OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or dam-
age to property.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
Caution
Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers
to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for any-
thing else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1989
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any
form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis-
sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change
without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa-
tion contained in this publication.
TABLE OF CONTENTS
PRECAUTIONS
xi
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience
xii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions
xii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions
xii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions
xiii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions
xiii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction
1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Nomenclature and Features
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2
System Configuration
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Wiring
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Setup
8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
I/O Allocation
11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Word Allocation
12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Bit Allocation
13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Settings and Displays
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Temperature Specification Settings
16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
Temperature Data Display
18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A.
Troubleshooting
23
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.
Standard Models
25
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.
Specifications
27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.
Table of Temperature-Sensing Elements
29
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E.
Using the C200H Temperature Sensor Unit with CS1-series PCs
37
. . . . . . . . . . . . . . . . . . .
Glossary
39
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index
47
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History
49
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About this Manual:
This manual describes the installation and operation of the C200H Temperature Sensor Unit and includes
the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting
to install and operate the C200H Temperature Sensor Unit.
Section 1 provides an introduction to the C200H Temperature Sensor Unit and includes details on no-
menclature and functions as well as the system configuration.
Section 2 explains the wiring procedure required when setting up the Unit.
Section 3 gives details on the word and bit allocations for the Unit.
Section 4 explains how to make temperature settings and how to read the display.
Appendices, a Glossary, and an Index are also included.
WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each
section in its entirety and be sure you understand the information provided in the section
and related sections before attempting any of the procedures or operations given.
!
This section provides general precautions for using the C200H Temperature Sensor Unit and related devices.
The information contained in this section is important for the safe and reliable application of the C200H Temperature
Sensor Unit. You must read this section and understand the information contained before attempting to set up or oper-
ate the C200H Temperature Sensor Unit.
1 Intended Audience
xii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions
xii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions
xii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions
xiii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions
xiii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
This manual is intended for the following personnel, who must also have knowl-
edge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2
General Precautions
The user must operate the product according to the performance specifications
described in the relevant manuals.
Before using the product under conditions which are not described in the manual
or applying the product to nuclear control systems, railroad systems, aviation
systems, vehicles, combustion systems, medical equipment, amusement ma-
chines, safety equipment, and other systems, machines, and equipment that
may have a serious influence on lives and property if used improperly, consult
your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide the
systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be
sure to read this manual before attempting to use the Unit and keep this manual
close at hand for reference during operation.
WARNING It is extremely important that a PC and all PC Units be used for the specified
purpose and under the specified conditions, especially in applications that can
directly or indirectly affect human life. You must consult with your OMRON
representative before applying a PC system to the above-mentioned
applications.
3
Safety Precautions
WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so
may result in electric shock.
WARNING Do not touch any of the terminals or terminal blocks while the power is being
supplied. Doing so may result in electric shock.
WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so
may result in malfunction, fire, or electric shock.
WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, in order to ensure safety in the system
if an abnormality occurs due to malfunction of the PC or another external factor
affecting the PC operation. Not doing so may result in serious accidents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety
measures must be provided in external control circuits.
• The PC will turn OFF all outputs when its self-diagnosis function detects any
error or when a severe failure alarm (FALS) instruction is executed. As a coun-
termeasure for such errors, external safety measures must be provided to en-
sure safety in the system.
• The PC outputs may remain ON or OFF due to deposition or burning of the
output relays or destruction of the output transistors. As a countermeasure for
such problems, external safety measures must be provided to ensure safety in
the system.
• When the 24-VDC output (service power supply to the PC) is overloaded or
short-circuited, the voltage may drop and result in the outputs being turned
OFF. As a countermeasure for such problems, external safety measures must
be provided to ensure safety in the system.
4
Operating Environment Precautions
Caution
Do not operate the control system in the following locations:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in
the specifications.
• Locations subject to condensation as the result of severe changes in tempera-
ture.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
Caution
Take appropriate and sufficient countermeasures when installing systems in the
following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
Caution
The operating environment of the PC system can have a large effect on the lon-
gevity and reliability of the system. Improper operating environments can lead to
malfunction, failure, and other unforeseeable problems with the PC system. Be
sure that the operating environment is within the specified conditions at installa-
tion and remains within the specified conditions during the life of the system.
5
Application Precautions
Observe the following precautions when using the PC system.
WARNING Always heed these precautions. Failure to abide by the following precautions
could lead to serious or possibly fatal injury.
• Always ground the system to 100 Ω or less when installing the Units. Not con-
necting to a ground of 100 Ω or less may result in electric shock.
• Always turn OFF the power supply to the PC before attempting any of the fol-
lowing. Not turning OFF the power supply may result in malfunction or electric
shock.
• Mounting or dismounting I/O Units, CPU Units, Memory Units, or any other
Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Connecting or disconnecting the connectors.
Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC or PC Units. Always heed these pre-
cautions.
• Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal lines,
momentary power interruptions, or other causes.
• Always use the power supply voltages specified in this manual. An incorrect
voltage may result in malfunction or burning.
• Take appropriate measures to ensure that the specified power with the rated
voltage and frequency is supplied. Be particularly careful in places where the
power supply is unstable. An incorrect power supply may result in malfunction.
• Install external breakers and take other safety measures against short-circuit-
ing in external wiring. Insufficient safety measures against short-circuiting may
result in burning.
• Do not apply voltages to the Input Units in excess of the rated input voltage.
Excess voltages may result in burning.
• Do not apply voltages or connect loads to the Output Units in excess of the
maximum switching capacity. Excess voltage or loads may result in burning.
• Disconnect the functional ground terminal when performing withstand voltage
tests. Not disconnecting the functional ground terminal may result in burning.
• Be sure that all the mounting screws, terminal screws, and cable connector
screws are tightened to the torque specified in this manual. Incorrect tighten-
ing torque may result in malfunction.
• Leave the label attached to the Unit when wiring. Removing the label may re-
sult in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipa-
tion. Leaving the label attached may result in malfunction.
• Double-check all wiring and switch settings before turning ON the power sup-
ply. Incorrect wiring may result in burning.
• Wire correctly. Incorrect wiring may result in burning.
• Mount Units only after checking terminal blocks and connectors completely.
• Be sure that the terminal blocks, Memory Units, expansion cables, and other
items with locking devices are properly locked into place. Improper locking
may result in malfunction.
• Check the user program for proper execution before actually running it on the
Unit. Not checking the program may result in an unexpected operation.
• Confirm that no adverse effect will occur in the system before attempting any of
the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PC.
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Resume operation only after transferring to the new CPU Unit the contents of
the DM Area, HR Area, and other data required for resuming operation. Not
doing so may result in an unexpected operation.
• Do not pull on the cables or bend the cables beyond their natural limit. Doing
either of these may break the cables.
• Do not place objects on top of the cables or other wiring lines. Doing so may
break the cables.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to
terminals. Connection of bare stranded wires may result in burning.
• When replacing parts, be sure to confirm that the rating of a new part is correct.
Not doing so may result in malfunction or burning.
• Before touching a Unit, be sure to first touch a grounded metallic object in order
to discharge any static built-up. Not doing so may result in malfunction or dam-
age.
Nomenclature and Features
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2
System Configuration
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Nomenclature and Features
The Temperature Sensor Unit detects temperatures and sends the resultant
BCD (Binary Coded Decimal) data to the PC (Programmable Controller). This
data can be further manipulated and transferred to other I/O Units for ex-
tended system control.
The C200H Temperature Sensor Unit is available in four models. The
C200H-TS001/002 are for use with thermocouples, and can be used with K
(CA), J (IC) and L (Fe-CuNi) thermocouples. The C200H-TS101/102 are for
use with platinum resistance sensors.
The Unit has the following components:
Front Panel
Indicator
panel
Unit no.
selector
Input terminal
block. Refer to
Section 2 Wiring
for details.
Cold- junction
compensating
resistor
C200H-TS001/002
(Thermocouple)
C200H-TS101/102
(Platinum RTD)
Indicator
panel
Unit no.
selector
Input termi-
nal block.
Refer to
Section 2
Wiring for
details.
Unit Number Selector
(7)
(9)
(5)
(1)
(3)
0
8
6
4
2
The arrow on the selector indicates the unit number. Use a standard screw-
driver to rotate the switch and set the desired unit number. Be sure to set dif-
ferent unit numbers from those of other Special I/O Units connected to the
same PC. Otherwise, an “I/O Unit Over” error is generated and the Unit will
not operate properly. IR word numbers are assigned as shown in the follow-
ing table.
