eta PelletsUnit Service Manual
Text of the manual
A-4716 Hofkirchen an der Trattnach
Tel: +43 (0) 7734 / 22 88 -0
Fax: +43 (0) 7734 / 22 88 -22
[email protected]
www.eta.co.at
Support for cleaning and maintenance
This document helps support you with the cleaning
and maintenance of the boiler. The required steps are
listed in detail here.
Take note of the date of the cleaning or maintenance
and any faults that may have occurred. This facilitates
troubleshooting for the expert (system operator,
heating technician...).
For services (such as commissioning, mainte-
nance, fault fixing provided by ETA customer
service), the service reports are provided in digital
form. For clarity, you should staple these reports to this
document or enclose them.
Commissioning data
Enter the boiler number (printed on the type plate), the
date of commissioning as well as the heating
technician who commissioned the system.
Copyright
All contents of this document are property of ETA
Heiztechnik GmbH and are protected by copyright.
Any reproduction, transfer to third parties or use for
other purposes is prohibited without written permission
from the owner.
Subject to technical changes
We reserve the right to make technical modifications
without notice. Printing and typesetting errors or
changes of any kind made in the interim are not cause
for claims. Individual configurations depicted or
described here are only available optionally. In the
event of contradictions between individual documents
regarding delivery scope, the information in our current
price list applies.
Explanation of symbols
Instructions and information
Layout of safety instructions
SIGNAL WORD!
Type and source of danger
Possible effects
•
Measures for avoiding the danger
Types of safety instruction
CAUTION!
On non-compliance with this safety instruction, there is
a risk of material damage.
WARNING!
On non-compliance with this safety instruction, there is
a risk of physical injury.
DANGER!
On non-compliance with this safety instruction, there is
a risk of major physical injury.
Commissioning data
Boiler number:
________________________________________
Commissioned on:
_________________________________________
Commissioned by (company):
_________________________________________
_________________________________________
_________________________________________
Cleaning and maintenance
2
Cleaning and maintenance
2.1
Maintenance notes
Performing regular cleaning and maintenance
To ensure satisfactory functioning, cleaning and
maintenance must be performed at regular intervals.
Carry out this work within the intervals stated here.
All tasks where the maintenance table reads
"Customer" or "Customer or expert" in the column
"To be carried out by" can be carried out by any trained
adult. Instructions can be provided by the heating
technician or our customer service.
Steps that are marked with "Expert" only can only be
carried out by the heating technician or our customer
service.
Operation only by trained personnel
The product may be operated by trained adults only.
Training may be provided by the heating technician or
our customer service. Please read the associated doc-
umentation carefully in order to avoid errors during
operation and maintenance.
Persons who lack experience and knowledge as well
as children may not operate, clean, or maintain the
product.
Display maintenance steps on the screen
With this boiler, the maintenance steps can also be
displayed on the ETAtouch control system screen. The
required activities will be explained to you step-by-step
and supplemented with detailed graphics. Each
maintenance is saved and the details can be viewed at
any time. So you can maintain a long-term overview of
the maintenance carried out. Of course, the
maintenance can also be carried out using the service
guide, without the support of the ETAtouch control
system.
To access maintenance, switch to settings in the boiler
function block (
[Settings] button) and then select
the function
[Maintenance].
Fig. 2-1: Overview (example)
You can also access this overview by pressing
the maintenance switch. Also when the message
appears that maintenance of the boiler is required.
In the overview the different maintenance intervals are
listed in the upper area. This includes the maintenance
already carried out. With the
button, information
about the selected maintenance is displayed.
Maintenance that you can carry out as an end
customer is labelled with the
symbol. All others are
reserved for specialists and require authorisation.
Press the
button to start the maintenance. The
individual steps are displayed on the screen. You can
switch to the next or the previous screen respectively
with the arrow keys on the left and right side of the
screen.
Fig. 2-2: Maintenance step (example)
Cleaning and maintenance
Maintenance notes
5
Follow the on-screen instructions and carry out all
steps carefully. Enter your name at the end of
maintenance (
button) and save the maintenance
with the
button.
