Nortec MH Series Installation Manual

Specifications

Brand: Nortec
Category: Humidifier
Model: MH Series (Installation Manual)
File Type: PDF
File Size: —
Pages: 40

Read Online

Read the Nortec MH Series Installation Manual online using the built-in PDF viewer.

Text of the manual

This document and the information disclosed herein are proprietary data of

WALTER MEIER LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of WALTER MEIER LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the NORTEC name should be taken as referring to WALTER MEIER LTD. LIABILITY NOTICE WALTER MEIER LTD. does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by WALTER MEIER LTD. COPYRIGHT NOTICE Copyright 2008, WALTER MEIER LTD. All rights reserved. RECORD OF REVISIONS For each revision, put the revised pages in your manual and discard the superseded pages. Write the revision number and revision date, date put in manual, and the incorporator’s initials in the applicable columns on the Record of Revisions. Revision Number Revision Date Date Put In Manual By Revision Number Revision Date Date Put In Manual By

TABLE OF CONTENTS

Subject Page 10-00 INTRODUCTION 1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.1 NOTES ON THE OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.2 SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2. OPERATING THE MH CONTROL UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.1 FUNCTION OF THE DISPLAY AND OPERATING ELEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2 SWITCHING THE CONTROL UNIT ON AND OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2.3 REMOTE OPERATING AND FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2.4 OVERVIEW AND OPERATING OF THE MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3. EXPLANATION OF CONFIGURATION SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.1 EXPLANATION OF THE STATUS INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.2 EXPLANATION OF UNIT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.3 EXPLANATION OF ERROR HISTORY LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10-10 CONFIGURATION 1. CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.1 UNIT SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.2 MODBUS SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 10-20 OPERATIONAL FUNCATIONS 1. OPERATIONAL FUNCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 1.1 CARRYING OUT MANUAL DRAINING / PIPE FLUSHING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 1.2 RESETTING THE MAINTENANCE INDICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 1.3 RESETTING THE HOURS METER OF THE UV LAMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 10-30 TROUBLESHOOTING 1. FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 1.1 FAULT INDICATION 28 1.2 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 1.3 RESETTING THE ERROR INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 WARRANTY

1.1 NOTES ON THE OPERATING INSTRUCTIONS

Limitation These operating instructions are an addendum to the installation and operating instructions for the Nortec MH and describe the operating of the MH control unit, which is used with the models Nortec MHTC Flow, MHB Reflow, MHTC Reflow. These operating instructions are meant for well trained personnel being sufficiently qualified. Safekeeping Please safeguard these operating instructions in a safe place, where they can be immediately accessed. If the equipment changes hands, the documentation must be passed on to the new operator. If the documentation gets lost, please contact your local Nortec representative. Copyright protection The present operating instructions are protected under the Copyright Act. Passing-on and reproduction of the manual (or part thereof) as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to legal prosecution and arises liability for indemnification. The manufacturer reserves the right to fully exploit commercial patent rights. 1.2 SAFETY Every person operating the MH control unit must have read and understood the operating instructions of the MH control unit as well as the installation and operating instructions of the Nortec MH (specially the safety instructions). Knowing and understanding the contents of the operating instructions of the MH control unit and the installation and operating instructions of the Nortec MH is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.

