echoflex Elaho Configuration Manual
Read Online
Read the echoflex Elaho Configuration Manual online using the built-in PDF viewer.
Text of the manual
Part Number: 8186M1230-2.0.0 Rev A
Released: 2018-09
all-guide
s.com
® and Inspire
® are registered trademarks of Electronic Theatre
Controls, Inc. in the United States and other countries.
All other trademarks, both marked and not marked, are the
property of their respective owners. Echoflex intends this
document, whether printed or electronic, to be provided in its
entirety.
Table of Contents
Elaho Astronomical TimeClock
i
Overview
1
Features
1
Warnings and Notice Conventions
2
Help from Technical Services
3
Specification
4
Ambient Environment
4
Compliance
4
Electrical Requirements
4
Mounting Requirements
6
Elaho Control System
7
E-ATC installed in an Elaho Room Controller 7
E-ATC with External 24 VDC Auxiliary
Power
7
E-ATC with Elaho Station Power Module
with Aux Power
8
Installation and Setup
9
Connect Wiring
9
Install the E-ATC into the Back Box
11
Install the Faceplate
12
User Interface Overview
13
Keypad
13
Display
13
Status Display
13
Menu
13
Hold
14
Auto Timed Hold
16
Schedule an Event
17
Open/Close Settings
18
Timeclock Settings
19
Change Current Time
19
Change Time Style
19
Change Current Date
20
Configure Hold Time
20
Set Flick Warn
20
Set Warn Time
21
Set Time Zone
21
Set Latitude and Longitude
21
Set Daylight Saving Time
22
Set Manual DST Dates
22
Presets
23
Activate a Preset
23
Record a Preset
24
Deactivate
24
Holiday Shut-Off
25
Configuration of Holiday Spaces
25
Change default Shut-Off Time duration
26
Menu Flow Chart
27
ii
Elaho Astronomical TimeClock
Welcome to the Elaho Astronomical TimeClock (E-ATC) Installation
and Configuration Manual. This guide contains the procedures for
successful programming of the E-ATC when used as part of an Elaho
control system.
The E-ATC provides Elaho power control systems with low-cost, easy-
to-use, and easy-to-program time-based control.
The six-button user interface and large back lit display allow for
simple setup and operation for time based events, manual control
hold, override, event recurrence mode, and built-in FlickWarn.
Features
• Supports 16 Elaho control spaces
• Astronomical timeclock with +/- sunset or sunrise settings and
programmable latitude/longitude
• 24-hour real time clock with user configurable Daylight Saving
Time (DST)
• 50 field-programmable events
• Manual Hold, keeps the system in the current event up to two
hours or until canceled
• Simple manual control of presets with overrides
• Resumes program automatically after a power loss event
• Backlit graphical LCD display
• Meets California Title 24 and ASHRAE-90.1 requirements
Elaho Astronomical TimeClock
Warnings and Notice Conventions
These symbols are used throughout Echoflex documentation to alert
you to danger or important information.
Note: Notes are helpful hints and information that are supplemental
to the main text.
CAUTION: A Caution statement indicates situations where there
may be undefined or unwanted consequences of an action, potential
for data loss or an equipment problem.
WARNING: A Warning statement indicates situations where
damage may occur, people may be harmed, or there are serious or
dangerous consequences of an action.
WARNING: RISK OF ELECTRIC SHOCK! This warning statement
indicates situations where there is a risk of electric shock.
all-guide
s.com
Help from Technical Services
If you are having difficulties, your most convenient resources are the
references given in this document. To search more widely, try the
Echoflex website at echoflexsolutions.com. If none of these resources
are sufficient, contact Echoflex Technical Services directly at one of the
offices identified below.
When calling for help, take these steps first:
• Prepare a detailed description of the problem
• Go near the equipment for troubleshooting
• Find your notification number if you have called in previously
Echoflex
38924 Queensway Unit #1
Squamish, British Columbia
Canada, V8B 0K8
888-324-6359 (toll-free)
+1-778 733-0111
[email protected]
Elaho Astronomical TimeClock
Specification
Note: Installation must follow all national and local codes for
electrical equipment.
Ambient Environment
For indoor, commercial controls use only. Operating temperature
0-40°C, 5-95% non-condensing humidity.
Compliance
• UL and cUL LISTED
• CE marked
• Meets California Title 24
• Meets ASHRAE-90.1
Electrical Requirements
The E-ATC ships with a termination kit for the required terminations.
This kit contains a 24 VDC auxiliary power pigtail, EchoConnect
® bus
pigtail, ESD ground wire pigtail, spacers, and all required wire
termination connectors for installation.
The E-ATC requires external power provided to the unit by an auxiliary
24 VDC (Class 2) power supply and EchoConnect which supports data
and control to the EchoConnect station communication bus.
