Remote Controller (Wireless Type)
Control Systems
47
2
2.3
BRC7F634F / BRC7F635F (For FXFQ-P)
2.3.1
Features
BRC7F634F (for Heat Pump)
BRC7F635F (for Cooling Only)
� The same operation modes and settings as with wired remote controllers are possible.
� A light receiver unit for a Ceiling Mounted Cassette (Round Flow) type is mounted into the indoor unit.
� This unit supports the three-speed airflow rate control (HH / H / L).
2.3.2
Function
Signal receiver unit
(Installed type)
Signal receiver unit can
be installed on the panel
Model
BRC7F634F/635F
ON/OFF
Possible
Temp. setting
Possible
Air flow rate setting
Possible
Air flow direction setting
Possible
Timer setting
Possible
Mode setting
Possible
Filter sign reset
Possible
Inspection/Test operation
Possible
2.2 BRC7E61W / BRC7E65 / 2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
48
Control Systems
2.3.3
Dimensions
• REMOTE CONTROLLER HOLDER
INSTALLATION PROCEDURE
LIQUID CRYSTAL
REMOTE CONTROLLER
TRANSMITTING PART
DRAIN PIPING
SIDE
• RECEIVER INSTALLATION PROCEDURE
REFRIGERANT
PIPING SIDE
• RECEIVER DETAIL
• WIRELESS REMOTE CONTROLLER KIT FOR EACH DECORATION PANEL
• REMOTE CONTROLLER DIMENSIONS
RECEIVER
DECORATION PANEL
62
157
17.5
BYCP125K-W1
DECORATION PANEL
WIRELESS REMOTE
CONTROLLER KIT
HOLDER
REMOTE CONTROLLER
(WIRELESS)
3D052918B
BRC7F632F BRC7F634F BRC7F635F
Remote Controller (Wireless Type)
Control Systems
49
2
2.3.4
Operation Manual
� Names and Functions of the Operating Section
1
1-3
2
1-1
1-2
8
10
13
11
12
15
14
16
17
9
1
3
4
6
2
5
7
DOWN
FAN
UP
ON
OFF
M
H
L
C
hr.
hr.
TEST
MODE
TIMER
RESERVE CANCEL
DOWN
UP
TEST
SWING
FAN
TIME
TEMP
ON
OFF
M
H
L
C
hr.
hr.
TEST
24
25
COOL/HEAT CHANGEOVER
REMOTE CONTROL SWITCH
19
23
22
18
20
21
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
50
Control Systems
See Fig. 1, 2
1
DISPLAY “
” (SIGNAL TRANSMISSION)
This lights up when a signal is being transmitted.
2
DISPLAY “
” “
” “
” “
” “
” (OPERATION MODE)
This display shows the current OPERATION MODE. For cooling only type, “
” (Auto)
and “
” (Heating) are not installed.
3
DISPLAY “
” (SET TEMPERATURE)
This display shows the set temperature.
4
DISPLAY “
” (PROGRAMMED TIME)
This display shows PROGRAMMED TIME of the system start or stop.
5
DISPLAY “
” (AIR FLOW FLAP)
Refer to page 56.
6
DISPLAY “
” “
” “
” (FAN SPEED)
The display shows the set fan speed.
7
DISPLAY “
” (INSPECTION/ TEST OPERATION)
When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the
system mode is in.
8
ON/OFF BUTTON
Press the button and the system will start. Press the button again and the system will stop.
9
FAN SPEED CONTROL BUTTON
Press this button to select the fan speed, HH, H, L of your choice.
10
TEMPERATURE SETTING BUTTON
Use this button for SETTING TEMPERATURE
(Operates with the front cover of the remote controller closed.)
11
PROGRAMMING TIMER BUTTON
Use this button for programming “START and/or STOP” time.
(Operates with the front cover of the remote controller opened.)
12
TIMER MODE START/STOP BUTTON
Refer to page 57.
13
TIMER RESERVE/CANCEL BUTTON
Refer to page 57.
14
AIR FLOW DIRECTION ADJUST BUTTON
Refer to page 56.
15
OPERATION MODE SELECTOR BUTTON
Press this button to select OPERATION MODE.
16
FILTER SIGN RESET BUTTON
Refer to the section of MAINTENANCE in the operation manual attached to the indoor unit.
17
INSPECTION/TEST OPERATION BUTTON
This button is used only by qualified service persons for maintenance purposes.
18
EMERGENCY OPERATION SWITCH
This switch is readily used if the remote controller does not work.
19
RECEIVER
This receives the signals from the remote controller.