2. OPERATING THE MH CONTROL UNIT

2.1 FUNCTION OF THE DISPLAY AND OPERATING ELEMENTS Figure 1. Display

2.2 SWITCHING THE CONTROL UNIT ON AND OFF

NOTE: For putting the unit into operation and taking the unit out of operation please follow the procedures described in the installation and operating instructions for the Nortec MH. Switching the MH control unit on The control carries out a system test, during which all the LEDs light up and the opposite display is shown. If a failure occurs on the system test, a corresponding error message is shown in the display. After the system test the control is in normal operation mode. The display shows the standard operating display. Note: The contents of the standard operating display depends on the type (MHTC Flow, MHTC Reflow), the actual operating status and on the configuration of the Nortec MH and can differ from the opposite display. Switching the MH control unit off The display goes out. On models MHB Reflow and MHTC Reflow the drain valve opens and the water tub empties. Note: The different hygiene functions (regular draining, flushing of the supply line, etc.) remain active also in times without humidification / cooling demand, the control unit should only be switched off for maintenance or, troubleshooting, or to disable completely operation (as in seasonal shutdown). 2.3 REMOTE OPERATING AND FAULT INDICATION If your control is equipped with a remote indication board (accessory) the following operating status are shown remotely: Activated remote indication relay When? Display on Unit H1 “Error” A fault is present, further operation is not possible Red LED lights. An error message is shown in the display H2 “Service” Maintenance or UV lamp (option) replacement is due. The unit remains operational for a certain time Yellow LED lights. The service warning message is shown in the display H3 “Humidification” Unit is humidifying Green LED lights H4 “Unit on” Unit ready for operation Unit switch lights

2.4 OVERVIEW AND OPERATING OF THE MENU

The operating and display is operated via the four keys located just below the display. The four status fields at the bottom of the display show the current function of the keys. Keys Figure 2. Menu Overview

3. EXPLANATION OF CONFIGURATION SETTINGS

3.1 EXPLANATION OF THE STATUS INFORMATION (INDICATION STATUS) In normal operation mode the control unit is in the status level. The status level forms a loop that includes several pages holding operating information which can be accessed with the arrow keys. The various displays of the status level are shown below. Standard operating display The appearance of the standard operating display depends on the actual operating status and the configuration of the Nortec MH Standard operating display with external control via the external controller. Standby (no humidity demand) or Demand % (humidity demand present). Standard operating display with internal control. - Actual humidity in %rh. - Configured humidity setpoint in %rh. Info Page: Settings - Software version. - Selected control signal source. - Configured control signal range. - Configured Modbus address of the unit. Info Page: Performance data - Configure power limitation in % of the maximum output. - Actual output unit A in kg/h. - Actual total output in kg/h (the same as Capacity A unless a second module is connected to control unit). . Info Page: Operating hours - Total operating hours of the Nortec MH. - Remaining operating hours to the next maintenance.

Info Page: Clean Trg. 1

This page shows the current settings for the time based and externally activated forced draining/box cleaning (MHTC Reflow) or the box cleaning (MHTC Flow), respectively. Note: Wash = draining with simultaneous box cleaning (MHTC Reflow) or box cleaning only (MHTC Flow), Drain = draining only. – Time controlled draining/box cleaning (Timer). – Actual time of day. – Point in time of the next draining/cleaning cycle. – Configured cleaning mode. – Interval controlled draining/box cleaning (Periodic). – Configured interval time in hours. – Remaining time in hours up to the next draining/cleaning cycle. – Configured cleaning mode. – Externally controlled draining/box cleaning (Demand). – Actual status of the draining/cleaning demand. – Configured cleaning mode. – Clean Trg. 1 deactivated (can appear only with module MHTC Flow). Info Page: Clean Trg. 2 (Note: This page is not shown with model MHTC Flow) – Fill cycle controlled draining (Cycle). – Number of fill cycles between cleaning/draining cycles. – Remaining fill cycles up to the next draining. – Cleaning mode (Wash= Draining with simultaneous box cleaning or box cleaning only, Drain= draining only). – Conductivity controlled draining/cleaning (µSensor) -- >Option. – Set conductivity limit value inn µS/cm. – Actual conductivity value of the water in the tub in µS/cm. – Configured cleaning mode. – Operation-dependent draining deactivated (Off).

Info Page: Box drying

This page shows the settings for box drying. – Time controlled box drying (Timer) – Actual time of day – Point in time of the next drying cycle – Interval controlled box drying (Periodic) – Configured interval time in hours – Remaining time in hours up to the next drying cycle Info Page: Supply line flushing function/water quantity reduction function – Indicates if the supply line flushing function. – Indicates if the "Softstart" water conservation function is enabled. Info Page: UV Module (option) Indicates if the UV water treatment option is enabled (Note: UV treatment requires optional components be installed).

