SEW MOVITRAC LTP-B Operating Instruction
Read Online
Read the SEW MOVITRAC LTP-B Operating Instruction online using the built-in PDF viewer.
Text of the manual
Drive Technology \ Drive Automation \ System Integration \ Services
Operating Instructions
Standard Inverters
MOVITRAC® LTP-B
Edition 09/2016
22872051/EN
Table of contents
Operating Instructions – MOVITRAC® LTP-B 3
Table of contents
1
General information.................................................................................................................. 8
1.1
About this documentation ............................................................................................... 8
1.2
Structure of the safety notes........................................................................................... 8
1.2.1
Meaning of signal words ................................................................................ 8
1.2.2
Structure of section-related safety notes........................................................ 8
1.2.3
Structure of embedded safety notes .............................................................. 8
1.3
Rights to claim under limited warranty............................................................................ 9
1.4
Content of the documentation......................................................................................... 9
1.5
Exclusion of liability......................................................................................................... 9
1.6
Product names and trademarks...................................................................................... 9
1.7
Copyright notice.............................................................................................................. 9
2
Safety notes ............................................................................................................................ 10
2.1
Preliminary information ................................................................................................. 10
2.2
Operator's duties........................................................................................................... 10
2.3
Target group ................................................................................................................. 10
2.4
Designated use............................................................................................................. 11
2.4.1
Hoist applications ......................................................................................... 11
2.5
Functional safety technology ........................................................................................ 12
2.6
Transport....................................................................................................................... 12
2.7
Installation/assembly..................................................................................................... 12
2.7.1
Restrictions of use........................................................................................ 13
2.8
Electrical connection..................................................................................................... 13
2.8.1
Required preventive measure ...................................................................... 13
2.8.2
Stationary application................................................................................... 13
2.9
Protective separation .................................................................................................... 14
2.10
Startup/operation .......................................................................................................... 14
3
Device structure ..................................................................................................................... 15
3.1
Nameplate..................................................................................................................... 15
3.2
Type designation........................................................................................................... 15
3.3
Device structure of the standard inverter...................................................................... 16
3.3.1
Inverters with degree of protection IP20/NEMA 1 ........................................ 16
3.3.2
Inverters with degree of protection IP66/NEMA 4X...................................... 17
3.3.3
Inverters with degree of protection IP55/NEMA 12K.................................... 18
4
Installation............................................................................................................................... 19
4.1
General information ...................................................................................................... 19
4.2
Permitted tightening torques......................................................................................... 20
4.3
Mechanical installation.................................................................................................. 21
4.3.1
IP20 housing: Installation and installation space ......................................... 21
4.3.2
IP55/IP66 housing: Installation and control cabinet dimensions.................. 22
4.4
Electrical installation ..................................................................................................... 23
4.4.1
Before installation......................................................................................... 23
4.4.2
Line contactors............................................................................................. 24
4.4.3
Mains fuses .................................................................................................. 25
22872051/EN – 09/2016
Table of contents
Operating Instructions – MOVITRAC® LTP-B
4
4.4.4
Operation on an IT system........................................................................... 26
4.4.5
Operation on a TN system with an RCD switch (IP20) ................................ 27
4.4.6
Permitted voltage supply systems................................................................ 27
4.4.7
Help card...................................................................................................... 27
4.4.8
Removing the terminal cover ....................................................................... 28
4.4.9
Cable gland plate ......................................................................................... 30
4.4.10
Connecting and installing the braking resistor ............................................. 31
4.4.11
Motor temperature protection TF, TH, KTY84, PT1000 ............................... 32
4.4.12
Multi-motor drive/group drive ....................................................................... 33
4.4.13
Motor cables and fusing ............................................................................... 33
4.4.14
Connecting AC brakemotors ........................................................................ 33
4.4.15
UL-compliant installation .............................................................................. 34
4.4.16
Information regarding UL ............................................................................. 37
4.4.17
Electromagnetic compatibility (EMC) ........................................................... 38
4.4.18
Overview of signal terminals ........................................................................ 44
4.4.19
Communication socket RJ45 ....................................................................... 47
4.4.20
24 V backup mode ....................................................................................... 48
4.4.21
DC link connection ....................................................................................... 49
4.5
Wiring diagram.............................................................................................................. 49
4.5.1
Brake control ................................................................................................ 51
5
Startup ..................................................................................................................................... 52
5.1
User interface................................................................................................................ 52
5.1.1
Keypads ....................................................................................................... 52
5.1.2
Resetting parameters to default settings...................................................... 54
5.1.3
Key combinations......................................................................................... 54
5.1.4
Software LT Shell......................................................................................... 55
5.1.5
MOVITOOLS® MotionStudio engineering software...................................... 57
5.2
Automatic measuring procedure "Auto tune" ............................................................... 59
5.3
Startup for motors ......................................................................................................... 59
5.3.1
Startup for asynchronous motors with V/f control ........................................ 60
5.3.2
Startup for asynchronous motors with VFC speed control........................... 60
5.3.3
Startup for asynchronous motors with VFC torque control .......................... 61
5.3.4
Startup of synchronous motors without encoder feedback (PMVC control).......
62
5.3.5
Startup with LSPM motors from SEW‑EURODRIVE ................................... 63
5.3.6
Startup with preset motors from SEW‑EURODRIVE ................................... 64
5.4
Startup of control........................................................................................................... 65
5.4.1
Terminal mode (factory setting) P1-12 = 0................................................... 65
5.4.2
Keypad mode (P1-12 = 1 or 2)..................................................................... 66
5.4.3
PID controller mode (P1-12 = 3) .................................................................. 66
5.4.4
Master-slave mode (P1-12 = 4).................................................................... 68
5.4.5
Fieldbus mode (P1-12 = 5, 6 or 7) ............................................................... 69
5.4.6
MultiMotion mode (P1-12 = 8)...................................................................... 69
5.5
Hoist function ................................................................................................................ 70
5.5.1
General information...................................................................................... 71
5.5.2
Startup for hoist function .............................................................................. 71
22872051/EN – 09/2016
Table of contents
Operating Instructions – MOVITRAC® LTP-B 5
5.5.3
Hoisting mode .............................................................................................. 72
5.5.4
Troubleshooting and optimizing the hoist function ....................................... 73
5.6
Fire mode/emergency mode......................................................................................... 74
5.7
Operation at 87 Hz characteristic.................................................................................. 75
5.8
Motor potentiometer function – crane application......................................................... 75
5.8.1
Motor potentiometer operation ..................................................................... 76
5.8.2
Terminal assignment.................................................................................... 77
5.8.3
Parameter settings ....................................................................................... 77
5.9
Examples of analog input scaling and offset setting..................................................... 78
5.9.1
Example 1: Analog input scaling .................................................................. 78
5.9.2
Example 2: Analog input offset .................................................................... 79
5.9.3
Example 3: Analog input scaling and offset ................................................. 80
5.10
Fans and pumps ........................................................................................................... 81
5.11
Motor potentiometer...................................................................................................... 81
5.12
3-wire control ................................................................................................................ 82
5.12.1
Control signal source 3-wire control............................................................. 82
6
Operation................................................................................................................................. 83
6.1
Inverter status ............................................................................................................... 83
6.1.1
Static inverter status..................................................................................... 83
6.1.2
Operating state of the inverter...................................................................... 84
6.1.3
Status displays of the parameter module..................................................... 85
6.1.4
Fault reset .................................................................................................... 85
6.2
Troubleshooting ............................................................................................................ 86
6.3
Error history .................................................................................................................. 86
6.4
Error codes ................................................................................................................... 87
7
Fieldbus mode ........................................................................................................................ 92
7.1
General information ...................................................................................................... 92
7.1.1
Structure and settings of process data words .............................................. 92
7.1.2
Communication example.............................................................................. 94
7.1.3
Parameter settings for the inverter............................................................... 94
7.1.4
Connecting the signal terminals at the inverter ............................................ 95
7.1.5
Establishing a CANopen/SBus network ....................................................... 95
7.2
Connecting a gateway or controller (SBus MOVILINK®) .............................................. 96
7.2.1
Specification................................................................................................. 96
7.2.2
Electrical installation..................................................................................... 96
7.2.3
Startup at gateway ....................................................................................... 97
7.2.4
Startup at a CCU.......................................................................................... 98
7.2.5
MOVI‑PLC® motion protocol (P1-12 = 8)...................................................... 98
7.3
Modbus RTU................................................................................................................. 99
7.3.1
Specification................................................................................................. 99
7.3.2
Electrical installation..................................................................................... 99
7.3.3
Register allocation of the process data words ........................................... 100
7.3.4
Data flow example...................................................................................... 101
7.4
CANopen .................................................................................................................... 103
7.4.1
Specification............................................................................................... 103
22872051/EN – 09/2016
Table of contents
Operating Instructions – MOVITRAC® LTP-B
6
7.4.2
Electrical installation................................................................................... 103
7.4.3
COB IDs and functions in the inverter........................................................ 103
7.4.4
Supported transmission modes.................................................................. 104
7.4.5
Default allocation plan of process data objects (PDO)............................... 104
7.4.6
Data flow example...................................................................................... 105
7.4.7
Table of CANopen-specific objects ............................................................ 106
7.4.8
Table of manufacturer-specific objects ...................................................... 108
7.4.9
Emergency code objects............................................................................ 108
8
Service................................................................................................................................... 109
8.1
Electronics Service by SEW‑EURODRIVE................................................................. 109
8.2
Extended storage........................................................................................................ 109
8.3
Waste disposal............................................................................................................ 110
9
Parameters ............................................................................................................................ 111
9.1
Overview of parameters.............................................................................................. 111
9.1.1
Parameters for realtime monitoring (read only).......................................... 111
9.1.2
Parameter register ..................................................................................... 116
9.2
Explanation of the parameters.................................................................................... 122
9.2.1
Parameter group 1: Basic parameters (level 1) ......................................... 122
9.2.2
Parameter group 1: Servo-specific parameters (level 1)............................ 130
9.2.3
Parameter group 2: Extended parameter setting (level 2) ......................... 132
9.2.4
Parameter group 3: PID controller (level 2)................................................ 142
9.2.5
Parameter group 4: Motor control (level 2) ................................................ 145
9.2.6
Parameter group 5: Fieldbus communication (level 2)............................... 151
9.2.7
Parameter group 6: Extended parameters (level 3) ................................... 155
9.2.8
Parameter group 7: Motor control parameters (level 3) ............................. 161
9.2.9
Parameter group 8: Application-specific parameters (only LTX) (level 3).. 164
9.2.10
Parameter group 9: Digital inputs defined by the user (level 3) ................. 166
10
Technical data....................................................................................................................... 173
10.1
Markings ..................................................................................................................... 173
10.2
Ambient conditions...................................................................................................... 174
10.3
Technical data............................................................................................................. 175
10.3.1
1-phase system AC 200 – 240 V ............................................................... 175
10.3.2
3-phase system AC 200 – 240 V ............................................................... 176
10.3.3
3-phase system AC 380 – 480 V ............................................................... 180
10.3.4
3-phase system AC 500 – 600 V ............................................................... 184
10.4
Input voltage ranges ................................................................................................... 187
10.5
Overload capacity ....................................................................................................... 187
10.6
Housing variants and dimensions............................................................................... 188
10.6.1
Housing variants ........................................................................................ 188
10.6.2
Dimensions ................................................................................................ 189
10.6.3
Dimensions ................................................................................................ 190
10.7
Protection function ...................................................................................................... 192
11
Functional safety (STO) ....................................................................................................... 193
11.1
Integrated safety technology....................................................................................... 193
22872051/EN – 09/2016
Table of contents
Operating Instructions – MOVITRAC® LTP-B 7
11.1.1
Safe condition ............................................................................................ 193
11.1.2
Safety concept ........................................................................................... 193
11.1.3
Restrictions ................................................................................................ 196
11.2
Safety conditions......................................................................................................... 197
11.2.1
Storage requirements................................................................................. 197
11.2.2
Installation requirements ............................................................................ 197
11.2.3
Requirements on the external safety controller.......................................... 199
11.2.4
Requirements for safety relays .................................................................. 200
11.2.5
Requirements on startup............................................................................ 200
11.2.6
Requirements on operation........................................................................ 200
11.3
Connection variants .................................................................................................... 202
11.3.1
General information.................................................................................... 202
11.3.2
Disconnection of a single drive .................................................................. 203
11.4
Safety characteristics.................................................................................................. 206
11.5
Signal terminal block for STO safety contact.............................................................. 206
12
Declaration of conformity .................................................................................................... 207
Index ...................................................................................................................................... 208
13
Address list ........................................................................................................................... 214
22872051/EN – 09/2016
About this documentation
Operating Instructions – MOVITRAC® LTP-B
8
1
General information
1.1
About this documentation
This documentation is an integral part of the product. The documentation is written for
all employees who assemble, install, start up, and service this product.
Make sure this documentation is accessible and legible. Ensure that persons respons-
ible for the machinery and its operation as well as persons who work on the product
independently have read through the documentation carefully and understood it. If you
are unclear about any of the information in this documentation or require further in-
formation, contact SEW‑EURODRIVE.
1.2
Structure of the safety notes
1.2.1
Meaning of signal words
The following table shows the grading and meaning of the signal words for safety
notes.
Signal word
Meaning
Consequences if disregarded
DANGER
Imminent hazard
Severe or fatal injuries.
WARNING
Possible dangerous situation
Severe or fatal injuries.
CAUTION
Possible dangerous situation
Minor injuries
NOTICE
Possible damage to property
Damage to the drive system or its
environment.
INFORMATION
Useful information or tip: Simplifies
handling of the drive system.
1.2.2
Structure of section-related safety notes
Section-related safety notes do not apply to a specific action but to several actions
pertaining to one subject. The hazard symbols used either indicate a general hazard
or a specific hazard.
This is the formal structure of a safety note for a specific section:
SIGNAL WORD
Type and source of hazard.
Possible consequence(s) if disregarded.
•
Measure(s) to prevent the hazard.
1.2.3
Structure of embedded safety notes
Embedded safety notes are directly integrated into the instructions just before the de-
scription of the dangerous action.
This is the formal structure of an embedded safety note:
SIGNAL WORD Type and source of hazard. Possible consequence(s) if disreg-
arded. Measure(s) to prevent the hazard.
22872051/EN – 09/2016
Rights to claim under limited warranty
Operating Instructions – MOVITRAC® LTP-B 9
1.3
Rights to claim under limited warranty
Read the information in this documentation. This is essential for fault-free operation
and fulfillment of any rights to claim under limited warranty. Read the documentation
before you start working with the product.
1.4
Content of the documentation
The current version of the operating instructions is the original.
This document contains additional safety-relevant information and conditions for use
in safety-related applications.
1.5
Exclusion of liability
Read the information in this documentation, otherwise safe operation is impossible.
You must comply with the information contained in this documentation to achieve the
specified product characteristics and performance features. SEW‑EURODRIVE as-
sumes no liability for injury to persons or damage to equipment or property resulting
from
non-observance
of
these
operating
instructions.
In
such
cases,
SEW‑EURODRIVE assumes no liability for defects.
1.6
Product names and trademarks
The brands and product names in this documentation are trademarks or registered
trademarks of their respective titleholders.
1.7
Copyright notice
© 2016 SEW‑EURODRIVE. All rights reserved. Unauthorized reproduction, modifica-
tion, distribution or any other use of the whole or any part of this documentation is
strictly prohibited.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
10
2
Safety notes
2.1
Preliminary information
The following general safety notes have the purpose to avoid injury and damage to
property. They primarily apply to the use of products described in this documentation.
If you use additional components also observe the relevant warning and safety notes.
2.2
Operator's duties
Make sure that the basic safety notes are read and observed. Make sure that persons
responsible for the machinery and its operation as well as persons who work on the
device independently have read through the documentation carefully and understood
it. If you are unclear about any of the information in this documentation, or if you re-
quire further information, contact SEW‑EURODRIVE.
The operator must ensure that the following works are only performed by qualified per-
sonnel:
•
Transport
•
Storage
•
Setup and assembly
•
Installation and connection
•
Startup
•
Maintenance and repair
•
Shutdown
•
Disassembly
•
Waste disposal
Make sure persons working on the product adhere to the following regulations, re-
quirements, documents and information:
•
National and regional safety and accident prevention regulations
•
Warning and safety signs on the product
•
All other relevant project planning documents, installation and startup instructions,
wiring diagrams and schematics
•
Do not assemble, install or operate damaged products
•
All specific specifications and requirements for the system
Make sure that systems with the product installed are equipped with additional moni-
toring and protection devices. Observe the applicable safety regulations and legisla-
tion governing technical equipment and accident prevention regulations.
2.3
Target group
Specialist for
mechanical work
Any mechanical work may only be performed by adequately qualified personnel. Qual-
ified personnel in the context of this documentation are persons familiar with the
design, mechanical installation, troubleshooting and maintenance of the product, who
possess the following qualifications:
•
Qualification in the field of mechanics according to applicable national regulation.
•
They are familiar with this documentation
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 11
Specialist for elec-
trotechnical work
Any electronic work may only be performed by adequately skilled persons (electric-
ally). Qualified electricians in the context of this documentation are persons familiar
with electrical installation, startup, troubleshooting and servicing of the product who
possess the following qualifications:
•
Qualification in the field of electrical engineering according to applicable national
regulation.