20
OPERATING INDICATOR LAMP (Red)
This lamp stays lit while the air conditioner runs. It flashes when the unit is in trouble.
21
TIMER INDICATOR LAMP (Green)
This lamp stays lit while the timer is set.
22
AIR FILTER CLEANING TIME INDICATOR LAMP (Red)
Lights up when it is time to clean the air filter.
23
DEFROST LAMP (Orange)
Lights up when the defrosting operation has started.
(For cooling only type this lamp does not turn on.)
M
H
L
C
hr.
hr.
TEST
Remote Controller (Wireless Type)
Control Systems
51
2
NOTES
� For the sake of explanation, all indications are shown on the display in Figure 1 contrary to actual
running situations.
� Fig. 1-2 shows the remote controller with the front cover opened.
� Fig. 1-3 shows this remote controller can be used in conjunction with the one provided with the VRV
system.
� If the air filter cleaning time indicator lamp lights up, clean the air filter as explained in the operation
manual provided with the indoor unit.
After cleaning and reinstalling the air filter, press the filter sign reset button on the remote controller. The
air filter cleaning time indicator lamp on the receiver will go out.
� The Defrost Lamp will flash when the power is turned on. This is not a malfunction.
� Handling for Wireless Remote Controller
Precautions in handling remote controller
Direct the transmitting part of the remote controller to the receiving part of the air conditioner.
If something blocks the transmitting and receiving path of the indoor unit and the remote controller as
curtains, it will not operate.
Transmitting distance is approximately 7 m.
Do not drop or get it wet.
It may be damaged.
Never press the button of the remote controller with a hard, pointed object.
The remote controller may be damaged.
Installation site
� It is possible that signals will not be received in rooms that have electronic fluorescent lighting. Please
consult with the salesman before buying new fluorescent lights.
� If the remote controller operated some other electrical apparatus, move that machine away or consult
your dealer.
24
FAN/AIR CONDITIONING SELECTOR SWITCH
Set the switch to “
” (FAN) for FAN and “
” (A/C) for HEAT or COOL.
25
COOL/HEAT CHANGEOVER SWITCH
Set the switch to “
” (COOL) for COOL and “
” (HEAT) for HEAT.
2 short beeps
from the receiver
indicates that the
transmission is
properly done.
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
52
Control Systems
Placing the remote controller in the remote controller holder
Install the remote controller holder to a wall or a pillar with the attached screw. (Make sure it transmits)
How to put the dry batteries
(1) Remove the back cover of the remote controller to the direction pointed by the
arrow mark.
(2) Put the batteries
Use two LR03 dry cell batteries.
Put dry batteries correctly to fit their (+) and (–).
(3) Close the cover
When to change batteries
Under normal use, batteries last about a year. However, change them whenever the indoor unit doesn’t
respond or responds slowly to commands, or if the display becomes dark.
[CAUTIONS]
� Replace all batteries at the same time, do not use new and old batteries intermixed.
� In case the remote controller is not used for a long time take out all batteries in order to prevent liquid
leak of the battery.
IN THE CASE OF CENTRALIZED CONTROL SYSTEM
If the indoor unit is under centralized control, it is necessary to switch the remote controller’s setting.
In this case, contact your DAIKIN dealer.
Placing the remote
controller
Slide from above
Remote
controller
holder
Removing the
remote controller
Pull it upward
Remote Controller (Wireless Type)
Control Systems
53
2
� Operation Range
Split System
If the temperature or the humidity is beyond the following conditions, safety devices may work and the air
conditioner may not operate, or sometimes, water may drop from the indoor unit.
COOLING
[°C]
HEATING
[°C]
DB : Dry bulb temperature
WB: Wet bulb temperature
The setting temperature range of the remote controller is 16°C to 32°C.
VRV System
See the operation manual provided with the air conditioner.
� Operation Procedure
Refer to figure 1 on page 49
� Operating procedure varies with heat pump type and cooling only type. Contact your Daikin dealer to
confirm your system type.
� To protect the unit, turn on the main power switch 6 hours before operation.
� If the main power supply is turned off during operation, operation will restart automatically after the
power turns back on again.
COOLING, HEATING, AUTOMATIC, FAN, AND PROGRAM DRY OPERATION
Operate in the following order.
� AUTOMATIC OPERATION can be selected only by Heat pump split system or Heat recovery VRV
system.
� For cooling only type, “COOLING”, and “FAN” and “DRY”operation are able to select.
(1) For Systems Without Cool / Heat Changeover Remote Control Switch
Refer to figure 1-1, 2 on page 49
OPERATION MODE SELECTOR
Press OPERATION MODE SELECTOR button several times and select the OPERATION MODE of
your choice as follows.