Note: NEC Class 2 product to be wired in accordance to NEC Article
725 and local jurisdiction requirements.
Note: All control wiring should be installed and terminated by a
qualified installer and should follow standard wiring installation
practices.
Leave approximately 8" (20 cm) of wiring in the back box for
connection and to allow slack for future service needs.
24 VDC
Requires two 16 AWG (1.5mm
2) wires (typically a black and red wire
pair), which terminate to a provided 24 VDC auxiliary power pigtail.
WAGO
® cage clamp connectors are provided.
The 24 VDC auxiliary power pigtail is connectorized for installation to
the two position receptacle on the rear side of the E-ATC.
EchoConnect
The E-ATC requires EchoConnect. EchoConnect is a bidirectional
protocol that uses one pair of wires (data + and data -) for both data
and power. Echoflex recommends using Belden 8471 (or approved
equal) Class 2 wire. The total combined length of an EchoConnect
wire run (using Belden 8471, or equal) may not exceed 1,640 feet
(500 m).
EchoConnect and ESD ground wire pigtails are provided, as well as
the required wire termination connectors, to make the terminations
from the building wire to the pigtails.
Note: Category 5 (Cat5) wiring is supported for the EchoConnect
station communication bus with some limitations. Reference the Cat5
Cable Preparation Setup Guide for more details. Echoflex
documentation is available for download from our website at
echoflexsolutions.com.
The EchoConnect bus pigtail is connectorized for installation to the
two position receptacle on the rear side of the E-ATC. The ESD ground
wire pigtail has a spade terminal for installation to the receptacle on
the E-ATC, near the EchoConnect bus connection.
Elaho Astronomical TimeClock
Mounting Requirements
The E-ATC is capable of flush or surface mounting for installation in
any location with conditions meeting the ambient environment
requirements listed Ambient Environment on page 4.
Alternatively, the E-ATC can be integrated into an Elaho Room
Controller.
Flush
Flush mount the E-ATC to an industry standard two gang back box,
not provided. The back box should be installed plumb and square for
best results. Ensure that the back box is clean and free of obstructions
and that all wiring is installed correctly.
Surface
A surface mounted back box is available, sold separately, from
Echoflex.
Elaho Room Controller
Echoflex offers the Elaho Room Controller with integrated Elaho
Astronomical TimeClock. Reference the Elaho Room Controller
Installation and Configuration Manual information for wire
terminations in this installation scenario. Refer back to this manual
for timeclock configuration information.
Elaho Control System
Elaho control system utilizes the EchoConnect bus for communication,
allowing Elaho enabled products to interact. An Elaho control system
is limited to 16 Elaho control products and 16 Elaho output products.
If more Elaho products are required in a system, an Elaho Expansion
Bridge may be added to the system.
The Elaho Astronomical TimeClock (E-ATC) is considered to be a
control station when calculating the system limitations.
E-ATC installed in an Elaho Room
Controller
EchoConnect (Belden 8471 + (1) 14 AWG ESD ground wire)
Room Controller
with integrated
TimeClock and 24 VDC
Back
Up
Enter
Recall
Preset
Hold
Down
E-ATC with External 24 VDC Auxiliary
Power
24 VDC Power Supply
(not included)
Back
Up
Enter
Recall
Preset
Hold
Down
EchoConnect (Belden 8471 + (1) 14 AWG ESD ground wire)
TimeClock
24 VDC
Power
+
-
all-guide
s.com
Elaho Astronomical TimeClock
E-ATC with Elaho Station Power Module
with Aux Power
TimeClock
Station Power Supply with Aux Power
a variety of form factors and mounting
options are available (not included)
Back
Up
Enter
Recall
Preset
Hold
Down
EchoConnect (Belden 8471 + (1) 14 AWG ESD ground wire)
Installation and Setup
The Elaho Astronomical Timeclock (E-ATC) is designed to install into a
flush mounted, industry standard, two gang back box (provided by
others). Installation should follow local codes and standard practices.
Install the back box flush and square for best installation results.
Alternatively, a surface mounted back box may be used (sold
separately and available from Echoflex.)
Connect Wiring
The E-ATC ships with an EchoConnect pigtail, a 24 VDC power pigtail,
spacers and all required screws and connectors for the installation.
24 VDC power
pigtail connects
here
EchoConnect bus
pigtail connects
here
ESD ground
pigtail connects
here
Note: When using Category 5 (or equivalent) cable on the
EchoConnect communication bus, please note the following:
• Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the
Cat5 Termination Kit (8186A1207) for information to
terminate Cat5 wiring.
• Not all topologies are supported using Cat5; careful
planning is required to ensure the proper termination kits
are available and the wire is pulled appropriately.
