Apollo Smoke Detector XP95 Installation Manual

Text of the manual

FIRE DETECTORS LIMITED

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754 Email: [email protected] Website: www.apollo-fire.co.uk 4 1 XP95 Output Unit Installation Guide General The XP95 Output Unit, part no 55000-819, is supplied with a backbox for surface mounting. It is also available without a backbox for flush fitting — part no 55000-817. For flush fitting the installer will need to provide a suitable metal box with fixing centres of 120.6mm (UK standard 2-gang accessory box). Note: The XP95 Output Unit is not designed for outdoor use unless it is mounted in a suitable weatherproof enclosure. Surface Mounting 1. Mount the backbox as required and install all cables for termination. Ensure that earth continuity is maintained. 2. Remove the cover plate (if secured) from the Output Unit assembly by inserting the blade of a terminal screwdriver into each of the four securing clips in turn, gently prising the outer edge of the cover plate over the clips underneath. DO NOT USE EXCESSIVE FORCE. 3. Terminate all cables. 4. Gently push the completed assembly towards the back box until the mounting holes are aligned and secure with the two mounting screws provided. DO NOT OVERTIGHTEN. 5. Set the address of the unit as shown on page 3. 6. Finally, when commissioning is complete, fit the cover plate by placing it in position, observing the correct orientation (LEDs on the PCB must be aligned with viewing holes). Apply pressure to the cover plate until all four clips are holding it in position. Flush Mounting 1. Secure a suitable metal back box (30mm minimum depth) in position and install all cables for termination. Ensure that earth continuity is maintained. 2. Follow steps 2 to 6 as above. Functional Test Data Output Bit Function Input Bit Function 2 NOT USED 2 NOT USED 1 NOT USED 1 NOT USED 0 OPERATES RELAY 0 NOT USED 1 = ON 0 = OFF For further information on protocol bit usage refer to the XP95 Output PIN sheet, PP2018. Troubleshooting Before investigating individual units for faults, it is very important to check that the system wiring is fault free. Earth faults on a data loop or any ancillary zone wiring may cause communication errors. Many fault conditions are the result of simple wiring errors. Check all connections to the unit and make sure that the correct value resistors are fitted where necessary. Fault finding Problem Possible Cause No response or missing Incorrect address setting Incorrect loop wiring Relay fails to operate Incorrect wiring Control panel has incorrect cause and effect programming Relay energised continuously Incorrect loop wiring Incorrect address setting The part no of this guide is 39214-073/Issue 3

All wiring terminals will accept solid or stranded cables up to 2.5mm²

Address Setting The address of the Output Unit is set using the lower seven segments of the DIL switch. Each segment of the switch must be set to “0” or “1”, using a small screwdriver or similar tool. A complete list of address settings is shown below. DIL switch DIL switch DIL switch DIL switch DIL switch addr setting addr setting addr setting addr setting addr setting 1234567 1234567 1234567 1234567 1234567 1 1000000 11 1101000 21 1010100 31 1111100 41 1001010 2 0100000 12 0011000 22 0110100 32 0000010 42 0101010 3 1100000 13 1011000 23 1110100 33 1000010 43 1101010 4 0010000 14 0111000 24 0001100 34 0100010 44 0011010 5 1010000 15 1111000 25 1001100 35 1100010 45 1011010 6 0110000 16 0000100 26 0101100 36 0010010 46 0111010 7 1110000 17 1000100 27 1101100 37 1010010 47 1111010 8 0001000 18 0100100 28 0011100 38 0110010 48 0000110 9 1001000 19 1100100 29 1011100 39 1110010 49 1000110 10 0101000 20 0010100 30 0111100 40 0001010 50 0100110 51 1100110 61 1011110 71 1110001 81 1000101 91 1101101 52 0010110 62 0111110 72 0001001 82 0100101 92 0011101 53 1010110 63 1111110 73 1001001 83 1100101 93 1011101 54 0110110 64 0000001 74 0101001 84 0010101 94 0111101 55 1110110 65 1000001 75 1101001 85 1010101 95 1111101 56 0001110 66 0100001 76 0011001 86 0110101 96 0000011 57 1001110 67 1100001 77 1011001 87 1110101 97 1000011 58 0101110 68 0010001 78 0111001 88 0001101 98 0100011 59 1101110 69 1010001 79 1111001 89 1001101 99 1100011 60 0011110 70 0110001 80 0000101 90 0101101 100 0010011 101 1010011 111 1111011 121 1001111 102 0110011 112 0000111 122 0101111 103 1110011 113 1000111 123 1101111 104 0001011 114 0100111 124 0011111 105 1001011 115 1100111 125 1011111 106 0101011 116 0010111 126 0111111 107 1101011 117 1010111 108 0011011 118 0110111 109 1011011 119 1110111 110 0111011 120 0001111 Commissioning It is important that the XP95 Output Unit be fully tested after installation. An XP95 Test Set, part no 55000- 870, may be used to carry out functional testing of individual units. It can also be used to perform data integrity tests of an entire system. LED Indicators ! Relay On Illuminated red when relay is energised The use of the LEDs can be inhibited by setting the ‘LED ENABLE’ segment of the DIL switch to ‘0’. Currrent consumption, max @ 24V switch-on surge, max 100 ms 3mA quiescent 720µA relay operated 3.3mA For a full technical specification of the Output Unit, please refer to the XP95 Output Unit PIN Sheet, PP2018. { XP95 LOOP L1 (–ve)* L2 (+ve)* N/C COM N/O RELAY OUTPUT 1A @ 30V MAX 30V AC or DC { * L1 and L2 are polarity insensitive, but, for the sake of consistency, it is recommended that L1 be kept negative

Other Smoke Alarm Manuals