Nomenclature and Features
Section 1-1
100 through 109
1
110 through 119
2
120 through 129
3
130 through 139
4
140 through 149
5
150 through 159
6
160 through 169
7
170 through 179
8
180 through 189
9
190 through 199
Indicator panel
There are two LEDs in the indicator panel, which function as follows:
Indicator
Color
Function
RUN
Green
Lit during normal operation. Unlit during errors.
BROKEN
WIRE
Red
Lit when input is disconnected. Blinks when
data is outside of set range.
DIP Switch Setting
C200H-TS001/002
1
2
3
4
ON
2
0
1
No. of Input Points
0
0
4 input points (Inputs
1 through 4)
0
1
1
0
1
1
1 input point (Input 1)
2 input points (Inputs
1 and 2)
Not Used
3
Function
Either K (CA) (0° through 400°C), J
(IC) (0° through 300°C), or L (Fe-
CuNi) (0° through 300°C). Once this
pin has been set to ON, this setting
becomes invalid and the tempera-
ture must be set through the PC
program.
1
Set the temperature depending on
PC program.
4
0
1
Function
K ( CA)
J (IC), L(Fe-
CuNi)
OFF: 0
ON: 1
Number of Input Points
Temperature Selector
Sensor Selector
All switches are OFF before shipment from the factory.
The temperature specifications must be set identically for all four points.
These points cannot be used for different thermocouples or with different
temperature specifications.
The cold-junction compensating resistor connected to the C200H-TS001/002
terminal block (for the thermocouple) has been preset to the Unit’s internal
circuits. Do not remove or replace it. If it is necessary to remove it, when
reattaching, confirm that the number marked on the resistor matches the
number on the Unit, as shown in the following diagram. The output tempera-
ture data may be incorrect if the numbers do not match.
Nomenclature and Features
Section 1-1
DIP Switch Setting
C200H-TS101/102
1
2
3
4
ON
2
0
1
No. of Input Points
0
0
4 input points (Inputs
1 through 4)
0
1
1
0
1
1
1 input point (Input 1)
2 input points (Inputs
1 and 2)
Not Used
3
Function
J Pt (0° through 100°C)/Pt (0°
through 100°C). Once this pin is set
to ON, this setting becomes invalid
and the temperature must be set
through the PC program.
1
Set the temperature depending on
PC program.
OFF: 0
ON: 1
Number of Input Points
Temperature Selector
Not Used
All switches are set to OFF before shipment from the factory.
1-2
System Configuration
The Special I/O Units are not allocated the word number of the slot they are
mounted to. They are allocated word numbers according to the unit number
setting on the front panel (refer to page 2).
If possible, avoid mounting the Temperature Sensor Units in either of the two
rightmost CPU Rack slots. However, if this is unavoidable, use one of the
Programming Console Base Units (C200H-BP001 or C200H-BP002) when
mounting peripheral devices to the PC.
No Special I/O Units can be mounted on a C200H Slave Rack connected to a
Master on a PC other than a C200H.
The thermocouple or RTD registers the temperature and sends the data
through the Temperature Sensor Unit to the PC in 4-digit BCD. After the PC
processes this data, the data can be output to a display, or used for control-
ling system devices.
System Configuration
Section 1-2
Temperature Sensor Unit
C200H-TS001/002/101/102
Output Unit
High-Density and Multiplex
I/O Unit C200H-OD215
CPUs
C200H-
CPU01-E/03-E/11-E
•
Temperature-
sensing element
A maximum of 10 Special I/O Units (including the PC Link Units) can be
mounted on the CPU Rack, Expansion I/O Rack, or Slave Rack. However,
the maximum current supplied or consumed may limit the actual number of
I/O Units that can be connected. Refer to the C200H Installation Guide for
maximum current levels. Note that the specific limit, resulting from data trans-
mission, placed on the Slave Rack is as shown in the following table.
The number of Special I/O Units that can be mounted on a Slave Rack is lim-
ited. The table below shows the maximum number of Special I/O Units that
can be mounted to one Slave Rack.
A
B
C
D
Maximum number
of High-Speed
Counter Units,
Position Control
Units
(NC111/NC112),
ASCII Units,
Analog I/O Units,
and ID Sensor
Units
Maximum number
of High-Density
and Multiplex I/O
Units.
Maximum number
of Voice and
Temperature
Sensor Units.
Maximum number
of Position Control
Units (NC211)
4 Units
8 Units
6 Units
2 Units
Note 1. When using a combination of Units, use the following formula:
3A+B+2C+6D≤12 and, A+B+C+D≤8
2. These Units can be used on other Racks, but the total number cannot
exceed 10.
Mounting Temperature
Sensor Units
Special I/O Units on Slave
Racks
System Configuration
Section 1-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R0 : Cold-junction compensating resistor
The cold-junction compensating resistor connecting terminals B4 and B5 on the
C200H-TS001/002 is fully integrated in the internal circuitry of the Unit and
serves to maintain accuracy. Be careful not to remove this resistor and be sure
the screws are always tight.
Unused Input Terminals
For TS001/002 (thermocouple input), short the positive and negative poles of
the thermocouple inputs (for example, terminals A8 and B8 in Input 4).
For TS101/102 (platinum RTD input), short the B and B′ terminals (for exam-
ple, terminals A8 and B9 for Input 4), and connect a 100 Ω (1/8 W minimum)
resistor between terminals A and B. (For example, A8 and B8 for input 4.)
Removable Terminal Block Connections
When Using Solderless Crimp Leads
Use M3.5 screws (with self-rising pressure plates) for mounting solderless
crimp terminals.
7 mm max.
7 mm max.
Setup
Section 2-1
Carefully tin the 5- to 7-mm exposed end of the lead wire.
+
ÉÉÉ
5 to 7 mm
10 mm
Tighten the screws to a
torque of 0.8 N � m.
Wiring Notes
To avoid influence from induced noise, keep the input signal wires (compen-
sating wires or lead wires) away from the power source line or load line by at
least 300 mm. Also be sure not to lay them parallel to, or in the same cable
as, the power line. Using shield wires in separated ducts or pipes is also an
effective way to reduce influence from noise. Attach surge absorbers or noise
filters to peripheral devices that generate noise (in particular, devices that
possess inductance components, such as motors, transistors, solenoids, or
magnet coils). Install away from devices that generate strong, high-frequency
waves or that generate surges.
Connect the thermocouples with the compensating wires as shown in the
following diagram. Connect platinum RTDs with lead wires of low resistance
(for example, copper wires). Make the three lead wires extending from the
platinum RTDs equal in length. Do not short-circuit the B wire and B’ wire
near the terminal block connector, because it causes measurement errors.
Input Signal Wire Extension
The input signal wire should be as short as possible so that the effect of out-
side noise is minimized. The following table has more information on type
and length of the signal wire.
Sensor-Input
Wire
Configuration
Maximum
Extension Length
K (CA)
Compensating conductor
WX-H, WX-H6
0.3 mm2 x 7 leads
80 m
J (IC)
Compensating conductor
JX-H, JX-H6
0.3 mm2 x 7 leads
70 m
L (Fe-CuNi)
Compensating conductors
JX
0.3 mm2 x 7 leads
70 m
JPt 100 ΩPt
100Ω
Copper wire
0.5 mm2
120 m
Setup
Section 2-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Bit Allocation
13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The unit number setting (on the front panel of the Temperature Sensor Unit)
determines the words allocated to the Unit. Ten words are assigned to any
given Special I/O Unit, but only six words are actually used by the Tempera-
ture Sensor Unit. The following figure shows which words are available ac-
cording to the unit number setting.
Unit 0
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
Unit 9
100 through 109
120 through 129
130 through 139
140 through 149
150 through 159
160 through 169
170 through 179
180 through 189
190 through 199
110 through 119
Each time the PC data
is refreshed, output
data is written from the
PC to the Temperature
Sensor, then input data
is read from the Tem-
perature Sensor to the
PC.
Output refresh
Input refresh
Word n
Words n+1
through
n+5
Only six words are
used. Words n+6
through n+9 are avail-
able as work bits
n = 100 + 10 x unit no.
PCs IR area
Note When setting a unit number, be sure not to select the same number used for
another Special I/O Unit. Otherwise, an “I/O UNIT OVER” error is generated
and the Sensor Unit will not operate properly.
Word Allocation
Section 3-1
code no.: 00 through 25
Data
hold
enable
x 101
x 100
Input
n + 1
Code
0: positive
Conversion data of Input 1
1: negative
x 103
x 102
x 101
x 100
n + 2
Code
0: positive
Conversion data of Input 2
1: negative
x 103
x 102
x 101
x 100
n + 3
Code
0: positive
Conversion data of Input 3
1: negative
x 103
x 102
x 101
x 100
n + 4
Code
0: positive
Conversion data of Input 4
1: negative
x 103
x 102
x 101
x 100
n + 5
Running
Temperature specification
code no.: 00 through 25
Data
inval-
id
Stand
by for
Memory
error
Disconnection
detected
Setting
error
x 101
x 100
set-
ting
Input
4
Input
3
Input
2
Input
1
Note n = 100 + 10 x unit no.