1.
Pull all required wiring (data+, data-) into the back box. As
needed, pull an additional ESD ground wire (required only
when the station is not installed in grounded metal conduit).
Elaho Astronomical TimeClock
2.
Connect station ESD ground wire pigtail.
a.
Strip 7/16” (11 mm) of insulation from the ends of the
station ground wire pigtail, provided in the termination
kit, and the incoming ground wire.
b.
Use one WAGO 221 Series LEVER-NUTS® provided in the
termination kit to connect the station ESD ground pigtail
and the incoming ground. For stations using grounded
metal conduit, connect the ground pigtail to the metal
back box ground location.
c.
Install the ESD ground wire pigtail FASTON connector to
the mating receptacle on the station electronics.
3.
Terminate EchoConnect wires. EchoConnect is topology free:
you may install the wires in any combination of bus, star, loop,
or home-run.
a.
Strip 7/16” (11 mm) from the ends of each power pigtail
wire provided in the termination kit and the installed
control wires.
b.
Use the WAGO connectors provided to connect the power
pigtail wires and the installed Belden 8471 control wires.
One WAGO should be used for the white wire pair (data +)
and one for the black wire pair (data -). Open the terminal
levers on the WAGO connector and insert the installed
Belden 8471 wire and the lead from the power pigtail into
the terminals then close the levers.
c.
Install the two pin connector from the power pigtail to the
mating receptacle on the station electronics.
4.
Terminate and connect 24 VDC auxiliary power wires. 24 VDC is
required to power the Astronomical TimeClock.
a.
Strip 7/16” (11 mm) from the ends of each wire.
b.
Use the WAGO connectors provided to connect the
auxiliary power pigtail and the installed auxiliary power
wires .One WAGO should be used for the red pair (positive
+) and one for the black wire pair (negative -). Open the
terminal levers on the WAGO connector and insert the
installed auxiliary power wire and the lead from the pigtail
into the terminals, then close the levers.
5.
Install the two position connector from the 24 VDC aux power
pigtail to the mating receptacle on the station electronics.
Install the E-ATC into the Back Box
Receptacle spacers are provided to help align the station and cover
flush against the wall in flush mount applications. The spacers are not
required when installing the station into a surface mount back box.
1.
Insert the station electronics and wiring into the back box.
2.
Use spacers as needed to provide a flush mounted station.
a.
Fold the spacer in a zig-zag fashion and press the stack
together to achieve the thickness needed to fill the gap
between the station, wall surface, and the back box.
b.
Cut off and discard the excess.
c.
Place the stack between the station electronics and the
flush mounted back box.
3.
Secure each station electronics in place using the two screws
provided. If using spacers, insert the screws through the spacers
as well.
4.
Secure the station in place using the four screws provided.
5.
Using a level, align the E-ATC perfectly square to the walls. If
the station is not installed level and flush, the faceplate will not
fit properly to the unit or against the wall. Refer to step 2 for
information regarding use of the provided spacers to mitigate
flush mount issues.
Elaho Astronomical TimeClock
Install the Faceplate
The faceplate is secured to the station with built-in magnets.
1.
Align the top of the faceplate to the station and angle the
bottom approximately 20 degrees.
2.
Hook the top of the faceplate to the tabs located on the
electronics assembly. To ensure the faceplate is hooked
properly on the top hook, wiggle it slightly side to side.
3.
Swing the bottom of the faceplate down until the magnets
engage.
4.
If the faceplate does not fully attach automatically, wiggle the
bottom of the plate until the magnets are seated properly to
the station nd the plate is secure.
all-guide
s.com
User Interface Overview
Keypad
The user interface has an easy to use
menu-navigation keypad that includes
[Up], [Down], [Back], and [Enter] buttons.
The [Recall Preset] and [Hold] buttons are
provided for everyday time clock
operation.
Pressing [Up], [Down], or [Enter] will activate the main menu. Pressing
the [Recall Preset] or [Hold] buttons wakes the LCD and invokes the
respective timeclock function.
Display
The display is backlit for easy viewing. Press any button to wake the
display and backlight. The backlight sleeps after two minutes of
inactivity.
To change the display contrast press and hold the [Back] button while
tapping the up or down button.
Status Display
The default menu reverts to the status display after two minutes of
inactivity. The status display may also be viewed by pressing the [Back]
button while navigating the main menu.
Mon, Sep 26, 2016
9:51AM
Event 12 Active
v2.0.0
Lighting Timeclock
current date / time
software version
system status message
Menu
The menu is displayed during manual activity. After two minutes of
inactivity the menu will revert to the status display.