Fig. 2-3: End of maintenance
To end maintenance prematurely, press the right
arrow key several times until you get to the end.
There you can end the maintenance with the
button. Cancellation during a maintenance step is not
possible.
Explanation of the maintenance switch
The maintenance switch on the boiler is needed for
performing maintenance with the aid of the
[Main-
tenance] function in the ETAtouch control system. This
displays the individual maintenance steps on the boiler
screen.
With this variant the heating mode is stopped, but
the boiler remains on at the mains switch. So that
all drives are disconnected, the safety chain of the
boiler is disrupted with the maintenance switch. The
screen will display a message when it is time to actuate
the maintenance switch.
Fig. 2-4: Maintenance switch
The maintenance switch is marked with the
symbol and has two settings.
•
"1" = regular operation
This is the standard position of the maintenance
switch. The boiler can execute heating mode in this
position.
•
"0" = maintenance mode
In this position, all drives are disconnected to
perform
maintenance.
The
circuit
boards,
however, are still live.
Explanation of pictograms
Switch the boiler on/off with the mains switch.
Perform a visual check of the components.
Clean the components, for example, with a
soft cloth.
Remove deposits with a vacuum or an ash
vacuum.
Remove deposits with the poker.
Remove deposits with the cleaning brush.
Replace the wear parts (e.g. seals) on the
components.
Lubricate the components. The lubricant to
use is listed in the respective step.
Install the components with some force (for
example the retaining tube or the Lambda
probe).
Handle the components carefully, since they
break very easily.
Clean panels
If necessary, clean the panels of the boiler and the
ETAtouch screen with a moist cloth.
Under
no
circumstances
use
aggressive
solvents, chemicals or scouring agents. They can
lead to stress cracks and damage.
Cleaning and maintenance
Checking the boiler counters
The counters can be seen in the boiler's text menu.
Counter [Consump. since maint.] is used for the
service intervals. If it has reached one of the listed
intervals, maintenance is required. This counter is in:
Counters
Consump. since maint.
Maintenance openings in the boiler
Cleaning and maintenance
2.2
Maintenance openings in the
boiler
Maintenance openings and components
1
Heat exchanger cover
2
Vacuum turbine for pellet transport
3
Firebed switch
4
Stoker drive chain
5
Water pressure sensor
6
Ignition
7
Position switch for ash box
Cleaning and maintenance
Maintenance openings in the boiler
9
1
Fill level sensor for pellet hopper
2
Safety valve
3
Flue gas temperature sensor
4
Draught fan
5
De-ashing drive chain
6
Filling and draining valve
7
Underpressure sensor
Cleaning and maintenance
2.3
Maintenance table
Tasks
Regularl
y
Every
3,000 kg
pellets
or
1 year
Every
5000 kg
pellets
or
3 years
to be
performed by
Empty the ash box
•
Empty the ash box
•
Check the seals
X
X
X
Customer
Check the pressure of the heating system
X
X
X
Customer
Visual check of the safety valves
X
X
Customer or
specialist
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
X
X
Customer or
specialist
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
X
X
Customer or
specialist
Clean the draught fan
X
Specialist
Clean the temperature sensor
X
Specialist
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
X
Specialist
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
X
Specialist
Check the stoker unit
•
Checking the stoker drive chain
X
Specialist
Check de-ashing
•
Check the de-ashing drive chain
X
Specialist
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
X
Specialist
Check the ash box position switch
X
Specialist
Calibrate the lambda probe
X
Specialist
Reset the maintenance counter
X
Specialist
Perform heating test
X
Specialist
Cleaning and maintenance
Regularly
11
2.4
Regularly
2.4.1
Preparation
Stop heating
End the boiler's heating mode with the On/Off switch
in the boiler overview window. The boiler
performs an ember burnout and then changes to
[Switched off] mode. Press the [De-ash]
button to
make the boiler perform a final de-ashing.