•
They are familiar with this documentation
In addition to that, these persons must be familiar with the valid safety regulations and
laws, as well as with the requirements of the standards, directives and laws specified
in this documentation. The above mentioned persons must have the authorization ex-
pressly issued by the company to operate, program, configure, label and ground
devices, systems and circuits in accordance with the standards of safety technology.
Instructed persons
All work in the areas of transportation, storage, operation and waste disposal must be
carried out by persons who are trained appropriately. The purpose of the instruction is
that the persons are capable of performing the required tasks and work steps in a safe
and correct manner.
2.4
Designated use
The product is intended for installation in electrical plants or machines.
In case of installation in electrical systems or machines, startup of the product is pro-
hibited until it is determined that the machine meets the requirements stipulated in the
local laws and directives. For Europe, Machinery Directive 2006/42/EC as well as the
EMC Directive 2014/30/EU apply. Observe EN 60204-1 (Safety of machinery - elec-
trical equipment of machines). The product meets the requirements stipulated in the
Low Voltage Directive 2014/35/EU.
The standards given in the declaration of conformity apply to the product.
The systems can be mobile or stationary. The motors must be suitable for operation
with inverters. Do not connect any other loads to the product. Never connect capacit-
ive loads to the product.
The product can be used to operate the following motors in industrial and commercial
systems:
•
AC asynchronous motors with squirrel-cage rotor
•
Permanent-field AC synchronous motors
Technical data and information on the connection conditions are provided on the
nameplate and in chapter "Technical data" in the documentation. Always comply with
the data and conditions.
Unintended or improper use of the product may result in severe injury to persons and
damage to property.
2.4.1
Hoist applications
To avoid danger of fatal injury by falling hoists, observe the following points when us-
ing the product in lifting applications:
•
Use mechanical protection devices.
•
Perform a hoist startup.
22872051/EN – 09/2016
Functional safety technology
Operating Instructions – MOVITRAC® LTP-B
12
2.5
Functional safety technology
The product must not perform any safety functions without a higher-level safety sys-
tem, unless explicitly allowed by the documentation.
2.6
Transport
Inspect the shipment for damage as soon as you receive the delivery. Inform the ship-
ping company immediately about any damage. If the product is damaged, it must not
be assembled, installed or started up.
Observe the following notes when transporting the device:
•
Ensure that the product is not subject to mechanical impact during transportation.
•
Before transportation, cover the connections with the supplied protection caps.
•
Only place the product on the cooling fins or on the side without connectors during
transportation.
•
Always use lifting eyes if available.
If necessary, use suitable, sufficiently dimensioned handling equipment.
Observe the information on climatic conditions in chapter "Technical data" of the docu-
mentation.
2.7
Installation/assembly
Ensure that the product is installed and cooled according to the regulations in the doc-
umentation.
Protect the product from excessive mechanical strain. The product and its mounted
components must not protrude into the path of persons or vehicles. Ensure that com-
ponents are not deformed and that insulation spaces are maintained, particularly dur-
ing transportation. Electric components must not be mechanically damaged or des-
troyed.
Observe the notes in the chapter "Mechanical installation" of the documentation.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 13
2.7.1
Restrictions of use
The following applications are prohibited unless explicitly permitted:
•
Use in potentially explosive areas
•
Use in areas exposed to harmful oils, acids, gases, vapors, dust, and radiation
•
Operation in applications with impermissibly high mechanical vibration and shock
loads in excess of the regulations stipulated in EN 61800-5-1
•
Operation at installation altitudes above 4000 m above sea level
The product can be used at altitudes above 1000 m asl up to 4000 m asl under the fol-
lowing conditions:
•
Taking the reduced continuous rated current into consideration, see chapter
"Technical data" of the documentation.
•
Above 2000 m asl, the air and creeping distances are only sufficient for over-
voltage class II according to EN 60664. If the installation requires overvoltage cat-
egory III according to EN 60664 you have to reduce the overvoltages on the sys-
tem side from category III to II using additional external overvoltage protection.
•
If a protective electrical separation is required, then implement this outside the
product at altitudes of more than 2000 m above sea level (protective separation in
accordance with EN 61800‑5‑1 and EN 60204‑1)
2.8
Electrical connection
Make yourself familiar with the applicable national accident prevention guidelines be-
fore you work on the product.
Perform electrical installation according to the pertinent regulations (e.g. cable cross
sections, fusing, protective conductor connection). The documentation at hand con-
tains additional information.
Make sure that all required covers are installed correctly after electrical installation.
Make sure that preventive measures and protection devices comply with the applic-
able regulations (e.g. EN 60204-1 or EN 61800-5-1).
2.8.1
Required preventive measure
Make sure that the product is correctly attached to the ground connection.
2.8.2
Stationary application
Necessary preventive measure for the product is:
Type of energy transfer
Preventive measure
Direct power supply
•
Ground connection
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
14
2.9
Protective separation
The product meets all requirements for protective separation of power and electronics
connections in accordance with EN 61800-5-1. To ensure protective separation, all
connected circuits must also meet the requirements for protective separation.
2.10
Startup/operation
Observe the safety notes in the chapters "Startup" and "Operation" in the documenta-
tion.
Make sure that the present transport protection is removed.
Do not deactivate monitoring and protection devices of the machine or system even
for a test run.
Make sure the connection boxes are closed and screwed before connecting the sup-
ply voltage.
Depending on the degree of protection, products may have live, uninsulated, and
sometimes moving or rotating parts, as well as hot surfaces during operation.
Additional preventive measures may be required for applications with increased haz-
ard potential. You have to check the protection devices after each modification.
When in doubt, switch off the product whenever changes occur in relation to normal
operation. Possible changes are e.g. increased temperatures, noise, or oscillation. De-
termine the cause. Contact SEW‑EURODRIVE if necessary.
When the device is switched on, dangerous voltages are present at all power connec-
tions as well as at any connected cables and terminals. This also applies even when
the product is inhibited and the motor is at standstill.
Do not separate the connection to the product during operation.
This may result in dangerous electric arcs damaging the product.
If you disconnect the product from the voltage supply, do not touch any live compon-
ents or power connections because capacitors might still be charged. Observe the fol-
lowing minimum switch-off time:
10 minutes.
Observe the corresponding information signs on the product.
The fact that the operation LED and other display elements are no longer illuminated
does not indicate that the product has been disconnected from the supply system and
no longer carries any voltage.
Mechanical blocking or internal safety functions of the product can cause a motor
standstill. Eliminating the cause of the problem or performing a reset may result in the
drive re-starting automatically. If, for safety reasons, this is not permitted for the drive-
controlled machine, first disconnect the product from the supply system and then start
troubleshooting.
Risk of burns: The surface temperature of the product can exceed 60 °C during opera-
tion.
Do not touch the product during operation.
Let the product cool down before touching it.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 15
3
Device structure
3.1
Nameplate
The following figure shows an example of a nameplate.
18014412064772491
3.2
Type designation
Example: MCLTP-B 0015-2B1-4-00 (60 Hz)
Product name
MCLTP
MOVITRAC® LTP-B
Version
B
Version status of the device series
Recommended motor
power
0015
0015 = 1.5 kW
Connection voltage
2
2 = 200 – 240 V
5 = 380 – 480 V
6 = 500 – 600 V
Interference suppression
on the input
B
0 = Class 0
A = Class C2
B = Class C1
Connection type
1
1 = 1-phase
3 = 3-phase
Quadrants
4
4 = 4-quadrant operation
Design
00
00 = Standard IP20 housing
10 = IP66/NEMA-4X housing
10 = IP55/NEMA-12K housing
Country-specific variant
(60 Hz)
60 Hz design
22872051/EN – 09/2016
Device structure of the standard inverter
Operating Instructions – MOVITRAC® LTP-B
16
3.3
Device structure of the standard inverter
3.3.1
Inverters with degree of protection IP20/NEMA 1
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
0.75 – 5.5 kW
400 V
0.75 – 11 kW
575 V
0.75 – 15 kW
+
-DC L1/L
L2/N L3
BR
U
V
W
MOVITRAC
® LTP-B
[1]
[2]
[3]
[4]
[5]
[7]
[8]
[6]
17957766667
[1]
Connecting terminal strip PE, -DC, L1/L, L2/N, L3
[2]
Auxiliary card with terminal assignment and basic parameters
[3]
Keypad with a 6-digit 7-segment display
[4]
Control terminal strip (pluggable)
[5]
RJ45 communication socket
[6]
Option card slot
[7]
Connecting terminal strip PE, +, BR, U, V, W
[8]
Relay terminal strip (pluggable)
22872051/EN – 09/2016
Device structure of the standard inverter
Operating Instructions – MOVITRAC® LTP-B 17
3.3.2
Inverters with degree of protection IP66/NEMA 4X
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
0.75 – 4 kW
400 V
0.75 – 7.5 kW
575 V
0.75 – 11 kW
[1]
[2]
[3]
[4]
[5]
[6]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[7]
17957961099
[1]
Full text display/6-digit 7-segment display
[2]
Keypad
[3]
Control terminal strip (pluggable)
[4]
Relay terminal strip (pluggable)
[5]
Connecting terminal strip PE, L1/L, L2/N, L3, -DC, +, BR, U, V, W
[6]
RJ45 communication socket
[7]
Option card slot
22872051/EN – 09/2016
Device structure of the standard inverter
Operating Instructions – MOVITRAC® LTP-B
18
3.3.3
Inverters with degree of protection IP55/NEMA 12K
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
5.5 – 75 kW
400 V
11 – 160 kW
575 V
15 – 110 kW
L1
+DC
U
V
W
BR -DC
L2
L3
[1]
[2]
[3]
[5]
[6]
[7]
L1
+DC
U
V
W
BR -DC
L2
L3
[1]
[2]
[3]
[5]
[6]
[7]
[4]
[4]
17957963531
[1]
Full text display/6-digit 7-segment display
[2]
Keypad
[3]
Control terminal strip (pluggable)
[4]
Option card slot
[5]
Relay terminal strip (pluggable)
[6]
RJ45 communication socket
[7]
Connecting terminal strip PE, L1/L, L2/N, L3, -DC, +, BR, U, V, W
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 19
4
Installation
4.1
General information
•
Carefully check the inverter for damage before the installation.
•
Store the inverter in its original packaging until it is used. The storage location
must be clean and dry with an ambient temperature between ‑40 °C and +60 °C.
•
Install the inverter in a suitable housing on a level, vertical, non-flammable, and vi-
bration-free surface. If a certain IP degree of protection is required, observe
EN 60529.
•
Keep flammable materials away from the inverter.
•
Prevent the ingress of conductive or flammable foreign objects.
•
The relative humidity must be kept below 95% (condensation is not permitted).
•
Protect the IP55/IP66 inverter from direct sunlight. Use a cover when using the in-
verter outdoors.
•
Inverters can be installed next to each other. Ensure sufficient ventilation space
between the individual devices. If the inverter is to be installed above another in-
verter or another device that dissipates heat, then there must be a vertical min-
imum clearance of 150 mm. To enable self-cooling, the control cabinet must either
be cooled through forced ventilation, or dimensioned accordingly. See chapter
"IP20 housing: Installation and installation space" (→ 2 21).
•
The permitted ambient temperatures are defined in chapter "Ambient
conditions" (→ 2 174).
•
The mounting rail installation is only possible for the following inverters with degree
of protection IP20.
–
230 V: 0.75 – 2.2 kW
–
400 V: 0.75 – 4 kW
–
575 V: 0.75 – 5.5 kW
The mounting rail must have the dimensions 35 × 15 mm or 35 × 7.5 mm and be
designed according to EN 50022.
•
Install the frequency inverter only as depicted in the following figure:
+
-DC L1/L
L2/N L3
BR
U
V
W
MOVITRAC
® LTP-B
+
-DC L1/L
L2/N L3
BR
U
V
W
MOVITRAC
® LTP-B
+
-DC L1/L
L2/N L3
BR
U
V
W
MOVITRAC
® LTP-B
7312622987
22872051/EN – 09/2016
Permitted tightening torques
Operating Instructions – MOVITRAC® LTP-B
20
4.2
Permitted tightening torques
Power of the inverter
Tightening torque in Nm for inverter
Control terminals
Power terminals
Nominal line voltage 230 V
0.75 – 2.2 kW
0.8
1
3 – 5.5 kW (IP20)
3 – 4 kW (IP66)
5.5 kW (IP66)
1 (IP20)
1 (IP66)
4 (IP66)
7.5 – 11 kW
4
15 – 18.5 kW
15
22 – 45 kW
20
55 – 75 kW
20
Nominal line voltage 400 V
0.75 – 4 kW
0.8
1
5.5 – 11 kW (IP20)
5.5 – 7.5 kW (IP66)
11 kW (IP66)
1 (IP20)
1 (IP66)
4 (IP66)
15 – 22 kW
4
30 – 37 kW
15
45 – 90 kW
20
110 – 160 kW
20
Nominal line voltage 575 V
0.75 – 5.5 kW
0.8
1
7.5 – 15 kW (IP20)
7.5 – 11 kW (IP66)
15 kW (IP66)
1 (IP20)
1 (IP66)
4 (IP66)
18.5 – 30 kW
4
37 – 45 kW
15
55 – 110 kW
20
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 21
4.3
Mechanical installation
4.3.1
IP20 housing: Installation and installation space
Inverters with degree of protection IP20 must be installed in a control cabinet. Observe
the following requirements:
•
The control cabinet must be made of a heat conductive material unless it has
forced cooling.
•
When using a control cabinet with ventilation openings, the openings must be
provided above and underneath the inverter to allow for unobstructed circulation of
air. The air must be supplied underneath the inverter and dissipated above it.
•
If the inverter is operated in environments with particles of dirt (such as dust), vent-
ilation openings either have to be equipped with a suitable particle filter or forced
cooling has to be used. The filter has to be serviced and cleaned.
•
In environments with a high level of humidity, salt or chemicals, a suitable en-
closed control cabinet (without ventilation openings) must be used.
•
The inverters with degree of protection IP20 can be installed right next to each
other without clearance.
+
-DC L1/L
L2/N L3
BR
U
V
W
MOVITRAC
® LTP-B
A
A
17958518795
Power of the inverter
A in mm
Air flow rate per in-
verter
230 V: 0.75 kW, 1.5 kW
400 V: 0.75 kW, 1.5 kW, 2.2 kW
575 V: 0.75 – 5.5 kW
60
> 45 m3/h
230 V: 2.2 kW
100
> 45 m3/h
All other power ranges
100
> 80 m3/h
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
22
4.3.2
IP55/IP66 housing: Installation and control cabinet dimensions
Inverters with degree of protection IP55/IP66 can be used indoors.
In control cabinets or in field, the following minimum distances must not be underrun.
A
A
A
B
B
B
9007208910888971
Power of the inverter
A in mm
B in mm
230 V
0.75 – 4 kW
5.5 – 75 kW
100
200
10
10
400 V
0.75 – 7.5 kW
11 – 160 kW
100
200
10
10
575 V
0.75 – 11 kW
15 – 110 kW
100
200
10
10
INFORMATION
If the IP55/IP66 inverter is installed in a control cabinet, a sufficient control cabinet
ventilation must be ensured.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 23
4.4
Electrical installation
WARNING
Electric shock due to charged capacitors. Dangerous voltage levels may still be
present inside the device and at the terminals up to 10 minutes after disconnection
from the power supply.
Severe or fatal injuries.
•
Wait 10 minutes after you have de-energized the inverter and have switched off
the line voltage and the DC 24 V voltage. Do not start working on the device until
you have made sure that it is de-energized.
WARNING
Danger of fatal injury due to falling hoist.
Severe or fatal injuries.
•
The inverter is not designed for use as a safety device in lifting applications. Use
monitoring systems or mechanical protection devices to ensure safety.
•
The inverters may only be installed by electrical specialists in compliance with the
applicable directives and regulations.
•
The grounding cable must be designed for the maximum fault current of the
voltage source that is usually limited by fuses or motor protection switches.
•
The inverter has the degree of protection IP20. For a higher IP degree of protec-
tion, a suitable enclosure or the IP55/NEMA 12K or the IP66/NEMA 4X variant has
to be used.
•
Make sure the devices are properly grounded. Adhere to the wiring diagram in
chapter "Connecting the inverter and motor" (→ 2 49).
4.4.1
Before installation
•
Make sure that supply voltage, frequency, and number of phases (single- or three-
phase) correspond with the nominal values of the inverter on delivery.
•
A disconnecting switch or similar disconnecting element must be installed between
voltage supply and inverter.
•
Never connect the power supply to the output terminals U, V or W of the inverter.
•
Do not install contactors between inverter and motor. Adhere to a minimum clear-
ance of 100 mm at points where control cables and electric power lines are in-
stalled close to each other, and an angle of 90° for crossing cables.
•
The cables are only protected by slow-blow high-power fuses or motor circuit
breaker. You find more information in section "Permitted voltage supply
systems" (→ 2 27).
•
It is recommended that you use a 4-core PVC-insulated and shielded cable as the
power cable. Route this cable according to the applicable national regulations of
the industry sector as well as the rules and standards. Conductor end sleeves are
required for connecting the power cables to the inverter.
•
Make sure that shieldings and sheaths of power cables are designed according to
the wiring diagram in section "Connecting inverter and motor" (→ 2 49).
•
The grounding terminal of each inverter must be connected individually and dir-
ectly to the ground busbar (mass) of the installation site (via filter, if available).