Main Menu
Schedule Events
Open/Close Settings
Timeclock Settings
Presets
Holiday Shut-Off
August 13, 2016 09:51am
Elaho Astronomical TimeClock
Hold
A Hold triggers an override to one or more scheduled events, allowing
manual lighting control to persist. When a hold is active, regularly
scheduled events are ignored and “-Schedule on Hold -” is displayed
for the affected space.
When an active hold is cleared, the originally scheduled event is
restored. Without an active hold condition any manual lighting
control will be replaced by the next scheduled event that occurs.
Pushing the [HOLD] button cycles through the available hold types
including Timed Hold, Indefinite Hold, and No Hold.
A Holiday Shutoff is an additional type of hold that is configured from
the main menu and also shuts off lights for a period of time. For more
information, Holiday Shut-Off on page 25
All Events are
on Hold for
x hrs xx mins
Push Hold twice to
cancel and
reinstate schedule.
Timed Hold
Mon Sep 26, 2016
9:51AM
v2.0.0
Lighting Timeclock
All Events in all
all spaces are
on Hold
Push Hold to
cancel and
reinstate schedule.
Indefinite Hold
press
HOLD
Mon, Sep 26, 2016
9:51AM
v2.0.0
Lighting Timeclock
press
HOLD
press
HOLD
No Holds are
active
Timed Hold
is active
Indefinite
Hold is active
No Holds are
active
Pressing the [HOLD] button once during a Timed Hold will start an
Indefinite Hold, pressing twice will cancel the hold and reinstate the
normal schedule.
If only some spaces have an active Timed Hold but not all, the first
press of [HOLD] will start a new Timed Hold in all spaces.
Timed Hold
Timed Holds can be initiated two ways:
Pressing the [HOLD] button triggers a Timed Hold in all spaces.
By default, all scheduled events default to allow Auto Timed Hold. A
scheduled event with Auto Timed Hold enabled can be interrupted by
a manually triggering a preset or sequence.
Set Auto Timed Hold within the Schedule Events Menu to dictate if an
event responds to a manually activated preset or sequence by starting
a Timed Hold automatically. For more information Auto Timed Hold
on page 16.
The display indicates the affected space with a Timed Hold enabled.
Both the space number and the time remaining are shown. If
additional spaces have a Timed Hold enabled, the display will cycle
through all spaces at two second intervals.
Mon, Sep 26, 2016
9:51AM
Lighting Timeclock
-Schedule on Hold-
-in Space 1-
Time remaining 1:31
Mon, Sep 26, 2016
9:51AM
Lighting Timeclock
-Schedule on Hold-
-in Space 3-
Time remaining 0:15
Mon, Sep 26, 2016
9:51AM
Lighting Timeclock
Push Hold three times
to reinstate schedule
A Timed Hold will automatically clear after the configured Hold Time,
which defaults to two hours (120 min).
Indefinite Hold
Manual Indefinite Hold is enabled by pressing the [Hold] button;
press once if a Timed Hold is already active, or twice if no hold is
currently active.
An Indefinite Hold can only be cleared by pressing the [Hold] button
once. Until cleared, all scheduled events will be overridden and will
not occur. When the Indefinite Hold is cleared, the current scheduled
event will be reinstated.
Mon, Sep 26, 2016
9:51AM
Echo Timeclock
- schedule on Hold -
Indefinite Hold
Mon, Sep 26, 2016
9:51AM
Echo Timeclock
Push Hold to
reinstate schedule.
Indefinite Hold
Recall Preset
The [RECALL PRESET] button provides easy, manual preset activation.
When pressed, the Presets Menu displays.
Presets
Space:
1
Preset 15 active
Preset #
12
Activate
Record
- S c h e d u l e o n H o l d -
Use the [UP] and [DOWN] buttons to scroll to and select the desired
preset number. See for information on programming presets.
Press the [Back] button to exit the Presets menu.
Elaho Astronomical TimeClock
Main Menu
The Main Menu provides access to set up and configure events,
timeclock settings, Preset and Sequence controls, and Holiday Shut-
Off settings.
Main Menu
Schedule Events
Open/Close Settings
Timeclock Settings
Presets
Holiday Shut-Off
August 13, 2016 09:51am
Schedule Events
Main Menu
Schedule Events
Open/Close Settings
Timeclock Settings
Presets
Holiday Shut-Off
May 13, 2016 09:51am
Enter
Schedule Events
Event Number:
50
Action:
None
The E-ATC supports up to 50 programmed events. Event control
actions may include Preset, Sequence, Off, or None. Events may be set
to occur and re-occur every day, on weekdays, on weekends, or on
individual days of the week.
Events can also be set to occur at a particular time of day by specifying
hours and minutes, and am. or pm., or with an offset time based on
an astronomical event, such as before sunrise, after sunrise, before
sunset, or after sunset.