2.4.2
Empty the ash box
Empty the ash box and inspect the seals
Open the boiler door and fold the locking lever
forwards. Remove the ash box from the boiler.
Fig. 2-5: Locking lever
Take off the cover of the ash box by loosening the two
fasteners and empty the ash box.
Fig. 2-6: Lid
Check the ash for embers. Never put hot ash into
the waste bin!
Inspect the seal on the ash box lid for integrity, and
replace it if necessary.
Fig. 2-7: Seal
Inspect the integrity of the ash box seals on the boiler,
replace them if necessary.
Fig. 2-8: Seals
Attaching the ash box to the boiler
Reattach the cover of the ash box and secure with the
fasteners. Push the ash box over the connection on
the boiler and attach it to the boiler with the locking
lever.
Fig. 2-9: Locking lever
Cleaning and maintenance
2.4.3
Check pressure of the heating
system
Checking the heating system water pressure
In buildings with up to three storeys, the optimum
water pressure in a cold heating system is between 1
and 2 bar. For a warm heating system, the optimum
water pressure is between 1.5 and 2.5 bar.
Fig. 2-10: Pressure gauge
The control system displays a warning on the
screen as soon as the boiler pressure drops
below 1.2 bar. If the boiler pressure falls below 0.8 bar
or rises above 2.8 bar, the control system automatical-
ly switches the boiler off.
You can adjust the pressure in the heating system on
the filling and draining connection of the boiler.
Fig. 2-11: Filling and draining connection
If the water pressure is too low, fill the cold
heating system to approx. 2 bar. Do not fill to a
higher pressure, as water expands with increasing
temperature and the water pressure also rises when
the boiler is in heating mode. The safety valve triggers
at approx. 2.8 bar.
If the water pressure drops several times a year,
contact a heating professional. When refilling
water in the heating system, the same water as used
during initial filling should be used whenever possible
(e.g. prepared water).
2.4.4
Establish operational readiness
Switching on the boiler
Switch the boiler back on with the On/Off
switch.
Cleaning and maintenance
3,000 kg / annually
13
2.5
3,000 kg / annually
2.5.1
Preparation
Stop heating
End the boiler's heating mode with the On/Off switch
in the boiler overview window. The boiler
performs an ember burnout and then changes to
[Switched off] mode. Press the [De-ash]
button to
make the boiler perform a final de-ashing.
Switch off boiler via mains switch
WARNING!
Switch off the electricity to the boiler via the mains
switch. This prevents injuries caused by switching
the boiler on inadvertently.
WARNING!
Burns caused by hot parts
Risk of burning on parts located behind the
boiler housing, even after shutting the
boiler down.
Allow the boiler to cool down sufficiently
before starting any activities.
2.5.2
Check safety devices
Checking the safety valves
Perform a visual check of all safety valves of the
heating system. The outlets of the safety valves may
not drip.
Fig. 2-12: Safety valve
If the safety valve drips, open it with a quarter turn of
the red cap and rinse it out (danger of scalding). If the
safety valve still cannot be sealed effectively after
being rinsed several times, it must be cleaned or
replaced by an installer (heating technician).
A manual check of the safety valve is carried out
with a 1/4 turn of the red cap. This rinses the
safety valve. However it is very likely that the seal will
be damaged in the process and thus the outlet will drip.
That is why you should only perform this check on
weekdays and never on weekends in cold winter, as no
heating technician may be available if the seal is
defective.
3,000 kg / annually
Cleaning and maintenance
2.5.3
Chimney
Cleaning the flue tube
Sweep the flue tube from the flue outlet to the chimney
and remove flue ash from the chimney using a vacuum
cleaner.
Sweep the ash into the chimney, not into the
boiler. Otherwise, ash will collect in the
fan housing and can block the draught fan.
Fig. 2-13: Flue tube
Rinse the chimney's condensate drain
Check the chimney's condensate drain to make sure it
is free, as ash can block the outlet. To check, rinse the
outlet with some water.
Fig. 2-14: Condensate drain
2.5.4
Cleaning the combustion chamber
Removing the panel on the top
Remove the panel on the top of the boiler.