The four words from words n+6 through n+9 can be used as work bits. Refer
to the C200H Operation Manual for details.
IR Bit Allocation
IR
Name
Function
Word
Bit
Output
n
00
Data hold
When this bit is turned ON, conversion of the temperature input
data is stopped and data is returned to its status just prior to turning the
bit ON. When this bit is turned OFF, the temperature input data is
converted to BCD data in cycles.
01
through
07
---
Always turned OFF.
08
through
13
Temperature
specification
code number
These bits specify the temperature specification code number of the
temperature sensing element used in the Unit. A total of 41 code
numbers (thermocouple K (CA) = 11, thermocouple J (IC) = 4, L(Fe-CuNi)
= 4, platinum RTD JPt = 11, platinum RTD Pt= 11 numbers) can be
specified in 2-digit BCD from 00 through 25. (Refer to pages 3 and 16 for
details.) The temperature specification code number becomes valid after
the temperature specification setting flag (word n bit 15) is turned ON.
14
---
Not used. Always turned OFF.
15
Temperature
specification
enable
When this bit is turned ON, the temperature specification code number
specified for word n bits 08 through 13 becomes valid. Be sure to confirm
beforehand that the temperature specification switch (pin 3) on the back
panel has been set to the ON position and that the setting standby flag
(word n+5 bit 06) has also been turned ON. Otherwise the code number
is invalid.
Bit Allocation
Section 3-2
n + 1
00
through
15
Input 1
conversion
0
1
+
–
x 103 x 102 x 101 x 100
15
00
The temperature input data
of input 1 is displayed in
BCD.
n + 2
00
through
15
Input 2
conversion
0
1
+
–
x 103 x 102 x 101 x 100
15
00
The temperature input data
of input 2 is displayed in
BCD.
n + 3
00
through
15
Input 3
conversion
x 103 x 102 x 101 x 100
15
00
The temperature input data
of input 3 is displayed in
BCD.
0
1
+
–
n + 4
00
through
15
Input 4
conversion data
0
1
+
–
x 103 x 102 x 101 x 100
15
00
The temperature input data
of input 3 is displayed in
BCD.
n + 5
00
Setting Error
This bit turns ON when the specified temperature specification code
number (word n bits 08 through 13) results in one of the following: 1) a
figure above 26; or 2) the temperature sensing element corresponds to a
different specified code number than the one actually connected to the
Temperature Sensor Unit. For example, if pin 4 is set for K(CA) and the
temperature specification code number is set to 11-25, a setting error is
generated.
01
Input 1
Discon-
If a disconnection is detected in one of the inputs, the bit corresponding
02
Input 2
nection
to that particular input turns ON. The conversion data of the word
03
Input 3
de-
tected
corresponding to the disconnected input (words n+1 through n+4)
becomes “E039.”
04
Input 4
tected
becomes “E039.”
05
Memory error
Whenever an error occurs in the Temperature Sensor’s internal memory
(the memory storing the conversion data from each of the four inputs),
this bit turns ON.
06
Setting standby
This bit keeps the setting of the temperature specification code number
on standby. After the temperature specification switch (pin 3) on the back
panel is set to the ON position, and while the power supply is ON or
during Restart, this bit remains ON until the setting is completed. When
setting the temperature specification, turn the temperature specification
setting flag (word n bit 15) ON. Refer to page 17 Temperature
specification setting flag.
07
Data invalid
After the power supply is turned ON, or after restart, the conversion data
remains unstable for several seconds; during this period, this bit turns
ON. Once all the data stabilizes, the bit turns OFF. While this bit is OFF,
program with the conversion data from words n+1 through n+3. Refer to
page 21 for conversion data listing.
08
through
13
Temperature
specification
code number
These bits pinpoint the current settings of the temperature specification
code number and represent the confirmation area (00 through 25).
14
---
Not used
15
Running
Turns ON while the Unit is operating.
Bit Allocation
Section 3-2
Settings and Displays
4-1
Temperature Specification Settings
16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
Temperature Data Display
18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature Specification Settings
Before shipment from the factory, the Temperature Sensor Unit’s temperature
specifications are preset for the parameters shown in the following table. If
using the Unit according to these settings, keep pin 3 of the DIP switch on
the back panel in the OFF position. When using the C200H-TS001 with the
J-type (0° through 300°C) sensing element, or when using C200H-TS002
with the L-type (0° through 300°C) sensing element, set the K (CA)/J (IC) and
K (CA)/L (Fe-CuNi) selector (pin 4) on the back panel DIP switch to the ON
position.
Model
Sensor-input
Default range
Temperature
specification
code number
C200H-TS001
K (CA)
0° through 400°C
02
J (IC)
0° through 300°C
12
C200H-TS002
K (CA)
0° through 400°C
02
L (Fe-CuNi)
0° through 300°C
12
C200H-TS101
Pt 100 Ω
0° through 100°C
18
C200H-TS102
Pt 100 Ω
0° through 100°C
18
If using temperature specifications as shown in the above table, the setting
sequence described in the next paragraph can be ignored. However, note
that programming the temperature specification code is necessary even
when one of the codes listed in the above table is used after turning ON the
temperature specification selector DIP switch (pin 3) on the back panel.
For operation at temperatures other than those specified in the above table,
program the temperature specification codes according to the following se-
quence:
1, 2, 3... 1.
First set the temperature specification selector on the back panel (pin 3)
to the ON position. For TS001/002, set the K (CA)/J (IC) , and K (CA) L
(Fe-CuNi) selector on the back panel (pin 4) to the name of the temper-
ature-sensing element in actual use.
OFF
K (CA) used
ON
J (IC) / L (Fe-CuNi) used
2.
Set the program to the new temperature specification code of the sens-
ing element using word n bits 13 to 08. Reset the Unit with the restart
flag and check that the standby flag (word n+5 bit 06) is turned ON.
Then set the program that turns ON the temperature specification set-
ting flag (word n bit 15). Refer to page 17 for a programming example
based on the above sequence.
Note Whenever the temperature specification selector (pin 3) on the back panel is
set to OFF, the temperature specification code cannot be set. When the tem-
perature specification code is set at a number beyond 26, or when a code
corresponding to a temperature-sensing element that cannot be used with
the Temperature Sensor Unit is selected, the setting error flag (word n+5 bit
00) turns ON to signal an alarm. Especially when using TS001/002, be sure
to confirm that the K (CA)/J (IC), and K (CA)/L (Fe-CuNi) selector (pin 4) on
the back panel are correctly set.
The reset flags range from AR0100 through AR0109, and correspond to re-
spective Special I/O Unit numbers. For example, unit number 3 corresponds
to reset flag AR0103.
The C200H-TS001 offers 15 ranges for thermocouple input: 11 for type K
(CA) sensors and 4 for type J (IC) sensors. The C200H-TS002 offers 15
Setting Temperature
Specification Codes
Temperature Specification
Codes
Temperature Specification Settings
Section 4-1
ranges for thermocouple input: 11 for type K (CA) sensors, and 4 for type L
(Fe-CuNi) sensors. The C200H-TS101 offers 11 ranges for platinum-RTD
(JPt) input. The C200H-TS102 offers 11 ranges for platinum-RTD (PT) input.
A separate code number from 00 through 25 is assigned to each Tempera-
ture Sensor/range specification.
C200H-TS001/002
Temperature-
Thermocouple
sensing element
K (CA): chromel-alumel
J (IC):iron-
constantan/
L (Fe-CuNi)
Measuring unit
°C
°F
°C
Measurement
range
1600
1000
800
600
500
400
300
200
150
100
80
50
0
Temperature
specification code
(2-digit BCD)
00 01 02 05 06 07 08
09 10 11 12 13 14
03 04
C200H-TS101/102
Temperature
Platinum RTD
sensing element
JPt 100 Ω/Pt 100 Ω
Measuring unit
°C
°F
Measuring
range
500
400
300
200
150
100
80
50
0
-20
-50
Temperature
specification code
(2-digit BCD)
15 16 17 18 21 22 23
24 25
19 20
Programming Example
In this example, the temperature specification code of the temperature sens-
ing element is programmed. For this example a thermocouple K (CA), 0°
through 800°C (Code 07) is used, and the Temperature Sensor Unit is set to
0.
