Paradox PGM82 Installation Manual
Read Online
Read the Paradox PGM82 Installation Manual online using the built-in PDF viewer.
Text of the manual
The 8-PGM Expansion Module PGM82 includes eight programmable
relay outputs and is compatible with all Paradox control panels.
Outputs can be independently activated using the Insite GOLD mobile
application, manually by pressing the PGM button on the front cover or
they can be programmed to follow system events. Manual activation
does not require a bus connection.
Compatibility
•
EVO192, EVOHD v6.80 and higher
•
MG5000, MG5050, SP5500, SP6000, SP7000 v6.80 and higher
•
PGM4 v5.01 and higher
•
BabyWare v5.1 and higher
•
Infield v5.1 and higher
•
Insite GOLD iOs v1.5; Android v1.4
Connections
Connect the four terminals labeled RED BLK GRN YEL of the module to
the corresponding terminals on the control panel’s four-wire combus as
shown below.
Manual activation is timed and will shutdown after 15 minutes (default).
Upgrading Firmware
The PGM82’s firmware can be upgraded in Infield via BabyWare
using a 307USB Direct Connect Interface.
LED Indicators
* If control panel has an AC Loss, all LEDs are turned off.
Insite Gold
Adding PGMs to Camera and Security
Screens
1.
Press from the Security or
Video screen.
2.
Select the PGM you wish to add.
3.
Press Save.
The selected PGMs will appear on Security
and Video screens.
To Enable/Disable PGMs
1.
Open Insite GOLD app.
2.
Select the PGM tab on the bottom.
3.
Press the toggle button to enable/dis-
able the PGM.
4.
When activating a PGM a countdown
clock will be shown.
In the EDIT PEN icon, you can label each
PGM and change the OFF time; default is
set to 15 minutes.
Labels will be saved in the EVO panels.
On MG/SP, it is saved only on the mobile
device (need to be labeled on each mobile
device).
Manual Switches
Output Relays
LED
OFF
ON
PGM1 to PGM8
Deactivated
Activated
DATA
No clock / no data
Panel connected
POWER
No Power
10.5 to 16V
Flash - Below 10.3V
Manual Activation
and Display
Data
Power
Lock
Enter section [0901] - [0932].
2.
Enter the eight-digit serial number and three-digit output number.
3.
Enter the 3-digit Event Group, Feature Group, Start # and End #
for PGM activation.
4.
Enter the 3-digit Event Group, Feature Group, Start #, and End#
for PGM deactivation.
5.
Define the PGM Delay Value (001 to 255 x 1 sec./min.). Default
set to 5 sec./min.
6.
Set your PGM options, refer to table.
Programming MGSP
1.
Enter section [236] - [251].
2.
Enter the 3-digit Event Group, Sub Group, and Partition for PGM
activation.
Section default values are set to 00/00/00 with the exception of
Section [244] - activation default values are set to 08/99/01;
Section [246] - activation default values are set to 09/99/01.
3.
Enter the 3-digit Event Group, Sub Group, and Partition for PGM
deactivation.
Section default values are set to 00/00/00 with the exception of
Section [245] - deactivation default values are set to 08/99/01;
Section [247] - deactivation default values are set to 09/99/01.
4.
Enter section [269] - [276] to define the PGM Delay Value (001 to
255 x 1 sec./min.).
5.
Enter section [349] - [356] to define your PGM Labels.
6.
Set your PGM options, refer to table below.
Technical Specifications
OPTION DESCRIPTION
PGM #
OFF
ON
1
PGM deactivation after (OFF =
deactivation event; ON = PGM timer)
2
PGM base time (OFF = seconds;
ON = minutes)
3
Flexible PGM deactivation option
(OFF = PGM timer only; ON = PGM
timer and/or deactivation event)
4
PGM initial state (OFF = normally open;
ON = normally closed)
5
PGM Time base (Off = follow option 2,
1 = hour)
6 to 8
Future use
-
-
OPTION DESCRIPTION
PGM #
OFF
ON
1
PGM base time (OFF = sec., ON = min.)
2
PGM state (OFF = N.O., ON = N.C.)
3
PGM supervision (not applicable to
SP4000
4
PGM activation mode (OFF = steady,
ON = pulse)
5
PGM pulse once every 30 seconds, if
armed
6
PGM pulse on any alarm
7
PGM pulse on any alarm (OFF - partition
1, ON = partition 2)
8
Flexible PGM deactivation option
(OFF* = PGM delay only, two activation
events, ON = PGM delay or deactivation
event, whichever comes first)
* If a PGM delay is programmed (OFF option), the deactivation event
can be used as a second activation event.
Input Voltage
11 to 16 Vdc
Current Consumption
315 mA max (all PGMs activated)
Number of outputs
8 Form ‘C’ relays
Output
24V, 4A any load
Operating Temperature
-20 C to +50 C (-4 F to 122 F)
Humidity
95% maximum
Box Dimensions
(H x W x D)
16.5 cm x 10.2 cm x 2.5 cm
(6.5 in x 4 in x 1 in)
Warranty
For complete warranty information on this product, please refer to the Limited
Warranty Statement is found on the website:
www.paradox.com/terms or contact your local distributor. Specifications may
change without prior notice.
Patents
US, Canadian and international patents may apply. Paradox is a trademark or
registered trademark of Paradox Security Systems (Bahamas) Ltd.