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
24
•
Do not loop the ground connections of the inverter from one inverter to the other.
Neither route the ground connections to the inverters from other inverters.
•
The impedance of the ground circuit must comply with the local safety regulations
of the industry sector.
•
Make sure that all terminals are tightened with the respective tightening torques,
see chapter "Technical data" (→ 2 173).
•
To comply with UL regulations, all earth connections must be designed with UL lis-
ted crimping cable lugs.
Unlike direct operation in the supply system, inverters on the motor generate suitable
fast-switching output voltages (PWM). In the case of motors wound for operation with
adjustable-speed drives, no further preventive actions are necessary. If, however, the
insulation quality is unknown, contact the manufacturer of the motor because prevent-
ive actions may be necessary.
INFORMATION
Make sure that the earth connections are properly connected. The inverter can gen-
erate leakage currents > 3.5 mA. The grounding cable must be sufficiently dimen-
sioned to carry the maximum fault current of the voltage source that is usually limited
by fuses or miniature circuit breakers. Sufficiently rated fuses or miniature circuit
breakers must be integrated into the inverter's mains supply in accordance with local
laws and/or regulations.
4.4.2
Line contactors
Use only line contactors in utilization category AC-3 (EN 60947-4-1).
Make sure to wait at least 30 seconds between 2 switching cycles.
� 30 s
t
UN
18442995979
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 25
4.4.3
Mains fuses
Fuse types:
•
Line protection types in operation classes gL, gG:
–
Rated fusing voltage ≥ rated line voltage
–
The nominal fusing current must be designed for at least 100% of the inverter
nominal input current depending on the inverter utilization.
•
Power circuit breaker with characteristic B:
–
Nominal circuit breaker voltage ≥ nominal line voltage
–
The nominal currents of the power circuit breakers must be 10% higher than
the nominal inverter current.
Residual current device
WARNING
No protection against electric shock if an incorrect type of residual current device is
used.
Severe or fatal injuries.
•
Use only universal current sensitive residual current devices of type B for invert-
ers.
•
Inverters generate a DC current component in the leakage current and can signi-
ficantly reduce the sensitivity of an residual current device of type A. A type A re-
sidual current device is this not permitted as protection device.
•
If the use of a residual current device is not mandatory according to the standards,
SEW‑EURODRIVE recommends not to use a residual current device.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
26
4.4.4
Operation on an IT system
IP20 devices can be operated on the IT system as described below. Please contact
SEW‑EURODRIVE for all other devices.
For operation on the IT system, the connection of the overvoltage protection and the
EMC filter to PE has to be separated. Screw out the EMC and VAR screw on the side
of the device.
WARNING
Danger of electric shock. Dangerous voltage levels may still be present inside the in-
verter and at the terminals up to 10 minutes after disconnection from the power sup-
ply.
Severe or fatal injuries.
•
Disconnect the inverter from the power supply at least 10 minutes before you
screw out the EMC and VAR screw.
[1] [2]
3034074379
[1] EMC screw
[2] VAR screw
L3
N/L2
L/L1
Internal
EMC
Filter
Internal
Surge
Protection
Earth
EMC
VAR
9007204745593611
SEW‑EURODRIVE recommends using earth-leakage monitors with pulse code meas-
urement in voltage supply systems with a non-grounded star point (IT systems). Use
of such devices prevents the insulation monitor mis-tripping due to the earth capacit-
ance of the inverter.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 27
4.4.5
Operation on a TN system with an RCD switch (IP20)
IP20 inverters with integrated EMC filter (such as MOVITRAC® LT xxxx xAx-x-00 or
MOVITRAC® LT xxxx xBx-x-00) have a higher leakage current than devices without
EMC filter. The EMC filter may cause errors when operated with a RCCB. Deactivate
the EMC filter to reduce the leakage current. To do so, screw out the EMC and VAR
screw on the side of the device. See figure in chapter "Operation on an IT
system" (→ 2 26).
4.4.6
Permitted voltage supply systems
•
Voltage supply systems with grounded star point
Inverters with all degrees of protection are intended for operation on TN and TT
systems with directly grounded star point.
•
Voltage supply systems with non-grounded star point
Operation on voltage supply systems with non-grounded star point (for example IT
systems) is only permitted for inverters with degree of protection IP20. See chapter
"Operation on an IT system" (→ 2 26).
•
Voltage systems with grounded outer conductor
On voltage supply systems, the inverters with all degrees of protection may only
be operated with a maximum phase-to-ground AC voltage of 300 V.
4.4.7
Help card
The help card contains an overview of the terminal assignment and additionally an
overview of the basic parameters of parameter group 1.
In the IP55/IP66 housing, the help card is attached behind the removable front cover.
In the IP20 housing, the help card is inserted in a slot above the display.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
28
4.4.8
Removing the terminal cover
To access the terminals of inverters with degree of protection IP55/IP66, remove the
front cover of the frequency inverter. Only use cross-head or slot screwdrivers to open
the terminal cover.
The connection terminals can be accessed when the screws on the front of the
product are removed as shown below.
The front cover is attached by proceeding in reverse order.
Inverters with degree of protection IP66/NEMA 4X
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
0.75 – 4 kW
400 V
0.75 – 7.5 kW
575 V
0.75 – 11 kW
18157858827
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 29
Inverters with degree of protection IP55/NEMA 12K
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
5.5 – 75 kW
400 V
11 – 160 kW
575 V
15 – 110 kW
MOVITRAC®LTP B
MOVITRAC®LTP B
MOVITRAC®LTP B
MOVITRAC®LTP B
[1]
[2]
[3]
[4]
9007212609488907
[1]
•
230 V: 5.5 – 11 kW
•
400 V: 11 – 22 kW
•
575 V: 15 – 30 kW
[3]
•
230 V: 22 – 45 kW
•
400 V: 45 – 90 kW
•
575 V: 55 – 110 kW
[2]
•
230 V: 15 – 18.5 kW
•
400 V: 30 – 37 kW
•
575 V: 37 – 45 kW
[4]
•
230 V: 55 – 75 kW
•
400 V: 110 – 160 kW
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
30
4.4.9
Cable gland plate
A suitable cable gland system is required to maintain the respective IP/NEMA degree
of protection. Cable entry holes have to be drilled that correspond to this system.
NOTICE
Drilling cable entry holes may lead to particles entering the inverter.
Possible damage to property.
•
Be careful when drilling the hole to prevent particles from entering the inverter.
→ Remove all particles at and in the inverter.
Some guide sizes are listed below:
Recommended hole sizes and hole types for the cable gland.
Power of the inverter
Hole size
Imperial
Metrical
230 V: 0.75 – 4 kW
400 V: 0.75 – 7.5 kW
575 V: 0.75 – 11 kW
25 mm
PG16
M25
Hole sizes for flexible electrical installation ducts
Power of the inverter
Hole size
Commercial size
Metrical
230 V: 0.75 – 4 kW
400 V: 0.75 – 7.5 kW
575 V: 0.75 – 11 kW
35 mm
1 in
M25
An IP degree of protection is only ensured when the cables are installed with a bush-
ing or sleeve for a flexible electrical installation duct approved by UL.
When installing electrical installation ducts, the insertion holes of the duct must have
standard openings for the required sizes according to NEC specifications.
Not intended for rigid electrical installation ducts.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 31
4.4.10
Connecting and installing the braking resistor
WARNING
Danger of electric shock. The supply cables to the braking resistors carry a high
voltage (approx. DC 900 V) during rated operation.
Severe or fatal injuries.
•
Before removing the supply cable, disconnect the inverter from the power supply
and wait at least 10 minutes.
CAUTION
Risk of burns. The surfaces of the braking resistors get very hot when the braking
resistors are loaded with PN.
Minor injuries.
•
Choose a suitable installation location.
•
Do not touch the braking resistors.
•
Install a suitable touch guard.
The braking resistor is connected between the inverter terminals "BR" and "+". In case
of a new device, these terminals have a cover installed that can be broken out. Break
out the cover prior to first use.
•
Shorten the cables to the required length.
•
Use 2 tightly twisted leads or a 2-core shielded power cable. The cable cross sec-
tion has to be dimensioned according to the tripping current IF of F16, the nominal
voltage according to DIN VDE 0298.
•
Protect the braking resistor with a bimetallic relay and set the tripping current IF of
the respective braking resistor.
•
The flat-type braking resistors have internal thermal overload protection (fuse can-
not be replaced). Install the flatpack resistors using appropriate touch guards.
•
For braking resistors in the BW..-...T series, you can connect the integrated tem-
perature sensor using a 2-core, shielded cable as an alternative to a bimetallic re-
lay.
U
V
W
+
BR
BW...
F16
affects
K11
9007202440373003
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
32
4.4.11
Motor temperature protection TF, TH, KTY84, PT1000
Motors with internal temperature sensor (TF, TH, KTY84, PT1000 or similar) can be
directly connected to the inverter.
If the thermal protection is triggered, the inverter displays the error "F-PTC".
For motor protection monitoring, the following types can be selected:
•
PTC-th for thermal sensor TF or bimetallic switch TH with trigger threshold 2.5 kΩ
•
KTY84 in temperature classes B (120 °C), F (155 °C) and H (180 °C)
•
PT1000 in temperature classes B (120 °C), F (155 °C) and H (180 °C)
When parameter P2-33 is configured for motor protection, this setting automatically
overwrites the function selection of the digital inputs (P1-15) to analog input AI2 = mo-
tor protection.
INFORMATION
Configure the temperature sensor on the inverter using P2-33, before the temperat-
ure sensor is connected. Then, connect the temperature sensor according to the wir-
ing diagram. Incorrect connection may lead to damage of sensor or inverter.
For information regarding the parameter P2-33, refer to chapter "P2-33 Analog input 2
format / motor protection" (→ 2 140).
Connection example for various temperature sensors:
Thermal sensor TF
Bimetallic switch TH
KTY84
PT1000
+24 VIO
DI 1
DI 2
DI 3
+10 V
AI 1 / DI 4
0 V
AO 1 / DO 1
0 V
AO 2 / DO 2
STO+
STO–
AI 2 / DI 5
1
2
3
4
5
6
7
8
9
10 11 12 13
17409280907
+24 VIO
DI 1
DI 2
DI 3
+10 V
AI 1 / DI 4
0 V
AO 1 / DO 1
0 V
AO 2 / DO 2
STO+
STO–
AI 2 / DI 5
1
2
3
4
5
6
7
8
9
10 11 12 13
17409278475
P2-33 = PTC-th
P2-33 = KTY84 or PT1000 (B, F, H)
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 33
4.4.12
Multi-motor drive/group drive
The total of the motor currents must not exceed the nominal current of the inverter.
The maximum permitted cable length for the group is limited to the values of single
connection. See chapter "Technical data" (→ 2 173).
The motor group is limited to five motors and must not differ by more than 3 frame
sizes.
Multi-motor operation is only possible with AC asynchronous motors, not with syn-
chronous motors.
SEW‑EURODRIVE recommends to use an output choke "HD LT xxx", additionally un-
shielded cables, and a maximum permitted output frequency of 4 kHz for groups of
more than 3 motors.
4.4.13
Motor cables and fusing
Comply with the regulations issued by specific countries and for specific machines re-
garding fusing and the selection of supply system leads and motor cables.
Determine the permitted length of all motor cables connected in parallel as follows:
I
I
n
tot
max
≤
3172400139
Itot
=
Total length of the motor cables connected in parallel
Imax
=
Recommended maximum motor cable length
n
=
Number of motors connected in parallel
No additional fusing is required if the cross section of the motor cable corresponds to
the cross section of the supply system lead. If the cross section of the motor cable is
smaller than the cross section of the supply system lead, you must protect the motor
cable against a short circuit for the corresponding cross section. Motor protection
switches are suited to this purpose.
4.4.14
Connecting AC brakemotors
For detailed information about the SEW‑EURODRIVE brake system, refer to the "AC
Motors" catalog, which you can order from SEW‑EURODRIVE.
SEW‑EURODRIVE brake systems are disk brakes with a DC coil that release electric-
ally and brake using spring force. A brake rectifier supplies the brake with DC voltage.
INFORMATION
The brake rectifier must have a separate supply system cable for inverter operation.
Supply via the motor voltage is not permitted.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
34
4.4.15
UL-compliant installation
Note the following information for UL-compliant installation:
Ambient temperatures
The inverters can be operated at the following ambient temperatures:
Degree of protection
Ambient temperature
IP20/NEMA 1
-10 °C to 50 °C
IP55/NEMA 12K
-10 °C to 40 °C
IP66/NEMA 4X
Use only copper connection cables suited for ambient temperatures up to 75 °C.
Tightening torques for the power and control terminals
Refer to chapter "Permitted tightening torques" (→ 2 20) for the permitted tightening
torques for the inverters.
External DC 24 V supply
Use only certified devices with a limited output voltage (Umax = DC 30 V) and limited
output current (I ≤ 8 A) as an external DC 24 V voltage source.
Voltage supply systems and fusing
The inverters are suitable for operation in voltage supply systems with earthed star
point (TN and TT systems) that can supply a maximum line current and a maximum
line voltage in accordance with the following table. The fuses listed in the following
tables are the maximum permitted fuses for each inverter. Only use melting fuses.
UL certification does not apply to operation in voltage supply systems with a non-
grounded star point (IT systems).
1 × 200 – 240 V devices
1 × 200 − 240 V
Fuse or MCB (type B)
Max. supply short circuit
current
Max. line voltage
0008
15 A
100 kA rms (AC)
240 V
0015
20 A
0022
25 A
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 35
3 × 200 – 240 V devices
3 × 200 − 240 V
Fuse or MCB (type B)
Max. supply short circuit
current
Max. line voltage
0008
10 A
100 kA rms (AC)
240 V
0015
15 A
0022
17.5 A
0030
30 A
0040
30 A
0055
40 A
0075
50 A
0110
70 A
0150
90 A
0185
110 A
0220
150 A
0300
175 A
0370
225 A
0450
250 A
0550
300 A
0750
350 A
3 × 380 – 480 V devices
3 × 380 − 480 V
Fuse or MCB (type B)
Max. supply short circuit
current
Max. line voltage
0008
6 A
100 kA rms (AC)
480 V
0015
10 A
0022
10 A
0040
15 A
0055
25 A
0075
30 A
0110
40 A
0150
50 A
0185
60 A
0220
70 A
0300
80 A
0370
100 A
0450
125 A
0550
150 A
0750
200 A
0900
250 A
1100
300 A
1320
350 A
1600
400 A
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
36
3 × 500 – 600 V devices
3 × 500 − 600 V
Fuse or MCB (type B)
Max. supply short circuit
current
Max. line voltage
0008
6 A
100 kA rms (AC)
600V
0015
6 A
0022
10 A
0040
10 A
0055
15 A
0075
20 A
0110
30 A
0150
35 A
0185
45 A
0220
60 A
0300
70 A
0370
80 A
0450
100 A
0550
125 A
0750
150 A
0900
175 A
1100
200 A
Thermal motor protection
The inverter is provided with thermal motor overload protection according to NEC (Na-
tional Electrical Code, US).
Thermal motor overload protection shall be provided by one of the following means:
•
NEC compliant installation of a motor temperature sensor, see also chapter "Motor
temperature protection (TF/TH)" (→ 2 32).
•
Using internal thermal motor overload protection by activating parameter P4-17.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 37
4.4.16
Information regarding UL
INFORMATION
Due to UL requirements, the following chapters are always printed in English inde-
pendent of the language of the revision:
Thermal motor protection
Thermal motor overload protection shall be provided by one of the following means:
•
NEC compliant installation of a motor temperature sensor, see also section "Motor
temperature protection (TF/TH)" in the chapter "Electrical Installation" of the oper-
ating instructions.
•
Using internal thermal motor overload protection according to NEC (National Elec-
trical Code, US). Thermal motor overload protection can be activated via para-
meter P4-17.
•
Implementing external measures to ensure thermal motor overload protection
according to NEC (National Electrical Code).
Parameter
The following additional parameter was added to MOVITRAC® LTP-B/LTX inverters to
implement internal thermal motor protection according to NEC:
•
P4-17 Thermal motor protection according to NEC
–
0: disabled
–
1: enabled
Functional principle
The motor current is accumulated in an internal memory over the course of time. The
inverter goes to fault state as soon as the thermal limit is exceeded (I.t-trP).
Once the output current of the inverter is less than the set rated motor current, the in-
ternal memory is decremented depending on the output current.
•
When P4-17 is disabled, thermal memory retention is reset upon shutdown or
power loss.
•
When P4-17 is enabled, thermal memory retention is maintained upon shutdown
or power loss.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
38
4.4.17
Electromagnetic compatibility (EMC)
Inverters with EMC filters are designed for use in machines and drive systems. They
meet the EMC product standard EN 61800-3 for drives with variable speed. Observe
the specifications of Directive 2014/30/EU for EMC‑compliant installation of the drive
system.
Interference immunity
With regard to interference immunity, the frequency inverter with an EMC filter meets
the limit values defined in the standard EN 61800-3 and can therefore be used for
both industrial and domestic (light industrial) applications.
Interference emission
With regard to interference emission, the inverter meets the EMC limit values of the
standard EN 61800-3:2004. The inverters are suitable for industrial as well as house-
hold applications (light industry).