Temperature Specification Settings
Section 4-1
OFF: Thermocouple K (CA).
ON: Temperature specification selector.
DIP Switch Setting
1
2
3
4
ON
Set the temperature specification code 07 (word data #0700) for K (CA), 0°
through 800°C to word 100. The specified data (code 07) is transferred to
word 100.
Unit 0 restart flag
Turns ON the restart flag (AR 0100 for unit 0) during RUN and after 1 scan
when (25315) or starting input (0000) is ON, then resets the Unit.
Confirms that the signal setting on standby (10506) is ON. Provided the
alarm setting error flag (10500) is OFF, turns the temperature specification
setting flag (10015) ON, and executes the setting. After the setting, the signal
setting on standby turns OFF and the temperature specification setting pro-
cess is ended.
25313
(Always ON)
25315 (1 scan ON)
0000
25313
10506
10500
10500
10015
AR
0100
MOV (21)
#0700
100
(Always ON)
(Setting on
standby)
FAL (06) 01
(Setting error)
C200H-TS101
The setting switch on the back panel (pin 4) is not used. Otherwise, program-
ming and operating functions follow the pattern described for the C200H-
TS001.
Note Whenever setting the temperature specification code, be sure to turn ON DIP
switch pin 3 (temperature specification selector) on the back panel. If the
switch is OFF, the setting is invalid. Before setting the temperature specifica-
tion, be sure the setting standby flag (10506) is ON and the setting error flag
(10500) is OFF, then turn the temperature specification setting flag (10015)
ON.
4-2
Temperature Data Display
The following example describes the display of temperature data when a Dis-
play Unit is connected to the Transistor Output Unit C200H-OD215. The
C200H-OD215 is set as unit 2 and the C200H-TS001 is set as unit 0.
Temperature specification
setting flag (sets code to 07
when this flag rises)
Temperature Data Display
Section 4-2
Input points 2
K (CA)/J (IC) selector
Temperature specification selector, with pins 3
and 4 preset to the OFF position at time of de-
livery. Operation based on temperature sensor
conforming to type K (CA) (0° through 400°C)
C200H-TS001 DIP Switch Setting
1
2
3
4
ON
1
2
3
4
ON
128-point Dynamic output mode (turn ON)
Negative logic output (set to OFF)
Setting is irrelevant
5
6
Setting is irrelevant
C200H-OD215 DIP Switch Setting
Temperature Data Display
Section 4-2
Display Data 1
Display Data 3
Display Data 4
Display Data 5
Display Data 6
Display Data 7
Display Data 2
Ground
24 V
NC
NC
Output Strobe 4
Output Strobe 3
Output Strobe 2
Output Strobe 1
Signal
Display Data 0
Display Data 1
Display Data 3
Display Data 4
Display Data 5
Display Data 6
Display Data 7
Display Data 2
24 V
NC
NC
Output Strobe 4
Output Strobe 3
Output Strobe 2
Output Strobe 1
Signal
CN 1
24 VDC
+
Transistor Output Unit
C200H-OD215
Display Unit
(Negative logic input,
power supply 24 VDC)
Ground
Temperature Data Display
Section 4-2
Note As the operating current is extremely small, use shielded cables for connec-
tions and/or keep wiring as distant as possible from power lines. Further-
more, keep all connections are as short as possible, and not more than 10
meters in length.
Program
Masks the signal bit (10115) corresponding to the temperature data (word
101) of Input 1, and outputs to word 120 of the High-Density and Multiplex
I/O Unit.
When the temperature is negative (when bit 10115 is ON), word 121 bit 15
(of the High-Density and Multiplex I/O Unit) turns ON. A negative sign is then
shown on the display.
The above also applies to temperature data (word 102) of Input 2.
25313
(Always ON)
12115
ANDW (34)
#7FFF
101
120
10507
(Data invalid)
10115
ANDW (34)
#7FFF
102
122
10215
12315
Checks data validity
Signal bit of Input 1 data
Signal bit of Input 1 data
Note The Display Unit displays numerical data only if each digit is in BCD. Other-
wise, the display remains blank. The display range is -9,999,999 to
9,999,999. Refer to each manual for more details on the Transistor Output
Unit C200H-OD215 and Display Unit.
Input Data Conversion
The temperature data to be input is converted to 4-digit BCD in the Master
and then output to the conversion words, n+1 through n+4. This conversion
data has an error tolerance of 10 beyond the standard temperature range.
When the conversion result is not within the tolerance range, the data of
words n+1 through n+4 becomes FFFF. If the input temperature is negative,
bit 15 for each of the conversion words (n+1 through n+4) turns ON and the
data becomes 8XXX.
Temperature Data Display
Section 4-2
Conversion data (words n+1 through n+4, BCD)
C200H-
K(CA)
°C
0 to 200
00
FFFF
8020 to 8001
0000 to 0200
to 0220
FFFF
TS001/TS002
0 to 300
01
8030 to 8001
0000 to 0300
to 0330
0 to 400
02
8040 to 8001
0000 to 0400
to 0440
0 to 500
05
8050 to 8001
0000 to 0500
to 0550
0 to 600
06
8060 to 8001
0000 to 0600
to 0660
0 to 800
07
8080 to 8001
0000 to 0800
to 0880
0 to 1000
08
8100 to 8001
0000 to 1000
to 1100
°F
0 to 400
03
8040 to 8001
0000 to 0400
to 0440
0 to 500
04
8050 to 8001
0000 to 0500
to 0550
0 to 1000
09
8100 to 8001
0000 to 1000
to 1100
0 to 1600
10
8160 to 8001
0000 to 1600
to 1760
J (IC)/
°C
0 to 200
11
8020 to 8001
0000 to 0200
to 0220
L(Fe-Cu
0 to 300
12
8030 to 8001
0000 to 0300
to 0330
Ni)
0 to 400
13
8040 to 8001
0000 to 0400
to 0440
0 to 500
14
8050 to 8001
0000 to 0500
to 0550
C200H-
Jpt100/
°C
-50 to 50
15
8060 to
0000 to 0050
to 0060
TS101/TS102
pt100
-50 to 100
16
8065 to
0000 to 0100
to 0115
-20 to 80
17
8030 to
0000 to 0080
to 0090
0 to 100
18
8010 to 8001
0000 to 0100
to 0110
0 to 200
21
8020 to 8001
0000 to 0200
to 0220
0 to 300
22
8030 to 8001
0000 to 0300
to 0330
0 to 400
23
8040 to 8001
0000 to 0400
to 0440
°F
-50 to 100
19
8065 to
0000 to 0100
to 0115
0 to 200
20
8020 to 8001
0000 to 0200
to 0220
0 to 400
24
8040 to 8001
0000 to 0400
to 0440
0 to 500
25
8050 to 8001
0000 to 0500
to 0550
Outside
range
-10% F.S.
Outside
range
F.S.
+10% F.S.
Temperature Data Display
Section 4-2
Should you encounter any errors during operation of the Temperature Sensor Unit, refer to the following table
for corrective measures.
Error
LED indicator
Input flag word n+5
IR
Possible cause
Remedy
RUN
BROKEN
05
01 to 04
00
Words
WIRE
Memory
error
Discon-
nection
detected
Setting
error
n+1
through
n+4
Outside
range
Lit
Blinking
OFF
OFF
OFF
FFFF
Input exceeds
tolerance of ±10%
for the temperature
specification range.
Confirm that the
temperatures to be
measured are within
the specified range.
Discon-
nection
Lit
Lit
OFF
ON
OFF
E039
Disconnection
detected in input.
(See note 1.)
Check both the
sensing element
and the wiring.
Temper-
ature
specifi-
cation
setting
error
Unlit
Unlit
OFF
OFF
ON
---
Error detected in
setting of
temperature
specification.
Recheck the K
(CA)/J (IC) selection
(pin 4) on the back
panel of the Unit,
the specified area
(word n bits 08
through 13) for the
temperature
specification codes,
and the setting
program.
Memory
error
Unlit
Unlit
ON
OFF
OFF
E003
E004
E005
Internal memory
(storing modified
data) of Unit
defective.
Disturbance from
noise or irregularity
in hardware are
possible causes. If
alarm flag does not
light after removing
CPU
error
Unlit
Unlit
---
---
---
---
Error detected in
the watchdog timer
of the Temperature
Sensor. The PC
registers a Special
I/O Unit error.
disturbance and/or
turning power ON
and OFF
repeatedly, call
sales agent.
Replacement may
be necessary. (See
note 2.)
Note 1. A broken wire is detected if the positive or negative wires of the thermo-
couple, or the internal A or B wires of the platinum RTD are disconnected.