3.2 EXPLANATION OF UNIT INFORMATION

Path: Main menu > Info > Unit Status Press <> and <> keys, in order to select the unit information available in the list: – System Operation Hour: Total operating hours of the control unit (unit on) since the initial commissioning of the unit. – Relay Humidity: Actual status of the remote indication relay “Humidify”. – Relay Service: Actual status of the remote indication relay “Service”. – Relay Error: Actual status of the remote indication relay “Error”. – Relay Unit On: Actual status of the remote indication relay “Unit on”. – Drain Valve: Actual operating status of the drain valve. – Inlet Valve: Actual operating status of the inlet valve. – Pump: Actual operating status of the circulation pump. – UV Lamp: Actual operating status of the UV lamp – Stage 1 Valve: Actual operating status of the step valve 1 – Stage 2 Valve: Actual operating status of the step valve 2 – Stage 3 Valve: Actual operating status of the step valve 3 – Pressure Sensor (MHTC Flow only): Actual operating status of the minimum pressure switch – Max Level Sensor (MHTC Reflow only): Actual operating status of the minimum level sensor – Thermal Contact (MHTC Reflow only): Actual operating status of the thermal contact (pump motor protection) – Extension Present: Indication, whether or not a unit extension is present. – Wash Demand: Actual status of the external demand triggering a wash cycle. Press the key several times to quit the information list and to return to the standard operating display.

3.3 EXPLANATION OF ERROR HISTORY LIST

The last 10 faults that occurred during operation are saved in the error history list and can be reviewed. Path: Main menu > Info > Error History The last error that occurred is shown with: – Current Error being viewed / Total number of errors recorded. – date and time of occurrence – error code (Warning: W..., Error: E...– error message – additional info text regarding the error Press <�> and <�> keys, in order to select further error messages in the list. Press the key several times to quit the error history list and to return to the standard operating display.

1.1 UNIT SETTINGS

1.1.1 Launching the unit settings menu Path: Main menu > User > Password entry: 8808 > Settings Press the <�> and <�> keys in order to select the individual settings in the settings menu. Detailed information on the different settings are found in the following chapters sections. 1.1.2 Select dialogue language Select “Language” in the settings menu, then press the key. In the following modification dialogue select the desired dialogue language. After confirmation, the unit automatically switches to the selected dialogue language. Factory setting: English Options: French, Spanish

1.1.3 Control Settings

Select “Controls” in the settings menu, then press the key. The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maximum number of settings available. DESCRIPTION OF THE SETTINGS SignalSource Selecting the signal source. Factory setting: Analog Options: Analog Modbus Hum.Control: Selecting the control type. Factory setting: External Options: External (external continuous controller) 24VOn/Off (external On/Off humidistat) Int. (P) (Internal P controller) Int. (PI) (Internal PI controller) Controlsign. Selecting the control signal. NOTE: This setting is available only if control type “External”, “Int. (P)” or “Int. (PI)” is selected. Factory setting: 0–10V Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2– 16V, 0–20mA, 4–20mA Hum.Setpoint: Setting the nominal humidity value inn %rh. NOTE: This setting is available only if the internal P or PI controller is activated. Factory setting: 50 %rH Setting range: 20...99 %rH P-Band: Setting the proportional range inn % for the internal P/PI conntroller. NOTE: This setting is available only if the internal P or PI controller is activated. Factory setting: 18 % Setting range: 1...100 % Integr.-Time: Setting the integral time in minutes for the internal PI controller. NOTE: This setting is available only if the internal P or PI controller is activated. Factory setting: 18 Minutes Setting range: 1...60 Minutes