Install the inverters as specified in chapter Installation to ensure best possible electro-
magnetic compatibility. Ensure proper ground connections for the inverters. Use shiel-
ded motor cables to comply with the specifications on interference emission.
The conditions for use in drive applications are defined in the table below.
Inverter type
Cat. C1 (class B)
Cat. C2 (class A)
Cat. C3
in accordance with EN 61800-3
230 V, 1-phase
LTP-B xxxx 2B1-x-xx
No additional filtering required.
Use a shielded motor cable.
230 V, 3-phase
LTP-B xxxx 2A3-x-xx
400 V, 3-phase
LTP-B xxxx 5A3-x-xx
Use an external filter
of the type NF LTxxx
xxx.
Use a shielded motor
cable.
No additional filtering required.
Use a shielded motor cable.
575 V, 3-phase
LTP‑B xxxx 603-x-xx
If necessary, you can use a line filter of the type
NF LT xxx to minimize the electromagnetic interference
emission. However, compliance with the limit classes
cannot be guaranteed.
Use a shielded motor cable.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 39
General information about connecting the motor shield
We strongly recommend that you use the shield plate with LTX applications.
Connect the shield by the shortest possible route and make sure it is earthed over a
wide area at both ends. This also applies to cables with several shielded core strands.
9007200661451659
Recommendation for motor shield connection at frequency inverters with IP20
Inverters with de-
gree of protection
IP20/NEMA 1
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
0.75 – 5.5 kW
400 V
0.75 – 11 kW
575 V
0.75 – 15 kW
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
40
Example LTP-B inverter
Example LTP-B inverter with LTX module
[1]
[1]
[2]
[2]
[4]
[4]
[5]
[3]
[5]
[6]
[7]
9007212157809419
[1]
Motor cable
[5]
Control cables
[2]
Additional PE connection
[6]
• 230 V: 0.75 – 2.2 kW
• 400 V: 0.75 – 4 kW
• 575 V: 0.75 – 5.5 kW
[3]
Encoder cable
[7]
• 230 V: 3 – 5.5 kW
• 400 V: 5.5 – 11 kW
• 575 V: 7.5 – 15 kW
[4]
Communication cable RJ45
The shield plate can be used optionally for the inverters in IP20 design listed above.
Proceed as follows to adjust:
1. Loosen the 4 screws on the slotted holes.
2. Move the plate up to the stop according to the required size.
3. Tighten the screws again.
Make sure that the plate is correctly attached to the PE connection.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 41
Recommendation for motor shield connection at frequency inverters with IP55/IP66
The use of metal screw fittings is recommended to connect the motor shield to the
device. For the inverters listed below, the threads must be at least 8 mm.
Inverters with de-
gree of protection
IP66/NEMA 4X
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
0.75 – 4 kW
400 V
0.75 – 7.5 kW
575 V
0.75 – 11 kW
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
42
≥8 mm
[1]
[2]
[3]
[4]
[6]
[5]
LTP-B
LTP-B + LTX
9007212157811595
[1]
Metal counter nut
[4]
LTX module
[2]
Metal cable gland
[5]
Motor cable
[3]
Enclosed rubber gasket
[6]
Supply system cable
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 43
Recommendation for routing the encoder, control and communication cables
[1]
[2]
[3]
[4]
[5]
9007212386365579
[1]
Encoder cable, if LTX module
[4]
Signal terminal/communication
[2]
Signal terminal/communication
[5]
Supply system cable
[3]
Motor cable
Inverters with de-
gree of protection
IP55/NEMA 12K
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
5.5 – 18.5 kW
400 V
11 – 37 kW
575 V
15 – 45 kW
L1
+DC
U
V
W
BR -DC
L2
L3
[1]
[2]
[3]
18242097931
[1]
Supply system cable
[2]
Metal cable gland
[3]
Motor cable
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
44
The following inverters have the housing shown below:
Nominal line voltage
Power of the inverter
230 V
22 – 75 kW
400 V
45 – 160 kW
575 V
55 – 110 kW
+
BR
L1
+
U
V
W
BR
-
L2
L3
[2]
[3]
[1]
18243537675
[1]
Supply system cable
[2]
Metal cable gland
[3]
Motor cable
4.4.18
Overview of signal terminals
Main terminals
NOTICE
Applying voltages of more than 30 V to the signal terminals can damage the control-
ler.
Possible damage to property.
•
The voltage applied to the signal terminals must not exceed 30 V.
+24 VIO
DI 1
DI 2
DI 3
+10 V
AI 1 / DI 4
0 V
AO 1 / DO 1
0 V
AO 2 / DO 2
STO+
STO–
AI 2 / DI 5
1
2
3
4
5
6
7
8
9
10 11 12 13
45035999276880139
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 45
The signal terminal block is equipped with the following connections:
Ter-
minal
no.
Signal
Connection
Description
1
+24 VIO
+24 V: Reference voltage/
backup voltage
Reference voltage for controlling the digital inputs
(max. 100 mA)1)
Adhere to the "Note for connecting the STO
function" (→ 2 46).
2
DI 1
Digital input 1
Positive logic
"Logic 1" input voltage range: DC 8 – 30 V
"Logic 0" input voltage range: DC 0 – 2 V
Compatible with PLC requirement if 0 V is connected
to terminal 7 or 9.
3
DI 2
Digital input 2
4
DI 3
Digital input 3
5
+10 V
Output +10 V: Reference
voltage
10 V: Reference voltage for analog input
(Potential supply +, 10 mA max., 1 – 10 kΩ)
6
AI 1 / DI 4
Analog input 1 (12 bit)
Digital input 4
analog: 0 – 10 V, 10 – 0 V, -10 – 10 V, 0 – 20 mA, 4 –
20 mA, 20 – 4 mA
digital: "Logic 1" input voltage range:
DC 8 – 30 V
7
0 V
0 V: Reference potential
Adhere to the "Note for connecting the STO
function" (→ 2 46).
8
AO 1 / DO 1
Analog output 1 (10 bit)
Digital output 1
analog: 0 – 10 V, 10 – 0 V, 0 – 20 mA, 20 – 0 mA,
4 – 20 mA, 20 – 4 mA
digital: 0 / 24 V maximum output current: 20 mA
9
0 V
0 V: Reference potential
Adhere to the "Note for connecting the STO
function" (→ 2 46).
10
AI 2 / DO 5
Analog input 2 (12 bit)
Digital input 5 / thermistor
contact
analog: 0 – 10 V, 10 – 0 V, PTC-th, 0 – 20 mA,
4 – 20 mA, 20 – 4 mA, KTY84, PT1000
digital: "Logic 1" input voltage range:
DC 8 – 30 V
11
AO 2 / DO 2
Analog output 2 (10 bit)
Binary output 2
analog: 0 – 10 V, 10 – 0 V, 0 – 20 mA, 20 – 0 mA,
4 – 20 mA, 20 – 4 mA
digital: 0 / 24 V maximum output current: 20 mA
12
STO+
Output stage enable
DC +24 V input, max. 100 mA current consumption
STO safety contact, high = DC 18 – 30 V
Adhere to the "Note for connecting the STO
function" (→ 2 46).
13
STO-
GND reference potential for DC +24 V input
STO safety contact
Adhere to the "Note for connecting the STO
function" (→ 2 46).
1) With inverter operation with fieldbus option, terminal 1 can be used to supply the backup voltage.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
46
All digital inputs are enabled with an input voltage in the range of 8 – 30 V. This
means they are +24 V compatible.
The response time of the digital and analog inputs is less than 4 ms. The resolution of
the analog inputs is 12 Bit at an accuracy of ±2% in reference to the set maximum
scaling.
Note for connecting the STO function
If terminal 12 is permanently supplied with 24 V, and terminal 13 is permanently con-
nected to GND, then the "STO" function is permanently disabled.
0 V
0 V
STO+
STO–
1
2
3
4
5
6
7
8
9
10 11 12 13
–
+
DI 1
[1]
[2]
18481633291
[1]
External DC 24 V supply
[2]
Optional safety relay
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 47
Relay terminals
14
15
16
17
18
NOTICE
Possible damage to property
Do not connect any inductive loads to the relay contact.
Ter-
minal
no.
Signal
Relay function selec-
tion
Description
14
Relay output 1 reference
P2-15
Relay contact (AC 250 V / DC 30 V,
max. 5 A)
15
Relay output 1 NO contact
16
Relay output 1 NC contact
17
Relay output 2 reference
P2-18
18
Relay output 2 NO contact
4.4.19
Communication socket RJ45
Socket at device
8
1
9007212770640779
[1]
SBus-/CAN bus-
[2]
SBus+/CAN bus+
[3]
0 V
[4]
RS485- (engineering)
[5]
RS485+ (engineering)
[6]
+24 V (output voltage/backup voltage)
[7]
RS485- (Modbus RTU)
[8]
RS485+ (Modbus RTU)
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
48
4.4.20
24 V backup mode
The inverter allows for realizing a backup mode via external 24 V. This means the
control electronics and the option cards such as the fieldbus cards are fully functional
even when the power supply is switched off.
Requirements
Firmware version 1.20 (can be seen in P0-28).
Range of functions
•
Parameter access (reading only, no writing)
•
Fieldbus communication
Setting up 24 V backup mode
All inverters that are connected to each other in a communication network and use the
24 V backup mode have to be supplied simultaneously with external 24 V. Make sure
that individual devices that are connected in the network are not separated from 24 V.
INFORMATION
Errors in the fieldbus network may occur if the inverters are not supplied by the power
supply and individual devices that are in the RJ45 network or the optional fieldbus
network are separated from the 24 V supply. Make sure that all connected inverters
are always supplied with external 24 V at the same time.
Example of a wiring diagram
Supply
Supply
24 V
0 V/GND
Communication
via RJ45 or
optional
fieldbus card
+24 VIO
DI 1
DI 2
DI 3
+10 V
AI 1 / DI 4
AI 2 / DI 5
AO 1 / DC
AO 2 / DC
STO+
STO-
0 V
0 V
1 2
RJ45
Relay
Option
3 4 5 6 7 8 9 10111213
14 15161718
Supply
+24 VIO
DI 1
DI 2
DI 3
+10 V
AI 1 / DI 4
AI 2 / DI 5
AO 1 / DC
AO 2 / DC
STO+
STO-
0 V
0 V
1 2
RJ45
Relay
Option
3 4 5 6 7 8 9 10111213
14 15161718
Supply
+24 VIO
DI 1
DI 2
DI 3
+10 V
AI 1 / DI 4
AI 2 / DI 5
AO 1 / DC
AO 2 / DC
STO+
STO-
0 V
0 V
1 2
RJ45
Relay
Option
3 4 5 6 7 8 9 10111213
14 15161718
18364546315
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 49
4.4.21
DC link connection
The DC link is routed on terminals for all power ratings. It is thus possible to couple all
devices with a DC link connection or to directly supply them with DC voltage.
Contact SEW‑EURODRIVE in such a case.
4.5
Wiring diagram
WARNING
Danger of electric shock. Incorrect wiring can lead to dangerously high voltages.
Severe or fatal injuries.
•
Adhere to the following.
In the following applications, always cut-off the brake in the AC and DC circuits:
•
All lifting applications.
•
Applications that require a quick brake reaction time.
Please note the following:
•
The following inverters with degree of protection IP66/NEMA 4X already have
openings for supply system, motor and control cables.
–
230 V: 0.75 – 4 kW
–
400 V: 0.75 – 7.5 kW
–
575 V: 0.75 – 11 kW
The following inverters with degree of protection IP55/NEMA 12K are equipped
with a metal entry board. The user has the possibility to drill the cable entries ac-
cording to his requirements.
–
230 V: 5.5 – 75 kW
–
400 V: 11 – 160 kW
–
575 V: 15 – 110 kW
•
Connect the brake rectifier using a separate supply system lead.
•
Supply via the motor voltage is not permitted.
INFORMATION
In case of a new device, the terminal slots DC-, + (DC+) and BR have a cover in-
stalled that can be broken out if required.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
50
BW
L1
L2
L3
L1 ' L 2'
L3 '
F11/F12/F13
K10
(AC-3)
L1
L2/N
L3
PE
L1
L2
L3
U
W
M
BR
B W .. / BW..-T
+
[1]
V
[2]
3-phase
Option ND.. input choke
Power section
braking resistor
not single-phase 230 V
connection*
DC bus “–” access
DC bus “+” access
18380767883
[1]
Line contactor between supply system and inverter.
[2]
Brake
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 51
4.5.1
Brake control
F14/F15
F14/F15
1
2
3
4
5
1
2
3
4
5
K12
(AC-3)
K12
(AC-3)
GND
GND
GND
BG
BG E
BG
BG E
F14/F15
K11
(AC-3)
K11
(AC-3)
K11
(A
C-3)
1
2
3
4
13
14
15
BM K
V AC
V AC
V AC
DR/DT/DV:
DR/DT/DV:
white
red
blue
17
18
V+
V+
V+
17
18
17
18
[1]
[3]
[2]
(BMK)
V DC (BMV)
BM V
[3]
[2]
[3]
white
red
bue
red
white
blue
Cut-off in the AC circuit
Cut-off in the DC
and AC circuits
18475023883
[1]
Power supply of the brake rectifier, switched simultaneously via K10.
[2]
Control contactor/control relay, is powered by the internal relay contact [3] of
the inverter and supplies the brake rectifier.
[3]
Isolated relay contact of the inverter.
V+
External voltage supply AC 250 V / DC 30 V at max. 5 A
VDC
(BMV) DC voltage supply BMV.
VAC
(BMK) AC voltage supply BMK.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
52
5
Startup
5.1
User interface
5.1.1
Keypads
The inverters in IP20 design are equipped with a standard keypad.
The inverters in IP55/IP66 design are equipped with a full text display with language
switching function.
Both keypads allow for operation and setup of the inverter without additional devices.
Standard keypad
MOVITRAC® LT
[4]
[5]
[6]
[1]
[2]
[3]
9007202188405387
[1]
6-digit 7-segment display
[4]
Navigate button
[2]
Start button
[5]
Up button
[3]
Stop/Reset button
[6]
Down button
Keypad with full text display
MOVITRAC® LT
[4]
[5]
[6]
[1]
[2]
[3]
18364520203
[1]
Full text display (multilingual)
[4]
Navigate button
[2]
Start button
[5]
Up button
[3]
Stop/Reset button
[6]
Down button
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 53
Operation
Both keypads have 5 keys with the following functions:
Key
Start [2]
•
Enable drive
•
Changing the direction of rotation
Key
Stop [3]
•
Stop drive
•
Acknowledge error
Key
Navigate [4]
•
Switch menu
•
Save parameter values
•
Display real time information
Key
Up [5]
•
Increase speed
•
Increase parameter values
Key
Down [6]
•
Decrease speed
•
Decrease parameter values
The parameter edit menu can only be accessed by pressing the key [4].
•
To switch between the menu for changing parameters and real-time display (oper-
ating speed/operating current): keep the key pressed for longer than 1 second.
•
Switch between operating speed and operating current of the running inverter:
press the key briefly (< 1 second).
The operating speed is only displayed if a nominal motor speed has been entered in
P1-10. Otherwise, the electrical rotating field speed is displayed.
Switching the language at the keypad with full text display
To switch the language in the full text display, press the key and the key simultaneously. The inverter must not be enabled during this opera-
tion.
The list of available languages is now displayed.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
54
5.1.2
Resetting parameters to default settings
To reset the parameters to the factory setting, proceed as follows:
1. The inverter must not be enabled and the display must show "Inhibit".
2. Press the 3 keys
,
, and
simultaneously for at least 2 s.
"P-deF" appears on the display.
3. Press the
key to acknowledge the "P-deF" message.
INFORMATION
If the inverter is set to the factory settings, the and keys of the keypad
are disabled. To enable using the / keys on the keypad, set the para-
meter P-12 to "1" or "2".
5.1.3
Key combinations
Function
The device
displays:
Press:
Result
Example
Quick parameter
group selection1) Px-xx
+ keys
+
The next higher para-
meter group is selected.
"P1-10" is displayed:
• Press the + keys.
• Now, "P2-01" is displayed.
Px-xx
+ keys
+
The next lower para-
meter group is selected.
"P2-26" is displayed:
• Press the + keys.
• "P1-01" is now displayed.
Selection of the
lowest group
parameter
Px-xx
+ keys
+
The first parameter of a
group is selected.
"P1-10" is displayed:
• Press the + keys.
• "P1-01" is now displayed.
Set the para-
meter to the low-
est value
Numerical
value (when
changing a
parameter
value)
+ keys
+
The parameter is set to
the lowest value.
When changing P1-01:
• "50.0" is displayed.
• Press the + keys.
• "0.0" is now displayed.
Changing indi-
vidual digits of a
parameter value
Numerical
value (when
changing a
parameter
value)
+
keys
+
The individual para-
meter digits can be
modified.
When changing P1-10:
• "0" is displayed.
• Press the + keys.
• "_0" is now displayed.
• Press the key.
• "10" is now displayed.
• Press the + keys.
• "_10" is now displayed.
• Press the key.
• "110" is now displayed.
etc.
Switching lan-
guages
Select lan-
guage
and
+
The desired language
can be selected now.
• English
• German
• French
• Spanish
• .....
1) Parameter group access must be activated: Set P1-14 to "101" or "201".