In this case, the input data becomes “E039.” However, be careful not to
confuse the B wire of the platinum RTD with the B’ wire leading out from
the same sensor. If the B’ wire is disconnected, the input data will be
FFFF.
2. When returning the C200H-TS001/002 Temperature Sensor for repair,
assemble the main body of the Unit to the terminal block connector (as
originally delivered.)
JPt 100 Ω/Pt 100 Ω
Measuring unit
°C
°F
Measure-
ment range
500
400
300
200
150
100
80
50
0
-20
-50
Temperature
specification code
(2-digit BCD)
15 16 17 18 21 22 23
24 25
19 20
Dimensions
C200H-TS001/002/101/102
x
x
x
x
x
x
x
x
130
35
Back-
plane
128
*When mounted to Backplane.
145*
(unit: mm)
K(CA) or J(IC)
C200H-TS001
Thermocouple:
K(CA) or L(Fe-CuNi) (DIN)
C200H-TS002
Platinum resistance thermometer
bulb: JPt 100 Ω
C200H-TS101
Platinum resistance thermometer
bulb: Pt 100 Ω (DIN/1989JIS)
C200H-TS102
External input signal (type of
temperature sensing
element).
Thermocouple: K
(CA) or J (IC)
Selectable
Thermocouple: K
(CA) or L (Fe-CuNi)
(DIN) Selectable
Platinum resistance
thermometer bulb:
JPt 100 Ω
Platinum resistance
thermometer bulb: Pt
100 Ω (DIN/ 1989 JIS)
External input points
4 points max. per Unit (1, 2, or 4 points selectable)
Output code to PC
4-digit BCD
Accuracy
± (1% Full scale + 1°C) max. (See note.)
Conversion time
1.2 sec max. per point
Conversion cycle
4.8 sec max. at 4 points per Unit
2.4 sec max. at 2 points per Unit
1.2 sec max. at 1 point per Unit
PC booting time
Conversion cycle + 1 PC scan time
Terminal connections
Terminal block (removable)
Insulation mode
Non-insulated between words. Insulated by photocoupler between input terminal and
PC signals.
Internal power supply
450 mA max. at 5 VDC
External dimensions
35 (W) x 130 (H) x 128 (D)
Weight
400 g max.
Note For example, at a specification of 0° through 400°C, 400°C x 1% + 1°C = ±5°C
max.
Input Specifications
C200H-TS001/002
Temperature
Thermocouple
sensing element
K (CA): chromel-alumel
J (IC):
iron-constant
an/ L
(Fe-CuNi)
Measuring unit
°C
°F
°C
Measurement
range
1600
1000
800
600
500
400
300
200
150
100
80
50
0
Temperature
specification code
(2-digit BCD)
00 01 02 05 06 07 08
03 04 09 10 11 12 13 14
Table of Temperature-Sensing Elements
General-Purpose
Appearance
Model no.
Length (L) of
protecting tube
(mm)
Diameter (D) of protecting
tube (mm)
D
L
E52-__15A
150
1,
1.6, 3.2
E52-__20A
200
1,
1.6, 3.2, 4.8, 6.4, 8
E52-__35A
350
1,
1.6, 3.2, 4.8, 6.4, 8
E52-__50A
500
3.2, 4.8, 6.4, 8
D
L
E52-__20B
200
3.2, 4.8, 6.4,
E52-__35B
350
3.2, 4.8, 6.4, 8
E52-__50B
500
3.2, 4.8, 6.4, 8
E52-__75B
750
4.8, 6.4, 8
D
L
E52-__20C
200
3.2, 4.8, 6.4
E52-__35C
350
3.2, 4.8, 6.4, 8
E52-__50C
500
3.2, 4.8, 6.4, 8
E52-__75C
750
4.8, 6.4, 8
D
L
E52-__35B
350
10, 12,
15
E52-__50B
500
10, 12,
15
22
E52-__75B
750
10, 12,
15
22
E52-__100B
1000
10, 12,
15
22
D
L
E52-__35C
350
10, 12,
15
E52-__50C
500
10, 12,
15
22
E52-__75C
750
10, 12,
15
22
E52-__100C
1000
10, 12,
15
22
D
L
E52-PT15A
150
3.2
E52-PT20A
200
3.2, 4.8, 6.4
E52-PT35A
350
3.2, 4.8, 6.4
E52-PT50A
500
4.8, 6.4
Table of Temperature-Sensing Elements
Appendix D
30
Appearance
Diameter (D) of protecting
tube (mm)
Length (L) of
protecting tube
(mm)
Model no.
D
L
E52-PT20C
200
3.2, 4.8, 6.4
E52-PT35C
350
3.2, 4.8, 6.4
E52-PT50C
500
3.2, 4.8, 6.4
E52-PT75C
750
4.8, 6.4
D
L
E52-PT20B
200
8
E52-PT35B
350
8,
10
E52-PT50B
500
8,
10
E52-PT75B
750
10
E52-PT100B
1000
10
D
L
E52-PT20C
200
8
E52-PT35C
350
8,
10
E52-PT50C
500
8,
10
E52-PT750C
750
10
E52-PT100C
1000
10
D
D
L
D
L
L
E52-__6AS
60
4.8
E52-__10AS
100
4.8
E52-__15AS
150
4.8
E52-__20AS
200
4.8
E52-__1D
10
Screw pitch W1/4,M6, M8
E52-__6F
60
4
E52-__6D
60
4
E52-__10AE
100
3.2
D
L
E52-PT10AE
100
3.2
E52-PT6D
60
4
E52-PT6F
60
4
Table of Temperature-Sensing Elements
31
Sensor
Element
Style
Grade
Model no.
Shape of
terminal
box
Quality of
tube
Tempera-
ture
range**
Sheathed
K (CA)
No ground
0.75
E52-__15A
Open lead
SUS 316
0° to
thermocouple
J (IC)
E52-__20A
wire
Inconel
1050°C
(See note 1.)
E52-__35A
(See note 3.)
E52-__50A
E52-__20B
Exposed
E52-__35B
terminal
E52-__50B
E52-__75B
E52-__20C
Covered
E52-__35C
terminal
E52-__50C
E52-__75C
Universal
E52-__35B
Exposed
SUS 316
0° to
thermocouple
E52-__50B
terminal
SUS 310S
1000°C
E52-__75B
SUS 304
E52-__100B
(See note 3.)
E52-__35C
Covered
E52-__50C
terminal
E52-__75C
E52-__100C
Sheathed
JPt 100 Ω
Three-wire
0.5
E52-PT15A
Open lead
SUS 316
-200° to
platinum
E52-PT20A
wire
450°C
resistance
E52-PT35A
thermometer
E52-PT50A
bulb
E52-PT20C
Covered
E52-PT35C
terminal
E52-PT50C
E52-PT75C
Universal
JPt 100 Ω
Three-wire
0.5
E52-PT20B
Exposed
SUS 316
0° to 400°C
platinum
E52-PT35B
terminal
resistance
E52-PT50B
thermometer
E52-PT75B
bulb
E52-PT100B
E52-PT20C
Covered
E52-PT35C
terminal
E52-PT50C
E52-PT75C
E52-PT100C
Table of Temperature-Sensing Elements
Appendix D
32
Sensor
Tempera-
ture
range**
Quality of
tube
Shape of
terminal
box
Model no.
Grade
Style
Element
Low-cost
K (CA) J (IC)
No ground
0.75
E52-__6AS
Open lead
SUS 304
0° to 400°C
Thermocouple
(See note 1.)
E52-__10AS
wire
E52-__15AS
Ground
E52-__20AS
E52-__1D
E52-__6F
E52-__6D
No ground
E52-__10AE
Low-cost
Platinum
JPt 100 Ω
Three-wire
0.5
E52-_PT10AE
-50° to
250°C
resistance
thermometer
E52-_PT6D
bulb
E52-_PT6F
Note 1. In this table, each model number preceded by a dash, e.g., E52-__15A,
can be either K(CA) or J(IC).
2. JIS standard signals
3. Actual temperature range will vary with the diameter of the protecting
tube.