1.1.4 Setting the capacity limitation

Select “Power Limit” in the settings menu, then press the key. In the upcoming modification dialogue set the desired capacity limitation in % of the maximum capacity of the humidifier. Factory setting: 100 % Setting range: 30...100 % 1.1.5 Configuring the supply pipe flushing Select “Inlet Flush” in the settings menu, then press the key. Used to configure the unit to flush supply lines even if there is no demand signal. You can; - enable / disable inlet flush - set length of flush - set time between flushes DESCRIPTION OF THE SETTINGS Inlet Flush Enable or disable the supply pipe flushing. Factory setting: On Options: On (enable) Off (disable) Drain Time Setting the flushing time in seconds. Factory setting: 60s Setting range: 5...600s Periodic Int Setting the time without demand after which the supply pipe should be flushed. Factory setting: 12.0 h Setting range: 0.5 ... 24.0 h

1.1.6 Setting the Cleaning Mode (MHTC Reflow only)

NOTE: The cleaning mode may only be set with the MHTC Reflow. With the cleaning mode you determine whether the humidification boxes will be washed simultaneously during a draining or operation dependent draining /cleaning cycle. This option does not appear for other models. Select “Clean Mode” in the settings menu, then press the key. In the upcoming modification dialogue select the desired cleaning/draining mode. Factory setting: Drain Options: Drain (draining only) Wash (Draining w/box cleaning) NOTE: During operation, the washing process of the humidification boxes can lead to a temporary humidity increase.

1.1.7 Configuring the cleaning trigger 1 (Clean Trg. 1)

With the cleaning trigger 1 settings you determine whether the forced draining/cleaning (MHTC Reflow) or the box cleaning (MHTC Flow) is time or interval controlled or triggered via an external signal. The forced draining can be deactivated, however the box cleaning can be deactivated. The forced draining cannot be deactivated for the MHTC Reflow. The washing can be deactivated for either the MHTC Flow or Reflow. Note: the forced cleaning/draining serves to empty the water tub regularly and independent of the operation time of the Nortec MH. Select “Clean Trg. 1” in the settings menu, then press the key. The current settings for the forced draining/box cleaning appear. The available settings depend on whether the interval controlled (Periodic (factory setting), timer controlled (Timer) or external signal controlled (Demand) triggering of the forced draining/box cleaning is selected. Interval controlled draining/box cleaning (Periodic). With Periodic Int you can determine in which time intervals the draining/box cleaning is performed (setting range: 0.5 ...24 .0h, factory setting: 2.0h). Time controlled draining/box cleaning (Timer)With the parameters “time 1” to “time 4” you can define up to four times of day to start the draining/box cleaning (factory setting: no starting times defined). Triggering the draining/box cleaning via an external signal (Demand). In order to trigger the draining/box cleaning via an external signal a potential-free contact (B4 ) must be connected to the control board of the control unit MH. Closing the contact results in a draining/box cleaning cycle. Cleaning trigger 1 deactivated (Off)Note: this option is only available/visible for model MHTC Flow.

1.1.8 Configuring the cleaning trigger 2 (Clean Trg. 2) (MHTC Reflow only)

Note: The cleaning trigger 2 to configure operation dependent draining appears only with the MHTC Reflow. With the cleaning trigger 2 settings you determine whether operation dependent draining is triggered depending on the fill cycles or on the conductivity of the water in the water tub (option) or whether the cleaning trigger 2 should be deactivated. Select “Clean Trg. 2” in the settings menu, then press the key. The current settings for the operation dependent draining appear. The settings available depend on whether the operation dependent draining is deactivated (Off, factory setting) or the fill cycle (Cycle) or the conductivity controlled (µ Sensor) triggering of the operation dependent draining is selected. Operation dependent draining deactivated (Off) Fill cycle controlled draining (Cycle). With the parameter “Cycle” you can determine after how many filling cycles a drain is performed (setting range: 10...10000, factory setting: 100). Conductivity controlled draining (µ Sensor) (Requires optional components). With the parameter “µS Limit” you can set a conductivity limit value. If during operation the conductivity value of the water in the tub reaches the set limit, a draining is performed (setting range: 10...5 000 µS, factory setting: 1000µS).