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 55
5.1.4
Software LT Shell
The LT Shell software enables an easy and quick startup of the inverters. It is avail-
able for download on the SEW‑EURODRIVE website. After the installation, perform
software updates on a regular basis.
In combination with the engineering package (cable set C) and the USB11A interface
adapter, the inverter can be connected to the software.
Maximum 63 inverters can be connected to an LT Shell in a network.
The software can be used to carry out the following tasks:
•
Observe, upload and download parameters.
•
Save parameter settings.
•
Firmware update (manual and automatic).
•
Export inverter parameters to Microsoft® Word.
•
Monitor the state of the inputs and outputs and the motor.
•
Control inverter/manual mode.
•
Scope.
Connection to LT Shell
The connection is performed via an RS485 interface (USB11A + PC engineering
package) or via Bluetooth® (parameter module).
RS485
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
SEW
LTP-B
[2]
[7]
[6]
[8]
[5]
9288836235
[2]
RJ45 to RJ45 cable
[7]
Cable USB A-B
[5]
RJ10 to RJ10 cable
[8]
RJ adapter (2 x RJ45, 1 x RJ10)
[6]
USB11A
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
56
Bluetooth®
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
LTP-B
[1]
9007216440559755
[1]
Parameter module
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 57
5.1.5
MOVITOOLS® MotionStudio engineering software
The software can be connected to the inverter as follows:
•
Via an SBus-connection between PC and inverter. A CAN dongle is required. A
prefabricated cable is not available and must be manufactured according to the
RJ45 assignment and the inverter interface.
•
Via a connection of the PC with a gateway or a MOVI‑PLC®. The connection
between PC and gateway/MOVI‑PLC® is possible via USB11A, USB or Ethernet.
The following functions are available in MOVITOOLS® MotionStudio:
•
Observe, upload and download parameter
•
Save parameter settings
•
Monitor the state of the inputs/outputs and the motor.
Connection to MOVITOOLS® MotionStudio
The connection can be set up indirectly via SEW‑EURODRIVE gateway or
SEW‑EURODRIVE controller.
Gateway
DFP 21B
RUN
X30
BUS
FAULT
ADDRESS
20
0
1
21
22
23
24
25
26
nc
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
SEW
LTP-B
[4]
[6]
[1]
[3]
[2]
[5]
17186235147
[1]
Cable USB A-B
[4]
RJ45 cable with open end
[2]
USB11A
[5]
Terminating connector (120 Ω)
[3]
RJ10 to RJ10 cable
[6]
Cable splitter
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
58
Controller
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
SEW
LTP-B
[4]
[6]
[1]
[3]
[2]
[5]
X34
22
23
24
25
26
DHP 11B
X31
X32
X33
X30
ON
20
21
[7]
[8]
17186293003
[1]
Cable USB A-B
[5]
Terminating connector (120 Ω)
[2]
USB11A
[6]
Cable splitter
[3]
RJ10 to RJ10 cable
[7]
Cable USB A-B
[4]
RJ45 cable with open end
[8]
RJ45 Ethernet cable
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 59
5.2
Automatic measuring procedure "Auto tune"
Auto tune
With the automatic measuring procedure, the inverter can measure almost any motor
to determine the motor data.
•
After a reset to the factory settings, the measuring procedure starts automatically
after the first enable and takes up to 2 minutes depending on the control type. Do
not interrupt the measuring procedure.
•
You can also start the automatic measuring procedure "Auto tune" manually with
the parameter P4-02 after entering the motor data. Only enable the inverter after
you have entered all motor data correctly in the parameters.
•
For STO, the terminals 12 and 13 have to be supplied with voltage. Enable is not
required. "Stop" has to be displayed.
INFORMATION
Perform an automatic measuring procedure "Auto tune" after the initial startup or after
changing the control mode in P4-01 when the motor is cold. You can also start auto-
tuning manually via the parameter P4-02 at any time.
5.3
Startup for motors
WARNING
When parameter P4-02 is set to "1" (auto tune) the motor may start up automatic-
ally.
Severe or fatal injuries.
•
Make sure that no persons are within the reach of moving parts of the system.
INFORMATION
The ramp times in parameters P1-03 and P1-04 refer to 50 Hz. If P1-16 is set to "In-
Syn", overload capacity is set to "150%" depending on P1-08.
22872051/EN – 09/2016
Startup for motors
Operating Instructions – MOVITRAC® LTP-B
60
5.3.1
Startup for asynchronous motors with V/f control
1. Connect the motor to the inverter. During the connection, adhere to the nominal
motor voltage.
2. Enter the motor data indicated on the motor nameplate:
•
P1-07 = nominal voltage of the motor
•
P1-08 = rated current of the motor
•
P1-09 = rated frequency of the motor
•
P1-10 = rated speed of the motor
- Value = 0: Slip compensation deactivated
- Value ≠ 0: Slip compensation activated
3. Set the maximum and minimum speed using P1-01 and P1-02.
4. Set the acceleration and deceleration ramps using P1-03 and P1-04.
5. Start the automatic motor measurement procedure "Auto Tune" as described in
chapter "Auto Tune" (→ 2 59).
5.3.2
Startup for asynchronous motors with VFC speed control
1. Connect the motor to the inverter. During the connection, adhere to the nominal
motor voltage.
2. Enter the motor data indicated on the motor nameplate:
•
P1-07 = nominal voltage of the motor
•
P1-08 = rated current of the motor
•
P1-09 = rated frequency of the motor
•
P1-10 = rated speed of the motor
•
P1-14 = 201 (Extended parameter menu)
•
P4-01 = 0 (VFC speed control)
•
P4-05 = power factor.
3. Set the maximum and minimum speed using P1-01 and P1-02.
4. Set the acceleration and deceleration ramps using P1-03 and P1-04.
5. Start the automatic motor measurement procedure "Auto Tune" as described in
chapter "Auto Tune" (→ 2 59).
6. In case of insufficient control performance, the control behavior can be optimized
via the parameter P7-10.
22872051/EN – 09/2016
Startup for motors
Operating Instructions – MOVITRAC® LTP-B 61
5.3.3
Startup for asynchronous motors with VFC torque control
1. Connect the motor to the inverter. During the connection, adhere to the nominal
motor voltage.
2. Enter the motor data indicated on the motor nameplate:
•
P1-07 = nominal voltage of the motor
•
P1-08 = rated current of the motor
•
P1-09 = rated frequency of the motor
•
P1-10 = rated speed of the motor
•
P1-14 = 201 (Extended parameter menu)
•
P4-01 = 1 (VFC torque control)
•
P4-05 = power factor.
3. Set the maximum and minimum speed using P1-01 and P1-02.
4. Set the acceleration and deceleration ramps using P1-03 and P1-04.
5. Start the automatic motor measurement procedure "Auto Tune" as described in
chapter "Auto Tune" (→ 2 59).
6. In case of insufficient control performance, the control behavior can be optimized
via the parameter P7-10.
Example: The following example shows analog input 2 as torque reference source,
analog input 1 sets the speed:
•
P1-15
=
3 (input terminal assignment)
•
P4-06
=
2 (Torque reference via analog input 2)
•
P6-17
=
0 (Switching off the torque timeout threshold)
=
>0 (Adjusting the timeout time for the maximum torque limit)
22872051/EN – 09/2016
Startup for motors
Operating Instructions – MOVITRAC® LTP-B
62
5.3.4
Startup of synchronous motors without encoder feedback (PMVC control)
The synchronous motors are permanent magnet motors.
INFORMATION
The operation of synchronous motors without encoder must be checked in a test ap-
plication. Stable operation in this operating mode cannot be ensured for all applica-
tion cases. Using this operating mode is thus in the sole responsibility of the user.
1. Connect the motor to the inverter. During the connection, adhere to the nominal
motor voltage.
2. Enter the motor data indicated on the motor nameplate:
•
P1-07 = For synchronous motors, not the system voltage is set, but the internal
voltage for nominal motor speed.
•
P1-08 = rated current of the motor
•
P1-09 = rated frequency of the motor
•
P1-10 = rated speed of the motor
•
P1-14 = 201 (Extended parameter menu)
•
P4-01 = 3 (PMVC speed control)
•
P2-24 = PWM frequency (at least 8−16 kHz).
3. Set the maximum and minimum speed using P1-01 and P1-02.
4. Set the acceleration and deceleration ramps using P1-03 and P1-04.
5. Start the automatic motor measurement procedure "Auto Tune" as described in
chapter "Auto Tune" (→ 2 59).
6. In case of insufficient control performance, the control behavior can be optimized
via the parameter P7-10.
In case of unexpected motor control problems, check or set the following:
•
To achieve a higher torque in the lower speed range, the parameters P7-14 and
P7-15 must be increased. Note that the motor may heat up significantly due to the
increased current flow.
•
Sometimes it may be required to align the rotor of motors with higher inertia before
the start. The premagnetization time P7-12 as well as the field strength during the
premagnetization time can be slightly adjusted up or down in P7-14.
In rare cases, it can be helpful to compare the parameters determined in the automatic
motor measurement procedure to the parameters of the motor data. Correct them if
necessary. Note that the values may deviate in case of long motor cables.
No repeated measuring procedure is required:
•
P7-01 = stator resistance of the motor (Rphase-phase or 2 × R1 (20 °C))
•
P7-02 = 0 (Rotor resistance of the motor)
•
P7-03 = Stator inductance (Lsd)
•
P7-06 = Stator inductance (Lsq).
22872051/EN – 09/2016
Startup for motors
Operating Instructions – MOVITRAC® LTP-B 63
5.3.5
Startup with LSPM motors from SEW‑EURODRIVE
DR..J type motors are motors with LSPM technology (Line Start Permanent Magnet
motors).
1. Connect the motor to the inverter. During the connection, adhere to the nominal
motor voltage.
2. Enter the motor data indicated on the motor nameplate:
•
P1-07 = internal voltage at nominal motor speed
•
P1-08 = rated current of the motor
•
P1-09 = rated frequency of the motor
•
P1-10 = rated speed of the motor
•
P1-14 = 201 (Extended parameter menu)
•
P4-01 = 6 (LSPM speed control).
3. Set the maximum speed P1-01 and minimum speed P1-02 to 300 1/min.
4. Set the acceleration and deceleration ramps using P1-03 and P1-04.
5. Start the automatic motor measurement procedure "Auto Tune" as described in
chapter "Auto Tune" (→ 2 59).
6. Adjust the boost parameters. A default setting is:
•
P7-14 = 10%
•
P7-15 = 10%.
7. In case of insufficient control performance, the control behavior can be optimized
via the parameter P7-10.
22872051/EN – 09/2016
Startup for motors
Operating Instructions – MOVITRAC® LTP-B
64
5.3.6
Startup with preset motors from SEW‑EURODRIVE
Startup can be performed if one of the following CMP.. motors (speed class 4500 1/
min) or MGF..-DSM motors (speed class 2000 1/min) are connected to the inverter:
Motor type
Display
CMP40M
40M
CMP50S / CMP50M /CMP50L
50S / 50M / 50L
CMP63S / CMP63M / CMP63L
63S / 63M / 63L
CMP71S / CMP71M / CMP71L
71S / 71M / 71L
MGF..2-DSM
gf-2
MGF..4-DSM
gf-4
MGF..4/XT-DSM
gf-4Ht
Procedure
•
Set P1-14 to "1" for access to LTX-specific parameters.
•
Set P1-16 to the preset motor; see chapter "LTX-specific parameters (level 1)" in
the "MOVITRAC® LTX" addendum to the operating instructions.
Example
Example:
CMP.. size
50S
40M, 50S, 50M, 50L, 63S, 63M, 63L, 71S, 71M, 71L
Motor system voltage
4
•
2 = 230 V
•
4 = 400 V
Brakemotors
b
b = flashes for brakemotors
All the required parameters (voltage, current, etc.) are set automatically.
INFORMATION
"Auto Tune" is not necessary for preset motors.
If a CMP.. motor with electronic nameplate is connected to the inverter, P1-16 is se-
lected automatically.
If a MGF..-DSM is selected, the upper torque limit in P4-07 is automatically set to
200%. This value has to be adapted according to the documentation "Addendum to
the Operating Instructions, Drive Unit MGF..-DSM on LTP-B Inverter".
All necessary motor data are set automatically. For motor protection, the KTY tem-
perature sensor has to be connected to terminal 5 (+10 V) and terminal 10 (analog in-
put 2) and activated via parameter P2-33. Refer to the chapter "Motor temperature
protection TF, TH, KTY84, PT1000" (→ 2 32).
•
Refer to chapter "Parameter group 1: Servo-specific parameters (level
1)" (→ 2 130) for a detailed list.
22872051/EN – 09/2016
Startup of control
Operating Instructions – MOVITRAC® LTP-B 65
5.4
Startup of control
WARNING
Installing sensors or switches at the terminals may cause an enable signal. The mo-
tor may start up automatically.
Severe or fatal injuries.
•
Make sure that no persons are within the reach of moving parts of the system.
•
Install the switches in open state.
•
If you install a potentiometer, set it to 0 first.
5.4.1
Terminal mode (factory setting) P1-12 = 0
For operation in terminal mode (factory setting):
•
P1-12 must be set to "0" (factory setting).
•
Change the input terminal configuration according to your demands in P1-15.
Refer to chapter P1-15 Digital inputs function selection for the possible settings.
•
Connect a switch between terminals 1 and 2 on the user terminal block.
•
Connect a potentiometer (1 k – 10 k) between terminals 5, 6 and 7. The center tap
is connected to terminal 6.
•
Connect the terminals 12 and 13 of the STO input according to chapter
"Disconnection of a single drive" (→ 2 203).
•
Enable the inverter by establishing a connection between terminals 1 and 2.
•
Set the speed using the potentiometer.
22872051/EN – 09/2016
Startup of control
Operating Instructions – MOVITRAC® LTP-B
66
5.4.2
Keypad mode (P1-12 = 1 or 2)
For operation in keypad mode:
•
Set P1-12 to "1" (uni-directional) or "2" (bi-directional).
•
Connect a jumper or switch between terminals 1 and 2 on the terminal block to en-
able the inverter.
•
Connect the terminals 12 and 13 of the STO input according to chapter
"Disconnection of a single drive" (→ 2 203).
•
Press the key. The inverter is enabled with 0.0 Hz.
•
To increase the speed, press the key. To decrease the speed, press the
key.
•
To stop the inverter, press the key.
•
To resume to the original speed, press the "Start" key again. If bi-directional mode
is enabled (P1-12 = 2), the direction is reversed by pressing the key again.
INFORMATION
You can preset the required target speed by pressing the key at stand-
still. Pressing the key then moves the drive along the preset ramp until it has
reached the required speed.
5.4.3
PID controller mode (P1-12 = 3)
The implemented PID controller can be used for temperature control, pressure control
or other applications.
The following figure shows the configuration options for the PID controller.
P gain time P3-01
I time constant P3-02
D time constant P3-03
-1
PID
setpoint
P0-10
PID controller upper limit
Fixed setpoint of P3-07: (P3-09=0)
Analog input 1: (P3-09=1)
PID correcting variable + analog input 1: (P3-09=3)
PID
error threshold
P3-11
Acceleration ramp
P1-03
Deceleration ramp
P1-04
Speed controller
setpoint
P0-04
PID
feedback
P0-09
PID-
ref.
P0-08
0
1
Selection PID
feedback P3-10
Analog input 2
Analog input 1
0
1
2
3
Fixed setpoint reference
Analog input 1
Analog input 2
Fieldbus PID reference
PID
reference selection
P3-05
PID
operating mode
P3-04
PID controller activation
with P1-12 = 3
Display values
Parameters
0
1
0%
>0%
PID controller lower limit
Fixed setpoint of P3-08:
(P3-09=0)
Analog input 1: (P3-09=2)
-
+
Standby function
x
Scaling factor
P3-12
Display
rXXX
&
Activation delay
P2-27 <>0
Minimum speed/
frequency
P1-02
PID wake-up level
P3-13 >
control deviation
S
R
Standby mode active
Legend
Parameter selection
27021600768510347
22872051/EN – 09/2016
Startup of control
Operating Instructions – MOVITRAC® LTP-B 67
General informa-
tion on the use
Connect the sensor for the controlled variable to analog input 1 or 2 depending on
P3-10. You can scale the sensor value using parameter P3-12 in such a way that the
value is indicated on the inverter display with the proper quantity, for example 0 –
10 bar.
You can set the target reference for the PID controller using P3-05.
The setting of the speed ramp times has no effect when the PID controller is active.
Acceleration and deceleration ramps can be activated depending on the control devi-
ation (target value – actual value) using P3-11.
Fixed setpoint
reference
The fixed setpoint reference entered in P3-06 is used with the setting P3-05 = 0.
When the parameters P9-34 and P9-35 have another value than "OFF", 3 additional
fixed setpoint references P3-14 to P3-16 are activated and are selected according to
the table below:
Terminal selection via
P9-34
Terminal selection via
P9-35
Fixed setpoint reference
0 (LOW)
0 (LOW)
P3-06
1 (HIGH)
0 (LOW)
P3-14
0 (LOW)
1 (HIGH)
P3-15
1 (HIGH)
1 (HIGH)
P3-16
Fieldbus PID ref-
erence
The following parameters must be set in the inverter:
P1-12
=
5 (e.g. control signal source SBus)
P1-14
=
201 (extended parameter menu)
P1-15
=
0 (free function selection of the digital inputs)
P3-05
=
3 (PID reference via the fieldbus)
P5-09 – 11 =
4 (selection of the process output data word for the PID reference)
P9-01
=
Selection of the digital input for enabling the inverter
P9-10
=
PID (speed source of the inverter)
22872051/EN – 09/2016
Startup of control
Operating Instructions – MOVITRAC® LTP-B
68
5.4.4
Master-slave mode (P1-12 = 4)
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
Master
Slave 1
Slave 2
[1]
max 63x
[2]
[1]
[2]
IOIOI
IOIOI
IOIOI
9007212609546891
[1]
RJ45 to RJ45 cable
[2]
Cable splitter
The inverter has an integrated master-slave function.