Fig. 2-15: Panel
Remove heat exchanger cover
Remove the insulation over the heat exchanger cover.
Fig. 2-16: Insulation
Cleaning and maintenance
3,000 kg / annually
15
Remove the heat exchanger cover by loosening the
two wing nuts.
Fig. 2-17: Heat exchanger cover
Removing the combustion chamber cover
Using the poker, remove the combustion chamber
cover from the combustion chamber.
Fig. 2-18: Combustion chamber cover
Cleaning the inner walls of the combustion
chamber
Wipe the ash off the inner walls of the combustion
chamber and push it onto the grate or into the heat
exchanger tubes. Use a vacuum cleaner to remove
flue ash from the upper part of the heat exchanger
tubes.
Fig. 2-19: Cleaning the inner walls
Cleaning the ignition tube
Check the ignition tube for combustion residues and
clean it by vacuuming.
Fig. 2-20: Ignition tube
3,000 kg / annually
Cleaning and maintenance
Checking the movability of the firebed switch
Check the mobility of the firebed button in the
combustion chamber by repeated lifting.
Fig. 2-21: Firebed button
Replacing the combustion chamber cover
Clean the combustion chamber cover and re-insert it in
the combustion chamber.
Fig. 2-22: Combustion chamber cover
Cleaning the lambda probe
Vacuum out the head of the lambda probe using a
vacuum cleaner. Do not dismantle the lambda probe.
Fig. 2-23: Head of the lambda probe
Check heat exchanger tubes
Inspect the heat exchanger tubes for tar deposits.
Fig. 2-24: Heat exchanger tubes
If there are tar deposits in the heat exchanger
tubes, contact customer service immediately. Tar
deposits can have several causes, for example:
•
Air leaks through the heat exchanger cover or the
lambda probe
•
insufficient boiler runtime (start-stop operation)
•
too little heat consumption due to incorrect control
system settings
•
Usage
for
an
individual room temperature control but
without
buffer storage tank in heating system
•
an incorrectly calibrated lambda probe
•
an incorrect differential pressure measurement
Cleaning and maintenance
3,000 kg / annually
17
Checking the seal on the heat exchanger cover
Clean the heat exchanger cover. Inspect the integrity
of the seal on the heat exchanger cover and replace if
necessary.
Fig. 2-25: Heat exchanger cover
CAUTION!
Avoid operation with damaged seals
Never operate the boiler with damaged seals.
Otherwise, leak air is sucked in, disturbing the
combustion process and causing increased wear.
Always replace seals as soon as they are
damaged.
Close heat exchanger cover
Fit the heat exchanger cover evenly using the two wing
nuts.
Fig. 2-26: Heat exchanger cover
Then replace the insulation.
Fig. 2-27: Insulation
Mounting the top panel
Remount the panel on the top of the boiler again.
Fig. 2-28: Panel
3,000 kg / annually
Cleaning and maintenance
2.5.5
Establish operational readiness
Switch the boiler on via the mains switch and start
de-ashing.
Establish the boiler's power supply at the mains switch.
Press the [De-ash]
button to de-ash the boiler.
Switch the boiler back on with the On/Off
switch.
Cleaning and maintenance
5,000 kg / 3 years
19
2.6
5,000 kg / 3 years
2.6.1
Preparation
Before this maintenance, perform all steps for the
preceding maintenance intervals
Before this maintenance, all steps for the
preceding
maintenance
intervals
must
be
performed.
WARNING!
The following activities may only be performed by
qualified specialist personnel.
If you carry out these activities without the correspond-
ing specialist training, and above all without the
required experience, safe operation is no longer
guaranteed. The resulting defects and consequential
damage are excluded from the guarantee and
warranty.
Equally an incorrect performance of these activities
can lead to serious injuries.
Stop heating
End the boiler's heating mode with the On/Off switch
in the boiler overview window. The boiler
performs an ember burnout and then changes to
[Switched off] mode. Press the [De-ash]
button to
make the boiler perform a final de-ashing.
