable the drive to brake to standstill after selection, the time in p9556 must be selected
to be large enough for the drive to be able to brake along the OFF3 ramp (p1135) from any
speed of the work process to below the shutdown speed (p9560).
Note
Setting the delay time
To enable the drive to travel the entire OFF3 ramp and close any existing motor holding
brake, you must set the delay time as follows:
• Motor holding brake parameterized: Delay time ≥ p1135 + p1228 + p1217
• Motor holding brake not parameterized: Delay time ≥ p1135 + p1228
The shutdown speed defined in p9560 must be set in such a way that coasting down (due to
the subsequent STO function) does not represent any risk for man and machine.
Responses: System error
1. STOP F with subsequent STOP B, followed by STOP A
2. Safety message C01711
Status for "Safe Stop 1"
The status of the "Safe Stop 1" function is displayed using the following parameters:
● r9722.1 CO/BO: SI Motion drive-integrated status signals, SS1 active
● r9722.0 CO/BO: SI Motion drive-integrated status signals, STO or safe pulse suppression
active
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
89
4.2.5.2
Safe Stop 1 without encoder
Two encoderless Safe Stop 1 (SS1) monitoring functions can be set with parameter p9506:
● p9506 = 3: Safe monitoring of acceleration (SAM) / delay time
The function is identical to "Safe Stop 1" with encoder, which was described in the
previous section.
In this case, we also talk about "SS1 (time and acceleration controlled)".
● p9506 = 1: Safe brake ramp monitoring (SBR)
In this case, there is no SS1 delay time active. The transition from SS1 to STO depends
entirely on the speed falling below the shutdown speed (p9560). You will find more
information on the function "Safe Brake Ramp (SBR)" in Chapter "Safe Brake Ramp
(SBR) (Page 144)." In this case, we also talk about "SS1 (speed controlled)".
Image 4-3
Sequence for "Safe Stop 1" without encoder with SBR monitoring (p9506 = 1)
Functional feature of Safe Stop 1 without encoder
● Selection and monitoring of the brake ramp (SBR) or the acceleration (SAM) are
implemented in two channels, however braking at the OFF3 ramp is only through one
channel.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
90
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2.5.3
Safe Stop 1 with external stop
General description
NOTICE
Danger to life due to any axis movement
During the delay time (p9652), for "Safe Stop 1 (time-controlled) with external stop," any
axis movements are possible.
• If there is a hazard due to unwanted motion in your application, take measures to
counter it, for example, by using a brake with safe monitoring. Further information can
be found in Section "Safe Brake Control (Page 91)".
With external stop, "Safe Stop 1" basically works exactly as described in the previous
Chapters "Safe Stop 1 with encoder (time and acceleration controlled)" and "Safe Stop 1
without encoder (speed controlled)." Note, however, the following differences:
Differences between "Safe Stop 1 with OFF3" and "SS1 with external stop"
● In order to activate "Safe Stop 1 with external stop", additionally set p9507.3 = 1.
● When SS1 with external stop is selected, the drive is not braked along the OFF3 ramp:
You are responsible in applying suitable measures to brake the drive. After the delay time
has expired (p9556), only STO/SBC are automatically initiated. After the function has
been selected, the delay timer runs down - even if the function is deselected during this
time. In this case, after the delay time has expired, the STO/SBC function is selected and
then again deselected immediately.
● The brake ramp (SBR) and the acceleration (SAM) are not monitored and there is no
standstill detection.
● With this configuration, STO becomes active after the SS1 timer p9556 has expired; this
also applies if SBR has been configured.
● Further information can be found in Section Stop responses (Page 365).
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
91
4.2.5.4
Function diagrams and parameters
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2819
SI Extended Functions - SS1, SS2, SOS, internal STOP B, C, D, F
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p1135[0...n]
OFF3 ramp-down time
• p9501
SI Motion enable safety functions (Control Unit)
• p9506
SI Motion function specification (Control Unit)
• p9560
SI Motion STO shutdown speed (Control Unit)
• r9722.0...31
CO/BO: SI Motion drive-integrated status signals
Only for SS1 (Extended Functions) with external stop
• p9507
SI Motion function configuration (Control Unit)
4.2.6
Safe Brake Control (SBC)
For the control options and the functionality for "Safe Brake Control" (STO), see Section
"Safe Brake Control (SBC) (Page 71)".
Note
No SBC for SINAMICS HLA
SINAMICS HLA does not support Safe Brake Control.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
92
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2.7
Safe Operating Stop (SOS)
This function serves for fail-safe monitoring of the standstill position of a drive.