The master-slave communication is obtained via a special protocol. In this case, the
inverter communicates via the RS485 engineering interface. Up to 63 inverters can be
connected with one another in a communication network using RJ45 connectors.
One inverter is configured as master, the remaining inverters as slaves. Each network
may have only one master inverter. This master inverter sends its operating state
(such as stopped, running) and output frequency every 30 ms. The slave inverters
then follow the state of the master frequency inverter.
Configuring the master inverter
The master inverter of each network must have the communication address "1". Set:
•
P1-12 ≠ 4 (control signal source)
•
P1-14 = 201 (extended parameter menu)
•
P5-01 = 1 (inverter address communication)
22872051/EN – 09/2016
Startup of control
Operating Instructions – MOVITRAC® LTP-B 69
Configuring the slave inverters
•
Each connected slave must have a unique slave communication address that is
set with the inverter address P5-01. You can assign slave addresses from 2 to 63.
Set:
•
P1-12 = 4 (control signal source)
•
P1-14 = 201 (extended parameter menu)
•
P5-01 = 2 - 63 (inverter address communication)
•
the type of speed scaling in P2-28
•
the scaling factor in P2-29.
•
Make sure that the ramps at the slave inverter are set equal to or smaller than the
value at the master.
INFORMATION
Cable set B can be used for setting up the master-slave network. It is not necessary
to use a terminating resistor. For information on the cable sets refer to the catalog.
5.4.5
Fieldbus mode (P1-12 = 5, 6 or 7)
See chapter "Fieldbus mode" (→ 2 92).
5.4.6
MultiMotion mode (P1-12 = 8)
See "Addendum to the MOVITRAC® LTX operating instructions".
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
70
5.5
Hoist function
The inverter is equipped with a hoist function. When the hoist function is active, all rel-
evant parameters and functions are activated and locked, if necessary. For proper
functioning, a correct motor startup has to be performed as described in chapter
"Startup for hoist function" (→ 2 71).
Also observe the following points in particular:
•
The motor brake control has to performed by the inverter. Connect a brake rectifier
between inverter relay 2 (terminal 17 and 18) and brake, see chapter "Electrical
installation" (→ 2 23).
•
Use a sufficiently dimensioned braking resistor.
•
SEW‑EURODRIVE recommends not to run the motor in very low speed ranges or
to keep the load at zero speed without application of the brake.
•
If you need sufficient torque, operate the motor within its nominal range.
To ensure safe operation when the hoist function is active, the following parameters
are preset or ignored by the firmware in case of changes:
•
P1-06: Energy-saving function is deactivated.
•
P2-09/P2-10: Skip frequencies are ignored.
•
P2-26: The flying start function is deactivated.
•
P2-27: The standby mode is deactivated.
•
P2-36: The start mode is edge-triggered (Edgr-r).
•
P2-38: Voltage failure results in coast to a stop.
•
P4-06/P4-07: Maximum torque limits are set to the maximum values.
•
P4-08: Minimum torque limits are set to "0".
•
P4-09: The upper limit for the regenerative torque is set to the maximum permitted
value.
The following hoist parameters are already preset for motors of the same performance
class. However, they can be changed at any time to optimize the system:
•
P2-07: Fixed setpoint speed 7 is the brake release speed (≥ slip speed of the mo-
tor).
•
P2-08: Fixed setpoint speed 8 is the brake application speed (≥ slip speed of the
motor).
•
P2-23: Zero speed holding time.
•
P4-13: Release time of the motor brake.
•
P4-14: Application time of the motor brake.
•
P4-15: Torque threshold for the brake release.
•
P4-16: Torque threshold timeout.
The following parameters are locked:
•
P2-18: Relay contact 2 for controlling the brake rectifier.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 71
5.5.1
General information
•
Clockwise rotating field of the motor corresponds to upward direction.
•
Counterclockwise rotating field of the motor corresponds to downward direction.
•
Stop the motor to reverse the direction of rotation. To do so, activate the brake.
Set the controller inhibit before you reverse the direction of rotation.
5.5.2
Startup for hoist function
Refer to the following section for recommendations for the startup.
Motor data:
•
P1-03/04: Ramp time as short as possible
•
P1-07: Nominal motor voltage
•
P1-08: Nominal motor current
•
P1-09: Rated motor frequency
•
P1-10: Nominal motor speed
Parameter activation:
•
P1-14 = 201 (extended parameter menu)
Motor control:
•
P4-01 = 0 (VFC speed control)
•
P4-05 = Cos φ
In VFC operation, the automatic measuring procedure has to be performed. To
do so, the motor has to be as cold as possible.
Hoist parameter:
P4-12 = 1 (hoist function activated)
Thermal braking resistor protection:
If no sensor is used for protecting the braking resistor, the following parameters can
be used optionally for protection against overtemperature of the braking resistor. How-
ever, only a sensor provides adequate protection.
•
P6-19: Braking resistance value
•
P6-20: Braking resistance power
INFORMATION
When hoist mode is activated, the inverter has to be started with the enable. If the
enable is set at the same time or prior to STO, the inverter stays in "STOP" mode.
To ensure fault-free operation, a braking resistor has to be installed.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
72
5.5.3
Hoisting mode
The following diagram shows hoisting mode.
Setpoint speed
Brake application
speed P2-08
Enable (DI01)
Mechanical brake
Contact relay 2
Brake release
speed P2-07
t1
t2
t4
t 6
t 5
t7
t 3
STO
18014401720170891
t1
Inverter enable
t1 - t2 The motor runs up to brake release speed
(fixed setpoint speed 7).
t2
Brake release speed is reached.
t2 - t3 Torque threshold P4-15 verified. The inverter indicates a fault if the torque
threshold exceeds the timeout set in P4-16.
t3
Relay opens.
t3 - t4 Brake opens within brake release time P4-13.
t4
Brake is released. The drive runs up to the setpoint speed.
t4 - t5 Normal operation
t5
Inverter lock
t5 - t6 Drive slows down to brake application speed
(fixed setpoint speed 8).
t6
Relay closes.
t6 - t7 Brake applied within brake application time P4-14.
t7
Brake is closed and drive stopped.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 73
5.5.4
Troubleshooting and optimizing the hoist function
SP-Err / ENC02:
Increase the speed error window in P6-07 if this error message appears.
In case of problems such as sagging of the hoist, check the following parameters and/
or adapt:
P1-03/04
=
Reduce ramp times, pass through slow speed ranges as quickly as
possible.
P7-10
=
Adjustment of the stiffness, higher values increase the stiffness of
the application.
P4-15
=
Increase torque threshold to brake release.
P7-14/15
=
In case of sagging of the hoist, it is recommended to increase the
boost parameters.
P7-07
=
Set this parameter to 1.
22872051/EN – 09/2016
Fire mode/emergency mode
Operating Instructions – MOVITRAC® LTP-B
74
5.6
Fire mode/emergency mode
Set the fire mode/emergency mode as follows:
•
Perform a motor startup.
•
Set parameter P1-14 to "201" to access further parameters.
•
Set parameter P1-15 to "0" to configure the digital inputs.
•
Configure the inputs depending on the requirements in parameter group P9-xx.
For control via terminals, set parameter P9-09 to "9 = terminal control".
•
Set parameter P9-33 Fire mode/emergency mode input selection to the required
input.
•
Set parameter P6-13 to "0" or "1" depending on the wiring.
•
Set parameter P6-14 to the speed that is to be used in fire mode/emergency
mode. You can specify a positive or a negative speed setpoint.
For evaluating the fire mode/emergency modem, the following two indices can be
read-out via index communication:
•
SBus index 11358 is the fire mode/emergency mode start time: Time stamp re-
lated to (P0-65) at the time of activation of the fire mode/emergency mode.
•
SBus index 11359 is the fire mode/emergency mode runtime in minutes. It spe-
cifies how long the fire mode/emergency mode was active.
INFORMATION
Activating the fire mode/emergency mode has the inverter drive the motor with the
preset values. In this mode, the inverter ignores all faults, shutdowns, setpoints and
enable signals and operates the motor until it is destroyed or even until the loss of
voltage supply. It is also not possible in this mode to perform a reset to the factory
setting.
22872051/EN – 09/2016
Operation at 87 Hz characteristic
Operating Instructions – MOVITRAC® LTP-B 75
5.7
Operation at 87 Hz characteristic
The V/f ratio remains the same at 87 Hz operation. However, higher power and
speeds are generated which causes a higher current flow.
U
f
50 Hz
87 Hz
400 V
230 V
9007206616827403
Do the following to set "87 Hz characteristic" operation:
•
Set parameter P1-07 to star voltage (data on the motor nameplate).
•
Set parameter P1-08 to delta current (data on the motor nameplate).
•
Set parameter P1-09 to "87 Hz".
•
Set parameter P1-10 to "(synchronous speed at nominal frequency) × (87 Hz /
50 Hz) - (slip speed at nominal frequency)".
Example for calculating P1-10:
DRN80M4: 0.75 kW, 50 Hz
Nominal speed 1440 1/min
P1-10 = 1500 1/min × (87 Hz / 50 Hz) - (1500 1/min - 1440 1/min) = 2550 1/min
INFORMATION
Set P1-01 maximum speed according to your requirements. In 87 Hz operation, the
inverter has to provide a current that is √3-times higher. For this purpose, select an
inverter with a √3-times higher power rating.
5.8
Motor potentiometer function – crane application
The motor potentiometer works like an electromechanical potentiometer that increases
or decreases the internal value depending on the signals at the inputs, and con-
sequently increases or decreases the motor speed.
INFORMATION
In case of deviating terminal assignment, the inputs can also be configured individu-
ally.
22872051/EN – 09/2016
Motor potentiometer function – crane application
Operating Instructions – MOVITRAC® LTP-B
76
5.8.1
Motor potentiometer operation
The following figure shows the basic function of the motor potentiometer. The descrip-
tion in chapter "Parameter settings" (→ 2 77) is based on the frequently used crane
function and works according to the terminal assignment in chapter "Terminal
assignment" (→ 2 77).
Maximum speed
Minimum speed
Enable input source
CW/CCW input source
Motor potentiometer
up input source
Fixed setpoint speed 1
input source
Fixed setpoint speed 1
Motor potentiometer
down input source
t1 t2 t3 t4 t5 t6 t7 t8 t9 t10 t11 t12 t13
18014406340232971
t1
Inverter enable
t1 - t2
Motor runs up to the set minimum speed (P1-02).
t2 - t3
Motor maintains minimum speed.
t3
Motor potentiometer up (P9-28) is activated.
t3 - t4
As long as the signal is present at P9-28, the motor speed is increased along acceleration ramp
P1-03.
t4 - t5
If no signal is present any longer at P9-28, the actual speed is maintained.
t5
Motor potentiometer up (P9-28) is activated.
t5 - t6
As long as the signal is present at P9-28, the motor speed is increased along the acceleration ramp
(P1-03) until it reaches maximum speed (P1-01).
t6 - t7
The maximum speed is not exceeded and is maintained when the signal is no longer present at
P9-28.
t7
Motor potentiometer down (P9-29) is activated.
t7 - t8
As long as the signal is present at P9-29, the motor speed is decreased along deceleration ramp
P1-04.
t8 - t9
If no signal is present any longer at P9-28, the actual speed is maintained.
t9
Fixed setpoint speed is activated.
t9 - t11
As long as the signal is present at fixed setpoint speed, the motor speed is decreased along decel-
eration ramp P1-04 until it reaches the fixed setpoint speed. This speed is then maintained.
t11
Motor potentiometer down (P9-29) is activated.
t11 - t12
As long as the signal is present at P9-29, the motor speed is decreased along deceleration ramp
P1-04 but not below the minimum speed P1-02.
22872051/EN – 09/2016
Motor potentiometer function – crane application
Operating Instructions – MOVITRAC® LTP-B 77
5.8.2
Terminal assignment
1
2
3
4
5
6
[1] [2] [3]
[4]
7834026891
[1]
DI1 Reduce enable/speed
[2]
DI2 Increase speed
[3]
DI3 Fixed setpoint speed 1
[4]
DI4 Change of direction (clockwise rotation/counterclockwise rotation)
5.8.3
Parameter settings
Start up the motor as described in chapter "Startup" (→ 2 59).
Make the following settings to being able to use the motor potentiometer:
•
P1-12 = 0 (control signal source terminal mode)
•
P1-14 = 201 (extended parameter menu)
•
P1-15 = 0 (digital input function selection)
•
P2-37 = 6 (keypad restart speed).
Input configuration:
•
P9-01 = din-1 (input source enable)
•
P9-03 = din-1 (input source for clockwise rotation)
•
P9-06 = din-4 (direction of rotation reversal)
•
P9-09 = on (terminal control enable source)
•
P9-10 = d-Pot (speed source 1)
•
P9-11 = PrE-1 (speed source 2)
•
P9-18 = din-3 (input speed selection 0)
•
P9-28 = din-2 (input source motor potentiometer open).
User settings:
•
P1-02 = minimum speed
•
P1-03 = acceleration ramp time
•
P1-04 = deceleration ramp time
•
P2-01 = fixed setpoint speed 1.
22872051/EN – 09/2016
Examples of analog input scaling and offset setting
Operating Instructions – MOVITRAC® LTP-B
78
5.9
Examples of analog input scaling and offset setting
Analog input format, scaling and offset are connected to each other.
Inverter setting:
P1-01 = 50 Hz
5.9.1
Example 1: Analog input scaling
Control 0 – 40 Hz with analog input 0 – 10 V:
n1 = 0 Hz, n2 = 40 Hz
0
2
4
6
8
10
Analog input
Speed
0
10
20
30
40
50
P2-31 = 80%
Hz
V
13627147915
P2 - 31
n - n
P1- 01
Hz
Hz
Hz
2
1
=
×
=
−
×
=
100
40
0
50
100
80
%
�
%
%
13624278667
22872051/EN – 09/2016
Examples of analog input scaling and offset setting
Operating Instructions – MOVITRAC® LTP-B 79
5.9.2
Example 2: Analog input offset
Control 15 – 35 Hz with analog input 0 – 10 V:
n1 = nOffset = 15 Hz, n2 = 35 Hz
0
2
4
6
8
10
Analog input
P2-31 = 40%, P2-32 = -75%
Speed
0
10
20
30
40
50
5
15
25
45
35
V
Hz
13627144971
P2 - 31
n - n
P1- 01
Hz
Hz
Hz
2
1
=
×
=
−
×
=
100
35
15
50
100
40
%
�
%
%
13624281611
P2 - 32
n
P1- 01
P2 - 31
Hz
Hz
Offset
=
−
×
=
−
×
= −
100
15
50
100
0 40
75
%
�
%
.
%
13624284555
22872051/EN – 09/2016
Examples of analog input scaling and offset setting
Operating Instructions – MOVITRAC® LTP-B
80
5.9.3
Example 3: Analog input scaling and offset
Control 15 - 45 Hz with analog input 3 - 8 V:
3
4
5
6
7
8
0
10
20
30
40
50
5
15
25
45
35
V
Hz
Analog input
Speed
P2-31 = 120%, P2-32 = 5%
18364553227
18364558219
18364573451
22872051/EN – 09/2016
Fans and pumps
Operating Instructions – MOVITRAC® LTP-B 81
5.10
Fans and pumps
The following functions are available for applications with pumps or fans:
•
Voltage increase/boost (P1-11)
•
Adjustment of the V/f characteristic curve (P4-10, P4-11)
•
Energy-saving function (P1-06)
•
Flying start function (P2-26)
•
Zero speed holding time (P2-23)
•
Standby mode (P2-27)
•
PID controller, see "Parameter group 3: PID controller (level 2)" (→ 2 142)
•
Fire mode/emergency mode, see "Fire mode/emergency mode" (→ 2 74)
•
Deactivating slip compensation via rated motor speed (P1-10)
5.11
Motor potentiometer
The motor potentiometer function lets the inverter respond to key commands.
If the digital inputs are activated that increase or decrease the speed, the speed
changes along the preset ramp P1-03 and P1-04.
If both digital inputs are activated at the same time, the inverter stops along the rapid
stop ramp P2-25. If none of the two inputs are activated, the current speed and direc-
tion of rotation are maintained.
The enable is superordinate to this function and is necessary for the function.
To use the motor potentiometer function, select one of the possible function selections
of the digital inputs with P1-15 = 10 or 20. See also chapter "P1-15 Digital input
function selection" (→ 2 126).
When using this function, the arrow-up and arrow-down keys can be used directly at
the inverter.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
82
5.12
3-wire control
The function is activated via the digital input function selection P1-15 = 21.
The 3-wire control principle determines the control.
The enable and direction of rotation signals of the inverter then react edge controlled.
•
Connect start key with NO contact to digital input DI1.
•
Connect start key with NO contact to digital input DI3.