Switch off boiler via mains switch
WARNING!
Switch off the electricity to the boiler via the mains
switch. This prevents injuries caused by switching
the boiler on inadvertently.
WARNING!
Burns caused by hot parts
Risk of burning on parts located behind the
boiler housing, even after shutting the
boiler down.
Allow the boiler to cool down sufficiently
before starting any activities.
2.6.2
Removing panels
Removing the panel on the top
Remove the panel on the top of the boiler.
Fig. 2-29: Panel
Removing the side panel
Remove the protective screen for the boiler's supply
air.
Fig. 2-30: Protective screen
5,000 kg / 3 years
Cleaning and maintenance
Remove the side panel.
Fig. 2-31: Side panel
Removing the panel from the front
Unscrew the screws on the panel, lift and remove it.
Fig. 2-32: Panel
2.6.3
Clean draught fan
Cleaning the draught fan
Take the draught fan off the boiler by loosening the
screws.
Fig. 2-33: Draught fan
Remove the ash from the fan housing on the boiler.
Fig. 2-34: Clean the fan housing
Cleaning and maintenance
5,000 kg / 3 years
21
Carefully clean the impeller of the draught fan with a
soft brush (not a wire brush) or with compressed air, so
that the impeller does not move out of balance.
Replace the seal on the draught fan.
Fig. 2-35: Clean impeller; replace seal
Lubricate the screws with heat-resistant lubricant and
reattach the draught fan to the fan housing. Tighten the
screws evenly.
2.6.4
Clean temperature sensor
Cleaning the flue gas temperature sensor
To clean, loosen the screw and pull out the flue gas
temperature sensor. Clean the sensor with a soft cloth
and then re-install it. When fixing the temperature
sensor in place, only tighten the screw hand-tight so as
not to damage the sensor.
Fig. 2-36: Flue gas temperature sensor
5,000 kg / 3 years
Cleaning and maintenance
2.6.5
Check the combustion chamber and
heat exchanger
Remove heat exchanger cover
Remove the insulation over the heat exchanger cover.
Fig. 2-37: Insulation
Remove the heat exchanger cover by loosening the
two wing nuts.
Fig. 2-38: Heat exchanger cover
Removing the combustion chamber cover
Using the poker, remove the combustion chamber
cover from the combustion chamber.
Fig. 2-39: Combustion chamber cover
Checking the firebed button and firebed switch
Check the mobility of the firebed button in the
combustion chamber by repeated lifting.
Fig. 2-40: Firebed button
The firebed switch must be actuated when lifting.
Fig. 2-41: Firebed switch
Replacing the combustion chamber cover
Clean the combustion chamber cover and re-insert it in
the combustion chamber.
Fig. 2-42: Combustion chamber cover
Cleaning and maintenance
5,000 kg / 3 years
23
Check heat exchanger tubes
Inspect the heat exchanger tubes for tar deposits.
Fig. 2-43: Heat exchanger tubes
If there are tar deposits in the heat exchanger
tubes, contact customer service immediately. Tar
deposits can have several causes, for example:
•
Air leaks through the heat exchanger cover or the
lambda probe
•
insufficient boiler runtime (start-stop operation)
•
too little heat consumption due to incorrect control
system settings
•
Usage
for
an
individual room temperature control but
without
buffer storage tank in heating system
•
an incorrectly calibrated lambda probe
•
an incorrect differential pressure measurement
Checking the seal on the heat exchanger cover
Clean the heat exchanger cover. Inspect the integrity
of the seal on the heat exchanger cover and replace if
necessary.
Fig. 2-44: Heat exchanger cover
CAUTION!
Avoid operation with damaged seals
Never operate the boiler with damaged seals.
Otherwise, leak air is sucked in, disturbing the
combustion process and causing increased wear.
Always replace seals as soon as they are
damaged.
Close heat exchanger cover
Fit the heat exchanger cover evenly using the two wing
nuts.
Fig. 2-45: Heat exchanger cover
5,000 kg / 3 years
Cleaning and maintenance
Then replace the insulation.