WARNING
Danger to life: Drive can be forced out of the SOS position by mechanical forces
Mechanical forces greater than the maximum drive torque may force a drive currently
operated in the position control mode out of the Safe Operating Stop (SOS) and trigger stop
function category 1 according to EN 60204-1 (fault response function STOP B).
• If there is a hazard due to unwanted movement in your application, take measures to
counter it, for example, by using a brake with safe monitoring. For further information,
see Chapter "Safe Brake Control (SBC) (Page 71)."
Note
SOS only with encoder
In particular, the motor is energized while the SOS function is performing position control.
• Ensure that the motor cannot be touched while it is in the SOS state.
Drive stopping is monitored using an SOS tolerance window (p9530).
Note
Size of the tolerance window
The size of the tolerance window should be slightly above the standard standstill monitoring
limit, otherwise the standard monitoring functions will no longer be effective.
Parameter r9731 displays the safe position accuracy (load side) that can be achieved as a
maximum, based on the acquisition of the actual value for the safe motion monitoring
functions.
STOP B is the stop response after the standstill tolerance window has been violated.
The SOS function comes into effect in the following cases:
● After SOS is selected and the delay time in p9551 has elapsed
The drive must be braked to standstill within this delay time (e.g. by the controller).
● As a consequence of SS2
● As a consequence of STOP C (corresponds to selection of SS2)
● As a consequence of STOP D (corresponds to selection of SOS)
● As a consequence of STOP E (corresponds to selecting SOS with additional activation of
the standard "Extended stop and retract (ESR)" function)
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
93
Responses
● Standstill tolerance violated in p9530
– STOP B with subsequent STOP A
– Safety message C01707
● System error
– STOP F
– Safety message C01711
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2819
SI Extended Functions - SS1, SS2, SOS, internal STOP B, C, D, F
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p9501
SI Motion enable safety functions (Control Unit)
• p9530
SI Motion standstill tolerance (Control Unit)
• p9551
SI Motion SLS(SG) switchover/SOS(SBH) delay time (CU)
• r9722.0...31
CO/BO: SI Motion drive-integrated status signals
• r9731
SI Motion safe positioning accuracy
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
94
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2.8
Safe Stop 2 (SS2)
Note
The "Safe Stop 2" (SS2) safety function can only be used with an encoder.
The safety function "Safe Stop 2" (SS2) is used to brake the motor of the OFF3 deceleration
ramp (p1135) safely with transition after the delay time (p9552) has expired in to the SOS
state (see Chapter "Safe Operating Stop (SOS) (Page 92)"). The delay time set must allow
the drive to brake to a standstill from every speed of the operating process within this time.
The standstill tolerance (p9530) may not be violated after this time.
After braking, the drives remain in speed control mode with the speed setpoint n = 0. The full
torque is available.
The default setpoint (e.g. from the setpoint channel, or from a higher-level controller)
remains inhibited as long as SS2 is selected.
During braking, one of the following functions is active:
● If p9506 = 0:
Braking is monitored with the "Safe Acceleration Monitor" function (see Chapter "Safe
Acceleration Monitor (SAM) (Page 142)").
● If p9506 = 2:
Here, also for SS1, the monitoring function "Safe Brake Ramp" is active (see Chapter
"Safe Brake Ramp (SBR) (Page 144)").
The selection and monitoring of the acceleration (SAM) are realized through two channels –
however, braking along the OFF3 ramp, only through one channel.
Interruption of the ramp function with OFF2
Activating SS2 can mean that the higher-level controller (PLC, motion controller) which
specifies the speed setpoint, interrupts the ramp function (e.g. with OFF2). The device
behaves in this way as a result of a fault reaction triggered by OFF3 activation. This fault
reaction must be avoided by assigning appropriate parameters or configurations.
Responses
● Speed limit violated (SAM):
– STOP A
– Safety message C01706
● Standstill tolerance violated in p9530 (SOS):
– STOP B with subsequent STOP A
– Safety message C01707
● System fault:
– STOP F with subsequent STOP A
– Safety message C01711
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
95
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2814
SI Basic Functions - SBC (Safe Brake Control), SBA (Safe Brake Adapter)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p1135[0...n]
OFF3 ramp-down time
• p9501
SI Motion enable safety functions (Control Unit)
• p9530
SI Motion standstill tolerance (Control Unit)
• p9548
SI Motion SAM actual speed tolerance (Control Unit)
• p9552
SI Motion transition time STOP C to SOS (SBH) (Control Unit)1)
• r9722.0...31
CO/BO: SI Motion drive-integrated status signals
1) STOP C corresponds to SS2.