4. K(CA) only
Table of Temperature-Sensing Elements
33
K Standard Thermoelectromotive Force
JIS-C 1602-1981 Unit: µV
Temperature (°C)
0
10
20
30
40
50
60
70
80
90
Temperature (°C)
0
0
397
798
1203
1611
2022
2436
2850
3266
3681
0
100
4095
4508
4919
5327
5733
6137
6539
6939
7338
7737
100
200
8137
8537
8938
9341
9745
10151
10560
10969
11381
11793
200
300
12207
12623
13039
13456
13874
14292
14712
15132
15552
15974
300
400
16395
16818
17241
17664
18088
18513
18938
19363
19788
20214
400
500
20640
21066
21493
21919
22346
22772
23198
23624
24050
24476
500
600
24902
25327
25751
26176
26599
27022
27445
27867
28288
28709
600
700
29128
29547
29965
30383
30799
31214
31629
32042
32455
32866
700
800
33277
33686
34095
34502
34909
35314
35718
36121
36524
36925
800
900
37325
37724
38122
38519
38915
39310
39703
40096
40488
40879
900
1000
41269
41657
42045
42432
42817
43202
43585
43968
44349
44729
1000
1100
45108
45486
45863
46238
46612
46985
47356
47726
48095
48462
1100
1200
48828
49192
49555
49916
50276
50633
50990
51344
51697
52049
1200
1300
52398
52747
53093
53439
53782
54125
54466
54807
---
---
1300
J Standard Thermoelectromotive Force
JIS-C 1602-1981 Unit: µV
Temperature (°C)
0
10
20
30
40
50
60
70
80
90
Temperature (°C)
0
0
507
1019
1536
2058
2585
3115
3649
4186
4725
0
100
5268
5812
6359
6907
7457
8008
8560
9113
9667
10222
100
200
10777
11332
11887
12442
12998
13553
14108
14663
15217
15771
200
300
16325
16879
17432
17984
18537
19089
19640
20192
20743
21295
300
400
21846
22397
22949
23501
24054
24607
25161
25716
26272
26829
400
500
27388
37949
28511
29075
29642
30210
30782
31356
31933
32513
500
600
33096
33683
34273
34867
35464
36066
36671
37280
37893
38510
600
700
39130
39754
40382
41013
41647
42283
42922
43563
44207
44852
700
800
45498
46144
46790
47434
48076
48716
49354
49989
50621
51249
800
900
51875
52496
53115
53729
54351
54948
55553
56155
56753
57349
900
1000
57942
58533
59121
59708
60293
60876
61459
62039
62619
63199
1000
1100
63777
64355
64933
65510
66087
66664
67240
67815
68390
68964
1100
1200
69536
---
---
---
---
---
---
---
---
---
1200
Note The temperature of standard contact should be 0°C.
Table of Temperature-Sensing Elements
Appendix D
34
L (Fe-CuNi) Standard Thermoelectromotive Force
DIN 1985 43710 Unit: µV
Temperature (°C)
0
10
20
30
40
50
60
70
80
90
Temperature (°C)
0
0
520
1050
1580
2110
2650
3190
3730
4270
4820
0
100
5370
5920
6470
7030
7590
8150
8710
9270
9830
10390
100
200
10950
11510
12070
12630
13190
13750
14310
14880
15440
16000
200
300
16560
17120
17680
18240
18800
19360
19920
20480
21040
21600
300
400
22160
22720
23290
23860
24430
25000
25570
26140
26710
27280
400
500
27850
28430
29010
29590
30170
30750
31330
31910
32490
33080
500
600
33670
34260
34850
35440
36040
36640
37250
37850
38470
39090
600
700
39720
40350
40980
41620
42270
42920
43570
44230
44890
45550
700
800
46220
46890
47570
48250
48940
49630
50320
51020
51720
52430
800
Note The temperature of standard contact should be 0°C.
Platinum Resistance Thermometer Bulb JPt 100 Ω Standard Thermoelectromotive
Force (R0 = 100 Ω R100/R0 = 1.3916)
JIS C1604 1989 Unit: Ω
Temperature (°C)
–100
0
Temperature (°C)
0
100
200
300
400
500
0
59.57
100.00
0
100.00
139.16
177.13
213.93
249.56
284.02
–10
55.44
96.02
10
103.97
143.01
180.86
217.54
253.06
---
–20
51.29
92.02
20
107.93
146.85
184.58
221.15
256.55
---
–30
47.11
88.01
30
111.88
150.67
188.29
224.74
260.02
---
–40
42.91
83.99
40
115.81
154.49
191.99
228.32
263.49
---
–50
38.68
79.96
50
119.73
158.29
195.67
231.89
266.94
---
–60
34.42
75.91
60
123.64
162.08
199.35
235.45
270.38
---
–70
30.12
71.85
70
127.54
165.86
203.01
238.99
273.80
---
–80
25.80
67.77
80
131.42
169.63
206.66
242.53
277.22
---
–90
21.46
63.68
90
135.30
173.38
210.30
246.05
280.63
---
–100
17.14
59.57
100
139.16
177.13
213.93
249.56
284.02
---
Note The temperature of standard contact should be 0°C.
Table of Temperature-Sensing Elements
35
Platinum Resistance Thermometer Bulb
Pt 100 Ω Standard Thermoelectromotive Force (R0 = 100 Ω R100/R0 = 1.3850)
DIN 43760 1980, JIS C1604 1989 Unit: Ω
Temperature (°C)
–100
0
Temperature (°C)
0
100
200
300
400
500
600
0
60.25
100.00
0
100
138.50
175.84
212.02
247.04
280.90
313.59
–10
56.19
96.09
10
103.90
142.29
179.51
215.57
250.48
284.22
316.80
–20
52.11
92.16
20
107.79
146.06
183.17
219.12
253.90
287.53
319.99
–30
48.00
88.22
30
111.67
149.82
186.82
222.65
257.32
290.83
323.18
–40
43.87
84.27
40
115.54
153.58
190.45
226.17
260.72
294.11
326.35
–50
39.71
80.31
50
119.40
157.31
194.07
229.67
264.11
297.39
329.51
–60
35.53
76.33
60
123.24
161.04
197.69
233.17
267.49
300.65
---
–70
31.32
72.33
70
127.07
164.76
201.29
236.65
270.86
303.91
---
–80
27.08
68.33
80
130.89
168.46
204.88
240.13
274.22
307.15
---
–90
22.80
64.30
90
134.70
172.16
208.45
243.59
277.56
310.38
---
–100
18.49
60.25
100
138.50
175.84
212.02
247.04
280.90
313.59
---
Note The temperature of standard contact should be 0°C.
Using the C200H Temperature Sensor Unit
with CS1-series PCs
I/O Allocation
When using the C200H Temperature Sensor Unit with a CS1-series PC, the first
word, n, of I/O memory allocated to a Unit will be given by n = 2000 + unit no. × 10
(not n = 100 + 10 × unit no.). Other than this, there are no points that need particu-
lar attention.
Data Configuration
Bit Allocation
The following table shows the bit allocation for the Temperature Sensor Unit
when using a CS1-series PC.
Word no.
Bit
Allocation
Contents
Direction
n
0 to
Commands from CPU Unit
Temperature specification code no.
CPU to Temperature Sensor Unit
n + 1
15
Analog input status
Conversion data of input 1
Temperature Sensor Unit to CPU
n + 2
Conversion data of input 2
n + 3
Conversion data of input 3
n + 4
Conversion data of input 4
n + 5
Disconnection detection, setting
errors etc.
Note In the above table, n = 2000 + unit no. × 10.
DM Area allocation
The DM area is not used.
Settings and Operation
Initial Settings (Hardware Settings)
Make the following settings before using the Temperature Sensor Unit.
1, 2, 3...
1. Using the DIP switch on the back panel of the Temperature Sensor Unit, set
the number of input points and the sensor type.
2. Using the switch on the front panel, set the unit number.
3. Mount to a CS1 CPU Rack, a C200H Expansion I/O Rack, a CS1 Expansion
I/O Rack or a SYSMAC BUS Remote I/O Slave Unit. In the basic configura-
tion up to 10 Units can be mounted. (There are no restrictions with regard to
mounting position.)
4. Connect the Temperature Sensor.
5. Connect the Programming Device to the PC.
6. Turn ON power for the PC.
7. Create I/O tables.
Ladder Program
Make the following settings using the ladder program.
1, 2, 3...
1. Set the temperature specification code (range) using the MOV instruction.
2. Read temperature data using the MOV instruction.
Ladder Program
The ladder program is used in the following way.
1, 2, 3...
1. The temperature specification code (word n) is set with the MOV instruction
using the always ON flag as the input condition.
2. If the signal setting on standby (word n + 5, bit 06) is ON and the setting error
flag (word n + 5, bit 00) is OFF, the temperature specification setting flag
(word n, bit 15) will be turned ON, using for example, the OUT instruction.
Using the C200H Temperature Sensor Unit with CS1-series PCs
Appendix E
38
Programming Example
The following example shows how to set the temperature specification code us-
ing the ladder program, when using the C200H-TS001.
In this example, the temperature specification code of the temperature sensing
element is programmed. For this example a thermocouple K (CA), 0° through
800°C (Code 07) is used and the unit number of the Temperature Sensor Unit is
set to 0.