It’s also possible to program master Open and Close settings that
remain available to all scheduled events. See Open/Close Settings on
page 18.
Manual control replaces an active or scheduled event in a last takes
precedence (LTP) manner. If there is not an active hold condition when
the next scheduled event should occur, the scheduled event will
execute and the manual control will be overridden.
Auto Timed Hold
All scheduled events support a configurable Auto Timed Hold
property with options of No, Yes, and While Closed. By default, all
events are set to use While Closed for the Auto Timed Hold setting.
When a preset or sequence is manually triggered during an event and
Auto Timed Hold is set to Yes, that active event is placed on hold until
the interrupting action has completed and the hold timer lapses (hold
timer is default is 120 minutes), or in the case of the While Closed
setting, the Open event occurs.
When the hold timer expires, the currently scheduled event executes.
When a manual lighting control event occurs during an event, and
Auto Timed Hold set to No, the events schedule is not placed on hold.
Instead the next scheduled event will override the manual control at
its pre-configured event time.
Schedule an Event
1.
From the Main Menu, select Schedule Events. The Schedule
Events menu appears with event number selected.
2.
Press [Enter] to modify the event number.
3.
Use the [Up] and [Down] buttons to increment / decrement the
list of available event numbers. Press [Enter] to accept the
current displayed selection.
Schedule Events
Event Number:
50
Action:
Preset
Space
1
Preset
1
Recurrence:
Everyday
When:
Time of Day
Time:
--:-- am
Auto Timed Hold:
While Closed
4.
Scroll to select Action and press [Enter].
Each press of [Enter] cycles through the
available list of action options including
Preset, Sequence, Off, and None.
a.
Scroll to select either Preset or
Sequence and press [Enter]. The
focus changes to Action.
• When Preset or Sequence is the selected action,
additional menu options display for specification.
b.
Press [Down] to advance to Space.
c.
Press [Enter] to choose the Space number.
d.
Use the [Up] and [Down] buttons to scroll to the desired
Space number from the available Spaces in the system. A
maximum of 16 spaces can be programmed per system.
e.
Press [Enter] to commit the selection.
5.
Scroll through the Schedule Events menu and select either
Preset or Sequence, depending on what was chosen in Step 4a.
6.
Press [Enter] to modify the number.
7.
Scroll to select the Preset or Sequence number and press [Enter]
to commit the current displayed selection.
8.
Press [Enter] to return to Preset or Sequence.
all-guide
s.com
Elaho Astronomical TimeClock
9.
Scroll to select Recurrence from the menu list and press [Enter].
The recurrence list displays for selection.
a.
Scroll the recurrence list and select the desired option.
b.
Press [Enter] to accept the selection.
10.
Scroll to select When from the menu list and press [Enter]. A list
displays for selection of either a time of day or astronomical
time settings.
a.
Scroll the listing and select the desired option.
b.
Press [Enter] to accept the selection.
11.
Scroll to select Time from the menu list and press [Enter]. Time
displays differently depending on the type of When menu
selection made in step Schedule an Event.
• If Time of Day was selected, the time selection will display
as hh:mm (am or pm).
• If an astronomical setting was selected, the time selection
will display as 00h: 00m (##:## am). You must enter the
specific desired hour and minute offset from the selected
astronomical setting. For example, if Before Sunset is
selected, you must choose how long before sunset you
would like your event to execute in hours and minutes. The
time displayed in parenthesis is the automatically calculated
time of execution based on your selected offset.
• If Open/Close times are selected for an event, Time will not
be available. The Open/Close times take precedence.
12.
Scroll to select Auto Timed Hold from the menu list and press
[Enter] to change the setting from default While Closed to
either No or Yes.
• See Auto Timed Hold on page 16 for operation details.
Open/Close Settings
The Open/Close settings allow you to program the E-ATC to have a
master Open and Close time that will be available to all scheduled
events.
1.
From the Main Menu, navigate to Open/Close Settings and
press [Enter].
2.
Press [Enter] once to navigate to the Time field. Each
subsequent press of [Enter] commits the current selection and
progresses to the next available selection field. Pressing [Back]
discards any changes and highlights the previous selection.
• The default for Open is 8:00 am.
• The default for Close is 9:00 pm.
Jun / 6 / 2015
Hold Time:
120 min
Flick Warn:
Yes
Warn Time:
2 min
Time Zone:
GMT -6
Latitude:
43 8 N
Longitude:
89 20 W
DST:
US
Manual DST Dates
Restore Defaults
The Timeclock Settings menu provides access to display preferences
such as current Time and Time Style (12 hour or 24 hour clock),
current Date, Hold Time, Flick Warn, Warn Time, Time Zone, and
Daylight Saving Time (DST) location details. In addition, this menu
provides the ability to restore the Timeclock to factory defaults.
