Anybus CompactCom 40 Modbus-TCP Network Manual
Read Online
Read the Anybus CompactCom 40 Modbus-TCP Network Manual online using the built-in PDF viewer.
Text of the manual
Important User Information
Liability
Every care has been taken in the preparation of this document. Please inform HMS Industrial Networks AB of any
inaccuracies or omissions. The data and illustrations found in this document are not binding. We, HMS Industrial
Networks AB, reserve the right to modify our products in line with our policy of continuous product development.
The information in this document is subject to change without notice and should not be considered as a commit-
ment by HMS Industrial Networks AB. HMS Industrial Networks AB assumes no responsibility for any errors that
may appear in this document.
There are many applications of this product. Those responsible for the use of this device must ensure that all the
necessary steps have been taken to verify that the applications meet all performance and safety requirements in-
cluding any applicable laws, regulations, codes, and standards.
HMS Industrial Networks AB will under no circumstances assume liability or responsibility for any problems that
may arise as a result from the use of undocumented features, timing, or functional side effects found outside the
documented scope of this product. The effects caused by any direct or indirect use of such aspects of the product
are undefined, and may include e.g. compatibility issues and stability issues.
The examples and illustrations in this document are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular implementation, HMS Industrial Networks AB cannot as-
sume responsibility for actual use based on these examples and illustrations.
Intellectual Property Rights
HMS Industrial Networks AB has intellectual property rights relating to technology embodied in the product de-
scribed in this document. These intellectual property rights may include patents and pending patent applications in
the USA and other countries.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Table of Contents
Page
1
Preface............................................................................................................................... 5
1.1
About this document ......................................................................................................5
1.2
Related Documents .......................................................................................................5
1.3
Document History ..........................................................................................................5
1.4
Document Conventions ..................................................................................................5
1.5
Document Specific Conventions......................................................................................6
1.6
Abbreviations ................................................................................................................6
1.7
Trademark Information ...................................................................................................6
2
About the Anybus CompactCom 40 PROFIBUS DPV1/DPV0 .............................. 8
2.1
General.........................................................................................................................8
2.2
Features .......................................................................................................................8
3
Fieldbus Conformance and Certification.................................................................. 9
3.1
Fieldbus Conformance Notes..........................................................................................9
3.2
Certification ...................................................................................................................9
4
Basic Operation.............................................................................................................10
4.1
General Information .....................................................................................................10
4.2
Communication Settings............................................................................................... 11
4.3
Device Identity.............................................................................................................12
4.4
Data Exchange............................................................................................................13
4.5
Parameterization Data Handling....................................................................................14
4.6
Configuration Data Handling.........................................................................................15
4.7
Set Slave Address .......................................................................................................18
4.8
Parameter Read/Write with Call ....................................................................................18
4.9
Identification & Maintenance (I&M)................................................................................21
5
Diagnostics.....................................................................................................................23
5.1
Standard Diagnostics ...................................................................................................23
5.2
Additional Diagnostics Information ................................................................................23
6
Anybus Module Objects ..............................................................................................24
6.1
General Information .....................................................................................................24
6.2
Anybus Object (01h) ....................................................................................................25
6.3
Diagnostic Object (02h) ................................................................................................26
6.4
Network Object (03h) ...................................................................................................28
6.5
Network Configuration Object (04h)...............................................................................30
6.6
PROFIBUS DP-V0 Diagnostic Object (10h) ...................................................................32
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Table of Contents
7
Host Application Objects ............................................................................................34
7.1
General Information .....................................................................................................34
7.2
Modular Device Object (ECh)........................................................................................35
7.3
PROFIBUS DP-V1 Object (FDh) ...................................................................................36
A
Categorization of Functionality.................................................................................41
A.1
Basic...........................................................................................................................41
A.2
Extended.....................................................................................................................41
B
Implementation Details................................................................................................42
B.1
SUP-Bit Definition ........................................................................................................42
B.2
Anybus State Machine .................................................................................................42
B.3
Watchdog Behavior (Application Stopped) .....................................................................42
C
Error Handling................................................................................................................43
C.1
Translation of Anybus Error Codes................................................................................43
C.2
Other Errors ................................................................................................................43
D
GSD File Customization ..............................................................................................44
D.1
General.......................................................................................................................44
D.2
Device Identification.....................................................................................................44
D.3
Supported Hardware Features ......................................................................................45
D.4
Supported DP Features................................................................................................46
D.5
Supported Baud Rates .................................................................................................46
D.6
Maximum Responder Time for Supported Baud Rates....................................................47
D.7
Maximum Polling Frequency.........................................................................................47
D.8
I/O Related Keywords ..................................................................................................47
D.9
Definition of Modules....................................................................................................48
D.10
Parameterization Related Keywords..............................................................................53
D.11
Diagnostic Related Keywords .......................................................................................54
D.12
Identification & Maintenance Related Keywords .............................................................54
D.13
Status Diagnostics Messages .......................................................................................55
D.14
DP-V1 Related Keywords .............................................................................................56
D.15
Alarm Related Keywords ..............................................................................................56
E
Technical Specification ...............................................................................................57
E.1
Front View...................................................................................................................57
E.2
Functional Earth (FE) Requirements..............................................................................58
E.3
Power Supply ..............................................................................................................58
E.4
Environmental Specification..........................................................................................59
E.5
EMC Compliance.........................................................................................................59
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Table of Contents
F
Timing & Performance.................................................................................................60
F.1
General Information .....................................................................................................60
F.2
Internal Timing.............................................................................................................60
G
Backward Compatibility ..............................................................................................62
G.1
Initial Considerations....................................................................................................62
G.2
Hardware Compatibility ................................................................................................62
G.3
General Software.........................................................................................................68
G.4
Network Specific — PROFIBUS....................................................................................70
About this document
This document is intended to provide a good understanding of the functionality offered by the
Anybus CompactCom 40 PROFIBUS DPV1/DPV0. The document describes the features that
are specific to Anybus CompactCom 40 PROFIBUS DPV1/DPV0. For general information re-
garding Anybus CompactCom, consult the Anybus CompactCom design guides.
The reader of this document is expected to be familiar with high level software design and com-
munication systems in general. The information in this network guide should normally be suffi-
cient to implement a design. However if advanced PROFIBUS specific functionality is to be
used, in-depth knowledge of PROFIBUS networking internals and/or information from the offi-
cial PROFIBUS specifications may be required. In such cases, the persons responsible for the
implementation of this product should either obtain the PROFIBUS specification to gain suffi-
cient knowledge or limit their implementation in such a way that this is not necessary.
For additional related documentation and file downloads, please visit the support website at
www.anybus.com/support.
1.2
Related Documents
Document
Author
Document ID
Anybus CompactCom 40 Software Design Guide
HMS
HMSI-216–125
Anybus CompactCom M40 Hardware Design Guide
HMS
HMSI-216–126
Anybus CompactCom B40 Design Guide
HMS
HMSI-27-230
Anybus CompactCom Host Application Implementation
Guide
HMS
HMSI-27-334
PROFIBUS Profile Guidelines Part 1: Identification & Main-
tenance Functions
PNO
Specification for PROFIBUS Device Description and Device
Integration Volume 1: GSD (order. no. 2.122)
PNO
1.3
Document History
Version
Date
Description
1.00
2014-03-25
First official revision
1.10
2014-04-28
Added information on DP-V0
1.20
2014-08-11
Major updates
1.30
2015-11-13
Minor updates
2.0
2017-01-04
Moved from FM to DOX, M12 connectors added, misc. updates
2.1
2017-02-24
Minor corrections
2.2
2017-07-10
Added appendix on backward compatibility
Minor correction
2.3
2018-05-28
Misc. corrections
1.4
Document Conventions
Ordered lists are used for instructions that must be carried out in sequence:
1.
First do this
2.
Then do this
Unordered (bulleted) lists are used for:
•
Itemized information
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Instructions that can be carried out in any order
...and for action-result type instructions:
►
This action...
➨
leads to this result
Bold typeface indicates interactive parts such as connectors and switches on the hardware, or
menus and buttons in a graphical user interface.
Monospaced text is used to indicate program code and other
kinds of data input/output such as configuration scripts.
This is a cross-reference within this document: Document Conventions, p. 5
This is an external link (URL): www.hms-networks.com
This is additional information which may facilitate installation and/or operation.
This instruction must be followed to avoid a risk of reduced functionality and/or
damage to the equipment, or to avoid a network security risk.
Caution
This instruction must be followed to avoid a risk of personal injury.
WARNING
This instruction must be followed to avoid a risk of death or serious injury.
1.5
Document Specific Conventions
•
The terms “Anybus” or “module” refers to the Anybus CompactCom module.
•
The terms “host” or “host application” refer to the device that hosts the Anybus.
•
Hexadecimal values are written in the format NNNNh or 0xNNNN, where NNNN is the hex-
adecimal value.
•
A byte always consists of 8 bits.
•
The terms “basic” and “extended” are used to classify objects, instances and attributes.
1.6
Abbreviations
Abbreviation
Meaning
API
assigned packet interval
RPI
requested packet interval
T
target (in this case the module)
O
origin (in this case the master)
1.7
Trademark Information
Anybus
® is a registered trademark of HMS Industrial Networks AB.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
All other trademarks are the property of their respective holders.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
About the Anybus CompactCom 40 PROFIBUS
DPV1/DPV0
2.1
General
The Anybus CompactCom 40 PROFIBUS DPV1/DPV0 communication module provides instant
PROFIBUS conformance tested connectivity via the patented Anybus CompactCom host inter-
face. Any device that supports this standard can take advantage of the features provided by the
module, allowing seamless network integration regardless of network type.
This product conforms to all aspects of the host interface for Anybus CompactCom 40 modules
defined in the Anybus CompactCom 40 Hardware and Software Design Guides, making it fully
interchangeable with any other device following that specification. Generally, no additional net-
work related software support is needed, however in order to be able to take full advantage of
advanced network specific functionality, a certain degree of dedicated software support may be
necessary.
2.2
Features
•
Supports PROFIBUS DP-V1 and DP-V0
•
PROFIBUS connector (9-pin female D-Sub) or M12 connectors
•
Automatic baud rate detection
•
Max. read process data: 244 bytes
•
Max. write process data: 244 bytes
•
Max. process data (read + write, in bytes): 488 bytes
•
Generic and PROFIBUS specific diagnostic support
•
User Parameterization Data support
•
Set Slave Address support
•
ADI access via DP-V1 read/write services
•
Device identity customization
•
Example GSD file provided
•
Support for Modular Device Mode
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Fieldbus Conformance and Certification
9 (72)
3
Fieldbus Conformance and Certification
3.1
Fieldbus Conformance Notes
Using the GSD file supplied by HMS Industrial Networks AB, the module is precertified for net-
work compliance. However, since parameter changes which require deviations from the stand-
ard GSD file are necessary, a recertification is advised, though not mandatory.
For further information, please contact HMS Industrial Networks AB.
3.2
Certification
The following items are necessary to perform to obtain a certification:
Change PNO Ident Number:
The PNO Ident Number can be requested from PNO (PROFIBUS Nutzerorganisation e.V.). Re-
place the default PNO Ident Number with this. This is done by implementing the PROFIBUS
DP-V1 object (FDh), instance #1, attribute #1, and returning the PNO Ident Number when re-
ceiving a Get_Attribute request.
Add Node Address Information:
If the host application does not set a valid node address by messaging the Network Configura-
tion Object (04h), instance 1 (“Node Address”), the PROFIBUS Set Slave Address (SSA) serv-
ice is enabled.
If SSA functionality is enabled, it is mandatory to provide a mechanism for resetting the node
address to its default value (126). This is because it is possible to lock the value from the net-
work side. See Set Slave Address, p. 18 for more information.
Change Manufacturer Id, Order Id, serial number and revision information:
This is done by implementing the PROFIBUS DP-V1 object (FDh), instance #1, attributes #8 -
#12, and returning the corresponding attributes when receiving a Get_Attribute request.
The Manufacturer Id can be requested from PNO (PROFIBUS Nutzerorganisation e.V.).