4.2.8.1
Interaction with EPOS
Since the function SS2 – with its setpoint-independent braking – is not suitable for use with
EPOS, the Safe Operating Stop (SOS) function can be used with delay.
On selection of SOS, the EPOS function "intermediate stop" (p2640 = 0) ensures that EPOS
is able to stop the drive in its tracks and then keep it under control in this state before the
SOS becomes active. The maximum necessary braking time (from p2573 and p2645) must
then be entered in the delay time for SLS/SOS (p9551) with a safety margin: This ensures
that the drive is at a standstill before SOS is active.
To do this, proceed as follows:
1. Connect the EPOS function "intermediate stop" (p2640) with the control signal "Deselect
SOS" (r9720.3).
2. Enter the maximum necessary EPOS braking time (depending on the values set in p2573
and p2645) with a safety margin (approx. +5%) in the SOS delay time (p9551).
Since the STOP C stop response – with its setpoint-independent braking – is not suitable for
use with EPOS, the Safe Operating Stop (SOS) function can be used with delay.
On selection of SOS, the EPOS function "intermediate stop" (p2640 = 0) ensures that EPOS
is able to stop the drive in its tracks and then keep it under control in this state before the
SOS becomes active. The maximum required braking time (from p2573 and p2645) must
then be entered in the "Transition time STOP D to SOS" (p9553) with a small safety margin:
This ensures that the drive is at a standstill before SOS is active.
To do this, proceed as follows:
1. Parameterize "STOP D" as stop response.
2. Connect the EPOS function "intermediate stop" (p2640) with the control signal "Deselect
SOS" (r9720.3).
3. Enter the maximum required EPOS braking time (depending on the values set in p2573
and p2645) with a safety margin (approx. +5%) in the "Transition time STOP D to SOS"
(p9553).
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
96
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2.8.2
SS2 with external stop (SS2E)
WARNING
Danger to life through unexpected axis movement
When function "Safe Stop 2 with external stop" (SS2E) is active, during the delay time
(p9553) the speed follows the setpoint issued from the higher-level control system. As a
consequence, unexpected axis motion is possible, which can lead to severe injury and
death.
• During delay time (p9553), avoid that persons enter the hazardous area of the machine
or system, e.g. by keeping protective equipment closed.
Image 4-4
Selecting function SS2E
With external stop, "Safe Stop 2" functions in principle exactly the same way as described in
the previous sections. Note, however, the following differences:
Differences between "Safe Stop 2 with OFF3" and "SS2 with external stop (SS2E)"
● When SS2 is selected with external stop, the drive does not automatically brake the
motor, but instead, follows the specified speed setpoint.
● During delay time p9553, the brake ramp (SBR) and the acceleration (SAM) are not
monitored and there is no standstill detection.
● SOS becomes active after the delay time p9553 expires.
When function SS2E is active, the higher-level control must issue the speed setpoint so
that at the latest after delay time p9553 expires, the motor has come to a complete
standstill.
● In order to activate "Safe Stop 2 with external stop", set p9501.18 = 1.
● PROFIsafe STW2.28 selects function SS2E. PROFIsafe STW2.28 is included in
telegrams 30, 901 and 902.
● PROFIsafe ZSW2.28 indicates whether function SS2E is active. PROFIsafe ZSW2.28 is
included in telegrams 30, 901 and 902. The associated diagnostics parameter is
r9722.28.
In the "Safety Info Channel", status word S_ZSW3B.11 indicates whether function SS2E
is active. The associated diagnostics parameter is r10234.11.
Diagnostic parameters p9722.28 and p10234.11 are also set during an internal STOP D.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
97
For additional information, see Section "Safety faults (Page 365)".
Deselecting function SS2E while SS2E is active
Image 4-5
Deselecting function SS2E while SS2E is active
After the function has been selected, the delay time starts to expire - even if the function is
deselected during this time. In this case, after the delay time has expired, the SOS function
is briefly active. Afterwards, the drive may accelerate the motor back to the speed setpoint.
Interruption of the active SS2E function by functions SS1 and SS2
Image 4-6
Interruption of function SS2E by functions SS1 (shown at the left) and SS2 (shown at the
right)
When selecting SS1, the drive brakes the motor along the OFF3 ramp and monitors the
speed using the SAM function. Function STO becomes active when the motor is at a
standstill.