Change Current Time
1.
Select Timeclock Settings from the Main Menu. The Timeclock
Settings menu displays with current Time selected.
2.
Press [Enter] to modify the current hour.
a.
Use the [Up] or [Down] buttons to increment/decrement
the current hour. The Time Style determines a.m. and p.m.
settings.
b.
Press [Enter] to accept the selection.
3.
Scroll to the current minute and press [Enter] to modify the
selection.
a.
Use the [Up] or [Down] buttons to increment/decrement
the current minute.
b.
Press [Enter] to accept the selection.
Change Time Style
Change the Timeclock display style from a 12 hour clock to a 24 hour
clock.
1.
Select Time Style from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
a.
Use the [Up] or [Down] buttons to scroll the menu and
select either 12 Hour or 24 Hour, then press [Enter].
Elaho Astronomical TimeClock
Change Current Date
1.
Select Date from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection. The Month field
will display selected.
3.
Use the [Up] or [Down] buttons to scroll to the current month
and press [Enter]. The Day field will display selected.
4.
Use the [Up] or [Down] buttons to scroll to the current day and
press [Enter] to select a new date. The Year field will display
selected.
5.
Use the [Up] or [Down] buttons to scroll to the current year and
press [Enter] to select a new year.
Configure Hold Time
Hold Time is the length of time that all Timed Hold conditions will
remain, until the schedule resumes normal operation. Hold Time is set
to 120 minutes by factory default to comply with energy conservation
standards. You may change the Hold Time to any value from 10-360
minutes, in 10 minute increments.
1.
Select Hold Time from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
3.
Use the [Up] or [Down] buttons to scroll to the desired Hold
Time and press [Enter].
Set Flick Warn
Flick Warn is a feature that provides visual warning to occupants in a
space when the next pending scheduled event is intended to turn all
of the lights off. The E-ATC will flash the lights on and off for a set
length of time before the pending event occurs, allowing a user to
either issue a Hold command, or use manual lighting control to issue
an Auto Timed Hold. The amount of time before Flick Warn activates is
determined by the Warn Time setting within the Timeclock Settings
menu. This setting applies to all scheduled events.
1.
Select Flick Warn from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
3.
Use the [Up] or [Down] buttons to scroll and select either Yes or
No, then press [Enter] to confirm the current displayed
selection.
Set Warn Time
Warn Time is the amount of time before the TimeClock issues a
scheduled Off action, preceding a Flick Warn. Factory default Warn
Time is two minutes, but can be set to any value from 1-60 minutes.
1.
Select Warn Time from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
3.
Use the [Up] or [Down] buttons to scroll to the desired Warn
Time and press [Enter].
Set Time Zone
For accurate real-time and astronomical events, the E-ATC must be set
to reflect your current time zone. Select the time zone based on hours
offset from GMT (Greenwich Mean Time). Visit
http://wwp.greenwichmeantime.com/ for a complete listing of GMT
time zones.
1.
Select Time Zone from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
3.
Use the [Up] or [Down] buttons to scroll and select the current
GMT time zone offset and press [Enter].
Set Latitude and Longitude
Set your accurate location for proper calculation of sunrise and sunset
times.
1.
Select Latitude from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
3.
Use the [Up] or [Down] buttons to scroll and select the accurate
angle and press [Enter].
4.
Use the [Up] or [Down] buttons to scroll and select the accurate
minutes location and press [Enter].
5.
Use the [Up] or [Down] buttons to scroll and select either N
(North) or S (South), then press [Enter].
6.
Select Longitude from the Timeclock Settings menu and repeat
steps 2 through 5 above.
Elaho Astronomical TimeClock
Set Daylight Saving Time
Set the current Daylight Saving Time (DST) location. Selecting an
option from this menu list utilizes default Daylight Saving Time dates
for the selected location.
1.
Select DST from the Timeclock Settings menu.
2.
Press [Enter] to modify the current selection.
3.
Use the [Up] or [Down] buttons to scroll to the correct Daylight
Saving Time location (choices include None, US, EU, and
Manual), then press [Enter].
Set Manual DST Dates
Set custom or manual Daylight Saving Time dates as needed.
1.
Select Manual DST Dates from the Timeclock Settings menu.
2.
Press [Enter] again. The manual DST Dates menu list displays
with the current DST start and end dates displayed.
3.
Press [Enter] to set new start and end dates.
4.
Using typical E-ATC navigation and menu set techniques ([Up]
or [Down] buttons to scroll and [Enter] to set), select and set the
start of daylight saving time Month, Day of Week, and
Occurrence settings.
5.