•
Connect stop key as NC contact to digital input DI2.
If you connect and at the same time, the drive decelerates along the
rapid stop ramp P2-25.
5.12.1
Control signal source 3-wire control
fA Hz
DI 1
DI 2
DI 3
+10 V
+24 V
AI 1
0 V
10
11
12
13
STO+
STO-
DI 1
DI 3
DI 2
AI 1
18826070667
DI 1
CW/stop
CW
Clockwise rotation
DI 3
CCW/stop
CCW
CCW rotation
DI 2
Enable/stop
[1]
Ramp up (P1-03)
AI 1
Setpoint input AI
[2]
Ramp down (P1-04)
fA
Output frequency
f0
Start/stop frequency
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 83
6
Operation
The following information is displayed to being able to read off the operating state of
the inverter at any time:
Status
Abbreviation display
Drive OK
Static inverter status
Drive running
Operating state of the inverter
Fault / trip
Fault
6.1
Inverter status
6.1.1
Static inverter status
The list below shows the abbreviations that are displayed to indicate the inverter
status when the motor is at standstill.
Abbrevi-
ation
Description
StoP
Power section of inverter disabled. This message is displayed when the inverter is at a standstill
and no error is pending. The inverter is ready for normal operation. The inverter is not enabled.
P-deF
Preset parameters are loaded. This message appears when the user issues the command for
loading the parameters set at the factory. You have to press the key before the in-
verter can resume operation.
Standby
The inverter is in standby mode. When P2-27 > 0 s, this message appears when the inverter has
stopped and the setpoint is also "0".
Inhibit
Is displayed when 24 V and GND are not present at the STO contacts. The output stage is inhib-
ited.
ETL 24
External voltage supply is connected. The functions are limited, see also chapter "24 V backup
mode" (→ 2 48).
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
84
6.1.2
Operating state of the inverter
The list below shows the abbreviations that are displayed to indicate the inverter
status when the motor is running.
Pressing the "Navigate" key on the keypad lets you toggle between output frequency,
output current, output power and speed.
Abbrevi-
ation
Description
H xxx
Output frequency of the inverter (in Hz). This message is displayed while the inverter is run-
ning.
A xxx
Output current of the inverter (in Ampere). This message is displayed while the inverter is run-
ning.
P xxx
Current output power of the inverter (in kW). This message is displayed while the inverter is
running.
L xxx
The parameter is locked for changes. Make sure that:
- The parameter lock P2-39 is not activated.
- The inverter is not enabled.
- The inverter is supplied with line voltage.
Auto-t
The motor parameters are measured automatically to configure the motor parameters. Auto
tune runs automatically when receiving the first enable signal after operation with factory-set
parameters. No hardware enable is required for running auto tune.
Ho-run
Reference travel started. Wait until the inverter has reached the reference position. After suc-
cessful reference travel, "Stop" appears on the display.
xxxx
Output speed of the inverter (in 1/min). This message appears while the inverter is running if
the rated speed of the motor was entered in parameter P1-10.
C xxx
Is the scaling factor "Speed" (P2-21 / P2-22).
. . . . . .
(flashing
dots)
The output current of the inverter exceeds the current value entered in P1-08.
The inverter monitors the extent and the duration of the overload. The inverter indicates fault
"I.t-trP" depending on the extent of the overload.
FirE
Fire mode/emergency mode is active.
Select lan-
guage
List to select one of the available languages. To select a language, use the key.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 85
6.1.3
Status displays of the parameter module
The parameter module status is displayed on the frequency inverter display.
Display
Description
PASS-r
The parameter module successful read/saved the frequency inverter parameters.
OS-Loc
The parameter module is locked. Attempt to read parameter from frequency inverter with
activated parameter module lock.
FAiL-r
The parameter module could not read parameters from the frequency inverter.
PASS-t
The parameter module successfully transferred the parameters to the frequency inverter.
Writing of parameters to the frequency inverter.
FAiL-P
The power ratings of the parameter stored in the parameter module do not match the power
ratings of the programmed frequency inverter.
FAiL-t
The parameter module could not transfer the parameter set to the frequency inverter.
no-dAt
No parameter data was saved in the parameter module.
dr-Loc
The frequency inverter parameters were locked. No new parameter settings could be trans-
ferred. Unlock the parameter set of the frequency inverter.
dr-rUn
Frequency inverter is running and cannot accept any new parameter settings. Stop the fre-
quency inverter before programming.
tyPE-E
The parameters for the frequency inverter type saved in the parameter module do not
match the frequency inverter type to be programmed (only writing).
tyPE-F
The parameter module does not yet support the programmed frequency inverter type.
6.1.4
Fault reset
You can reset a fault by pressing the key or by opening and closing di-
gital input 1. For further information, refer to chapter "Error codes" (→ 2 87).
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
86
6.2
Troubleshooting
Symptom
Cause and solution
Overload or overcurrent error of the
unloaded motor during acceleration
Check the star/delta terminal connection in the motor. The nominal
operating voltage of motor and inverter must match. Delta connec-
tion always yields the lower voltage of a multi-voltage motor.
Overload or overcurrent – motor does
not turn
Check whether the rotor is blocked. Make sure that the mechanical
brake is released (if installed).
No enable for the inverter – display
shows "StoP"
•
Check whether the hardware enable signal is present at digital
input 1.
•
Ensure proper +10 V user output voltage (between terminals 5
and 7).
•
If faulty, check the wiring of the user terminal strip.
•
Check P1-12 for terminal mode/keypad mode.
•
If keypad mode is selected, press the "Start" key.
•
The line voltage must correspond with the specified values.
The inverter does not start at ex-
tremely cold ambient conditions
The inverter might not start at ambient temperatures below –10 °C
Under such conditions, provide a heat source that keeps the ambi-
ent temperature on site above –10 °C.
No access to advanced menus
P1-14 must be set to advanced access code. The value is "101"
unless the user has changed the code in P2-40.
6.3
Error history
Parameter P1-13 in parameter mode archives the 4 most recent errors and/or events.
Each error is displayed in abbreviated form. The most recent error is shown first (when
calling P1-13).
This means that any new error is entered at the top of the list followed by the sub-
sequent errors in the order of their appearance. The oldest fault will be deleted from
the error history.
•
INFORMATION
If the latest error in the error history is an undervoltage fault, no further under-
voltage faults will be entered in the error history. The reason is to avoid that the
error history is filled with undervoltage faults, which occur every time the inverter is
switched off.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 87
6.4
Error codes
Error message
Inverter display P0-13
error history
Error code
status word if
Bit5 = 1
CANopen
Emer-
gency
Code
Explanation
Solution
Inverter
display
MotionStu
dio cod-
ing dec
dec
hex
hex
4-20 F
18
113
0x71
0x1012
Signal loss 4 –
20 mA
• Check whether the input current in P2-30 and P2-33 lies
within the defined range.
• Check the connection cable.
AtF-01
40
81
0x51
0x1028
The measured
stator resistance
fluctuates between
the phases.
The measured stator resistance of the motor is asymmetrical.
Check to see, if:
• the motor is connected correctly and without error.
• the winding has the correct resistance and symmetry.
AtF-02
41
81
0x51
0x1029
The measured
stator resistance is
too high.
The measured stator resistance of the motor is too high.
Check to see, if:
• the motor is connected correctly and without error.
• the power rating of the motor corresponds with the power
rating of the connected inverter.
AtF-03
42
81
0x51
0x102A
Measured motor
inductance is too
low.
The measured motor inductance is too low.
Make sure that the motor is connected correctly and without
error.
AtF-04
43
81
0x51
0x102B
Measured motor
inductance is too
high.
The measured motor inductance is too high. Check to see, if:
• the motor is connected correctly and without error.
• the power rating of the motor corresponds with the power
rating of the connected inverter.
AtF-05
44
81
0x51
0x102C
Timeout of induct-
ance measure-
ment
The measured motor parameters are not convergent. Check
to see, if:
• the motor is connected correctly and without error.
• the power rating of the motor corresponds with the power
rating of the connected inverter.
dAtA-E
19
98
0x62
0x1013
Internal memory
error (DSP)
Contact the SEW‑EURODRIVE Service.
dAtA-F
17
98
0x62
0x1011
Internal memory
error (IO)
Contact the SEW‑EURODRIVE Service.
E-triP
11
26
0x1A
0x100B
External error at
digital input 5.
NC contact was opened.
• Check motor thermistor (if connected).
Enc-01
30
14
0x0E
0x101E
Communication
error between en-
coder card and in-
verter.
The encoder feedback is activated in P6-05, and no encoder
card is plugged in or the encoder card is not recognized.
ENC02/
SP-Err
31
14
0x0E
0x101F
Speed fault
(P6-07)
The difference between actual speed and setpoint speed is
perceptually larger than the value set in P6-07. This error ap-
plies only to vector control or control with encoder feedback.
Set a higher value in P6-07.
If you wish to deactivate the speed monitoring, set P6-07 to
100%.
Enc-03
32
14
0x0E
0x1020
Incorrect PPR
count setting.
Check the parameter settings in P6-06 and P1-10.
Enc-04
33
14
0x0E
0x1021
Encoder channel
A error
The A track of the encoder feedback is not present. Check
the wiring.
Enc-05
34
14
0x0E
0x1022
Encoder channel
B error
The B track of the encoder feedback is not present. Check
the wiring.
Enc-06
35
14
0x0E
0x1023
Encoder channel
A or B error
The A and B track of the encoder feedback are not present.
Check the wiring.
Enc-07
36
14
0x0E
0x1024
RS485 data chan-
nel error,
HIPERFACE® data
channel error
Communication error between encoder card and encoder.
Check the encoder card for correct seat and contact.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
88
Error message
Inverter display P0-13
error history
Error code
status word if
Bit5 = 1
CANopen
Emer-
gency
Code
Explanation
Solution
Inverter
display
MotionStu
dio cod-
ing dec
dec
hex
hex
Enc-08
37
14
0x0E
0x1025
HIPERFACE® I/O
communication
channel error
Communication error between encoder card and inverter.
Check the encoder card for correct seat and contact.
Enc-09
38
14
0x0E
0x1026
HIPERFACE® type
not supported.
During the use of Smart Servo Package, a wrong motor/in-
verter combination was used. Check to see, if:
• The speed class of the CMP.. motor is 4500 1/min.
• The nominal motor voltage equals the nominal inverter
voltage.
• A HIPERFACE® encoder is used.
Enc-10
39
14
0x0E
0x1027
Trigger: KTY
KTY not triggered or not connected.
Er-LED
Display error
Contact the SEW‑EURODRIVE Service.
Err-SC
The keypad lost
the communication
connection to the
inverter.
Press the STOP key to reset. Check the address of the fre-
quency inverter.
Etl-24
External 24 V sup-
ply.
Line voltage supply not connected. The inverter is externally
supplied with 24 V.
FAULtY
The communica-
tion between con-
troller and power
section is interrup-
ted.
Contact the SEW‑EURODRIVE Service.
F-Ptc
21
31
0x1F
0x1015
Motor protection
triggered
The connected motor protection sensor is defined in P2-33
(PTC, TF, TH, KTY or PT1000), and connected to the analog
input 2 (terminal 10).
FAN-F
22
50
0x32
0x1016
Internal fan error.
Contact the SEW‑EURODRIVE Service.
FLt-dc
13
7
0x07
0x320D
DC link ripple too
high.
Check the current supply.
Ho-trP
27
39
0x27
0x101B
Error during refer-
ence travel.
• Check reference cams
• Check limit switch connection
• Check reference travel type setting and the parameters re-
quired for it.
Inhibit
STO safety circuit
open.
Check to see if the terminals 12 and 13 are connected cor-
rectly.
Lag-Er
28
42
0x2A
0x101C
Lag error
Check:
• the encoder connection
• the wiring of encoder, motor and line phases
• if the mechanical components can move freely and are not
blocked.
• Extend the ramps.
• Set a higher P component.
• Parameterize the speed controller again.
• Extend the lag error tolerance.
• Set PLC Prog Task Priority to 10 ms
• The inverter is operated in Derating and cannot provide the
current for acceleration/constant travel.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 89
Error message
Inverter display P0-13
error history
Error code
status word if
Bit5 = 1
CANopen
Emer-
gency
Code
Explanation
Solution
Inverter
display
MotionStu
dio cod-
ing dec
dec
hex
hex
I.t-trp
04
8
0x08
0x1004
Overload of in-
verter/motor
(l2t error)
Make sure that:
• The motor nameplate parameters are correctly inserted in
P1-07, P1-08 and P1-09.
• In vector mode (P4-01 = 0 or 1), the motor power factor in
P4-05 is correct.
• Auto Tune has correctly been performed.
Check to see, if:
• The decimals flash (inverter overloaded), increase the ac-
celeration ramp (P1-03) or decrease the motor load.
• The length of the cable meets the requirements.
• The load can move freely and there are no blockages or
other mechanical faults (mechanically check the load).
• The thermal motor protection to UL508C is activated in
P4-17.
O-I
03
1
0x01
0x2303
Short-term over-
current at the in-
verter output.
High motor over-
load.
Fault during stop procedure:
Check for premature brake application.
Fault while enabling the inverter:
Check to see, if:
• The motor nameplate parameters are correctly inserted in
P1-07, P1-08 and P1-09.
• In vector mode (P4-01 = 0 or 1), the motor power factor in
P4-05 is correct.
• Auto Tune has correctly been performed.
• The load can move freely and there are no blockages or
other mechanical faults (mechanically check the load).
• A short circuit between the phases or a ground fault of a
phase occurred at the motor and motor connection cable.
• The brake is connected correctly, controlled correctly and
correctly releases when the motor has a holding brake.
Reduce the settings of the voltage enhancement in P1-11.
Set a longer run-up time in P1-03.
Disconnect the motor from the inverter. Enable the inverter
again. If this error occurs again, check the entire system and
completely replace the inverter.
Fault during operation:
Check:
• For sudden overload or malfunction.
• the cable connection between inverter and motor.
The acceleration/deceleration time is too short and requires
too much power. If you cannot increase P1-03 or P1-04, use
a larger inverter.
hO-I
15
1
0x01
0x230F
Hardware overcur-
rent error at the in-
verter output
(IGBT self-protec-
tion in case of
overload).
O-hEAt
23
124
0x7C
0x4117
Ambient temperat-
ure too high.
Check if the ambient conditions are within the range specified
for inverters.
O-t
8
11
0x0B
Heat sink overtem-
perature
The heat sink temperature can be displayed via P0-21. A his-
torical protocol is saved in parameter P0-38 in 30 s intervals
prior to a switch off with error. This error message is dis-
played at a heat sink temperature of ≥90 °C.
Check:
• The ambient temperature of the inverter.
• The inverter cooling and housing dimensions.
• The function of the internal cooling fan of the inverter.
Reduce the settings of the effective clock frequency in para-
meter P2-24, or the load at motor/inverter.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
90
Error message
Inverter display P0-13
error history
Error code
status word if
Bit5 = 1
CANopen
Emer-
gency
Code
Explanation
Solution
Inverter
display
MotionStu
dio cod-
ing dec
dec
hex
hex
O-torq
24
52
0x34
0x1018
Maximum torque
limit timeout.
Check the motor load.
Set a higher value in P6-17 if required.
If you wish to deactivate the torque monitoring, set P6-07 to
0.0 s.
O-Volt
06
7
0x07
0x3206
DC link over-
voltage
The error occurs if a high flywheel load or overhauling load is
connected, and the excess regenerative energy is transferred
back to the inverter.
If an error occurs while stopping or during deceleration, in-
crease the deceleration ramp time P1-04 or connect a suit-
able braking resistor to the inverter.
The proportional gain in P4-03 is reduced in vector mode.
In PID control mode ensure that the ramps are active by re-
ducing P3-11.
Additionally check if the supply voltage is within the specified
range.
Information: The value of the DC bus voltage can be dis-
played on P0-20. A historical protocol is saved in parameter
P0-36 in 256 ms intervals prior to a switch off with error.
OI-b
01
4
0x04
0x2301
Brake channel
overcurrent,
Brake resistor
overload
Make sure that the connected braking resistor does not fall
below the minimum value approved for the inverter (see tech-
nical data). Check the braking resistor and the wiring for pos-
sible short circuits.
OL-br
02
4
0x04
0x1002
Braking resistor
overload
The software detected an overload at the braking resistor
and switches off to protect the resistor. Make sure that the
braking resistor is operated within the planned parameters
before performing any changes to parameters or system. To
reduce the load at the resistor, increase the deceleration
time, reduce the loads mass moment of inertia, or connect
additional braking resistors in parallel. Note the minimum res-
istor values for the used inverter.
OF-01
60
28
0x1C
0x103C
Internal connec-
tion to option
module error.
Contact the SEW‑EURODRIVE Service.
OF-02
61
28
0x1C
0x103D
Option module
error
Contact the SEW‑EURODRIVE Service.
Out-F
26
82
0x52
0x101A
Inverter output
stage error
Contact the SEW‑EURODRIVE Service.
P-LOSS
14
6
0x06
0x310E
Input phase failure An input phase has been separated or interrupted at an in-
verter planned for a 3-phase supply.
P-dEF
10
9
0x09
0x100A
Factory settings
are restored.
Ph-Ib
Unequal voltage at
the input phases
• Check the device input voltage.
• Check the values in P0-22, P0-23, P0-24.