� COOLING OPERATION...................................................“
”
� HEATING OPERATION....................................................“
”
� AUTOMATIC OPERATION ..............................................“
”
� In this operation mode, COOL/HEAT changeover is automatically conducted.
� FAN OPERATION ............................................................“
”
� DRY OPERATION............................................................“
”
� The function of this program is to decrease the humidity in your room with the minimum temperature
decrease.
� The set point is the air temperature when starting operation by dry operation.
� Micro computer automatically determines TEMPERATURE and FAN SPEED.
� This system does not go into operation if the room temperature is below 16°C.
INDOOR
OUTDOOR
TEMPERATURE
TEMPERATURE
HUMIDITY
DB
21 to 35
80% or
below
DB
– 5 to 50
WB
14 to 25
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
DB
15 to 27
DB
– 14 to 21
WB
– 15 to 15.5
1
MODE
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
54
Control Systems
ON/OFF
Press ON/OFF button.
OPERATION lamp lights up or goes off and the system starts or stops OPERATION.
NOTE
� Do not turn OFF power immediately after the unit stops. Then, wait no less than 5 minutes.
Water is leaking or there is something else wrong with the unit.
(2) For Systems with Cool/Heat Changeover Remote Control Switch
Refer to figure 1-1,3 on page 49
OPERATION MODE SELECTOR
(1) Select OPERATION MODE with the COOL/HEAT CHANGEOVER REMOTE CONTROL SWITCH as
follows.
� COOLING OPERATION...................................................“
”
� HEATING OPERATION....................................................“
”
� FAN OPERATION ............................................................“
”
� DRY OPERATION............................................................“
”
� See “FOR SYSTEM WITHOUT COOL/HEAT CHANGEOVER REMOTE CONTROL SWITCH” for
details on dry operation.
(2) Press OPERATION MODE SELECTOR button several times and select “
”.
(This operation is only available during dry operation.)
ON/OFF
Press ON/OFF button.
OPERATION lamp lights up or goes off and the system starts or stops OPERATION.
� The fan may keep on running for about 1 minute after the heating operation stops for removing the heat
in the indoor unit.
� The air flow rate may be adjusted automatically depending on the room temperature or the fan may stop
immediately. This is not a malfunction.
NOTE
� Do not turn OFF power immediately after the unit stops. Then, wait no less than 5 minutes.
Water is leaking or there is something else wrong with the unit.
[EXPLANATION OF HEATING OPERATION]
� For general heating operation, it may take longer to reach the set temperature than in cooling operation.
We recommend starting the operation which was used before using timer operation.
DEFROST OPERATION
� As the frost on the coil of an outdoor unit increase, heating effect decreases and the system goes into
DEFROST OPERATION.
� The fan operation stops and the DEFROST lamp of the indoor unit goes on.
After 6 to 8 minutes (maximum 10 minutes) of DEFROST OPERATION, the system returns to
HEATING OPERATION.
2
ON
OFF
1
2
ON
OFF
Remote Controller (Wireless Type)
Control Systems
55
2
Heating capacity & Outdoor air temperature
� Heating capacity drops as outdoor air temperature lowers. If feeling cold, use another heater at the
same time as this air conditioner.
� Hot air is circulated to warm the room. It will take some time from when the air conditioner is first started
until the entire room becomes warm. The internal fan automatically turns at low speed until the air
conditioner reaches a certain temperature on the inside. In this situation, all you can do is wait.
� If hot air accumulates on the ceiling and feet are left feeling cold, it is recommended to use a circulator.
For details, contact the place of purchase.
(3) Adjustment
For programming TEMPERATURE, FAN SPEED and AIR FLOW DIRECTION, follow the procedure shown
below.
TEMPERATURE SETTING
Press TEMPERATURE SETTING button and program the setting temperature.
Each time this button is pressed, setting temperature rises 1°C.
Each time this button is pressed, setting temperature lowers 1°C.
In case of automatic operation
Each time this button is pressed, setting temperature shifts to “H” side.
Each time this button is pressed, setting temperature shifts to “L” side.
[°C]
� The setting is impossible for fan operation.
NOTE
� The setting temperature range of the remote controller is 16°C to 32°C.
FAN SPEED CONTROL
Press FAN SPEED CONTROL button.
Fan speed (HH, H, L) can be selected.
The microchip may sometimes control the fan speed in order to protect the unit.
DOWN
UP
H
•
M
•
L
Setting
temperature
25
23
22
21
19
DOWN
UP
DOWN
UP
FAN
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
56
Control Systems
AIR FLOW DIRECTION ADJUST
UP AND DOWN DIRECTION
� The movable limit of the flap is changeable. Contact your Daikin dealer for details.