Fig. 2-46: Insulation
Dismantling the ignition and cleaning the ignition
tube
Carefully remove the ignition by loosening the screws.
Make sure that the springs supplied do not get lost.
Fig. 2-47: Springs
The ceramic igniter is very fragile. Make sure that
it is not damaged.
Fig. 2-48: Ceramic igniter
Take the ignition tube out of the bracket on the boiler.
Fig. 2-49: Ignition tube
Check the ignition tube for deposits and remove it, for
example with a screwdriver.
Fig. 2-50: Cleaning the ignition tube
Push the ignition tube back into the bracket and attach
the ignition with the bracket and the screws.
Cleaning and maintenance
5,000 kg / 3 years
25
Only hand tighten the screws so that the ignition
is kept away from the springs. Do not overtighten
the screws, otherwise the ignition may be damaged.
Fig. 2-51: Only hand tighten the screws
2.6.6
Check pellet hopper
Removing the panel above the pellet hopper
housing
Remove the panel above the boiler's pellet hopper.
Fig. 2-52: Panel
Cleaning the fill level sensor
Detach the mounting panel of the fill level sensor by
loosening the round-headed screws.
Fig. 2-53: Mounting the panel for the fill level sensor
Mark the correct installation position of the
mounting panel for the fill level sensor - with a
pen, for example.
Inspect the seal on the underside of the mounting
panel, and replace if necessary. Clean the fill level
sensor with a soft cloth.
Fig. 2-54: Checking the seal, cleaning the fill level sensor
5,000 kg / 3 years
Cleaning and maintenance
Cleaning the strainer in the pellet hopper
Clean the strainer in the pellet hopper by tapping and
vacuuming.
Fig. 2-55: Strainer
Reinstalling the fill level sensor
Re-attach the mounting panel and fill level sensor to
the pellet hopper. Make sure the installation position is
correct.
Fig. 2-56: Mounting the panel for the fill level sensor
Mount the panel over the pellet hopper.
Mount the panel over the boiler's pellet hopper again.
Fig. 2-57: Panel
2.6.7
Check stoker unit
Checking the stoker drive chain
Check the chain tension. The chain may sag by 2-3 cm
without any force applied. Tension the chain by shifting
the motor. Lubricate the drive chain with chain spray.
Fig. 2-58: Stoker drive chain
Cleaning and maintenance
5,000 kg / 3 years
27
2.6.8
Check de-ashing
Checking the de-ashing drive chain
Check the chain tension. The chain may sag by 1 cm
without any force applied. Tension the chain by shifting
the motor. Lubricate the drive chain with chain spray.
Fig. 2-59: De-ashing the drive chain
2.6.9
Check underpressure sensor
Cleaning the silicon hoses for the underpressure
sensor
The underpressure sensor is situated on the right-
hand side of the boiler above the supply air hole.
Fig. 2-60: Underpressure sensor
Take the silicon hoses off the underpressure sensor
and clean them by carefully blowing out or vacuuming
out with a vacuum.
Fig. 2-61: Silicon hoses
5,000 kg / 3 years
Cleaning and maintenance
Calibrate the underpressure sensor
With the boiler switched off and silicone hose
removed, the control system must display a measured
value of 0 Pa. This measured value can be seen with
the [Service] authorisation in the text menu under:
If a different value is shown, a calibration using the
[Offset] parameter must be carried out.
For this parameter, enter the difference from the target
value of 0 Pa. Example:
Measuring orifice = 2 Pa => Offset = -2
Reconnecting the silicon hoses
Reconnect the silicon hoses to the vacuum actuator.
Ensure the correct position when connecting. The
silicon hoses may not be kinked.
2.6.10
Check ash box position switch
Checking the ash box position switch
Inspect the function of the ash box position switch. It
must be actuated when the ash box is fitted.
Fig. 2-62: Position switch for ash box
Inputs
Measuring orifice
Inputs
Measuring orifice
Offset
Cleaning and maintenance
5,000 kg / 3 years
29
2.6.11
Attaching panels
Installing the side panels
Remount the side panels.