OFF: Thermocouple K (CA).
ON: Temperature specification selector.
DIP Switch Setting
1
2
3
4
ON
Set the temperature specification code 07 (word data #0700) for K (CA), 0°
through 800°C to word 2000 (word n). The specified data (code 07) is trans-
ferred to word 2000.
Unit 0 Restart Flag
Turns ON the restart flag and turns ON the Temperature Sensor Unit after one
scan at startup or when starting input “a” is ON.
Temperature Specification Setting Flag
(Sets Code to 07 when this Flag Rises)
Confirms that the signal setting on standby (200506) is ON. Provided the alarm
setting error flag (200500) is OFF, turns the temperature specification setting
flag (200015) ON, and executes the setting. After the setting, the signal setting
on standby turns OFF, the temperature specification setting flag turns OFF, and
the temperature specification setting process ends. If a setting error (200500)
occurs, the FAL instruction will be executed, and a user-defined non-fatal error
will be generated.
ON
Always ON
A 20011
ON
200506
(Word n + 5, bit 06)
20015
(Word n, bit 15)
A 50200
MOV (021)
#0700
2000
(Word n)
Always ON
Signal setting
on standby
Setting error
200500
(Word n + 5, bit 00)
FAL (006)
#0001
#0000
ON after 1
scan at startup
Starting input a
Unit 0 restart flag
200500
(Word n + 5, bit 00)
Setting error
Temperature specification
setting flag
The location in memory where data is stored. For data areas, an address
consists of a two-letter data area designation and a number that designate
the word and/or bit location. For the UM area, an address designates the in-
struction location (UM area); for the FM area, the block location (FM area),
etc.
allocation
The process by which the PC assigns certain bits or words in memory for
various functions. This includes pairing I/O bits to I/O points on Units.
AR area
A PC data area allocated to flags, control bits, and word bits.
ASCII
Short for American Standard Code for Information Interchange. ASCII is
used to code characters for output to printers and other external devices.
Backplane
A base to which Units are mounted to form a Rack. Backplanes provide a
series of connectors for these Units along with wiring to connect them to the
CPU and Power Supply. Backplanes also provide connectors used to con-
nect them to other Backplanes. In some Systems, different Backplanes are
used for different Racks; in other Systems, Racks differ only by the Units
mounted to them.
back-up
A copy of existing data which is valuable if data is accidentally erased.
BCD
Short for binary-coded decimal.
BCD calculation
An arithmetic calculation that uses numbers expressed in binary-coded deci-
mal.
binary-coded decimal
A system used to represent numbers so that each four binary bits is numeri-
cally equivalent to one decimal digit.
bit
The smallest piece of information that can be represented on a computer. A
bit has the value of either zero or one, corresponding to the electrical signals
ON and OFF. A bit is one binary digit.
bit address
The location in memory where a bit of data is stored. A bit address must
specify (sometimes by default) the data area and word that is being ad-
dressed as well as the number of the bit.
bit number
A number that indicates the location of a bit within a word. Bit 00 is the right-
most (least-significant) bit; bit 15 is the leftmost (most-significant) bit.
block instruction
A special class of instruction used within ladder-diagram programming to al-
low flowchart-like coding, which is often difficult to write with ladder diagrams.
Function codes for block instructions are indicated between pointed paren-
theses.
block program
A section of program written within a ladder diagram but based on block in-
structions. Block programs can also contain some, but not all, of the ladder-
diagram instructions.
A PC that is constructed from individual components, or“ building blocks.”
With building- block PCs, there is no one Unit that is independently identifi-
able as a PC. The PC is rather a functional assembly of components.
carry flag
A flag that is used with arithmetic operations to hold a carry from an addition
or multiplication operation, or to indicate that the result is negative in a sub-
traction operation. The carry flag is also used with certain types of shift oper-
ations.
central processing unit
A device that is capable of storing a program and data, and executing the set
of instructions contained in the program. In a PC System, the central pro-
cessing unit executes the program, processes I/O signals, communicates
with external devices, etc.
channel
See “word”
control bit
A bit in a memory area that is set either through the program or via a Pro-
gramming Device to achieve a specific purpose, e.g., a Result bit is turned
ON and OFF to restart a Unit.
counter
A PC function that counts the number of occurrences of a certain event.
CPU
An acronym for central processing unit.
CPU Backplane
A Backplane used to create a CPU Rack.
CPU Rack
Part of a Rack PC, the CPU Rack contains the CPU, a Power Supply, and
other Units.
data area
An area in the PC’s memory that is designed to hold a specific type of data,
e.g., the LR area is designed to hold common data in a PC Link System.
Memory areas that hold programs are not considered data areas.
data area boundary
The highest address available in a data area. When designating an operand
that requires multiple words, it is necessary that the highest address in the
data area is not exceeded.
default condition
The original condition of a function or system. For example, the FIT’s default
condition is to start from its hard drive, but this default condition can be
changed so that it starts from a floppy disk drive.
digit
A unit of storage in memory that consists of four bits.
DM area
A data area used to hold word data. A word in the DM area cannot be ac-
cessed bit by bit.
EEPROM
[E(lectrically) E(rasable) P(rogrammable) R(ead) O(nly) M(emory)] A type of
ROM in which stored data can be erased and reprogrammed. This is accom-
plished using a special control lead connected to the EEPROM chip and can
be done without having to remove the EEPROM chip from the device in
which it is mounted.
EPROM
[E(rasable) P(rogrammable) R(ead) O(nly) M(emory)] A type of ROM in
which stored data can be erased, by ultraviolet light or other means, and re-
programmed.
Expansion I/O Backplane
A Backplane used to create an Expansion I/O Rack.
Expansion I/O Rack
Part of a Rack PC, an Expansion I/O Rack is connected to a CPU Rack to
increase the number of slots available for mounting Units.
Expansion I/O Unit
An I/O Unit for a Package-type PC that provides more I/O points to the PC.
expansion slot
Allows FIT to be modified by addition of optional circuit cards. These circuit
cards are made by OMRON and other companies to customize systems for
particular functions.
flag
A bit that is turned ON and OFF automatically by the system in order to pro-
vide status information.
hardware error
An error originating in the hardware structure (electronic components) of the
PC, as opposed to a software error, which originates in software (i.e., pro-
grams).
hexadecimal
Number system used to represent numbers in base 16 with digits
0,1,2...9,A,B...F.
increment
Increasing a numeric value.
indirect address
An address whose contents indicates another address. The contents of the
second address will be used as the operand. Indirect addressing is possible
in the DM area only.
instruction execution time
The time required to execute an instruction. The execution time for any one
instruction can vary with the execution conditions for the instruction and the
operands used within it.
instruction line
A group of conditions that lie together on the same horizontal line of a ladder
diagram. Instruction lines can branch apart or join together to form instruction
blocks.
interface
An interface is the conceptual boundary between systems or devices and
usually involves changes in the way the communicated data is represented.
Interface devices such as NSBs perform operations like changing the coding,
format, or speed of the data.
I/O capacity
The number of inputs and outputs that a PC is able to handle. This number
ranges from around one hundred for smaller PCs to two thousand for the
largest ones.
I/O Control Unit
A Unit mounted to the CPU Rack in certain PCs to monitor and control I/O
points on Expansion I/O Units.
I/O point
The place at which an input signal enters the PC System or an output signal
leaves the PC System. In physical terms, an I/O point corresponds to termi-
nals or connector pins on a Unit; in terms of programming, an I/O point corre-
sponds to an I/O bit in the IR area.
I/O Unit
The most basic type of Unit mounted to a Backplane. I/O Units include Input
Units and Output Units, each of which is available in a range of specifica-
tions. I/O Units do not include Special I/O Units, Link Units, etc.
A word in the IR area that is allocated to a Unit in the PC System.
IR area
A data area whose principal function is to hold the status of inputs coming
into the system and that of outputs that are to be set out of the system. Bits
and words in the IR that are used this way are called I/O bits and I/O words.
The remaining bits in the IR area are work bits.
ladder diagram (program)
A form of program arising out of relay- based control systems that uses cir-
cuit- type diagrams to represent the logic flow of programming instructions.
The appearance of the program is similar to a ladder, and thus the name.
ladder diagram symbol
A symbol used in a ladder- diagram program.
ladder instruction
An instruction that represents the “rung” portion of a ladder- diagram pro-
gram. The other instructions in a ladder diagram fall along the right side of
the diagram and are called terminal instructions.
LOAD instruction
Starts the operation of a line of programming. Each new line off the bus bar
has an address number, a LD instruction, and a relay number.