1.1.9 Configuring the humidification box drying

An occasional drying of the humidification boxes helps prevent germs and bacteria from developing in the humidification boxes. The drying process can be time triggered or, interval controlled, or it can be deactivated. Note: During operation, the drying process of the humidification boxes can lead to a temporary humidity decrease. Select “Box Drying” in the settings menu, then press the key. The current settings for the box drying function appear. The settings available depend on whether the box drying function is deactivated (Off, factory setting) or whether the time controlled (Timer) or the interval controlled (Periodic) triggering of the drying function is selected. Drying function deactivated (Off ---> factory setting) Time controlled drying (Timer)With the parameters “time 1” to “time 4 ” you can define up to four times of day to start a box drying process (factory setting: no starting times defined). Interval controlled drying (Periodic) With the parameter “Periodic Int” you can determine inn which time intervals a box drying process is performed (setting range: 0.5 ...24 .0h, factory setting: 12.0h).

1.1.10 Configuring the Humidifier Maintenance Interval

Select “Maintenance” in the settings menu, then press the key. In the following dialogue set the desired maintenance interval time in hours. After the maintenance interval time has elapsed a maintenance message appears in the display and the yellow LED lights up. If the maintenance is not performed and the maintenance indication is not reset within a certain time (168 h) , an error message is triggered. Factory setting: 800 h Setting range: 100... 50000 h Note: to determine the maintenance interval time please refer to 1.3 in section 10-40 of the installation and operating instructions for the Nortec MH. 1.1.11 Activating/deactivating the softstart function If the mats in the humidifier boxes became dry due to a operation interruption, they need a certain time until they are again moistened with water. In order to prevent too much water flows over the humidification boxes in this phase and water droplets are carried in the air flow, the amount of water can be reduced for a fixed time with the “Softstart” function. Select “Softstart” in the settings menu, then press the key. In the modification dialogue you can activate or deactivate the softstart function. Factory setting: Off Options: Off (Softstart function deactivated) On (Softstart function activated)

1.1.12 Performing remote relay tests

With the test functions under “Remote Test” you can check the function of the relays “Humidification”, “Service”, “Error” and “Unit on”. Select “Remote Test” in the settings menu, then press the key. Press the <�> and <�> keys in order to select the relay you want to test and press the key to activate/deactivate the corresponding relay for testing. 1.1.13 Setting the date Select “Date” in the settings menu, then press the key. In the following dialogue set the actual date (format “tt.mm.jj”). 1.1.14 Setting the time Select “Time” in the settings menu, then press the key. In the following dialogue set the actual time (format “hh.mm”). 1.1.15 Setting the display contrast Select “Contrast” in the settings menu, then press the key. In the following dialogue set the desired value for the display contrast. Factory setting: 20 Setting range: 0 (no display) ...100 (display turns black).

1.2 Modbus Settings

Select the Modbuus menu: Path: Main menu > User > Password entry: 8808 > Modbus The settings for the Modbuus appear. Description of Modbus Settings Modbus Add.: Setting the modbus address of the Nortec MH. Factory setting: 1 Setting range: 1...247 Parity: Selecting the parity bit for the data transmission. Factory setting: None. Options: None1, None2, Odd, Even Timeout: Setting the time out time for the data transmission. Factory setting: 5 Seconds Setting range: 1...600 Seconds

1. OPEARTIONAL FUNCTIONS

1.1 CARRYING OUT MANUAL DRAINING / PIPE FLUSHING To carry out a manual draining (MHTC Reflow) or pipe flushing (MHTC Flow) proceed as follows: Drain 1. Briefly press the drain key. The drain/flush dialogue appears in the display. 2. Press the key. – Models MHTC Reflow: The drain valve opens after a delay of up to 3 minutes and the water tub empties. The yellow LED flashes. – Model MHTC Flow: The inlet valve and the flushing valve open and the pipe is flushed. The yellow LED flashes. To stop the drain/flush cycle press the key. Note: By pressing the key the control unit returns to the standard operating display. A drain/flush cycle in progress will be stopped automatically.