Modify the GSD file:
Modify the PROFIBUS DP-V1 GSD file so that it corresponds to the changes made above.
In addition, all modules used in the application must be defined in the GSD file. For more infor-
mation, see Configuration Data Handling, p. 15.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
No additional network support code needs to be written in order to support the Anybus Com-
pactCom 40 PROFIBUS DPV1/DPV0, however certain restrictions must be taken into account:
•
Due to the nature of the PROFIBUS networking system, at least one ADI must be mapped
to Process Data.
•
Only ADIs with instance numbers less than 65026 can be accessed acyclically from the
network.
•
The host application must be able to provide a response to an ADI request within the time
period specified by the GSD file (DP-V1 Related Keywords, p. 56, “C1_Response_Time-
out”), or the master will terminate the connection and reparameterize the slave. The default
value for this parameter (i.e. the time specified by the example GSD file supplied by HMS
Industrial Networks AB) is 1 (one) second.
•
The order in which ADIs are mapped to Process Data is significant and must be replicated
in the PROFIBUS master when setting up the network communication (i.e. the I/O modules
must be set up in the same order, and with the same size and direction, as the mapped
ADIs). If not taken into account, the network connection establishment will fail and no com-
munication will take place.
•
The use of advanced PROFIBUS specific functionality may require in-depth knowledge in
PROFIBUS networking internals and/or information from the official PROFIBUS specifica-
tion (IEC 61158). In such cases, the ones responsible for the implementation of this product
should either obtain the PROFIBUS specification to gain sufficient knowledge or limit their
implementation is such a way that this is not necessary.
4.1.2
Support for DP-V1 and DP-V0
The Anybus CompactCom PROFIBUS module supports both DP-V1 and DP-V0. At delivery
the default settings give full DP-V1 functionality. However the PROFIBUS network master can
choose to limit the functionality to DP-V0 via the parametrization telegrams during startup.
4.1.3
Electronic Data Sheet (GSD)
On PROFIBUS, the characteristics of a device is stored in an ASCII data file with the suffix GSD.
This file is used by the PROFIBUS configuration tool when setting up the network.
HMS Industrial Networks AB provides an example GSD file, which corresponds to the default
settings in the module. However, due to the flexible nature of the Anybus CompactCom con-
cept, it is possible to alter the behavior of the product in a way that invalidates the example
GSD file.
The example GSD file supports full DP-V1 functionality, another GSD file is needed if the mod-
ule is to run only DP-V0 functionality.
See also...
•
Fieldbus Conformance Notes, p. 9
•
GSD File Customization, p. 44
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Network related communication settings are grouped in the Network Configuration Object (04h).
Node Address:
See Network Configuration Object (04h), p. 30 for more information
Baud Rate:
The baud rate is detected automatically by the module. The following baud rates are supported:
•
9.6 kbps
•
19.2 kbps
•
45.45 kbps
•
93.75 kbps
•
187.5 kbps
•
500 kbps
•
1.5 Mbps
•
3 Mbps
•
6 Mbps
•
12 Mbps
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
By default, the Anybus CompactCom module appears as a generic HMS Industrial Networks
AB device with the following network identity:
Vendor Name
“HMS Industrial Networks”
Model Name
“Anybus CompactCom 40 DP-V1”
Ident Number
1815h
It is possible to customize the network identity information so that the Anybus module appears
as a vendor specific implementation rather than a generic HMS Industrial Networks AB product.
The PROFIBUS I&M-functionality (Identification & Maintenance) provides a standard way of
gathering information about an I/O device. The I&M information is accessed by the master by
means of the Call State Machine using DP-V1 read/write services.
By default, Anybus module supports I&M records 0... 4 for slot #0 (which is the device itself).
Optionally, the host application can implement the commands Get_IM_Record and Set_IM_Re-
cord’-commands (PROFIBUS DP-V1 Object (FDh), p. 36) to support all I&M records for all slots.
See also...
•
PROFIBUS Profile Guidelines Part 1: Identification & Maintenance Functions
•
Network Configuration Object (04h), p. 30
•
PROFIBUS DP-V1 Object (FDh), p. 36
–
Attribute #1, PNO Ident Number
–
Command details for Get_IM_Record
–
Command details for Set_IM_Record
•
Device Identification, p. 44
•
Identification & Maintenance Related Keywords, p. 54
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Application Data Instances (ADIs)
ADIs can be accessed acyclically from the network using DP-V1 read/write services. The mod-
ule translates these services into object requests towards the Application Data Object. If the
host application responds with an error to such a request, the error code in the response will be
translated to DP-V1 standard.
If the Modular Device Object is implemented in the application, the addressing of ADIs is carried
out in accordance with the Modular Device Object. For more information, see Modular Device
Object (ECh), p. 35. If the Modular Device Object is not implemented, ADIs are mapped to slots
and indexes as follows:
Correlation:
ADI = slot • 255 + index + 1
slot = (ADI - 1) / 255
index = (ADI - 1) MOD 255
Examples:
ADI
Slot
Index
256
1
0
510
1
0
65025
254
254
The length parameter in the DP-V1 request specifies the number of bytes to read/write.
•
When reading more data than the actual size of the ADI, the response will only contain the
actual ADI data, i.e. no padding on the data is performed by the module.
•
When reading less data than the actual size of the ADI, only the requested amount of data
is returned by the module.
•
The maximum ADI data size that can be accessed is 240 bytes for acyclic DP-V1 read/
writes and 234 bytes for acyclic read/writes using the call service.
•
When writing to an ADI, the length parameter is not checked by the module, i.e. the host
application must respond with an error if the length differs from the actual size of the re-
quested ADI.
Due to technical reasons, it is generally not recommended to use ADI numbers 1... 255 since this
may cause trouble with certain PROFIBUS configuration tools.
See also..
•
GSD File Customization, p. 44
•
Implementation Details, p. 42
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Mapping an ADI to Write Process Data results in PROFIBUS input data, and mapping an ADI to
Read Process Data results in PROFIBUS output data. If the host application tries to map more
data than PROFIBUS permits, the module will go into the EXCEPTION state (exception code
06h) after “Setup Complete”.
See also..
•
GSD File Customization, p. 44
•
PROFIBUS DP-V1 Object (FDh), p. 36
4.5
Parameterization Data Handling
4.5.1
General Information
The master identifies itself to the slaves by sending Parameterization Data, specifying how the
slave shall operate (i.e. Master address, PNO-ID, Sync/Freeze capabilities etc.).
DP Standard
Parameters
DP-V1 Status Bytes
User Parameterization Data
Size
7 bytes
3 bytes
Dynamic
Defined by
IEC
IEC
Host application
Evaluated by
Module
Module
Host application
Supported in the example
HMS GSD file
Yes
Yes
No
User Parameterization Data is not supported by default. Optionally, User Parameterization Data
can be supported by implementing the attribute Parameterization Data (#2) in the PROFIBUS
DP-V1 Object (FDh). In such case, the example GSD file supplied by HMS must be modified.
The maximum amount of User Parameterization Data that can be handled by the module is 234
bytes.
See also...
•
GSD File Customization, p. 44
•
PROFIBUS DP-V1 Object (FDh), p. 36(Attribute #2, Parameterization Data)
•
Parameterization Related Keywords, p. 53
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
The User Parameterization Data must be evaluated by the host application. This is handled
through the attribute Parameterization Data (#2) in the PROFIBUS DP-V1 Object (FDh), p. 36..
Attribute Parameterization Data not implemented
If the Parameterization Data contains any User Parameterization Data, the module will reject
the Parameterization Data.
Attribute Parameterization Data implemented
The application must evaluate the contents of the attribute and provide a suitable response.
•
To accept the Parameterization Data, respond with no error code.
•
To reject the Parameterization Data, respond with one of the following error codes:
–
NOT_ENOUGH_DATA
–
TOO_MUCH_DATA
–
OUT_OF_RANGE
4.6
Configuration Data Handling
4.6.1
General Information
The Anybus module determines its Expected Configuration Data based on the ADI mapping
process. Alternatively, it can be specified by the host application by implementing the Get serv-
ice of the attribute configuration Data (#3) in the PROFIBUS DP-V1 Object (FDh), p. 36.
Implementing this attribute in the PROFIBUS DP-V1 Object (FDh) in the host application is
optional.
The maximum amount of configuration data that can be handled by the module is 244 bytes.
See also...
•
PROFIBUS DP-V1 Object (FDh), p. 36 (Attribute #3, Configuration Data)
•
I/O Related Keywords, p. 47
•
Definition of Modules, p. 48
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Using the Chk_Cfg service, the PROFIBUS master will send the Actual Configuration Data
needed for the application to the module. The module will compare the Actual Configuration Da-
ta with the Expected Configuration Data. In case of a mismatch, the module will send the Actual
Configuration Data to the host application for further evaluation.
Attribute Configuration Data not implemented
The module will calculate the Expected Configuration Data. The way this is done will depend on
whether the application has implemented the Modular Device Object or not. For more detailed
information...
•
Definition of Modules, p. 48 (Modular Device Object Implemented)
•
Parameterization Related Keywords, p. 53
In case of a mismatch between the Actual Configuration Data and the Expected Configuration
Data, the module will send a remap command to the application based on the Actual Configura-
tion Data.
If the application approves the new configuration, the module will accept it and go online.
If the application discards the remap command, the module will signal configuration fault on the
network.
For backward compatibility with the Anybus CompactCom 30 series, it is also possible for the
module to approve the configuration if the following criteria are met:
•
Actual Configuration Data is not in special format
•
The lengths of the Actual Configuration Data and the Expected Configuration Data are
equal
•
Bit 0 (ChkCfg mode) in byte 2 of the DP-V1 status is set to 1
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Attribute Configuration Data implemented
Expected Configuration Data is provided by the application. The format of the configuration data
is not specified or known by the module. The module will however calculate the total input and
output lengths based on the parts of the configuration that it can interpret. If the provided config-
uration data length does not match the length of all mapped ADIs, the module will enter EXCEP-
TION state.
If the Actual Configuration Data matches the Expected Configuration Data, the module will ap-
prove the configuration.
If the Actual Configuration Data does not match the Expected Configuration Data, and if bit 0
(ChkCfg mode) in byte 2 of the DP-V1 status is set to 1, the host application must evaluate the
contents of the Configuration Data attribute.
•
To accept the Configuration Data, respond with no error code.
If the new configuration affects the Process Data mapping, it is important that the
host application updates the Process Data before responding. Failure to observe
this may cause erroneous data to be sent to the bus on the next state shift.
Preferably, choose to reject the Actual Configuration Data and adapt to it by
restarting the Anybus module and then revise the Process Data map and/or the
Expected Configuration Data. Also note that the new configuration must exist in
the GSD file of the product.
Please note that if the application accepts the Configuration Data, but the length of the Ex-
pected Configuration Data is less than the length of the Actual Configuration Data, the con-
figuration will be rejected by the module.
•
To reject the Configuration Data, respond with one of the following error codes:
–
NOT_ENOUGH_DATA
–
TOO_MUCH_DATA
–
OUT_OF_RANGE
–
INVALID_STATE
–
NO_RESOURCES
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Set Slave Address
The module supports the Set Slave Address service, which enables a master or configuration
tool to set the node address from the network.
This service features a flag which specifies whether or not it is allowed to change the device ad-
dress from the network again at a later stage. If the service is accepted, the module saves the
value of this flag in nonvolatile memory; the only way to restore it again is by performing a Fac-
tory Default-reset on the Network Configuration Object (consult the general Anybus Compact-
Com 40 Software Design Guide for more information). This behavior is mandatory for the
application to pass PROFIBUS network certification.
The module will accept new settings received via this service under the following conditions:
•
The Device Address attribute (Network Configuration Object (04h)) is set to a value higher
than 125.
The SSA Enabled attribute (PROFIBUS DP-V1 Object (FDh))) is set to TRUE (or not
implemented).
The module is not in Data Exchange.
The module is addressed with the correct Ident Number.
No previous Set Slave Address request prevents the module from accepting the new
settings.
See also...