Press the AIR FLOW DIRECTION ADJUST button to select the air direction as shown below.
DISPLAY appears and the air flow direction continuously varies. (Automatic swing
setting)
Press AIR FLOW DIRECTION ADJUST button to select the air direction of your choice.
DISPLAY vanishes the air flow direction is fixed (Fixed air flow direction setting).
MOVEMENT OF THE AIR FLOW FLAP
For the following conditions, micro computer controls the air flow direction so it may be different from the
display.
NOTES
� If you try cooling or programmed drying, while the flaps are facing downward, air flow direction may
change unexpectedly. There is nothing wrong with the equipment. This serves to prevent dew formed
on parts in the air discharge outlet from dripping.
� Operation mode includes automatic operation.
(4) Program Timer Operation
Operate in the following order.
� The timer is operated in the following two ways.
Programming the stop time (
)
.... The system stops
operating after the set time has elapsed.
Programming the start time (
)
.... The system starts
operating after the set time has elapsed.
� The timer can be programmed a maximum of 72 hours.
� The start and the stop time can be simultaneously programmed.
SWING
Operation mode
Cooling
Heating
Operation conditions
� When operating continuously at
horizontal air flow direction
� When room temperature is higher
than the set temperature
� At defrost operation
(The flaps blow horizontally to
avoid blowing cold air directly on
the occupants of the room.)
Up and down adjustment
Remote Controller (Wireless Type)
Control Systems
57
2
TIMER MODE START/STOP
Press the TIMER MODE START/STOP button several times and select the mode on the display.
The display flashes.
For setting the timer stop .... “
”
For setting the timer start .... “
”
PROGRAMMING TIME
Press the PROGRAMMING TIME button and set the time for stopping or starting the system.
When this button is pressed, the time advances by 1 hour.
When this button is pressed, the time goes backward by 1 hour.
TIMER RESERVE
Press the TIMER RESERVE button.
The timer setting procedure ends.
The display or changes from flashing light to a constant light.
TIMER CANCEL
Press the TIMER OFF button to cancel programming. The display vanishes.
For example.
When the timer is programmed to stop the system after 3 hours and start the system after 4 hours, the
system will stop after 3 hours and then 1 hour later the system will start.
NOTES
� When the timer is programmed to stop the system after 3 hours and start the system after 4 hours, the
system will stop after 3 hours and then 1 hour later the system will start.
� After the timer is programmed, the display shows the remaining time.
1
TIMER
2
DOWN
UP
DOWN
UP
3
RESERVE
4
CANCEL
MODE
TIMER
RESERVE CANCEL
DOWN
UP
FAN
TIME
TEMP
ON
OFF
C
hr.
hr.
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
58
Control Systems
(5) How to Set Master Remote Controller (For VRV System)
� When the system is installed as shown below, it is necessary to designate the master remote controller.
� For Heat pump system
When one outdoor unit is connected with several indoor units.
� For Heat recovery system
When one BS unit is connected with several indoor units.
� Only the master remote controller can select HEATING, COOLING or AUTOMATIC (only Heat recovery
system) OPERATION.
When the indoor unit with master remote controller is set to “COOL”, you can switch over operation
mode between “FAN”, “DRY” and “COOL”.
When the indoor unit with master remote controller is set to “HEAT”, you can switch over operation
mode between “FAN” and “HEAT”.
When the indoor unit with master remote controller is set to “FAN”, you cannot switch operation mode.
When attempting settings than that consented above, a “peep” is emitted as a warning.
Only with Heat recovery system, you can set the indoor unit to AUTOMATIC. Attempting to do so, a
“peep” will be emitted as a warning.
How to designate the master remote controller
Operate in the following order.
One of these remote controllers needs
to be designated as the master remote
controller.
Outdoor unit
Indoor unit
One of these remote controllers needs
to be designated as the master remote
controller.
Outdoor unit
Indoor unit
BS unit
Remote Controller (Wireless Type)
Control Systems
59
2
Continuously press the OPERATION MODE SELECTOR button for 4 seconds.
The displays showing “
” of all slave indoor unit connected to the same outdoor unit or BS unit flash.
Press the OPERATION MODE SELECTOR button to the indoor unit that you wish to designate as
the master remote controller. Then designation is completed. This indoor unit is designated as the
master remote controller and the display showing “
” vanishes.
� To change settings, repeat steps 1 and 2 .
(6) Emergency Operation
When the remote controller does not work due to battery failure or the absence thereof, use this switch
which is located beside the discharge grille on the main unit. When the remote controller does not work, but
the battery low indicator on it is not lit, contact your dealer.