The values may deviate maximum ±10%. Use an input choke
if required.
PS-trP
05
200
0xC8
0x1005
Output stage error
(IGBT self-protec-
tion in case of
overload)
See error O-I.
SC-0b5
12
29
1D
Connection
between inverter
and keypad inter-
rupted.
Connection between inverter and keypad.
SC-F03
52
41
0x29
0x1034
Fieldbus module
communication
error (fieldbus
side)
Contact the SEW‑EURODRIVE Service.
SC-F04
53
41
0x29
0x1035
Communication
error IO option
card
Contact the SEW‑EURODRIVE Service.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 91
Error message
Inverter display P0-13
error history
Error code
status word if
Bit5 = 1
CANopen
Emer-
gency
Code
Explanation
Solution
Inverter
display
MotionStu
dio cod-
ing dec
dec
hex
hex
SC-F05
54
41
0x29
0x1036
LTX module com-
munication error
Contact the SEW‑EURODRIVE Service.
SC-F01
50
43
0x2B
0x1032
Modbus commu-
nication error
Check the communication settings.
SC-F02
51
47
0x2F
0x1033
SBus/CANopen
communication
error
Check:
• The communication connection between inverter and ex-
ternal devices.
• The clearly assigned address per inverter in the network.
SC-LoS
The communica-
tion between con-
troller and power
section is interrup-
ted.
Contact the SEW‑EURODRIVE Service.
SC-OBS
The keypad lost
the communication
connection to the
frequency inverter.
Press the key to reset. Check the address of the in-
verter.
Sto-F
29
115
0x73
0x101D
STO circuit error
Inverter is defective, replace device.
StoP
The inverter is not
enabled.
Activate the enable. Make sure that the enable is switched on
after the STO for the hoist function.
th-Flt
16
31
0x1F
0x1010
Faulty thermistor
at heat sink.
Contact the SEW‑EURODRIVE Service.
type-f
Parameter module
and inverter are
not compatible.
The used parameter module is not of type LT BP C.
U-dEF
User settings
loaded.
The parameter set saved in P6-26 has been restored.
U-torq
25
52
0x34
0x1019
Minimum torque
limit timeout
(hoist).
The torque threshold has not been exceeded in time.
Increase the time in P4-16 or the torque limit in P4-15.
U-t
09
117
0x75
0x4209
Undertemperature Occurs at an ambient temperature below -10 °C. Increase
the temperature to above -10 °C to start the inverter.
U-Volt
07
198
0xC6
0x3207
DC link under-
voltage
Occurs routinely when switching off the inverter.
Check line voltage if this occurs while the inverter is running.
USr-cL
Parameter backup
successfully de-
leted.
The parameter set was successfully deleted using P6-26.
USr-PS
Parameter backup
successfully com-
pleted.
The parameter set was successful saved using P6-26.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
92
7
Fieldbus mode
7.1
General information
7.1.1
Structure and settings of process data words
Control and status word have a fixed assignment. All the other process data words
can be freely configured as required using parameter group P5-xx.
The structure of process data words is identical for SBus/Modbus RTU/CANopen, as
well as with inserted communication card.
High byte
Low byte
Bit
15 – 8
7 – 0
Process output words
Description
Bit
Settings
PA1
Control
word
0
Output stage inhibit (the motor
coasts to a stop), for brakemotors
the brake is applied immediately.
0: Start
1: Stop
1
Rapid stop along the second decel-
eration ramp/rapid stop ramp
(P2-25)
0: Rapid stop
1: Start
2
Stop along process ramp P1-03 /
P1-04 or PO3
0: Stop
1: Start
3 – 5
Reserved
0
6
Error reset
Edge 0 set to 1 =
error reset
7 – 15 Reserved
0
PO2
Setpoint speed in % (default setting), freely configurable via P5-09
PO3
No function, freely configurable via P5-10
PO4
No function, freely configurable via P5-11
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 93
Process input words
Description
Bit
Settings
Byte
PI1
Status word 0
Output stage enable
0: Disabled
1: Enabled
Low byte
1
Frequency inverter ready
for operation
0: Not ready
1: Ready
2
PO data enabled
1 if P1-12 = 5
3 – 4
Reserved
5
Fault/warning
0: No error
1: Fault
6
Positive limit switch active
(limit switch assignment
can be set via P1-15 or
P9-30/P9-31).1)
0: Disabled
1: Enabled
7
Negative limit switch act-
ive (limit switch assign-
ment can be set via P1-15
or P9-30/P9-31).
0: Disabled
1: Enabled
8 – 15
Frequency inverter status if bit 5 = 0
0x01 = STO – Safe torque off active
0x02 = no enable
0x05 = speed control
0x06 = torque control
0x0A = technology function
0x0C = reference travel
High byte
Frequency inverter status if bit 5 = 1
PI2
Actual
speed
Freely configurable via P5-12
PI3
Actual cur-
rent
Freely configurable via P5-13
PI4
No function, freely configurable via P5-14
1) Refer to the addendum to the operating instructions "MOVITRAC® LTX Servo Module for MOVITRAC®
LTP-B".
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
94
7.1.2
Communication example
The following information is sent to the inverter if
•
The digital inputs have been configured and wired properly to enable the inverter.
Description
Value
Description
PO1
Control word
0x0000
Stop along the second Deceleration ramp (P2-25).
0x0001
Coast to a stop
0x0002
Stop along the process ramp (P1-04) or (PO3).
0x0003 -
0x0005
Reserved
0x0006
Accelerate along a ramp (P1-03) or (PO3) and run at setpoint speed
(PO2)
PO2
Setpoint speed 0x4000
= 16384 = max. speed, e.g. 50 Hz (P1-01) CW
0x2000
= 8192 = 50% of the max. speed, e.g. 25 Hz CW
0xC000
= -16384 = max. speed, e.g. 50 Hz (P1-01) CCW
0x0000
= 0 = min. speed, set in P1-02
0xF100
= 8192 = 50% of the max. speed, e.g. 25 Hz CCW
The process data sent by the inverter should look as follows during operation:
Description
Value
Description
PI1
Status word
0x0407
Status = running, output stage enabled;
inverter ready, PO data enabled
PI2
Actual speed
Should correspond to PO2 (setpoint speed)
PI3
Actual current
Depends on speed and load
7.1.3
Parameter settings for the inverter
•
Take the inverter into operation as described in chapter "Simple startup" (→ 2 59).
•
Set the following parameters depending on the bus system used:
Parameters
SBus
CANopen
Modbus RTU1)
P1-12 (control signal source)
5
6
7
P1-14 (extended parameter menu)
201
201
201
P1-15 (function selection digital inputs)
12)
12)
12)
P5-01 (inverter address)
1 – 63
1 – 63
1 – 63
P5-02 (SBus baud rate)
Baud rate
Baud rate
--
P5-03 (Modbus baud rate)
--
--
Baud rate
P5-04 (Modbus data format)
--
--
Data format
P5-053) (behavior in the event of communica-
tion failure)
0-1-2-3
0-1-2-3
0-1-2-3
P5-063) (communication failure timeout)
0.0 – 1.0 – 5.0 s
Communication monitoring is
covered by the Lifetime or Heart-
beat functions integrated in
CANopen.
0.0 – 1.0 – 5.0 s
P5-073) (ramp specified via fieldbus)
0 = Specified via P1-03/04
1 = specified via fieldbus4)
0 = specified via P1-03/04
1 = specified via fieldbus4)
0 = specified via
P1-03/04
1 = specified via
fieldbus4)
P5-XX (fieldbus parameter)
More setting options5) .
More setting options5)
More setting options5)
1) Modbus RTU is not available when the LTX encoder module is installed.
2) Default setting; for more setting options, refer to the description of parameter P1-15.
3) These parameters can remain set to their default values for the time being.
4) When specifying the ramp via fieldbus, P5-10 =3 must be set (PO3 = ramp time).
5) You can make more fieldbus settings and define the process data in detail in parameter group P5-xx, see chapter "Parameter group
5"
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 95
7.1.4
Connecting the signal terminals at the inverter
For bus mode, you can connect the signal terminals using the default setting of P1-15
as described in chapter "Overview of signal terminals" (→ 2 44). When the DI3 signal
level changes, the system toggles between the speed setpoint source fieldbus (low)
and fixed setpoint 1 (high).
7.1.5
Establishing a CANopen/SBus network
A CAN network as depicted in the figure below should always have a linear bus struc-
ture without stub lines [1] or only with very short ones [2]. The network must have ex-
actly one terminating resistor RT = 120 Ω installed on both ends of the bus. The cable
sets described in the "MOVITRAC® LTP-B" catalog are available for easily establish-
ing such a network.
[1]
[2]
CAN-High
CAN-Low
RT
CAN-High
CAN-Low
RT
7338031755
7338031755
Cable length
The permitted total cable length depends on the baud rate set in parameter P5-02:
•
125 kBd: 500 m (1640 ft)
•
250 kBd: 250 m (820 ft)
•
500 kBd: 100 m (328 ft)
•
1000 kBd: 25 m (82 ft)
22872051/EN – 09/2016
Connecting a gateway or a controller (SBus MOVILINK)
Operating Instructions – MOVITRAC® LTP-B
96
7.2
Connecting a gateway or controller (SBus MOVILINK®)
Connecting
a gateway
or a
controller
(SBus MOV
ILINK)
7.2.1
Specification
The
MOVILINK®
profile
via
CAN/SBus
is
an
application
profile
from
SEW‑EURODRIVE specifically adjusted to SEW inverters. For detailed information,
refer to the "MOVIDRIVE® MDX60B/61B Communication and Fieldbus Device Profile"
manual.
For using SBus, configure the inverter as described in chapter "Parameter settings for
the inverter" (→ 2 94). Status and control word are fixed, all other process data words
can be configured as required in parameter group P5-xx.
For detailed information on the structure of process data words, refer to chapter Struc-
ture of process data words of inverters with factory setting. You find a detailed list of
all parameters including the necessary indexes as well as the scaling in chapter
"Parameter register" (→ 2 116).
7.2.2
Electrical installation
Connecting gateway and MOVI‑PLC®.
B
D
D
D
C
E
max. 8
F
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
MOVITRAC
® LT
L1/L L2/N L3
+
BR
U
V
W
1 2 3 4 5 6 7 8 9 10 1112 13
14 15 16 17 18
IOIOI
IOIOI
IOIOI
A
B
DFP 21B
RUN
X30
BUS
FAULT
ADDRESS
20
0
1
21
22
23
24
25
26
nc
9007206593403147
[A]
Bus connection
[D]
Splitter
[B]
Gateway, e.g. DFx/UOH
[E]
Connection cable
[C]
Connection cable
[F]
Y connector with terminating resistor
INFORMATION
As of firmware version 1.20, a backup mode for maintaining communication in the
event of a power failure is possible, for older versions this is not possible. Please also
observe chapter "24 V backup mode" (→ 2 48).
The terminating connector [F] is equipped with 2 terminating resistors and therefore
establishes the terminating connection to CAN/SBus and Modbus RTU.
Instead of a terminating connector of cable set A, you can use the Y adapter of engin-
eering cable set C. This set also includes a terminating resistor. You find detailed in-
formation on cable sets in the "MOVITRAC® LTP-B" catalog.
22872051/EN – 09/2016
Connecting a gateway or a controller (SBus MOVILINK)
Operating Instructions – MOVITRAC® LTP-B 97
Wiring from the control to the "communication socket RJ45" (→ 2 47) of the inverter:
Side view
Designation
Terminal at CCU/PLC
Signal
RJ45 socket1)
Signal
2 3 4 5 6 7
1
X26
MOVI-PLC® or Gate-
way (DFX/UOH)
X26:1
CAN 1H
2
SBus/CAN bus h
X26:2
CAN 1L
1
SBus/CAN bus l
X26:3
DGND
3
GND
X26:4
Reserved
X26:5
Reserved
X26:6
DGND
X26:7
DC 24 V
Third party controller
X:?2)
Modbus RTU+
8
RS485+ (Modbus RTU)
X:?2)
Modbus RTU-
7
RS485- (Modbus RTU)
X:?2)
DGND
3
GND
1) Please observe: The terminal assignment for the socket of the inverter, not the connector, is specified above.
2) Assignment depends on the third-party controller.
7.2.3
Startup at gateway
•
Connect the gateway as described in chapter "Electrical installation" (→ 2 96).
•
Reset all settings of the gateway to the factory setting.
•
If required, set all connected inverters to SBus MOVILINK® mode as described in
chapter "Parameter settings for the inverter" (→ 2 94). Assign unique SBus ad-
dresses (≠ 0!) and set a baud rate matching the gateway (default = 500 kBaud).
•
Set DIP switch AS (auto-setup) on the DFx/UOH gateway from "OFF" to "ON" to
perform an auto-setup for the fieldbus gateway.
The "H1" LED on the gateway lights up repeatedly and then goes off completely.
When the "H1" LED is lit, the gateway or one of the inverters at the SBus has not
been wired properly or has not been taken into operation properly.
•
Refer to the relevant DFx manual for information on how to establish fieldbus com-
munication between DFx/UOH gateway and bus master.
Monitoring sent data
The data sent via gateway can be monitored as follows:
•
Using MOVITOOLS® MotionStudio via the X24 engineering interface of the gate-
way or optionally via Ethernet.
•
Via the website of the gateway, for example to the DFE3x Ethernet gateway.
•
You can check which process data are transferred with the respective parameters
in parameter group 0.
22872051/EN – 09/2016
Connecting a gateway or a controller (SBus MOVILINK)
Operating Instructions – MOVITRAC® LTP-B
98
7.2.4
Startup at a CCU
Before taking the inverter into operation with "Drive Startup" in MotionStudio, you have
to set the following parameters directly on the inverter:
•
Set parameter P1-14 to "1" to obtain access to the LTX-specific parameter group
P1-01 – P1-20.
•
If a HIPERFACE® encoder is connected to the encoder card, then P1-16 must in-
dicate the proper motor type. If not, select the proper motor type using the
and keys.
•
Assign a unique inverter address in P1-19. Changing these parameters will directly
affect parameters P5-01 and P5-02.
•
Set the SBus baud rate (P1-20) to 500 kBaud.
7.2.5
MOVI‑PLC® motion protocol (P1-12 = 8)
If you operate the inverter with or without LTX encoder module, with MOVI-PLC® or
CCU, the following parameters have to be set on the inverter:
•
Set P1-14 to "1" for access to the LTX-specific parameter group. Parameters
P1-01 – P1-20 are then visible.
•
If a HIPERFACE® encoder is connected to the encoder card, then P1-16 indicates
the proper motor type. If not, select the respective motor type using the "Up" and
"Down" keys.
•
Assign a unique inverter address in P1-19.
•
Set the SBus baud rate (P1-20) to "1000 kBaud".
•
Perform a Drive Startup with the MOVITOOLS® MotionStudio software.
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B 99
7.3
Modbus RTU
The inverters support communication via Modbus RTU. Holding registers (03) are
used for reading, and single holding registers (06) for writing. For using Modbus RTU,
configure the inverter as described in chapter "Parameter settings for the
inverter" (→ 2 94).
Note: Modbus RTU is not available when the LTX encoder module is plugged.
7.3.1
Specification
Protocol
Modbus RTU
Error checking
CRC
Baud rate
9600 bps, 19200 bps, 38400 bps, 57600 bps, 115200 bps
(default)
Data format
1 start bit, 8 data bits, 1 stop bit, no parity
Physical format
RS485 2 core
User interface
RJ45
7.3.2
Electrical installation
The structure is the same as for the CAN/SBus network. The maximum number of bus
nodes is 32. The permitted cable length depends on the baud rate. With a baud rate of
115200 bps and a 0.5 mm2 cable, the maximum cable length is 1200 m. For the con-
nection assignment for the RJ45 communication socket, refer to chapter "RJ45
communication socket" (→ 2 47).
22872051/EN – 09/2016
Operating Instructions – MOVITRAC® LTP-B
100
7.3.3
Register allocation of the process data words
The process data words are allocated to the Modbus registers shown in the table. The
status and control words have a fixed allocation. The other process data words can be
configured as required in parameter group P5-xx.
The table shows the default allocation of process data words. All other registers are
usually allocated in such a way that they correspond to the parameter number (101 =
P1-01). However, this does not apply to parameter group 0.
Register
Upper byte
Lower byte
Com-
mand
Type
1
PO1 control word (fixed)
03, 06
Read / Write
2
PO2 (default setting in P5-09 =1; speed setpoint)
03, 06
Read / Write
3
PO3 (default setting in P5-10 =7; no function)
03, 06
Read / Write
4
PO4 (default setting in P5-11 =7; no function)
03, 06
Read / Write
5
Reserved
-
03
Read
6
PI1 status word (fixed)
03
Read
7
PI2 (defafult setting in P5-12 =1; actual speed)
03
Read
8
PI3 (default setting in P5-13 =2; actual current)
03
Read
9
PI4 (default setting in P5-14 =4; power)
03
Read
…
For more registers, refer to chapter "Parameter registers" (→ 2 116).
You find the complete allocation of parameters and registers as well as the scaling of
data in the memory allocation plan in chapter "Parameter registers" (→ 2 116).
INFORMATION
Many bus masters address the first register as register 0. It might therefore be neces-
sary to deduct the value "1" from the register number given below to obtain the cor-
rect register address.
22872051/EN – 09/2016