Fig. 2-63: Side panel
Reinstall the protective screen.
Fig. 2-64: Protective screen
Mounting the panel on the front
Suspend the panel on the boiler and secure it with the
screws.
Fig. 2-65: Panel
Mounting the top panel
Remount the panel on the top of the boiler again.
Fig. 2-66: Panel
5,000 kg / 3 years
Cleaning and maintenance
2.6.12
Calibrate lambda probe
Calibrating the lambda probe
The boiler's built-in lambda probe checks the
residual oxygen content of the flue gas and uses
it to control the combustion. To ensure reliability, the
control system autonomously performs an automatic
calibration after every 500 hours of operation.
If you wish to perform an additional lambda probe cal-
ibration, the control system features the [Addl. calibra-
tion] function. This function can be selected with the
[Service] access level and can be found under:
Switch on this function and the additional calibration
will now start. If the boiler is heating, it is automatically
stopped first. De-ashing begins, then the boiler is
purged with fresh air. After this, the residual oxygen
content is measured and the lambda probe is automat-
ically calibrated. Altogether, these steps last approxi-
mately 45 minutes. When the calibration is complete,
the boiler goes back into operation and starts heating,
if necessary.
After another 100 hours of operation, the control
system automatically performs another calibra-
tion.
2.6.13
Establish operational readiness
Reset maintenance counter [Consump. since
maint.]
When maintenance is complete, reset the counter.
With the [Service] access level, it will be visible in the
boiler text menu under:
Perform heating test
To perform the heating test, put the log boiler into
emissions measurement mode. To do this, carry out
the following steps.
Place logs in the fuel chamber, ignite them and wait
15 minutes. In the log boiler overview window, press
the [Measurement] button
in order to enter the
emissions measurement settings window.
Fig. 2-67: Settings window for emissions measurement
Press the [Start now]
button so the boiler will start
immediately. The control system ensures that
sufficient heat is channelled to the buffer, the heating
circuits and the hot water tank.
After around 10 minutes, a residual oxygen value of
4.5% to 7% should be reached. The current residual
oxygen content is displayed in the boiler's text menu
under:
If the value does not drop below 12% residual
oxygen, the boiler is receiving leak air. The
reason (leaky boiler doors, heat exchanger cover,
lambda probe installation etc.) must be identified and
corrected.
Inputs
Residual O2
Addl. calibration
Counters
Consump. since maint.
Reset counter?
Boiler
Residual O2
Cleaning and maintenance
5,000 kg / 3 years
31
If possible, perform a flue gas measurement
during the heating test.
After the heating test, switch the boiler back to normal
mode. To do this, press the [Deactivate measurement]
button in the settings window.
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This cleaning is to be carried out once a year or after 3,000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
performed on: _________________________
performed by: _________________________
This maintenance is to be carried out every 3 years or after 5000 kg of pellets.
Comments:
Tasks
Notes
Empty the ash box
•
Empty the ash box
•
Check the seals
Check the pressure of the heating system
______ bar
Visual check of the safety valves
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
Clean combustion chamber
•
Clean the inner walls of the combustion chamber
•
Clean the ignition tube
•
Checking the movability of the firebed switch
•
Clean the lambda probe
Clean the draught fan
Clean the temperature sensor
Check the combustion chamber and heat exchanger
•
Check the firebed button and firebed switch
•
Check heat exchanger tubes
•
Check the seal on heat exchanger cover
•
Dismantle the ignition and clean the ignition tube
Check the pellet hopper
•
Cleaning the fill level sensor
•
Clean the strainer
Check the stoker unit
•
Checking the stoker drive chain
Check de-ashing
•
Check the de-ashing drive chain
Check the underpressure sensor
•
Clean the silicon hoses
•
Calibrate the underpressure sensor
Check the ash box position switch
Calibrate the lambda probe
Reset the maintenance counter
Perform heating test
performed on: _________________________
performed by: _________________________