1.2 RESETTING THE MAINTENANCE INDICATION

After completing maintenance work, the maintenance indication (yellow LED lights) must be reset on the models MHTC Flow, MHB Reflow, MHTC Reflow. Note: If the maintenance indication is not reset within 168 hours a fault is triggered and the unit stops operation. Select the maintenance menu: Path: Main menu > User > Password entry: 8808 > Maintenance Select “Module A”, then press the key. Select "Stage Reset”, then press the key. The reset dialogue shows up in the display. Press the key to reset the maintenance hours of the unit. Note: Press the or key if you wish to abort the reset procedure. To return to the standard operating display press the key several times.

1.3 RESETTING THE HOURS METER OF THE UV LAMP

After replacing the UV lamp (option) the hours meter of the UV lamp must be reset. Note: If the hours meter of the UV lamp is not reset within 168 hours the UV maintenance warning an error message is triggered. Select the maintenance menu: Path: Main menu > User > Password entry: 8808 > Maintenance Select “Module A”, then press the key. Select "UV lamp Rst”, then press the key. The reset dialogue shows up in the display. Press the key to reset the hours meter of the UV lamp. Note: Press the or key if you wish to abort the reset procedure. To return to the standard operating display press the key several times.

1. FAULT INDICATION

1.1 FAULT INDICATION Malfunctions during operation are indicated by a corresponding warning or error message in the display of the control unit: Warning messages (additionally to the error message the red LED is on) Further operation is still possible. If the cause of the malfunction disappears of its own accord, the warning message will automatically switch off. If the cause of the malfunction does not disappear even after a longer period of time, an error message is triggered. Error message (additionally to the error message the red LED is on) Further operation is not possible. The malfunction is stored in the error list. By pressing the key additional information are displayed for each warning or error message. By pressing the key the control unit returns to the standard operating display.

1.2.1 System Faults

Warning Error Cause Remedy LED Display LED Display MH Card missing (Test run possible) MH Card Missing Red flashes Red lights No MH Card installed on the control board. Install MH Card or start test run. MH Card is Empty -- -- Red lights No data stored on the MH Card Install new MH Card. MH Card is defective -- -- Red lights Invalid data stored on the MH Card Install new MH Card. MH Card is incompatible -- -- Red lights The MH Card is not compatible with the hardware or the basic settings on the control board. Install new MH Card. Modify basic settings. Unit Module B missing -- -- Red lights No response from module B. Flat ribbon cable interrupted or disconnected 120V supply cable disconnected. Plug in flat ribbon cable, plug in 120V supply cable. Wrong parameter settings -- -- Red lights Data of CPU and MH Card do not match. Install correct MH Card. Contact your Nortec supplier. Hardware Fault (flash) -- -- CPU on control board defective. Replace control board. Hardware Fault (clock) -- -- CPU on control board defective. Replace control board.

1.2.2 Unit Faults

Warning Error Cause Remedy LED Display LED Display External safety chain is open Red and green flash -- Air proving interlock open. If applicable, check/turn on fan. Air flow monitor triggered Check fan/filter of the fan system. Safety humidistat triggered. Wait, if applicable, check safety humidistat Error level sensor Error level sensor Red flashes Red lights The level sensor is blocked or defective (broken or short- circuited). Check/clean or replace level sensor. Check level sensor with ohmmeter: If no water is in the tub, the circuit of the level sensor must be closed. If the water in the tub is on maximum level sensor must be open. Maximum filling time exceeded (30 minutes) Maximum filling time exceeded (more than 4 hours) Red flashes Red lights Note: This error message is reset automatically as soon as the water supply functions again. Water supply blocked/shut-off valve closed/water pressure too low. Water treatment unit (fully demineralised water) is regenerating. Check water supply (filter, pipes, etc.), Check/open shut- off valve, Check water pressure. Inlet valve blocked or defective. Check strainer in the inlet valve, clean if necessary. Replace inlet valve. Drain valve open, blocked in open position or not electrically connected. Drain valve is open unless powered Check/replace drain valve, connect drain valve. Leakage in the water drain system. Check/seal water drain system.