When selecting SS2, the drive also brakes the motor along the OFF3 ramp and monitors the
speed using the SAM function. Function SOS becomes active after time p9552.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
98
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2.8.3
Overview of important parameters
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p2573
EPOS maximum delay
• p2594
CI: EPOS maximum speed, externally limited
• p2640
BI: EPOS intermediate stop (0 signal)
• p2645
CI: EPOS direct setpoint input/MDI, deceleration override
• p9551
SI Motion SLS(SG) switchover/SOS(SBH) delay time (CU)
• p9552
SI motion transition time STOP C to SOS (SBH) (Control Unit)
• p9553
SI motion transition time STOP D to SOS (SBH) (Control Unit)
• r9720.0...27
CO/BO: SI Motion drive-integrated control signals
• r9733[0...2]
CO: SI Motion speed setpoint limit active
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
99
4.2.9
Safely-Limited Speed (SLS)
The Safely Limited Speed (SLS) function is used to protect a drive against unintentionally
high speeds in both directions of rotation. This is achieved by monitoring the current drive
speed up to a speed limit.
Safely Limited Speed prevents a parameterized speed limit from being exceeded. Limits
must be specified based on results of the risk analysis. Up to four different SLS speed limits
can be parameterized using parameter p9531[0..3]; it is possible to switch between them
even if the SLS is activated.
An override can also be added to SLS limit value 1. In operation, this override can be varied
using a PROFIsafe telegram.
Note
Deviation of the displayed speed limit
The SLS speed limit displayed in r9714[2] can deviate slightly from the specified SLS speed
limit. The reason for this is the internal resolution (r9732) of the speed values.
Note
Response in the event of a communication error
If p9580 ≠ 0 and SLS is active, in the event of communication failure, the parameterized
ESR reaction is only realized if, as SLS response, a STOP with delayed pulse cancellation
when the bus fails has been parameterized (p9563[0...3] ≥ 10).
Note
Setpoint speed limit and SLS
• It makes sense to configure the set velocity limit if SLS is also parameterized. This is
done in a higher-level controller that evaluates the safety information channel, for
example, or by wiring r9733[0/1] to the speed limits of the ramp-function generator
(p1051/p1052).
• It does not make sense to use the positive and negative setpoint limiting for SLS in
conjunction with standard telegram 105 and others: With this combination, the velocity
setpoint of the standard telegram is only effective after the setpoint limiting.
Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Safety Integrated
100
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
4.2.9.1
Safely Limited Speed (SLS)
Features
● When SLS is selected, the monitoring only takes effect after the configured delay time
has expired (p9551). Within this time, the actual speed must be below the (selected) limit.
The delay time is not effective when SLS is deselected.
● After switching to a lower limit value (p9531), the actual speed of the drive must have
dropped below the new limit within the delay time (p9551). The existing limit remains
active during the delay time. The lower limit value becomes active after the delay time
expires. This also applies to a reduction of the limit value via PROFIsafe.
● If the actual speed of the drive is higher than the new Safely Limited Speed limit after the
delay time has elapsed, a message is generated with the parameterized stop response.
● The stop response (STOP A, STOP B, STOP C, STOP D or STOP E) is parameterized
with p9563.
● During changeover to a higher limit value, the delay time is not active and the high limit
value becomes immediately active. This also applies to increasing the limit value via
PROFIsafe.
● 4 parameterizable limit values p9531[0...3]
● The first limit value can be entered via the PROFIsafe telegrams 901 and 902 (for
p9501.24 = 1)
● In parameter p9533 enter the weighting factor to determine the setpoint limit from the
selected actual speed limit in percent. The active limit value is evaluated using this factor,
and is provided as setpoint limit in r9733.
– r9733[0] = p9531[x] x p9533 (converted from the load to the motor side)
– r9733[1] = - p9531[x] x p9533 (converted from the load to the motor side)
[x] = selected SLS stage
Conversion factor from the motor to the load side:
– Motor type = rotary and axis type = linear: p9522/(p9521 × p9520)
– Otherwise: p9522/p9521
● Limit value
– r9733[0] = p9531[x] x p9533; x = selected SLS limit value
– r9733[1] = - p9531[x] x p9533; x = selected SLS limit value
r9733 is used, for example, for transferring values to a higher-level controller, which can
then, for example, adjust traversing speeds to the SLS levels or at the setpoint channel
(p1051). r9733 is a part of the Safety Info Channel (SIC).
● The currently monitored limit value is displayed in parameter r9714[2].