Apollo Smoke Detector XP95 Installation Manual
Text of the manual
FIRE DETECTORS LIMITED
Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: [email protected] Website: www.apollo-fire.co.uk
4
1
XP95 Output Unit
Installation Guide
General
The XP95 Output Unit, part no 55000-819, is supplied with a backbox for surface mounting. It is also
available without a backbox for flush fitting — part no 55000-817. For flush fitting the installer will need to
provide a suitable metal box with fixing centres of 120.6mm (UK standard 2-gang accessory box).
Note: The XP95 Output Unit is not designed for outdoor use unless it is mounted in a suitable weatherproof
enclosure.
Surface Mounting
1.
Mount the backbox as required and install all cables for termination. Ensure that earth continuity is
maintained.
2.
Remove the cover plate (if secured) from the Output Unit assembly by inserting the blade of a terminal
screwdriver into each of the four securing clips in turn, gently prising the outer edge of the cover plate
over the clips underneath. DO NOT USE EXCESSIVE FORCE.
3.
Terminate all cables.
4.
Gently push the completed assembly towards the back box until the mounting holes are aligned and
secure with the two mounting screws provided. DO NOT OVERTIGHTEN.
5.
Set the address of the unit as shown on page 3.
6.
Finally, when commissioning is complete, fit the cover plate by placing it in position, observing the
correct orientation (LEDs on the PCB must be aligned with viewing holes). Apply pressure to the cover
plate until all four clips are holding it in position.
Flush Mounting
1.
Secure a suitable metal back box (30mm minimum depth) in position and install all cables for
termination. Ensure that earth continuity is maintained.
2.
Follow steps 2 to 6 as above.
Functional Test Data
Output Bit
Function
Input Bit
Function
2
NOT USED
2
NOT USED
1
NOT USED
1
NOT USED
0
OPERATES RELAY
0
NOT USED
1 = ON
0 = OFF
For further information on protocol bit usage refer to the XP95 Output PIN sheet, PP2018.
Troubleshooting
Before investigating individual units for faults, it is very important to check that the system wiring is fault free.
Earth faults on a data loop or any ancillary zone wiring may cause communication errors.
Many fault conditions are the result of simple wiring errors. Check all connections to the unit and make sure
that the correct value resistors are fitted where necessary.
Fault finding
Problem
Possible Cause
No response or missing
Incorrect address setting
Incorrect loop wiring
Relay fails to operate
Incorrect wiring
Control panel has incorrect cause and effect programming
Relay energised continuously
Incorrect loop wiring
Incorrect address setting
The part no of this guide is 39214-073/Issue 3
All wiring terminals will accept solid or stranded cables up to 2.5mm²
Address Setting
The address of the Output Unit is set using the lower seven segments of the DIL switch. Each segment of
the switch must be set to “0” or “1”, using a small screwdriver or similar tool. A complete list of address
settings is shown below.
DIL switch
DIL switch
DIL switch
DIL switch
DIL switch
addr
setting
addr
setting
addr
setting
addr
setting
addr
setting
1234567
1234567
1234567
1234567
1234567
1
1000000
11
1101000
21
1010100
31
1111100
41
1001010
2
0100000
12
0011000
22
0110100
32
0000010
42
0101010
3
1100000
13
1011000
23
1110100
33
1000010
43
1101010
4
0010000
14
0111000
24
0001100
34
0100010
44
0011010
5
1010000
15
1111000
25
1001100
35
1100010
45
1011010
6
0110000
16
0000100
26
0101100
36
0010010
46
0111010
7
1110000
17
1000100
27
1101100
37
1010010
47
1111010
8
0001000
18
0100100
28
0011100
38
0110010
48
0000110
9
1001000
19
1100100
29
1011100
39
1110010
49
1000110
10
0101000
20
0010100
30
0111100
40
0001010
50
0100110
51
1100110
61
1011110
71
1110001
81
1000101
91
1101101
52
0010110
62
0111110
72
0001001
82
0100101
92
0011101
53
1010110
63
1111110
73
1001001
83
1100101
93
1011101
54
0110110
64
0000001
74
0101001
84
0010101
94
0111101
55
1110110
65
1000001
75
1101001
85
1010101
95
1111101
56
0001110
66
0100001
76
0011001
86
0110101
96
0000011
57
1001110
67
1100001
77
1011001
87
1110101
97
1000011
58
0101110
68
0010001
78
0111001
88
0001101
98
0100011
59
1101110
69
1010001
79
1111001
89
1001101
99
1100011
60
0011110
70
0110001
80
0000101
90
0101101
100
0010011
101
1010011
111
1111011
121
1001111
102
0110011
112
0000111
122
0101111
103
1110011
113
1000111
123
1101111
104
0001011
114
0100111
124
0011111
105
1001011
115
1100111
125
1011111
106
0101011
116
0010111
126
0111111
107
1101011
117
1010111
108
0011011
118
0110111
109
1011011
119
1110111
110
0111011
120
0001111
Commissioning
It is important that the XP95 Output Unit be fully tested after installation. An XP95 Test Set, part no 55000-
870, may be used to carry out functional testing of individual units. It can also be used to perform data
integrity tests of an entire system.
LED Indicators
!
Relay On
Illuminated red when relay is energised
The use of the LEDs can be inhibited by setting the ‘LED ENABLE’ segment of the DIL switch to ‘0’.
Currrent consumption, max @ 24V
switch-on surge, max 100 ms
3mA
quiescent
720µA
relay operated
3.3mA
For a full technical specification of the Output Unit, please refer to the XP95 Output Unit PIN Sheet,
PP2018.
{
XP95 LOOP
L1 (–ve)*
L2 (+ve)*
N/C
COM
N/O
RELAY
OUTPUT
1A @ 30V
MAX 30V AC
or DC
{
* L1 and L2 are polarity insensitive, but, for the sake of consistency, it is recommended that L1 be kept negative