[START]
To press the emergency operation switch.
The machine runs in the previous mode.
The system operates with the previously set air flow direction.
[STOP]
Press the EMERGENCY OPERATION switch again.
(7) Precautions for Group Control System or Two Remote Controller Control System
This system provides two other control systems beside individual control (one remote controller controls
one indoor unit) system. Confirm the following if your unit is of the following control system type.
� Group control system
One remote controller controls up to 16 indoor units.
All indoor units are equally set.
� Two remote controller control system
Two remote controllers control one indoor unit. (In case of group control system, one group of indoor
units)
The unit follows individual operation.
NOTES
� Cannot have two remote controller control system with only wireless remote controllers. (It will be a two
remote controller control system having one wired and one wireless remote controllers.)
� Under two remote controller control system, wireless remote controller cannot control timer operation.
� Only the operating indicator lamp out of 3 other lamps on the indoor unit display functions.
1
MODE
2
MODE
1
1 2
2
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
60
Control Systems
NOTE
� Contact your Daikin dealer in case of changing the combination or setting of group control and two
remote controller control systems.
� Not Malfunction of the Air Conditioner
The following symptoms do not indicate air conditioner malfunction
I.
THE SYSTEM DOES NOT OPERATE
� The system does not restart immediately after the ON/OFF button is pressed.
If the OPERATION lamp lights, the system is in normal condition. It does not restart immediately
because a safety device operates to prevent overload of the system. After 3 minutes, the system will
turn on again automatically.
� The system does not restart immediately when TEMPERATURE SETTING button is returned to
the former position after pushing the button.
It does not restart immediately because a safety device operates to prevent overload of the system.
After 3 minutes, the system will turn on again automatically.
� If the reception beep is rapidly repeated 3 times (It sounds only twice when operating normally.)
Control is set to the optional controller for centralized control.
� If the defrost lamp on the indoor unit’s display is lit when heating is started.
This indication is to warn against cold air being blown from the unit. There is nothing wrong with the
equipment.
II. THE UNIT STOPS ONCE IN A WHILE
� The remote controller indicates “U4” and “U5”, the unit stops. Within several minutes the unit
restarts.
Due to electrical noise other than that from the air conditioner, the communication between the units is
cut off and the unit stops.
When the noise is gone, the unit automatically restarts.
III. NO CHANGEOVER IS AVAILABLE BETWEEN HEATING AND COOLING MODES
� The indoor unit makes a “PEEE” receiving sound.
When operation changeover is under control, the control is set to the mode that cannot be carried out.
IV. AIR FLOW RATE CANNOT BE OBTAINED AS SET
� Even if the air flow rate adjusting button is pressed, the air flow rate does not change.
When the room temperature reaches the indoor unit set temperature, the outdoor unit stops and the air
flow rate of indoor unit drops to the minimum.
This is to avoid the cold air from getting in contact with the people in the room.
V. AIR DISCHARGE DIRECTION IS NOT AS SET
� The remote controller indication and the air discharge direction is not the same.
Air discharge direction swing is impossible.
Because it is controlled by microcomputer. Refer to “AIR FLOW DIRECTION ADJUST” on page 56.
VI. ONLY A PART OF INDICATION SHOWS
� Even if the unit is operated, only the operation indication shows, or even if the indication shows,
soon after, the indication other than that for operation disappears.
The corresponding indoor unit is that for multi-system and the remote controller is set to the multi-
system.
VII.NO INDICATION SHOWS OR ALL INDICATION SHOW
� When the remote controller button is pressed.
The battery is dead.
VIII.INSUFFICIENT COOLING
� It is in program dry operation.
The program dry operation is an operation mode trying to keep the room temperature constant as much
as possible. Refer to “Cooling, Heating, Automatic, Fan and Program dry operation” on page 53.
� How to Diagnose Trouble Spots
I.
EMERGENCY STOP
Remote Controller (Wireless Type)
Control Systems
61
2
When the air conditioner stops in emergency, the run lamp on the indoor unit starts blinking. Take the
following steps yourself to read the malfunction code that appears on the display. Contact your dealer with
this code. It will help pinpoint the cause of the trouble, speeding up the repair.
Press the INSPECTION/TEST button to select the inspection mode “0”.
“0” appears on display and blinks. “UNIT” lights up.
Press PROGRAMMING TIMER BUTTON and change the unit number.
Press to change the unit number until the indoor unit beeps and perform the following operation according
to the number of beeps.
Number of beeps
3 short beeps .........................Perform all steps from 3 to 6 .