•
PROFIBUS DP-V1 Object (FDh), p. 36 (Attribute #4, SSA Enabled)
•
Supported DP Features, p. 46
It is possible to disable support for this service by implementing the SSA Enabled attribute in the
PROFIBUS DP-V1 Object (FDh). In such a case, a new GSD file must be created, and fieldbus
re-certification is necessary.
4.8
Parameter Read/Write with Call
4.8.1
General information
Parameter Read/Write with Call enables addressing of ADIs based on instance numbers rather
than Slot and Index. This is useful if the ADI implementation is primarily designed for a linear
addressing scheme as used on most other networks. It may also prove useful when using mas-
ters with limited addressing capabilities for slot 0, since such masters may otherwise have trou-
ble accessing ADI instances 1... 255.
Unlike the standard DP-V1 Read/Write service, Parameter Read/Write with Call uses the Call
application service. On the PROFIBUS telegram level, the Parameter Read with Call service re-
quest consists of a standard DP-V1 header, a Call header, and the ADI number. When received
by the module, this is translated into a standard object request towards the application data
object.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Parameter Read with Call Handling
The Parameter Read with Call service request looks as follows:
Byte #
Contents
Field Name
Value
Notes
1
DP-V1
Header
Function no.
5Fh
Indicates a DP-V1 Write service
2
Slot
00h
(must not be set to FFh)
3
Index
FFh
(fixed)
4
Length
06h
Size of telegram (Call Header + ADI
number)
5
Call Header
Ext. Function no.
08h
Call service
6
(reserved)
00h
(reserved, set to zero)
7
Subindex (high)
00h
Subindex 0002h, used when reading
8
Subindex (low)
02h
9
ADI number
ADI (high)
0000h... FFFFh
Number of the ADI which shall be read
10
ADI (low)
Upon reception, the module translates this into a Get_Attribute request towards the Application
Data Object. In the same manner, the response from the host application will be transformed in-
to an appropriate response telegram on PROFIBUS as follows:
Parameter Read with Call response:
Byte #
Contents
Field Name
Value
Notes
1
DP-V1
Header
Function no.
5Eh
Indicates a DP-V1 Write service
2
Slot
00h
(must not be set to FFh)
3
Index
FFh
(fixed)
4
Length
06... F0h
Size of telegram (Call Header + ADI
number + Data)
5
Call Header
Ext. Function no.
08h
Call service
6
(reserved)
00h
(reserved, set to zero)
7
Subindex (high)
00h
Subindex 0002h, used when reading
8
Subindex (low)
02h
9
ADI number
ADI (high)
0000... FFFFh
Number of the ADI which shall be read
10
ADI (low)
11...n
Data
(actual data)
-
Data returned from the host application
The max value of n = 244
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Parameter Write with Call Handling
The Parameter Write with Call service request looks as follows:
Byte #
Contents
Field Name
Value
Notes
1
DP-V1
Header
Function no.
5Fh
Indicates a DP-V1 Write service
2
Slot
00h
(must not be set to FFh)
3
Index
FFh
(fixed)
4
Length
06... F0h
Size of telegram (Call Header + ADI
number + Data)
5
Call Header
Ext. Function no.
08h
Call service
6
(reserved)
00h
(reserved, set to zero)
7
Subindex (high)
00h
Subindex 0001h, used when writing
8
Subindex (low)
01h
9
ADI number
ADI (high)
0000h... FFFFh
Number of the ADI which shall be read
10
ADI (low)
11...n
Data
(actual data)
-
Data which will be sent to the host
application
The max value of n = 244
Upon reception, the module translates this into a Set_Attribute request towards the Application
Data Object. In the same manner, the response from the host application will be transformed in-
to an appropriate response telegram on PROFIBUS as follows:
Parameter Write with Call response:
Byte #
Contents
Field Name
Value
Notes
1
DP-V1
Header
Function no.
5Eh
Indicates a DP-V1 Read service
2
Slot
00h
(must not be set to FFh)
3
Index
FFh
(fixed)
4
Length
06... F0h
Size of telegram (Call Header + ADI
number)
5
Call Header
Ext. Function no.
08h
Call service
6
(reserved)
00h
(reserved, set to zero)
7
Subindex (high)
00h
Subindex 0001h, used when reading
8
Subindex (low)
01h
9
ADI number
ADI (high)
0000... FFFFh
Number of the ADI which shall be read
10
ADI (low)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Identification & Maintenance (I&M)
4.9.1
General Information
Identification & Maintenance (I&M) provides a standard way of gathering information about an I/
O device. The I&M information can be accessed by the PROFIBUS master by means of acyclic
Record Data Read/Write services.
Default I&M0 Information:
IM Manufacturer ID
010Ch (HMS Industrial Networks)
IM Order ID
“ABCC 40-DPV1”
IM Serial Number
(unique serial number, set during manufacturing)
IM Hardware Revision
(Anybus hardware revision ID, set during manufacturing)
IM Software Revision
(Anybus software revision, set during manufacturing)
IM Revision Counter
(Revision counter)
IM Profile ID
F600h (Generic Device)
IM Profile Specific Type
0004h (Communication Module)
IM Version
0101h
IM Supported
001Eh (IM0..4 supported)
Optionally, the host application can customize the information for these I&M entries, or imple-
ment the support for the Get_IM_Record and Set_IM_Record commands to support all I&M re-
cord for all slots.
See also ...
•
PROFIBUS DP-V1 Object (FDh), p. 36
–
Command Details: Get_IM_Record
–
Command Details: Set_IM_Record
•
Network Configuration Object (04h), p. 30
4.9.2
I&M Data Structures
The I&M records uses the following data structures.
Re-
cord
Content
Size
Description/Comment
I&M0
Manufacturer Id
2
bytes
PROFIBUS DP-V1 Object (FDh), attribute #8 (‘Vendor ID/I&M Vendor
ID’)
Order Id
20
bytes
PROFIBUS DP-V1 Object (FDh), attribute #9 (‘I&M Order ID’)
Serial number
16
bytes
PROFIBUS DP-V1 Object (FDh), attribute #10 (‘I&M Serial number’)
Hardware
revision
2
bytes
PROFIBUS DP-V1 Object (FDh), attribute #11 (‘I&M Hardware
revision)’
Software
revision
4
bytes
PROFIBUS DP-V1 Object (FDh), attribute #12 (‘I&M Software
revision’)
Revision counter
2
bytes
PROFIBUS DP-V1 Object (FDh), attribute #13 (‘I&M Revision
counter’)
Profile Id
2
bytes
PROFIBUS DP-V1 Object (FDh), attribute #14 (‘I&M Profile ID’)
Profile specific
type
2
bytes
PROFIBUS DP-V1 Object (FDh), attribute #15 (‘I&M Profile specific
type’)
I&M1
Tag Function
32
bytes
(Data of this field can only be accessed from the network by the IO
Controller/Supervisor.)
Tag Location
22
bytes
(Data of this field can only be accessed from the network by the IO
Controller/Supervisor.)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
(Data of this field can only be accessed from the network by the IO
Controller/Supervisor.)
I&M3
Descriptor
54
bytes
(Data of this field can only be accessed from the network by the IO
Controller/Supervisor.)
I&M4
Signature
54
bytes
(Data of this field can only be accessed from the network by the IO
Controller/Supervisor.)
See also...
•
PROFIBUS DP-V1 Object (FDh), p. 36
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
PROFIBUS diagnostics contains two parts: standard diagnostics and extended diagnostics (op-
tional). The standard diagnostics are contained in the first 6 bytes of the diagnostics data tele-
gram and, optionally, extended diagnostics can follow after that.
The application defines whether to use transparent diagnostics using the DP-V0 diagnostic ob-
ject (10h), or to use the Anybus diagnostic object (02h). It is not possible to change type of diag-
nostics at runtime, thus it has to be defined in the indesign phase.
Extended diagnosis are produced by the Anybus module if any of the following events occur:
•
Configuration mismatch: if the configuration is calculated by the module, identifier related
and module status diagnosis will be sent to clarify in which of the slots the configuration is
faulty.
•
Application creates diagnostics using the DP-V0 diagnostic object (10h).
•
Application creates diagnostics using the diagnostic object (02h).
See also ...
•
PROFIBUS DP-V0 Diagnostic Object (10h), p. 32
•
Diagnostic Object (02h), p. 26
5.1
Standard Diagnostics
The Standard Diagnostics are handled automatically, with the exception of the following flags:
Ext Diag Overflow
This flag can be controlled by the host application via the attribute Ext Diag Overflow (#12) in
the PROFIBUS DP-V0 Diagnostic Object (10h). If the flag is set, it indicates that there is more
diagnostic data than the diagnostic telegram can hold (244 bytes).
Static Diag Flag
This flag can be controlled by the host application via the attribute Static Diag (#13) in the PRO-
FIBUS DP-V0 Diagnostic Object (10h). This flag is set if the application reports an error (only
applicable for event based communication). For more information, see Anybus CompactCom
40 Software Design Guide, “Application Status Register”.
5.2
Additional Diagnostics Information
5.2.1
Extended Diagnostics
The extended diagnostics can be divided into four groups.
Identifier Related
The diagnosis information is related to modules of a slave.
Channel Related
The diagnosis information informs about errors of channels within modules.
Device Related - Status
Model
The diagnosis telegram contains special slot based information that will be
transferred to the master.
Device Related - Alarm
Model
The diagnosis telegram contains device related information defined by alarms.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
24 (72)
6
Anybus Module Objects
6.1
General Information
This chapter specifies the Anybus Module Object implementation and how the objects corre-
spond to the functionality in the Anybus CompactCom 40 PROFIBUS DPV1/DPV0.
Standard Objects:
•
Anybus Object (01h), p. 25
•
Diagnostic Object (02h), p. 26
•
Network Object (03h), p. 28
•
Network Configuration Object (04h), p. 30
Network Specific Objects:
•
PROFIBUS DP-V0 Diagnostic Object (10h), p. 32
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
25 (72)
6.2
Anybus Object (01h)
Category
Basic
Object Description
This object assembles all common Anybus data, and is described thoroughly in the general Anybus
CompactCom 40 Software Design Guide.
Supported Commands
Object:
Get_Attribute
Instance:
Get_Attribute
Set_Attribute
Get_Enum_String
Object Attributes (Instance #0)
(Consult the general Anybus CompactCom 40 Software Design Guide for further information).
Instance Attributes (Instance #1)
Basic
#
Name
Access
Type
Value
1
Module type
Get
UINT16
0403h (Standard Anybus CompactCom 40)
2... 11
-
-
-
See the general Anybus CompactCom 40 Software De-
sign Guide for further information.
12
LED colors
Get
struct of:
Value: Color:
UINT8 (LED1A)
01h Green
UINT8 (LED1B)
02h Red
UINT8 (LED2A)
01h Green
UINT8 (LED2B)
02h Red
13...1-
6
LED status
Get
UINT8
See the general Anybus CompactCom 40 Software De-
sign Guide for further information.
Extended
#
Name
Access
Type
Value
17
Virtual attributes
Get/Set
-
See the general Anybus CompactCom 40 Software De-
sign Guide for further information.
18
Black list/white list
Get/Set
19
Network time
Get
UINT64
Not used (Always 0)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
26 (72)
6.3
Diagnostic Object (02h)
Category
Extended
Object Description
This object provides a standardised way of handling host application events, alarms, and diagnostics, and is
thoroughly described in the general Anybus CompactCom 40 Software Design Guide. In the case of PROFI-
BUS, each instance created in this object adds one Status PDU to the Extended Diagnostics.
Please note that this object cannot be used at the same time as the transparent diagnostics (DP-V0 diagnos-
tic object (10h)).
Supported Commands
Object:
Get_Attribute
Create
Delete
Instance:
Get_Attribute
Object Attributes (Instance #0)
#
Name
Access
Type
Value
Description
1... 4
-
-
-
See the general Anybus CompactCom
40 Software Design Guide for further
information.
11
Max no. of instances
Get
UINT16
6
One instance of type major unrecover-
able and five instances of other severity
types can be created.
12
Supported Functionality
Get
BITS32
1
Bit 0 = 1: Latching events are supported.
Instance Attributes (Instance #1...n)
Extended
The use of attribute #3 is optional; if not implemented, the module will use slot no. 0 (zero), and the ‘Severity’
and ‘Event Code’ attributes will be reported as application specific data. If implemented, a custom GSD file
may be required.
#
Name
Access
Type
Value
1
Severity
Get
UINT8
See “Severity” below
2
Event Code
Get
UINT8
See the general Anybus CompactCom 40 Software De-
sign Guide for further information.
3
NW specific extension
Get
Array of UINT8
Element
Color
0
(reserved)
1
(reserved)
2...57
Application Specific Field
4
Slot
Get
UINT16
See the general Anybus CompactCom 40 Software De-
sign Guide for further information.
5
ADI
Get
UINT16
6
Element
Get
UINT8
7
Bit
Get
UINT8
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
27 (72)
See also...
•
PROFIBUS DP-V1 Object (FDh), p. 36
•
Status Diagnostics Messages, p. 55
Severity
This parameter indicates the severity level of the event, and describes the kind of PROFIBUS diagnostics
generated for the different levels. It also indicates whether extended diagnostics are used by the instance.
For more information, see the Anybus CompactCom 40 Software Design Guide.
Severity Levels
#
Severity
Modular Device Object not
Implemented (and slot
number = 0)
Modular Device Object Implemented (and slot number >
0)
00h
Minor, recoverable
Status message.
Identifier related + channel related
For more information, see Additional Diagnostics Informa-
tion, p. 23
10h
Minor, unrecoverable
Status message.
Unrecoverable events cannot
be deleted.
20h
Major, recoverable
Status message.
30h
Major, unrecoverable
Causes a state-shift to EXCEPTION.
50h
Minor, latching
Diagnosis alarm.
See the Anybus CompactCom 40 Software Design Guide for more information.
60h
Major, latching
(other)
-
(reserved for future use)
Network Specific Error Codes (Latching Events)
In case of an unsuccessful create command for a latching event, the following network specific error codes
are returned.
Error Code
Description
8
Alarm type disabled
9
Too many active alarms
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
28 (72)
6.4
Network Object (03h)
Category
Basic
Object Description
This object contains network specific data for the module. It also controls the mapping of ADIs to the process
data part of the telegrams. For more information, consult the general Anybus CompactCom 40 Software De-
sign Guide.
The order in which ADIs are mapped to Process Data is significant and must be replicated in the PROFIBUS
master when setting up the network communication.
Supported Commands
Object:
Get_Attribute
Instance:
Get_Attribute
Set_Attribute
Get_Enum_String
Map_ADI_Write_Area
Map_ADI_Read_Area
Map_ADI_Write_Ext_Area
Map_ADI_Read_Ext_Area
Object Attributes (Instance #0)
(Consult the general Anybus CompactCom 40 Software Design Guide for further information)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
29 (72)
Instance Attributes (Instance #1)
Basic
#
Name
Access
Type
Value
1
Network type
Get
UINT16
0005h
2
Network type string
Get
Array of CHAR
“PROFIBUS DP-V1”
3
Data format
Get
ENUM
0001h (MSB first)
4
Parameter Data support
Get
BOOL
True
(This attribute indicates if the network supports acyclic
data services and must not be confused with PROFI-
BUS Parameterization Data.)
5
Write process data size
Get
UINT16
Current write process data size (in bytes)
Updated on every successful Map_ADI_Write_Area
Consult the general Anybus CompactCom 40 Software
Design Guide for further information.
6
Read process data size
Get
UINT16
Current read process data size (in bytes)
Updated on every successful Map_ADI_Read_Area
Consult the general Anybus CompactCom 40 Software
Design Guide for further information.
7
Exception Information
Get
UINT8
Additional PROFIBUS specific exception information is
presented here in case the Anybus module has shifted
to the EXCEPTION state.
Exception Information
This attribute holds additional information when the Anybus module shifts to the EXCEPTION state.
#
Value
00h
No information.
01h
The ADI mapping resulted in too much configuration data.
02h
The configuration data attribute in the PROFIBUS DP-V1 object contains too much data.
03h
Configuration error. The ‘Configuration Data’ attribute does not match the actual Process Data map.
04h
Reserved.
05h
Reserved.
06h
Implementation error. Support for the Set Slave Address (SSA) telegram has been disabled (‘SSA Enable’ attrib-
ute, PROFIBUS DP-V1 Object (FDh), p. 36), but no valid device address has been supplied by the application.
07h
Reserved.
08h
Reserved.
09h
Reserved.
0Ah
Reserved.
0Bh
Reserved.
0Ch
The Modular Device Object has mapped process data on slot 0.
0Dh
The Modular Device Object has mapped data on an empty slot.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
30 (72)
6.5
Network Configuration Object (04h)
Category
Basic
Object Description
This object contains network specific configuration parameters that may be configured by the end user.
A Reset command towards this object will cause the module to revert all instance values to their factory de-
fault values.
Supported Commands
Object:
Get_Attribute
Reset
Instance:
Get_Attribute
Set_Attribute
Get_Enum_String
Object Attributes (Instance #0)
(Consult the general Anybus CompactCom 40 Software Design Guide for further information).
Instance Attributes (Instance #1)
Basic
The module must be assigned a unique node address (a.k.a. device address) in order to be able to communi-
cate on the PROFIBUS network. Valid settings range from 0... 125. The node address is set either from the
network (SSA service) or from the application.
Address 126 is reserved for SSA functionality, see Set Slave Address, p. 18. This feature allows the device
address to be set from the PROFIBUS master. Default after factory reset is 126.
#
Name
Access
Data Type
Description
1
Name
Get
Array of
CHAR
“Node address”
(Multilingual, see page 31)
2
Data type
Get
UINT8
04h (= UINT8)
3
Number of elements
Get
UINT8
01h (one element)
4
Descriptor
Get
UINT8
07h (read/write/shared access)
5
Value
Get/Set
UINT8
Value
Meaning
0... 125
Node address
(other)
Get node address using SSA (default)
(Note that support for SSA can be globally disabled by imple-
menting the PROFIBUS object, see PROFIBUS DP-V1 Object
(FDh), p. 36)
6
Configured Value
Get
UINT8
Holds the configured value, which will be written to attribute #5
after the module has been reset.
If SSA is enabled (attribute 5 set to 126) the saved SSA address
is returned.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
31 (72)
Multilingual String
The instance name in this object is multilingual, and is translated based on the current language settings as
follows:
Instance
English
German
Spanish
Italian
French
1
IP address
IP-Adresse
Dirección IP
Indirizzo IP
Adresse IP
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
32 (72)
6.6
PROFIBUS DP-V0 Diagnostic Object (10h)
Object Description
Implementing this object makes it possible to create transparent diagnostic data, instead of using the stand-
ard diagnostic data.
For the diagnostic functionality to work correctly during the connection phase with the master, the application
must write zero bytes to attribute #1 in instance #1 before setting setup complete.
It is not possible to switch between the use of transparent diagnostics and the use of standard diagnostics at
runtime. The PROFIBUS DP-V0 Diagnostic Object (10h) object cannot be used at the same time as the Diag-
nostic Object (02h).
Supported Commands
Object:
Get_Attribute
Set_Attribute
Instance:
Get_Attribute
Set_Attribute
Object Attributes (Instance #0)
#
Name
Access
Type
Value
1
Name
Get
Array of CHAR
“PROFIBUS DP-V0 Diagnostic”
2
Revision
Get
UINT8
01h
3
Number of instances
Get
UINT16
0001h
4
Highest instance no.
Get
UINT16
0001h
12
Ext Diag Overflow
Get/Set
BOOL
False (Default): Ext Diag Overflow is cleared
True: Ext Diag Overflow is set
13
Static Diag
Get/Set
BOOL
False (Default): Static Diag is cleared
True: Static Diag is set
Instance Attributes (Instance #1)
Extended
#
Name
Access
Type
Value
1
Diagnostic Data
Get
Array of UINT8
Array of bytes, containing the diagnostic data. For more
information, see “Diagnostic Data Layout” below.
Diagnostic Data Layout
Data Byte
Contents
Description
0
Extended diagnostic data
flag
0 - No extended diagnostic data
1 - Extended diagnostic data is available
1 - 238
Diagnostic data
The user specific part of the diagnostic buffer
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Anybus Module Objects
33 (72)
Object Specific Error Codes
Number
Name
In Response to Command
01h
Diagnostic Object (02h) in
use
Set_Attribute
02h
Invalid extended diagnostic
data flag value
Set_Attribute
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
34 (72)
7
Host Application Objects
7.1
General Information
The objects listed in this chapter may optionally be implemented within the host application firm-
ware to expand the PROFIBUS implementation.
Standard Objects:
•
Application Object (see Anybus CompactCom 40 Software Design Guide)
•
Application Data Object (see Anybus CompactCom 40 Software Design Guide)
•
Modular Device Object (ECh), p. 35
Network Specific Object:
•
PROFIBUS DP-V1 Object (FDh), p. 36
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
35 (72)
7.2
Modular Device Object (ECh)
Category
Extended
Object Description
This object is used to describe a modular device. Modular devices consist of a backplane with a certain num-
ber of “slots”. The first slot is occupied by the “coupler” which contains the Anybus CompactCom module. All
other slots may be empty or occupied by modules.
Each instance of this object describes a slot in the modular device. Instance 1 corresponds to the coupler.
When mapping ADIs to process data, the application shall map the process data of each module in slot order.
If the application maps the process data in any other order, the Anybus CompactCom module will enter EX-
CEPTION state.
For more information, see Anybus CompactCom 40 Software Design Guide, “Modular Device Object (ECh)”
Supported Commands
Object:
Get_Attribute
Get_List
Instance:
-
Object Attributes (Instance #0)
#
Name
Access
Type
Value
1
Name
Get
Array of CHAR
“Modular device”
2
Revision
Get
UINT8
01h
3
Number of instances
Get
UINT16
Number of connected modules. For limitations, see
Number of slots (attribute #11)
4
Highest instance no.
Get
UINT16
Highest connected module
11
Number of slots
Get
UINT16
The maximum value according to PROFIBUS is 255 (0-
254).
However, due to the definition of the PROFIBUS config-
uration data, the maximum number of slots which can
be guaranteed to work is 40. Each slot can contain be-
tween 2 and 16 bytes of configuration data. The total
amount of configuration data must not exceed 244 bytes.
(If not all slots have process data, the number of slots
can be increased since empty slots only needs 1 byte
configuration data)
12
Number of ADIs per slot
Get
UINT16
The maximum value for this attribute is 255 for PROFI-
BUS, since Index only may have values in the range 0-
254.
However, for the application to be able to send ADI spe-
cific diagnostics for the whole ADI range, this value must
not exceed 64.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
36 (72)
7.3
PROFIBUS DP-V1 Object (FDh)
Category
Basic, extended
Object Description
This object implements PROFIBUS specific settings in the host application.
The implementation of this object is optional; the host application can support none, some, or all of the attrib-
utes specified below. The module will attempt to retrieve the values of these attributes during startup; if an at-
tribute is not implemented in the host application, simply respond with an error message (06h, Invalid
CmdExt[0]). In such cases, the module will use its default value.
If the module attempts to retrieve a value of an attribute not listed below, respond with an error message
(06h, Invalid CmdExt[0]).
During operation, the host application must always be able to respond to requests from the module. Respond
either with the requested data or an adequate error message. Never leave a request from the module
unattended.
Altering the default settings within this object may require a new GSD file, which in turn requires fieldbus
recertification.
See also...
•
Technical Specification, p. 57
•
Support for DP-V1 and DP-V0, p. 10
•
GSD File Customization, p. 44
•
Guideline Information & Maintenance functions
•
Anybus CompactCom Software Design Guide, “Error Codes”
Supported Commands
Object:
Get_Attribute
Get_IM_Record
Set_IM_Record
Instance:
Get_Attribute
Set_Attribute
Object Attributes (Instance #0)
#
Name
Access
Type
Value
1
Name
Get
Array of CHAR
“PROFIBUS DP-V1”
2
Revision
Get
UINT8
04h
3
Number of instances
Get
UINT16
0001h
4
Highest instance no.
Get
UINT16
0001h
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
37 (72)
Instance Attributes (Instance #1)
Basic
#
Name
Access
Type
Value
1
PNO Ident Number
Get
UINT16
PNO Ident Number (default = 1815h)
Extended
#
Name
Access
Type
Comment
2
Parameterization data
Set
Array of UINT8
The module attempts to forward the Parameterization
Data to this attribute during network startup.
Max number of elements in array: 244
3
Expected configuration
Get/Set
Array of UINT8
This attribute is used both to specify the Expected Con-
figuration Data, and for evaluation of the Actual Configu-
ration Data.
Max number of elements in array: 244
If this attribute doesn’t match the Process Data map, or
if it doesn’t fit into the Configuration Data Buffer, the
module will enter the EXCEPTION state (exception code
06h)
4
SSA enabled
Get
BOOL
This attribute enables/disables support for Set Slave
Address
Value:
Meaning:
True
Enabled (default)
False
Disabled
5 - 7
(not used)
-
-
( Used in Anybus CompactCom 30 series)
8
Manufacturer ID
Get
UINT16
Device Manufacturer ID (default = 010Ch)
9
Order ID
Get
Array of CHAR
Device Order ID, up to 20 characters (default = “ABCC
40 -DPV1”)
Maximum number of elements in array: 20
10
Serial Number
Get
Array of CHAR
Serial number, up to 16 characters. If not implemented,
the serial number from the Application Object (FFh), at-
tribute #3 will be used. If this attribute is also missing,
the Anybus CompactCom defaults to its production as-
signed serial number.
11
Hardware Revision
Get
UINT16
Hardware revision of the device.
Value:
Meaning:
0... FFFEh
Hardware revision
FFFFh
Indicates profile specific information
If not implemented, the module defaults to its hardware
functionality ID.
12
Software Revision
Get
Struct of:
CHAR (Type)
UINT8 (Major)
UINT8 (Minor)
UINT8 (Build)
Software revision of the device. If not implemented, the
module defaults to the Anybus firmware revision.
13
Revision Counter
Get
UINT16
Revision counter; a changed value of this counter marks
a change of the hardware or of its parameters. If not im-
plemented, the module defaults to 0 (zero).
14
Profile ID
Get
UINT16
Specifies the Profile ID.
Default: F600h (Generic Device)
The attribute does not affect the behavior of the module,
since the module does not handle profiles.
15
Profile specific type
Get
UINT16
Specifies the Profile specific type.
Default: 0004h (Communication Module)
The attribute does not affect the behavior of the module,
since the module does not handle profiles.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
38 (72)
#
Name
Access
Type
Comment
18
IM header
Get
Array of UINT8
This header will be sent to the master together with
I&M0... 4 for slot 0. The master is then required to supply
this information back with each write request to these
records.
If not implemented, the header will be filled with zeroes.
The maximum number of elements in the array is 10.
19
(not used)
Software Revision Structure
Member
Contents
Comments
CHAR
Letter
Meaning
-
“V”
Official release
“R”
Revision
“P”
Prototype
“U”
Under test (field test)
“T”
Test device
UINT8
Major version
Range: 0,,, 255
Functional enhancement
UINT8
Minor version
Range: 0,,, 255
Bug fix
UINT8
Internal change
Range: 0,,, 255
No impact on function
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
39 (72)
Command Details: Get_IM_Record
Category
Extended
Details
Command Code:
10h
Valid for:
Object
Description
This command is sent to the host application when the master (Class 1 or Class 2) asks for an I&M Record
other than I&M0... 4 for slot 0, and for all I&M Records for slots other than 0. If the command is rejected, the
original I&M-request from the PROFIBUS master will be rejected as well.
See also
•
Guideline Information & Maintenance functions.
•
Command Details
Field
Comments
CmdExt[0]
I&M Record index (0... 199)
CmdExt[1]
(reserved, ignore)
Msg_Data[0]
Slot number (0... 254)
Msg_Data[1... 3]
(reserved, ignore)
•
Response Details (Success)
Field
Comments
Msg_Data[0... 9]
I&M user specific header
Msg_Data[10... 63]
I&M Record; I&M parameters associated with the request
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Host Application Objects
40 (72)
Command Details: Set_IM_Record
Category
Extended
Details
Command Code:
11h
Valid for:
Object
Description
This command is sent to the host application when the master (Class 1 or Class 2) requests to update an I&M
Record other than I&M0... 4 for slot 0, and for all I&M Records for slots other than 0. If the command is re-
jected, the original I&M-request from the PROFIBUS master will be rejected as well.
See also
•
Guideline Information & Maintenance functions.
•
Command Details
Field
Comments
CmdExt[0]
I&M Record index (0... 199)
CmdExt[1]
(reserved, ignore)
Msg_Data[0]
Slot number (0... 254)
Msg_Data[1... 3]
(reserved, ignore)
Msg_Data[4... 13]
I&M user specific header.
Msg_Data[14... 67]
I&M Record; I&M parameters associated with the request
•
Response Details (Success)
(no data)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix A: Categorization of Functionality
41 (72)
A
Categorization of Functionality
The objects, including attributes and services, of the Anybus CompactCom and the application
are divided into two categories: basic and extended.
A.1
Basic
This category includes objects, attributes and services that are mandatory to implement or to
use. They will be enough for starting up the Anybus CompactCom and sending/receiving data
with the chosen network protocol. The basic functions of the industrial network are used.
Additional objects etc, that will make it possible to certify the product also belong to this
category.
A.2
Extended
Use of the objects in this category extends the functionality of the application. Access is given
to the more specific characteristics of the industrial network, not only the basic moving of data
to and from the network. Extra value is given to the application.
Some of the functionality offered may be specialized and/or seldom used. As most of the avail-
able network functionality is enabled and accessible, access to the specification of the industrial
network may be required.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix B: Implementation Details
42 (72)
B
Implementation Details
B.1
SUP-Bit Definition
The supervised bit (SUP) indicates that the network participation is supervised by another net-
work device. For PROFIBUS, this bit is set when any of the following conditions are fulfilled.
•
Parameterization and Configuration Data has been accepted (i.e. MS0 connection
established)
•
An MS2 connection is open
B.2
Anybus State Machine
The table below describes how the Anybus state machine relates to the PROFIBUS network
Anybus State
Description
WAIT_PROCESS
No MS0 connection
DP state = Power-On/WaitPrm/WaitCfg
MS2 connection may be open
ERROR
Not used
PROCESS_ACTIVE
Master Mode = Operate
DP State = DataExchange
MS0 connection established
MS2 connection may be open
IDLE
Master Mode = Clear
DP State = DataExchange
MS0 connection established
MS2 connection may be open
EXCEPTION
MS0, MS1 and MS2 connections will be closed.
The module will enter this state in the following cases:
•
Invalid Device Address and “SSA Enabled” = FALSE
•
Size of ‘Configuration Data’ attribute is larger than the size of the Configuration
Data Buffer
•
Major Unrecoverable event created in Diagnostic Object
•
Configuration Data does not match the mapped Process Data
B.3
Watchdog Behavior (Application Stopped)
If the application watchdog expires, the module will enter the EXCEPTION state, terminate all
open PROFIBUS connections (MS0, MS1 and MS2) and leave the network.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix C: Error Handling
43 (72)
C
Error Handling
C.1
Translation of Anybus Error Codes
When a DP-V1 request is received from the network, the module translates this request into an
object request to the application data object. When such requests are rejected by the host appli-
cation, the error code in the response is translated to DP-V1 standard as described in the table
below. Note that error code 2 will always be 0 when handling a CALL request.
Anybus Error Code
Resulting DP-V1 Error Codes
Error
Decode
Error Code 1
Error Code 2
Error Class
Error Code
‘Unsupported Object’
DP-V1 (128)
Access
Invalid area
Same as the Anybus
error code
‘Unsupported Instance’
Access
Invalid index
‘Unsupported Command’
Access
Access denied
‘Invalid CmdExt0’
Access
Invalid
parameter
‘Invalid CmdExt1’
Access
Invalid
parameter
‘Attribute not Setable’
Access
Access denied
‘Attribute not Getable’
Access
Access denied
‘Too Much Data’
Access
Write error
length
‘Not Enough Data’
Access
Write error
length
‘Out of range’
Access
Invalid range
‘Value too high’
Access
Invalid range
‘Value too low’
Access
Invalid range
‘Invalid State’
Access
State conflict
‘Out of Resources’
Resource
Resource busy
‘Object Specific Error’
Application
User specific
(10)
(All other Anybus error
codes)
Application
User specific
(11)
C.2
Other Errors
Error
Resulting DP-V1 Error Codes
Error
Decode
Error Code 1
Error Code 2
Error Class
Error Code
ADI truncated
DP-V1 (128)
Application
User specific
(12)
0
No free source IDs
Resource
Resource busy
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
44 (72)
D
GSD File Customization
D.1
General
The GSD file specifies the characteristics of the device, and is used by the PROFIBUS configu-
ration tool when setting up the network.
HMS provides an example GSD file, which corresponds to the default settings in the module.
However, due to the flexible nature of the Anybus CompactCom concept, it is possible to alter
the behavior of the product in a way that invalidates the example GSD file. In such case, a cus-
tom GSD file must be created, and fieldbus recertification is necessary.
This chapter is intended to provide a brief overview of the GSD entries that may need alteration,
and how they correspond to settings within the Anybus module. Some of the entries should not
be changed, and the others are divided in the same way as the objects and object attributes, in-
to the groups Basic and Extended.
For further information, consult the Specification for PROFIBUS Device Description and Device
Integration Volume 1: GSD (order. no. 2.122).
The user is expected to have sufficient knowledge in the PROFIBUS networking system to
understand the concepts involved when performing the changes specified in this chapter. In case
of uncertainties, send the customized GSD file to HMS for verification.
D.2
Device Identification
D.2.1
General
By default, the module will appear as a generic Anybus implementation (“Anybus CompactCom
40 DPV1”) from HMS Industrial Networks (PROFIBUS ident no. 1815h).
However, the identity of the module can be customized to appear as a vendor specific imple-
mentation by creating a custom GSD file and implementing the attribute PNO Ident Number
(#1) in the PROFIBUS DP-V1 Object (FDh), p. 36.
Contact PNO to obtain a unique Ident Number.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
45 (72)
D.2.2
GSD File Entries
; Device identification
Vendor_Name
= ""
Model_Name
= ""
Revision
= ""
Ident_Number
=
Protocol_Ident
= 0
; DP protocol
Station_Type
= 0
; Slave device
FMS_supp
= 0
; FMS not supported
Slave_Family
= 0
; General device
Hardware_Release
= "Version "
Software_Release
= "Version "
Basic
Setting
Description
Vendor name as text (e.g. “HMS Industrial Networks”)
Product name as text (e.g. “Anybus CompactCom DPV1”)
Product revision (major.minor) (e.g. “1.01”)
PNO Ident Number in HEX. Written as 0xNNNN, where NNNN is the hexadecimal value.
Hardware revision (major.minor) (e.g. “Version 1.00”)
Software revision (major.minor) (e.g. “Version 1.00”)
D.2.3
Related Information
•
Device Identity, p. 12
•
PROFIBUS DP-V1 Object (FDh), p. 36, attribute #1
D.3
Supported Hardware Features
D.3.1
General
Do not change the standard settings.
D.3.2
GSD File Entries
; Supported hardware features
Redundancy = 0 ; not supported
Repeater_Ctrl_Sig = 2 ; TTL
24V_Pins = 0 ; not connected
Implementation_Type = "NP40"
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
46 (72)
D.4
Supported DP Features
D.4.1
GSD File Entries
; Supported DP features
Freeze_Mode_supp = 1
Sync_Mode_supp = 1
Auto_Baud_supp = 1
Set_Slave_Add_supp =
Fail_Safe = 1
Extended
Setting
Description
This value must be set to match the ‘SSA enable’-attribute in the PROFIBUS DP-V1 Object
(FDh), p. 36:
0: ‘SSA enabled’-attribute set to FALSE
1: ‘SSA enabled’-attribute set to TRUE (or not implemented)
D.4.2
Related Information
•
Set Slave Address, p. 18
•
PROFIBUS DP-V1 Object (FDh), p. 36
D.5
Supported Baud Rates
D.5.1
General
Do not change the standard settings.
D.5.2
GSD File Entries
; Supported baud rates
9.6_supp = 1
19.2_supp = 1
45.45_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
47 (72)
D.6
Maximum Responder Time for Supported Baud Rates
D.6.1
General
Do not change the standard settings.
D.6.2
GSD File Entries
; Maximum responder time for supported baud rates
MaxTsdr_9.6 = 15
MaxTsdr_19.2 = 15
MaxTsdr_45.45 = 15
MaxTsdr_93.75 = 15
MaxTsdr_187.5 = 15
MaxTsdr_500 = 15
MaxTsdr_1.5M = 25
MaxTsdr_3M = 50
MaxTsdr_6M = 100
MaxTsdr_12M = 200
D.7
Maximum Polling Frequency
D.7.1
General
Use the GSD file default value (1)
D.7.2
GSD File Entries
; Maximum polling frequency
Min_Slave_Intervall = 1 ; 100 µs
D.8
I/O Related Keywords
D.8.1
GSD File Entries
; I/O related keywords
Modular_Station = 1
Max_Module =
Max_Input_Len =
Max_Output_Len =
Appendix D: GSD File Customization
48 (72)
D.9
Definition of Modules
D.9.1
General
These parameters need to be altered if customizing module names, if the Configuration Data
attribute
(PROFIBUS DP-V1 Object (FDh), p. 36 ) has been implemented.
D.9.2
GSD File Entries
; Definition of modules
Module = ""
EndModule
Basic
Setting
Description
Name of module
Configuration Identifier; hexadecimal value (written as NNh where NN is the hexadecimal val-
ue) specifying the properties of the module (see below).
Decimal number, must be unique for each module. Max. 16 bits when converted to
hexadecimal.
D.9.3
Identifier Explanation
The identifiers will differ slightly, depending on whether the Modular Device Object has been im-
plemented or not. Both possibilities are exemplified below. Big endian format is used
throughout.
Modular Device Object Not Implemented
If the modular device object is NOT implemented in the application, every slot in the configura-
tion is seen as an ADI. The module will calculate the expected configuration as follows:
First Configuration Identifier for Each Slot
Header
Bit 0 - 3:
Length of vendor specific data
0000 = No data
0001 - 1110 = 1 - 14 bytes
1111 = No data
Bit 4 - 5:
Special format (00)
Bit 6 - 7:
Input/output
00 = No I/O data specification follows
01 = One byte I/O data specification for input follows
10 = One byte I/O data specification for output follows
11 = Two bytes I/O data specification follows (not valid)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
49 (72)
I/O Data Specification
Bit 0 - 5:
Data length (max 64 elements)
000000 = 1 byte/word
111111 = 64 bytes/words
Bit 6:
Size
0 = Byte
1 = Word
Bit 7:
Data consistency
0 = Byte/word
1 = Whole length (The module will set this bit to 1 if the module only contains one ADI or
only one ADI input and output)
Vendor Specific Data
Byte 0:
Bit 7:
More cfg follows
Byte 1 - 2:
ADI number
Following Configuration Identifiers (If More than 64 Elements in One ADI)
Note: the module will start a new configuration identifier when: size changes, total data length
exceeds 64 elements or when the ADI index is full.
Header
Bit 0 - 3:
Length of vendor specific data
0000 = No data
0001 - 1110 = 1 - 14 bytes
1111 = No data
Bit 4 - 5:
Special format (00)
Bit 6 - 7:
Input/output
00 = No I/O data specification follows
01 = One byte I/O data specification for in-
put follows
10 = One byte I/O data specification for out-
put follows
11 = Two bytes I/O data specification follows
(not valid)
I/O Data Specification
Bit 0 - 5:
Data length (max 64 elements)
000000 = 1 byte/word
111111 = 64 bytes/words
Bit 6:
Size
0 = Byte
1 = Word
Bit 7:
Data consistency
0 = Byte/word
1 = Whole length (The module will set this bit to 1 if the module only contains one ADI or
only one ADI input and output)
Vendor Specific Data
Byte 0:
Bit 7:
More cfg follows
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
50 (72)
Example
The application maps the following ADI’s to process data:
ADI Number
Direction
Data Type
Number of Elements
300
Input
UINT8
2
600
Output
UINT8
66
The expected configuration will then look as follows:
[0x43 0x81 0x00 0x2C 0x01] (Slot 1)
[0x83 0xBF 0x80 0x58 0x02] [0x81 0x81 0x00] (Slot 2)
GSD Entries
Modular_Station = 1
Modul_Offset
= 1
DPV1_Data_Types = 0
Chk_Cfg_Mode
= 0
Max_Module
= 48
(244/5=48 min conf data to describe one ADI)
; Definition of modules
Module = "ADI 300" 0x43,0x81,0x00,0x2C,0x01;
1
EndModule
;
Module = "ADI 600" 0x83,0xBF,0x80,0x58,0x02,0x81,0x81,0x00;
2
EndModule
Modular Device Object Implemented
If the modular device object is implemented in the application, every slot in the configuration is
seen as a module containing one or several ADI’s. Note that it is not allowed to have any ADIs
mapped on the coupler (slot 0).
The module will calculate the expected configuration as follows:
First Configuration Identifier for a Specific Module with I/O Data
Header
Bit 0 - 3:
Length of vendor specific data
0000 = No data
0001 - 1110 = 1 - 14 bytes
1111 = No data
Bit 4 - 5:
Special format (00)
Bit 6 - 7:
Input/output
00 = No I/O data specification follows
01 = One byte I/O data specification for input follows
10 = One byte I/O data specification for output follows
11 = Two bytes I/O data specification follows
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
51 (72)
I/O Data Specification
Bit 0 - 5:
Data length (max 64 elements)
000000 = 1 byte/word
111111 = 64 bytes/words
Bit 6:
Size
0 = Byte
1 = Word
Bit 7:
Data consistency
0 = Byte/word
1 = Whole length (The module will set this bit to 1 if the module only contains one ADI or
only one ADI input and output)
Vendor Specific Data
Byte 0:
Bit 0 -3:
Bit 7:
No. of output ADI index follows
More config for this slot follows
Byte 1 - 2:
Module ID
Byte 3 - 13:
ADI index in the module, i.e. which ADIs within a slot that are mapped to this module (1
byte for each ADI, outputs first)
Following Configuration Identifiers
The module will start a new configuration identifier when: size changes, total data length ex-
ceeds 64 elements or when the ADI index is full.
Header
Bit 0 - 3:
Length of vendor specific data
0000 = No data
0001 - 1110 = 1 - 14 bytes
1111 = No data
Bit 4 - 5:
Special format (00)
Bit 6 - 7:
Input/output
00 = No I/O data specification follows
01 = One byte I/O data specification for input follows
10 = One byte I/O data specification for output follows
11 = Two bytes I/O data specification follows
I/O Data Specification
Bit 0 - 5:
Data length (max 64 elements)
000000 = 1 byte/word
111111 = 64 bytes/words
Bit 6:
Size
0 = Byte
1 = Word
Bit 7:
Data consistency
0 = Byte/word
1 = Whole length (The module will set this bit to 1 if the module only contains one ADI or
only one ADI input and output)
Vendor Specific Data
Byte 0:
Bit 0 -3:
Bit 7:
No. of output ADI index follows
More config for this slot follows
Byte 1 - 13:
ADI index in the module, i.e. which ADIs within a slot that are mapped to this module (1
byte for each ADI, outputs first)
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
52 (72)
Configuration Identifier for a Specific Module Without I/O Data
Header
Bit 0 - 3:
Length of vendor specific data
0003 = 3 bytes
Bit 4 - 5:
Special format (00)
Bit 6 - 7:
Input/output
00 = No I/O
Vendor Specific Data
Byte 0:
Reserved
Byte 1 - 2:
Module ID
Configuration Identifier for an Empty Slot
Header
Bit 0 - 3:
Length of vendor specific data
0000 = No data
Bit 4 - 5:
Special format (00)
Bit 6 - 7:
Input/output
00 = No I/O
Example
The application maps the following ADI’s to process data:
Slot
Module
Module ID
ADI Range
0
Coupler
0x00000001
1 - 50
1
No 1 (module with input data)
0x00000002
51 - 100
2
No 2 (module without I/O)
0x00000003
101 - 150
3
Empty Slot
0x00000000
151 - 200
4
No 4 (Module with both input and output data)
0x00000004
201 - 250
The application maps the following ADI’s to process data:
ADI Number
Direction
Data Type
Number of Elements
51
Input
UINT8
2
210
Output
UINT16
1
211
Output
UINT16
1
220
Input
UINT16
1
The expected configuration will then look as follows:
[0x44 0x81 0x00 0x02 0x00 0x00] (Slot 1 - ADI 51)
[0x03 0x00 0x03 0x00] (Slot 2 - Module without I/O data)
[0x00] (Slot 3 - empty slot)
[0xC6 0x41 0xC0 0x02 0x04 0x00 0x09 0x0A 0x13] (Slot 4 - ADI 210, 211, 220)
GSD Entries
Modular_Station = 1
Modul_Offset
= 1
DPV1_Data_Types = 0
Chk_Cfg_Mode
= 0
Max_Module
= 40
Number of slots in Modular object
; Definition of modules
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
53 (72)
Module = "No 1" 0x44,0x81,0x00,0x02,0x00,0x00;
1
EndModule
;
Module = "No 2" 0x03,0x00,0x03,0x00;
2
EndModule
;
Module = "Empty slot" 0x00;
3
EndModule
;
Module = "No 4" 0xC6,0x41,0xC0,0x02,0x04,0x00,0x09,0x0A,0x13;
4
EndModule
;
D.10
Parameterization Related Keywords
D.10.1
General
These parameters generally only need to be altered in advanced implementations which re-
quires the use of User Parameterization Data. The details about such implementations are be-
yond the scope of this document and requires in-depth knowledge in the PROFIBUS
networking system.
D.10.2
GSD File Entries
; Parameterization related keywords
Max_User_Prm_Data_Len
=
Ext_User_Prm_Data_Const(0)
=
Extended
Setting
Unit
Description
bytes
Size of User Parameterization Data
-
Actual User Parameterization Data as hexadecimal values.
The first three bytes are fixed and should be set to C0h, 00h, 00h.
D.10.3
Related Information
•
PROFIBUS DP-V1 Object (FDh), p. 36
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
54 (72)
D.11
Diagnostic Related Keywords
D.11.1
GSD File Entries
; Diagnostic related keywords
Max_Diag_Data_Len =
Basic
Setting
Unit
Description
bytes
D.11.2
Related Information
•
PROFIBUS DP-V1 Object (FDh), p. 36
•
Diagnostic Object (02h), p. 26
•
Diagnostics, p. 23
D.12
Identification & Maintenance Related Keywords
D.12.1
GSD File Entries
; Identification & Maintenance related keywords
Ident_Maintenance_supp = <1>
Basic
Setting
Description
1: I&M supported
D.12.2
Related Information
•
PROFIBUS DP-V1 Object (FDh), p. 36
•
Device Identity, p. 12
•
Network Configuration Object (04h), p. 30
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
55 (72)
D.13
Status Diagnostics Messages
D.13.1
General
These settings may need alteration when the “NW specific extension” of the Diagnostic Object
is used. It is generally recommended to remove diagnostic codes which are not used by the im-
plementation (e.g. remove “Value (48) = ‘Voltage’” if this code is not applicable for the end
product).
D.13.2
GSD File Entries
;Status diagnostic messages
Unit_Diag_Area=16-17
Value(0) = "Status not changed"
Value(1) = "Status appears"
Value(2) = "Status disappears"
Unit_Diag_Area_End
Unit_Diag_Area = -
Value() = ""
Value() = ""
Value() = ""
...
Value() = ""
Unit_Diag_Area_End
Unit_Diag_Area = -
Value() = ""
Value() = ""
Value() = ""
...
Value() = ""
Unit_Diag_Area_End
Unit_Diag_Area = -
Value() = ""
Value() = ""
Value() = ""
...
Value() = ""
Unit_Diag_Area_End
Extended
Setting
Description
These settings specify the bit range to associated with and .
Value
String associated with the value of
D.13.3
Related Information
•
Diagnostic Object (02h), p. 26
•
Diagnostics, p. 23
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix D: GSD File Customization
56 (72)
D.14
DP-V1 Related Keywords
D.14.1
GSD File Entries
; DPV1 related keywords
DPV1_Slave = 1
Check_Cfg_Mode = 1
C1_Read_Write_Supp = 1
C1_Max_Data_Len =
C1_Response_Timeout =
C2_Read_Write_Supp = 1
C2_Max_Data_Len =
C2_Response_Timeout =
C2_Max_Count_Channels = 1
Max_Initiate_PDU_Length = 52
Basic
Setting
Unit
Description
bytes
10 ms
bytes
1: I&M supported
D.15
Alarm Related Keywords
D.15.1
General
Do not change the standard settings.
The application cannot influence these settings. Changing the keywords may result in errors
when making a Conformance test.
D.15.2
GSD File Entries
; Alarm
Extra_Alarm_SAP_supp
= 1
; Do not change
Alarm_Sequence_Mode_Count
= 32
; Max. allowed value
Alarm_Type_Mode_supp
= 1
Diagnostic_Alarm_supp
= 1
Process_Alarm_supp
= 0
Pull_Plug_Alarm_supp
= 0
Status_Alarm_supp
= 0
Update_Alarm_supp
= 0
Manufacturer_Specific_Alarm_supp
= 0
Diagnostic_Alarm_required
= 0
Process_Alarm_required
= 0
Pull_Plug_Alarm_required
= 0
Status_Alarm_required
= 0
Update_Alarm_required
= 0
Manufacturer_Specific_Alarm_required
= 0
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix E: Technical Specification
57 (72)
E
Technical Specification
E.1
Front View
E.1.1
Front View, PROFIBUS Connector
#
Item
1
Operation Mode
1
2
3
5
6
9
1
2
Status
3
PROFIBUS Connector, 9-pin
female D-Sub
E.1.2
Front View, M12 Connectors
#
Item
1
Network Status LED
1
2
3
4
2
Module Status LED
3
M12 Female Connector
4
M12 Male Connector
E.1.3
Operation Mode
LED State
Indication
Comments
Off
Not online / No power
-
Green
Online, data exchange
-
Flashing Green
Online, clear
-
Flashing Red (1
flash)
Parameterization error
See Parameterization Data Handling, p. 14
Flashing Red (2
flashes)
PROFIBUS Configuration
error
See Configuration Data Handling, p. 15
E.1.4
Status
LED State
Indication
Comments
Off
Not initialized
Anybus state = SETUP or NW_INIT
Green
Initialized
Anybus module has left the NW_INITstate
Flashing Green
Initialized, diagnostic event
(s) present
Extended diagnostic bit is set
Red
Exception error
Anybus state = EXCEPTION
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix E: Technical Specification
58 (72)
E.1.5
PROFIBUS Connector (DB9F)
The current drawn from this pin will affect the total power consumption. To simplify develop-
ment, the output supplies up to 60 mA when operated in room temperature (20 - 22 °C), which
is sufficient to power e.g. master simulators etc. During normal operating conditions (or higher
temperatures), i.e.in an industrial environment, the specified max. current for this output is 10
mA. See also Power Consumption, p. 59.
Pin
Signal
Description
1
-
-
2
-
-
3
B Line
Positive RxD/TxD, RS485 level
4
RTS
Request to send
5
GND Bus
Ground (isolated)
6
+5 V Bus Output
+5 V termination power (isolated, short-circuit protected)
7
-
-
8
A Line
Negative RxD/TxD, RS485 level
9
-
-
Housing
Cable Shield
Internally connected to the Anybus protective earth via cable shield fil-
ters according to the PROFIBUS standard.
E.1.6
M12 Connectors, Code B
The female M12 connector is used when modules are used in a daisy-chain topology.
Pin
Name (Male/
Female)
Male
Female
1
NC / P5V
Not connected
Power Supply, 5V
DC
1
2
3
4
5
2
1
4
3
5
Male
Female
2
RxD/TxD-P (A) /
RxD/TxD-P (A)
Receive/Transmit
negative
Receive/Transmit
negative
3
NC / DGND
Not Connected
Power ground, 0 V
4
RxD/TxD-P (B) /
RxD/TxD-P (B)
Receive/Transmit
positive
Receive/Transmit
positive
5
(Thread)
Shield
Shield
Shield
E.2
Functional Earth (FE) Requirements
In order to ensure proper EMC behavior, the module must be properly connected to functional
earth via the FE pad / FE mechanism described in the general Anybus CompactCom M40 Hard-
ware Design Guide.
HMS Industrial Networks AB does not guarantee proper EMC behaviour unless these FE re-
quirements are fulfilled.
E.3
Power Supply
E.3.1
Supply Voltage
The module requires a regulated 3.3V power source as specified in the general Anybus Com-
pactCom M40 Hardware Design Guide.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix E: Technical Specification
59 (72)
E.3.2
Power Consumption
The Anybus CompactCom 40 PROFIBUS DPV1/DPV0 is designed to fulfil the requirements of
a Class A module. For more information about the power consumption classification used on
the Anybus CompactCom platform, consult the general Anybus CompactCom Hardware Design
Guide.
At 12 Mbit the current hardware design consumes up to 200 mA. This value is valid under the
condition that no current is being drawn from bus connector pin 6 (+5 V termination power; see
PROFIBUS Connector (DB9F), p. 58
It is strongly advised to design the power supply in the host application based on the power con-
sumption classifications described in the general Anybus CompactCom Hardware Design Guide,
and not on the exact power requirements of a single product.
In line with HMS policy of continuous product development, we reserve the right to change the
exact power requirements of this product without prior notification. Note however that in any
case, the Anybus CompactCom 40 PROFIBUS DPV1/DPV0 will remain as a Class A module.
E.4
Environmental Specification
Consult the Anybus CompactCom Hardware M40 Design Guide for further information.
E.5
EMC Compliance
Consult the Anybus CompactCom Hardware M40 Design Guide for further information.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix F: Timing & Performance
60 (72)
F
Timing & Performance
F.1
General Information
This chapter specifies timing and performance parameters that are verified and documented for
the Anybus CompactCom 40 PROFIBUS DPV1/DPV0.
The following timing aspects are measured:
Category
Parameters
Page
Startup Delay
T1, T2
60
NW_INIT Handling
T100
60
Event Based WrMsg Busy Time
T103
60
Event Based Process Data Delay
T101, T102
61
For further information, please consult the Anybus CompactCom 40 Software Design Guide.
F.2
Internal Timing
F.2.1
Startup Delay
The following parameters are defined as the time measured from the point where /RESET is re-
leased to the point where the specified event occurs.
Parameter
Description
Max.
Unit.
T1
The Anybus CompactCom 40 PROFIBUS DPV1/DPV0 module
generates the first application interrupt (parallel mode)
7.1
ms
T2
The Anybus CompactCom 40 PROFIBUS DPV1/DPV0 module is
able to receive and handle the first application telegram (serial
mode)
7.1
ms
F.2.2
NW_INIT Handling
This test measures the time required by the Anybus CompactCom 40 PROFIBUS DPV1/DPV0
module to perform the necessary actions in the NW_INIT-state.
Parameter
Conditions
No. of network specific commands
Max.
No. of ADIs (single UINT8) mapped to Process Data in each direction. (If the network
specific maximum is less than the value given here, the network specific value will be
used.)
32
Event based application message response time
> 1 ms
Ping-pong application response time
> 10 ms
No. of simultaneously outstanding Anybus CompactCom commands that the applica-
tion can handle
1
Parameter
Description
Communication
Max.
Unit.
T100
NW_INIT handling
Event based modes
14.6
ms
F.2.3
Event Based WrMsg Busy Time
The Event based WrMsg busy time is defined as the time it takes for the module to return the
H_WRMSG area to the application after the application has posted a message.
Parameter
Description
Min.
Max.
Unit.
T103
H_WRMSG area busy time
2.8
7.2
μs
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix F: Timing & Performance
61 (72)
F.2.4
Event Based Process Data Delay
“Read process data delay” is defined as the time from when the last bit of the network frame
has been received by the network interface, to when the RDPDI interrupt is asserted to the
application.
“Write process data delay” is defined in two different ways, depending on network type.
•
For software stack based cyclic/polled networks, it is defined as the time from when the
module exchanges write process data buffers, to when the first bit of the new process data
frame is sent out on the net work.
•
For COS (Change Of State) networks, it is defined as the time from when the application
exchanges write process data buffers, to when the first bit of the new process data frame is
sent out on the network.
Parameter
Description
Measured Time
Unit
Comment
T101
Read process data delay
380
ns
Time from last input
bit received until
nIRQ goes active on
the chip
T102
Write process data delay
1.1
μs
Time from when the
Anybus Compact-
Com module ex-
changes write
process data buffers,
to when the first bit of
the new process data
frame is sent out on
the network interface
towards the PHY.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
62 (72)
G
Backward Compatibility
The Anybus CompactCom M40 series of industrial network modules have significantly better
performance and include more functionality than the modules in the Anybus CompactCom 30
series. The 40 series is backward compatible with the 30 series in that an application developed
for the 30 series should be possible to use with the 40 series, without any major changes. Also
it is possible to mix 30 and 40 series modules in the same application.
This appendix presents the backwards compatibility issues that have to be considered for Any-
bus CompactCom 40 PROFIBUS DPV1/DPV0, when designing with both series in one applica-
tion, or when adapting a 30 series application for the 40 series.
G.1
Initial Considerations
There are two options to consider when starting the work to modify a host application developed
for Anybus CompactCom 30-series modules to also be compatible with the 40-series modules:
•
Add support with as little work as possible i.e. reuse as much as possible of the current
design.
–
This is the fastest and easiest solution but with the drawback that many of the new fea-
tures available in the 40-series will not be enabled (e.g. enhanced and faster commu-
nication interfaces, larger memory areas, and faster communication protocols).
–
You have to check the hardware and software differences below to make sure the host
application is compatible with the 40-series modules. Small modifications to your cur-
rent design may be needed.
•
Make a redesign and take advantage of all new features presented in the 40-series.
–
A new driver and host application example code are available at www.anybus.com/
starterkit40 to support the new communication protocol.This driver supports both 30-
series and 40-series modules.
–
You have to check the hardware differences below and make sure the host application
is compatible with the 40-series modules.
This documentation only deals with differences between the 30-series and the 40-series. For a
description of new and enhanced functionality in the Anybus CompactCom 40-series, please
consult our support pages, where you can find all documentation.
Link to support page: www.anybus.com/support.
G.2
Hardware Compatibility
Anybus CompactCom is available in three hardware formats; Module, Chip, and Brick.
G.2.1
Module
The modules in the 30-series and the 40-series share physical characteristics, like dimensions,
outline, connectors, LED indicators, mounting parts etc. They are also available as modules
without housing.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
63 (72)
Fig. 1
Anybus CompactCom M30/M40
G.2.2
Chip
The chip (C30/C40) versions of the Anybus CompactCom differ completely when it comes to
physical dimensions.
There is no way to migrate a chip solution from the 30-series to the 40-series
without a major hardware update.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
64 (72)
G.2.3
Brick
The Anybus CompactCom B40-1 does not share dimensions with the Anybus CompactCom
B30. The B40-1 is thus not suitable for migration. However HMS Industrial Networks AB has de-
veloped a separate brick version in the 40-series, that can be used for migration. This product,
B40-2, shares dimensions etc. with the B30. Please contact HMS Industrial Networks AB for
more information on the Anybus CompactCom B40-2.