When draining the water

tub float is not open within 8 minutes When draining the water tub the float is not open within 4 hours Red flashes Red lights Drain valve blocked/defective or clogged. Check/clean or replace drain valve. Siphon clogged. Clean siphon. Relay defective (weld-shut). Replace control board. Level sensor stucked or short circuited. Clean/Replace level sensor. Backpressure in the siphon. Install special siphon. Conductivity of the water in the tub too high Conductivity of the water in the tub too high Red flashes Red lights Conductivity after draining, restart or cleaning cycle during 10 minutes higher than the set nominal value. Increase the nominal value or enhance water quality. Conductivity sensor defective. Replace conductivity sensor. Conductivity transmitter defective. Replace conductivity transmitter.

Maintenance not performed

and/or maintenance indication not reset Red flashes and yellow lights red and yellow lights Maintenance due. Perform maintenance according to section 10-40 of the installation and operating instructions for the Nortec MH. Then, reset the maintenance indication. Maintenance not performed and/or maintenance indication not reset within 168 h (1 week). Perform maintenance according to section 10-40 of the installation and operating instructions for the Nortec MH. Then, reset the maintenance indication. Maximum lifespan of the UV lamp reached Maximum lifespan of the UV lamp reached red flashes and yellow lights red and yellow light Maximum lifespan of the UV lamp reached. Replace UV lamp and clean glass tube UV lamp not replaced or hours counter of the UV lamp not reset after replacement of the UV lamp. Unit switches off after 168 hours. Replace UV lamp and clean glass tube (see 1.4.2 in section 10-40), then reset hours counter of the UV lamp. Wrong UV lamp installed. Install correct UV lamp. No signal from humidity sensor No signal from humidity sensor Red flashes Red lights Sensor cable not connected or sensor cable interrupted. Connect/replace sensor cable. Humidity sensor defective. Replace humidity sensor.

No signal from

conductivity sensor No signal from conductivity sensor Red flashes Red lights Sensor cable not connected or sensor cable interrupted. Connect/replace sensor cable. Conductivity transmitter defective or wrong version (conductivity constant). Replace conductivity transmitter. Conductivity transmitter not configured correctly. Contact your Nortec supplier. Conductivity sensor defective. Replace conductivity sensor. Nortec SH2 deactivated via Modbus Modbus system failed Red flashes Red lights Nortec MH deactivated via Modbus. None or activate Nortec MH via Modbus. Modbus system failed. Check/activate Modbus system. Timeout Modbus Red flashes -- Red lights Timeout. No activity from Modbus Activate Modbus system Cleaning of humidification boxes in progress -- -- -- Cleaning of humidification boxes in progress. None (wait). Draining of water tub in progress -- -- -- Draining of water tub in progress. None (wait).

Water pressure too low

(flow only) Water pressure for more than 4 hours too low (flow only) Red flashes Red Lights Water supply blocked/shut-off valve closed/water pressure too low. Water treatment unit (fully demineralised water) is regenerating. Check water supply (filter, pipes, etc.), Check/open shut-off valve. Check water pressure. Inlet valve blocked or defective. Check strainer in the inlet valve, clean if necessary. Replace inlet valve. Flushing valve leaking. Replace flushing valve. 1.3 RESETTING THE ERROR INDICATION To reset the error indication: Investigate and correct cause of error. Turn control panel ON/OFF switch to OFF. Wait approx. 5 seconds, then turn control panel ON/OFF switch to On position. Note: If the fault has not been eliminated, the error indication reappears after a short while.

(1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collectively referred

to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations. (2) THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer. (3) The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY. (4) THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier. (5) THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment. (6) THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment. (7) THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation.

Walter Meier (Climate USA) Inc.

826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: [email protected] WEBSITE: www.humidity.com CANADA Walter Meier (Climate Canada) Ltd. 2740 Fenton Road Ottawa, ON K1T 3T7 TEL: 1-866-NORTEC-1 FAX: (613) 822-7964 Authorized Agent: