Maple Systems HMI5000 Series Information Sheet
Text of the manual
. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com
1036-0204
Page 1 of 4
Rev. 01, 12/03/2013
C O N T R O L L E R I N F O R M A T I O N S H E E T
Maple Model(s)
PLC or Controller
HMI5000 Series
Omron FINS/TCP
(Ethernet)
Summary
Maple Systems’ HMI5000 Series Human/Machine Interface Terminals (Maple HMIs)
communicate with devices that support the Omron FINS protocol. When configured with
EZware, the Maple HMI is the master in a point-to-point single master, multiple slave format.
Please refer to the Installation and Operations Manual for information on connecting multiple
Maple HMIs to a single PLC port.
Compatible PLCs
Communications Cable
The Maple HMI should be connected to the Ethernet port on the PLC. If the HMI is connected
directly to the PLC, use a crossover cable from the HMI to the PLC.
A list of communications cables offered by Maple Systems as well as cable assembly
instructions to assist you in assembling your own communications cable are available on our
website at www.maplesystems.com.
WARNING If your communications cable is not wired exactly as shown in our cable
assembly instructions, damage to the HMI or loss of communications can
result.
Family
Model
FINS/TCP Devices
All
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: [email protected] • www.maplesystems.com
1036-0204
Page 2 of 4
Rev. 01, 12/03/2013
Accessible PLC Memory
Register Memory
The following table lists the PLC’s register memory ranges that the Maple HMIs are able to
access. Please note that your PLC’s memory range may be smaller or larger than that
supported by these HMIs. The following register memory can be displayed in 16 or 32-bit
format on the Maple HMI.
(Note: d=decimal )
PLC Register Type
Address Range
Format
PLC Register Description
CIO
0-32767
ddddd
Channel I/O
W
0-32767
ddddd
Work Area
H
0-32767
ddddd
Holding Area
A
0-32767
ddddd
Auxiliary Relay (Read Only)
C
0-32767
ddddd
Counter
T
0-32767
ddddd
Timer
D
0-32767
ddddd
Data Memory
EM0-EMC
0-32767
ddddd
Extended Memory (this
Extended Memory resides in the
PLC, and is different than the
HMI’s EM areas)
Discrete Memory
The following table lists the PLC’s discrete memory ranges that the Maple HMIs are able to
access. Please note that your PLC’s memory range may be smaller or larger than that
supported by these HMIs. The following discrete memory is displayable in single-bit format
on the Maple HMI.
(Note: d=decimal, b=bit)
PLC Bit Type
Address Range
Format
PLC Bit Description
CIO_Bit
000-3276715
dddddbb
Channel I/O
W_Bit
000-3276715
dddddbb
Work Area
H_Bit
000-3276715
dddddbb
Holding Area
A_Bit
000-3276715
dddddbb
Auxiliary Relay (Read Only)
D_Bit
000-3276715
dddddbb
Counter
T_Bit
000-3276715
dddddbb
Timer
C_Bit
000-3276715
dddddbb
Data Memory
C_Flag
0-4095
dddd
Counter Flag
T_Flag
0-4095
dddd
Timer Flag
. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333
1036-0204
Page 3 of 4
Rev. 01, 12/03/2013
Important Memory Considerations
If your PLC’s memory range is smaller than the range supported by the Maple HMIs, it is possible
to configure the HMI to monitor a PLC memory address that does not exist. This can cause
unpredictable results. When you configure the HMI please ensure that all selected PLC memory
addresses are valid for your PLC model.
Do not configure the HMI to write to any PLC memory address that should only be written to
by the PLC.
EZware Settings
The following table lists the communications settings that must be configured in
EZware. These settings can be found in the Edit-Set System Parameters menu under
the Device tab. Please note:
The Recommended Settings column provides the recommended setting
based upon the default settings most commonly used in the Omron
devices.
The Options column lists EZware’s options; your PLC may not support
every option
Name
Recommended
Settings
Options
Important Notes
Name:
Omron
(Ethernet –
FINS/TCP)
Description label
HMI or PLC
PLC
Location
Local
Local, Remote
Select Local if PLC directly
connected to HMI, Remote
if PLC connected thru
another HMI
PLC type:
Omron
(Ethernet –
FINS/TCP)
PLC I/F:
Ethernet
Ethernet
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: [email protected] • www.maplesystems.com
1036-0204
Page 4 of 4
Rev. 01, 12/03/2013
Name
Recommended
Settings
Options
Important Notes
Settings: IP Address:
xxx.xxx.xxx.xxx
0.0.0.0-
255.255.255.255
Must match the controller
port’s IP Address
Settings: Port
9600
0-65535
Must be 9600.
Settings: Timeout
(sec)
1
0.1 to 25.5
Adjust if longer timeout is
required
Settings: Turn around
delay (ms):
0
0-1000
Timeout period between OIT
polls
Settings: Send ACK
Delay :
0
Not Applicable
Settings: Parameter 1: 0
Not Applicable
Settings: Parameter 2: 0
Not Applicable
Settings: Parameter 3: 0
Not Applicable
Setting: Use UDP:
Unchecked
Checked or
Unchecked
Must be unchecked.
PLC default station
no.:
0
0-255
Must match the controller’s
setting.
Interval of Block Pack
(words):
5
0-512
Max. read-command
size (words):
256
Not Adjustable
Max. write-command
size (words):
256
Not Adjustable