Scroll to DST End Date and set the end of daylight saving time
Month, Day of Week, and Occurrence settings.
all-guide
s.com
The Presets menu provides access to manually activate, record, and
deactivate host presets. The number of presets available is dependant
on the product type.
• Elaho Relay Panel and ETC's Sensor IQ - up to 64 presets
• ETC's Unison DRd rack with E-ACP - up to 64 presets
• ETC's Sensor3 with CEM3 - up to 64 presets
• Elaho Zone Controllers - up to 8 presets
• Elaho Room Controller - up to 16 presets
• Elaho DMX Scene Controller - up to 32 presets
Presets
Space:
1
Preset 15 active
Preset #
12
Activate
Record
- S c h e d u l e o n H o l d -
The Presets menu displays the status of the
active preset in the selected space. When no
preset is active, “No Active Preset” appears
and the last preset that was controlled from
the E-ATC menu displays for control activation
or recording.
Recording a preset from this menu records the preset data across all
connected hosts for that specific preset number.
Activate a Preset
1.
Select Presets from the Main Menu.
2.
Press [Enter] to modify the currently selected Space number.
3.
Use the [Up] or [Down] button to scroll the list of available
Spaces, numbered 1-16, then press [Enter] to commit the
selection.
4.
Press [Down] to advance to Preset #, then press [Enter] to
modify the current selected Preset number.
5.
Use the [Up] or [Down] button to scroll the list of available
preset numbers from 1-64, then press [Enter] to select the new
selection. (Maximum number of preset is dependent on the
host product type.)
6.
Press the [Down] button once to advance to Activate, then press
[Enter]. The selected preset will activate across all connected
Echo hosts.
Elaho Astronomical TimeClock
Record a Preset
Before recording a new preset or recording over an existing preset, set
the desired lighting look using Elaho Inspire or Preset stations, the
product user interface, or an external DMX control source.
Note: Recording a preset will affect the function of the button
stations and other products in the system.
1.
Select Presets from the Main Menu.
2.
Press [Down] to advance to Preset #, then press [Enter] to
modify the current selected preset number.
3.
Use the [Up] or [Down] button to scroll the list of available
preset numbers from 1-64, then press [Enter] to select the new
selection. (Maximum number of preset is dependant on the
product type.)
4.
Press the [Down] button twice to advance to Record, then press
[Enter] to initiate the record action. This will record the new
preset values to the selected preset across all connected Elaho
hosts.
Deactivate
1.
Select Presets from the Main Menu. The Presets menu displays
the status of the active preset in the selected space.
2.
Press [Down] to advance the selection to Deactivate, then press
[Enter]. The preset will deactivate and the status will display
“No Active Preset”.
The Holiday Shut-Off feature enables override of scheduled events
(per individual space) for a specified period of time (1-7 days). The
default override is set to 1 day. The Holiday Shut-Off feature is
compliant with California Title 24.
Holiday Shut-Off
Star t Holiday Shutof f
Config Holiday Spaces
Holiday Shut- Of f
begins in 5:00
Lights will shut of f
and Scheduled Events
will be on Hold
for x x days.
[Enter to Star t now]
[Back to Cancel]
Holiday Shut- Of f
This feature shuts
of f lighting and
ignores scheduled
events in the
configured Spaces.
Star t Shut- Of f
Shut- Of f for: 1 days
Enter
Enter
When “Start Shut-Off” is selected, a five minute countdown begins.
At any time during this countdown, you may cancel the Holiday Shut-
Off by pressing the [Back] button.
After five minutes have lapsed, the Shut-Off executes an Off command
in the specified spaces and the status display shows the time
remaining before the Holiday Shut-Off expires. To reinstate the
normal event schedule, press the [HOLD] button.
If manual control is initiated while a Holiday Shut-Off is applied, a
Timed Hold will start, temporarily permitting the manual lighting
control. When the Hold Time expires, lights will shut-off in the
specified spaces, replacing any manual control, and Holiday Shut-Off
will be reinstated using the time remaining.
Configuration of Holiday Spaces
All spaces default to Shut-Off but can be individually configured to be
excluded from the Holiday Shut-Off feature, set to unaffected,
meaning their normal scheduled events will persist on schedule.
Spaces that are configured to Shut-Off will suspend all scheduled
events and their connected lights will be forced off for the selected
number of days. See Holiday Shut-Off above for more information.
Spaces set to Unaffected will continue to allow normally scheduled
events.
1.
Select Holiday Shut-Off from the Main Menu and press [Enter].
2.
Press [Down] to scroll to Config Holiday Spaces and press
[Enter]. The spaces that are configured to the connected system
display with their currently set Shut-Off status.
3.
Use the [Up] or [Down] buttons so scroll through the list and
select the space to be modified, then press [Enter] to select the
space.