LR area
A data area that is used in a PC Link System so that data can be transferred
between two or more PCs. If a PC Link System is not used, the LR area is
available for use as work bits.
Master
Short for Remote I/O Master Unit.
normal condition
A condition that produces an ON execution condition when the bit assigned
to it is ON, and an OFF execution condition when the bit assigned to it is
OFF.
OFF
The status of an input or output when a signal is said not to be present. the
OFF sate is generally represented by a low voltage or by non-conductivity,
but can be defined as the opposite of either.
OFF delay
The delay between the time when a signal is switched OFF (e.g., by an input
device or PC) and the time when the signal reaches a state readable as an
OFF signal (i.e., as no signal) by a receiving party (e.g., output device or
PC).
ON
The status of an input or output when a signal is said to be present. The ON
state is generally represented by a high voltage or by conductivity, but can be
defined as the opposite of either.
ON delay
The delay between the time when an ON signal is initiated (e.g., by an input
device or PC) and the time when the signal reaches a state readable as an
ON signal by a receiving party (e.g., output device or PC).
operating error
An error that occurs during actual PC operation as opposed to an initializa-
tion error, which occurs before actual operations can begin.
OR
A logic operation whereby the result is true if either of two premises is true, or
if both are true. In ladder-diagram programming the premises are usually ON/
OFF states of bits or the logical combination of such states called execution
conditions.
The signal sent from the PC to an external device. The term output is often
used abstractly or collectively to refer to outgoing signals.
output bit
A bit in the IR area that is allocated to hold the status to be sent to an output
device.
output signal
A signal being sent to an external device. Generally an output signal is said
to exist when, for example, a connection point goes from low to high voltage
or from a nonconductive to a conductive state.
parity
Adjustment of the number of ON bits in a word or other unit of data so that
the total is always an even number or always an odd number. Parity is gener-
ally used to check the accuracy of data after being transmitted by confirming
that the number of ON bits is still even or still odd.
PC
An acronym for Programmable Controller.
peripheral device
Devices connected to a PC System to aid in system operation. Peripheral
devices include printers, programming devices, external storage media, etc.
port
A connector on a PC or computer that serves as a connection to an external
device.
Power Supply
A Unit that mounts to a Backplane in a Rack PC. It provides power at the
voltage required by the other Units on the Rack.
present value
The current value registered in a device at any instant during its operation.
Present value is abbreviated as PV.
Programmable Controller
A small, computer-like device that can control peripheral equipment, such as
an electric door or quality control devices, based on programming and pe-
ripheral input devices. Any process that can be controlled using electrical
signals can be controlled by a PC. PCs can be used independently or net-
worked together into a system to control more complex operations.
programmed alarm
An alarm given as a result of the execution of an instruction designed to gen-
erate the alarm in the program, as opposed to one generated by the system.
programmed error
An error arising as a result of the execution of an instruction designed to gen-
erate the error in the program, as opposed to one generated by the system.
programmed message
A message generated as a result of execution of an instruction designed to
generate the message in the program, as opposed to one generated by the
system.
PROM
[P(rogrammable) R(ead) O(nly) M(emory)] A type of ROM into which the pro-
gram or data may be written after manufacture, by a customer, but which is
fixed from that time on.
PROM programmer
A PROM programmer is a device used to write data to ROM, PROM, and
EPROM storage devices.
Rack
An assembly that forms a functional unit in a Rack PC System. A Rack con-
sists of a Backplane and the Units mounted to it. These Units include the
Power Supply, CPU, and I/O Units. Racks include CPU Racks, Expansion I/O
Racks, and I/O Racks. The CPU Rack is the Rack with the CPU mounted to
it. An Expansion I/O Rack is an additional Rack that holds extra I/O Units. An
I/O Rack is used in the C2000H Duplex System, because there is no room
for any I/O Units on the CPU Rack in this System.
Rack PC
A PC that is composed of Units mounted to one or more Racks. This configu-
ration is the most flexible, and most large PCs are Rack PCs. A Rack PC is
the opposite of a Package-type PC, which has all of the basic I/O, storage,
and control functions built into a single package.
refresh
The process of updating output status sent to external devices so that it
agrees with the status of output bits held in memory and of updating input
bits in memory so that they agree with the status of inputs from external de-
vices.
reset
The process of turning a bit or signal OFF or of changing the present value of
a timer or counter to its set value or to zero.
RUN mode
The operating mode used by the PC for normal control operations.
scan
The process used to execute a ladder-diagram program. The program is ex-
amined sequentially from start to finish and each instruction is executed in
turn based on execution conditions.
scan time
The total time it takes the PC to perform internal operations, i.e., reset the
watchdog timer, read the program, receive input data, send output data, and
execute instructions. Scan time is monitored by the watchdog timer within the
PC, and if it takes longer than a certain specified amount of time, an error
message may be generated, or the CPU may just stop. Scan times will differ
depending on the configuration of the system.
sensor
An input device that “senses” a property of the real world and relays it to the
Control System. The property can be a measurement of an object, or simply
a signal indicating the presence of the object.
Slave
Short for Remote I/O Slave Unit.
Slave Rack
A rack containing a Remote I/O Slave Unit and controlled through a remote
I/O Master Unit. Slave Racks are generally located away from the CPU Rack.
Special I/O Unit
A dedicated Unit that is designed for a specific purpose. Special I/O Units
include Position Control Units, High-Speed Counters, Analog I/O Units, etc.
switch
An input device that sends either an ON or OFF signal to the Control System.
A switch can be operated either by a person or by the movement of a piece
of equipment or material.
TC area
A data area that can be used only for timers and counters. Each bit in the TC
area serves as the access point for the SV, PV, and Completion flag for the
timer or counter defined with that bit.
TC number
A definer that corresponds to a bit in the TC area and used to define the bit
as either a timer or counter.
TM area
A memory area used to store the results of a trace.
A data area used to store execution conditions so that they can be reloaded
later for use with other instructions.
UM area
The memory area used to hold the active program, i.e., the program that is
being currently executed.
Unit
In OMRON PC terminology, the word Unit is capitalized to indicate any prod-
uct sold for a PC System. Though most of the names of these products end
with the word Unit, not all do, e.g., a Remote Terminal is referred to in a col-
lective sense as a Unit. Context generally makes any limitations of this word
clear.
unit number
A number assigned to some Link Units and Special I/O Units to facilitate
identification when assigning words or other operating parameters to it.
watchdog timer
A timer within the system that ensures that the scan time stays within speci-
fied limits. When limits are reached, either warnings are given or PC opera-
tion is stopped depending on the particular limit that is reached.
word
In digital circuits, a group of bits. Usually a word consists of four, eight, or
sixteen bits. In C-series PCs, a word consists of sixteen bits. Words can be
used to store data, or they can be used for I/O.
work bit
A bit in a work word.
“I/O Unit Over” error, 12
A–C
applications, precautions, xiii
Binary Coded Decimal, 2, 4, 13, 21
cold-junction compensating resistor, 3, 8
CS1-series PCs, 37
D–H
DIP switch setting, 3, 4, 16, 18
CS1 Series, 38
Display Unit, 18, 21
error flag, 16, 18
High-Density and Multiplex I/O Unit, 21
I
input points, 3
inputs
RTD, 8
thermocouple, 8
installation, precautions, xiii
IR word numbers, 2
L–N
LEDs, 3
Master, 21
mounting, 4, 5
noise, 9
nomenclature, 2
O–P
operating environment, precautions, xiii
platinum resistance sensors, 2
precautions, xi
applications, xiii
general, xii
operating environment, xiii
safety, xii
Programmable Controller, 2, 4
R
Racks, 5
reset flag, 16
restart flag, 16
S
safety precautions. See precautions
signal wire, 9
Slave Rack, 5
Special I/O Units, 2, 5
standby flag, 16, 18
T
temperature selector, 3
temperature specification code number, 14
temperature specification setting flag, 16, 18
thermocouple, 2
Transistor Output Unit, 20, 21
U–W
unit number, 4, 12
unit number selector, 2
work bits, 13
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W124-E1-5
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version.
Revision code
Date
Revised content
1
February 1989
Original production
2
July 1989
Redundancies removed, and general cleaning of text and graphics.
3
December 1990
The C200H-TS002/102 were added.
May 1991
Reformatted.
4
September 1999
Page ix : About this Manual corrected.
Page xi: PRECAUTIONS added.
Page 9: Tightening torque changed from 0.8 kg/cm to 0.8 N � m in the dia-
gram.
Page 39: Appendix E added to provide information relating to CS1-series PCs.
5
April 2000
Front cover: “GUIDE” changed to “MANUAL.”
Page 9: Information on reducing noise added.