1 short beep...........................Perform 3 and 6 steps
1 long beep ............................Normal state
Press OPERATION MODE SELECTOR BUTTON.
“0” on the left-hand of the malfunction code blinks.
Press PROGRAMMING TIMER BUTTON and change the malfunction code.
Press until the indoor unit beeps twice.
Press OPERATION MODE SELECTOR BUTTON.
“0” on the right-hand of the malfunction code blinks.
Press PROGRAMMING TIMER BUTTON and change the malfunction code.
Press until the indoor unit makes a long beep.
The malfunction code is fixed when the indoor unit makes a long beep.
1
TEST
2
DOWN
UP
MODE
3
4
DOWN
UP
5
MODE
6
DOWN
UP
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
62
Control Systems
Reset of the display
Press OPERATION MODE SELECTOR BUTTON to get the display back to the normal state.
II. IN CASE BESIDES EMERGENCY STOP
1. The unit does not operate at all.
� Check if the receiver is exposed of sunlight or strong light. Keep receiver away from light.
� Check if there are batteries in the remote controller. Place the batteries.
� Check if the indoor unit number and wireless remote controller number are equal.
Operate the indoor unit with the remote controller of the same number.
Signal transmitted from a remote controller of a different number cannot be accepted. (If the number is not
mentioned, it is considered as “1”)
2. The system operates but it does not sufficiently cool or heat.
� If the set temperature is not proper.
� If the FAN SPEED is set to LOW SPEED.
� If the air flow angle is not proper.
Contact the place of purchase in the following case.
WARNING
When you detect a burning odor, shut OFF power immediately and contact the place of purchase. Using
the equipment in anything but proper working condition can result in equipment damage, electric shock
and/or fire.
7
MODE
UNIT NO.
CODE
MODE
TIMER
RESERVE CANCEL
DOWN
UP
/TEST
SWING
FAN
TIME
TEMP
1
2 4
6
3 5
7
ON
OFF
2 4
6
Number
Number
1
Remote Controller (Wireless Type)
Control Systems
63
2
[Trouble]
The RUN lamp of the indoor unit is flashing and the unit does not work at all.
[Remedial action]
Check the malfunction code (A1 - UF) on the remote control and contact the place of purchase. (See page
60.)
MODE
TIMER
RESERVE CANCEL
DOWN
UP
/TEST
SWING
FAN
TIME
TEMP
ON
OFF
UNIT NO.
CODE
Malfunction Code
Unit No. which
sensed trouble
INSPECTION
display
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
64
Control Systems
2.3.5
Installation
� Safety Precautions
Please read these “SAFETY PRECAUTIONS” carefully before installing air conditioning unit and be sure to
install it correctly.
After completing installation, conduct a trial operation to check for faults and explain to the customer how to
operate the air conditioner and take care of it with the aid of the operation manual. Ask the customer to
store the installation manual along with the operation manual for future reference.
Meaning of CAUTION notices
CAUTION
Failure to observe these instructions properly may result in property damage or personal injury, which may
be serious depending on the circumstances.
CAUTION
� Refer also to the installation manual attached to the indoor unit and the installation manual attached to
the decoration panel.
� Confirm that following conditions are satisfied prior to installation.
� Ensure that noting interrupts the operation of the wireless remote controller. (Ensure that there is
neither a source of light nor fluorescent lamp near the receiver. Also, ensure that the receiver is not
exposed of direct sun light.)
� Ensure that the operaiton display lamp and other indicators are easy to see.
� The installation position of this kit is 1 position of the decoration panel. Therefore, confirm that its
position is set so that the single form the wireless remote controller can be easily transmitted and its
display can be easily seen.
� If both this kit and fresh air intake kit are installed, only one duct chamber shall be used. Refer to the
installation manual of the fresh air intake kit (optional hand book).
� Before Installation
(1) Accessories
Check if the following accessories are included with your unit.
(2) Note to the Installer
� Be sure to instruct the customer how to properly operate the system showing him/her the attached
operation manual.
Name
Receiver
Wireless remote
controller
Transmission
Remote controller
holder
Screw for installing
transmission
Screw for installing
remote controller
holder
Quantity
1 set
1 pc.
1 set
1 pc.
2 pcs.
2 pcs.
Shape
Name
Clamp
Dry cell battery
LR03 (AM4)
Unit No. label
Field setting label
Operation manual
Installation manual
Quantity
1 pc.
2 pcs.
1 pc.
1 pc.
1 pc.
1 pc.
Shape
Remote Controller (Wireless Type)
Control Systems
65
2
� Remote Controller Installation
NOTES
� Do not throw the remote controller or impose large shocks. Also, do not store where it may be exposed
to moisture or direct sunlight.