Elaho Astronomical TimeClock
4.
Press [Down] to cycle through the option of Unaffected or Shut-
Off.
5.
Press [Enter] to commit the current selection.
6.
Repeat steps 3 through 5 for all spaces you want to configure.
Change default Shut-Off Time duration
1.
Select Start Holiday Shut-Off from the Holiday Shut-Off menu
and press [Enter].
2.
Use [Up] and [Down] to scroll to Shut-Off for:, then press
[Enter].
3.
Press the [Up] or [Down] buttons to increment or decrement the
value, then press [Enter] to accept the selection.
Menu Flow Chart
Monday, Sep 26, 2016
9:51AM
v2.0.0
Lighting Timeclock
Monday, Sep 26, 2016
9:51AM
-Schedule on Hold -
-in Space 1-
Time remaining 1:31
Lighting Timeclock
All Events in all
all spaces are
on Hold
Push Hold to
cancel and
reinstate schedule.
Indefinite Hold
All Events are
on Hold for
x hrs xx mins
Push Hold twice to
cancel and
reinstate schedule.
Timed Hold
Monday, Sep 26, 2016
9:51AM
-Schedule on Hold -
Time remaining 1:31
Lighting Timeclock
Status Screen
Hold Screen
Variants
Monday, Sep 26, 2016
9:51AM
- Holiday Shut-Off -
- Schedule on Hold -
Time remaining 1:31
Lighting Timeclock
all-guide
s.com
Elaho Astronomical TimeClock
Main Menu
Schedule Events
Open/Close Settings
Timeclock Settings
Presets
Holiday Shut-off
Sep 26, 2016 09:51am
Timeclock Settings
See following page for
Timeclock Settings
Menu Flow
Schedule Events
Event Number: 50
Action: None
Presets
Schedule Events
Event Number: 50
Action: Preset
Space 1
Preset 1
Recurrence: Everyday
When: Time of Day
Time: --:-- am
Auto Timed Hold: Yes
Recurrence
Everyday
Weekdays
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
When
Time of Day
Before Sunrise
After Sunrise
Before Sunset
After Sunset
At Open Time
At Closed Time
Holiday Shut-Off
See following page for
Holiday Shut-Off
Menu Flow
Space:
1
Preset 15 Active
Preset:
12
Activate
Record
- Schedule on Hold -
Open/Close Settings
Weekdays
Open Time:
8:00 am
Close Time:
9:00 pm
Saturday
Open Time:
8:00 am
Close Time:
9:00 pm
Sunday
Open Time:
8:00 am
Close Time:
9:00 pm
Set Manual DST Dates
Month:
March
Day of week:
Sunday
Occurrence:
Second
Month:
November
Day of week:
Sunday
Occurrence:
First
DST End Date
Time:
10:10 am
Time Style:
12 Hour
Date:
6/9/2008
Hold Time:
120min
Flick Warn:
Yes
Warn Time:
2 min
Time Zone:
GMT -6
Latitude:
43 8 N
Longitude:
89 20 W
DST:
US
Manual DST Dates
Restore Defaults
Timeclock Settings
Manual DST Dates
DST Start Date
Select Day of Week
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Select Month
January
February
March
April
May
June
July
August
September
October
November
December
Restore Defaults
This will clear all
settings and memory.
Are you Sure?
No
Yes
Attention:
Lights will shut off
in: mm:ss due to
a pending event.
Press HOLD now
to postpone
[Back to dismiss]
Main Menu
Schedule Events
Open/Close Settings
Timeclock Settings
Presets
Holiday Shut-off
Sep 26, 2016 09:51am
Elaho Astronomical TimeClock
Holiday Shut-Off
This feature shuts
off lighting and
ignores scheduled
events in the
configured Spaces.
Star t Shut- Off
Shut- Off for: 1 days
Holiday Shut- Off
begins in 5:00
Lights will shut off
and Scheduled Events
will be on Hold
for xx days.
[Enter to Star t now]
[Back to Cancel]
Holiday Shut-Off
Star t Holiday Shutoff
Config Holiday Spaces
Config Holiday Spaces
Space 1:
Shut-Off
Space 2:
Shut-Off
Space 3:
Shut-Off
Space 4:
Shut-Off
Space 5:
Unaffected
Space 6:
Shut-Off
Space 7:
Shut-Off
Main Office n Squamish, BC, Canada n Toll Free +888 324 6359 n Phone +778 733 0111 n Fax +604 815 0078
Email [email protected] n Web echoflexsolutions.com n Product information and specifications subject to change.
©2018 Echoflex Solutions, Inc. n Echoflex intends this document to be provided in its entirety.
8186M1230-2.0.0 n Revision A n Released 2018-09
all-guide