Fig. 2
Anybus CompactCom B30
Fig. 3
Anybus CompactCom B40–1 (not for migration)
Fig. 4
Anybus CompactCom B40–2
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
65 (72)
G.2.4
Host Application Interface
25
50
1
26
MD1
A1
A3
A5
A7
A9
A11
A13
D6
D4
D2
D0
VDD
VSS
OM1
CE
IRQ
RESET
GOP0
GIP0
LED2B
LED1B
Tx/OM3
MI1
VSS
VSS
A0
A2
A4
A6
A8
A10
A12
D7
D5
D3
D1
VDD
VSS
OM0
OM2
R/W
OE
GOP1
GIP1
LED2A
LED1A
Rx
MI0
MD0
Fig. 5
Some signals in the host application interface have modified functionality and/or functions which
must be checked for compatibility. See the following sections.
Tx/OM3
In the 30-series, this pin is only used for Tx. It is tri-stated during power up, and driven by the
Anybus CompactCom UARTafter initialization. In the 40-series this pin is used as a fourth oper-
ating mode setting pin (OM3). During startup after releasing the reset, this pin is read to deter-
mine the operating mode to use. The pin is then changed to a Tx output.
In the 40-series, this pin has a built-in weak pull-up. If this pin, on a 30-series module or brick is
unconnected, pulled high, or connected to a high-Z digital input on the host processor, it will be
compatible with the 40-series. An external pull-up is recommended, but not required.
If this pin is pulled low by the host during startup in a 30-series application, any 40-
series module or brick, substituted in the application, will not enter the expected
operating mode.
Related Information: Anybus CompactCom M40 Hardware Design Guide (HMSI-216-126), Sec-
tion “Application Connector Pin Overview”
Module Identification (MI[0..1])
These pins are used by the host application (i.e your product) to identify what type of Anybus
CompactCom that is mounted. The identification differs between the 30-series and the 40-
series.
If your software use this identification you need to handle the new identification value.
MI1
MI0
Module Type
LOW
LOW
Active Anybus CompactCom 30
HIGH
LOW
Active Anybus CompactCom 40
MI[0..1] shall only be sampled by the application during the time period from power up to the
end of SETUP state. The pins are low at power up and before reset release.
Related Information: Anybus CompactCom M40 Hardware Design Guide (HMSI-216-126), Sec-
tion “Settings/Sync”.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
66 (72)
GIP[0..1]/LED3[A..B]
These pins are tri-stated inputs by default in the 30-series. In the 40-series, these pins are tri-
stated until the state NW_INIT. After that they become open-drain, active low LED outputs (LE-
D3A/LED3B).
No modification of the hardware is needed, if your current design has
•
tied these pins to GND
•
pulled up the pins
•
pulled down the pins
•
left the pins unconnected
However, if the application drive the pins high, a short circuit will occur.
If you connect the pins to LEDs, a pull-up is required.
In the 40-series, there is a possibility to set the GIP[0..1] and GOP[0..1] in high impedance state
(tri-state) by using attribute #16 (GPIO configuration) in the Anybus object (01h). I.e. if it is not
possible to change the host application hardware, this attribute can be configured for high impe-
dance state of GIP and GOP before leaving NW_INITstate.
Related Information: Anybus CompactCom M40 Hardware Design Guide (HMSI-216-126), Sec-
tion “LED Interface/D8-D15 (Data Bus)”.
GOP[0..1]/LED4[A..B]
These pins are outputs (high state) by default in the 30-series. In the 40-series, these pins are
tri-stated until the state NW_INIT, and after that they become push-pull, active low LED outputs
(LED4A/LED4B).
This change should not affect your product.
Related Information: Anybus CompactCom M40 Hardware Design Guide (HMSI-216-126), Sec-
tion 3.2.3, “LED Interface/D8-D15 (Data Bus)”.
Address Pins A[11..13]
The address pins 11, 12, and 13 are ignored by the 30-series. These pins must be high when
accessing the 40-series module in backwards compatible 8-bit parallel mode. If you have left
these pins unconnected or connected to GND, you need to make a hardware modification to tie
them high.
Max Input Signal Level (VIH)
The max input signal level for the 30-series is specified as VIH=VDD+0,2 V, and for the 40-series
as VIH=3.45 V. Make sure that you do not exceed 3.45V for a logic high level.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
67 (72)
RMII Compatibility
If the RMII mode is being used on an Anybus CompactCom 40 module and it is desired to re-
main compatible with the 30 series, it is important to disable this connection when switching to
an Anybus CompactCom 30 module due to pin conflicts. The RMII port of the host processor
should be set to tristate by default, and only be enabled if an RMII capable Anybus Compact-
Com 40 is detected. In case the RMII connection cannot be disabled through an internal hard-
ware control on the host processor, it will be necessary to design in external hardware (ie. a
FET bus switch) to prevent short circuits
Related Information: Anybus CompactCom M40 Hardware Design Guide (HMSI-216-126), Sec-
tion 3.2.5, “RMII — Reduced Media-Independent Interface”.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
68 (72)
G.3
General Software
G.3.1
Extended Memory Areas
The memory areas have been extended in the 40-series, and it is now possible to access larger
sizes of process data (up to 4096 bytes instead of former maximum 256 bytes) and message
data (up to 1524 bytes instead of former maximum 255 bytes). The 30-series has reserved
memory ranges that the application should not use. The 40-series implements new functionality
in some of these memory areas.
To use the extended memory areas you need to implement a new communication protocol which
is not part of this document.
Memory areas not supported by the specific network cannot be used. Make sure you do not ac-
cess these areas, e.g. for doing read/write memory tests.
Related Information: Anybus CompactCom 40 Software Design Guide (HMSI-216-125), Sec-
tion “Memory Map”
G.3.2
Faster Ping-Pong Protocol
The ping-pong protocol (the protocol used in the 30-series) is faster in the 40-series. A 30-ser-
ies module typically responds to a “ping” within 10-100 µs. The 40-series typically responds to a
“ping” within 2 µs.
Interrupt-driven applications (parallel operating mode) may see increased CPU load due to the
increased speed.
G.3.3
Requests from CompactCom to Host Application During Startup
All requests to software objects in the host application must be handled and responded to (even
if the object does not exist). This applies for both the 30-series and the 40-series. The 40-series
introduces additional objects for new functionality.
There may also be additional commands in existing objects added to the 40-series that must be
responded to (even if it is not supported).
If your implementation already responds to all commands it cannot process, which is the ex-
pected behavior, you do not need to change anything.
G.3.4
Anybus Object (01h)
Attribute
30-series
40-series
Change/Action/Comment
#1, Module Type
0401h
0403h
Make sure the host application accepts the
new module type value for the 40-series.
#15, Auxiliary Bit
Available
Removed
It is not possible to turn off the “Changed Data
Indication” in the 40-series. Also see “Control
Register CTRL_AUX-bit” and “Status Regis-
ter STAT_AUX-bit” below.
#16, GPIO
Configuration
Default: General
input and output
pins
Default: LED3
and LED4
outputs
See also ..
•
GIP[0..1]/LED3[A..B], p. 66
•
GOP[0..1]/LED4[A..B], p. 66
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
69 (72)
G.3.5
Control Register CTRL_AUX-bit
30-series
The CTRL_AUX bit in the control register indicates to the Anybus CompactCom if the
process data in the current telegram has changed compared to the previous one.
40-series
The value of the CTRL_AUX bit is always ignored. Process data is always accepted.
All released Anybus CompactCom 30 example drivers from HMS comply with this difference.
Related Information: Anybus CompactCom 40 Software Design Guide (HMSI-216-125), section
“Control Register”.
G.3.6
Status Register STAT_AUX-bit
30-series
The STAT_AUX bit in the status register indicates if the output process data in the current
telegram has changed compared to the previous one. This functionality must be enabled
in the Anybus object (01h), Attribute #15. By default, the STAT_AUX bit functionality is
disabled.
40-series
The STAT_AUX bit indicates updated output process data (not necessarily changed data)
from the network compared to the previous telegram. The functionality is always enabled.
All released Anybus CompactCom 30 example drivers from HMS comply with this difference.
Related Information: Anybus CompactCom 40 Software Design Guide (HMSI-216-125), section
“Status Register”.
G.3.7
Control Register CTRL_R-bit
30-series
The application may change this bit at any time.
40-series
For the 8-bit parallel operating mode, the bit is only allowed to transition from 1 to 0 when
the STAT_M-bit is set in the status register. When using the serial operating modes, it is
also allowed to transition from 1 to 0 in the telegram immediately after the finalizing empty
fragment.
All released CompactCom 30 example drivers from HMS comply with this difference.
Related Information: Anybus CompactCom 40 Software Design Guide (HMSI-216-125), section
“Control Register”.
G.3.8
Modifications of Status Register, Process Data Read Area, and
Message Data Read Area
In the 40-series, the Status Register, the Process Data Read Area, and the Message Data Read
Area are write protected in hardware (parallel interface). If the software for some reason writes
to any of those areas, a change is needed.
All released Anybus CompactCom 30 example drivers from HMS comply with this difference.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
70 (72)
G.4
Network Specific — PROFIBUS
G.4.1
Additional Diagnostic Object (05h)
Object removed in the 40-series. To create diagnostics, use Diagnostic Object (02h).
Another option is to use the PROFIBUS DP-V0 Diagnostic Object (10h) where diagnostics can
be sent transparently from the host application to the network.
If you use the Additional Diagnostic Object you need to update your software implementation.
G.4.2
Network PROFIBUS DP-V1 Object (0Bh)
Object removed in the 40-series, i.e. commands Map_ADI_Specified_Write_Area and Map_
ADI_Specified_Read_Area are not supported.
G.4.3
PROFIBUS DP-V1 Object (FDh)
Attribute
30-series
40-series
Change/Action/Comment
#1, PNO Ident
Number
1811h
1815h
If the attribute is implemented in the host ap-
plication, it overrides the default value and
there is no difference between the 30-series
and the 40-series.
If the attribute is not implemented, the default
value is used.
#2, Parameterization
Data
See Comment
In the first 10 bytes, only the Parameter Struct
bit (bit 3) is copied to this attribute in the 40-
series. All other bits are set to 0.
In the 30-series all information in the first 10
bytes were copied.
#5, Size of Identifier
Related Diagnostics
Available
Removed
Attribute removed in the 40-series. The Any-
bus CompactCom will never request this
attribute.
Nothing needs to be changed.
#6, Buffer Mode
Available
Removed
Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. No buffer modes needed in the 40-
series since maximum sizes for all buffers are
supported.
Nothing needs to be changed.
#7, Alarm Settings
Available
Removed
Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. Only Diagnostic Alarms supported.
#16, I&M Version
Available
Removed
Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. The host application cannot influence
the I&M version implemented by the Anybus
CompactCom.
#17, I&M Supported
Available
Removed
Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. The host application cannot influence
the I&M version supported by the Anybus
CompactCom.
#19, Check Config
Behavior
Available
Removed
Attribute removed in the 40-series. The Any-
bus CompactCom will never request this
attribute.
The 40-series depends on CheckCfgMode
(often configurable in the PROFIBUS master)
in default mode. Either the expected and ac-
tual configuration must match exactly or can
differ as long as the expected input and out-
put sizes are equal or larger than the actual
sizes.
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide
HMSI-27-210-EN 2.3
Appendix G: Backward Compatibility
71 (72)
G.4.4
Network Configuration Object (04h)
The following attributes are removed in the 40–series. The Anybus CompactCom will never re-
quest these attributes. It is only possible to set these values via the network (I&M1-4) – end user
configuration.
•
Instance #3, Function Tag
•
Instance #4, Location Tag
•
Instance #5, Installation Date
•
Instance #6, Description
G.4.5
GSD file (PROFIBUS configuration file used by engineering tool)
Implementation Type
If the keyword “Implementation Type” is present in the GSD-file (optional
keyword), the value for the 30-series shall be “NP30” and the value for the 40-
series shall be “NP40”.
Length Related
Keywords
The following keywords are possible to set to maximum values if neeed in the 40-
series. In the 30-series the maximum lengths were dependent of the buffer mode
setting.
•
Max_Input_Len
•
Max_Output_Len
•
Max_Data_Len
•
Max_User_Prm_Data_Len
•
Max_Diag_Data_Len
Anybus
® CompactCom™ 40 PROFIBUS DP-V0/DP-V1 Network Guide