� When operating, point the transmitting part of the remote controller in the direction of the receiver.
� The direct transmitting distance of the remote controller is approximately 7 meters.
� The signal cannot be transmitted if something such as curtains blocks the receiver and the remote
controller.
� When attaching in a wall or a pillar
1. Fix the remote controller holder with the screws.
2. Slide the remote controller into the remote controller holder from
the top.
� How to insert the batteries
1. Open the back cover of the remote controller by sliding it in the
direction of the arrow.
2. Insert the attached dry cell batteries. Properly insert, set the
batteries by matching the (+) and (–) polarity marks as
indicated. Then close the cover as before.
� Address Set Up
Determination of address and MAIN/SUB remote controller.
If setting multiple wireless remote controllers to operate in one room, perform address setting for the
receiver and the wireless remote controller.
If setting multiple wired remote controllers in one room, change the MAIN/SUB switch of the receiver.
SETTING PROCEDURE
(1) Setting the receiver
Set the wireless address switch (SS2) on the printed circuit board according to the table below.
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller should
be set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the receiver to SUB.
Unit No.
No. 1
No. 2
No. 3
Wireless address
switch (SS2)
MAIN
SUB
MAIN/SUB switch
(SS1)
1 2 3
1 2 3
1 2 3
S
M
S
M
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
66
Control Systems
(2) Setting the address of wireless remote controller (It is factory set to “ 1 ” )
〈Setting from the remote controller〉
1. Hold down the
button and the
button for at least 4 seconds to get the Field Set
mode.
(Indicated in the display area in the figure at right.)
2. Press the
button and select a multiple
setting (A/b). Each time the button is pressed the
display switches between “A” and “b”.
3. Press the “
” button or “
” button to set the
address.
Address can be set from 1 to 6, but set it to 1 ~ 3
and to same address as the receiver. (The receiver
does not work with address 4 ~ 6.)
4. Press the
button to enter the setting.
5. Hold down the
button for at least 1
second to quit the Field Set mode and return to the
normal display.
Multiple settings A/b
When the indoor unit is being operating by outside control (central remote controller, etc.), it sometimes
does not respond to ON/OFF and temperature setting commands from this remote controller. Check what
setting the customer wants and make the multiple setting as shown below.
(3) Stick the Unit No. label on
the air outlet of the
decoration panel and the
back of the wireless remote
controller.
[PRECAUTIONS]
Set the Unit No. of the receiver
and the wireless remote controller
to be equal. If the settings differ,
the signal from the remote
controller cannot be transmitted.
Remote controller
Movement when the operation is controlled by the other
air conditioners and equipment
Multiple setting
Remote controller display
A: Standard
All items displayed.
When operation changeover, temperature setting or the
like is carried out from the remote controller, the indoor
unit rejects the instruction.
(Signal receiving sound “peeh” or “pick-pick-pick”)
As a result, a discrepancy between the operation state of
the indoor unit and the indication of the remote controller
display occurs.
b: Multi System
Operations remain displayed
shortly after execution.
Since the indication of the remote controller is turned off,
no discrepancy such as mentioned above occurs.
MODE
TIMER
RESERVE CANCEL
DOWN
UP
/TEST
SWING
FAN
TIME
TEMP
ON
OFF
SETTING
3
2
4
1
5
Mode
Address
Multiple
setting
/TEST
FAN
UP
DOWN
1
2
3
4
5
6
RESERVE
/TEST
Unit No. label
Remote Controller (Wireless Type)
Control Systems
67
2
� Installation of the Transmission
1. Remove the lid of the terminal box as described in the Installation Manual supplied with the indoor unit.
2. Fix the transmission at the bottom of the bell mouths on the indoor unit body using provided
transmission fixing screws as shown below.
3. Connect the wire harness (shorter one) from the transmission to X24A connector on the printed circuit
board in the indoor unit. Bring out the wire harness (longer one) from the transmission to outside of the
unit through the field wiring pathway (low voltage side) of the indoor unit.
4. Fix two wire harnesses from the transmission using provided clamps.
� Installation of the Decoration Panel
Install the decoration panel as described in the Installation Manual supplied with the decoration panel.
NOTE
� Watch that the wire harness (longer one) from the transmission is not caught between the indoor unit
and the decoration panel, and ceiling and the decoration panel.
1. Remove the lid of the
terminal box by sliding
in the direction of the
arrow (two screws).
2. Fix the transmission (two screws).
(Be aware of the direction of
bringing out the wire harness.)
Bell mouth
Transmission
Terminal box lid
4. Fix to the wires of the
indoor unit using
provided clamps.
X24A connector
(color: black)
Hitch to a tab
Wire harness
(shorter one)
Transmission
3. Field wiring pathway
(low voltage side)
Wire harness
(longer one)
Outside
the unit
2.3 BRC7F634F / BRC7F635F
Remote Controller (Wireless Type)
OH08-1
68
Control Systems
� Installation of the Receiver
1. Remove the corner decoration lid of the decoration panel, locating at the opposing corner of the drain
piping section. The lid will be no longer in use.
2. Remove a backside cover of the receiver.
3. Connect the wire harness (longer one) from the transmission to the connector of the printed circuit
board of the receiver.
4. Attach the backside cover of the receiver in reverse procedure to 2.
5. Install the receiver to the decoration panel.
� Field Setting
If optional accessories are mounted on the indoor
unit, the indoor unit setting may have to be
changed. Refer to the instruction manual (optional
hand book) for each optional accessory.
Procedure
1. When in the normal mode, press the
button for a minimum of four
seconds, and the FIELD SET MODE is
entered.
2. Select the desired MODE NO. with the
button.
3. Push the “
” button and select the FIRST
CODE NO.
4. Push the “
” button and select the
SECOND CODE NO.
5. Push the
button and the present
settings are SET.
6. Push the
button to return to the
NORMAL MODE.
Be sure to install the receiver to this corner.
1
2
3
4
5
Remove the corner
decoration lid.
Drain piping
section
Receiver
Remove the
fixing screw (one). Cover
Connector
(backside of
the board)
Wire harness
(longer one)
Clamp for the wire
harness shall be inside
the wall.
Connector
(backside of
the board)
Receiver
Hook the tab of
the cover to a hole
of the receiver
Cover
Tab
Receiver
Install to the
decoration
panel.
DOWN
FAN
UP
MODE
TIMER
RESERVE CANCEL
/TEST
SWING
ON
OFF
SETTING
TIME
TEMP
3
2
5
4
1, 6
MODE NO.
FIELD SET MODE
FIRST CODE NO.
SECOND CODE NO.
/TEST
MODE
UP
DOWN
RESERVE
/TEST
Remote Controller (Wireless Type)
Control Systems
69
2
(Example)
If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “10”, FIRST CODE NO.
to “0”, and SECOND CODE NO. to “02”.
NOTE
� The SECOND CODE NO. is factory set to “01”. However, for the following cases it is set to “02”.
� Air Flow Direction Range Setting
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)
� Test Operation
� Perform test operation according to the instructions in the installation manual attached to the indoor
unit.
� After refrigerant piping, drain piping, and electric wiring, operate according to the table to protect the
unit.
[PRECAUTIONS]
1. Refer to malfunction diagnosis in the installation manual attached to the indoor unit for split types.
2. Refer to malfunction diagnosis in the installation manual attached to the outdoor unit for VRV system
types.
MODE
NO.
FIRST
CODE
NO.
DESCRIPTION OF SETTING
SECOND CODE NO. NOTE)
01
02
03
10
0
Filter Contamination-
Heavy/Light (Setting for
spacing time of display
time to clean air filter)
(Setting for when filter
contamination is heavy,
and spacing time of
display time to clean air
filter is to be halved)
Ultra-long-
life type
light
approx.
10,000
hours
heavy
approx.
5,000 hours
-
Long-life
type
approx.
2,500 hours
approx.
1,250 hours
Standard
type
approx.
200 hours
approx.
100 hours
1
Long-life filter type (Setting of filter
sign indication time)
(Change setting when Ultra-long-life
filter is installed)
Long-life filter
Ultra-long-life filter
-
3
Spacing time of display time to clean
air filter count
(Setting for when the filter sign is not
to be displayed)
Display
Do not display
-
13
0
High ceiling setting (Setting for when
installed in a ceiling higher than 2.7 m)
Normal
High Ceiling 1
High
Ceiling 2
1
Selection of Air Flow Direction
(Setting for when a blocking pad kit
has been installed)
F
T
W
4
Air Flow Direction Range Setting
Upper
Normal
-
Order
Operation
(1)
Open gas side stop valve.
(2)
Open liquid side stop valve.
(3)
Electrify crank case heater for 6 hours. (Not necessary for cooling type units)
(4)
Set to cooling with the remote controller and push
button to start operation.
(5)
Push
button twice and operate in TEST OPERATION.
(6)
Push
button and confirm its operation.
(7)
Push
button and operate normally.
(8)
Confirm its function according to the operation manual.
ON/OFF
/TEST
SWING
/TEST
2.3 BRC7F634F / BRC7F635F